Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904
Simulation Timestamp: 2023-10-16 08:40:51
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1087.37 | 520.19 | 520.19 |
Net Site Energy | 1087.37 | 520.19 | 520.19 |
Total Source Energy | 3438.84 | 1645.13 | 1645.13 |
Net Source Energy | 3438.84 | 1645.13 | 1645.13 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 2.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 79.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 230.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 62.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1085.04 | 2.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 2.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 79.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 230.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 62.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 2.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 79.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 230.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 62.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 178.25 | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 519.08 | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 178.25 | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 519.08 | 1.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1085.040 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1085.040 | 100.00 |
Total On-Site and Utility Electric Sources | 1085.040 | 100.00 |
Total Electricity End Uses | 1085.040 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 322.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Latitude [deg] | 32.58 |
Longitude [deg] | -117.0 |
Elevation [m] | 159.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 16-OCT-11:00 | 30-MAR-08:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 52641.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 43128.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13230.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5453.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 98620.33 | 52641.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 52641.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 43128.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13230.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5453.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 2.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 251.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 384.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 731.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 197.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3436.32 | 2.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 120.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 349.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1643.92 | 1.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 1.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 120.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 349.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 94.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1643.92 | 1.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.99 |
SMSTORE1 DIRECT AIR | 1.04 |
SMSTORE2 DIRECT AIR | 1.03 |
SMSTORE3 DIRECT AIR | 1.06 |
SMSTORE4 DIRECT AIR | 1.03 |
LGSTORE2 DIRECT AIR | 1.88 |
SMSTORE5 DIRECT AIR | 0.972886 |
SMSTORE6 DIRECT AIR | 0.967734 |
SMSTORE7 DIRECT AIR | 0.961450 |
SMSTORE8 DIRECT AIR | 1.05 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.99 | 1.00 | 1.000000 | 1.99 |
PSZ-AC_2:2 | 1.04 | 1.04 | 1.04 | 1.04 | 1.06 | 1.06 | 1.00 | 0.982225 | 1.06 |
PSZ-AC_3:3 | 1.03 | 1.03 | 1.03 | 1.03 | 1.06 | 1.06 | 1.00 | 0.976391 | 1.06 |
PSZ-AC_4:4 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.06 | 1.00 | 1.000000 | 1.06 |
PSZ-AC_5:5 | 1.03 | 1.03 | 1.03 | 1.03 | 1.05 | 1.05 | 1.00 | 0.974998 | 1.05 |
PSZ-AC_6:6 | 1.88 | 1.88 | 1.88 | 1.88 | 1.88 | 1.88 | 1.00 | 0.999994 | 1.88 |
PSZ-AC_7:7 | 0.972886 | 0.972886 | 0.972886 | 0.972886 | 0.976513 | 0.976513 | 1.00 | 0.996286 | 0.976513 |
PSZ-AC_8:8 | 0.967734 | 0.967734 | 0.967734 | 0.967734 | 0.971676 | 0.971676 | 1.00 | 0.995943 | 0.971676 |
PSZ-AC_9:9 | 0.961450 | 0.961450 | 0.961450 | 0.961450 | 0.966443 | 0.966443 | 1.00 | 0.994833 | 0.966443 |
PSZ-AC_10:10 | 1.05 | 1.05 | 1.05 | 1.05 | 1.06 | 1.06 | 1.00 | 0.988550 | 1.06 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.99 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.06 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.05 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.88 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.976513 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.971676 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.966443 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.06 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.99 | 2130.79 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1171.40 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1172.96 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1176.51 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.05 | 1167.18 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.88 | 2008.32 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.976513 | 1081.15 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.971676 | 1075.80 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.966443 | 1070.01 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.06 | 1176.27 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.99 | 1.99 | 1.99 | 1.99 | 34709.37 | 53130.88 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 18328.97 | 27542.47 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 18324.99 | 27653.18 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 18374.76 | 28295.50 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.05 | 1.05 | 1.05 | 1.05 | 18244.53 | 27508.99 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.88 | 1.88 | 1.88 | 1.88 | 32940.04 | 50562.52 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.976513 | 0.976513 | 0.976513 | 0.976513 | 17048.21 | 26054.49 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.971676 | 0.971676 | 0.971676 | 0.971676 | 16974.49 | 25938.91 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.966443 | 0.966443 | 0.966443 | 0.966443 | 16863.23 | 25797.94 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.06 | 1.06 | 1.06 | 1.06 | 18219.68 | 27790.73 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.99 | 0.995653 | 1.99 | 34709.37 | 17030.56 | 34709.37 | 0.800160 | 0.800160 |
PSZ-AC_2:2 COOLING COIL | 1.06 | 0.529010 | 1.06 | 18328.97 | 9009.90 | 18328.97 | 0.800310 | 0.800310 |
PSZ-AC_3:3 COOLING COIL | 1.06 | 0.529718 | 1.06 | 18324.99 | 9007.71 | 18324.99 | 0.800850 | 0.800850 |
PSZ-AC_4:4 COOLING COIL | 1.06 | 0.531319 | 1.06 | 18374.76 | 9032.12 | 18374.76 | 0.800960 | 0.800960 |
PSZ-AC_5:5 COOLING COIL | 1.05 | 0.527108 | 1.05 | 18244.53 | 8968.27 | 18244.53 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 1.88 | 0.938426 | 1.88 | 32940.04 | 16165.15 | 32940.04 | 0.800770 | 0.800770 |
PSZ-AC_7:7 COOLING COIL | 0.976510 | 0.488256 | 0.976510 | 17048.21 | 8381.76 | 17048.21 | 0.800600 | 0.800600 |
PSZ-AC_8:8 COOLING COIL | 0.971680 | 0.485838 | 0.971680 | 16974.49 | 8345.62 | 16974.49 | 0.800380 | 0.800380 |
PSZ-AC_9:9 COOLING COIL | 0.966440 | 0.483222 | 0.966440 | 16863.23 | 8290.77 | 16863.23 | 0.800790 | 0.800790 |
PSZ-AC_10:10 COOLING COIL | 1.06 | 0.531211 | 1.06 | 18219.68 | 8954.62 | 18219.68 | 0.800890 | 0.800890 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 53130.88 |
PSZ-AC_2:2 HEATING COIL | 27542.47 |
PSZ-AC_3:3 HEATING COIL | 27653.18 |
PSZ-AC_4:4 HEATING COIL | 28295.50 |
PSZ-AC_5:5 HEATING COIL | 27508.99 |
PSZ-AC_6:6 HEATING COIL | 50562.52 |
PSZ-AC_7:7 HEATING COIL | 26054.49 |
PSZ-AC_8:8 HEATING COIL | 25938.91 |
PSZ-AC_9:9 HEATING COIL | 25797.94 |
PSZ-AC_10:10 HEATING COIL | 27790.73 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.80 | 14.30 | 13.60 | 13.20 | 13.30 | 12.60 | 15.30 | 15.60 | 17.70 | 19.40 | 19.70 | 18.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 | 32.58 | -116.98 | -8.00 | 159.00 | 99429 | 1.1818 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 16.00 | 7.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 35 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.283 | 8.131E-004 | 4.479E-004 | 0.565 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 0.162 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.202 | 1.162E-003 | 5.390E-004 | 0.807 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22193.78147 | 26632.53777 | 1.65942 | 1.99131 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 31.30000 | 8.23349E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 14909.84183 | 17891.81019 | 0.65492 | 0.78591 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11915.08419 | 14298.10103 | 0.86601 | 1.03921 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 6899.22749 | 8279.07299 | 0.30306 | 0.36367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11864.25875 | 14237.11050 | 0.86202 | 1.03442 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 7473.54883 | 8968.25860 | 0.31971 | 0.38365 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11843.38421 | 14212.06106 | 0.88553 | 1.06264 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 7567.69551 | 9081.23462 | 0.32384 | 0.38860 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11790.80624 | 14148.96749 | 0.85655 | 1.02786 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 26.40500 | 8.22575E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 7892.79551 | 9471.35462 | 0.33809 | 0.40570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20917.69943 | 25101.23931 | 1.56403 | 1.87684 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 31.00333 | 8.23302E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 14194.43162 | 17033.31794 | 0.62351 | 0.74821 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11172.38325 | 13406.85990 | 0.81074 | 0.97289 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 7506.88771 | 9008.26526 | 0.32975 | 0.39570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11114.74091 | 13337.68909 | 0.80644 | 0.96773 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 7507.74446 | 9009.29335 | 0.32979 | 0.39574 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11044.25808 | 13253.10970 | 0.80121 | 0.96145 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 7762.19892 | 9314.63871 | 0.34096 | 0.40916 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 12037.47596 | 14444.97116 | 0.87521 | 1.05026 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 27.91800 | 8.22813E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 9661.76274 | 11594.11529 | 0.42439 | 0.50927 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 3.80000 | 5.05843E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29842.36 | 1.99131 | 1.99131 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 26088.77 | 0.78591 | 0.78591 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15706.89 | 1.05802 | 1.05802 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 12387.31 | 0.36367 | 0.36367 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15713.54 | 1.05944 | 1.05944 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 12882.54 | 0.38365 | 0.38365 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15753.84 | 1.06264 | 1.06264 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 12995.29 | 0.38860 | 0.38860 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15643.27 | 1.05422 | 1.05422 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 13384.14 | 0.40570 | 0.40570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28237.21 | 1.87685 | 1.87685 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 25242.90 | 0.74821 | 0.74821 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14573.52 | 0.97651 | 0.97651 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 13105.88 | 0.39570 | 0.39570 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14501.10 | 0.97168 | 0.97168 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 13106.90 | 0.39574 | 0.39574 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14456.77 | 0.96644 | 0.96644 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 13407.79 | 0.40916 | 0.40916 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15560.46 | 1.06242 | 1.06242 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 15653.95 | 0.50927 | 0.50927 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.99131 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03921 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.03442 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.06264 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02786 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.87684 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.97289 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96773 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96145 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.05026 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.99131 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.99131 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.99131 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.99131 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.99131 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.99131 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03921 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03921 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03921 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03921 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05802 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05802 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98222 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.03442 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.03442 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.03442 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.03442 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05944 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05944 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.97639 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.06264 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.06264 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.06264 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.06264 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06264 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06264 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02786 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02786 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02786 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02786 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.05422 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.05422 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.97500 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.87684 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.87684 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.87684 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.87684 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.87685 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.87685 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.99999 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.97289 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.97289 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.97289 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.97289 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97651 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97651 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99629 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96773 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96773 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96773 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96773 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.97168 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.97168 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99594 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96145 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96145 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96145 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96145 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96644 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96644 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.99483 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.05026 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.05026 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.05026 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.05026 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.06242 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.06242 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.98855 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.99131 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.05802 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.05944 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.06264 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.05422 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.87685 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.97651 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.97168 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.96644 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.06242 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.99131 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.99131 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2130.79241 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.99131 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.99131 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.99131 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.99131 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.99131 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.99565 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.99131 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 34709.37000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17030.56020 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 34709.37000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80016 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80016 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 34709.37000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 53130.88219 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 53130.88219 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05802 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05802 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1171.39508 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05802 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05802 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05802 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05802 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05802 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52901 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05802 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18328.97000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9009.90302 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18328.97000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80031 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80031 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18328.97000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27542.46554 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 27542.46554 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05944 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05944 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1172.96301 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05944 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05944 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05944 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05944 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05944 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52972 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05944 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18324.99000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9007.71449 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18324.99000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80085 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80085 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18324.99000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27653.17516 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 27653.17516 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06264 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06264 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1176.50889 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06264 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06264 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06264 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06264 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06264 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53132 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06264 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18374.76000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 9032.11830 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18374.76000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80096 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80096 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18374.76000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28295.50164 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 28295.50164 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.05422 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.05422 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1167.18440 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.05422 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.05422 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.05422 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.05422 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.05422 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.52711 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.05422 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18244.53000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8968.26727 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18244.53000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18244.53000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27508.99353 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 27508.99353 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.87685 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.87685 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2008.32121 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.87685 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.87685 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.87685 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.87685 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.87685 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.93843 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.87685 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 32940.04000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 16165.15286 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 32940.04000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80077 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80077 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 32940.04000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 50562.51803 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 50562.51803 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97651 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97651 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1081.15461 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97651 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97651 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97651 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97651 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97651 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48826 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97651 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17048.21000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8381.75628 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17048.21000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80060 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80060 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17048.21000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 26054.49078 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 26054.49078 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.97168 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.97168 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1075.79907 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.97168 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.97168 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.97168 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.97168 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.97168 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48584 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.97168 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16974.49000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8345.62316 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16974.49000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80038 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80038 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16974.49000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25938.90766 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 25938.90766 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96644 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96644 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1070.00606 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96644 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96644 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96644 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96644 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96644 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48322 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96644 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16863.23000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8290.77193 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16863.23000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80079 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80079 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16863.23000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 25797.94279 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 25797.94279 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.06242 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.06242 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1176.27074 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.06242 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.06242 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.06242 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.06242 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.06242 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.53121 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.06242 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 18219.68000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8954.62109 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 18219.68000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80089 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80089 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 18219.68000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27790.72985 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 27790.72985 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 33147.7 | 10.83 | 10.83 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 17499.3 | 11.09 | 11.09 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 17494.2 | 11.09 | 11.09 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 17541.5 | 11.09 | 11.09 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 17417.8 | 11.09 | 11.09 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 31468.0 | 10.85 | 10.85 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 16282.4 | 11.11 | 11.11 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 16212.4 | 11.11 | 11.11 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 16105.3 | 11.11 | 11.11 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 17386.7 | 11.07 | 11.07 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.6087839746E-002 | 6.8384897766E-002 | Pass | Pass | 2.3143767042E-002 | 9.0021111285E-002 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 5.7150824957E-002 | 0.1103107318 | Pass | Pass | 0.3355710872 | 2.9904285873 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 4.3729635585E-002 | 6.4001685064E-002 | Pass | Pass | 2.6121753092E-002 | 0.1104911088 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.6477533994E-002 | 5.3215460591E-002 | Pass | Pass | 0.1344098289 | 1.0444142705 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 2.8811503774E-002 | 4.3009160863E-002 | Pass | Pass | 6.3576747180E-002 | 0.3123624777 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 2.5856095134E-002 | 4.9401024055E-002 | Pass | Pass | 0.1882752144 | 0.6235818293 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 2.5248534749E-002 | 4.8885139984E-002 | Pass | Pass | 0.4218569387 | 3.1943460859 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 2.8865376754E-002 | 5.2044512524E-002 | Pass | Pass | 0.3031873135 | 1.5065726828 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.2648398277E-002 | 6.2921690316E-002 | Pass | Pass | 0.2558360943 | 0.8697507210 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.4301129616E-002 | 9.6368742643E-002 | Pass | Pass | 8.9892853688E-002 | 0.2471953043 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3518.27 | 111.04 | 0.00 | 459.76 | 386.25 | 4475.34 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 3.80 | 0.00 | 3.80 | Wetbulb [C] | 3.00 | 120.00 |
SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 31.30 | 8.90 | 18.40 | Wetbulb [C] | 4.10 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.00 | 2 | |||
Feb | 59.00 | 53 | |||
Mar | 58.58 | 43 | |||
Apr | 46.42 | 14 | |||
May | 18.00 | 12 | |||
Jun | 0.00 | 0 | |||
Jul | 0.00 | 0 | |||
Aug | 0.00 | 0 | |||
Sep | 3.00 | 6 | |||
Oct | 0.00 | 0 | |||
Nov | 18.00 | 12 | |||
Dec | 4.00 | 4 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.632 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.632 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.75 | 83.75 | 121.42 | |
Exterior Lighting Total | 7723.26 | 121.42 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 34709.37 | 27773.05 | 6936.32 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18328.97 | 14668.86 | 3660.11 | 0.80 | 3.91 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18324.99 | 14675.57 | 3649.42 | 0.80 | 3.91 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18374.76 | 14717.45 | 3657.31 | 0.80 | 3.91 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18244.53 | 14607.67 | 3636.86 | 0.80 | 3.91 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 32940.04 | 26377.40 | 6562.64 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17048.21 | 13648.80 | 3399.41 | 0.80 | 3.91 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16974.49 | 13586.04 | 3388.45 | 0.80 | 3.91 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16863.23 | 13503.91 | 3359.32 | 0.80 | 3.91 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 18219.68 | 14591.96 | 3627.72 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 33147.7 | 10.83 | 10.83 | ||||
PSZ-AC_2:2 COOLING COIL | 17499.3 | 11.09 | 11.09 | ||||
PSZ-AC_3:3 COOLING COIL | 17494.2 | 11.09 | 11.09 | ||||
PSZ-AC_4:4 COOLING COIL | 17541.5 | 11.09 | 11.09 | ||||
PSZ-AC_5:5 COOLING COIL | 17417.8 | 11.09 | 11.09 | ||||
PSZ-AC_6:6 COOLING COIL | 31468.0 | 10.85 | 10.85 | ||||
PSZ-AC_7:7 COOLING COIL | 16282.4 | 11.11 | 11.11 | ||||
PSZ-AC_8:8 COOLING COIL | 16212.4 | 11.11 | 11.11 | ||||
PSZ-AC_9:9 COOLING COIL | 16105.3 | 11.11 | 11.11 | ||||
PSZ-AC_10:10 COOLING COIL | 17386.7 | 11.07 | 11.07 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 53130.88 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 27542.47 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 27653.18 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 28295.50 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 27508.99 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 50562.52 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 26054.49 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 25938.91 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 25797.94 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 27790.73 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.99 | 2130.79 | 1070.05 | 1.00 | 1.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1171.40 | 1107.16 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1172.96 | 1107.16 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1176.51 | 1107.16 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.05 | 1167.18 | 1107.16 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.88 | 2008.32 | 1070.05 | 1.00 | 1.32 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.98 | 1081.15 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1075.80 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1070.01 | 1107.16 | 1.00 | 1.41 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.06 | 1176.27 | 1107.16 | 1.00 | 1.39 | General | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22193.78 | 26632.54 | 76.45 | 1.659 | 1.991 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 23.89 | 23.89 | 0.00894 | 31.30 | 0.00823 | 0.411 | 0.00 |
SMSTORE1 | 11915.08 | 14298.10 | 82.08 | 0.866 | 1.039 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00913 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE2 | 11864.26 | 14237.11 | 81.73 | 0.862 | 1.034 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00931 | 26.41 | 0.00823 | 0.206 | 0.00 |
SMSTORE3 | 11843.38 | 14212.06 | 81.59 | 0.886 | 1.063 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00891 | 31.00 | 0.00823 | 0.206 | 0.00 |
SMSTORE4 | 11790.81 | 14148.97 | 81.23 | 0.857 | 1.028 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00932 | 26.41 | 0.00823 | 0.206 | 0.00 |
LGSTORE2 | 20917.70 | 25101.24 | 72.05 | 1.564 | 1.877 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 23.89 | 23.89 | 0.00897 | 31.00 | 0.00823 | 0.411 | 0.00 |
SMSTORE5 | 11172.38 | 13406.86 | 76.97 | 0.811 | 0.973 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00927 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE6 | 11114.74 | 13337.69 | 76.57 | 0.806 | 0.968 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00929 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE7 | 11044.26 | 13253.11 | 76.08 | 0.801 | 0.961 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00931 | 27.92 | 0.00823 | 0.206 | 0.00 |
SMSTORE8 | 12037.48 | 14444.97 | 82.93 | 0.875 | 1.050 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00911 | 27.92 | 0.00823 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 14909.84 | 17891.81 | 51.36 | 0.655 | 0.786 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00716 | 3.80 | 0.00506 | 0.411 | 0.00 |
SMSTORE1 | 6899.23 | 8279.07 | 47.53 | 0.303 | 0.364 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00713 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE2 | 7473.55 | 8968.26 | 51.48 | 0.320 | 0.384 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.00729 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE3 | 7567.70 | 9081.23 | 52.13 | 0.324 | 0.389 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.00731 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE4 | 7892.80 | 9471.35 | 54.37 | 0.338 | 0.406 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 21.11 | 21.11 | 0.00734 | 3.80 | 0.00506 | 0.206 | 0.00 |
LGSTORE2 | 14194.43 | 17033.32 | 48.89 | 0.624 | 0.748 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00720 | 3.80 | 0.00506 | 0.411 | 0.00 |
SMSTORE5 | 7506.89 | 9008.27 | 51.71 | 0.330 | 0.396 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00717 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE6 | 7507.74 | 9009.29 | 51.72 | 0.330 | 0.396 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00717 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE7 | 7762.20 | 9314.64 | 53.47 | 0.341 | 0.409 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00719 | 3.80 | 0.00506 | 0.206 | 0.00 |
SMSTORE8 | 9661.76 | 11594.12 | 66.56 | 0.424 | 0.509 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00718 | 3.80 | 0.00506 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.99 | 1.99 | 0.79 | 0.79 | 1.9913 | 1.9913 | 1.9913 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.06 | 1.06 | 0.36 | 0.36 | 1.0580 | 1.0392 | 1.0580 | 0.9822 | 1.0000 |
PSZ-AC_3:3 | 1.06 | 1.06 | 0.38 | 0.38 | 1.0594 | 1.0344 | 1.0594 | 0.9764 | 1.0000 |
PSZ-AC_4:4 | 1.06 | 1.06 | 0.39 | 0.39 | 1.0626 | 1.0626 | 1.0626 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.05 | 1.05 | 0.41 | 0.41 | 1.0542 | 1.0279 | 1.0542 | 0.9750 | 1.0000 |
PSZ-AC_6:6 | 1.88 | 1.88 | 0.75 | 0.75 | 1.8769 | 1.8768 | 1.8769 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 0.98 | 0.98 | 0.40 | 0.40 | 0.9765 | 0.9729 | 0.9765 | 0.9963 | 1.0000 |
PSZ-AC_8:8 | 0.97 | 0.97 | 0.40 | 0.40 | 0.9717 | 0.9677 | 0.9717 | 0.9959 | 1.0000 |
PSZ-AC_9:9 | 0.97 | 0.97 | 0.41 | 0.41 | 0.9664 | 0.9615 | 0.9664 | 0.9948 | 1.0000 |
PSZ-AC_10:10 | 1.06 | 1.06 | 0.51 | 0.51 | 1.0624 | 1.0503 | 1.0624 | 0.9885 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 34709.370 | 27773.049 | 1.991310 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | 34709.37 | 33106.25 | 1.991310 | 26.31 | 17.24 | 0.00879058 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 20.6637 | 23.89 | 0.00893567 | 47.4923 | 22193.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 53130.882 | 53130.882 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 53130.88 | 53130.88 | 1.991307 | 17.53 | 12.10 | 0.00672294 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 20.6638 | 21.11 | 0.00715648 | 45.1647 | 14909.84 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 18328.970 | 14668.858 | 1.058020 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 18328.97 | 17500.65 | 1.058020 | 26.25 | 17.21 | 0.00878297 | 12.80 | 11.93 | 0.00850000 | 31.30 | 0.00823349 | 18.45 | 19.4457 | 23.89 | 0.00891604 | 47.3893 | 11761.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 27542.466 | 27542.466 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27542.47 | 27542.47 | 1.058019 | 17.74 | 12.19 | 0.00672467 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 19.4457 | 21.11 | 0.00712689 | 44.9797 | 6899.23 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 18324.990 | 14675.568 | 1.059440 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 18324.99 | 17496.54 | 1.059440 | 26.23 | 17.21 | 0.00878276 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 19.4196 | 23.89 | 0.00891551 | 47.3865 | 11782.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 27653.175 | 27653.175 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27653.18 | 27653.18 | 1.059435 | 17.57 | 12.25 | 0.00685519 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 19.4197 | 21.11 | 0.00728820 | 45.9851 | 7473.55 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 18374.760 | 14717.448 | 1.062640 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 18374.76 | 17545.10 | 1.062640 | 26.23 | 17.21 | 0.00878232 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 19.3612 | 23.89 | 0.00891448 | 47.3811 | 11817.02 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 28295.502 | 28295.502 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 28295.50 | 28295.50 | 1.062638 | 17.58 | 12.27 | 0.00687149 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 19.3612 | 21.11 | 0.00730680 | 46.1010 | 7567.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 18244.530 | 14607.665 | 1.054220 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | 18244.53 | 17417.93 | 1.054220 | 26.24 | 17.21 | 0.00878354 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 19.5158 | 23.89 | 0.00891732 | 47.3960 | 11723.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 27508.994 | 27508.994 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | 27508.99 | 27508.99 | 1.054216 | 17.55 | 12.28 | 0.00689610 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 19.5159 | 21.11 | 0.00734169 | 46.3186 | 7892.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 32940.040 | 26377.396 | 1.876850 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | 32940.04 | 31334.33 | 1.876850 | 26.39 | 17.28 | 0.00880915 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 21.9239 | 23.89 | 0.00897135 | 47.6793 | 20865.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 50562.518 | 50562.518 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 50562.52 | 50562.52 | 1.876853 | 17.31 | 12.02 | 0.00673315 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.9239 | 21.11 | 0.00720342 | 45.4569 | 14194.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 17048.210 | 13648.797 | 0.976510 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 17048.21 | 16250.38 | 0.976510 | 26.36 | 17.26 | 0.00879567 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 21.0688 | 23.89 | 0.00894692 | 47.5511 | 11172.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 26054.491 | 26054.491 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 26054.49 | 26054.49 | 0.976513 | 17.46 | 12.07 | 0.00672501 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.0688 | 21.11 | 0.00716987 | 45.2479 | 7506.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 16974.490 | 13586.042 | 0.971680 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 16974.49 | 16178.41 | 0.971680 | 26.37 | 17.27 | 0.00879651 | 12.80 | 11.93 | 0.00850000 | 31.23 | 0.00823338 | 18.43 | 21.1736 | 23.89 | 0.00894908 | 47.5624 | 11114.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 25938.908 | 25938.908 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 25938.91 | 25938.91 | 0.971676 | 17.44 | 12.06 | 0.00672293 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.1737 | 21.11 | 0.00717004 | 45.2490 | 7507.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 16863.230 | 13503.906 | 0.966440 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 16863.23 | 16070.43 | 0.966440 | 26.36 | 17.26 | 0.00879703 | 12.80 | 11.93 | 0.00850000 | 31.15 | 0.00823326 | 18.40 | 21.2884 | 23.89 | 0.00895017 | 47.5681 | 11044.26 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 25797.943 | 25797.943 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 25797.94 | 25797.94 | 0.966443 | 17.42 | 12.07 | 0.00673357 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 21.2883 | 21.11 | 0.00718662 | 45.3525 | 7762.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 18219.680 | 14591.960 | 1.062420 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 18219.68 | 17430.84 | 1.062420 | 26.17 | 17.18 | 0.00876907 | 12.80 | 11.93 | 0.00850000 | 30.86 | 0.00823278 | 18.30 | 19.3652 | 23.89 | 0.00889938 | 47.3018 | 11730.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 27790.730 | 27790.730 | -999.0 | -999.0 | -999.000 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 27790.73 | 27790.73 | 1.062423 | 17.76 | 12.24 | 0.00676903 | 40.00 | 20.96 | 0.00800000 | 3.80 | 0.00505843 | 3.80 | 19.3651 | 21.11 | 0.00717984 | 45.3116 | 9661.76 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 34709.370 | 27773.049 | 1.991310 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1812 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.991307 | 2.35328389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:30:00 | Sensible | 34709.37 | 33106.25 | 1.0000 | 2.35328767 | 1.991310 | 26.31 | 17.24 | 0.00879058 | 48848.4 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34709.37 | 31.30 | 0.00823349 | 18.45 | 0.41147883 | 20.6637 | 23.89 | 0.00893567 | 23.89 | 0.00893567 | 47.4923 | 22193.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 53130.882 | 53130.882 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.991307 | 2.35328389 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 53130.88 | 53130.88 | 1.0000 | 2.35328389 | 1.991307 | 17.53 | 12.10 | 0.00672294 | 34649.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 53130.88 | 3.80 | 0.00505843 | 3.80 | 0.41147883 | 20.6638 | 21.11 | 0.00715648 | 21.11 | 0.00715648 | 45.1647 | 14909.84 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18328.970 | 14668.858 | 1.058020 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1671 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.058019 | 1.25034439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | Sensible | 18328.97 | 17500.65 | 1.0000 | 1.25034546 | 1.058020 | 26.25 | 17.21 | 0.00878297 | 48772.1 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18328.97 | 31.30 | 0.00823349 | 18.45 | 0.20573941 | 19.4457 | 23.89 | 0.00891604 | 23.89 | 0.00891604 | 47.3893 | 11761.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27542.466 | 27542.466 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.058019 | 1.25034439 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27542.47 | 27542.47 | 1.0000 | 1.25034439 | 1.058019 | 17.74 | 12.19 | 0.00672467 | 34868.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27542.47 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 19.4457 | 21.11 | 0.00712689 | 21.11 | 0.00712689 | 44.9797 | 6899.23 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18324.990 | 14675.568 | 1.059440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1667 | 1004.8586 | 1.1818 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.059435 | 1.25201799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | Sensible | 18324.99 | 17496.54 | 1.0000 | 1.25202359 | 1.059440 | 26.23 | 17.21 | 0.00878276 | 48754.2 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18324.99 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 19.4196 | 23.89 | 0.00891551 | 23.89 | 0.00891551 | 47.3865 | 11782.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27653.175 | 27653.175 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.059435 | 1.25201799 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 27653.18 | 27653.18 | 1.0000 | 1.25201799 | 1.059435 | 17.57 | 12.25 | 0.00685519 | 35022.0 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27653.18 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 19.4197 | 20.89 | 0.00728820 | 21.11 | 0.00728820 | 45.9851 | 7473.55 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18374.760 | 14717.448 | 1.062640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1659 | 1004.8586 | 1.1818 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.062638 | 1.25580285 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | Sensible | 18374.76 | 17545.10 | 1.0000 | 1.25580528 | 1.062640 | 26.23 | 17.21 | 0.00878232 | 48748.8 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18374.76 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 19.3612 | 23.89 | 0.00891448 | 23.89 | 0.00891448 | 47.3811 | 11817.02 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28295.502 | 28295.502 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.062638 | 1.25580285 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 28295.50 | 28295.50 | 1.0000 | 1.25580285 | 1.062638 | 17.58 | 12.27 | 0.00687149 | 35071.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28295.50 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 19.3612 | 20.89 | 0.00730680 | 21.11 | 0.00730680 | 46.1010 | 7567.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18244.530 | 14607.665 | 1.054220 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1682 | 1004.8586 | 1.1818 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.054216 | 1.24584991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | Sensible | 18244.53 | 17417.93 | 1.0000 | 1.24585470 | 1.054220 | 26.24 | 17.21 | 0.00878354 | 48763.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18244.53 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 19.5158 | 23.89 | 0.00891732 | 23.89 | 0.00891732 | 47.3960 | 11723.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27508.994 | 27508.994 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.054216 | 1.24584991 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 09:00:00 | Sensible | 27508.99 | 27508.99 | 1.0000 | 1.24584991 | 1.054216 | 17.55 | 12.28 | 0.00689610 | 35104.9 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27508.99 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 19.5159 | 20.88 | 0.00734169 | 21.11 | 0.00734169 | 46.3186 | 7892.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 32940.040 | 26377.396 | 1.876850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2158 | 1004.8586 | 1.1818 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.876853 | 2.21802459 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:10:00 | Sensible | 32940.04 | 31334.33 | 1.0000 | 2.21802128 | 1.876850 | 26.39 | 17.28 | 0.00880915 | 48978.6 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32940.04 | 31.23 | 0.00823338 | 18.43 | 0.41147883 | 21.9239 | 23.89 | 0.00897135 | 23.89 | 0.00897135 | 47.6793 | 20865.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 50562.518 | 50562.518 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.876853 | 2.21802459 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 50562.52 | 50562.52 | 1.0000 | 2.21802459 | 1.876853 | 17.31 | 12.02 | 0.00673315 | 34453.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 50562.52 | 3.80 | 0.00505843 | 3.80 | 0.41147883 | 21.9239 | 21.11 | 0.00720342 | 21.11 | 0.00720342 | 45.4569 | 14194.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17048.210 | 13648.797 | 0.976510 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1907 | 1004.8586 | 1.1818 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976513 | 1.15402192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 17048.21 | 16250.38 | 1.0000 | 1.15401868 | 0.976510 | 26.36 | 17.26 | 0.00879567 | 48917.1 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17048.21 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 21.0688 | 23.89 | 0.00894692 | 23.89 | 0.00894692 | 47.5511 | 11172.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 26054.491 | 26054.491 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.976513 | 1.15402192 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 26054.49 | 26054.49 | 1.0000 | 1.15402192 | 0.976513 | 17.46 | 12.07 | 0.00672501 | 34583.5 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 26054.49 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 21.0688 | 21.11 | 0.00716987 | 21.11 | 0.00716987 | 45.2479 | 7506.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16974.490 | 13586.042 | 0.971680 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1923 | 1004.8586 | 1.1818 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.971676 | 1.14830543 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 16974.49 | 16178.41 | 1.0000 | 1.14831069 | 0.971680 | 26.37 | 17.27 | 0.00879651 | 48928.3 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16974.49 | 31.23 | 0.00823338 | 18.43 | 0.20573941 | 21.1736 | 23.89 | 0.00894908 | 23.89 | 0.00894908 | 47.5624 | 11114.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25938.908 | 25938.908 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.971676 | 1.14830543 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 25938.91 | 25938.91 | 1.0000 | 1.14830543 | 0.971676 | 17.44 | 12.06 | 0.00672293 | 34559.8 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25938.91 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 21.1737 | 21.11 | 0.00717004 | 21.11 | 0.00717004 | 45.2490 | 7507.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16863.230 | 13503.906 | 0.966440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1932 | 1004.8586 | 1.1818 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.966443 | 1.14212199 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 16863.23 | 16070.43 | 1.0000 | 1.14211817 | 0.966440 | 26.36 | 17.26 | 0.00879703 | 48916.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16863.23 | 31.15 | 0.00823326 | 18.40 | 0.20573941 | 21.2884 | 23.89 | 0.00895017 | 23.89 | 0.00895017 | 47.5681 | 11044.26 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 25797.943 | 25797.943 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.966443 | 1.14212199 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 25797.94 | 25797.94 | 1.0000 | 1.14212199 | 0.966443 | 17.42 | 12.07 | 0.00673357 | 34566.6 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25797.94 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 21.2883 | 21.11 | 0.00718662 | 21.11 | 0.00718662 | 45.3525 | 7762.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 18219.680 | 14591.960 | 1.062420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.1413 | 1004.8586 | 1.1818 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.062423 | 1.25554866 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 18219.68 | 17430.84 | 1.0000 | 1.25554529 | 1.062420 | 26.17 | 17.18 | 0.00876907 | 48651.7 | 12.80 | 11.93 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 18219.68 | 30.86 | 0.00823278 | 18.30 | 0.20573941 | 19.3652 | 23.89 | 0.00889938 | 23.89 | 0.00889938 | 47.3018 | 11730.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27790.730 | 27790.730 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1818 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.062423 | 1.25554866 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | SAN.DIEGO-BROWN.FIELD.MUNI.AP_CA_USA ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 27790.73 | 27790.73 | 1.0000 | 1.25554866 | 1.062423 | 17.76 | 12.24 | 0.00676903 | 34994.7 | 40.00 | 20.96 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27790.73 | 3.80 | 0.00505843 | 3.80 | 0.20573941 | 19.3651 | 21.11 | 0.00717984 | 21.11 | 0.00717984 | 45.3116 | 9661.76 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.99 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.05 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.88 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.98 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.06 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2988.17 | 1624.67 | 244.33 |
SMSTORE1 | 3285.50 | 933.83 | 162.67 |
SMSTORE2 | 2412.83 | 879.83 | 112.17 |
SMSTORE3 | 2341.00 | 957.17 | 114.50 |
SMSTORE4 | 2221.17 | 1108.83 | 124.00 |
LGSTORE2 | 1821.83 | 1324.67 | 134.67 |
SMSTORE5 | 1705.00 | 1395.00 | 136.50 |
SMSTORE6 | 1658.00 | 1459.67 | 137.67 |
SMSTORE7 | 1567.50 | 1634.67 | 146.33 |
SMSTORE8 | 1472.67 | 1898.50 | 164.83 |
Facility | 3363.33 | 2761.33 | 322.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.657 | 0.233 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 1.792 | 0.246 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.906 | 0.321 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.889 | 0.321 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.834 | 0.321 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 1.650 | 0.309 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.693 | 0.342 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.672 | 0.342 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.625 | 0.342 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.666 | 0.370 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.814 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.814 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.813 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 17036712.10 | 0.00 | 17036712.10 | 2758987.14 | 19795699.23 | 12976396.34 | 3170.89 | 1628.61 | 3960.50 | 0.00 |
SMSTORE1 | 9213931.63 | 0.00 | 9213931.63 | 1368026.47 | 10581958.10 | 6488198.17 | 3575.34 | 786.46 | 4398.20 | 0.00 |
SMSTORE2 | 7376184.06 | 0.00 | 7376184.06 | 1397034.38 | 8773218.44 | 6488198.17 | 4365.00 | 1350.19 | 3044.81 | 0.00 |
SMSTORE3 | 7310245.13 | 0.00 | 7310245.13 | 1397034.38 | 8707279.50 | 6488198.17 | 4365.00 | 1390.08 | 3004.92 | 0.00 |
SMSTORE4 | 7097386.68 | 0.00 | 7097386.68 | 1397034.38 | 8494421.06 | 6488198.17 | 4365.00 | 1509.22 | 2885.78 | 0.00 |
LGSTORE2 | 11708192.78 | 0.00 | 11708192.78 | 2569253.52 | 14277446.30 | 12976396.34 | 4730.00 | 1514.82 | 2515.18 | 0.00 |
SMSTORE5 | 6006888.41 | 0.00 | 6006888.41 | 1407666.05 | 7414554.45 | 6488198.17 | 4730.00 | 1515.10 | 2514.90 | 0.00 |
SMSTORE6 | 5932394.21 | 0.00 | 5932394.21 | 1407666.05 | 7340060.26 | 6488198.17 | 4730.00 | 1564.72 | 2465.28 | 0.00 |
SMSTORE7 | 5765014.95 | 0.00 | 5765014.95 | 1407666.05 | 7172681.00 | 6488198.17 | 4730.00 | 1699.31 | 2330.69 | 0.00 |
SMSTORE8 | 5910606.15 | 0.00 | 5910606.15 | 1736138.18 | 7646744.32 | 6488198.17 | 4730.00 | 1864.88 | 2165.12 | 0.00 |
Total Facility | 83357556.09 | 0.00 | 83357556.09 | 16846506.57 | 0.10E+09 | 77858378.04 | 4730.00 | 2730.94 | 4629.37 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.8103 | 0.0000 | 0.8103 | 0.1143 | 0.9246 | 0.4115 | 250.89 | 1628.61 | 3960.50 |
SMSTORE1 | 0.4383 | 0.0000 | 0.4383 | 0.0601 | 0.4983 | 0.2057 | 655.34 | 786.46 | 4398.20 |
SMSTORE2 | 0.4662 | 0.0000 | 0.4662 | 0.0785 | 0.5447 | 0.2057 | 0.00 | 1350.19 | 3044.81 |
SMSTORE3 | 0.4620 | 0.0000 | 0.4620 | 0.0785 | 0.5406 | 0.2057 | 0.00 | 1390.08 | 3004.92 |
SMSTORE4 | 0.4486 | 0.0000 | 0.4486 | 0.0785 | 0.5271 | 0.2057 | 0.00 | 1509.22 | 2885.78 |
LGSTORE2 | 0.8070 | 0.0000 | 0.8070 | 0.1511 | 0.9582 | 0.4115 | 0.00 | 1514.82 | 2515.18 |
SMSTORE5 | 0.4140 | 0.0000 | 0.4140 | 0.0838 | 0.4978 | 0.2057 | 0.00 | 1515.10 | 2514.90 |
SMSTORE6 | 0.4089 | 0.0000 | 0.4089 | 0.0838 | 0.4927 | 0.2057 | 0.00 | 1564.72 | 2465.28 |
SMSTORE7 | 0.3974 | 0.0000 | 0.3974 | 0.0838 | 0.4811 | 0.2057 | 0.00 | 1699.31 | 2330.69 |
SMSTORE8 | 0.4074 | 0.0000 | 0.4074 | 0.0905 | 0.4979 | 0.2057 | 0.00 | 1864.88 | 2165.12 |
Total Facility | 5.0601 | 0.0000 | 5.0601 | 0.9029 | 5.9631 | 2.4689 | 763.47 | 2730.94 | 4629.37 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 23793485.91 | 0.00 | 23793485.91 | 12976396.34 | 3166.17 | 0.17 | 5593.67 | 0.00 |
PSZ-AC_2:2 | 12868184.38 | 0.00 | 12868184.38 | 6488198.17 | 3534.68 | 8.08 | 5217.24 | 0.00 |
PSZ-AC_3:3 | 10301584.64 | 0.00 | 10301584.64 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 10209494.26 | 0.00 | 10209494.26 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 9912215.99 | 0.00 | 9912215.99 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 16351766.55 | 0.00 | 16351766.55 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 8389225.21 | 0.00 | 8389225.21 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 8285186.56 | 0.00 | 8285186.56 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 8051424.55 | 0.00 | 8051424.55 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 8254757.33 | 0.00 | 8254757.33 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 1.1317 | 0.0000 | 1.1317 | 0.4115 | 246.17 | 0.17 | 5593.67 |
