Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000
Simulation Timestamp: 2023-10-16 08:40:27
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1865.20 | 892.30 | 892.30 |
Net Site Energy | 1865.20 | 892.30 | 892.30 |
Total Source Energy | 5907.09 | 2825.93 | 2825.93 |
Net Source Energy | 5907.09 | 2825.93 | 2825.93 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 825.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 269.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1865.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 825.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 269.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 825.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 269.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 551.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 892.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 551.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 892.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1865.202 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1865.202 | 100.00 |
Total On-Site and Utility Electric Sources | 1865.202 | 100.00 |
Total Electricity End Uses | 1865.202 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 78.33 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3648.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Latitude [deg] | 10.82 |
Longitude [deg] | 106.67 |
Elevation [m] | 5.00 |
Time Zone | 7.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-JUN-12:30 | - | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 83114.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 15645.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5437.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 141004.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 83114.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 15645.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5437.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2613.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 384.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 854.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 5907.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1250.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 184.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 408.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2825.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1250.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 184.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 408.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2825.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.40 |
SMSTORE1 DIRECT AIR | 1.23 |
SMSTORE2 DIRECT AIR | 1.23 |
SMSTORE3 DIRECT AIR | 1.22 |
SMSTORE4 DIRECT AIR | 1.22 |
LGSTORE2 DIRECT AIR | 2.19 |
SMSTORE5 DIRECT AIR | 1.15 |
SMSTORE6 DIRECT AIR | 1.15 |
SMSTORE7 DIRECT AIR | 1.15 |
SMSTORE8 DIRECT AIR | 1.31 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 1.00 | 1.00 | 2.40 |
PSZ-AC_2:2 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 1.00 | 1.23 |
PSZ-AC_3:3 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.23 | 1.00 | 0.994177 | 1.23 |
PSZ-AC_4:4 | 1.22 | 1.22 | 1.22 | 1.22 | 1.24 | 1.24 | 1.00 | 0.985723 | 1.24 |
PSZ-AC_5:5 | 1.22 | 1.22 | 1.22 | 1.22 | 1.23 | 1.23 | 1.00 | 0.994046 | 1.23 |
PSZ-AC_6:6 | 2.19 | 2.19 | 2.19 | 2.19 | 2.19 | 2.19 | 1.00 | 1.000000 | 2.19 |
PSZ-AC_7:7 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 0.999937 | 1.15 |
PSZ-AC_8:8 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 0.999948 | 1.15 |
PSZ-AC_9:9 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.15 | 1.00 | 1.00 | 1.15 |
PSZ-AC_10:10 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.31 | 1.00 | 1.00 | 1.31 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.40 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.23 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.23 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.24 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.23 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.19 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.15 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.31 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.40 | 2569.73 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1367.00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1365.46 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1368.97 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.23 | 1360.79 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.19 | 2346.15 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1275.84 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1270.55 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.15 | 1273.21 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.31 | 1447.36 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.40 | 2.40 | 2.40 | 2.40 | 59635.15 | 55366.07 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 30660.24 | 28458.36 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 30625.81 | 28262.38 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 30704.61 | 28095.63 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.23 | 1.23 | 1.23 | 1.23 | 30520.99 | 28162.67 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.19 | 2.19 | 2.19 | 2.19 | 54446.59 | 50592.21 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 28615.65 | 26575.41 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 28497.13 | 26465.81 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.15 | 1.15 | 1.15 | 1.15 | 28556.77 | 26522.83 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.31 | 1.31 | 1.31 | 1.31 | 32462.79 | 30201.94 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.40 | 1.20 | 2.40 | 59635.15 | 29817.58 | 59635.15 | 0.701080 | 0.701080 |
PSZ-AC_2:2 COOLING COIL | 1.23 | 0.617344 | 1.23 | 30660.24 | 15330.12 | 30660.24 | 0.701080 | 0.701080 |
PSZ-AC_3:3 COOLING COIL | 1.23 | 0.616651 | 1.23 | 30625.81 | 15312.89 | 30625.81 | 0.701080 | 0.701080 |
PSZ-AC_4:4 COOLING COIL | 1.24 | 0.618237 | 1.24 | 30704.61 | 15352.25 | 30704.61 | 0.701080 | 0.701080 |
PSZ-AC_5:5 COOLING COIL | 1.23 | 0.614540 | 1.23 | 30520.99 | 15260.49 | 30520.99 | 0.701080 | 0.701080 |
PSZ-AC_6:6 COOLING COIL | 2.19 | 1.10 | 2.19 | 54446.59 | 27223.24 | 54446.59 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.15 | 0.576176 | 1.15 | 28615.65 | 14307.80 | 28615.65 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.15 | 0.573790 | 1.15 | 28497.13 | 14248.56 | 28497.13 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.15 | 0.574991 | 1.15 | 28556.77 | 14278.37 | 28556.77 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.31 | 0.653638 | 1.31 | 32462.79 | 16231.39 | 32462.79 | 0.701080 | 0.701080 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 55366.07 |
PSZ-AC_2:2 HEATING COIL | 28458.36 |
PSZ-AC_3:3 HEATING COIL | 28262.38 |
PSZ-AC_4:4 HEATING COIL | 28095.63 |
PSZ-AC_5:5 HEATING COIL | 28162.67 |
PSZ-AC_6:6 HEATING COIL | 50592.21 |
PSZ-AC_7:7 HEATING COIL | 26575.41 |
PSZ-AC_8:8 HEATING COIL | 26465.81 |
PSZ-AC_9:9 HEATING COIL | 26522.83 |
PSZ-AC_10:10 HEATING COIL | 30201.94 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 26.90 | 26.70 | 26.00 | 26.40 | 27.50 | 28.30 | 29.20 | 29.00 | 28.90 | 27.20 | 27.50 | 27.60 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 | 10.82 | 106.67 | 7.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.60 | 3.20 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7544 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.092 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.31526305E-12 | 0.65421067E-14 | -0.96995935E-13 | 0.16372101E-15 |
23 | 6 | 0.28934589E-07 | 0.21281465E-09 | 0.66261080E-08 | -0.13661131E-12 |
24 | 5 | -0.19144321E-03 | 0.18179002E-05 | -0.98452505E-04 | 0.65494719E-08 |
25 | 4 | 0.29370911 | 0.88327295E-03 | 0.10024532 | -0.33791493E-04 |
26 | 3 | -7.2972687 | 0.27321832E-01 | -2.3480939 | 0.29160644E-01 |
27 | 2 | 40.973187 | 0.96992104E-01 | 15.302757 | -0.33447687 |
28 | 1 | -80.623988 | 0.43709902E-01 | -29.175449 | 1.0802857 |
29 | 0 | 46.824338 | 0.87814252E-03 | 16.290426 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.283 | 8.131E-004 | 4.479E-004 | 0.565 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 0.162 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.202 | 1.162E-003 | 5.390E-004 | 0.807 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 27242.37184 | 32690.84620 | 2.00126 | 2.40151 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 35.11500 | 1.71580E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 1929.80138 | 2315.76166 | 8.14655E-002 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 14006.38985 | 16807.66782 | 1.02891 | 1.23469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 35.05833 | 1.71579E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 925.92593 | 1111.11112 | 3.92057E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 14258.64218 | 17110.37062 | 1.02177 | 1.22612 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 1006.07069 | 1207.28482 | 4.25858E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 14175.87286 | 17011.04743 | 1.01568 | 1.21882 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 1041.83885 | 1250.20663 | 4.40668E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 14208.75567 | 17050.50680 | 1.01813 | 1.22176 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 30.52500 | 1.71492E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 1187.69064 | 1425.22877 | 5.01172E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 24875.27127 | 29850.32553 | 1.82714 | 2.19256 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 34.91667 | 1.71576E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 2235.26319 | 2682.31583 | 9.39791E-002 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 13073.40540 | 15688.08647 | 0.96023 | 1.15228 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71575E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 1121.43978 | 1345.72773 | 4.73737E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 13019.40507 | 15623.28609 | 0.95627 | 1.14752 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71575E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 1112.59800 | 1335.11760 | 4.70065E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 13047.33667 | 15656.80400 | 0.95832 | 1.14998 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 34.84583 | 1.71575E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 1220.32549 | 1464.39059 | 5.14463E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 14831.86750 | 17798.24101 | 1.08940 | 1.30728 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 34.77500 | 1.71573E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 1255.21542 | 1506.25850 | 5.29942E-002 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 20.10000 | 1.47983E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 37817.98 | 2.40151 | 2.40151 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 9903.44 | 0.41148 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 19356.64 | 1.23469 | 1.23469 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 19328.72 | 1.23330 | 1.23330 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 19369.14 | 1.23647 | 1.23647 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 19270.08 | 1.22908 | 1.22908 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 34977.26 | 2.19256 | 2.19256 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 9903.44 | 0.41148 | 0.41148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 18234.05 | 1.15235 | 1.15235 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 18169.62 | 1.14758 | 1.14758 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 18195.97 | 1.14998 | 1.14998 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 20233.28 | 1.30728 | 1.30728 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 4951.72 | 0.20574 | 0.20574 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.40151 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23469 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22612 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.21882 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.22176 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.19256 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.15228 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14752 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.14998 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.30728 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.40151 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.40151 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.40151 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.40151 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.40151 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.40151 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23469 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23469 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23469 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23469 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23469 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23469 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22612 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22612 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22612 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22612 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23330 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23330 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.99418 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.21882 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.21882 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.21882 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.21882 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23647 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23647 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.98572 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.22176 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.22176 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.22176 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.22176 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.22908 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.22908 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.99405 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.19256 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.19256 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.19256 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.19256 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.19256 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.19256 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.15228 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.15228 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.15228 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.15228 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.15235 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.15235 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99994 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14752 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14752 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14752 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14752 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14758 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14758 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99995 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.14998 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.14998 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.14998 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.14998 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.14998 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.14998 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.30728 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.30728 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.30728 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.30728 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.30728 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.30728 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.40151 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.23469 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.23330 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.23647 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.22908 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.19256 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.15235 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.14758 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.14998 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.30728 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.40151 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.40151 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2569.72665 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.40151 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.40151 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.40151 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.40151 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.40151 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.20075 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.40151 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 59635.15000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 29817.57626 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 59635.15000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 59635.15000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 55366.07215 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 55366.07215 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23469 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23469 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1366.99543 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23469 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23469 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23469 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23469 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23469 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61734 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23469 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30660.24000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15330.11967 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30660.24000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30660.24000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28458.35507 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 28458.35507 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23330 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23330 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1365.46038 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23330 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23330 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23330 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23330 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23330 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61665 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23330 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30625.81000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15312.88801 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30625.81000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30625.81000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28262.38296 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28262.38296 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23647 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23647 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1368.97367 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23647 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23647 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23647 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23647 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23647 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61824 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23647 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30704.61000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15352.24733 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30704.61000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30704.61000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28095.62874 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28095.62874 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.22908 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.22908 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1360.78696 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.22908 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.22908 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.22908 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.22908 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.22908 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61454 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.22908 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30520.99000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15260.49168 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30520.99000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30520.99000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28162.67099 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28162.67099 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.19256 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.19256 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2346.14741 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.19256 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.19256 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.19256 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.19256 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.19256 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.09628 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.19256 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 54446.59000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 27223.24311 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 54446.59000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 54446.59000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50592.21453 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 50592.21453 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.15235 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.15235 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1275.83688 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.15235 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.15235 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.15235 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.15235 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.15235 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57618 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.15235 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28615.65000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14307.79737 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28615.65000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28615.65000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26575.40823 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26575.40823 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14758 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14758 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1270.55250 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14758 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14758 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14758 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14758 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14758 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57379 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14758 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28497.13000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14248.56407 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28497.13000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28497.13000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26465.80525 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 26465.80525 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.14998 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.14998 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1273.21177 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.14998 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.14998 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.14998 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.14998 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.14998 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.57499 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.14998 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 28556.77000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 14278.37100 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 28556.77000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 28556.77000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26522.82598 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 26522.82598 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.30728 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.30728 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1447.36263 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.30728 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.30728 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.30728 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.30728 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.30728 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.65364 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.30728 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32462.79000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16231.39471 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32462.79000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32462.79000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30201.93789 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 30201.93789 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 57740.6 | 11.23 | 11.23 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 29686.2 | 11.40 | 11.40 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 29652.8 | 11.40 | 11.40 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 29729.1 | 11.40 | 11.40 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 29551.4 | 11.40 | 11.40 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 52716.9 | 11.23 | 11.23 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 27706.5 | 11.40 | 11.40 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 27591.8 | 11.40 | 11.40 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 27649.5 | 11.40 | 11.40 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 31431.5 | 11.40 | 11.40 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.9805154473E-002 | 0.1695144153 | Pass | Pass | 6.4050108737E-002 | 0.4367712568 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 3.1554157555E-002 | 0.1851382631 | Pass | Pass | 6.7684171378E-002 | 0.4959688828 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.3399263190E-002 | 0.2321494404 | Pass | Pass | 0.6225233411 | 5.8651264354 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.2397937046E-002 | 0.2331946142 | Pass | Pass | 0.1168406915 | 0.6095056872 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.4793676716E-002 | 0.2319504272 | Pass | Pass | 0.1495559406 | 0.9669783508 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.4570115067E-002 | 0.2309718667 | Pass | Pass | 0.1288176222 | 0.6373932672 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.2579978497E-002 | 0.2263795947 | Pass | Pass | 0.1392437540 | 0.6801055977 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 5.2645608858E-002 | 0.2259970716 | Pass | Pass | 0.1480826242 | 0.8476412735 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.3410125769E-002 | 0.2259253102 | Pass | Pass | 0.1237984544 | 0.6123137609 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 5.9319011957E-002 | 0.2348018097 | Pass | Pass | 8.6007324456E-002 | 0.4242388928 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3422.23 | -626.9 | 0.00 | -1462.2 | 3950.48 | 5283.64 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 20.10 | 0.00 | 20.10 | Wetbulb [C] | 1.80 | 0.00 |
HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 35.20 | 8.50 | 25.80 | Wetbulb [C] | 4.10 | 160.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 57.00 | 12 | |||
Feb | 0.00 | 0 | |||
Mar | 153.60 | 31 | |||
Apr | 87.00 | 59 | |||
May | 227.22 | 128 | |||
Jun | 144.58 | 109 | |||
Jul | 42.40 | 24 | |||
Aug | 164.90 | 163 | |||
Sep | 119.60 | 50 | |||
Oct | 365.70 | 188 | |||
Nov | 70.90 | 67 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 0.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.83 | 83.83 | 121.54 | |
Exterior Lighting Total | 7723.26 | 121.54 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 59635.15 | 41809.01 | 17826.14 | 0.70 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30660.24 | 21495.28 | 9164.96 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30625.81 | 21471.14 | 9154.67 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30704.61 | 21526.39 | 9178.22 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30520.99 | 21397.66 | 9123.33 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 54446.59 | 38171.42 | 16275.17 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28615.65 | 20061.86 | 8553.79 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28497.13 | 19978.77 | 8518.36 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 28556.77 | 20020.58 | 8536.19 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32462.79 | 22759.01 | 9703.78 | 0.70 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 57740.6 | 11.23 | 11.23 | ||||
PSZ-AC_2:2 COOLING COIL | 29686.2 | 11.40 | 11.40 | ||||
PSZ-AC_3:3 COOLING COIL | 29652.8 | 11.40 | 11.40 | ||||
PSZ-AC_4:4 COOLING COIL | 29729.1 | 11.40 | 11.40 | ||||
PSZ-AC_5:5 COOLING COIL | 29551.4 | 11.40 | 11.40 | ||||
PSZ-AC_6:6 COOLING COIL | 52716.9 | 11.23 | 11.23 | ||||
PSZ-AC_7:7 COOLING COIL | 27706.5 | 11.40 | 11.40 | ||||
PSZ-AC_8:8 COOLING COIL | 27591.8 | 11.40 | 11.40 | ||||
PSZ-AC_9:9 COOLING COIL | 27649.5 | 11.40 | 11.40 | ||||
PSZ-AC_10:10 COOLING COIL | 31431.5 | 11.40 | 11.40 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 55366.07 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 28458.36 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28262.38 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28095.63 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28162.67 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 50592.21 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26575.41 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 26465.81 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 26522.83 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 30201.94 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.40 | 2569.73 | 1070.05 | 1.00 | 1.29 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1367.00 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1365.46 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1368.97 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.23 | 1360.79 | 1107.16 | 1.00 | 1.35 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.19 | 2346.15 | 1070.05 | 1.00 | 1.30 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1275.84 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1270.55 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.15 | 1273.21 | 1107.16 | 1.00 | 1.37 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.31 | 1447.36 | 1107.16 | 1.00 | 1.34 | General | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 27242.37 | 32690.85 | 93.84 | 2.001 | 2.402 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 23.89 | 23.88 | 0.01040 | 35.12 | 0.01716 | 0.411 | 0.00 |
SMSTORE1 | 14006.39 | 16807.67 | 96.49 | 1.029 | 1.235 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 23.89 | 23.88 | 0.01042 | 35.06 | 0.01716 | 0.206 | 0.00 |
SMSTORE2 | 14258.64 | 17110.37 | 98.23 | 1.022 | 1.226 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 23.89 | 23.88 | 0.00955 | 30.53 | 0.01715 | 0.206 | 0.00 |
SMSTORE3 | 14175.87 | 17011.05 | 97.66 | 1.016 | 1.219 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 23.89 | 23.88 | 0.00954 | 30.53 | 0.01715 | 0.206 | 0.00 |
SMSTORE4 | 14208.76 | 17050.51 | 97.88 | 1.018 | 1.222 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 09:00:00 | 23.89 | 23.88 | 0.00955 | 30.53 | 0.01715 | 0.206 | 0.00 |
LGSTORE2 | 24875.27 | 29850.33 | 85.68 | 1.827 | 2.193 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 23.89 | 23.88 | 0.01046 | 34.92 | 0.01716 | 0.411 | 0.00 |
SMSTORE5 | 13073.41 | 15688.09 | 90.06 | 0.960 | 1.152 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01053 | 34.85 | 0.01716 | 0.206 | 0.00 |
SMSTORE6 | 13019.41 | 15623.29 | 89.69 | 0.956 | 1.148 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01053 | 34.85 | 0.01716 | 0.206 | 0.00 |
SMSTORE7 | 13047.34 | 15656.80 | 89.88 | 0.958 | 1.150 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 23.89 | 23.88 | 0.01053 | 34.85 | 0.01716 | 0.206 | 0.00 |
SMSTORE8 | 14831.87 | 17798.24 | 102.18 | 1.089 | 1.307 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 23.89 | 23.88 | 0.01049 | 34.78 | 0.01716 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 1929.80 | 2315.76 | 6.65 | 0.081 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01269 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE1 | 925.93 | 1111.11 | 6.38 | 0.039 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01233 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE2 | 1006.07 | 1207.28 | 6.93 | 0.043 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01296 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE3 | 1041.84 | 1250.21 | 7.18 | 0.044 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01292 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE4 | 1187.69 | 1425.23 | 8.18 | 0.050 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.01274 | 20.10 | 0.01480 | 0.206 | 0.00 |
LGSTORE2 | 2235.26 | 2682.32 | 7.70 | 0.094 | 0.411 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01284 | 20.10 | 0.01480 | 0.411 | 0.00 |
SMSTORE5 | 1121.44 | 1345.73 | 7.73 | 0.047 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01294 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE6 | 1112.60 | 1335.12 | 7.66 | 0.047 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01295 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE7 | 1220.33 | 1464.39 | 8.41 | 0.051 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01282 | 20.10 | 0.01480 | 0.206 | 0.00 |
SMSTORE8 | 1255.22 | 1506.26 | 8.65 | 0.053 | 0.206 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 21.11 | 21.11 | 0.01338 | 20.10 | 0.01480 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.40 | 2.40 | 0.41 | 0.41 | 2.4015 | 2.4015 | 2.4015 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.23 | 1.23 | 0.21 | 0.21 | 1.2347 | 1.2347 | 1.2347 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.23 | 1.23 | 0.21 | 0.21 | 1.2333 | 1.2261 | 1.2333 | 0.9942 | 1.0000 |
PSZ-AC_4:4 | 1.24 | 1.24 | 0.21 | 0.21 | 1.2365 | 1.2188 | 1.2365 | 0.9857 | 1.0000 |
PSZ-AC_5:5 | 1.23 | 1.23 | 0.21 | 0.21 | 1.2291 | 1.2218 | 1.2291 | 0.9940 | 1.0000 |
PSZ-AC_6:6 | 2.19 | 2.19 | 0.41 | 0.41 | 2.1926 | 2.1926 | 2.1926 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.15 | 1.15 | 0.21 | 0.21 | 1.1524 | 1.1523 | 1.1524 | 0.9999 | 1.0000 |
PSZ-AC_8:8 | 1.15 | 1.15 | 0.21 | 0.21 | 1.1476 | 1.1475 | 1.1476 | 0.9999 | 1.0000 |
PSZ-AC_9:9 | 1.15 | 1.15 | 0.21 | 0.21 | 1.1500 | 1.1500 | 1.1500 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.31 | 1.31 | 0.21 | 0.21 | 1.3073 | 1.3073 | 1.3073 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 59635.150 | 41809.011 | 2.401510 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | 59635.15 | 39574.69 | 2.401510 | 26.69 | 19.74 | 0.01156205 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 17.1342 | 23.88 | 0.01040494 | 56.2152 | 27242.16 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 55366.072 | 55366.072 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 55366.07 | 55366.07 | 2.401508 | 20.94 | 18.62 | 0.01249559 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.1342 | 21.11 | 0.01201946 | 76.6484 | 1082.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 30660.240 | 21495.281 | 1.234690 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | 30660.24 | 20374.09 | 1.234690 | 26.66 | 19.72 | 0.01154528 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 16.6632 | 23.88 | 0.01042239 | 56.3077 | 13999.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 28458.355 | 28458.355 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28458.36 | 28458.36 | 1.234688 | 20.94 | 18.57 | 0.01243081 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.6633 | 21.11 | 0.01195743 | 76.2606 | 517.27 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 30625.810 | 21471.143 | 1.233300 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 30625.81 | 20343.19 | 1.233300 | 26.67 | 19.73 | 0.01154950 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 16.6820 | 23.88 | 0.01042517 | 56.3225 | 13976.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28262.383 | 28262.383 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28262.38 | 28262.38 | 1.233301 | 20.94 | 19.25 | 0.01330483 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.6820 | 20.45 | 0.01300581 | 86.2238 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 30704.610 | 21526.388 | 1.236470 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 30704.61 | 20406.80 | 1.236470 | 26.66 | 19.72 | 0.01154357 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 16.6393 | 23.88 | 0.01042134 | 56.3022 | 14010.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28095.629 | 28095.629 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | 28095.63 | 28095.63 | 1.236475 | 20.94 | 19.23 | 0.01327834 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.6392 | 20.43 | 0.01297495 | 86.1782 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 30520.990 | 21397.656 | 1.229080 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | 30520.99 | 20257.17 | 1.229080 | 26.67 | 19.74 | 0.01155820 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 16.7393 | 23.88 | 0.01043081 | 56.3524 | 13926.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28162.671 | 28162.671 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 28162.67 | 28162.67 | 1.229080 | 20.94 | 19.12 | 0.01314310 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 16.7393 | 20.33 | 0.01281033 | 85.6029 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 54446.590 | 38171.415 | 2.192560 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 54446.59 | 35649.34 | 2.192560 | 26.87 | 19.92 | 0.01172438 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 18.7670 | 23.88 | 0.01046684 | 56.5426 | 24837.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 50592.215 | 50592.215 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | 50592.21 | 50592.21 | 2.192564 | 20.92 | 19.12 | 0.01315407 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 18.7670 | 20.29 | 0.01277421 | 85.5611 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 28615.650 | 20061.860 | 1.152350 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 28615.65 | 18714.20 | 1.152350 | 26.80 | 19.90 | 0.01172011 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 17.8539 | 23.88 | 0.01053572 | 56.9097 | 13049.82 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26575.408 | 26575.408 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26575.41 | 26575.41 | 1.152352 | 20.93 | 19.18 | 0.01322477 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.8539 | 20.39 | 0.01288277 | 85.7762 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 28497.130 | 19978.768 | 1.147580 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | 28497.13 | 18618.98 | 1.147580 | 26.81 | 19.91 | 0.01173074 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 17.9281 | 23.88 | 0.01054262 | 56.9463 | 12995.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 26465.805 | 26465.805 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | 26465.81 | 26465.81 | 1.147579 | 20.93 | 19.10 | 0.01312557 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.9281 | 21.11 | 0.01276017 | 81.2738 | 921.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 28556.770 | 20020.580 | 1.149980 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | 28556.77 | 18665.14 | 1.149980 | 26.81 | 19.90 | 0.01172642 | 12.80 | 12.09 | 0.00850000 | 35.20 | 0.01715815 | 25.83 | 17.8907 | 23.88 | 0.01053984 | 56.9315 | 13017.59 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 26522.826 | 26522.826 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | 26522.83 | 26522.83 | 1.149981 | 20.93 | 19.11 | 0.01312857 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 17.8907 | 20.31 | 0.01276475 | 85.3993 | 0.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 32462.790 | 22759.013 | 1.307280 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | 32462.79 | 21511.14 | 1.307280 | 26.49 | 19.66 | 0.01153645 | 12.80 | 12.09 | 0.00850000 | 34.78 | 0.01715734 | 25.72 | 15.7380 | 23.88 | 0.01048661 | 56.6507 | 14831.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 30201.938 | 30201.938 | -999.0 | -999.0 | -999.000 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 | 30201.94 | 30201.94 | 1.307277 | 20.90 | 19.34 | 0.01345176 | 40.00 | 21.18 | 0.00800000 | 20.10 | 0.01479830 | 20.10 | 15.7380 | 21.11 | 0.01320026 | 84.0165 | 994.86 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 59635.150 | 41809.011 | 2.401510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3333 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.401508 | 2.89044249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 15:10:00 | Sensible | 59635.15 | 39574.69 | 1.0000 | 2.89044538 | 2.401510 | 26.69 | 19.74 | 0.01156205 | 56305.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 59635.15 | 35.20 | 0.01715815 | 25.83 | 0.41147883 | 17.1342 | 23.88 | 0.01040494 | 23.88 | 0.01040494 | 56.2152 | 27242.16 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 55366.072 | 55366.072 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.401508 | 2.89044249 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 55366.07 | 55366.07 | 1.0000 | 2.89044249 | 2.401508 | 20.94 | 18.62 | 0.01249559 | 52776.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 55366.07 | 20.10 | 0.01479830 | 20.10 | 0.41147883 | 17.1342 | 21.11 | 0.01201946 | 21.11 | 0.01201946 | 76.6484 | 1082.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30660.240 | 21495.281 | 1.234690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3021 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.234688 | 1.48606409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:40:00 | Sensible | 30660.24 | 20374.09 | 1.0000 | 1.48606669 | 1.234690 | 26.66 | 19.72 | 0.01154528 | 56239.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30660.24 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 16.6632 | 23.88 | 0.01042239 | 23.88 | 0.01042239 | 56.3077 | 13999.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28458.355 | 28458.355 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.234688 | 1.48606409 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 28458.36 | 28458.36 | 1.0000 | 1.48606409 | 1.234688 | 20.94 | 18.57 | 0.01243081 | 52616.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28458.36 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.6633 | 21.11 | 0.01195743 | 21.11 | 0.01195743 | 76.2606 | 517.27 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30625.810 | 21471.143 | 1.233300 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3099 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.233301 | 1.48439533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 30625.81 | 20343.19 | 1.0000 | 1.48439369 | 1.233300 | 26.67 | 19.73 | 0.01154950 | 56253.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30625.81 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 16.6820 | 23.88 | 0.01042517 | 23.88 | 0.01042517 | 56.3225 | 13976.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28262.383 | 28262.383 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.233301 | 1.48439533 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 28262.38 | 28262.38 | 1.0000 | 1.48439533 | 1.233301 | 20.94 | 19.25 | 0.01330483 | 54836.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28262.38 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.6820 | 21.11 | 0.01300581 | 20.45 | 0.01300581 | 86.2238 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30704.610 | 21526.388 | 1.236470 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2989 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.236475 | 1.48821464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 30704.61 | 20406.80 | 1.0000 | 1.48820909 | 1.236470 | 26.66 | 19.72 | 0.01154357 | 56234.1 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30704.61 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 16.6393 | 23.88 | 0.01042134 | 23.88 | 0.01042134 | 56.3022 | 14010.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28095.629 | 28095.629 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.236475 | 1.48821464 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:00:00 | Sensible | 28095.63 | 28095.63 | 1.0000 | 1.48821464 | 1.236475 | 20.94 | 19.23 | 0.01327834 | 54769.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28095.63 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.6392 | 21.11 | 0.01297495 | 20.43 | 0.01297495 | 86.1782 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30520.990 | 21397.656 | 1.229080 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.3261 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.229080 | 1.47931485 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:30:00 | Sensible | 30520.99 | 20257.17 | 1.0000 | 1.47931452 | 1.229080 | 26.67 | 19.74 | 0.01155820 | 56283.0 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30520.99 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 16.7393 | 23.88 | 0.01043081 | 23.88 | 0.01043081 | 56.3524 | 13926.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28162.671 | 28162.671 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.229080 | 1.47931485 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 28162.67 | 28162.67 | 1.0000 | 1.47931485 | 1.229080 | 20.94 | 19.12 | 0.01314310 | 54425.1 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28162.67 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 16.7393 | 21.11 | 0.01281033 | 20.33 | 0.01281033 | 85.6029 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 54446.590 | 38171.415 | 2.192560 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6350 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.192564 | 2.63895935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 54446.59 | 35649.34 | 1.0000 | 2.63895421 | 2.192560 | 26.87 | 19.92 | 0.01172438 | 56912.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54446.59 | 35.20 | 0.01715815 | 25.83 | 0.41147883 | 18.7670 | 23.88 | 0.01046684 | 23.88 | 0.01046684 | 56.5426 | 24837.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50592.215 | 50592.215 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.192564 | 2.63895935 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | Sensible | 50592.21 | 50592.21 | 1.0000 | 2.63895935 | 2.192564 | 20.92 | 19.12 | 0.01315407 | 54431.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50592.21 | 20.10 | 0.01479830 | 20.10 | 0.41147883 | 18.7670 | 21.11 | 0.01277421 | 20.29 | 0.01277421 | 85.5611 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28615.650 | 20061.860 | 1.152350 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6271 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.152352 | 1.38696541 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 28615.65 | 18714.20 | 1.0000 | 1.38696268 | 1.152350 | 26.80 | 19.90 | 0.01172011 | 56826.6 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28615.65 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 17.8539 | 23.88 | 0.01053572 | 23.88 | 0.01053572 | 56.9097 | 13049.82 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26575.408 | 26575.408 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.152352 | 1.38696541 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26575.41 | 26575.41 | 1.0000 | 1.38696541 | 1.152352 | 20.93 | 19.18 | 0.01322477 | 54620.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26575.41 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.8539 | 21.11 | 0.01288277 | 20.39 | 0.01288277 | 85.7762 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28497.130 | 19978.768 | 1.147580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6469 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.147579 | 1.38122075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:20:00 | Sensible | 28497.13 | 18618.98 | 1.0000 | 1.38122153 | 1.147580 | 26.81 | 19.91 | 0.01173074 | 56862.4 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28497.13 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 17.9281 | 23.88 | 0.01054262 | 23.88 | 0.01054262 | 56.9463 | 12995.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26465.805 | 26465.805 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.147579 | 1.38122075 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:30:00 | Sensible | 26465.81 | 26465.81 | 1.0000 | 1.38122075 | 1.147579 | 20.93 | 19.10 | 0.01312557 | 54368.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26465.81 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.9281 | 21.11 | 0.01276017 | 21.11 | 0.01276017 | 81.2738 | 921.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 28556.770 | 20020.580 | 1.149980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.6388 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.149981 | 1.38411164 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 14:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:10:00 | Sensible | 28556.77 | 18665.14 | 1.0000 | 1.38411016 | 1.149980 | 26.81 | 19.90 | 0.01172642 | 56847.9 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28556.77 | 35.20 | 0.01715815 | 25.83 | 0.20573941 | 17.8907 | 23.88 | 0.01053984 | 23.88 | 0.01053984 | 56.9315 | 13017.59 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26522.826 | 26522.826 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.149981 | 1.38411164 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 00:10:00 | Sensible | 26522.83 | 26522.83 | 1.0000 | 1.38411164 | 1.149981 | 20.93 | 19.11 | 0.01312857 | 54376.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26522.83 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 17.8907 | 21.11 | 0.01276475 | 20.31 | 0.01276475 | 85.3993 | 0.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32462.790 | 22759.013 | 1.307280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1026.2857 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.307277 | 1.57343147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN CLG .4% CONDNS DB=>MWB | 4/21 13:00:00 | Sensible | 32462.79 | 21511.14 | 1.0000 | 1.57343565 | 1.307280 | 26.49 | 19.66 | 0.01153645 | 56041.8 | 12.80 | 12.09 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32462.79 | 34.78 | 0.01715734 | 25.72 | 0.20573941 | 15.7380 | 23.88 | 0.01048661 | 23.88 | 0.01048661 | 56.6507 | 14831.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30201.938 | 30201.938 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.307277 | 1.57343147 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 | unknown | unknown | HO.CHI.MINH.CITY-TAN.SON.NHAT.AP_VNM ANN HTG 99.6% CONDNS DB | 12/21 10:20:00 | Sensible | 30201.94 | 30201.94 | 1.0000 | 1.57343147 | 1.307277 | 20.90 | 19.34 | 0.01345176 | 55163.6 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30201.94 | 20.10 | 0.01479830 | 20.10 | 0.20573941 | 15.7380 | 21.05 | 0.01320026 | 21.11 | 0.01320026 | 84.0165 | 994.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5840.00 | 2937.00 | 2937.00 |
