Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930
Simulation Timestamp: 2023-10-16 08:40:56
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1294.58 | 619.32 | 619.32 |
Net Site Energy | 1294.58 | 619.32 | 619.32 |
Total Source Energy | 3597.39 | 1720.97 | 1720.97 |
Net Source Energy | 3597.39 | 1720.97 | 1720.97 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 241.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 40.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 64.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1053.32 | 241.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 241.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 40.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 64.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 241.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 40.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 236.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 64.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 163.21 | 115.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 503.90 | 115.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 163.21 | 115.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 503.90 | 115.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1053.319 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1053.319 | 100.00 |
Total On-Site and Utility Electric Sources | 1053.319 | 100.00 |
Total Electricity End Uses | 1053.319 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1341.83 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Latitude [deg] | 47.47 |
Longitude [deg] | -122.3 |
Elevation [m] | 122.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-16:40 | 26-DEC-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 169477.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 35599.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 7561.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 93658.55 | 169477.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 169477.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 35599.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 7561.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 261.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 127.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 383.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 749.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 203.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3335.86 | 261.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 125.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 358.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1595.86 | 125.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 125.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 60.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 358.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 97.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1595.86 | 125.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.05 |
SMSTORE1 DIRECT AIR | 1.10 |
SMSTORE2 DIRECT AIR | 1.10 |
SMSTORE3 DIRECT AIR | 1.10 |
SMSTORE4 DIRECT AIR | 1.10 |
LGSTORE2 DIRECT AIR | 1.96 |
SMSTORE5 DIRECT AIR | 0.999318 |
SMSTORE6 DIRECT AIR | 0.993420 |
SMSTORE7 DIRECT AIR | 0.984991 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 2.05 | 1.00 | 1.00 | 2.05 |
PSZ-AC_2:2 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC_3:3 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.000000 | 1.10 |
PSZ-AC_4:4 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC_5:5 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.10 | 1.00 | 1.00 | 1.10 |
PSZ-AC_6:6 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.00 | 1.000000 | 1.96 |
PSZ-AC_7:7 | 0.999318 | 0.999318 | 0.999318 | 0.999318 | 1.01 | 1.01 | 1.00 | 0.986030 | 1.01 |
PSZ-AC_8:8 | 0.993420 | 0.993420 | 0.993420 | 0.993420 | 1.01 | 1.01 | 1.00 | 0.986130 | 1.01 |
PSZ-AC_9:9 | 0.984991 | 0.984991 | 0.984991 | 0.984991 | 1.00 | 1.00 | 1.00 | 0.981832 | 1.00 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.07 | 1.07 | 1.00 | 0.982029 | 1.07 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.05 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.96 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.00 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.07 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.05 | 2190.07 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1216.74 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1218.06 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1221.75 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1212.98 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.96 | 2096.81 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1122.08 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1115.34 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.00 | 1110.72 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.07 | 1185.78 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.05 | 2.05 | 2.05 | 2.05 | 35452.55 | 58542.54 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18886.43 | 30975.21 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18904.86 | 31002.07 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18956.04 | 31077.09 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 18834.51 | 30898.59 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.96 | 34119.06 | 56577.74 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17572.77 | 28729.44 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 17479.06 | 28596.53 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.00 | 1.00 | 1.00 | 1.00 | 17414.86 | 28406.58 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.07 | 1.07 | 1.07 | 1.07 | 18287.69 | 29912.00 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.05 | 1.02 | 2.05 | 35452.55 | 17395.78 | 35452.55 | 0.800350 | 0.800350 |
PSZ-AC_2:2 COOLING COIL | 1.10 | 0.549488 | 1.10 | 18886.43 | 9283.88 | 18886.43 | 0.800140 | 0.800140 |
PSZ-AC_3:3 COOLING COIL | 1.10 | 0.550084 | 1.10 | 18904.86 | 9292.91 | 18904.86 | 0.800170 | 0.800170 |
PSZ-AC_4:4 COOLING COIL | 1.10 | 0.551749 | 1.10 | 18956.04 | 9318.01 | 18956.04 | 0.800290 | 0.800290 |
PSZ-AC_5:5 COOLING COIL | 1.10 | 0.547788 | 1.10 | 18834.51 | 9258.42 | 18834.51 | 0.800010 | 0.800010 |
PSZ-AC_6:6 COOLING COIL | 1.96 | 0.979773 | 1.96 | 34119.06 | 16743.48 | 34119.06 | 0.800530 | 0.800530 |
PSZ-AC_7:7 COOLING COIL | 1.01 | 0.506738 | 1.01 | 17572.77 | 8639.74 | 17572.77 | 0.801000 | 0.801000 |
PSZ-AC_8:8 COOLING COIL | 1.01 | 0.503696 | 1.01 | 17479.06 | 8593.78 | 17479.06 | 0.800760 | 0.800760 |
PSZ-AC_9:9 COOLING COIL | 1.00 | 0.501609 | 1.00 | 17414.86 | 8562.30 | 17414.86 | 0.800600 | 0.800600 |
PSZ-AC_10:10 COOLING COIL | 1.07 | 0.535504 | 1.07 | 18287.69 | 8988.67 | 18287.69 | 0.800420 | 0.800420 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 58542.54 |
PSZ-AC_2:2 HEATING COIL | 30975.21 |
PSZ-AC_3:3 HEATING COIL | 31002.07 |
PSZ-AC_4:4 HEATING COIL | 31077.09 |
PSZ-AC_5:5 HEATING COIL | 30898.59 |
PSZ-AC_6:6 HEATING COIL | 56577.74 |
PSZ-AC_7:7 HEATING COIL | 28729.44 |
PSZ-AC_8:8 HEATING COIL | 28596.53 |
PSZ-AC_9:9 HEATING COIL | 28406.58 |
PSZ-AC_10:10 HEATING COIL | 29912.00 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 11.40 | 8.10 | 5.40 | 4.50 | 5.80 | 8.30 | 10.90 | 13.00 | 15.60 | 17.70 | 18.80 | 15.10 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 | 47.47 | -122.32 | -8.00 | 122.00 | 99868 | 1.1870 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 11.22 | 14.30 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 35 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22911.05297 | 27493.26356 | 1.70558 | 2.04670 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 29.40000 | 8.82150E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 20158.13923 | 24189.76708 | 0.88150 | 1.05781 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12302.16706 | 14762.60047 | 0.91581 | 1.09898 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 29.40000 | 8.82150E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 9335.28968 | 11202.34762 | 0.40823 | 0.48988 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12315.51008 | 14778.61210 | 0.91681 | 1.10017 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9468.04630 | 11361.65556 | 0.41404 | 0.49685 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12352.78079 | 14823.33694 | 0.91958 | 1.10350 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9575.00667 | 11490.00800 | 0.41872 | 0.50246 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12264.11311 | 14716.93574 | 0.91298 | 1.09558 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9755.02665 | 11706.03197 | 0.42659 | 0.51191 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21935.40020 | 26322.48024 | 1.63296 | 1.95955 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 29.31333 | 8.82136E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 18963.16840 | 22755.80207 | 0.82927 | 0.99512 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11517.38935 | 13820.86722 | 0.83277 | 0.99932 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 10078.42631 | 12094.11158 | 0.44073 | 0.52888 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11451.02459 | 13741.22951 | 0.82785 | 0.99342 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 10073.44492 | 12088.13390 | 0.44051 | 0.52862 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11355.94469 | 13627.13362 | 0.82083 | 0.98499 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 10327.90194 | 12393.48233 | 0.45164 | 0.54197 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12105.07287 | 14526.08744 | 0.87647 | 1.05176 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 25.44800 | 8.81519E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12694.38807 | 15233.26569 | 0.55510 | 0.66612 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -4.20000 | 2.69032E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29773.41 | 2.04670 | 2.04670 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 36257.96 | 1.05781 | 1.05781 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15886.95 | 1.09898 | 1.09898 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 17249.50 | 0.48988 | 0.48988 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15901.97 | 1.10017 | 1.10017 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 17406.49 | 0.49685 | 0.49685 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15945.23 | 1.10350 | 1.10350 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 17532.98 | 0.50246 | 0.50246 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15840.64 | 1.09558 | 1.09558 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17745.86 | 0.51191 | 0.51191 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28611.83 | 1.95955 | 1.95955 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 34845.09 | 0.99512 | 0.99512 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14753.60 | 1.01348 | 1.01348 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 18128.28 | 0.52888 | 0.52888 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14673.16 | 1.00739 | 1.00739 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 18122.39 | 0.52862 | 0.52862 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14617.03 | 1.00322 | 1.00322 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 18423.30 | 0.54197 | 0.54197 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15389.40 | 1.07101 | 1.07101 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 21221.53 | 0.66612 | 0.66612 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.04670 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09898 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10017 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.10350 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.09558 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.95955 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99932 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99342 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.98499 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05176 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.04670 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.04670 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.04670 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.04670 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.04670 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.04670 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09898 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09898 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09898 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09898 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09898 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09898 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10017 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10017 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10017 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10017 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10017 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10017 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.10350 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.10350 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.10350 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.10350 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10350 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10350 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.09558 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.09558 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.09558 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.09558 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.09558 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.09558 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.95955 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.95955 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.95955 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.95955 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.95955 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.95955 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99932 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99932 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99932 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99932 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01348 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01348 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98603 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99342 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99342 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99342 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99342 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00739 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00739 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98613 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.98499 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.98499 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.98499 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.98499 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00322 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00322 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98183 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05176 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05176 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05176 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05176 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.07101 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.07101 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98203 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.04670 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.09898 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.10017 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.10350 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.09558 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.95955 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.01348 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.00739 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.00322 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.07101 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.04670 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.04670 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2190.06788 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.04670 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.04670 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.04670 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.04670 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.04670 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02335 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.04670 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 35452.55000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17395.78316 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 35452.55000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80035 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80035 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 35452.55000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58542.53884 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 58542.53884 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09898 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09898 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1216.74120 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09898 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09898 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09898 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09898 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09898 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54949 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09898 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18886.43000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9283.87923 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18886.43000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80014 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80014 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18886.43000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30975.20663 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 30975.20663 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10017 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10017 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1218.06109 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10017 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10017 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10017 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10017 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10017 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55008 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10017 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18904.86000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9292.91212 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18904.86000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80017 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80017 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18904.86000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31002.06518 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 31002.06518 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10350 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10350 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1221.74732 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10350 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10350 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10350 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10350 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10350 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55175 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10350 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18956.04000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9318.01066 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18956.04000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80029 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80029 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18956.04000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 31077.09210 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 31077.09210 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.09558 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.09558 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1212.97759 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.09558 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.09558 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.09558 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.09558 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.09558 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.54779 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.09558 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18834.51000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9258.42125 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18834.51000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80001 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80001 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18834.51000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30898.59119 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 30898.59119 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.95955 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.95955 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2096.80760 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.95955 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.95955 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.95955 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.95955 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.95955 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.97977 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.95955 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34119.06000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16743.48409 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 34119.06000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80053 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80053 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34119.06000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 56577.74303 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 56577.74303 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01348 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01348 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1122.07964 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01348 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01348 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01348 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01348 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01348 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50674 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01348 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17572.77000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8639.73768 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17572.77000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80100 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80100 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17572.77000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28729.44378 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 28729.44378 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00739 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00739 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1115.34366 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00739 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00739 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00739 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00739 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00739 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50370 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00739 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17479.06000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8593.78286 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17479.06000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80076 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80076 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17479.06000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28596.52631 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 28596.52631 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00322 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00322 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1110.72068 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00322 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00322 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00322 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00322 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00322 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50161 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00322 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17414.86000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8562.30455 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17414.86000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80060 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80060 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17414.86000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28406.58247 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 28406.58247 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.07101 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.07101 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1185.77690 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.07101 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.07101 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.07101 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.07101 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.07101 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53550 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.07101 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18287.69000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8988.67065 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18287.69000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80042 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80042 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18287.69000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29911.99957 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 29911.99957 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 33847.5 | 10.82 | 10.82 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 18024.7 | 11.08 | 11.08 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 18042.2 | 11.08 | 11.08 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 18090.8 | 11.07 | 11.07 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 17975.5 | 11.08 | 11.08 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 32582.3 | 10.83 | 10.83 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 16778.0 | 11.09 | 11.09 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 16689.1 | 11.09 | 11.09 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 16628.1 | 11.10 | 11.10 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 17448.0 | 11.06 | 11.06 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 3.2316252331E-002 | 0.1232936020 | Pass | Pass | 0.3575146237 | 2.2279069813 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.4177625515E-002 | 8.2287226705E-002 | Pass | Pass | 9.1153276035E-002 | 0.2467179539 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.2472249793E-002 | 0.1193424770 | Pass | Pass | 9.9126831115E-002 | 0.3095467665 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.8840634164E-002 | 0.1548325802 | Pass | Pass | 9.5709515941E-002 | 0.3545064556 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 4.3662096648E-002 | 0.1846366730 | Pass | Pass | 7.6781718286E-002 | 0.3123771526 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 5.9339322422E-002 | 0.2439216500 | Pass | Pass | 6.5372423178E-002 | 0.2856059762 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 5.8664935460E-002 | 0.2420670656 | Pass | Pass | 0.1159178702 | 0.8427511771 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.0379199261E-002 | 0.2484194228 | Pass | Pass | 8.4250312503E-002 | 0.4591316031 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 6.1166192262E-002 | 0.2555470595 | Pass | Pass | 6.3785462347E-002 | 0.2552601776 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.9505921299E-002 | 0.3329650997 | Pass | Pass | 4.9008434794E-002 | 0.1917958011 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3446.40 | 209.05 | 0.00 | 614.48 | 242.89 | 4512.83 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | -4.20 | 0.00 | -4.20 | Wetbulb [C] | 4.30 | 20.00 |
SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 29.40 | 10.40 | 18.30 | Wetbulb [C] | 4.20 | 350.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 22.00 | 23 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 16.00 | 20 | |||
Jul | 0.00 | 0 | |||
Aug | 24.00 | 18 | |||
Sep | 12.00 | 15 | |||
Oct | 61.00 | 41 | |||
Nov | 0.00 | 0 | |||
Dec | 45.00 | 41 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.143 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.204 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.55 | 83.55 | 121.12 | |
Exterior Lighting Total | 7723.26 | 121.12 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 35452.55 | 28374.45 | 7078.10 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18886.43 | 15111.79 | 3774.64 | 0.80 | 3.91 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18904.86 | 15127.10 | 3777.76 | 0.80 | 3.91 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18956.04 | 15170.33 | 3785.71 | 0.80 | 3.91 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18834.51 | 15067.80 | 3766.71 | 0.80 | 3.91 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34119.06 | 27313.33 | 6805.73 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17572.77 | 14075.79 | 3496.98 | 0.80 | 3.91 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17479.06 | 13996.53 | 3482.53 | 0.80 | 3.91 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17414.86 | 13942.34 | 3472.52 | 0.80 | 3.91 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18287.69 | 14637.83 | 3649.86 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 33847.5 | 10.82 | 10.82 | ||||
PSZ-AC_2:2 COOLING COIL | 18024.7 | 11.08 | 11.08 | ||||
PSZ-AC_3:3 COOLING COIL | 18042.2 | 11.08 | 11.08 | ||||
PSZ-AC_4:4 COOLING COIL | 18090.8 | 11.07 | 11.07 | ||||
PSZ-AC_5:5 COOLING COIL | 17975.5 | 11.08 | 11.08 | ||||
PSZ-AC_6:6 COOLING COIL | 32582.3 | 10.83 | 10.83 | ||||
PSZ-AC_7:7 COOLING COIL | 16778.0 | 11.09 | 11.09 | ||||
PSZ-AC_8:8 COOLING COIL | 16689.1 | 11.09 | 11.09 | ||||
PSZ-AC_9:9 COOLING COIL | 16628.1 | 11.10 | 11.10 | ||||
PSZ-AC_10:10 COOLING COIL | 17448.0 | 11.06 | 11.06 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 58542.54 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 30975.21 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 31002.07 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 31077.09 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 30898.59 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 56577.74 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 28729.44 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 28596.53 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 28406.58 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 29912.00 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.05 | 2190.07 | 1070.05 | 1.00 | 1.31 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1216.74 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1218.06 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1221.75 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1212.98 | 1107.16 | 1.00 | 1.38 | General | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.96 | 2096.81 | 1070.05 | 1.00 | 1.32 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1122.08 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1115.34 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.00 | 1110.72 | 1107.16 | 1.00 | 1.40 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.07 | 1185.78 | 1107.16 | 1.00 | 1.39 | General | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22911.05 | 27493.26 | 78.92 | 1.706 | 2.047 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00901 | 29.40 | 0.00882 | 0.411 | 0.00 |
SMSTORE1 | 12302.17 | 14762.60 | 84.75 | 0.916 | 1.099 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00898 | 29.40 | 0.00882 | 0.206 | 0.00 |
SMSTORE2 | 12315.51 | 14778.61 | 84.84 | 0.917 | 1.100 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00898 | 29.31 | 0.00882 | 0.206 | 0.00 |
SMSTORE3 | 12352.78 | 14823.34 | 85.10 | 0.920 | 1.103 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00898 | 29.31 | 0.00882 | 0.206 | 0.00 |
SMSTORE4 | 12264.11 | 14716.94 | 84.49 | 0.913 | 1.096 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00898 | 29.31 | 0.00882 | 0.206 | 0.00 |
LGSTORE2 | 21935.40 | 26322.48 | 75.56 | 1.633 | 1.960 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00904 | 29.31 | 0.00882 | 0.411 | 0.00 |
SMSTORE5 | 11517.39 | 13820.87 | 79.34 | 0.833 | 0.999 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00930 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE6 | 11451.02 | 13741.23 | 78.88 | 0.828 | 0.993 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00932 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE7 | 11355.94 | 13627.13 | 78.23 | 0.821 | 0.985 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00935 | 25.45 | 0.00882 | 0.206 | 0.00 |
SMSTORE8 | 12105.07 | 14526.09 | 83.39 | 0.876 | 1.052 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00924 | 25.45 | 0.00882 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 20158.14 | 24189.77 | 69.43 | 0.882 | 1.058 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00674 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE1 | 9335.29 | 11202.35 | 64.31 | 0.408 | 0.490 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00666 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE2 | 9468.05 | 11361.66 | 65.22 | 0.414 | 0.497 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00667 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE3 | 9575.01 | 11490.01 | 65.96 | 0.419 | 0.502 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00668 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE4 | 9755.03 | 11706.03 | 67.20 | 0.427 | 0.512 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00669 | -4.20 | 0.00269 | 0.206 | 0.00 |
LGSTORE2 | 18963.17 | 22755.80 | 65.32 | 0.829 | 0.995 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00677 | -4.20 | 0.00269 | 0.411 | 0.00 |
SMSTORE5 | 10078.43 | 12094.11 | 69.43 | 0.441 | 0.529 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE6 | 10073.44 | 12088.13 | 69.39 | 0.441 | 0.529 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE7 | 10327.90 | 12393.48 | 71.15 | 0.452 | 0.542 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00674 | -4.20 | 0.00269 | 0.206 | 0.00 |
SMSTORE8 | 12694.39 | 15233.27 | 87.45 | 0.555 | 0.666 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00677 | -4.20 | 0.00269 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.05 | 2.05 | 1.06 | 1.06 | 2.0467 | 2.0467 | 2.0467 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.10 | 1.10 | 0.49 | 0.49 | 1.0990 | 1.0990 | 1.0990 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.10 | 1.10 | 0.50 | 0.50 | 1.1002 | 1.1002 | 1.1002 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.10 | 1.10 | 0.50 | 0.50 | 1.1035 | 1.1035 | 1.1035 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.10 | 1.10 | 0.51 | 0.51 | 1.0956 | 1.0956 | 1.0956 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 1.96 | 1.96 | 1.00 | 1.00 | 1.9595 | 1.9595 | 1.9595 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.01 | 1.01 | 0.53 | 0.53 | 1.0135 | 0.9993 | 1.0135 | 0.9860 | 1.0000 |
PSZ-AC_8:8 | 1.01 | 1.01 | 0.53 | 0.53 | 1.0074 | 0.9934 | 1.0074 | 0.9861 | 1.0000 |
PSZ-AC_9:9 | 1.00 | 1.00 | 0.54 | 0.54 | 1.0032 | 0.9850 | 1.0032 | 0.9818 | 1.0000 |
PSZ-AC_10:10 | 1.07 | 1.07 | 0.67 | 0.67 | 1.0710 | 1.0518 | 1.0710 | 0.9820 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 35452.550 | 28374.448 | 2.046700 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 35452.55 | 32767.60 | 2.046700 | 25.88 | 17.29 | 0.00897563 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.1045 | 23.89 | 0.00901441 | 48.1171 | 22911.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 58542.539 | 58542.539 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 58542.54 | 58542.54 | 2.046702 | 16.02 | 10.69 | 0.00592197 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.1045 | 21.11 | 0.00673516 | 42.7274 | 20158.14 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 18886.430 | 15111.788 | 1.098980 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 18886.43 | 17516.32 | 1.098980 | 25.83 | 17.26 | 0.00895262 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 18.7209 | 23.89 | 0.00898283 | 47.9507 | 12302.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 30975.207 | 30975.207 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30975.21 | 30975.21 | 1.098976 | 16.37 | 10.83 | 0.00591322 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.7210 | 21.11 | 0.00665555 | 42.2273 | 9335.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 18904.860 | 15127.102 | 1.100170 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18904.86 | 17534.19 | 1.100170 | 25.83 | 17.26 | 0.00895231 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 18.7007 | 23.89 | 0.00898241 | 47.9485 | 12314.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 31002.065 | 31002.065 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31002.07 | 31002.07 | 1.100168 | 16.37 | 10.84 | 0.00592392 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.7007 | 21.11 | 0.00666773 | 42.3038 | 9468.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 18956.040 | 15170.329 | 1.103500 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18956.04 | 17583.98 | 1.103500 | 25.83 | 17.26 | 0.00895139 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 18.6443 | 23.89 | 0.00898117 | 47.9420 | 12351.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 31077.092 | 31077.092 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 31077.09 | 31077.09 | 1.103498 | 16.39 | 10.86 | 0.00593371 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.6443 | 21.11 | 0.00667700 | 42.3620 | 9575.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 18834.510 | 15067.796 | 1.095580 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 18834.51 | 17465.65 | 1.095580 | 25.84 | 17.26 | 0.00895363 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 18.7790 | 23.89 | 0.00898418 | 47.9578 | 12262.97 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 30898.591 | 30898.591 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30898.59 | 30898.59 | 1.095577 | 16.35 | 10.85 | 0.00594118 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 18.7791 | 21.11 | 0.00669281 | 42.4613 | 9755.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 34119.060 | 27313.331 | 1.959550 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 34119.06 | 31465.92 | 1.959550 | 25.93 | 17.32 | 0.00899110 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.9986 | 23.89 | 0.00903619 | 48.2317 | 21927.86 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 56577.743 | 56577.743 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 56577.74 | 56577.74 | 1.959547 | 15.79 | 10.58 | 0.00591548 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.9987 | 21.11 | 0.00677274 | 42.9622 | 18963.17 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17572.770 | 14075.789 | 1.013480 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17572.77 | 16239.24 | 1.013480 | 25.92 | 17.31 | 0.00897802 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.3003 | 23.89 | 0.00901790 | 48.1352 | 11342.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 28729.444 | 28729.444 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28729.44 | 28729.44 | 1.013477 | 15.97 | 10.64 | 0.00590145 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.3004 | 21.11 | 0.00671936 | 42.6279 | 10078.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 17479.060 | 13996.532 | 1.007390 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17479.06 | 16148.35 | 1.007390 | 25.93 | 17.31 | 0.00897991 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.4230 | 23.89 | 0.00902058 | 48.1493 | 11274.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 28596.526 | 28596.526 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28596.53 | 28596.53 | 1.007393 | 15.94 | 10.63 | 0.00589624 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.4230 | 21.11 | 0.00671902 | 42.6258 | 10073.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 17414.860 | 13942.337 | 1.003220 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17414.86 | 16086.05 | 1.003220 | 25.93 | 17.32 | 0.00898124 | 12.80 | 11.97 | 0.00850000 | 29.40 | 0.00882150 | 18.34 | 20.5079 | 23.89 | 0.00902247 | 48.1593 | 11227.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 28406.582 | 28406.582 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 28406.58 | 28406.58 | 1.003217 | 15.92 | 10.63 | 0.00590880 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 20.5080 | 21.11 | 0.00673912 | 42.7520 | 10327.90 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 18287.690 | 14637.833 | 1.071010 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 18287.69 | 16937.88 | 1.071010 | 25.76 | 17.24 | 0.00895884 | 12.80 | 11.97 | 0.00850000 | 28.88 | 0.00882066 | 18.17 | 19.2098 | 23.89 | 0.00899170 | 47.9973 | 11989.03 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 29912.000 | 29912.000 | -999.0 | -999.0 | -999.000 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 29912.00 | 29912.00 | 1.071009 | 16.25 | 10.85 | 0.00598250 | 40.00 | 21.01 | 0.00800000 | -4.20 | 0.00269032 | -4.20 | 19.2099 | 21.11 | 0.00676530 | 42.9184 | 12694.39 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 35452.550 | 28374.448 | 2.046700 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5252 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.046702 | 2.42941639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 35452.55 | 32767.60 | 1.0000 | 2.42941404 | 2.046700 | 25.88 | 17.29 | 0.00897563 | 48883.2 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35452.55 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 20.1045 | 23.89 | 0.00901441 | 23.89 | 0.00901441 | 48.1171 | 22911.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58542.539 | 58542.539 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.046702 | 2.42941639 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 58542.54 | 58542.54 | 1.0000 | 2.42941639 | 2.046702 | 16.02 | 10.69 | 0.00592197 | 31083.5 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58542.54 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 20.1045 | 21.11 | 0.00673516 | 21.11 | 0.00673516 | 42.7274 | 20158.14 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18886.430 | 15111.788 | 1.098980 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4825 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.098976 | 1.30447473 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 18886.43 | 17516.32 | 1.0000 | 1.30447913 | 1.098980 | 25.83 | 17.26 | 0.00895262 | 48778.0 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18886.43 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 18.7209 | 23.89 | 0.00898283 | 23.89 | 0.00898283 | 47.9507 | 12302.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30975.207 | 30975.207 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.098976 | 1.30447473 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30975.21 | 30975.21 | 1.0000 | 1.30447473 | 1.098976 | 16.37 | 10.83 | 0.00591322 | 31417.2 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30975.21 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.7210 | 21.11 | 0.00665555 | 21.11 | 0.00665555 | 42.2273 | 9335.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18904.860 | 15127.102 | 1.100170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4819 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.100168 | 1.30588979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18904.86 | 17534.19 | 1.0000 | 1.30589165 | 1.100170 | 25.83 | 17.26 | 0.00895231 | 48776.1 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18904.86 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 18.7007 | 23.89 | 0.00898241 | 23.89 | 0.00898241 | 47.9485 | 12314.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31002.065 | 31002.065 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.100168 | 1.30588979 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31002.07 | 31002.07 | 1.0000 | 1.30588979 | 1.100168 | 16.37 | 10.84 | 0.00592392 | 31449.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31002.07 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.7007 | 21.11 | 0.00666773 | 21.11 | 0.00666773 | 42.3038 | 9468.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18956.040 | 15170.329 | 1.103500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4802 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.103498 | 1.30984181 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18956.04 | 17583.98 | 1.0000 | 1.30984433 | 1.103500 | 25.83 | 17.26 | 0.00895139 | 48770.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18956.04 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 18.6443 | 23.89 | 0.00898117 | 23.89 | 0.00898117 | 47.9420 | 12351.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 31077.092 | 31077.092 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.103498 | 1.30984181 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 31077.09 | 31077.09 | 1.0000 | 1.30984181 | 1.103498 | 16.39 | 10.86 | 0.00593371 | 31488.8 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31077.09 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.6443 | 21.11 | 0.00667700 | 21.11 | 0.00667700 | 42.3620 | 9575.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18834.510 | 15067.796 | 1.095580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4843 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.095577 | 1.30043974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 18834.51 | 17465.65 | 1.0000 | 1.30044336 | 1.095580 | 25.84 | 17.26 | 0.00895363 | 48783.9 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18834.51 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 18.7790 | 23.89 | 0.00898418 | 23.89 | 0.00898418 | 47.9578 | 12262.97 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30898.591 | 30898.591 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.095577 | 1.30043974 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30898.59 | 30898.59 | 1.0000 | 1.30043974 | 1.095577 | 16.35 | 10.85 | 0.00594118 | 31473.1 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30898.59 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 18.7791 | 21.11 | 0.00669281 | 21.11 | 0.00669281 | 42.4613 | 9755.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34119.060 | 27313.331 | 1.959550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5540 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.959547 | 2.32596387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 34119.06 | 31465.92 | 1.0000 | 2.32596779 | 1.959550 | 25.93 | 17.32 | 0.00899110 | 48973.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34119.06 | 29.40 | 0.00882150 | 18.34 | 0.41147883 | 20.9986 | 23.89 | 0.00903619 | 23.89 | 0.00903619 | 48.2317 | 21927.86 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 56577.743 | 56577.743 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.959547 | 2.32596387 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 56577.74 | 56577.74 | 1.0000 | 2.32596387 | 1.959547 | 15.79 | 10.58 | 0.00591548 | 30837.6 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 56577.74 | -4.20 | 0.00269032 | -4.20 | 0.41147883 | 20.9987 | 21.11 | 0.00677274 | 21.11 | 0.00677274 | 42.9622 | 18963.17 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17572.770 | 14075.789 | 1.013480 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5297 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013477 | 1.20298757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17572.77 | 16239.24 | 1.0000 | 1.20299142 | 1.013480 | 25.92 | 17.31 | 0.00897802 | 48931.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17572.77 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 20.3003 | 23.89 | 0.00901790 | 23.89 | 0.00901790 | 48.1352 | 11342.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28729.444 | 28729.444 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013477 | 1.20298757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28729.44 | 28729.44 | 1.0000 | 1.20298757 | 1.013477 | 15.97 | 10.64 | 0.00590145 | 30981.4 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28729.44 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.3004 | 21.11 | 0.00671936 | 21.11 | 0.00671936 | 42.6279 | 10078.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17479.060 | 13996.532 | 1.007390 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5332 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007393 | 1.19576589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17479.06 | 16148.35 | 1.0000 | 1.19576265 | 1.007390 | 25.93 | 17.31 | 0.00897991 | 48943.6 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17479.06 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 20.4230 | 23.89 | 0.00902058 | 23.89 | 0.00902058 | 48.1493 | 11274.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28596.526 | 28596.526 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.007393 | 1.19576589 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28596.53 | 28596.53 | 1.0000 | 1.19576589 | 1.007393 | 15.94 | 10.63 | 0.00589624 | 30936.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28596.53 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.4230 | 21.11 | 0.00671902 | 21.11 | 0.00671902 | 42.6258 | 10073.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17414.860 | 13942.337 | 1.003220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.5357 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.003217 | 1.19080956 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17414.86 | 16086.05 | 1.0000 | 1.19081289 | 1.003220 | 25.93 | 17.32 | 0.00898124 | 48951.8 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17414.86 | 29.40 | 0.00882150 | 18.34 | 0.20573941 | 20.5079 | 23.89 | 0.00902247 | 23.89 | 0.00902247 | 48.1593 | 11227.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28406.582 | 28406.582 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.003217 | 1.19080956 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 28406.58 | 28406.58 | 1.0000 | 1.19080956 | 1.003217 | 15.92 | 10.63 | 0.00590880 | 30946.7 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28406.58 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 20.5080 | 21.11 | 0.00673912 | 21.11 | 0.00673912 | 42.7520 | 10327.90 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18287.690 | 14637.833 | 1.071010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.4940 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.071009 | 1.27127773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SEATTLE SEATTLE TACOMA INTL A ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 18287.69 | 16937.88 | 1.0000 | 1.27127900 | 1.071010 | 25.76 | 17.24 | 0.00895884 | 48719.3 | 12.80 | 11.97 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18287.69 | 28.88 | 0.00882066 | 18.17 | 0.20573941 | 19.2098 | 23.89 | 0.00899170 | 23.89 | 0.00899170 | 47.9973 | 11989.03 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29912.000 | 29912.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1870 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.071009 | 1.27127773 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SEATTLE SEATTLE TACOMA INTL A ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 29912.00 | 29912.00 | 1.0000 | 1.27127773 | 1.071009 | 16.25 | 10.85 | 0.00598250 | 31466.3 | 40.00 | 21.01 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29912.00 | -4.20 | 0.00269032 | -4.20 | 0.20573941 | 19.2099 | 21.11 | 0.00676530 | 21.11 | 0.00676530 | 42.9184 | 12694.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.05 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.10 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.10 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.10 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.10 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.96 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.00 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.07 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1769.17 | 3547.17 | 483.67 |