PSZ-AC_2:2 | 0.6121 | 0.0000 | 0.6121 | 0.2057 | 614.68 | 8.08 | 5217.24 |
PSZ-AC_3:3 | 0.6511 | 0.0000 | 0.6511 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.6453 | 0.0000 | 0.6453 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.6265 | 0.0000 | 0.6265 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 1.1271 | 0.0000 | 1.1271 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.5782 | 0.0000 | 0.5782 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.5711 | 0.0000 | 0.5711 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.5550 | 0.0000 | 0.5550 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.5690 | 0.0000 | 0.5690 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 3147.43 | 2462.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 2476.25 | 3094.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 2795.11 | 1599.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 2803.40 | 1591.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 2883.75 | 1511.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 2756.09 | 1273.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 2747.93 | 1282.07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 2782.09 | 1247.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 2873.40 | 1156.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 2965.16 | 1064.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 1.2426 | 1.0962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.7585 | 0.5483 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.6742 | 0.6110 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.6674 | 0.6067 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.6418 | 0.5977 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 1.1452 | 1.0889 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.5877 | 0.5584 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.5782 | 0.5555 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.5566 | 0.5515 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.5662 | 0.5774 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
ElectricityPurchased:Plant | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
Cogeneration:ElectricityPurchased | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
General:Cogeneration:ElectricityPurchased | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
ElectricityNet:Plant | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
Cogeneration:ElectricityNet | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
General:Cogeneration:ElectricityNet | 1085.04 | 3178.87 | 01-JAN-07:00 | 98620.33 | 16-OCT-12:00 |
Electricity:HVAC | 310.29 | 0.00 | 01-JAN-00:10 | 57293.08 | 16-OCT-11:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 79.45 | 0.00 | 01-JAN-00:10 | 44062.68 | 16-OCT-11:10 |
General:Cooling:Electricity | 79.45 | 0.00 | 01-JAN-00:10 | 44062.68 | 16-OCT-11:10 |
Fans:Electricity | 230.84 | 0.00 | 01-JAN-00:10 | 13230.40 | 20-APR-10:20 |
General:Fans:Electricity | 230.84 | 0.00 | 01-JAN-00:10 | 13230.40 | 20-APR-10:20 |
ExteriorLights:Electricity | 121.42 | 0.00 | 01-JAN-07:00 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.42 | 0.00 | 01-JAN-07:00 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 62.30 | 1218.00 | 30-APR-17:10 | 11785.29 | 17-JAN-19:00 |
WaterSystems:Electricity | 62.30 | 1218.00 | 30-APR-17:10 | 11785.29 | 17-JAN-19:00 |
Water Heater:WaterSystems:Electricity | 62.30 | 1218.00 | 30-APR-17:10 | 11785.29 | 17-JAN-19:00 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 2.33 | 0.00 | 01-JAN-00:10 | 52641.18 | 30-MAR-08:10 |
NaturalGas:HVAC | 2.33 | 0.00 | 01-JAN-00:10 | 52641.18 | 30-MAR-08:10 |
Heating:NaturalGas | 2.33 | 0.00 | 01-JAN-00:10 | 52641.18 | 30-MAR-08:10 |
General:Heating:NaturalGas | 2.33 | 0.00 | 01-JAN-00:10 | 52641.18 | 30-MAR-08:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 794.08 | 0.00 | 01-JAN-00:10 | 242423.23 | 16-OCT-12:10 |
EnergyTransfer:Building | 485.88 | 0.00 | 01-JAN-00:10 | 97144.82 | 16-OCT-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 107.20 | 0.00 | 01-JAN-00:10 | 16257.14 | 29-SEP-13:00 |
Heating:EnergyTransfer | 15.03 | 0.00 | 01-JAN-00:10 | 28646.15 | 30-MAR-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 2.20 | 0.00 | 01-JAN-00:10 | 4920.20 | 30-MAR-08:10 |
General:Heating:EnergyTransfer | 15.03 | 0.00 | 01-JAN-00:10 | 28646.15 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 2.20 | 0.00 | 01-JAN-00:10 | 4920.20 | 30-MAR-08:10 |
Cooling:EnergyTransfer | 470.86 | 0.00 | 01-JAN-00:10 | 97144.82 | 16-OCT-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 105.00 | 0.00 | 01-JAN-00:10 | 16257.14 | 29-SEP-13:00 |
General:Cooling:EnergyTransfer | 470.86 | 0.00 | 01-JAN-00:10 | 97144.82 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 105.00 | 0.00 | 01-JAN-00:10 | 16257.14 | 29-SEP-13:00 |
EnergyTransfer:Zone:SMSTORE1 | 62.63 | 0.00 | 01-JAN-00:10 | 10503.30 | 05-FEB-18:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.18 | 0.00 | 01-JAN-00:10 | 1133.25 | 28-MAR-08:00 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.18 | 0.00 | 01-JAN-00:10 | 1133.25 | 28-MAR-08:00 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 61.45 | 0.00 | 01-JAN-00:10 | 10503.30 | 05-FEB-18:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 61.45 | 0.00 | 01-JAN-00:10 | 10503.30 | 05-FEB-18:10 |
EnergyTransfer:Zone:SMSTORE2 | 44.52 | 0.00 | 01-JAN-00:10 | 8428.13 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 1.28 | 0.00 | 01-JAN-00:10 | 1704.44 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 1.28 | 0.00 | 01-JAN-00:10 | 1704.44 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 43.24 | 0.00 | 01-JAN-00:10 | 8428.13 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 43.24 | 0.00 | 01-JAN-00:10 | 8428.13 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 43.34 | 0.00 | 01-JAN-00:10 | 8456.27 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 1.28 | 0.00 | 01-JAN-00:10 | 1707.78 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 1.28 | 0.00 | 01-JAN-00:10 | 1707.78 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 42.06 | 0.00 | 01-JAN-00:10 | 8456.27 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 42.06 | 0.00 | 01-JAN-00:10 | 8456.27 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 40.59 | 0.00 | 01-JAN-00:10 | 8317.59 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 1.28 | 0.00 | 01-JAN-00:10 | 1716.59 | 15-OCT-16:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 1.28 | 0.00 | 01-JAN-00:10 | 1716.59 | 15-OCT-16:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 39.31 | 0.00 | 01-JAN-00:10 | 8317.59 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 39.31 | 0.00 | 01-JAN-00:10 | 8317.59 | 16-OCT-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 65.24 | 0.00 | 01-JAN-00:10 | 15516.51 | 15-OCT-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 2.34 | 0.00 | 01-JAN-00:10 | 5592.73 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 2.34 | 0.00 | 01-JAN-00:10 | 5592.73 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 62.90 | 0.00 | 01-JAN-00:10 | 15243.17 | 16-OCT-12:20 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 62.90 | 0.00 | 01-JAN-00:10 | 15243.17 | 16-OCT-12:20 |
EnergyTransfer:Zone:SMSTORE5 | 32.68 | 0.00 | 01-JAN-00:10 | 7992.24 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.29 | 0.00 | 01-JAN-00:10 | 3173.46 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.29 | 0.00 | 01-JAN-00:10 | 3173.46 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 31.39 | 0.00 | 01-JAN-00:10 | 7992.24 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 31.39 | 0.00 | 01-JAN-00:10 | 7992.24 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 31.82 | 0.00 | 01-JAN-00:10 | 7932.88 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.29 | 0.00 | 01-JAN-00:10 | 3568.68 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.29 | 0.00 | 01-JAN-00:10 | 3568.68 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 30.53 | 0.00 | 01-JAN-00:10 | 7932.88 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 30.53 | 0.00 | 01-JAN-00:10 | 7932.88 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 29.67 | 0.00 | 01-JAN-00:10 | 7850.04 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.32 | 0.00 | 01-JAN-00:10 | 4408.35 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.32 | 0.00 | 01-JAN-00:10 | 4408.35 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 28.35 | 0.00 | 01-JAN-00:10 | 7850.04 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 28.35 | 0.00 | 01-JAN-00:10 | 7850.04 | 16-OCT-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 28.20 | 0.00 | 01-JAN-00:10 | 8896.67 | 16-OCT-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.58 | 0.00 | 01-JAN-00:10 | 6947.47 | 30-MAR-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.58 | 0.00 | 01-JAN-00:10 | 6947.47 | 30-MAR-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 26.62 | 0.00 | 01-JAN-00:10 | 8896.67 | 16-OCT-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 26.62 | 0.00 | 01-JAN-00:10 | 8896.67 | 16-OCT-12:10 |
EnergyTransfer:HVAC | 308.19 | 0.00 | 01-JAN-00:10 | 145278.41 | 16-OCT-12:10 |
HeatingCoils:EnergyTransfer | 1.86 | 0.00 | 01-JAN-00:10 | 42112.94 | 30-MAR-08:10 |
CoolingCoils:EnergyTransfer | 306.33 | 0.00 | 01-JAN-00:10 | 145278.41 | 16-OCT-12:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 2.197 | -105.002 | 0.000 | 0.000 | 23.411 | 106.728 | 26.357 | 18.720 | 0.000 | 0.605 | 0.000 | 0.000 | -8.735 | 0.000 | -18.459 | -45.822 |
SMSTORE1 | 0.000 | 0.000 | 1.178 | -61.453 | 0.000 | 0.000 | 11.641 | 62.296 | 13.179 | 9.273 | 0.000 | 0.322 | 0.000 | 0.000 | -4.525 | 0.000 | -8.755 | -23.158 |
SMSTORE2 | 0.000 | 0.000 | 1.277 | -43.244 | 0.000 | 0.000 | 7.018 | 44.966 | 10.467 | 9.272 | 0.000 | 0.321 | 0.001 | 0.000 | -4.536 | 0.000 | -9.068 | -16.473 |
SMSTORE3 | 0.000 | 0.000 | 1.281 | -42.058 | 0.000 | 0.000 | 7.025 | 44.966 | 10.467 | 9.287 | 0.000 | 0.321 | 0.000 | 0.000 | -4.492 | 0.000 | -9.022 | -17.775 |
SMSTORE4 | 0.000 | 0.000 | 1.282 | -39.306 | 0.000 | 0.000 | 7.038 | 44.966 | 10.467 | 9.314 | 0.000 | 0.321 | 0.001 | 0.000 | -4.430 | 0.000 | -8.946 | -20.706 |
LGSTORE2 | 0.000 | 0.000 | 2.338 | -62.906 | 0.000 | 0.000 | 24.215 | 51.668 | 19.261 | 18.759 | 0.000 | 0.577 | 0.001 | 0.000 | -8.545 | 0.000 | -16.406 | -28.962 |
SMSTORE5 | 0.000 | 0.000 | 1.287 | -31.390 | 0.000 | 0.000 | 12.110 | 26.679 | 9.631 | 9.369 | 0.000 | 0.320 | 0.000 | 0.000 | -4.261 | 0.000 | -8.878 | -14.866 |
SMSTORE6 | 0.000 | 0.000 | 1.289 | -30.527 | 0.000 | 0.000 | 12.123 | 26.679 | 9.631 | 9.385 | 0.000 | 0.320 | 0.000 | 0.000 | -4.233 | 0.000 | -8.835 | -15.831 |
SMSTORE7 | 0.000 | 0.000 | 1.319 | -28.355 | 0.000 | 0.000 | 12.160 | 26.679 | 9.631 | 9.425 | 0.000 | 0.321 | 0.000 | 0.000 | -4.152 | 0.000 | -8.709 | -18.317 |
SMSTORE8 | 0.000 | 0.000 | 1.581 | -26.622 | 0.000 | 0.000 | 12.220 | 26.679 | 9.631 | 9.503 | 0.000 | 0.344 | 0.000 | 0.000 | -3.884 | 0.000 | -11.366 | -18.086 |
Total Facility | 0.000 | 0.000 | 15.029 | -470.863 | 0.000 | 0.000 | 128.961 | 462.305 | 128.721 | 112.307 | 0.000 | 3.772 | 0.005 | 0.000 | -51.792 | 0.000 | -108.444 | -219.996 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 | -34712.02 | 0.00 | 0.00 | 182.05 | 2916.31 | 749.03 | 312.49 | 0.00 | 0.00 | 30836.54 | 0.00 | -0.00 | 0.00 | -284.39 | 0.00 |
SMSTORE1 | 24-MAY-08:62 | 0.00 | 0.00 | 0.00 | -21178.08 | 0.00 | 0.00 | 87.92 | 1702.23 | 374.52 | 147.14 | 0.00 | 0.00 | 19014.67 | 0.00 | -0.00 | 0.00 | -148.39 | 0.00 |
SMSTORE2 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21206.25 | 0.00 | 0.00 | 87.94 | 1536.36 | 374.52 | 229.60 | 0.00 | 0.00 | 19143.04 | 0.00 | -0.00 | 0.00 | -165.20 | 0.00 |
SMSTORE3 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -21260.02 | 0.00 | 0.00 | 87.95 | 1536.36 | 374.52 | 229.62 | 0.00 | 0.00 | 19196.64 | 0.00 | -0.00 | 0.00 | -165.07 | 0.00 |
SMSTORE4 | 18-OCT-07:02 | 0.00 | 0.00 | 0.00 | -20969.47 | 0.00 | 0.00 | 88.92 | 1536.36 | 374.52 | 232.04 | 0.00 | 0.00 | 18899.63 | 0.00 | -0.00 | 0.00 | -161.99 | 0.00 |
LGSTORE2 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -33231.82 | 0.00 | 0.00 | 394.44 | 1920.56 | 749.03 | 1666.35 | 0.00 | 0.00 | 28620.16 | 0.00 | -0.00 | 0.00 | -118.72 | 0.00 |
SMSTORE5 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -17085.05 | 0.00 | 0.00 | 198.23 | 991.67 | 374.52 | 832.56 | 0.00 | 0.00 | 14750.71 | 0.00 | -0.00 | 0.00 | -62.63 | 0.00 |
SMSTORE6 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -16974.96 | 0.00 | 0.00 | 198.99 | 991.67 | 374.52 | 833.65 | 0.00 | 0.00 | 14637.67 | 0.00 | -0.00 | 0.00 | -61.53 | 0.00 |
SMSTORE7 | 18-OCT-08:62 | 0.00 | 0.00 | 0.00 | -16074.09 | 0.00 | 0.00 | 201.73 | 991.67 | 374.52 | 837.14 | 0.00 | 0.00 | 13727.32 | 0.00 | -0.00 | 0.00 | -58.28 | 0.00 |
SMSTORE8 | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | -16367.43 | 0.00 | 0.00 | 186.08 | 991.67 | 374.52 | 976.63 | 0.00 | 4.17 | 13834.36 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 30-SEP-08:61 | 0.00 | 0.00 | 0.00 | -153110.91 | 0.00 | 0.00 | 1936.31 | 19263.00 | 5393.02 | 11754.90 | 0.00 | 106.63 | 114687.73 | 0.00 | 0.00 | 0.00 | -30.69 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 30-MAR-08:61 | 0.00 | 0.00 | 28039.00 | 0.00 | 0.00 | 0.00 | 237.95 | 2916.31 | 749.03 | 968.57 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -749.39 | -32161.47 |
SMSTORE1 | 29-SEP-08:05 | 0.00 | 0.00 | 2756.03 | 0.00 | 0.00 | 0.00 | 83.67 | 1702.23 | 374.52 | 1086.64 | 0.00 | 116.81 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -6119.89 |
SMSTORE2 | 15-OCT-08:06 | 0.00 | 0.00 | 2634.78 | 0.00 | 0.00 | 0.00 | 82.53 | 1536.36 | 374.52 | 1080.18 | 0.00 | 150.13 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5858.49 |
SMSTORE3 | 15-OCT-08:06 | 0.00 | 0.00 | 2640.43 | 0.00 | 0.00 | 0.00 | 82.42 | 1536.36 | 374.52 | 1079.77 | 0.00 | 150.23 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -5863.72 |
SMSTORE4 | 30-MAR-07:03 | 0.00 | 0.00 | 3167.00 | 0.00 | 0.00 | 0.00 | 116.99 | 1536.36 | 374.52 | 9.16 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -396.10 | -4807.93 |
LGSTORE2 | 30-MAR-08:61 | 0.00 | 0.00 | 32341.68 | 0.00 | 0.00 | 0.00 | 525.92 | 1920.56 | 749.03 | 966.98 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -622.63 | -35881.55 |
SMSTORE5 | 30-MAR-08:61 | 0.00 | 0.00 | 17803.33 | 0.00 | 0.00 | 0.00 | 263.73 | 991.67 | 374.52 | 482.00 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -337.40 | -19577.84 |
SMSTORE6 | 30-MAR-08:61 | 0.00 | 0.00 | 20575.74 | 0.00 | 0.00 | 0.00 | 265.18 | 991.67 | 374.52 | 484.65 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -337.25 | -22354.51 |
SMSTORE7 | 30-MAR-08:61 | 0.00 | 0.00 | 23225.48 | 0.00 | 0.00 | 0.00 | 270.19 | 991.67 | 374.52 | 493.41 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -328.13 | -25027.13 |
SMSTORE8 | 02-JAN-09:02 | 0.00 | 0.00 | 25619.25 | 0.00 | 0.00 | 0.00 | 277.36 | 991.67 | 374.52 | 809.82 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -262.28 | -27810.33 |
Total Facility | 30-MAR-08:61 | -3520.14 | 3520.14 | 147341.43 | -3520.14 | 0.00 | 0.00 | 2650.42 | 19263.00 | 5393.02 | 5770.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4158.23 | -172739.54 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9913 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9913 | 0.2066 | 1.0000 | Not calculated | 0.4115 | 0.2066 | ||
PSZ-AC_2:2 | 1.0392 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0580 | 0.1945 | 1.0000 | Not calculated | 0.2057 | 0.1945 | ||
PSZ-AC_3:3 | 1.0344 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0594 | 0.1942 | 1.0000 | Not calculated | 0.2057 | 0.1942 | ||
PSZ-AC_4:4 | 1.0626 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0626 | 0.1936 | 1.0000 | Not calculated | 0.2057 | 0.1936 | ||
PSZ-AC_5:5 | 1.0279 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0542 | 0.1952 | 1.0000 | Not calculated | 0.2057 | 0.1952 | ||
PSZ-AC_6:6 | 1.8768 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8769 | 0.2192 | 1.0000 | Not calculated | 0.4115 | 0.2192 | ||
PSZ-AC_7:7 | 0.9729 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9765 | 0.2107 | 1.0000 | Not calculated | 0.2057 | 0.2107 | ||
PSZ-AC_8:8 | 0.9677 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9717 | 0.2117 | 1.0000 | Not calculated | 0.2057 | 0.2117 | ||
PSZ-AC_9:9 | 0.9615 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9664 | 0.2129 | 1.0000 | Not calculated | 0.2057 | 0.2129 | ||
PSZ-AC_10:10 | 1.0503 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0624 | 0.1937 | 1.0000 | Not calculated | 0.2057 | 0.1937 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.9913 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9913 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2066 | ||
PSZ-AC_2:2 | 1.0392 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0392 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1980 | ||
PSZ-AC_3:3 | 1.0344 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0344 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1989 | ||
PSZ-AC_4:4 | 1.0626 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0626 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1936 | ||
PSZ-AC_5:5 | 1.0279 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0279 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_6:6 | 1.8768 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8768 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2192 | ||
PSZ-AC_7:7 | 0.9729 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9729 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2115 | ||
PSZ-AC_8:8 | 0.9677 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9677 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2126 | ||
PSZ-AC_9:9 | 0.9615 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9615 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2140 | ||
PSZ-AC_10:10 | 1.0503 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0503 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1959 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9913 | 1.9913 | 1.9913 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0392 | 1.0392 | 1.0392 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0344 | 1.0344 | 1.0344 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0626 | 1.0626 | 1.0626 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0279 | 1.0279 | 1.0279 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8768 | 1.8768 | 1.8768 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9729 | 0.9729 | 0.9729 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9677 | 0.9677 | 0.9677 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9615 | 0.9615 | 0.9615 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0503 | 1.0503 | 1.0503 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9913 | 1.9913 | 1.9913 | 1.9913 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0392 | 1.0580 | 1.0392 | 1.0392 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0344 | 1.0594 | 1.0344 | 1.0344 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0626 | 1.0626 | 1.0626 | 1.0626 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0279 | 1.0542 | 1.0279 | 1.0279 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8768 | 1.8769 | 1.8768 | 1.8768 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9729 | 0.9765 | 0.9729 | 0.9729 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9677 | 0.9717 | 0.9677 | 0.9677 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9615 | 0.9664 | 0.9615 | 0.9615 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0503 | 1.0624 | 1.0503 | 1.0503 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9913 | 1.9913 | 1.9913 | No | 0.4115 | 0.5236 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0392 | 1.0392 | 1.0392 | No | 0.2057 | 0.5657 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0344 | 1.0344 | 1.0344 | No | 0.2057 | 0.5363 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0626 | 1.0626 | 1.0626 | No | 0.2057 | 0.5294 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0279 | 1.0279 | 1.0279 | No | 0.2057 | 0.5071 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8768 | 1.8768 | 1.8768 | No | 0.4115 | 0.5500 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9729 | 0.9729 | 0.9729 | No | 0.2057 | 0.5199 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9677 | 0.9677 | 0.9677 | No | 0.2057 | 0.5199 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9615 | 0.9615 | 0.9615 | No | 0.2057 | 0.5028 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0503 | 1.0503 | 1.0503 | No | 0.2057 | 0.4040 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.9913 | 1.9913 | 1.9913 | 1.9913 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0392 | 1.0392 | 1.0392 | 1.0392 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0344 | 1.0344 | 1.0344 | 1.0344 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0626 | 1.0626 | 1.0626 | 1.0626 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0279 | 1.0279 | 1.0279 | 1.0279 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.8768 | 1.8768 | 1.8768 | 1.8768 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9729 | 0.9729 | 0.9729 | 0.9729 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9677 | 0.9677 | 0.9677 | 0.9677 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9615 | 0.9615 | 0.9615 | 0.9615 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.0503 | 1.0503 | 1.0503 | 1.0503 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** San Diego-Brown Field Muni AP CA USA TMY3 WMO#=722904 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 2.33 | 52641.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 79.45 | 44062.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.42 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 230.84 | 13230.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 62.30 | 11785.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1085.04 |
Natural Gas | 0.00 | 2.33 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1087.37 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 38.01 |
Fans (All) | 110.43 |
Service Water Heating | 29.80 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 519.08 |
Subtotal | 519.08 |
Natural Gas [MJ/m2] | |
Space Heating | 1.11 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 1.11 |
Subtotal | 1.11 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 42.52 |
Space Heating | 0.21 |
Space Cooling | 7.31 |
Fans (All) | 21.23 |
Service Water Heating | 5.73 |
Receptacle Equipment | 11.84 |
Miscellaneous | 11.17 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8759.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.83 | 0.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 8759.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 0.50 | 0.00 | 0.00 | 0.00 |
Average | 8759.88 | 0.12 | 0.00 | 0.00 | 0.00 |
Sum | 87598.83 | 1.17 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.67 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.83 | 0.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93211.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.67 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93211.00 | 0.33 | 0.00 | 0.00 | 0.00 |
Average | 48610.12 | 0.08 | 0.00 | 0.00 | 0.00 |
Sum | 486101.17 | 0.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8185.33 | 574.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8198.67 | 561.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 7931.50 | 828.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 7944.33 | 815.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 7979.17 | 780.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8036.67 | 723.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8060.00 | 700.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8078.83 | 681.17 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8135.00 | 625.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8331.33 | 428.67 | 0.00 | 0.00 | 0.00 |
Min | 7931.50 | 428.67 | 0.00 | 0.00 | 0.00 |
Max | 8331.33 | 828.50 | 0.00 | 0.00 | 0.00 |
Average | 8088.08 | 671.92 | 0.00 | 0.00 | 0.00 |
Sum | 80880.83 | 6719.17 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86731.00 | 2310.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43040.00 | 737.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25119.00 | 356.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25113.83 | 361.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25091.00 | 384.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 91427.50 | 1783.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45034.83 | 877.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45026.67 | 885.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45001.00 | 911.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 44880.00 | 1032.00 | 0.00 | 0.00 | 0.00 |
Min | 25091.00 | 356.00 | 0.00 | 0.00 | 0.00 |
Max | 91427.50 | 2310.00 | 0.00 | 0.00 | 0.00 |
Average | 47646.48 | 963.72 | 0.00 | 0.00 | 0.00 |
Sum | 476464.83 | 9637.17 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:51
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3C
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_CA_SANDIEGO
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 13.221 |
February | 13.282 |
March | 12.638 |
April | 15.303 |
May | 15.556 |
June | 17.667 |
July | 19.435 |
August | 19.664 |
September | 18.470 |
October | 18.770 |
November | 14.323 |
December | 13.589 |
Annual Sum or Average | 16.011 |
Minimum of Months | 12.638 |
Maximum of Months | 19.664 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.662329E+10 | 22484.10 | 21-JAN-09:02 | 14.33 | 13.47 | 0.136527E+10 | 1685.87 | 20-JAN-13:20 | 14.33 | 13.47 |
February | 0.533481E+10 | 14309.85 | 01-FEB-09:02 | 22.33 | 11.86 | 0.123129E+10 | 1685.85 | 03-FEB-13:20 | 22.33 | 8.61 |
March | 0.588513E+10 | 8143.88 | 23-MAR-14:00 | 23.00 | 17.27 | 0.132951E+10 | 1685.95 | 19-MAR-12:00 | 23.00 | 17.27 |
April | 0.786373E+10 | 31220.57 | 27-APR-08:62 | 17.33 | 15.22 | 0.135784E+10 | 1685.99 | 30-APR-12:39 | 24.33 | 16.98 |
May | 0.805470E+10 | 34721.98 | 24-MAY-08:62 | 18.00 | 8.80 | 0.139945E+10 | 1685.96 | 19-MAY-12:39 | 18.00 | 8.80 |
June | 0.968242E+10 | 33968.01 | 23-JUN-08:62 | 18.50 | 14.15 | 0.135494E+10 | 1685.96 | 02-JUN-12:30 | 18.50 | 14.15 |
July | 0.123639E+11 | 33383.78 | 10-JUL-08:62 | 19.33 | 14.88 | 0.141370E+10 | 1685.96 | 04-JUL-17:30 | 19.33 | 14.88 |
August | 0.125260E+11 | 33632.04 | 22-AUG-08:62 | 17.58 | 14.22 | 0.139507E+10 | 1685.94 | 27-AUG-17:49 | 18.33 | 15.67 |
September | 0.110748E+11 | 33251.23 | 27-SEP-08:62 | 16.17 | 14.19 | 0.136568E+10 | 1685.96 | 15-SEP-12:09 | 16.17 | 14.19 |
October | 0.114461E+11 | 34598.07 | 18-OCT-08:62 | 21.67 | 11.19 | 0.141003E+10 | 1685.99 | 29-OCT-12:00 | 22.00 | 15.83 |
November | 0.721194E+10 | 22552.84 | 28-NOV-09:02 | 20.17 | 7.85 | 0.135886E+10 | 1685.85 | 10-NOV-13:20 | 20.17 | 7.85 |
December | 0.693378E+10 | 30272.90 | 05-DEC-09:02 | 24.33 | 12.02 | 0.138462E+10 | 1685.85 | 16-DEC-13:39 | 25.20 | 13.44 |
Annual Sum or Average | 0.105001E+12 | 0.163663E+11 | ||||||||
Minimum of Months | 0.533481E+10 | 8143.88 | 14.33 | 7.85 | 0.123129E+10 | 1685.85 | 14.33 | 7.85 | ||
Maximum of Months | 0.125260E+11 | 34721.98 | 24.33 | 17.27 | 0.141370E+10 | 1685.99 | 25.20 | 17.27 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.394557E+10 | 19804.85 | 15-JAN-18:01 | 16.67 | 11.87 | 0.698827E+09 | 842.94 | 20-JAN-13:20 | 18.33 | 15.04 |
February | 0.326637E+10 | 17934.53 | 05-FEB-18:10 | 12.83 | 9.79 | 0.629776E+09 | 842.91 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.344033E+10 | 8221.27 | 18-MAR-08:63 | 15.17 | 13.16 | 0.686164E+09 | 842.96 | 24-MAR-12:00 | 19.00 | 15.88 |
April | 0.474004E+10 | 16872.89 | 27-APR-08:62 | 17.33 | 15.22 | 0.680412E+09 | 842.98 | 30-APR-12:00 | 24.00 | 17.03 |
May | 0.485766E+10 | 21186.07 | 24-MAY-08:62 | 18.00 | 8.80 | 0.700803E+09 | 842.95 | 19-MAY-12:09 | 18.00 | 8.80 |
June | 0.563164E+10 | 18293.94 | 23-JUN-08:62 | 18.50 | 14.15 | 0.677371E+09 | 842.96 | 03-JUN-12:00 | 18.50 | 14.15 |
July | 0.689538E+10 | 17892.85 | 10-JUL-08:62 | 19.33 | 14.88 | 0.704887E+09 | 842.96 | 04-JUL-16:00 | 19.33 | 14.88 |
August | 0.702084E+10 | 18109.13 | 22-AUG-08:62 | 17.58 | 14.22 | 0.696198E+09 | 842.90 | 13-AUG-17:10 | 17.58 | 14.22 |
September | 0.631990E+10 | 18818.53 | 02-SEP-08:62 | 17.17 | 12.94 | 0.682166E+09 | 842.95 | 16-SEP-12:09 | 20.17 | 15.70 |
October | 0.664821E+10 | 20279.00 | 13-OCT-21:24 | 18.50 | 10.51 | 0.703401E+09 | 842.98 | 29-OCT-12:00 | 22.00 | 15.83 |
November | 0.448166E+10 | 18061.26 | 28-NOV-09:02 | 20.17 | 7.85 | 0.681617E+09 | 842.90 | 10-NOV-13:20 | 20.17 | 7.85 |
December | 0.420432E+10 | 17744.50 | 07-DEC-09:02 | 18.50 | 11.61 | 0.705114E+09 | 842.90 | 16-DEC-13:39 | 25.20 | 13.44 |
Annual Sum or Average | 0.614519E+11 | 0.824674E+10 | ||||||||
Minimum of Months | 0.326637E+10 | 8221.27 | 12.83 | 7.85 | 0.629776E+09 | 842.90 | 17.58 | 7.85 | ||
Maximum of Months | 0.702084E+10 | 21186.07 | 20.17 | 15.22 | 0.705114E+09 | 842.98 | 25.20 | 17.03 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.273847E+10 | 15754.85 | 21-JAN-08:62 | 13.17 | 13.07 | 0.411550E+09 | 842.90 | 14-JAN-13:20 | 13.17 | 13.07 |
February | 0.222472E+10 | 7224.92 | 16-FEB-08:63 | 14.17 | 12.90 | 0.373183E+09 | 842.90 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.241684E+10 | 7457.74 | 24-MAR-07:03 | 13.17 | 13.07 | 0.416203E+09 | 842.90 | 11-MAR-13:20 | 13.17 | 13.07 |
April | 0.321850E+10 | 16869.90 | 27-APR-07:03 | 16.17 | 14.82 | 0.408994E+09 | 842.95 | 29-APR-12:20 | 19.67 | 15.00 |
May | 0.329969E+10 | 17567.42 | 04-MAY-07:03 | 18.17 | 14.03 | 0.424823E+09 | 842.90 | 27-MAY-12:00 | 19.00 | 13.73 |