SMSTORE1 | 5831.83 | 2220.17 | 2220.17 |
SMSTORE2 | 4395.00 | 2535.50 | 2535.50 |
SMSTORE3 | 4395.00 | 2527.83 | 2527.83 |
SMSTORE4 | 4395.00 | 2574.33 | 2574.33 |
LGSTORE2 | 4030.00 | 2648.33 | 2648.33 |
SMSTORE5 | 4030.00 | 2646.83 | 2646.83 |
SMSTORE6 | 4030.00 | 2661.33 | 2661.33 |
SMSTORE7 | 4030.00 | 2654.33 | 2654.33 |
SMSTORE8 | 4030.00 | 2280.00 | 2280.00 |
Facility | 5943.00 | 3648.83 | 3648.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 23.50 | 0.00 | 23.50 |
SMSTORE1 | 0.00 | 6.17 | 0.00 | 6.17 |
SMSTORE2 | 0.00 | 30.33 | 0.00 | 30.33 |
SMSTORE3 | 0.00 | 29.17 | 0.00 | 29.17 |
SMSTORE4 | 0.00 | 31.17 | 0.00 | 31.17 |
LGSTORE2 | 0.00 | 45.00 | 0.00 | 45.00 |
SMSTORE5 | 0.00 | 39.67 | 0.00 | 39.67 |
SMSTORE6 | 0.00 | 40.50 | 0.00 | 40.50 |
SMSTORE7 | 0.00 | 40.17 | 0.00 | 40.17 |
SMSTORE8 | 0.00 | 29.00 | 0.00 | 29.00 |
Facility | 0.00 | 78.33 | 0.00 | 78.33 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.850 | 0.347 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.690 | 0.381 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.851 | 0.499 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.851 | 0.499 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.851 | 0.499 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.851 | 0.467 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.851 | 0.532 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.851 | 0.532 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.851 | 0.532 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.851 | 0.556 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.832 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.093 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.09 | 28.12 | 902.60 | 0.830 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.09 | 28.12 | 902.60 | 0.830 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.09 | 28.12 | 902.60 | 0.830 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.81 | 56.25 | 1805.20 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.833 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.09 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.81 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.09 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803507.24 | 0.00 | 8803507.24 | 3864581.27 | 12668088.51 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3585784.69 | 0.00 | 3585784.69 | 2040076.50 | 5625861.19 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525550.60 | 0.00 | 3525550.60 | 2084070.60 | 5609621.21 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525550.60 | 0.00 | 3525550.60 | 2084070.60 | 5609621.21 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525550.60 | 0.00 | 3525550.60 | 2084070.60 | 5609621.21 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510418.03 | 0.00 | 6510418.03 | 3717456.58 | 10227874.61 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255003.25 | 0.00 | 3255003.25 | 2093131.57 | 5348134.81 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255039.96 | 0.00 | 3255039.96 | 2093131.57 | 5348171.53 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255209.01 | 0.00 | 3255209.01 | 2093131.57 | 5348340.58 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255209.01 | 0.00 | 3255209.01 | 2425949.00 | 5681158.02 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
Total Facility | 42496823.01 | 0.00 | 42496823.01 | 24579669.87 | 67076492.87 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 730.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1677 | 0.5792 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1669 | 0.0000 | 0.1669 | 0.0922 | 0.2591 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1205 | 0.3262 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2256 | 0.6371 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3341 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3341 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1284 | 0.3341 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1343 | 0.3401 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4300 | 0.0000 | 2.4300 | 1.3665 | 3.7965 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5194514.29 | 0.00 | 5194514.29 | 6488198.17 | 4303.00 | 0.00 | 4457.00 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2418 | 0.0000 | 0.2418 | 0.2057 | 1486.00 | 0.00 | 4354.00 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2418 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
ElectricityPurchased:Plant | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
Cogeneration:ElectricityPurchased | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
General:Cogeneration:ElectricityPurchased | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
ElectricityNet:Plant | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
Cogeneration:ElectricityNet | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
General:Cogeneration:ElectricityNet | 1865.20 | 3178.87 | 01-JAN-06:20 | 141004.83 | 16-JUN-12:30 |
Electricity:HVAC | 1094.95 | 0.00 | 01-JAN-00:10 | 100966.63 | 16-JUN-13:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 825.09 | 0.00 | 01-JAN-00:10 | 85321.58 | 16-JUN-13:00 |
General:Cooling:Electricity | 825.09 | 0.00 | 01-JAN-00:10 | 85321.58 | 16-JUN-13:00 |
Fans:Electricity | 269.86 | 0.00 | 01-JAN-00:10 | 15645.05 | 01-JAN-09:10 |
General:Fans:Electricity | 269.86 | 0.00 | 01-JAN-00:10 | 15645.05 | 01-JAN-09:10 |
ExteriorLights:Electricity | 121.54 | 0.00 | 01-JAN-06:20 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.54 | 0.00 | 01-JAN-06:20 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 57.69 | 1218.00 | 01-JAN-09:10 | 11776.47 | 02-JAN-13:20 |
WaterSystems:Electricity | 57.69 | 1218.00 | 01-JAN-09:10 | 11776.47 | 02-JAN-13:20 |
Water Heater:WaterSystems:Electricity | 57.69 | 1218.00 | 01-JAN-09:10 | 11776.47 | 02-JAN-13:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 4396.12 | 0.00 | 01-JAN-00:10 | 447423.68 | 16-JUN-13:00 |
EnergyTransfer:Building | 1270.73 | 0.00 | 01-JAN-00:10 | 131781.91 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 255.25 | 0.00 | 01-JAN-00:10 | 21852.82 | 06-MAY-13:00 |
Heating:EnergyTransfer | 13.68 | 0.00 | 01-JAN-00:10 | 25427.28 | 29-MAY-16:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.85 | 0.00 | 01-JAN-00:10 | 2832.64 | 26-MAY-07:10 |
General:Heating:EnergyTransfer | 13.68 | 0.00 | 01-JAN-00:10 | 25427.28 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.85 | 0.00 | 01-JAN-00:10 | 2832.64 | 26-MAY-07:10 |
Cooling:EnergyTransfer | 1257.05 | 0.00 | 01-JAN-00:10 | 131781.91 | 06-MAY-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 254.40 | 0.00 | 01-JAN-00:10 | 21852.82 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer | 1257.05 | 0.00 | 01-JAN-00:10 | 131781.91 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 254.40 | 0.00 | 01-JAN-00:10 | 21852.82 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 132.87 | 0.00 | 01-JAN-00:10 | 11324.40 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.41 | 0.00 | 01-JAN-00:10 | 1372.22 | 26-MAY-07:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.41 | 0.00 | 01-JAN-00:10 | 1372.22 | 26-MAY-07:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 132.46 | 0.00 | 01-JAN-00:10 | 11324.40 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 132.46 | 0.00 | 01-JAN-00:10 | 11324.40 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE2 | 105.12 | 0.00 | 01-JAN-00:10 | 11377.41 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.96 | 0.00 | 01-JAN-00:10 | 2841.59 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.96 | 0.00 | 01-JAN-00:10 | 2841.59 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 103.16 | 0.00 | 01-JAN-00:10 | 11377.41 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 103.16 | 0.00 | 01-JAN-00:10 | 11377.41 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 105.69 | 0.00 | 01-JAN-00:10 | 11422.90 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.91 | 0.00 | 01-JAN-00:10 | 2838.12 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.91 | 0.00 | 01-JAN-00:10 | 2838.12 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 103.78 | 0.00 | 01-JAN-00:10 | 11422.90 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 103.78 | 0.00 | 01-JAN-00:10 | 11422.90 | 06-MAY-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 104.15 | 0.00 | 01-JAN-00:10 | 11301.00 | 06-MAY-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 2.03 | 0.00 | 01-JAN-00:10 | 2841.83 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 2.03 | 0.00 | 01-JAN-00:10 | 2841.83 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 102.13 | 0.00 | 01-JAN-00:10 | 11301.00 | 06-MAY-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 102.13 | 0.00 | 01-JAN-00:10 | 11301.00 | 06-MAY-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 178.79 | 0.00 | 01-JAN-00:10 | 20160.06 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 1.96 | 0.00 | 01-JAN-00:10 | 5582.25 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 1.96 | 0.00 | 01-JAN-00:10 | 5582.25 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 176.83 | 0.00 | 01-JAN-00:10 | 20160.06 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 176.83 | 0.00 | 01-JAN-00:10 | 20160.06 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE5 | 93.91 | 0.00 | 01-JAN-00:10 | 10688.33 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.13 | 0.00 | 01-JAN-00:10 | 2840.69 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.13 | 0.00 | 01-JAN-00:10 | 2840.69 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 92.78 | 0.00 | 01-JAN-00:10 | 10688.33 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 92.78 | 0.00 | 01-JAN-00:10 | 10688.33 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE6 | 93.40 | 0.00 | 01-JAN-00:10 | 10648.85 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.17 | 0.00 | 01-JAN-00:10 | 2841.23 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.17 | 0.00 | 01-JAN-00:10 | 2841.23 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 92.23 | 0.00 | 01-JAN-00:10 | 10648.85 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 92.23 | 0.00 | 01-JAN-00:10 | 10648.85 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE7 | 93.62 | 0.00 | 01-JAN-00:10 | 10724.22 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.20 | 0.00 | 01-JAN-00:10 | 2839.18 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.20 | 0.00 | 01-JAN-00:10 | 2839.18 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 92.43 | 0.00 | 01-JAN-00:10 | 10724.22 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 92.43 | 0.00 | 01-JAN-00:10 | 10724.22 | 06-MAY-13:10 |
EnergyTransfer:Zone:SMSTORE8 | 107.92 | 0.00 | 01-JAN-00:10 | 12472.44 | 06-MAY-13:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.08 | 0.00 | 01-JAN-00:10 | 2802.39 | 29-MAY-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.08 | 0.00 | 01-JAN-00:10 | 2802.39 | 29-MAY-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 106.85 | 0.00 | 01-JAN-00:10 | 12472.44 | 06-MAY-13:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 106.85 | 0.00 | 01-JAN-00:10 | 12472.44 | 06-MAY-13:10 |
EnergyTransfer:HVAC | 3125.39 | 0.00 | 01-JAN-00:10 | 322722.74 | 16-JUN-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 3125.39 | 0.00 | 01-JAN-00:10 | 322722.74 | 16-JUN-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.850 | -254.394 | 0.000 | 0.000 | 23.185 | 106.728 | 26.357 | 17.251 | 0.000 | 29.025 | 52.605 | 0.000 | -1.161 | 0.000 | -0.445 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.409 | -132.454 | 0.000 | 0.000 | 11.592 | 62.296 | 13.179 | 8.679 | 0.000 | 16.035 | 20.986 | 0.000 | -0.573 | 0.000 | -0.148 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 1.960 | -103.158 | 0.000 | 0.000 | 6.960 | 44.966 | 10.467 | 8.553 | 0.000 | 15.786 | 15.478 | 0.000 | -0.779 | 0.000 | -0.233 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 1.908 | -103.777 | 0.000 | 0.000 | 6.960 | 44.966 | 10.467 | 8.544 | 0.000 | 15.778 | 16.197 | 0.000 | -0.801 | 0.000 | -0.243 | -0.002 |
SMSTORE4 | 0.000 | 0.000 | 2.026 | -102.122 | 0.000 | 0.000 | 6.961 | 44.966 | 10.467 | 8.556 | 0.000 | 15.788 | 14.360 | 0.000 | -0.775 | 0.000 | -0.226 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 1.958 | -176.824 | 0.000 | 0.000 | 23.901 | 51.668 | 19.261 | 17.075 | 0.000 | 27.640 | 37.122 | 0.000 | -1.376 | 0.000 | -0.425 | -0.002 |
SMSTORE5 | 0.000 | 0.000 | 1.135 | -92.774 | 0.000 | 0.000 | 11.950 | 26.679 | 9.631 | 8.569 | 0.000 | 15.732 | 19.939 | 0.000 | -0.653 | 0.000 | -0.208 | -0.001 |
SMSTORE6 | 0.000 | 0.000 | 1.166 | -92.228 | 0.000 | 0.000 | 11.950 | 26.679 | 9.631 | 8.575 | 0.000 | 15.735 | 19.343 | 0.000 | -0.646 | 0.000 | -0.205 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 1.198 | -92.423 | 0.000 | 0.000 | 11.950 | 26.679 | 9.631 | 8.569 | 0.000 | 15.737 | 19.507 | 0.000 | -0.648 | 0.000 | -0.200 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 1.076 | -106.840 | 0.000 | 0.000 | 11.949 | 26.679 | 9.631 | 8.459 | 0.000 | 16.488 | 33.708 | 0.000 | -0.694 | 0.000 | -0.455 | -0.001 |
Total Facility | 0.000 | 0.000 | 13.685 | -1256.993 | 0.000 | 0.000 | 127.358 | 462.305 | 128.721 | 102.830 | 0.000 | 183.744 | 249.244 | 0.000 | -8.106 | 0.000 | -2.788 | -0.010 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -40683.37 | 0.00 | 0.00 | 158.25 | 2916.31 | 749.03 | 1627.85 | 0.00 | 0.00 | 35255.11 | 0.00 | -0.00 | 0.00 | -23.17 | 0.00 |
SMSTORE1 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -22561.70 | 0.00 | 0.00 | 79.09 | 1702.23 | 374.52 | 813.07 | 0.00 | 0.00 | 19601.55 | 0.00 | -0.00 | 0.00 | -8.76 | 0.00 |
SMSTORE2 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -20151.02 | 0.00 | 0.00 | 79.08 | 1536.36 | 374.52 | 476.09 | 0.00 | 34.11 | 17650.87 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -20208.12 | 0.00 | 0.00 | 79.08 | 1536.36 | 374.52 | 475.24 | 0.00 | 34.25 | 17708.68 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25-FEB-08:61 | 0.00 | 0.00 | 0.00 | -20053.11 | 0.00 | 0.00 | 79.08 | 1536.36 | 374.52 | 476.53 | 0.00 | 34.02 | 17552.61 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -36979.24 | 0.00 | 0.00 | 347.93 | 1920.56 | 749.03 | 1139.30 | 0.00 | 0.00 | 32875.24 | 0.00 | -0.00 | 0.00 | -52.81 | 0.00 |
SMSTORE5 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -19365.71 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 569.98 | 0.00 | 0.00 | 17283.74 | 0.00 | -0.00 | 0.00 | -28.15 | 0.00 |
SMSTORE6 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -19275.39 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 570.39 | 0.00 | 0.00 | 17193.15 | 0.00 | -0.00 | 0.00 | -28.29 | 0.00 |
SMSTORE7 | 25-FEB-09:01 | 0.00 | 0.00 | 0.00 | -19305.25 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 570.19 | 0.00 | 0.00 | 17223.08 | 0.00 | -0.00 | 0.00 | -28.17 | 0.00 |
SMSTORE8 | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -21405.27 | 0.00 | 0.00 | 174.03 | 991.67 | 374.52 | 804.03 | 0.00 | 0.00 | 19073.68 | 0.00 | -0.00 | 0.00 | -12.65 | 0.00 |
Total Facility | 24-FEB-09:01 | 0.00 | 0.00 | 0.00 | -194479.29 | 0.00 | 0.00 | 1873.13 | 19263.00 | 5393.02 | 9826.48 | 0.00 | 203.75 | 158033.34 | 0.00 | 0.00 | 0.00 | -113.44 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 28-MAY-07:07 | 0.00 | 0.00 | 7101.81 | 0.00 | 0.00 | 0.00 | 158.08 | 291.61 | 74.90 | 602.48 | 0.00 | 606.05 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8834.95 |
SMSTORE1 | 28-MAY-07:06 | 0.00 | 0.00 | 3813.04 | 0.00 | 0.00 | 0.00 | 79.09 | 170.22 | 37.45 | 302.02 | 0.00 | 332.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -4733.92 |
SMSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 3358.85 | 0.00 | 0.00 | 0.00 | 98.50 | 1536.36 | 374.52 | 419.38 | 0.00 | 2603.25 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8390.86 |
SMSTORE3 | 29-MAY-16:01 | 0.00 | 0.00 | 3357.07 | 0.00 | 0.00 | 0.00 | 98.50 | 1536.36 | 374.52 | 418.97 | 0.00 | 2602.68 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8388.10 |
SMSTORE4 | 29-MAY-16:01 | 0.00 | 0.00 | 3357.84 | 0.00 | 0.00 | 0.00 | 98.50 | 1536.36 | 374.52 | 419.20 | 0.00 | 2603.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8389.86 |
LGSTORE2 | 29-MAY-16:01 | 0.00 | 0.00 | 6598.38 | 0.00 | 0.00 | 0.00 | 433.43 | 1920.56 | 749.03 | 835.05 | 0.00 | 4575.85 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -15112.30 |
SMSTORE5 | 29-MAY-16:01 | 0.00 | 0.00 | 3342.13 | 0.00 | 0.00 | 0.00 | 216.71 | 991.67 | 374.52 | 420.65 | 0.00 | 2607.74 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7953.41 |
SMSTORE6 | 29-MAY-16:01 | 0.00 | 0.00 | 3341.47 | 0.00 | 0.00 | 0.00 | 216.71 | 991.67 | 374.52 | 420.88 | 0.00 | 2608.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7953.33 |
SMSTORE7 | 29-MAY-16:01 | 0.00 | 0.00 | 3340.30 | 0.00 | 0.00 | 0.00 | 216.71 | 991.67 | 374.52 | 420.28 | 0.00 | 2607.65 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7951.12 |
SMSTORE8 | 19-MAR-09:06 | 0.00 | 0.00 | 3368.78 | 0.00 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 598.30 | 0.00 | 390.14 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5897.35 |
Total Facility | 29-MAY-16:01 | -29569.41 | 29569.41 | 30042.10 | -29569.41 | 0.00 | 0.00 | 5142.03 | 19271.53 | 5393.02 | 5048.20 | 0.00 | 30361.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -65689.10 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4015 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4015 | 0.1713 | 1.0000 | Not calculated | 0.4115 | 0.1713 | ||
PSZ-AC_2:2 | 1.2347 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2347 | 0.1666 | 1.0000 | Not calculated | 0.2057 | 0.1666 | ||
PSZ-AC_3:3 | 1.2261 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2333 | 0.1668 | 1.0000 | Not calculated | 0.2057 | 0.1668 | ||
PSZ-AC_4:4 | 1.2188 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2365 | 0.1664 | 1.0000 | Not calculated | 0.2057 | 0.1664 | ||
PSZ-AC_5:5 | 1.2218 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2291 | 0.1674 | 1.0000 | Not calculated | 0.2057 | 0.1674 | ||
PSZ-AC_6:6 | 2.1926 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1926 | 0.1877 | 1.0000 | Not calculated | 0.4115 | 0.1877 | ||
PSZ-AC_7:7 | 1.1523 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1524 | 0.1785 | 1.0000 | Not calculated | 0.2057 | 0.1785 | ||
PSZ-AC_8:8 | 1.1475 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1476 | 0.1793 | 1.0000 | Not calculated | 0.2057 | 0.1793 | ||
PSZ-AC_9:9 | 1.1500 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1500 | 0.1789 | 1.0000 | Not calculated | 0.2057 | 0.1789 | ||
PSZ-AC_10:10 | 1.3073 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3073 | 0.1574 | 1.0000 | Not calculated | 0.2057 | 0.1574 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.4015 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.4015 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1713 | ||
PSZ-AC_2:2 | 1.2347 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2347 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1666 | ||
PSZ-AC_3:3 | 1.2261 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2261 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1678 | ||
PSZ-AC_4:4 | 1.2188 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2188 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1688 | ||
PSZ-AC_5:5 | 1.2218 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2218 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1684 | ||
PSZ-AC_6:6 | 2.1926 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.1926 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1877 | ||
PSZ-AC_7:7 | 1.1523 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1523 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1785 | ||
PSZ-AC_8:8 | 1.1475 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1475 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1793 | ||
PSZ-AC_9:9 | 1.1500 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1500 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1789 | ||
PSZ-AC_10:10 | 1.3073 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3073 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1574 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4015 | 2.4015 | 2.4015 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2347 | 1.2347 | 1.2347 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2261 | 1.2261 | 1.2261 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2188 | 1.2188 | 1.2188 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2218 | 1.2218 | 1.2218 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1926 | 2.1926 | 2.1926 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1523 | 1.1523 | 1.1523 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1475 | 1.1475 | 1.1475 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1500 | 1.1500 | 1.1500 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3073 | 1.3073 | 1.3073 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4015 | 2.4015 | 2.4015 | 2.4015 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2347 | 1.2347 | 1.2347 | 1.2347 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2261 | 1.2333 | 1.2261 | 1.2261 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2188 | 1.2365 | 1.2188 | 1.2188 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2218 | 1.2291 | 1.2218 | 1.2218 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1926 | 2.1926 | 2.1926 | 2.1926 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1523 | 1.1524 | 1.1523 | 1.1523 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1475 | 1.1476 | 1.1475 | 1.1475 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1500 | 1.1500 | 1.1500 | 1.1500 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3073 | 1.3073 | 1.3073 | 1.3073 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.4015 | 2.4015 | 2.4015 | No | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2347 | 1.2347 | 1.2347 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2261 | 1.2261 | 1.2261 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2188 | 1.2188 | 1.2188 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2218 | 1.2218 | 1.2218 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.1926 | 2.1926 | 2.1926 | No | 0.4115 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1523 | 1.1523 | 1.1523 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1475 | 1.1475 | 1.1475 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1500 | 1.1500 | 1.1500 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3073 | 1.3073 | 1.3073 | No | 0.2057 | 1.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.4015 | 2.4015 | 2.4015 | 2.4015 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.2347 | 1.2347 | 1.2347 | 1.2347 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.2261 | 1.2261 | 1.2261 | 1.2261 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.2188 | 1.2188 | 1.2188 | 1.2188 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.2218 | 1.2218 | 1.2218 | 1.2218 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.1926 | 2.1926 | 2.1926 | 2.1926 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.1523 | 1.1523 | 1.1523 | 1.1523 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.1475 | 1.1475 | 1.1475 | 1.1475 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.1500 | 1.1500 | 1.1500 | 1.1500 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.3073 | 1.3073 | 1.3073 | 1.3073 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Ho Chi Minh City-Tan Son Nhat Intl AP - VNM IWEC2 WMO#=489000 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 78.33 |
Number of hours not met | 78.33 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 825.09 | 85321.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.54 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 269.86 | 15645.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.69 | 11776.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1865.20 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1865.20 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 394.72 |
Fans (All) | 129.10 |
Service Water Heating | 27.60 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 892.30 |
Subtotal | 892.30 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.79 |
Space Heating | 0.00 |
Space Cooling | 44.24 |
Fans (All) | 14.47 |
Service Water Heating | 3.09 |
Receptacle Equipment | 6.90 |
Miscellaneous | 6.52 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 7963.83 | 796.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8422.67 | 337.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4901.17 | 3855.17 | 3.67 | 0.00 | 0.00 |
SMSTORE3 | 4763.17 | 3992.33 | 4.50 | 0.00 | 0.00 |
SMSTORE4 | 5094.67 | 3661.67 | 3.67 | 0.00 | 0.00 |
LGSTORE2 | 6495.83 | 2260.67 | 3.50 | 0.00 | 0.00 |
SMSTORE5 | 6694.17 | 2062.50 | 3.33 | 0.00 | 0.00 |
SMSTORE6 | 6745.00 | 2011.67 | 3.33 | 0.00 | 0.00 |
SMSTORE7 | 6820.50 | 1936.00 | 3.50 | 0.00 | 0.00 |
SMSTORE8 | 6185.83 | 2516.50 | 57.67 | 0.00 | 0.00 |
Min | 4763.17 | 337.33 | 0.00 | 0.00 | 0.00 |
Max | 8422.67 | 3992.33 | 57.67 | 0.00 | 0.00 |
Average | 6408.68 | 2343.00 | 8.32 | 0.00 | 0.00 |
Sum | 64086.83 | 23430.00 | 83.17 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 88679.67 | 361.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43621.50 | 155.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25258.50 | 214.67 | 1.83 | 0.00 | 0.00 |
SMSTORE3 | 25258.17 | 214.83 | 2.00 | 0.00 | 0.00 |
SMSTORE4 | 25262.50 | 210.67 | 1.83 | 0.00 | 0.00 |
LGSTORE2 | 92762.00 | 439.00 | 10.00 | 0.00 | 0.00 |
SMSTORE5 | 45682.50 | 224.50 | 5.00 | 0.00 | 0.00 |
SMSTORE6 | 45683.50 | 223.50 | 5.00 | 0.00 | 0.00 |
SMSTORE7 | 45683.50 | 223.50 | 5.00 | 0.00 | 0.00 |
SMSTORE8 | 45667.00 | 238.50 | 6.50 | 0.00 | 0.00 |
Min | 25258.17 | 155.50 | 0.00 | 0.00 | 0.00 |
Max | 92762.00 | 439.00 | 10.00 | 0.00 | 0.00 |
Average | 48355.88 | 250.60 | 3.72 | 0.00 | 0.00 |
Sum | 483558.83 | 2506.00 | 37.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 2875.33 | 5884.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 5083.83 | 3676.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 1783.83 | 6974.67 | 1.50 | 0.00 | 0.00 |
SMSTORE3 | 1793.17 | 6963.50 | 3.33 | 0.00 | 0.00 |
SMSTORE4 | 1750.00 | 7008.33 | 1.67 | 0.00 | 0.00 |
LGSTORE2 | 1375.50 | 7382.50 | 2.00 | 0.00 | 0.00 |
SMSTORE5 | 1382.67 | 7374.67 | 2.67 | 0.00 | 0.00 |
SMSTORE6 | 1365.83 | 7391.67 | 2.50 | 0.00 | 0.00 |
SMSTORE7 | 1375.00 | 7382.83 | 2.17 | 0.00 | 0.00 |
SMSTORE8 | 1739.33 | 6932.33 | 88.33 | 0.00 | 0.00 |
Min | 1365.83 | 3676.17 | 0.00 | 0.00 | 0.00 |
Max | 5083.83 | 7391.67 | 88.33 | 0.00 | 0.00 |
Average | 2052.45 | 6697.13 | 10.42 | 0.00 | 0.00 |
Sum | 20524.50 | 66971.33 | 104.17 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 46069.67 | 42971.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 25203.17 | 18573.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 11022.33 | 14452.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 11053.33 | 14421.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 10813.17 | 14661.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 32647.00 | 60564.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 15854.00 | 30058.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 15679.67 | 30232.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 15778.67 | 30133.33 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 20222.17 | 25689.83 | 0.00 | 0.00 | 0.00 |
Min | 10813.17 | 14421.67 | 0.00 | 0.00 | 0.00 |
Max | 46069.67 | 60564.00 | 0.00 | 0.00 | 0.00 |
Average | 20434.32 | 28175.88 | 0.00 | 0.00 | 0.00 |
Sum | 204343.17 | 281758.83 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:27
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0A
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY VNM_HOCHIMINH_TANSONHOA
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 26.415 |
February | 27.500 |
March | 28.331 |
April | 29.151 |
May | 29.006 |
June | 28.856 |
July | 27.250 |
August | 27.543 |
September | 27.578 |
October | 26.894 |
November | 26.683 |
December | 25.974 |
Annual Sum or Average | 27.594 |
Minimum of Months | 25.974 |
Maximum of Months | 29.151 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.211694E+11 | 39528.84 | 23-JAN-09:01 | 24.37 | 19.55 | 0.141227E+10 | 1685.86 | 01-JAN-18:40 | 24.37 | 19.55 |
February | 0.200709E+11 | 40693.99 | 24-FEB-09:01 | 25.53 | 19.50 | 0.127508E+10 | 1685.86 | 26-FEB-18:40 | 29.87 | 23.11 |
March | 0.226061E+11 | 38370.54 | 04-MAR-09:01 | 29.40 | 20.98 | 0.140054E+10 | 1685.86 | 12-MAR-17:30 | 30.50 | 23.70 |
April | 0.220894E+11 | 31215.82 | 23-APR-07:02 | 25.42 | 24.10 | 0.136440E+10 | 1685.86 | 30-APR-17:30 | 31.00 | 26.90 |
May | 0.227363E+11 | 28398.22 | 14-MAY-07:02 | 27.50 | 26.59 | 0.140466E+10 | 1685.86 | 14-MAY-17:30 | 32.00 | 26.79 |
June | 0.226653E+11 | 31799.79 | 25-JUN-07:02 | 25.75 | 24.65 | 0.135747E+10 | 1685.86 | 11-JUN-17:30 | 25.75 | 24.65 |
July | 0.212791E+11 | 36475.60 | 16-JUL-07:01 | 24.92 | 23.77 | 0.141543E+10 | 1685.86 | 30-JUL-17:40 | 30.43 | 24.41 |
August | 0.207720E+11 | 29907.81 | 27-AUG-07:02 | 26.67 | 25.88 | 0.139715E+10 | 1685.86 | 27-AUG-17:40 | 30.67 | 26.92 |
September | 0.205279E+11 | 32772.63 | 10-SEP-07:02 | 26.50 | 25.49 | 0.136775E+10 | 1685.86 | 04-SEP-17:30 | 26.50 | 25.49 |
October | 0.200705E+11 | 32720.90 | 08-OCT-07:02 | 25.75 | 24.25 | 0.141247E+10 | 1685.86 | 22-OCT-17:30 | 24.25 | 23.31 |
November | 0.197822E+11 | 37678.50 | 25-NOV-09:01 | 23.67 | 20.24 | 0.136596E+10 | 1685.86 | 11-NOV-18:30 | 23.67 | 20.24 |
December | 0.206325E+11 | 38496.93 | 27-DEC-09:01 | 26.40 | 20.69 | 0.141918E+10 | 1685.86 | 17-DEC-18:30 | 26.40 | 20.69 |
Annual Sum or Average | 0.254402E+12 | 0.165924E+11 | ||||||||
Minimum of Months | 0.197822E+11 | 28398.22 | 23.67 | 19.50 | 0.127508E+10 | 1685.86 | 23.67 | 19.55 | ||
Maximum of Months | 0.227363E+11 | 40693.99 | 29.40 | 26.59 | 0.141918E+10 | 1685.86 | 32.00 | 26.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.111072E+11 | 22142.03 | 16-JAN-08:62 | 22.05 | 20.01 | 0.706167E+09 | 842.90 | 29-JAN-18:40 | 29.33 | 23.62 |
February | 0.104419E+11 | 22565.79 | 24-FEB-09:01 | 25.53 | 19.50 | 0.637546E+09 | 842.91 | 26-FEB-18:40 | 29.87 | 23.11 |
March | 0.116579E+11 | 20836.36 | 03-MAR-09:01 | 27.33 | 21.00 | 0.700260E+09 | 842.91 | 12-MAR-17:30 | 30.50 | 23.70 |
April | 0.113889E+11 | 19661.96 | 23-APR-07:02 | 25.42 | 24.10 | 0.682179E+09 | 842.91 | 30-APR-17:30 | 31.00 | 26.90 |
May | 0.117930E+11 | 18540.02 | 14-MAY-07:02 | 27.50 | 26.59 | 0.702314E+09 | 842.91 | 14-MAY-17:30 | 32.00 | 26.79 |
June | 0.116921E+11 | 20259.91 | 25-JUN-07:02 | 25.75 | 24.65 | 0.678721E+09 | 842.91 | 11-JUN-17:30 | 25.75 | 24.65 |
July | 0.110553E+11 | 22298.97 | 16-JUL-07:01 | 24.92 | 23.77 | 0.707711E+09 | 842.90 | 30-JUL-17:40 | 30.43 | 24.41 |
August | 0.108164E+11 | 18921.09 | 27-AUG-07:02 | 26.67 | 25.88 | 0.698564E+09 | 842.91 | 27-AUG-17:40 | 30.67 | 26.92 |
September | 0.106776E+11 | 20302.68 | 10-SEP-07:02 | 26.50 | 25.49 | 0.683863E+09 | 842.91 | 04-SEP-17:30 | 26.50 | 25.49 |
October | 0.105809E+11 | 20503.88 | 08-OCT-07:02 | 25.75 | 24.25 | 0.706246E+09 | 842.90 | 22-OCT-17:40 | 23.83 | 22.97 |
November | 0.103989E+11 | 20912.32 | 25-NOV-09:01 | 23.67 | 20.24 | 0.682982E+09 | 842.90 | 26-NOV-18:30 | 23.95 | 22.31 |
December | 0.108505E+11 | 21213.34 | 25-DEC-08:62 | 24.33 | 24.11 | 0.709610E+09 | 842.90 | 17-DEC-18:40 | 24.33 | 24.11 |
Annual Sum or Average | 0.132461E+12 | 0.829616E+10 | ||||||||
Minimum of Months | 0.103989E+11 | 18540.02 | 22.05 | 19.50 | 0.637546E+09 | 842.90 | 23.83 | 22.31 | ||
Maximum of Months | 0.117930E+11 | 22565.79 | 27.50 | 26.59 | 0.709610E+09 | 842.91 | 32.00 | 26.92 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.864285E+10 | 19273.35 | 24-JAN-08:62 | 19.83 | 17.92 | 0.421483E+09 | 842.90 | 07-JAN-13:09 | 19.83 | 17.92 |
February | 0.819752E+10 | 20156.76 | 25-FEB-08:61 | 26.67 | 20.13 | 0.382918E+09 | 842.90 | 18-FEB-13:09 | 26.67 | 20.13 |
March | 0.925261E+10 | 19208.20 | 04-MAR-08:61 | 26.50 | 20.59 | 0.432758E+09 | 842.90 | 11-MAR-13:09 | 32.67 | 25.12 |
April | 0.887884E+10 | 15561.17 | 27-APR-07:01 | 27.08 | 24.31 | 0.412067E+09 | 842.90 | 22-APR-12:09 | 27.08 | 24.31 |
May | 0.929061E+10 | 13975.97 | 09-MAY-07:01 | 24.50 | 24.40 | 0.427281E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.927048E+10 | 14477.91 | 27-JUN-07:01 | 25.75 | 24.54 | 0.418143E+09 | 842.90 | 03-JUN-12:00 | 25.75 | 24.54 |
July | 0.842975E+10 | 16251.76 | 06-JUL-07:01 | 25.92 | 23.26 | 0.421075E+09 | 842.90 | 08-JUL-12:09 | 29.70 | 24.62 |
August | 0.846733E+10 | 14609.32 | 30-AUG-07:01 | 25.50 | 24.07 | 0.432607E+09 | 842.90 | 05-AUG-12:00 | 25.50 | 24.07 |
September | 0.822201E+10 | 14423.67 | 16-SEP-07:01 | 24.75 | 24.21 | 0.411860E+09 | 842.90 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.810279E+10 | 14552.99 | 11-OCT-07:01 | 24.92 | 24.20 | 0.421434E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.805755E+10 | 18883.28 | 25-NOV-08:61 | 22.25 | 19.45 | 0.407130E+09 | 842.90 | 25-NOV-13:00 | 26.20 | 22.05 |
December | 0.835043E+10 | 19219.49 | 27-DEC-08:61 | 23.50 | 19.75 | 0.420877E+09 | 842.90 | 16-DEC-13:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.103163E+12 | 0.500963E+10 | ||||||||
Minimum of Months | 0.805755E+10 | 13975.97 | 19.83 | 17.92 | 0.382918E+09 | 842.90 | 19.83 | 17.92 | ||
Maximum of Months | 0.929061E+10 | 20156.76 | 27.08 | 24.54 | 0.432758E+09 | 842.90 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.869148E+10 | 19357.63 | 24-JAN-08:62 | 19.83 | 17.92 | 0.421490E+09 | 842.90 | 07-JAN-13:09 | 19.83 | 17.92 |
February | 0.824273E+10 | 20213.88 | 25-FEB-08:61 | 26.67 | 20.13 | 0.382923E+09 | 842.90 | 18-FEB-13:09 | 26.67 | 20.13 |
March | 0.930060E+10 | 19264.84 | 04-MAR-08:61 | 26.50 | 20.59 | 0.432763E+09 | 842.90 | 11-MAR-13:09 | 32.67 | 25.12 |
April | 0.893606E+10 | 15608.55 | 27-APR-07:01 | 27.08 | 24.31 | 0.412071E+09 | 842.90 | 22-APR-12:09 | 27.08 | 24.31 |
May | 0.936552E+10 | 14075.92 | 09-MAY-07:01 | 24.50 | 24.40 | 0.427287E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.934032E+10 | 14536.00 | 27-JUN-07:01 | 25.75 | 24.54 | 0.418150E+09 | 842.90 | 03-JUN-12:00 | 25.75 | 24.54 |
July | 0.849182E+10 | 16321.19 | 06-JUL-07:01 | 25.92 | 23.26 | 0.421082E+09 | 842.90 | 08-JUL-12:09 | 29.70 | 24.62 |
August | 0.851047E+10 | 14660.88 | 30-AUG-07:01 | 25.50 | 24.07 | 0.432612E+09 | 842.90 | 05-AUG-12:00 | 25.50 | 24.07 |
September | 0.827483E+10 | 14490.66 | 09-SEP-07:01 | 25.08 | 24.00 | 0.411864E+09 | 842.90 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.814944E+10 | 14616.95 | 11-OCT-07:01 | 24.92 | 24.20 | 0.421435E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.809430E+10 | 18970.05 | 25-NOV-08:61 | 22.25 | 19.45 | 0.407132E+09 | 842.90 | 25-NOV-13:00 | 26.20 | 22.05 |
December | 0.838404E+10 | 19312.88 | 27-DEC-08:61 | 23.50 | 19.75 | 0.420878E+09 | 842.90 | 16-DEC-13:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.103782E+12 | 0.500969E+10 | ||||||||
Minimum of Months | 0.809430E+10 | 14075.92 | 19.83 | 17.92 | 0.382923E+09 | 842.90 | 19.83 | 17.92 | ||
Maximum of Months | 0.936552E+10 | 20213.88 | 27.08 | 24.54 | 0.432763E+09 | 842.90 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.855033E+10 | 19153.75 | 24-JAN-08:62 | 19.83 | 17.92 | 0.421454E+09 | 842.90 | 07-JAN-13:09 | 19.83 | 17.92 |
February | 0.811633E+10 | 20058.85 | 25-FEB-08:61 | 26.67 | 20.13 | 0.382893E+09 | 842.90 | 18-FEB-13:09 | 26.67 | 20.13 |
March | 0.915768E+10 | 19100.53 | 04-MAR-08:61 | 26.50 | 20.59 | 0.432730E+09 | 842.90 | 11-MAR-13:09 | 32.67 | 25.12 |
April | 0.880146E+10 | 15438.53 | 27-APR-07:01 | 27.08 | 24.31 | 0.412041E+09 | 842.90 | 22-APR-12:09 | 27.08 | 24.31 |
May | 0.923190E+10 | 13914.64 | 09-MAY-07:01 | 24.50 | 24.40 | 0.427259E+09 | 842.90 | 27-MAY-12:09 | 33.22 | 26.33 |
June | 0.920242E+10 | 14387.26 | 27-JUN-07:01 | 25.75 | 24.54 | 0.418118E+09 | 842.90 | 03-JUN-12:00 | 25.75 | 24.54 |
July | 0.835540E+10 | 16200.65 | 06-JUL-07:01 | 25.92 | 23.26 | 0.421050E+09 | 842.90 | 08-JUL-12:09 | 29.70 | 24.62 |
August | 0.836380E+10 | 14497.41 | 30-AUG-07:01 | 25.50 | 24.07 | 0.432579E+09 | 842.90 | 05-AUG-12:00 | 25.50 | 24.07 |
September | 0.814026E+10 | 14311.14 | 09-SEP-07:01 | 25.08 | 24.00 | 0.411835E+09 | 842.90 | 16-SEP-12:00 | 24.40 | 24.15 |
October | 0.800912E+10 | 14467.77 | 11-OCT-07:01 | 24.92 | 24.20 | 0.421404E+09 | 842.90 | 14-OCT-12:09 | 30.33 | 26.72 |
November | 0.795911E+10 | 18750.09 | 25-NOV-08:61 | 22.25 | 19.45 | 0.407102E+09 | 842.90 | 25-NOV-13:00 | 26.20 | 22.05 |
December | 0.823924E+10 | 19105.67 | 27-DEC-08:61 | 23.50 | 19.75 | 0.420842E+09 | 842.90 | 16-DEC-13:00 | 23.50 | 19.75 |
Annual Sum or Average | 0.102127E+12 | 0.500931E+10 | ||||||||
Minimum of Months | 0.795911E+10 | 13914.64 | 19.83 | 17.92 | 0.382893E+09 | 842.90 | 19.83 | 17.92 | ||
Maximum of Months | 0.923190E+10 | 20058.85 | 27.08 | 24.54 | 0.432730E+09 | 842.90 | 33.22 | 26.72 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.148069E+11 | 34870.53 | 21-JAN-09:01 | 25.35 | 20.11 | 0.143773E+10 | 2247.80 | 07-JAN-15:00 | 25.35 | 20.11 |
February | 0.140685E+11 | 36988.31 | 25-FEB-09:01 | 25.22 | 19.84 | 0.130922E+10 | 2247.80 | 11-FEB-15:00 | 25.22 | 19.84 |
March | 0.159141E+11 | 35064.27 | 04-MAR-09:01 | 29.40 | 20.98 | 0.148258E+10 | 2247.80 | 11-MAR-15:09 | 32.10 | 24.95 |
April | 0.152602E+11 | 28166.22 | 27-APR-08:61 | 28.25 | 24.48 | 0.141287E+10 | 2247.80 | 22-APR-14:00 | 28.25 | 24.48 |
May | 0.160448E+11 | 24394.33 | 06-MAY-08:61 | 32.17 | 26.12 | 0.146063E+10 | 2247.80 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.160427E+11 | 26663.14 | 21-JUN-08:61 | 28.17 | 24.45 | 0.143234E+10 | 2247.80 | 03-JUN-14:00 | 28.17 | 24.45 |
July | 0.144520E+11 | 29664.33 | 06-JUL-08:61 | 26.75 | 24.00 | 0.144089E+10 | 2247.80 | 01-JUL-14:00 | 26.75 | 24.00 |
August | 0.144649E+11 | 25703.26 | 30-AUG-08:61 | 27.33 | 25.50 | 0.148221E+10 | 2247.81 | 19-AUG-14:00 | 27.33 | 25.50 |
September | 0.140630E+11 | 26141.16 | 28-SEP-08:61 | 26.33 | 24.77 | 0.141249E+10 | 2247.81 | 16-SEP-14:09 | 26.33 | 24.77 |
October | 0.138031E+11 | 27648.97 | 20-OCT-08:61 | 27.67 | 23.84 | 0.143781E+10 | 2247.80 | 21-OCT-14:00 | 29.50 | 25.84 |
November | 0.137167E+11 | 33971.98 | 25-NOV-09:01 | 23.67 | 20.24 | 0.138452E+10 | 2247.81 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.141948E+11 | 35399.74 | 27-DEC-09:01 | 26.40 | 20.69 | 0.144028E+10 | 2247.81 | 09-DEC-15:00 | 26.40 | 20.69 |
Annual Sum or Average | 0.176832E+12 | 0.171336E+11 | ||||||||
Minimum of Months | 0.137167E+11 | 24394.33 | 23.67 | 19.84 | 0.130922E+10 | 2247.80 | 25.22 | 19.84 | ||
Maximum of Months | 0.160448E+11 | 36988.31 | 32.17 | 26.12 | 0.148258E+10 | 2247.81 | 32.10 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.776908E+10 | 18254.33 | 21-JAN-09:01 | 25.35 | 20.11 | 0.718853E+09 | 1123.88 | 28-JAN-15:39 | 32.07 | 21.72 |
February | 0.738902E+10 | 19370.68 | 25-FEB-09:01 | 25.22 | 19.84 | 0.654594E+09 | 1123.88 | 04-FEB-15:20 | 25.22 | 19.84 |
March | 0.836143E+10 | 18359.24 | 04-MAR-09:01 | 29.40 | 20.98 | 0.741271E+09 | 1123.88 | 25-MAR-14:00 | 34.00 | 24.67 |
April | 0.802228E+10 | 14774.18 | 27-APR-08:61 | 28.25 | 24.48 | 0.706412E+09 | 1123.88 | 01-APR-14:20 | 28.25 | 24.48 |
May | 0.843485E+10 | 12808.92 | 06-MAY-08:61 | 32.17 | 26.12 | 0.730288E+09 | 1123.88 | 06-MAY-14:20 | 37.00 | 27.34 |
June | 0.841841E+10 | 14123.85 | 21-JUN-08:61 | 28.17 | 24.45 | 0.716154E+09 | 1123.88 | 24-JUN-14:09 | 35.50 | 27.39 |
July | 0.757004E+10 | 15456.15 | 06-JUL-08:61 | 26.75 | 24.00 | 0.720423E+09 | 1123.88 | 15-JUL-14:39 | 33.00 | 25.65 |
August | 0.758389E+10 | 13489.27 | 30-AUG-08:61 | 27.33 | 25.50 | 0.741085E+09 | 1123.88 | 26-AUG-14:20 | 27.33 | 25.50 |
September | 0.737469E+10 | 13705.41 | 28-SEP-08:61 | 26.33 | 24.77 | 0.706219E+09 | 1123.88 | 30-SEP-14:09 | 32.50 | 27.49 |
October | 0.723261E+10 | 14487.57 | 20-OCT-08:61 | 27.67 | 23.84 | 0.718886E+09 | 1123.88 | 07-OCT-14:09 | 27.67 | 23.84 |
November | 0.718285E+10 | 17796.42 | 25-NOV-09:01 | 23.67 | 20.24 | 0.692245E+09 | 1123.88 | 04-NOV-14:20 | 23.67 | 20.24 |
December | 0.743877E+10 | 18558.02 | 27-DEC-09:01 | 26.40 | 20.69 | 0.720120E+09 | 1123.88 | 30-DEC-15:09 | 30.88 | 25.17 |
Annual Sum or Average | 0.927779E+11 | 0.856655E+10 | ||||||||
Minimum of Months | 0.718285E+10 | 12808.92 | 23.67 | 19.84 | 0.654594E+09 | 1123.88 | 23.67 | 19.84 | ||
Maximum of Months | 0.843485E+10 | 19370.68 | 32.17 | 26.12 | 0.741271E+09 | 1123.88 | 37.00 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.771760E+10 | 18161.90 | 21-JAN-09:01 | 25.35 | 20.11 | 0.718840E+09 | 1123.88 | 14-JAN-15:09 | 25.35 | 20.11 |
February | 0.734591E+10 | 19280.34 | 25-FEB-09:01 | 25.22 | 19.84 | 0.654587E+09 | 1123.88 | 04-FEB-15:20 | 25.22 | 19.84 |
March | 0.831534E+10 | 18272.65 | 04-MAR-09:01 | 29.40 | 20.98 | 0.741264E+09 | 1123.88 | 25-MAR-14:00 | 34.00 | 24.67 |
April | 0.798243E+10 | 14695.40 | 27-APR-08:61 | 28.25 | 24.48 | 0.706406E+09 | 1123.88 | 01-APR-14:20 | 28.25 | 24.48 |
May | 0.838997E+10 | 12736.74 | 06-MAY-08:61 | 32.17 | 26.12 | 0.730281E+09 | 1123.88 | 06-MAY-14:20 | 37.00 | 27.34 |
June | 0.837247E+10 | 13896.15 | 21-JUN-08:61 | 28.17 | 24.45 | 0.716143E+09 | 1123.88 | 24-JUN-14:09 | 35.50 | 27.39 |
July | 0.752621E+10 | 15373.62 | 06-JUL-08:61 | 26.75 | 24.00 | 0.720414E+09 | 1123.88 | 15-JUL-14:39 | 33.00 | 25.65 |
August | 0.753805E+10 | 13409.93 | 30-AUG-08:61 | 27.33 | 25.50 | 0.741079E+09 | 1123.88 | 26-AUG-14:20 | 27.33 | 25.50 |
September | 0.733416E+10 | 13625.74 | 28-SEP-08:61 | 26.33 | 24.77 | 0.706218E+09 | 1123.88 | 30-SEP-14:09 | 32.50 | 27.49 |
October | 0.718655E+10 | 14403.39 | 20-OCT-08:61 | 27.67 | 23.84 | 0.718879E+09 | 1123.88 | 07-OCT-14:20 | 27.67 | 23.84 |
November | 0.713463E+10 | 17694.74 | 25-NOV-09:01 | 23.67 | 20.24 | 0.692237E+09 | 1123.88 | 04-NOV-14:20 | 23.67 | 20.24 |
December | 0.738833E+10 | 18469.17 | 27-DEC-09:01 | 26.40 | 20.69 | 0.720112E+09 | 1123.88 | 30-DEC-15:09 | 30.88 | 25.17 |
Annual Sum or Average | 0.922316E+11 | 0.856646E+10 | ||||||||
Minimum of Months | 0.713463E+10 | 12736.74 | 23.67 | 19.84 | 0.654587E+09 | 1123.88 | 23.67 | 19.84 | ||
Maximum of Months | 0.838997E+10 | 19280.34 | 32.17 | 26.12 | 0.741264E+09 | 1123.88 | 37.00 | 27.49 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.770829E+10 | 18173.04 | 21-JAN-09:01 | 25.35 | 20.11 | 0.718826E+09 | 1123.87 | 07-JAN-15:00 | 25.35 | 20.11 |
February | 0.735616E+10 | 19310.23 | 25-FEB-09:01 | 25.22 | 19.84 | 0.654582E+09 | 1123.87 | 11-FEB-15:00 | 25.22 | 19.84 |
March | 0.833684E+10 | 18292.30 | 04-MAR-09:01 | 29.40 | 20.98 | 0.741255E+09 | 1123.87 | 11-MAR-15:09 | 32.10 | 24.95 |
April | 0.801944E+10 | 14722.10 | 27-APR-08:61 | 28.25 | 24.48 | 0.706402E+09 | 1123.87 | 22-APR-14:00 | 28.25 | 24.48 |
May | 0.842749E+10 | 12771.31 | 06-MAY-08:61 | 32.17 | 26.12 | 0.730279E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.841725E+10 | 13914.17 | 21-JUN-08:61 | 28.17 | 24.45 | 0.716141E+09 | 1123.87 | 03-JUN-14:00 | 28.17 | 24.45 |
July | 0.755411E+10 | 15403.25 | 06-JUL-08:61 | 26.75 | 24.00 | 0.720411E+09 | 1123.87 | 01-JUL-14:00 | 26.75 | 24.00 |
August | 0.756085E+10 | 13428.13 | 30-AUG-08:61 | 27.33 | 25.50 | 0.741073E+09 | 1123.87 | 19-AUG-14:00 | 27.33 | 25.50 |
September | 0.736114E+10 | 13646.85 | 28-SEP-08:61 | 26.33 | 24.77 | 0.706215E+09 | 1123.87 | 16-SEP-14:09 | 26.33 | 24.77 |
October | 0.718298E+10 | 14405.98 | 20-OCT-08:61 | 27.67 | 23.84 | 0.718871E+09 | 1123.87 | 21-OCT-14:00 | 29.50 | 25.84 |
November | 0.712895E+10 | 17687.39 | 25-NOV-09:01 | 23.67 | 20.24 | 0.692228E+09 | 1123.87 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.737301E+10 | 18486.10 | 27-DEC-09:01 | 26.40 | 20.69 | 0.720101E+09 | 1123.87 | 09-DEC-15:00 | 26.40 | 20.69 |
Annual Sum or Average | 0.924265E+11 | 0.856638E+10 | ||||||||
Minimum of Months | 0.712895E+10 | 12771.31 | 23.67 | 19.84 | 0.654582E+09 | 1123.87 | 25.22 | 19.84 | ||
Maximum of Months | 0.842749E+10 | 19310.23 | 32.17 | 26.12 | 0.741255E+09 | 1123.87 | 32.10 | 26.17 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.873850E+10 | 20688.04 | 23-JAN-09:01 | 24.37 | 19.55 | 0.718964E+09 | 1123.87 | 07-JAN-15:00 | 24.37 | 19.55 |
February | 0.847899E+10 | 21411.86 | 24-FEB-09:01 | 25.53 | 19.50 | 0.654712E+09 | 1123.87 | 11-FEB-15:00 | 25.53 | 19.50 |
March | 0.970443E+10 | 20322.07 | 04-MAR-09:01 | 29.40 | 20.98 | 0.741390E+09 | 1123.87 | 11-MAR-15:09 | 32.10 | 24.95 |
April | 0.944354E+10 | 15904.77 | 27-APR-08:61 | 28.25 | 24.48 | 0.706561E+09 | 1123.87 | 22-APR-14:00 | 28.25 | 24.48 |
May | 0.982284E+10 | 14212.90 | 06-MAY-08:61 | 32.17 | 26.12 | 0.730422E+09 | 1123.87 | 13-MAY-14:00 | 31.50 | 26.17 |
June | 0.991022E+10 | 15085.32 | 21-JUN-08:61 | 28.17 | 24.45 | 0.716268E+09 | 1123.87 | 03-JUN-14:00 | 28.17 | 24.45 |
July | 0.878081E+10 | 17291.43 | 19-JUL-08:61 | 26.70 | 24.36 | 0.720597E+09 | 1123.87 | 01-JUL-14:00 | 26.70 | 24.36 |
August | 0.880227E+10 | 14642.89 | 30-AUG-08:61 | 27.33 | 25.50 | 0.741184E+09 | 1123.87 | 19-AUG-14:00 | 27.33 | 25.50 |
September | 0.858568E+10 | 14861.43 | 13-SEP-08:61 | 28.75 | 25.91 | 0.706360E+09 | 1123.87 | 16-SEP-14:09 | 25.75 | 24.54 |
October | 0.814025E+10 | 15654.89 | 20-OCT-08:61 | 27.67 | 23.84 | 0.719007E+09 | 1123.87 | 21-OCT-14:00 | 29.50 | 25.84 |
November | 0.809963E+10 | 19867.49 | 25-NOV-09:01 | 23.67 | 20.24 | 0.692331E+09 | 1123.87 | 25-NOV-15:00 | 25.40 | 22.47 |
December | 0.833841E+10 | 20441.34 | 27-DEC-09:01 | 26.40 | 20.69 | 0.720230E+09 | 1123.87 | 09-DEC-15:00 | 26.40 | 20.69 |
Annual Sum or Average | 0.106846E+12 | 0.856803E+10 | ||||||||
Minimum of Months | 0.809963E+10 | 14212.90 | 23.67 | 19.50 | 0.654712E+09 | 1123.87 | 24.37 | 19.50 | ||
Maximum of Months | 0.991022E+10 | 21411.86 | 32.17 | 26.12 | 0.741390E+09 | 1123.87 | 32.10 | 26.17 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 81491760.55 | 5933.65 | 03-JAN-09:06 | 29.27 |
February | 75304280.55 | 5729.65 | 18-FEB-09:06 | 28.72 |
March | 83908368.17 | 6348.38 | 09-MAR-09:06 | 30.22 |
April | 48751357.17 | 5525.19 | 27-APR-08:06 | 28.25 |
May | 44283602.94 | 7103.14 | 28-MAY-07:07 | 32.25 |
June | 32848119.66 | 5605.56 | 29-JUN-08:07 | 29.33 |
July | 92911224.13 | 5414.86 | 03-JUL-08:06 | 28.13 |
August | 72541871.48 | 5675.30 | 09-AUG-08:07 | 29.33 |
September | 71169363.13 | 5452.24 | 01-SEP-08:07 | 29.17 |
October | 95893888.74 | 5079.83 | 20-OCT-08:06 | 27.67 |
November | 58608562.52 | 5494.11 | 22-NOV-09:06 | 28.22 |
December | 92036369.73 | 5840.35 | 08-DEC-09:06 | 29.03 |
Annual Sum or Average | 0.849749E+09 | |||
Minimum of Months | 32848119.66 | 5079.83 | 27.67 | |
Maximum of Months | 95893888.74 | 7103.14 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 35225544.72 | 2827.36 | 03-JAN-09:06 | 29.27 |
February | 33830639.33 | 2772.03 | 28-FEB-09:05 | 28.33 |
March | 38972210.16 | 3086.23 | 10-MAR-09:05 | 29.20 |
April | 25847688.86 | 3428.13 | 15-APR-08:06 | 31.00 |
May | 21903509.83 | 3812.95 | 28-MAY-07:06 | 32.25 |
June | 18224250.04 | 3054.44 | 23-JUN-08:06 | 29.33 |
July | 43076448.82 | 2669.96 | 01-JUL-08:06 | 27.67 |
August | 36597208.74 | 3266.43 | 28-AUG-08:06 | 30.17 |
September | 36828585.00 | 3036.99 | 06-SEP-08:06 | 29.17 |
October | 50825315.09 | 2869.03 | 06-OCT-08:06 | 28.67 |
November | 29016018.30 | 2913.76 | 14-NOV-09:06 | 28.67 |
December | 38879991.78 | 3016.78 | 09-DEC-09:05 | 29.07 |
Annual Sum or Average | 0.409227E+09 | |||
Minimum of Months | 18224250.04 | 2669.96 | 27.67 | |
Maximum of Months | 50825315.09 | 3812.95 | 32.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154768E+09 | 3017.70 | 11-JAN-08:06 | 29.33 |
February | 0.157923E+09 | 2656.68 | 05-FEB-09:06 | 27.37 |
March | 0.182409E+09 | 3288.31 | 19-MAR-16:01 | 34.25 |
April | 0.190769E+09 | 3077.72 | 02-APR-16:01 | 33.25 |
May | 0.177988E+09 | 3357.88 | 29-MAY-16:01 | 34.50 |
June | 0.171074E+09 | 3290.66 | 11-JUN-16:01 | 34.25 |
July | 0.166409E+09 | 3059.58 | 15-JUL-17:11 | 32.67 |
August | 0.160740E+09 | 2940.70 | 27-AUG-16:11 | 32.67 |
September | 0.159191E+09 | 2948.36 | 04-SEP-16:11 | 32.67 |
October | 0.159322E+09 | 2398.52 | 15-OCT-08:07 | 27.67 |
November | 0.135618E+09 | 2850.46 | 23-NOV-09:06 | 28.57 |
December | 0.142813E+09 | 2818.18 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.195902E+10 | |||
Minimum of Months | 0.135618E+09 | 2398.52 | 27.37 | |
Maximum of Months | 0.190769E+09 | 3357.88 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.152803E+09 | 3054.88 | 11-JAN-08:06 | 29.33 |
February | 0.153553E+09 | 2626.24 | 05-FEB-09:06 | 27.37 |
March | 0.175771E+09 | 3287.89 | 19-MAR-16:01 | 34.25 |
April | 0.184359E+09 | 3076.91 | 02-APR-16:01 | 33.25 |
May | 0.175466E+09 | 3356.10 | 29-MAY-16:01 | 34.50 |
June | 0.168610E+09 | 3289.05 | 11-JUN-16:01 | 34.25 |
July | 0.160625E+09 | 3062.14 | 15-JUL-17:11 | 32.67 |
August | 0.156071E+09 | 2942.56 | 27-AUG-16:11 | 32.67 |
September | 0.155826E+09 | 2949.65 | 04-SEP-16:11 | 32.67 |
October | 0.154015E+09 | 2539.42 | 05-OCT-07:06 | 27.75 |
November | 0.131659E+09 | 2827.79 | 23-NOV-09:06 | 28.57 |
December | 0.138826E+09 | 2600.09 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.190758E+10 | |||
Minimum of Months | 0.131659E+09 | 2539.42 | 27.37 | |
Maximum of Months | 0.184359E+09 | 3356.10 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.160189E+09 | 2507.01 | 03-JAN-08:06 | 27.00 |
February | 0.162346E+09 | 2641.78 | 05-FEB-09:06 | 27.37 |
March | 0.189624E+09 | 3289.46 | 19-MAR-16:01 | 34.25 |
April | 0.194252E+09 | 3078.14 | 02-APR-16:01 | 33.25 |
May | 0.183005E+09 | 3356.87 | 29-MAY-16:01 | 34.50 |
June | 0.173001E+09 | 3290.17 | 11-JUN-16:01 | 34.25 |