SMSTORE1 | 1490.50 | 3121.83 | 72.17 |
SMSTORE2 | 1306.50 | 2479.50 | 153.83 |
SMSTORE3 | 1331.67 | 2523.33 | 196.17 |
SMSTORE4 | 1328.00 | 2613.33 | 259.67 |
LGSTORE2 | 1281.83 | 2523.50 | 443.83 |
SMSTORE5 | 1204.50 | 2565.50 | 452.50 |
SMSTORE6 | 1207.33 | 2611.50 | 478.83 |
SMSTORE7 | 1269.00 | 2714.33 | 594.00 |
SMSTORE8 | 1681.50 | 2886.17 | 1088.17 |
Facility | 2903.33 | 4118.67 | 1341.83 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 4.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.33 | 0.00 | 0.00 | 0.00 |
Facility | 5.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.218 | 0.230 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 1.181 | 0.245 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.316 | 0.320 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.310 | 0.320 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.285 | 0.320 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 1.222 | 0.307 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.238 | 0.341 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.226 | 0.341 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.201 | 0.341 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.194 | 0.359 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.805 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 12610579.61 | 0.00 | 12610579.61 | 2751627.34 | 15362206.95 | 12976396.34 | 3179.42 | 3676.48 | 1904.10 | 0.00 |
SMSTORE1 | 6105432.07 | 0.00 | 6105432.07 | 1379735.90 | 7485167.97 | 6488198.17 | 4083.61 | 2496.49 | 2179.90 | 0.00 |
SMSTORE2 | 5122567.91 | 0.00 | 5122567.91 | 1417116.89 | 6539684.80 | 6488198.17 | 4365.00 | 2943.32 | 1451.68 | 0.00 |
SMSTORE3 | 5102345.15 | 0.00 | 5102345.15 | 1417116.89 | 6519462.04 | 6488198.17 | 4365.00 | 2976.37 | 1418.63 | 0.00 |
SMSTORE4 | 5004985.51 | 0.00 | 5004985.51 | 1417116.89 | 6422102.40 | 6488198.17 | 4365.00 | 3046.24 | 1348.76 | 0.00 |
LGSTORE2 | 8728802.24 | 0.00 | 8728802.24 | 2601776.73 | 11330578.97 | 12976396.34 | 4730.00 | 2851.53 | 1178.47 | 0.00 |
SMSTORE5 | 4421917.53 | 0.00 | 4421917.53 | 1426859.02 | 5848776.55 | 6488198.17 | 4730.00 | 2862.03 | 1167.97 | 0.00 |
SMSTORE6 | 4379871.79 | 0.00 | 4379871.79 | 1426859.02 | 5806730.82 | 6488198.17 | 4730.00 | 2894.35 | 1135.65 | 0.00 |
SMSTORE7 | 4290466.26 | 0.00 | 4290466.26 | 1426859.02 | 5717325.28 | 6488198.17 | 4730.00 | 2964.97 | 1065.03 | 0.00 |
SMSTORE8 | 4265633.08 | 0.00 | 4265633.08 | 1741640.55 | 6007273.63 | 6488198.17 | 4730.00 | 3072.57 | 957.43 | 0.00 |
Total Facility | 60032601.15 | 0.00 | 60032601.15 | 17006708.25 | 77039309.40 | 77858378.04 | 4730.00 | 4366.07 | 2358.67 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5998 | 0.0000 | 0.5998 | 0.1134 | 0.7132 | 0.4115 | 259.42 | 3676.48 | 1904.10 |
SMSTORE1 | 0.2904 | 0.0000 | 0.2904 | 0.0605 | 0.3509 | 0.2057 | 1163.61 | 2496.49 | 2179.90 |
SMSTORE2 | 0.3238 | 0.0000 | 0.3238 | 0.0789 | 0.4027 | 0.2057 | 0.00 | 2943.32 | 1451.68 |
SMSTORE3 | 0.3225 | 0.0000 | 0.3225 | 0.0789 | 0.4014 | 0.2057 | 0.00 | 2976.37 | 1418.63 |
SMSTORE4 | 0.3163 | 0.0000 | 0.3163 | 0.0789 | 0.3952 | 0.2057 | 0.00 | 3046.24 | 1348.76 |
LGSTORE2 | 0.6017 | 0.0000 | 0.6017 | 0.1515 | 0.7532 | 0.4115 | 0.00 | 2851.53 | 1178.47 |
SMSTORE5 | 0.3048 | 0.0000 | 0.3048 | 0.0842 | 0.3889 | 0.2057 | 0.00 | 2862.03 | 1167.97 |
SMSTORE6 | 0.3019 | 0.0000 | 0.3019 | 0.0842 | 0.3860 | 0.2057 | 0.00 | 2894.35 | 1135.65 |
SMSTORE7 | 0.2957 | 0.0000 | 0.2957 | 0.0842 | 0.3799 | 0.2057 | 0.00 | 2964.97 | 1065.03 |
SMSTORE8 | 0.2940 | 0.0000 | 0.2940 | 0.0886 | 0.3826 | 0.2057 | 0.00 | 3072.57 | 957.43 |
Total Facility | 3.6509 | 0.0000 | 3.6509 | 0.9032 | 4.5541 | 2.4689 | 1268.77 | 4366.07 | 2358.67 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 17767639.82 | 0.00 | 17767639.82 | 12976396.34 | 3178.56 | 0.17 | 5581.28 | 0.00 |
PSZ-AC_2:2 | 8602230.85 | 0.00 | 8602230.85 | 6488198.17 | 4073.86 | 1.83 | 4684.31 | 0.00 |
PSZ-AC_3:3 | 7217427.30 | 0.00 | 7217427.30 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 7188934.50 | 0.00 | 7188934.50 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 7051759.92 | 0.00 | 7051759.92 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 12298420.78 | 0.00 | 12298420.78 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 6230247.96 | 0.00 | 6230247.96 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 6171007.75 | 0.00 | 6171007.75 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 6045040.08 | 0.00 | 6045040.08 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 6010051.45 | 0.00 | 6010051.45 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.8451 | 0.0000 | 0.8451 | 0.4115 | 258.56 | 0.17 | 5581.28 |
PSZ-AC_2:2 | 0.4092 | 0.0000 | 0.4092 | 0.2057 | 1153.86 | 1.83 | 4684.31 |
PSZ-AC_3:3 | 0.4562 | 0.0000 | 0.4562 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.4544 | 0.0000 | 0.4544 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.4457 | 0.0000 | 0.4457 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.8477 | 0.0000 | 0.8477 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.4294 | 0.0000 | 0.4294 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.4254 | 0.0000 | 0.4254 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.4167 | 0.0000 | 0.4167 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.4143 | 0.0000 | 0.4143 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4378.22 | 1222.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3283.61 | 1745.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3512.94 | 882.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3540.51 | 854.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3592.14 | 802.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3378.99 | 651.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3387.64 | 642.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3410.65 | 619.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3453.13 | 576.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3516.35 | 513.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.8122 | 1.1290 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.4523 | 0.5184 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.4199 | 0.6010 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.4180 | 0.6057 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.4108 | 0.6026 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.7927 | 1.1342 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.4001 | 0.5851 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3965 | 0.5851 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3888 | 0.5846 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3866 | 0.6043 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
ElectricityPurchased:Plant | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
Cogeneration:ElectricityPurchased | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
General:Cogeneration:ElectricityPurchased | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
ElectricityNet:Plant | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
Cogeneration:ElectricityNet | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
General:Cogeneration:ElectricityNet | 1053.32 | 3178.87 | 15-JAN-08:00 | 93658.55 | 10-AUG-16:40 |
Electricity:HVAC | 276.79 | 0.00 | 01-JAN-00:10 | 49600.17 | 29-AUG-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 40.22 | 0.00 | 01-JAN-00:10 | 35909.85 | 29-AUG-15:00 |
General:Cooling:Electricity | 40.22 | 0.00 | 01-JAN-00:10 | 35909.85 | 29-AUG-15:00 |
Fans:Electricity | 236.57 | 0.00 | 01-JAN-00:10 | 13690.32 | 01-JAN-09:30 |
General:Fans:Electricity | 236.57 | 0.00 | 01-JAN-00:10 | 13690.32 | 01-JAN-09:30 |
ExteriorLights:Electricity | 121.12 | 0.00 | 01-JAN-08:10 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.12 | 0.00 | 01-JAN-08:10 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 64.38 | 1218.00 | 02-JAN-08:10 | 12629.38 | 03-FEB-13:20 |
WaterSystems:Electricity | 64.38 | 1218.00 | 02-JAN-08:10 | 12629.38 | 03-FEB-13:20 |
Water Heater:WaterSystems:Electricity | 64.38 | 1218.00 | 02-JAN-08:10 | 12629.38 | 03-FEB-13:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 241.26 | 0.00 | 01-JAN-00:10 | 169477.83 | 26-DEC-09:10 |
NaturalGas:HVAC | 241.26 | 0.00 | 01-JAN-00:10 | 169477.83 | 26-DEC-09:10 |
Heating:NaturalGas | 241.26 | 0.00 | 01-JAN-00:10 | 169477.83 | 26-DEC-09:10 |
General:Heating:NaturalGas | 241.26 | 0.00 | 01-JAN-00:10 | 169477.83 | 26-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 751.18 | 0.00 | 01-JAN-00:10 | 224479.93 | 26-DEC-09:10 |
EnergyTransfer:Building | 403.75 | 0.00 | 01-JAN-00:10 | 89105.71 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE1 | 85.03 | 0.00 | 01-JAN-00:10 | 18086.19 | 26-DEC-09:10 |
Heating:EnergyTransfer | 66.85 | 0.00 | 01-JAN-00:10 | 85384.44 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 8.59 | 0.00 | 01-JAN-00:10 | 15899.20 | 19-FEB-09:10 |
General:Heating:EnergyTransfer | 66.85 | 0.00 | 01-JAN-00:10 | 85384.44 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 8.59 | 0.00 | 01-JAN-00:10 | 15899.20 | 19-FEB-09:10 |
Cooling:EnergyTransfer | 336.90 | 0.00 | 01-JAN-00:10 | 89105.71 | 10-AUG-16:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 76.44 | 0.00 | 01-JAN-00:10 | 15404.29 | 10-AUG-16:20 |
General:Cooling:EnergyTransfer | 336.90 | 0.00 | 01-JAN-00:10 | 89105.71 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 76.44 | 0.00 | 01-JAN-00:10 | 15404.29 | 10-AUG-16:20 |
EnergyTransfer:Zone:SMSTORE1 | 46.83 | 0.00 | 01-JAN-00:10 | 12047.81 | 08-AUG-22:00 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.37 | 0.00 | 01-JAN-00:10 | 4787.80 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.37 | 0.00 | 01-JAN-00:10 | 4787.80 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 44.46 | 0.00 | 01-JAN-00:10 | 12047.81 | 08-AUG-22:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 44.46 | 0.00 | 01-JAN-00:10 | 12047.81 | 08-AUG-22:00 |
EnergyTransfer:Zone:SMSTORE2 | 35.16 | 0.00 | 01-JAN-00:10 | 8405.94 | 16-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.50 | 0.00 | 01-JAN-00:10 | 7464.97 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.50 | 0.00 | 01-JAN-00:10 | 7464.97 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 31.66 | 0.00 | 01-JAN-00:10 | 7841.63 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 31.66 | 0.00 | 01-JAN-00:10 | 7841.63 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE3 | 34.63 | 0.00 | 01-JAN-00:10 | 8672.39 | 26-DEC-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.01 | 0.00 | 01-JAN-00:10 | 8023.92 | 16-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 4.01 | 0.00 | 01-JAN-00:10 | 8023.92 | 16-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 30.62 | 0.00 | 01-JAN-00:10 | 7855.28 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 30.62 | 0.00 | 01-JAN-00:10 | 7855.28 | 10-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE4 | 33.17 | 0.00 | 01-JAN-00:10 | 9579.84 | 17-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 4.80 | 0.00 | 01-JAN-00:10 | 8654.99 | 17-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 4.80 | 0.00 | 01-JAN-00:10 | 8654.99 | 17-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 28.37 | 0.00 | 01-JAN-00:10 | 7724.23 | 10-AUG-16:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 28.37 | 0.00 | 01-JAN-00:10 | 7724.23 | 10-AUG-16:10 |
EnergyTransfer:Zone:LGSTORE2 | 55.27 | 0.00 | 01-JAN-00:10 | 17497.47 | 18-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 9.85 | 0.00 | 01-JAN-00:10 | 16957.06 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 9.85 | 0.00 | 01-JAN-00:10 | 16957.06 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 45.42 | 0.00 | 01-JAN-00:10 | 14034.18 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 45.42 | 0.00 | 01-JAN-00:10 | 14034.18 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE5 | 28.19 | 0.00 | 01-JAN-00:10 | 9101.50 | 02-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 5.84 | 0.00 | 01-JAN-00:10 | 8970.80 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 5.84 | 0.00 | 01-JAN-00:10 | 8970.80 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.36 | 0.00 | 01-JAN-00:10 | 7305.64 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 22.36 | 0.00 | 01-JAN-00:10 | 7305.64 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE6 | 27.72 | 0.00 | 01-JAN-00:10 | 9144.18 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 6.13 | 0.00 | 01-JAN-00:10 | 9105.43 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 6.13 | 0.00 | 01-JAN-00:10 | 9105.43 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 21.59 | 0.00 | 01-JAN-00:10 | 7244.47 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 21.59 | 0.00 | 01-JAN-00:10 | 7244.47 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE7 | 27.04 | 0.00 | 01-JAN-00:10 | 10075.95 | 26-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 7.47 | 0.00 | 01-JAN-00:10 | 9977.67 | 26-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 7.47 | 0.00 | 01-JAN-00:10 | 9977.67 | 26-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 19.57 | 0.00 | 01-JAN-00:10 | 7174.25 | 10-AUG-14:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 19.57 | 0.00 | 01-JAN-00:10 | 7174.25 | 10-AUG-14:50 |
EnergyTransfer:Zone:SMSTORE8 | 30.70 | 0.00 | 01-JAN-00:10 | 12767.67 | 16-JAN-10:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 14.30 | 0.00 | 01-JAN-00:10 | 12767.67 | 16-JAN-10:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 14.30 | 0.00 | 01-JAN-00:10 | 12767.67 | 16-JAN-10:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.41 | 0.00 | 01-JAN-00:10 | 7583.27 | 10-AUG-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 16.41 | 0.00 | 01-JAN-00:10 | 7583.27 | 10-AUG-14:40 |
EnergyTransfer:HVAC | 347.42 | 0.00 | 01-JAN-00:10 | 135582.26 | 26-DEC-09:10 |
HeatingCoils:EnergyTransfer | 193.01 | 0.00 | 01-JAN-00:10 | 135582.26 | 26-DEC-09:10 |
CoolingCoils:EnergyTransfer | 154.42 | 0.00 | 01-JAN-00:10 | 134312.79 | 29-AUG-14:50 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 8.586 | -76.443 | 0.000 | 0.000 | 25.090 | 106.728 | 26.357 | 21.080 | 0.000 | 0.453 | 0.002 | 0.000 | -9.407 | 0.000 | -32.082 | -70.363 |
SMSTORE1 | 0.000 | 0.000 | 2.373 | -44.461 | 0.000 | 0.000 | 12.294 | 62.296 | 13.179 | 10.422 | 0.000 | 0.246 | 0.001 | 0.000 | -4.999 | 0.000 | -16.147 | -35.204 |
SMSTORE2 | 0.000 | 0.000 | 3.505 | -31.659 | 0.000 | 0.000 | 7.499 | 44.966 | 10.467 | 10.414 | 0.000 | 0.240 | 0.001 | 0.000 | -4.933 | 0.000 | -16.543 | -23.957 |
SMSTORE3 | 0.000 | 0.000 | 4.014 | -30.618 | 0.000 | 0.000 | 7.515 | 44.966 | 10.467 | 10.431 | 0.000 | 0.240 | 0.002 | 0.000 | -4.868 | 0.000 | -16.449 | -25.698 |
SMSTORE4 | 0.000 | 0.000 | 4.798 | -28.372 | 0.000 | 0.000 | 7.541 | 44.966 | 10.467 | 10.460 | 0.000 | 0.240 | 0.000 | 0.000 | -4.794 | 0.000 | -16.315 | -28.992 |
LGSTORE2 | 0.000 | 0.000 | 9.849 | -45.417 | 0.000 | 0.000 | 26.016 | 51.668 | 19.261 | 21.057 | 0.000 | 0.432 | 0.001 | 0.000 | -9.227 | 0.000 | -29.652 | -43.988 |
SMSTORE5 | 0.000 | 0.000 | 5.837 | -22.355 | 0.000 | 0.000 | 13.015 | 26.679 | 9.631 | 10.516 | 0.000 | 0.240 | 0.000 | 0.000 | -4.611 | 0.000 | -16.173 | -22.779 |
SMSTORE6 | 0.000 | 0.000 | 6.130 | -21.592 | 0.000 | 0.000 | 13.033 | 26.679 | 9.631 | 10.531 | 0.000 | 0.241 | 0.000 | 0.000 | -4.581 | 0.000 | -16.117 | -23.953 |
SMSTORE7 | 0.000 | 0.000 | 7.468 | -19.574 | 0.000 | 0.000 | 13.078 | 26.679 | 9.631 | 10.570 | 0.000 | 0.241 | 0.001 | 0.000 | -4.485 | 0.000 | -15.962 | -27.644 |
SMSTORE8 | 0.000 | 0.000 | 14.295 | -16.407 | 0.000 | 0.000 | 13.154 | 26.679 | 9.631 | 10.673 | 0.000 | 0.250 | 0.002 | 0.000 | -4.152 | 0.000 | -19.486 | -34.637 |
Total Facility | 0.000 | 0.000 | 66.854 | -336.899 | 0.000 | 0.000 | 138.234 | 462.305 | 128.721 | 126.155 | 0.000 | 2.824 | 0.009 | 0.000 | -56.056 | 0.000 | -194.925 | -337.215 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 19-JUL-08:62 | 0.00 | 0.00 | 0.00 | -39790.43 | 0.00 | 0.00 | 178.32 | 2916.31 | 749.03 | 424.57 | 0.00 | 0.00 | 35903.48 | 0.00 | -0.00 | 0.00 | -381.28 | 0.00 |
SMSTORE1 | 05-JUL-08:62 | 0.00 | 0.00 | 0.00 | -22800.89 | 0.00 | 0.00 | 87.79 | 1702.23 | 374.52 | 368.32 | 0.00 | 0.00 | 20495.11 | 0.00 | -0.00 | 0.00 | -227.08 | 0.00 |
SMSTORE2 | 22-JUN-07:02 | 0.00 | 0.00 | 0.00 | -22323.08 | 0.00 | 0.00 | 87.83 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 20655.52 | 0.00 | -28.34 | 0.00 | -302.80 | 0.00 |
SMSTORE3 | 22-JUN-07:02 | 0.00 | 0.00 | 0.00 | -22385.48 | 0.00 | 0.00 | 87.81 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 20717.97 | 0.00 | -28.41 | 0.00 | -302.77 | 0.00 |
SMSTORE4 | 01-AUG-07:02 | 0.00 | 0.00 | 0.00 | -22083.44 | 0.00 | 0.00 | 84.30 | 1536.36 | 374.52 | 16.87 | 0.00 | 0.00 | 20411.45 | 0.00 | -0.00 | 0.00 | -340.06 | 0.00 |
LGSTORE2 | 19-JUL-08:62 | 0.00 | 0.00 | 0.00 | -38606.92 | 0.00 | 0.00 | 392.43 | 1920.56 | 749.03 | 418.80 | 0.00 | 0.00 | 35479.26 | 0.00 | -0.00 | 0.00 | -353.15 | 0.00 |
SMSTORE5 | 01-AUG-08:62 | 0.00 | 0.00 | 0.00 | -19762.75 | 0.00 | 0.00 | 193.98 | 991.67 | 374.52 | 390.40 | 0.00 | 0.00 | 18125.86 | 0.00 | -0.00 | 0.00 | -313.66 | 0.00 |
SMSTORE6 | 01-AUG-08:62 | 0.00 | 0.00 | 0.00 | -19596.10 | 0.00 | 0.00 | 194.94 | 991.67 | 374.52 | 391.56 | 0.00 | 0.00 | 17955.76 | 0.00 | -0.00 | 0.00 | -312.34 | 0.00 |
SMSTORE7 | 01-AUG-08:62 | 0.00 | 0.00 | 0.00 | -19330.04 | 0.00 | 0.00 | 197.94 | 991.67 | 374.52 | 394.76 | 0.00 | 0.00 | 17678.93 | 0.00 | -0.00 | 0.00 | -307.77 | 0.00 |
SMSTORE8 | 23-JUL-09:02 | 0.00 | 0.00 | 0.00 | -18850.30 | 0.00 | 0.00 | 190.53 | 991.67 | 374.52 | 712.50 | 0.00 | 0.00 | 16746.33 | 0.00 | -0.00 | 0.00 | -165.23 | 0.00 |
Total Facility | 15-AUG-08:62 | 0.00 | 0.00 | 0.00 | -177291.82 | 0.00 | 0.00 | 2013.21 | 19263.00 | 5393.02 | 2026.93 | 0.00 | 0.00 | 150476.73 | 0.00 | 0.00 | 0.00 | -1881.07 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 28-DEC-09:01 | 0.00 | 0.00 | 53412.69 | 0.00 | 0.00 | 0.00 | 243.22 | 2916.31 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -194.09 | 0.00 | -659.59 | -56467.57 |
SMSTORE1 | 20-FEB-09:01 | 0.00 | 0.00 | 26504.71 | 0.00 | 0.00 | 0.00 | 121.54 | 1702.23 | 374.52 | 109.84 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -509.64 | -28303.20 |
SMSTORE2 | 01-JAN-09:01 | 0.00 | 0.00 | 27919.84 | 0.00 | 0.00 | 0.00 | 123.14 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -111.31 | 0.00 | -331.84 | -29510.72 |
SMSTORE3 | 01-JAN-09:01 | 0.00 | 0.00 | 28110.09 | 0.00 | 0.00 | 0.00 | 125.72 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -101.66 | 0.00 | -319.37 | -29725.66 |
SMSTORE4 | 01-JAN-09:01 | 0.00 | 0.00 | 28027.78 | 0.00 | 0.00 | 0.00 | 127.59 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -95.03 | 0.00 | -309.93 | -29661.29 |
LGSTORE2 | 26-DEC-08:61 | 0.00 | 0.00 | 56570.90 | 0.00 | 0.00 | 0.00 | 0.00 | 192.04 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -678.52 | 0.00 | -902.14 | -55257.18 |
SMSTORE5 | 26-DEC-08:61 | 0.00 | 0.00 | 28750.08 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -340.86 | 0.00 | -497.65 | -28048.18 |
SMSTORE6 | 26-DEC-08:61 | 0.00 | 0.00 | 28621.70 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -339.01 | 0.00 | -495.18 | -27924.13 |
SMSTORE7 | 26-DEC-08:61 | 0.00 | 0.00 | 28441.74 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -330.84 | 0.00 | -483.93 | -27763.59 |
SMSTORE8 | 16-JAN-09:01 | 0.00 | 0.00 | 29916.14 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -95.70 | 0.00 | -546.62 | -29410.43 |
Total Facility | 20-FEB-09:01 | 0.00 | 0.00 | 329035.79 | 0.00 | 0.00 | 0.00 | 758.78 | 9816.32 | 2471.80 | 1707.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5464.67 | -338325.20 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0467 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0467 | 0.2010 | 1.0000 | Not calculated | 0.4115 | 0.2010 | ||
PSZ-AC_2:2 | 1.0990 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0990 | 0.1872 | 1.0000 | Not calculated | 0.2057 | 0.1872 | ||
PSZ-AC_3:3 | 1.1002 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1002 | 0.1870 | 1.0000 | Not calculated | 0.2057 | 0.1870 | ||
PSZ-AC_4:4 | 1.1035 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1035 | 0.1864 | 1.0000 | Not calculated | 0.2057 | 0.1864 | ||
PSZ-AC_5:5 | 1.0956 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0956 | 0.1878 | 1.0000 | Not calculated | 0.2057 | 0.1878 | ||
PSZ-AC_6:6 | 1.9595 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9595 | 0.2100 | 1.0000 | Not calculated | 0.4115 | 0.2100 | ||
PSZ-AC_7:7 | 0.9993 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0135 | 0.2030 | 1.0000 | Not calculated | 0.2057 | 0.2030 | ||
PSZ-AC_8:8 | 0.9934 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0074 | 0.2042 | 1.0000 | Not calculated | 0.2057 | 0.2042 | ||
PSZ-AC_9:9 | 0.9850 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0032 | 0.2051 | 1.0000 | Not calculated | 0.2057 | 0.2051 | ||
PSZ-AC_10:10 | 1.0518 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0710 | 0.1921 | 1.0000 | Not calculated | 0.2057 | 0.1921 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0467 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0467 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2010 | ||
PSZ-AC_2:2 | 1.0990 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0990 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1872 | ||
PSZ-AC_3:3 | 1.1002 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1002 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1870 | ||
PSZ-AC_4:4 | 1.1035 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1035 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1864 | ||
PSZ-AC_5:5 | 1.0956 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0956 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1878 | ||
PSZ-AC_6:6 | 1.9595 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9595 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2100 | ||
PSZ-AC_7:7 | 0.9993 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9993 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2059 | ||
PSZ-AC_8:8 | 0.9934 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9934 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2071 | ||
PSZ-AC_9:9 | 0.9850 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9850 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2089 | ||
PSZ-AC_10:10 | 1.0518 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0518 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1956 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0467 | 2.0467 | 2.0467 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0990 | 1.0990 | 1.0990 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1002 | 1.1002 | 1.1002 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1035 | 1.1035 | 1.1035 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0956 | 1.0956 | 1.0956 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9595 | 1.9595 | 1.9595 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9993 | 0.9993 | 0.9993 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9934 | 0.9934 | 0.9934 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9850 | 0.9850 | 0.9850 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0518 | 1.0518 | 1.0518 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0467 | 2.0467 | 2.0467 | 2.0467 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0990 | 1.0990 | 1.0990 | 1.0990 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1002 | 1.1002 | 1.1002 | 1.1002 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1035 | 1.1035 | 1.1035 | 1.1035 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0956 | 1.0956 | 1.0956 | 1.0956 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9595 | 1.9595 | 1.9595 | 1.9595 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9993 | 1.0135 | 0.9993 | 0.9993 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9934 | 1.0074 | 0.9934 | 0.9934 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9850 | 1.0032 | 0.9850 | 0.9850 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0518 | 1.0710 | 1.0518 | 1.0518 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0467 | 2.0467 | 2.0467 | No | 0.4115 | 0.3890 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0990 | 1.0990 | 1.0990 | No | 0.2057 | 0.4200 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1002 | 1.1002 | 1.1002 | No | 0.2057 | 0.4141 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.1035 | 1.1035 | 1.1035 | No | 0.2057 | 0.4095 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0956 | 1.0956 | 1.0956 | No | 0.2057 | 0.4019 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9595 | 1.9595 | 1.9595 | No | 0.4115 | 0.4135 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9993 | 0.9993 | 0.9993 | No | 0.2057 | 0.3890 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9934 | 0.9934 | 0.9934 | No | 0.2057 | 0.3892 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9850 | 0.9850 | 0.9850 | No | 0.2057 | 0.3796 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0518 | 1.0518 | 1.0518 | No | 0.2057 | 0.3089 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0467 | 2.0467 | 2.0467 | 2.0467 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0990 | 1.0990 | 1.0990 | 1.0990 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.1002 | 1.1002 | 1.1002 | 1.1002 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.1035 | 1.1035 | 1.1035 | 1.1035 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0956 | 1.0956 | 1.0956 | 1.0956 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9595 | 1.9595 | 1.9595 | 1.9595 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9993 | 0.9993 | 0.9993 | 0.9993 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9934 | 0.9934 | 0.9934 | 0.9934 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9850 | 0.9850 | 0.9850 | 0.9850 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0518 | 1.0518 | 1.0518 | 1.0518 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Seattle Seattle Tacoma Intl A WA USA TMY3 WMO#=727930 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 241.26 | 169477.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 40.22 | 35909.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.12 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 236.57 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 64.38 | 12629.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1053.32 |
Natural Gas | 0.00 | 241.26 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1294.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 19.24 |
Fans (All) | 113.17 |
Service Water Heating | 30.80 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 503.90 |
Subtotal | 503.90 |
Natural Gas [MJ/m2] | |
Space Heating | 115.42 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 115.42 |
Subtotal | 115.42 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 35.71 |
Space Heating | 18.64 |
Space Cooling | 3.11 |
Fans (All) | 18.27 |
Service Water Heating | 4.97 |
Receptacle Equipment | 9.94 |
Miscellaneous | 9.36 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8748.67 | 11.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8751.67 | 8.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8755.50 | 4.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8756.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8757.50 | 2.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
Min | 8748.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 11.33 | 0.00 | 0.00 | 0.00 |
Average | 8755.35 | 4.65 | 0.00 | 0.00 | 0.00 |
Sum | 87553.50 | 46.50 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25471.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25471.33 | 3.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25472.00 | 3.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45908.00 | 4.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45909.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45909.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45908.50 | 3.50 | 0.00 | 0.00 | 0.00 |
Min | 25471.33 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93203.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Average | 48607.02 | 3.18 | 0.00 | 0.00 | 0.00 |
Sum | 486070.17 | 31.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8724.00 | 36.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8721.83 | 38.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8730.00 | 30.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8742.00 | 18.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8743.33 | 16.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8744.33 | 15.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8746.50 | 13.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8749.67 | 10.33 | 0.00 | 0.00 | 0.00 |
Min | 8721.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 38.17 | 0.00 | 0.00 | 0.00 |
Average | 8742.15 | 17.85 | 0.00 | 0.00 | 0.00 |
Sum | 87421.50 | 178.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43776.83 | 0.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25468.83 | 6.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25468.83 | 6.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25469.00 | 6.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93195.00 | 16.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45904.00 | 8.00 | 0.00 | 0.00 | 0.00 |
Min | 25468.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93195.00 | 16.00 | 0.00 | 0.00 | 0.00 |
Average | 48603.55 | 6.65 | 0.00 | 0.00 | 0.00 |
Sum | 486035.50 | 66.50 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:56
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 4C
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_SEATTLE
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.496 |
February | 5.822 |
March | 8.326 |
April | 10.851 |
May | 12.973 |
June | 15.587 |
July | 17.665 |
August | 18.800 |
September | 15.086 |
October | 11.426 |
November | 8.070 |
December | 5.416 |
Annual Sum or Average | 11.241 |
Minimum of Months | 4.496 |
Maximum of Months | 18.800 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.128512E+10 | 10580.25 | 07-JAN-09:04 | -3.1 | -3.3 | 0.106482E+10 | 1275.40 | 08-JAN-18:00 | 3.30 | -0.3 |
February | 0.209066E+10 | 9286.63 | 18-FEB-09:04 | -0.3 | -1.0 | 0.983633E+09 | 1475.55 | 26-FEB-17:19 | 13.30 | 9.51 |
March | 0.418483E+10 | 7437.82 | 05-MAR-09:03 | 3.40 | 2.59 | 0.112226E+10 | 1654.34 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.578683E+10 | 11109.07 | 27-APR-16:10 | 27.02 | 16.89 | 0.121566E+10 | 1685.91 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.778771E+10 | 22162.28 | 06-MAY-08:62 | 18.07 | 14.60 | 0.136024E+10 | 1685.95 | 07-MAY-12:20 | 19.80 | 15.95 |
June | 0.938562E+10 | 38177.51 | 20-JUN-08:62 | 17.38 | 12.62 | 0.134976E+10 | 1685.99 | 11-JUN-12:50 | 17.38 | 12.62 |
July | 0.123882E+11 | 39792.26 | 19-JUL-08:62 | 15.97 | 12.08 | 0.141295E+10 | 1686.00 | 30-JUL-17:40 | 26.70 | 17.74 |
August | 0.128943E+11 | 39689.96 | 01-AUG-08:62 | 11.85 | 11.55 | 0.139460E+10 | 1686.03 | 13-AUG-12:00 | 26.50 | 18.40 |
September | 0.931817E+10 | 36806.56 | 11-SEP-08:62 | 15.28 | 12.74 | 0.135428E+10 | 1685.97 | 08-SEP-12:00 | 15.28 | 12.74 |
October | 0.633335E+10 | 13713.57 | 04-OCT-08:62 | 14.18 | 9.87 | 0.127931E+10 | 1685.86 | 08-OCT-16:10 | 19.72 | 12.98 |
November | 0.313506E+10 | 8198.11 | 13-NOV-09:03 | 1.70 | 1.46 | 0.107863E+10 | 1685.90 | 04-NOV-12:00 | 1.70 | 1.46 |
December | 0.185331E+10 | 9616.33 | 26-DEC-09:04 | -0.9 | -0.9 | 0.107075E+10 | 1363.75 | 03-DEC-13:00 | -0.9 | -0.9 |
Annual Sum or Average | 0.764432E+11 | 0.146869E+11 | ||||||||
Minimum of Months | 0.128512E+10 | 7437.82 | -3.1 | -3.3 | 0.983633E+09 | 1275.40 | -0.9 | -0.9 | ||
Maximum of Months | 0.128943E+11 | 39792.26 | 27.02 | 16.89 | 0.141295E+10 | 1686.03 | 26.70 | 18.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.723954E+09 | 5134.49 | 07-JAN-09:03 | -3.1 | -3.3 | 0.554417E+09 | 785.42 | 29-JAN-18:00 | 9.40 | 5.55 |
February | 0.120513E+10 | 4488.17 | 18-FEB-09:03 | -0.3 | -1.0 | 0.520581E+09 | 842.90 | 26-FEB-18:00 | 10.00 | 7.75 |
March | 0.224022E+10 | 3120.17 | 01-MAR-09:02 | 4.37 | 0.91 | 0.612917E+09 | 842.90 | 19-MAR-17:00 | 10.00 | 6.56 |
April | 0.319822E+10 | 21318.49 | 02-APR-17:44 | 18.07 | 11.30 | 0.646839E+09 | 842.95 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.470788E+10 | 21904.70 | 14-MAY-19:33 | 17.40 | 10.65 | 0.693568E+09 | 842.96 | 07-MAY-12:09 | 17.40 | 10.65 |
June | 0.575895E+10 | 21631.04 | 29-JUN-08:62 | 12.38 | 11.31 | 0.675341E+09 | 842.98 | 11-JUN-12:39 | 12.38 | 11.31 |
July | 0.721963E+10 | 22802.10 | 05-JUL-08:62 | 15.10 | 10.62 | 0.703517E+09 | 842.97 | 28-JUL-12:20 | 22.57 | 15.61 |
August | 0.753434E+10 | 21711.16 | 01-AUG-08:62 | 11.85 | 11.55 | 0.693686E+09 | 842.99 | 13-AUG-12:00 | 26.50 | 18.40 |
September | 0.559163E+10 | 20600.23 | 11-SEP-08:62 | 15.28 | 12.74 | 0.680255E+09 | 842.98 | 08-SEP-12:00 | 15.28 | 12.74 |
October | 0.352936E+10 | 20860.03 | 04-OCT-20:01 | 16.65 | 10.41 | 0.676551E+09 | 842.91 | 08-OCT-16:10 | 19.72 | 12.98 |
November | 0.175427E+10 | 4143.98 | 04-NOV-14:00 | 21.10 | 15.94 | 0.573208E+09 | 842.95 | 04-NOV-12:50 | 21.10 | 15.94 |
December | 0.997313E+09 | 4616.02 | 26-DEC-09:03 | -0.9 | -0.9 | 0.563359E+09 | 842.90 | 03-DEC-18:00 | -0.9 | -0.9 |
Annual Sum or Average | 0.444609E+11 | 0.759424E+10 | ||||||||
Minimum of Months | 0.723954E+09 | 3120.17 | -3.1 | -3.3 | 0.520581E+09 | 785.42 | -0.9 | -0.9 | ||
Maximum of Months | 0.753434E+10 | 22802.10 | 21.10 | 15.94 | 0.703517E+09 | 842.99 | 26.50 | 18.40 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.415195E+09 | 5248.09 | 07-JAN-08:03 | -3.8 | -3.8 | 0.317667E+09 | 637.68 | 07-JAN-13:09 | 0.97 | 0.44 |
February | 0.835718E+09 | 4992.86 | 19-FEB-09:04 | -3.1 | -4.3 | 0.297587E+09 | 762.71 | 25-FEB-13:00 | 14.40 | 11.58 |
March | 0.185477E+10 | 3284.31 | 02-MAR-08:63 | 2.15 | 1.10 | 0.355716E+09 | 842.88 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.236285E+10 | 16620.31 | 28-APR-07:03 | 11.28 | 10.34 | 0.375303E+09 | 842.95 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.326988E+10 | 19148.94 | 05-MAY-07:03 | 14.18 | 11.86 | 0.418116E+09 | 842.90 | 06-MAY-12:00 | 23.90 | 17.58 |
June | 0.402436E+10 | 22328.06 | 22-JUN-07:02 | 11.78 | 10.81 | 0.415919E+09 | 842.95 | 10-JUN-12:09 | 11.78 | 10.81 |
July | 0.504664E+10 | 22212.51 | 19-JUL-07:02 | 15.10 | 11.63 | 0.419907E+09 | 842.97 | 22-JUL-12:09 | 23.12 | 15.83 |
August | 0.551025E+10 | 22255.78 | 01-AUG-07:02 | 11.47 | 11.42 | 0.431623E+09 | 842.96 | 12-AUG-12:00 | 24.40 | 16.56 |
September | 0.386989E+10 | 22213.21 | 16-SEP-07:02 | 10.68 | 10.68 | 0.408533E+09 | 842.95 | 09-SEP-12:00 | 10.68 | 10.68 |
October | 0.257862E+10 | 9509.12 | 05-OCT-07:03 | 9.50 | 6.06 | 0.389429E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.123683E+10 | 3723.36 | 04-NOV-14:00 | 21.10 | 15.94 | 0.323301E+09 | 842.95 | 04-NOV-12:00 | 21.10 | 15.94 |
December | 0.653799E+09 | 4365.12 | 26-DEC-08:03 | -1.1 | -1.2 | 0.318213E+09 | 713.49 | 02-DEC-13:00 | -1.1 | -1.2 |
Annual Sum or Average | 0.316588E+11 | 0.447132E+10 | ||||||||
Minimum of Months | 0.415195E+09 | 3284.31 | -3.8 | -4.3 | 0.297587E+09 | 637.68 | -1.1 | -1.2 | ||
Maximum of Months | 0.551025E+10 | 22328.06 | 21.10 | 15.94 | 0.431623E+09 | 842.97 | 24.40 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.338567E+09 | 5254.44 | 07-JAN-08:03 | -3.8 | -3.8 | 0.317511E+09 | 637.68 | 14-JAN-13:09 | 5.00 | 2.36 |
February | 0.726169E+09 | 5125.75 | 19-FEB-09:04 | -3.1 | -4.3 | 0.296483E+09 | 750.53 | 25-FEB-13:00 | 14.40 | 11.58 |
March | 0.168373E+10 | 3236.13 | 05-MAR-09:03 | 3.40 | 2.59 | 0.352029E+09 | 842.75 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.223849E+10 | 15889.31 | 28-APR-07:03 | 11.28 | 10.34 | 0.371553E+09 | 842.95 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.317238E+10 | 18742.44 | 05-MAY-07:03 | 14.18 | 11.86 | 0.417200E+09 | 842.90 | 06-MAY-12:00 | 23.90 | 17.58 |
June | 0.397189E+10 | 22390.49 | 22-JUN-07:02 | 11.78 | 10.81 | 0.415838E+09 | 842.95 | 10-JUN-12:09 | 11.78 | 10.81 |
July | 0.503022E+10 | 22242.76 | 19-JUL-07:02 | 15.10 | 11.63 | 0.419899E+09 | 842.97 | 22-JUL-12:09 | 23.12 | 15.83 |
August | 0.551518E+10 | 22378.60 | 01-AUG-07:02 | 11.47 | 11.42 | 0.431621E+09 | 842.96 | 12-AUG-12:00 | 24.40 | 16.56 |
September | 0.381292E+10 | 22276.80 | 16-SEP-07:02 | 10.68 | 10.68 | 0.408241E+09 | 842.95 | 09-SEP-12:00 | 10.68 | 10.68 |
October | 0.247081E+10 | 9034.83 | 05-OCT-07:03 | 9.50 | 6.06 | 0.385383E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.110203E+10 | 3905.77 | 13-NOV-08:04 | 0.78 | 0.74 | 0.321265E+09 | 842.94 | 04-NOV-12:00 | 0.78 | 0.74 |
December | 0.556022E+09 | 4645.41 | 26-DEC-08:03 | -1.1 | -1.2 | 0.317856E+09 | 706.43 | 02-DEC-13:00 | -1.1 | -1.2 |
Annual Sum or Average | 0.306184E+11 | 0.445488E+10 | ||||||||
Minimum of Months | 0.338567E+09 | 3236.13 | -3.8 | -4.3 | 0.296483E+09 | 637.68 | -1.1 | -1.2 | ||
Maximum of Months | 0.551518E+10 | 22390.49 | 15.10 | 11.86 | 0.431621E+09 | 842.97 | 24.40 | 17.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.244354E+09 | 5040.95 | 15-JAN-09:03 | -2.5 | -3.9 | 0.317330E+09 | 637.68 | 07-JAN-13:30 | -2.5 | -3.9 |
February | 0.578694E+09 | 5270.18 | 19-FEB-09:04 | -3.1 | -4.3 | 0.295019E+09 | 732.27 | 25-FEB-13:00 | 14.40 | 11.58 |
March | 0.145153E+10 | 3429.85 | 05-MAR-09:03 | 3.40 | 2.59 | 0.347125E+09 | 842.11 | 18-MAR-12:00 | 17.20 | 10.94 |
April | 0.204376E+10 | 13082.85 | 28-APR-07:03 | 11.28 | 10.34 | 0.365529E+09 | 842.94 | 29-APR-12:00 | 20.00 | 14.70 |
May | 0.294548E+10 | 18231.17 | 07-MAY-08:62 | 17.52 | 14.34 | 0.414766E+09 | 842.90 | 06-MAY-12:00 | 17.52 | 14.34 |
June | 0.374568E+10 | 21938.98 | 22-JUN-07:02 | 11.78 | 10.81 | 0.415424E+09 | 842.94 | 10-JUN-12:09 | 11.78 | 10.81 |
July | 0.481930E+10 | 21937.53 | 19-JUL-07:02 | 15.10 | 11.63 | 0.419815E+09 | 842.97 | 22-JUL-12:09 | 23.12 | 15.83 |
August | 0.530342E+10 | 22090.08 | 01-AUG-07:02 | 11.47 | 11.42 | 0.431536E+09 | 842.96 | 12-AUG-12:00 | 24.40 | 16.56 |
September | 0.360197E+10 | 21975.27 | 16-SEP-07:02 | 10.68 | 10.68 | 0.407213E+09 | 842.95 | 09-SEP-12:00 | 10.68 | 10.68 |
October | 0.228726E+10 | 7379.89 | 05-OCT-07:03 | 9.50 | 6.06 | 0.379121E+09 | 842.89 | 07-OCT-12:09 | 16.28 | 11.84 |
November | 0.926834E+09 | 4086.34 | 13-NOV-08:04 | 0.78 | 0.74 | 0.318444E+09 | 842.92 | 04-NOV-12:00 | 0.78 | 0.74 |
December | 0.424244E+09 | 4667.32 | 26-DEC-08:03 | -1.1 | -1.2 | 0.317395E+09 | 693.32 | 02-DEC-13:00 | -1.1 | -1.2 |
Annual Sum or Average | 0.283725E+11 | 0.442872E+10 | ||||||||
Minimum of Months | 0.244354E+09 | 3429.85 | -3.1 | -4.3 | 0.295019E+09 | 637.68 | -2.5 | -3.9 | ||
Maximum of Months | 0.530342E+10 | 22090.08 | 17.52 | 14.34 | 0.431536E+09 | 842.97 | 24.40 | 16.56 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.188165E+09 | 10560.96 | 07-JAN-09:04 | -3.1 | -3.3 | 0.108369E+10 | 1700.53 | 07-JAN-15:39 | 2.97 | 1.40 |
February | 0.721200E+09 | 10129.98 | 19-FEB-10:04 | -2.1 | -3.8 | 0.100364E+10 | 1994.92 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.219261E+10 | 7126.16 | 24-MAR-08:02 | 4.08 | -0.6 | 0.116543E+10 | 2247.76 | 18-MAR-14:09 | 4.08 | -0.6 |
April | 0.332270E+10 | 9902.20 | 27-APR-14:50 | 27.02 | 17.21 | 0.122074E+10 | 2247.95 | 29-APR-14:50 | 22.02 | 15.16 |
May | 0.477998E+10 | 33149.61 | 07-MAY-09:02 | 16.38 | 13.91 | 0.140128E+10 | 2247.80 | 06-MAY-14:00 | 16.38 | 13.91 |
June | 0.608717E+10 | 37017.05 | 20-JUN-08:62 | 17.38 | 12.62 | 0.142130E+10 | 2247.86 | 03-JUN-14:09 | 17.38 | 12.62 |
July | 0.805237E+10 | 38606.63 | 19-JUL-08:62 | 15.97 | 12.08 | 0.143720E+10 | 2247.97 | 22-JUL-14:00 | 25.60 | 16.99 |
August | 0.889372E+10 | 38593.04 | 01-AUG-08:62 | 11.85 | 11.55 | 0.147972E+10 | 2247.98 | 12-AUG-14:00 | 25.70 | 17.07 |
September | 0.588563E+10 | 37009.07 | 11-SEP-08:62 | 15.28 | 12.74 | 0.138785E+10 | 2247.98 | 09-SEP-14:09 | 15.28 | 12.74 |
October | 0.364311E+10 | 11908.93 | 04-OCT-08:62 | 14.18 | 9.87 | 0.126036E+10 | 2247.72 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.123913E+10 | 7960.43 | 11-NOV-10:03 | 1.97 | 1.65 | 0.107143E+10 | 2247.81 | 04-NOV-14:09 | 1.97 | 1.65 |
December | 0.411504E+09 | 8718.76 | 22-DEC-09:04 | 0.78 | -0.8 | 0.108623E+10 | 1752.49 | 02-DEC-15:09 | 0.78 | -0.8 |
Annual Sum or Average | 0.454173E+11 | 0.150189E+11 | ||||||||
Minimum of Months | 0.188165E+09 | 7126.16 | -3.1 | -3.8 | 0.100364E+10 | 1700.53 | 0.78 | -0.8 | ||
Maximum of Months | 0.889372E+10 | 38606.63 | 27.02 | 17.21 | 0.147972E+10 | 2247.98 | 25.70 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 80696220.29 | 5218.85 | 07-JAN-09:04 | -3.1 | -3.3 | 0.541825E+09 | 850.24 | 07-JAN-15:09 | 3.22 | 1.63 |
February | 0.319920E+09 | 5007.95 | 19-FEB-10:04 | -2.1 | -3.8 | 0.501562E+09 | 997.43 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.998057E+09 | 3493.33 | 24-MAR-08:02 | 4.08 | -0.6 | 0.581734E+09 | 1123.85 | 18-MAR-14:09 | 4.08 | -0.6 |
April | 0.155885E+10 | 5102.16 | 27-APR-14:50 | 27.02 | 17.21 | 0.608083E+09 | 1123.94 | 29-APR-14:50 | 22.02 | 15.16 |
May | 0.231184E+10 | 15391.06 | 07-MAY-09:02 | 16.38 | 13.91 | 0.698926E+09 | 1123.87 | 06-MAY-14:09 | 16.38 | 13.91 |
June | 0.303275E+10 | 18664.41 | 28-JUN-08:62 | 17.98 | 13.05 | 0.710439E+09 | 1123.89 | 03-JUN-14:09 | 17.98 | 13.05 |
July | 0.408698E+10 | 19760.51 | 19-JUL-08:62 | 15.97 | 12.08 | 0.718565E+09 | 1123.95 | 22-JUL-14:00 | 25.60 | 16.99 |
August | 0.454171E+10 | 19769.12 | 01-AUG-08:62 | 11.85 | 11.55 | 0.739835E+09 | 1123.95 | 12-AUG-14:00 | 25.70 | 17.07 |
September | 0.294259E+10 | 18966.35 | 11-SEP-08:62 | 15.28 | 12.74 | 0.693547E+09 | 1123.96 | 09-SEP-14:09 | 15.28 | 12.74 |
October | 0.173108E+10 | 4864.83 | 04-OCT-08:62 | 14.18 | 9.87 | 0.628671E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.565670E+09 | 3940.15 | 11-NOV-10:03 | 1.97 | 1.65 | 0.535212E+09 | 1123.87 | 04-NOV-14:09 | 1.97 | 1.65 |
December | 0.185030E+09 | 4281.68 | 22-DEC-09:04 | 0.78 | -0.8 | 0.543084E+09 | 879.42 | 02-DEC-15:09 | 0.78 | -0.8 |
Annual Sum or Average | 0.223552E+11 | 0.750148E+10 | ||||||||
Minimum of Months | 80696220.29 | 3493.33 | -3.1 | -3.8 | 0.501562E+09 | 850.24 | 0.78 | -0.8 | ||
Maximum of Months | 0.454171E+10 | 19769.12 | 27.02 | 17.21 | 0.739835E+09 | 1123.96 | 25.70 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 69279759.60 | 4959.82 | 06-JAN-09:04 | -2.0 | -2.0 | 0.541782E+09 | 850.24 | 07-JAN-15:20 | 3.13 | 1.56 |
February | 0.294497E+09 | 4985.27 | 19-FEB-10:04 | -2.1 | -3.8 | 0.501017E+09 | 997.43 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.932551E+09 | 3464.04 | 24-MAR-08:02 | 4.08 | -0.6 | 0.579486E+09 | 1123.85 | 18-MAR-14:00 | 4.08 | -0.6 |
April | 0.148139E+10 | 4964.65 | 27-APR-14:50 | 27.02 | 17.21 | 0.604481E+09 | 1123.94 | 29-APR-14:50 | 22.02 | 15.16 |
May | 0.221897E+10 | 14236.62 | 07-MAY-09:02 | 16.38 | 13.91 | 0.694909E+09 | 1123.87 | 06-MAY-14:09 | 16.38 | 13.91 |
June | 0.293530E+10 | 18494.56 | 28-JUN-08:62 | 17.98 | 13.05 | 0.709589E+09 | 1123.89 | 03-JUN-14:09 | 17.98 | 13.05 |
July | 0.399777E+10 | 18930.48 | 19-JUL-08:62 | 15.97 | 12.08 | 0.718462E+09 | 1123.95 | 22-JUL-14:00 | 25.60 | 16.99 |
August | 0.445811E+10 | 19602.40 | 01-AUG-08:62 | 11.85 | 11.55 | 0.739764E+09 | 1123.95 | 12-AUG-14:00 | 25.70 | 17.07 |
September | 0.286195E+10 | 18790.88 | 11-SEP-08:62 | 15.28 | 12.74 | 0.691917E+09 | 1123.96 | 09-SEP-14:09 | 15.28 | 12.74 |
October | 0.165025E+10 | 4542.17 | 04-OCT-15:00 | 21.70 | 11.49 | 0.625071E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.527671E+09 | 4005.58 | 11-NOV-10:03 | 1.97 | 1.65 | 0.534188E+09 | 1123.88 | 04-NOV-14:09 | 1.97 | 1.65 |
December | 0.164610E+09 | 4340.71 | 22-DEC-09:04 | 0.78 | -0.8 | 0.542999E+09 | 873.30 | 02-DEC-15:09 | 0.78 | -0.8 |
Annual Sum or Average | 0.215924E+11 | 0.748367E+10 | ||||||||
Minimum of Months | 69279759.60 | 3464.04 | -2.1 | -3.8 | 0.501017E+09 | 850.24 | 0.78 | -0.8 | ||
Maximum of Months | 0.445811E+10 | 19602.40 | 27.02 | 17.21 | 0.739764E+09 | 1123.96 | 25.70 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 37005752.28 | 4708.95 | 21-JAN-09:04 | -1.0 | -1.1 | 0.541665E+09 | 850.24 | 28-JAN-15:39 | 6.70 | 5.64 |
February | 0.213937E+09 | 4216.16 | 08-FEB-09:04 | 0.87 | -0.5 | 0.499614E+09 | 986.88 | 27-FEB-17:10 | 18.62 | 12.15 |
March | 0.738660E+09 | 3420.91 | 05-MAR-10:04 | 3.98 | 2.65 | 0.574298E+09 | 1123.85 | 18-MAR-14:00 | 20.00 | 10.34 |
April | 0.127670E+10 | 4683.30 | 27-APR-15:00 | 27.20 | 17.29 | 0.596251E+09 | 1123.94 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.199271E+10 | 10425.27 | 07-MAY-09:02 | 16.38 | 13.91 | 0.684453E+09 | 1123.87 | 06-MAY-14:09 | 16.38 | 13.91 |
June | 0.269230E+10 | 17206.25 | 12-JUN-08:62 | 15.28 | 14.11 | 0.706677E+09 | 1123.89 | 03-JUN-14:09 | 15.28 | 14.11 |
July | 0.376798E+10 | 18244.55 | 20-JUL-08:62 | 17.38 | 13.38 | 0.718039E+09 | 1123.95 | 22-JUL-14:00 | 25.60 | 16.99 |