June | 0.397687E+10 | 18429.66 | 23-JUN-07:02 | 17.17 | 13.94 | 0.416304E+09 | 842.96 | 03-JUN-12:00 | 17.17 | 13.94 |
July | 0.487971E+10 | 17901.52 | 10-JUL-07:02 | 18.17 | 14.44 | 0.419746E+09 | 842.90 | 29-JUL-12:09 | 23.00 | 19.54 |
August | 0.517890E+10 | 18493.26 | 22-AUG-07:02 | 16.22 | 13.67 | 0.431348E+09 | 842.90 | 05-AUG-12:09 | 16.22 | 13.67 |
September | 0.451338E+10 | 18421.28 | 15-SEP-07:03 | 14.33 | 12.38 | 0.410372E+09 | 842.95 | 16-SEP-12:09 | 20.17 | 15.70 |
October | 0.478899E+10 | 21216.17 | 18-OCT-07:02 | 17.67 | 10.06 | 0.420014E+09 | 842.96 | 21-OCT-12:00 | 21.00 | 14.99 |
November | 0.307155E+10 | 16129.66 | 19-NOV-09:02 | 24.33 | 12.78 | 0.404657E+09 | 842.90 | 18-NOV-13:09 | 24.33 | 12.78 |
December | 0.293557E+10 | 8651.92 | 07-DEC-08:63 | 14.67 | 10.50 | 0.414479E+09 | 842.90 | 16-DEC-13:20 | 25.60 | 13.38 |
Annual Sum or Average | 0.432432E+11 | 0.495167E+10 | ||||||||
Minimum of Months | 0.222472E+10 | 7224.92 | 13.17 | 10.06 | 0.373183E+09 | 842.90 | 13.17 | 12.78 | ||
Maximum of Months | 0.517890E+10 | 21216.17 | 24.33 | 14.82 | 0.431348E+09 | 842.96 | 25.60 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.257913E+10 | 14861.77 | 21-JAN-08:62 | 13.17 | 13.07 | 0.409839E+09 | 842.90 | 14-JAN-13:09 | 13.17 | 13.07 |
February | 0.210669E+10 | 5894.99 | 16-FEB-08:63 | 14.17 | 12.90 | 0.371824E+09 | 842.90 | 18-FEB-13:00 | 19.00 | 13.20 |
March | 0.228269E+10 | 6747.72 | 24-MAR-07:03 | 13.17 | 13.07 | 0.413861E+09 | 842.90 | 11-MAR-13:09 | 13.17 | 13.07 |
April | 0.309614E+10 | 16849.74 | 27-APR-07:03 | 16.17 | 14.82 | 0.408774E+09 | 842.95 | 29-APR-12:20 | 19.67 | 15.00 |
May | 0.319332E+10 | 17214.16 | 04-MAY-07:03 | 18.17 | 14.03 | 0.424731E+09 | 842.90 | 27-MAY-12:20 | 19.00 | 13.73 |
June | 0.389868E+10 | 18435.08 | 23-JUN-07:02 | 17.17 | 13.94 | 0.416278E+09 | 842.96 | 03-JUN-12:00 | 17.17 | 13.94 |
July | 0.482894E+10 | 17886.28 | 10-JUL-07:02 | 18.17 | 14.44 | 0.419731E+09 | 842.90 | 29-JUL-12:09 | 23.00 | 19.54 |
August | 0.513107E+10 | 18501.78 | 22-AUG-07:02 | 16.22 | 13.67 | 0.431334E+09 | 842.90 | 05-AUG-12:09 | 16.22 | 13.67 |
September | 0.444785E+10 | 18079.59 | 27-SEP-07:02 | 16.00 | 14.12 | 0.410351E+09 | 842.95 | 16-SEP-12:09 | 16.00 | 14.12 |
October | 0.474044E+10 | 21270.00 | 18-OCT-07:02 | 17.67 | 10.06 | 0.419993E+09 | 842.96 | 21-OCT-12:00 | 21.00 | 14.99 |
November | 0.295218E+10 | 16074.54 | 19-NOV-09:02 | 24.33 | 12.78 | 0.404489E+09 | 842.90 | 18-NOV-13:09 | 24.33 | 12.78 |
December | 0.280045E+10 | 7918.97 | 07-DEC-08:63 | 14.67 | 10.50 | 0.413683E+09 | 842.90 | 16-DEC-13:09 | 25.80 | 13.34 |
Annual Sum or Average | 0.420576E+11 | 0.494489E+10 | ||||||||
Minimum of Months | 0.210669E+10 | 5894.99 | 13.17 | 10.06 | 0.371824E+09 | 842.90 | 13.17 | 12.78 | ||
Maximum of Months | 0.513107E+10 | 21270.00 | 24.33 | 14.82 | 0.431334E+09 | 842.96 | 25.80 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.232327E+10 | 12733.60 | 21-JAN-08:62 | 13.17 | 13.07 | 0.407417E+09 | 842.90 | 14-JAN-13:20 | 13.17 | 13.07 |
February | 0.189859E+10 | 4020.37 | 03-FEB-14:00 | 23.00 | 8.84 | 0.369092E+09 | 842.90 | 04-FEB-13:50 | 20.17 | 9.01 |
March | 0.205158E+10 | 4948.24 | 24-MAR-07:03 | 13.17 | 13.07 | 0.409519E+09 | 842.90 | 11-MAR-13:30 | 13.17 | 13.07 |
April | 0.284744E+10 | 14859.29 | 27-APR-07:03 | 16.17 | 14.82 | 0.408234E+09 | 842.94 | 29-APR-12:20 | 19.67 | 15.00 |
May | 0.294750E+10 | 15674.90 | 03-MAY-07:03 | 17.33 | 15.22 | 0.424461E+09 | 842.90 | 13-MAY-12:09 | 18.00 | 13.19 |
June | 0.367322E+10 | 18147.91 | 23-JUN-07:02 | 17.17 | 13.94 | 0.416198E+09 | 842.95 | 03-JUN-12:00 | 17.17 | 13.94 |
July | 0.461870E+10 | 17598.75 | 10-JUL-07:02 | 18.17 | 14.44 | 0.419671E+09 | 842.90 | 29-JUL-12:09 | 23.00 | 19.54 |
August | 0.491734E+10 | 18222.05 | 22-AUG-07:02 | 16.22 | 13.67 | 0.431273E+09 | 842.90 | 05-AUG-12:09 | 16.22 | 13.67 |
September | 0.423285E+10 | 17804.36 | 30-SEP-07:01 | 23.92 | 14.07 | 0.410281E+09 | 842.95 | 16-SEP-12:09 | 23.92 | 14.07 |
October | 0.452505E+10 | 20979.28 | 18-OCT-07:02 | 17.67 | 10.06 | 0.419907E+09 | 842.96 | 21-OCT-12:00 | 21.00 | 14.99 |
November | 0.271168E+10 | 15383.80 | 19-NOV-09:02 | 24.33 | 12.78 | 0.404047E+09 | 842.90 | 18-NOV-13:09 | 24.33 | 12.78 |
December | 0.255799E+10 | 6168.43 | 07-DEC-08:63 | 14.67 | 10.50 | 0.411870E+09 | 842.90 | 16-DEC-13:20 | 25.60 | 13.38 |
Annual Sum or Average | 0.393052E+11 | 0.493197E+10 | ||||||||
Minimum of Months | 0.189859E+10 | 4020.37 | 13.17 | 8.84 | 0.369092E+09 | 842.90 | 13.17 | 9.01 | ||
Maximum of Months | 0.491734E+10 | 20979.28 | 24.33 | 15.22 | 0.431273E+09 | 842.96 | 25.60 | 19.54 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.360861E+10 | 19495.78 | 21-JAN-09:02 | 14.33 | 13.47 | 0.138300E+10 | 2247.80 | 14-JAN-15:09 | 14.33 | 13.47 |
February | 0.302838E+10 | 6966.35 | 03-FEB-14:00 | 23.00 | 8.84 | 0.124199E+10 | 2247.80 | 11-FEB-15:00 | 18.00 | 13.88 |
March | 0.331851E+10 | 7349.31 | 23-MAR-14:10 | 22.83 | 17.30 | 0.137842E+10 | 2247.80 | 11-MAR-15:20 | 22.83 | 17.30 |
April | 0.442534E+10 | 29351.18 | 27-APR-08:62 | 17.33 | 15.22 | 0.140089E+10 | 2247.90 | 29-APR-14:09 | 19.93 | 14.56 |
May | 0.455729E+10 | 30560.56 | 04-MAY-08:62 | 19.17 | 14.74 | 0.145280E+10 | 2247.89 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.583871E+10 | 32059.43 | 23-JUN-08:62 | 18.50 | 14.15 | 0.142870E+10 | 2247.89 | 03-JUN-14:09 | 18.50 | 14.15 |
July | 0.758395E+10 | 31253.49 | 10-JUL-08:62 | 19.33 | 14.88 | 0.143779E+10 | 2247.80 | 29-JUL-14:09 | 24.00 | 19.89 |
August | 0.811003E+10 | 31709.93 | 22-AUG-08:62 | 17.58 | 14.22 | 0.147999E+10 | 2247.80 | 26-AUG-14:00 | 23.00 | 18.99 |
September | 0.688404E+10 | 31370.40 | 27-SEP-08:62 | 16.17 | 14.19 | 0.140905E+10 | 2247.96 | 02-SEP-14:09 | 16.17 | 14.19 |
October | 0.738015E+10 | 33244.99 | 18-OCT-08:62 | 21.67 | 11.19 | 0.143476E+10 | 2247.93 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.415366E+10 | 28284.57 | 19-NOV-10:02 | 26.00 | 14.09 | 0.137285E+10 | 2247.80 | 18-NOV-15:09 | 26.00 | 14.09 |
December | 0.401577E+10 | 24100.58 | 05-DEC-09:02 | 24.33 | 12.02 | 0.139945E+10 | 2247.80 | 16-DEC-15:00 | 21.00 | 13.55 |
Annual Sum or Average | 0.629044E+11 | 0.168197E+11 | ||||||||
Minimum of Months | 0.302838E+10 | 6966.35 | 14.33 | 8.84 | 0.124199E+10 | 2247.80 | 14.33 | 13.47 | ||
Maximum of Months | 0.811003E+10 | 33244.99 | 26.00 | 17.30 | 0.147999E+10 | 2247.96 | 26.00 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.173625E+10 | 9012.51 | 21-JAN-09:02 | 14.33 | 13.47 | 0.691242E+09 | 1123.87 | 14-JAN-15:20 | 14.33 | 13.47 |
February | 0.142988E+10 | 3554.60 | 03-FEB-14:00 | 23.00 | 8.84 | 0.620039E+09 | 1123.87 | 11-FEB-15:00 | 18.00 | 13.88 |
March | 0.155814E+10 | 3746.70 | 23-MAR-14:10 | 22.83 | 17.30 | 0.687251E+09 | 1123.87 | 11-MAR-15:30 | 22.83 | 17.30 |
April | 0.217157E+10 | 13722.23 | 27-APR-08:62 | 17.33 | 15.22 | 0.700447E+09 | 1123.92 | 29-APR-14:09 | 19.93 | 14.56 |
May | 0.224734E+10 | 15702.06 | 04-MAY-08:62 | 19.17 | 14.74 | 0.726429E+09 | 1123.91 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.294382E+10 | 16475.28 | 23-JUN-08:62 | 18.50 | 14.15 | 0.714332E+09 | 1123.91 | 03-JUN-14:09 | 18.50 | 14.15 |
July | 0.387222E+10 | 16065.81 | 10-JUL-08:62 | 19.33 | 14.88 | 0.718860E+09 | 1123.87 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.415030E+10 | 16312.74 | 22-AUG-08:62 | 17.58 | 14.22 | 0.739959E+09 | 1123.87 | 26-AUG-14:00 | 23.00 | 18.99 |
September | 0.350259E+10 | 15661.99 | 28-SEP-08:62 | 17.33 | 15.31 | 0.704511E+09 | 1123.94 | 02-SEP-14:09 | 17.33 | 15.31 |
October | 0.378061E+10 | 17092.05 | 18-OCT-08:62 | 21.67 | 11.19 | 0.717365E+09 | 1123.93 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.204159E+10 | 14530.69 | 19-NOV-10:02 | 26.00 | 14.09 | 0.686734E+09 | 1123.87 | 18-NOV-15:30 | 26.00 | 14.09 |
December | 0.195553E+10 | 10815.56 | 05-DEC-09:02 | 24.33 | 12.02 | 0.699669E+09 | 1123.87 | 16-DEC-15:00 | 21.00 | 13.55 |
Annual Sum or Average | 0.313899E+11 | 0.840684E+10 | ||||||||
Minimum of Months | 0.142988E+10 | 3554.60 | 14.33 | 8.84 | 0.620039E+09 | 1123.87 | 14.33 | 13.47 | ||
Maximum of Months | 0.415030E+10 | 17092.05 | 26.00 | 17.30 | 0.739959E+09 | 1123.94 | 26.00 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.166738E+10 | 8140.48 | 21-JAN-09:02 | 14.33 | 13.47 | 0.689125E+09 | 1123.87 | 14-JAN-15:30 | 14.33 | 13.47 |
February | 0.136462E+10 | 3455.10 | 03-FEB-14:00 | 23.00 | 8.84 | 0.616765E+09 | 1123.86 | 11-FEB-15:00 | 18.00 | 13.88 |
March | 0.149146E+10 | 3650.49 | 23-MAR-14:10 | 22.83 | 17.30 | 0.683204E+09 | 1123.87 | 11-MAR-15:30 | 22.83 | 17.30 |
April | 0.209311E+10 | 12596.60 | 27-APR-08:62 | 17.33 | 15.22 | 0.699936E+09 | 1123.91 | 29-APR-14:09 | 19.93 | 14.56 |
May | 0.216835E+10 | 15041.06 | 04-MAY-08:62 | 19.17 | 14.74 | 0.726077E+09 | 1123.91 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.286863E+10 | 16347.78 | 23-JUN-08:62 | 18.50 | 14.15 | 0.714278E+09 | 1123.91 | 03-JUN-14:09 | 18.50 | 14.15 |
July | 0.380500E+10 | 15932.93 | 10-JUL-08:62 | 19.33 | 14.88 | 0.718832E+09 | 1123.87 | 15-JUL-14:00 | 22.00 | 18.09 |
August | 0.408204E+10 | 16187.25 | 22-AUG-08:62 | 17.58 | 14.22 | 0.739934E+09 | 1123.87 | 26-AUG-14:00 | 23.00 | 18.99 |
September | 0.343257E+10 | 15536.48 | 28-SEP-08:62 | 17.33 | 15.31 | 0.704466E+09 | 1123.94 | 02-SEP-14:09 | 17.33 | 15.31 |
October | 0.370951E+10 | 16981.89 | 18-OCT-08:62 | 21.67 | 11.19 | 0.717333E+09 | 1123.93 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.196442E+10 | 14436.28 | 19-NOV-10:02 | 26.00 | 14.09 | 0.685953E+09 | 1123.87 | 18-NOV-15:20 | 26.00 | 14.09 |
December | 0.187975E+10 | 9163.07 | 05-DEC-09:02 | 24.33 | 12.02 | 0.697669E+09 | 1123.87 | 16-DEC-15:00 | 21.00 | 13.55 |
Annual Sum or Average | 0.305268E+11 | 0.839357E+10 | ||||||||
Minimum of Months | 0.136462E+10 | 3455.10 | 14.33 | 8.84 | 0.616765E+09 | 1123.86 | 14.33 | 13.47 | ||
Maximum of Months | 0.408204E+10 | 16981.89 | 26.00 | 17.30 | 0.739934E+09 | 1123.94 | 26.00 | 18.99 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.149457E+10 | 4883.17 | 21-JAN-09:02 | 14.33 | 13.47 | 0.683244E+09 | 1123.87 | 14-JAN-15:30 | 14.33 | 13.47 |
February | 0.120096E+10 | 3189.97 | 03-FEB-14:00 | 23.00 | 8.84 | 0.608207E+09 | 1123.85 | 18-FEB-15:20 | 16.67 | 13.33 |
March | 0.133356E+10 | 3424.72 | 23-MAR-14:10 | 22.83 | 17.30 | 0.673491E+09 | 1123.87 | 11-MAR-15:09 | 22.83 | 17.30 |
April | 0.189844E+10 | 8851.17 | 27-APR-08:62 | 17.33 | 15.22 | 0.698159E+09 | 1123.91 | 29-APR-14:20 | 19.87 | 14.55 |
May | 0.195895E+10 | 11581.16 | 04-MAY-08:62 | 19.17 | 14.74 | 0.724573E+09 | 1123.90 | 06-MAY-14:00 | 20.00 | 15.11 |
June | 0.266771E+10 | 15192.58 | 21-JUN-08:62 | 19.50 | 15.48 | 0.714065E+09 | 1123.90 | 03-JUN-14:09 | 19.50 | 15.48 |
July | 0.365537E+10 | 15629.27 | 10-JUL-08:62 | 19.33 | 14.88 | 0.718752E+09 | 1123.87 | 29-JUL-14:09 | 24.00 | 19.89 |
August | 0.392866E+10 | 14524.33 | 30-AUG-08:62 | 19.50 | 16.07 | 0.739861E+09 | 1123.87 | 26-AUG-14:00 | 19.50 | 16.07 |
September | 0.325228E+10 | 15251.43 | 28-SEP-08:62 | 17.33 | 15.31 | 0.704283E+09 | 1123.94 | 02-SEP-14:09 | 17.33 | 15.31 |
October | 0.352193E+10 | 16080.63 | 18-OCT-08:62 | 21.67 | 11.19 | 0.717195E+09 | 1123.92 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.175743E+10 | 14238.37 | 19-NOV-10:02 | 26.00 | 14.09 | 0.683219E+09 | 1123.87 | 18-NOV-15:20 | 26.00 | 14.09 |
December | 0.168463E+10 | 4032.39 | 05-DEC-09:02 | 24.33 | 12.02 | 0.691994E+09 | 1123.87 | 16-DEC-15:00 | 21.00 | 13.55 |
Annual Sum or Average | 0.283545E+11 | 0.835704E+10 | ||||||||
Minimum of Months | 0.120096E+10 | 3189.97 | 14.33 | 8.84 | 0.608207E+09 | 1123.85 | 14.33 | 13.33 | ||
Maximum of Months | 0.392866E+10 | 16080.63 | 26.00 | 17.30 | 0.739861E+09 | 1123.94 | 26.00 | 19.89 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.121508E+10 | 3825.80 | 18-JAN-13:40 | 25.07 | 14.79 | 0.674333E+09 | 1123.87 | 14-JAN-15:00 | 25.07 | 14.79 |
February | 0.871517E+09 | 2962.71 | 01-FEB-13:10 | 23.17 | 14.41 | 0.594678E+09 | 1123.86 | 18-FEB-15:30 | 16.50 | 13.26 |
March | 0.104034E+10 | 3416.38 | 23-MAR-14:10 | 22.83 | 17.30 | 0.661337E+09 | 1123.87 | 11-MAR-15:00 | 22.83 | 17.30 |
April | 0.177968E+10 | 4888.35 | 26-APR-13:00 | 27.00 | 17.13 | 0.694307E+09 | 1123.90 | 29-APR-14:09 | 19.93 | 14.56 |
May | 0.176225E+10 | 5460.23 | 04-MAY-08:62 | 19.17 | 14.74 | 0.720812E+09 | 1123.86 | 13-MAY-14:09 | 17.67 | 12.74 |
June | 0.256457E+10 | 15346.13 | 25-JUN-09:02 | 22.17 | 16.55 | 0.713292E+09 | 1123.90 | 03-JUN-14:09 | 22.17 | 16.55 |
July | 0.386573E+10 | 16051.36 | 04-JUL-09:02 | 22.00 | 15.93 | 0.718710E+09 | 1123.87 | 29-JUL-14:09 | 24.00 | 19.89 |
August | 0.413066E+10 | 14173.18 | 05-AUG-08:62 | 19.50 | 17.18 | 0.739799E+09 | 1123.87 | 26-AUG-14:00 | 23.00 | 18.99 |
September | 0.317998E+10 | 16367.13 | 30-SEP-08:61 | 25.38 | 14.89 | 0.703675E+09 | 1123.93 | 02-SEP-14:09 | 25.38 | 14.89 |
October | 0.341134E+10 | 15101.49 | 17-OCT-08:62 | 26.50 | 12.89 | 0.716794E+09 | 1123.90 | 21-OCT-14:00 | 20.00 | 15.11 |
November | 0.144131E+10 | 14799.91 | 19-NOV-10:02 | 26.00 | 14.09 | 0.677042E+09 | 1123.87 | 18-NOV-15:50 | 26.00 | 14.09 |
December | 0.135865E+10 | 3923.17 | 19-DEC-13:10 | 25.50 | 11.30 | 0.681433E+09 | 1123.87 | 16-DEC-15:00 | 25.50 | 11.30 |
Annual Sum or Average | 0.266211E+11 | 0.829621E+10 | ||||||||
Minimum of Months | 0.871517E+09 | 2962.71 | 19.17 | 11.30 | 0.594678E+09 | 1123.86 | 16.50 | 11.30 | ||
Maximum of Months | 0.413066E+10 | 16367.13 | 27.00 | 17.30 | 0.739799E+09 | 1123.93 | 26.00 | 19.89 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190577E+09 | 2086.05 | 12-JAN-08:25 | 7.50 |
February | 0.174542E+09 | 2053.71 | 11-FEB-08:13 | 9.97 |
March | 0.202494E+09 | 28038.85 | 30-MAR-08:61 | 9.50 |
April | 0.186932E+09 | 2020.50 | 26-APR-08:05 | 22.17 |
May | 0.182918E+09 | 1977.97 | 09-MAY-07:15 | 13.33 |
June | 0.173172E+09 | 2000.98 | 30-JUN-07:02 | 18.33 |
July | 0.175469E+09 | 2668.41 | 02-JUL-07:07 | 18.17 |
August | 0.186857E+09 | 2464.31 | 14-AUG-08:05 | 23.33 |
September | 0.172120E+09 | 5619.77 | 29-SEP-08:05 | 29.67 |
October | 0.182033E+09 | 4136.52 | 17-OCT-08:05 | 26.50 |
November | 0.175115E+09 | 1980.13 | 10-NOV-08:62 | 16.33 |
December | 0.194911E+09 | 3095.34 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.219714E+10 | |||
Minimum of Months | 0.172120E+09 | 1977.97 | 7.50 | |
Maximum of Months | 0.202494E+09 | 28038.85 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.100221E+09 | 1155.57 | 24-JAN-09:05 | 21.33 |
February | 92297230.84 | 1311.06 | 01-FEB-09:05 | 22.33 |
March | 0.107389E+09 | 1133.25 | 28-MAR-08:00 | 9.00 |
April | 96375728.50 | 1273.96 | 26-APR-08:05 | 22.17 |
May | 95877254.82 | 1096.36 | 06-MAY-08:00 | 14.00 |
June | 97376617.40 | 1272.78 | 25-JUN-07:10 | 18.17 |
July | 98515362.74 | 1616.81 | 02-JUL-07:07 | 18.17 |
August | 0.103630E+09 | 1467.87 | 20-AUG-07:07 | 19.03 |
September | 95356144.85 | 2756.43 | 29-SEP-08:05 | 29.67 |
October | 96497257.84 | 2342.84 | 16-OCT-08:06 | 28.50 |
November | 91590400.78 | 1085.95 | 10-NOV-08:15 | 16.67 |
December | 0.103232E+09 | 1402.78 | 04-DEC-09:05 | 22.50 |
Annual Sum or Average | 0.117836E+10 | |||
Minimum of Months | 91590400.78 | 1085.95 | 9.00 | |
Maximum of Months | 0.107389E+09 | 2756.43 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105434E+09 | 1078.77 | 31-JAN-08:00 | 13.00 |
February | 95130051.97 | 1112.76 | 12-FEB-09:00 | 15.00 |
March | 0.106050E+09 | 1459.43 | 30-MAR-07:07 | 7.33 |
April | 0.103061E+09 | 1087.32 | 05-APR-07:00 | 13.00 |
May | 0.105255E+09 | 1090.30 | 09-MAY-07:00 | 13.00 |
June | 0.103083E+09 | 1079.08 | 12-JUN-07:00 | 14.00 |
July | 0.111141E+09 | 1075.59 | 11-JUL-07:00 | 17.00 |
August | 0.112888E+09 | 1101.88 | 13-AUG-08:06 | 22.33 |
September | 0.110479E+09 | 1801.39 | 29-SEP-19:03 | 28.33 |
October | 0.116949E+09 | 2634.84 | 15-OCT-08:06 | 29.67 |
November | 0.102404E+09 | 1757.29 | 19-NOV-09:05 | 24.33 |
December | 0.104842E+09 | 1083.94 | 08-DEC-08:00 | 12.20 |
Annual Sum or Average | 0.127672E+10 | |||
Minimum of Months | 95130051.97 | 1075.59 | 7.33 | |
Maximum of Months | 0.116949E+09 | 2634.84 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.106493E+09 | 1080.28 | 31-JAN-08:00 | 13.00 |
February | 95366901.76 | 1115.74 | 12-FEB-09:00 | 15.00 |
March | 0.106887E+09 | 1084.64 | 13-MAR-07:00 | 12.00 |
April | 0.103488E+09 | 1088.66 | 05-APR-07:00 | 13.00 |
May | 0.105495E+09 | 1091.72 | 09-MAY-07:00 | 13.00 |
June | 0.103344E+09 | 1079.95 | 12-JUN-07:00 | 14.00 |
July | 0.111474E+09 | 1076.82 | 11-JUL-07:00 | 17.00 |
August | 0.113154E+09 | 1083.18 | 13-AUG-08:06 | 22.33 |
September | 0.110694E+09 | 1806.89 | 29-SEP-19:03 | 28.33 |
October | 0.117188E+09 | 2640.49 | 15-OCT-08:06 | 29.67 |
November | 0.102769E+09 | 1781.46 | 19-NOV-09:05 | 24.33 |
December | 0.105025E+09 | 1085.11 | 08-DEC-08:00 | 12.20 |
Annual Sum or Average | 0.128138E+10 | |||
Minimum of Months | 95366901.76 | 1076.82 | 12.00 | |
Maximum of Months | 0.117188E+09 | 2640.49 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.110383E+09 | 2111.83 | 03-JAN-08:65 | 7.67 |
February | 94946803.73 | 1109.14 | 12-FEB-09:00 | 15.00 |
March | 0.108178E+09 | 3167.04 | 30-MAR-07:03 | 7.33 |
April | 0.103511E+09 | 1082.65 | 05-APR-07:00 | 13.00 |
May | 0.104892E+09 | 1084.30 | 09-MAY-07:00 | 13.00 |
June | 0.102763E+09 | 1073.88 | 12-JUN-07:00 | 14.00 |
July | 0.110917E+09 | 1259.82 | 23-JUL-08:05 | 23.33 |
August | 0.112371E+09 | 1074.36 | 21-AUG-07:00 | 17.00 |
September | 0.110358E+09 | 1812.07 | 29-SEP-19:03 | 28.33 |
October | 0.116426E+09 | 2033.13 | 15-OCT-16:02 | 29.50 |
November | 0.102318E+09 | 1777.27 | 19-NOV-09:05 | 24.33 |
December | 0.104768E+09 | 1079.06 | 08-DEC-08:00 | 12.20 |
Annual Sum or Average | 0.128183E+10 | |||
Minimum of Months | 94946803.73 | 1073.88 | 7.33 | |
Maximum of Months | 0.116426E+09 | 3167.04 | 29.50 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.202550E+09 | 21868.00 | 02-JAN-09:02 | 13.00 |
February | 0.167730E+09 | 1936.27 | 11-FEB-08:13 | 9.97 |
March | 0.197515E+09 | 32341.50 | 30-MAR-08:61 | 9.50 |
April | 0.192826E+09 | 1932.79 | 30-APR-09:07 | 22.50 |
May | 0.189481E+09 | 1878.87 | 09-MAY-07:15 | 13.33 |
June | 0.189609E+09 | 1964.73 | 18-JUN-09:05 | 22.00 |
July | 0.206441E+09 | 2697.19 | 23-JUL-09:07 | 25.00 |
August | 0.212863E+09 | 2725.41 | 13-AUG-09:06 | 24.00 |
September | 0.195862E+09 | 5401.50 | 29-SEP-08:05 | 29.67 |
October | 0.213124E+09 | 6460.99 | 15-OCT-09:06 | 32.67 |
November | 0.182220E+09 | 3282.59 | 19-NOV-10:06 | 26.00 |
December | 0.187761E+09 | 2830.26 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.233798E+10 | |||
Minimum of Months | 0.167730E+09 | 1878.87 | 9.50 | |
Maximum of Months | 0.213124E+09 | 32341.50 | 32.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.112950E+09 | 12289.89 | 02-JAN-09:02 | 13.00 |
February | 91908099.00 | 1042.16 | 11-FEB-08:13 | 9.97 |
March | 0.111367E+09 | 17803.23 | 30-MAR-08:61 | 9.50 |
April | 0.107190E+09 | 1012.55 | 22-APR-08:00 | 13.00 |
May | 0.103693E+09 | 1016.48 | 06-MAY-08:00 | 14.00 |
June | 0.104135E+09 | 1101.97 | 18-JUN-09:05 | 22.00 |
July | 0.113145E+09 | 1098.58 | 19-JUL-08:05 | 22.67 |
August | 0.116783E+09 | 1418.34 | 13-AUG-09:06 | 24.00 |
September | 0.106584E+09 | 2713.62 | 29-SEP-08:05 | 29.67 |
October | 0.116027E+09 | 2046.18 | 17-OCT-08:05 | 26.50 |
November | 99624492.97 | 1498.75 | 19-NOV-10:06 | 26.00 |
December | 0.103487E+09 | 1455.75 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.128689E+10 | |||
Minimum of Months | 91908099.00 | 1012.55 | 9.50 | |
Maximum of Months | 0.116783E+09 | 17803.23 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.114390E+09 | 13913.82 | 02-JAN-09:02 | 13.00 |
February | 92006742.89 | 1037.77 | 11-FEB-08:13 | 9.97 |
March | 0.114307E+09 | 20575.63 | 30-MAR-08:61 | 9.50 |
April | 0.107463E+09 | 1009.24 | 22-APR-08:00 | 13.00 |
May | 0.103279E+09 | 1012.54 | 06-MAY-08:00 | 14.00 |
June | 0.103730E+09 | 1102.82 | 18-JUN-09:05 | 22.00 |
July | 0.112628E+09 | 1066.44 | 19-JUL-08:05 | 22.67 |
August | 0.116307E+09 | 1386.29 | 13-AUG-09:06 | 24.00 |
September | 0.106144E+09 | 2681.72 | 29-SEP-08:05 | 29.67 |
October | 0.115506E+09 | 2256.89 | 14-OCT-08:04 | 27.67 |
November | 99354692.09 | 1004.48 | 02-NOV-07:15 | 12.67 |
December | 0.103915E+09 | 1396.26 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.128903E+10 | |||
Minimum of Months | 92006742.89 | 1004.48 | 9.50 | |
Maximum of Months | 0.116307E+09 | 20575.63 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.124457E+09 | 19249.12 | 02-JAN-09:02 | 13.00 |
February | 96158735.02 | 3699.81 | 28-FEB-09:02 | 12.67 |
March | 0.127769E+09 | 23225.35 | 30-MAR-08:61 | 9.50 |
April | 0.109601E+09 | 5507.93 | 01-APR-08:62 | 15.67 |
May | 0.102721E+09 | 1009.49 | 06-MAY-08:00 | 14.00 |
June | 0.103215E+09 | 1013.80 | 25-JUN-09:04 | 22.17 |
July | 0.111846E+09 | 1018.22 | 20-JUL-07:02 | 17.17 |
August | 0.115378E+09 | 1305.74 | 13-AUG-09:06 | 24.00 |
September | 0.105667E+09 | 2582.91 | 29-SEP-08:05 | 29.67 |
October | 0.114788E+09 | 2290.03 | 14-OCT-08:04 | 27.67 |
November | 0.100020E+09 | 1896.70 | 19-NOV-10:04 | 26.00 |
December | 0.107248E+09 | 1225.20 | 05-DEC-09:04 | 24.33 |
Annual Sum or Average | 0.131887E+10 | |||
Minimum of Months | 96158735.02 | 1009.49 | 9.50 | |
Maximum of Months | 0.127769E+09 | 23225.35 | 29.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.174374E+09 | 25619.52 | 02-JAN-09:02 | 13.00 |
February | 0.144432E+09 | 18506.37 | 27-FEB-09:02 | 12.00 |
March | 0.215173E+09 | 25355.95 | 30-MAR-08:61 | 9.50 |
April | 0.118182E+09 | 16557.18 | 01-APR-08:62 | 15.67 |
May | 0.107442E+09 | 1094.97 | 09-MAY-07:15 | 13.33 |
June | 0.109144E+09 | 1167.19 | 25-JUN-09:04 | 22.17 |
July | 0.118163E+09 | 1341.66 | 30-JUL-09:05 | 23.17 |
August | 0.120314E+09 | 1428.08 | 13-AUG-09:06 | 24.00 |
September | 0.112441E+09 | 1909.13 | 30-SEP-08:04 | 25.38 |
October | 0.122123E+09 | 2612.03 | 16-OCT-08:04 | 28.50 |
November | 0.108609E+09 | 2083.95 | 19-NOV-10:04 | 26.00 |
December | 0.130592E+09 | 5280.78 | 13-DEC-09:05 | 11.33 |
Annual Sum or Average | 0.158099E+10 | |||
Minimum of Months | 0.107442E+09 | 1094.97 | 9.50 | |
Maximum of Months | 0.215173E+09 | 25619.52 | 28.50 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12641155.59 | 0.223416E+10 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1230945.25 | 0.233575E+10 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 250301.10 | 0.253315E+10 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11760570.22 | 0.154196E+10 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 150813.44 | 0.165624E+10 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1406339.08 | 0.954884E+09 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 76448975.28 | 0.503622E+09 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 87197177.20 | 0.545672E+09 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132871E+09 | 0.880363E+09 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260454E+09 | 0.100428E+10 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12400570.18 | 0.206426E+10 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7888744.13 | 0.220459E+10 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.604701E+09 | 0.184589E+11 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 150813.44 | 0.503622E+09 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.260454E+09 | 0.253315E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6812722.60 | 0.108050E+10 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 644321.30 | 0.112434E+10 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.38 | 0.122723E+10 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6283346.33 | 0.734146E+09 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81155.10 | 0.771958E+09 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 739488.01 | 0.458664E+09 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 40731671.77 | 0.232955E+09 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 46606161.46 | 0.232024E+09 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 71370198.12 | 0.424485E+09 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138226E+09 | 0.435983E+09 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6642593.96 | 0.977127E+09 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4206358.43 | 0.105529E+10 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322477E+09 | 0.875470E+10 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 81155.10 | 0.232024E+09 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.138226E+09 | 0.122723E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6812735.13 | 0.109510E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644321.21 | 0.115034E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.38 | 0.125128E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6283686.40 | 0.760780E+09 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81159.94 | 0.803479E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739487.82 | 0.487847E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40668056.14 | 0.264855E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46606263.67 | 0.262806E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71488309.31 | 0.445069E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136411E+09 | 0.461516E+09 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6640130.82 | 0.100523E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209822.47 | 0.107982E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320718E+09 | 0.906812E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81159.94 | 0.262806E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136411E+09 | 0.125128E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6812734.89 | 0.108588E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644321.21 | 0.114155E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.38 | 0.123955E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6283757.06 | 0.758408E+09 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81158.37 | 0.801567E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739487.76 | 0.487041E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40668055.77 | 0.264441E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46606367.34 | 0.262294E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71488362.22 | 0.444422E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136412E+09 | 0.460577E+09 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6641100.47 | 0.100241E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209822.45 | 0.107400E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320720E+09 | 0.902213E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81158.37 | 0.262294E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136412E+09 | 0.123955E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6812735.12 | 0.107453E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644321.21 | 0.112714E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.38 | 0.122020E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6283937.36 | 0.754500E+09 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81160.28 | 0.798229E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739487.49 | 0.485395E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40668055.88 | 0.262921E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46606467.12 | 0.260362E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71488644.22 | 0.442848E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136443E+09 | 0.457965E+09 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6642662.33 | 0.997963E+09 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4209822.41 | 0.106410E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320753E+09 | 0.894615E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81160.28 | 0.260362E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136443E+09 | 0.122020E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 12240845.50 | 0.195456E+10 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1164430.87 | 0.204559E+10 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 239926.41 | 0.220435E+10 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11327809.64 | 0.138766E+10 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 146159.31 | 0.147692E+10 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 1335608.61 | 0.897229E+09 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 73257000.30 | 0.491557E+09 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 84000631.17 | 0.493619E+09 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128538E+09 | 0.815619E+09 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245837E+09 | 0.863690E+09 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 11803571.85 | 0.183559E+10 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7588954.98 | 0.193997E+10 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.577480E+09 | 0.164063E+11 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 146159.31 | 0.491557E+09 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.245837E+09 | 0.220435E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6803252.44 | 0.106118E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644321.21 | 0.110598E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.38 | 0.119006E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6284445.42 | 0.753362E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81173.06 | 0.799499E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739486.43 | 0.487169E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40627487.51 | 0.264399E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46603995.49 | 0.262003E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71364996.37 | 0.443787E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136297E+09 | 0.461990E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6559305.47 | 0.996851E+09 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4208907.38 | 0.105154E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320347E+09 | 