July | 0.170303E+09 | 3060.61 | 15-JUL-17:11 | 32.67 |
August | 0.168024E+09 | 2940.11 | 27-AUG-16:11 | 32.67 |
September | 0.168722E+09 | 2946.78 | 04-SEP-16:11 | 32.67 |
October | 0.164917E+09 | 2526.47 | 05-OCT-07:06 | 27.75 |
November | 0.142773E+09 | 2842.79 | 23-NOV-09:06 | 28.57 |
December | 0.148299E+09 | 2722.32 | 31-DEC-09:06 | 28.47 |
Annual Sum or Average | 0.202545E+10 | |||
Minimum of Months | 0.142773E+09 | 2507.01 | 27.00 | |
Maximum of Months | 0.194252E+09 | 3356.87 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.156119E+09 | 5093.51 | 16-JAN-10:06 | 28.17 |
February | 0.163648E+09 | 4920.30 | 22-FEB-09:06 | 27.47 |
March | 0.175871E+09 | 6462.75 | 19-MAR-16:01 | 34.25 |
April | 0.170141E+09 | 6030.75 | 02-APR-16:01 | 33.25 |
May | 0.157647E+09 | 6596.60 | 29-MAY-16:01 | 34.50 |
June | 0.122105E+09 | 6465.69 | 11-JUN-16:01 | 34.25 |
July | 0.203139E+09 | 5836.44 | 15-JUL-17:11 | 32.67 |
August | 0.157785E+09 | 5686.88 | 27-AUG-16:02 | 32.83 |
September | 0.171316E+09 | 5698.41 | 04-SEP-16:02 | 32.83 |
October | 0.181434E+09 | 5294.04 | 05-OCT-08:07 | 29.17 |
November | 0.128648E+09 | 4921.79 | 14-NOV-09:07 | 28.67 |
December | 0.169284E+09 | 5273.25 | 09-DEC-09:06 | 29.07 |
Annual Sum or Average | 0.195714E+10 | |||
Minimum of Months | 0.122105E+09 | 4920.30 | 27.47 | |
Maximum of Months | 0.203139E+09 | 6596.60 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 92105106.89 | 2909.83 | 03-JAN-09:06 | 29.27 |
February | 94118026.19 | 3093.85 | 26-FEB-10:06 | 29.92 |
March | 0.102871E+09 | 3276.82 | 19-MAR-16:01 | 34.25 |
April | 95053923.07 | 3063.09 | 02-APR-16:01 | 33.25 |
May | 91219519.02 | 3341.18 | 29-MAY-16:01 | 34.50 |
June | 71842430.49 | 3277.21 | 11-JUN-16:01 | 34.25 |
July | 0.113644E+09 | 3003.36 | 15-JUL-17:11 | 32.67 |
August | 95814931.40 | 2886.80 | 27-AUG-16:02 | 32.83 |
September | 0.100239E+09 | 2891.83 | 04-SEP-16:02 | 32.83 |
October | 0.104932E+09 | 2813.09 | 08-OCT-09:07 | 29.67 |
November | 74950166.70 | 2639.75 | 22-NOV-09:06 | 28.22 |
December | 98166593.07 | 2858.86 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.113496E+10 | |||
Minimum of Months | 71842430.49 | 2639.75 | 28.22 | |
Maximum of Months | 0.113644E+09 | 3341.18 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 93532030.84 | 2894.94 | 03-JAN-09:06 | 29.27 |
February | 96595946.24 | 3073.08 | 26-FEB-10:06 | 29.92 |
March | 0.105970E+09 | 3276.34 | 19-MAR-16:01 | 34.25 |
April | 99751132.72 | 3062.38 | 02-APR-16:01 | 33.25 |
May | 92387676.02 | 3340.52 | 29-MAY-16:01 | 34.50 |
June | 73169286.16 | 3276.70 | 11-JUN-16:01 | 34.25 |
July | 0.115332E+09 | 3000.07 | 15-JUL-17:11 | 32.67 |
August | 97469872.15 | 2886.58 | 27-AUG-16:02 | 32.83 |
September | 0.103796E+09 | 2891.48 | 04-SEP-16:02 | 32.83 |
October | 0.107902E+09 | 2817.99 | 08-OCT-09:07 | 29.67 |
November | 77790272.26 | 2622.02 | 22-NOV-09:06 | 28.22 |
December | 0.101796E+09 | 2862.69 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.116549E+10 | |||
Minimum of Months | 73169286.16 | 2622.02 | 28.22 | |
Maximum of Months | 0.115332E+09 | 3340.52 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 97853292.15 | 2905.80 | 03-JAN-09:06 | 29.27 |
February | 99068180.14 | 3097.50 | 26-FEB-10:06 | 29.92 |
March | 0.109017E+09 | 3275.84 | 19-MAR-16:01 | 34.25 |
April | 99531110.14 | 3061.39 | 02-APR-16:01 | 33.25 |
May | 94483463.81 | 3339.35 | 29-MAY-16:01 | 34.50 |
June | 74300726.31 | 3274.78 | 11-JUN-16:01 | 34.25 |
July | 0.118620E+09 | 3003.29 | 15-JUL-17:11 | 32.67 |
August | 0.100492E+09 | 2885.15 | 27-AUG-16:02 | 32.83 |
September | 0.106049E+09 | 2889.92 | 04-SEP-16:02 | 32.83 |
October | 0.111352E+09 | 2818.02 | 08-OCT-09:07 | 29.67 |
November | 80400460.35 | 2637.56 | 22-NOV-09:06 | 28.22 |
December | 0.106454E+09 | 2860.14 | 03-DEC-10:06 | 29.17 |
Annual Sum or Average | 0.119762E+10 | |||
Minimum of Months | 74300726.31 | 2637.56 | 28.22 | |
Maximum of Months | 0.118620E+09 | 3339.35 | 34.50 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 95145964.89 | 3047.34 | 03-JAN-09:06 | 29.27 |
February | 89464068.75 | 3202.95 | 26-FEB-10:06 | 29.92 |
March | 90900705.93 | 3369.68 | 19-MAR-09:06 | 30.78 |
April | 83803814.44 | 3071.23 | 02-APR-16:01 | 33.25 |
May | 84738478.72 | 3350.14 | 29-MAY-16:11 | 34.40 |
June | 64503740.29 | 3272.51 | 11-JUN-16:01 | 34.25 |
July | 0.107680E+09 | 3102.34 | 15-JUL-17:11 | 32.67 |
August | 86642080.05 | 2983.61 | 27-AUG-16:11 | 32.67 |
September | 91976112.63 | 2989.97 | 04-SEP-16:11 | 32.67 |
October | 0.105083E+09 | 2696.14 | 20-OCT-08:06 | 27.67 |
November | 74862202.96 | 2825.42 | 22-NOV-09:06 | 28.22 |
December | 0.100742E+09 | 3053.20 | 08-DEC-09:06 | 29.03 |
Annual Sum or Average | 0.107554E+10 | |||
Minimum of Months | 64503740.29 | 2696.14 | 27.67 | |
Maximum of Months | 0.107680E+09 | 3369.68 | 34.40 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226547E+10 | 93252839.56 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245834E+10 | 28054471.68 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.299107E+10 | 36281411.22 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296928E+10 | 6270520.07 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301750E+10 | 17121158.19 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.293627E+10 | 17505119.27 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219499E+10 | 19782782.19 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223644E+10 | 32602383.08 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.218430E+10 | 18186245.20 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192087E+10 | 34778285.12 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184414E+10 | 45584222.10 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200643E+10 | 96064093.04 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.290251E+11 | 0.445484E+09 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184414E+10 | 6270520.07 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301750E+10 | 96064093.04 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126448E+10 | 31596544.12 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136464E+10 | 10274356.83 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164248E+10 | 11258539.11 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163192E+10 | 2140201.17 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164956E+10 | 5497860.09 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161097E+10 | 5386567.41 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121253E+10 | 7551679.78 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.122674E+10 | 10972442.81 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121094E+10 | 6181719.74 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.106706E+10 | 12145699.21 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102990E+10 | 14774066.77 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112346E+10 | 30490892.71 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160347E+11 | 0.148271E+09 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102990E+10 | 2140201.17 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164956E+10 | 31596544.12 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124109E+10 | 41907946.87 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133988E+10 | 12914979.15 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162080E+10 | 18438384.21 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160835E+10 | 4528015.37 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162661E+10 | 9109772.10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159171E+10 | 10646087.88 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118659E+10 | 12083326.86 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121270E+10 | 20437244.43 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119225E+10 | 12959272.88 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104797E+10 | 22681516.91 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101448E+10 | 24129361.31 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110363E+10 | 43023182.64 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157861E+11 | 0.232859E+09 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101448E+10 | 4528015.37 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162661E+10 | 43023182.64 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124095E+10 | 43081030.20 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133952E+10 | 13686224.58 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161990E+10 | 19776211.87 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160673E+10 | 4905266.96 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162488E+10 | 9661771.30 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159027E+10 | 11386425.78 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118599E+10 | 12803888.93 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121218E+10 | 21424679.19 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119175E+10 | 13636437.52 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104775E+10 | 23560770.35 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101431E+10 | 24816057.08 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110356E+10 | 43836878.21 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157778E+11 | 0.242576E+09 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101431E+10 | 4905266.96 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162488E+10 | 43836878.21 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.124122E+10 | 41141731.20 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134000E+10 | 12458706.40 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162107E+10 | 17579188.86 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160879E+10 | 4335908.00 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162653E+10 | 8809656.11 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159188E+10 | 10514945.45 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118669E+10 | 11828405.91 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121288E+10 | 19465301.69 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119236E+10 | 12470310.00 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104814E+10 | 22071870.17 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101462E+10 | 23350251.18 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110372E+10 | 42051325.83 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157879E+11 | 0.226078E+09 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101462E+10 | 4335908.00 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162653E+10 | 42051325.83 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.217347E+10 | 83926199.99 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.234669E+10 | 26632105.60 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284356E+10 | 27812400.12 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.282610E+10 | 6972764.59 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285705E+10 | 15236737.46 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279422E+10 | 18666032.43 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.207614E+10 | 24137551.34 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212079E+10 | 30515865.89 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.208251E+10 | 22133605.82 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182768E+10 | 41303379.72 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176732E+10 | 44146340.14 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192428E+10 | 83264732.89 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.276398E+11 | 0.424748E+09 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176732E+10 | 6972764.59 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.285705E+10 | 83926199.99 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123852E+10 | 42072270.00 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133655E+10 | 13046806.58 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161764E+10 | 12826089.90 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160771E+10 | 3343204.92 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162380E+10 | 7159268.06 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158924E+10 | 8946988.78 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118172E+10 | 11995243.06 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120602E+10 | 14603774.54 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118595E+10 | 10773646.61 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104095E+10 | 20485964.01 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100733E+10 | 21915945.72 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109694E+10 | 41143433.75 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157324E+11 | 0.208313E+09 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100733E+10 | 3343204.92 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162380E+10 | 42072270.00 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123866E+10 | 41602863.64 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133673E+10 | 12805888.44 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161802E+10 | 12503819.47 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160815E+10 | 3257395.59 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162421E+10 | 7030565.45 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158963E+10 | 8807392.11 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118193E+10 | 11794955.13 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120624E+10 | 14295184.76 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118613E+10 | 10577216.26 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104110E+10 | 20154468.98 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100748E+10 | 21589759.98 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109702E+10 | 40676415.72 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157353E+11 | 0.205096E+09 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100748E+10 | 3257395.59 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162421E+10 | 41602863.64 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123879E+10 | 40745400.19 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133685E+10 | 12410185.07 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161838E+10 | 11961594.85 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160836E+10 | 3108945.22 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162428E+10 | 6840094.90 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.158965E+10 | 8654139.36 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118191E+10 | 11583187.18 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120639E+10 | 13772059.21 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118620E+10 | 10312617.20 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104127E+10 | 19581343.34 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100767E+10 | 20947995.44 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109711E+10 | 39804164.11 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157369E+11 | 0.199722E+09 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100767E+10 | 3108945.22 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162428E+10 | 40745400.19 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127963E+10 | 86526693.34 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138973E+10 | 27708105.57 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.170830E+10 | 32702057.00 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169921E+10 | 7056568.68 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172918E+10 | 17928337.20 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168190E+10 | 22369960.75 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123704E+10 | 25498358.12 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.127627E+10 | 33443366.63 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.123638E+10 | 24473920.26 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108224E+10 | 41647567.64 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104022E+10 | 44923530.81 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112823E+10 | 90740869.25 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164883E+11 | 0.455019E+09 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104022E+10 | 7056568.68 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.172918E+10 | 90740869.25 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4850.31 | 04-JAN-13:00 | 1227.64 | 07-JAN-05:00 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5334.42 | 28-FEB-15:00 | 316.67 | 01-FEB-07:00 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5873.58 | 21-MAR-13:00 | 238.86 | 03-MAR-05:30 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5318.63 | 01-APR-14:00 | 480.50 | 14-APR-16:00 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6355.18 | 06-MAY-13:00 | 238.94 | 21-MAY-13:00 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5705.31 | 13-JUN-15:00 | 288.78 | 20-JUN-23:20 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4339.02 | 28-JUL-13:00 | 351.41 | 03-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4798.01 | 27-AUG-14:00 | 855.28 | 20-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4746.97 | 06-SEP-14:00 | 460.94 | 15-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4295.25 | 04-OCT-14:00 | 436.64 | 30-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4830.94 | 18-NOV-13:00 | 306.94 | 25-NOV-08:10 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4238.24 | 07-DEC-14:00 | 473.27 | 21-DEC-05:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4238.24 | 238.86 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6355.18 | 1227.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.73 | 04-JAN-13:00 | 384.00 | 07-JAN-05:00 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.92 | 28-FEB-15:00 | 151.25 | 21-FEB-10:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.46 | 21-MAR-13:00 | 110.91 | 15-MAR-08:00 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.89 | 01-APR-14:00 | 269.99 | 14-APR-16:00 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 06-MAY-13:00 | 134.26 | 21-MAY-13:00 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.93 | 13-JUN-15:00 | 132.72 | 30-JUN-13:00 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.13 | 15-JUL-16:00 | 193.25 | 03-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.66 | 27-AUG-14:00 | 475.35 | 20-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.65 | 06-SEP-14:00 | 250.91 | 15-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.22 | 04-OCT-14:00 | 244.00 | 30-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.49 | 18-NOV-13:00 | 166.42 | 25-NOV-08:10 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 07-DEC-14:00 | 188.18 | 21-DEC-08:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 110.91 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 475.35 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.73 | 04-JAN-13:00 | 411.52 | 07-JAN-05:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.92 | 28-FEB-15:00 | 311.74 | 05-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.46 | 21-MAR-13:00 | 217.90 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.89 | 01-APR-14:00 | 354.74 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 06-MAY-13:00 | 170.07 | 08-MAY-22:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.93 | 13-JUN-15:00 | 243.03 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.13 | 15-JUL-16:00 | 600.56 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.66 | 27-AUG-14:00 | 475.35 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.65 | 06-SEP-14:00 | 620.73 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.22 | 04-OCT-14:00 | 527.98 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.49 | 18-NOV-13:00 | 694.29 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 07-DEC-14:00 | 542.85 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 170.07 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 694.29 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.73 | 04-JAN-13:00 | 417.22 | 07-JAN-05:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.92 | 28-FEB-15:00 | 319.57 | 05-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.46 | 21-MAR-13:00 | 223.60 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.89 | 01-APR-14:00 | 360.91 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 06-MAY-13:00 | 175.32 | 08-MAY-22:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.93 | 13-JUN-15:00 | 249.93 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.13 | 15-JUL-16:00 | 606.18 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.66 | 27-AUG-14:00 | 475.35 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.65 | 06-SEP-14:00 | 626.15 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.22 | 04-OCT-14:00 | 535.08 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.49 | 18-NOV-13:00 | 695.47 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 07-DEC-14:00 | 545.48 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 175.32 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 695.47 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.73 | 04-JAN-13:00 | 404.37 | 07-JAN-05:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.92 | 28-FEB-15:00 | 307.28 | 05-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.46 | 21-MAR-13:00 | 210.97 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.89 | 01-APR-14:00 | 348.91 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 06-MAY-13:00 | 167.91 | 08-MAY-22:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.93 | 13-JUN-15:00 | 245.10 | 25-JUN-19:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.13 | 15-JUL-16:00 | 594.54 | 16-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.66 | 27-AUG-14:00 | 475.35 | 20-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.65 | 06-SEP-14:00 | 614.43 | 03-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.22 | 04-OCT-14:00 | 523.10 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.49 | 18-NOV-13:00 | 682.25 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 07-DEC-14:00 | 531.71 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 167.91 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 682.25 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4735.31 | 04-JAN-13:00 | 742.00 | 07-JAN-05:00 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5179.64 | 28-FEB-15:00 | 491.23 | 05-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5734.32 | 21-MAR-13:00 | 307.26 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5253.79 | 01-APR-14:00 | 550.64 | 09-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6233.29 | 06-MAY-13:00 | 295.70 | 08-MAY-22:00 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5570.04 | 13-JUN-15:00 | 443.57 | 25-JUN-19:00 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4236.14 | 28-JUL-13:00 | 982.48 | 16-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4684.25 | 27-AUG-14:00 | 835.00 | 20-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4655.93 | 06-SEP-14:00 | 1021.95 | 03-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4212.87 | 04-OCT-14:00 | 868.82 | 29-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4760.66 | 18-NOV-13:00 | 1130.48 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4176.58 | 07-DEC-14:00 | 863.52 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 4176.58 | 295.70 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 6233.29 | 1130.48 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.70 | 04-JAN-13:00 | 362.58 | 07-JAN-05:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.89 | 28-FEB-15:00 | 250.05 | 05-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.42 | 21-MAR-13:00 | 156.30 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.86 | 01-APR-14:00 | 296.41 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.29 | 06-MAY-13:00 | 140.75 | 08-MAY-22:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.90 | 13-JUN-15:00 | 234.13 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.10 | 15-JUL-16:00 | 547.96 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.64 | 27-AUG-14:00 | 475.37 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.62 | 06-SEP-14:00 | 568.85 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.19 | 04-OCT-14:00 | 471.44 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.46 | 18-NOV-13:00 | 635.96 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.43 | 07-DEC-14:00 | 478.51 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.43 | 140.75 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.29 | 635.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.71 | 04-JAN-13:00 | 359.58 | 07-JAN-05:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.89 | 28-FEB-15:00 | 245.48 | 05-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.43 | 21-MAR-13:00 | 151.76 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.86 | 01-APR-14:00 | 292.45 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.30 | 06-MAY-13:00 | 139.96 | 08-MAY-22:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.91 | 13-JUN-15:00 | 232.84 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.11 | 15-JUL-16:00 | 544.70 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.64 | 27-AUG-14:00 | 475.36 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.62 | 06-SEP-14:00 | 565.33 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.20 | 04-OCT-14:00 | 466.63 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.47 | 18-NOV-13:00 | 632.22 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.43 | 07-DEC-14:00 | 473.84 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.43 | 139.96 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.30 | 632.22 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2695.73 | 04-JAN-13:00 | 354.88 | 07-JAN-05:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2945.92 | 28-FEB-15:00 | 247.40 | 05-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3264.46 | 21-MAR-13:00 | 152.45 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2996.89 | 01-APR-14:00 | 291.65 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 06-MAY-13:00 | 139.18 | 08-MAY-22:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3170.93 | 13-JUN-15:00 | 233.23 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2413.13 | 15-JUL-16:00 | 545.68 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2666.67 | 27-AUG-14:00 | 475.35 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2652.65 | 06-SEP-14:00 | 567.23 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2400.22 | 04-OCT-14:00 | 467.53 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714.49 | 18-NOV-13:00 | 626.16 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 07-DEC-14:00 | 470.41 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2381.46 | 139.18 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3551.32 | 626.16 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2810.73 | 04-JAN-13:00 | 790.27 | 07-JAN-05:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3100.69 | 28-FEB-15:00 | 368.01 | 05-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3403.71 | 21-MAR-13:00 | 250.68 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3061.73 | 01-APR-14:00 | 345.65 | 09-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3673.21 | 06-MAY-13:00 | 358.25 | 08-MAY-22:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3306.20 | 13-JUN-15:00 | 399.05 | 25-JUN-19:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2514.44 | 28-JUL-13:00 | 646.17 | 16-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2780.42 | 27-AUG-14:00 | 495.63 | 20-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2743.69 | 06-SEP-14:00 | 693.40 | 03-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2482.60 | 04-OCT-14:00 | 585.72 | 09-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2784.77 | 18-NOV-13:00 | 692.96 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2443.11 | 07-DEC-14:00 | 537.35 | 17-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2443.11 | 250.68 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 3673.21 | 790.27 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 39528.84 | 23-JAN-09:01 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.28 |
February | 40693.99 | 24-FEB-09:01 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.17 |
March | 38370.54 | 04-MAR-09:01 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 341.04 | 0.00 |
April | 31215.82 | 23-APR-07:02 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 18.52 | 0.00 |
May | 28398.22 | 14-MAY-07:02 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 140.59 | 0.00 |
June | 31799.79 | 25-JUN-07:02 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 18.86 | 0.00 |
July | 36475.60 | 16-JUL-07:01 | 2362.52 | 2041.29 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 49.56 |
August | 29907.81 | 27-AUG-07:02 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 77.94 | 0.00 |
September | 32772.63 | 10-SEP-07:02 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 81.30 | 0.00 |
October | 32720.90 | 08-OCT-07:02 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 38.63 | 0.00 |
November | 37678.50 | 25-NOV-09:01 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 163.19 |
December | 38496.93 | 27-DEC-09:01 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 46.33 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 28398.22 | 2025.02 | 1749.68 | 449.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 40693.99 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 341.04 | 163.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22142.03 | 16-JAN-08:62 | 843.73 | 851.11 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 101.23 |
February | 22565.79 | 24-FEB-09:01 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 8.76 |
March | 20836.36 | 03-MAR-09:01 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 62.31 | 0.00 |
April | 19661.96 | 23-APR-07:02 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 12.52 | 0.00 |
May | 18540.02 | 14-MAY-07:02 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 | 0.00 |
June | 20259.91 | 25-JUN-07:02 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 15.55 | 0.00 |
July | 22298.97 | 16-JUL-07:01 | 1181.23 | 1191.56 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.54 |
August | 18921.09 | 27-AUG-07:02 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 49.78 | 0.00 |
September | 20302.68 | 10-SEP-07:02 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 49.57 | 0.00 |
October | 20503.88 | 08-OCT-07:02 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 24.67 | 0.00 |
November | 20912.32 | 25-NOV-09:01 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.49 |
December | 21213.34 | 25-DEC-08:62 | 1012.48 | 1021.34 | 224.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 18540.02 | 843.73 | 851.11 | 187.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 22565.79 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 81.32 | 101.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19273.35 | 24-JAN-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 200.77 |
February | 20156.76 | 25-FEB-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 34.11 | 0.00 |
March | 19208.20 | 04-MAR-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 28.53 | 0.00 |
April | 15561.17 | 27-APR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 42.61 | 0.00 |
May | 13975.97 | 09-MAY-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.35 |
June | 14477.91 | 27-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.14 |
July | 16251.76 | 06-JUL-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.36 |
August | 14609.32 | 30-AUG-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.25 |
September | 14423.67 | 16-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.55 |
October | 14552.99 | 11-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.02 |
November | 18883.28 | 25-NOV-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.70 |
December | 19219.49 | 27-DEC-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.09 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13975.97 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20156.76 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 42.61 | 200.77 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19357.63 | 24-JAN-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 202.29 |
February | 20213.88 | 25-FEB-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 34.25 | 0.00 |
March | 19264.84 | 04-MAR-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 28.58 | 0.00 |
April | 15608.55 | 27-APR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 | 0.00 |
May | 14075.92 | 09-MAY-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.36 |
June | 14536.00 | 27-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.06 |
July | 16321.19 | 06-JUL-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3.05 |
August | 14660.88 | 30-AUG-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.21 |
September | 14490.66 | 09-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.85 |
October | 14616.95 | 11-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.97 |
November | 18970.05 | 25-NOV-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.34 |
December | 19312.88 | 27-DEC-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 93.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14075.92 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20213.88 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 43.72 | 202.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19153.75 | 24-JAN-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.70 |
February | 20058.85 | 25-FEB-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 34.02 | 0.00 |
March | 19100.53 | 04-MAR-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 28.54 | 0.00 |
April | 15438.53 | 27-APR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 | 0.00 |
May | 13914.64 | 09-MAY-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 65.51 |
June | 14387.26 | 27-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.21 |
July | 16200.65 | 06-JUL-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 5.90 |
August | 14497.41 | 30-AUG-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.34 |
September | 14311.14 | 09-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 40.07 |
October | 14467.77 | 11-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.09 |
November | 18750.09 | 25-NOV-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 141.23 |
December | 19105.67 | 27-DEC-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 90.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 13914.64 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20058.85 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 43.25 | 198.70 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 34870.53 | 21-JAN-09:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 42.22 |
February | 36988.31 | 25-FEB-09:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 52.81 |
March | 35064.27 | 04-MAR-09:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 288.60 | 0.00 |
April | 28166.22 | 27-APR-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 167.50 | 0.00 |
May | 24394.33 | 06-MAY-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 496.42 | 0.00 |
June | 26663.14 | 21-JUN-08:61 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 136.64 | 0.00 |
July | 29664.33 | 06-JUL-08:61 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.67 | 0.00 |
August | 25703.26 | 30-AUG-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 87.28 | 0.00 |
September | 26141.16 | 28-SEP-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 14.85 | 0.00 |
October | 27648.97 | 20-OCT-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 117.18 | 0.00 |
November | 33971.98 | 25-NOV-09:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 155.97 |
December | 35399.74 | 27-DEC-09:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 35.98 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24394.33 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 36988.31 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 496.42 | 155.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18254.33 | 21-JAN-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.90 |
February | 19370.68 | 25-FEB-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.15 |
March | 18359.24 | 04-MAR-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 162.22 | 0.00 |
April | 14774.18 | 27-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 95.14 | 0.00 |
May | 12808.92 | 06-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 277.31 | 0.00 |
June | 14123.85 | 21-JUN-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 68.17 | 0.00 |
July | 15456.15 | 06-JUL-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 25.79 | 0.00 |
August | 13489.27 | 30-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 50.39 | 0.00 |
September | 13705.41 | 28-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 9.42 | 0.00 |
October | 14487.57 | 20-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 67.09 | 0.00 |
November | 17796.42 | 25-NOV-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.08 |
December | 18558.02 | 27-DEC-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 21.82 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12808.92 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19370.68 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 277.31 | 86.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18161.90 | 21-JAN-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.69 |
February | 19280.34 | 25-FEB-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.29 |
March | 18272.65 | 04-MAR-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 162.10 | 0.00 |
April | 14695.40 | 27-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 95.01 | 0.00 |
May | 12736.74 | 06-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 277.25 | 0.00 |
June | 13896.15 | 21-JUN-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 78.44 | 0.00 |
July | 15373.62 | 06-JUL-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 25.69 | 0.00 |
August | 13409.93 | 30-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 50.29 | 0.00 |
September | 13625.74 | 28-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 9.28 | 0.00 |
October | 14403.39 | 20-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 66.99 | 0.00 |
November | 17694.74 | 25-NOV-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 85.09 |
December | 18469.17 | 27-DEC-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 21.78 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12736.74 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19280.34 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 277.25 | 85.09 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 18173.04 | 21-JAN-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 21.01 |
February | 19310.23 | 25-FEB-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.17 |
March | 18292.30 | 04-MAR-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 162.23 | 0.00 |
April | 14722.10 | 27-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 95.10 | 0.00 |
May | 12771.31 | 06-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 277.18 | 0.00 |
June | 13914.17 | 21-JUN-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 78.51 | 0.00 |
July | 15403.25 | 06-JUL-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 25.77 | 0.00 |
August | 13428.13 | 30-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 50.40 | 0.00 |
September | 13646.85 | 28-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 9.38 | 0.00 |
October | 14405.98 | 20-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 67.10 | 0.00 |
November | 17687.39 | 25-NOV-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.28 |
December | 18486.10 | 27-DEC-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 22.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 12771.31 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19310.23 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 277.18 | 83.28 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 20688.04 | 23-JAN-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.17 |
February | 21411.86 | 24-FEB-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 12.65 |
March | 20322.07 | 04-MAR-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 212.50 | 0.00 |
April | 15904.77 | 27-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 115.91 | 0.00 |
May | 14212.90 | 06-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 359.58 | 0.00 |
June | 15085.32 | 21-JUN-08:61 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 85.26 | 0.00 |
July | 17291.43 | 19-JUL-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 30.42 | 0.00 |
August | 14642.89 | 30-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 58.83 | 0.00 |
September | 14861.43 | 13-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 125.32 | 0.00 |
October | 15654.89 | 20-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 79.73 | 0.00 |
November | 19867.49 | 25-NOV-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.35 |
December | 20441.34 | 27-DEC-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 30.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 14212.90 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21411.86 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 359.58 | 102.35 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.149691E+12 | 123988.50 | 04-JAN-14:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.139454E+12 | 128855.90 | 15-FEB-13:50 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.159070E+12 | 129195.66 | 28-MAR-14:50 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.158402E+12 | 132574.86 | 01-APR-13:50 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.168918E+12 | 140741.75 | 04-MAY-12:00 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.166024E+12 | 141004.83 | 16-JUN-12:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.153319E+12 | 128984.51 | 15-JUL-13:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.162356E+12 | 136967.55 | 13-AUG-13:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.154805E+12 | 132722.12 | 05-SEP-12:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.155412E+12 | 129669.17 | 28-OCT-12:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.148541E+12 | 124935.53 | 15-NOV-13:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.149209E+12 | 122431.69 | 10-DEC-13:30 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.186520E+13 | 0.00 | ||||
Minimum of Months | 0.139454E+12 | 122431.69 | 0.00 | 0.00 | ||
Maximum of Months | 0.168918E+12 | 141004.83 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.108249E+11 | 0.108804E+11 | 0.00 | 0.227927E+11 | 0.00 | 0.00 | 0.611693E+11 | 0.00 | 0.00 | 0.00 | 0.492405E+10 | 0.00 |
February | 0.353889E+11 | 0.962473E+10 | 0.985143E+10 | 0.00 | 0.206388E+11 | 0.00 | 0.00 | 0.594952E+11 | 0.00 | 0.00 | 0.00 | 0.445452E+10 | 0.00 |
March | 0.396588E+11 | 0.103291E+11 | 0.110560E+11 | 0.00 | 0.231808E+11 | 0.00 | 0.00 | 0.699059E+11 | 0.00 | 0.00 | 0.00 | 0.493909E+10 | 0.00 |
April | 0.379231E+11 | 0.975911E+10 | 0.105544E+11 | 0.00 | 0.221307E+11 | 0.00 | 0.00 | 0.732996E+11 | 0.00 | 0.00 | 0.00 | 0.473522E+10 | 0.00 |
May | 0.393718E+11 | 0.991203E+10 | 0.109629E+11 | 0.00 | 0.230104E+11 | 0.00 | 0.00 | 0.807793E+11 | 0.00 | 0.00 | 0.00 | 0.488177E+10 | 0.00 |
June | 0.383312E+11 | 0.948107E+10 | 0.106855E+11 | 0.00 | 0.224291E+11 | 0.00 | 0.00 | 0.803736E+11 | 0.00 | 0.00 | 0.00 | 0.472352E+10 | 0.00 |
July | 0.389786E+11 | 0.987496E+10 | 0.108424E+11 | 0.00 | 0.227208E+11 | 0.00 | 0.00 | 0.660540E+11 | 0.00 | 0.00 | 0.00 | 0.484865E+10 | 0.00 |
August | 0.396438E+11 | 0.100001E+11 | 0.110491E+11 | 0.00 | 0.231823E+11 | 0.00 | 0.00 | 0.735943E+11 | 0.00 | 0.00 | 0.00 | 0.488659E+10 | 0.00 |
September | 0.379380E+11 | 0.992593E+10 | 0.105613E+11 | 0.00 | 0.221355E+11 | 0.00 | 0.00 | 0.695205E+11 | 0.00 | 0.00 | 0.00 | 0.472367E+10 | 0.00 |
October | 0.390997E+11 | 0.105237E+11 | 0.108804E+11 | 0.00 | 0.228074E+11 | 0.00 | 0.00 | 0.672079E+11 | 0.00 | 0.00 | 0.00 | 0.489325E+10 | 0.00 |
November | 0.378782E+11 | 0.103893E+11 | 0.105443E+11 | 0.00 | 0.221035E+11 | 0.00 | 0.00 | 0.628719E+11 | 0.00 | 0.00 | 0.00 | 0.475421E+10 | 0.00 |
December | 0.389936E+11 | 0.108944E+11 | 0.108529E+11 | 0.00 | 0.227233E+11 | 0.00 | 0.00 | 0.608207E+11 | 0.00 | 0.00 | 0.00 | 0.492393E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121539E+12 | 0.128721E+12 | 0.00 | 0.269855E+12 | 0.00 | 0.00 | 0.825092E+12 | 0.00 | 0.00 | 0.00 | 0.576885E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.948107E+10 | 0.985143E+10 | 0.00 | 0.206388E+11 | 0.00 | 0.00 | 0.594952E+11 | 0.00 | 0.00 | 0.00 | 0.445452E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.108944E+11 | 0.110560E+11 | 0.00 | 0.231823E+11 | 0.00 | 0.00 | 0.807793E+11 | 0.00 | 0.00 | 0.00 | 0.493909E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 15645.05 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 15645.05 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 15645.05 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 15645.05 | 01-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 15645.05 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 15645.05 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 15645.05 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 15645.05 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 15645.05 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 15645.05 | 01-OCT-09:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 15645.05 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 15645.05 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 15645.05 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 15645.05 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 65453.31 | 04-JAN-13:20 | 0.00 | 0.00 | 0.00 | 11776.47 | 02-JAN-13:20 | 0.00 |
February | 71001.55 | 15-FEB-13:00 | 0.00 | 0.00 | 0.00 | 7551.18 | 06-FEB-14:30 | 0.00 |
March | 73443.06 | 27-MAR-12:00 | 0.00 | 0.00 | 0.00 | 7549.42 | 04-MAR-14:09 | 0.00 |
April | 77022.78 | 01-APR-13:00 | 0.00 | 0.00 | 0.00 | 7527.97 | 06-APR-18:40 | 0.00 |
May | 84249.50 | 04-MAY-12:00 | 0.00 | 0.00 | 0.00 | 7535.00 | 27-MAY-14:09 | 0.00 |
June | 85321.58 | 16-JUN-12:00 | 0.00 | 0.00 | 0.00 | 7513.84 | 22-JUN-19:30 | 0.00 |
July | 69048.17 | 28-JUL-12:00 | 0.00 | 0.00 | 0.00 | 9652.90 | 15-JUL-13:09 | 0.00 |
August | 79681.71 | 13-AUG-14:20 | 0.00 | 0.00 | 0.00 | 7547.99 | 11-AUG-12:39 | 0.00 |
September | 75585.55 | 30-SEP-11:39 | 0.00 | 0.00 | 0.00 | 9621.19 | 06-SEP-10:20 | 0.00 |
October | 71776.52 | 28-OCT-12:00 | 0.00 | 0.00 | 0.00 | 7551.82 | 27-OCT-12:20 | 0.00 |
November | 69764.22 | 18-NOV-12:00 | 0.00 | 0.00 | 0.00 | 7552.29 | 29-NOV-13:50 | 0.00 |
December | 66154.19 | 30-DEC-13:00 | 0.00 | 0.00 | 0.00 | 8808.74 | 01-DEC-13:00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 65453.31 | 0.00 | 0.00 | 0.00 | 7513.84 | 0.00 | ||
Maximum of Months | 85321.58 | 0.00 | 0.00 | 0.00 | 11776.47 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 123988.50 | 04-JAN-14:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 63983.83 | 0.00 |
February | 128855.90 | 15-FEB-13:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 70962.03 | 0.00 |
March | 129195.66 | 28-MAR-14:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 71645.95 | 0.00 |
April | 132574.86 | 01-APR-13:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 76794.01 | 0.00 |
May | 140741.75 | 04-MAY-12:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 84249.50 | 0.00 |
June | 141004.83 | 16-JUN-12:30 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 83114.83 | 0.00 |
July | 128984.51 | 15-JUL-13:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 66878.80 | 0.00 |
August | 136967.55 | 13-AUG-13:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 79098.36 | 0.00 |
September | 132722.12 | 05-SEP-12:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 72721.47 | 0.00 |
October | 129669.17 | 28-OCT-12:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 71776.52 | 0.00 |
November | 124935.53 | 15-NOV-13:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 64931.15 | 0.00 |
December | 122431.69 | 10-DEC-13:30 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 64049.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 122431.69 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 63983.83 | 0.00 | |
Maximum of Months | 141004.83 | 28718.22 | 8089.53 | 0.00 | 0.00 | 15645.05 | 0.00 | 0.00 | 84249.50 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.67 | 24.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.47 | 2.83 | 24.47 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.56 | 4.83 | 24.56 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.59 | 4.00 | 24.59 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.46 | 0.17 | 24.46 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.54 | 4.67 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.49 | 2.83 | 24.49 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 2.83 | 24.47 | 2.83 | 24.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.67 | 24.46 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 23.50 | 24.52 | 23.50 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.59 | 4.83 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.49 | 2.50 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.47 | 1.83 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.17 | 24.49 | 6.17 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.50 | 24.49 | 2.50 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.46 | 0.67 | 24.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.49 | 3.33 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.57 | 4.67 | 24.57 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.52 | 5.00 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 4.33 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.49 | 4.50 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 1.33 | 24.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.47 | 1.00 | 24.47 |
Annual Sum or Average | 0.00 | 0.00 | 30.33 | 24.52 | 30.33 | 24.52 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.59 | 5.00 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.49 | 3.00 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.58 | 5.17 | 24.58 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.58 | 4.67 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.53 | 5.00 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.50 | 4.33 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 24.48 | 4.17 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.47 | 0.83 | 24.47 |
Annual Sum or Average | 0.00 | 0.00 | 29.17 | 24.53 | 29.17 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.58 | 5.17 | 24.58 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.46 | 0.83 | 24.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.33 | 24.49 | 3.33 | 24.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.59 | 5.17 | 24.59 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.58 | 4.67 | 24.58 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.53 | 5.00 | 24.53 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 4.50 | 24.51 | 4.50 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.33 | 24.49 | 4.33 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 2.00 | 24.47 | 2.00 | 24.47 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.47 | 1.00 | 24.47 |