August | 0.425705E+10 | 19336.27 | 01-AUG-08:62 | 11.85 | 11.55 | 0.739504E+09 | 1123.95 | 12-AUG-14:00 | 25.70 | 17.07 |
September | 0.265675E+10 | 17904.50 | 10-SEP-09:02 | 16.28 | 13.48 | 0.687044E+09 | 1123.95 | 09-SEP-14:09 | 16.28 | 13.48 |
October | 0.143484E+10 | 4270.16 | 04-OCT-15:00 | 21.70 | 11.49 | 0.616863E+09 | 1123.83 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.406521E+09 | 4158.19 | 13-NOV-09:04 | 1.70 | 1.46 | 0.532047E+09 | 1123.92 | 04-NOV-14:50 | 1.70 | 1.46 |
December | 99867344.95 | 4285.37 | 22-DEC-09:04 | 0.78 | -0.8 | 0.542730E+09 | 855.78 | 02-DEC-15:09 | 0.78 | -0.8 |
Annual Sum or Average | 0.195743E+11 | 0.743918E+10 | ||||||||
Minimum of Months | 37005752.28 | 3420.91 | -1.0 | -1.1 | 0.499614E+09 | 850.24 | 0.78 | -0.8 | ||
Maximum of Months | 0.425705E+10 | 19336.27 | 27.20 | 17.29 | 0.739504E+09 | 1123.95 | 25.70 | 17.07 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3774647.25 | 3421.86 | 26-JAN-09:04 | 4.40 | 4.13 | 0.541591E+09 | 850.24 | 07-JAN-15:09 | 4.40 | 4.13 |
February | 62872419.35 | 4016.14 | 10-FEB-09:04 | 1.88 | 0.51 | 0.497367E+09 | 961.62 | 27-FEB-15:00 | 19.40 | 12.42 |
March | 0.316209E+09 | 3531.84 | 24-MAR-08:04 | 4.08 | -0.6 | 0.567556E+09 | 1123.86 | 18-MAR-14:00 | 4.08 | -0.6 |
April | 0.873006E+09 | 4633.00 | 27-APR-14:50 | 27.02 | 17.21 | 0.585013E+09 | 1123.93 | 29-APR-14:00 | 22.20 | 15.23 |
May | 0.157160E+10 | 4461.72 | 15-MAY-14:10 | 23.30 | 13.36 | 0.665746E+09 | 1123.87 | 06-MAY-14:09 | 23.30 | 13.36 |
June | 0.240066E+10 | 9717.19 | 28-JUN-08:62 | 17.98 | 13.05 | 0.699168E+09 | 1123.89 | 03-JUN-14:09 | 17.98 | 13.05 |
July | 0.353414E+10 | 18852.18 | 23-JUL-09:02 | 19.27 | 13.97 | 0.716140E+09 | 1123.95 | 22-JUL-14:00 | 19.27 | 13.97 |
August | 0.413469E+10 | 18115.98 | 09-AUG-08:62 | 21.72 | 14.33 | 0.738467E+09 | 1123.96 | 12-AUG-14:00 | 25.70 | 17.07 |
September | 0.236009E+10 | 15865.31 | 10-SEP-09:02 | 16.28 | 13.48 | 0.675331E+09 | 1123.95 | 09-SEP-14:20 | 16.28 | 13.48 |
October | 0.963669E+09 | 3814.15 | 04-OCT-14:50 | 21.60 | 11.48 | 0.604319E+09 | 1123.84 | 07-OCT-14:09 | 17.38 | 12.04 |
November | 0.166669E+09 | 3951.56 | 11-NOV-10:04 | 1.97 | 1.65 | 0.529573E+09 | 1123.90 | 04-NOV-14:50 | 1.97 | 1.65 |
December | 19435661.36 | 3496.49 | 30-DEC-09:04 | 4.18 | 3.83 | 0.542514E+09 | 850.24 | 16-DEC-15:20 | 4.18 | 3.83 |
Annual Sum or Average | 0.164068E+11 | 0.736279E+10 | ||||||||
Minimum of Months | 3774647.25 | 3421.86 | 1.88 | -0.6 | 0.497367E+09 | 850.24 | 1.97 | -0.6 | ||
Maximum of Months | 0.413469E+10 | 18852.18 | 27.02 | 17.21 | 0.738467E+09 | 1123.96 | 25.70 | 17.07 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.259776E+10 | 52467.05 | 01-JAN-09:01 | 7.80 |
February | 0.145677E+10 | 52229.89 | 22-FEB-09:01 | 7.38 |
March | 0.410226E+09 | 51085.75 | 25-MAR-08:61 | 4.78 |
April | 0.225450E+09 | 31485.99 | 18-APR-08:61 | 4.50 |
May | 0.199689E+09 | 2180.45 | 17-MAY-07:25 | 9.15 |
June | 0.179863E+09 | 2151.74 | 01-JUN-07:25 | 11.65 |
July | 0.174243E+09 | 2318.71 | 30-JUL-07:07 | 16.97 |
August | 0.186844E+09 | 2555.74 | 13-AUG-07:07 | 18.17 |
September | 0.176627E+09 | 2120.83 | 16-SEP-07:13 | 10.77 |
October | 0.205629E+09 | 2946.08 | 30-OCT-08:07 | 7.30 |
November | 0.795954E+09 | 51212.83 | 30-NOV-09:01 | 5.40 |
December | 0.197715E+10 | 53412.02 | 28-DEC-09:01 | 10.02 |
Annual Sum or Average | 0.858621E+10 | |||
Minimum of Months | 0.174243E+09 | 2120.83 | 4.50 | |
Maximum of Months | 0.259776E+10 | 53412.02 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.584337E+09 | 26495.45 | 17-JAN-09:01 | 1.88 |
February | 0.337216E+09 | 26505.31 | 20-FEB-09:01 | 1.47 |
March | 0.121445E+09 | 1604.78 | 05-MAR-09:05 | 3.40 |
April | 0.110330E+09 | 1203.11 | 08-APR-07:25 | 6.95 |
May | 0.107962E+09 | 1211.37 | 18-MAY-07:25 | 6.10 |
June | 98777486.01 | 1229.92 | 11-JUN-07:10 | 12.98 |
July | 96632375.56 | 1521.05 | 23-JUL-07:07 | 16.38 |
August | 0.106291E+09 | 1610.95 | 13-AUG-07:07 | 18.17 |
September | 97753500.66 | 1350.00 | 03-SEP-07:10 | 13.40 |
October | 0.108423E+09 | 1207.91 | 12-OCT-07:25 | 6.95 |
November | 0.164340E+09 | 3459.52 | 29-NOV-09:09 | 6.70 |
December | 0.439183E+09 | 25850.74 | 26-DEC-09:01 | -0.9 |
Annual Sum or Average | 0.237269E+10 | |||
Minimum of Months | 96632375.56 | 1203.11 | -0.9 | |
Maximum of Months | 0.584337E+09 | 26505.31 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.985873E+09 | 27919.68 | 01-JAN-09:01 | 7.80 |
February | 0.519095E+09 | 26696.53 | 20-FEB-09:01 | 1.47 |
March | 0.144064E+09 | 4124.27 | 05-MAR-09:02 | 3.40 |
April | 0.113674E+09 | 1525.51 | 18-APR-07:08 | 3.98 |
May | 0.111386E+09 | 1124.75 | 17-MAY-07:00 | 8.90 |
June | 0.110621E+09 | 1118.22 | 11-JUN-08:00 | 13.90 |
July | 0.127081E+09 | 1668.08 | 23-JUL-16:12 | 27.43 |
August | 0.135472E+09 | 1953.09 | 10-AUG-19:03 | 29.18 |
September | 0.108703E+09 | 1133.70 | 17-SEP-08:00 | 11.10 |
October | 0.111830E+09 | 1151.27 | 22-OCT-08:00 | 7.80 |
November | 0.298427E+09 | 10000.78 | 24-NOV-08:62 | 1.97 |
December | 0.738290E+09 | 26146.61 | 25-DEC-09:01 | -0.1 |
Annual Sum or Average | 0.350452E+10 | |||
Minimum of Months | 0.108703E+09 | 1118.22 | -0.1 | |
Maximum of Months | 0.985873E+09 | 27919.68 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116685E+10 | 28109.93 | 01-JAN-09:01 | 7.80 |
February | 0.607074E+09 | 27041.20 | 13-FEB-08:61 | 3.72 |
March | 0.165284E+09 | 9622.20 | 05-MAR-09:02 | 3.40 |
April | 0.116523E+09 | 4014.09 | 18-APR-07:20 | 4.07 |
May | 0.111702E+09 | 1125.54 | 17-MAY-07:00 | 8.90 |
June | 0.110976E+09 | 1117.13 | 11-JUN-08:00 | 13.90 |
July | 0.127290E+09 | 1671.98 | 23-JUL-16:12 | 27.43 |
August | 0.135774E+09 | 1954.95 | 10-AUG-19:03 | 29.18 |
September | 0.108958E+09 | 1135.18 | 17-SEP-08:00 | 11.10 |
October | 0.112091E+09 | 1155.02 | 22-OCT-08:00 | 7.80 |
November | 0.376072E+09 | 15111.83 | 24-NOV-08:62 | 1.97 |
December | 0.875435E+09 | 26311.94 | 27-DEC-08:62 | 4.50 |
Annual Sum or Average | 0.401403E+10 | |||
Minimum of Months | 0.108958E+09 | 1117.13 | 1.97 | |
Maximum of Months | 0.116685E+10 | 28109.93 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144492E+10 | 28027.62 | 01-JAN-09:01 | 7.80 |
February | 0.746259E+09 | 26941.42 | 13-FEB-08:61 | 3.72 |
March | 0.203457E+09 | 15455.59 | 05-MAR-09:02 | 3.40 |
April | 0.120709E+09 | 2082.75 | 19-APR-07:03 | 4.18 |
May | 0.111389E+09 | 1120.24 | 17-MAY-07:00 | 8.90 |
June | 0.110765E+09 | 1110.44 | 11-JUN-08:00 | 13.90 |
July | 0.127213E+09 | 1670.73 | 23-JUL-16:12 | 27.43 |
August | 0.136017E+09 | 1961.16 | 10-AUG-19:03 | 29.18 |
September | 0.108534E+09 | 1129.76 | 17-SEP-08:00 | 11.10 |
October | 0.112881E+09 | 1149.98 | 15-OCT-08:00 | 8.30 |
November | 0.484873E+09 | 20081.65 | 24-NOV-08:62 | 1.97 |
December | 0.109056E+10 | 26793.45 | 27-DEC-08:62 | 4.50 |
Annual Sum or Average | 0.479757E+10 | |||
Minimum of Months | 0.108534E+09 | 1110.44 | 1.97 | |
Maximum of Months | 0.144492E+10 | 28027.62 | 29.18 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.304234E+10 | 56565.79 | 15-JAN-09:01 | -2.5 |
February | 0.155682E+10 | 56508.60 | 20-FEB-09:01 | 1.47 |
March | 0.470649E+09 | 50366.04 | 06-MAR-09:01 | 7.30 |
April | 0.235812E+09 | 38946.25 | 18-APR-08:61 | 4.50 |
May | 0.203977E+09 | 2082.68 | 18-MAY-07:25 | 6.10 |
June | 0.195302E+09 | 2054.54 | 01-JUN-07:25 | 11.65 |
July | 0.220803E+09 | 3094.55 | 23-JUL-16:12 | 27.43 |
August | 0.216705E+09 | 3325.73 | 13-AUG-16:02 | 28.08 |
September | 0.197236E+09 | 2029.55 | 16-SEP-07:13 | 10.77 |
October | 0.212522E+09 | 8038.91 | 30-OCT-08:62 | 7.30 |
November | 0.101477E+10 | 51510.91 | 27-NOV-09:01 | 10.60 |
December | 0.228195E+10 | 56570.92 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.984888E+10 | |||
Minimum of Months | 0.195302E+09 | 2029.55 | -2.5 | |
Maximum of Months | 0.304234E+10 | 56570.92 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.179207E+10 | 28747.46 | 15-JAN-09:01 | -2.5 |
February | 0.939493E+09 | 28718.25 | 20-FEB-09:01 | 1.47 |
March | 0.295791E+09 | 25668.13 | 06-MAR-09:01 | 7.30 |
April | 0.136127E+09 | 22020.97 | 18-APR-08:61 | 4.50 |
May | 0.110905E+09 | 1117.20 | 18-MAY-07:25 | 6.10 |
June | 0.106742E+09 | 1102.87 | 01-JUN-07:25 | 11.65 |
July | 0.120071E+09 | 1621.14 | 23-JUL-16:12 | 27.43 |
August | 0.117812E+09 | 1707.73 | 13-AUG-16:02 | 28.08 |
September | 0.107041E+09 | 1086.24 | 16-SEP-07:13 | 10.77 |
October | 0.118493E+09 | 6372.06 | 30-OCT-08:62 | 7.30 |
November | 0.631950E+09 | 26227.75 | 27-NOV-09:01 | 10.60 |
December | 0.136035E+10 | 28750.09 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.583685E+10 | |||
Minimum of Months | 0.106742E+09 | 1086.24 | -2.5 | |
Maximum of Months | 0.179207E+10 | 28750.09 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.186691E+10 | 28619.53 | 15-JAN-09:01 | -2.5 |
February | 0.998818E+09 | 28590.58 | 20-FEB-09:01 | 1.47 |
March | 0.331889E+09 | 25797.04 | 07-MAR-09:01 | 9.22 |
April | 0.144541E+09 | 24771.92 | 18-APR-08:61 | 4.50 |
May | 0.110510E+09 | 1112.05 | 18-MAY-07:25 | 6.10 |
June | 0.106335E+09 | 1097.29 | 01-JUN-07:25 | 11.65 |
July | 0.119625E+09 | 1618.82 | 23-JUL-16:12 | 27.43 |
August | 0.117388E+09 | 1707.84 | 13-AUG-16:02 | 28.08 |
September | 0.106596E+09 | 1080.23 | 16-SEP-07:13 | 10.77 |
October | 0.122770E+09 | 9410.81 | 30-OCT-08:62 | 7.30 |
November | 0.677545E+09 | 26127.19 | 27-NOV-09:01 | 10.60 |
December | 0.142683E+10 | 28621.71 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.612976E+10 | |||
Minimum of Months | 0.106335E+09 | 1080.23 | -2.5 | |
Maximum of Months | 0.186691E+10 | 28621.71 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.224376E+10 | 28441.70 | 09-JAN-08:61 | 0.10 |
February | 0.126144E+10 | 28408.21 | 20-FEB-09:01 | 1.47 |
March | 0.475907E+09 | 25721.41 | 07-MAR-09:01 | 9.22 |
April | 0.187075E+09 | 25108.28 | 12-APR-08:61 | 7.07 |
May | 0.111522E+09 | 1107.91 | 17-MAY-07:25 | 9.15 |
June | 0.106377E+09 | 1094.02 | 01-JUN-07:25 | 11.65 |
July | 0.119837E+09 | 1620.98 | 23-JUL-16:12 | 27.43 |
August | 0.117380E+09 | 1711.74 | 13-AUG-16:02 | 28.08 |
September | 0.106564E+09 | 1077.82 | 16-SEP-07:13 | 10.77 |
October | 0.150298E+09 | 18107.22 | 30-OCT-08:62 | 7.30 |
November | 0.855267E+09 | 26035.03 | 27-NOV-09:01 | 10.60 |
December | 0.173255E+10 | 28441.75 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.746797E+10 | |||
Minimum of Months | 0.106377E+09 | 1077.82 | -1.1 | |
Maximum of Months | 0.224376E+10 | 28441.75 | 28.08 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.408271E+10 | 29916.13 | 16-JAN-09:01 | -0.5 |
February | 0.255188E+10 | 29844.54 | 20-FEB-09:01 | 1.47 |
March | 0.124211E+10 | 29286.13 | 05-MAR-09:02 | 3.40 |
April | 0.457921E+09 | 27608.20 | 01-APR-08:62 | 11.57 |
May | 0.149049E+09 | 16024.63 | 18-MAY-08:62 | 6.28 |
June | 0.109466E+09 | 1158.13 | 01-JUN-07:25 | 11.65 |
July | 0.123783E+09 | 1680.03 | 30-JUL-16:12 | 27.43 |
August | 0.121120E+09 | 1740.52 | 13-AUG-16:02 | 28.08 |
September | 0.112025E+09 | 1490.33 | 28-SEP-08:65 | 10.28 |
October | 0.344878E+09 | 27194.27 | 31-OCT-08:62 | 11.70 |
November | 0.172824E+10 | 29052.19 | 24-NOV-08:62 | 1.97 |
December | 0.327206E+10 | 29893.51 | 26-DEC-08:61 | -1.1 |
Annual Sum or Average | 0.142952E+11 | |||
Minimum of Months | 0.109466E+09 | 1158.13 | -1.1 | |
Maximum of Months | 0.408271E+10 | 29916.13 | 28.08 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448194E+10 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359668E+10 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329686E+10 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 24394332.37 | 0.265333E+10 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2652904.25 | 0.230135E+10 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13745509.15 | 0.168630E+10 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.130166E+09 | 0.114836E+10 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278894E+09 | 0.951174E+09 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3237651.02 | 0.159938E+10 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273276E+10 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353680E+10 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409732E+10 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453090E+09 | 0.320823E+11 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951174E+09 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.278894E+09 | 0.448194E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226104E+10 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181718E+10 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169426E+10 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13269978.87 | 0.135446E+10 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1458183.26 | 0.114234E+10 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7466067.51 | 0.797025E+09 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 70583124.23 | 0.524828E+09 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151692E+09 | 0.423828E+09 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1783357.67 | 0.822485E+09 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140893E+10 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180304E+10 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.209742E+10 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.246252E+09 | 0.161468E+11 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423828E+09 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.151692E+09 | 0.226104E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231765E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185755E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.171108E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13066887.75 | 0.138212E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455406.33 | 0.118238E+10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466017.19 | 0.834052E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66945728.59 | 0.563176E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149413E+09 | 0.455722E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1783533.59 | 0.846619E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142524E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182410E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.214329E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240131E+09 | 0.165430E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455722E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149413E+09 | 0.231765E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231156E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184920E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.169354E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13070150.72 | 0.136418E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455584.14 | 0.117726E+10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466019.58 | 0.833032E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66946179.18 | 0.562989E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149411E+09 | 0.455811E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1783529.55 | 0.844976E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140648E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181236E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213758E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240132E+09 | 0.164490E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455811E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149411E+09 | 0.231156E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230625E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184028E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.167237E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13077494.69 | 0.133768E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455924.13 | 0.116550E+10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7466014.00 | 0.829141E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 66973746.24 | 0.560474E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149427E+09 | 0.453486E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1783529.46 | 0.839935E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137912E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179809E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213223E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240184E+09 | 0.163146E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.453486E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149427E+09 | 0.230625E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420246E+10 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.334961E+10 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302634E+10 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 23576935.42 | 0.240289E+10 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2616620.70 | 0.211131E+10 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 13428924.36 | 0.153427E+10 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.120715E+09 | 0.104586E+10 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268949E+09 | 0.851984E+09 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3204923.58 | 0.151766E+10 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.247369E+10 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325991E+10 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387558E+10 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.432491E+09 | 0.296516E+11 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851984E+09 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.268949E+09 | 0.420246E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230457E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183356E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.165014E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13117136.70 | 0.130077E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456549.73 | 0.114429E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7465552.46 | 0.830033E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67105664.46 | 0.562711E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149547E+09 | 0.456548E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784839.78 | 0.831429E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134550E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178464E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212853E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240477E+09 | 0.161727E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456548E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149547E+09 | 0.230457E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230303E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183103E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.164337E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13125024.35 | 0.129077E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456631.83 | 0.113412E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7465547.17 | 0.826973E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67121534.18 | 0.561408E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149556E+09 | 0.455478E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784840.44 | 0.827466E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133616E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178061E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212705E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240510E+09 | 0.161175E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.455478E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149556E+09 | 0.230303E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.229607E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182222E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162528E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13148668.98 | 0.126629E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1456631.68 | 0.110714E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7465550.37 | 0.816812E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 67156659.01 | 0.556914E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149574E+09 | 0.451933E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1784839.60 | 0.815346E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131355E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.176970E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.212062E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.240587E+09 | 0.159619E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451933E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149574E+09 | 0.229607E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273961E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219620E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198078E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 13763287.26 | 0.158735E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1493600.53 | 0.136553E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7780966.14 | 0.106350E+10 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 70001602.63 | 0.765459E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155529E+09 | 0.643295E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 1819865.03 | 0.939222E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.160227E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211153E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249089E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250388E+09 | 0.194856E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.643295E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155529E+09 | 0.273961E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6851.57 | 07-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 7078.81 | 18-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5122.21 | 22-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 996.74 | 01-APR-16:00 | 4438.64 | 18-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 321.59 | 05-MAY-16:00 | 4385.22 | 23-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 818.09 | 28-JUN-17:00 | 3812.00 | 13-JUN-14:00 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1924.05 | 24-JUL-15:00 | 3054.50 | 09-JUL-13:00 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.61 | 10-AUG-17:00 | 3187.33 | 01-AUG-11:10 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 323.57 | 14-SEP-17:00 | 3551.06 | 16-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3842.84 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5652.45 | 12-NOV-17:00 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6746.90 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3054.50 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2236.61 | 7078.81 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2418.52 | 18-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.89 | 05-MAY-16:00 | 2502.87 | 23-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.26 | 28-JUN-17:00 | 2153.29 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.61 | 24-JUL-15:00 | 1677.41 | 09-JUL-13:00 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.69 | 14-SEP-17:00 | 2019.85 | 16-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2158.44 | 29-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.72 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.41 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 176.90 | 05-MAY-16:00 | 2484.00 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.27 | 28-JUN-17:00 | 2138.78 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.61 | 24-JUL-15:00 | 1677.42 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.69 | 14-SEP-17:00 | 2030.43 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2114.96 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.42 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.01 | 05-MAY-16:00 | 2471.78 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.27 | 28-JUN-17:00 | 2135.40 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.61 | 24-JUL-15:00 | 1677.42 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.69 | 14-SEP-17:00 | 2030.57 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2086.77 | 27-OCT-16:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.42 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2443.32 | 23-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.27 | 28-JUN-17:00 | 2115.34 | 13-JUN-14:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.61 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 10-AUG-17:00 | 1742.22 | 01-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.69 | 14-SEP-17:00 | 2024.59 | 16-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.27 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 6800.61 | 07-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6907.61 | 18-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 5000.04 | 22-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 966.74 | 01-APR-16:00 | 4340.23 | 18-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 317.93 | 05-MAY-16:00 | 4249.39 | 23-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 807.01 | 28-JUN-17:00 | 3689.87 | 13-JUN-14:00 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1898.04 | 24-JUL-15:00 | 3013.29 | 09-JUL-13:00 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.13 | 10-AUG-17:00 | 3126.95 | 01-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 319.18 | 14-SEP-17:00 | 3607.07 | 16-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3682.21 | 31-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 5588.12 | 12-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 6644.20 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3013.29 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 2211.13 | 6907.61 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2358.96 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.25 | 28-JUN-17:00 | 2045.93 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.60 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.26 | 10-AUG-17:00 | 1737.22 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 | 14-SEP-17:00 | 2005.94 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.26 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2337.33 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.25 | 28-JUN-17:00 | 2034.32 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.60 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.26 | 10-AUG-17:00 | 1735.01 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 | 14-SEP-17:00 | 1997.45 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.26 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3788.98 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3839.40 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2779.27 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 536.87 | 01-APR-16:00 | 2413.10 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.04 | 05-MAY-16:00 | 2286.69 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 449.25 | 28-JUN-17:00 | 1999.01 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1056.60 | 24-JUL-15:00 | 1677.43 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.26 | 10-AUG-17:00 | 1729.52 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 177.68 | 14-SEP-17:00 | 1970.75 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2041.32 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3111.71 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3697.90 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.43 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1231.26 | 3839.40 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 3839.94 | 07-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4010.60 | 18-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 2901.44 | 22-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 566.87 | 01-APR-16:00 | 2511.52 | 18-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 180.70 | 05-MAY-16:00 | 2258.21 | 23-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 460.29 | 28-JUN-17:00 | 2000.39 | 13-JUN-14:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1082.57 | 24-JUL-15:00 | 1677.79 | 09-JUL-13:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.71 | 10-AUG-17:00 | 1788.71 | 01-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 182.05 | 14-SEP-17:00 | 1926.43 | 16-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2201.94 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3176.04 | 12-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 3817.59 | 26-DEC-13:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1677.79 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.71 | 4010.60 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10580.25 | 07-JAN-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1211.05 |
February | 9286.63 | 18-FEB-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.23 |
March | 7437.82 | 05-MAR-09:03 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 950.73 |
April | 11109.07 | 27-APR-16:10 | 3375.03 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 911.76 | 0.00 |
May | 22162.28 | 06-MAY-08:62 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.28 |
June | 38177.51 | 20-JUN-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.06 |
July | 39792.26 | 19-JUL-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 381.28 |
August | 39689.96 | 01-AUG-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 630.04 |
September | 36806.56 | 11-SEP-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 420.70 |
October | 13713.57 | 04-OCT-08:62 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 472.47 |
November | 8198.11 | 13-NOV-09:03 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1011.17 |
December | 9616.33 | 26-DEC-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1156.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7437.82 | 1350.01 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 39792.26 | 3375.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 911.76 | 1211.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5134.49 | 07-JAN-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.81 |
February | 4488.17 | 18-FEB-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 541.78 |
March | 3120.17 | 01-MAR-09:02 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.26 |
April | 21318.49 | 02-APR-17:44 | 18224.65 | 29108.10 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 131.36 |
May | 21904.70 | 14-MAY-19:33 | 13499.74 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 24.36 |
June | 21631.04 | 29-JUN-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 290.12 |
July | 22802.10 | 05-JUL-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 227.08 |
August | 21711.16 | 01-AUG-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.50 |
September | 20600.23 | 11-SEP-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.52 |
October | 20860.03 | 04-OCT-20:01 | 10124.81 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 |
November | 4143.98 | 04-NOV-14:00 | 1349.97 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.00 |
December | 4616.02 | 26-DEC-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.34 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3120.17 | 843.73 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.03 | |
Maximum of Months | 22802.10 | 18224.65 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 620.81 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5248.09 | 07-JAN-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.00 |
February | 4992.86 | 19-FEB-09:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.35 |
March | 3284.31 | 02-MAR-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 494.88 |
April | 16620.31 | 28-APR-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.18 |
May | 19148.94 | 05-MAY-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.90 |
June | 22328.06 | 22-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.80 |
July | 22212.51 | 19-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.64 |
August | 22255.78 | 01-AUG-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.77 |
September | 22213.21 | 16-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.15 |
October | 9509.12 | 05-OCT-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.86 |
November | 3723.36 | 04-NOV-14:00 | 1349.97 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.00 |
December | 4365.12 | 26-DEC-08:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 576.93 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3284.31 | 506.24 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 224.64 | |
Maximum of Months | 22328.06 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5254.44 | 07-JAN-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.29 |
February | 5125.75 | 19-FEB-09:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.97 |
March | 3236.13 | 05-MAR-09:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.41 |
April | 15889.31 | 28-APR-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 315.06 |
May | 18742.44 | 05-MAY-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.85 |
June | 22390.49 | 22-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.77 |
July | 22242.76 | 19-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.92 |
August | 22378.60 | 01-AUG-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 343.08 |
September | 22276.80 | 16-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.16 |
October | 9034.83 | 05-OCT-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.74 |
November | 3905.77 | 13-NOV-08:04 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 475.58 |
December | 4645.41 | 26-DEC-08:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 582.12 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3236.13 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 223.92 | |
Maximum of Months | 22390.49 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 676.97 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5040.95 | 15-JAN-09:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.15 |
February | 5270.18 | 19-FEB-09:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.07 |
March | 3429.85 | 05-MAR-09:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.69 |
April | 13082.85 | 28-APR-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 314.58 |
May | 18231.17 | 07-MAY-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.76 |
June | 21938.98 | 22-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 299.43 |
July | 21937.53 | 19-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.57 |
August | 22090.08 | 01-AUG-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 340.06 |
September | 21975.27 | 16-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 318.04 |
October | 7379.89 | 05-OCT-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.28 |
November | 4086.34 | 13-NOV-08:04 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.25 |
December | 4667.32 | 26-DEC-08:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.72 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3429.85 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 164.76 | |
Maximum of Months | 22090.08 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 679.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10560.96 | 07-JAN-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1121.70 |
February | 10129.98 | 19-FEB-10:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1193.65 |
March | 7126.16 | 24-MAR-08:02 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 923.53 |
April | 9902.20 | 27-APR-14:50 | 4657.54 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 896.91 | 0.00 |
May | 33149.61 | 07-MAY-09:02 | 2970.03 | 7682.23 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.72 |
June | 37017.05 | 20-JUN-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 306.76 |
July | 38606.63 | 19-JUL-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 353.15 |
August | 38593.04 | 01-AUG-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 577.16 |
September | 37009.07 | 11-SEP-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 393.03 |
October | 11908.93 | 04-OCT-08:62 | 2970.03 | 7682.23 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 431.01 |
November | 7960.43 | 11-NOV-10:03 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.62 |
December | 8718.76 | 22-DEC-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 960.44 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7126.16 | 2970.03 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 38606.63 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 896.91 | 1193.65 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5218.85 | 07-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 618.99 |
February | 5007.95 | 19-FEB-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 651.43 |
March | 3493.33 | 24-MAR-08:02 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.55 |
April | 5102.16 | 27-APR-14:50 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 499.07 | 0.00 |
May | 15391.06 | 07-MAY-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.02 |
June | 18664.41 | 28-JUN-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.28 |
July | 19760.51 | 19-JUL-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.70 |
August | 19769.12 | 01-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 313.66 |
September | 18966.35 | 11-SEP-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.92 |
October | 4864.83 | 04-OCT-08:62 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 237.08 |
November | 3940.15 | 11-NOV-10:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 474.94 |
December | 4281.68 | 22-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3493.33 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19769.12 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 499.07 | 651.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4959.82 | 06-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.64 |
February | 4985.27 | 19-FEB-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 649.01 |
March | 3464.04 | 24-MAR-08:02 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 496.81 |
April | 4964.65 | 27-APR-14:50 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 499.07 | 0.00 |
May | 14236.62 | 07-MAY-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.83 |
June | 18494.56 | 28-JUN-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.78 |
July | 18930.48 | 19-JUL-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 191.15 |
August | 19602.40 | 01-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.34 |
September | 18790.88 | 11-SEP-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 212.30 |
October | 4542.17 | 04-OCT-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 4005.58 | 11-NOV-10:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 476.08 |
December | 4340.71 | 22-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 529.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3464.04 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19602.40 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 499.07 | 649.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4708.95 | 21-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.49 |
February | 4216.16 | 08-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 495.27 |
March | 3420.91 | 05-MAR-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 446.06 |
April | 4683.30 | 27-APR-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 528.69 | 0.00 |
May | 10425.27 | 07-MAY-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 189.25 |
June | 17206.25 | 12-JUN-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.93 |
July | 18244.55 | 20-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.43 |
August | 19336.27 | 01-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 307.77 |
September | 17904.50 | 10-SEP-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.95 |
October | 4270.16 | 04-OCT-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 359.31 |
November | 4158.19 | 13-NOV-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.15 |
December | 4285.37 | 22-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 521.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3420.91 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 19336.27 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 528.69 | 521.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3421.86 | 26-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 460.48 |
February | 4016.14 | 10-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 547.34 |
March | 3531.84 | 24-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 668.94 |
April | 4633.00 | 27-APR-14:50 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 514.24 | 0.00 |
May | 4461.72 | 15-MAY-14:10 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 99.78 |
June | 9717.19 | 28-JUN-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.36 |
July | 18852.18 | 23-JUL-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.23 |
August | 18115.98 | 09-AUG-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.28 |
September | 15865.31 | 10-SEP-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 198.05 |
October | 3814.15 | 04-OCT-14:50 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 390.22 |
November | 3951.56 | 11-NOV-10:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 531.95 |
December | 3496.49 | 30-DEC-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 437.28 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3421.86 | 1856.21 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 18852.18 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 514.24 | 668.94 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.885101E+11 | 68294.16 | 12-JAN-16:40 | 0.738899E+11 | 160041.20 | 07-JAN-09:09 |
February | 0.790793E+11 | 67916.05 | 11-FEB-17:49 | 0.463747E+11 | 152260.18 | 18-FEB-09:09 |
March | 0.870828E+11 | 66891.97 | 15-MAR-18:49 | 0.185465E+11 | 87290.19 | 24-MAR-08:09 |
April | 0.833133E+11 | 80426.56 | 27-APR-14:00 | 0.480957E+10 | 76379.97 | 18-APR-08:09 |
May | 0.865055E+11 | 77624.64 | 06-MAY-13:50 | 0.333793E+09 | 18455.86 | 18-MAY-08:39 |
June | 0.856838E+11 | 79420.59 | 28-JUN-16:10 | 1992949.46 | 819.13 | 15-JUN-08:20 |
July | 0.940060E+11 | 89117.22 | 24-JUL-14:39 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.100578E+12 | 93658.55 | 10-AUG-16:40 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.874974E+11 | 80420.31 | 14-SEP-13:39 | 17309828.41 | 2641.60 | 27-SEP-08:09 |
October | 0.870652E+11 | 67549.70 | 04-OCT-13:39 | 0.274542E+10 | 42759.68 | 30-OCT-08:09 |
November | 0.853882E+11 | 65789.49 | 17-NOV-17:10 | 0.336508E+11 | 111854.80 | 13-NOV-09:09 |
December | 0.886094E+11 | 67113.31 | 04-DEC-19:30 | 0.608875E+11 | 169477.83 | 26-DEC-09:09 |
Annual Sum or Average | 0.105332E+13 | 0.241257E+12 | ||||
Minimum of Months | 0.790793E+11 | 65789.49 | 0.00 | 0.00 | ||
Maximum of Months | 0.100578E+12 | 93658.55 | 0.738899E+11 | 169477.83 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.131697E+11 | 0.108804E+11 | 0.00 | 0.197705E+11 | 0.00 | 0.00 | 16749.37 | 0.00 | 0.00 | 0.00 | 0.558979E+10 | 0.00 |
February | 0.353889E+11 | 0.108574E+11 | 0.985143E+10 | 0.00 | 0.179145E+11 | 0.00 | 0.00 | 495710.19 | 0.00 | 0.00 | 0.00 | 0.506665E+10 | 0.00 |
March | 0.396588E+11 | 0.105979E+11 | 0.110560E+11 | 0.00 | 0.201544E+11 | 0.00 | 0.00 | 2811295.18 | 0.00 | 0.00 | 0.00 | 0.561302E+10 | 0.00 |
April | 0.379231E+11 | 0.882769E+10 | 0.105544E+11 | 0.00 | 0.193572E+11 | 0.00 | 0.00 | 0.131032E+10 | 0.00 | 0.00 | 0.00 | 0.534059E+10 | 0.00 |
May | 0.393718E+11 | 0.784065E+10 | 0.109629E+11 | 0.00 | 0.202925E+11 | 0.00 | 0.00 | 0.259043E+10 | 0.00 | 0.00 | 0.00 | 0.544728E+10 | 0.00 |
June | 0.383312E+11 | 0.689996E+10 | 0.106855E+11 | 0.00 | 0.198589E+11 | 0.00 | 0.00 | 0.467973E+10 | 0.00 | 0.00 | 0.00 | 0.522862E+10 | 0.00 |
July | 0.389786E+11 | 0.744677E+10 | 0.108424E+11 | 0.00 | 0.201204E+11 | 0.00 | 0.00 | 0.113042E+11 | 0.00 | 0.00 | 0.00 | 0.531368E+10 | 0.00 |
August | 0.396438E+11 | 0.854965E+10 | 0.110491E+11 | 0.00 | 0.204761E+11 | 0.00 | 0.00 | 0.155117E+11 | 0.00 | 0.00 | 0.00 | 0.534811E+10 | 0.00 |
September | 0.379380E+11 | 0.963399E+10 | 0.105613E+11 | 0.00 | 0.196557E+11 | 0.00 | 0.00 | 0.453870E+10 | 0.00 | 0.00 | 0.00 | 0.516964E+10 | 0.00 |
October | 0.390997E+11 | 0.114320E+11 | 0.108804E+11 | 0.00 | 0.200274E+11 | 0.00 | 0.00 | 0.222354E+09 | 0.00 | 0.00 | 0.00 | 0.540331E+10 | 0.00 |
November | 0.378782E+11 | 0.123588E+11 | 0.105443E+11 | 0.00 | 0.192390E+11 | 0.00 | 0.00 | 57346022.77 | 0.00 | 0.00 | 0.00 | 0.531061E+10 | 0.00 |
December | 0.389936E+11 | 0.135080E+11 | 0.108529E+11 | 0.00 | 0.197027E+11 | 0.00 | 0.00 | 24693.04 | 0.00 | 0.00 | 0.00 | 0.555218E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121122E+12 | 0.128721E+12 | 0.00 | 0.236569E+12 | 0.00 | 0.00 | 0.402181E+11 | 0.00 | 0.00 | 0.00 | 0.643835E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.689996E+10 | 0.985143E+10 | 0.00 | 0.179145E+11 | 0.00 | 0.00 | 16749.37 | 0.00 | 0.00 | 0.00 | 0.506665E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.135080E+11 | 0.110560E+11 | 0.00 | 0.204761E+11 | 0.00 | 0.00 | 0.155117E+11 | 0.00 | 0.00 | 0.00 | 0.561302E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.738899E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.463747E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.185465E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.480957E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.333793E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 1992949.46 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 17309828.41 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.274542E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.336508E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.608875E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.241257E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.738899E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 13690.32 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 13690.32 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 13690.32 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 13690.32 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 13690.32 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 13690.32 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 13690.32 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 13690.32 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13690.32 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 13690.32 | 01-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 13690.32 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 13690.32 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 13690.32 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 13690.32 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 27.92 | 11-JAN-21:00 | 0.00 | 0.00 | 0.00 | 11861.38 | 12-JAN-13:50 | 0.00 |
February | 281.75 | 27-FEB-23:10 | 0.00 | 0.00 | 0.00 | 12629.38 | 03-FEB-13:20 | 0.00 |
March | 430.71 | 18-MAR-21:00 | 0.00 | 0.00 | 0.00 | 9731.37 | 20-MAR-12:00 | 0.00 |
April | 24474.03 | 27-APR-14:00 | 0.00 | 0.00 | 0.00 | 9691.17 | 20-APR-11:09 | 0.00 |
May | 21888.24 | 06-MAY-12:00 | 0.00 | 0.00 | 0.00 | 9691.58 | 31-MAY-14:09 | 0.00 |
June | 24289.04 | 28-JUN-16:00 | 0.00 | 0.00 | 0.00 | 9717.00 | 03-JUN-12:39 | 0.00 |
July | 33717.54 | 24-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9687.81 | 05-JUL-11:30 | 0.00 |
August | 35909.85 | 29-AUG-14:00 | 0.00 | 0.00 | 0.00 | 9704.11 | 01-AUG-13:50 | 0.00 |
September | 25185.55 | 14-SEP-13:00 | 0.00 | 0.00 | 0.00 | 9706.23 | 30-SEP-13:00 | 0.00 |
October | 12097.58 | 04-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9718.49 | 13-OCT-12:39 | 0.00 |
November | 6211.93 | 04-NOV-14:39 | 0.00 | 0.00 | 0.00 | 7600.70 | 18-NOV-13:00 | 0.00 |
December | 19.25 | 03-DEC-22:30 | 0.00 | 0.00 | 0.00 | 11852.92 | 20-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 19.25 | 0.00 | 0.00 | 0.00 | 7600.70 | 0.00 | ||
Maximum of Months | 35909.85 | 0.00 | 0.00 | 0.00 | 12629.38 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 68294.16 | 12-JAN-16:40 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67916.05 | 11-FEB-17:49 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66891.97 | 15-MAR-18:49 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 80426.56 | 27-APR-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 24474.03 | 0.00 |
May | 77624.64 | 06-MAY-13:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 21659.67 | 0.00 |
June | 79420.59 | 28-JUN-16:10 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 23477.87 | 0.00 |
July | 89117.22 | 24-JUL-14:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 33170.70 | 0.00 |
August | 93658.55 | 10-AUG-16:40 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 35599.45 | 0.00 |
September | 80420.31 | 14-SEP-13:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 24460.54 | 0.00 |
October | 67549.70 | 04-OCT-13:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 9465.86 | 0.00 |