0.887782E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81173.06 | 0.262003E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136297E+09 | 0.119006E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6808950.36 | 0.105520E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 644321.23 | 0.109664E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.39 | 0.117961E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6284493.32 | 0.751296E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81172.55 | 0.797604E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739486.35 | 0.486386E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40627617.71 | 0.263793E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46603828.02 | 0.261285E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71368487.76 | 0.443100E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136329E+09 | 0.460971E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6569215.44 | 0.993825E+09 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4208636.37 | 0.104523E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320398E+09 | 0.883494E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81172.55 | 0.261285E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136329E+09 | 0.117961E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6828762.96 | 0.103789E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 643812.45 | 0.107138E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 133021.56 | 0.115325E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6284675.21 | 0.744306E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81176.40 | 0.790389E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 739486.24 | 0.483537E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 40627962.79 | 0.261826E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 46603476.82 | 0.258837E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 71381209.88 | 0.440648E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136422E+09 | 0.457203E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6603468.80 | 0.983204E+09 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4208063.23 | 0.102674E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.320557E+09 | 0.870920E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 81176.40 | 0.258837E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136422E+09 | 0.115325E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7328148.93 | 0.131690E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 711083.17 | 0.136447E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 143388.67 | 0.148708E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6717908.08 | 0.957582E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85743.83 | 0.104447E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 810180.88 | 0.625972E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 43622619.35 | 0.365878E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 49794682.90 | 0.398683E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 75674596.63 | 0.559251E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147640E+09 | 0.666937E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 7096692.81 | 0.126343E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4529743.85 | 0.131486E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344155E+09 | 0.113655E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 85743.83 | 0.365878E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147640E+09 | 0.148708E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 629.34 | 13-JAN-14:00 | 4333.93 | 06-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 539.79 | 01-FEB-12:10 | 3936.27 | 25-FEB-13:00 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.97 | 11-MAR-14:00 | 4145.20 | 29-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 937.47 | 26-APR-13:00 | 3900.27 | 17-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 03-MAY-13:00 | 3435.28 | 12-MAY-17:00 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 288.16 | 29-JUN-11:10 | 2195.42 | 06-JUN-17:00 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1256.33 | 31-JUL-13:00 | 1534.31 | 09-JUL-17:00 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1237.17 | 17-AUG-14:00 | 1841.29 | 22-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3541.82 | 29-SEP-13:00 | 2110.57 | 27-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3895.58 | 16-OCT-11:10 | 2235.67 | 23-OCT-15:00 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 938.06 | 19-NOV-13:00 | 3519.25 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 633.71 | 19-DEC-13:00 | 3814.09 | 24-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 31.45 | 1534.31 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3895.58 | 4333.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2435.56 | 06-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 2203.70 | 25-FEB-13:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2287.93 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.53 | 26-APR-13:00 | 2088.36 | 17-APR-17:00 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 03-MAY-13:00 | 1877.00 | 12-MAY-17:00 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1171.98 | 06-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 822.35 | 09-JUL-17:00 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.95 | 22-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1146.13 | 24-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1183.15 | 23-OCT-15:00 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1971.77 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 2190.51 | 24-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 822.35 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2435.56 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2407.04 | 06-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 2213.48 | 25-FEB-13:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2279.88 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.53 | 26-APR-13:00 | 2060.08 | 17-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 03-MAY-13:00 | 1863.23 | 12-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1190.76 | 11-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 1049.42 | 09-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.95 | 22-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1252.66 | 24-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1277.09 | 22-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1856.61 | 25-NOV-16:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 2069.85 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 990.95 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2407.04 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2390.77 | 06-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 2197.61 | 25-FEB-13:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2277.16 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.53 | 26-APR-13:00 | 2048.70 | 17-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 03-MAY-13:00 | 1858.15 | 12-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1183.02 | 11-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 1045.33 | 09-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.95 | 22-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1247.32 | 24-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1271.63 | 22-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1854.76 | 25-NOV-16:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 2061.21 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 990.95 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2390.77 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2359.52 | 06-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 2158.75 | 25-FEB-13:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2277.16 | 29-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.53 | 26-APR-13:00 | 2027.59 | 17-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 03-MAY-13:00 | 1842.34 | 12-MAY-17:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1171.99 | 06-JUN-17:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 1032.06 | 09-JUL-17:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.95 | 22-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1234.06 | 24-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1258.26 | 22-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1843.59 | 25-NOV-16:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 2039.97 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.93 | 990.95 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2359.52 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 614.42 | 13-JAN-14:00 | 4081.17 | 06-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 522.16 | 01-FEB-12:10 | 3750.60 | 25-FEB-13:00 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.76 | 11-MAR-14:00 | 4090.46 | 29-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 908.56 | 26-APR-13:00 | 3549.32 | 17-APR-17:00 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.51 | 04-MAY-12:00 | 3216.02 | 12-MAY-17:00 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 278.13 | 29-JUN-11:10 | 2112.74 | 06-JUN-17:00 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1209.02 | 31-JUL-13:00 | 1776.83 | 09-JUL-17:00 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1199.06 | 17-AUG-14:00 | 1784.55 | 22-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3432.72 | 29-SEP-13:00 | 2125.98 | 24-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3733.32 | 16-OCT-11:10 | 2170.45 | 22-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 909.16 | 19-NOV-13:00 | 3280.93 | 25-NOV-16:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 616.42 | 19-DEC-13:00 | 3540.21 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 30.51 | 1776.83 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3733.32 | 4090.46 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2275.88 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 2070.63 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2277.16 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.51 | 26-APR-13:00 | 1964.85 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 04-MAY-12:00 | 1784.10 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1171.98 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 983.30 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.93 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1182.81 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1206.77 | 22-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1823.30 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 1976.23 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 983.30 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2277.16 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2263.79 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 2049.39 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2277.16 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.51 | 26-APR-13:00 | 1954.81 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 04-MAY-12:00 | 1774.40 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1171.98 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 978.72 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.93 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1177.91 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1201.49 | 22-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1812.36 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 1966.15 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 978.72 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2277.16 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 341.53 | 13-JAN-14:00 | 2234.92 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 289.87 | 01-FEB-12:10 | 1995.21 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.07 | 11-MAR-14:00 | 2277.16 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.51 | 26-APR-13:00 | 1925.87 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 04-MAY-12:00 | 1746.25 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 154.35 | 29-JUN-11:10 | 1171.99 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 670.67 | 31-JUL-13:00 | 967.08 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 665.82 | 17-AUG-14:00 | 990.94 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1906.14 | 29-SEP-13:00 | 1165.06 | 24-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 16-OCT-11:10 | 1187.67 | 22-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 504.84 | 19-NOV-13:00 | 1782.98 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 342.47 | 19-DEC-13:00 | 1937.36 | 21-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.94 | 967.08 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2069.70 | 2277.16 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 356.45 | 13-JAN-14:00 | 2250.61 | 06-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 307.50 | 01-FEB-12:10 | 2144.54 | 25-FEB-13:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 18.27 | 11-MAR-14:00 | 2331.90 | 29-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 533.38 | 26-APR-13:00 | 2076.89 | 17-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 03-MAY-13:00 | 1822.14 | 12-MAY-17:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 164.38 | 29-JUN-11:10 | 1254.66 | 06-JUN-17:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 717.97 | 31-JUL-13:00 | 1029.05 | 09-JUL-17:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 703.92 | 17-AUG-14:00 | 1047.65 | 22-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2015.23 | 29-SEP-13:00 | 1195.41 | 27-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2231.96 | 16-OCT-11:10 | 1283.58 | 23-OCT-15:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 533.74 | 19-NOV-13:00 | 1832.67 | 25-NOV-16:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 359.76 | 19-DEC-13:00 | 1913.68 | 02-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 17.88 | 1029.05 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2231.96 | 2331.90 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22484.10 | 21-JAN-09:02 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 484.40 |
February | 14309.85 | 01-FEB-09:02 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 82.00 |
March | 8143.88 | 23-MAR-14:00 | 2700.03 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.15 |
April | 31220.57 | 27-APR-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 321.41 |
May | 34721.98 | 24-MAY-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.39 |
June | 33968.01 | 23-JUN-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 298.54 |
July | 33383.78 | 10-JUL-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 254.36 |
August | 33632.04 | 22-AUG-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.32 |
September | 33251.23 | 27-SEP-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 326.44 |
October | 34598.07 | 18-OCT-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 132.57 |
November | 22552.84 | 28-NOV-09:02 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 260.51 |
December | 30272.90 | 05-DEC-09:02 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8143.88 | 1350.01 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 34721.98 | 2700.03 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 10.14 | 484.40 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19804.85 | 15-JAN-18:01 | 20249.61 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.33 |
February | 17934.53 | 05-FEB-18:10 | 4049.92 | 6468.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.80 |
March | 8221.27 | 18-MAR-08:63 | 506.24 | 5106.68 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.47 |
April | 16872.89 | 27-APR-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.88 |
May | 21186.07 | 24-MAY-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.39 |
June | 18293.94 | 23-JUN-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.53 |
July | 17892.85 | 10-JUL-08:62 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.07 |
August | 18109.13 | 22-AUG-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.63 |
September | 18818.53 | 02-SEP-08:62 | 674.99 | 6808.91 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.89 |
October | 20279.00 | 13-OCT-21:24 | 9112.33 | 29108.10 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 |
November | 18061.26 | 28-NOV-09:02 | 674.99 | 6808.91 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.02 |
December | 17744.50 | 07-DEC-09:02 | 674.99 | 6808.91 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 142.46 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 8221.27 | 506.24 | 5106.68 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.13 | |
Maximum of Months | 21186.07 | 20249.61 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 197.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 15754.85 | 21-JAN-08:62 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.69 |
February | 7224.92 | 16-FEB-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.78 |
March | 7457.74 | 24-MAR-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.23 |
April | 16869.90 | 27-APR-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.99 |
May | 17567.42 | 04-MAY-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.59 |
June | 18429.66 | 23-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.19 |
July | 17901.52 | 10-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 159.72 |
August | 18493.26 | 22-AUG-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 194.31 |
September | 18421.28 | 15-SEP-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 210.41 |
October | 21216.17 | 18-OCT-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.20 |
November | 16129.66 | 19-NOV-09:02 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 0.00 |
December | 8651.92 | 07-DEC-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7224.92 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21216.17 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 2.13 | 277.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 14861.77 | 21-JAN-08:62 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.56 |
February | 5894.99 | 16-FEB-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.43 |
March | 6747.72 | 24-MAR-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 268.04 |
April | 16849.74 | 27-APR-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.64 |
May | 17214.16 | 04-MAY-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.98 |
June | 18435.08 | 23-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 178.15 |
July | 17886.28 | 10-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.22 |
August | 18501.78 | 22-AUG-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.36 |
September | 18079.59 | 27-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 201.73 |
October | 21270.00 | 18-OCT-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 165.07 |
November | 16074.54 | 19-NOV-09:02 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 0.00 |
December | 7918.97 | 07-DEC-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.54 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5894.99 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 21270.00 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.66 | 277.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12733.60 | 21-JAN-08:62 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 277.19 |
February | 4020.37 | 03-FEB-14:00 | 1349.97 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.34 |
March | 4948.24 | 24-MAR-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 267.55 |
April | 14859.29 | 27-APR-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 169.91 |
May | 15674.90 | 03-MAY-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.44 |
June | 18147.91 | 23-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.78 |
July | 17598.75 | 10-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.68 |
August | 18222.05 | 22-AUG-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 190.28 |
September | 17804.36 | 30-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 33.87 |
October | 20979.28 | 18-OCT-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 161.99 |
November | 15383.80 | 19-NOV-09:02 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 0.00 |
December | 6168.43 | 07-DEC-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.05 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4020.37 | 506.24 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 20979.28 | 1349.97 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 8.12 | 277.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 19495.78 | 21-JAN-09:02 | 2970.03 | 7682.23 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.58 |
February | 6966.35 | 03-FEB-14:00 | 4792.55 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 275.20 |
March | 7349.31 | 23-MAR-14:10 | 4657.54 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.35 |
April | 29351.18 | 27-APR-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 286.45 |
May | 30560.56 | 04-MAY-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 205.53 |
June | 32059.43 | 23-JUN-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.16 |
July | 31253.49 | 10-JUL-08:62 | 4455.04 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 222.70 |
August | 31709.93 | 22-AUG-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 292.57 |
September | 31370.40 | 27-SEP-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 311.23 |
October | 33244.99 | 18-OCT-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.72 |
November | 28284.57 | 19-NOV-10:02 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 | 0.00 |
December | 24100.58 | 05-DEC-09:02 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 20.93 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6966.35 | 2970.03 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33244.99 | 4792.55 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 59.54 | 435.58 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9012.51 | 21-JAN-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.16 |
February | 3554.60 | 03-FEB-14:00 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.34 |
March | 3746.70 | 23-MAR-14:10 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.66 |
April | 13722.23 | 27-APR-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.07 |
May | 15702.06 | 04-MAY-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 111.06 |
June | 16475.28 | 23-JUN-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 140.16 |
July | 16065.81 | 10-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.18 |
August | 16312.74 | 22-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 158.27 |
September | 15661.99 | 28-SEP-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 154.82 |
October | 17092.05 | 18-OCT-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.63 |
November | 14530.69 | 19-NOV-10:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 0.00 |
December | 10815.56 | 05-DEC-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.40 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3554.60 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 17092.05 | 2396.20 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 35.96 | 239.16 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8140.48 | 21-JAN-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.02 |
February | 3455.10 | 03-FEB-14:00 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.34 |
March | 3650.49 | 23-MAR-14:10 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.66 |
April | 12596.60 | 27-APR-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.96 |
May | 15041.06 | 04-MAY-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.54 |
June | 16347.78 | 23-JUN-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.89 |
July | 15932.93 | 10-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.79 |
August | 16187.25 | 22-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.06 |
September | 15536.48 | 28-SEP-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.69 |
October | 16981.89 | 18-OCT-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.53 |
November | 14436.28 | 19-NOV-10:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 | 0.00 |
December | 9163.07 | 05-DEC-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 11.59 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3455.10 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16981.89 | 2396.20 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 38.23 | 239.02 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4883.17 | 21-JAN-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 238.52 |
February | 3189.97 | 03-FEB-14:00 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 152.34 |
March | 3424.72 | 23-MAR-14:10 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 175.66 |
April | 8851.17 | 27-APR-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 156.59 |
May | 11581.16 | 04-MAY-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 110.23 |
June | 15192.58 | 21-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 122.93 |
July | 15629.27 | 10-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 113.87 |
August | 14524.33 | 30-AUG-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 112.96 |
September | 15251.43 | 28-SEP-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.62 |
October | 16080.63 | 18-OCT-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 58.28 |
November | 14238.37 | 19-NOV-10:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 | 0.00 |
December | 4032.39 | 05-DEC-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 12.17 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3189.97 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16080.63 | 2396.20 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 45.13 | 238.52 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3825.80 | 18-JAN-13:40 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 200.34 | 0.00 |
February | 2962.71 | 01-FEB-13:10 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.90 |
March | 3416.38 | 23-MAR-14:10 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.72 |
April | 4888.35 | 26-APR-13:00 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 533.38 | 0.00 |
May | 5460.23 | 04-MAY-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 123.62 |
June | 15346.13 | 25-JUN-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 70.62 |
July | 16051.36 | 04-JUL-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.63 |
August | 14173.18 | 05-AUG-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 125.73 |
September | 16367.13 | 30-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 4.17 | 0.00 |
October | 15101.49 | 17-OCT-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 64.96 | 0.00 |
November | 14799.91 | 19-NOV-10:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 62.93 | 0.00 |
December | 3923.17 | 19-DEC-13:10 | 2396.20 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 275.18 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2962.71 | 1856.21 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16367.13 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 533.38 | 185.72 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.886058E+11 | 75394.35 | 14-JAN-14:00 | 0.670166E+09 | 32394.71 | 02-JAN-09:09 |
February | 0.783143E+11 | 70872.89 | 01-FEB-11:50 | 0.312879E+09 | 10919.15 | 27-FEB-09:30 |
March | 0.871971E+11 | 71804.94 | 23-MAR-13:00 | 0.127276E+10 | 52641.18 | 30-MAR-08:09 |
April | 0.849975E+11 | 78024.36 | 26-APR-12:20 | 6168291.58 | 7939.70 | 01-APR-08:09 |
May | 0.864683E+11 | 74959.04 | 03-MAY-12:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.892517E+11 | 77615.43 | 27-JUN-13:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.100064E+12 | 87107.90 | 31-JUL-12:20 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.103824E+12 | 88549.31 | 14-AUG-12:50 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.928369E+11 | 96545.66 | 29-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.988465E+11 | 98620.33 | 16-OCT-11:00 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.855919E+11 | 75084.88 | 19-NOV-12:00 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.890421E+11 | 76350.43 | 19-DEC-12:50 | 64331271.69 | 4895.97 | 13-DEC-20:00 |
Annual Sum or Average | 0.108504E+13 | 0.232631E+10 | ||||
Minimum of Months | 0.783143E+11 | 70872.89 | 0.00 | 0.00 | ||
Maximum of Months | 0.103824E+12 | 98620.33 | 0.127276E+10 | 52641.18 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.119649E+11 | 0.108804E+11 | 0.00 | 0.194062E+11 | 0.00 | 0.00 | 0.190916E+10 | 0.00 | 0.00 | 0.00 | 0.534544E+10 | 0.00 |
February | 0.353889E+11 | 0.102271E+11 | 0.985143E+10 | 0.00 | 0.175600E+11 | 0.00 | 0.00 | 0.445354E+09 | 0.00 | 0.00 | 0.00 | 0.484152E+10 | 0.00 |
March | 0.396588E+11 | 0.104820E+11 | 0.110560E+11 | 0.00 | 0.196911E+11 | 0.00 | 0.00 | 0.924254E+09 | 0.00 | 0.00 | 0.00 | 0.538502E+10 | 0.00 |
April | 0.379231E+11 | 0.931889E+10 | 0.105544E+11 | 0.00 | 0.189770E+11 | 0.00 | 0.00 | 0.308434E+10 | 0.00 | 0.00 | 0.00 | 0.513976E+10 | 0.00 |
May | 0.393718E+11 | 0.889720E+10 | 0.109629E+11 | 0.00 | 0.197265E+11 | 0.00 | 0.00 | 0.222608E+10 | 0.00 | 0.00 | 0.00 | 0.528377E+10 | 0.00 |
June | 0.383312E+11 | 0.824844E+10 | 0.106855E+11 | 0.00 | 0.192644E+11 | 0.00 | 0.00 | 0.762754E+10 | 0.00 | 0.00 | 0.00 | 0.509473E+10 | 0.00 |
July | 0.389786E+11 | 0.868403E+10 | 0.108424E+11 | 0.00 | 0.194877E+11 | 0.00 | 0.00 | 0.168667E+11 | 0.00 | 0.00 | 0.00 | 0.520439E+10 | 0.00 |
August | 0.396438E+11 | 0.930035E+10 | 0.110491E+11 | 0.00 | 0.198810E+11 | 0.00 | 0.00 | 0.187056E+11 | 0.00 | 0.00 | 0.00 | 0.524391E+10 | 0.00 |
September | 0.379380E+11 | 0.979155E+10 | 0.105613E+11 | 0.00 | 0.190027E+11 | 0.00 | 0.00 | 0.104791E+11 | 0.00 | 0.00 | 0.00 | 0.506413E+10 | 0.00 |