Annual Sum or Average | 0.00 | 0.00 | 31.17 | 24.53 | 31.17 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.59 | 5.17 | 24.59 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.49 | 0.83 | 24.49 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 2.67 | 24.48 | 2.67 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.54 | 5.00 | 24.54 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.67 | 5.17 | 24.67 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.66 | 5.00 | 24.66 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 4.00 | 24.49 | 4.00 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.65 | 5.17 | 24.65 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.58 | 5.00 | 24.58 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.54 | 5.17 | 24.54 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.50 | 3.83 | 24.50 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.50 | 2.17 | 24.50 |
Annual Sum or Average | 0.00 | 0.00 | 45.00 | 24.57 | 45.00 | 24.57 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.48 | 0.83 | 24.48 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.67 | 5.17 | 24.67 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.50 | 24.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.48 | 3.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.61 | 5.17 | 24.61 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.55 | 5.00 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.49 | 3.17 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
Annual Sum or Average | 0.00 | 0.00 | 39.67 | 24.56 | 39.67 | 24.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.50 | 24.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.63 | 5.17 | 24.63 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.46 | 0.83 | 24.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.49 | 1.33 | 24.49 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.48 | 3.17 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 5.17 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.56 | 5.00 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.49 | 3.00 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 1.67 | 24.49 |
Annual Sum or Average | 0.00 | 0.00 | 40.50 | 24.56 | 40.50 | 24.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.50 | 24.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.48 | 0.50 | 24.48 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.46 | 0.83 | 24.46 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 1.33 | 24.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.63 | 5.00 | 24.63 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.48 | 3.00 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.62 | 5.17 | 24.62 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.56 | 5.00 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 4.83 | 24.52 | 4.83 | 24.52 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 3.00 | 24.49 | 3.00 | 24.49 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.51 | 1.50 | 24.51 |
Annual Sum or Average | 0.00 | 0.00 | 40.17 | 24.56 | 40.17 | 24.56 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.46 | 0.50 | 24.46 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.64 | 5.17 | 24.64 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.46 | 0.83 | 24.46 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 3.67 | 24.50 | 3.67 | 24.50 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.61 | 5.17 | 24.61 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 4.67 | 24.61 | 4.67 | 24.61 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.47 | 0.67 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 5.00 | 24.57 | 5.00 | 24.57 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 3.83 | 24.52 | 3.83 | 24.52 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 3.17 | 24.50 | 3.17 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.48 | 1.00 | 24.48 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 | 24.46 | 0.83 | 24.46 |
Annual Sum or Average | 0.00 | 0.00 | 29.00 | 24.55 | 29.00 | 24.55 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 5.17 | 24.61 | 5.17 | 24.61 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 42.83 | 24.81 | 496.00 | 24.05 | 42.83 | 24.10 |
February | 33.50 | 24.81 | 448.00 | 24.04 | 33.50 | 24.09 |
March | 51.33 | 24.90 | 497.00 | 24.08 | 51.33 | 24.15 |
April | 213.17 | 24.11 | 479.00 | 24.03 | 213.17 | 24.05 |
May | 405.50 | 24.02 | 496.00 | 24.01 | 405.50 | 24.01 |
June | 409.17 | 24.01 | 481.00 | 24.00 | 409.17 | 24.01 |
July | 179.67 | 24.15 | 495.00 | 24.03 | 179.67 | 24.05 |
August | 458.67 | 24.01 | 497.00 | 24.01 | 458.67 | 24.01 |
September | 400.50 | 24.00 | 479.00 | 23.99 | 400.50 | 23.99 |
October | 403.67 | 24.01 | 496.00 | 24.00 | 403.67 | 24.00 |
November | 235.67 | 24.10 | 480.00 | 24.03 | 235.67 | 24.04 |
December | 103.33 | 24.23 | 496.00 | 24.02 | 103.33 | 24.05 |
Annual Sum or Average | 2937.00 | 24.08 | 5840.00 | 24.02 | 2937.00 | 24.03 |
Minimum of Months | 33.50 | 24.00 | 448.00 | 23.99 | 33.50 | 23.99 |
Maximum of Months | 458.67 | 24.90 | 497.00 | 24.08 | 458.67 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 15.00 | 24.50 | 495.33 | 24.00 | 15.00 | 24.01 |
February | 18.83 | 24.09 | 446.83 | 23.99 | 18.83 | 23.99 |
March | 32.50 | 25.16 | 496.00 | 24.07 | 32.50 | 24.13 |
April | 172.67 | 24.14 | 479.00 | 24.03 | 172.67 | 24.05 |
May | 318.67 | 24.05 | 495.67 | 24.02 | 318.67 | 24.03 |
June | 325.83 | 24.03 | 481.00 | 24.01 | 325.83 | 24.01 |
July | 131.83 | 24.00 | 495.00 | 23.99 | 131.83 | 23.99 |
August | 355.83 | 24.02 | 497.00 | 24.01 | 355.83 | 24.01 |
September | 312.33 | 23.99 | 479.00 | 23.99 | 312.33 | 23.99 |
October | 307.67 | 24.00 | 496.00 | 23.99 | 307.67 | 23.99 |
November | 171.83 | 24.04 | 478.17 | 24.00 | 171.83 | 24.01 |
December | 57.17 | 24.03 | 492.83 | 23.98 | 57.17 | 23.98 |
Annual Sum or Average | 2220.17 | 24.05 | 5831.83 | 24.01 | 2220.17 | 24.01 |
Minimum of Months | 15.00 | 23.99 | 446.83 | 23.98 | 15.00 | 23.98 |
Maximum of Months | 355.83 | 25.16 | 497.00 | 24.07 | 355.83 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 50.17 | 25.08 | 371.00 | 24.24 | 50.17 | 24.33 |
February | 52.17 | 25.02 | 336.00 | 24.25 | 52.17 | 24.34 |
March | 58.83 | 25.10 | 379.00 | 24.26 | 58.83 | 24.36 |
April | 194.00 | 24.35 | 360.00 | 24.22 | 194.00 | 24.25 |
May | 320.50 | 24.19 | 375.00 | 24.17 | 320.50 | 24.17 |
June | 338.17 | 24.17 | 366.00 | 24.16 | 338.17 | 24.16 |
July | 190.00 | 24.34 | 369.00 | 24.20 | 190.00 | 24.24 |
August | 367.83 | 24.13 | 379.00 | 24.12 | 367.83 | 24.12 |
September | 330.17 | 24.15 | 360.00 | 24.14 | 330.17 | 24.14 |
October | 326.33 | 24.15 | 371.00 | 24.13 | 326.33 | 24.14 |
November | 210.67 | 24.26 | 360.00 | 24.16 | 210.67 | 24.19 |
December | 96.67 | 24.60 | 369.00 | 24.21 | 96.67 | 24.28 |
Annual Sum or Average | 2535.50 | 24.27 | 4395.00 | 24.18 | 2535.50 | 24.20 |
Minimum of Months | 50.17 | 24.13 | 336.00 | 24.12 | 50.17 | 24.12 |
Maximum of Months | 367.83 | 25.10 | 379.00 | 24.26 | 367.83 | 24.36 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 49.83 | 25.09 | 371.00 | 24.24 | 49.83 | 24.33 |
February | 52.33 | 25.04 | 336.00 | 24.25 | 52.33 | 24.35 |
March | 58.50 | 25.11 | 379.00 | 24.26 | 58.50 | 24.36 |
April | 192.50 | 24.35 | 360.00 | 24.22 | 192.50 | 24.25 |
May | 319.00 | 24.19 | 375.00 | 24.17 | 319.00 | 24.18 |
June | 337.33 | 24.17 | 366.00 | 24.16 | 337.33 | 24.16 |
July | 188.33 | 24.34 | 369.00 | 24.20 | 188.33 | 24.24 |
August | 366.83 | 24.13 | 379.00 | 24.12 | 366.83 | 24.12 |
September | 329.33 | 24.15 | 360.00 | 24.14 | 329.33 | 24.14 |
October | 325.17 | 24.15 | 371.00 | 24.13 | 325.17 | 24.14 |
November | 211.50 | 24.26 | 360.00 | 24.16 | 211.50 | 24.19 |
December | 97.17 | 24.60 | 369.00 | 24.21 | 97.17 | 24.28 |
Annual Sum or Average | 2527.83 | 24.27 | 4395.00 | 24.18 | 2527.83 | 24.20 |
Minimum of Months | 49.83 | 24.13 | 336.00 | 24.12 | 49.83 | 24.12 |
Maximum of Months | 366.83 | 25.11 | 379.00 | 24.26 | 366.83 | 24.36 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 51.83 | 25.03 | 371.00 | 24.23 | 51.83 | 24.32 |
February | 53.83 | 24.96 | 336.00 | 24.24 | 53.83 | 24.33 |
March | 60.67 | 25.04 | 379.00 | 24.25 | 60.67 | 24.35 |
April | 197.83 | 24.34 | 360.00 | 24.21 | 197.83 | 24.25 |
May | 321.50 | 24.19 | 375.00 | 24.16 | 321.50 | 24.17 |
June | 340.00 | 24.17 | 366.00 | 24.16 | 340.00 | 24.16 |
July | 193.50 | 24.32 | 369.00 | 24.20 | 193.50 | 24.23 |
August | 369.33 | 24.12 | 379.00 | 24.12 | 369.33 | 24.12 |
September | 332.33 | 24.15 | 360.00 | 24.13 | 332.33 | 24.14 |
October | 331.67 | 24.14 | 371.00 | 24.13 | 331.67 | 24.13 |
November | 221.17 | 24.24 | 360.00 | 24.16 | 221.17 | 24.18 |
December | 100.67 | 24.56 | 369.00 | 24.21 | 100.67 | 24.27 |
Annual Sum or Average | 2574.33 | 24.26 | 4395.00 | 24.17 | 2574.33 | 24.20 |
Minimum of Months | 51.83 | 24.12 | 336.00 | 24.12 | 51.83 | 24.12 |
Maximum of Months | 369.33 | 25.04 | 379.00 | 24.25 | 369.33 | 24.35 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 54.83 | 24.37 | 340.00 | 24.03 | 54.83 | 24.07 |
February | 61.67 | 24.32 | 308.00 | 24.04 | 61.67 | 24.08 |
March | 62.50 | 24.33 | 348.00 | 24.03 | 62.50 | 24.07 |
April | 226.00 | 24.05 | 330.00 | 24.02 | 226.00 | 24.03 |
May | 317.67 | 24.00 | 344.00 | 24.00 | 317.67 | 24.00 |
June | 333.33 | 23.98 | 336.00 | 23.98 | 333.33 | 23.98 |
July | 228.67 | 24.05 | 338.00 | 24.02 | 228.67 | 24.03 |
August | 347.50 | 23.97 | 348.00 | 23.97 | 347.50 | 23.97 |
September | 326.17 | 23.99 | 330.00 | 23.99 | 326.17 | 23.99 |
October | 333.17 | 23.99 | 340.00 | 23.99 | 333.17 | 23.99 |
November | 245.00 | 24.00 | 330.00 | 23.98 | 245.00 | 23.99 |
December | 111.83 | 24.17 | 338.00 | 24.03 | 111.83 | 24.06 |
Annual Sum or Average | 2648.33 | 24.03 | 4030.00 | 24.00 | 2648.33 | 24.01 |
Minimum of Months | 54.83 | 23.97 | 308.00 | 23.97 | 54.83 | 23.97 |
Maximum of Months | 347.50 | 24.37 | 348.00 | 24.04 | 347.50 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 55.67 | 24.34 | 340.00 | 24.03 | 55.67 | 24.07 |
February | 63.50 | 24.30 | 308.00 | 24.04 | 63.50 | 24.08 |
March | 63.00 | 24.32 | 348.00 | 24.03 | 63.00 | 24.07 |
April | 229.00 | 24.05 | 330.00 | 24.02 | 229.00 | 24.03 |
May | 315.83 | 24.00 | 344.00 | 24.00 | 315.83 | 24.00 |
June | 331.50 | 23.98 | 336.00 | 23.98 | 331.50 | 23.98 |
July | 229.33 | 24.05 | 338.00 | 24.02 | 229.33 | 24.03 |
August | 347.00 | 23.97 | 348.00 | 23.97 | 347.00 | 23.97 |
September | 325.00 | 23.99 | 330.00 | 23.99 | 325.00 | 23.99 |
October | 332.00 | 23.99 | 340.00 | 23.98 | 332.00 | 23.98 |
November | 243.67 | 24.00 | 330.00 | 23.98 | 243.67 | 23.99 |
December | 111.33 | 24.17 | 338.00 | 24.03 | 111.33 | 24.06 |
Annual Sum or Average | 2646.83 | 24.03 | 4030.00 | 24.00 | 2646.83 | 24.01 |
Minimum of Months | 55.67 | 23.97 | 308.00 | 23.97 | 55.67 | 23.97 |
Maximum of Months | 347.00 | 24.34 | 348.00 | 24.04 | 347.00 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.33 | 24.33 | 340.00 | 24.03 | 57.33 | 24.07 |
February | 65.33 | 24.28 | 308.00 | 24.04 | 65.33 | 24.07 |
March | 63.83 | 24.32 | 348.00 | 24.03 | 63.83 | 24.07 |
April | 231.17 | 24.05 | 330.00 | 24.02 | 231.17 | 24.03 |
May | 317.00 | 24.00 | 344.00 | 24.00 | 317.00 | 24.00 |
June | 332.33 | 23.98 | 336.00 | 23.98 | 332.33 | 23.98 |
July | 230.67 | 24.05 | 338.00 | 24.02 | 230.67 | 24.03 |
August | 347.50 | 23.97 | 348.00 | 23.97 | 347.50 | 23.97 |
September | 325.33 | 23.99 | 330.00 | 23.99 | 325.33 | 23.99 |
October | 332.17 | 23.99 | 340.00 | 23.98 | 332.17 | 23.98 |
November | 245.33 | 24.00 | 330.00 | 23.98 | 245.33 | 23.99 |
December | 113.33 | 24.17 | 338.00 | 24.03 | 113.33 | 24.06 |
Annual Sum or Average | 2661.33 | 24.03 | 4030.00 | 24.00 | 2661.33 | 24.01 |
Minimum of Months | 57.33 | 23.97 | 308.00 | 23.97 | 57.33 | 23.97 |
Maximum of Months | 347.50 | 24.33 | 348.00 | 24.04 | 347.50 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 57.67 | 24.32 | 340.00 | 24.03 | 57.67 | 24.07 |
February | 65.00 | 24.29 | 308.00 | 24.04 | 65.00 | 24.07 |
March | 63.50 | 24.32 | 348.00 | 24.03 | 63.50 | 24.07 |
April | 228.67 | 24.05 | 330.00 | 24.02 | 228.67 | 24.03 |
May | 315.17 | 24.00 | 344.00 | 24.00 | 315.17 | 24.00 |
June | 331.00 | 23.98 | 336.00 | 23.98 | 331.00 | 23.98 |
July | 230.00 | 24.05 | 338.00 | 24.02 | 230.00 | 24.03 |
August | 346.83 | 23.97 | 348.00 | 23.97 | 346.83 | 23.97 |
September | 324.67 | 23.99 | 330.00 | 23.99 | 324.67 | 23.99 |
October | 332.17 | 23.99 | 340.00 | 23.98 | 332.17 | 23.98 |
November | 245.33 | 24.00 | 330.00 | 23.98 | 245.33 | 23.98 |
December | 114.33 | 24.16 | 338.00 | 24.03 | 114.33 | 24.06 |
Annual Sum or Average | 2654.33 | 24.03 | 4030.00 | 24.00 | 2654.33 | 24.01 |
Minimum of Months | 57.67 | 23.97 | 308.00 | 23.97 | 57.67 | 23.97 |
Maximum of Months | 346.83 | 24.32 | 348.00 | 24.04 | 346.83 | 24.07 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 39.33 | 24.61 | 340.00 | 24.05 | 39.33 | 24.10 |
February | 45.33 | 24.54 | 308.00 | 24.06 | 45.33 | 24.12 |
March | 42.67 | 24.56 | 348.00 | 24.04 | 42.67 | 24.09 |
April | 163.00 | 24.12 | 330.00 | 24.04 | 163.00 | 24.06 |
May | 283.83 | 24.02 | 344.00 | 24.01 | 283.83 | 24.01 |
June | 299.67 | 24.00 | 336.00 | 23.99 | 299.67 | 24.00 |
July | 164.17 | 24.13 | 338.00 | 24.05 | 164.17 | 24.07 |
August | 334.67 | 23.98 | 348.00 | 23.97 | 334.67 | 23.97 |
September | 294.17 | 24.01 | 330.00 | 24.00 | 294.17 | 24.00 |
October | 311.00 | 24.00 | 340.00 | 23.99 | 311.00 | 23.99 |
November | 212.50 | 24.02 | 330.00 | 23.99 | 212.50 | 24.00 |
December | 89.67 | 24.25 | 338.00 | 24.04 | 89.67 | 24.08 |
Annual Sum or Average | 2280.00 | 24.06 | 4030.00 | 24.02 | 2280.00 | 24.03 |
Minimum of Months | 39.33 | 23.98 | 308.00 | 23.97 | 39.33 | 23.97 |
Maximum of Months | 334.67 | 24.61 | 348.00 | 24.06 | 334.67 | 24.12 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.97976 | 58.52572 | 0.66746 | 14.51543 |
February | 448.00000 | 23.98384 | 58.66584 | 0.67751 | 14.80513 |
March | 497.00000 | 23.99440 | 60.05206 | 0.69138 | 15.25991 |
April | 479.00000 | 23.98909 | 64.59100 | 0.72525 | 16.26447 |
May | 496.00000 | 23.99827 | 68.39056 | -0.0716 | 5.50301 |
June | 481.00000 | 23.99596 | 68.17171 | -0.0621 | 5.47531 |
July | 495.00000 | 23.98299 | 63.44646 | -0.1232 | 5.57601 |
August | 497.00000 | 24.00238 | 69.19986 | -0.0891 | 5.55310 |
September | 479.00000 | 23.98202 | 67.81772 | -0.0956 | 5.50160 |
October | 496.00000 | 23.98754 | 67.57030 | 0.72101 | 16.11949 |
November | 480.00000 | 23.99129 | 64.57522 | 0.70694 | 15.70372 |
December | 496.00000 | 23.97216 | 60.84616 | 0.67715 | 14.78498 |
Annual Sum or Average | 5840.00000 | 23.98834 | 64.34624 | 0.36677 | 11.23151 |
Minimum of Months | 448.00000 | 23.97216 | 58.52572 | -0.1232 | 5.47531 |
Maximum of Months | 497.00000 | 24.00238 | 69.19986 | 0.72525 | 16.26447 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.98234 | 55.01070 | 0.62516 | 13.38855 |
February | 448.00000 | 23.98493 | 55.35109 | 0.63326 | 13.60907 |
March | 497.00000 | 23.99404 | 56.85961 | 0.64520 | 13.97285 |
April | 479.00000 | 23.98746 | 60.92763 | 0.67497 | 14.80395 |
May | 496.00000 | 23.99665 | 64.30559 | -0.1321 | 5.78472 |
June | 481.00000 | 23.99431 | 64.20265 | -0.1250 | 5.75668 |
July | 495.00000 | 23.98299 | 59.67149 | -0.1791 | 5.96721 |
August | 497.00000 | 24.00101 | 65.02227 | -0.1464 | 5.86215 |
September | 479.00000 | 23.98092 | 63.60106 | -0.1547 | 5.85394 |
October | 496.00000 | 23.98780 | 63.12610 | 0.67364 | 14.77355 |
November | 480.00000 | 23.99129 | 60.47832 | 0.66076 | 14.40504 |
December | 496.00000 | 23.97396 | 56.81437 | 0.63213 | 13.57910 |
Annual Sum or Average | 5840.00000 | 23.98817 | 60.46946 | 0.31531 | 10.62671 |
Minimum of Months | 448.00000 | 23.97396 | 55.01070 | -0.1791 | 5.75668 |
Maximum of Months | 497.00000 | 24.00101 | 65.02227 | 0.67497 | 14.80395 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.12171 | 58.29787 | 0.68839 | 15.25908 |
February | 336.00000 | 24.12927 | 58.72070 | 0.69836 | 15.57491 |
March | 379.00000 | 24.13076 | 59.87066 | 0.70397 | 15.75562 |
April | 360.00000 | 24.14908 | 64.75018 | 0.74389 | 17.03844 |
May | 375.00000 | 24.14592 | 68.55845 | -0.0471 | 5.80684 |
June | 366.00000 | 24.14864 | 68.65720 | -0.0366 | 5.79479 |
July | 369.00000 | 24.13236 | 64.34685 | -0.0927 | 5.81926 |
August | 379.00000 | 24.11915 | 69.99006 | -0.0680 | 5.69035 |
September | 360.00000 | 24.12835 | 68.74517 | -0.0660 | 5.73383 |
October | 371.00000 | 24.11756 | 68.36346 | 0.74575 | 17.01510 |
November | 360.00000 | 24.10834 | 64.85944 | 0.72611 | 16.38308 |
December | 369.00000 | 24.11367 | 60.60231 | 0.69822 | 15.55608 |
Annual Sum or Average | 4395.00000 | 24.12871 | 64.68501 | 0.38806 | 11.74444 |
Minimum of Months | 336.00000 | 24.10834 | 58.29787 | -0.0927 | 5.69035 |
Maximum of Months | 379.00000 | 24.14908 | 69.99006 | 0.74575 | 17.03844 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.12229 | 58.27088 | 0.68994 | 15.30712 |
February | 336.00000 | 24.12990 | 58.69345 | 0.69995 | 15.62523 |
March | 379.00000 | 24.13130 | 59.84229 | 0.70546 | 15.80285 |
April | 360.00000 | 24.14973 | 64.69922 | 0.74556 | 17.09476 |
May | 375.00000 | 24.14670 | 68.48634 | -0.0443 | 5.81142 |
June | 366.00000 | 24.14957 | 68.59223 | -0.0339 | 5.80082 |
July | 369.00000 | 24.13311 | 64.28819 | -0.0901 | 5.81675 |
August | 379.00000 | 24.11971 | 69.96047 | -0.0662 | 5.69154 |
September | 360.00000 | 24.12898 | 68.70014 | -0.0638 | 5.73545 |
October | 371.00000 | 24.11787 | 68.32521 | 0.74712 | 17.06133 |
November | 360.00000 | 24.10869 | 64.84370 | 0.72730 | 16.42195 |
December | 369.00000 | 24.11395 | 60.59017 | 0.69934 | 15.59199 |
Annual Sum or Average | 4395.00000 | 24.12930 | 64.64577 | 0.38992 | 11.77204 |
Minimum of Months | 336.00000 | 24.10869 | 58.27088 | -0.0901 | 5.69154 |
Maximum of Months | 379.00000 | 24.14973 | 69.96047 | 0.74712 | 17.09476 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.11855 | 58.41881 | 0.68717 | 15.21560 |
February | 336.00000 | 24.12621 | 58.84013 | 0.69723 | 15.53428 |
March | 379.00000 | 24.12776 | 59.99897 | 0.70277 | 15.71231 |
April | 360.00000 | 24.14631 | 64.87365 | 0.74320 | 17.00924 |
May | 375.00000 | 24.14352 | 68.66561 | -0.0475 | 5.79419 |
June | 366.00000 | 24.14602 | 68.77349 | -0.0373 | 5.78079 |
July | 369.00000 | 24.12961 | 64.46723 | -0.0938 | 5.80890 |
August | 379.00000 | 24.11602 | 70.18700 | -0.0700 | 5.68012 |
September | 360.00000 | 24.12552 | 68.91212 | -0.0675 | 5.72275 |
October | 371.00000 | 24.11432 | 68.53975 | 0.74483 | 16.97900 |
November | 360.00000 | 24.10510 | 65.03526 | 0.72488 | 16.33699 |
December | 369.00000 | 24.11008 | 60.76258 | 0.69654 | 15.49929 |
Annual Sum or Average | 4395.00000 | 24.12573 | 64.82786 | 0.38692 | 11.71504 |
Minimum of Months | 336.00000 | 24.10510 | 58.41881 | -0.0938 | 5.68012 |
Maximum of Months | 379.00000 | 24.14631 | 70.18700 | 0.74483 | 17.00924 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97905 | 59.77529 | 0.66580 | 14.46828 |
February | 308.00000 | 23.98558 | 60.27004 | 0.67674 | 14.81377 |
March | 348.00000 | 23.97368 | 61.41581 | 0.67934 | 14.88013 |
April | 330.00000 | 23.99984 | 66.35459 | 0.72099 | 16.16189 |
May | 344.00000 | 23.99359 | 70.12727 | -0.0821 | 5.57953 |
June | 336.00000 | 23.98339 | 70.24880 | -0.0738 | 5.51770 |
July | 338.00000 | 24.00041 | 65.95760 | -0.1236 | 5.70654 |
August | 348.00000 | 23.96942 | 71.87035 | -0.1060 | 5.54270 |
September | 330.00000 | 23.99000 | 70.51272 | -0.0997 | 5.57545 |
October | 340.00000 | 23.98413 | 70.18165 | 0.72451 | 16.22955 |
November | 330.00000 | 23.96987 | 66.65684 | 0.70366 | 15.56343 |
December | 338.00000 | 23.98425 | 62.16688 | 0.67647 | 14.80281 |
Annual Sum or Average | 4030.00000 | 23.98436 | 66.33462 | 0.36023 | 11.19647 |
Minimum of Months | 308.00000 | 23.96942 | 59.77529 | -0.1236 | 5.51770 |
Maximum of Months | 348.00000 | 24.00041 | 71.87035 | 0.72451 | 16.22955 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97873 | 59.75092 | 0.64673 | 13.94012 |
February | 308.00000 | 23.98508 | 60.25780 | 0.65703 | 14.25895 |
March | 348.00000 | 23.97301 | 61.39533 | 0.65957 | 14.31914 |
April | 330.00000 | 23.99887 | 66.37595 | 0.70142 | 15.57506 |
May | 344.00000 | 23.99245 | 70.18361 | -0.1095 | 5.68674 |
June | 336.00000 | 23.98244 | 70.34002 | -0.1022 | 5.61995 |
July | 338.00000 | 23.99960 | 65.99504 | -0.1502 | 5.85657 |
August | 348.00000 | 23.96854 | 71.95170 | -0.1312 | 5.66331 |
September | 330.00000 | 23.98884 | 70.59377 | -0.1257 | 5.69467 |
October | 340.00000 | 23.98334 | 70.25203 | 0.70712 | 15.70279 |
November | 330.00000 | 23.96923 | 66.70615 | 0.68565 | 15.03506 |
December | 338.00000 | 23.98376 | 62.17638 | 0.65809 | 14.28619 |
Annual Sum or Average | 4030.00000 | 23.98358 | 66.37160 | 0.33808 | 10.93241 |
Minimum of Months | 308.00000 | 23.96854 | 59.75092 | -0.1502 | 5.61995 |
Maximum of Months | 348.00000 | 23.99960 | 71.95170 | 0.70712 | 15.70279 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97826 | 59.82390 | 0.64523 | 13.89782 |
February | 308.00000 | 23.98476 | 60.32688 | 0.65566 | 14.21985 |
March | 348.00000 | 23.97273 | 61.46255 | 0.65829 | 14.28251 |
April | 330.00000 | 23.99861 | 66.44985 | 0.70030 | 15.54064 |
May | 344.00000 | 23.99225 | 70.26390 | -0.1112 | 5.69257 |
June | 336.00000 | 23.98210 | 70.42200 | -0.1040 | 5.62545 |
July | 338.00000 | 23.99925 | 66.07233 | -0.1521 | 5.86538 |
August | 348.00000 | 23.96836 | 72.04064 | -0.1329 | 5.67096 |
September | 330.00000 | 23.98875 | 70.67964 | -0.1274 | 5.70145 |
October | 340.00000 | 23.98304 | 70.34642 | 0.70595 | 15.66671 |
November | 330.00000 | 23.96891 | 66.79641 | 0.68439 | 14.99709 |
December | 338.00000 | 23.98337 | 62.25821 | 0.65665 | 14.24477 |
Annual Sum or Average | 4030.00000 | 23.98329 | 66.45200 | 0.33658 | 10.91316 |
Minimum of Months | 308.00000 | 23.96836 | 59.82390 | -0.1521 | 5.62545 |
Maximum of Months | 348.00000 | 23.99925 | 72.04064 | 0.70595 | 15.66671 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.97792 | 59.84341 | 0.64687 | 13.94245 |
February | 308.00000 | 23.98466 | 60.31729 | 0.65792 | 14.28289 |
March | 348.00000 | 23.97260 | 61.44208 | 0.66079 | 14.35334 |
April | 330.00000 | 23.99860 | 66.39364 | 0.70328 | 15.63008 |
May | 344.00000 | 23.99233 | 70.21321 | -0.1071 | 5.67802 |
June | 336.00000 | 23.98216 | 70.35237 | -0.0996 | 5.61017 |
July | 338.00000 | 23.99929 | 66.03467 | -0.1482 | 5.84413 |
August | 348.00000 | 23.96819 | 72.01135 | -0.1294 | 5.65394 |
September | 330.00000 | 23.98871 | 70.63788 | -0.1235 | 5.68429 |
October | 340.00000 | 23.98282 | 70.36494 | 0.70785 | 15.72398 |
November | 330.00000 | 23.96862 | 66.81351 | 0.68619 | 15.04963 |
December | 338.00000 | 23.98305 | 62.28951 | 0.65817 | 14.28692 |
Annual Sum or Average | 4030.00000 | 23.98317 | 66.43289 | 0.33945 | 10.94067 |
Minimum of Months | 308.00000 | 23.96819 | 59.84341 | -0.1482 | 5.61017 |
Maximum of Months | 348.00000 | 23.99929 | 72.01135 | 0.70785 | 15.72398 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.98408 | 58.86060 | 0.67560 | 14.77162 |
February | 308.00000 | 23.99179 | 59.14121 | 0.69126 | 15.26448 |
March | 348.00000 | 23.97853 | 60.26353 | 0.69651 | 15.41387 |
April | 330.00000 | 24.00630 | 64.82046 | 0.74071 | 16.80770 |
May | 344.00000 | 23.99865 | 68.69777 | -0.0555 | 5.59109 |
June | 336.00000 | 23.98829 | 68.61089 | -0.0435 | 5.52259 |
July | 338.00000 | 24.00814 | 64.57486 | -0.0981 | 5.67296 |
August | 348.00000 | 23.97282 | 70.48834 | -0.0830 | 5.52787 |
September | 330.00000 | 23.99587 | 68.98931 | -0.0742 | 5.56574 |
October | 340.00000 | 23.98903 | 69.14105 | 0.73268 | 16.51725 |
November | 330.00000 | 23.97342 | 65.57055 | 0.71159 | 15.82618 |
December | 338.00000 | 23.98926 | 61.22815 | 0.68466 | 15.06472 |
Annual Sum or Average | 4030.00000 | 23.98959 | 65.07194 | 0.37830 | 11.41974 |
Minimum of Months | 308.00000 | 23.97282 | 58.86060 | -0.0981 | 5.52259 |
Maximum of Months | 348.00000 | 24.00814 | 70.48834 | 0.74071 | 16.80770 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.454055E+11 | 0.124820E+11 | 491.10 | 0.294194E+11 | 0.159861E+11 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 67991.18 | 10-JAN-09:01 | 43377.54 | 23-JAN-09:01 | 35302.67 | 10-JAN-09:04 | 14990.60 | 03-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.438288E+11 | 0.121208E+11 | 446.73 | 0.283571E+11 | 0.154717E+11 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 67795.24 | 16-FEB-09:01 | 44980.89 | 24-FEB-09:01 | 34650.25 | 16-FEB-09:04 | 14893.51 | 18-FEB-09:03 | 0.00 | 01-FEB-00:03 |
March | 0.509568E+11 | 0.141305E+11 | 499.32 | 0.324455E+11 | 0.185113E+11 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 68277.10 | 27-MAR-08:61 | 44458.10 | 04-MAR-09:01 | 36176.98 | 27-MAR-08:04 | 15164.02 | 09-MAR-09:01 | 0.00 | 01-MAR-00:03 |
April | 0.554586E+11 | 0.150573E+11 | 484.88 | 0.322021E+11 | 0.232565E+11 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 68428.14 | 03-APR-08:61 | 35614.05 | 27-APR-08:61 | 37112.01 | 20-APR-08:04 | 15291.04 | 15-APR-08:04 | 0.00 | 01-APR-00:03 |
May | 0.616963E+11 | 0.163903E+11 | 501.07 | 0.330818E+11 | 0.286145E+11 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 68842.03 | 17-MAY-08:61 | 33654.19 | 06-MAY-08:61 | 42406.47 | 19-MAY-08:06 | 15546.95 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.612378E+11 | 0.161729E+11 | 487.79 | 0.326657E+11 | 0.285722E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 68748.39 | 01-JUN-08:61 | 36249.61 | 25-JUN-07:02 | 42006.53 | 10-JUN-08:06 | 15207.83 | 14-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.510083E+11 | 0.136773E+11 | 495.67 | 0.297767E+11 | 0.212316E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 68287.51 | 01-JUL-08:61 | 41218.64 | 09-JUL-07:02 | 36252.92 | 01-JUL-08:04 | 14794.35 | 03-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.569807E+11 | 0.148598E+11 | 499.66 | 0.295450E+11 | 0.274357E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 68793.56 | 19-AUG-08:61 | 34676.31 | 27-AUG-07:02 | 43165.33 | 11-AUG-08:06 | 15164.11 | 28-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.542767E+11 | 0.142513E+11 | 483.31 | 0.290545E+11 | 0.252222E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 68818.28 | 21-SEP-08:61 | 37739.72 | 10-SEP-07:02 | 39416.34 | 25-SEP-08:04 | 14996.35 | 14-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.524769E+11 | 0.137602E+11 | 495.03 | 0.281708E+11 | 0.243060E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 68821.64 | 23-OCT-08:61 | 37332.31 | 08-OCT-07:02 | 39133.24 | 23-OCT-08:04 | 14973.56 | 05-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.483440E+11 | 0.128561E+11 | 480.85 | 0.275772E+11 | 0.207669E+11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 68295.51 | 03-NOV-08:61 | 40947.35 | 25-NOV-09:01 | 36357.12 | 03-NOV-08:04 | 14901.65 | 14-NOV-09:13 | 0.00 | 01-NOV-00:10 |
December | 0.461959E+11 | 0.125132E+11 | 493.61 | 0.285075E+11 | 0.176884E+11 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-01:05 | 67690.51 | 18-DEC-09:01 | 43079.88 | 27-DEC-09:01 | 34348.69 | 18-DEC-09:04 | 14949.96 | 09-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.627866E+12 | 0.168272E+12 | 5859.02 | 0.360803E+12 | 0.267063E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.438288E+11 | 0.121208E+11 | 446.73 | 0.275772E+11 | 0.154717E+11 | 0.00 | 1.00 | 0.00 | 67690.51 | 33654.19 | 34348.69 | 14794.35 | 0.00 | |||||||
Maximum of Months | 0.616963E+11 | 0.163903E+11 | 501.07 | 0.330818E+11 | 0.286145E+11 | 0.00 | 1.00 | 0.00 | 68842.03 | 44980.89 | 43165.33 | 15546.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.221742E+11 | 0.603062E+10 | 492.80 | 0.147990E+11 | 0.737517E+10 | 0.00 | 1.00 | 01-JAN-08:62 | 0.00 | 01-JAN-00:05 | 34255.58 | 10-JAN-09:01 | 24472.68 | 16-JAN-08:62 | 15468.06 | 10-JAN-09:03 | 7564.24 | 03-JAN-09:01 | 0.00 | 01-JAN-00:05 |
February | 0.212558E+11 | 0.581840E+10 | 449.12 | 0.141182E+11 | 0.713754E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 34181.62 | 16-FEB-09:01 | 24987.08 | 24-FEB-09:01 | 15234.16 | 16-FEB-09:03 | 7520.46 | 18-FEB-09:01 | 0.00 | 01-FEB-00:03 |
March | 0.245648E+11 | 0.675262E+10 | 500.49 | 0.160556E+11 | 0.850921E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 34436.19 | 27-MAR-08:61 | 24049.66 | 04-MAR-09:01 | 16388.97 | 27-MAR-08:04 | 7654.21 | 09-MAR-09:01 | 0.00 | 01-MAR-00:03 |
April | 0.264621E+11 | 0.713153E+10 | 485.22 | 0.158410E+11 | 0.106211E+11 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 34598.69 | 20-APR-08:61 | 22280.43 | 23-APR-07:02 | 17079.85 | 20-APR-08:13 | 7734.40 | 15-APR-08:03 | 0.00 | 01-APR-00:03 |
May | 0.295415E+11 | 0.778903E+10 | 501.68 | 0.163961E+11 | 0.131455E+11 | 0.00 | 1.00 | 01-MAY-08:61 | 0.00 | 01-MAY-00:10 | 35158.71 | 16-MAY-08:61 | 21536.68 | 14-MAY-07:02 | 19792.69 | 22-MAY-08:04 | 7864.83 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.293750E+11 | 0.769543E+10 | 487.91 | 0.161801E+11 | 0.131949E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 35121.88 | 10-JUN-08:61 | 22955.77 | 25-JUN-07:02 | 19701.17 | 10-JUN-08:04 | 7707.54 | 14-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.245660E+11 | 0.652361E+10 | 497.13 | 0.147795E+11 | 0.978649E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 34283.12 | 01-JUL-08:61 | 24693.37 | 16-JUL-07:01 | 15598.48 | 01-JUL-08:03 | 7471.90 | 03-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.274897E+11 | 0.710056E+10 | 500.46 | 0.147406E+11 | 0.127491E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 35220.60 | 25-AUG-08:61 | 21751.59 | 27-AUG-07:02 | 19926.88 | 11-AUG-08:04 | 7654.24 | 28-AUG-08:04 | 0.00 | 01-AUG-00:10 |
September | 0.260910E+11 | 0.678761E+10 | 484.37 | 0.144482E+11 | 0.116429E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 34781.98 | 01-SEP-08:61 | 23230.64 | 10-SEP-07:02 | 17708.91 | 25-SEP-08:13 | 7577.77 | 11-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.254559E+11 | 0.660566E+10 | 496.03 | 0.141711E+11 | 0.112848E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 34622.16 | 23-OCT-08:61 | 23266.04 | 08-OCT-07:02 | 17312.37 | 23-OCT-08:04 | 7577.27 | 05-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.234890E+11 | 0.618237E+10 | 480.96 | 0.138773E+11 | 0.961170E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 34318.73 | 14-NOV-09:01 | 23310.37 | 23-NOV-08:61 | 16054.48 | 14-NOV-09:04 | 7518.89 | 07-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.225280E+11 | 0.604156E+10 | 496.03 | 0.144060E+11 | 0.812193E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-01:05 | 33965.20 | 01-DEC-09:01 | 23713.94 | 25-DEC-08:62 | 14395.98 | 01-DEC-09:03 | 7554.03 | 09-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.302993E+12 | 0.804590E+11 | 5872.20 | 0.179813E+12 | 0.123180E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.212558E+11 | 0.581840E+10 | 449.12 | 0.138773E+11 | 0.713754E+10 | 0.00 | 1.00 | 0.00 | 33965.20 | 21536.68 | 14395.98 | 7471.90 | 0.00 | |||||||
Maximum of Months | 0.295415E+11 | 0.778903E+10 | 501.68 | 0.163961E+11 | 0.131949E+11 | 0.00 | 1.00 | 0.00 | 35220.60 | 24987.08 | 19926.88 | 7864.83 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.183510E+11 | 0.496046E+10 | 353.73 | 0.119737E+11 | 0.637731E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 | 35203.96 | 02-JAN-08:61 | 20891.55 | 16-JAN-09:01 | 19255.38 | 02-JAN-08:04 | 7568.08 | 11-JAN-08:04 | 0.00 | 01-JAN-00:05 |
February | 0.177389E+11 | 0.482073E+10 | 324.29 | 0.115129E+11 | 0.622601E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 35088.82 | 16-FEB-08:61 | 22677.47 | 25-FEB-08:61 | 18781.34 | 16-FEB-08:04 | 7472.78 | 20-FEB-09:04 | 0.00 | 01-FEB-00:03 |
March | 0.207865E+11 | 0.568000E+10 | 374.58 | 0.132874E+11 | 0.749909E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 35241.97 | 25-MAR-07:01 | 21625.59 | 04-MAR-08:61 | 19419.26 | 28-MAR-07:04 | 7565.42 | 26-MAR-08:04 | 0.00 | 01-MAR-00:03 |
April | 0.221919E+11 | 0.591490E+10 | 357.95 | 0.128800E+11 | 0.931182E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 35305.96 | 24-APR-07:01 | 17888.86 | 27-APR-07:01 | 20155.84 | 03-APR-07:04 | 7564.26 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.251666E+11 | 0.655007E+10 | 373.54 | 0.134446E+11 | 0.117220E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35350.51 | 17-MAY-07:03 | 16494.31 | 06-MAY-07:01 | 22792.87 | 22-MAY-07:04 | 7729.72 | 07-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.251920E+11 | 0.651969E+10 | 364.65 | 0.133476E+11 | 0.118444E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 35326.65 | 01-JUN-07:01 | 16392.35 | 27-JUN-07:01 | 22322.04 | 05-JUN-07:06 | 7629.55 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.203738E+11 | 0.533540E+10 | 364.44 | 0.117488E+11 | 0.862503E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 35318.45 | 01-JUL-07:01 | 18329.30 | 06-JUL-07:01 | 19634.53 | 01-JUL-07:04 | 7425.29 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.235123E+11 | 0.599698E+10 | 374.19 | 0.120514E+11 | 0.114610E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35343.57 | 19-AUG-07:01 | 16469.17 | 30-AUG-07:01 | 21642.49 | 21-AUG-07:04 | 7553.93 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.219709E+11 | 0.563752E+10 | 357.00 | 0.116224E+11 | 0.103485E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 35355.52 | 18-SEP-07:01 | 16472.73 | 13-SEP-07:01 | 22074.07 | 25-SEP-07:06 | 7515.60 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.213425E+11 | 0.546706E+10 | 364.26 | 0.113492E+11 | 0.999323E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 35355.05 | 23-OCT-07:01 | 16484.92 | 08-OCT-08:61 | 20900.50 | 23-OCT-07:03 | 7497.06 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.196214E+11 | 0.511535E+10 | 352.33 | 0.112185E+11 | 0.840294E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 35300.00 | 05-NOV-08:61 | 20280.15 | 25-NOV-08:61 | 20792.86 | 12-NOV-09:04 | 7501.61 | 23-NOV-09:04 | 0.00 | 01-NOV-00:10 |
December | 0.185422E+11 | 0.494375E+10 | 351.15 | 0.115759E+11 | 0.696630E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 35299.04 | 11-DEC-08:61 | 20955.32 | 21-DEC-08:62 | 20314.62 | 11-DEC-08:04 | 7492.75 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.254790E+12 | 0.669419E+11 | 4312.09 | 0.146012E+12 | 0.108778E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.177389E+11 | 0.482073E+10 | 324.29 | 0.112185E+11 | 0.622601E+10 | 0.00 | 1.00 | 0.00 | 35088.82 | 16392.35 | 18781.34 | 7425.29 | 0.00 | |||||||
Maximum of Months | 0.251920E+11 | 0.655007E+10 | 374.58 | 0.134446E+11 | 0.118444E+11 | 0.00 | 1.00 | 0.00 | 35355.52 | 22677.47 | 22792.87 | 7729.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.184307E+11 | 0.498139E+10 | 354.38 | 0.120288E+11 | 0.640188E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 | 35273.71 | 02-JAN-08:61 | 20989.13 | 16-JAN-09:01 | 19231.68 | 02-JAN-08:04 | 7587.66 | 11-JAN-08:04 | 0.00 | 01-JAN-00:05 |
February | 0.178171E+11 | 0.484165E+10 | 325.46 | 0.115672E+11 | 0.624991E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 35174.06 | 16-FEB-08:61 | 22747.35 | 25-FEB-08:61 | 18814.54 | 16-FEB-08:04 | 7492.09 | 20-FEB-09:04 | 0.00 | 01-FEB-00:03 |
March | 0.208761E+11 | 0.570438E+10 | 375.08 | 0.133478E+11 | 0.752825E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 35328.75 | 28-MAR-07:01 | 21691.03 | 04-MAR-08:61 | 19414.20 | 28-MAR-07:04 | 7585.15 | 26-MAR-08:04 | 0.00 | 01-MAR-00:03 |
April | 0.222999E+11 | 0.594344E+10 | 358.80 | 0.129496E+11 | 0.935028E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 35396.82 | 24-APR-07:01 | 17965.12 | 27-APR-07:01 | 20040.13 | 10-APR-07:03 | 7585.41 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.252975E+11 | 0.658344E+10 | 373.95 | 0.135277E+11 | 0.117698E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35441.49 | 17-MAY-07:01 | 16596.40 | 06-MAY-07:01 | 22762.39 | 22-MAY-07:04 | 7751.68 | 07-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.253169E+11 | 0.655165E+10 | 364.84 | 0.134253E+11 | 0.118916E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 35417.56 | 01-JUN-07:01 | 16463.61 | 27-JUN-07:01 | 22268.99 | 11-JUN-07:01 | 7651.27 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.204872E+11 | 0.536446E+10 | 365.06 | 0.118223E+11 | 0.866491E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 35401.33 | 01-JUL-07:01 | 18419.26 | 06-JUL-07:01 | 19653.15 | 01-JUL-07:04 | 7444.44 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.236034E+11 | 0.602067E+10 | 375.02 | 0.121048E+11 | 0.114986E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35434.53 | 19-AUG-07:01 | 16530.89 | 30-AUG-07:01 | 21674.19 | 21-AUG-07:04 | 7573.89 | 27-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.220720E+11 | 0.566346E+10 | 357.38 | 0.116838E+11 | 0.103882E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 35446.51 | 18-SEP-07:01 | 16529.55 | 13-SEP-07:01 | 22018.64 | 25-SEP-07:06 | 7536.27 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.214374E+11 | 0.549151E+10 | 365.36 | 0.114066E+11 | 0.100308E+11 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 35446.04 | 23-OCT-07:01 | 16591.82 | 08-OCT-08:61 | 20920.72 | 23-OCT-07:03 | 7516.99 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.196956E+11 | 0.513485E+10 | 353.67 | 0.112644E+11 | 0.843114E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 35368.31 | 05-NOV-08:61 | 20365.88 | 25-NOV-08:61 | 20794.37 | 12-NOV-09:04 | 7520.91 | 23-NOV-09:04 | 0.00 | 01-NOV-00:10 |
December | 0.186082E+11 | 0.496145E+10 | 353.26 | 0.116185E+11 | 0.698970E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 35389.88 | 11-DEC-08:61 | 21037.71 | 27-DEC-08:61 | 20281.87 | 11-DEC-08:04 | 7512.09 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.255942E+12 | 0.672424E+11 | 4322.25 | 0.146747E+12 | 0.109195E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.178171E+11 | 0.484165E+10 | 325.46 | 0.112644E+11 | 0.624991E+10 | 0.00 | 1.00 | 0.00 | 35174.06 | 16463.61 | 18814.54 | 7444.44 | 0.00 | |||||||
Maximum of Months | 0.253169E+11 | 0.658344E+10 | 375.08 | 0.135277E+11 | 0.118916E+11 | 0.00 | 1.00 | 0.00 | 35446.51 | 22747.35 | 22762.39 | 7751.68 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.182180E+11 | 0.492556E+10 | 351.92 | 0.118706E+11 | 0.634740E+10 | 0.00 | 1.00 | 01-JAN-09:01 | 0.00 | 01-JAN-00:05 | 35083.51 | 02-JAN-08:61 | 20817.72 | 16-JAN-09:01 | 19193.69 | 02-JAN-08:04 | 7541.84 | 11-JAN-08:04 | 0.00 | 01-JAN-00:05 |
February | 0.176226E+11 | 0.478987E+10 | 322.84 | 0.114227E+11 | 0.619986E+10 | 0.00 | 1.00 | 01-FEB-08:61 | 0.00 | 01-FEB-00:03 | 34999.26 | 16-FEB-08:61 | 22566.51 | 25-FEB-08:61 | 18821.68 | 16-FEB-08:04 | 7447.20 | 20-FEB-09:04 | 0.00 | 01-FEB-00:03 |
March | 0.206460E+11 | 0.564230E+10 | 373.23 | 0.131793E+11 | 0.746665E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:03 | 35147.51 | 25-MAR-07:01 | 21507.40 | 04-MAR-08:61 | 19425.73 | 28-MAR-07:04 | 7539.31 | 26-MAR-08:04 | 0.00 | 01-MAR-00:03 |
April | 0.220761E+11 | 0.588361E+10 | 358.11 | 0.127933E+11 | 0.928274E+10 | 0.00 | 1.00 | 01-APR-07:01 | 0.00 | 01-APR-00:03 | 35185.11 | 24-APR-07:01 | 17759.70 | 27-APR-07:01 | 20013.01 | 10-APR-07:04 | 7538.43 | 30-APR-08:13 | 0.00 | 01-APR-00:03 |
May | 0.250676E+11 | 0.652247E+10 | 373.22 | 0.133748E+11 | 0.116928E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 35229.52 | 17-MAY-07:01 | 16387.19 | 06-MAY-07:01 | 22718.48 | 22-MAY-07:04 | 7703.84 | 07-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.250861E+11 | 0.649079E+10 | 364.93 | 0.132718E+11 | 0.118143E+11 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 35205.73 | 01-JUN-07:01 | 16291.03 | 27-JUN-07:01 | 22230.90 | 05-JUN-07:06 | 7603.80 | 18-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.202605E+11 | 0.530565E+10 | 362.93 | 0.116651E+11 | 0.859538E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 35197.57 | 01-JUL-07:01 | 18237.43 | 06-JUL-07:01 | 19678.24 | 01-JUL-07:04 | 7399.84 | 30-JUL-08:04 | 0.00 | 01-JUL-00:05 |
August | 0.233431E+11 | 0.595372E+10 | 372.93 | 0.119347E+11 | 0.114084E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 35222.60 | 19-AUG-07:01 | 16345.94 | 30-AUG-07:01 | 21639.41 | 21-AUG-07:04 | 7528.07 | 13-AUG-08:13 | 0.00 | 01-AUG-00:10 |
September | 0.218330E+11 | 0.560165E+10 | 355.41 | 0.115252E+11 | 0.103079E+11 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 35234.51 | 18-SEP-07:01 | 16343.51 | 13-SEP-07:01 | 21980.27 | 25-SEP-07:06 | 7489.42 | 10-SEP-08:13 | 0.00 | 01-SEP-00:05 |
October | 0.211934E+11 | 0.542911E+10 | 363.24 | 0.112446E+11 | 0.994881E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 35234.04 | 23-OCT-07:01 | 16421.99 | 08-OCT-08:61 | 20864.83 | 23-OCT-07:03 | 7470.93 | 29-OCT-08:13 | 0.00 | 01-OCT-00:10 |
November | 0.194684E+11 | 0.507626E+10 | 351.48 | 0.111075E+11 | 0.836091E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 35181.52 | 05-NOV-08:61 | 20151.65 | 25-NOV-08:61 | 20772.34 | 12-NOV-09:04 | 7476.00 | 23-NOV-09:04 | 0.00 | 01-NOV-00:10 |
December | 0.183825E+11 | 0.490287E+10 | 349.67 | 0.114549E+11 | 0.692764E+10 | 0.00 | 1.00 | 01-DEC-08:61 | 0.00 | 01-DEC-00:10 | 35178.22 | 11-DEC-08:61 | 20829.23 | 27-DEC-08:61 | 20282.01 | 11-DEC-08:04 | 7467.02 | 31-DEC-09:04 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.253197E+12 | 0.665239E+11 | 4299.91 | 0.144844E+12 | 0.108353E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.176226E+11 | 0.478987E+10 | 322.84 | 0.111075E+11 | 0.619986E+10 | 0.00 | 1.00 | 0.00 | 34999.26 | 16291.03 | 18821.68 | 7399.84 | 0.00 | |||||||
Maximum of Months | 0.250861E+11 | 0.652247E+10 | 373.23 | 0.133748E+11 | 0.118143E+11 | 0.00 | 1.00 | 0.00 | 35234.51 | 22566.51 | 22718.48 | 7703.84 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.327442E+11 | 0.895727E+10 | 345.30 | 0.209879E+11 | 0.117562E+11 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 62534.81 | 02-JAN-09:01 | 38538.13 | 16-JAN-10:01 | 33788.63 | 02-JAN-09:04 | 13686.60 | 03-JAN-09:03 | 0.00 | 01-JAN-00:05 |
February | 0.317308E+11 | 0.871655E+10 | 317.24 | 0.202299E+11 | 0.115009E+11 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 62067.54 | 16-FEB-09:01 | 40494.93 | 24-FEB-09:01 | 32171.72 | 16-FEB-09:04 | 13793.74 | 26-FEB-10:03 | 0.00 | 01-FEB-00:03 |
March | 0.372473E+11 | 0.102817E+11 | 364.27 | 0.234031E+11 | 0.138442E+11 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 62522.28 | 27-MAR-08:61 | 40567.06 | 04-MAR-09:01 | 33826.58 | 27-MAR-08:04 | 14082.31 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.398671E+11 | 0.107137E+11 | 346.48 | 0.226765E+11 | 0.171906E+11 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 62522.28 | 24-APR-08:61 | 32677.28 | 27-APR-08:61 | 35827.74 | 03-APR-08:04 | 13965.66 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.453591E+11 | 0.118797E+11 | 362.97 | 0.237008E+11 | 0.216583E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 62852.47 | 17-MAY-08:61 | 30634.70 | 06-MAY-08:61 | 40836.94 | 29-MAY-08:61 | 14186.08 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.455989E+11 | 0.118752E+11 | 356.08 | 0.236263E+11 | 0.219726E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 62766.97 | 01-JUN-08:61 | 30847.17 | 21-JUN-08:61 | 39753.90 | 11-JUN-08:61 | 14031.16 | 11-JUN-09:25 | 0.00 | 01-JUN-00:10 |
July | 0.362988E+11 | 0.959593E+10 | 349.40 | 0.204814E+11 | 0.158174E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 62701.73 | 24-JUL-08:61 | 33240.21 | 06-JUL-08:61 | 34651.04 | 24-JUL-08:04 | 13604.26 | 04-JUL-09:04 | 0.00 | 01-JUL-00:05 |
August | 0.421898E+11 | 0.108369E+11 | 363.61 | 0.210196E+11 | 0.211702E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 62808.21 | 19-AUG-08:61 | 29620.80 | 30-AUG-08:61 | 40218.39 | 21-AUG-08:06 | 13901.44 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.392932E+11 | 0.101583E+11 | 342.66 | 0.202591E+11 | 0.190341E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 62852.47 | 18-SEP-08:61 | 30452.15 | 13-SEP-08:61 | 39415.75 | 25-SEP-08:06 | 13768.98 | 03-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.380611E+11 | 0.982988E+10 | 350.72 | 0.196902E+11 | 0.183708E+11 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 62833.85 | 23-OCT-08:61 | 31837.25 | 20-OCT-08:61 | 38418.88 | 23-OCT-08:04 | 13768.38 | 29-OCT-09:13 | 0.00 | 01-OCT-00:10 |
November | 0.349492E+11 | 0.919782E+10 | 343.32 | 0.194667E+11 | 0.154825E+11 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 62612.08 | 13-NOV-09:01 | 36615.77 | 25-NOV-09:01 | 36363.95 | 12-NOV-10:06 | 13857.91 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.328606E+11 | 0.885949E+10 | 344.95 | 0.200931E+11 | 0.127675E+11 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 62749.53 | 18-DEC-09:01 | 39391.36 | 27-DEC-09:01 | 34771.45 | 18-DEC-09:04 | 13953.88 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.456200E+12 | 0.120903E+12 | 4187.01 | 0.255635E+12 | 0.200565E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.317308E+11 | 0.871655E+10 | 317.24 | 0.194667E+11 | 0.115009E+11 | 0.00 | 1.00 | 0.00 | 62067.54 | 29620.80 | 32171.72 | 13604.26 | 0.00 | |||||||
Maximum of Months | 0.455989E+11 | 0.118797E+11 | 364.27 | 0.237008E+11 | 0.219726E+11 | 0.00 | 1.00 | 0.00 | 62852.47 | 40567.06 | 40836.94 | 14186.08 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.170968E+11 | 0.460062E+10 | 343.78 | 0.109818E+11 | 0.611499E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 32882.27 | 02-JAN-09:01 | 20246.76 | 16-JAN-10:01 | 17765.00 | 02-JAN-09:04 | 7067.16 | 03-JAN-09:03 | 0.00 | 01-JAN-00:05 |
February | 0.165672E+11 | 0.447734E+10 | 316.04 | 0.105810E+11 | 0.598622E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 32622.28 | 16-FEB-09:01 | 21328.25 | 24-FEB-09:01 | 16882.87 | 16-FEB-09:04 | 7122.56 | 26-FEB-10:03 | 0.00 | 01-FEB-00:03 |
March | 0.194298E+11 | 0.527729E+10 | 363.17 | 0.122306E+11 | 0.719917E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 32860.02 | 27-MAR-08:61 | 21310.24 | 04-MAR-09:01 | 17744.00 | 27-MAR-08:04 | 7271.87 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.207906E+11 | 0.549886E+10 | 346.15 | 0.118528E+11 | 0.893780E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 32860.02 | 24-APR-08:61 | 17207.96 | 27-APR-08:61 | 18807.34 | 03-APR-08:04 | 7212.52 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.236420E+11 | 0.609494E+10 | 361.77 | 0.123880E+11 | 0.112540E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 33033.55 | 17-MAY-08:03 | 16099.87 | 06-MAY-08:61 | 21659.20 | 29-MAY-08:61 | 7326.44 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.237436E+11 | 0.608766E+10 | 355.33 | 0.123332E+11 | 0.114104E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 32988.62 | 01-JUN-08:61 | 16348.50 | 21-JUN-08:61 | 20986.62 | 11-JUN-08:61 | 7230.95 | 11-JUN-09:13 | 0.00 | 01-JUN-00:10 |
July | 0.189326E+11 | 0.492476E+10 | 348.34 | 0.107084E+11 | 0.822416E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 32963.57 | 24-JUL-08:61 | 17444.21 | 06-JUL-08:61 | 18196.11 | 24-JUL-08:04 | 7025.05 | 04-JUL-09:04 | 0.00 | 01-JUL-00:05 |
August | 0.219787E+11 | 0.555591E+10 | 362.68 | 0.109833E+11 | 0.109955E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 33010.29 | 19-AUG-08:61 | 15619.50 | 30-AUG-08:61 | 21148.69 | 21-AUG-08:06 | 7178.15 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.204847E+11 | 0.521140E+10 | 341.91 | 0.105903E+11 | 0.989436E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 33033.55 | 18-SEP-08:03 | 16045.60 | 13-SEP-08:61 | 20697.53 | 25-SEP-08:06 | 7111.54 | 03-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.198490E+11 | 0.504385E+10 | 349.67 | 0.102981E+11 | 0.955091E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 33023.76 | 23-OCT-08:04 | 16756.07 | 20-OCT-08:61 | 20172.39 | 23-OCT-08:04 | 7110.58 | 29-OCT-09:13 | 0.00 | 01-OCT-00:10 |
November | 0.182282E+11 | 0.471960E+10 | 342.38 | 0.101794E+11 | 0.804876E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 32907.21 | 13-NOV-09:01 | 19317.07 | 25-NOV-09:01 | 19143.72 | 12-NOV-10:04 | 7155.76 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.171495E+11 | 0.454849E+10 | 344.13 | 0.105100E+11 | 0.663943E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 32979.45 | 18-DEC-09:01 | 20755.22 | 27-DEC-09:01 | 18304.88 | 18-DEC-09:04 | 7205.50 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.237893E+12 | 0.620407E+11 | 4175.36 | 0.133637E+12 | 0.104256E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.165672E+11 | 0.447734E+10 | 316.04 | 0.101794E+11 | 0.598622E+10 | 0.00 | 1.00 | 0.00 | 32622.28 | 15619.50 | 16882.87 | 7025.05 | 0.00 | |||||||
Maximum of Months | 0.237436E+11 | 0.609494E+10 | 363.17 | 0.123880E+11 | 0.114104E+11 | 0.00 | 1.00 | 0.00 | 33033.55 | 21328.25 | 21659.20 | 7326.44 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.170190E+11 | 0.457895E+10 | 343.42 | 0.109221E+11 | 0.609696E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 32752.99 | 02-JAN-09:01 | 20152.43 | 16-JAN-10:01 | 17715.79 | 02-JAN-09:04 | 7037.91 | 03-JAN-09:03 | 0.00 | 01-JAN-00:05 |
February | 0.164997E+11 | 0.445792E+10 | 315.19 | 0.105290E+11 | 0.597072E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 32497.40 | 16-FEB-09:01 | 21224.21 | 24-FEB-09:01 | 16847.26 | 16-FEB-09:04 | 7093.03 | 26-FEB-10:03 | 0.00 | 01-FEB-00:03 |
March | 0.193549E+11 | 0.525531E+10 | 362.66 | 0.121739E+11 | 0.718108E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 32723.90 | 27-MAR-08:61 | 21210.22 | 04-MAR-09:01 | 17688.54 | 27-MAR-08:04 | 7241.64 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.207204E+11 | 0.547784E+10 | 345.41 | 0.118013E+11 | 0.891916E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 32723.90 | 24-APR-08:61 | 17116.24 | 27-APR-08:61 | 18743.14 | 03-APR-08:04 | 7182.28 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.235673E+11 | 0.607280E+10 | 361.62 | 0.123348E+11 | 0.112326E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 32896.72 | 17-MAY-08:61 | 16017.86 | 06-MAY-08:61 | 21585.31 | 29-MAY-08:61 | 7295.68 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.236685E+11 | 0.606543E+10 | 355.25 | 0.122794E+11 | 0.113891E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 32851.97 | 01-JUN-08:61 | 16141.11 | 21-JUN-08:61 | 20916.07 | 11-JUN-08:61 | 7201.00 | 11-JUN-09:13 | 0.00 | 01-JUN-00:10 |
July | 0.188604E+11 | 0.490444E+10 | 347.73 | 0.106560E+11 | 0.820436E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 32832.82 | 24-JUL-08:61 | 17349.46 | 06-JUL-08:61 | 18138.70 | 24-JUL-08:04 | 6995.80 | 04-JUL-09:04 | 0.00 | 01-JUL-00:05 |
August | 0.218989E+11 | 0.553347E+10 | 362.28 | 0.109286E+11 | 0.109703E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 32873.55 | 19-AUG-08:61 | 15528.10 | 30-AUG-08:61 | 21090.95 | 21-AUG-08:06 | 7148.41 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.204115E+11 | 0.519040E+10 | 340.81 | 0.105389E+11 | 0.987258E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 32896.72 | 18-SEP-08:61 | 15952.67 | 13-SEP-08:61 | 20636.19 | 25-SEP-08:06 | 7081.50 | 03-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.197688E+11 | 0.502165E+10 | 349.20 | 0.102421E+11 | 0.952672E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 32886.97 | 23-OCT-08:04 | 16659.21 | 20-OCT-08:61 | 20109.17 | 23-OCT-08:04 | 7080.64 | 29-OCT-09:13 | 0.00 | 01-OCT-00:10 |