November | 65789.49 | 17-NOV-17:10 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 67113.31 | 04-DEC-19:30 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 65789.49 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13690.32 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 93658.55 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13690.32 | 0.00 | 0.00 | 35599.45 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 160041.20 | 07-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 152260.18 | 18-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 87290.19 | 24-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 76379.97 | 18-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 18455.86 | 18-MAY-08:39 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 819.13 | 15-JUN-08:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 2641.60 | 27-SEP-08:09 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 42759.68 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 111854.80 | 13-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 169477.83 | 26-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 169477.83 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.50 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
February | 1.17 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
December | 1.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
Annual Sum or Average | 4.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.50 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 | 0.00 | 20.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.00 | 175.83 | 20.95 | 175.83 | 20.91 |
February | 447.00 | 21.19 | 123.50 | 21.10 | 123.50 | 21.04 |
March | 497.00 | 21.50 | 33.00 | 21.45 | 33.00 | 21.40 |
April | 401.00 | 22.18 | 29.67 | 22.25 | 6.50 | 22.22 |
May | 218.17 | 22.86 | 73.17 | 23.12 | 0.00 | 23.12 |
June | 68.33 | 23.38 | 165.33 | 23.75 | 0.00 | 23.75 |
July | 17.50 | 23.70 | 340.67 | 23.90 | 0.00 | 23.90 |
August | 13.00 | 23.61 | 405.33 | 23.92 | 0.00 | 23.92 |
September | 86.17 | 23.23 | 249.17 | 23.73 | 0.00 | 23.73 |
October | 351.83 | 22.25 | 18.67 | 22.33 | 0.00 | 22.33 |
November | 455.17 | 21.32 | 43.50 | 21.32 | 33.50 | 21.27 |
December | 496.00 | 21.02 | 111.33 | 20.96 | 111.33 | 20.92 |
Annual Sum or Average | 3547.17 | 21.63 | 1769.17 | 22.10 | 483.67 | 21.99 |
Minimum of Months | 13.00 | 21.00 | 18.67 | 20.95 | 0.00 | 20.91 |
Maximum of Months | 497.00 | 23.70 | 405.33 | 23.92 | 175.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.47 | 33.50 | 21.42 | 33.50 | 21.38 |
February | 436.33 | 21.76 | 20.50 | 21.71 | 20.50 | 21.67 |
March | 483.83 | 22.41 | 0.17 | 22.41 | 0.17 | 22.41 |
April | 332.67 | 22.95 | 40.17 | 23.05 | 0.00 | 23.05 |
May | 113.67 | 23.35 | 90.83 | 23.59 | 0.00 | 23.59 |
June | 20.17 | 23.60 | 196.83 | 23.90 | 0.00 | 23.90 |
July | 5.83 | 23.49 | 340.00 | 23.93 | 0.00 | 23.93 |
August | 2.17 | 22.78 | 400.33 | 23.94 | 0.00 | 23.94 |
September | 21.33 | 23.46 | 295.67 | 23.88 | 0.00 | 23.88 |
October | 274.17 | 23.02 | 34.17 | 23.12 | 0.00 | 23.12 |
November | 439.67 | 21.97 | 22.33 | 22.05 | 2.00 | 22.04 |
December | 496.00 | 21.58 | 16.00 | 21.55 | 16.00 | 21.53 |
Annual Sum or Average | 3121.83 | 22.14 | 1490.50 | 22.67 | 72.17 | 22.63 |
Minimum of Months | 2.17 | 21.47 | 0.17 | 21.42 | 0.00 | 21.38 |
Maximum of Months | 496.00 | 23.60 | 400.33 | 23.94 | 33.50 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 67.83 | 21.12 | 67.83 | 21.12 |
February | 333.50 | 21.34 | 36.33 | 21.32 | 36.33 | 21.30 |
March | 373.00 | 21.76 | 3.67 | 21.75 | 3.67 | 21.74 |
April | 275.83 | 22.46 | 30.33 | 22.61 | 0.00 | 22.61 |
May | 107.83 | 23.03 | 75.67 | 23.45 | 0.00 | 23.45 |
June | 22.67 | 23.45 | 168.67 | 24.00 | 0.00 | 24.00 |
July | 4.67 | 23.86 | 285.33 | 24.05 | 0.17 | 24.05 |
August | 3.33 | 24.19 | 339.17 | 24.04 | 0.50 | 24.04 |
September | 35.17 | 23.28 | 219.67 | 23.90 | 0.00 | 23.90 |
October | 238.67 | 22.50 | 23.83 | 22.64 | 0.00 | 22.64 |
November | 344.83 | 21.47 | 17.67 | 21.54 | 7.00 | 21.53 |
December | 369.00 | 21.14 | 38.33 | 21.14 | 38.33 | 21.13 |
Annual Sum or Average | 2479.50 | 21.72 | 1306.50 | 22.40 | 153.83 | 22.35 |
Minimum of Months | 3.33 | 21.12 | 3.67 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 373.00 | 24.19 | 339.17 | 24.05 | 67.83 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 80.67 | 21.12 | 80.67 | 21.12 |
February | 336.00 | 21.33 | 45.17 | 21.30 | 45.17 | 21.28 |
March | 379.00 | 21.70 | 8.00 | 21.69 | 8.00 | 21.68 |
April | 286.33 | 22.37 | 29.67 | 22.52 | 0.00 | 22.52 |
May | 117.00 | 23.00 | 72.50 | 23.41 | 0.00 | 23.41 |
June | 24.00 | 23.44 | 163.83 | 23.99 | 0.00 | 23.99 |
July | 5.17 | 23.85 | 285.17 | 24.05 | 0.17 | 24.05 |
August | 3.33 | 24.19 | 339.83 | 24.04 | 0.50 | 24.04 |
September | 39.33 | 23.25 | 215.17 | 23.88 | 0.00 | 23.88 |
October | 247.50 | 22.38 | 20.83 | 22.50 | 0.00 | 22.50 |
November | 345.67 | 21.42 | 21.83 | 21.47 | 12.67 | 21.46 |
December | 369.00 | 21.13 | 49.00 | 21.13 | 49.00 | 21.13 |
Annual Sum or Average | 2523.33 | 21.69 | 1331.67 | 22.36 | 196.17 | 22.30 |
Minimum of Months | 3.33 | 21.12 | 8.00 | 21.12 | 0.00 | 21.12 |
Maximum of Months | 379.00 | 24.19 | 339.83 | 24.05 | 80.67 | 24.05 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.12 | 104.67 | 21.11 | 104.67 | 21.11 |
February | 336.00 | 21.28 | 58.17 | 21.26 | 58.17 | 21.24 |
March | 379.00 | 21.58 | 13.50 | 21.56 | 13.50 | 21.55 |
April | 298.33 | 22.23 | 23.17 | 22.35 | 0.83 | 22.34 |
May | 140.67 | 22.93 | 66.00 | 23.30 | 0.00 | 23.30 |
June | 35.83 | 23.41 | 149.00 | 23.94 | 0.00 | 23.94 |
July | 7.50 | 23.80 | 275.83 | 24.04 | 0.17 | 24.04 |
August | 5.67 | 23.94 | 332.67 | 24.03 | 0.50 | 24.04 |
September | 55.50 | 23.18 | 200.50 | 23.82 | 0.00 | 23.82 |
October | 266.50 | 22.23 | 17.00 | 22.34 | 0.00 | 22.34 |
November | 348.33 | 21.35 | 23.67 | 21.38 | 18.00 | 21.37 |
December | 369.00 | 21.12 | 63.83 | 21.12 | 63.83 | 21.12 |
Annual Sum or Average | 2613.33 | 21.66 | 1328.00 | 22.27 | 259.67 | 22.20 |
Minimum of Months | 5.67 | 21.12 | 13.50 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.94 | 332.67 | 24.04 | 104.67 | 24.04 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 168.00 | 21.11 | 168.00 | 21.11 |
February | 308.00 | 21.23 | 112.17 | 21.20 | 112.17 | 21.18 |
March | 348.00 | 21.41 | 20.67 | 21.39 | 20.67 | 21.38 |
April | 292.17 | 22.04 | 18.83 | 22.13 | 2.50 | 22.12 |
May | 177.17 | 22.84 | 47.83 | 23.08 | 0.00 | 23.08 |
June | 46.17 | 23.31 | 99.17 | 23.76 | 0.00 | 23.76 |
July | 10.83 | 23.59 | 230.33 | 23.93 | 0.00 | 23.93 |
August | 8.17 | 23.68 | 283.17 | 23.93 | 0.33 | 23.93 |
September | 72.50 | 23.01 | 149.83 | 23.63 | 0.00 | 23.63 |
October | 260.50 | 21.98 | 8.83 | 22.04 | 0.00 | 22.04 |
November | 322.00 | 21.25 | 29.67 | 21.26 | 26.83 | 21.25 |
December | 338.00 | 21.11 | 113.33 | 21.11 | 113.33 | 21.11 |
Annual Sum or Average | 2523.50 | 21.62 | 1281.83 | 22.07 | 443.83 | 21.97 |
Minimum of Months | 8.17 | 21.11 | 8.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.68 | 283.17 | 23.93 | 168.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 166.83 | 21.11 | 166.83 | 21.11 |
February | 308.00 | 21.23 | 114.83 | 21.19 | 114.83 | 21.18 |
March | 348.00 | 21.40 | 24.83 | 21.38 | 24.83 | 21.36 |
April | 295.67 | 22.03 | 18.00 | 22.11 | 3.50 | 22.10 |
May | 195.50 | 22.89 | 39.00 | 23.07 | 0.00 | 23.07 |
June | 53.67 | 23.37 | 81.00 | 23.74 | 0.00 | 23.74 |
July | 12.50 | 23.64 | 214.17 | 23.94 | 0.00 | 23.94 |
August | 9.33 | 23.70 | 263.33 | 23.93 | 0.33 | 23.93 |
September | 77.33 | 23.05 | 135.17 | 23.62 | 0.00 | 23.62 |
October | 264.67 | 21.99 | 5.17 | 22.03 | 0.00 | 22.03 |
November | 322.83 | 21.25 | 29.33 | 21.24 | 29.33 | 21.23 |
December | 338.00 | 21.11 | 112.83 | 21.11 | 112.83 | 21.11 |
Annual Sum or Average | 2565.50 | 21.64 | 1204.50 | 22.04 | 452.50 | 21.94 |
Minimum of Months | 9.33 | 21.11 | 5.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.70 | 263.33 | 23.94 | 166.83 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 173.33 | 21.11 | 173.33 | 21.11 |
February | 308.00 | 21.22 | 117.83 | 21.19 | 117.83 | 21.17 |
March | 348.00 | 21.37 | 30.33 | 21.35 | 30.33 | 21.33 |
April | 297.67 | 21.98 | 18.00 | 22.05 | 4.33 | 22.04 |
May | 212.50 | 22.86 | 36.67 | 23.03 | 0.00 | 23.03 |
June | 64.00 | 23.35 | 76.67 | 23.70 | 0.00 | 23.70 |
July | 15.00 | 23.63 | 209.00 | 23.93 | 0.00 | 23.93 |
August | 11.67 | 23.68 | 258.17 | 23.92 | 0.33 | 23.93 |
September | 83.33 | 23.00 | 130.17 | 23.57 | 0.00 | 23.57 |
October | 269.33 | 21.95 | 4.67 | 21.98 | 0.17 | 21.98 |
November | 324.00 | 21.24 | 32.50 | 21.23 | 32.50 | 21.22 |
December | 338.00 | 21.11 | 120.00 | 21.11 | 120.00 | 21.11 |
Annual Sum or Average | 2611.50 | 21.64 | 1207.33 | 22.02 | 478.83 | 21.92 |
Minimum of Months | 11.67 | 21.11 | 4.67 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.68 | 258.17 | 23.93 | 173.33 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 205.67 | 21.11 | 205.67 | 21.11 |
February | 308.00 | 21.20 | 132.67 | 21.17 | 132.67 | 21.15 |
March | 348.00 | 21.30 | 45.33 | 21.28 | 45.33 | 21.26 |
April | 300.67 | 21.86 | 20.67 | 21.92 | 8.83 | 21.89 |
May | 236.17 | 22.70 | 32.83 | 22.86 | 0.00 | 22.86 |
June | 92.00 | 23.29 | 65.17 | 23.58 | 0.00 | 23.58 |
July | 23.50 | 23.59 | 198.83 | 23.92 | 0.00 | 23.92 |
August | 15.33 | 23.56 | 246.17 | 23.91 | 0.33 | 23.92 |
September | 109.00 | 22.92 | 118.67 | 23.45 | 0.00 | 23.45 |
October | 279.00 | 21.86 | 2.83 | 21.87 | 1.00 | 21.86 |
November | 324.67 | 21.21 | 47.00 | 21.19 | 47.00 | 21.18 |
December | 338.00 | 21.11 | 153.17 | 21.11 | 153.17 | 21.11 |
Annual Sum or Average | 2714.33 | 21.64 | 1269.00 | 21.95 | 594.00 | 21.84 |
Minimum of Months | 15.33 | 21.11 | 2.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.59 | 246.17 | 23.92 | 205.67 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 321.00 | 21.11 | 321.00 | 21.11 |
February | 308.00 | 21.17 | 191.50 | 21.14 | 191.50 | 21.13 |
March | 348.00 | 21.21 | 112.33 | 21.19 | 112.33 | 21.17 |
April | 305.33 | 21.70 | 38.50 | 21.69 | 31.17 | 21.64 |
May | 260.50 | 22.39 | 24.17 | 22.51 | 1.50 | 22.50 |
June | 137.17 | 23.10 | 57.33 | 23.36 | 0.00 | 23.36 |
July | 47.83 | 23.37 | 179.67 | 23.83 | 0.00 | 23.83 |
August | 29.00 | 23.31 | 223.00 | 23.87 | 0.33 | 23.87 |
September | 146.17 | 22.66 | 103.67 | 23.19 | 0.00 | 23.19 |
October | 300.50 | 21.76 | 11.67 | 21.74 | 11.67 | 21.71 |
November | 325.67 | 21.17 | 148.33 | 21.15 | 148.33 | 21.14 |
December | 338.00 | 21.11 | 270.33 | 21.11 | 270.33 | 21.10 |
Annual Sum or Average | 2886.17 | 21.61 | 1681.50 | 21.79 | 1088.17 | 21.66 |
Minimum of Months | 29.00 | 21.11 | 11.67 | 21.11 | 0.00 | 21.10 |
Maximum of Months | 348.00 | 23.37 | 321.00 | 23.87 | 321.00 | 23.87 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.00269 | 30.51819 | -0.5275 | 11.17265 |
February | 448.00000 | 21.19194 | 32.04370 | -0.4370 | 9.95454 |
March | 497.00000 | 21.50081 | 32.99318 | -0.3065 | 7.75438 |
April | 479.00000 | 22.44738 | 35.74151 | -0.0316 | 6.61019 |
May | 496.00000 | 23.42467 | 38.58613 | -0.6872 | 16.34814 |
June | 481.00000 | 23.81993 | 39.95722 | -0.5100 | 10.82230 |
July | 495.00000 | 23.90607 | 44.01020 | -0.4067 | 8.71368 |
August | 497.00000 | 23.91733 | 47.06907 | -0.3801 | 8.25579 |
September | 479.00000 | 23.76449 | 45.75146 | -0.4919 | 10.69302 |
October | 496.00000 | 22.71933 | 39.53750 | 0.06581 | 6.39646 |
November | 480.00000 | 21.45240 | 38.66056 | -0.3032 | 8.26230 |
December | 496.00000 | 21.02338 | 32.74215 | -0.4900 | 10.28049 |
Annual Sum or Average | 5840.00000 | 22.52101 | 38.16261 | -0.3755 | 9.60817 |
Minimum of Months | 448.00000 | 21.00269 | 30.51819 | -0.6872 | 6.39646 |
Maximum of Months | 497.00000 | 23.91733 | 47.06907 | 0.06581 | 16.34814 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.47307 | 32.77856 | -0.3644 | 8.24383 |
February | 448.00000 | 21.81657 | 33.39880 | -0.2559 | 7.61151 |
March | 497.00000 | 22.44937 | 33.17159 | -0.0761 | 6.10462 |
April | 479.00000 | 23.23300 | 34.98384 | 0.15579 | 6.42092 |
May | 496.00000 | 23.75988 | 37.81394 | -0.5633 | 12.15210 |
June | 481.00000 | 23.88734 | 39.60498 | -0.4696 | 9.77046 |
July | 495.00000 | 23.88753 | 43.73734 | -0.4056 | 8.64595 |
August | 497.00000 | 23.88805 | 46.68302 | -0.3827 | 8.27722 |
September | 479.00000 | 23.86976 | 45.21227 | -0.4433 | 9.36958 |
October | 496.00000 | 23.41106 | 38.52535 | 0.22874 | 6.67180 |
November | 480.00000 | 22.12958 | 39.61060 | -0.1229 | 6.82411 |
December | 496.00000 | 21.58433 | 34.79955 | -0.3160 | 7.63059 |
Annual Sum or Average | 5840.00000 | 22.95468 | 38.38364 | -0.2516 | 8.14840 |
Minimum of Months | 448.00000 | 21.47307 | 32.77856 | -0.5633 | 6.10462 |
Maximum of Months | 497.00000 | 23.88805 | 46.68302 | 0.22874 | 12.15210 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.12329 | 30.27301 | -0.4632 | 9.62436 |
February | 336.00000 | 21.36171 | 31.40277 | -0.3650 | 8.61955 |
March | 379.00000 | 21.79080 | 31.78315 | -0.2139 | 6.81424 |
April | 360.00000 | 22.80180 | 34.36577 | 0.06443 | 6.46997 |
May | 375.00000 | 23.67081 | 37.67294 | -0.5866 | 13.15364 |
June | 366.00000 | 23.94160 | 38.89138 | -0.4557 | 9.64610 |
July | 369.00000 | 24.01129 | 43.58369 | -0.3643 | 8.12156 |
August | 379.00000 | 24.01719 | 46.70843 | -0.3363 | 7.70489 |
September | 360.00000 | 23.88058 | 44.82554 | -0.4393 | 9.54055 |
October | 371.00000 | 23.00474 | 37.95824 | 0.14282 | 6.42296 |
November | 360.00000 | 21.57609 | 37.87720 | -0.2503 | 7.55731 |
December | 369.00000 | 21.13844 | 32.08630 | -0.4310 | 9.00661 |
Annual Sum or Average | 4395.00000 | 22.70369 | 37.32467 | -0.3084 | 8.55979 |
Minimum of Months | 336.00000 | 21.12329 | 30.27301 | -0.5866 | 6.42296 |
Maximum of Months | 379.00000 | 24.01719 | 46.70843 | 0.14282 | 13.15364 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.12031 | 30.27936 | -0.4778 | 9.91672 |
February | 336.00000 | 21.32791 | 31.48678 | -0.3839 | 8.83810 |
March | 379.00000 | 21.69925 | 31.95077 | -0.2437 | 7.03716 |
April | 360.00000 | 22.69151 | 34.59047 | 0.03298 | 6.50074 |
May | 375.00000 | 23.63844 | 37.76259 | -0.6026 | 13.64368 |
June | 366.00000 | 23.93722 | 38.90900 | -0.4598 | 9.73474 |
July | 369.00000 | 24.01044 | 43.58780 | -0.3654 | 8.14177 |
August | 379.00000 | 24.01682 | 46.70995 | -0.3363 | 7.70509 |
September | 360.00000 | 23.86883 | 44.87036 | -0.4461 | 9.70788 |
October | 371.00000 | 22.88826 | 38.23269 | 0.11121 | 6.41202 |
November | 360.00000 | 21.51635 | 38.03358 | -0.2744 | 7.72180 |
December | 369.00000 | 21.13070 | 32.09738 | -0.4451 | 9.26304 |
Annual Sum or Average | 4395.00000 | 22.66436 | 37.41466 | -0.3244 | 8.72162 |
Minimum of Months | 336.00000 | 21.12031 | 30.27936 | -0.6026 | 6.41202 |
Maximum of Months | 379.00000 | 24.01682 | 46.70995 | 0.11121 | 13.64368 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11629 | 30.28855 | -0.4954 | 10.28008 |
February | 336.00000 | 21.28389 | 31.59878 | -0.4074 | 9.13990 |
March | 379.00000 | 21.57963 | 32.17917 | -0.2813 | 7.34811 |
April | 360.00000 | 22.51821 | 34.95080 | -0.0141 | 6.56232 |
May | 375.00000 | 23.55240 | 37.99637 | -0.6399 | 14.82223 |
June | 366.00000 | 23.91543 | 38.98892 | -0.4758 | 10.08917 |
July | 369.00000 | 24.00319 | 43.63779 | -0.3755 | 8.30256 |
August | 379.00000 | 24.00970 | 46.77052 | -0.3458 | 7.84346 |
September | 360.00000 | 23.82814 | 45.02175 | -0.4677 | 10.23242 |
October | 371.00000 | 22.70774 | 38.66660 | 0.06396 | 6.43180 |
November | 360.00000 | 21.43461 | 38.25331 | -0.3051 | 7.93840 |
December | 369.00000 | 21.12193 | 32.11048 | -0.4624 | 9.59133 |
Annual Sum or Average | 4395.00000 | 22.59977 | 37.57736 | -0.3507 | 9.05267 |
Minimum of Months | 336.00000 | 21.11629 | 30.28855 | -0.6399 | 6.43180 |
Maximum of Months | 379.00000 | 24.00970 | 46.77052 | 0.06396 | 14.82223 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10869 | 31.80581 | -0.5394 | 11.21574 |
February | 308.00000 | 21.22854 | 33.21996 | -0.4541 | 9.87064 |
March | 348.00000 | 21.40832 | 34.00274 | -0.3417 | 7.96276 |
April | 330.00000 | 22.25463 | 36.85680 | -0.0857 | 6.71488 |
May | 344.00000 | 23.35404 | 39.73351 | -0.7173 | 17.29148 |
June | 336.00000 | 23.82035 | 40.12566 | -0.5205 | 11.02737 |
July | 338.00000 | 23.91874 | 44.73500 | -0.4089 | 8.78292 |
August | 348.00000 | 23.91222 | 47.79752 | -0.3834 | 8.33300 |
September | 330.00000 | 23.69625 | 46.48272 | -0.5227 | 11.58623 |
October | 340.00000 | 22.42637 | 40.66122 | -0.0112 | 6.56036 |
November | 330.00000 | 21.31184 | 40.05482 | -0.3634 | 8.53998 |
December | 338.00000 | 21.11225 | 33.61605 | -0.5048 | 10.44123 |
Annual Sum or Average | 4030.00000 | 22.47306 | 39.12912 | -0.4046 | 9.86693 |
Minimum of Months | 308.00000 | 21.10869 | 31.80581 | -0.7173 | 6.56036 |
Maximum of Months | 348.00000 | 23.91874 | 47.79752 | -0.0112 | 17.29148 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10836 | 31.68498 | -0.5390 | 11.20920 |
February | 308.00000 | 21.22602 | 33.10707 | -0.4582 | 9.93126 |
March | 348.00000 | 21.40013 | 33.90874 | -0.3529 | 8.10871 |
April | 330.00000 | 22.22851 | 36.80609 | -0.1040 | 6.77707 |
May | 344.00000 | 23.33379 | 39.70588 | -0.7435 | 18.12125 |
June | 336.00000 | 23.81941 | 40.07060 | -0.5407 | 11.47130 |
July | 338.00000 | 23.91901 | 44.69074 | -0.4307 | 9.15110 |
August | 348.00000 | 23.91290 | 47.75382 | -0.4048 | 8.66494 |
September | 330.00000 | 23.69455 | 46.42250 | -0.5415 | 11.99329 |
October | 340.00000 | 22.41353 | 40.59314 | -0.0255 | 6.57984 |
November | 330.00000 | 21.30545 | 39.95870 | -0.3703 | 8.61410 |
December | 338.00000 | 21.11153 | 33.49343 | -0.5058 | 10.46152 |
Annual Sum or Average | 4030.00000 | 22.46647 | 39.05477 | -0.4183 | 10.09884 |
Minimum of Months | 308.00000 | 21.10836 | 31.68498 | -0.7435 | 6.57984 |
Maximum of Months | 348.00000 | 23.91901 | 47.75382 | -0.0255 | 18.12125 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10809 | 31.68590 | -0.5438 | 11.32044 |
February | 308.00000 | 21.21774 | 33.12873 | -0.4655 | 10.05414 |
March | 348.00000 | 21.36976 | 33.96679 | -0.3660 | 8.27734 |
April | 330.00000 | 22.17166 | 36.92776 | -0.1223 | 6.86765 |
May | 344.00000 | 23.26487 | 39.88677 | -0.7727 | 19.18453 |
June | 336.00000 | 23.80182 | 40.14032 | -0.5525 | 11.78661 |
July | 338.00000 | 23.91586 | 44.72306 | -0.4368 | 9.27025 |
August | 348.00000 | 23.91028 | 47.78674 | -0.4101 | 8.76234 |
September | 330.00000 | 23.66474 | 46.53156 | -0.5564 | 12.43556 |
October | 340.00000 | 22.35557 | 40.73913 | -0.0434 | 6.62819 |
November | 330.00000 | 21.28747 | 40.01091 | -0.3799 | 8.72921 |
December | 338.00000 | 21.11079 | 33.49447 | -0.5111 | 10.57552 |
Annual Sum or Average | 4030.00000 | 22.44183 | 39.12389 | -0.4303 | 10.33433 |
Minimum of Months | 308.00000 | 21.10809 | 31.68590 | -0.7727 | 6.62819 |
Maximum of Months | 348.00000 | 23.91586 | 47.78674 | -0.0434 | 19.18453 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10642 | 31.68121 | -0.5612 | 11.73202 |
February | 308.00000 | 21.19670 | 33.17523 | -0.4879 | 10.46772 |
March | 348.00000 | 21.30102 | 34.09447 | -0.3990 | 8.75193 |
April | 330.00000 | 22.04203 | 37.19977 | -0.1643 | 7.12639 |
May | 344.00000 | 23.08464 | 40.34564 | -0.8449 | 21.98081 |
June | 336.00000 | 23.74123 | 40.34686 | -0.5845 | 12.72554 |
July | 338.00000 | 23.90365 | 44.82253 | -0.4509 | 9.57561 |
August | 348.00000 | 23.90086 | 47.87329 | -0.4212 | 8.99214 |
September | 330.00000 | 23.57479 | 46.84478 | -0.5961 | 13.71459 |
October | 340.00000 | 22.22147 | 41.07333 | -0.0849 | 6.76413 |
November | 330.00000 | 21.25038 | 40.11156 | -0.4041 | 9.07221 |
December | 338.00000 | 21.10834 | 33.48921 | -0.5288 | 10.96847 |
Annual Sum or Average | 4030.00000 | 22.37933 | 39.29420 | -0.4610 | 11.00251 |
Minimum of Months | 308.00000 | 21.10642 | 31.68121 | -0.8449 | 6.76413 |
Maximum of Months | 348.00000 | 23.90365 | 47.87329 | -0.0849 | 21.98081 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10524 | 31.51562 | -0.6308 | 13.51578 |
February | 308.00000 | 21.16504 | 33.07994 | -0.5620 | 12.10239 |
March | 348.00000 | 21.21372 | 34.13524 | -0.4811 | 10.24126 |
April | 330.00000 | 21.86173 | 37.45743 | -0.2465 | 7.90949 |
May | 344.00000 | 22.76393 | 40.98341 | -0.9886 | 28.12785 |
June | 336.00000 | 23.58490 | 40.70885 | -0.6595 | 15.31591 |
July | 338.00000 | 23.85117 | 44.93931 | -0.4853 | 10.52718 |
August | 348.00000 | 23.86591 | 47.95186 | -0.4429 | 9.62823 |
September | 330.00000 | 23.35596 | 47.44523 | -0.6915 | 17.27821 |
October | 340.00000 | 22.00620 | 41.45805 | -0.1721 | 7.31660 |
November | 330.00000 | 21.20554 | 40.03433 | -0.4716 | 10.30927 |
December | 338.00000 | 21.10566 | 33.33097 | -0.5960 | 12.59168 |
Annual Sum or Average | 4030.00000 | 22.26671 | 39.46080 | -0.5360 | 12.92194 |
Minimum of Months | 308.00000 | 21.10524 | 31.51562 | -0.9886 | 7.31660 |
Maximum of Months | 348.00000 | 23.86591 | 47.95186 | -0.1721 | 28.12785 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 838.20 | 236.64 | 0.33 | 838.20 | 0.00 | 0.00 | 0.00 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 1.34 | 18-MAR-16:10 | 1.34 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 | 0.38 | 18-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.911882E+09 | 0.250129E+09 | 35.86 | 0.882139E+09 | 29743812.28 | 0.00 | 0.51 | 27-APR-16:10 | 0.00 | 01-APR-00:10 | 15441.53 | 27-APR-16:10 | 14852.95 | 27-APR-16:10 | 868.72 | 27-APR-17:00 | 4192.12 | 27-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.190153E+10 | 0.507245E+09 | 87.62 | 0.171898E+10 | 0.182548E+09 | 0.00 | 0.62 | 06-MAY-08:62 | 0.00 | 01-MAY-00:10 | 19174.63 | 06-MAY-08:62 | 14736.46 | 06-MAY-08:62 | 4438.16 | 06-MAY-08:62 | 4605.86 | 06-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.331633E+10 | 0.887575E+09 | 158.89 | 0.315505E+10 | 0.161275E+09 | 0.00 | 1.00 | 10-JUN-08:62 | 0.00 | 01-JUN-00:10 | 35168.21 | 12-JUN-08:62 | 29686.21 | 20-JUN-08:62 | 12556.52 | 12-JUN-08:62 | 7489.26 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.827134E+10 | 0.219414E+10 | 278.19 | 0.726194E+10 | 0.100940E+10 | 0.00 | 1.00 | 07-JUL-08:62 | 0.00 | 01-JUL-00:05 | 36447.67 | 31-JUL-08:61 | 30655.02 | 24-JUL-08:61 | 13886.61 | 11-JUL-08:62 | 7749.49 | 31-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.111233E+11 | 0.296273E+10 | 314.03 | 0.977148E+10 | 0.135180E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 36570.10 | 29-AUG-08:62 | 33687.15 | 09-AUG-08:62 | 14881.19 | 30-AUG-08:62 | 7759.46 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.317569E+10 | 0.831416E+09 | 130.57 | 0.265622E+10 | 0.519475E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 35332.04 | 14-SEP-08:62 | 24806.29 | 12-SEP-08:62 | 12471.07 | 14-SEP-08:62 | 7523.40 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.148641E+09 | 39929618.45 | 12.69 | 0.146944E+09 | 1697146.27 | 0.00 | 0.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 7771.05 | 04-OCT-15:00 | 7771.05 | 04-OCT-15:00 | 412.33 | 08-OCT-14:00 | 2058.19 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 37564609.16 | 10339621.56 | 3.83 | 28746568.18 | 8818040.99 | 0.00 | 0.15 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 4166.79 | 04-NOV-14:00 | 3232.57 | 04-NOV-14:00 | 934.22 | 04-NOV-14:00 | 1137.36 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.288863E+11 | 0.768350E+10 | 1022.02 | 0.256215E+11 | 0.326476E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.111233E+11 | 0.296273E+10 | 314.03 | 0.977148E+10 | 0.135180E+10 | 0.00 | 1.00 | 0.00 | 36570.10 | 33687.15 | 14881.19 | 7759.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 60851.45 | 16749.37 | 0.17 | 54630.04 | 6221.41 | 0.00 | 0.01 | 11-JAN-22:00 | 0.00 | 01-JAN-00:05 | 101.42 | 11-JAN-22:00 | 91.05 | 11-JAN-22:00 | 10.37 | 11-JAN-22:00 | 27.92 | 11-JAN-22:00 | 0.00 | 01-JAN-00:05 |
February | 1804778.23 | 491163.67 | 1.92 | 1721913.87 | 82864.36 | 0.00 | 0.07 | 27-FEB-23:10 | 0.00 | 01-FEB-00:10 | 1040.87 | 27-FEB-23:10 | 958.98 | 27-FEB-23:10 | 81.88 | 27-FEB-23:10 | 281.75 | 27-FEB-23:10 | 0.00 | 01-FEB-00:10 |
March | 9620589.18 | 2601735.79 | 7.22 | 9396281.87 | 224307.31 | 0.00 | 0.13 | 19-MAR-17:20 | 0.00 | 01-MAR-00:10 | 1739.94 | 19-MAR-17:20 | 1739.94 | 19-MAR-17:20 | 157.60 | 10-MAR-21:10 | 462.05 | 19-MAR-17:20 | 0.00 | 01-MAR-00:10 |
April | 0.623892E+09 | 0.161530E+09 | 43.19 | 0.603139E+09 | 20753170.10 | 0.00 | 1.00 | 01-APR-18:31 | 0.00 | 01-APR-00:10 | 18466.05 | 29-APR-18:01 | 17963.47 | 01-APR-18:31 | 3546.35 | 29-APR-18:01 | 3877.74 | 01-APR-18:31 | 0.00 | 01-APR-00:10 |
May | 0.127667E+10 | 0.320920E+09 | 93.60 | 0.114694E+10 | 0.129732E+09 | 0.00 | 1.00 | 04-MAY-20:01 | 0.00 | 01-MAY-00:10 | 19176.84 | 07-MAY-17:02 | 18016.00 | 14-MAY-18:00 | 5874.00 | 06-MAY-19:00 | 3984.56 | 07-MAY-17:02 | 0.00 | 01-MAY-00:10 |
June | 0.221587E+10 | 0.558785E+09 | 170.04 | 0.209000E+10 | 0.125875E+09 | 0.00 | 1.00 | 02-JUN-20:04 | 0.00 | 01-JUN-00:10 | 18904.31 | 11-JUN-18:00 | 18269.60 | 25-JUN-17:30 | 6563.59 | 12-JUN-08:62 | 3959.09 | 10-JUN-18:07 | 0.00 | 01-JUN-00:10 |
July | 0.511365E+10 | 0.127854E+10 | 271.07 | 0.445698E+10 | 0.656673E+09 | 0.00 | 1.00 | 05-JUL-08:62 | 0.00 | 01-JUL-00:05 | 19641.31 | 15-JUL-18:02 | 17992.44 | 23-JUL-19:17 | 7300.14 | 11-JUL-08:62 | 4107.67 | 15-JUL-18:02 | 0.00 | 01-JUL-00:05 |
August | 0.669321E+10 | 0.168074E+10 | 301.08 | 0.584525E+10 | 0.847959E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 19517.21 | 26-AUG-18:02 | 18466.01 | 08-AUG-22:00 | 7663.31 | 30-AUG-08:62 | 4141.19 | 24-AUG-20:58 | 0.00 | 01-AUG-00:10 |
September | 0.204096E+10 | 0.506424E+09 | 136.81 | 0.169717E+10 | 0.343795E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 19362.83 | 23-SEP-18:02 | 18044.55 | 10-SEP-17:01 | 7147.87 | 23-SEP-08:62 | 3992.22 | 23-SEP-18:02 | 0.00 | 01-SEP-00:10 |
October | 0.126715E+09 | 33039380.33 | 22.24 | 0.123926E+09 | 2788958.09 | 0.00 | 1.00 | 04-OCT-20:01 | 0.00 | 01-OCT-00:10 | 17773.31 | 04-OCT-20:01 | 17773.31 | 04-OCT-20:01 | 636.44 | 04-OCT-08:62 | 3654.47 | 04-OCT-20:01 | 0.00 | 01-OCT-00:10 |
November | 43429554.44 | 11444806.86 | 7.25 | 33583947.80 | 9845606.64 | 0.00 | 0.23 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 3534.45 | 04-NOV-14:00 | 2755.02 | 04-NOV-14:00 | 779.43 | 04-NOV-14:00 | 916.81 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 90161.96 | 24693.04 | 0.50 | 90161.96 | 0.00 | 0.00 | 0.01 | 03-DEC-22:30 | 0.00 | 01-DEC-00:03 | 70.29 | 03-DEC-22:30 | 70.29 | 03-DEC-22:30 | 0.00 | 03-DEC-19:40 | 19.25 | 03-DEC-22:30 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.181460E+11 | 0.455455E+10 | 1055.08 | 0.160083E+11 | 0.213773E+10 | 0.00 | ||||||||||||||
Minimum of Months | 60851.45 | 16749.37 | 0.17 | 54630.04 | 0.00 | 0.00 | 0.01 | 0.00 | 70.29 | 70.29 | 0.00 | 19.25 | 0.00 | |||||||
Maximum of Months | 0.669321E+10 | 0.168074E+10 | 301.08 | 0.584525E+10 | 0.847959E+09 | 0.00 | 1.00 | 0.00 | 19641.31 | 18466.01 | 7663.31 | 4141.19 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 589789.50 | 160937.03 | 1.33 | 589785.40 | 4.10 | 0.00 | 0.03 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 359.25 | 18-MAR-16:00 | 359.25 | 18-MAR-16:00 | 0.00 | 10-MAR-14:30 | 97.83 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.457084E+09 | 0.121060E+09 | 31.39 | 0.441794E+09 | 15289027.34 | 0.00 | 0.59 | 28-APR-07:03 | 0.00 | 01-APR-00:10 | 9303.47 | 30-APR-08:62 | 7862.01 | 27-APR-15:00 | 3426.37 | 30-APR-08:62 | 2187.17 | 30-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.940875E+09 | 0.243164E+09 | 82.03 | 0.850395E+09 | 90479424.22 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 18871.50 | 07-MAY-08:62 | 13615.55 | 07-MAY-08:62 | 5255.95 | 07-MAY-08:62 | 3902.34 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.162018E+10 | 0.419959E+09 | 150.81 | 0.154325E+10 | 76934334.62 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 18650.93 | 12-JUN-07:02 | 15442.31 | 10-JUN-07:02 | 5816.00 | 12-JUN-07:02 | 3857.28 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.374377E+10 | 0.963824E+09 | 231.68 | 0.330025E+10 | 0.443519E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 19220.48 | 31-JUL-07:01 | 15627.66 | 20-JUL-07:02 | 6913.29 | 11-JUL-07:02 | 3968.11 | 31-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.504329E+10 | 0.130435E+10 | 261.38 | 0.443527E+10 | 0.608025E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19313.59 | 30-AUG-07:02 | 15902.21 | 09-AUG-07:01 | 7963.02 | 30-AUG-07:02 | 3984.47 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.161694E+10 | 0.409475E+09 | 121.36 | 0.134723E+10 | 0.269711E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18671.97 | 01-SEP-07:02 | 13615.46 | 11-SEP-07:02 | 7110.47 | 24-SEP-08:62 | 3861.69 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 86841727.41 | 22617933.67 | 15.97 | 85643417.58 | 1198309.83 | 0.00 | 0.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4408.75 | 01-OCT-08:63 | 4281.11 | 04-OCT-15:00 | 1474.96 | 01-OCT-08:63 | 1127.21 | 01-OCT-08:63 | 0.00 | 01-OCT-00:10 |
November | 29680993.88 | 7842655.44 | 5.00 | 22725799.56 | 6955194.32 | 0.00 | 0.20 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2996.93 | 04-NOV-14:00 | 2333.05 | 04-NOV-14:00 | 663.88 | 04-NOV-14:00 | 784.31 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.135393E+11 | 0.349246E+10 | 900.95 | 0.120272E+11 | 0.151211E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.504329E+10 | 0.130435E+10 | 261.38 | 0.443527E+10 | 0.608025E+09 | 0.00 | 1.00 | 0.00 | 19313.59 | 15902.21 | 7963.02 | 3984.47 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 165048.96 | 45118.64 | 0.50 | 165048.96 | -0.0 | 0.00 | 0.01 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 185.86 | 18-MAR-16:00 | 185.86 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 | 50.78 | 18-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.442721E+09 | 0.117543E+09 | 30.17 | 0.427883E+09 | 14838197.89 | 0.00 | 0.52 | 28-APR-07:03 | 0.00 | 01-APR-00:10 | 8081.45 | 28-APR-07:03 | 7747.83 | 27-APR-15:00 | 2973.96 | 30-APR-08:62 | 2141.71 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.919828E+09 | 0.238005E+09 | 79.55 | 0.831592E+09 | 88236273.93 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 18921.58 | 07-MAY-08:62 | 13646.77 | 07-MAY-08:62 | 5274.81 | 07-MAY-08:62 | 3912.70 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.159833E+10 | 0.414590E+09 | 148.96 | 0.152267E+10 | 75666934.91 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 18701.42 | 12-JUN-07:02 | 15480.22 | 10-JUN-07:02 | 5830.92 | 12-JUN-07:02 | 3867.72 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.373308E+10 | 0.961358E+09 | 230.55 | 0.329048E+10 | 0.442601E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 19275.23 | 31-JUL-07:01 | 15668.47 | 20-JUL-07:02 | 6933.38 | 11-JUL-07:02 | 3979.34 | 31-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.504611E+10 | 0.130531E+10 | 260.76 | 0.443757E+10 | 0.608548E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19366.89 | 30-AUG-07:02 | 15959.20 | 09-AUG-07:01 | 8014.08 | 30-AUG-07:03 | 3995.43 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.160107E+10 | 0.405706E+09 | 120.15 | 0.133428E+10 | 0.266784E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18722.33 | 01-SEP-07:02 | 13656.49 | 11-SEP-07:02 | 6949.79 | 24-SEP-08:62 | 3872.10 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 82114270.19 | 21400258.62 | 16.69 | 81141231.97 | 973038.22 | 0.00 | 0.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4203.75 | 04-OCT-15:00 | 4203.75 | 04-OCT-15:00 | 918.16 | 01-OCT-08:63 | 1080.40 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 24594175.00 | 6531138.77 | 4.00 | 18853590.62 | 5740584.38 | 0.00 | 0.17 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2633.61 | 04-NOV-14:00 | 2048.65 | 04-NOV-14:00 | 584.96 | 04-NOV-14:00 | 693.46 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.134480E+11 | 0.347049E+10 | 891.33 | 0.119446E+11 | 0.150339E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.504611E+10 | 0.130531E+10 | 260.76 | 0.443757E+10 | 0.608548E+09 | 0.00 | 1.00 | 0.00 | 19366.89 | 15959.20 | 8014.08 | 3995.43 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 23.46 | 6.46 | 0.33 | 23.46 | 0.00 | 0.00 | 0.00 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 | 0.03 | 27-FEB-17:00 | 0.03 | 27-FEB-17:00 | 0.00 | 27-FEB-16:50 | 0.01 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 |
March | 15.78 | 4.34 | 0.17 | 15.78 | 0.00 | 0.00 | 0.00 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 0.03 | 14-MAR-16:00 | 0.03 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 | 0.01 | 14-MAR-16:00 | 0.00 | 01-MAR-00:10 |
April | 0.414651E+09 | 0.110555E+09 | 30.61 | 0.400955E+09 | 13696395.33 | 0.00 | 0.49 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7803.48 | 27-APR-15:00 | 7484.28 | 27-APR-16:10 | 1627.10 | 30-APR-08:62 | 2076.48 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.862324E+09 | 0.223755E+09 | 76.62 | 0.780317E+09 | 82007354.16 | 0.00 | 1.00 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 | 18794.46 | 07-MAY-08:62 | 13519.26 | 07-MAY-08:62 | 5275.20 | 07-MAY-08:62 | 3886.46 | 07-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.151722E+10 | 0.394354E+09 | 141.86 | 0.144618E+10 | 71034751.79 | 0.00 | 1.00 | 10-JUN-07:02 | 0.00 | 01-JUN-00:10 | 18575.71 | 12-JUN-07:02 | 15341.63 | 10-JUN-07:02 | 5822.47 | 12-JUN-07:02 | 3841.70 | 12-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.360329E+10 | 0.929514E+09 | 226.58 | 0.317625E+10 | 0.427036E+09 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 19147.40 | 31-JUL-07:01 | 15530.69 | 20-JUL-07:02 | 6918.77 | 11-JUL-07:02 | 3953.07 | 31-JUL-07:01 | 0.00 | 01-JUL-00:05 |
August | 0.488948E+10 | 0.126721E+10 | 254.89 | 0.430246E+10 | 0.587025E+09 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19237.38 | 30-AUG-07:02 | 15820.92 | 09-AUG-07:01 | 7961.06 | 30-AUG-07:02 | 3968.89 | 30-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.153101E+10 | 0.388695E+09 | 114.97 | 0.127656E+10 | 0.254456E+09 | 0.00 | 1.00 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 | 18596.55 | 01-SEP-07:02 | 13537.15 | 11-SEP-07:02 | 6873.90 | 14-SEP-07:02 | 3846.07 | 01-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 73394174.41 | 19138533.90 | 13.19 | 72800525.72 | 593648.69 | 0.00 | 0.28 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4024.06 | 04-OCT-15:00 | 4024.06 | 04-OCT-15:00 | 205.75 | 08-OCT-14:00 | 1036.96 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 17991724.73 | 4810490.35 | 3.67 | 13812116.60 | 4179608.13 | 0.00 | 0.14 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 | 2119.37 | 04-NOV-14:00 | 1646.09 | 04-NOV-14:00 | 473.28 | 04-NOV-14:00 | 562.71 | 04-NOV-14:00 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.129094E+11 | 0.333804E+10 | 862.89 | 0.114693E+11 | 0.144003E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.488948E+10 | 0.126721E+10 | 254.89 | 0.430246E+10 | 0.587025E+09 | 0.00 | 1.00 | 0.00 | 19237.38 | 15820.92 | 7961.06 | 3968.89 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.701727E+09 | 0.193401E+09 | 27.03 | 0.673640E+09 | 28087281.07 | 0.00 | 0.50 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 14578.30 | 27-APR-15:00 | 13633.11 | 27-APR-15:00 | 953.11 | 27-APR-17:00 | 3971.89 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.141242E+10 | 0.378388E+09 | 67.26 | 0.127341E+10 | 0.139014E+09 | 0.00 | 1.00 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 33844.82 | 07-MAY-09:02 | 23344.37 | 07-MAY-09:02 | 10500.45 | 07-MAY-09:02 | 7207.44 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.260823E+10 | 0.700580E+09 | 129.44 | 0.247863E+10 | 0.129603E+09 | 0.00 | 1.00 | 10-JUN-08:62 | 0.00 | 01-JUN-00:10 | 33749.19 | 12-JUN-08:62 | 28883.68 | 28-JUN-08:62 | 11554.00 | 12-JUN-08:62 | 7187.14 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.640062E+10 | 0.170236E+10 | 215.92 | 0.559479E+10 | 0.805828E+09 | 0.00 | 1.00 | 07-JUL-08:62 | 0.00 | 01-JUL-00:05 | 35072.40 | 31-JUL-08:61 | 30025.54 | 24-JUL-08:61 | 12772.16 | 11-JUL-08:62 | 7457.27 | 31-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.884239E+10 | 0.236105E+10 | 243.69 | 0.771162E+10 | 0.113078E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 35142.47 | 30-AUG-08:62 | 32278.40 | 09-AUG-08:62 | 14275.85 | 30-AUG-08:62 | 7463.96 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.262552E+10 | 0.687260E+09 | 102.67 | 0.217861E+10 | 0.446910E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 34054.78 | 14-SEP-08:62 | 26821.76 | 04-SEP-09:02 | 12217.48 | 14-SEP-08:62 | 7251.02 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.118577E+09 | 31871693.14 | 10.18 | 0.117737E+09 | 839434.56 | 0.00 | 0.28 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 7443.40 | 04-OCT-15:00 | 7443.40 | 04-OCT-15:00 | 282.85 | 08-OCT-14:10 | 1972.18 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 24900101.68 | 6879401.76 | 3.00 | 19036129.09 | 5863972.59 | 0.00 | 0.12 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 | 3296.34 | 04-NOV-14:30 | 2550.64 | 04-NOV-14:40 | 746.49 | 04-NOV-14:30 | 905.70 | 04-NOV-14:30 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.227344E+11 | 0.606179E+10 | 799.19 | 0.200475E+11 | 0.268692E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.884239E+10 | 0.236105E+10 | 243.69 | 0.771162E+10 | 0.113078E+10 | 0.00 | 1.00 | 0.00 | 35142.47 | 32278.40 | 14275.85 | 7463.96 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 5.92 | 1.63 | 0.17 | 5.92 | 0.00 | 0.00 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 | 0.01 | 27-FEB-14:30 | 0.01 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 | 0.00 | 27-FEB-14:30 | 0.00 | 01-FEB-00:10 |
March | 28.69 | 7.89 | 0.33 | 28.69 | 0.00 | 0.00 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.04 | 18-MAR-13:30 | 0.04 | 18-MAR-13:30 | 0.00 | 18-MAR-13:30 | 0.01 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.357840E+09 | 95816323.99 | 27.31 | 0.343848E+09 | 13992748.88 | 0.00 | 0.50 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7523.67 | 27-APR-15:00 | 7045.45 | 27-APR-15:00 | 478.68 | 29-APR-14:50 | 1990.30 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.718720E+09 | 0.187072E+09 | 68.01 | 0.649216E+09 | 69503772.61 | 0.00 | 0.89 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 14991.58 | 07-MAY-09:02 | 10345.72 | 07-MAY-09:02 | 4645.86 | 07-MAY-09:02 | 3212.93 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.133293E+10 | 0.347888E+09 | 128.30 | 0.126938E+10 | 63550064.10 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17382.73 | 12-JUN-08:62 | 14881.05 | 28-JUN-08:62 | 5948.09 | 12-JUN-08:62 | 3595.09 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.329103E+10 | 0.850118E+09 | 213.72 | 0.288276E+10 | 0.408267E+09 | 0.00 | 1.00 | 07-JUL-08:62 | 0.00 | 01-JUL-00:05 | 18064.03 | 31-JUL-08:61 | 15475.08 | 24-JUL-08:61 | 6574.18 | 11-JUL-08:62 | 3730.16 | 31-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.455777E+10 | 0.118168E+10 | 242.60 | 0.398361E+10 | 0.574155E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18099.87 | 30-AUG-08:62 | 16630.01 | 09-AUG-08:62 | 7350.50 | 30-AUG-08:62 | 3733.34 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.135306E+10 | 0.343872E+09 | 102.91 | 0.112561E+10 | 0.227456E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17539.86 | 14-SEP-08:62 | 12937.92 | 11-SEP-08:62 | 6290.29 | 14-SEP-08:62 | 3626.99 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 61494015.89 | 16042891.70 | 10.18 | 61072987.49 | 421028.40 | 0.00 | 0.29 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3900.85 | 04-OCT-15:00 | 3900.85 | 04-OCT-15:00 | 142.92 | 08-OCT-14:10 | 1002.55 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 12617399.98 | 3385510.57 | 3.00 | 9671551.49 | 2945848.49 | 0.00 | 0.12 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1724.80 | 04-NOV-14:40 | 1337.86 | 04-NOV-14:40 | 386.94 | 04-NOV-14:40 | 460.02 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.116855E+11 | 0.302587E+10 | 796.54 | 0.103252E+11 | 0.136029E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.455777E+10 | 0.118168E+10 | 242.60 | 0.398361E+10 | 0.574155E+09 | 0.00 | 1.00 | 0.00 | 18099.87 | 16630.01 | 7350.50 | 3733.34 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 7435.14 | 2048.70 | 0.33 | 7435.14 | -0.0 | 0.00 | 0.00 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 | 12.36 | 27-FEB-17:00 | 12.36 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 | 3.41 | 27-FEB-17:00 | 0.00 | 01-FEB-00:10 |
March | 71.95 | 19.80 | 0.17 | 71.95 | 0.00 | 0.00 | 0.00 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.12 | 18-MAR-13:30 | 0.12 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 | 0.03 | 18-MAR-13:30 | 0.00 | 01-MAR-00:10 |
April | 0.345937E+09 | 92801511.70 | 26.08 | 0.332367E+09 | 13570103.24 | 0.00 | 0.49 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7373.50 | 27-APR-15:00 | 6901.61 | 27-APR-15:00 | 471.89 | 27-APR-15:00 | 1954.12 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.689713E+09 | 0.179784E+09 | 64.43 | 0.622897E+09 | 66815964.34 | 0.00 | 0.82 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 13358.57 | 07-MAY-09:02 | 9204.21 | 07-MAY-09:02 | 4154.37 | 07-MAY-09:02 | 2930.86 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.129556E+10 | 0.338526E+09 | 125.21 | 0.123410E+10 | 61460144.53 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17287.03 | 12-JUN-08:62 | 14783.48 | 28-JUN-08:62 | 5932.23 | 12-JUN-08:62 | 3575.29 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.323228E+10 | 0.835615E+09 | 211.77 | 0.283103E+10 | 0.401253E+09 | 0.00 | 1.00 | 08-JUL-08:62 | 0.00 | 01-JUL-00:05 | 17965.43 | 31-JUL-08:61 | 15374.30 | 24-JUL-08:61 | 6553.17 | 11-JUL-08:62 | 3709.89 | 31-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.449213E+10 | 0.116536E+10 | 240.75 | 0.392606E+10 | 0.566070E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18001.66 | 30-AUG-08:62 | 16524.32 | 09-AUG-08:62 | 7325.16 | 30-AUG-08:62 | 3713.16 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.132278E+10 | 0.336394E+09 | 101.26 | 0.110043E+10 | 0.222351E+09 | 0.00 | 1.00 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 | 17444.07 | 14-SEP-08:62 | 12851.27 | 11-SEP-08:62 | 6269.14 | 14-SEP-08:62 | 3607.20 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 57993162.24 | 15140870.47 | 9.62 | 57647545.85 | 345616.38 | 0.00 | 0.28 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3797.87 | 04-OCT-15:00 | 3797.87 | 04-OCT-15:00 | 129.27 | 08-OCT-14:10 | 977.57 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 11058764.19 | 2972640.17 | 2.83 | 8482007.25 | 2576756.94 | 0.00 | 0.12 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1591.70 | 04-NOV-14:40 | 1233.84 | 04-NOV-14:40 | 357.87 | 04-NOV-14:40 | 425.48 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.114475E+11 | 0.296660E+10 | 782.45 | 0.101130E+11 | 0.133444E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.449213E+10 | 0.116536E+10 | 240.75 | 0.392606E+10 | 0.566070E+09 | 0.00 | 1.00 | 0.00 | 18001.66 | 16524.32 | 7325.16 | 3713.16 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 9036.26 | 2489.73 | 0.17 | 9036.26 | -0.0 | 0.00 | 0.00 | 27-FEB-16:20 | 0.00 | 01-FEB-00:10 | 15.06 | 27-FEB-16:20 | 15.06 | 27-FEB-16:20 | 0.00 | 01-FEB-00:10 | 4.15 | 27-FEB-16:20 | 0.00 | 01-FEB-00:10 |
March | 280.29 | 77.09 | 0.33 | 280.29 | 0.00 | 0.00 | 0.00 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 | 0.24 | 18-MAR-13:40 | 0.24 | 18-MAR-13:40 | 0.00 | 18-MAR-13:40 | 0.07 | 18-MAR-13:40 | 0.00 | 01-MAR-00:10 |
April | 0.319488E+09 | 86118688.26 | 24.83 | 0.307004E+09 | 12483932.87 | 0.00 | 0.48 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7074.45 | 27-APR-15:00 | 6616.64 | 27-APR-15:00 | 457.81 | 27-APR-15:00 | 1883.38 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.623916E+09 | 0.163282E+09 | 60.12 | 0.563520E+09 | 60395767.83 | 0.00 | 0.52 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 | 7805.02 | 07-MAY-09:02 | 5560.74 | 04-MAY-15:00 | 2452.25 | 07-MAY-09:02 | 1870.39 | 07-MAY-09:02 | 0.00 | 01-MAY-00:10 |
June | 0.120656E+10 | 0.316358E+09 | 116.04 | 0.115078E+10 | 55785288.75 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17213.80 | 12-JUN-08:62 | 13230.44 | 28-JUN-08:62 | 5955.68 | 12-JUN-08:62 | 3560.14 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.308965E+10 | 0.800989E+09 | 203.65 | 0.270808E+10 | 0.381564E+09 | 0.00 | 1.00 | 20-JUL-08:62 | 0.00 | 01-JUL-00:05 | 17892.79 | 31-JUL-08:61 | 15276.08 | 24-JUL-08:61 | 5501.06 | 25-JUL-08:62 | 3695.18 | 31-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.435254E+10 | 0.113117E+10 | 234.61 | 0.380590E+10 | 0.546643E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17930.12 | 30-AUG-08:62 | 16426.50 | 09-AUG-08:62 | 7334.11 | 30-AUG-08:62 | 3698.81 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.125157E+10 | 0.319022E+09 | 97.90 | 0.104176E+10 | 0.209808E+09 | 0.00 | 1.00 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 | 17373.06 | 14-SEP-08:62 | 12730.88 | 10-SEP-09:02 | 6279.67 | 14-SEP-08:62 | 3592.57 | 14-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 49797282.06 | 13038100.17 | 8.67 | 49638797.59 | 158484.46 | 0.00 | 0.27 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3529.08 | 04-OCT-15:00 | 3529.08 | 04-OCT-15:00 | 82.14 | 08-OCT-14:10 | 912.74 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 7775751.86 | 2099832.08 | 2.67 | 5973878.97 | 1801872.89 | 0.00 | 0.09 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 1263.19 | 04-NOV-14:40 | 978.17 | 04-NOV-14:40 | 285.01 | 04-NOV-14:40 | 339.66 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.109013E+11 | 0.283208E+10 | 748.99 | 0.963266E+10 | 0.126864E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.435254E+10 | 0.113117E+10 | 234.61 | 0.380590E+10 | 0.546643E+09 | 0.00 | 1.00 | 0.00 | 17930.12 | 16426.50 | 7334.11 | 3698.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 | 0.00 | 01-JAN-00:05 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 11521.54 | 3157.96 | 1.50 | 11521.54 | -0.0 | 0.00 | 0.00 | 18-MAR-16:50 | 0.00 | 01-MAR-00:10 | 18.17 | 18-MAR-16:50 | 18.17 | 18-MAR-16:50 | 0.00 | 18-MAR-16:20 | 4.98 | 18-MAR-16:50 | 0.00 | 01-MAR-00:10 |
April | 0.300012E+09 | 81366977.92 | 25.17 | 0.288706E+09 | 11306898.90 | 0.00 | 0.46 | 27-APR-15:00 | 0.00 | 01-APR-00:10 | 7100.56 | 27-APR-15:00 | 6633.51 | 27-APR-15:00 | 467.05 | 27-APR-15:00 | 1900.71 | 27-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.565447E+09 | 0.148819E+09 | 56.17 | 0.511685E+09 | 53762310.31 | 0.00 | 0.43 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 | 6728.94 | 06-MAY-13:30 | 5534.11 | 06-MAY-13:40 | 1229.52 | 06-MAY-12:50 | 1711.54 | 06-MAY-13:30 | 0.00 | 01-MAY-00:10 |
June | 0.114292E+10 | 0.301112E+09 | 107.08 | 0.109169E+10 | 51225856.68 | 0.00 | 0.47 | 28-JUN-15:00 | 0.00 | 01-JUN-00:10 | 7164.82 | 28-JUN-17:00 | 7087.98 | 28-JUN-15:00 | 917.84 | 28-JUN-08:62 | 1903.01 | 28-JUN-17:00 | 0.00 | 01-JUN-00:10 |
July | 0.302738E+10 | 0.787738E+09 | 192.32 | 0.266214E+10 | 0.365232E+09 | 0.00 | 1.00 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 | 18785.45 | 31-JUL-08:61 | 15910.42 | 24-JUL-08:61 | 4599.09 | 31-JUL-08:03 | 3879.70 | 31-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.442916E+10 | 0.115206E+10 | 219.00 | 0.388071E+10 | 0.548444E+09 | 0.00 | 1.00 | 08-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18824.78 | 10-AUG-08:61 | 17178.88 | 09-AUG-08:62 | 7836.79 | 30-AUG-08:62 | 3884.59 | 10-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.121184E+10 | 0.310433E+09 | 89.28 | 0.100788E+10 | 0.203960E+09 | 0.00 | 0.83 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 | 14014.59 | 10-SEP-09:02 | 10428.64 | 10-SEP-09:02 | 3585.95 | 10-SEP-09:02 | 3063.44 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 |