October | 0.390997E+11 | 0.109732E+11 | 0.108804E+11 | 0.00 | 0.195459E+11 | 0.00 | 0.00 | 0.130967E+11 | 0.00 | 0.00 | 0.00 | 0.525052E+10 | 0.00 |
November | 0.378782E+11 | 0.113671E+11 | 0.105443E+11 | 0.00 | 0.189288E+11 | 0.00 | 0.00 | 0.175168E+10 | 0.00 | 0.00 | 0.00 | 0.512183E+10 | 0.00 |
December | 0.389936E+11 | 0.121688E+11 | 0.108529E+11 | 0.00 | 0.193681E+11 | 0.00 | 0.00 | 0.233412E+10 | 0.00 | 0.00 | 0.00 | 0.532466E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121424E+12 | 0.128721E+12 | 0.00 | 0.230839E+12 | 0.00 | 0.00 | 0.794508E+11 | 0.00 | 0.00 | 0.00 | 0.622997E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.824844E+10 | 0.985143E+10 | 0.00 | 0.175600E+11 | 0.00 | 0.00 | 0.445354E+09 | 0.00 | 0.00 | 0.00 | 0.484152E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.121688E+11 | 0.110560E+11 | 0.00 | 0.198810E+11 | 0.00 | 0.00 | 0.187056E+11 | 0.00 | 0.00 | 0.00 | 0.538502E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.670166E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.312879E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.127276E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 6168291.58 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 64331271.69 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.232631E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.127276E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 13230.40 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 13230.40 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 13230.40 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 13230.40 | 20-APR-10:20 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 13230.40 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 13230.40 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 13230.40 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 13230.40 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13230.40 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 13230.40 | 15-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 13230.40 | 30-NOV-10:50 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 13230.40 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 13230.40 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 13230.40 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 19466.62 | 14-JAN-14:00 | 0.00 | 0.00 | 0.00 | 11785.29 | 17-JAN-18:00 | 0.00 |
February | 16475.94 | 01-FEB-12:09 | 0.00 | 0.00 | 0.00 | 9672.73 | 09-FEB-18:40 | 0.00 |
March | 16622.82 | 23-MAR-13:00 | 0.00 | 0.00 | 0.00 | 9706.94 | 25-MAR-12:30 | 0.00 |
April | 23685.95 | 26-APR-12:00 | 0.00 | 0.00 | 0.00 | 8785.80 | 08-APR-12:20 | 0.00 |
May | 18765.22 | 04-MAY-12:09 | 0.00 | 0.00 | 0.00 | 9665.55 | 13-MAY-15:09 | 0.00 |
June | 23204.03 | 28-JUN-12:09 | 0.00 | 0.00 | 0.00 | 7577.69 | 14-JUN-12:30 | 0.00 |
July | 32196.00 | 31-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7577.31 | 28-JUL-12:20 | 0.00 |
August | 31504.39 | 17-AUG-13:00 | 0.00 | 0.00 | 0.00 | 11636.49 | 11-AUG-11:20 | 0.00 |
September | 43169.59 | 29-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7576.56 | 05-SEP-12:50 | 0.00 |
October | 44062.68 | 16-OCT-11:09 | 0.00 | 0.00 | 0.00 | 7580.23 | 25-OCT-12:39 | 0.00 |
November | 21724.12 | 19-NOV-12:00 | 0.00 | 0.00 | 0.00 | 9666.66 | 06-NOV-18:19 | 0.00 |
December | 19420.28 | 19-DEC-13:09 | 0.00 | 0.00 | 0.00 | 9686.07 | 22-DEC-12:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 16475.94 | 0.00 | 0.00 | 0.00 | 7576.56 | 0.00 | ||
Maximum of Months | 44062.68 | 0.00 | 0.00 | 0.00 | 11785.29 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 75394.35 | 14-JAN-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 19466.62 | 0.00 |
February | 70872.89 | 01-FEB-11:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 14857.96 | 0.00 |
March | 71804.94 | 23-MAR-13:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 16622.82 | 0.00 |
April | 78024.36 | 26-APR-12:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 22525.68 | 0.00 |
May | 74959.04 | 03-MAY-12:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 17349.61 | 0.00 |
June | 77615.43 | 27-JUN-13:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 22121.79 | 0.00 |
July | 87107.90 | 31-JUL-12:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 31613.37 | 0.00 |
August | 88549.31 | 14-AUG-12:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 28816.17 | 0.00 |
September | 96545.66 | 29-SEP-12:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 43169.59 | 0.00 |
October | 98620.33 | 16-OCT-11:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 43128.92 | 0.00 |
November | 75084.88 | 19-NOV-12:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 21724.12 | 0.00 |
December | 76350.43 | 19-DEC-12:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 18745.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 70872.89 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 14857.96 | 0.00 | |
Maximum of Months | 98620.33 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13230.40 | 0.00 | 0.00 | 43169.59 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 32394.71 | 02-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 10919.15 | 27-FEB-09:30 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 52641.18 | 30-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 7939.70 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 4895.97 | 13-DEC-20:00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 52641.18 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 251.17 | 22.99 | 71.83 | 23.18 | 0.33 | 23.18 |
February | 228.50 | 22.98 | 62.33 | 23.18 | 0.17 | 23.18 |
March | 277.50 | 22.66 | 86.00 | 22.94 | 1.50 | 22.93 |
April | 84.17 | 23.46 | 233.00 | 23.78 | 0.00 | 23.78 |
May | 66.00 | 23.55 | 239.33 | 23.82 | 0.00 | 23.82 |
June | 10.17 | 23.74 | 402.00 | 23.91 | 1.50 | 23.91 |
July | 73.00 | 23.99 | 487.50 | 23.94 | 73.00 | 23.94 |
August | 75.50 | 24.01 | 494.17 | 23.94 | 75.50 | 23.95 |
September | 35.83 | 23.88 | 432.17 | 23.91 | 33.00 | 23.91 |
October | 99.83 | 23.92 | 306.50 | 23.92 | 59.33 | 23.93 |
November | 143.33 | 23.61 | 139.33 | 23.75 | 0.00 | 23.75 |
December | 279.67 | 23.30 | 34.00 | 23.36 | 0.00 | 23.36 |
Annual Sum or Average | 1624.67 | 23.26 | 2988.17 | 23.68 | 244.33 | 23.70 |
Minimum of Months | 10.17 | 22.66 | 34.00 | 22.94 | 0.00 | 22.93 |
Maximum of Months | 279.67 | 24.01 | 494.17 | 23.94 | 75.50 | 23.95 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 152.67 | 23.54 | 107.67 | 23.69 | 0.00 | 23.69 |
February | 125.33 | 23.46 | 95.17 | 23.65 | 0.00 | 23.65 |
March | 163.00 | 23.19 | 133.50 | 23.51 | 0.00 | 23.51 |
April | 37.00 | 23.75 | 274.17 | 23.89 | 0.00 | 23.89 |
May | 19.33 | 23.79 | 273.33 | 23.90 | 0.00 | 23.90 |
June | 1.83 | 23.84 | 424.83 | 23.93 | 1.67 | 23.93 |
July | 53.67 | 24.02 | 489.67 | 23.94 | 53.67 | 23.94 |
August | 51.17 | 24.09 | 496.17 | 23.95 | 51.17 | 23.96 |
September | 23.50 | 23.89 | 446.50 | 23.92 | 23.33 | 23.92 |
October | 65.00 | 23.84 | 316.00 | 23.91 | 32.83 | 23.92 |
November | 80.17 | 23.87 | 167.00 | 23.90 | 0.00 | 23.90 |
December | 161.17 | 23.76 | 61.50 | 23.80 | 0.00 | 23.80 |
Annual Sum or Average | 933.83 | 23.64 | 3285.50 | 23.86 | 162.67 | 23.86 |
Minimum of Months | 1.83 | 23.19 | 61.50 | 23.51 | 0.00 | 23.51 |
Maximum of Months | 163.00 | 24.09 | 496.17 | 23.95 | 53.67 | 23.96 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 147.83 | 23.14 | 69.00 | 23.39 | 0.00 | 23.39 |
February | 123.00 | 23.11 | 65.33 | 23.38 | 0.17 | 23.38 |
March | 163.17 | 22.81 | 92.17 | 23.21 | 0.00 | 23.21 |
April | 44.00 | 23.42 | 194.00 | 23.84 | 0.00 | 23.84 |
May | 30.33 | 23.59 | 205.83 | 23.89 | 0.00 | 23.89 |
June | 3.50 | 23.72 | 314.67 | 23.96 | 0.83 | 23.96 |
July | 29.83 | 24.20 | 364.67 | 24.01 | 29.83 | 24.02 |
August | 32.50 | 24.21 | 376.33 | 24.01 | 32.50 | 24.02 |
September | 15.17 | 24.02 | 334.17 | 23.98 | 14.00 | 23.98 |
October | 55.33 | 23.98 | 238.00 | 24.01 | 34.83 | 24.02 |
November | 79.33 | 23.71 | 119.83 | 23.83 | 0.00 | 23.83 |
December | 155.83 | 23.52 | 38.83 | 23.60 | 0.00 | 23.60 |
Annual Sum or Average | 879.83 | 23.37 | 2412.83 | 23.81 | 112.17 | 23.82 |
Minimum of Months | 3.50 | 22.81 | 38.83 | 23.21 | 0.00 | 23.21 |
Maximum of Months | 163.17 | 24.21 | 376.33 | 24.01 | 34.83 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 159.83 | 23.06 | 62.00 | 23.31 | 0.00 | 23.31 |
February | 134.50 | 23.05 | 54.50 | 23.30 | 0.33 | 23.30 |
March | 177.50 | 22.75 | 78.50 | 23.11 | 0.00 | 23.11 |
April | 51.00 | 23.40 | 184.83 | 23.81 | 0.00 | 23.81 |
May | 33.67 | 23.56 | 199.67 | 23.88 | 0.00 | 23.88 |
June | 4.33 | 23.70 | 311.50 | 23.96 | 0.83 | 23.96 |
July | 31.00 | 24.20 | 364.17 | 24.01 | 31.00 | 24.02 |
August | 33.33 | 24.20 | 375.83 | 24.00 | 33.33 | 24.02 |
September | 15.33 | 24.02 | 332.17 | 23.98 | 14.00 | 23.98 |
October | 56.50 | 23.97 | 236.00 | 24.00 | 35.00 | 24.01 |
November | 86.83 | 23.69 | 107.33 | 23.81 | 0.00 | 23.81 |
December | 173.33 | 23.49 | 34.50 | 23.56 | 0.00 | 23.56 |
Annual Sum or Average | 957.17 | 23.32 | 2341.00 | 23.78 | 114.50 | 23.79 |
Minimum of Months | 4.33 | 22.75 | 34.50 | 23.11 | 0.00 | 23.11 |
Maximum of Months | 177.50 | 24.20 | 375.83 | 24.01 | 35.00 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 178.00 | 22.98 | 49.67 | 23.19 | 0.17 | 23.19 |
February | 163.50 | 23.00 | 40.00 | 23.17 | 0.50 | 23.17 |
March | 206.33 | 22.66 | 67.83 | 22.97 | 0.17 | 22.97 |
April | 61.17 | 23.34 | 168.50 | 23.77 | 0.00 | 23.77 |
May | 42.83 | 23.51 | 182.83 | 23.85 | 0.00 | 23.85 |
June | 6.33 | 23.67 | 303.17 | 23.95 | 1.00 | 23.95 |
July | 33.17 | 24.18 | 361.50 | 24.00 | 33.17 | 24.02 |
August | 36.67 | 24.17 | 374.83 | 24.00 | 36.67 | 24.01 |
September | 16.67 | 23.99 | 325.33 | 23.97 | 14.83 | 23.97 |
October | 62.33 | 23.94 | 229.50 | 23.99 | 37.50 | 24.00 |
November | 101.67 | 23.63 | 90.00 | 23.76 | 0.00 | 23.76 |
December | 200.17 | 23.42 | 28.00 | 23.48 | 0.00 | 23.48 |
Annual Sum or Average | 1108.83 | 23.25 | 2221.17 | 23.73 | 124.00 | 23.74 |
Minimum of Months | 6.33 | 22.66 | 28.00 | 22.97 | 0.00 | 22.97 |
Maximum of Months | 206.33 | 24.18 | 374.83 | 24.00 | 37.50 | 24.02 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 207.17 | 22.95 | 22.00 | 23.03 | 0.17 | 23.03 |
February | 214.33 | 22.93 | 15.67 | 22.99 | 1.83 | 23.00 |
March | 239.17 | 22.54 | 46.83 | 22.76 | 0.33 | 22.76 |
April | 75.00 | 23.36 | 126.67 | 23.70 | 0.00 | 23.70 |
May | 57.50 | 23.49 | 117.17 | 23.76 | 0.00 | 23.76 |
June | 8.67 | 23.68 | 257.17 | 23.90 | 1.00 | 23.90 |
July | 34.33 | 23.96 | 329.83 | 23.93 | 34.33 | 23.94 |
August | 36.83 | 23.96 | 344.17 | 23.92 | 36.83 | 23.93 |
September | 21.17 | 23.89 | 292.83 | 23.92 | 17.33 | 23.92 |
October | 67.50 | 23.89 | 199.17 | 23.93 | 42.83 | 23.93 |
November | 123.50 | 23.60 | 55.83 | 23.69 | 0.00 | 23.69 |
December | 239.50 | 23.32 | 14.50 | 23.36 | 0.00 | 23.36 |
Annual Sum or Average | 1324.67 | 23.17 | 1821.83 | 23.60 | 134.67 | 23.62 |
Minimum of Months | 8.67 | 22.54 | 14.50 | 22.76 | 0.00 | 22.76 |
Maximum of Months | 239.50 | 23.96 | 344.17 | 23.93 | 42.83 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 214.17 | 22.98 | 19.33 | 23.04 | 0.67 | 23.04 |
February | 222.17 | 22.94 | 9.83 | 22.98 | 1.83 | 22.99 |
March | 254.17 | 22.58 | 40.67 | 22.76 | 0.50 | 22.76 |
April | 82.17 | 23.41 | 110.00 | 23.69 | 0.00 | 23.69 |
May | 63.67 | 23.54 | 91.50 | 23.75 | 0.00 | 23.75 |
June | 11.00 | 23.72 | 241.33 | 23.91 | 1.00 | 23.91 |
July | 34.83 | 23.96 | 326.33 | 23.93 | 34.83 | 23.94 |
August | 37.50 | 23.96 | 341.50 | 23.92 | 37.50 | 23.93 |
September | 21.50 | 23.89 | 283.50 | 23.92 | 17.17 | 23.92 |
October | 72.00 | 23.90 | 182.00 | 23.93 | 43.00 | 23.93 |
November | 129.00 | 23.63 | 46.33 | 23.70 | 0.00 | 23.70 |
December | 252.83 | 23.36 | 12.67 | 23.38 | 0.00 | 23.38 |
Annual Sum or Average | 1395.00 | 23.20 | 1705.00 | 23.59 | 136.50 | 23.61 |
Minimum of Months | 11.00 | 22.58 | 9.83 | 22.76 | 0.00 | 22.76 |
Maximum of Months | 254.17 | 23.96 | 341.50 | 23.93 | 43.00 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 220.50 | 22.94 | 18.50 | 23.01 | 0.67 | 23.00 |
February | 231.50 | 22.89 | 7.67 | 22.92 | 1.83 | 22.93 |
March | 263.83 | 22.54 | 37.00 | 22.70 | 0.50 | 22.70 |
April | 90.17 | 23.39 | 103.33 | 23.67 | 0.00 | 23.67 |
May | 70.67 | 23.52 | 83.33 | 23.73 | 0.00 | 23.73 |
June | 12.67 | 23.71 | 234.33 | 23.90 | 1.00 | 23.90 |
July | 35.33 | 23.96 | 324.67 | 23.93 | 35.33 | 23.94 |
August | 37.67 | 23.96 | 340.67 | 23.92 | 37.67 | 23.93 |
September | 22.83 | 23.88 | 280.17 | 23.92 | 17.50 | 23.92 |
October | 73.67 | 23.89 | 177.67 | 23.93 | 43.17 | 23.93 |
November | 138.17 | 23.60 | 39.33 | 23.66 | 0.00 | 23.66 |
December | 262.67 | 23.33 | 11.33 | 23.35 | 0.00 | 23.35 |
Annual Sum or Average | 1459.67 | 23.17 | 1658.00 | 23.57 | 137.67 | 23.58 |
Minimum of Months | 12.67 | 22.54 | 7.67 | 22.70 | 0.00 | 22.70 |
Maximum of Months | 263.83 | 23.96 | 340.67 | 23.93 | 43.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 242.00 | 22.86 | 18.00 | 22.92 | 1.33 | 22.91 |
February | 254.00 | 22.77 | 5.33 | 22.79 | 1.67 | 22.79 |
March | 282.83 | 22.43 | 29.67 | 22.55 | 1.50 | 22.54 |
April | 107.83 | 23.30 | 89.33 | 23.58 | 0.00 | 23.58 |
May | 87.83 | 23.42 | 69.17 | 23.63 | 0.00 | 23.63 |
June | 20.33 | 23.66 | 217.50 | 23.89 | 1.17 | 23.89 |
July | 36.83 | 23.96 | 322.00 | 23.93 | 36.67 | 23.94 |
August | 41.00 | 23.96 | 338.67 | 23.92 | 41.00 | 23.93 |
September | 27.67 | 23.82 | 274.17 | 23.91 | 17.83 | 23.91 |
October | 82.67 | 23.88 | 172.17 | 23.92 | 45.17 | 23.92 |
November | 166.17 | 23.50 | 23.83 | 23.55 | 0.00 | 23.55 |
December | 285.50 | 23.23 | 7.67 | 23.25 | 0.00 | 23.25 |
Annual Sum or Average | 1634.67 | 23.09 | 1567.50 | 23.49 | 146.33 | 23.51 |
Minimum of Months | 20.33 | 22.43 | 5.33 | 22.55 | 0.00 | 22.54 |
Maximum of Months | 285.50 | 23.96 | 338.67 | 23.93 | 45.17 | 23.94 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 278.00 | 22.77 | 19.67 | 22.78 | 6.50 | 22.75 |
February | 273.50 | 22.53 | 6.17 | 22.54 | 3.50 | 22.53 |
March | 296.33 | 22.24 | 25.33 | 22.33 | 5.17 | 22.31 |
April | 133.67 | 23.14 | 79.33 | 23.42 | 0.50 | 23.42 |
May | 129.33 | 23.30 | 45.33 | 23.45 | 0.00 | 23.45 |
June | 37.67 | 23.49 | 196.50 | 23.85 | 1.33 | 23.85 |
July | 41.33 | 23.96 | 319.33 | 23.93 | 39.17 | 23.94 |
August | 43.67 | 23.94 | 334.00 | 23.92 | 42.17 | 23.93 |
September | 37.67 | 23.66 | 261.50 | 23.88 | 18.17 | 23.89 |
October | 100.83 | 23.83 | 165.17 | 23.90 | 47.17 | 23.90 |
November | 213.33 | 23.31 | 15.33 | 23.34 | 0.67 | 23.34 |
December | 313.17 | 23.05 | 5.00 | 23.05 | 0.50 | 23.05 |
Annual Sum or Average | 1898.50 | 22.96 | 1472.67 | 23.37 | 164.83 | 23.38 |
Minimum of Months | 37.67 | 22.24 | 5.00 | 22.33 | 0.00 | 22.31 |
Maximum of Months | 313.17 | 23.96 | 334.00 | 23.93 | 47.17 | 23.94 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.42197 | 38.24357 | 0.22399 | 6.99984 |
February | 448.00000 | 23.41377 | 40.94933 | 0.23324 | 6.86119 |
March | 497.00000 | 23.18354 | 44.23342 | 0.19873 | 7.07813 |
April | 479.00000 | 23.80822 | 46.23670 | 0.39494 | 8.54227 |
May | 496.00000 | 23.84436 | 45.61739 | -0.5031 | 10.60396 |
June | 481.00000 | 23.90829 | 51.51953 | -0.4037 | 8.57025 |
July | 495.00000 | 23.92779 | 57.32421 | -0.3145 | 7.17518 |
August | 497.00000 | 23.93240 | 59.14156 | -0.3002 | 6.98287 |
September | 479.00000 | 23.91194 | 54.10037 | -0.3592 | 7.85864 |
October | 496.00000 | 23.90666 | 44.90914 | 0.44913 | 9.52656 |
November | 480.00000 | 23.80131 | 38.53017 | 0.33318 | 7.66987 |
December | 496.00000 | 23.54082 | 33.35842 | 0.22389 | 6.56606 |
Annual Sum or Average | 5840.00000 | 23.71760 | 46.20732 | 0.01311 | 7.87451 |
Minimum of Months | 448.00000 | 23.18354 | 33.35842 | -0.5031 | 6.56606 |
Maximum of Months | 497.00000 | 23.93240 | 59.14156 | 0.44913 | 10.60396 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.78404 | 37.95783 | 0.31977 | 7.49569 |
February | 448.00000 | 23.76869 | 40.29649 | 0.32724 | 7.51081 |
March | 497.00000 | 23.65163 | 43.45744 | 0.31488 | 7.66493 |
April | 479.00000 | 23.88985 | 45.82639 | 0.42371 | 8.88812 |
May | 496.00000 | 23.90923 | 45.27392 | -0.4683 | 9.71818 |
June | 481.00000 | 23.92649 | 51.22338 | -0.3908 | 8.30031 |
July | 495.00000 | 23.92043 | 56.70899 | -0.3226 | 7.28723 |
August | 497.00000 | 23.93385 | 58.48160 | -0.3044 | 7.03415 |
September | 479.00000 | 23.91932 | 53.70458 | -0.3543 | 7.74427 |
October | 496.00000 | 23.90235 | 44.50068 | 0.45274 | 9.54007 |
November | 480.00000 | 23.90372 | 38.17280 | 0.36997 | 8.07424 |
December | 496.00000 | 23.84153 | 32.90632 | 0.30596 | 7.17183 |
Annual Sum or Average | 5840.00000 | 23.86281 | 45.73647 | 0.05439 | 8.03761 |
Minimum of Months | 448.00000 | 23.65163 | 32.90632 | -0.4683 | 7.03415 |
Maximum of Months | 497.00000 | 23.93385 | 58.48160 | 0.45274 | 9.71818 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.59394 | 36.63633 | 0.27134 | 7.30097 |
February | 336.00000 | 23.59425 | 39.61709 | 0.28683 | 7.20790 |
March | 379.00000 | 23.41618 | 43.30113 | 0.26482 | 7.42263 |
April | 360.00000 | 23.85415 | 45.17379 | 0.41092 | 8.76347 |
May | 375.00000 | 23.89459 | 44.60095 | -0.4780 | 9.98600 |
June | 366.00000 | 23.94956 | 50.57464 | -0.3878 | 8.29655 |
July | 369.00000 | 23.99254 | 56.19424 | -0.3001 | 7.04377 |
August | 379.00000 | 23.98704 | 57.96021 | -0.2851 | 6.83661 |
September | 360.00000 | 23.96597 | 53.04073 | -0.3411 | 7.61244 |
October | 371.00000 | 23.96959 | 43.66754 | 0.46515 | 9.83280 |
November | 360.00000 | 23.85204 | 37.32089 | 0.35533 | 7.89859 |
December | 369.00000 | 23.72460 | 31.93209 | 0.27793 | 6.92733 |
Annual Sum or Average | 4395.00000 | 23.81688 | 45.05783 | 0.04222 | 7.93133 |
Minimum of Months | 336.00000 | 23.41618 | 31.93209 | -0.4780 | 6.83661 |
Maximum of Months | 379.00000 | 23.99254 | 57.96021 | 0.46515 | 9.98600 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.53672 | 36.76670 | 0.25101 | 7.23810 |
February | 336.00000 | 23.54272 | 39.76978 | 0.26943 | 7.08151 |
March | 379.00000 | 23.34365 | 43.49397 | 0.24218 | 7.28605 |
April | 360.00000 | 23.84019 | 45.24248 | 0.40282 | 8.65170 |
May | 375.00000 | 23.88736 | 44.64839 | -0.4861 | 10.16473 |
June | 366.00000 | 23.94703 | 50.61430 | -0.3926 | 8.37707 |
July | 369.00000 | 23.99104 | 56.22592 | -0.3030 | 7.07840 |
August | 379.00000 | 23.98560 | 57.99276 | -0.2878 | 6.86607 |
September | 360.00000 | 23.96395 | 53.08563 | -0.3450 | 7.66798 |
October | 371.00000 | 23.96758 | 43.69060 | 0.46301 | 9.79360 |
November | 360.00000 | 23.84150 | 37.37491 | 0.34831 | 7.80730 |
December | 369.00000 | 23.69421 | 32.01295 | 0.26537 | 6.81848 |
Annual Sum or Average | 4395.00000 | 23.79588 | 45.13242 | 0.03288 | 7.90745 |
Minimum of Months | 336.00000 | 23.34365 | 32.01295 | -0.4861 | 6.81848 |
Maximum of Months | 379.00000 | 23.99104 | 57.99276 | 0.46301 | 10.16473 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.45397 | 36.96688 | 0.22275 | 7.12308 |
February | 336.00000 | 23.44046 | 40.08135 | 0.23837 | 6.87387 |
March | 379.00000 | 23.20904 | 43.86037 | 0.20318 | 7.07237 |
April | 360.00000 | 23.80852 | 45.39614 | 0.38779 | 8.45442 |
May | 375.00000 | 23.86725 | 44.76901 | -0.5027 | 10.55588 |
June | 366.00000 | 23.93968 | 50.72017 | -0.4037 | 8.56910 |
July | 369.00000 | 23.98529 | 56.38554 | -0.3118 | 7.18798 |
August | 379.00000 | 23.97996 | 58.16596 | -0.2962 | 6.96658 |
September | 360.00000 | 23.95732 | 53.19726 | -0.3551 | 7.81948 |
October | 371.00000 | 23.95959 | 43.79965 | 0.45600 | 9.66476 |
November | 360.00000 | 23.81567 | 37.49825 | 0.33520 | 7.64614 |
December | 369.00000 | 23.62717 | 32.18496 | 0.24199 | 6.63537 |
Annual Sum or Average | 4395.00000 | 23.75462 | 45.30766 | 0.01526 | 7.88747 |
Minimum of Months | 336.00000 | 23.20904 | 32.18496 | -0.5027 | 6.63537 |
Maximum of Months | 379.00000 | 23.98529 | 58.16596 | 0.45600 | 10.55588 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.30539 | 38.94936 | 0.17470 | 6.80614 |
February | 308.00000 | 23.20885 | 42.33998 | 0.17476 | 6.45323 |
March | 348.00000 | 22.94888 | 46.00252 | 0.13145 | 6.74090 |
April | 330.00000 | 23.76584 | 46.70379 | 0.36349 | 8.06212 |
May | 344.00000 | 23.82308 | 46.02226 | -0.5407 | 11.39234 |
June | 336.00000 | 23.89713 | 51.75696 | -0.4367 | 9.13079 |
July | 338.00000 | 23.92805 | 57.53753 | -0.3411 | 7.54098 |
August | 348.00000 | 23.91867 | 59.23331 | -0.3263 | 7.31879 |
September | 330.00000 | 23.90716 | 54.30862 | -0.3845 | 8.23961 |
October | 340.00000 | 23.91555 | 45.19358 | 0.44034 | 9.31193 |
November | 330.00000 | 23.75928 | 39.10040 | 0.30918 | 7.28008 |
December | 338.00000 | 23.47613 | 34.17166 | 0.19569 | 6.25494 |
Annual Sum or Average | 4030.00000 | 23.65588 | 46.83085 | -0.0227 | 7.88894 |
Minimum of Months | 308.00000 | 22.94888 | 34.17166 | -0.5407 | 6.25494 |
Maximum of Months | 348.00000 | 23.92805 | 59.23331 | 0.44034 | 11.39234 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.30732 | 38.86690 | 0.16506 | 6.74031 |
February | 308.00000 | 23.19959 | 42.28855 | 0.16175 | 6.37442 |
March | 348.00000 | 22.92710 | 45.96827 | 0.11521 | 6.66736 |
April | 330.00000 | 23.76958 | 46.63529 | 0.35246 | 7.89831 |
May | 344.00000 | 23.82748 | 45.95285 | -0.5550 | 11.71577 |
June | 336.00000 | 23.89828 | 51.71696 | -0.4530 | 9.42781 |
July | 338.00000 | 23.92806 | 57.52310 | -0.3602 | 7.81720 |
August | 348.00000 | 23.91874 | 59.22038 | -0.3457 | 7.58498 |
September | 330.00000 | 23.90835 | 54.27078 | -0.4021 | 8.52127 |
October | 340.00000 | 23.91665 | 45.13972 | 0.42838 | 9.08957 |
November | 330.00000 | 23.77113 | 38.99700 | 0.30164 | 7.17916 |
December | 338.00000 | 23.48177 | 34.08623 | 0.18661 | 6.18252 |
Annual Sum or Average | 4030.00000 | 23.65587 | 46.77653 | -0.0365 | 7.94609 |
Minimum of Months | 308.00000 | 22.92710 | 34.08623 | -0.5550 | 6.18252 |
Maximum of Months | 348.00000 | 23.92806 | 59.22038 | 0.42838 | 11.71577 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.26630 | 38.97710 | 0.15149 | 6.69223 |
February | 308.00000 | 23.13303 | 42.48683 | 0.14201 | 6.29474 |
March | 348.00000 | 22.85915 | 46.15585 | 0.09531 | 6.62035 |
April | 330.00000 | 23.75303 | 46.71823 | 0.34462 | 7.80824 |
May | 344.00000 | 23.81568 | 46.02469 | -0.5643 | 11.96541 |
June | 336.00000 | 23.89614 | 51.76336 | -0.4584 | 9.53671 |
July | 338.00000 | 23.92722 | 57.57430 | -0.3641 | 7.87724 |
August | 348.00000 | 23.91808 | 59.27420 | -0.3494 | 7.64077 |
September | 330.00000 | 23.90662 | 54.31451 | -0.4068 | 8.60426 |
October | 340.00000 | 23.91552 | 45.17788 | 0.42526 | 9.03570 |
November | 330.00000 | 23.75044 | 39.08775 | 0.29302 | 7.08660 |
December | 338.00000 | 23.44121 | 34.20046 | 0.17293 | 6.11661 |
Annual Sum or Average | 4030.00000 | 23.63345 | 46.86673 | -0.0460 | 7.95390 |
Minimum of Months | 308.00000 | 22.85915 | 34.20046 | -0.5643 | 6.11661 |
Maximum of Months | 348.00000 | 23.92722 | 59.27420 | 0.42526 | 11.96541 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.15204 | 39.28371 | 0.11717 | 6.60737 |
February | 308.00000 | 22.95856 | 42.98144 | 0.09310 | 6.16268 |
March | 348.00000 | 22.69508 | 46.61059 | 0.04985 | 6.57371 |
April | 330.00000 | 23.69756 | 46.96783 | 0.32404 | 7.60367 |
May | 344.00000 | 23.77030 | 46.25337 | -0.5905 | 12.72200 |
June | 336.00000 | 23.88755 | 51.90211 | -0.4708 | 9.80948 |
July | 338.00000 | 23.92521 | 57.70241 | -0.3697 | 7.96867 |
August | 348.00000 | 23.91646 | 59.41562 | -0.3548 | 7.72480 |
September | 330.00000 | 23.90020 | 54.44442 | -0.4165 | 8.79294 |
October | 340.00000 | 23.91039 | 45.29283 | 0.41865 | 8.93228 |
November | 330.00000 | 23.67726 | 39.36967 | 0.26789 | 6.85115 |
December | 338.00000 | 23.32431 | 34.52122 | 0.13709 | 5.98775 |
Annual Sum or Average | 4030.00000 | 23.57012 | 47.11447 | -0.0688 | 7.99475 |
Minimum of Months | 308.00000 | 22.69508 | 34.52122 | -0.5905 | 5.98775 |
Maximum of Months | 348.00000 | 23.92521 | 59.41562 | 0.41865 | 12.72200 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.97254 | 39.29732 | 0.05388 | 6.58611 |
February | 308.00000 | 22.67957 | 43.32374 | 0.00064 | 6.22347 |
March | 348.00000 | 22.48440 | 46.92450 | -0.0222 | 6.75329 |
April | 330.00000 | 23.58969 | 47.13234 | 0.28820 | 7.36933 |
May | 344.00000 | 23.66926 | 46.44686 | -0.6435 | 14.46647 |
June | 336.00000 | 23.85759 | 52.00084 | -0.4937 | 10.44794 |
July | 338.00000 | 23.92679 | 57.56304 | -0.3607 | 7.86104 |
August | 348.00000 | 23.91745 | 59.28286 | -0.3466 | 7.64286 |
September | 330.00000 | 23.87976 | 54.52661 | -0.4309 | 9.19085 |
October | 340.00000 | 23.89429 | 45.21207 | 0.40682 | 8.79060 |
November | 330.00000 | 23.51236 | 39.49523 | 0.20863 | 6.44558 |
December | 338.00000 | 23.10625 | 34.62451 | 0.06306 | 5.91357 |
Annual Sum or Average | 4030.00000 | 23.46090 | 47.20281 | -0.1086 | 8.16116 |
Minimum of Months | 308.00000 | 22.48440 | 34.62451 | -0.6435 | 5.91357 |
Maximum of Months | 348.00000 | 23.92679 | 59.28286 | 0.40682 | 14.46647 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.127206E+10 | 0.348841E+09 | 68.46 | 0.121570E+10 | 56361991.77 | 0.00 | 0.54 | 24-JAN-09:02 | 0.00 | 01-JAN-00:10 | 15631.61 | 24-JAN-09:02 | 15631.61 | 24-JAN-09:02 | 5664.90 | 21-JAN-09:02 | 3853.49 | 24-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.271838E+09 | 74652644.90 | 31.76 | 0.268454E+09 | 3384688.06 | 0.00 | 0.49 | 01-FEB-09:02 | 0.00 | 01-FEB-00:10 | 14103.57 | 01-FEB-09:02 | 14103.57 | 01-FEB-09:02 | 807.37 | 16-FEB-09:02 | 3570.89 | 01-FEB-09:02 | 0.00 | 01-FEB-00:10 |
March | 0.611022E+09 | 0.166147E+09 | 40.72 | 0.522450E+09 | 88572298.89 | 0.00 | 0.38 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 11311.20 | 23-MAR-14:00 | 10058.29 | 11-MAR-14:00 | 2608.19 | 23-MAR-15:00 | 2961.65 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.214415E+10 | 0.578514E+09 | 121.37 | 0.180884E+10 | 0.335313E+09 | 0.00 | 1.00 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 35197.68 | 27-APR-08:62 | 22350.15 | 27-APR-08:62 | 12847.53 | 27-APR-08:62 | 7484.78 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.154963E+10 | 0.419895E+09 | 122.64 | 0.130361E+10 | 0.246025E+09 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 35375.74 | 03-MAY-08:62 | 27522.62 | 24-MAY-08:62 | 11025.64 | 03-MAY-08:62 | 7517.51 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.531124E+10 | 0.140306E+10 | 223.37 | 0.397599E+10 | 0.133525E+10 | 0.00 | 1.00 | 17-JUN-08:62 | 0.00 | 01-JUN-00:10 | 36248.05 | 30-JUN-08:62 | 27120.15 | 23-JUN-08:62 | 16472.99 | 28-JUN-08:62 | 7662.27 | 30-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.121246E+11 | 0.313758E+10 | 342.20 | 0.851797E+10 | 0.360663E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 37125.01 | 19-JUL-08:62 | 27006.29 | 10-JUL-08:62 | 17482.75 | 20-JUL-08:03 | 7901.11 | 19-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.132703E+11 | 0.341431E+10 | 336.67 | 0.915067E+10 | 0.411965E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 37400.90 | 14-AUG-08:62 | 25790.74 | 23-AUG-08:62 | 16815.79 | 25-AUG-08:62 | 7982.12 | 14-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.724257E+10 | 0.194088E+10 | 258.99 | 0.552819E+10 | 0.171438E+10 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 37616.31 | 22-SEP-08:62 | 34234.46 | 30-SEP-08:61 | 18492.20 | 22-SEP-08:62 | 8392.70 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.887512E+10 | 0.241284E+10 | 291.21 | 0.747404E+10 | 0.140107E+10 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 37163.18 | 01-OCT-07:03 | 33454.58 | 17-OCT-08:62 | 19461.57 | 01-OCT-07:03 | 8160.88 | 16-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.116479E+10 | 0.317948E+09 | 73.17 | 0.113410E+10 | 30686098.05 | 0.00 | 0.69 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 21900.39 | 10-NOV-09:02 | 18975.67 | 28-NOV-09:02 | 6278.88 | 10-NOV-09:02 | 5139.41 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.155004E+10 | 0.423728E+09 | 99.35 | 0.154008E+10 | 9965934.78 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 33279.73 | 05-DEC-09:02 | 33279.73 | 05-DEC-09:02 | 1179.53 | 07-DEC-14:00 | 7485.75 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.553874E+11 | 0.146384E+11 | 2009.91 | 0.424401E+11 | 0.129473E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.271838E+09 | 74652644.90 | 31.76 | 0.268454E+09 | 3384688.06 | 0.00 | 0.38 | 0.00 | 11311.20 | 10058.29 | 807.37 | 2961.65 | 0.00 | |||||||
Maximum of Months | 0.132703E+11 | 0.341431E+10 | 342.20 | 0.915067E+10 | 0.411965E+10 | 0.00 | 1.00 | 0.00 | 37616.31 | 34234.46 | 19461.57 | 8392.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.847463E+09 | 0.222991E+09 | 89.73 | 0.804398E+09 | 43064948.83 | 0.00 | 1.00 | 15-JAN-18:01 | 0.00 | 01-JAN-00:10 | 17724.06 | 21-JAN-09:02 | 16935.97 | 15-JAN-18:01 | 6727.30 | 21-JAN-09:02 | 3685.13 | 21-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.242634E+09 | 63723013.66 | 48.50 | 0.233652E+09 | 8981935.80 | 0.00 | 1.00 | 05-FEB-18:10 | 0.00 | 01-FEB-00:10 | 17382.37 | 05-FEB-18:10 | 17250.70 | 05-FEB-18:10 | 3635.62 | 16-FEB-09:02 | 3579.84 | 05-FEB-18:10 | 0.00 | 01-FEB-00:10 |
March | 0.460417E+09 | 0.120564E+09 | 56.25 | 0.392736E+09 | 67681676.12 | 0.00 | 0.42 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 6642.65 | 23-MAR-14:00 | 6051.08 | 11-MAR-14:00 | 1507.71 | 22-MAR-13:00 | 1671.31 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.140665E+10 | 0.364881E+09 | 140.40 | 0.118683E+10 | 0.219819E+09 | 0.00 | 1.00 | 26-APR-08:62 | 0.00 | 01-APR-00:10 | 18750.11 | 26-APR-08:62 | 15205.95 | 30-APR-17:07 | 6677.07 | 27-APR-08:62 | 3918.53 | 26-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.107645E+10 | 0.280832E+09 | 145.60 | 0.904346E+09 | 0.172101E+09 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 18697.41 | 03-MAY-08:62 | 17248.71 | 24-MAY-08:62 | 5718.09 | 03-MAY-08:62 | 3858.25 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.318088E+10 | 0.808146E+09 | 229.63 | 0.239731E+10 | 0.783571E+09 | 0.00 | 1.00 | 03-JUN-08:62 | 0.00 | 01-JUN-00:10 | 19160.37 | 30-JUN-08:62 | 14433.97 | 23-JUN-08:62 | 8601.78 | 28-JUN-08:62 | 3932.34 | 30-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.711542E+10 | 0.176118E+10 | 332.79 | 0.500493E+10 | 0.211049E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 19605.93 | 19-JUL-08:62 | 14334.21 | 10-JUL-08:62 | 10061.27 | 19-JUL-20:34 | 4070.61 | 23-JUL-17:02 | 0.00 | 01-JUL-00:05 |