November | 0.181477E+11 | 0.469746E+10 | 341.61 | 0.101216E+11 | 0.802608E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 32770.90 | 13-NOV-09:01 | 19206.70 | 25-NOV-09:01 | 19097.64 | 12-NOV-10:04 | 7126.05 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.170677E+11 | 0.452585E+10 | 343.17 | 0.104490E+11 | 0.661865E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 32842.84 | 18-DEC-09:01 | 20653.50 | 27-DEC-09:01 | 18259.37 | 18-DEC-09:04 | 7175.54 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.236985E+12 | 0.617815E+11 | 4168.35 | 0.132977E+12 | 0.104008E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.164997E+11 | 0.445792E+10 | 315.19 | 0.101216E+11 | 0.597072E+10 | 0.00 | 1.00 | 0.00 | 32497.40 | 15528.10 | 16847.26 | 6995.80 | 0.00 | |||||||
Maximum of Months | 0.236685E+11 | 0.607280E+10 | 362.66 | 0.123348E+11 | 0.113891E+11 | 0.00 | 1.00 | 0.00 | 32896.72 | 21224.21 | 21585.31 | 7295.68 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.170040E+11 | 0.457643E+10 | 342.90 | 0.109117E+11 | 0.609232E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 32835.12 | 02-JAN-09:01 | 20177.61 | 16-JAN-10:01 | 17801.81 | 02-JAN-09:04 | 7052.65 | 03-JAN-09:03 | 0.00 | 01-JAN-00:05 |
February | 0.165113E+11 | 0.446188E+10 | 314.81 | 0.105392E+11 | 0.597214E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 32571.74 | 16-FEB-09:01 | 21259.90 | 24-FEB-09:01 | 16906.13 | 16-FEB-09:04 | 7107.86 | 26-FEB-10:03 | 0.00 | 01-FEB-00:03 |
March | 0.193814E+11 | 0.526317E+10 | 362.32 | 0.121952E+11 | 0.718614E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 32792.40 | 27-MAR-08:61 | 21237.09 | 04-MAR-09:01 | 17739.49 | 27-MAR-08:04 | 7256.79 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.207727E+11 | 0.549205E+10 | 345.62 | 0.118412E+11 | 0.893151E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 32792.40 | 24-APR-08:61 | 17149.45 | 27-APR-08:61 | 18779.59 | 03-APR-08:04 | 7197.47 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.236179E+11 | 0.608646E+10 | 361.45 | 0.123730E+11 | 0.112449E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 32965.57 | 17-MAY-08:61 | 16053.52 | 06-MAY-08:61 | 21635.87 | 29-MAY-08:61 | 7311.23 | 06-MAY-08:13 | 0.00 | 01-MAY-00:10 |
June | 0.237310E+11 | 0.608178E+10 | 355.11 | 0.123256E+11 | 0.114054E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 32920.73 | 01-JUN-08:61 | 16164.63 | 21-JUN-08:61 | 20946.74 | 11-JUN-08:61 | 7216.07 | 11-JUN-09:13 | 0.00 | 01-JUN-00:10 |
July | 0.188970E+11 | 0.491411E+10 | 347.00 | 0.106833E+11 | 0.821369E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 32906.47 | 24-JUL-08:61 | 17385.19 | 06-JUL-08:61 | 18200.79 | 24-JUL-08:04 | 7010.19 | 04-JUL-09:04 | 0.00 | 01-JUL-00:05 |
August | 0.219285E+11 | 0.554172E+10 | 361.96 | 0.109512E+11 | 0.109773E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 32942.36 | 19-AUG-08:61 | 15552.67 | 30-AUG-08:61 | 21191.26 | 21-AUG-08:06 | 7163.38 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.204478E+11 | 0.520017E+10 | 340.38 | 0.105663E+11 | 0.988149E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 32965.57 | 18-SEP-08:03 | 15984.08 | 13-SEP-08:61 | 20687.25 | 25-SEP-08:06 | 7096.82 | 03-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.197601E+11 | 0.502084E+10 | 348.28 | 0.102380E+11 | 0.952203E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 32955.81 | 23-OCT-08:61 | 16667.80 | 20-OCT-08:61 | 20189.24 | 23-OCT-08:04 | 7095.26 | 29-OCT-09:13 | 0.00 | 01-OCT-00:10 |
November | 0.181380E+11 | 0.469632E+10 | 341.27 | 0.101162E+11 | 0.802178E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 32839.49 | 13-NOV-09:01 | 19214.61 | 25-NOV-09:01 | 19166.52 | 12-NOV-10:06 | 7140.91 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.170430E+11 | 0.452093E+10 | 342.64 | 0.104320E+11 | 0.661099E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 32911.58 | 18-DEC-09:01 | 20680.13 | 27-DEC-09:01 | 18342.13 | 18-DEC-09:04 | 7190.51 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.237233E+12 | 0.618559E+11 | 4163.74 | 0.133173E+12 | 0.104060E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.165113E+11 | 0.446188E+10 | 314.81 | 0.101162E+11 | 0.597214E+10 | 0.00 | 1.00 | 0.00 | 32571.74 | 15552.67 | 16906.13 | 7010.19 | 0.00 | |||||||
Maximum of Months | 0.237310E+11 | 0.608646E+10 | 362.32 | 0.123730E+11 | 0.114054E+11 | 0.00 | 1.00 | 0.00 | 32965.57 | 21259.90 | 21635.87 | 7311.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.187074E+11 | 0.507602E+10 | 345.24 | 0.121701E+11 | 0.653732E+10 | 0.00 | 1.00 | 01-JAN-10:01 | 0.00 | 01-JAN-00:05 | 37378.81 | 02-JAN-09:01 | 22855.52 | 23-JAN-09:01 | 20403.54 | 02-JAN-09:04 | 8017.25 | 03-JAN-09:03 | 0.00 | 01-JAN-00:05 |
February | 0.183116E+11 | 0.499008E+10 | 318.05 | 0.118772E+11 | 0.643439E+10 | 0.00 | 1.00 | 01-FEB-09:01 | 0.00 | 01-FEB-00:03 | 37300.78 | 16-FEB-09:01 | 23850.52 | 24-FEB-09:01 | 20151.47 | 16-FEB-09:04 | 8079.89 | 26-FEB-10:04 | 0.00 | 01-FEB-00:03 |
March | 0.216314E+11 | 0.591857E+10 | 364.98 | 0.138144E+11 | 0.781697E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:03 | 37288.89 | 15-MAR-08:61 | 23666.46 | 04-MAR-09:01 | 20580.87 | 24-MAR-08:03 | 8250.70 | 26-MAR-09:13 | 0.00 | 01-MAR-00:03 |
April | 0.231809E+11 | 0.618636E+10 | 347.53 | 0.135018E+11 | 0.967911E+10 | 0.00 | 1.00 | 01-APR-08:61 | 0.00 | 01-APR-00:03 | 37416.30 | 21-APR-08:61 | 18647.05 | 27-APR-08:61 | 22644.61 | 30-APR-08:61 | 8190.40 | 09-APR-09:13 | 0.00 | 01-APR-00:03 |
May | 0.261165E+11 | 0.681005E+10 | 363.31 | 0.140093E+11 | 0.121072E+11 | 0.00 | 1.00 | 01-MAY-07:01 | 0.00 | 01-MAY-00:10 | 37474.61 | 17-MAY-08:03 | 17771.57 | 06-MAY-08:61 | 25227.52 | 30-MAY-07:01 | 8312.84 | 07-MAY-09:13 | 0.00 | 01-MAY-00:10 |
June | 0.263528E+11 | 0.683301E+10 | 356.03 | 0.140539E+11 | 0.122989E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 37423.63 | 01-JUN-08:04 | 17640.29 | 21-JUN-08:61 | 24436.33 | 11-JUN-08:03 | 8220.93 | 11-JUN-09:15 | 0.00 | 01-JUN-00:10 |
July | 0.210033E+11 | 0.550838E+10 | 349.92 | 0.121455E+11 | 0.885773E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 37430.49 | 24-JUL-08:61 | 19782.96 | 19-JUL-08:61 | 20800.44 | 01-JUL-08:03 | 7969.29 | 04-JUL-09:04 | 0.00 | 01-JUL-00:05 |
August | 0.242442E+11 | 0.619452E+10 | 364.96 | 0.124400E+11 | 0.118042E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 37448.22 | 19-AUG-08:61 | 17096.45 | 30-AUG-08:61 | 24261.59 | 13-AUG-08:61 | 8143.37 | 27-AUG-09:13 | 0.00 | 01-AUG-00:10 |
September | 0.226346E+11 | 0.581874E+10 | 344.27 | 0.120259E+11 | 0.106087E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 37474.61 | 18-SEP-08:03 | 17676.47 | 13-SEP-08:61 | 23341.35 | 25-SEP-08:06 | 8082.23 | 03-SEP-09:13 | 0.00 | 01-SEP-00:05 |
October | 0.215531E+11 | 0.553813E+10 | 350.36 | 0.114289E+11 | 0.101242E+11 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 37463.50 | 23-OCT-08:61 | 18252.68 | 20-OCT-08:61 | 22934.48 | 23-OCT-08:04 | 8071.28 | 29-OCT-09:13 | 0.00 | 01-OCT-00:10 |
November | 0.198643E+11 | 0.519583E+10 | 343.59 | 0.113143E+11 | 0.854997E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 37357.62 | 01-NOV-08:61 | 21770.54 | 25-NOV-09:01 | 21679.58 | 12-NOV-10:04 | 8118.30 | 19-NOV-10:13 | 0.00 | 01-NOV-00:10 |
December | 0.186915E+11 | 0.500308E+10 | 344.85 | 0.116286E+11 | 0.706285E+10 | 0.00 | 1.00 | 01-DEC-09:01 | 0.00 | 01-DEC-00:10 | 37413.23 | 18-DEC-09:01 | 23041.57 | 27-DEC-09:01 | 20978.94 | 18-DEC-09:03 | 8175.47 | 31-DEC-10:13 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.262292E+12 | 0.690728E+11 | 4193.09 | 0.150410E+12 | 0.111882E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.183116E+11 | 0.499008E+10 | 318.05 | 0.113143E+11 | 0.643439E+10 | 0.00 | 1.00 | 0.00 | 37288.89 | 17096.45 | 20151.47 | 7969.29 | 0.00 | |||||||
Maximum of Months | 0.263528E+11 | 0.683301E+10 | 364.98 | 0.140539E+11 | 0.122989E+11 | 0.00 | 1.00 | 0.00 | 37474.61 | 23850.52 | 25227.52 | 8312.84 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.80 | 9.65 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.16 | 7.32 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.50 | 5.10 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 66.24 | 2.43 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 67.95 | 2.94 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.96 | 3.21 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 61.33 | 5.61 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.08 | 4.44 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.56 | 4.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.56 | 5.64 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.56 | 6.88 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.81 | 11.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.57 | 5.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.08 | 2.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.80 | 11.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.80 | 9.65 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.16 | 7.32 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.50 | 5.10 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 66.24 | 2.43 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 67.95 | 2.94 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.96 | 3.21 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 61.33 | 5.61 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.08 | 4.44 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.56 | 4.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.56 | 5.64 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.56 | 6.88 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.81 | 11.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.57 | 5.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.08 | 2.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.80 | 11.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.80 | 9.65 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.16 | 7.32 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.50 | 5.10 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 66.24 | 2.43 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 67.95 | 2.94 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.96 | 3.21 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 61.33 | 5.61 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.08 | 4.44 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.56 | 4.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.56 | 5.64 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.56 | 6.88 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.81 | 11.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.57 | 5.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.08 | 2.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.80 | 11.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.80 | 9.65 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.16 | 7.32 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.50 | 5.10 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 66.24 | 2.43 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 67.95 | 2.94 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.96 | 3.21 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 61.33 | 5.61 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.08 | 4.44 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.56 | 4.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.56 | 5.64 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.56 | 6.88 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.81 | 11.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.57 | 5.74 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.08 | 2.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.80 | 11.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.18 | 32.62 | 45.56 | 151.99 | 11.62 | 0.00 | 0.00 | 0.00 |
February | 66.39 | 21.65 | 44.74 | 137.91 | 8.88 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 6.08 | 39.22 | 102.20 | 6.23 | 0.00 | 0.00 | 0.00 |
April | 33.78 | 0.02 | 33.76 | 78.93 | 2.98 | 0.00 | 0.00 | 0.00 |
May | 33.80 | 0.00 | 33.80 | 81.03 | 3.56 | 0.00 | 0.00 | 0.00 |
June | 33.68 | 0.00 | 33.68 | 79.83 | 3.88 | 0.00 | 0.00 | 0.00 |
July | 34.70 | 0.00 | 34.70 | 73.33 | 6.74 | 0.00 | 0.00 | 0.00 |
August | 33.78 | 0.05 | 33.72 | 70.58 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 37.39 | 1.22 | 36.17 | 80.80 | 5.41 | 0.00 | 0.00 | 0.00 |
October | 48.92 | 7.80 | 41.12 | 98.90 | 6.77 | 0.00 | 0.00 | 0.00 |
November | 63.61 | 19.41 | 44.21 | 125.29 | 8.28 | 0.00 | 0.00 | 0.00 |
December | 78.14 | 33.25 | 44.90 | 149.63 | 13.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.91 | 10.13 | 38.77 | 102.37 | 6.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.68 | 0.00 | 33.68 | 70.58 | 2.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.18 | 33.25 | 45.56 | 151.99 | 13.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.18 | 32.62 | 45.56 | 151.99 | 11.62 | 0.00 | 0.00 | 0.00 |
February | 66.39 | 21.65 | 44.74 | 137.91 | 8.88 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 6.08 | 39.22 | 102.20 | 6.23 | 0.00 | 0.00 | 0.00 |
April | 33.78 | 0.02 | 33.76 | 78.93 | 2.98 | 0.00 | 0.00 | 0.00 |
May | 33.80 | 0.00 | 33.80 | 81.03 | 3.56 | 0.00 | 0.00 | 0.00 |
June | 33.68 | 0.00 | 33.68 | 79.83 | 3.88 | 0.00 | 0.00 | 0.00 |
July | 34.70 | 0.00 | 34.70 | 73.33 | 6.74 | 0.00 | 0.00 | 0.00 |
August | 33.78 | 0.05 | 33.72 | 70.58 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 37.39 | 1.22 | 36.17 | 80.80 | 5.41 | 0.00 | 0.00 | 0.00 |
October | 48.92 | 7.80 | 41.12 | 98.90 | 6.77 | 0.00 | 0.00 | 0.00 |
November | 63.61 | 19.41 | 44.21 | 125.29 | 8.28 | 0.00 | 0.00 | 0.00 |
December | 78.14 | 33.25 | 44.90 | 149.63 | 13.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.91 | 10.13 | 38.77 | 102.37 | 6.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.68 | 0.00 | 33.68 | 70.58 | 2.98 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.18 | 33.25 | 45.56 | 151.99 | 13.35 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 127.06 | 9.62 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.61 | 7.23 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 86.16 | 4.97 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.11 | 2.33 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.73 | 2.89 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 67.80 | 3.11 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 61.88 | 5.51 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.66 | 4.35 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.13 | 4.41 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.90 | 5.62 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.88 | 6.86 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 125.02 | 11.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 86.11 | 5.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.66 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 127.06 | 11.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 127.06 | 9.62 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.61 | 7.23 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 86.16 | 4.97 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 67.11 | 2.33 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 68.73 | 2.89 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 67.80 | 3.11 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 61.88 | 5.51 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.66 | 4.35 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 68.13 | 4.41 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.90 | 5.62 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.88 | 6.86 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 125.02 | 11.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 86.11 | 5.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.66 | 2.33 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 127.06 | 11.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.18 | 32.62 | 45.56 | 152.31 | 11.58 | 0.00 | 0.00 | 0.00 |
February | 66.39 | 21.65 | 44.74 | 138.45 | 8.76 | 0.00 | 0.00 | 0.00 |
March | 45.31 | 6.08 | 39.22 | 102.98 | 6.08 | 0.00 | 0.00 | 0.00 |
April | 33.78 | 0.02 | 33.76 | 79.95 | 2.86 | 0.00 | 0.00 | 0.00 |
May | 33.80 | 0.00 | 33.80 | 81.95 | 3.49 | 0.00 | 0.00 | 0.00 |
June | 33.68 | 0.00 | 33.68 | 80.83 | 3.76 | 0.00 | 0.00 | 0.00 |
July | 34.70 | 0.00 | 34.70 | 73.98 | 6.62 | 0.00 | 0.00 | 0.00 |
August | 33.78 | 0.05 | 33.72 | 71.27 | 5.27 | 0.00 | 0.00 | 0.00 |
September | 37.39 | 1.22 | 36.17 | 81.48 | 5.31 | 0.00 | 0.00 | 0.00 |
October | 48.92 | 7.80 | 41.12 | 99.32 | 6.75 | 0.00 | 0.00 | 0.00 |
November | 63.61 | 19.41 | 44.21 | 125.71 | 8.25 | 0.00 | 0.00 | 0.00 |
December | 78.14 | 33.25 | 44.90 | 149.90 | 13.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.91 | 10.13 | 38.77 | 103.01 | 6.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.68 | 0.00 | 33.68 | 71.27 | 2.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 78.18 | 33.25 | 45.56 | 152.31 | 13.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.64 | 12.22 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.04 | 9.79 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.38 | 7.29 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.89 | 3.62 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.49 | 4.22 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.79 | 4.59 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.50 | 7.57 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.84 | 6.43 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.89 | 6.37 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.16 | 7.89 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.38 | 9.13 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.76 | 13.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.01 | 7.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.84 | 3.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.64 | 13.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.64 | 12.22 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.04 | 9.79 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.38 | 7.29 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.89 | 3.62 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.49 | 4.22 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.79 | 4.59 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.50 | 7.57 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.84 | 6.43 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.89 | 6.37 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.16 | 7.89 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.38 | 9.13 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.76 | 13.64 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.01 | 7.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.84 | 3.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.64 | 13.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 151.00 | 14.55 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 137.06 | 11.72 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.57 | 8.80 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 76.99 | 4.41 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 78.92 | 5.06 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.08 | 5.50 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 71.99 | 9.01 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 69.96 | 7.69 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.62 | 7.60 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 97.92 | 9.38 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.44 | 10.86 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.78 | 16.23 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.19 | 9.24 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 69.96 | 4.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 151.00 | 16.23 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.56 | 12.43 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.96 | 10.01 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.31 | 7.53 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.77 | 3.86 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.31 | 4.43 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.66 | 4.85 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.40 | 7.83 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.77 | 6.64 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.81 | 6.61 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.09 | 8.12 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.32 | 9.31 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.70 | 13.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.92 | 7.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.77 | 3.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.56 | 13.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.56 | 12.43 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.96 | 10.01 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.31 | 7.53 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.77 | 3.86 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.31 | 4.43 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.66 | 4.85 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.40 | 7.83 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.77 | 6.64 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.81 | 6.61 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.09 | 8.12 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.32 | 9.31 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.70 | 13.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.92 | 7.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.77 | 3.86 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.56 | 13.82 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 150.91 | 14.81 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 136.97 | 11.98 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.49 | 9.09 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 76.85 | 4.69 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 78.71 | 5.31 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 77.93 | 5.81 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 71.87 | 9.32 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 69.88 | 7.94 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.52 | 7.87 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 97.84 | 9.65 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.36 | 11.08 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.71 | 16.43 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.09 | 9.50 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 69.88 | 4.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 150.91 | 16.43 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.68 | 12.16 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.08 | 9.74 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.42 | 7.24 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.90 | 3.62 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.46 | 4.23 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.80 | 4.62 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.50 | 7.57 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.89 | 6.35 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.93 | 6.34 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.20 | 7.84 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.44 | 9.04 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.82 | 13.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.04 | 7.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.89 | 3.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.68 | 13.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.68 | 12.16 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.08 | 9.74 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.42 | 7.24 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.90 | 3.62 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.46 | 4.23 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.80 | 4.62 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.50 | 7.57 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.89 | 6.35 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.93 | 6.34 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.20 | 7.84 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.44 | 9.04 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.82 | 13.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.04 | 7.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.89 | 3.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.68 | 13.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 151.05 | 14.49 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 137.10 | 11.66 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.61 | 8.74 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 77.01 | 4.40 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 78.88 | 5.07 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.09 | 5.54 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 71.99 | 9.01 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 70.02 | 7.60 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.66 | 7.56 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 97.97 | 9.32 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.51 | 10.76 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.86 | 16.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.23 | 9.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 70.02 | 4.40 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 151.05 | 16.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.46 | 11.19 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.77 | 8.75 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.15 | 6.25 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.85 | 2.97 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.34 | 3.57 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.71 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.26 | 6.69 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.67 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.79 | 5.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.04 | 6.92 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.22 | 8.13 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.62 | 12.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.85 | 6.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.67 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.46 | 12.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.46 | 11.19 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.77 | 8.75 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.15 | 6.25 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.85 | 2.97 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.34 | 3.57 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.71 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.26 | 6.69 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.67 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.79 | 5.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.04 | 6.92 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.22 | 8.13 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.62 | 12.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.85 | 6.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.67 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.46 | 12.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.46 | 11.19 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.77 | 8.75 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.15 | 6.25 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.85 | 2.97 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.34 | 3.57 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.71 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.26 | 6.69 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.67 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.79 | 5.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.04 | 6.92 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.22 | 8.13 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.62 | 12.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.85 | 6.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.67 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.46 | 12.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.46 | 11.19 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.77 | 8.75 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.15 | 6.25 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 64.85 | 2.97 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.34 | 3.57 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 65.71 | 3.94 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.26 | 6.69 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.67 | 5.38 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 66.79 | 5.50 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.04 | 6.92 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.22 | 8.13 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.62 | 12.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.85 | 6.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.67 | 2.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.46 | 12.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 150.78 | 13.35 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 136.75 | 10.49 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.30 | 7.56 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 76.95 | 3.61 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 78.76 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.00 | 4.72 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 71.71 | 7.97 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 69.77 | 6.45 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.50 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 97.78 | 8.23 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.25 | 9.69 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.61 | 15.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.01 | 8.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 69.77 | 3.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 150.78 | 15.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 150.78 | 13.35 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 136.75 | 10.49 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.30 | 7.56 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 76.95 | 3.61 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 78.76 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.00 | 4.72 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 71.71 | 7.97 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 69.77 | 6.45 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.50 | 6.56 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 97.78 | 8.23 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.25 | 9.69 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.61 | 15.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.01 | 8.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 69.77 | 3.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 150.78 | 15.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.63 | 10.82 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.00 | 8.35 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.47 | 5.82 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.38 | 2.67 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.87 | 3.29 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.25 | 3.63 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.56 | 6.34 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.99 | 5.00 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.10 | 5.16 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.25 | 6.56 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.41 | 7.78 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.76 | 12.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.17 | 6.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.99 | 2.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.63 | 12.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.63 | 10.82 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.00 | 8.35 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.47 | 5.82 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.38 | 2.67 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.87 | 3.29 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.25 | 3.63 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.56 | 6.34 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.99 | 5.00 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.10 | 5.16 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.25 | 6.56 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.41 | 7.78 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.76 | 12.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.17 | 6.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.99 | 2.67 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.63 | 12.25 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 151.00 | 12.91 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 137.03 | 10.02 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.68 | 7.06 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 77.56 | 3.25 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 79.37 | 3.95 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.62 | 4.35 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 72.07 | 7.56 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 70.16 | 6.00 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.87 | 6.16 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 98.05 | 7.81 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.49 | 9.27 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.80 | 14.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.39 | 7.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 70.16 | 3.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 151.00 | 14.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.69 | 10.75 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.07 | 8.28 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.53 | 5.75 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.45 | 2.62 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.94 | 3.25 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.32 | 3.57 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.61 | 6.28 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.05 | 4.93 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.16 | 5.10 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.31 | 6.49 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.47 | 7.71 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.82 | 12.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.23 | 6.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.05 | 2.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.69 | 12.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.69 | 10.75 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.07 | 8.28 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.53 | 5.75 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.45 | 2.62 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.94 | 3.25 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.32 | 3.57 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.61 | 6.28 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 59.05 | 4.93 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.16 | 5.10 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.31 | 6.49 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.47 | 7.71 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.82 | 12.17 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.23 | 6.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 59.05 | 2.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.69 | 12.17 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 151.08 | 12.82 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 137.11 | 9.93 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.75 | 6.97 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 77.64 | 3.19 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 79.46 | 3.90 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.70 | 4.29 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 72.14 | 7.48 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 70.22 | 5.92 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.94 | 6.09 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 98.12 | 7.72 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.57 | 9.18 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.88 | 14.49 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.47 | 7.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 70.22 | 3.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 151.08 | 14.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.69 | 10.72 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.02 | 8.29 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.47 | 5.77 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.34 | 2.66 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.82 | 3.28 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.19 | 3.63 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.53 | 6.33 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.98 | 4.96 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.07 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.28 | 6.48 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.45 | 7.69 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.82 | 12.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.17 | 6.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.98 | 2.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.69 | 12.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 126.69 | 10.72 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 115.02 | 8.29 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 85.47 | 5.77 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 65.34 | 2.66 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 66.82 | 3.28 | 0.00 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 66.19 | 3.63 | 0.00 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 60.53 | 6.33 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 58.98 | 4.96 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 67.07 | 5.14 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 82.28 | 6.48 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 104.45 | 7.69 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.82 | 12.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 85.17 | 6.43 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 58.98 | 2.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 126.69 | 12.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 151.07 | 12.79 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 137.06 | 9.95 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 101.67 | 7.01 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 77.50 | 3.24 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 79.31 | 3.94 | 0.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 78.55 | 4.35 | 0.00 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 72.04 | 7.54 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 70.14 | 5.96 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 79.84 | 6.14 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 98.08 | 7.72 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 124.55 | 9.17 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.88 | 14.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 101.39 | 7.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 70.14 | 3.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 151.07 | 14.45 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 125.92 | 10.99 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.03 | 8.72 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 84.36 | 6.27 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 63.84 | 3.15 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 65.32 | 3.71 | 8.17 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 64.69 | 4.18 | 0.67 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 59.39 | 6.98 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 57.89 | 5.53 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 65.91 | 5.75 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 81.46 | 6.87 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 103.64 | 8.02 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.13 | 12.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.08 | 6.88 | 8.83 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 57.89 | 3.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 125.92 | 12.38 | 8.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 65.04 | 27.13 | 37.90 | 125.92 | 10.99 | 0.00 | 0.00 | 0.00 |
February | 55.23 | 18.01 | 37.22 | 114.03 | 8.72 | 0.00 | 0.00 | 0.00 |
March | 37.69 | 5.06 | 32.63 | 84.36 | 6.27 | 0.00 | 0.00 | 0.00 |
April | 28.10 | 0.01 | 28.09 | 63.84 | 3.15 | 0.00 | 0.00 | 0.00 |
May | 28.12 | 0.00 | 28.12 | 65.32 | 3.71 | 8.17 | 0.00 | 0.00 |
June | 28.02 | 0.00 | 28.02 | 64.69 | 4.18 | 0.67 | 0.00 | 0.00 |
July | 28.86 | 0.00 | 28.86 | 59.39 | 6.98 | 0.00 | 0.00 | 0.00 |
August | 28.10 | 0.04 | 28.05 | 57.89 | 5.53 | 0.00 | 0.00 | 0.00 |
September | 31.10 | 1.02 | 30.09 | 65.91 | 5.75 | 0.00 | 0.00 | 0.00 |
October | 40.69 | 6.49 | 34.21 | 81.46 | 6.87 | 0.00 | 0.00 | 0.00 |
November | 52.92 | 16.14 | 36.77 | 103.64 | 8.02 | 0.00 | 0.00 | 0.00 |
December | 65.00 | 27.66 | 37.35 | 124.13 | 12.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 40.68 | 8.43 | 32.25 | 84.08 | 6.88 | 8.83 | 0.00 | 0.00 |
Minimum of Months | 28.02 | 0.00 | 28.02 | 57.89 | 3.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 65.04 | 27.66 | 37.90 | 125.92 | 12.38 | 8.17 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 77.76 | 32.44 | 45.32 | 150.15 | 13.12 | 0.00 | 0.00 | 0.00 |
February | 66.03 | 21.53 | 44.50 | 135.86 | 10.47 | 0.00 | 0.00 | 0.00 |
March | 45.06 | 6.05 | 39.01 | 100.36 | 7.60 | 0.00 | 0.00 | 0.00 |
April | 33.59 | 0.02 | 33.58 | 75.74 | 3.85 | 0.00 | 0.00 | 0.00 |
May | 33.62 | 0.00 | 33.62 | 77.53 | 4.47 | 10.00 | 0.00 | 0.00 |
June | 33.50 | 0.00 | 33.50 | 76.76 | 5.02 | 0.67 | 0.00 | 0.00 |
July | 34.51 | 0.00 | 34.51 | 70.67 | 8.32 | 0.00 | 0.00 | 0.00 |
August | 33.59 | 0.05 | 33.54 | 68.84 | 6.64 | 0.00 | 0.00 | 0.00 |
September | 37.19 | 1.21 | 35.97 | 78.45 | 6.86 | 0.00 | 0.00 | 0.00 |
October | 48.65 | 7.76 | 40.90 | 97.10 | 8.18 | 0.00 | 0.00 | 0.00 |
November | 63.27 | 19.30 | 43.96 | 123.57 | 9.56 | 0.00 | 0.00 | 0.00 |
December | 77.72 | 33.07 | 44.65 | 148.05 | 14.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 48.64 | 10.08 | 38.56 | 100.09 | 8.24 | 10.67 | 0.00 | 0.00 |
Minimum of Months | 33.50 | 0.00 | 33.50 | 68.84 | 3.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 77.76 | 33.07 | 45.32 | 150.15 | 14.74 | 10.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339633E+09 | 25844503.06 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278593E+09 | 17719669.39 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.229007E+09 | 13656648.25 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.171698E+09 | 6311158.65 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.182009E+09 | 7885792.95 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.173547E+09 | 8326307.38 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.164277E+09 | 15020280.66 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158233E+09 | 11901520.32 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.175119E+09 | 11656618.34 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.221133E+09 | 15093607.90 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.271012E+09 | 17842536.17 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334293E+09 | 29770879.75 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.269855E+10 | 0.181030E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158233E+09 | 6311158.65 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339633E+09 | 29770879.75 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339633E+09 | 25844503.06 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278593E+09 | 17719669.39 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.229007E+09 | 13656648.25 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.171698E+09 | 6311158.65 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.182009E+09 | 7885792.95 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.173547E+09 | 8326307.38 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.164277E+09 | 15020280.66 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158233E+09 | 11901520.32 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.175119E+09 | 11656618.34 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.221133E+09 | 15093607.90 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.271012E+09 | 17842536.17 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334293E+09 | 29770879.75 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.269855E+10 | 0.181030E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158233E+09 | 6311158.65 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339633E+09 | 29770879.75 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339633E+09 | 25844503.06 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278593E+09 | 17719669.39 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.229007E+09 | 13656648.25 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.171698E+09 | 6311158.65 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.182009E+09 | 7885792.95 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.173547E+09 | 8326307.38 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.164277E+09 | 15020280.66 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158233E+09 | 11901520.32 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.175119E+09 | 11656618.34 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.221133E+09 | 15093607.90 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.271012E+09 | 17842536.17 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334293E+09 | 29770879.75 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.269855E+10 | 0.181030E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158233E+09 | 6311158.65 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339633E+09 | 29770879.75 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339633E+09 | 25844503.06 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278593E+09 | 17719669.39 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.229007E+09 | 13656648.25 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.171698E+09 | 6311158.65 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.182009E+09 | 7885792.95 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.173547E+09 | 8326307.38 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.164277E+09 | 15020280.66 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158233E+09 | 11901520.32 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.175119E+09 | 11656618.34 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.221133E+09 | 15093607.90 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.271012E+09 | 17842536.17 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334293E+09 | 29770879.75 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.269855E+10 | 0.181030E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158233E+09 | 6311158.65 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339633E+09 | 29770879.75 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209406E+09 | 87366389.65 | 0.122039E+09 | 0.407080E+09 | 31122364.81 |
February | 0.160609E+09 | 52364500.94 | 0.108244E+09 | 0.333631E+09 | 21470861.26 |
March | 0.121350E+09 | 16297375.08 | 0.105052E+09 | 0.273743E+09 | 16696058.86 |
April | 87553716.91 | 39303.53 | 87514413.39 | 0.204581E+09 | 7727318.23 |
May | 90533949.20 | 0.00 | 90533949.20 | 0.217022E+09 | 9530946.63 |
June | 87298096.43 | 0.00 | 87298096.43 | 0.206907E+09 | 10060002.11 |
July | 92927874.03 | 0.00 | 92927874.03 | 0.196395E+09 | 18051298.55 |
August | 90465989.17 | 139817.09 | 90326172.08 | 0.189033E+09 | 14399303.15 |
September | 96921591.97 | 3165530.57 | 93756061.40 | 0.209423E+09 | 14035011.75 |
October | 0.131028E+09 | 20891455.15 | 0.110137E+09 | 0.264882E+09 | 18137434.20 |
November | 0.164884E+09 | 50303904.00 | 0.114580E+09 | 0.324755E+09 | 21452058.66 |
December | 0.209298E+09 | 89047898.11 | 0.120250E+09 | 0.400758E+09 | 35751566.40 |
Annual Sum or Average | 0.154228E+10 | 0.319616E+09 | 0.122266E+10 | 0.322821E+10 | 0.218434E+09 |
Minimum of Months | 87298096.43 | 0.00 | 87298096.43 | 0.189033E+09 | 7727318.23 |
Maximum of Months | 0.209406E+09 | 89047898.11 | 0.122039E+09 | 0.407080E+09 | 35751566.40 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209406E+09 | 87366389.65 | 0.122039E+09 | 0.407080E+09 | 31122364.81 |
February | 0.160609E+09 | 52364500.94 | 0.108244E+09 | 0.333631E+09 | 21470861.26 |
March | 0.121350E+09 | 16297375.08 | 0.105052E+09 | 0.273743E+09 | 16696058.86 |
April | 87553716.91 | 39303.53 | 87514413.39 | 0.204581E+09 | 7727318.23 |
May | 90533949.20 | 0.00 | 90533949.20 | 0.217022E+09 | 9530946.63 |
June | 87298096.43 | 0.00 | 87298096.43 | 0.206907E+09 | 10060002.11 |
July | 92927874.03 | 0.00 | 92927874.03 | 0.196395E+09 | 18051298.55 |
August | 90465989.17 | 139817.09 | 90326172.08 | 0.189033E+09 | 14399303.15 |
September | 96921591.97 | 3165530.57 | 93756061.40 | 0.209423E+09 | 14035011.75 |
October | 0.131028E+09 | 20891455.15 | 0.110137E+09 | 0.264882E+09 | 18137434.20 |
November | 0.164884E+09 | 50303904.00 | 0.114580E+09 | 0.324755E+09 | 21452058.66 |
December | 0.209298E+09 | 89047898.11 | 0.120250E+09 | 0.400758E+09 | 35751566.40 |
Annual Sum or Average | 0.154228E+10 | 0.319616E+09 | 0.122266E+10 | 0.322821E+10 | 0.218434E+09 |
Minimum of Months | 87298096.43 | 0.00 | 87298096.43 | 0.189033E+09 | 7727318.23 |