October | 38358981.82 | 10134560.73 | 5.92 | 38358981.82 | -0.0 | 0.00 | 0.22 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3022.34 | 04-OCT-15:00 | 3022.34 | 04-OCT-15:00 | 0.00 | 04-OCT-15:00 | 791.37 | 04-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 3821772.79 | 1039925.21 | 2.00 | 2944031.81 | 877740.98 | 0.00 | 0.05 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 | 771.53 | 04-NOV-14:40 | 596.75 | 04-NOV-14:40 | 174.79 | 04-NOV-14:40 | 209.50 | 04-NOV-14:40 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.107189E+11 | 0.279270E+10 | 698.44 | 0.948413E+10 | 0.123481E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.442916E+10 | 0.115206E+10 | 219.00 | 0.388071E+10 | 0.548444E+09 | 0.00 | 1.00 | 0.00 | 18824.78 | 17178.88 | 7836.79 | 3884.59 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.09 | 68.53 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.01 | 60.20 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.38 | 51.54 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.59 | 44.07 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.84 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.84 | 30.65 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.77 | 27.69 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.65 | 27.05 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.52 | 38.09 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.70 | 49.03 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.87 | 57.00 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.11 | 69.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.30 | 46.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.09 | 27.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.52 | 69.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.09 | 68.53 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.01 | 60.20 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.38 | 51.54 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.59 | 44.07 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.84 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.84 | 30.65 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.77 | 27.69 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.65 | 27.05 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.52 | 38.09 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.70 | 49.03 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.87 | 57.00 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.11 | 69.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.30 | 46.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.09 | 27.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.52 | 69.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.09 | 68.53 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.01 | 60.20 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.38 | 51.54 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.59 | 44.07 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.84 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.84 | 30.65 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.77 | 27.69 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.65 | 27.05 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.52 | 38.09 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.70 | 49.03 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.87 | 57.00 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.11 | 69.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.30 | 46.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.09 | 27.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.52 | 69.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.09 | 68.53 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.01 | 60.20 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.38 | 51.54 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.59 | 44.07 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.84 | 38.48 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.84 | 30.65 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.77 | 27.69 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.65 | 27.05 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.52 | 38.09 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.70 | 49.03 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.87 | 57.00 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.11 | 69.69 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.30 | 46.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.09 | 27.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.52 | 69.69 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 67.75 | 81.28 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 118.19 | 71.49 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 133.02 | 61.23 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 147.72 | 52.35 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 134.77 | 45.75 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 125.09 | 36.47 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 148.92 | 32.99 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 164.32 | 32.27 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 171.40 | 45.43 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 144.18 | 58.31 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 73.42 | 67.67 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 78.49 | 82.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 125.63 | 55.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 67.75 | 32.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 171.40 | 82.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 67.75 | 81.28 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 118.19 | 71.49 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 133.02 | 61.23 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 147.72 | 52.35 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 134.77 | 45.75 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 125.09 | 36.47 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 148.92 | 32.99 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 164.32 | 32.27 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 171.40 | 45.43 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 144.18 | 58.31 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 73.42 | 67.67 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 78.49 | 82.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 125.63 | 55.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 67.75 | 32.27 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 171.40 | 82.75 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.11 | 73.12 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.56 | 64.54 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.54 | 56.54 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.45 | 47.87 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.36 | 40.58 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.93 | 31.76 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.25 | 28.27 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.20 | 27.55 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.78 | 39.19 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.14 | 52.51 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.76 | 61.27 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.19 | 74.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.12 | 49.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.11 | 27.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.78 | 74.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.11 | 73.12 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.56 | 64.54 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.54 | 56.54 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.45 | 47.87 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.36 | 40.58 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.93 | 31.76 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.25 | 28.27 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.20 | 27.55 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.78 | 39.19 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.14 | 52.51 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 59.76 | 61.27 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.19 | 74.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.12 | 49.73 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.11 | 27.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.78 | 74.34 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 73.22 | 43.48 | 29.74 | 66.57 | 86.68 | 0.00 | 0.00 | 0.00 |
February | 112.60 | 69.70 | 42.90 | 116.47 | 76.60 | 0.00 | 0.00 | 0.00 |
March | 121.13 | 64.60 | 56.53 | 130.83 | 67.10 | 0.00 | 0.00 | 0.00 |
April | 127.89 | 55.53 | 72.36 | 145.20 | 56.80 | 0.00 | 0.00 | 0.00 |
May | 116.94 | 34.84 | 82.10 | 133.03 | 48.21 | 0.00 | 0.00 | 0.00 |
June | 106.99 | 28.72 | 78.26 | 124.03 | 37.77 | 0.00 | 0.00 | 0.00 |
July | 116.67 | 42.73 | 73.94 | 148.33 | 33.67 | 0.00 | 0.00 | 0.00 |
August | 125.35 | 58.45 | 66.90 | 163.82 | 32.85 | 0.00 | 0.00 | 0.00 |
September | 138.88 | 76.70 | 62.19 | 170.54 | 46.73 | 0.00 | 0.00 | 0.00 |
October | 125.80 | 77.67 | 48.13 | 142.36 | 62.41 | 0.00 | 0.00 | 0.00 |
November | 74.38 | 42.63 | 31.75 | 72.11 | 72.68 | 0.00 | 0.00 | 0.00 |
December | 77.82 | 50.36 | 27.46 | 77.40 | 88.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.76 | 53.68 | 56.07 | 124.25 | 59.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 73.22 | 28.72 | 27.46 | 66.57 | 32.85 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.88 | 77.67 | 82.10 | 170.54 | 88.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.29 | 70.69 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.90 | 62.44 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.97 | 54.65 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.82 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.41 | 40.91 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.78 | 32.78 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.97 | 29.77 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.98 | 29.23 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.74 | 40.16 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 51.72 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.10 | 59.29 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.42 | 72.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.25 | 49.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.29 | 29.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.74 | 72.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.29 | 70.69 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 96.90 | 62.44 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 108.97 | 54.65 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 120.82 | 47.00 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.41 | 40.91 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.78 | 32.78 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.97 | 29.77 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.98 | 29.23 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.74 | 40.16 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.46 | 51.72 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.10 | 59.29 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.42 | 72.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.25 | 49.17 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.29 | 29.23 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.74 | 72.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.43 | 83.37 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.25 | 73.72 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 130.63 | 64.51 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 144.86 | 55.47 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.37 | 48.32 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 123.18 | 38.74 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.19 | 35.23 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.65 | 34.62 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.56 | 47.59 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 141.95 | 61.14 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.12 | 69.97 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.25 | 85.10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.72 | 58.08 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.43 | 34.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.56 | 85.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.43 | 69.59 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.15 | 61.47 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.29 | 53.58 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.20 | 46.12 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.58 | 40.53 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.83 | 32.64 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.99 | 29.75 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.97 | 29.25 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.81 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.76 | 50.82 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.33 | 58.24 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.56 | 71.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.43 | 48.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.43 | 29.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.81 | 71.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.43 | 69.59 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.15 | 61.47 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.29 | 53.58 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.20 | 46.12 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.58 | 40.53 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 102.83 | 32.64 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 122.99 | 29.75 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 135.97 | 29.25 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 141.81 | 39.96 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 118.76 | 50.82 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.33 | 58.24 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.56 | 71.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.43 | 48.53 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.43 | 29.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 141.81 | 71.08 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.61 | 82.06 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.55 | 72.57 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 131.01 | 63.25 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.31 | 54.44 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 132.58 | 47.88 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 123.24 | 38.57 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.21 | 35.20 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.65 | 34.65 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.63 | 47.36 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.31 | 60.07 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.40 | 68.72 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.43 | 83.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 123.93 | 57.32 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.61 | 34.65 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.63 | 83.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.62 | 68.65 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.45 | 60.61 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.68 | 52.53 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.76 | 45.11 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.96 | 39.92 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.04 | 32.25 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.13 | 29.42 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.10 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.01 | 39.50 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.20 | 49.72 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.62 | 57.24 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.74 | 70.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.71 | 47.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.62 | 28.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.01 | 70.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 55.62 | 68.65 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 97.45 | 60.61 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 109.68 | 52.53 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 121.76 | 45.11 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 110.96 | 39.92 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.04 | 32.25 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.13 | 29.42 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.10 | 28.92 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.01 | 39.50 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.20 | 49.72 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 60.62 | 57.24 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 64.74 | 70.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 103.71 | 47.78 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 55.62 | 28.92 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.01 | 70.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 66.83 | 80.95 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 116.90 | 71.56 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 131.49 | 62.03 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 145.97 | 53.25 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 133.03 | 47.16 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 123.50 | 38.12 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.38 | 34.82 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 162.80 | 34.26 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 169.87 | 46.82 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 142.83 | 58.78 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 72.74 | 67.55 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 77.64 | 82.85 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.27 | 56.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 66.83 | 34.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 169.87 | 82.85 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.32 | 66.13 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.38 | 58.48 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.61 | 50.39 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.89 | 43.05 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.87 | 38.39 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.57 | 31.09 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.43 | 28.37 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.33 | 27.81 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.46 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.09 | 47.62 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 54.99 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.33 | 67.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.40 | 45.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.32 | 27.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.46 | 67.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.32 | 66.13 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.38 | 58.48 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.61 | 50.39 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.89 | 43.05 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.87 | 38.39 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.57 | 31.09 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.43 | 28.37 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.33 | 27.81 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.46 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.09 | 47.62 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 54.99 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.33 | 67.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.40 | 45.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.32 | 27.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.46 | 67.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.32 | 66.13 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.38 | 58.48 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.61 | 50.39 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.89 | 43.05 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.87 | 38.39 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.57 | 31.09 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.43 | 28.37 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.33 | 27.81 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.46 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.09 | 47.62 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 54.99 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.33 | 67.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.40 | 45.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.32 | 27.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.46 | 67.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.32 | 66.13 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.38 | 58.48 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.61 | 50.39 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.89 | 43.05 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.87 | 38.39 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.57 | 31.09 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.43 | 28.37 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.33 | 27.81 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.46 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.09 | 47.62 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.32 | 54.99 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.33 | 67.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.40 | 45.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.32 | 27.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.46 | 67.79 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.65 | 78.01 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.99 | 69.08 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.57 | 59.52 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.28 | 50.85 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.07 | 45.37 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.10 | 36.77 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.71 | 33.60 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.05 | 32.97 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.39 | 45.40 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.87 | 56.32 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.56 | 64.92 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.33 | 80.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.06 | 54.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.65 | 32.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.39 | 80.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.65 | 78.01 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.99 | 69.08 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.57 | 59.52 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.28 | 50.85 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.07 | 45.37 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.10 | 36.77 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.71 | 33.60 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.05 | 32.97 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.39 | 45.40 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.87 | 56.32 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.56 | 64.92 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.33 | 80.04 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.06 | 54.34 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.65 | 32.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.39 | 80.04 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.10 | 66.52 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.13 | 58.68 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.43 | 50.35 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.77 | 42.90 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.79 | 38.23 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.47 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.34 | 28.20 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.25 | 27.61 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.37 | 38.12 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.95 | 47.45 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.19 | 55.11 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.17 | 68.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.26 | 45.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.10 | 27.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.37 | 68.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.10 | 66.52 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.13 | 58.68 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.43 | 50.35 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 122.77 | 42.90 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 111.79 | 38.23 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.47 | 30.96 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.34 | 28.20 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.25 | 27.61 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.37 | 38.12 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 119.95 | 47.45 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.19 | 55.11 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.17 | 68.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.26 | 45.96 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.10 | 27.61 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.37 | 68.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.41 | 78.43 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.73 | 69.28 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.39 | 59.45 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.18 | 50.65 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.03 | 45.16 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.01 | 36.61 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.65 | 33.38 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.00 | 32.72 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.32 | 45.19 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.73 | 56.10 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.43 | 65.02 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.16 | 80.39 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 124.94 | 54.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.41 | 32.72 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.32 | 80.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.15 | 66.25 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.24 | 58.39 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.60 | 49.94 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.02 | 42.47 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.10 | 37.81 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.63 | 30.75 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.45 | 28.05 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.34 | 27.47 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.51 | 37.86 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.15 | 46.99 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.30 | 54.76 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.23 | 67.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.41 | 45.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.15 | 27.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.51 | 67.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.15 | 66.25 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.24 | 58.39 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 110.60 | 49.94 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.02 | 42.47 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.10 | 37.81 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 103.63 | 30.75 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.45 | 28.05 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.34 | 27.47 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.51 | 37.86 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.15 | 46.99 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.30 | 54.76 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.23 | 67.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.41 | 45.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.15 | 27.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.51 | 67.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.48 | 78.11 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 117.86 | 68.93 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 132.60 | 58.96 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 147.48 | 50.14 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 134.39 | 44.68 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.21 | 36.35 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 147.77 | 33.20 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.10 | 32.56 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.49 | 44.88 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 143.97 | 55.56 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.56 | 64.61 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.24 | 80.06 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.11 | 53.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.48 | 32.56 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.49 | 80.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.37 | 65.11 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.60 | 57.27 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 111.07 | 48.69 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.63 | 41.30 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.85 | 36.71 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.08 | 30.09 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.71 | 27.59 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.54 | 27.08 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.89 | 37.12 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.63 | 45.80 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.59 | 53.66 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.45 | 66.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.80 | 44.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.37 | 27.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.89 | 66.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 56.37 | 65.11 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 98.60 | 57.27 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 111.07 | 48.69 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 123.63 | 41.30 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 112.85 | 36.71 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 104.08 | 30.09 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 123.71 | 27.59 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.54 | 27.08 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 142.89 | 37.12 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 120.63 | 45.80 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 61.59 | 53.66 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 65.45 | 66.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 104.80 | 44.70 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 56.37 | 27.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 142.89 | 66.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 67.74 | 76.76 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 118.29 | 67.61 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 133.15 | 57.49 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 148.20 | 48.77 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 135.29 | 43.37 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 124.75 | 35.58 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 148.09 | 32.67 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.34 | 32.10 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 170.95 | 44.00 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 144.54 | 54.15 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 73.92 | 63.32 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 78.50 | 78.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 125.58 | 52.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 67.74 | 32.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 170.95 | 78.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 57.15 | 60.53 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 99.77 | 52.99 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 112.35 | 44.43 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 125.02 | 37.61 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 114.54 | 33.36 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 105.20 | 27.74 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 124.39 | 25.79 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.99 | 25.51 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 143.84 | 34.66 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 121.78 | 42.26 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 62.44 | 49.95 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 66.18 | 62.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 105.82 | 41.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 57.15 | 25.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 143.84 | 62.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 60.91 | 36.17 | 24.74 | 57.15 | 60.53 | 0.00 | 0.00 | 0.00 |
February | 93.67 | 57.98 | 35.69 | 99.77 | 52.99 | 0.00 | 0.00 | 0.00 |
March | 100.76 | 53.73 | 47.02 | 112.35 | 44.43 | 0.00 | 0.00 | 0.00 |
April | 106.38 | 46.19 | 60.19 | 125.02 | 37.61 | 0.00 | 0.00 | 0.00 |
May | 97.27 | 28.98 | 68.29 | 114.54 | 33.36 | 0.00 | 0.00 | 0.00 |
June | 88.99 | 23.89 | 65.10 | 105.20 | 27.74 | 0.00 | 0.00 | 0.00 |
July | 97.05 | 35.55 | 61.51 | 124.39 | 25.79 | 0.00 | 0.00 | 0.00 |
August | 104.27 | 48.62 | 55.65 | 136.99 | 25.51 | 0.00 | 0.00 | 0.00 |
September | 115.53 | 63.80 | 51.73 | 143.84 | 34.66 | 0.00 | 0.00 | 0.00 |
October | 104.65 | 64.61 | 40.04 | 121.78 | 42.26 | 0.00 | 0.00 | 0.00 |
November | 61.87 | 35.46 | 26.41 | 62.44 | 49.95 | 0.00 | 0.00 | 0.00 |
December | 64.74 | 41.89 | 22.84 | 66.18 | 62.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 91.30 | 44.66 | 46.64 | 105.82 | 41.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 60.91 | 23.89 | 22.84 | 57.15 | 25.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 115.53 | 64.61 | 68.29 | 143.84 | 62.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 72.82 | 43.24 | 29.58 | 68.69 | 71.36 | 0.00 | 0.00 | 0.00 |
February | 111.99 | 69.32 | 42.67 | 119.70 | 62.56 | 0.00 | 0.00 | 0.00 |
March | 120.46 | 64.24 | 56.22 | 134.70 | 52.48 | 0.00 | 0.00 | 0.00 |
April | 127.19 | 55.22 | 71.96 | 149.88 | 44.44 | 0.00 | 0.00 | 0.00 |
May | 116.30 | 34.65 | 81.65 | 137.31 | 39.44 | 0.00 | 0.00 | 0.00 |
June | 106.40 | 28.57 | 77.83 | 126.08 | 32.82 | 0.00 | 0.00 | 0.00 |
July | 116.03 | 42.50 | 73.54 | 148.90 | 30.54 | 0.00 | 0.00 | 0.00 |
August | 124.66 | 58.13 | 66.53 | 163.88 | 30.25 | 0.00 | 0.00 | 0.00 |
September | 138.12 | 76.28 | 61.85 | 172.08 | 41.10 | 0.00 | 0.00 | 0.00 |
October | 125.12 | 77.25 | 47.87 | 145.92 | 49.99 | 0.00 | 0.00 | 0.00 |
November | 73.97 | 42.39 | 31.58 | 74.94 | 58.94 | 0.00 | 0.00 | 0.00 |
December | 77.40 | 50.09 | 27.31 | 79.38 | 73.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 109.16 | 53.39 | 55.77 | 126.80 | 48.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 72.82 | 28.57 | 27.31 | 68.69 | 30.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 138.12 | 77.25 | 81.65 | 172.08 | 73.60 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150244E+09 | 0.183547E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237106E+09 | 0.145629E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295649E+09 | 0.138054E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.317746E+09 | 0.114224E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299547E+09 | 0.103074E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269148E+09 | 79453506.66 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331507E+09 | 74161080.35 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365998E+09 | 72448511.66 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369421E+09 | 98728890.32 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.320593E+09 | 0.131317E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157782E+09 | 0.147748E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174395E+09 | 0.186670E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328914E+10 | 0.147505E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150244E+09 | 72448511.66 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369421E+09 | 0.186670E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150244E+09 | 0.183547E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237106E+09 | 0.145629E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295649E+09 | 0.138054E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.317746E+09 | 0.114224E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299547E+09 | 0.103074E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269148E+09 | 79453506.66 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331507E+09 | 74161080.35 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365998E+09 | 72448511.66 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369421E+09 | 98728890.32 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.320593E+09 | 0.131317E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157782E+09 | 0.147748E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174395E+09 | 0.186670E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328914E+10 | 0.147505E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150244E+09 | 72448511.66 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369421E+09 | 0.186670E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150244E+09 | 0.183547E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237106E+09 | 0.145629E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295649E+09 | 0.138054E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.317746E+09 | 0.114224E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299547E+09 | 0.103074E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269148E+09 | 79453506.66 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331507E+09 | 74161080.35 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365998E+09 | 72448511.66 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369421E+09 | 98728890.32 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.320593E+09 | 0.131317E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157782E+09 | 0.147748E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174395E+09 | 0.186670E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328914E+10 | 0.147505E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150244E+09 | 72448511.66 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369421E+09 | 0.186670E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150244E+09 | 0.183547E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237106E+09 | 0.145629E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295649E+09 | 0.138054E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.317746E+09 | 0.114224E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299547E+09 | 0.103074E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269148E+09 | 79453506.66 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331507E+09 | 74161080.35 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365998E+09 | 72448511.66 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369421E+09 | 98728890.32 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.320593E+09 | 0.131317E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157782E+09 | 0.147748E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174395E+09 | 0.186670E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328914E+10 | 0.147505E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150244E+09 | 72448511.66 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369421E+09 | 0.186670E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.181458E+09 | 0.217704E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.285915E+09 | 0.172945E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.356272E+09 | 0.163991E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.382889E+09 | 0.135685E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.360967E+09 | 0.122538E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.324242E+09 | 94534779.21 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.398872E+09 | 88362396.08 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.440127E+09 | 86422316.34 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.444269E+09 | 0.117763E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.386159E+09 | 0.156188E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.190315E+09 | 0.175391E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.210235E+09 | 0.221632E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.396172E+10 | 0.175316E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.181458E+09 | 86422316.34 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.444269E+09 | 0.221632E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.181458E+09 | 0.217704E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.285915E+09 | 0.172945E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.356272E+09 | 0.163991E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.382889E+09 | 0.135685E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.360967E+09 | 0.122538E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.324242E+09 | 94534779.21 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.398872E+09 | 88362396.08 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.440127E+09 | 86422316.34 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.444269E+09 | 0.117763E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.386159E+09 | 0.156188E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.190315E+09 | 0.175391E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.210235E+09 | 0.221632E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.396172E+10 | 0.175316E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.181458E+09 | 86422316.34 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.444269E+09 | 0.221632E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147597E+09 | 0.195840E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.233586E+09 | 0.156146E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290710E+09 | 0.151449E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.312197E+09 | 0.124069E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295576E+09 | 0.108689E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266785E+09 | 82333290.67 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330104E+09 | 75728954.53 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364798E+09 | 73776891.00 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367497E+09 | 0.101577E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.316431E+09 | 0.140643E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154894E+09 | 0.158816E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.171929E+09 | 0.199107E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325211E+10 | 0.156818E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147597E+09 | 73776891.00 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367497E+09 | 0.199107E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.147597E+09 | 0.195840E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.233586E+09 | 0.156146E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.290710E+09 | 0.151449E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.312197E+09 | 0.124069E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295576E+09 | 0.108689E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266785E+09 | 82333290.67 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330104E+09 | 75728954.53 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364798E+09 | 73776891.00 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367497E+09 | 0.101577E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.316431E+09 | 0.140643E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.154894E+09 | 0.158816E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.171929E+09 | 0.199107E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325211E+10 | 0.156818E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.147597E+09 | 73776891.00 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367497E+09 | 0.199107E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.196113E+09 | 0.116453E+09 | 79660284.81 | 0.178305E+09 | 0.232158E+09 |
February | 0.272406E+09 | 0.168623E+09 | 0.103783E+09 | 0.281753E+09 | 0.185306E+09 |
March | 0.324426E+09 | 0.173013E+09 | 0.151413E+09 | 0.350426E+09 | 0.179714E+09 |
April | 0.331483E+09 | 0.143928E+09 | 0.187555E+09 | 0.376362E+09 | 0.147237E+09 |
May | 0.313202E+09 | 93305917.62 | 0.219896E+09 | 0.356316E+09 | 0.129119E+09 |
June | 0.277305E+09 | 74452992.86 | 0.202852E+09 | 0.321493E+09 | 97902491.94 |
July | 0.312494E+09 | 0.114452E+09 | 0.198042E+09 | 0.397275E+09 | 90189112.23 |
August | 0.335735E+09 | 0.156559E+09 | 0.179176E+09 | 0.438763E+09 | 87974128.21 |
September | 0.359982E+09 | 0.198794E+09 | 0.161188E+09 | 0.442032E+09 | 0.121120E+09 |
October | 0.336952E+09 | 0.208043E+09 | 0.128909E+09 | 0.381286E+09 | 0.167148E+09 |
November | 0.192791E+09 | 0.110485E+09 | 82305443.16 | 0.186897E+09 | 0.188384E+09 |
December | 0.208438E+09 | 0.134889E+09 | 73549600.79 | 0.207314E+09 | 0.236289E+09 |
Annual Sum or Average | 0.346133E+10 | 0.169300E+10 | 0.176833E+10 | 0.391822E+10 | 0.186254E+10 |
Minimum of Months | 0.192791E+09 | 74452992.86 | 73549600.79 | 0.178305E+09 | 87974128.21 |