August | 0.768767E+10 | 0.189658E+10 | 331.44 | 0.531199E+10 | 0.237568E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 19755.65 | 14-AUG-08:62 | 14208.47 | 19-AUG-18:08 | 9280.96 | 06-AUG-19:12 | 4094.06 | 14-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.431085E+10 | 0.110473E+10 | 258.07 | 0.326183E+10 | 0.104903E+10 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:10 | 19692.45 | 21-SEP-20:52 | 18153.34 | 30-SEP-08:61 | 9872.07 | 21-SEP-20:02 | 4314.91 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.539621E+10 | 0.139123E+10 | 286.78 | 0.450139E+10 | 0.894817E+09 | 0.00 | 1.00 | 01-OCT-07:03 | 0.00 | 01-OCT-00:10 | 19623.90 | 01-OCT-07:03 | 17825.28 | 17-OCT-08:62 | 10151.91 | 01-OCT-07:03 | 4197.89 | 16-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.790882E+09 | 0.207355E+09 | 88.72 | 0.761276E+09 | 29606733.80 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 18442.20 | 10-NOV-09:02 | 16339.30 | 28-NOV-09:02 | 5190.34 | 10-NOV-09:02 | 3811.72 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.108142E+10 | 0.283951E+09 | 118.80 | 0.107136E+10 | 10060199.53 | 0.00 | 1.00 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 17617.12 | 05-DEC-09:02 | 17617.12 | 05-DEC-09:02 | 747.17 | 07-DEC-13:40 | 3848.60 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.335969E+11 | 0.850616E+10 | 2126.71 | 0.258320E+11 | 0.776490E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.242634E+09 | 63723013.66 | 48.50 | 0.233652E+09 | 8981935.80 | 0.00 | 0.42 | 0.00 | 6642.65 | 6051.08 | 747.17 | 1671.31 | 0.00 | |||||||
Maximum of Months | 0.768767E+10 | 0.189658E+10 | 332.79 | 0.531199E+10 | 0.237568E+10 | 0.00 | 1.00 | 0.00 | 19755.65 | 18153.34 | 10151.91 | 4314.91 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.736356E+09 | 0.195290E+09 | 78.82 | 0.704135E+09 | 32220818.67 | 0.00 | 0.78 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 | 12991.91 | 21-JAN-08:62 | 7640.52 | 21-JAN-08:62 | 5351.39 | 21-JAN-08:62 | 2887.55 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.177844E+09 | 47186647.77 | 40.72 | 0.175844E+09 | 2000083.78 | 0.00 | 0.39 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 5813.01 | 01-FEB-12:10 | 5813.01 | 01-FEB-12:10 | 468.33 | 01-FEB-13:40 | 1563.78 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.378516E+09 | 99412150.90 | 50.58 | 0.325939E+09 | 52577101.08 | 0.00 | 0.39 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 6162.99 | 23-MAR-14:00 | 5775.75 | 11-MAR-14:00 | 1420.72 | 22-MAR-13:00 | 1562.45 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.116753E+10 | 0.305729E+09 | 119.76 | 0.991052E+09 | 0.176479E+09 | 0.00 | 1.00 | 27-APR-07:03 | 0.00 | 01-APR-00:10 | 18471.80 | 27-APR-07:03 | 11363.23 | 27-APR-07:03 | 7108.57 | 27-APR-07:03 | 3817.24 | 27-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.873828E+09 | 0.229265E+09 | 124.51 | 0.737226E+09 | 0.136601E+09 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18549.75 | 03-MAY-07:03 | 13928.02 | 04-MAY-07:03 | 6493.25 | 03-MAY-07:03 | 3831.71 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.283800E+10 | 0.726638E+09 | 219.16 | 0.214380E+10 | 0.694201E+09 | 0.00 | 1.00 | 15-JUN-07:03 | 0.00 | 01-JUN-00:10 | 19009.67 | 30-JUN-07:02 | 13896.29 | 25-JUN-08:62 | 8917.36 | 29-JUN-07:02 | 3909.53 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.605206E+10 | 0.152105E+10 | 310.30 | 0.430434E+10 | 0.174772E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 19581.56 | 23-JUL-08:62 | 14036.36 | 04-JUL-08:62 | 9453.06 | 20-JUL-07:03 | 4078.44 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.677911E+10 | 0.169339E+10 | 311.11 | 0.472632E+10 | 0.205280E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19569.32 | 19-AUG-07:02 | 13104.39 | 06-AUG-08:62 | 9660.69 | 18-AUG-07:02 | 4012.03 | 13-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.372250E+10 | 0.966826E+09 | 243.94 | 0.283849E+10 | 0.884009E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 19507.35 | 22-SEP-07:02 | 18141.76 | 29-SEP-07:02 | 9305.62 | 22-SEP-07:02 | 3978.21 | 22-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.452397E+10 | 0.119386E+10 | 260.94 | 0.383364E+10 | 0.690331E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 19595.64 | 05-OCT-07:01 | 17669.03 | 16-OCT-07:02 | 9064.42 | 05-OCT-07:03 | 4290.59 | 15-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.669787E+09 | 0.176778E+09 | 78.36 | 0.652072E+09 | 17715757.18 | 0.00 | 1.00 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 | 17789.68 | 19-NOV-09:02 | 17789.68 | 19-NOV-09:02 | 5655.35 | 10-NOV-08:62 | 3885.56 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.942843E+09 | 0.249562E+09 | 116.44 | 0.936325E+09 | 6517785.39 | 0.00 | 0.46 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 6763.69 | 19-DEC-13:10 | 6763.69 | 19-DEC-13:10 | 697.93 | 07-DEC-13:50 | 1783.63 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.288623E+11 | 0.740499E+10 | 1954.65 | 0.223692E+11 | 0.649317E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.177844E+09 | 47186647.77 | 40.72 | 0.175844E+09 | 2000083.78 | 0.00 | 0.39 | 0.00 | 5813.01 | 5775.75 | 468.33 | 1562.45 | 0.00 | |||||||
Maximum of Months | 0.677911E+10 | 0.169339E+10 | 311.11 | 0.472632E+10 | 0.205280E+10 | 0.00 | 1.00 | 0.00 | 19595.64 | 18141.76 | 9660.69 | 4290.59 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.705061E+09 | 0.187436E+09 | 69.69 | 0.675121E+09 | 29940531.28 | 0.00 | 0.70 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 | 11422.89 | 21-JAN-08:62 | 6709.00 | 21-JAN-08:62 | 4713.89 | 21-JAN-08:62 | 2600.86 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.168126E+09 | 44668765.72 | 37.22 | 0.166665E+09 | 1461456.11 | 0.00 | 0.39 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 5683.46 | 01-FEB-12:10 | 5683.46 | 01-FEB-12:10 | 440.75 | 01-FEB-13:40 | 1532.71 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.355514E+09 | 93550196.54 | 43.25 | 0.306336E+09 | 49178670.98 | 0.00 | 0.39 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 6051.26 | 23-MAR-14:00 | 5620.39 | 11-MAR-14:00 | 1379.69 | 22-MAR-13:00 | 1537.25 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.111250E+10 | 0.291807E+09 | 114.81 | 0.944531E+09 | 0.167970E+09 | 0.00 | 1.00 | 27-APR-07:03 | 0.00 | 01-APR-00:10 | 18519.40 | 27-APR-07:03 | 11381.77 | 27-APR-07:03 | 7137.63 | 27-APR-07:03 | 3827.13 | 27-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.827561E+09 | 0.217381E+09 | 119.50 | 0.698945E+09 | 0.128616E+09 | 0.00 | 1.00 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 18598.24 | 03-MAY-07:03 | 13578.10 | 04-MAY-07:03 | 6520.67 | 03-MAY-07:03 | 3841.77 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.277504E+10 | 0.711384E+09 | 216.64 | 0.209562E+10 | 0.679424E+09 | 0.00 | 1.00 | 16-JUN-07:03 | 0.00 | 01-JUN-00:10 | 19060.79 | 30-JUN-07:02 | 13921.88 | 25-JUN-08:62 | 8948.68 | 29-JUN-07:02 | 3920.07 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.598874E+10 | 0.150660E+10 | 309.03 | 0.425989E+10 | 0.172885E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 19634.53 | 23-JUL-08:62 | 14068.00 | 04-JUL-08:62 | 9404.13 | 20-JUL-07:02 | 4089.50 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.671829E+10 | 0.167989E+10 | 309.92 | 0.468530E+10 | 0.203299E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19622.39 | 19-AUG-07:02 | 13131.53 | 06-AUG-08:62 | 9690.35 | 18-AUG-07:02 | 4022.81 | 13-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.365813E+10 | 0.951507E+09 | 241.79 | 0.279234E+10 | 0.865789E+09 | 0.00 | 1.00 | 01-SEP-07:03 | 0.00 | 01-SEP-00:10 | 19559.37 | 22-SEP-07:02 | 18189.73 | 29-SEP-07:02 | 9335.63 | 22-SEP-07:02 | 3988.90 | 22-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.448394E+10 | 0.118440E+10 | 260.10 | 0.380049E+10 | 0.683449E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 19649.41 | 05-OCT-07:01 | 17721.26 | 16-OCT-07:03 | 9090.09 | 05-OCT-07:03 | 4302.75 | 15-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.642902E+09 | 0.170037E+09 | 73.79 | 0.626944E+09 | 15957816.94 | 0.00 | 1.00 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 | 17831.65 | 19-NOV-09:02 | 17831.65 | 19-NOV-09:02 | 5085.35 | 10-NOV-08:62 | 3894.78 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.890728E+09 | 0.236395E+09 | 107.14 | 0.884742E+09 | 5985863.01 | 0.00 | 0.46 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 6635.34 | 19-DEC-13:10 | 6635.34 | 19-DEC-13:10 | 678.59 | 07-DEC-13:50 | 1754.18 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.283265E+11 | 0.727506E+10 | 1902.89 | 0.219369E+11 | 0.638961E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.168126E+09 | 44668765.72 | 37.22 | 0.166665E+09 | 1461456.11 | 0.00 | 0.39 | 0.00 | 5683.46 | 5620.39 | 440.75 | 1532.71 | 0.00 | |||||||
Maximum of Months | 0.671829E+10 | 0.167989E+10 | 309.92 | 0.468530E+10 | 0.203299E+10 | 0.00 | 1.00 | 0.00 | 19649.41 | 18189.73 | 9690.35 | 4302.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.645394E+09 | 0.172291E+09 | 67.86 | 0.619277E+09 | 26117164.59 | 0.00 | 0.51 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 | 7877.86 | 21-JAN-08:62 | 6316.11 | 18-JAN-13:10 | 3267.10 | 21-JAN-08:62 | 1894.41 | 21-JAN-08:62 | 0.00 | 01-JAN-00:10 |
February | 0.151064E+09 | 40260327.21 | 33.31 | 0.150116E+09 | 948418.51 | 0.00 | 0.37 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 5398.15 | 01-FEB-12:10 | 5398.15 | 01-FEB-12:10 | 391.39 | 01-FEB-13:40 | 1461.88 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.314746E+09 | 83120914.55 | 42.42 | 0.271372E+09 | 43374523.10 | 0.00 | 0.37 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 | 5783.90 | 23-MAR-14:00 | 5302.27 | 11-MAR-14:00 | 1292.20 | 22-MAR-13:00 | 1474.60 | 23-MAR-14:00 | 0.00 | 01-MAR-00:10 |
April | 0.101400E+10 | 0.266742E+09 | 110.47 | 0.860929E+09 | 0.153075E+09 | 0.00 | 0.87 | 27-APR-07:03 | 0.00 | 01-APR-00:10 | 15381.75 | 27-APR-07:03 | 9425.17 | 27-APR-07:03 | 5956.58 | 27-APR-07:03 | 3314.02 | 27-APR-07:03 | 0.00 | 01-APR-00:10 |
May | 0.738715E+09 | 0.194537E+09 | 111.44 | 0.624891E+09 | 0.113824E+09 | 0.00 | 0.96 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 | 17444.23 | 03-MAY-07:03 | 11515.75 | 04-MAY-07:03 | 6149.86 | 03-MAY-07:03 | 3653.82 | 03-MAY-07:03 | 0.00 | 01-MAY-00:10 |
June | 0.260814E+10 | 0.670360E+09 | 212.72 | 0.196704E+10 | 0.641100E+09 | 0.00 | 1.00 | 19-JUN-07:03 | 0.00 | 01-JUN-00:10 | 18921.52 | 30-JUN-07:02 | 13784.35 | 25-JUN-08:62 | 8914.77 | 29-JUN-07:02 | 3891.64 | 30-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.574703E+10 | 0.144889E+10 | 304.92 | 0.408207E+10 | 0.166495E+10 | 0.00 | 1.00 | 01-JUL-07:02 | 0.00 | 01-JUL-00:05 | 19491.37 | 23-JUL-08:62 | 13931.43 | 04-JUL-08:62 | 9374.43 | 20-JUL-07:02 | 4060.14 | 23-JUL-08:62 | 0.00 | 01-JUL-00:05 |
August | 0.646582E+10 | 0.162035E+10 | 307.41 | 0.450422E+10 | 0.196160E+10 | 0.00 | 1.00 | 01-AUG-07:02 | 0.00 | 01-AUG-00:10 | 19479.69 | 19-AUG-07:02 | 12997.77 | 06-AUG-08:62 | 9657.19 | 18-AUG-07:02 | 3993.79 | 13-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.347151E+10 | 0.905887E+09 | 237.55 | 0.265550E+10 | 0.816015E+09 | 0.00 | 1.00 | 06-SEP-07:02 | 0.00 | 01-SEP-00:10 | 19415.14 | 22-SEP-07:02 | 18053.97 | 29-SEP-07:02 | 9302.85 | 22-SEP-07:02 | 3959.95 | 22-SEP-07:02 | 0.00 | 01-SEP-00:10 |
October | 0.429822E+10 | 0.113861E+10 | 256.96 | 0.364826E+10 | 0.649954E+09 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 19507.05 | 05-OCT-07:01 | 17586.44 | 16-OCT-07:02 | 9060.84 | 05-OCT-07:03 | 4267.70 | 15-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.594438E+09 | 0.157777E+09 | 71.85 | 0.581119E+09 | 13318923.84 | 0.00 | 0.98 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 | 17236.76 | 19-NOV-09:02 | 17236.76 | 19-NOV-09:02 | 3723.15 | 10-NOV-08:62 | 3789.36 | 19-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 0.802815E+09 | 0.213914E+09 | 106.47 | 0.797435E+09 | 5380590.52 | 0.00 | 0.44 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 6377.07 | 19-DEC-13:10 | 6377.07 | 19-DEC-13:10 | 636.16 | 07-DEC-13:50 | 1692.07 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.268519E+11 | 0.691274E+10 | 1863.37 | 0.207622E+11 | 0.608966E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.151064E+09 | 40260327.21 | 33.31 | 0.150116E+09 | 948418.51 | 0.00 | 0.37 | 0.00 | 5398.15 | 5302.27 | 391.39 | 1461.88 | 0.00 | |||||||
Maximum of Months | 0.646582E+10 | 0.162035E+10 | 307.41 | 0.450422E+10 | 0.196160E+10 | 0.00 | 1.00 | 0.00 | 19507.05 | 18053.97 | 9657.19 | 4267.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.100730E+10 | 0.278035E+09 | 54.14 | 0.965867E+09 | 41429473.42 | 0.00 | 0.46 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 | 12630.32 | 20-JAN-09:02 | 10974.73 | 14-JAN-15:00 | 4293.56 | 21-JAN-09:02 | 3176.13 | 20-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.233513E+09 | 64372015.55 | 19.75 | 0.232121E+09 | 1392377.59 | 0.00 | 0.35 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 9083.46 | 01-FEB-12:10 | 9083.46 | 01-FEB-12:10 | 627.88 | 01-FEB-13:40 | 2547.62 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.482966E+09 | 0.131676E+09 | 32.00 | 0.415301E+09 | 67664773.88 | 0.00 | 0.36 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 10041.14 | 23-MAR-14:10 | 8547.31 | 11-MAR-14:00 | 2448.49 | 23-MAR-14:50 | 2638.93 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.165476E+10 | 0.448919E+09 | 95.06 | 0.139447E+10 | 0.260288E+09 | 0.00 | 1.00 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 33336.47 | 27-APR-08:62 | 21298.72 | 27-APR-08:62 | 12037.74 | 27-APR-08:62 | 7090.65 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.117018E+10 | 0.317572E+09 | 94.54 | 0.987228E+09 | 0.182953E+09 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 33560.17 | 03-MAY-08:62 | 25301.60 | 04-MAY-08:62 | 10525.15 | 03-MAY-08:62 | 7132.08 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.430292E+10 | 0.114034E+10 | 187.93 | 0.322677E+10 | 0.107614E+10 | 0.00 | 1.00 | 17-JUN-08:62 | 0.00 | 01-JUN-00:10 | 34255.65 | 30-JUN-08:62 | 27019.40 | 25-JUN-09:02 | 15663.28 | 28-JUN-08:62 | 7262.64 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.969977E+10 | 0.251567E+10 | 282.91 | 0.682187E+10 | 0.287790E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 35540.15 | 30-JUL-09:02 | 27408.26 | 04-JUL-09:02 | 16592.65 | 20-JUL-08:62 | 7705.88 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 |
August | 0.109106E+11 | 0.281277E+10 | 282.46 | 0.754317E+10 | 0.336744E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 35477.10 | 14-AUG-08:62 | 24562.19 | 23-AUG-08:62 | 16219.15 | 25-AUG-08:62 | 7607.52 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.587039E+10 | 0.157881E+10 | 213.09 | 0.448935E+10 | 0.138103E+10 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 35529.83 | 22-SEP-08:62 | 32832.60 | 29-SEP-08:62 | 16846.65 | 22-SEP-08:62 | 7987.91 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.718503E+10 | 0.196127E+10 | 235.11 | 0.610505E+10 | 0.107998E+10 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 35270.80 | 01-OCT-09:02 | 32086.25 | 17-OCT-08:62 | 16451.96 | 05-OCT-08:03 | 8390.56 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.932209E+09 | 0.255727E+09 | 53.09 | 0.912668E+09 | 19541129.46 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 32407.28 | 19-NOV-10:02 | 32407.28 | 19-NOV-10:02 | 4027.50 | 10-NOV-09:02 | 7488.02 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.122221E+10 | 0.336861E+09 | 86.93 | 0.121384E+10 | 8377229.30 | 0.00 | 0.89 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 27177.19 | 05-DEC-09:02 | 27177.19 | 05-DEC-09:02 | 1105.94 | 07-DEC-14:00 | 6333.37 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.446719E+11 | 0.118420E+11 | 1637.02 | 0.343077E+11 | 0.103641E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.233513E+09 | 64372015.55 | 19.75 | 0.232121E+09 | 1392377.59 | 0.00 | 0.35 | 0.00 | 9083.46 | 8547.31 | 627.88 | 2547.62 | 0.00 | |||||||
Maximum of Months | 0.109106E+11 | 0.281277E+10 | 282.91 | 0.754317E+10 | 0.336744E+10 | 0.00 | 1.00 | 0.00 | 35540.15 | 32832.60 | 16846.65 | 8390.56 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.513820E+09 | 0.137805E+09 | 54.85 | 0.493215E+09 | 20605344.10 | 0.00 | 0.42 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5691.42 | 14-JAN-15:00 | 5691.42 | 14-JAN-15:00 | 1520.33 | 21-JAN-09:02 | 1534.27 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.117354E+09 | 31435171.08 | 19.88 | 0.116702E+09 | 652685.12 | 0.00 | 0.34 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4659.06 | 01-FEB-12:10 | 4659.06 | 01-FEB-12:10 | 308.05 | 01-FEB-13:40 | 1270.03 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.239601E+09 | 63490056.96 | 30.83 | 0.206082E+09 | 33519508.82 | 0.00 | 0.36 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 5165.18 | 23-MAR-14:10 | 4383.73 | 11-MAR-14:00 | 1254.42 | 23-MAR-14:50 | 1319.01 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.832089E+09 | 0.219365E+09 | 94.37 | 0.701699E+09 | 0.130390E+09 | 0.00 | 0.90 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 15003.41 | 27-APR-08:62 | 9586.34 | 27-APR-08:62 | 5417.07 | 27-APR-08:62 | 3203.69 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.584834E+09 | 0.154215E+09 | 92.35 | 0.494282E+09 | 90551826.03 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17368.70 | 03-MAY-08:62 | 13097.78 | 04-MAY-08:62 | 5443.53 | 03-MAY-08:62 | 3584.76 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.219407E+10 | 0.565005E+09 | 186.89 | 0.164690E+10 | 0.547166E+09 | 0.00 | 1.00 | 17-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17727.71 | 30-JUN-08:62 | 13980.56 | 25-JUN-09:02 | 8101.42 | 28-JUN-08:62 | 3650.39 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.499218E+10 | 0.125804E+10 | 283.10 | 0.351671E+10 | 0.147547E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 18394.08 | 30-JUL-09:02 | 14188.19 | 04-JUL-09:02 | 8592.25 | 20-JUL-08:62 | 3873.28 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 |
August | 0.562642E+10 | 0.140924E+10 | 282.58 | 0.389665E+10 | 0.172977E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18363.23 | 14-AUG-08:62 | 12715.20 | 23-AUG-08:62 | 8391.34 | 25-AUG-08:62 | 3823.82 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.300810E+10 | 0.786221E+09 | 212.55 | 0.230465E+10 | 0.703450E+09 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18390.71 | 22-SEP-08:62 | 16919.64 | 29-SEP-08:62 | 8723.82 | 22-SEP-08:62 | 4014.41 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.371326E+10 | 0.984528E+09 | 235.45 | 0.315809E+10 | 0.555170E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 18257.77 | 01-OCT-09:02 | 16600.02 | 17-OCT-08:62 | 8512.66 | 05-OCT-08:03 | 4212.75 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.478365E+09 | 0.127481E+09 | 53.87 | 0.468630E+09 | 9734845.10 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 16758.18 | 19-NOV-10:02 | 16758.18 | 19-NOV-10:02 | 1588.26 | 10-NOV-09:02 | 3761.13 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.620130E+09 | 0.166078E+09 | 85.02 | 0.615867E+09 | 4263945.55 | 0.00 | 0.81 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 12432.21 | 05-DEC-09:02 | 12432.21 | 05-DEC-09:02 | 569.03 | 07-DEC-14:00 | 2888.49 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.229202E+11 | 0.590291E+10 | 1631.73 | 0.176195E+11 | 0.530075E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.117354E+09 | 31435171.08 | 19.88 | 0.116702E+09 | 652685.12 | 0.00 | 0.34 | 0.00 | 4659.06 | 4383.73 | 308.05 | 1270.03 | 0.00 | |||||||
Maximum of Months | 0.562642E+10 | 0.140924E+10 | 283.10 | 0.389665E+10 | 0.172977E+10 | 0.00 | 1.00 | 0.00 | 18394.08 | 16919.64 | 8723.82 | 4212.75 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.493525E+09 | 0.132579E+09 | 53.17 | 0.474103E+09 | 19421942.99 | 0.00 | 0.41 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5571.52 | 18-JAN-13:10 | 5571.52 | 18-JAN-13:10 | 1034.71 | 20-JAN-09:02 | 1503.52 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.111526E+09 | 29921715.73 | 18.79 | 0.110943E+09 | 583413.39 | 0.00 | 0.34 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4533.97 | 01-FEB-12:10 | 4533.97 | 01-FEB-12:10 | 284.06 | 01-FEB-13:40 | 1238.33 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.226478E+09 | 60105498.77 | 29.17 | 0.194869E+09 | 31609533.70 | 0.00 | 0.35 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 5040.78 | 23-MAR-14:10 | 4268.12 | 11-MAR-14:00 | 1222.60 | 23-MAR-14:40 | 1289.51 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.800959E+09 | 0.211403E+09 | 91.26 | 0.675296E+09 | 0.125662E+09 | 0.00 | 0.82 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 13272.42 | 27-APR-08:62 | 8469.04 | 27-APR-08:62 | 4803.38 | 27-APR-08:62 | 2906.89 | 27-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.559155E+09 | 0.147555E+09 | 90.64 | 0.472665E+09 | 86489308.53 | 0.00 | 1.00 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 17291.73 | 03-MAY-08:62 | 12458.05 | 04-MAY-08:62 | 5434.79 | 03-MAY-08:62 | 3568.93 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.213882E+10 | 0.551234E+09 | 185.49 | 0.160430E+10 | 0.534523E+09 | 0.00 | 1.00 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 | 17649.87 | 30-JUN-08:62 | 13903.17 | 25-JUN-09:02 | 8078.40 | 28-JUN-08:62 | 3634.26 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.491303E+10 | 0.123897E+10 | 282.01 | 0.345852E+10 | 0.145450E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 18313.04 | 30-JUL-09:02 | 14110.09 | 04-JUL-09:02 | 8564.18 | 20-JUL-08:62 | 3856.42 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 |
August | 0.554534E+10 | 0.138994E+10 | 282.13 | 0.383825E+10 | 0.170709E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18282.31 | 14-AUG-08:62 | 12645.42 | 23-AUG-08:62 | 8366.78 | 25-AUG-08:62 | 3807.15 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.294751E+10 | 0.771231E+09 | 209.99 | 0.225990E+10 | 0.687609E+09 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18308.88 | 22-SEP-08:62 | 16812.41 | 29-SEP-08:62 | 8695.74 | 22-SEP-08:62 | 3996.54 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.365148E+10 | 0.969127E+09 | 234.42 | 0.310707E+10 | 0.544407E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 18177.40 | 01-OCT-09:02 | 16520.44 | 17-OCT-08:62 | 8488.22 | 05-OCT-08:03 | 4192.99 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.460454E+09 | 0.122904E+09 | 53.31 | 0.451465E+09 | 8988936.44 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 16670.87 | 19-NOV-10:02 | 16670.87 | 19-NOV-10:02 | 1159.72 | 10-NOV-09:02 | 3742.08 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.589528E+09 | 0.158167E+09 | 84.18 | 0.585469E+09 | 4059118.97 | 0.00 | 0.72 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 | 10745.90 | 05-DEC-09:02 | 10745.90 | 05-DEC-09:02 | 554.60 | 07-DEC-14:00 | 2564.98 | 05-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.224378E+11 | 0.578314E+10 | 1614.55 | 0.172329E+11 | 0.520495E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.111526E+09 | 29921715.73 | 18.79 | 0.110943E+09 | 583413.39 | 0.00 | 0.34 | 0.00 | 4533.97 | 4268.12 | 284.06 | 1238.33 | 0.00 | |||||||
Maximum of Months | 0.554534E+10 | 0.138994E+10 | 282.13 | 0.383825E+10 | 0.170709E+10 | 0.00 | 1.00 | 0.00 | 18313.04 | 16812.41 | 8695.74 | 4192.99 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.445354E+09 | 0.120103E+09 | 51.42 | 0.429021E+09 | 16332788.16 | 0.00 | 0.39 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 | 5329.30 | 18-JAN-13:10 | 5329.30 | 18-JAN-13:10 | 724.69 | 17-JAN-14:00 | 1441.61 | 14-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 96470806.28 | 25984993.09 | 16.00 | 96050991.10 | 419815.18 | 0.00 | 0.32 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4241.50 | 01-FEB-12:10 | 4241.50 | 01-FEB-12:10 | 230.08 | 01-FEB-13:40 | 1164.17 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.198317E+09 | 52827389.69 | 26.50 | 0.171033E+09 | 27283781.52 | 0.00 | 0.33 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 4745.53 | 23-MAR-14:10 | 4026.10 | 11-MAR-14:00 | 1143.47 | 23-MAR-14:40 | 1219.53 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.728286E+09 | 0.192791E+09 | 86.21 | 0.614475E+09 | 0.113811E+09 | 0.00 | 0.51 | 27-APR-08:62 | 0.00 | 01-APR-00:10 | 7393.85 | 27-APR-08:62 | 6274.80 | 26-APR-13:00 | 2692.55 | 27-APR-08:62 | 1830.90 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.496388E+09 | 0.131332E+09 | 83.77 | 0.420411E+09 | 75977593.37 | 0.00 | 0.78 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 | 12426.84 | 03-MAY-08:62 | 8970.42 | 04-MAY-08:62 | 3935.20 | 03-MAY-08:62 | 2755.32 | 03-MAY-08:62 | 0.00 | 01-MAY-00:10 |
June | 0.199943E+10 | 0.516548E+09 | 181.07 | 0.149848E+10 | 0.500948E+09 | 0.00 | 1.00 | 21-JUN-08:62 | 0.00 | 01-JUN-00:10 | 17530.02 | 30-JUN-08:62 | 13779.25 | 25-JUN-09:02 | 7945.06 | 28-JUN-08:62 | 3607.48 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.473787E+10 | 0.119682E+10 | 278.25 | 0.333356E+10 | 0.140431E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 18188.33 | 30-JUL-09:02 | 13988.61 | 04-JUL-09:02 | 8532.56 | 20-JUL-08:62 | 3830.88 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 |
August | 0.536716E+10 | 0.134766E+10 | 279.69 | 0.371374E+10 | 0.165342E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 18157.45 | 14-AUG-08:62 | 12261.64 | 13-AUG-09:02 | 8344.29 | 25-AUG-08:62 | 3781.80 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.279430E+10 | 0.733513E+09 | 204.76 | 0.214979E+10 | 0.644505E+09 | 0.00 | 1.00 | 06-SEP-08:62 | 0.00 | 01-SEP-00:10 | 18181.58 | 22-SEP-08:62 | 16640.68 | 30-SEP-08:61 | 8663.10 | 22-SEP-08:62 | 3968.78 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.349456E+10 | 0.930119E+09 | 230.33 | 0.297950E+10 | 0.515061E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 18054.26 | 01-OCT-09:02 | 16390.06 | 17-OCT-08:62 | 8463.53 | 05-OCT-08:03 | 4161.69 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.414599E+09 | 0.111127E+09 | 50.38 | 0.407680E+09 | 6918997.66 | 0.00 | 1.00 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 16520.44 | 19-NOV-10:02 | 16520.44 | 19-NOV-10:02 | 652.06 | 10-NOV-13:10 | 3709.86 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.516847E+09 | 0.139288E+09 | 76.34 | 0.513386E+09 | 3460671.57 | 0.00 | 0.41 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 5429.80 | 05-DEC-09:02 | 5429.80 | 05-DEC-09:02 | 509.44 | 07-DEC-14:00 | 1442.80 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.212896E+11 | 0.549811E+10 | 1564.73 | 0.163271E+11 | 0.496245E+10 | 0.00 | ||||||||||||||
Minimum of Months | 96470806.28 | 25984993.09 | 16.00 | 96050991.10 | 419815.18 | 0.00 | 0.32 | 0.00 | 4241.50 | 4026.10 | 230.08 | 1164.17 | 0.00 | |||||||
Maximum of Months | 0.536716E+10 | 0.134766E+10 | 279.69 | 0.371374E+10 | 0.165342E+10 | 0.00 | 1.00 | 0.00 | 18188.33 | 16640.68 | 8663.10 | 4161.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.419722E+09 | 0.113787E+09 | 45.67 | 0.405415E+09 | 14306286.34 | 0.00 | 0.37 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 | 5409.33 | 18-JAN-13:10 | 5409.33 | 18-JAN-13:10 | 699.89 | 17-JAN-14:00 | 1466.17 | 18-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 85404090.83 | 23148760.20 | 13.83 | 85104944.65 | 299146.18 | 0.00 | 0.31 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 | 4434.31 | 01-FEB-12:10 | 4434.31 | 01-FEB-12:10 | 210.67 | 01-FEB-13:30 | 1220.20 | 01-FEB-12:10 | 0.00 | 01-FEB-00:10 |
March | 0.199848E+09 | 53361475.84 | 25.33 | 0.172762E+09 | 27086044.57 | 0.00 | 0.31 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 | 4763.39 | 23-MAR-14:10 | 4109.77 | 11-MAR-13:50 | 1125.64 | 23-MAR-14:20 | 1231.41 | 23-MAR-14:10 | 0.00 | 01-MAR-00:10 |
April | 0.770908E+09 | 0.204189E+09 | 85.49 | 0.652873E+09 | 0.118035E+09 | 0.00 | 0.48 | 26-APR-13:00 | 0.00 | 01-APR-00:10 | 7526.89 | 26-APR-13:00 | 6832.14 | 26-APR-13:00 | 1154.86 | 25-APR-13:00 | 1990.04 | 26-APR-13:00 | 0.00 | 01-APR-00:10 |
May | 0.503897E+09 | 0.133496E+09 | 78.48 | 0.428334E+09 | 75562620.39 | 0.00 | 0.40 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 | 6181.87 | 04-MAY-12:10 | 5437.24 | 04-MAY-12:10 | 953.42 | 04-MAY-13:00 | 1589.27 | 04-MAY-12:10 | 0.00 | 01-MAY-00:10 |
June | 0.206600E+10 | 0.534829E+09 | 176.09 | 0.155441E+10 | 0.511599E+09 | 0.00 | 1.00 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 | 18938.86 | 30-JUN-08:62 | 14933.02 | 25-JUN-09:02 | 6543.46 | 30-JUN-08:62 | 3896.82 | 25-JUN-09:02 | 0.00 | 01-JUN-00:10 |
July | 0.507288E+10 | 0.128194E+10 | 273.38 | 0.359238E+10 | 0.148050E+10 | 0.00 | 1.00 | 01-JUL-08:62 | 0.00 | 01-JUL-00:05 | 19641.21 | 30-JUL-09:02 | 15191.15 | 04-JUL-09:02 | 9285.05 | 20-JUL-08:62 | 4139.99 | 23-JUL-09:02 | 0.00 | 01-JUL-00:05 |
August | 0.573899E+10 | 0.144147E+10 | 277.02 | 0.399566E+10 | 0.174333E+10 | 0.00 | 1.00 | 03-AUG-08:62 | 0.00 | 01-AUG-00:10 | 19612.90 | 14-AUG-08:62 | 13278.10 | 13-AUG-09:02 | 8814.67 | 18-AUG-08:62 | 4086.20 | 13-AUG-09:02 | 0.00 | 01-AUG-00:10 |
September | 0.280425E+10 | 0.739544E+09 | 193.39 | 0.217978E+10 | 0.624470E+09 | 0.00 | 1.00 | 10-SEP-09:02 | 0.00 | 01-SEP-00:10 | 19645.23 | 22-SEP-08:62 | 17972.17 | 30-SEP-08:61 | 9472.43 | 22-SEP-08:62 | 4264.66 | 29-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 0.347262E+10 | 0.930745E+09 | 216.57 | 0.300093E+10 | 0.471693E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 19507.35 | 01-OCT-09:02 | 17549.08 | 17-OCT-08:62 | 9195.01 | 05-OCT-08:62 | 4491.58 | 15-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.387734E+09 | 0.104543E+09 | 47.10 | 0.383473E+09 | 4260646.53 | 0.00 | 0.99 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 | 17369.36 | 19-NOV-10:02 | 17369.36 | 19-NOV-10:02 | 516.76 | 10-NOV-13:10 | 3930.10 | 19-NOV-10:02 | 0.00 | 01-NOV-00:10 |