Maximum of Months | 0.209406E+09 | 89047898.11 | 0.122039E+09 | 0.407080E+09 | 35751566.40 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.340318E+09 | 25765191.01 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.279673E+09 | 17501376.14 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.230778E+09 | 13322107.27 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.173946E+09 | 6045826.73 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184094E+09 | 7730065.84 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.175746E+09 | 8068361.35 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.165744E+09 | 14755799.37 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.159789E+09 | 11658631.39 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.176582E+09 | 11423774.43 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.222042E+09 | 15044529.39 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.271859E+09 | 17784304.50 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334859E+09 | 29733325.57 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.271543E+10 | 0.178833E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.159789E+09 | 6045826.73 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.340318E+09 | 29733325.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.340318E+09 | 25765191.01 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.279673E+09 | 17501376.14 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.230778E+09 | 13322107.27 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.173946E+09 | 6045826.73 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.184094E+09 | 7730065.84 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.175746E+09 | 8068361.35 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.165744E+09 | 14755799.37 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.159789E+09 | 11658631.39 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.176582E+09 | 11423774.43 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.222042E+09 | 15044529.39 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.271859E+09 | 17784304.50 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334859E+09 | 29733325.57 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.271543E+10 | 0.178833E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.159789E+09 | 6045826.73 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.340318E+09 | 29733325.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209406E+09 | 87366389.65 | 0.122039E+09 | 0.407957E+09 | 31017554.62 |
February | 0.160609E+09 | 52364500.94 | 0.108244E+09 | 0.334940E+09 | 21195542.93 |
March | 0.121350E+09 | 16297375.08 | 0.105052E+09 | 0.275828E+09 | 16277332.94 |
April | 87553716.91 | 39303.53 | 87514413.39 | 0.207234E+09 | 7422685.84 |
May | 90533949.20 | 0.00 | 90533949.20 | 0.219487E+09 | 9345208.16 |
June | 87298096.43 | 0.00 | 87298096.43 | 0.209505E+09 | 9750759.95 |
July | 92927874.03 | 0.00 | 92927874.03 | 0.198157E+09 | 17731256.02 |
August | 90465989.17 | 139817.09 | 90326172.08 | 0.190889E+09 | 14110334.54 |
September | 96921591.97 | 3165530.57 | 93756061.40 | 0.211188E+09 | 13757430.11 |
October | 0.131028E+09 | 20891455.15 | 0.110137E+09 | 0.266010E+09 | 18074418.76 |
November | 0.164884E+09 | 50303904.00 | 0.114580E+09 | 0.325827E+09 | 21381041.88 |
December | 0.209298E+09 | 89047898.11 | 0.120250E+09 | 0.401496E+09 | 35691663.51 |
Annual Sum or Average | 0.154228E+10 | 0.319616E+09 | 0.122266E+10 | 0.324852E+10 | 0.215755E+09 |
Minimum of Months | 87298096.43 | 0.00 | 87298096.43 | 0.190889E+09 | 7422685.84 |
Maximum of Months | 0.209406E+09 | 89047898.11 | 0.122039E+09 | 0.407957E+09 | 35691663.51 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339185E+09 | 32717370.85 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278315E+09 | 23676757.81 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228671E+09 | 19525059.43 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168186E+09 | 9380964.23 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.178093E+09 | 11299891.70 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170528E+09 | 11898762.84 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162032E+09 | 20275479.34 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157591E+09 | 17211335.07 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173387E+09 | 16521575.34 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220057E+09 | 21144679.54 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270550E+09 | 23657621.51 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334148E+09 | 36541654.13 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268074E+10 | 0.243851E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157591E+09 | 9380964.23 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339185E+09 | 36541654.13 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339185E+09 | 32717370.85 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278315E+09 | 23676757.81 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228671E+09 | 19525059.43 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168186E+09 | 9380964.23 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.178093E+09 | 11299891.70 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170528E+09 | 11898762.84 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162032E+09 | 20275479.34 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157591E+09 | 17211335.07 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173387E+09 | 16521575.34 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220057E+09 | 21144679.54 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270550E+09 | 23657621.51 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334148E+09 | 36541654.13 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268074E+10 | 0.243851E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157591E+09 | 9380964.23 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339185E+09 | 36541654.13 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.404428E+09 | 38980616.53 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.331581E+09 | 28341649.62 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.272038E+09 | 23578032.24 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.199560E+09 | 11419122.57 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.211391E+09 | 13545045.66 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.202387E+09 | 14259895.62 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.192807E+09 | 24131056.46 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.187373E+09 | 20594557.36 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.206367E+09 | 19689028.96 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.262268E+09 | 25128599.68 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322543E+09 | 28151433.70 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398486E+09 | 43459474.88 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.319123E+10 | 0.291279E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.187373E+09 | 11419122.57 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.404428E+09 | 43459474.88 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.338988E+09 | 33297053.70 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278123E+09 | 24224898.12 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228499E+09 | 20180143.47 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.167879E+09 | 10002356.71 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.177615E+09 | 11878165.57 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170200E+09 | 12567695.45 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.161771E+09 | 20970166.81 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157418E+09 | 17779975.42 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173177E+09 | 17126723.30 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.219880E+09 | 21742852.06 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270392E+09 | 24131814.82 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.333997E+09 | 37003450.03 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.267794E+10 | 0.250905E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157418E+09 | 10002356.71 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.338988E+09 | 37003450.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.338988E+09 | 33297053.70 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278123E+09 | 24224898.12 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228499E+09 | 20180143.47 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.167879E+09 | 10002356.71 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.177615E+09 | 11878165.57 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170200E+09 | 12567695.45 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.161771E+09 | 20970166.81 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157418E+09 | 17779975.42 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173177E+09 | 17126723.30 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.219880E+09 | 21742852.06 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270392E+09 | 24131814.82 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.333997E+09 | 37003450.03 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.267794E+10 | 0.250905E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157418E+09 | 10002356.71 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.338988E+09 | 37003450.03 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.404191E+09 | 39664586.03 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.331352E+09 | 28990036.85 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.271833E+09 | 24350392.51 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.199201E+09 | 12158925.20 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.210829E+09 | 14233236.11 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.202003E+09 | 15053936.34 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.192496E+09 | 24952793.75 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.187168E+09 | 21265807.03 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.206117E+09 | 20404557.25 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.262056E+09 | 25835890.99 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322353E+09 | 28712447.38 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398305E+09 | 44003659.62 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.318791E+10 | 0.299626E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.187168E+09 | 12158925.20 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.404191E+09 | 44003659.62 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339299E+09 | 32572660.72 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278402E+09 | 23566847.43 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228778E+09 | 19387948.83 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168233E+09 | 9372472.77 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.178002E+09 | 11321745.68 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170556E+09 | 11972681.64 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162053E+09 | 20269132.34 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157728E+09 | 17012880.20 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173474E+09 | 16433182.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220175E+09 | 20995442.06 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270696E+09 | 23440408.59 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334325E+09 | 36281050.96 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268172E+10 | 0.242626E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157728E+09 | 9372472.77 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339299E+09 | 36281050.96 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339299E+09 | 32572660.72 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278402E+09 | 23566847.43 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228778E+09 | 19387948.83 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168233E+09 | 9372472.77 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.178002E+09 | 11321745.68 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170556E+09 | 11972681.64 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162053E+09 | 20269132.34 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157728E+09 | 17012880.20 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173474E+09 | 16433182.82 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220175E+09 | 20995442.06 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270696E+09 | 23440408.59 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334325E+09 | 36281050.96 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268172E+10 | 0.242626E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157728E+09 | 9372472.77 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339299E+09 | 36281050.96 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.404563E+09 | 38815663.70 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.331684E+09 | 28216188.96 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.272165E+09 | 23422114.86 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.199615E+09 | 11413038.06 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.211284E+09 | 13577088.44 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.202421E+09 | 14352510.79 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.192831E+09 | 24129570.24 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.187537E+09 | 20366828.34 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.206471E+09 | 19589896.25 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.262409E+09 | 24958026.65 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322718E+09 | 27900343.25 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398697E+09 | 43156887.80 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.319240E+10 | 0.289898E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.187537E+09 | 11413038.06 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.404563E+09 | 43156887.80 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.338722E+09 | 29979204.02 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.277662E+09 | 21168718.06 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228071E+09 | 16732436.89 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168092E+09 | 7696598.19 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.177689E+09 | 9551611.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170329E+09 | 10203715.72 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.161394E+09 | 17923056.55 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157139E+09 | 14399252.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173125E+09 | 14263147.26 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.219737E+09 | 18536590.62 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270128E+09 | 21085180.24 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.333771E+09 | 33764547.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.267586E+10 | 0.215304E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157139E+09 | 7696598.19 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.338722E+09 | 33764547.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.338722E+09 | 29979204.02 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.277662E+09 | 21168718.06 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228071E+09 | 16732436.89 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168092E+09 | 7696598.19 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.177689E+09 | 9551611.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170329E+09 | 10203715.72 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.161394E+09 | 17923056.55 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157139E+09 | 14399252.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173125E+09 | 14263147.26 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.219737E+09 | 18536590.62 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270128E+09 | 21085180.24 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.333771E+09 | 33764547.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.267586E+10 | 0.215304E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157139E+09 | 7696598.19 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.338722E+09 | 33764547.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.338722E+09 | 29979204.02 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.277662E+09 | 21168718.06 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228071E+09 | 16732436.89 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168092E+09 | 7696598.19 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.177689E+09 | 9551611.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170329E+09 | 10203715.72 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.161394E+09 | 17923056.55 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157139E+09 | 14399252.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173125E+09 | 14263147.26 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.219737E+09 | 18536590.62 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270128E+09 | 21085180.24 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.333771E+09 | 33764547.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.267586E+10 | 0.215304E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157139E+09 | 7696598.19 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.338722E+09 | 33764547.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.338722E+09 | 29979204.02 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.277662E+09 | 21168718.06 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228071E+09 | 16732436.89 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.168092E+09 | 7696598.19 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.177689E+09 | 9551611.12 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.170329E+09 | 10203715.72 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.161394E+09 | 17923056.55 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157139E+09 | 14399252.05 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173125E+09 | 14263147.26 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.219737E+09 | 18536590.62 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270128E+09 | 21085180.24 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.333771E+09 | 33764547.48 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.267586E+10 | 0.215304E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157139E+09 | 7696598.19 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.338722E+09 | 33764547.48 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.403861E+09 | 35747969.71 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.330816E+09 | 25371458.24 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.271333E+09 | 20243249.68 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.199456E+09 | 9362144.16 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.210949E+09 | 11451361.20 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.202169E+09 | 12223414.86 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.192073E+09 | 21350084.97 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.186875E+09 | 17268083.21 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.206073E+09 | 17008542.05 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.261899E+09 | 22048755.72 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322043E+09 | 25110993.53 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398033E+09 | 40186361.43 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.318558E+10 | 0.257372E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.186875E+09 | 9362144.16 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.403861E+09 | 40186361.43 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.403861E+09 | 35747969.71 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.330816E+09 | 25371458.24 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.271333E+09 | 20243249.68 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.199456E+09 | 9362144.16 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.210949E+09 | 11451361.20 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.202169E+09 | 12223414.86 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.192073E+09 | 21350084.97 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.186875E+09 | 17268083.21 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.206073E+09 | 17008542.05 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.261899E+09 | 22048755.72 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322043E+09 | 25110993.53 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398033E+09 | 40186361.43 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.318558E+10 | 0.257372E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.186875E+09 | 9362144.16 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.403861E+09 | 40186361.43 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339159E+09 | 28987312.17 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278216E+09 | 20196524.39 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228919E+09 | 15579410.35 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.169474E+09 | 6910409.90 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.179103E+09 | 8817653.85 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.171716E+09 | 9398256.28 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162195E+09 | 16977011.57 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158007E+09 | 13382008.93 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173921E+09 | 13384694.31 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220308E+09 | 17580382.39 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270624E+09 | 20172067.73 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334146E+09 | 32810046.46 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268579E+10 | 0.204196E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158007E+09 | 6910409.90 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339159E+09 | 32810046.46 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339159E+09 | 28987312.17 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278216E+09 | 20196524.39 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228919E+09 | 15579410.35 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.169474E+09 | 6910409.90 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.179103E+09 | 8817653.85 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.171716E+09 | 9398256.28 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162195E+09 | 16977011.57 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158007E+09 | 13382008.93 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173921E+09 | 13384694.31 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220308E+09 | 17580382.39 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270624E+09 | 20172067.73 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334146E+09 | 32810046.46 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268579E+10 | 0.204196E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158007E+09 | 6910409.90 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339159E+09 | 32810046.46 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.404444E+09 | 34581813.00 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.331508E+09 | 24233914.94 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.272333E+09 | 18900836.73 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.201040E+09 | 8432718.81 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.212591E+09 | 10586046.67 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.203777E+09 | 11273955.82 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.193033E+09 | 20235522.42 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.187903E+09 | 16078749.02 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.207030E+09 | 15974161.58 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.262619E+09 | 20919285.83 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322689E+09 | 24034833.93 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398548E+09 | 39059170.49 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.319751E+10 | 0.244311E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.187903E+09 | 8432718.81 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.404444E+09 | 39059170.49 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339338E+09 | 28779614.40 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278367E+09 | 20024074.43 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.229076E+09 | 15391637.32 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.169656E+09 | 6781860.53 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.179300E+09 | 8694996.57 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.171901E+09 | 9264430.46 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162346E+09 | 16807546.84 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158158E+09 | 13203713.22 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.174070E+09 | 13223741.91 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220471E+09 | 17378912.26 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270791E+09 | 19978784.54 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334320E+09 | 32596860.13 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268779E+10 | 0.202126E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158158E+09 | 6781860.53 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339338E+09 | 32596860.13 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339338E+09 | 28779614.40 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278367E+09 | 20024074.43 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.229076E+09 | 15391637.32 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.169656E+09 | 6781860.53 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.179300E+09 | 8694996.57 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.171901E+09 | 9264430.46 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162346E+09 | 16807546.84 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.158158E+09 | 13203713.22 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.174070E+09 | 13223741.91 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220471E+09 | 17378912.26 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270791E+09 | 19978784.54 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334320E+09 | 32596860.13 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268779E+10 | 0.202126E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.158158E+09 | 6781860.53 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339338E+09 | 32596860.13 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.404657E+09 | 34335636.51 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.331688E+09 | 24028655.18 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.272519E+09 | 18678651.09 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.201256E+09 | 8278735.25 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.212825E+09 | 10438809.67 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.203998E+09 | 11114018.83 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.193213E+09 | 20034361.83 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.188084E+09 | 15866801.51 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.207208E+09 | 15782496.75 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.262813E+09 | 20679388.84 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322889E+09 | 23805718.35 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398756E+09 | 38806997.57 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.319991E+10 | 0.241850E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.188084E+09 | 8278735.25 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.404657E+09 | 38806997.57 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339316E+09 | 28716904.63 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278266E+09 | 20045580.30 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228912E+09 | 15457768.37 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.169349E+09 | 6886131.48 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.178959E+09 | 8787924.42 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.171575E+09 | 9397644.61 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162122E+09 | 16949492.10 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157966E+09 | 13289395.08 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173852E+09 | 13331122.05 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220379E+09 | 17364839.83 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270739E+09 | 19938780.69 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334328E+09 | 32511836.81 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268576E+10 | 0.202677E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157966E+09 | 6886131.48 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339316E+09 | 32511836.81 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.339316E+09 | 28716904.63 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.278266E+09 | 20045580.30 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.228912E+09 | 15457768.37 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.169349E+09 | 6886131.48 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.178959E+09 | 8787924.42 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.171575E+09 | 9397644.61 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.162122E+09 | 16949492.10 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.157966E+09 | 13289395.08 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.173852E+09 | 13331122.05 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.220379E+09 | 17364839.83 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.270739E+09 | 19938780.69 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.334328E+09 | 32511836.81 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.268576E+10 | 0.202677E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.157966E+09 | 6886131.48 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.339316E+09 | 32511836.81 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.404628E+09 | 34268695.72 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.331565E+09 | 24061508.33 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.272322E+09 | 18764144.18 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.200890E+09 | 8408456.86 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.212418E+09 | 10555797.98 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.203609E+09 | 11279363.59 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.192944E+09 | 20207856.15 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.187853E+09 | 15975118.05 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.206944E+09 | 15917313.36 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.262702E+09 | 20670495.54 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.322824E+09 | 23765330.44 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.398762E+09 | 38713198.23 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.319746E+10 | 0.242587E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.187853E+09 | 8408456.86 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.404628E+09 | 38713198.23 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.337269E+09 | 29445270.40 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.275856E+09 | 21100335.97 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.225960E+09 | 16789824.11 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.165484E+09 | 8176623.81 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.174959E+09 | 9947430.60 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.167665E+09 | 10845255.15 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.159065E+09 | 18698201.29 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.155051E+09 | 14801415.82 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.170833E+09 | 14899129.90 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.218188E+09 | 18410836.32 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.268639E+09 | 20793549.17 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.332482E+09 | 33158343.99 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.265145E+10 | 0.217066E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.155051E+09 | 8176623.81 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.337269E+09 | 33158343.99 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.174192E+09 | 72674876.28 | 0.101517E+09 | 0.337269E+09 | 29445270.40 |
February | 0.133601E+09 | 43558897.68 | 90041949.64 | 0.275856E+09 | 21100335.97 |
March | 0.100944E+09 | 13556811.98 | 87386884.58 | 0.225960E+09 | 16789824.11 |
April | 72830702.63 | 32694.25 | 72798008.38 | 0.165484E+09 | 8176623.81 |
May | 75309779.70 | 0.00 | 75309779.70 | 0.174959E+09 | 9947430.60 |
June | 72618067.23 | 0.00 | 72618067.23 | 0.167665E+09 | 10845255.15 |
July | 77301142.63 | 0.00 | 77301142.63 | 0.159065E+09 | 18698201.29 |
August | 75253247.81 | 116305.48 | 75136942.33 | 0.155051E+09 | 14801415.82 |
September | 80623277.82 | 2633215.63 | 77990062.20 | 0.170833E+09 | 14899129.90 |
October | 0.108995E+09 | 17378352.53 | 91616393.78 | 0.218188E+09 | 18410836.32 |
November | 0.137157E+09 | 41844810.28 | 95312322.01 | 0.268639E+09 | 20793549.17 |
December | 0.174103E+09 | 74073622.63 | 0.100029E+09 | 0.332482E+09 | 33158343.99 |
Annual Sum or Average | 0.128293E+10 | 0.265870E+09 | 0.101706E+10 | 0.265145E+10 | 0.217066E+09 |
Minimum of Months | 72618067.23 | 0.00 | 72618067.23 | 0.155051E+09 | 8176623.81 |
Maximum of Months | 0.174192E+09 | 74073622.63 | 0.101517E+09 | 0.337269E+09 | 33158343.99 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.208261E+09 | 86888977.69 | 0.121372E+09 | 0.402166E+09 | 35144050.08 |
February | 0.159731E+09 | 52078356.13 | 0.107653E+09 | 0.328677E+09 | 25324677.73 |
March | 0.120687E+09 | 16208318.39 | 0.104478E+09 | 0.268797E+09 | 20355786.07 |
April | 87075281.30 | 39088.75 | 87036192.55 | 0.196306E+09 | 9975765.44 |
May | 90039228.17 | 0.00 | 90039228.17 | 0.207668E+09 | 11960253.44 |
June | 86821057.65 | 0.00 | 86821057.65 | 0.198956E+09 | 13015585.20 |
July | 92420071.44 | 0.00 | 92420071.44 | 0.189287E+09 | 22287016.71 |
August | 89971639.51 | 139053.06 | 89832586.44 | 0.184368E+09 | 17773389.68 |
September | 96391965.79 | 3148232.59 | 93243733.19 | 0.203330E+09 | 17785438.42 |
October | 0.130312E+09 | 20777294.20 | 0.109535E+09 | 0.260069E+09 | 21918066.96 |
November | 0.163983E+09 | 50029019.28 | 0.113954E+09 | 0.320293E+09 | 24781957.90 |
December | 0.208155E+09 | 88561297.57 | 0.119593E+09 | 0.396537E+09 | 39489413.24 |
Annual Sum or Average | 0.153385E+10 | 0.317870E+09 | 0.121598E+10 | 0.315645E+10 | 0.259811E+09 |
Minimum of Months | 86821057.65 | 0.00 | 86821057.65 | 0.184368E+09 | 9975765.44 |
Maximum of Months | 0.208261E+09 | 88561297.57 | 0.121372E+09 | 0.402166E+09 | 39489413.24 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 811.19 | 61.83 | 416.51 | 173.77 | 242.74 | 0.00 | 0.00 |
February | 736.45 | 47.04 | 353.68 | 115.31 | 238.37 | 0.00 | 0.00 |
March | 546.41 | 32.86 | 241.37 | 32.42 | 208.95 | 0.00 | 0.00 |
April | 422.82 | 15.70 | 179.95 | 0.08 | 179.87 | 0.00 | 0.00 |
May | 433.87 | 18.89 | 180.07 | 0.00 | 180.07 | 0.00 | 0.00 |
June | 427.47 | 20.61 | 179.42 | 0.00 | 179.42 | 0.00 | 0.00 |
July | 391.99 | 35.91 | 184.83 | 0.00 | 184.83 | 0.00 | 0.00 |
August | 377.46 | 28.53 | 179.94 | 0.28 | 179.66 | 0.00 | 0.00 |
September | 431.84 | 28.82 | 199.20 | 6.51 | 192.70 | 0.00 | 0.00 |
October | 528.04 | 36.08 | 260.62 | 41.55 | 219.06 | 0.00 | 0.00 |
November | 668.81 | 44.09 | 338.89 | 103.39 | 235.50 | 0.00 | 0.00 |
December | 798.49 | 71.15 | 416.30 | 177.12 | 239.18 | 0.00 | 0.00 |
Annual Sum or Average | 547.01 | 36.81 | 260.54 | 53.99 | 206.54 | 0.00 | 0.00 |
Minimum of Months | 377.46 | 15.70 | 179.42 | 0.00 | 179.42 | 0.00 | 0.00 |
Maximum of Months | 811.19 | 71.15 | 416.51 | 177.12 | 242.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 406.43 | 30.82 | 208.25 | 86.89 | 121.37 | 0.00 | 0.00 |
February | 369.66 | 23.23 | 176.84 | 57.66 | 119.18 | 0.00 | 0.00 |
March | 275.31 | 16.02 | 120.68 | 16.21 | 104.48 | 0.00 | 0.00 |
April | 214.17 | 7.53 | 89.97 | 0.04 | 89.93 | 0.00 | 0.00 |
May | 219.41 | 9.26 | 90.04 | 0.00 | 90.04 | 0.00 | 0.00 |
June | 216.43 | 9.99 | 89.71 | 0.00 | 89.71 | 0.00 | 0.00 |
July | 197.75 | 17.64 | 92.42 | 0.00 | 92.42 | 0.00 | 0.00 |
August | 190.59 | 13.97 | 89.97 | 0.14 | 89.83 | 0.00 | 0.00 |
September | 217.73 | 14.12 | 99.60 | 3.25 | 96.35 | 0.00 | 0.00 |
October | 265.12 | 17.98 | 130.31 | 20.78 | 109.53 | 0.00 | 0.00 |
November | 335.47 | 21.97 | 169.44 | 51.70 | 117.75 | 0.00 | 0.00 |
December | 399.94 | 35.53 | 208.15 | 88.56 | 119.59 | 0.00 | 0.00 |
Annual Sum or Average | 275.22 | 18.18 | 130.27 | 27.00 | 103.27 | 0.00 | 0.00 |
Minimum of Months | 190.59 | 7.53 | 89.71 | 0.00 | 89.71 | 0.00 | 0.00 |
Maximum of Months | 406.43 | 35.53 | 208.25 | 88.56 | 121.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.27 | 38.98 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 367.15 | 31.29 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 272.32 | 23.38 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 206.76 | 11.64 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 211.91 | 13.49 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 209.66 | 14.68 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 192.98 | 24.15 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 187.63 | 20.54 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 213.40 | 20.34 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 262.24 | 25.17 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 333.20 | 29.12 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 398.29 | 43.51 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 271.20 | 24.70 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 187.63 | 11.64 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 404.27 | 43.51 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.03 | 39.67 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 366.90 | 32.01 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 272.11 | 24.16 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 206.39 | 12.41 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 211.34 | 14.18 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 209.26 | 15.50 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 192.67 | 24.97 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 187.43 | 21.22 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 213.14 | 21.09 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 262.03 | 25.88 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 333.00 | 29.70 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 398.11 | 44.06 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 270.92 | 25.41 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 187.43 | 12.41 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 404.03 | 44.06 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.41 | 38.81 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 367.26 | 31.15 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 272.45 | 23.22 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 206.82 | 11.63 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 211.80 | 13.52 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 209.70 | 14.77 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 193.00 | 24.14 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 187.80 | 20.31 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 213.51 | 20.24 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 262.38 | 25.00 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 333.38 | 28.85 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 398.50 | 43.20 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 271.30 | 24.58 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 187.80 | 11.63 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 404.41 | 43.20 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 807.43 | 71.46 | 415.65 | 173.42 | 242.24 | 0.00 | 0.00 |
February | 732.59 | 55.97 | 352.95 | 115.08 | 237.88 | 0.00 | 0.00 |
March | 543.21 | 40.10 | 240.87 | 32.35 | 208.52 | 0.00 | 0.00 |
April | 413.30 | 19.10 | 179.58 | 0.08 | 179.50 | 0.00 | 0.00 |
May | 422.88 | 22.81 | 179.70 | 0.00 | 179.70 | 0.00 | 0.00 |
June | 418.85 | 25.18 | 179.06 | 0.00 | 179.06 | 0.00 | 0.00 |
July | 384.45 | 42.71 | 184.46 | 0.00 | 184.46 | 0.00 | 0.00 |
August | 374.22 | 34.40 | 179.57 | 0.28 | 179.29 | 0.00 | 0.00 |
September | 426.18 | 35.13 | 198.80 | 6.49 | 192.30 | 0.00 | 0.00 |
October | 523.73 | 44.15 | 260.08 | 41.47 | 218.61 | 0.00 | 0.00 |
November | 665.35 | 51.91 | 338.19 | 103.18 | 235.01 | 0.00 | 0.00 |
December | 795.68 | 80.43 | 415.44 | 176.75 | 238.69 | 0.00 | 0.00 |
Annual Sum or Average | 541.43 | 43.63 | 260.00 | 53.88 | 206.12 | 0.00 | 0.00 |
Minimum of Months | 374.22 | 19.10 | 179.06 | 0.00 | 179.06 | 0.00 | 0.00 |
Maximum of Months | 807.43 | 80.43 | 415.65 | 176.75 | 242.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.26 | 34.56 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 367.04 | 26.71 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 272.61 | 18.69 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 208.33 | 8.58 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 213.11 | 10.54 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 211.11 | 11.60 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 193.18 | 20.23 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 188.14 | 16.00 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 214.07 | 16.49 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 262.56 | 20.94 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 333.31 | 24.84 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 398.31 | 39.08 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 271.72 | 20.70 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 188.14 | 8.58 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 404.26 | 39.08 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.47 | 34.31 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 367.24 | 26.49 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 272.80 | 18.47 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 208.55 | 8.43 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 213.35 | 10.39 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 211.34 | 11.44 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 193.36 | 20.03 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 188.32 | 15.78 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 214.25 | 16.29 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 262.75 | 20.70 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 333.51 | 24.60 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 398.52 | 38.83 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 271.93 | 20.49 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 188.32 | 8.43 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 404.47 | 38.83 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 404.44 | 34.24 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 367.10 | 26.52 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 272.60 | 18.55 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 208.17 | 8.56 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 212.94 | 10.50 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 210.94 | 11.60 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 193.10 | 20.20 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 188.09 | 15.89 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 213.98 | 16.43 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 262.64 | 20.68 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 333.45 | 24.55 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 398.53 | 38.73 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 271.72 | 20.55 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 188.09 | 8.56 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 404.44 | 38.73 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 401.99 | 35.11 | 207.83 | 86.71 | 121.12 | 0.00 | 0.00 |
February | 363.92 | 27.91 | 176.48 | 57.54 | 118.94 | 0.00 | 0.00 |
March | 269.08 | 20.14 | 120.44 | 16.17 | 104.26 | 0.00 | 0.00 |
April | 203.42 | 10.16 | 89.79 | 0.04 | 89.75 | 0.00 | 0.00 |
May | 208.18 | 11.89 | 89.85 | 0.00 | 89.85 | 0.00 | 0.00 |
June | 206.13 | 13.39 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
July | 189.45 | 22.28 | 92.23 | 0.00 | 92.23 | 0.00 | 0.00 |
August | 184.61 | 17.69 | 89.78 | 0.14 | 89.65 | 0.00 | 0.00 |
September | 210.26 | 18.36 | 99.40 | 3.25 | 96.15 | 0.00 | 0.00 |
October | 260.02 | 21.93 | 130.04 | 20.73 | 109.31 | 0.00 | 0.00 |
November | 330.85 | 25.61 | 169.10 | 51.59 | 117.51 | 0.00 | 0.00 |
December | 396.32 | 39.50 | 207.72 | 88.38 | 119.34 | 0.00 | 0.00 |
Annual Sum or Average | 268.24 | 22.00 | 130.00 | 26.94 | 103.06 | 0.00 | 0.00 |
Minimum of Months | 184.61 | 10.16 | 89.53 | 0.00 | 89.53 | 0.00 | 0.00 |
Maximum of Months | 401.99 | 39.50 | 207.83 | 88.38 | 121.12 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.217269E+10 | 0.165618E+09 | 0.111558E+10 | 0.465432E+09 | 0.650147E+09 | 0.00 | 0.00 |
February | 0.178162E+10 | 0.113806E+09 | 0.855621E+09 | 0.278965E+09 | 0.576656E+09 | 0.00 | 0.00 |
March | 0.146349E+10 | 87998941.83 | 0.646475E+09 | 86821998.08 | 0.559653E+09 | 0.00 | 0.00 |
April | 0.109595E+10 | 40698008.44 | 0.466430E+09 | 209384.06 | 0.466221E+09 | 0.00 | 0.00 |
May | 0.116208E+10 | 50603025.06 | 0.482307E+09 | 0.00 | 0.482307E+09 | 0.00 | 0.00 |
June | 0.110800E+10 | 53423073.65 | 0.465068E+09 | 0.00 | 0.465068E+09 | 0.00 | 0.00 |
July | 0.104989E+10 | 96181200.58 | 0.495060E+09 | 0.00 | 0.495060E+09 | 0.00 | 0.00 |
August | 0.101099E+10 | 76401643.30 | 0.481945E+09 | 744856.10 | 0.481200E+09 | 0.00 | 0.00 |
September | 0.111932E+10 | 74695419.60 | 0.516336E+09 | 16863923.66 | 0.499472E+09 | 0.00 | 0.00 |
October | 0.141429E+10 | 96647227.80 | 0.698036E+09 | 0.111296E+09 | 0.586740E+09 | 0.00 | 0.00 |
November | 0.173355E+10 | 0.114273E+09 | 0.878397E+09 | 0.267987E+09 | 0.610409E+09 | 0.00 | 0.00 |
December | 0.213868E+10 | 0.190580E+09 | 0.111501E+10 | 0.474390E+09 | 0.640618E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.172506E+11 | 0.116093E+10 | 0.821626E+10 | 0.170271E+10 | 0.651355E+10 | 0.00 | 0.00 |
Minimum of Months | 0.101099E+10 | 40698008.44 | 0.465068E+09 | 0.00 | 0.465068E+09 | 0.00 | 0.00 |
Maximum of Months | 0.217269E+10 | 0.190580E+09 | 0.111558E+10 | 0.474390E+09 | 0.650147E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108859E+10 | 82545442.90 | 0.557789E+09 | 0.232716E+09 | 0.325073E+09 | 0.00 | 0.00 |
February | 0.894283E+09 | 56194626.14 | 0.427810E+09 | 0.139482E+09 | 0.288328E+09 | 0.00 | 0.00 |
March | 0.737379E+09 | 42916173.42 | 0.323237E+09 | 43410999.04 | 0.279826E+09 | 0.00 | 0.00 |
April | 0.555126E+09 | 19512865.10 | 0.233215E+09 | 104692.03 | 0.233110E+09 | 0.00 | 0.00 |
May | 0.587673E+09 | 24803413.49 | 0.241154E+09 | 0.00 | 0.241154E+09 | 0.00 | 0.00 |
June | 0.560995E+09 | 25886436.01 | 0.232534E+09 | 0.00 | 0.232534E+09 | 0.00 | 0.00 |
July | 0.529643E+09 | 47241417.98 | 0.247530E+09 | 0.00 | 0.247530E+09 | 0.00 | 0.00 |
August | 0.510466E+09 | 37426871.31 | 0.240972E+09 | 372428.05 | 0.240600E+09 | 0.00 | 0.00 |
September | 0.564352E+09 | 36604433.55 | 0.258168E+09 | 8431961.83 | 0.249736E+09 | 0.00 | 0.00 |
October | 0.710093E+09 | 48162311.76 | 0.349018E+09 | 55648160.21 | 0.293370E+09 | 0.00 | 0.00 |
November | 0.869544E+09 | 56948731.30 | 0.439198E+09 | 0.133994E+09 | 0.305205E+09 | 0.00 | 0.00 |
December | 0.107121E+10 | 95157027.78 | 0.557504E+09 | 0.237195E+09 | 0.320309E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.867936E+10 | 0.573400E+09 | 0.410813E+10 | 0.851355E+09 | 0.325678E+10 | 0.00 | 0.00 |
Minimum of Months | 0.510466E+09 | 19512865.10 | 0.232534E+09 | 0.00 | 0.232534E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108859E+10 | 95157027.78 | 0.557789E+09 | 0.237195E+09 | 0.325073E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108280E+10 | 0.104414E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.888210E+09 | 75693640.53 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.729380E+09 | 62626946.00 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.535930E+09 | 30179741.00 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.567575E+09 | 36143715.39 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.543442E+09 | 38056435.54 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.516870E+09 | 64681809.05 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.502554E+09 | 55016922.39 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.553141E+09 | 52731967.48 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.702381E+09 | 67417355.43 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.863644E+09 | 75466586.32 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106678E+10 | 0.116542E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855271E+10 | 0.778971E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.502554E+09 | 30179741.00 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108280E+10 | 0.116542E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108217E+10 | 0.106257E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.887596E+09 | 77438221.85 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.728830E+09 | 64709369.98 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.534958E+09 | 32162029.45 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.566059E+09 | 37988840.84 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.542403E+09 | 40188703.73 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.516039E+09 | 66892710.22 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.502005E+09 | 56825373.87 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.552471E+09 | 54657679.06 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.701815E+09 | 69321040.16 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.863136E+09 | 76975950.36 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106630E+10 | 0.118010E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.854378E+10 | 0.801427E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.502005E+09 | 32162029.45 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108217E+10 | 0.118010E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108316E+10 | 0.103960E+09 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.888486E+09 | 75348727.94 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.729721E+09 | 62196846.30 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.536079E+09 | 30156809.78 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.567286E+09 | 36219129.61 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.543532E+09 | 38296529.31 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.516936E+09 | 64667496.63 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.502993E+09 | 54392473.26 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.553419E+09 | 52455712.86 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.702759E+09 | 66948508.34 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.864110E+09 | 74780877.03 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106735E+10 | 0.115719E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.855583E+10 | 0.775141E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.502993E+09 | 30156809.78 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108316E+10 | 0.115719E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.216261E+10 | 0.191410E+09 | 0.111329E+10 | 0.464477E+09 | 0.648813E+09 | 0.00 | 0.00 |