Maximum of Months | 0.359982E+09 | 0.208043E+09 | 0.219896E+09 | 0.442032E+09 | 0.236289E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148080E+09 | 0.189346E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.234428E+09 | 0.151063E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291855E+09 | 0.146363E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313178E+09 | 0.121815E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295716E+09 | 0.109578E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266397E+09 | 84954583.82 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329375E+09 | 79747398.82 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364202E+09 | 78280613.90 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367394E+09 | 0.104087E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317285E+09 | 0.138539E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155771E+09 | 0.153687E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172535E+09 | 0.193071E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325622E+10 | 0.155053E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148080E+09 | 78280613.90 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367394E+09 | 0.193071E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148080E+09 | 0.189346E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.234428E+09 | 0.151063E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.291855E+09 | 0.146363E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.313178E+09 | 0.121815E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.295716E+09 | 0.109578E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266397E+09 | 84954583.82 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329375E+09 | 79747398.82 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364202E+09 | 78280613.90 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367394E+09 | 0.104087E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.317285E+09 | 0.138539E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.155771E+09 | 0.153687E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172535E+09 | 0.193071E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.325622E+10 | 0.155053E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148080E+09 | 78280613.90 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367394E+09 | 0.193071E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.177923E+09 | 0.223286E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.281226E+09 | 0.178346E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.349879E+09 | 0.172795E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.375465E+09 | 0.143789E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.354534E+09 | 0.129430E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.319275E+09 | 0.100404E+09 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.394237E+09 | 94366420.28 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435652E+09 | 92731762.50 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.439493E+09 | 0.123366E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.380209E+09 | 0.163754E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.186927E+09 | 0.181353E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.206911E+09 | 0.227922E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.390173E+10 | 0.183154E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.177923E+09 | 92731762.50 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.439493E+09 | 0.227922E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148473E+09 | 0.186398E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235027E+09 | 0.148704E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.292713E+09 | 0.143504E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314159E+09 | 0.119548E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296185E+09 | 0.108567E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266544E+09 | 84591161.18 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329409E+09 | 79673560.59 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364187E+09 | 78337933.14 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367559E+09 | 0.103576E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318081E+09 | 0.136114E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.156376E+09 | 0.150960E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172923E+09 | 0.190374E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.326164E+10 | 0.153035E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148473E+09 | 78337933.14 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367559E+09 | 0.190374E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148473E+09 | 0.186398E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235027E+09 | 0.148704E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.292713E+09 | 0.143504E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.314159E+09 | 0.119548E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.296185E+09 | 0.108567E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.266544E+09 | 84591161.18 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329409E+09 | 79673560.59 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364187E+09 | 78337933.14 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.367559E+09 | 0.103576E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.318081E+09 | 0.136114E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.156376E+09 | 0.150960E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.172923E+09 | 0.190374E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.326164E+10 | 0.153035E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148473E+09 | 78337933.14 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.367559E+09 | 0.190374E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.178402E+09 | 0.219801E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.281947E+09 | 0.175558E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.350906E+09 | 0.169422E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.376636E+09 | 0.141119E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.355096E+09 | 0.128237E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.319450E+09 | 99975834.45 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.394279E+09 | 94279582.51 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.435633E+09 | 92799997.34 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.439690E+09 | 0.122761E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.381156E+09 | 0.160894E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.187651E+09 | 0.178129E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.207379E+09 | 0.224726E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.390823E+10 | 0.180770E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.178402E+09 | 92799997.34 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.439690E+09 | 0.224726E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148965E+09 | 0.183869E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235745E+09 | 0.146632E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.293777E+09 | 0.140708E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.315602E+09 | 0.116919E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.297202E+09 | 0.106922E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.267092E+09 | 83586307.96 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329799E+09 | 78797633.14 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364532E+09 | 77461909.76 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.368077E+09 | 0.102385E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.319259E+09 | 0.133174E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157125E+09 | 0.148375E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.173388E+09 | 0.187995E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.327056E+10 | 0.150682E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148965E+09 | 77461909.76 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.368077E+09 | 0.187995E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.148965E+09 | 0.183869E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.235745E+09 | 0.146632E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.293777E+09 | 0.140708E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.315602E+09 | 0.116919E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.297202E+09 | 0.106922E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.267092E+09 | 83586307.96 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.329799E+09 | 78797633.14 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364532E+09 | 77461909.76 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.368077E+09 | 0.102385E+09 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.319259E+09 | 0.133174E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.157125E+09 | 0.148375E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.173388E+09 | 0.187995E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.327056E+10 | 0.150682E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.148965E+09 | 77461909.76 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.368077E+09 | 0.187995E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.179002E+09 | 0.216813E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.282811E+09 | 0.173114E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.352179E+09 | 0.166129E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.378353E+09 | 0.138026E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.356310E+09 | 0.126303E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.320107E+09 | 98794812.35 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.394749E+09 | 93252291.38 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436049E+09 | 91770621.31 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.440311E+09 | 0.121355E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.382559E+09 | 0.157434E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.188548E+09 | 0.175081E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.207941E+09 | 0.221908E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.391892E+10 | 0.177998E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.179002E+09 | 91770621.31 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.440311E+09 | 0.221908E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150848E+09 | 0.177116E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238003E+09 | 0.141487E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296262E+09 | 0.134952E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318529E+09 | 0.111575E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299621E+09 | 0.102811E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268451E+09 | 80586960.88 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330592E+09 | 75994574.15 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365135E+09 | 74498409.24 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369245E+09 | 99254881.88 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321662E+09 | 0.127539E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158939E+09 | 0.142544E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174987E+09 | 0.181557E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329227E+10 | 0.144991E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150848E+09 | 74498409.24 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369245E+09 | 0.181557E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150848E+09 | 0.177116E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238003E+09 | 0.141487E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296262E+09 | 0.134952E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318529E+09 | 0.111575E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299621E+09 | 0.102811E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268451E+09 | 80586960.88 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330592E+09 | 75994574.15 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365135E+09 | 74498409.24 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369245E+09 | 99254881.88 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321662E+09 | 0.127539E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158939E+09 | 0.142544E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174987E+09 | 0.181557E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329227E+10 | 0.144991E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150848E+09 | 74498409.24 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369245E+09 | 0.181557E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150848E+09 | 0.177116E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238003E+09 | 0.141487E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296262E+09 | 0.134952E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318529E+09 | 0.111575E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299621E+09 | 0.102811E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268451E+09 | 80586960.88 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330592E+09 | 75994574.15 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365135E+09 | 74498409.24 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369245E+09 | 99254881.88 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321662E+09 | 0.127539E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158939E+09 | 0.142544E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174987E+09 | 0.181557E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329227E+10 | 0.144991E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150848E+09 | 74498409.24 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369245E+09 | 0.181557E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150848E+09 | 0.177116E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238003E+09 | 0.141487E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296262E+09 | 0.134952E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318529E+09 | 0.111575E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299621E+09 | 0.102811E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268451E+09 | 80586960.88 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330592E+09 | 75994574.15 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365135E+09 | 74498409.24 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369245E+09 | 99254881.88 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321662E+09 | 0.127539E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158939E+09 | 0.142544E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174987E+09 | 0.181557E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329227E+10 | 0.144991E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150848E+09 | 74498409.24 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369245E+09 | 0.181557E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.181206E+09 | 0.208938E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.285437E+09 | 0.167112E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.355071E+09 | 0.159418E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.381745E+09 | 0.131797E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.359103E+09 | 0.121518E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321660E+09 | 95304922.68 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395634E+09 | 89984133.97 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436722E+09 | 88312033.71 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.441655E+09 | 0.117683E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.385336E+09 | 0.150848E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190672E+09 | 0.168273E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209805E+09 | 0.214369E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.394405E+10 | 0.171356E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.181206E+09 | 88312033.71 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.441655E+09 | 0.214369E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.181206E+09 | 0.208938E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.285437E+09 | 0.167112E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.355071E+09 | 0.159418E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.381745E+09 | 0.131797E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.359103E+09 | 0.121518E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321660E+09 | 95304922.68 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395634E+09 | 89984133.97 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436722E+09 | 88312033.71 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.441655E+09 | 0.117683E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.385336E+09 | 0.150848E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190672E+09 | 0.168273E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209805E+09 | 0.214369E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.394405E+10 | 0.171356E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.181206E+09 | 88312033.71 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.441655E+09 | 0.214369E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150249E+09 | 0.178166E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237405E+09 | 0.141965E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295785E+09 | 0.134852E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318221E+09 | 0.111186E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299419E+09 | 0.102389E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268182E+09 | 80259462.61 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330365E+09 | 75535112.76 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364932E+09 | 73948670.80 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369012E+09 | 98808172.39 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321269E+09 | 0.127087E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158604E+09 | 0.142842E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174549E+09 | 0.182439E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328799E+10 | 0.144948E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150249E+09 | 73948670.80 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369012E+09 | 0.182439E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150249E+09 | 0.178166E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237405E+09 | 0.141965E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.295785E+09 | 0.134852E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318221E+09 | 0.111186E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.299419E+09 | 0.102389E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268182E+09 | 80259462.61 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330365E+09 | 75535112.76 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.364932E+09 | 73948670.80 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369012E+09 | 98808172.39 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321269E+09 | 0.127087E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158604E+09 | 0.142842E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174549E+09 | 0.182439E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.328799E+10 | 0.144948E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150249E+09 | 73948670.80 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369012E+09 | 0.182439E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180557E+09 | 0.210071E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.284811E+09 | 0.167599E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.354604E+09 | 0.159223E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.381489E+09 | 0.131277E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.358976E+09 | 0.120966E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321439E+09 | 94880678.74 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395463E+09 | 89414325.51 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436569E+09 | 87642446.54 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.441460E+09 | 0.117124E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.384968E+09 | 0.150254E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190332E+09 | 0.168542E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209339E+09 | 0.215316E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.394001E+10 | 0.171231E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180557E+09 | 87642446.54 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.441460E+09 | 0.215316E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150404E+09 | 0.177450E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237670E+09 | 0.141257E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296239E+09 | 0.133747E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318871E+09 | 0.110071E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.300237E+09 | 0.101283E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268612E+09 | 79692474.03 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330642E+09 | 75121539.70 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365164E+09 | 73573214.74 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369386E+09 | 98139751.32 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321797E+09 | 0.125854E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158883E+09 | 0.141938E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174720E+09 | 0.181687E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329263E+10 | 0.143981E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150404E+09 | 73573214.74 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369386E+09 | 0.181687E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150404E+09 | 0.177450E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.237670E+09 | 0.141257E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.296239E+09 | 0.133747E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.318871E+09 | 0.110071E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.300237E+09 | 0.101283E+09 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.268612E+09 | 79692474.03 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.330642E+09 | 75121539.70 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365164E+09 | 73573214.74 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.369386E+09 | 98139751.32 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.321797E+09 | 0.125854E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.158883E+09 | 0.141938E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.174720E+09 | 0.181687E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.329263E+10 | 0.143981E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150404E+09 | 73573214.74 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.369386E+09 | 0.181687E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.180744E+09 | 0.209221E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.285129E+09 | 0.166761E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.355150E+09 | 0.157920E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.382266E+09 | 0.129963E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.359952E+09 | 0.119663E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.321955E+09 | 94213775.76 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.395795E+09 | 88926025.04 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.436848E+09 | 87198784.49 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.441908E+09 | 0.116333E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.385600E+09 | 0.148802E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.190666E+09 | 0.167473E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.209545E+09 | 0.214424E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.394556E+10 | 0.170090E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.180744E+09 | 87198784.49 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.441908E+09 | 0.214424E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150969E+09 | 0.174380E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238539E+09 | 0.138553E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.297479E+09 | 0.130403E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320443E+09 | 0.107059E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.302270E+09 | 98314329.31 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269773E+09 | 78004593.74 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331343E+09 | 73907074.69 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365700E+09 | 72534277.87 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370380E+09 | 96211442.48 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.323093E+09 | 0.122661E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.159651E+09 | 0.139091E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.175307E+09 | 0.178681E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330495E+10 | 0.140980E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150969E+09 | 72534277.87 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370380E+09 | 0.178681E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.150969E+09 | 0.174380E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.238539E+09 | 0.138553E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.297479E+09 | 0.130403E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.320443E+09 | 0.107059E+09 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.302270E+09 | 98314329.31 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.269773E+09 | 78004593.74 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.331343E+09 | 73907074.69 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.365700E+09 | 72534277.87 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.370380E+09 | 96211442.48 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.323093E+09 | 0.122661E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.159651E+09 | 0.139091E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.175307E+09 | 0.178681E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.330495E+10 | 0.140980E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.150969E+09 | 72534277.87 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.370380E+09 | 0.178681E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.181428E+09 | 0.205593E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.286174E+09 | 0.163565E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.356640E+09 | 0.153977E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.384142E+09 | 0.126420E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.362370E+09 | 0.116167E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.323340E+09 | 92229582.85 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.396634E+09 | 87498712.04 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.437491E+09 | 85977160.84 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.443096E+09 | 0.114058E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.387148E+09 | 0.145041E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.191588E+09 | 0.164114E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.210251E+09 | 0.210865E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.396030E+10 | 0.166551E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.181428E+09 | 85977160.84 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.443096E+09 | 0.210865E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.153074E+09 | 0.162134E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.241356E+09 | 0.128195E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.300906E+09 | 0.119005E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.324061E+09 | 97492903.45 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.306794E+09 | 89351469.78 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.272668E+09 | 71903758.84 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.333162E+09 | 69067895.78 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366901E+09 | 68320460.13 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.372837E+09 | 89848109.16 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.326179E+09 | 0.113195E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.161855E+09 | 0.129467E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.177261E+09 | 0.167073E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.333705E+10 | 0.130505E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.153074E+09 | 68320460.13 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.372837E+09 | 0.167073E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.163135E+09 | 96870173.47 | 66264628.38 | 0.153074E+09 | 0.162134E+09 |
February | 0.226598E+09 | 0.140267E+09 | 86330724.75 | 0.241356E+09 | 0.128195E+09 |
March | 0.269870E+09 | 0.143919E+09 | 0.125951E+09 | 0.300906E+09 | 0.119005E+09 |
April | 0.275741E+09 | 0.119725E+09 | 0.156016E+09 | 0.324061E+09 | 97492903.45 |
May | 0.260534E+09 | 77615614.49 | 0.182918E+09 | 0.306794E+09 | 89351469.78 |
June | 0.230674E+09 | 61932993.53 | 0.168741E+09 | 0.272668E+09 | 71903758.84 |
July | 0.259945E+09 | 95205737.36 | 0.164739E+09 | 0.333162E+09 | 69067895.78 |
August | 0.279278E+09 | 0.130232E+09 | 0.149046E+09 | 0.366901E+09 | 68320460.13 |
September | 0.299447E+09 | 0.165365E+09 | 0.134083E+09 | 0.372837E+09 | 89848109.16 |
October | 0.280290E+09 | 0.173058E+09 | 0.107232E+09 | 0.326179E+09 | 0.113195E+09 |
November | 0.160371E+09 | 91906174.00 | 68464977.47 | 0.161855E+09 | 0.129467E+09 |
December | 0.173387E+09 | 0.112206E+09 | 61181515.67 | 0.177261E+09 | 0.167073E+09 |
Annual Sum or Average | 0.287927E+10 | 0.140830E+10 | 0.147097E+10 | 0.333705E+10 | 0.130505E+10 |
Minimum of Months | 0.160371E+09 | 61932993.53 | 61181515.67 | 0.153074E+09 | 68320460.13 |
Maximum of Months | 0.299447E+09 | 0.173058E+09 | 0.182918E+09 | 0.372837E+09 | 0.167073E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.195041E+09 | 0.115817E+09 | 79224982.71 | 0.183991E+09 | 0.191139E+09 |
February | 0.270917E+09 | 0.167701E+09 | 0.103216E+09 | 0.289582E+09 | 0.151347E+09 |
March | 0.322653E+09 | 0.172067E+09 | 0.150586E+09 | 0.360773E+09 | 0.140549E+09 |
April | 0.329671E+09 | 0.143141E+09 | 0.186530E+09 | 0.388479E+09 | 0.115178E+09 |
May | 0.311490E+09 | 92796049.21 | 0.218694E+09 | 0.367769E+09 | 0.105632E+09 |
June | 0.275790E+09 | 74046145.90 | 0.201744E+09 | 0.326793E+09 | 85069677.33 |
July | 0.310786E+09 | 0.113827E+09 | 0.196960E+09 | 0.398806E+09 | 81811496.90 |
August | 0.333901E+09 | 0.155704E+09 | 0.178197E+09 | 0.438924E+09 | 81023683.95 |
September | 0.358015E+09 | 0.197708E+09 | 0.160307E+09 | 0.446029E+09 | 0.106543E+09 |
October | 0.335111E+09 | 0.206906E+09 | 0.128205E+09 | 0.390841E+09 | 0.133895E+09 |
November | 0.191737E+09 | 0.109882E+09 | 81855686.64 | 0.194255E+09 | 0.152768E+09 |
December | 0.207299E+09 | 0.134152E+09 | 73147690.40 | 0.212617E+09 | 0.197135E+09 |
Annual Sum or Average | 0.344241E+10 | 0.168375E+10 | 0.175867E+10 | 0.399886E+10 | 0.154209E+10 |
Minimum of Months | 0.191737E+09 | 74046145.90 | 73147690.40 | 0.183991E+09 | 81023683.95 |
Maximum of Months | 0.358015E+09 | 0.206906E+09 | 0.218694E+09 | 0.446029E+09 | 0.197135E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 359.88 | 436.68 | 390.07 | 231.63 | 158.44 | 0.00 | 0.00 |
February | 628.41 | 383.76 | 599.87 | 371.33 | 228.54 | 0.00 | 0.00 |
March | 707.56 | 328.63 | 645.29 | 344.12 | 301.16 | 0.00 | 0.00 |
April | 785.79 | 280.97 | 681.30 | 295.82 | 385.48 | 0.00 | 0.00 |
May | 716.89 | 245.43 | 622.96 | 185.59 | 437.37 | 0.00 | 0.00 |
June | 665.54 | 195.56 | 569.95 | 153.02 | 416.92 | 0.00 | 0.00 |
July | 792.92 | 176.74 | 621.55 | 227.65 | 393.91 | 0.00 | 0.00 |
August | 875.24 | 172.73 | 667.78 | 311.40 | 356.38 | 0.00 | 0.00 |
September | 912.89 | 243.23 | 739.87 | 408.58 | 331.29 | 0.00 | 0.00 |
October | 767.13 | 312.74 | 670.20 | 413.80 | 256.40 | 0.00 | 0.00 |
November | 390.34 | 363.34 | 396.24 | 227.08 | 169.16 | 0.00 | 0.00 |
December | 417.43 | 444.27 | 414.59 | 268.29 | 146.29 | 0.00 | 0.00 |
Annual Sum or Average | 668.44 | 298.28 | 584.72 | 286.00 | 298.72 | 0.00 | 0.00 |
Minimum of Months | 359.88 | 172.73 | 390.07 | 153.02 | 146.29 | 0.00 | 0.00 |
Maximum of Months | 912.89 | 444.27 | 739.87 | 413.80 | 437.37 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 176.78 | 232.91 | 195.04 | 115.81 | 79.22 | 0.00 | 0.00 |
February | 309.58 | 205.69 | 299.93 | 185.66 | 114.27 | 0.00 | 0.00 |
March | 347.91 | 180.19 | 322.64 | 172.06 | 150.58 | 0.00 | 0.00 |
April | 386.09 | 152.54 | 340.65 | 147.91 | 192.74 | 0.00 | 0.00 |
May | 353.74 | 129.37 | 311.48 | 92.79 | 218.69 | 0.00 | 0.00 |
June | 329.88 | 101.30 | 284.97 | 76.51 | 208.46 | 0.00 | 0.00 |
July | 394.82 | 90.22 | 310.78 | 113.82 | 196.95 | 0.00 | 0.00 |
August | 436.22 | 87.94 | 333.89 | 155.70 | 178.19 | 0.00 | 0.00 |
September | 454.10 | 125.11 | 369.94 | 204.29 | 165.65 | 0.00 | 0.00 |
October | 378.64 | 167.43 | 335.10 | 206.90 | 128.20 | 0.00 | 0.00 |
November | 191.62 | 195.22 | 198.12 | 113.54 | 84.58 | 0.00 | 0.00 |
December | 205.78 | 236.90 | 207.29 | 134.15 | 73.15 | 0.00 | 0.00 |
Annual Sum or Average | 330.49 | 158.51 | 292.36 | 143.00 | 149.36 | 0.00 | 0.00 |
Minimum of Months | 176.78 | 87.94 | 195.04 | 76.51 | 73.15 | 0.00 | 0.00 |
Maximum of Months | 454.10 | 236.90 | 369.94 | 206.90 | 218.69 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.00 | 224.75 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 310.05 | 198.61 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 348.56 | 173.80 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 386.50 | 149.47 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 353.18 | 130.15 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 328.73 | 104.29 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 393.14 | 94.78 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 434.61 | 93.07 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 453.04 | 127.91 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 378.87 | 164.59 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 192.31 | 188.55 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 206.09 | 229.26 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 330.23 | 156.41 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 177.00 | 93.07 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 453.04 | 229.26 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 177.47 | 221.25 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 310.85 | 195.50 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 349.59 | 170.41 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 387.71 | 146.69 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 353.74 | 128.95 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 328.91 | 103.84 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 393.18 | 94.69 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 434.59 | 93.14 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 453.24 | 127.28 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 379.82 | 161.71 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 193.06 | 185.20 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 206.55 | 226.06 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 330.78 | 154.38 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 177.47 | 93.14 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 453.24 | 226.06 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 178.06 | 218.25 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 311.80 | 192.78 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 350.85 | 167.09 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 389.49 | 143.47 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 354.95 | 127.00 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 329.59 | 102.61 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 393.65 | 93.66 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.00 | 92.10 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 453.88 | 125.82 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 381.23 | 158.22 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 193.98 | 182.03 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 207.11 | 223.23 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 331.69 | 152.00 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 178.06 | 92.10 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 453.88 | 223.23 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 360.59 | 420.53 | 389.27 | 231.15 | 158.12 | 0.00 | 0.00 |
February | 629.50 | 372.09 | 598.64 | 370.57 | 228.07 | 0.00 | 0.00 |
March | 707.58 | 320.58 | 643.96 | 343.42 | 300.54 | 0.00 | 0.00 |
April | 786.11 | 273.88 | 679.90 | 295.21 | 384.69 | 0.00 | 0.00 |
May | 715.61 | 244.28 | 621.68 | 185.21 | 436.48 | 0.00 | 0.00 |
June | 662.47 | 197.90 | 568.78 | 152.71 | 416.07 | 0.00 | 0.00 |
July | 789.14 | 180.68 | 620.28 | 227.18 | 393.10 | 0.00 | 0.00 |
August | 871.41 | 177.20 | 666.41 | 310.76 | 355.65 | 0.00 | 0.00 |
September | 910.61 | 243.98 | 738.36 | 407.74 | 330.61 | 0.00 | 0.00 |
October | 768.12 | 303.11 | 668.83 | 412.95 | 255.88 | 0.00 | 0.00 |
November | 392.40 | 349.82 | 395.43 | 226.62 | 168.82 | 0.00 | 0.00 |
December | 418.00 | 431.22 | 413.73 | 267.74 | 145.99 | 0.00 | 0.00 |
Annual Sum or Average | 667.72 | 292.58 | 583.52 | 285.41 | 298.11 | 0.00 | 0.00 |
Minimum of Months | 360.59 | 177.20 | 389.27 | 152.71 | 145.99 | 0.00 | 0.00 |
Maximum of Months | 910.61 | 431.22 | 738.36 | 412.95 | 436.48 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.61 | 211.47 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 314.00 | 186.64 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 353.26 | 160.14 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 392.72 | 136.44 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 357.61 | 121.62 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 330.94 | 98.53 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 394.34 | 89.79 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.50 | 87.94 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 455.05 | 121.43 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 383.63 | 151.00 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 195.81 | 175.24 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 208.50 | 216.62 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.46 | 146.22 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 179.61 | 87.94 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 455.05 | 216.62 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 179.79 | 210.62 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 314.35 | 185.71 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 353.80 | 158.83 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 393.52 | 135.07 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 358.58 | 120.31 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 331.47 | 97.84 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 394.67 | 89.30 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 435.77 | 87.49 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 455.51 | 120.61 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 384.26 | 149.53 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 196.15 | 174.13 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 208.70 | 215.72 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 333.93 | 145.25 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 179.79 | 87.49 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 455.51 | 215.72 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 180.47 | 206.97 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 315.50 | 182.15 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 355.29 | 154.86 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 395.46 | 131.38 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 361.00 | 116.78 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 332.90 | 95.77 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 395.50 | 87.86 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 436.41 | 86.26 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 456.73 | 118.24 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 385.80 | 145.74 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 197.10 | 170.64 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 209.40 | 212.15 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 335.18 | 142.22 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 180.47 | 86.26 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 456.73 | 212.15 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 183.00 | 192.43 | 194.64 | 115.58 | 79.06 | 0.00 | 0.00 |
February | 319.23 | 168.54 | 299.32 | 185.28 | 114.04 | 0.00 | 0.00 |
March | 359.39 | 141.34 | 321.98 | 171.71 | 150.27 | 0.00 | 0.00 |
April | 399.92 | 119.66 | 339.95 | 147.60 | 192.35 | 0.00 | 0.00 |
May | 366.40 | 106.16 | 310.84 | 92.60 | 218.24 | 0.00 | 0.00 |
June | 336.47 | 88.30 | 284.39 | 76.35 | 208.03 | 0.00 | 0.00 |
July | 397.67 | 82.12 | 310.14 | 113.59 | 196.55 | 0.00 | 0.00 |
August | 437.85 | 81.27 | 333.21 | 155.38 | 177.83 | 0.00 | 0.00 |
September | 459.76 | 110.43 | 369.18 | 203.87 | 165.31 | 0.00 | 0.00 |
October | 389.49 | 134.51 | 334.41 | 206.48 | 127.94 | 0.00 | 0.00 |
November | 199.83 | 158.83 | 197.72 | 113.31 | 84.41 | 0.00 | 0.00 |
December | 211.74 | 198.36 | 206.87 | 133.87 | 73.00 | 0.00 | 0.00 |
Annual Sum or Average | 338.44 | 131.66 | 291.76 | 142.71 | 149.06 | 0.00 | 0.00 |
Minimum of Months | 183.00 | 81.27 | 194.64 | 76.35 | 73.00 | 0.00 | 0.00 |
Maximum of Months | 459.76 | 198.36 | 369.18 | 206.48 | 218.24 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.963892E+09 | 0.116959E+10 | 0.104477E+10 | 0.620386E+09 | 0.424379E+09 | 0.00 | 0.00 |
February | 0.152025E+10 | 0.928404E+09 | 0.145120E+10 | 0.898314E+09 | 0.552889E+09 | 0.00 | 0.00 |
March | 0.189514E+10 | 0.880193E+09 | 0.172833E+10 | 0.921701E+09 | 0.806632E+09 | 0.00 | 0.00 |
April | 0.203676E+10 | 0.728264E+09 | 0.176593E+10 | 0.766756E+09 | 0.999171E+09 | 0.00 | 0.00 |
May | 0.192012E+10 | 0.657369E+09 | 0.166854E+10 | 0.497074E+09 | 0.117146E+10 | 0.00 | 0.00 |
June | 0.172507E+10 | 0.506882E+09 | 0.147731E+10 | 0.396638E+09 | 0.108067E+10 | 0.00 | 0.00 |
July | 0.212377E+10 | 0.473368E+09 | 0.166477E+10 | 0.609727E+09 | 0.105504E+10 | 0.00 | 0.00 |
August | 0.234424E+10 | 0.462637E+09 | 0.178858E+10 | 0.834046E+09 | 0.954537E+09 | 0.00 | 0.00 |
September | 0.236622E+10 | 0.630441E+09 | 0.191775E+10 | 0.105905E+10 | 0.858706E+09 | 0.00 | 0.00 |
October | 0.205469E+10 | 0.837642E+09 | 0.179506E+10 | 0.110832E+10 | 0.686745E+09 | 0.00 | 0.00 |
November | 0.101176E+10 | 0.941773E+09 | 0.102707E+10 | 0.588595E+09 | 0.438471E+09 | 0.00 | 0.00 |
December | 0.111805E+10 | 0.118994E+10 | 0.111043E+10 | 0.718600E+09 | 0.391825E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.210800E+11 | 0.940651E+10 | 0.184397E+11 | 0.901920E+10 | 0.942053E+10 | 0.00 | 0.00 |
Minimum of Months | 0.963892E+09 | 0.462637E+09 | 0.102707E+10 | 0.396638E+09 | 0.391825E+09 | 0.00 | 0.00 |
Maximum of Months | 0.236622E+10 | 0.118994E+10 | 0.191775E+10 | 0.110832E+10 | 0.117146E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.473498E+09 | 0.623836E+09 | 0.522383E+09 | 0.310193E+09 | 0.212190E+09 | 0.00 | 0.00 |
February | 0.748925E+09 | 0.497598E+09 | 0.725601E+09 | 0.449157E+09 | 0.276444E+09 | 0.00 | 0.00 |
March | 0.931844E+09 | 0.482611E+09 | 0.864166E+09 | 0.460850E+09 | 0.403316E+09 | 0.00 | 0.00 |
April | 0.100076E+10 | 0.395374E+09 | 0.882964E+09 | 0.383378E+09 | 0.499586E+09 | 0.00 | 0.00 |
May | 0.947467E+09 | 0.346496E+09 | 0.834269E+09 | 0.248537E+09 | 0.585732E+09 | 0.00 | 0.00 |
June | 0.855061E+09 | 0.262568E+09 | 0.738653E+09 | 0.198319E+09 | 0.540334E+09 | 0.00 | 0.00 |
July | 0.105748E+10 | 0.241647E+09 | 0.832384E+09 | 0.304863E+09 | 0.527521E+09 | 0.00 | 0.00 |
August | 0.116836E+10 | 0.235528E+09 | 0.894292E+09 | 0.417023E+09 | 0.477269E+09 | 0.00 | 0.00 |
September | 0.117703E+10 | 0.324273E+09 | 0.958876E+09 | 0.529523E+09 | 0.429353E+09 | 0.00 | 0.00 |
October | 0.101415E+10 | 0.448433E+09 | 0.897532E+09 | 0.554160E+09 | 0.343372E+09 | 0.00 | 0.00 |
November | 0.496684E+09 | 0.506015E+09 | 0.513533E+09 | 0.294298E+09 | 0.219235E+09 | 0.00 | 0.00 |
December | 0.551171E+09 | 0.634503E+09 | 0.555213E+09 | 0.359300E+09 | 0.195913E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104224E+11 | 0.499888E+10 | 0.921987E+10 | 0.450960E+10 | 0.471026E+10 | 0.00 | 0.00 |
Minimum of Months | 0.473498E+09 | 0.235528E+09 | 0.513533E+09 | 0.198319E+09 | 0.195913E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117703E+10 | 0.634503E+09 | 0.958876E+09 | 0.554160E+09 | 0.585732E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.474078E+09 | 0.601973E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.750082E+09 | 0.480471E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.933587E+09 | 0.465518E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100182E+10 | 0.387418E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.945964E+09 | 0.348585E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.852069E+09 | 0.270313E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105299E+10 | 0.253860E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116406E+10 | 0.249292E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117428E+10 | 0.331540E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101478E+10 | 0.440832E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.498468E+09 | 0.488726E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.551979E+09 | 0.614062E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104141E+11 | 0.493259E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.474078E+09 | 0.249292E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117428E+10 | 0.614062E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.475346E+09 | 0.592594E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.751999E+09 | 0.472963E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.936332E+09 | 0.456428E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100495E+10 | 0.380211E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.947466E+09 | 0.345371E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.852537E+09 | 0.269158E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105310E+10 | 0.253626E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116401E+10 | 0.249475E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117481E+10 | 0.329914E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.101732E+10 | 0.433122E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.500402E+09 | 0.480047E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.553224E+09 | 0.605475E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104315E+11 | 0.486839E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.475346E+09 | 0.249475E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117481E+10 | 0.605475E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.476929E+09 | 0.584548E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.754301E+09 | 0.466376E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.939730E+09 | 0.447542E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.100956E+10 | 0.371862E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.950711E+09 | 0.340145E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.854290E+09 | 0.265967E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105435E+10 | 0.250847E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116511E+10 | 0.246694E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117647E+10 | 0.326124E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102108E+10 | 0.423781E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.502795E+09 | 0.471830E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.554716E+09 | 0.597895E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.104600E+11 | 0.479361E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.476929E+09 | 0.246694E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117647E+10 | 0.597895E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.965801E+09 | 0.112634E+10 | 0.104262E+10 | 0.619114E+09 | 0.423508E+09 | 0.00 | 0.00 |
February | 0.152288E+10 | 0.900170E+09 | 0.144823E+10 | 0.896471E+09 | 0.551754E+09 | 0.00 | 0.00 |
March | 0.189519E+10 | 0.858642E+09 | 0.172479E+10 | 0.919810E+09 | 0.804977E+09 | 0.00 | 0.00 |
April | 0.203761E+10 | 0.709889E+09 | 0.176230E+10 | 0.765183E+09 | 0.997122E+09 | 0.00 | 0.00 |
May | 0.191669E+10 | 0.654275E+09 | 0.166511E+10 | 0.496055E+09 | 0.116906E+10 | 0.00 | 0.00 |
June | 0.171712E+10 | 0.512956E+09 | 0.147428E+10 | 0.395824E+09 | 0.107845E+10 | 0.00 | 0.00 |
July | 0.211363E+10 | 0.483946E+09 | 0.166135E+10 | 0.608476E+09 | 0.105288E+10 | 0.00 | 0.00 |
August | 0.233398E+10 | 0.474618E+09 | 0.178491E+10 | 0.832335E+09 | 0.952579E+09 | 0.00 | 0.00 |
September | 0.236029E+10 | 0.632384E+09 | 0.191382E+10 | 0.105687E+10 | 0.856945E+09 | 0.00 | 0.00 |
October | 0.205732E+10 | 0.811848E+09 | 0.179138E+10 | 0.110605E+10 | 0.685336E+09 | 0.00 | 0.00 |
November | 0.101710E+10 | 0.906722E+09 | 0.102496E+10 | 0.587388E+09 | 0.437571E+09 | 0.00 | 0.00 |
December | 0.111956E+10 | 0.115497E+10 | 0.110815E+10 | 0.717126E+09 | 0.391021E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.210572E+11 | 0.922676E+10 | 0.184019E+11 | 0.900070E+10 | 0.940120E+10 | 0.00 | 0.00 |
Minimum of Months | 0.965801E+09 | 0.474618E+09 | 0.102496E+10 | 0.395824E+09 | 0.391021E+09 | 0.00 | 0.00 |
Maximum of Months | 0.236029E+10 | 0.115497E+10 | 0.191382E+10 | 0.110605E+10 | 0.116906E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.481055E+09 | 0.566402E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.759620E+09 | 0.451528E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.946171E+09 | 0.428923E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.101793E+10 | 0.353649E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.957812E+09 | 0.325744E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.857802E+09 | 0.255399E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105619E+10 | 0.240484E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116643E+10 | 0.235540E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.117948E+10 | 0.314740E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102750E+10 | 0.404426E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.507539E+09 | 0.454225E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.558436E+09 | 0.580194E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105160E+11 | 0.461125E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.481055E+09 | 0.235540E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.117948E+10 | 0.580194E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.481550E+09 | 0.564118E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.760469E+09 | 0.449275E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.947625E+09 | 0.425412E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.102001E+10 | 0.350104E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.960426E+09 | 0.322229E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.859177E+09 | 0.253597E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105708E+10 | 0.239168E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116718E+10 | 0.234345E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.118068E+10 | 0.312612E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.102919E+10 | 0.400509E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.508431E+09 | 0.451347E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.558985E+09 | 0.577797E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105308E+11 | 0.458051E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.481550E+09 | 0.234345E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118068E+10 | 0.577797E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.483364E+09 | 0.554351E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.763250E+09 | 0.440669E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.951597E+09 | 0.414782E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.102503E+10 | 0.340538E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.966909E+09 | 0.312794E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.862886E+09 | 0.248238E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.105932E+10 | 0.235313E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.116889E+10 | 0.231045E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.118386E+10 | 0.306481E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.103333E+10 | 0.390361E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.510888E+09 | 0.442294E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.560863E+09 | 0.568226E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105702E+11 | 0.448509E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.483364E+09 | 0.231045E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.118386E+10 | 0.568226E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.490136E+09 | 0.515403E+09 | 0.521311E+09 | 0.309557E+09 | 0.211754E+09 | 0.00 | 0.00 |
February | 0.772291E+09 | 0.407734E+09 | 0.724113E+09 | 0.448236E+09 | 0.275877E+09 | 0.00 | 0.00 |
March | 0.962583E+09 | 0.378557E+09 | 0.862394E+09 | 0.459905E+09 | 0.402488E+09 | 0.00 | 0.00 |
April | 0.103660E+10 | 0.310163E+09 | 0.881152E+09 | 0.382591E+09 | 0.498561E+09 | 0.00 | 0.00 |
May | 0.981356E+09 | 0.284333E+09 | 0.832557E+09 | 0.248027E+09 | 0.584530E+09 | 0.00 | 0.00 |
June | 0.872128E+09 | 0.228876E+09 | 0.737138E+09 | 0.197912E+09 | 0.539225E+09 | 0.00 | 0.00 |
July | 0.106513E+10 | 0.219947E+09 | 0.830677E+09 | 0.304238E+09 | 0.526439E+09 | 0.00 | 0.00 |
August | 0.117273E+10 | 0.217664E+09 | 0.892457E+09 | 0.416168E+09 | 0.476290E+09 | 0.00 | 0.00 |
September | 0.119170E+10 | 0.286239E+09 | 0.956909E+09 | 0.528437E+09 | 0.428472E+09 | 0.00 | 0.00 |
October | 0.104320E+10 | 0.360284E+09 | 0.895691E+09 | 0.553023E+09 | 0.342668E+09 | 0.00 | 0.00 |
November | 0.517962E+09 | 0.411699E+09 | 0.512480E+09 | 0.293694E+09 | 0.218786E+09 | 0.00 | 0.00 |
December | 0.567137E+09 | 0.531279E+09 | 0.554074E+09 | 0.358563E+09 | 0.195511E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106729E+11 | 0.415218E+10 | 0.920095E+10 | 0.450035E+10 | 0.470060E+10 | 0.00 | 0.00 |
Minimum of Months | 0.490136E+09 | 0.217664E+09 | 0.512480E+09 | 0.197912E+09 | 0.195511E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119170E+10 | 0.531279E+09 | 0.956909E+09 | 0.553023E+09 | 0.584530E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.50 | 3.10 | 1.22 | 3.91 | -4.2 | 29.50 | 44.23 | 0.00 |
February | 5.82 | 4.07 | 1.77 | 3.94 | -3.8 | 43.80 | 82.64 | 0.00 |
March | 8.33 | 5.86 | 2.94 | 3.85 | -1.4 | 65.55 | 100.60 | 0.02 |
April | 10.85 | 8.04 | 5.25 | 4.23 | 1.22 | 89.73 | 150.02 | 0.00 |
May | 12.97 | 10.02 | 7.49 | 3.85 | 3.75 | 114.98 | 168.60 | 0.00 |
June | 15.59 | 11.80 | 8.88 | 4.02 | 5.93 | 107.53 | 199.74 | 0.01 |
July | 17.66 | 13.41 | 10.38 | 3.76 | 8.02 | 92.25 | 247.81 | 0.00 |
August | 18.80 | 14.57 | 11.86 | 3.84 | 8.90 | 79.20 | 215.47 | 0.01 |
September | 15.09 | 12.55 | 10.74 | 2.23 | 5.47 | 68.06 | 162.11 | 0.01 |
October | 11.43 | 9.19 | 7.19 | 4.02 | 2.10 | 48.18 | 106.36 | 0.04 |
November | 8.07 | 6.72 | 5.29 | 3.86 | 0.13 | 33.26 | 46.10 | 0.00 |
December | 5.42 | 4.09 | 2.46 | 3.51 | -3.8 | 24.03 | 50.49 | 0.04 |
Annual Sum or Average | 11.24 | 8.64 | 6.31 | 3.75 | 1.89 | 66.43 | 131.49 | 0.01 |
Minimum of Months | 4.50 | 3.10 | 1.22 | 2.23 | -4.2 | 24.03 | 44.23 | 0.00 |
Maximum of Months | 18.80 | 14.57 | 11.86 | 4.23 | 8.90 | 114.98 | 247.81 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.40 | 11-JAN-14:20 | 10.49 | 7.20 | 8.40 | 3.89 | 99.17 | 130.33 |
February | 20.00 | 27-FEB-14:00 | 12.17 | 5.60 | 2.60 | 5.54 | 87.00 | 691.00 |
March | 20.60 | 18-MAR-15:00 | 10.43 | 0.00 | 6.20 | 6.55 | 111.50 | 465.50 |
April | 27.20 | 27-APR-15:09 | 17.22 | 11.02 | 4.10 | 12.63 | 151.33 | 598.33 |
May | 25.00 | 05-MAY-15:00 | 17.36 | 12.80 | 2.60 | 18.99 | 208.50 | 29.50 |
June | 26.70 | 28-JUN-16:00 | 16.74 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 30.60 | 24-JUL-14:00 | 18.78 | 12.20 | 3.10 | 20.75 | 267.00 | 383.50 |
August | 31.80 | 10-AUG-16:00 | 18.70 | 11.10 | 2.60 | 16.85 | 50.50 | 750.50 |
September | 25.00 | 14-SEP-16:00 | 16.69 | 11.70 | 3.10 | 13.54 | 100.50 | 235.00 |
October | 21.70 | 04-OCT-14:00 | 11.49 | 1.70 | 5.20 | 4.92 | 56.50 | 783.50 |
November | 21.10 | 04-NOV-13:00 | 15.94 | 12.80 | 0.00 | 6.95 | 52.50 | 729.00 |
December | 13.30 | 14-DEC-11:00 | 8.44 | 3.60 | 13.90 | 5.33 | 127.50 | 85.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.30 | 8.44 | 0.00 | 0.00 | 3.89 | 50.50 | 29.50 | |
Maximum of Months | 31.80 | 18.78 | 12.80 | 13.90 | 20.75 | 267.00 | 783.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -3.9 | 07-JAN-07:00 | -3.9 | -3.9 | 2.10 | -14.4 | 0.00 | 0.00 |
February | -5.6 | 19-FEB-05:10 | -6.1 | -7.3 | 3.77 | -22.8 | 0.00 | 0.00 |
March | -0.6 | 01-MAR-06:00 | -2.0 | -3.9 | 1.50 | -17.3 | 16.50 | 102.00 |
April | 1.70 | 19-APR-04:00 | 1.21 | 0.60 | 3.10 | -11.9 | 0.00 | 0.00 |
May | 4.40 | 11-MAY-02:00 | 3.92 | 3.30 | 3.10 | -10.9 | 0.00 | 0.00 |
June | 8.30 | 15-JUN-02:00 | 7.50 | 6.70 | 3.10 | -3.2 | 0.00 | 0.00 |
July | 11.10 | 03-JUL-03:00 | 8.19 | 5.00 | 2.60 | 5.54 | 0.00 | 0.00 |
August | 11.00 | 06-AUG-04:00 | 10.57 | 10.20 | 2.60 | -3.2 | 11.00 | 135.50 |
September | 7.20 | 27-SEP-04:49 | 6.72 | 6.20 | 0.25 | -4.0 | 0.00 | 0.00 |
October | 5.60 | 13-OCT-04:00 | 4.51 | 3.30 | 2.10 | -8.5 | 0.00 | 0.00 |
November | 0.00 | 11-NOV-06:00 | -0.2 | -0.6 | 2.10 | -16.0 | 0.00 | 0.00 |
December | -1.7 | 26-DEC-06:00 | -1.7 | -1.7 | 2.10 | -15.7 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -6.1 | -7.3 | 0.25 | -22.8 | 0.00 | 0.00 | |
Maximum of Months | 11.10 | 10.57 | 10.20 | 3.77 | 5.54 | 16.50 | 135.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.49 | 11-JAN-13:00 | 14.40 | 7.20 | 8.20 | 2.85 | 105.50 | 249.00 |
February | 12.42 | 27-FEB-15:00 | 19.40 | 6.70 | 2.60 | 6.35 | 88.00 | 342.50 |
March | 12.45 | 09-MAR-11:00 | 17.20 | 8.90 | 2.10 | 12.41 | 178.00 | 40.00 |
April | 17.29 | 27-APR-14:00 | 27.20 | 11.10 | 4.10 | 12.41 | 147.50 | 646.00 |
May | 17.58 | 06-MAY-12:00 | 23.90 | 13.90 | 5.20 | 15.57 | 365.50 | 282.50 |
June | 16.74 | 28-JUN-16:00 | 26.70 | 10.60 | 3.10 | 11.84 | 131.50 | 527.00 |
July | 19.18 | 31-JUL-15:00 | 28.90 | 13.90 | 4.10 | 14.65 | 45.00 | 848.50 |
August | 20.13 | 29-AUG-12:00 | 28.90 | 15.70 | 2.60 | 17.39 | 136.50 | 655.00 |
September | 17.97 | 23-SEP-13:00 | 23.30 | 15.00 | 2.10 | 9.72 | 148.00 | 670.50 |
October | 15.15 | 01-OCT-11:00 | 17.20 | 13.90 | 4.60 | 13.73 | 236.50 | 63.50 |
November | 16.05 | 04-NOV-12:00 | 20.60 | 13.30 | 0.00 | 7.95 | 62.00 | 746.50 |
December | 10.71 | 16-DEC-11:00 | 11.70 | 10.00 | 6.70 | 7.35 | 89.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.49 | 11.70 | 6.70 | 0.00 | 2.85 | 45.00 | 0.00 | |
Maximum of Months | 20.13 | 28.90 | 15.70 | 8.20 | 17.39 | 365.50 | 848.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.00 | 11-JAN-21:00 | 11.10 | 10.49 | 4.60 | 6.75 | 0.00 | 0.00 |
February | 11.70 | 24-FEB-00:00 | 12.80 | 12.15 | 4.10 | 8.74 | 0.00 | 0.00 |
March | 11.70 | 09-MAR-16:00 | 12.80 | 12.15 | 2.10 | 8.74 | 37.50 | 0.00 |
April | 12.80 | 28-APR-12:00 | 16.70 | 14.35 | 4.10 | 8.35 | 265.50 | 596.00 |
May | 13.90 | 05-MAY-16:00 | 22.80 | 17.10 | 2.60 | 19.17 | 111.50 | 27.50 |
June | 13.90 | 12-JUN-12:00 | 16.70 | 15.00 | 3.60 | 13.16 | 263.50 | 0.00 |
July | 15.00 | 11-JUL-09:20 | 16.13 | 15.49 | 4.60 | 12.91 | 204.17 | 28.17 |
August | 16.40 | 30-AUG-07:00 | 17.40 | 16.77 | 5.20 | 12.41 | 168.50 | 34.50 |
September | 15.00 | 14-SEP-11:20 | 20.37 | 16.93 | 2.10 | 6.89 | 152.83 | 748.17 |
October | 13.90 | 01-OCT-10:00 | 16.70 | 15.01 | 4.10 | 13.16 | 184.50 | 0.00 |
November | 13.90 | 03-NOV-19:00 | 15.00 | 14.31 | 4.60 | 11.46 | 0.00 | 0.00 |
December | 10.00 | 16-DEC-10:00 | 11.10 | 10.48 | 7.70 | 6.75 | 81.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 10.00 | 11.10 | 10.48 | 2.10 | 6.75 | 0.00 | 0.00 | |
Maximum of Months | 16.40 | 22.80 | 17.10 | 7.70 | 19.17 | 265.50 | 748.17 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 11.48 | 8.35 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 11.14 | 14.81 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 11.69 | 23.26 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 12.99 | 36.00 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 14.72 | 45.46 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 16.40 | 49.26 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 17.58 | 51.50 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 17.95 | 42.11 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 17.39 | 30.76 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 16.06 | 18.91 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 14.32 | 9.65 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 12.65 | 7.39 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 14.55 | 28.19 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 11.14 | 7.39 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 17.95 | 51.50 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.357791E+09 | -233292158.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124498409.6 | 58.99 | 0.00 | 0.00 |
February | 0.325018E+09 | -213321021.5 | 0.00 | 0.00 | 672.00 | 0.00 | -111696715.9 | 58.99 | 0.00 | 0.00 |
March | 0.359422E+09 | -237339534.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122082626.1 | 58.99 | 0.00 | 0.00 |
April | 0.335572E+09 | -220458301.6 | 0.00 | 0.00 | 720.00 | 0.00 | -115113568.9 | 58.99 | 0.00 | 0.00 |
May | 0.335005E+09 | -219623957.2 | 0.00 | 0.00 | 744.00 | 0.00 | -115380866.5 | 58.99 | 0.00 | 0.00 |
June | 0.316564E+09 | -206546226.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110017492.7 | 58.99 | 0.00 | 0.00 |
July | 0.316233E+09 | -203260971.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112972062.5 | 59.00 | 0.00 | 0.00 |
August | 0.318551E+09 | -205770357.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112780475.1 | 58.99 | 0.00 | 0.00 |
September | 0.309510E+09 | -199578183.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109932134.3 | 58.99 | 0.00 | 0.00 |
October | 0.328269E+09 | -210809867.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117459315.1 | 58.99 | 0.00 | 0.00 |
November | 0.329801E+09 | -211661468.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118139836.7 | 58.99 | 0.00 | 0.00 |
December | 0.351935E+09 | -227811318.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124123245.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.398367E+10 | -0.258947E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139420E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.309510E+09 | -237339534.2 | 0.00 | 0.00 | 672.00 | 0.00 | -124498409.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.359422E+09 | -199578183.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109932134.3 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.355540E+09 | -233294060.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122246320.5 | 58.99 | 0.00 | 0.00 |
February | 0.322657E+09 | -213321694.0 | 0.00 | 0.00 | 672.00 | 0.00 | -109335159.7 | 58.99 | 0.00 | 0.00 |
March | 0.355888E+09 | -237336486.0 | 0.00 | 0.00 | 744.00 | 0.00 | -118551480.5 | 58.99 | 0.00 | 0.00 |
April | 0.332656E+09 | -220462967.1 | 0.00 | 0.00 | 720.00 | 0.00 | -112192582.7 | 58.99 | 0.00 | 0.00 |
May | 0.333380E+09 | -219627763.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113752150.5 | 58.99 | 0.00 | 0.00 |
June | 0.315827E+09 | -206541030.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109286432.1 | 58.99 | 0.00 | 0.00 |
July | 0.315820E+09 | -203266989.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112552907.3 | 58.99 | 0.00 | 0.00 |
August | 0.318228E+09 | -205768527.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112459911.5 | 58.99 | 0.00 | 0.00 |
September | 0.308786E+09 | -199578901.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109206660.8 | 58.99 | 0.00 | 0.00 |
October | 0.325724E+09 | -210815473.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114908057.7 | 58.99 | 0.00 | 0.00 |
November | 0.327237E+09 | -211655289.4 | 0.00 | 0.00 | 720.00 | 0.00 | -115582117.2 | 58.99 | 0.00 | 0.00 |
December | 0.349521E+09 | -227817344.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121703293.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.396126E+10 | -0.258949E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137178E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.308786E+09 | -237336486.0 | 0.00 | 0.00 | 672.00 | 0.00 | -122246320.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.355888E+09 | -199578901.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109206660.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329269E+09 | -205149097.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124119862.1 | 58.99 | 0.00 | 0.00 |
February | 0.298759E+09 | -187759676.3 | 0.00 | 0.00 | 672.00 | 0.00 | -110999124.1 | 58.98 | 0.00 | 0.00 |
March | 0.332244E+09 | -211818271.9 | 0.00 | 0.00 | 744.00 | 0.00 | -120425397.2 | 59.00 | 0.00 | 0.00 |
April | 0.307055E+09 | -193894459.3 | 0.00 | 0.00 | 720.00 | 0.00 | -113160411.6 | 58.99 | 0.00 | 0.00 |
May | 0.308402E+09 | -194787109.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113614645.5 | 58.99 | 0.00 | 0.00 |
June | 0.292465E+09 | -183960645.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108504143.1 | 58.99 | 0.00 | 0.00 |
July | 0.288977E+09 | -177689341.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111287649.7 | 59.00 | 0.00 | 0.00 |
August | 0.294884E+09 | -183796613.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111087177.5 | 58.99 | 0.00 | 0.00 |
September | 0.283960E+09 | -175419585.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108540279.6 | 58.98 | 0.00 | 0.00 |
October | 0.301209E+09 | -185409236.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115800040.2 | 58.99 | 0.00 | 0.00 |
November | 0.304178E+09 | -186880060.9 | 0.00 | 0.00 | 720.00 | 0.00 | -117298131.4 | 58.99 | 0.00 | 0.00 |
December | 0.322439E+09 | -198843638.5 | 0.00 | 0.00 | 744.00 | 0.00 | -123595484.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366384E+10 | -0.228541E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.137843E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.283960E+09 | -211818271.9 | 0.00 | 0.00 | 672.00 | 0.00 | -124119862.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.332244E+09 | -175419585.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108504143.1 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.329757E+09 | -205166477.7 | 0.00 | 0.00 | 744.00 | 0.00 | -124590028.0 | 58.99 | 0.00 | 0.00 |
February | 0.299227E+09 | -187730335.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111496543.3 | 58.99 | 0.00 | 0.00 |
March | 0.332860E+09 | -211842461.2 | 0.00 | 0.00 | 744.00 | 0.00 | -121017596.4 | 58.98 | 0.00 | 0.00 |
April | 0.307627E+09 | -193899624.0 | 0.00 | 0.00 | 720.00 | 0.00 | -113727425.5 | 58.99 | 0.00 | 0.00 |
May | 0.308651E+09 | -194783823.3 | 0.00 | 0.00 | 744.00 | 0.00 | -113867286.7 | 58.99 | 0.00 | 0.00 |
June | 0.292537E+09 | -183949319.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108587483.2 | 58.99 | 0.00 | 0.00 |
July | 0.288997E+09 | -177699622.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111296958.6 | 59.00 | 0.00 | 0.00 |
August | 0.294861E+09 | -183813867.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111047064.6 | 58.98 | 0.00 | 0.00 |
September | 0.284073E+09 | -175433385.9 | 0.00 | 0.00 | 720.00 | 0.00 | -108639893.0 | 58.98 | 0.00 | 0.00 |
October | 0.301776E+09 | -185412723.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116362890.0 | 58.99 | 0.00 | 0.00 |
November | 0.304712E+09 | -186887281.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117825068.2 | 58.99 | 0.00 | 0.00 |
December | 0.322893E+09 | -198845332.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124047849.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.366797E+10 | -0.228546E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138251E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.284073E+09 | -211842461.2 | 0.00 | 0.00 | 672.00 | 0.00 | -124590028.0 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.332860E+09 | -175433385.9 | 0.00 | 0.00 | 744.00 | 0.00 | -108587483.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.320164E+09 | -193892604.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126271118.9 | 59.00 | 0.00 | 0.00 |
February | 0.290574E+09 | -177531519.6 | 0.00 | 0.00 | 672.00 | 0.00 | -113042048.6 | 59.00 | 0.00 | 0.00 |
March | 0.323466E+09 | -200433335.6 | 0.00 | 0.00 | 744.00 | 0.00 | -123032476.8 | 58.99 | 0.00 | 0.00 |
April | 0.299413E+09 | -183476343.2 | 0.00 | 0.00 | 720.00 | 0.00 | -115936165.2 | 59.00 | 0.00 | 0.00 |
May | 0.299701E+09 | -184191691.8 | 0.00 | 0.00 | 744.00 | 0.00 | -115509772.3 | 59.00 | 0.00 | 0.00 |
June | 0.283657E+09 | -174032094.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109624464.7 | 59.00 | 0.00 | 0.00 |
July | 0.280236E+09 | -168095751.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112140478.6 | 58.98 | 0.00 | 0.00 |
August | 0.285894E+09 | -173905857.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111988153.7 | 58.99 | 0.00 | 0.00 |
September | 0.275754E+09 | -166001105.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109753053.4 | 58.99 | 0.00 | 0.00 |
October | 0.293758E+09 | -175252821.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118505025.6 | 58.99 | 0.00 | 0.00 |
November | 0.296062E+09 | -176509040.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119552645.9 | 58.99 | 0.00 | 0.00 |
December | 0.313661E+09 | -188085874.8 | 0.00 | 0.00 | 744.00 | 0.00 | -125575239.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356234E+10 | -0.216141E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140093E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275754E+09 | -200433335.6 | 0.00 | 0.00 | 672.00 | 0.00 | -126271118.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323466E+09 | -166001105.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109624464.7 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.320117E+09 | -193893074.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126223748.5 | 59.00 | 0.00 | 0.00 |
February | 0.290573E+09 | -177531493.3 | 0.00 | 0.00 | 672.00 | 0.00 | -113041471.7 | 59.00 | 0.00 | 0.00 |
March | 0.323553E+09 | -200436294.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123116795.7 | 58.99 | 0.00 | 0.00 |
April | 0.299572E+09 | -183470216.2 | 0.00 | 0.00 | 720.00 | 0.00 | -116101758.9 | 59.00 | 0.00 | 0.00 |
May | 0.299851E+09 | -184207393.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115643754.6 | 58.99 | 0.00 | 0.00 |
June | 0.283743E+09 | -174046177.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109696953.8 | 59.00 | 0.00 | 0.00 |
July | 0.280335E+09 | -168064090.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112271352.7 | 58.99 | 0.00 | 0.00 |
August | 0.286007E+09 | -173901501.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112105975.1 | 58.99 | 0.00 | 0.00 |
September | 0.275857E+09 | -165977549.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109878956.2 | 59.00 | 0.00 | 0.00 |
October | 0.293890E+09 | -175223189.1 | 0.00 | 0.00 | 744.00 | 0.00 | -118667140.7 | 59.00 | 0.00 | 0.00 |
November | 0.296115E+09 | -176498792.2 | 0.00 | 0.00 | 720.00 | 0.00 | -119616411.4 | 58.99 | 0.00 | 0.00 |
December | 0.313633E+09 | -188084925.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125548252.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.356325E+10 | -0.216133E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140191E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.275857E+09 | -200436294.9 | 0.00 | 0.00 | 672.00 | 0.00 | -126223748.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.323553E+09 | -165977549.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109696953.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.320226E+09 | -193892002.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126334441.5 | 58.99 | 0.00 | 0.00 |
February | 0.290709E+09 | -177537975.1 | 0.00 | 0.00 | 672.00 | 0.00 | -113170739.6 | 58.99 | 0.00 | 0.00 |
March | 0.323795E+09 | -200429641.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123365367.5 | 58.99 | 0.00 | 0.00 |
April | 0.299853E+09 | -183485279.0 | 0.00 | 0.00 | 720.00 | 0.00 | -116367662.4 | 58.99 | 0.00 | 0.00 |
May | 0.300185E+09 | -184190158.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115994431.1 | 59.00 | 0.00 | 0.00 |
June | 0.283891E+09 | -174042306.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109849018.0 | 59.00 | 0.00 | 0.00 |
July | 0.280436E+09 | -168058378.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112377520.7 | 58.99 | 0.00 | 0.00 |
August | 0.286090E+09 | -173900883.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112189123.1 | 58.99 | 0.00 | 0.00 |
September | 0.276014E+09 | -166008986.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110005456.7 | 58.98 | 0.00 | 0.00 |
October | 0.294185E+09 | -175248421.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118936611.8 | 58.99 | 0.00 | 0.00 |
November | 0.296280E+09 | -176508950.3 | 0.00 | 0.00 | 720.00 | 0.00 | -119771159.3 | 58.99 | 0.00 | 0.00 |
December | 0.313762E+09 | -188064132.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125697908.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.356543E+10 | -0.216137E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140406E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.276014E+09 | -200429641.1 | 0.00 | 0.00 | 672.00 | 0.00 | -126334441.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.323795E+09 | -166008986.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109849018.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 237.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 259.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 247.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 379.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 427.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 375.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 366.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 301.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 245.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 242.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3714.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 160.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 471.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.108215E+11 | 58542.54 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.694226E+10 | 58542.54 | 06-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.246785E+10 | 58542.54 | 24-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.490289E+09 | 38591.71 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 14197734.51 | 7226.42 | 18-MAY-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.131515E+09 | 7586.37 | 30-OCT-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.463277E+10 | 58542.54 | 24-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.888982E+10 | 58542.54 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.343902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.108215E+11 | 58542.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.305664E+10 | 30975.21 | 06-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171995E+10 | 30975.21 | 18-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277943E+09 | 4755.96 | 05-MAR-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 25277659.49 | 3247.80 | 19-APR-08:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.103677E+10 | 5902.92 | 29-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.233964E+10 | 30975.21 | 26-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.845622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.305664E+10 | 30975.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.404676E+10 | 31002.07 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.239990E+10 | 31002.07 | 18-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.612500E+09 | 7467.90 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 86830741.64 | 4520.01 | 18-APR-07:08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57643.23 | 96.07 | 18-MAY-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 6999340.20 | 1567.80 | 16-OCT-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.160466E+10 | 14047.92 | 24-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.323126E+10 | 31002.07 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.119890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.404676E+10 | 31002.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.429926E+10 | 31077.09 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.257571E+10 | 31077.09 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.761506E+09 | 13244.98 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.126160E+09 | 7306.52 | 18-APR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 300089.15 | 500.15 | 18-MAY-08:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 24714098.35 | 2182.37 | 30-OCT-07:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178361E+10 | 19457.80 | 24-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.345969E+10 | 31077.09 | 25-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.130310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.429926E+10 | 31077.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.468335E+10 | 30898.59 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.285277E+10 | 30898.59 | 12-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.994748E+09 | 19379.25 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198585E+09 | 5168.87 | 19-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1204870.99 | 944.73 | 18-MAY-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 64957851.62 | 3046.90 | 30-OCT-07:17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.204022E+10 | 24717.24 | 24-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.381711E+10 | 30898.59 | 18-DEC-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.146529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.468335E+10 | 30898.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.952507E+10 | 56577.74 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.595917E+10 | 56577.74 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.250396E+10 | 56577.74 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.616468E+09 | 46349.73 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 13981137.21 | 3703.16 | 18-MAY-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.362176E+09 | 13112.04 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.455479E+10 | 56577.74 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.794975E+10 | 56577.74 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.314854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.952507E+10 | 56577.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.494840E+10 | 28729.44 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.309075E+10 | 28729.44 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.130726E+10 | 28729.44 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.331803E+09 | 25759.81 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 7511421.08 | 2026.61 | 18-MAY-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.198671E+09 | 8945.25 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.235936E+10 | 28729.44 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.411691E+10 | 28729.44 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.163607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.494840E+10 | 28729.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.504314E+10 | 28596.53 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.317970E+10 | 28596.53 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.140689E+10 | 28596.53 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383360E+09 | 28596.53 | 18-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 11534569.04 | 2287.87 | 18-MAY-08:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.241473E+09 | 12127.19 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.244352E+10 | 28596.53 | 12-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.421248E+10 | 28596.53 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.504314E+10 | 28596.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.545657E+10 | 28406.58 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.351905E+10 | 28406.58 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172537E+10 | 28406.58 | 05-MAR-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.546691E+09 | 28406.58 | 11-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 33081680.78 | 3541.44 | 18-MAY-08:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 304760.97 | 398.61 | 28-SEP-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.374370E+09 | 21218.91 | 30-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.273223E+10 | 28406.58 | 11-NOV-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.458757E+10 | 28406.58 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.189752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.545657E+10 | 28406.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.723129E+10 | 29912.00 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.486051E+10 | 29912.00 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.277916E+10 | 29912.00 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104219E+10 | 29912.00 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185165E+09 | 19620.48 | 18-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 1594359.57 | 858.73 | 15-JUN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 13543101.76 | 3140.94 | 28-SEP-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.791462E+09 | 29912.00 | 16-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373273E+10 | 29912.00 | 09-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.610574E+10 | 29912.00 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.267434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.723129E+10 | 29912.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 838.20 | 838.20 | 1.34 | 18-MAR-16:10 | 1.34 | 0.00 |
April | 0.00 | 0.00 | 0.911882E+09 | 0.882139E+09 | 15441.53 | 27-APR-16:10 | 14852.95 | 0.00 |
May | 0.00 | 0.00 | 0.190153E+10 | 0.171898E+10 | 19174.63 | 06-MAY-08:62 | 14736.46 | 0.00 |
June | 0.00 | 0.00 | 0.331633E+10 | 0.315505E+10 | 35168.21 | 12-JUN-08:62 | 22611.69 | 0.00 |
July | 0.00 | 0.00 | 0.827134E+10 | 0.726194E+10 | 36447.67 | 31-JUL-08:61 | 27703.67 | 0.00 |
August | 0.00 | 0.00 | 0.111233E+11 | 0.977148E+10 | 36570.10 | 29-AUG-08:62 | 26493.25 | 0.00 |
September | 0.00 | 0.00 | 0.317569E+10 | 0.265622E+10 | 35332.04 | 14-SEP-08:62 | 22860.97 | 0.00 |
October | 0.00 | 0.00 | 0.148641E+09 | 0.146944E+09 | 7771.05 | 04-OCT-15:00 | 7771.05 | 0.00 |
November | 0.00 | 0.00 | 37564609.16 | 28746568.18 | 4166.79 | 04-NOV-14:00 | 3232.57 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.288863E+11 | 0.256215E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.111233E+11 | 0.977148E+10 | 36570.10 | 27703.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 60851.45 | 54630.04 | 101.42 | 11-JAN-22:00 | 91.05 | 0.00 |
February | 0.00 | 0.00 | 1804778.23 | 1721913.87 | 1040.87 | 27-FEB-23:10 | 958.98 | 0.00 |
March | 0.00 | 0.00 | 9620589.18 | 9396281.87 | 1739.94 | 19-MAR-17:20 | 1739.94 | 0.00 |
April | 0.00 | 0.00 | 0.623892E+09 | 0.603139E+09 | 18466.05 | 29-APR-18:01 | 14919.70 | 0.00 |
May | 0.00 | 0.00 | 0.127667E+10 | 0.114694E+10 | 19176.84 | 07-MAY-17:02 | 15240.35 | 0.00 |
June | 0.00 | 0.00 | 0.221587E+10 | 0.209000E+10 | 18904.31 | 11-JUN-18:00 | 15875.44 | 0.00 |
July | 0.00 | 0.00 | 0.511365E+10 | 0.445698E+10 | 19641.31 | 15-JUL-18:02 | 14229.20 | 0.00 |
August | 0.00 | 0.00 | 0.669321E+10 | 0.584525E+10 | 19517.21 | 26-AUG-18:02 | 12969.61 | 0.00 |
September | 0.00 | 0.00 | 0.204096E+10 | 0.169717E+10 | 19362.83 | 23-SEP-18:02 | 13569.83 | 0.00 |
October | 0.00 | 0.00 | 0.126715E+09 | 0.123926E+09 | 17773.31 | 04-OCT-20:01 | 17773.31 | 0.00 |
November | 0.00 | 0.00 | 43429554.44 | 33583947.80 | 3534.45 | 04-NOV-14:00 | 2755.02 | 0.00 |
December | 0.00 | 0.00 | 90161.96 | 90161.96 | 70.29 | 03-DEC-22:30 | 70.29 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.181460E+11 | 0.160083E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 60851.45 | 54630.04 | 70.29 | 70.29 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.669321E+10 | 0.584525E+10 | 19641.31 | 17773.31 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 589789.50 | 589785.40 | 359.25 | 18-MAR-16:00 | 359.25 | 0.00 |
April | 0.00 | 0.00 | 0.457084E+09 | 0.441794E+09 | 9303.47 | 30-APR-08:62 | 5877.10 | 0.00 |
May | 0.00 | 0.00 | 0.940875E+09 | 0.850395E+09 | 18871.50 | 07-MAY-08:62 | 13615.55 | 0.00 |
June | 0.00 | 0.00 | 0.162018E+10 | 0.154325E+10 | 18650.93 | 12-JUN-07:02 | 12834.94 | 0.00 |
July | 0.00 | 0.00 | 0.374377E+10 | 0.330025E+10 | 19220.48 | 31-JUL-07:01 | 14419.85 | 0.00 |
August | 0.00 | 0.00 | 0.504329E+10 | 0.443527E+10 | 19313.59 | 30-AUG-07:02 | 11350.57 | 0.00 |
September | 0.00 | 0.00 | 0.161694E+10 | 0.134723E+10 | 18671.97 | 01-SEP-07:02 | 12451.47 | 0.00 |
October | 0.00 | 0.00 | 86841727.41 | 85643417.58 | 4408.75 | 01-OCT-08:63 | 2933.79 | 0.00 |
November | 0.00 | 0.00 | 29680993.88 | 22725799.56 | 2996.93 | 04-NOV-14:00 | 2333.05 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.135393E+11 | 0.120272E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.504329E+10 | 0.443527E+10 | 19313.59 | 14419.85 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 165048.96 | 165048.96 | 185.86 | 18-MAR-16:00 | 185.86 | 0.00 |
April | 0.00 | 0.00 | 0.442721E+09 | 0.427883E+09 | 8081.45 | 28-APR-07:03 | 5691.61 | 0.00 |
May | 0.00 | 0.00 | 0.919828E+09 | 0.831592E+09 | 18921.58 | 07-MAY-08:62 | 13646.77 | 0.00 |
June | 0.00 | 0.00 | 0.159833E+10 | 0.152267E+10 | 18701.42 | 12-JUN-07:02 | 12870.51 | 0.00 |
July | 0.00 | 0.00 | 0.373308E+10 | 0.329048E+10 | 19275.23 | 31-JUL-07:01 | 14476.37 | 0.00 |
August | 0.00 | 0.00 | 0.504611E+10 | 0.443757E+10 | 19366.89 | 30-AUG-07:02 | 11387.58 | 0.00 |
September | 0.00 | 0.00 | 0.160107E+10 | 0.133428E+10 | 18722.33 | 01-SEP-07:02 | 12484.74 | 0.00 |
October | 0.00 | 0.00 | 82114270.19 | 81141231.97 | 4203.75 | 04-OCT-15:00 | 4203.75 | 0.00 |
November | 0.00 | 0.00 | 24594175.00 | 18853590.62 | 2633.61 | 04-NOV-14:00 | 2048.65 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.134480E+11 | 0.119446E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.504611E+10 | 0.443757E+10 | 19366.89 | 14476.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 23.46 | 23.46 | 0.03 | 27-FEB-17:00 | 0.03 | 0.00 |
March | 0.00 | 0.00 | 15.78 | 15.78 | 0.03 | 14-MAR-16:00 | 0.03 | 0.00 |
April | 0.00 | 0.00 | 0.414651E+09 | 0.400955E+09 | 7803.48 | 27-APR-15:00 | 7481.77 | 0.00 |
May | 0.00 | 0.00 | 0.862324E+09 | 0.780317E+09 | 18794.46 | 07-MAY-08:62 | 13519.26 | 0.00 |
June | 0.00 | 0.00 | 0.151722E+10 | 0.144618E+10 | 18575.71 | 12-JUN-07:02 | 12753.24 | 0.00 |
July | 0.00 | 0.00 | 0.360329E+10 | 0.317625E+10 | 19147.40 | 31-JUL-07:01 | 14353.19 | 0.00 |
August | 0.00 | 0.00 | 0.488948E+10 | 0.430246E+10 | 19237.38 | 30-AUG-07:02 | 11276.31 | 0.00 |
September | 0.00 | 0.00 | 0.153101E+10 | 0.127656E+10 | 18596.55 | 01-SEP-07:02 | 12368.91 | 0.00 |
October | 0.00 | 0.00 | 73394174.41 | 72800525.72 | 4024.06 | 04-OCT-15:00 | 4024.06 | 0.00 |
November | 0.00 | 0.00 | 17991724.73 | 13812116.60 | 2119.37 | 04-NOV-14:00 | 1646.09 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.129094E+11 | 0.114693E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.488948E+10 | 0.430246E+10 | 19237.38 | 14353.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.701727E+09 | 0.673640E+09 | 14578.30 | 27-APR-15:00 | 13633.11 | 0.00 |
May | 0.00 | 0.00 | 0.141242E+10 | 0.127341E+10 | 33844.82 | 07-MAY-09:02 | 23344.37 | 0.00 |
June | 0.00 | 0.00 | 0.260823E+10 | 0.247863E+10 | 33749.19 | 12-JUN-08:62 | 22195.19 | 0.00 |
July | 0.00 | 0.00 | 0.640062E+10 | 0.559479E+10 | 35072.40 | 31-JUL-08:61 | 26873.66 | 0.00 |
August | 0.00 | 0.00 | 0.884239E+10 | 0.771162E+10 | 35142.47 | 30-AUG-08:62 | 20866.61 | 0.00 |
September | 0.00 | 0.00 | 0.262552E+10 | 0.217861E+10 | 34054.78 | 14-SEP-08:62 | 21837.30 | 0.00 |
October | 0.00 | 0.00 | 0.118577E+09 | 0.117737E+09 | 7443.40 | 04-OCT-15:00 | 7443.40 | 0.00 |
November | 0.00 | 0.00 | 24900101.68 | 19036129.09 | 3296.34 | 04-NOV-14:30 | 2549.85 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.227344E+11 | 0.200475E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.884239E+10 | 0.771162E+10 | 35142.47 | 26873.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 5.92 | 5.92 | 0.01 | 27-FEB-14:30 | 0.01 | 0.00 |
March | 0.00 | 0.00 | 28.69 | 28.69 | 0.04 | 18-MAR-13:30 | 0.04 | 0.00 |
April | 0.00 | 0.00 | 0.357840E+09 | 0.343848E+09 | 7523.67 | 27-APR-15:00 | 7045.45 | 0.00 |
May | 0.00 | 0.00 | 0.718720E+09 | 0.649216E+09 | 14991.58 | 07-MAY-09:02 | 10345.72 | 0.00 |
June | 0.00 | 0.00 | 0.133293E+10 | 0.126938E+10 | 17382.73 | 12-JUN-08:62 | 11434.63 | 0.00 |
July | 0.00 | 0.00 | 0.329103E+10 | 0.288276E+10 | 18064.03 | 31-JUL-08:61 | 13849.07 | 0.00 |
August | 0.00 | 0.00 | 0.455777E+10 | 0.398361E+10 | 18099.87 | 30-AUG-08:62 | 10749.36 | 0.00 |
September | 0.00 | 0.00 | 0.135306E+10 | 0.112561E+10 | 17539.86 | 14-SEP-08:62 | 11249.57 | 0.00 |
October | 0.00 | 0.00 | 61494015.89 | 61072987.49 | 3900.85 | 04-OCT-15:00 | 3900.85 | 0.00 |
November | 0.00 | 0.00 | 12617399.98 | 9671551.49 | 1724.80 | 04-NOV-14:40 | 1337.86 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.116855E+11 | 0.103252E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.455777E+10 | 0.398361E+10 | 18099.87 | 13849.07 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 7435.14 | 7435.14 | 12.36 | 27-FEB-17:00 | 12.36 | 0.00 |
March | 0.00 | 0.00 | 71.95 | 71.95 | 0.12 | 18-MAR-13:30 | 0.12 | 0.00 |
April | 0.00 | 0.00 | 0.345937E+09 | 0.332367E+09 | 7373.50 | 27-APR-15:00 | 6901.61 | 0.00 |
May | 0.00 | 0.00 | 0.689713E+09 | 0.622897E+09 | 13358.57 | 07-MAY-09:02 | 9204.21 | 0.00 |
June | 0.00 | 0.00 | 0.129556E+10 | 0.123410E+10 | 17287.03 | 12-JUN-08:62 | 11354.79 | 0.00 |
July | 0.00 | 0.00 | 0.323228E+10 | 0.283103E+10 | 17965.43 | 31-JUL-08:61 | 13757.00 | 0.00 |
August | 0.00 | 0.00 | 0.449213E+10 | 0.392606E+10 | 18001.66 | 30-AUG-08:62 | 10676.49 | 0.00 |
September | 0.00 | 0.00 | 0.132278E+10 | 0.110043E+10 | 17444.07 | 14-SEP-08:62 | 11174.93 | 0.00 |
October | 0.00 | 0.00 | 57993162.24 | 57647545.85 | 3797.87 | 04-OCT-15:00 | 3797.87 | 0.00 |
November | 0.00 | 0.00 | 11058764.19 | 8482007.25 | 1591.70 | 04-NOV-14:40 | 1233.84 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.114475E+11 | 0.101130E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.449213E+10 | 0.392606E+10 | 18001.66 | 13757.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 9036.26 | 9036.26 | 15.06 | 27-FEB-16:20 | 15.06 | 0.00 |
March | 0.00 | 0.00 | 280.29 | 280.29 | 0.24 | 18-MAR-13:40 | 0.24 | 0.00 |
April | 0.00 | 0.00 | 0.319488E+09 | 0.307004E+09 | 7074.45 | 27-APR-15:00 | 6616.64 | 0.00 |
May | 0.00 | 0.00 | 0.623916E+09 | 0.563520E+09 | 7805.02 | 07-MAY-09:02 | 5352.77 | 0.00 |
June | 0.00 | 0.00 | 0.120656E+10 | 0.115078E+10 | 17213.80 | 12-JUN-08:62 | 11258.12 | 0.00 |
July | 0.00 | 0.00 | 0.308965E+10 | 0.270808E+10 | 17892.79 | 31-JUL-08:61 | 13662.06 | 0.00 |
August | 0.00 | 0.00 | 0.435254E+10 | 0.380590E+10 | 17930.12 | 30-AUG-08:62 | 10596.01 | 0.00 |
September | 0.00 | 0.00 | 0.125157E+10 | 0.104176E+10 | 17373.06 | 14-SEP-08:62 | 11093.39 | 0.00 |
October | 0.00 | 0.00 | 49797282.06 | 49638797.59 | 3529.08 | 04-OCT-15:00 | 3529.08 | 0.00 |
November | 0.00 | 0.00 | 7775751.86 | 5973878.97 | 1263.19 | 04-NOV-14:40 | 978.17 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.109013E+11 | 0.963266E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.435254E+10 | 0.380590E+10 | 17930.12 | 13662.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:05 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 11521.54 | 11521.54 | 18.17 | 18-MAR-16:50 | 18.17 | 0.00 |
April | 0.00 | 0.00 | 0.300012E+09 | 0.288706E+09 | 7100.56 | 27-APR-15:00 | 6633.51 | 0.00 |
May | 0.00 | 0.00 | 0.565447E+09 | 0.511685E+09 | 6728.94 | 06-MAY-13:30 | 5527.33 | 0.00 |
June | 0.00 | 0.00 | 0.114292E+10 | 0.109169E+10 | 7164.82 | 28-JUN-17:00 | 6862.51 | 0.00 |
July | 0.00 | 0.00 | 0.302738E+10 | 0.266214E+10 | 18785.45 | 31-JUL-08:61 | 14294.99 | 0.00 |
August | 0.00 | 0.00 | 0.442916E+10 | 0.388071E+10 | 18824.78 | 10-AUG-08:61 | 14207.50 | 0.00 |
September | 0.00 | 0.00 | 0.121184E+10 | 0.100788E+10 | 14014.59 | 10-SEP-09:02 | 10428.64 | 0.00 |
October | 0.00 | 0.00 | 38358981.82 | 38358981.82 | 3022.34 | 04-OCT-15:00 | 3022.34 | 0.00 |
November | 0.00 | 0.00 | 3821772.79 | 2944031.81 | 771.53 | 04-NOV-14:40 | 596.75 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.107189E+11 | 0.948413E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.442916E+10 | 0.388071E+10 | 18824.78 | 14294.99 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.397630E+10 | 0.61 | 2190.07 | 01-JAN-12:20 | 0.89 |
February | 0.359735E+10 | 0.61 | 2190.07 | 01-FEB-10:00 | 0.89 |
March | 0.398963E+10 | 0.60 | 2190.07 | 01-MAR-09:03 | 0.89 |
April | 0.384751E+10 | 0.60 | 2190.07 | 01-APR-08:10 | 0.89 |
May | 0.397366E+10 | 0.60 | 2190.07 | 03-MAY-10:10 | 0.88 |
June | 0.386328E+10 | 0.60 | 2190.07 | 02-JUN-16:00 | 0.89 |
July | 0.397366E+10 | 0.60 | 2190.07 | 02-JUL-10:10 | 0.89 |
August | 0.398154E+10 | 0.60 | 2190.07 | 01-AUG-15:20 | 0.88 |
September | 0.385540E+10 | 0.60 | 2190.07 | 01-SEP-08:30 | 0.88 |
October | 0.397366E+10 | 0.60 | 2190.07 | 04-OCT-11:30 | 0.89 |
November | 0.384021E+10 | 0.60 | 2190.07 | 01-NOV-08:40 | 0.89 |
December | 0.399149E+10 | 0.61 | 2190.07 | 01-DEC-09:09 | 0.89 |
Annual Sum or Average | 0.468637E+11 | 0.60 | |||
Minimum of Months | 0.359735E+10 | 0.60 | 2190.07 | 0.88 | |
Maximum of Months | 0.399149E+10 | 0.61 | 2190.07 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.165143E+10 | 0.47 | 1216.74 | 01-JAN-11:20 | 0.92 |
February | 0.150898E+10 | 0.49 | 1216.74 | 01-FEB-12:20 | 0.92 |
March | 0.172626E+10 | 0.56 | 1216.74 | 03-MAR-12:30 | 0.92 |
April | 0.178775E+10 | 0.61 | 1216.74 | 01-APR-14:50 | 0.92 |
May | 0.202843E+10 | 0.62 | 1216.74 | 03-MAY-11:00 | 0.91 |
June | 0.205151E+10 | 0.61 | 1216.74 | 02-JUN-13:00 | 0.92 |
July | 0.207843E+10 | 0.60 | 1216.74 | 01-JUL-15:00 | 0.91 |
August | 0.205605E+10 | 0.59 | 1216.74 | 01-AUG-15:40 | 0.91 |
September | 0.207841E+10 | 0.61 | 1216.74 | 01-SEP-08:15 | 0.91 |
October | 0.191144E+10 | 0.62 | 1216.74 | 03-OCT-15:20 | 0.92 |
November | 0.167682E+10 | 0.52 | 1216.74 | 09-NOV-15:20 | 0.92 |
December | 0.164293E+10 | 0.47 | 1216.74 | 01-DEC-12:00 | 0.92 |
Annual Sum or Average | 0.221984E+11 | 0.56 | |||
Minimum of Months | 0.150898E+10 | 0.47 | 1216.74 | 0.91 | |
Maximum of Months | 0.207843E+10 | 0.62 | 1216.74 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176278E+10 | 0.50 | 1218.06 | 01-JAN-15:50 | 0.92 |
February | 0.159615E+10 | 0.50 | 1218.06 | 02-FEB-09:08 | 0.92 |
March | 0.179786E+10 | 0.51 | 1218.06 | 01-MAR-09:30 | 0.92 |
April | 0.171016E+10 | 0.50 | 1218.06 | 09-APR-08:50 | 0.92 |
May | 0.178032E+10 | 0.50 | 1218.06 | 03-MAY-10:05 | 0.92 |
June | 0.173647E+10 | 0.50 | 1218.06 | 02-JUN-12:20 | 0.92 |
July | 0.175401E+10 | 0.49 | 1218.06 | 01-JUL-15:20 | 0.92 |
August | 0.179786E+10 | 0.50 | 1218.06 | 03-AUG-16:10 | 0.92 |
September | 0.171016E+10 | 0.50 | 1218.06 | 01-SEP-08:10 | 0.91 |
October | 0.176278E+10 | 0.50 | 1218.06 | 03-OCT-07:05 | 0.92 |
November | 0.171016E+10 | 0.50 | 1218.06 | 02-NOV-07:40 | 0.92 |
December | 0.175401E+10 | 0.49 | 1218.06 | 01-DEC-11:50 | 0.92 |
Annual Sum or Average | 0.208727E+11 | 0.50 | |||
Minimum of Months | 0.159615E+10 | 0.49 | 1218.06 | 0.91 | |
Maximum of Months | 0.179786E+10 | 0.51 | 1218.06 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176811E+10 | 0.50 | 1221.75 | 01-JAN-09:05 | 0.92 |
February | 0.160098E+10 | 0.50 | 1221.75 | 01-FEB-09:06 | 0.92 |
March | 0.180330E+10 | 0.51 | 1221.75 | 01-MAR-09:03 | 0.92 |
April | 0.171533E+10 | 0.50 | 1221.75 | 01-APR-07:40 | 0.92 |
May | 0.178571E+10 | 0.50 | 1221.75 | 03-MAY-14:00 | 0.92 |
June | 0.174172E+10 | 0.50 | 1221.75 | 02-JUN-12:20 | 0.92 |
July | 0.175932E+10 | 0.49 | 1221.75 | 01-JUL-14:20 | 0.91 |
August | 0.180330E+10 | 0.50 | 1221.75 | 02-AUG-07:30 | 0.91 |
September | 0.171533E+10 | 0.50 | 1221.75 | 02-SEP-13:00 | 0.91 |
October | 0.176811E+10 | 0.50 | 1221.75 | 04-OCT-14:50 | 0.92 |
November | 0.171533E+10 | 0.50 | 1221.75 | 04-NOV-14:20 | 0.91 |
December | 0.175932E+10 | 0.49 | 1221.75 | 01-DEC-11:30 | 0.92 |
Annual Sum or Average | 0.209359E+11 | 0.50 | |||
Minimum of Months | 0.160098E+10 | 0.49 | 1221.75 | 0.91 | |
Maximum of Months | 0.180330E+10 | 0.51 | 1221.75 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.175542E+10 | 0.50 | 1212.98 | 01-JAN-09:08 | 0.92 |
February | 0.158949E+10 | 0.50 | 1212.98 | 01-FEB-08:62 | 0.92 |
March | 0.179035E+10 | 0.51 | 1212.98 | 01-MAR-08:20 | 0.92 |
April | 0.170302E+10 | 0.50 | 1212.98 | 01-APR-07:15 | 0.92 |
May | 0.177289E+10 | 0.50 | 1212.98 | 03-MAY-10:20 | 0.92 |
June | 0.172922E+10 | 0.50 | 1212.98 | 02-JUN-17:00 | 0.92 |
July | 0.174669E+10 | 0.49 | 1212.98 | 01-JUL-13:10 | 0.92 |
August | 0.179035E+10 | 0.50 | 1212.98 | 01-AUG-14:30 | 0.91 |
September | 0.170302E+10 | 0.50 | 1212.98 | 01-SEP-07:40 | 0.91 |
October | 0.175542E+10 | 0.50 | 1212.98 | 03-OCT-14:30 | 0.92 |
November | 0.170302E+10 | 0.50 | 1212.98 | 01-NOV-07:20 | 0.92 |
December | 0.174669E+10 | 0.49 | 1212.98 | 01-DEC-09:10 | 0.92 |
Annual Sum or Average | 0.207856E+11 | 0.50 | |||
Minimum of Months | 0.158949E+10 | 0.49 | 1212.98 | 0.91 | |
Maximum of Months | 0.179035E+10 | 0.51 | 1212.98 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.280050E+10 | 0.44 | 2096.81 | 01-JAN-09:01 | 0.89 |
February | 0.253630E+10 | 0.44 | 2096.81 | 01-FEB-08:62 | 0.89 |
March | 0.286088E+10 | 0.45 | 2096.81 | 26-MAR-14:50 | 0.89 |
April | 0.271746E+10 | 0.44 | 2096.81 | 11-APR-16:00 | 0.89 |
May | 0.283069E+10 | 0.45 | 2096.81 | 01-MAY-07:05 | 0.88 |
June | 0.276275E+10 | 0.45 | 2096.81 | 01-JUN-07:03 | 0.88 |
July | 0.278540E+10 | 0.44 | 2096.81 | 09-JUL-14:20 | 0.88 |
August | 0.286088E+10 | 0.45 | 2096.81 | 01-AUG-07:02 | 0.88 |
September | 0.271746E+10 | 0.44 | 2096.81 | 01-SEP-07:02 | 0.88 |
October | 0.280050E+10 | 0.44 | 2096.81 | 01-OCT-08:63 | 0.88 |
November | 0.271746E+10 | 0.44 | 2096.81 | 01-NOV-07:05 | 0.89 |
December | 0.278540E+10 | 0.44 | 2096.81 | 02-DEC-18:10 | 0.89 |
Annual Sum or Average | 0.331757E+11 | 0.44 | |||
Minimum of Months | 0.253630E+10 | 0.44 | 2096.81 | 0.88 | |
Maximum of Months | 0.286088E+10 | 0.45 | 2096.81 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.149865E+10 | 0.46 | 1122.08 | 01-JAN-13:00 | 0.92 |
February | 0.135727E+10 | 0.46 | 1122.08 | 01-FEB-15:00 | 0.92 |
March | 0.153097E+10 | 0.47 | 1122.08 | 06-MAR-12:10 | 0.92 |
April | 0.145422E+10 | 0.46 | 1122.08 | 03-APR-15:20 | 0.92 |
May | 0.151481E+10 | 0.46 | 1122.08 | 03-MAY-14:00 | 0.92 |
June | 0.147845E+10 | 0.47 | 1122.08 | 02-JUN-18:00 | 0.92 |
July | 0.149057E+10 | 0.45 | 1122.08 | 02-JUL-14:30 | 0.92 |
August | 0.153097E+10 | 0.47 | 1122.08 | 07-AUG-08:10 | 0.91 |
September | 0.145422E+10 | 0.46 | 1122.08 | 07-SEP-16:40 | 0.92 |
October | 0.149865E+10 | 0.46 | 1122.08 | 12-OCT-15:50 | 0.92 |
November | 0.145422E+10 | 0.46 | 1122.08 | 03-NOV-09:20 | 0.92 |
December | 0.149057E+10 | 0.46 | 1122.08 | 03-DEC-10:40 | 0.92 |
Annual Sum or Average | 0.177535E+11 | 0.46 | |||
Minimum of Months | 0.135727E+10 | 0.45 | 1122.08 | 0.91 | |
Maximum of Months | 0.153097E+10 | 0.47 | 1122.08 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148965E+10 | 0.46 | 1115.34 | 01-JAN-11:50 | 0.92 |
February | 0.134912E+10 | 0.46 | 1115.34 | 11-FEB-12:00 | 0.92 |
March | 0.152177E+10 | 0.47 | 1115.34 | 09-MAR-10:30 | 0.92 |
April | 0.144549E+10 | 0.46 | 1115.34 | 01-APR-08:07 | 0.92 |
May | 0.150571E+10 | 0.46 | 1115.34 | 03-MAY-10:20 | 0.91 |
June | 0.146958E+10 | 0.47 | 1115.34 | 02-JUN-13:40 | 0.92 |
July | 0.148162E+10 | 0.45 | 1115.34 | 01-JUL-12:50 | 0.92 |
August | 0.152177E+10 | 0.47 | 1115.34 | 19-AUG-14:00 | 0.91 |
September | 0.144549E+10 | 0.46 | 1115.34 | 02-SEP-12:10 | 0.91 |
October | 0.148965E+10 | 0.46 | 1115.34 | 03-OCT-15:00 | 0.92 |
November | 0.144549E+10 | 0.46 | 1115.34 | 01-NOV-08:50 | 0.92 |
December | 0.148162E+10 | 0.46 | 1115.34 | 28-DEC-09:05 | 0.92 |
Annual Sum or Average | 0.176470E+11 | 0.46 | |||
Minimum of Months | 0.134912E+10 | 0.45 | 1115.34 | 0.91 | |
Maximum of Months | 0.152177E+10 | 0.47 | 1115.34 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.148348E+10 | 0.46 | 1110.72 | 10-JAN-19:00 | 0.92 |
February | 0.134353E+10 | 0.46 | 1110.72 | 06-FEB-16:00 | 0.92 |
March | 0.151547E+10 | 0.47 | 1110.72 | 04-MAR-10:40 | 0.92 |
April | 0.143949E+10 | 0.46 | 1110.72 | 10-APR-17:30 | 0.92 |
May | 0.149947E+10 | 0.46 | 1110.72 | 04-MAY-19:25 | 0.92 |
June | 0.146349E+10 | 0.47 | 1110.72 | 01-JUN-07:03 | 0.91 |
July | 0.147548E+10 | 0.45 | 1110.72 | 01-JUL-07:02 | 0.91 |
August | 0.151547E+10 | 0.47 | 1110.72 | 01-AUG-07:02 | 0.91 |
September | 0.143949E+10 | 0.46 | 1110.72 | 01-SEP-19:10 | 0.91 |
October | 0.148348E+10 | 0.46 | 1110.72 | 01-OCT-08:63 | 0.91 |
November | 0.143949E+10 | 0.46 | 1110.72 | 01-NOV-07:05 | 0.92 |
December | 0.147548E+10 | 0.46 | 1110.72 | 01-DEC-08:62 | 0.92 |
Annual Sum or Average | 0.175738E+11 | 0.46 | |||
Minimum of Months | 0.134353E+10 | 0.45 | 1110.72 | 0.91 | |
Maximum of Months | 0.151547E+10 | 0.47 | 1110.72 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.158420E+10 | 0.46 | 1185.78 | 01-JAN-09:15 | 0.92 |
February | 0.143538E+10 | 0.46 | 1185.78 | 08-FEB-15:30 | 0.92 |
March | 0.161787E+10 | 0.47 | 1185.78 | 30-MAR-09:50 | 0.92 |
April | 0.153677E+10 | 0.46 | 1185.78 | 01-APR-07:05 | 0.92 |
May | 0.160080E+10 | 0.46 | 1185.78 | 01-MAY-08:25 | 0.92 |
June | 0.156238E+10 | 0.47 | 1185.78 | 30-JUN-15:00 | 0.91 |
July | 0.157519E+10 | 0.45 | 1185.78 | 01-JUL-13:40 | 0.91 |
August | 0.161787E+10 | 0.47 | 1185.78 | 01-AUG-08:62 | 0.91 |
September | 0.153677E+10 | 0.46 | 1185.78 | 01-SEP-19:10 | 0.91 |
October | 0.158372E+10 | 0.46 | 1185.78 | 02-OCT-08:15 | 0.92 |
November | 0.153677E+10 | 0.46 | 1185.78 | 01-NOV-09:00 | 0.92 |
December | 0.157519E+10 | 0.46 | 1185.78 | 11-DEC-08:30 | 0.92 |
Annual Sum or Average | 0.187629E+11 | 0.46 | |||
Minimum of Months | 0.143538E+10 | 0.45 | 1185.78 | 0.91 | |