February | 0.177228E+10 | 0.135414E+09 | 0.853866E+09 | 0.278392E+09 | 0.575473E+09 | 0.00 | 0.00 |
March | 0.145494E+10 | 0.107411E+09 | 0.645148E+09 | 86643884.70 | 0.558504E+09 | 0.00 | 0.00 |
April | 0.107128E+10 | 49507594.50 | 0.465473E+09 | 208954.51 | 0.465264E+09 | 0.00 | 0.00 |
May | 0.113265E+10 | 61107404.25 | 0.481318E+09 | 0.00 | 0.481318E+09 | 0.00 | 0.00 |
June | 0.108565E+10 | 65259698.70 | 0.464114E+09 | 0.00 | 0.464114E+09 | 0.00 | 0.00 |
July | 0.102972E+10 | 0.114392E+09 | 0.494045E+09 | 0.00 | 0.494045E+09 | 0.00 | 0.00 |
August | 0.100230E+10 | 92131099.76 | 0.480956E+09 | 743328.04 | 0.480213E+09 | 0.00 | 0.00 |
September | 0.110465E+10 | 91068645.08 | 0.515277E+09 | 16829327.70 | 0.498448E+09 | 0.00 | 0.00 |
October | 0.140275E+10 | 0.118243E+09 | 0.696604E+09 | 0.111068E+09 | 0.585536E+09 | 0.00 | 0.00 |
November | 0.172460E+10 | 0.134562E+09 | 0.876594E+09 | 0.267437E+09 | 0.609157E+09 | 0.00 | 0.00 |
December | 0.213115E+10 | 0.215430E+09 | 0.111272E+10 | 0.473417E+09 | 0.639304E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.170746E+11 | 0.137594E+10 | 0.819941E+10 | 0.169922E+10 | 0.650019E+10 | 0.00 | 0.00 |
Minimum of Months | 0.100230E+10 | 49507594.50 | 0.464114E+09 | 0.00 | 0.464114E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216261E+10 | 0.215430E+09 | 0.111329E+10 | 0.473417E+09 | 0.648813E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108276E+10 | 92555251.28 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.887938E+09 | 64624541.58 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.730170E+09 | 50058143.12 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.539987E+09 | 22251944.21 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.570794E+09 | 28219255.53 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.547207E+09 | 30069186.73 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.517422E+09 | 54189250.30 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.503916E+09 | 42842376.06 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.554872E+09 | 42743437.00 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.703235E+09 | 56079650.13 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.863936E+09 | 64378766.82 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106684E+10 | 0.104679E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.856908E+10 | 0.652691E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.503916E+09 | 22251944.21 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108276E+10 | 0.104679E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108333E+10 | 91893905.99 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.888419E+09 | 64074140.05 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.730669E+09 | 49460132.81 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.540566E+09 | 21841178.77 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.571424E+09 | 27827480.15 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.547799E+09 | 29641464.80 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.517904E+09 | 53649105.04 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.504399E+09 | 42273619.95 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.555348E+09 | 42229631.96 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.703755E+09 | 55436624.67 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.864470E+09 | 63763088.41 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106740E+10 | 0.104001E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.857548E+10 | 0.646091E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.504399E+09 | 21841178.77 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108333E+10 | 0.104001E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.108326E+10 | 91701401.48 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.888094E+09 | 64150244.78 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.730144E+09 | 49678461.11 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.539587E+09 | 22179253.38 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.570335E+09 | 28130334.96 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.546758E+09 | 30073598.52 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.517187E+09 | 54106512.82 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.503784E+09 | 42553547.54 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.554649E+09 | 42579297.46 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.703460E+09 | 55399778.53 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.864302E+09 | 63642692.55 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106742E+10 | 0.103737E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.856898E+10 | 0.647932E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.503784E+09 | 22179253.38 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108326E+10 | 0.103737E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.107670E+10 | 94032746.94 | 0.556645E+09 | 0.232239E+09 | 0.324406E+09 | 0.00 | 0.00 |
February | 0.880386E+09 | 67523197.53 | 0.426933E+09 | 0.139196E+09 | 0.287737E+09 | 0.00 | 0.00 |
March | 0.720714E+09 | 53931778.20 | 0.322574E+09 | 43321942.35 | 0.279252E+09 | 0.00 | 0.00 |
April | 0.527272E+09 | 26326970.56 | 0.232737E+09 | 104477.26 | 0.232632E+09 | 0.00 | 0.00 |
May | 0.557585E+09 | 31853245.19 | 0.240659E+09 | 0.00 | 0.240659E+09 | 0.00 | 0.00 |
June | 0.534284E+09 | 34704724.94 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
July | 0.507417E+09 | 59682934.04 | 0.247022E+09 | 0.00 | 0.247022E+09 | 0.00 | 0.00 |
August | 0.494469E+09 | 47375163.63 | 0.240478E+09 | 371664.02 | 0.240106E+09 | 0.00 | 0.00 |
September | 0.544997E+09 | 47583377.79 | 0.257639E+09 | 8414663.85 | 0.249224E+09 | 0.00 | 0.00 |
October | 0.696444E+09 | 58739138.67 | 0.348302E+09 | 55533999.25 | 0.292768E+09 | 0.00 | 0.00 |
November | 0.857571E+09 | 66368868.79 | 0.438297E+09 | 0.133719E+09 | 0.304579E+09 | 0.00 | 0.00 |
December | 0.106150E+10 | 0.105806E+09 | 0.556360E+09 | 0.236709E+09 | 0.319652E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.845934E+10 | 0.693928E+09 | 0.409970E+10 | 0.849609E+09 | 0.325009E+10 | 0.00 | 0.00 |
Minimum of Months | 0.494469E+09 | 26326970.56 | 0.232057E+09 | 0.00 | 0.232057E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107670E+10 | 0.105806E+09 | 0.556645E+09 | 0.236709E+09 | 0.324406E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 26.42 | 22.38 | 20.70 | 2.25 | 18.66 | 103.85 | 146.57 | 0.01 |
February | 27.50 | 22.91 | 21.01 | 2.37 | 18.54 | 110.59 | 164.59 | 0.00 |
March | 28.33 | 23.63 | 21.77 | 3.67 | 19.85 | 110.33 | 194.39 | 0.01 |
April | 29.15 | 25.37 | 24.04 | 2.98 | 21.51 | 118.69 | 185.56 | 0.03 |
May | 29.01 | 26.53 | 25.72 | 3.19 | 23.00 | 127.71 | 124.87 | 0.08 |
June | 28.86 | 26.50 | 25.74 | 3.10 | 22.78 | 123.38 | 156.09 | 0.05 |
July | 27.25 | 24.29 | 23.20 | 2.32 | 21.53 | 137.39 | 88.28 | 0.02 |
August | 27.54 | 25.86 | 25.31 | 3.22 | 21.55 | 129.55 | 122.00 | 0.07 |
September | 27.58 | 25.59 | 24.93 | 2.22 | 22.01 | 128.30 | 103.37 | 0.04 |
October | 26.89 | 25.07 | 24.46 | 2.18 | 21.39 | 123.79 | 92.41 | 0.11 |
November | 26.68 | 24.14 | 23.20 | 1.94 | 20.29 | 113.70 | 103.30 | 0.02 |
December | 25.97 | 22.85 | 21.57 | 2.00 | 18.63 | 101.83 | 131.96 | 0.00 |
Annual Sum or Average | 27.59 | 24.60 | 23.48 | 2.62 | 20.82 | 119.14 | 134.17 | 0.04 |
Minimum of Months | 25.97 | 22.38 | 20.70 | 1.94 | 18.54 | 101.83 | 88.28 | 0.00 |
Maximum of Months | 29.15 | 26.53 | 25.74 | 3.67 | 23.00 | 137.39 | 194.39 | 0.11 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 34.10 | 04-JAN-12:00 | 23.67 | 19.40 | 5.00 | 24.66 | 266.50 | 576.50 |
February | 35.00 | 21-FEB-13:00 | 22.02 | 16.00 | 2.10 | 24.16 | 230.00 | 672.50 |
March | 36.40 | 21-MAR-12:00 | 23.01 | 17.00 | 5.00 | 26.97 | 269.50 | 658.50 |
April | 35.50 | 01-APR-13:00 | 26.96 | 24.00 | 2.50 | 27.14 | 295.50 | 519.50 |
May | 37.60 | 06-MAY-12:00 | 26.43 | 22.60 | 4.00 | 29.39 | 317.00 | 525.50 |
June | 36.00 | 12-JUN-14:00 | 27.60 | 25.00 | 4.00 | 28.43 | 235.00 | 472.00 |
July | 33.20 | 15-JUL-15:00 | 25.63 | 23.00 | 2.00 | 27.95 | 219.00 | 181.00 |
August | 34.00 | 10-AUG-13:00 | 27.86 | 26.00 | 5.00 | 26.65 | 344.50 | 278.50 |
September | 34.00 | 06-SEP-13:00 | 26.51 | 24.00 | 4.00 | 25.00 | 258.00 | 581.50 |
October | 33.00 | 04-OCT-13:00 | 26.23 | 24.00 | 4.00 | 25.16 | 303.00 | 428.50 |
November | 34.30 | 18-NOV-12:00 | 25.34 | 22.20 | 3.00 | 25.49 | 289.50 | 511.50 |
December | 33.00 | 07-DEC-13:00 | 23.23 | 19.00 | 3.00 | 22.98 | 215.00 | 596.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 33.00 | 22.02 | 16.00 | 2.00 | 22.98 | 215.00 | 181.00 | |
Maximum of Months | 37.60 | 27.86 | 26.00 | 5.00 | 29.39 | 344.50 | 672.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 18.70 | 23-JAN-05:00 | 16.92 | 16.00 | 2.00 | 7.75 | 0.00 | 0.00 |
February | 20.30 | 21-FEB-09:00 | 19.04 | 18.40 | 2.00 | 10.50 | 258.50 | 564.00 |
March | 22.00 | 03-MAR-05:00 | 19.94 | 19.00 | 3.00 | 13.35 | 0.00 | 0.00 |
April | 22.90 | 14-APR-15:00 | 22.90 | 22.90 | 3.00 | 14.65 | 199.50 | 264.50 |
May | 22.00 | 10-MAY-19:00 | 22.00 | 22.00 | 2.00 | 18.28 | 0.00 | 0.00 |
June | 23.00 | 20-JUN-23:00 | 23.00 | 23.00 | 2.00 | 19.35 | 0.00 | 0.00 |
July | 23.00 | 13-JUL-04:00 | 22.27 | 22.00 | 0.00 | 13.91 | 0.00 | 0.00 |
August | 22.00 | 20-AUG-10:00 | 22.00 | 22.00 | 5.00 | 18.28 | 430.50 | 41.50 |
September | 22.90 | 19-SEP-03:00 | 22.78 | 22.78 | 0.00 | 21.27 | 0.00 | 0.00 |
October | 22.50 | 23-OCT-04:00 | 22.50 | 22.50 | 2.80 | 18.82 | 0.00 | 0.00 |
November | 20.00 | 25-NOV-04:00 | 18.63 | 18.00 | 2.00 | 10.69 | 0.00 | 0.00 |
December | 18.00 | 21-DEC-04:00 | 17.36 | 17.00 | 3.00 | 9.13 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.00 | 16.92 | 16.00 | 0.00 | 7.75 | 0.00 | 0.00 | |
Maximum of Months | 23.00 | 23.00 | 23.00 | 5.00 | 21.27 | 430.50 | 564.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 25.53 | 12-JAN-12:00 | 32.40 | 23.10 | 2.00 | 25.00 | 353.00 | 347.00 |
February | 26.17 | 14-FEB-15:00 | 32.30 | 24.20 | 2.00 | 25.16 | 200.00 | 199.00 |
March | 26.28 | 27-MAR-12:00 | 34.20 | 23.60 | 4.00 | 26.32 | 326.00 | 535.00 |
April | 27.93 | 10-APR-16:49 | 31.52 | 26.85 | 4.08 | 27.70 | 110.67 | 57.00 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 30.11 | 15-JUN-09:00 | 33.20 | 29.20 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.43 | 20-JUL-14:00 | 32.80 | 24.20 | 1.00 | 26.65 | 305.00 | 253.00 |
August | 28.81 | 14-AUG-16:00 | 32.00 | 28.00 | 1.00 | 25.16 | 107.50 | 223.00 |
September | 30.06 | 30-SEP-10:00 | 32.80 | 29.40 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 27.36 | 16-OCT-14:00 | 31.50 | 26.00 | 3.00 | 24.16 | 239.00 | 346.50 |
November | 27.56 | 10-NOV-12:00 | 31.00 | 26.40 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.86 | 03-DEC-12:00 | 31.50 | 25.30 | 1.00 | 23.49 | 301.00 | 468.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 25.53 | 29.00 | 23.10 | 1.00 | 22.47 | 0.00 | 0.00 | |
Maximum of Months | 30.11 | 34.20 | 29.40 | 6.00 | 28.11 | 398.00 | 535.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 24.20 | 09-JAN-21:00 | 26.50 | 24.77 | 4.00 | 25.16 | 0.00 | 0.00 |
February | 24.40 | 15-FEB-18:00 | 28.30 | 25.33 | 4.00 | 20.75 | 0.00 | 0.00 |
March | 25.30 | 28-MAR-06:00 | 27.20 | 25.72 | 3.00 | 19.87 | 103.00 | 28.00 |
April | 27.00 | 10-APR-17:00 | 30.50 | 27.87 | 4.50 | 25.00 | 20.00 | 20.50 |
May | 29.00 | 28-MAY-20:00 | 29.00 | 29.00 | 3.00 | 22.47 | 0.00 | 0.00 |
June | 29.20 | 15-JUN-09:00 | 33.20 | 30.11 | 5.00 | 26.48 | 320.50 | 421.00 |
July | 26.00 | 10-JUL-14:00 | 26.50 | 26.11 | 2.30 | 23.49 | 286.00 | 36.50 |
August | 28.00 | 02-AUG-10:00 | 31.00 | 28.65 | 4.00 | 24.16 | 419.00 | 195.50 |
September | 29.40 | 30-SEP-10:00 | 32.80 | 30.06 | 3.00 | 25.66 | 398.00 | 359.50 |
October | 26.50 | 16-OCT-08:00 | 29.00 | 27.04 | 2.50 | 21.78 | 300.00 | 326.00 |
November | 26.40 | 10-NOV-12:00 | 31.00 | 27.56 | 6.00 | 28.11 | 388.00 | 95.50 |
December | 26.00 | 10-DEC-17:00 | 29.00 | 26.74 | 3.00 | 21.78 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.20 | 26.50 | 24.77 | 2.30 | 19.87 | 0.00 | 0.00 | |
Maximum of Months | 29.40 | 33.20 | 30.11 | 6.00 | 28.11 | 419.00 | 421.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 29.71 | 38.82 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 29.90 | 44.34 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 30.35 | 50.49 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 30.97 | 51.18 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 31.58 | 43.47 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 32.02 | 46.77 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 32.16 | 39.95 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 31.97 | 43.65 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 31.50 | 40.53 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.87 | 37.35 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 30.27 | 35.77 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 29.84 | 36.19 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 30.93 | 42.35 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 29.71 | 35.77 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 32.16 | 51.18 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.255004E+09 | -143756362.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111247686.6 | 58.99 | 0.00 | 0.00 |
February | 0.230017E+09 | -129703954.7 | 0.00 | 0.00 | 672.00 | 0.00 | -100313231.4 | 58.99 | 0.00 | 0.00 |
March | 0.254594E+09 | -143665354.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110929067.0 | 58.99 | 0.00 | 0.00 |
April | 0.241387E+09 | -134263512.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107123330.2 | 58.99 | 0.00 | 0.00 |
May | 0.246585E+09 | -135944047.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110640751.5 | 58.99 | 0.00 | 0.00 |
June | 0.237845E+09 | -130792578.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107052863.7 | 58.99 | 0.00 | 0.00 |
July | 0.242588E+09 | -131713590.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110874861.5 | 58.99 | 0.00 | 0.00 |
August | 0.246314E+09 | -135467824.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110846490.3 | 58.99 | 0.00 | 0.00 |
September | 0.239151E+09 | -131878343.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107272705.1 | 58.99 | 0.00 | 0.00 |
October | 0.249032E+09 | -138038055.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110993919.7 | 58.99 | 0.00 | 0.00 |
November | 0.243578E+09 | -136108215.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107469967.3 | 58.99 | 0.00 | 0.00 |
December | 0.254625E+09 | -143309730.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111314908.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294072E+10 | -0.163464E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130608E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.230017E+09 | -143756362.0 | 0.00 | 0.00 | 672.00 | 0.00 | -111314908.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.255004E+09 | -129703954.7 | 0.00 | 0.00 | 744.00 | 0.00 | -100313231.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.254886E+09 | -143753265.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111132731.2 | 58.99 | 0.00 | 0.00 |
February | 0.229950E+09 | -129693700.1 | 0.00 | 0.00 | 672.00 | 0.00 | -100256797.3 | 58.99 | 0.00 | 0.00 |
March | 0.254548E+09 | -143667102.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110880425.9 | 58.99 | 0.00 | 0.00 |
April | 0.241403E+09 | -134276324.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107126373.9 | 58.99 | 0.00 | 0.00 |
May | 0.246581E+09 | -135936200.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110644732.9 | 58.99 | 0.00 | 0.00 |
June | 0.237855E+09 | -130806884.2 | 0.00 | 0.00 | 720.00 | 0.00 | -107047800.8 | 58.99 | 0.00 | 0.00 |
July | 0.242554E+09 | -131708598.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110845416.5 | 58.99 | 0.00 | 0.00 |
August | 0.246281E+09 | -135466314.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110814741.2 | 58.99 | 0.00 | 0.00 |
September | 0.239133E+09 | -131873713.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107259473.5 | 58.99 | 0.00 | 0.00 |
October | 0.248980E+09 | -138054848.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110925626.1 | 58.99 | 0.00 | 0.00 |
November | 0.243488E+09 | -136101671.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107386248.6 | 58.99 | 0.00 | 0.00 |
December | 0.254511E+09 | -143336487.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111174596.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.294017E+10 | -0.163468E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130549E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.229950E+09 | -143753265.0 | 0.00 | 0.00 | 672.00 | 0.00 | -111174596.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.254886E+09 | -129693700.1 | 0.00 | 0.00 | 744.00 | 0.00 | -100256797.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.235369E+09 | -126414817.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108954595.9 | 58.99 | 0.00 | 0.00 |
February | 0.212396E+09 | -114140755.0 | 0.00 | 0.00 | 672.00 | 0.00 | -98255713.8 | 58.99 | 0.00 | 0.00 |
March | 0.236917E+09 | -128222145.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108695153.3 | 58.99 | 0.00 | 0.00 |
April | 0.222868E+09 | -118077546.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104790395.5 | 58.99 | 0.00 | 0.00 |
May | 0.228802E+09 | -120553809.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108247725.6 | 58.99 | 0.00 | 0.00 |
June | 0.221247E+09 | -116503330.9 | 0.00 | 0.00 | 720.00 | 0.00 | -104744113.2 | 58.99 | 0.00 | 0.00 |
July | 0.223603E+09 | -115152510.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108450559.3 | 58.99 | 0.00 | 0.00 |
August | 0.229754E+09 | -121018836.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108735622.4 | 58.98 | 0.00 | 0.00 |
September | 0.220958E+09 | -115903879.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105054177.7 | 58.99 | 0.00 | 0.00 |
October | 0.230163E+09 | -121394835.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108768227.2 | 58.99 | 0.00 | 0.00 |
November | 0.225580E+09 | -120179737.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105399775.2 | 58.99 | 0.00 | 0.00 |
December | 0.234225E+09 | -125118244.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109107140.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.272188E+10 | -0.144268E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.127920E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.212396E+09 | -128222145.9 | 0.00 | 0.00 | 672.00 | 0.00 | -109107140.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.236917E+09 | -114140755.0 | 0.00 | 0.00 | 744.00 | 0.00 | -98255713.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.235262E+09 | -126411425.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108850500.4 | 58.99 | 0.00 | 0.00 |
February | 0.212288E+09 | -114156632.9 | 0.00 | 0.00 | 672.00 | 0.00 | -98131285.9 | 58.99 | 0.00 | 0.00 |
March | 0.236804E+09 | -128228823.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108574797.1 | 58.99 | 0.00 | 0.00 |
April | 0.222740E+09 | -118095047.6 | 0.00 | 0.00 | 720.00 | 0.00 | -104644471.2 | 58.99 | 0.00 | 0.00 |
May | 0.228646E+09 | -120541968.3 | 0.00 | 0.00 | 744.00 | 0.00 | -108104422.4 | 58.99 | 0.00 | 0.00 |
June | 0.221119E+09 | -116501384.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104617187.6 | 58.99 | 0.00 | 0.00 |
July | 0.223466E+09 | -115163379.6 | 0.00 | 0.00 | 744.00 | 0.00 | -108302591.4 | 58.99 | 0.00 | 0.00 |
August | 0.229642E+09 | -120973484.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108668628.6 | 59.00 | 0.00 | 0.00 |
September | 0.220837E+09 | -115906631.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104930464.0 | 58.99 | 0.00 | 0.00 |
October | 0.230053E+09 | -121390166.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108662763.3 | 58.99 | 0.00 | 0.00 |
November | 0.225488E+09 | -120175114.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105312944.6 | 58.99 | 0.00 | 0.00 |
December | 0.234138E+09 | -125114408.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109024061.7 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.272048E+10 | -0.144266E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.127782E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.212288E+09 | -128228823.1 | 0.00 | 0.00 | 672.00 | 0.00 | -109024061.7 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.236804E+09 | -114156632.9 | 0.00 | 0.00 | 744.00 | 0.00 | -98131285.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.228974E+09 | -119488619.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109485086.8 | 58.99 | 0.00 | 0.00 |
February | 0.206663E+09 | -107946550.2 | 0.00 | 0.00 | 672.00 | 0.00 | -98716489.7 | 58.99 | 0.00 | 0.00 |
March | 0.230599E+09 | -121337763.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109261571.3 | 58.99 | 0.00 | 0.00 |
April | 0.217008E+09 | -111735692.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105272480.8 | 58.99 | 0.00 | 0.00 |
May | 0.222678E+09 | -114014884.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108663259.7 | 58.98 | 0.00 | 0.00 |
June | 0.215465E+09 | -110221905.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105242805.0 | 58.99 | 0.00 | 0.00 |
July | 0.217801E+09 | -108920307.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108880826.0 | 58.99 | 0.00 | 0.00 |
August | 0.223790E+09 | -114480471.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109309907.5 | 58.99 | 0.00 | 0.00 |
September | 0.215208E+09 | -109669017.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105539132.9 | 58.99 | 0.00 | 0.00 |
October | 0.223978E+09 | -114747959.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109229947.6 | 58.99 | 0.00 | 0.00 |
November | 0.219406E+09 | -113489142.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105916818.4 | 58.99 | 0.00 | 0.00 |
December | 0.227953E+09 | -118324772.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109628257.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264952E+10 | -0.136438E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128515E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.206663E+09 | -121337763.9 | 0.00 | 0.00 | 672.00 | 0.00 | -109628257.4 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.230599E+09 | -107946550.2 | 0.00 | 0.00 | 744.00 | 0.00 | -98716489.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229106E+09 | -119487420.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109618329.3 | 58.99 | 0.00 | 0.00 |
February | 0.206797E+09 | -107943097.2 | 0.00 | 0.00 | 672.00 | 0.00 | -98853542.9 | 58.99 | 0.00 | 0.00 |
March | 0.230743E+09 | -121338563.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109404183.9 | 58.99 | 0.00 | 0.00 |
April | 0.217145E+09 | -111737864.1 | 0.00 | 0.00 | 720.00 | 0.00 | -105407391.7 | 58.99 | 0.00 | 0.00 |
May | 0.222829E+09 | -113990462.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108838579.4 | 58.99 | 0.00 | 0.00 |
June | 0.215625E+09 | -110238119.0 | 0.00 | 0.00 | 720.00 | 0.00 | -105386720.2 | 58.99 | 0.00 | 0.00 |
July | 0.217953E+09 | -108918758.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109034309.2 | 58.99 | 0.00 | 0.00 |
August | 0.223938E+09 | -114536486.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109401961.1 | 58.98 | 0.00 | 0.00 |
September | 0.215351E+09 | -109666394.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105684860.8 | 58.99 | 0.00 | 0.00 |
October | 0.224119E+09 | -114752057.7 | 0.00 | 0.00 | 744.00 | 0.00 | -109366820.3 | 58.99 | 0.00 | 0.00 |
November | 0.219536E+09 | -113496393.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106039938.9 | 58.99 | 0.00 | 0.00 |
December | 0.228089E+09 | -118335657.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109753186.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265123E+10 | -0.136444E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128679E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.206797E+09 | -121338563.7 | 0.00 | 0.00 | 672.00 | 0.00 | -109753186.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.230743E+09 | -107943097.2 | 0.00 | 0.00 | 744.00 | 0.00 | -98853542.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.229147E+09 | -119485885.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109660761.7 | 58.99 | 0.00 | 0.00 |
February | 0.206835E+09 | -107942250.2 | 0.00 | 0.00 | 672.00 | 0.00 | -98892285.7 | 58.99 | 0.00 | 0.00 |
March | 0.230776E+09 | -121330543.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109445783.0 | 58.99 | 0.00 | 0.00 |
April | 0.217174E+09 | -111750530.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105423396.9 | 58.98 | 0.00 | 0.00 |
May | 0.222864E+09 | -113990770.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108873135.7 | 58.99 | 0.00 | 0.00 |
June | 0.215661E+09 | -110223524.8 | 0.00 | 0.00 | 720.00 | 0.00 | -105437290.4 | 58.99 | 0.00 | 0.00 |
July | 0.217988E+09 | -108931824.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109055810.9 | 58.98 | 0.00 | 0.00 |
August | 0.223954E+09 | -114417512.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109536308.0 | 59.01 | 0.00 | 0.00 |
September | 0.215384E+09 | -109680143.9 | 0.00 | 0.00 | 720.00 | 0.00 | -105704176.2 | 58.99 | 0.00 | 0.00 |
October | 0.224157E+09 | -114751951.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109405043.1 | 58.99 | 0.00 | 0.00 |
November | 0.219573E+09 | -113511388.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106061135.8 | 58.98 | 0.00 | 0.00 |
December | 0.228138E+09 | -118330924.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109807295.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.265165E+10 | -0.136435E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128730E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.206835E+09 | -121330543.0 | 0.00 | 0.00 | 672.00 | 0.00 | -109807295.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.230776E+09 | -107942250.2 | 0.00 | 0.00 | 744.00 | 0.00 | -98892285.7 | 59.01 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 350.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 361.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 376.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 370.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 369.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 357.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 356.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 349.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4292.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 321.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 383.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.454055E+11 | 0.294194E+11 | 67991.18 | 10-JAN-09:01 | 33072.36 | 0.00 |
February | 0.00 | 0.00 | 0.438288E+11 | 0.283571E+11 | 67795.24 | 16-FEB-09:01 | 33588.18 | 0.00 |
March | 0.00 | 0.00 | 0.509568E+11 | 0.324455E+11 | 68277.10 | 27-MAR-08:61 | 32329.64 | 0.00 |
April | 0.00 | 0.00 | 0.554586E+11 | 0.322021E+11 | 68428.14 | 03-APR-08:61 | 31807.82 | 0.00 |
May | 0.00 | 0.00 | 0.616963E+11 | 0.330818E+11 | 68842.03 | 17-MAY-08:61 | 28944.32 | 0.00 |
June | 0.00 | 0.00 | 0.612378E+11 | 0.326657E+11 | 68748.39 | 01-JUN-08:61 | 29105.85 | 0.00 |
July | 0.00 | 0.00 | 0.510083E+11 | 0.297767E+11 | 68287.51 | 01-JUL-08:61 | 32297.66 | 0.00 |
August | 0.00 | 0.00 | 0.569807E+11 | 0.295450E+11 | 68793.56 | 19-AUG-08:61 | 30119.26 | 0.00 |
September | 0.00 | 0.00 | 0.542767E+11 | 0.290545E+11 | 68818.28 | 21-SEP-08:61 | 29859.32 | 0.00 |
October | 0.00 | 0.00 | 0.524769E+11 | 0.281708E+11 | 68821.64 | 23-OCT-08:61 | 29808.68 | 0.00 |
November | 0.00 | 0.00 | 0.483440E+11 | 0.275772E+11 | 68295.51 | 03-NOV-08:61 | 32285.96 | 0.00 |
December | 0.00 | 0.00 | 0.461959E+11 | 0.285075E+11 | 67690.51 | 18-DEC-09:01 | 33857.56 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.627866E+12 | 0.360803E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.438288E+11 | 0.275772E+11 | 67690.51 | 28944.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.616963E+11 | 0.330818E+11 | 68842.03 | 33857.56 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.221742E+11 | 0.147990E+11 | 34255.58 | 10-JAN-09:01 | 18964.78 | 0.00 |
February | 0.00 | 0.00 | 0.212558E+11 | 0.141182E+11 | 34181.62 | 16-FEB-09:01 | 19129.12 | 0.00 |
March | 0.00 | 0.00 | 0.245648E+11 | 0.160556E+11 | 34436.19 | 27-MAR-08:61 | 18418.07 | 0.00 |
April | 0.00 | 0.00 | 0.264621E+11 | 0.158410E+11 | 34598.69 | 20-APR-08:61 | 17970.86 | 0.00 |
May | 0.00 | 0.00 | 0.295415E+11 | 0.163961E+11 | 35158.71 | 16-MAY-08:61 | 16288.80 | 0.00 |
June | 0.00 | 0.00 | 0.293750E+11 | 0.161801E+11 | 35121.88 | 10-JUN-08:61 | 15746.25 | 0.00 |
July | 0.00 | 0.00 | 0.245660E+11 | 0.147795E+11 | 34283.12 | 01-JUL-08:61 | 18856.48 | 0.00 |
August | 0.00 | 0.00 | 0.274897E+11 | 0.147406E+11 | 35220.60 | 25-AUG-08:61 | 16251.97 | 0.00 |
September | 0.00 | 0.00 | 0.260910E+11 | 0.144482E+11 | 34781.98 | 01-SEP-08:61 | 17539.98 | 0.00 |
October | 0.00 | 0.00 | 0.254559E+11 | 0.141711E+11 | 34622.16 | 23-OCT-08:61 | 17690.00 | 0.00 |
November | 0.00 | 0.00 | 0.234890E+11 | 0.138773E+11 | 34318.73 | 14-NOV-09:01 | 18756.32 | 0.00 |
December | 0.00 | 0.00 | 0.225280E+11 | 0.144060E+11 | 33965.20 | 01-DEC-09:01 | 19780.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.302993E+12 | 0.179813E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.212558E+11 | 0.138773E+11 | 33965.20 | 15746.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.295415E+11 | 0.163961E+11 | 35220.60 | 19780.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.183510E+11 | 0.119737E+11 | 35203.96 | 02-JAN-08:61 | 16007.01 | 0.00 |
February | 0.00 | 0.00 | 0.177389E+11 | 0.115129E+11 | 35088.82 | 16-FEB-08:61 | 16452.82 | 0.00 |
March | 0.00 | 0.00 | 0.207865E+11 | 0.132874E+11 | 35241.97 | 25-MAR-07:01 | 16034.19 | 0.00 |
April | 0.00 | 0.00 | 0.221919E+11 | 0.128800E+11 | 35305.96 | 24-APR-07:01 | 15650.28 | 0.00 |
May | 0.00 | 0.00 | 0.251666E+11 | 0.134446E+11 | 35350.51 | 17-MAY-07:03 | 14216.25 | 0.00 |
June | 0.00 | 0.00 | 0.251920E+11 | 0.133476E+11 | 35326.65 | 01-JUN-07:01 | 15467.58 | 0.00 |
July | 0.00 | 0.00 | 0.203738E+11 | 0.117488E+11 | 35318.45 | 01-JUL-07:01 | 15738.76 | 0.00 |
August | 0.00 | 0.00 | 0.235123E+11 | 0.120514E+11 | 35343.57 | 19-AUG-07:01 | 15314.26 | 0.00 |
September | 0.00 | 0.00 | 0.219709E+11 | 0.116224E+11 | 35355.52 | 18-SEP-07:01 | 14269.96 | 0.00 |
October | 0.00 | 0.00 | 0.213425E+11 | 0.113492E+11 | 35355.05 | 23-OCT-07:01 | 14570.13 | 0.00 |
November | 0.00 | 0.00 | 0.196214E+11 | 0.112185E+11 | 35300.00 | 05-NOV-08:61 | 15749.03 | 0.00 |
December | 0.00 | 0.00 | 0.185422E+11 | 0.115759E+11 | 35299.04 | 11-DEC-08:61 | 15119.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.254790E+12 | 0.146012E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.177389E+11 | 0.112185E+11 | 35088.82 | 14216.25 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.251920E+11 | 0.134446E+11 | 35355.52 | 16452.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.184307E+11 | 0.120288E+11 | 35273.71 | 02-JAN-08:61 | 16109.97 | 0.00 |
February | 0.00 | 0.00 | 0.178171E+11 | 0.115672E+11 | 35174.06 | 16-FEB-08:61 | 16509.67 | 0.00 |
March | 0.00 | 0.00 | 0.208761E+11 | 0.133478E+11 | 35328.75 | 28-MAR-07:01 | 16050.66 | 0.00 |
April | 0.00 | 0.00 | 0.222999E+11 | 0.129496E+11 | 35396.82 | 24-APR-07:01 | 15772.75 | 0.00 |
May | 0.00 | 0.00 | 0.252975E+11 | 0.135277E+11 | 35441.49 | 17-MAY-07:01 | 14410.81 | 0.00 |
June | 0.00 | 0.00 | 0.253169E+11 | 0.134253E+11 | 35417.56 | 01-JUN-07:01 | 15537.62 | 0.00 |
July | 0.00 | 0.00 | 0.204872E+11 | 0.118223E+11 | 35401.33 | 01-JUL-07:01 | 15805.93 | 0.00 |
August | 0.00 | 0.00 | 0.236034E+11 | 0.121048E+11 | 35434.53 | 19-AUG-07:01 | 15386.00 | 0.00 |
September | 0.00 | 0.00 | 0.220720E+11 | 0.116838E+11 | 35446.51 | 18-SEP-07:01 | 14370.70 | 0.00 |
October | 0.00 | 0.00 | 0.214374E+11 | 0.114066E+11 | 35446.04 | 23-OCT-07:01 | 14642.39 | 0.00 |
November | 0.00 | 0.00 | 0.196956E+11 | 0.112644E+11 | 35368.31 | 05-NOV-08:61 | 15838.09 | 0.00 |
December | 0.00 | 0.00 | 0.186082E+11 | 0.116185E+11 | 35389.88 | 11-DEC-08:61 | 15246.08 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.255942E+12 | 0.146747E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.178171E+11 | 0.112644E+11 | 35174.06 | 14370.70 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.253169E+11 | 0.135277E+11 | 35446.51 | 16509.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.182180E+11 | 0.118706E+11 | 35083.51 | 02-JAN-08:61 | 15950.42 | 0.00 |
February | 0.00 | 0.00 | 0.176226E+11 | 0.114227E+11 | 34999.26 | 16-FEB-08:61 | 16310.51 | 0.00 |
March | 0.00 | 0.00 | 0.206460E+11 | 0.131793E+11 | 35147.51 | 25-MAR-07:01 | 15906.74 | 0.00 |
April | 0.00 | 0.00 | 0.220761E+11 | 0.127933E+11 | 35185.11 | 24-APR-07:01 | 15583.28 | 0.00 |
May | 0.00 | 0.00 | 0.250676E+11 | 0.133748E+11 | 35229.52 | 17-MAY-07:01 | 14195.55 | 0.00 |
June | 0.00 | 0.00 | 0.250861E+11 | 0.132718E+11 | 35205.73 | 01-JUN-07:01 | 15349.53 | 0.00 |
July | 0.00 | 0.00 | 0.202605E+11 | 0.116651E+11 | 35197.57 | 01-JUL-07:01 | 15584.88 | 0.00 |
August | 0.00 | 0.00 | 0.233431E+11 | 0.119347E+11 | 35222.60 | 19-AUG-07:01 | 15161.25 | 0.00 |
September | 0.00 | 0.00 | 0.218330E+11 | 0.115252E+11 | 35234.51 | 18-SEP-07:01 | 14170.12 | 0.00 |
October | 0.00 | 0.00 | 0.211934E+11 | 0.112446E+11 | 35234.04 | 23-OCT-07:01 | 14482.11 | 0.00 |
November | 0.00 | 0.00 | 0.194684E+11 | 0.111075E+11 | 35181.52 | 05-NOV-08:61 | 15670.74 | 0.00 |
December | 0.00 | 0.00 | 0.183825E+11 | 0.114549E+11 | 35178.22 | 11-DEC-08:61 | 15042.25 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.253197E+12 | 0.144844E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.176226E+11 | 0.111075E+11 | 34999.26 | 14170.12 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.250861E+11 | 0.133748E+11 | 35234.51 | 16310.51 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.327442E+11 | 0.209879E+11 | 62534.81 | 02-JAN-09:01 | 28881.14 | 0.00 |
February | 0.00 | 0.00 | 0.317308E+11 | 0.202299E+11 | 62067.54 | 16-FEB-09:01 | 30229.18 | 0.00 |
March | 0.00 | 0.00 | 0.372473E+11 | 0.234031E+11 | 62522.28 | 27-MAR-08:61 | 28835.76 | 0.00 |
April | 0.00 | 0.00 | 0.398671E+11 | 0.226765E+11 | 62522.28 | 24-APR-08:61 | 27801.72 | 0.00 |
May | 0.00 | 0.00 | 0.453591E+11 | 0.237008E+11 | 62852.47 | 17-MAY-08:61 | 25907.32 | 0.00 |
June | 0.00 | 0.00 | 0.455989E+11 | 0.236263E+11 | 62766.97 | 01-JUN-08:61 | 26601.69 | 0.00 |
July | 0.00 | 0.00 | 0.362988E+11 | 0.204814E+11 | 62701.73 | 24-JUL-08:61 | 28190.06 | 0.00 |
August | 0.00 | 0.00 | 0.421898E+11 | 0.210196E+11 | 62808.21 | 19-AUG-08:61 | 27508.23 | 0.00 |
September | 0.00 | 0.00 | 0.392932E+11 | 0.202591E+11 | 62852.47 | 18-SEP-08:61 | 24567.94 | 0.00 |
October | 0.00 | 0.00 | 0.380611E+11 | 0.196902E+11 | 62833.85 | 23-OCT-08:61 | 24740.36 | 0.00 |
November | 0.00 | 0.00 | 0.349492E+11 | 0.194667E+11 | 62612.08 | 13-NOV-09:01 | 26938.12 | 0.00 |
December | 0.00 | 0.00 | 0.328606E+11 | 0.200931E+11 | 62749.53 | 18-DEC-09:01 | 28114.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.456200E+12 | 0.255635E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.317308E+11 | 0.194667E+11 | 62067.54 | 24567.94 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.455989E+11 | 0.237008E+11 | 62852.47 | 30229.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.170968E+11 | 0.109818E+11 | 32882.27 | 02-JAN-09:01 | 15182.82 | 0.00 |
February | 0.00 | 0.00 | 0.165672E+11 | 0.105810E+11 | 32622.28 | 16-FEB-09:01 | 15919.19 | 0.00 |
March | 0.00 | 0.00 | 0.194298E+11 | 0.122306E+11 | 32860.02 | 27-MAR-08:61 | 15189.61 | 0.00 |
April | 0.00 | 0.00 | 0.207906E+11 | 0.118528E+11 | 32860.02 | 24-APR-08:61 | 14637.21 | 0.00 |
May | 0.00 | 0.00 | 0.236420E+11 | 0.123880E+11 | 33033.55 | 17-MAY-08:03 | 13568.76 | 0.00 |
June | 0.00 | 0.00 | 0.237436E+11 | 0.123332E+11 | 32988.62 | 01-JUN-08:61 | 14041.34 | 0.00 |
July | 0.00 | 0.00 | 0.189326E+11 | 0.107084E+11 | 32963.57 | 24-JUL-08:61 | 14843.71 | 0.00 |
August | 0.00 | 0.00 | 0.219787E+11 | 0.109833E+11 | 33010.29 | 19-AUG-08:61 | 14505.66 | 0.00 |
September | 0.00 | 0.00 | 0.204847E+11 | 0.105903E+11 | 33033.55 | 18-SEP-08:03 | 12820.22 | 0.00 |
October | 0.00 | 0.00 | 0.198490E+11 | 0.102981E+11 | 33023.76 | 23-OCT-08:04 | 12851.38 | 0.00 |
November | 0.00 | 0.00 | 0.182282E+11 | 0.101794E+11 | 32907.21 | 13-NOV-09:01 | 14167.81 | 0.00 |
December | 0.00 | 0.00 | 0.171495E+11 | 0.105100E+11 | 32979.45 | 18-DEC-09:01 | 14748.81 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237893E+12 | 0.133637E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.165672E+11 | 0.101794E+11 | 32622.28 | 12820.22 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237436E+11 | 0.123880E+11 | 33033.55 | 15919.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.170190E+11 | 0.109221E+11 | 32752.99 | 02-JAN-09:01 | 15100.16 | 0.00 |
February | 0.00 | 0.00 | 0.164997E+11 | 0.105290E+11 | 32497.40 | 16-FEB-09:01 | 15825.92 | 0.00 |
March | 0.00 | 0.00 | 0.193549E+11 | 0.121739E+11 | 32723.90 | 27-MAR-08:61 | 15112.50 | 0.00 |
April | 0.00 | 0.00 | 0.207204E+11 | 0.118013E+11 | 32723.90 | 24-APR-08:61 | 14534.30 | 0.00 |
May | 0.00 | 0.00 | 0.235673E+11 | 0.123348E+11 | 32896.72 | 17-MAY-08:61 | 13586.09 | 0.00 |
June | 0.00 | 0.00 | 0.236685E+11 | 0.122794E+11 | 32851.97 | 01-JUN-08:61 | 13948.87 | 0.00 |
July | 0.00 | 0.00 | 0.188604E+11 | 0.106560E+11 | 32832.82 | 24-JUL-08:61 | 14764.96 | 0.00 |
August | 0.00 | 0.00 | 0.218989E+11 | 0.109286E+11 | 32873.55 | 19-AUG-08:61 | 14417.48 | 0.00 |
September | 0.00 | 0.00 | 0.204115E+11 | 0.105389E+11 | 32896.72 | 18-SEP-08:61 | 12815.52 | 0.00 |
October | 0.00 | 0.00 | 0.197688E+11 | 0.102421E+11 | 32886.97 | 23-OCT-08:04 | 12777.80 | 0.00 |
November | 0.00 | 0.00 | 0.181477E+11 | 0.101216E+11 | 32770.90 | 13-NOV-09:01 | 14087.74 | 0.00 |
December | 0.00 | 0.00 | 0.170677E+11 | 0.104490E+11 | 32842.84 | 18-DEC-09:01 | 14660.05 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.236985E+12 | 0.132977E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.164997E+11 | 0.101216E+11 | 32497.40 | 12777.80 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.236685E+11 | 0.123348E+11 | 32896.72 | 15825.92 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.170040E+11 | 0.109117E+11 | 32835.12 | 02-JAN-09:01 | 15093.79 | 0.00 |
February | 0.00 | 0.00 | 0.165113E+11 | 0.105392E+11 | 32571.74 | 16-FEB-09:01 | 15841.37 | 0.00 |
March | 0.00 | 0.00 | 0.193814E+11 | 0.121952E+11 | 32792.40 | 27-MAR-08:61 | 15128.81 | 0.00 |
April | 0.00 | 0.00 | 0.207727E+11 | 0.118412E+11 | 32792.40 | 24-APR-08:61 | 14567.03 | 0.00 |
May | 0.00 | 0.00 | 0.236179E+11 | 0.123730E+11 | 32965.57 | 17-MAY-08:61 | 13596.74 | 0.00 |
June | 0.00 | 0.00 | 0.237310E+11 | 0.123256E+11 | 32920.73 | 01-JUN-08:61 | 13962.84 | 0.00 |
July | 0.00 | 0.00 | 0.188970E+11 | 0.106833E+11 | 32906.47 | 24-JUL-08:61 | 14782.44 | 0.00 |
August | 0.00 | 0.00 | 0.219285E+11 | 0.109512E+11 | 32942.36 | 19-AUG-08:61 | 14431.11 | 0.00 |
September | 0.00 | 0.00 | 0.204478E+11 | 0.105663E+11 | 32965.57 | 18-SEP-08:03 | 12753.64 | 0.00 |
October | 0.00 | 0.00 | 0.197601E+11 | 0.102380E+11 | 32955.81 | 23-OCT-08:61 | 12930.58 | 0.00 |
November | 0.00 | 0.00 | 0.181380E+11 | 0.101162E+11 | 32839.49 | 13-NOV-09:01 | 14084.26 | 0.00 |
December | 0.00 | 0.00 | 0.170430E+11 | 0.104320E+11 | 32911.58 | 18-DEC-09:01 | 14651.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.237233E+12 | 0.133173E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.165113E+11 | 0.101162E+11 | 32571.74 | 12753.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.237310E+11 | 0.123730E+11 | 32965.57 | 15841.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.187074E+11 | 0.121701E+11 | 37378.81 | 02-JAN-09:01 | 17023.92 | 0.00 |
February | 0.00 | 0.00 | 0.183116E+11 | 0.118772E+11 | 37300.78 | 16-FEB-09:01 | 17242.30 | 0.00 |
March | 0.00 | 0.00 | 0.216314E+11 | 0.138144E+11 | 37288.89 | 15-MAR-08:61 | 16856.47 | 0.00 |
April | 0.00 | 0.00 | 0.231809E+11 | 0.135018E+11 | 37416.30 | 21-APR-08:61 | 16408.28 | 0.00 |
May | 0.00 | 0.00 | 0.261165E+11 | 0.140093E+11 | 37474.61 | 17-MAY-08:03 | 14436.79 | 0.00 |
June | 0.00 | 0.00 | 0.263528E+11 | 0.140539E+11 | 37423.63 | 01-JUN-08:04 | 14605.12 | 0.00 |
July | 0.00 | 0.00 | 0.210033E+11 | 0.121455E+11 | 37430.49 | 24-JUL-08:61 | 16713.28 | 0.00 |
August | 0.00 | 0.00 | 0.242442E+11 | 0.124400E+11 | 37448.22 | 19-AUG-08:61 | 15331.12 | 0.00 |
September | 0.00 | 0.00 | 0.226346E+11 | 0.120259E+11 | 37474.61 | 18-SEP-08:03 | 14545.82 | 0.00 |
October | 0.00 | 0.00 | 0.215531E+11 | 0.114289E+11 | 37463.50 | 23-OCT-08:61 | 14711.37 | 0.00 |
November | 0.00 | 0.00 | 0.198643E+11 | 0.113143E+11 | 37357.62 | 01-NOV-08:61 | 16879.03 | 0.00 |
December | 0.00 | 0.00 | 0.186915E+11 | 0.116286E+11 | 37413.23 | 18-DEC-09:01 | 16541.45 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.262292E+12 | 0.150410E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.183116E+11 | 0.113143E+11 | 37288.89 | 14436.79 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.263528E+11 | 0.140539E+11 | 37474.61 | 17242.30 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.466251E+10 | 0.59 | 2569.73 | 03-JAN-08:50 | 0.86 |
February | 0.421846E+10 | 0.59 | 2569.73 | 03-FEB-08:50 | 0.86 |
March | 0.468101E+10 | 0.59 | 2569.73 | 05-MAR-22:40 | 0.87 |
April | 0.451450E+10 | 0.59 | 2569.73 | 01-APR-07:09 | 0.86 |
May | 0.466251E+10 | 0.58 | 2569.73 | 02-MAY-07:09 | 0.86 |
June | 0.453300E+10 | 0.59 | 2569.73 | 01-JUN-08:17 | 0.86 |
July | 0.466251E+10 | 0.59 | 2569.73 | 02-JUL-08:07 | 0.86 |
August | 0.467176E+10 | 0.58 | 2569.73 | 01-AUG-07:15 | 0.86 |
September | 0.452375E+10 | 0.59 | 2569.73 | 01-SEP-07:06 | 0.86 |
October | 0.466251E+10 | 0.58 | 2569.73 | 03-OCT-07:20 | 0.86 |
November | 0.450524E+10 | 0.58 | 2569.73 | 03-NOV-08:07 | 0.86 |
December | 0.468101E+10 | 0.59 | 2569.73 | 04-DEC-08:20 | 0.86 |
Annual Sum or Average | 0.549788E+11 | 0.59 | |||
Minimum of Months | 0.421846E+10 | 0.58 | 2569.73 | 0.86 | |
Maximum of Months | 0.468101E+10 | 0.59 | 2569.73 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.203548E+10 | 0.64 | 1367.00 | 02-JAN-10:30 | 0.89 |
February | 0.184516E+10 | 0.64 | 1367.00 | 02-FEB-10:10 | 0.90 |
March | 0.206789E+10 | 0.64 | 1367.00 | 01-MAR-08:07 | 0.89 |
April | 0.199995E+10 | 0.64 | 1367.00 | 01-APR-07:08 | 0.89 |
May | 0.208465E+10 | 0.64 | 1367.00 | 03-MAY-11:50 | 0.89 |
June | 0.202692E+10 | 0.64 | 1367.00 | 01-JUN-07:20 | 0.89 |
July | 0.204789E+10 | 0.64 | 1367.00 | 01-JUL-08:13 | 0.89 |
August | 0.207863E+10 | 0.64 | 1367.00 | 01-AUG-07:30 | 0.89 |
September | 0.199544E+10 | 0.64 | 1367.00 | 01-SEP-07:06 | 0.89 |
October | 0.205017E+10 | 0.64 | 1367.00 | 01-OCT-07:09 | 0.90 |
November | 0.198194E+10 | 0.64 | 1367.00 | 01-NOV-07:40 | 0.89 |
December | 0.203196E+10 | 0.65 | 1367.00 | 01-DEC-19:40 | 0.90 |
Annual Sum or Average | 0.242461E+11 | 0.64 | |||
Minimum of Months | 0.184516E+10 | 0.64 | 1367.00 | 0.89 | |
Maximum of Months | 0.208465E+10 | 0.65 | 1367.00 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.197609E+10 | 0.48 | 1365.46 | 04-JAN-07:40 | 0.89 |
February | 0.178930E+10 | 0.49 | 1365.46 | 08-FEB-11:00 | 0.90 |
March | 0.201542E+10 | 0.49 | 1365.46 | 01-MAR-19:00 | 0.90 |
April | 0.191711E+10 | 0.48 | 1365.46 | 05-APR-10:10 | 0.90 |
May | 0.199576E+10 | 0.49 | 1365.46 | 07-MAY-07:08 | 0.89 |
June | 0.194660E+10 | 0.49 | 1365.46 | 12-JUN-12:10 | 0.89 |
July | 0.196626E+10 | 0.48 | 1365.46 | 02-JUL-07:07 | 0.89 |
August | 0.201542E+10 | 0.49 | 1365.46 | 09-AUG-14:40 | 0.89 |
September | 0.191711E+10 | 0.48 | 1365.46 | 03-SEP-07:07 | 0.88 |
October | 0.197609E+10 | 0.48 | 1365.46 | 03-OCT-07:00 | 0.89 |
November | 0.191711E+10 | 0.48 | 1365.46 | 04-NOV-06:50 | 0.89 |
December | 0.196626E+10 | 0.48 | 1365.46 | 04-DEC-08:15 | 0.89 |
Annual Sum or Average | 0.233985E+11 | 0.49 | |||
Minimum of Months | 0.178930E+10 | 0.48 | 1365.46 | 0.88 | |
Maximum of Months | 0.201542E+10 | 0.49 | 1365.46 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.198118E+10 | 0.48 | 1368.97 | 04-JAN-08:07 | 0.89 |
February | 0.179390E+10 | 0.49 | 1368.97 | 07-FEB-09:07 | 0.90 |
March | 0.202061E+10 | 0.49 | 1368.97 | 28-MAR-07:09 | 0.89 |
April | 0.192204E+10 | 0.48 | 1368.97 | 06-APR-18:40 | 0.89 |
May | 0.200089E+10 | 0.49 | 1368.97 | 01-MAY-07:00 | 0.88 |
June | 0.195161E+10 | 0.49 | 1368.97 | 01-JUN-08:07 | 0.89 |
July | 0.197132E+10 | 0.48 | 1368.97 | 29-JUL-07:20 | 0.89 |
August | 0.202061E+10 | 0.49 | 1368.97 | 15-AUG-07:00 | 0.88 |
September | 0.192204E+10 | 0.48 | 1368.97 | 24-SEP-09:00 | 0.89 |
October | 0.198118E+10 | 0.48 | 1368.97 | 01-OCT-07:50 | 0.89 |
November | 0.192204E+10 | 0.48 | 1368.97 | 17-NOV-10:00 | 0.89 |
December | 0.197132E+10 | 0.48 | 1368.97 | 10-DEC-08:10 | 0.89 |
Annual Sum or Average | 0.234587E+11 | 0.49 | |||
Minimum of Months | 0.179390E+10 | 0.48 | 1368.97 | 0.88 | |
Maximum of Months | 0.202061E+10 | 0.49 | 1368.97 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.196933E+10 | 0.48 | 1360.79 | 01-JAN-09:50 | 0.89 |
February | 0.178318E+10 | 0.49 | 1360.79 | 02-FEB-09:20 | 0.90 |
March | 0.200852E+10 | 0.49 | 1360.79 | 01-MAR-08:07 | 0.89 |
April | 0.191054E+10 | 0.48 | 1360.79 | 01-APR-08:61 | 0.89 |
May | 0.198893E+10 | 0.49 | 1360.79 | 01-MAY-12:00 | 0.89 |
June | 0.193994E+10 | 0.49 | 1360.79 | 02-JUN-06:20 | 0.89 |
July | 0.195953E+10 | 0.48 | 1360.79 | 01-JUL-07:07 | 0.89 |
August | 0.200852E+10 | 0.49 | 1360.79 | 01-AUG-07:00 | 0.89 |
September | 0.191054E+10 | 0.48 | 1360.79 | 01-SEP-06:40 | 0.89 |
October | 0.196933E+10 | 0.48 | 1360.79 | 02-OCT-07:06 | 0.89 |
November | 0.191054E+10 | 0.48 | 1360.79 | 01-NOV-07:00 | 0.89 |
December | 0.195953E+10 | 0.48 | 1360.79 | 02-DEC-08:10 | 0.89 |
Annual Sum or Average | 0.233184E+11 | 0.49 | |||
Minimum of Months | 0.178318E+10 | 0.48 | 1360.79 | 0.89 | |
Maximum of Months | 0.200852E+10 | 0.49 | 1360.79 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.313351E+10 | 0.43 | 2346.15 | 01-JAN-09:20 | 0.86 |
February | 0.283790E+10 | 0.43 | 2346.15 | 01-FEB-09:50 | 0.87 |
March | 0.320108E+10 | 0.44 | 2346.15 | 01-MAR-10:20 | 0.86 |
April | 0.304061E+10 | 0.43 | 2346.15 | 01-APR-07:40 | 0.86 |
May | 0.316730E+10 | 0.43 | 2346.15 | 01-MAY-07:06 | 0.85 |
June | 0.309128E+10 | 0.44 | 2346.15 | 01-JUN-07:40 | 0.86 |
July | 0.311662E+10 | 0.43 | 2346.15 | 01-JUL-07:50 | 0.86 |
August | 0.320108E+10 | 0.44 | 2346.15 | 01-AUG-07:09 | 0.86 |
September | 0.304061E+10 | 0.43 | 2346.15 | 01-SEP-07:40 | 0.86 |
October | 0.313351E+10 | 0.43 | 2346.15 | 01-OCT-08:13 | 0.86 |
November | 0.304061E+10 | 0.43 | 2346.15 | 01-NOV-08:07 | 0.86 |
December | 0.311662E+10 | 0.43 | 2346.15 | 01-DEC-09:15 | 0.86 |
Annual Sum or Average | 0.371207E+11 | 0.43 | |||
Minimum of Months | 0.283790E+10 | 0.43 | 2346.15 | 0.85 | |
Maximum of Months | 0.320108E+10 | 0.44 | 2346.15 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170401E+10 | 0.45 | 1275.84 | 01-JAN-09:20 | 0.89 |
February | 0.154325E+10 | 0.45 | 1275.84 | 01-FEB-11:30 | 0.90 |
March | 0.174075E+10 | 0.46 | 1275.84 | 02-MAR-20:55 | 0.90 |
April | 0.165348E+10 | 0.45 | 1275.84 | 01-APR-07:08 | 0.89 |
May | 0.172238E+10 | 0.45 | 1275.84 | 01-MAY-07:20 | 0.88 |
June | 0.168104E+10 | 0.45 | 1275.84 | 02-JUN-07:20 | 0.89 |
July | 0.169482E+10 | 0.44 | 1275.84 | 01-JUL-10:00 | 0.89 |
August | 0.174075E+10 | 0.45 | 1275.84 | 01-AUG-07:10 | 0.89 |
September | 0.165348E+10 | 0.45 | 1275.84 | 01-SEP-08:07 | 0.89 |
October | 0.170401E+10 | 0.44 | 1275.84 | 01-OCT-08:09 | 0.89 |
November | 0.165348E+10 | 0.45 | 1275.84 | 01-NOV-19:15 | 0.89 |
December | 0.169482E+10 | 0.44 | 1275.84 | 01-DEC-19:00 | 0.89 |
Annual Sum or Average | 0.201863E+11 | 0.45 | |||
Minimum of Months | 0.154325E+10 | 0.44 | 1275.84 | 0.88 | |
Maximum of Months | 0.174075E+10 | 0.46 | 1275.84 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169695E+10 | 0.45 | 1270.55 | 01-JAN-09:30 | 0.89 |
February | 0.153686E+10 | 0.45 | 1270.55 | 01-FEB-09:30 | 0.90 |
March | 0.173354E+10 | 0.46 | 1270.55 | 08-MAR-20:55 | 0.89 |
April | 0.164664E+10 | 0.45 | 1270.55 | 01-APR-07:30 | 0.89 |
May | 0.171525E+10 | 0.45 | 1270.55 | 13-MAY-07:30 | 0.89 |
June | 0.167408E+10 | 0.45 | 1270.55 | 15-JUN-07:30 | 0.88 |
July | 0.168780E+10 | 0.44 | 1270.55 | 05-JUL-08:00 | 0.89 |
August | 0.173354E+10 | 0.45 | 1270.55 | 01-AUG-07:09 | 0.89 |
September | 0.164664E+10 | 0.45 | 1270.55 | 01-SEP-07:09 | 0.89 |
October | 0.169695E+10 | 0.44 | 1270.55 | 15-OCT-08:07 | 0.88 |
November | 0.164664E+10 | 0.45 | 1270.55 | 15-NOV-09:17 | 0.89 |
December | 0.168780E+10 | 0.44 | 1270.55 | 01-DEC-08:40 | 0.89 |
Annual Sum or Average | 0.201027E+11 | 0.45 | |||
Minimum of Months | 0.153686E+10 | 0.44 | 1270.55 | 0.88 | |
Maximum of Months | 0.173354E+10 | 0.46 | 1270.55 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170050E+10 | 0.45 | 1273.21 | 01-JAN-09:50 | 0.89 |
February | 0.154008E+10 | 0.45 | 1273.21 | 01-FEB-08:50 | 0.90 |
March | 0.173717E+10 | 0.46 | 1273.21 | 01-MAR-08:30 | 0.89 |
April | 0.165008E+10 | 0.45 | 1273.21 | 01-APR-07:20 | 0.89 |
May | 0.171884E+10 | 0.45 | 1273.21 | 01-MAY-07:03 | 0.88 |
June | 0.167758E+10 | 0.45 | 1273.21 | 12-JUN-07:09 | 0.88 |
July | 0.169133E+10 | 0.44 | 1273.21 | 01-JUL-08:00 | 0.89 |
August | 0.173717E+10 | 0.45 | 1273.21 | 01-AUG-07:10 | 0.89 |
September | 0.165008E+10 | 0.45 | 1273.21 | 01-SEP-07:40 | 0.89 |
October | 0.170050E+10 | 0.44 | 1273.21 | 01-OCT-08:06 | 0.89 |
November | 0.165008E+10 | 0.45 | 1273.21 | 01-NOV-10:10 | 0.89 |
December | 0.169133E+10 | 0.44 | 1273.21 | 01-DEC-09:09 | 0.89 |
Annual Sum or Average | 0.201448E+11 | 0.45 | |||
Minimum of Months | 0.154008E+10 | 0.44 | 1273.21 | 0.88 | |
Maximum of Months | 0.173717E+10 | 0.46 | 1273.21 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.193310E+10 | 0.45 | 1447.36 | 01-JAN-11:20 | 0.89 |
February | 0.175073E+10 | 0.45 | 1447.36 | 02-FEB-09:00 | 0.89 |
March | 0.197478E+10 | 0.46 | 1447.36 | 02-MAR-10:30 | 0.90 |
April | 0.187578E+10 | 0.45 | 1447.36 | 01-APR-07:13 | 0.89 |
May | 0.195394E+10 | 0.45 | 1447.36 | 01-MAY-08:10 | 0.89 |
June | 0.190705E+10 | 0.45 | 1447.36 | 03-JUN-07:30 | 0.89 |
July | 0.192268E+10 | 0.44 | 1447.36 | 01-JUL-07:40 | 0.89 |
August | 0.197478E+10 | 0.45 | 1447.36 | 01-AUG-07:45 | 0.89 |
September | 0.187578E+10 | 0.45 | 1447.36 | 04-SEP-08:30 | 0.89 |
October | 0.193310E+10 | 0.44 | 1447.36 | 03-OCT-07:50 | 0.89 |
November | 0.187578E+10 | 0.45 | 1447.36 | 08-NOV-09:06 | 0.89 |
December | 0.192268E+10 | 0.44 | 1447.36 | 01-DEC-20:10 | 0.90 |
Annual Sum or Average | 0.229002E+11 | 0.45 | |||
Minimum of Months | 0.175073E+10 | 0.44 | 1447.36 | 0.89 | |