Maximum of Months | 0.161787E+10 | 0.47 | 1185.78 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.397630E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.359735E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.398963E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.409764E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.448090E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.475086E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.616780E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.694427E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.468681E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.401359E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.385055E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.399149E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.545472E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.359735E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.694427E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.165145E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150947E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.172886E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194928E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.234935E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.261030E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.335697E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.373679E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.258483E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.194448E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.168827E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.164295E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.267530E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150947E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.373679E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176278E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159615E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.179802E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.183122E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.202348E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.215643E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.271783E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310221E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.211963E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.178540E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.171800E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.175401E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.243652E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159615E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310221E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176811E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160098E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180334E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.183288E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.202371E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.215631E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.272067E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310861E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.212104E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.178951E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172186E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.175932E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.244063E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160098E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310861E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.175542E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158949E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.179035E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.181358E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.199664E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.212357E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.267620E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.305757E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.209172E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.177456E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.170783E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.174669E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.241236E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158949E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.305757E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.280050E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.253630E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.286088E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.291086E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.320908E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.346333E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.448776E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.522193E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.340472E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.283237E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.272434E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.278540E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.392375E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.253630E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.522193E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.149865E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135727E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153097E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.155003E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.170188E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.182634E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.234069E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.271264E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179809E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151469E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145760E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149057E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.207794E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135727E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.271264E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148965E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134912E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152177E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.153829E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.168550E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.180810E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.231724E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.268714E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.178188E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150479E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144846E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.148162E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206136E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134912E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.268714E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.148348E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.134353E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151547E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.152561E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.166275E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.177984E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.227647E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.264663E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.175852E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.149652E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144159E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.147548E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.204059E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.134353E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.264663E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158420E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.143538E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.161788E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161813E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.174962E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.186349E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.236292E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.276993E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.184720E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.159386E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.153781E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.157519E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.215556E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.143538E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.276993E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.397630E+10 | 0.00 | 0.108215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359735E+10 | 0.00 | 0.694226E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398963E+10 | 838.20 | 0.246785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384751E+10 | 0.911882E+09 | 0.490289E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.397366E+10 | 0.190153E+10 | 14197734.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386328E+10 | 0.331633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397366E+10 | 0.827134E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.398154E+10 | 0.111233E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.385540E+10 | 0.317569E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397366E+10 | 0.148641E+09 | 0.131515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384021E+10 | 37564609.16 | 0.463277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399149E+10 | 0.00 | 0.888982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468637E+11 | 0.288863E+11 | 0.343902E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.399149E+10 | 0.111233E+11 | 0.108215E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.165143E+10 | 60851.45 | 0.305664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150898E+10 | 1804778.23 | 0.171995E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172626E+10 | 9620589.18 | 0.277943E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178775E+10 | 0.623892E+09 | 25277659.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202843E+10 | 0.127667E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205151E+10 | 0.221587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207843E+10 | 0.511365E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205605E+10 | 0.669321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207841E+10 | 0.204096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191144E+10 | 0.126715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167682E+10 | 43429554.44 | 0.103677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164293E+10 | 90161.96 | 0.233964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221984E+11 | 0.181460E+11 | 0.845622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150898E+10 | 60851.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207843E+10 | 0.669321E+10 | 0.305664E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176278E+10 | 0.00 | 0.404676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159615E+10 | 0.00 | 0.239990E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179786E+10 | 589789.50 | 0.612500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171016E+10 | 0.457084E+09 | 86830741.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178032E+10 | 0.940875E+09 | 57643.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173647E+10 | 0.162018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175401E+10 | 0.374377E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179786E+10 | 0.504329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171016E+10 | 0.161694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176278E+10 | 86841727.41 | 6999340.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171016E+10 | 29680993.88 | 0.160466E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175401E+10 | 0.00 | 0.323126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208727E+11 | 0.135393E+11 | 0.119890E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179786E+10 | 0.504329E+10 | 0.404676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176811E+10 | 0.00 | 0.429926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160098E+10 | 0.00 | 0.257571E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180330E+10 | 165048.96 | 0.761506E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171533E+10 | 0.442721E+09 | 0.126160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178571E+10 | 0.919828E+09 | 300089.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174172E+10 | 0.159833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175932E+10 | 0.373308E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180330E+10 | 0.504611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171533E+10 | 0.160107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176811E+10 | 82114270.19 | 24714098.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171533E+10 | 24594175.00 | 0.178361E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175932E+10 | 0.00 | 0.345969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209359E+11 | 0.134480E+11 | 0.130310E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180330E+10 | 0.504611E+10 | 0.429926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.175542E+10 | 0.00 | 0.468335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158949E+10 | 23.46 | 0.285277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179035E+10 | 15.78 | 0.994748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170302E+10 | 0.414651E+09 | 0.198585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177289E+10 | 0.862324E+09 | 1204870.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172922E+10 | 0.151722E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174669E+10 | 0.360329E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179035E+10 | 0.488948E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170302E+10 | 0.153101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175542E+10 | 73394174.41 | 64957851.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170302E+10 | 17991724.73 | 0.204022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174669E+10 | 0.00 | 0.381711E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207856E+11 | 0.129094E+11 | 0.146529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179035E+10 | 0.488948E+10 | 0.468335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.280050E+10 | 0.00 | 0.952507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253630E+10 | 0.00 | 0.595917E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286088E+10 | 0.00 | 0.250396E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271746E+10 | 0.701727E+09 | 0.616468E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283069E+10 | 0.141242E+10 | 13981137.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276275E+10 | 0.260823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.278540E+10 | 0.640062E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286088E+10 | 0.884239E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271746E+10 | 0.262552E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280050E+10 | 0.118577E+09 | 0.362176E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271746E+10 | 24900101.68 | 0.455479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278540E+10 | 0.00 | 0.794975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331757E+11 | 0.227344E+11 | 0.314854E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.253630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.286088E+10 | 0.884239E+10 | 0.952507E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.149865E+10 | 0.00 | 0.494840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135727E+10 | 5.92 | 0.309075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153097E+10 | 28.69 | 0.130726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145422E+10 | 0.357840E+09 | 0.331803E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151481E+10 | 0.718720E+09 | 7511421.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147845E+10 | 0.133293E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149057E+10 | 0.329103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153097E+10 | 0.455777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145422E+10 | 0.135306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149865E+10 | 61494015.89 | 0.198671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145422E+10 | 12617399.98 | 0.235936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149057E+10 | 0.00 | 0.411691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177535E+11 | 0.116855E+11 | 0.163607E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153097E+10 | 0.455777E+10 | 0.494840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148965E+10 | 0.00 | 0.504314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134912E+10 | 7435.14 | 0.317970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152177E+10 | 71.95 | 0.140689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144549E+10 | 0.345937E+09 | 0.383360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150571E+10 | 0.689713E+09 | 11534569.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146958E+10 | 0.129556E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148162E+10 | 0.323228E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152177E+10 | 0.449213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144549E+10 | 0.132278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148965E+10 | 57993162.24 | 0.241473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144549E+10 | 11058764.19 | 0.244352E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148162E+10 | 0.00 | 0.421248E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176470E+11 | 0.114475E+11 | 0.169221E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152177E+10 | 0.449213E+10 | 0.504314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.148348E+10 | 0.00 | 0.545657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134353E+10 | 9036.26 | 0.351905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151547E+10 | 280.29 | 0.172537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143949E+10 | 0.319488E+09 | 0.546691E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149947E+10 | 0.623916E+09 | 33081680.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146349E+10 | 0.120656E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147548E+10 | 0.308965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151547E+10 | 0.435254E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143949E+10 | 0.125157E+10 | 304760.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148348E+10 | 49797282.06 | 0.374370E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143949E+10 | 7775751.86 | 0.273223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147548E+10 | 0.00 | 0.458757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175738E+11 | 0.109013E+11 | 0.189752E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151547E+10 | 0.435254E+10 | 0.545657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.158420E+10 | 0.00 | 0.723129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143538E+10 | 0.00 | 0.486051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161787E+10 | 11521.54 | 0.277916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153677E+10 | 0.300012E+09 | 0.104219E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160080E+10 | 0.565447E+09 | 0.185165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156238E+10 | 0.114292E+10 | 1594359.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157519E+10 | 0.302738E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161787E+10 | 0.442916E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153677E+10 | 0.121184E+10 | 13543101.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158372E+10 | 38358981.82 | 0.791462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153677E+10 | 3821772.79 | 0.373273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157519E+10 | 0.00 | 0.610574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187629E+11 | 0.107189E+11 | 0.267434E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161787E+10 | 0.442916E+10 | 0.723129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.397630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.359735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.398963E+10 | 0.00 | 0.00 | 0.00 | 236.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.384751E+10 | 0.00 | 0.00 | 0.00 | 0.250129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.397366E+10 | 0.00 | 0.00 | 0.00 | 0.507245E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.386328E+10 | 0.00 | 0.00 | 0.00 | 0.887575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.397366E+10 | 0.00 | 0.00 | 0.00 | 0.219414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.398154E+10 | 0.00 | 0.00 | 0.00 | 0.296273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.385540E+10 | 0.00 | 0.00 | 0.00 | 0.831416E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397366E+10 | 0.00 | 0.00 | 0.00 | 39929618.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.384021E+10 | 0.00 | 0.00 | 0.00 | 10339621.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.399149E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468637E+11 | 0.00 | 0.00 | 0.00 | 0.768350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.359735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.399149E+10 | 0.00 | 0.00 | 0.00 | 0.296273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.165143E+10 | 0.00 | 0.00 | 0.00 | 16749.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150898E+10 | 0.00 | 0.00 | 0.00 | 491163.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172626E+10 | 0.00 | 0.00 | 0.00 | 2601735.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178775E+10 | 0.00 | 0.00 | 0.00 | 0.161530E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.202843E+10 | 0.00 | 0.00 | 0.00 | 0.320920E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205151E+10 | 0.00 | 0.00 | 0.00 | 0.558785E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207843E+10 | 0.00 | 0.00 | 0.00 | 0.127854E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205605E+10 | 0.00 | 0.00 | 0.00 | 0.168074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.207841E+10 | 0.00 | 0.00 | 0.00 | 0.506424E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.191144E+10 | 0.00 | 0.00 | 0.00 | 33039380.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.167682E+10 | 0.00 | 0.00 | 0.00 | 11444806.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164293E+10 | 0.00 | 0.00 | 0.00 | 24693.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221984E+11 | 0.00 | 0.00 | 0.00 | 0.455455E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150898E+10 | 0.00 | 0.00 | 0.00 | 16749.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.207843E+10 | 0.00 | 0.00 | 0.00 | 0.168074E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179786E+10 | 0.00 | 0.00 | 0.00 | 160937.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171016E+10 | 0.00 | 0.00 | 0.00 | 0.121060E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178032E+10 | 0.00 | 0.00 | 0.00 | 0.243164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173647E+10 | 0.00 | 0.00 | 0.00 | 0.419959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175401E+10 | 0.00 | 0.00 | 0.00 | 0.963824E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179786E+10 | 0.00 | 0.00 | 0.00 | 0.130435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171016E+10 | 0.00 | 0.00 | 0.00 | 0.409475E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176278E+10 | 0.00 | 0.00 | 0.00 | 22617933.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171016E+10 | 0.00 | 0.00 | 0.00 | 7842655.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208727E+11 | 0.00 | 0.00 | 0.00 | 0.349246E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159615E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179786E+10 | 0.00 | 0.00 | 0.00 | 0.130435E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180330E+10 | 0.00 | 0.00 | 0.00 | 45118.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171533E+10 | 0.00 | 0.00 | 0.00 | 0.117543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178571E+10 | 0.00 | 0.00 | 0.00 | 0.238005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174172E+10 | 0.00 | 0.00 | 0.00 | 0.414590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175932E+10 | 0.00 | 0.00 | 0.00 | 0.961358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180330E+10 | 0.00 | 0.00 | 0.00 | 0.130531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171533E+10 | 0.00 | 0.00 | 0.00 | 0.405706E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176811E+10 | 0.00 | 0.00 | 0.00 | 21400258.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171533E+10 | 0.00 | 0.00 | 0.00 | 6531138.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175932E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209359E+11 | 0.00 | 0.00 | 0.00 | 0.347049E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180330E+10 | 0.00 | 0.00 | 0.00 | 0.130531E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.175542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.158949E+10 | 0.00 | 0.00 | 0.00 | 6.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179035E+10 | 0.00 | 0.00 | 0.00 | 4.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.170302E+10 | 0.00 | 0.00 | 0.00 | 0.110555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.177289E+10 | 0.00 | 0.00 | 0.00 | 0.223755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.172922E+10 | 0.00 | 0.00 | 0.00 | 0.394354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.174669E+10 | 0.00 | 0.00 | 0.00 | 0.929514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179035E+10 | 0.00 | 0.00 | 0.00 | 0.126721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.170302E+10 | 0.00 | 0.00 | 0.00 | 0.388695E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175542E+10 | 0.00 | 0.00 | 0.00 | 19138533.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.170302E+10 | 0.00 | 0.00 | 0.00 | 4810490.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.174669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.207856E+11 | 0.00 | 0.00 | 0.00 | 0.333804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.158949E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179035E+10 | 0.00 | 0.00 | 0.00 | 0.126721E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.280050E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.253630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.271746E+10 | 0.00 | 0.00 | 0.00 | 0.193401E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283069E+10 | 0.00 | 0.00 | 0.00 | 0.378388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276275E+10 | 0.00 | 0.00 | 0.00 | 0.700580E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.278540E+10 | 0.00 | 0.00 | 0.00 | 0.170236E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286088E+10 | 0.00 | 0.00 | 0.00 | 0.236105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.271746E+10 | 0.00 | 0.00 | 0.00 | 0.687260E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280050E+10 | 0.00 | 0.00 | 0.00 | 31871693.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.271746E+10 | 0.00 | 0.00 | 0.00 | 6879401.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.278540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.331757E+11 | 0.00 | 0.00 | 0.00 | 0.606179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.253630E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.286088E+10 | 0.00 | 0.00 | 0.00 | 0.236105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.149865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135727E+10 | 0.00 | 0.00 | 0.00 | 1.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153097E+10 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145422E+10 | 0.00 | 0.00 | 0.00 | 95816323.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151481E+10 | 0.00 | 0.00 | 0.00 | 0.187072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147845E+10 | 0.00 | 0.00 | 0.00 | 0.347888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149057E+10 | 0.00 | 0.00 | 0.00 | 0.850118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153097E+10 | 0.00 | 0.00 | 0.00 | 0.118168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145422E+10 | 0.00 | 0.00 | 0.00 | 0.343872E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149865E+10 | 0.00 | 0.00 | 0.00 | 16042891.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145422E+10 | 0.00 | 0.00 | 0.00 | 3385510.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177535E+11 | 0.00 | 0.00 | 0.00 | 0.302587E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135727E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153097E+10 | 0.00 | 0.00 | 0.00 | 0.118168E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148965E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134912E+10 | 0.00 | 0.00 | 0.00 | 2048.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152177E+10 | 0.00 | 0.00 | 0.00 | 19.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144549E+10 | 0.00 | 0.00 | 0.00 | 92801511.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150571E+10 | 0.00 | 0.00 | 0.00 | 0.179784E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146958E+10 | 0.00 | 0.00 | 0.00 | 0.338526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148162E+10 | 0.00 | 0.00 | 0.00 | 0.835615E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152177E+10 | 0.00 | 0.00 | 0.00 | 0.116536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144549E+10 | 0.00 | 0.00 | 0.00 | 0.336394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148965E+10 | 0.00 | 0.00 | 0.00 | 15140870.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144549E+10 | 0.00 | 0.00 | 0.00 | 2972640.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.148162E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.176470E+11 | 0.00 | 0.00 | 0.00 | 0.296660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134912E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152177E+10 | 0.00 | 0.00 | 0.00 | 0.116536E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.148348E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.134353E+10 | 0.00 | 0.00 | 0.00 | 2489.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.151547E+10 | 0.00 | 0.00 | 0.00 | 77.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.143949E+10 | 0.00 | 0.00 | 0.00 | 86118688.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.149947E+10 | 0.00 | 0.00 | 0.00 | 0.163282E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.146349E+10 | 0.00 | 0.00 | 0.00 | 0.316358E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.147548E+10 | 0.00 | 0.00 | 0.00 | 0.800989E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.151547E+10 | 0.00 | 0.00 | 0.00 | 0.113117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.143949E+10 | 0.00 | 0.00 | 0.00 | 0.319022E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.148348E+10 | 0.00 | 0.00 | 0.00 | 13038100.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.143949E+10 | 0.00 | 0.00 | 0.00 | 2099832.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.147548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175738E+11 | 0.00 | 0.00 | 0.00 | 0.283208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.134353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.151547E+10 | 0.00 | 0.00 | 0.00 | 0.113117E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.158420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.143538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.161787E+10 | 0.00 | 0.00 | 0.00 | 3157.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.153677E+10 | 0.00 | 0.00 | 0.00 | 81366977.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.160080E+10 | 0.00 | 0.00 | 0.00 | 0.148819E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.156238E+10 | 0.00 | 0.00 | 0.00 | 0.301112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.157519E+10 | 0.00 | 0.00 | 0.00 | 0.787738E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.161787E+10 | 0.00 | 0.00 | 0.00 | 0.115206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.153677E+10 | 0.00 | 0.00 | 0.00 | 0.310433E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.158372E+10 | 0.00 | 0.00 | 0.00 | 10134560.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.153677E+10 | 0.00 | 0.00 | 0.00 | 1039925.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.157519E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.187629E+11 | 0.00 | 0.00 | 0.00 | 0.279270E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.143538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.161787E+10 | 0.00 | 0.00 | 0.00 | 0.115206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.671660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.757462E+10 | 0.00 | 0.00 | 0.53 |
February | 0.749332E+10 | 0.00 | 0.00 | 117750.59 | 0.00 | 0.424769E+10 | 0.148751E+09 | 0.00 | 0.54 |
March | 0.960199E+10 | 0.00 | 0.00 | 233908.18 | 0.00 | 0.114289E+10 | 0.323972E+09 | 0.00 | 0.54 |
April | 0.741128E+10 | 27600607.67 | 0.00 | 3490641.48 | 0.00 | 0.122780E+09 | 0.238529E+10 | 0.00 | 0.64 |
May | 0.375885E+10 | 18329644.94 | 0.00 | 10488052.39 | 0.00 | 1107494.82 | 0.702595E+10 | 0.00 | 0.87 |
June | 0.903509E+09 | 25170362.38 | 0.00 | 18240124.22 | 0.00 | 0.00 | 0.997443E+10 | 0.00 | 1.17 |
July | 0.198203E+09 | 0.369447E+09 | 0.00 | 23074081.34 | 230039.42 | 0.00 | 0.938006E+10 | 0.00 | 1.33 |
August | 0.185909E+09 | 0.825109E+09 | 0.00 | 22413561.21 | 2472.52 | 0.00 | 0.757669E+10 | 0.00 | 1.26 |
September | 0.152738E+10 | 38632919.47 | 0.00 | 16179029.95 | 0.00 | 0.00 | 0.950816E+10 | 0.00 | 1.11 |
October | 0.668231E+10 | 0.00 | 0.00 | 4555768.13 | 0.00 | 7345115.67 | 0.438838E+10 | 0.00 | 0.67 |
November | 0.819895E+10 | 0.00 | 0.00 | 537724.37 | 0.00 | 0.279919E+10 | 0.586559E+09 | 0.00 | 0.55 |
December | 0.762985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.592847E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.603081E+11 | 0.130429E+10 | 0.00 | 99330641.86 | 232511.94 | 0.218241E+11 | 0.512983E+11 | 0.00 | 0.81 |
Minimum of Months | 0.185909E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.53 |
Maximum of Months | 0.960199E+10 | 0.825109E+09 | 0.00 | 23074081.34 | 230039.42 | 0.757462E+10 | 0.997443E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.270638E+10 | 0.00 | 0.00 | 1091.93 | 0.00 | 0.253370E+10 | 804877.30 | 0.00 | 0.39 |
February | 0.310649E+10 | 0.00 | 0.00 | 212081.60 | 0.00 | 0.111330E+10 | 0.232562E+09 | 0.00 | 0.41 |
March | 0.386373E+10 | 0.00 | 0.00 | 551269.51 | 0.00 | 51879175.37 | 0.622594E+09 | 0.00 | 0.44 |
April | 0.222673E+10 | 14199361.65 | 0.00 | 3135080.00 | 0.00 | 3698843.10 | 0.252432E+10 | 0.00 | 0.61 |
May | 0.764768E+09 | 10967357.49 | 0.00 | 7342620.43 | 0.00 | 0.00 | 0.517019E+10 | 0.00 | 0.95 |
June | 0.111652E+09 | 13198630.82 | 0.00 | 10539836.85 | 0.00 | 0.00 | 0.597949E+10 | 0.00 | 1.29 |
July | 35647729.22 | 0.191363E+09 | 0.00 | 11238383.41 | 143613.84 | 0.00 | 0.497005E+10 | 0.00 | 1.37 |
August | 26801177.67 | 0.429531E+09 | 0.00 | 10170931.41 | 315230.69 | 0.00 | 0.396617E+10 | 0.00 | 1.24 |
September | 0.230746E+09 | 22709023.40 | 0.00 | 9546337.01 | 0.00 | 0.00 | 0.593919E+10 | 0.00 | 1.22 |
October | 0.203327E+10 | 0.00 | 0.00 | 4102694.97 | 0.00 | 0.00 | 0.368280E+10 | 0.00 | 0.69 |
November | 0.353792E+10 | 0.00 | 0.00 | 638244.99 | 0.00 | 0.525736E+09 | 0.608909E+09 | 0.00 | 0.45 |
December | 0.299531E+10 | 0.00 | 0.00 | 4849.56 | 0.00 | 0.193871E+10 | 4301582.31 | 0.00 | 0.38 |
Annual Sum or Average | 0.216394E+11 | 0.681968E+09 | 0.00 | 57483421.66 | 458844.53 | 0.616703E+10 | 0.337014E+11 | 0.00 | 0.79 |
Minimum of Months | 26801177.67 | 0.00 | 0.00 | 1091.93 | 0.00 | 0.00 | 804877.30 | 0.00 | 0.38 |
Maximum of Months | 0.386373E+10 | 0.429531E+09 | 0.00 | 11238383.41 | 315230.69 | 0.253370E+10 | 0.597949E+10 | 0.00 | 1.37 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.211777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330513E+10 | 0.00 | 0.00 | 0.41 |
February | 0.282061E+10 | 0.00 | 0.00 | 65125.26 | 0.00 | 0.158539E+10 | 74495030.20 | 0.00 | 0.43 |
March | 0.396128E+10 | 0.00 | 0.00 | 106825.11 | 0.00 | 0.240750E+09 | 0.146977E+09 | 0.00 | 0.44 |
April | 0.272888E+10 | 14657635.61 | 0.00 | 1275562.85 | 0.00 | 11313905.13 | 0.108107E+10 | 0.00 | 0.51 |
May | 0.128755E+10 | 10871908.36 | 0.00 | 4129445.87 | 0.00 | 0.00 | 0.300965E+10 | 0.00 | 0.74 |
June | 0.398477E+09 | 14241787.57 | 0.00 | 6693145.76 | 22089.65 | 0.00 | 0.395164E+10 | 0.00 | 1.00 |
July | 0.191762E+09 | 0.176685E+09 | 0.00 | 7495335.62 | 3510504.87 | 0.00 | 0.327069E+10 | 0.00 | 1.07 |
August | 0.174477E+09 | 0.402570E+09 | 0.00 | 6745491.87 | 6113041.38 | 0.00 | 0.278368E+10 | 0.00 | 1.00 |
September | 0.654847E+09 | 23372873.23 | 0.00 | 5858456.25 | 0.00 | 0.00 | 0.354069E+10 | 0.00 | 0.92 |
October | 0.253585E+10 | 0.00 | 0.00 | 2029530.38 | 0.00 | 0.00 | 0.188216E+10 | 0.00 | 0.56 |
November | 0.314015E+10 | 0.00 | 0.00 | 181040.61 | 0.00 | 0.110529E+10 | 0.176502E+09 | 0.00 | 0.43 |
December | 0.258578E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249979E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.225974E+11 | 0.642399E+09 | 0.00 | 34579959.58 | 9645635.89 | 0.874767E+10 | 0.199175E+11 | 0.00 | 0.66 |
Minimum of Months | 0.174477E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.396128E+10 | 0.402570E+09 | 0.00 | 7495335.62 | 6113041.38 | 0.330513E+10 | 0.395164E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.183904E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.358251E+10 | 0.00 | 0.00 | 0.41 |
February | 0.260793E+10 | 0.00 | 0.00 | 50999.12 | 0.00 | 0.178899E+10 | 64579703.54 | 0.00 | 0.42 |
March | 0.387116E+10 | 0.00 | 0.00 | 85221.02 | 0.00 | 0.308884E+09 | 0.127248E+09 | 0.00 | 0.43 |
April | 0.274381E+10 | 14633279.28 | 0.00 | 1128086.00 | 0.00 | 40444908.89 | 0.963491E+09 | 0.00 | 0.51 |
May | 0.135236E+10 | 10771953.23 | 0.00 | 3900261.45 | 0.00 | 0.00 | 0.287058E+10 | 0.00 | 0.73 |
June | 0.407800E+09 | 14241993.65 | 0.00 | 6580117.18 | 21938.68 | 0.00 | 0.391587E+10 | 0.00 | 0.99 |
July | 0.191109E+09 | 0.176824E+09 | 0.00 | 7473130.04 | 3495976.05 | 0.00 | 0.327032E+10 | 0.00 | 1.07 |
August | 0.174073E+09 | 0.402827E+09 | 0.00 | 6782487.18 | 6108249.12 | 0.00 | 0.279125E+10 | 0.00 | 1.00 |
September | 0.680084E+09 | 23132757.04 | 0.00 | 5731539.21 | 0.00 | 0.00 | 0.347772E+10 | 0.00 | 0.91 |
October | 0.259063E+10 | 0.00 | 0.00 | 1863700.01 | 0.00 | 0.00 | 0.174221E+10 | 0.00 | 0.55 |
November | 0.295632E+10 | 0.00 | 0.00 | 142717.63 | 0.00 | 0.130610E+10 | 0.132393E+09 | 0.00 | 0.43 |
December | 0.236111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.272141E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.217754E+11 | 0.642431E+09 | 0.00 | 33738258.83 | 9626163.84 | 0.974834E+10 | 0.193557E+11 | 0.00 | 0.66 |
Minimum of Months | 0.174073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.387116E+10 | 0.402827E+09 | 0.00 | 7473130.04 | 6108249.12 | 0.358251E+10 | 0.391587E+10 | 0.00 | 1.07 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.150693E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.391295E+10 | 0.00 | 0.00 | 0.41 |
February | 0.219543E+10 | 0.00 | 0.00 | 34623.63 | 0.00 | 0.218824E+10 | 55123733.60 | 0.00 | 0.42 |
March | 0.367534E+10 | 0.00 | 0.00 | 62312.96 | 0.00 | 0.482572E+09 | 95323972.85 | 0.00 | 0.43 |
April | 0.281615E+10 | 14572601.05 | 0.00 | 883904.65 | 0.00 | 75927140.80 | 0.738447E+09 | 0.00 | 0.50 |
May | 0.155852E+10 | 10302626.86 | 0.00 | 3338491.35 | 0.00 | 0.00 | 0.247720E+10 | 0.00 | 0.70 |
June | 0.471458E+09 | 14160310.03 | 0.00 | 6027472.39 | 22728.44 | 0.00 | 0.369312E+10 | 0.00 | 0.97 |
July | 0.202927E+09 | 0.175058E+09 | 0.00 | 7030539.91 | 3530972.47 | 0.00 | 0.316157E+10 | 0.00 | 1.05 |
August | 0.185218E+09 | 0.399250E+09 | 0.00 | 6335492.05 | 6140349.05 | 0.00 | 0.270639E+10 | 0.00 | 0.98 |
September | 0.784043E+09 | 22181509.33 | 0.00 | 5242149.49 | 0.00 | 0.00 | 0.321672E+10 | 0.00 | 0.88 |
October | 0.269543E+10 | 0.00 | 0.00 | 1596985.87 | 0.00 | 8779630.97 | 0.147423E+10 | 0.00 | 0.54 |
November | 0.264343E+10 | 0.00 | 0.00 | 105493.23 | 0.00 | 0.161405E+10 | 0.100317E+09 | 0.00 | 0.43 |
December | 0.202885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305022E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.207637E+11 | 0.635524E+09 | 0.00 | 30657465.53 | 9694049.95 | 0.113327E+11 | 0.177184E+11 | 0.00 | 0.64 |
Minimum of Months | 0.185218E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.367534E+10 | 0.399250E+09 | 0.00 | 7030539.91 | 6140349.05 | 0.391295E+10 | 0.369312E+10 | 0.00 | 1.05 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.173094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.841894E+10 | 0.00 | 0.00 | 0.38 |
February | 0.340776E+10 | 0.00 | 0.00 | 28735.32 | 0.00 | 0.480786E+10 | 61564493.36 | 0.00 | 0.38 |
March | 0.638401E+10 | 0.00 | 0.00 | 66903.62 | 0.00 | 0.133433E+10 | 0.131854E+09 | 0.00 | 0.39 |
April | 0.536289E+10 | 18066000.25 | 0.00 | 1309591.83 | 0.00 | 0.158521E+09 | 0.993004E+09 | 0.00 | 0.44 |
May | 0.324468E+10 | 7899389.50 | 0.00 | 4769262.58 | 0.00 | 0.00 | 0.377103E+10 | 0.00 | 0.60 |
June | 0.874402E+09 | 15092416.57 | 0.00 | 9581461.41 | 6377.31 | 0.00 | 0.629673E+10 | 0.00 | 0.82 |
July | 0.251576E+09 | 0.288660E+09 | 0.00 | 11346177.53 | 3723557.35 | 0.00 | 0.548198E+10 | 0.00 | 0.90 |
August | 0.194792E+09 | 0.684292E+09 | 0.00 | 10116160.36 | 3418697.93 | 0.00 | 0.457184E+10 | 0.00 | 0.84 |
September | 0.166087E+10 | 14673741.01 | 0.00 | 8335008.58 | 0.00 | 0.00 | 0.523095E+10 | 0.00 | 0.75 |
October | 0.501078E+10 | 0.00 | 0.00 | 2203381.76 | 0.00 | 74037051.46 | 0.226274E+10 | 0.00 | 0.46 |
November | 0.434636E+10 | 0.00 | 0.00 | 144597.63 | 0.00 | 0.364027E+10 | 0.162671E+09 | 0.00 | 0.39 |
December | 0.287730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.666471E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.353463E+11 | 0.102868E+10 | 0.00 | 47901280.62 | 7148632.60 | 0.250987E+11 | 0.289644E+11 | 0.00 | 0.56 |
Minimum of Months | 0.194792E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.638401E+10 | 0.684292E+09 | 0.00 | 11346177.53 | 3723557.35 | 0.841894E+10 | 0.629673E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.729557E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.433076E+10 | 0.00 | 0.00 | 0.38 |
February | 0.154823E+10 | 0.00 | 0.00 | 10514.44 | 0.00 | 0.255015E+10 | 25251153.96 | 0.00 | 0.38 |
March | 0.299206E+10 | 0.00 | 0.00 | 28900.18 | 0.00 | 0.858132E+09 | 56922930.59 | 0.00 | 0.39 |
April | 0.261886E+10 | 9216735.02 | 0.00 | 621515.88 | 0.00 | 0.142276E+09 | 0.471000E+09 | 0.00 | 0.44 |
May | 0.169402E+10 | 4156882.60 | 0.00 | 2288804.45 | 0.00 | 0.00 | 0.179902E+10 | 0.00 | 0.60 |
June | 0.462956E+09 | 7902863.64 | 0.00 | 4746944.90 | 2230.99 | 0.00 | 0.316126E+10 | 0.00 | 0.84 |
July | 0.129562E+09 | 0.146357E+09 | 0.00 | 5673774.86 | 1828952.47 | 0.00 | 0.279480E+10 | 0.00 | 0.93 |
August | 97158261.98 | 0.344941E+09 | 0.00 | 5030769.53 | 1679091.73 | 0.00 | 0.233964E+10 | 0.00 | 0.86 |
September | 0.849457E+09 | 7858930.47 | 0.00 | 4155596.95 | 0.00 | 0.00 | 0.263462E+10 | 0.00 | 0.77 |
October | 0.249788E+10 | 0.00 | 0.00 | 1083739.42 | 0.00 | 54686211.98 | 0.111725E+10 | 0.00 | 0.47 |
November | 0.201191E+10 | 0.00 | 0.00 | 67807.58 | 0.00 | 0.197036E+10 | 77038965.89 | 0.00 | 0.39 |
December | 0.127447E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348154E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.169061E+11 | 0.520434E+09 | 0.00 | 23708368.18 | 3510275.19 | 0.133879E+11 | 0.144768E+11 | 0.00 | 0.57 |
Minimum of Months | 97158261.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.299206E+10 | 0.344941E+09 | 0.00 | 5673774.86 | 1828952.47 | 0.433076E+10 | 0.316126E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.652925E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.440729E+10 | 0.00 | 0.00 | 0.38 |
February | 0.142479E+10 | 0.00 | 0.00 | 8100.82 | 0.00 | 0.267309E+10 | 21656610.59 | 0.00 | 0.38 |
March | 0.289986E+10 | 0.00 | 0.00 | 25755.31 | 0.00 | 0.944000E+09 | 50342737.94 | 0.00 | 0.39 |
April | 0.259625E+10 | 9167785.52 | 0.00 | 573200.22 | 0.00 | 0.165058E+09 | 0.436599E+09 | 0.00 | 0.44 |
May | 0.179496E+10 | 3993539.64 | 0.00 | 2079062.23 | 0.00 | 0.00 | 0.162347E+10 | 0.00 | 0.59 |
June | 0.538291E+09 | 7859066.70 | 0.00 | 4508688.09 | 2271.61 | 0.00 | 0.301440E+10 | 0.00 | 0.83 |
July | 0.139406E+09 | 0.145460E+09 | 0.00 | 5494877.38 | 1834117.21 | 0.00 | 0.274329E+10 | 0.00 | 0.91 |
August | 0.104919E+09 | 0.343235E+09 | 0.00 | 4873734.95 | 1675637.79 | 0.00 | 0.230155E+10 | 0.00 | 0.85 |
September | 0.917987E+09 | 7593060.82 | 0.00 | 3964715.40 | 0.00 | 0.00 | 0.250363E+10 | 0.00 | 0.75 |
October | 0.249622E+10 | 0.00 | 0.00 | 996101.91 | 0.00 | 80170422.55 | 0.104182E+10 | 0.00 | 0.46 |
November | 0.193272E+10 | 0.00 | 0.00 | 61844.82 | 0.00 | 0.204899E+10 | 70061936.86 | 0.00 | 0.39 |
December | 0.115605E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359964E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.166544E+11 | 0.517309E+09 | 0.00 | 22586081.14 | 3512026.61 | 0.139182E+11 | 0.138068E+11 | 0.00 | 0.56 |
Minimum of Months | 0.104919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.289986E+10 | 0.343235E+09 | 0.00 | 5494877.38 | 1834117.21 | 0.440729E+10 | 0.301440E+10 | 0.00 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.364320E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.469413E+10 | 0.00 | 0.00 | 0.38 |
February | 0.113192E+10 | 0.00 | 0.00 | 2948.67 | 0.00 | 0.296808E+10 | 8987936.40 | 0.00 | 0.38 |
March | 0.249193E+10 | 0.00 | 0.00 | 18609.44 | 0.00 | 0.132936E+10 | 42465461.93 | 0.00 | 0.39 |
April | 0.248887E+10 | 9073166.69 | 0.00 | 458748.42 | 0.00 | 0.285946E+09 | 0.351847E+09 | 0.00 | 0.43 |
May | 0.196846E+10 | 3616229.85 | 0.00 | 1684072.56 | 0.00 | 7321621.84 | 0.128052E+10 | 0.00 | 0.57 |
June | 0.709187E+09 | 7783399.42 | 0.00 | 3920924.21 | 2172.16 | 0.00 | 0.267440E+10 | 0.00 | 0.80 |
July | 0.179652E+09 | 0.143419E+09 | 0.00 | 4987257.23 | 1953291.35 | 0.00 | 0.260217E+10 | 0.00 | 0.89 |
August | 0.145913E+09 | 0.339474E+09 | 0.00 | 4451808.89 | 1635027.94 | 0.00 | 0.218379E+10 | 0.00 | 0.83 |
September | 0.104490E+10 | 6999318.32 | 0.00 | 3518823.38 | 0.00 | 0.00 | 0.222602E+10 | 0.00 | 0.73 |
October | 0.241960E+10 | 0.00 | 0.00 | 797158.73 | 0.00 | 0.215645E+09 | 0.864708E+09 | 0.00 | 0.45 |
November | 0.165675E+10 | 0.00 | 0.00 | 51513.83 | 0.00 | 0.231707E+10 | 62060519.16 | 0.00 | 0.39 |
December | 0.760995E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.399264E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.153625E+11 | 0.510364E+09 | 0.00 | 19891865.35 | 3590491.45 | 0.158102E+11 | 0.122970E+11 | 0.00 | 0.55 |
Minimum of Months | 0.145913E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.249193E+10 | 0.339474E+09 | 0.00 | 4987257.23 | 1953291.35 | 0.469413E+10 | 0.267440E+10 | 0.00 | 0.89 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 14820177.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.502161E+10 | 0.00 | 0.00 | 0.38 |
February | 0.344254E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.373193E+10 | 0.00 | 0.00 | 0.38 |
March | 0.142397E+10 | 0.00 | 0.00 | 4424.85 | 0.00 | 0.235454E+10 | 24814593.86 | 0.00 | 0.39 |
April | 0.195988E+10 | 9312015.21 | 0.00 | 357566.13 | 0.00 | 0.794109E+09 | 0.274423E+09 | 0.00 | 0.43 |
May | 0.193560E+10 | 3506045.70 | 0.00 | 1288175.93 | 0.00 | 0.135028E+09 | 0.984416E+09 | 0.00 | 0.57 |
June | 0.885120E+09 | 8210314.54 | 0.00 | 3296966.45 | 1087.22 | 0.00 | 0.233563E+10 | 0.00 | 0.79 |
July | 0.332561E+09 | 0.146033E+09 | 0.00 | 4250544.84 | 2080438.87 | 0.00 | 0.234319E+10 | 0.00 | 0.90 |
August | 0.215444E+09 | 0.351227E+09 | 0.00 | 3737817.74 | 1632138.02 | 0.00 | 0.201607E+10 | 0.00 | 0.83 |
September | 0.116004E+10 | 7007007.88 | 0.00 | 2979390.71 | 0.00 | 6103183.86 | 0.191389E+10 | 0.00 | 0.72 |
October | 0.194762E+10 | 0.00 | 0.00 | 535275.31 | 0.00 | 0.718111E+09 | 0.652216E+09 | 0.00 | 0.43 |
November | 0.662644E+09 | 0.00 | 0.00 | 41572.87 | 0.00 | 0.327155E+10 | 58985437.28 | 0.00 | 0.39 |
December | 0.111918E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.461978E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.109939E+11 | 0.525295E+09 | 0.00 | 16491734.84 | 3713664.11 | 0.206528E+11 | 0.106036E+11 | 0.00 | 0.55 |
Minimum of Months | 14820177.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.195988E+10 | 0.351227E+09 | 0.00 | 4250544.84 | 2080438.87 | 0.502161E+10 | 0.234319E+10 | 0.00 | 0.90 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:56
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.460599E+11 | 0.293455E+11 | 0.00 | 0.687053E+11 | 0.147781E+11 |
February | 0.121230E+12 | 0.237236E+11 | 0.00 | 0.563558E+11 | 0.927726E+10 |
March | 0.236623E+12 | 0.218002E+11 | 0.00 | 0.528542E+11 | 0.372249E+10 |
April | 0.391018E+12 | 0.176785E+11 | 0.00 | 0.450567E+11 | 0.714747E+10 |
May | 0.528992E+12 | 0.154292E+11 | 0.00 | 0.494984E+11 | 0.125686E+11 |
June | 0.538825E+12 | 0.111897E+11 | 0.00 | 0.507368E+11 | 0.225343E+11 |
July | 0.573093E+12 | 0.650723E+10 | 0.00 | 0.400187E+11 | 0.548103E+11 |
August | 0.442870E+12 | 0.381199E+10 | 0.00 | 0.302981E+11 | 0.749810E+11 |
September | 0.302989E+12 | 0.108951E+11 | 0.00 | 0.496207E+11 | 0.222726E+11 |
October | 0.175866E+12 | 0.182594E+11 | 0.00 | 0.512783E+11 | 0.161536E+10 |
November | 0.610735E+11 | 0.232458E+11 | 0.00 | 0.553020E+11 | 0.700094E+10 |
December | 0.277574E+11 | 0.271679E+11 | 0.00 | 0.647548E+11 | 0.121776E+11 |
Annual Sum or Average | 0.344640E+13 | 0.209054E+12 | 0.00 | 0.614480E+12 | 0.242886E+12 |
Minimum of Months | 0.277574E+11 | 0.381199E+10 | 0.00 | 0.302981E+11 | 0.161536E+10 |
Maximum of Months | 0.573093E+12 | 0.293455E+11 | 0.00 | 0.687053E+11 | 0.749810E+11 |