Maximum of Months | 0.197478E+10 | 0.46 | 1447.36 | 0.90 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.171445E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.163393E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.188115E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.195718E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.210528E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.207059E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.183398E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.195315E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.187750E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.184227E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.173613E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.171942E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.223250E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.163393E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.210528E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.806610E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.766356E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.882051E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.913148E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.987368E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.972236E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.857149E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.917918E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.878305E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.865583E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.816430E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.807352E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104705E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.766356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.987368E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.693656E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.661003E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.769542E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.783200E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.854582E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.846629E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.730166E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.801240E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.755463E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.744316E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.703246E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.691001E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.903404E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.661003E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.854582E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.696257E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.663555E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.772499E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.786548E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.858433E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.850326E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.733578E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.804128E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.758550E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.747269E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.705689E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.693278E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.907011E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.663555E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.858433E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.689489E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.657304E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.765082E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.779415E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.851140E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.843072E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.726518E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.796224E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.751219E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.739844E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.698681E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.686240E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.898423E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.657304E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.851140E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.120908E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115545E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.134828E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.137543E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.150470E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.149665E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.127126E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.140380E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.131989E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.129634E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.122384E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.119761E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.158023E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115545E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.150470E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.630462E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.602059E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.701804E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.715234E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.781732E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.776870E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.661958E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.729666E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.686489E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.674786E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.637308E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.624331E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.822270E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.602059E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.781732E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.627590E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.599478E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.698885E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.712448E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.778804E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.773951E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.659225E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.726701E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.683703E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.671860E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.634409E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.621366E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.818842E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.599478E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.778804E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.627693E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.600196E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.700034E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.714213E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.780530E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.775936E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.660544E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.727889E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.685026E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.672135E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.634640E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.621227E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.820006E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.600196E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.780530E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.700912E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.674081E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.789335E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.806214E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.876399E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.874006E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.743106E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.816931E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.769452E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.747123E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.707161E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.692576E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.919729E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.674081E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.876399E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.466251E+10 | 0.454055E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421846E+10 | 0.438288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468101E+10 | 0.509568E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451450E+10 | 0.554586E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466251E+10 | 0.616963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.453300E+10 | 0.612378E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.466251E+10 | 0.510083E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467176E+10 | 0.569807E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452375E+10 | 0.542767E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466251E+10 | 0.524769E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450524E+10 | 0.483440E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468101E+10 | 0.461959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549788E+11 | 0.627866E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421846E+10 | 0.438288E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468101E+10 | 0.616963E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.203548E+10 | 0.221742E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184516E+10 | 0.212558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206789E+10 | 0.245648E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199995E+10 | 0.264621E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208465E+10 | 0.295415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202692E+10 | 0.293750E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.204789E+10 | 0.245660E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207863E+10 | 0.274897E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199544E+10 | 0.260910E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205017E+10 | 0.254559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198194E+10 | 0.234890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203196E+10 | 0.225280E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242461E+11 | 0.302993E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.184516E+10 | 0.212558E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208465E+10 | 0.295415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.197609E+10 | 0.183510E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178930E+10 | 0.177389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201542E+10 | 0.207865E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191711E+10 | 0.221919E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199576E+10 | 0.251666E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194660E+10 | 0.251920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196626E+10 | 0.203738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201542E+10 | 0.235123E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191711E+10 | 0.219709E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197609E+10 | 0.213425E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191711E+10 | 0.196214E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196626E+10 | 0.185422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233985E+11 | 0.254790E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178930E+10 | 0.177389E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201542E+10 | 0.251920E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.198118E+10 | 0.184307E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179390E+10 | 0.178171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202061E+10 | 0.208761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192204E+10 | 0.222999E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200089E+10 | 0.252975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195161E+10 | 0.253169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197132E+10 | 0.204872E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202061E+10 | 0.236034E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192204E+10 | 0.220720E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198118E+10 | 0.214374E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192204E+10 | 0.196956E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197132E+10 | 0.186082E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234587E+11 | 0.255942E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179390E+10 | 0.178171E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202061E+10 | 0.253169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.196933E+10 | 0.182180E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178318E+10 | 0.176226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200852E+10 | 0.206460E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191054E+10 | 0.220761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198893E+10 | 0.250676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193994E+10 | 0.250861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195953E+10 | 0.202605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200852E+10 | 0.233431E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191054E+10 | 0.218330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196933E+10 | 0.211934E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191054E+10 | 0.194684E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195953E+10 | 0.183825E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233184E+11 | 0.253197E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178318E+10 | 0.176226E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200852E+10 | 0.250861E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.313351E+10 | 0.327442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283790E+10 | 0.317308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320108E+10 | 0.372473E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304061E+10 | 0.398671E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316730E+10 | 0.453591E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.309128E+10 | 0.455989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311662E+10 | 0.362988E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320108E+10 | 0.421898E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304061E+10 | 0.392932E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313351E+10 | 0.380611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304061E+10 | 0.349492E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311662E+10 | 0.328606E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371207E+11 | 0.456200E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283790E+10 | 0.317308E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.320108E+10 | 0.455989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170401E+10 | 0.170968E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154325E+10 | 0.165672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174075E+10 | 0.194298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165348E+10 | 0.207906E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172238E+10 | 0.236420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168104E+10 | 0.237436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169482E+10 | 0.189326E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174075E+10 | 0.219787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165348E+10 | 0.204847E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170401E+10 | 0.198490E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165348E+10 | 0.182282E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169482E+10 | 0.171495E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201863E+11 | 0.237893E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154325E+10 | 0.165672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174075E+10 | 0.237436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169695E+10 | 0.170190E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153686E+10 | 0.164997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173354E+10 | 0.193549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164664E+10 | 0.207204E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171525E+10 | 0.235673E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167408E+10 | 0.236685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168780E+10 | 0.188604E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173354E+10 | 0.218989E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164664E+10 | 0.204115E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169695E+10 | 0.197688E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164664E+10 | 0.181477E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168780E+10 | 0.170677E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201027E+11 | 0.236985E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153686E+10 | 0.164997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173354E+10 | 0.236685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170050E+10 | 0.170040E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154008E+10 | 0.165113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173717E+10 | 0.193814E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165008E+10 | 0.207727E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171884E+10 | 0.236179E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167758E+10 | 0.237310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169133E+10 | 0.188970E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173717E+10 | 0.219285E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165008E+10 | 0.204478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170050E+10 | 0.197601E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165008E+10 | 0.181380E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169133E+10 | 0.170430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201448E+11 | 0.237233E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154008E+10 | 0.165113E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173717E+10 | 0.237310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.193310E+10 | 0.187074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175073E+10 | 0.183116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197478E+10 | 0.216314E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187578E+10 | 0.231809E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195394E+10 | 0.261165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190705E+10 | 0.263528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192268E+10 | 0.210033E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197478E+10 | 0.242442E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.187578E+10 | 0.226346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193310E+10 | 0.215531E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187578E+10 | 0.198643E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192268E+10 | 0.186915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229002E+11 | 0.262292E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175073E+10 | 0.183116E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197478E+10 | 0.263528E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.466251E+10 | 0.00 | 0.00 | 0.00 | 0.124820E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.421846E+10 | 0.00 | 0.00 | 0.00 | 0.121208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.468101E+10 | 0.00 | 0.00 | 0.00 | 0.141305E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.451450E+10 | 0.00 | 0.00 | 0.00 | 0.150573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.466251E+10 | 0.00 | 0.00 | 0.00 | 0.163903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.453300E+10 | 0.00 | 0.00 | 0.00 | 0.161729E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.466251E+10 | 0.00 | 0.00 | 0.00 | 0.136773E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.467176E+10 | 0.00 | 0.00 | 0.00 | 0.148598E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.452375E+10 | 0.00 | 0.00 | 0.00 | 0.142513E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.466251E+10 | 0.00 | 0.00 | 0.00 | 0.137602E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.450524E+10 | 0.00 | 0.00 | 0.00 | 0.128561E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.468101E+10 | 0.00 | 0.00 | 0.00 | 0.125132E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.549788E+11 | 0.00 | 0.00 | 0.00 | 0.168272E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.421846E+10 | 0.00 | 0.00 | 0.00 | 0.121208E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.468101E+10 | 0.00 | 0.00 | 0.00 | 0.163903E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.203548E+10 | 0.00 | 0.00 | 0.00 | 0.603062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.184516E+10 | 0.00 | 0.00 | 0.00 | 0.581840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.206789E+10 | 0.00 | 0.00 | 0.00 | 0.675262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.199995E+10 | 0.00 | 0.00 | 0.00 | 0.713153E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.208465E+10 | 0.00 | 0.00 | 0.00 | 0.778903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.202692E+10 | 0.00 | 0.00 | 0.00 | 0.769543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.204789E+10 | 0.00 | 0.00 | 0.00 | 0.652361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.207863E+10 | 0.00 | 0.00 | 0.00 | 0.710056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199544E+10 | 0.00 | 0.00 | 0.00 | 0.678761E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.205017E+10 | 0.00 | 0.00 | 0.00 | 0.660566E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.198194E+10 | 0.00 | 0.00 | 0.00 | 0.618237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.203196E+10 | 0.00 | 0.00 | 0.00 | 0.604156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.242461E+11 | 0.00 | 0.00 | 0.00 | 0.804590E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.184516E+10 | 0.00 | 0.00 | 0.00 | 0.581840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.208465E+10 | 0.00 | 0.00 | 0.00 | 0.778903E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.197609E+10 | 0.00 | 0.00 | 0.00 | 0.496046E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178930E+10 | 0.00 | 0.00 | 0.00 | 0.482073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.201542E+10 | 0.00 | 0.00 | 0.00 | 0.568000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191711E+10 | 0.00 | 0.00 | 0.00 | 0.591490E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.199576E+10 | 0.00 | 0.00 | 0.00 | 0.655007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.194660E+10 | 0.00 | 0.00 | 0.00 | 0.651969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.196626E+10 | 0.00 | 0.00 | 0.00 | 0.533540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201542E+10 | 0.00 | 0.00 | 0.00 | 0.599698E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191711E+10 | 0.00 | 0.00 | 0.00 | 0.563752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.197609E+10 | 0.00 | 0.00 | 0.00 | 0.546706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191711E+10 | 0.00 | 0.00 | 0.00 | 0.511535E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.196626E+10 | 0.00 | 0.00 | 0.00 | 0.494375E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233985E+11 | 0.00 | 0.00 | 0.00 | 0.669419E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178930E+10 | 0.00 | 0.00 | 0.00 | 0.482073E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201542E+10 | 0.00 | 0.00 | 0.00 | 0.655007E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.198118E+10 | 0.00 | 0.00 | 0.00 | 0.498139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.179390E+10 | 0.00 | 0.00 | 0.00 | 0.484165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.202061E+10 | 0.00 | 0.00 | 0.00 | 0.570438E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.192204E+10 | 0.00 | 0.00 | 0.00 | 0.594344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.200089E+10 | 0.00 | 0.00 | 0.00 | 0.658344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.195161E+10 | 0.00 | 0.00 | 0.00 | 0.655165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.197132E+10 | 0.00 | 0.00 | 0.00 | 0.536446E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.202061E+10 | 0.00 | 0.00 | 0.00 | 0.602067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.192204E+10 | 0.00 | 0.00 | 0.00 | 0.566346E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198118E+10 | 0.00 | 0.00 | 0.00 | 0.549151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.192204E+10 | 0.00 | 0.00 | 0.00 | 0.513485E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.197132E+10 | 0.00 | 0.00 | 0.00 | 0.496145E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.234587E+11 | 0.00 | 0.00 | 0.00 | 0.672424E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.179390E+10 | 0.00 | 0.00 | 0.00 | 0.484165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.202061E+10 | 0.00 | 0.00 | 0.00 | 0.658344E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.196933E+10 | 0.00 | 0.00 | 0.00 | 0.492556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.178318E+10 | 0.00 | 0.00 | 0.00 | 0.478987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.200852E+10 | 0.00 | 0.00 | 0.00 | 0.564230E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.191054E+10 | 0.00 | 0.00 | 0.00 | 0.588361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.198893E+10 | 0.00 | 0.00 | 0.00 | 0.652247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.193994E+10 | 0.00 | 0.00 | 0.00 | 0.649079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.195953E+10 | 0.00 | 0.00 | 0.00 | 0.530565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.200852E+10 | 0.00 | 0.00 | 0.00 | 0.595372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191054E+10 | 0.00 | 0.00 | 0.00 | 0.560165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.196933E+10 | 0.00 | 0.00 | 0.00 | 0.542911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.191054E+10 | 0.00 | 0.00 | 0.00 | 0.507626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.195953E+10 | 0.00 | 0.00 | 0.00 | 0.490287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.233184E+11 | 0.00 | 0.00 | 0.00 | 0.665239E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.178318E+10 | 0.00 | 0.00 | 0.00 | 0.478987E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.200852E+10 | 0.00 | 0.00 | 0.00 | 0.652247E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.313351E+10 | 0.00 | 0.00 | 0.00 | 0.895727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.283790E+10 | 0.00 | 0.00 | 0.00 | 0.871655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.320108E+10 | 0.00 | 0.00 | 0.00 | 0.102817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.304061E+10 | 0.00 | 0.00 | 0.00 | 0.107137E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.316730E+10 | 0.00 | 0.00 | 0.00 | 0.118797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.309128E+10 | 0.00 | 0.00 | 0.00 | 0.118752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.311662E+10 | 0.00 | 0.00 | 0.00 | 0.959593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.320108E+10 | 0.00 | 0.00 | 0.00 | 0.108369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.304061E+10 | 0.00 | 0.00 | 0.00 | 0.101583E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.313351E+10 | 0.00 | 0.00 | 0.00 | 0.982988E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304061E+10 | 0.00 | 0.00 | 0.00 | 0.919782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.311662E+10 | 0.00 | 0.00 | 0.00 | 0.885949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.371207E+11 | 0.00 | 0.00 | 0.00 | 0.120903E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.283790E+10 | 0.00 | 0.00 | 0.00 | 0.871655E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.320108E+10 | 0.00 | 0.00 | 0.00 | 0.118797E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170401E+10 | 0.00 | 0.00 | 0.00 | 0.460062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154325E+10 | 0.00 | 0.00 | 0.00 | 0.447734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.174075E+10 | 0.00 | 0.00 | 0.00 | 0.527729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165348E+10 | 0.00 | 0.00 | 0.00 | 0.549886E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.172238E+10 | 0.00 | 0.00 | 0.00 | 0.609494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.168104E+10 | 0.00 | 0.00 | 0.00 | 0.608766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169482E+10 | 0.00 | 0.00 | 0.00 | 0.492476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.174075E+10 | 0.00 | 0.00 | 0.00 | 0.555591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165348E+10 | 0.00 | 0.00 | 0.00 | 0.521140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170401E+10 | 0.00 | 0.00 | 0.00 | 0.504385E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165348E+10 | 0.00 | 0.00 | 0.00 | 0.471960E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169482E+10 | 0.00 | 0.00 | 0.00 | 0.454849E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201863E+11 | 0.00 | 0.00 | 0.00 | 0.620407E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154325E+10 | 0.00 | 0.00 | 0.00 | 0.447734E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.174075E+10 | 0.00 | 0.00 | 0.00 | 0.609494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169695E+10 | 0.00 | 0.00 | 0.00 | 0.457895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153686E+10 | 0.00 | 0.00 | 0.00 | 0.445792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173354E+10 | 0.00 | 0.00 | 0.00 | 0.525531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164664E+10 | 0.00 | 0.00 | 0.00 | 0.547784E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171525E+10 | 0.00 | 0.00 | 0.00 | 0.607280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167408E+10 | 0.00 | 0.00 | 0.00 | 0.606543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168780E+10 | 0.00 | 0.00 | 0.00 | 0.490444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173354E+10 | 0.00 | 0.00 | 0.00 | 0.553347E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164664E+10 | 0.00 | 0.00 | 0.00 | 0.519040E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169695E+10 | 0.00 | 0.00 | 0.00 | 0.502165E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164664E+10 | 0.00 | 0.00 | 0.00 | 0.469746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168780E+10 | 0.00 | 0.00 | 0.00 | 0.452585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201027E+11 | 0.00 | 0.00 | 0.00 | 0.617815E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153686E+10 | 0.00 | 0.00 | 0.00 | 0.445792E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173354E+10 | 0.00 | 0.00 | 0.00 | 0.607280E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170050E+10 | 0.00 | 0.00 | 0.00 | 0.457643E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154008E+10 | 0.00 | 0.00 | 0.00 | 0.446188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173717E+10 | 0.00 | 0.00 | 0.00 | 0.526317E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165008E+10 | 0.00 | 0.00 | 0.00 | 0.549205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171884E+10 | 0.00 | 0.00 | 0.00 | 0.608646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167758E+10 | 0.00 | 0.00 | 0.00 | 0.608178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169133E+10 | 0.00 | 0.00 | 0.00 | 0.491411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173717E+10 | 0.00 | 0.00 | 0.00 | 0.554172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165008E+10 | 0.00 | 0.00 | 0.00 | 0.520017E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170050E+10 | 0.00 | 0.00 | 0.00 | 0.502084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165008E+10 | 0.00 | 0.00 | 0.00 | 0.469632E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169133E+10 | 0.00 | 0.00 | 0.00 | 0.452093E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201448E+11 | 0.00 | 0.00 | 0.00 | 0.618559E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154008E+10 | 0.00 | 0.00 | 0.00 | 0.446188E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173717E+10 | 0.00 | 0.00 | 0.00 | 0.608646E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.193310E+10 | 0.00 | 0.00 | 0.00 | 0.507602E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.175073E+10 | 0.00 | 0.00 | 0.00 | 0.499008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.197478E+10 | 0.00 | 0.00 | 0.00 | 0.591857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.187578E+10 | 0.00 | 0.00 | 0.00 | 0.618636E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195394E+10 | 0.00 | 0.00 | 0.00 | 0.681005E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.190705E+10 | 0.00 | 0.00 | 0.00 | 0.683301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.192268E+10 | 0.00 | 0.00 | 0.00 | 0.550838E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.197478E+10 | 0.00 | 0.00 | 0.00 | 0.619452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.187578E+10 | 0.00 | 0.00 | 0.00 | 0.581874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.193310E+10 | 0.00 | 0.00 | 0.00 | 0.553813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.187578E+10 | 0.00 | 0.00 | 0.00 | 0.519583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.192268E+10 | 0.00 | 0.00 | 0.00 | 0.500308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.229002E+11 | 0.00 | 0.00 | 0.00 | 0.690728E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.175073E+10 | 0.00 | 0.00 | 0.00 | 0.499008E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.197478E+10 | 0.00 | 0.00 | 0.00 | 0.683301E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14589387.75 | 0.137260E+11 | 0.00 | 104165.73 | 0.220444E+09 | 0.00 | 1946085.15 | 0.00 | 0.57 |
February | 10152400.75 | 0.139166E+11 | 0.00 | 92686.39 | 0.226430E+09 | 0.00 | 2003590.91 | 0.00 | 0.57 |
March | 0.00 | 0.165604E+11 | 0.00 | 0.00 | 0.249783E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
April | 0.00 | 0.205682E+11 | 0.00 | 0.00 | 0.237698E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
May | 0.00 | 0.242447E+11 | 0.00 | 0.00 | 0.248907E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
June | 0.00 | 0.240576E+11 | 0.00 | 0.00 | 0.211149E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
July | 0.00 | 0.174655E+11 | 0.00 | 0.00 | 0.479193E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
August | 0.00 | 0.217089E+11 | 0.00 | 0.00 | 0.399519E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
September | 0.00 | 0.204046E+11 | 0.00 | 0.00 | 0.409928E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
October | 0.00 | 0.190821E+11 | 0.00 | 0.00 | 0.460547E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
November | 140876.75 | 0.167561E+11 | 0.00 | 0.00 | 0.216135E+09 | 0.00 | 0.00 | 0.00 | 0.58 |
December | 7154749.75 | 0.145765E+11 | 0.00 | 269686.49 | 0.243044E+09 | 0.00 | 1145794.05 | 0.00 | 0.58 |
Annual Sum or Average | 32037415.00 | 0.223067E+12 | 0.00 | 466538.60 | 0.360278E+10 | 0.00 | 5095470.10 | 0.00 | 0.58 |
Minimum of Months | 0.00 | 0.137260E+11 | 0.00 | 0.00 | 0.211149E+09 | 0.00 | 0.00 | 0.00 | 0.57 |
Maximum of Months | 14589387.75 | 0.242447E+11 | 0.00 | 269686.49 | 0.479193E+09 | 0.00 | 2003590.91 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 607102.25 | 0.589027E+10 | 0.00 | 23518.62 | 0.200417E+09 | 0.00 | 69937.33 | 0.00 | 0.46 |
February | 0.00 | 0.595761E+10 | 0.00 | 0.00 | 0.203591E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
March | 0.00 | 0.706645E+10 | 0.00 | 0.00 | 0.227997E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
April | 0.00 | 0.870771E+10 | 0.00 | 0.00 | 0.213413E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
May | 0.00 | 0.103839E+11 | 0.00 | 0.00 | 0.209841E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
June | 0.00 | 0.104087E+11 | 0.00 | 0.00 | 0.188681E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
July | 0.00 | 0.738513E+10 | 0.00 | 0.00 | 0.376605E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.934091E+10 | 0.00 | 0.00 | 0.353239E+09 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.867708E+10 | 0.00 | 0.00 | 0.365234E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 0.00 | 0.813786E+10 | 0.00 | 0.00 | 0.405425E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
November | 0.00 | 0.722169E+10 | 0.00 | 0.00 | 0.193969E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
December | 860727.40 | 0.625187E+10 | 0.00 | 103902.57 | 0.221022E+09 | 0.00 | 17744.24 | 0.00 | 0.46 |
Annual Sum or Average | 1467829.65 | 0.954292E+11 | 0.00 | 127421.19 | 0.315943E+10 | 0.00 | 87681.56 | 0.00 | 0.47 |
Minimum of Months | 0.00 | 0.589027E+10 | 0.00 | 0.00 | 0.188681E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 860727.40 | 0.104087E+11 | 0.00 | 103902.57 | 0.405425E+09 | 0.00 | 69937.33 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 39521765.92 | 0.497089E+10 | 0.00 | 819795.79 | 0.356853E+09 | 0.00 | 4486616.21 | 0.00 | 0.46 |
February | 21759482.49 | 0.504378E+10 | 0.00 | 414790.88 | 0.359476E+09 | 0.00 | 930160.88 | 0.00 | 0.46 |
March | 1498727.23 | 0.616309E+10 | 0.00 | 46338.62 | 0.450878E+09 | 0.00 | 807251.85 | 0.00 | 0.47 |
April | 0.00 | 0.735661E+10 | 0.00 | 0.00 | 0.561788E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 212379.91 | 0.885102E+10 | 0.00 | 0.00 | 0.628568E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 148396.84 | 0.895209E+10 | 0.00 | 15.99 | 0.615162E+09 | 0.00 | 1934.31 | 0.00 | 0.47 |
July | 95454.18 | 0.624959E+10 | 0.00 | 0.00 | 0.500010E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 329295.00 | 0.814813E+10 | 0.00 | 0.00 | 0.592781E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 1846991.81 | 0.739838E+10 | 0.00 | 72364.32 | 0.580916E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 2912198.45 | 0.696107E+10 | 0.00 | 30352.92 | 0.550077E+09 | 0.00 | 77732.59 | 0.00 | 0.46 |
November | 12469356.62 | 0.605362E+10 | 0.00 | 327926.01 | 0.438269E+09 | 0.00 | 3399704.08 | 0.00 | 0.46 |
December | 21070955.93 | 0.521380E+10 | 0.00 | 585438.42 | 0.360434E+09 | 0.00 | 2638951.74 | 0.00 | 0.46 |
Annual Sum or Average | 0.101865E+09 | 0.813621E+11 | 0.00 | 2297022.96 | 0.599521E+10 | 0.00 | 12342351.66 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.497089E+10 | 0.00 | 0.00 | 0.356853E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 39521765.92 | 0.895209E+10 | 0.00 | 819795.79 | 0.628568E+09 | 0.00 | 4486616.21 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 40039186.23 | 0.498025E+10 | 0.00 | 823751.23 | 0.350769E+09 | 0.00 | 4392308.56 | 0.00 | 0.46 |
February | 21812224.29 | 0.505086E+10 | 0.00 | 413130.55 | 0.355967E+09 | 0.00 | 1181176.98 | 0.00 | 0.46 |
March | 1556783.72 | 0.617658E+10 | 0.00 | 45497.28 | 0.442678E+09 | 0.00 | 797368.75 | 0.00 | 0.47 |
April | 0.00 | 0.739515E+10 | 0.00 | 0.00 | 0.532984E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 123213.27 | 0.887199E+10 | 0.00 | 25.98 | 0.622002E+09 | 0.00 | 81131.20 | 0.00 | 0.47 |
June | 165159.12 | 0.898601E+10 | 0.00 | 0.00 | 0.593353E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
July | 89216.29 | 0.627481E+10 | 0.00 | 0.00 | 0.484750E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 190545.98 | 0.816755E+10 | 0.00 | 10.24 | 0.579035E+09 | 0.00 | 121964.49 | 0.00 | 0.47 |
September | 1814167.63 | 0.742358E+10 | 0.00 | 65842.59 | 0.563138E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 2065855.00 | 0.698376E+10 | 0.00 | 25173.00 | 0.533753E+09 | 0.00 | 901902.68 | 0.00 | 0.46 |
November | 9752628.13 | 0.606430E+10 | 0.00 | 327207.98 | 0.430122E+09 | 0.00 | 6118842.79 | 0.00 | 0.46 |
December | 18821766.61 | 0.522120E+10 | 0.00 | 591276.07 | 0.354652E+09 | 0.00 | 5253213.11 | 0.00 | 0.46 |
Annual Sum or Average | 96430746.28 | 0.815960E+11 | 0.00 | 2291914.91 | 0.584320E+10 | 0.00 | 18847908.55 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.498025E+10 | 0.00 | 0.00 | 0.350769E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 40039186.23 | 0.898601E+10 | 0.00 | 823751.23 | 0.622002E+09 | 0.00 | 6118842.79 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 38803320.78 | 0.495225E+10 | 0.00 | 816630.49 | 0.358407E+09 | 0.00 | 5307824.77 | 0.00 | 0.46 |
February | 21328070.08 | 0.502831E+10 | 0.00 | 407092.20 | 0.359450E+09 | 0.00 | 1241342.28 | 0.00 | 0.46 |
March | 1482924.23 | 0.613475E+10 | 0.00 | 50612.52 | 0.459318E+09 | 0.00 | 803816.65 | 0.00 | 0.47 |
April | 0.00 | 0.730760E+10 | 0.00 | 0.00 | 0.591915E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
May | 235279.13 | 0.881614E+10 | 0.00 | 0.00 | 0.646419E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
June | 153075.46 | 0.891781E+10 | 0.00 | 28.50 | 0.631536E+09 | 0.00 | 2275.81 | 0.00 | 0.47 |
July | 121896.31 | 0.622782E+10 | 0.00 | 0.00 | 0.503518E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
August | 332789.33 | 0.810062E+10 | 0.00 | 0.00 | 0.608307E+09 | 0.00 | 0.00 | 0.00 | 0.47 |
September | 1896352.66 | 0.735771E+10 | 0.00 | 77556.80 | 0.595206E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
October | 2610534.86 | 0.693017E+10 | 0.00 | 28402.45 | 0.553684E+09 | 0.00 | 333089.11 | 0.00 | 0.46 |
November | 13303138.68 | 0.601875E+10 | 0.00 | 319927.00 | 0.446315E+09 | 0.00 | 2463869.22 | 0.00 | 0.46 |
December | 21345599.09 | 0.518546E+10 | 0.00 | 577861.20 | 0.365782E+09 | 0.00 | 2252422.70 | 0.00 | 0.46 |
Annual Sum or Average | 0.101613E+09 | 0.809774E+11 | 0.00 | 2278111.17 | 0.611986E+10 | 0.00 | 12404640.56 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.495225E+10 | 0.00 | 0.00 | 0.358407E+09 | 0.00 | 0.00 | 0.00 | 0.46 |
Maximum of Months | 38803320.78 | 0.891781E+10 | 0.00 | 816630.49 | 0.646419E+09 | 0.00 | 5307824.77 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 52578286.71 | 0.950804E+10 | 0.00 | 907161.94 | 0.353468E+09 | 0.00 | 5138619.47 | 0.00 | 0.42 |
February | 13003797.59 | 0.966081E+10 | 0.00 | 110373.68 | 0.389163E+09 | 0.00 | 310937.18 | 0.00 | 0.42 |
March | 0.00 | 0.117046E+11 | 0.00 | 0.00 | 0.457767E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.140280E+11 | 0.00 | 0.00 | 0.553702E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.168570E+11 | 0.00 | 0.00 | 0.574265E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.172267E+11 | 0.00 | 0.00 | 0.506224E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.117721E+11 | 0.00 | 0.00 | 0.633636E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.154355E+11 | 0.00 | 0.00 | 0.694763E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 3797650.11 | 0.140202E+11 | 0.00 | 93876.58 | 0.684676E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 1090969.94 | 0.131642E+11 | 0.00 | 0.00 | 0.641321E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 8529020.33 | 0.115540E+11 | 0.00 | 379127.43 | 0.393783E+09 | 0.00 | 8449569.14 | 0.00 | 0.43 |
December | 10370287.53 | 0.980940E+10 | 0.00 | 470689.97 | 0.433585E+09 | 0.00 | 7646490.78 | 0.00 | 0.42 |
Annual Sum or Average | 89370012.21 | 0.154741E+12 | 0.00 | 1961229.59 | 0.631635E+10 | 0.00 | 21545616.57 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.950804E+10 | 0.00 | 0.00 | 0.353468E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 52578286.71 | 0.172267E+11 | 0.00 | 907161.94 | 0.694763E+09 | 0.00 | 8449569.14 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27210609.89 | 0.474834E+10 | 0.00 | 439319.72 | 0.186373E+09 | 0.00 | 1708063.25 | 0.00 | 0.42 |
February | 6279680.08 | 0.482844E+10 | 0.00 | 51298.64 | 0.198709E+09 | 0.00 | 198391.71 | 0.00 | 0.42 |
March | 0.00 | 0.584799E+10 | 0.00 | 0.00 | 0.236834E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.698053E+10 | 0.00 | 0.00 | 0.307186E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.839473E+10 | 0.00 | 0.00 | 0.311984E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.856431E+10 | 0.00 | 0.00 | 0.288012E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 42.50 | 0.587589E+10 | 0.00 | 4.06 | 0.321941E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
August | 0.00 | 0.767310E+10 | 0.00 | 0.00 | 0.379879E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 2153983.93 | 0.697577E+10 | 0.00 | 54465.59 | 0.365603E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 629026.36 | 0.655865E+10 | 0.00 | 0.00 | 0.334204E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 5379897.77 | 0.574898E+10 | 0.00 | 187776.10 | 0.218051E+09 | 0.00 | 3452016.56 | 0.00 | 0.43 |
December | 5250274.32 | 0.489216E+10 | 0.00 | 233637.29 | 0.228276E+09 | 0.00 | 3851680.92 | 0.00 | 0.42 |
Annual Sum or Average | 46903514.85 | 0.770889E+11 | 0.00 | 966501.41 | 0.337705E+10 | 0.00 | 9210152.44 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.474834E+10 | 0.00 | 0.00 | 0.186373E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 27210609.89 | 0.856431E+10 | 0.00 | 439319.72 | 0.379879E+09 | 0.00 | 3851680.92 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 27220465.45 | 0.473553E+10 | 0.00 | 436872.24 | 0.188494E+09 | 0.00 | 1631904.16 | 0.00 | 0.42 |
February | 6272935.53 | 0.481370E+10 | 0.00 | 52288.36 | 0.204021E+09 | 0.00 | 208731.52 | 0.00 | 0.42 |
March | 0.00 | 0.583357E+10 | 0.00 | 0.00 | 0.240681E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.696048E+10 | 0.00 | 0.00 | 0.315236E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.837610E+10 | 0.00 | 0.00 | 0.317489E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.854985E+10 | 0.00 | 0.00 | 0.289190E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 737.97 | 0.586347E+10 | 0.00 | 152.12 | 0.322542E+09 | 0.00 | 309.71 | 0.00 | 0.42 |
August | 0.00 | 0.765925E+10 | 0.00 | 0.00 | 0.379268E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 2147253.27 | 0.695621E+10 | 0.00 | 56455.43 | 0.371752E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 636094.24 | 0.653948E+10 | 0.00 | 0.00 | 0.338713E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 5386414.84 | 0.572832E+10 | 0.00 | 187183.74 | 0.224915E+09 | 0.00 | 3444862.75 | 0.00 | 0.43 |
December | 5243103.24 | 0.487201E+10 | 0.00 | 233196.55 | 0.236047E+09 | 0.00 | 3883313.41 | 0.00 | 0.42 |
Annual Sum or Average | 46907004.53 | 0.768880E+11 | 0.00 | 966148.44 | 0.342835E+10 | 0.00 | 9169121.56 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.473553E+10 | 0.00 | 0.00 | 0.188494E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 27220465.45 | 0.854985E+10 | 0.00 | 436872.24 | 0.379268E+09 | 0.00 | 3883313.41 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 26743258.67 | 0.472746E+10 | 0.00 | 430655.03 | 0.193971E+09 | 0.00 | 1683533.67 | 0.00 | 0.42 |
February | 6129926.54 | 0.481284E+10 | 0.00 | 50618.60 | 0.206389E+09 | 0.00 | 222096.51 | 0.00 | 0.42 |
March | 0.00 | 0.583571E+10 | 0.00 | 0.00 | 0.241490E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
April | 0.00 | 0.696984E+10 | 0.00 | 0.00 | 0.313987E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 0.00 | 0.837854E+10 | 0.00 | 0.00 | 0.322411E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
June | 0.00 | 0.855556E+10 | 0.00 | 0.00 | 0.293452E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 0.00 | 0.586143E+10 | 0.00 | 66.97 | 0.330067E+09 | 0.00 | 1039.47 | 0.00 | 0.42 |
August | 0.00 | 0.766008E+10 | 0.00 | 0.00 | 0.382859E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 2103966.18 | 0.695755E+10 | 0.00 | 57496.81 | 0.376454E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 641679.71 | 0.653635E+10 | 0.00 | 0.00 | 0.339025E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
November | 5992370.97 | 0.572075E+10 | 0.00 | 183444.03 | 0.229820E+09 | 0.00 | 2732248.49 | 0.00 | 0.43 |
December | 5951781.77 | 0.486630E+10 | 0.00 | 230483.19 | 0.237419E+09 | 0.00 | 3121374.21 | 0.00 | 0.42 |
Annual Sum or Average | 47562983.83 | 0.768824E+11 | 0.00 | 952764.61 | 0.346734E+10 | 0.00 | 7760292.35 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.472746E+10 | 0.00 | 0.00 | 0.193971E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 26743258.67 | 0.855556E+10 | 0.00 | 430655.03 | 0.382859E+09 | 0.00 | 3121374.21 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 32441334.12 | 0.488065E+10 | 0.00 | 569108.60 | 0.132049E+09 | 0.00 | 4817245.70 | 0.00 | 0.42 |
February | 12252450.14 | 0.498337E+10 | 0.00 | 213008.99 | 0.149108E+09 | 0.00 | 1811521.22 | 0.00 | 0.42 |
March | 882648.61 | 0.602514E+10 | 0.00 | 7595.03 | 0.140968E+09 | 0.00 | 109147.41 | 0.00 | 0.43 |
April | 0.00 | 0.721904E+10 | 0.00 | 0.00 | 0.196266E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
May | 1085001.76 | 0.859621E+10 | 0.00 | 80209.72 | 0.235764E+09 | 0.00 | 12120.78 | 0.00 | 0.43 |
June | 0.00 | 0.881315E+10 | 0.00 | 0.00 | 0.196105E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
July | 610258.24 | 0.608858E+10 | 0.00 | 3593.37 | 0.253128E+09 | 0.00 | 6168.62 | 0.00 | 0.42 |
August | 0.00 | 0.792926E+10 | 0.00 | 0.00 | 0.250040E+09 | 0.00 | 0.00 | 0.00 | 0.44 |
September | 2713219.29 | 0.723257E+10 | 0.00 | 56949.50 | 0.260391E+09 | 0.00 | 0.00 | 0.00 | 0.43 |
October | 805789.94 | 0.672598E+10 | 0.00 | 86.84 | 0.253591E+09 | 0.00 | 249772.95 | 0.00 | 0.43 |
November | 5884883.09 | 0.592028E+10 | 0.00 | 207074.09 | 0.151021E+09 | 0.00 | 3610855.80 | 0.00 | 0.43 |
December | 10452745.47 | 0.503817E+10 | 0.00 | 275587.86 | 0.172991E+09 | 0.00 | 4820365.22 | 0.00 | 0.42 |
Annual Sum or Average | 67128330.66 | 0.794524E+11 | 0.00 | 1413214.00 | 0.239142E+10 | 0.00 | 15437197.68 | 0.00 | 0.43 |
Minimum of Months | 0.00 | 0.488065E+10 | 0.00 | 0.00 | 0.132049E+09 | 0.00 | 0.00 | 0.00 | 0.42 |
Maximum of Months | 32441334.12 | 0.881315E+10 | 0.00 | 569108.60 | 0.260391E+09 | 0.00 | 4820365.22 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:27
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.244476E+12 | -0.392053E+11 | 0.00 | -0.827328E+11 | 0.286320E+12 |
February | 0.243191E+12 | -0.407260E+11 | 0.00 | -0.880753E+11 | 0.277379E+12 |
March | 0.318600E+12 | -0.497026E+11 | 0.00 | -0.109694E+12 | 0.324781E+12 |
April | 0.319078E+12 | -0.574834E+11 | 0.00 | -0.136461E+12 | 0.347120E+12 |
May | 0.319954E+12 | -0.674989E+11 | 0.00 | -0.163388E+12 | 0.389852E+12 |
June | 0.333462E+12 | -0.675291E+11 | 0.00 | -0.160156E+12 | 0.389676E+12 |
July | 0.276943E+12 | -0.486911E+11 | 0.00 | -0.118793E+12 | 0.316742E+12 |
August | 0.340155E+12 | -0.610616E+11 | 0.00 | -0.145726E+12 | 0.360764E+12 |
September | 0.269271E+12 | -0.562031E+11 | 0.00 | -0.136927E+12 | 0.339036E+12 |
October | 0.289289E+12 | -0.529120E+11 | 0.00 | -0.127303E+12 | 0.328106E+12 |
November | 0.237609E+12 | -0.456118E+11 | 0.00 | -0.106956E+12 | 0.302818E+12 |
December | 0.230201E+12 | -0.402705E+11 | 0.00 | -0.859647E+11 | 0.287890E+12 |
Annual Sum or Average | 0.342223E+13 | -0.626895E+12 | 0.00 | -0.146218E+13 | 0.395048E+13 |
Minimum of Months | 0.230201E+12 | -0.675291E+11 | 0.00 | -0.163388E+12 | 0.277379E+12 |
Maximum of Months | 0.340155E+12 | -0.392053E+11 | 0.00 | -0.827328E+11 | 0.389852E+12 |