December | 0.465582E+09 | 0.126179E+09 | 63.18 | 0.463027E+09 | 2555965.03 | 0.00 | 0.39 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 | 5494.02 | 19-DEC-13:10 | 5494.02 | 19-DEC-13:10 | 424.88 | 07-DEC-14:00 | 1480.53 | 19-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.219878E+11 | 0.568724E+10 | 1495.54 | 0.169141E+11 | 0.507370E+10 | 0.00 | ||||||||||||||
Minimum of Months | 85404090.83 | 23148760.20 | 13.83 | 85104944.65 | 299146.18 | 0.00 | 0.31 | 0.00 | 4434.31 | 4109.77 | 210.67 | 1220.20 | 0.00 | |||||||
Maximum of Months | 0.573899E+10 | 0.144147E+10 | 277.02 | 0.399566E+10 | 0.174333E+10 | 0.00 | 1.00 | 0.00 | 19645.23 | 17972.17 | 9472.43 | 4491.58 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.53 | 56.29 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.22 | 52.39 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.90 | 53.65 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.16 | 45.68 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.13 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.94 | 32.59 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.11 | 28.55 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.86 | 29.61 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.35 | 34.57 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.31 | 37.21 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.62 | 52.43 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.65 | 43.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.94 | 28.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.53 | 56.29 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.22 | 52.39 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.90 | 53.65 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.16 | 45.68 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.13 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.94 | 32.59 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.11 | 28.55 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.86 | 29.61 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.35 | 34.57 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.31 | 37.21 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.62 | 52.43 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.65 | 43.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.94 | 28.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.53 | 56.29 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.22 | 52.39 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.90 | 53.65 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.16 | 45.68 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.13 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.94 | 32.59 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.11 | 28.55 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.86 | 29.61 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.35 | 34.57 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.31 | 37.21 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.62 | 52.43 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.65 | 43.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.94 | 28.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.53 | 56.29 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.22 | 52.39 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.90 | 53.65 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.16 | 45.68 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.13 | 41.97 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.94 | 32.59 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.11 | 28.55 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.86 | 29.61 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.35 | 34.57 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.31 | 37.21 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.62 | 52.43 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.65 | 43.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.94 | 28.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.16 | 56.57 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.66 | 84.84 | 30.82 | 172.60 | 67.00 | 0.00 | 0.00 | 0.00 |
February | 90.90 | 55.99 | 34.91 | 128.03 | 62.27 | 0.00 | 0.00 | 0.00 |
March | 72.47 | 35.01 | 37.46 | 101.14 | 63.73 | 0.00 | 0.00 | 0.00 |
April | 60.55 | 23.09 | 37.46 | 89.30 | 54.38 | 0.00 | 0.00 | 0.00 |
May | 43.12 | 5.31 | 37.81 | 50.90 | 49.89 | 0.00 | 0.00 | 0.00 |
June | 37.83 | 2.28 | 35.54 | 44.54 | 38.83 | 0.00 | 0.00 | 0.00 |
July | 40.07 | 4.51 | 35.56 | 55.43 | 34.07 | 0.00 | 0.00 | 0.00 |
August | 51.47 | 16.24 | 35.24 | 82.75 | 35.30 | 0.00 | 0.00 | 0.00 |
September | 71.63 | 36.30 | 35.33 | 115.83 | 41.23 | 0.00 | 0.00 | 0.00 |
October | 91.09 | 60.90 | 30.19 | 148.21 | 44.36 | 0.00 | 0.00 | 0.00 |
November | 110.71 | 78.16 | 32.55 | 164.41 | 62.42 | 0.00 | 0.00 | 0.00 |
December | 123.56 | 94.05 | 29.52 | 185.43 | 67.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.69 | 41.34 | 34.35 | 111.50 | 51.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.83 | 2.28 | 29.52 | 44.54 | 34.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.56 | 94.05 | 37.81 | 185.43 | 67.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.66 | 84.84 | 30.82 | 172.60 | 67.00 | 0.00 | 0.00 | 0.00 |
February | 90.90 | 55.99 | 34.91 | 128.03 | 62.27 | 0.00 | 0.00 | 0.00 |
March | 72.47 | 35.01 | 37.46 | 101.14 | 63.73 | 0.00 | 0.00 | 0.00 |
April | 60.55 | 23.09 | 37.46 | 89.30 | 54.38 | 0.00 | 0.00 | 0.00 |
May | 43.12 | 5.31 | 37.81 | 50.90 | 49.89 | 0.00 | 0.00 | 0.00 |
June | 37.83 | 2.28 | 35.54 | 44.54 | 38.83 | 0.00 | 0.00 | 0.00 |
July | 40.07 | 4.51 | 35.56 | 55.43 | 34.07 | 0.00 | 0.00 | 0.00 |
August | 51.47 | 16.24 | 35.24 | 82.75 | 35.30 | 0.00 | 0.00 | 0.00 |
September | 71.63 | 36.30 | 35.33 | 115.83 | 41.23 | 0.00 | 0.00 | 0.00 |
October | 91.09 | 60.90 | 30.19 | 148.21 | 44.36 | 0.00 | 0.00 | 0.00 |
November | 110.71 | 78.16 | 32.55 | 164.41 | 62.42 | 0.00 | 0.00 | 0.00 |
December | 123.56 | 94.05 | 29.52 | 185.43 | 67.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.69 | 41.34 | 34.35 | 111.50 | 51.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.83 | 2.28 | 29.52 | 44.54 | 34.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.56 | 94.05 | 37.81 | 185.43 | 67.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.08 | 59.03 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 104.68 | 55.19 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.29 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.36 | 47.16 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.40 | 43.33 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.47 | 33.39 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.87 | 28.96 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.56 | 30.14 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 95.93 | 35.23 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.77 | 37.97 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.57 | 54.02 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 152.72 | 59.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.78 | 44.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.47 | 28.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 152.72 | 59.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.08 | 59.03 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 104.68 | 55.19 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.29 | 56.99 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.36 | 47.16 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.40 | 43.33 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.47 | 33.39 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.87 | 28.96 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.56 | 30.14 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 95.93 | 35.23 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.77 | 37.97 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.57 | 54.02 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 152.72 | 59.02 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.78 | 44.98 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.47 | 28.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 152.72 | 59.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.66 | 84.84 | 30.82 | 170.92 | 70.22 | 0.00 | 0.00 | 0.00 |
February | 90.90 | 55.99 | 34.91 | 126.24 | 65.56 | 0.00 | 0.00 | 0.00 |
March | 72.47 | 35.01 | 37.46 | 99.26 | 67.63 | 0.00 | 0.00 | 0.00 |
April | 60.55 | 23.09 | 37.46 | 88.38 | 56.12 | 0.00 | 0.00 | 0.00 |
May | 43.12 | 5.31 | 37.81 | 50.05 | 51.47 | 0.00 | 0.00 | 0.00 |
June | 37.83 | 2.28 | 35.54 | 43.99 | 39.76 | 0.00 | 0.00 | 0.00 |
July | 40.07 | 4.51 | 35.56 | 55.16 | 34.54 | 0.00 | 0.00 | 0.00 |
August | 51.47 | 16.24 | 35.24 | 82.42 | 35.91 | 0.00 | 0.00 | 0.00 |
September | 71.63 | 36.30 | 35.33 | 115.37 | 42.01 | 0.00 | 0.00 | 0.00 |
October | 91.09 | 60.90 | 30.19 | 147.60 | 45.24 | 0.00 | 0.00 | 0.00 |
November | 110.71 | 78.16 | 32.55 | 163.20 | 64.28 | 0.00 | 0.00 | 0.00 |
December | 123.56 | 94.05 | 29.52 | 183.76 | 70.26 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.69 | 41.34 | 34.35 | 110.48 | 53.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.83 | 2.28 | 29.52 | 43.99 | 34.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 123.56 | 94.05 | 37.81 | 183.76 | 70.26 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.56 | 58.20 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.03 | 54.43 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.65 | 56.11 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.55 | 47.21 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.54 | 43.52 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.54 | 34.06 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.84 | 30.16 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.58 | 31.31 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.00 | 36.20 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.75 | 39.09 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.81 | 53.97 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.03 | 58.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.95 | 45.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.54 | 30.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.03 | 58.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.56 | 58.20 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.03 | 54.43 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.65 | 56.11 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.55 | 47.21 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.54 | 43.52 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.54 | 34.06 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.84 | 30.16 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.58 | 31.31 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.00 | 36.20 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.75 | 39.09 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.81 | 53.97 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.03 | 58.61 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 91.95 | 45.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.54 | 30.16 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.03 | 58.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 170.55 | 68.86 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 125.97 | 64.30 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 99.14 | 66.22 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 88.12 | 55.84 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 49.94 | 51.39 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 43.83 | 40.31 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 54.82 | 35.75 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 81.99 | 37.07 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 114.82 | 42.90 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 146.78 | 46.30 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 162.60 | 63.85 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 183.12 | 69.38 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.09 | 53.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 43.83 | 35.75 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 183.12 | 69.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.88 | 57.37 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.29 | 53.67 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.96 | 55.24 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.70 | 46.71 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.66 | 43.13 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.62 | 33.81 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.89 | 30.03 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.62 | 31.18 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.05 | 35.99 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.80 | 38.93 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.96 | 53.51 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.26 | 57.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.10 | 44.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.62 | 30.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.26 | 57.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 142.88 | 57.37 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.29 | 53.67 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 82.96 | 55.24 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.70 | 46.71 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.66 | 43.13 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.62 | 33.81 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 45.89 | 30.03 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.62 | 31.18 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.05 | 35.99 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.80 | 38.93 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 135.96 | 53.51 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.26 | 57.99 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.10 | 44.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.62 | 30.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.26 | 57.99 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 170.93 | 67.87 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 126.28 | 63.41 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 99.51 | 65.20 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 88.30 | 55.26 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.08 | 50.93 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 43.92 | 40.01 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 54.88 | 35.59 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.04 | 36.92 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 114.88 | 42.65 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 146.84 | 46.11 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 162.78 | 63.32 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 183.39 | 68.65 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.27 | 52.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 43.92 | 35.59 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 183.39 | 68.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.30 | 56.45 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.73 | 52.72 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.48 | 54.12 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.96 | 46.08 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.89 | 42.60 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.80 | 33.39 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.05 | 29.66 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.76 | 30.81 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.19 | 35.57 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.95 | 38.53 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.22 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.62 | 57.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.37 | 44.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.80 | 29.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.62 | 57.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 143.30 | 56.45 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 105.73 | 52.72 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 83.48 | 54.12 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 73.96 | 46.08 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 41.89 | 42.60 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 36.80 | 33.39 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.05 | 29.66 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.76 | 30.81 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.19 | 35.57 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 122.95 | 38.53 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.22 | 52.95 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 153.62 | 57.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.37 | 44.13 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 36.80 | 29.66 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 153.62 | 57.21 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 171.44 | 66.79 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 126.80 | 62.29 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 100.13 | 63.89 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 88.61 | 54.50 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 50.36 | 50.31 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.14 | 39.52 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.07 | 35.15 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.21 | 36.48 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.05 | 42.15 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.02 | 45.63 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.08 | 62.65 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 183.82 | 67.74 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 110.60 | 52.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.14 | 35.15 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 183.82 | 67.74 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.30 | 54.39 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.91 | 50.42 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.71 | 51.60 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.60 | 44.48 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.52 | 41.16 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.20 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.24 | 28.62 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.96 | 29.70 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.52 | 34.45 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.33 | 37.38 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.97 | 51.44 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.03 | 42.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.20 | 28.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.30 | 54.39 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.91 | 50.42 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.71 | 51.60 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.60 | 44.48 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.52 | 41.16 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.20 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.24 | 28.62 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.96 | 29.70 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.52 | 34.45 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.33 | 37.38 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.97 | 51.44 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.03 | 42.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.20 | 28.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.30 | 54.39 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.91 | 50.42 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.71 | 51.60 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.60 | 44.48 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.52 | 41.16 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.20 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.24 | 28.62 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.96 | 29.70 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.52 | 34.45 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.33 | 37.38 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.97 | 51.44 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.03 | 42.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.20 | 28.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.30 | 54.39 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.91 | 50.42 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.71 | 51.60 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.60 | 44.48 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.52 | 41.16 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.20 | 32.26 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.24 | 28.62 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.96 | 29.70 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.52 | 34.45 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.33 | 37.38 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.97 | 51.44 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.03 | 42.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.20 | 28.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.60 | 55.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.59 | 64.38 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 128.16 | 59.60 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.56 | 60.95 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.36 | 52.64 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.10 | 48.64 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.61 | 38.19 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.29 | 33.93 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.44 | 35.19 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.42 | 40.83 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.45 | 44.29 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.94 | 60.88 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.95 | 65.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.36 | 50.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.61 | 33.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.95 | 65.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.59 | 64.38 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 128.16 | 59.60 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.56 | 60.95 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.36 | 52.64 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.10 | 48.64 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.61 | 38.19 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.29 | 33.93 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.44 | 35.19 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.42 | 40.83 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.45 | 44.29 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.94 | 60.88 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.95 | 65.50 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.36 | 50.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.61 | 33.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.95 | 65.50 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.13 | 54.33 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.72 | 50.29 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.62 | 51.45 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.49 | 44.40 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.43 | 41.13 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.19 | 32.13 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.28 | 28.43 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.95 | 29.52 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.41 | 34.28 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.17 | 37.24 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.72 | 51.43 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.39 | 55.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.92 | 42.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.19 | 28.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.39 | 55.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.13 | 54.33 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 106.72 | 50.29 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.62 | 51.45 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.49 | 44.40 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.43 | 41.13 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.19 | 32.13 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.28 | 28.43 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 68.95 | 29.52 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.41 | 34.28 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.17 | 37.24 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.72 | 51.43 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.39 | 55.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 92.92 | 42.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.19 | 28.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.39 | 55.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.44 | 64.29 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 127.99 | 59.42 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.49 | 60.75 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.25 | 52.52 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.01 | 48.58 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.62 | 38.03 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.36 | 33.70 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.44 | 34.97 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.33 | 40.62 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.30 | 44.12 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.69 | 60.86 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 184.75 | 65.40 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.26 | 50.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.62 | 33.70 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 184.75 | 65.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.34 | 53.95 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.00 | 49.76 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.90 | 50.94 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.63 | 44.11 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.57 | 40.88 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.29 | 31.96 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.36 | 28.30 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.02 | 29.39 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.49 | 34.11 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.25 | 37.09 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.88 | 51.14 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.61 | 54.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.07 | 42.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.29 | 28.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.61 | 54.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.34 | 53.95 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.00 | 49.76 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 84.90 | 50.94 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 74.63 | 44.11 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.57 | 40.88 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.29 | 31.96 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.36 | 28.30 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.02 | 29.39 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.49 | 34.11 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.25 | 37.09 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 136.88 | 51.14 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 154.61 | 54.84 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.07 | 42.16 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.29 | 28.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 154.61 | 54.84 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 172.69 | 63.84 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 128.32 | 58.79 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 101.83 | 60.14 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.43 | 52.18 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.18 | 48.29 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 44.74 | 37.83 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.46 | 33.55 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.53 | 34.81 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.42 | 40.43 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.40 | 43.93 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 163.89 | 60.51 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 185.02 | 64.94 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.44 | 49.89 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 44.74 | 33.55 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 185.02 | 64.94 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.91 | 52.89 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.73 | 48.33 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 85.56 | 49.63 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 75.02 | 43.24 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.96 | 40.10 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.57 | 31.42 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.53 | 27.94 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.17 | 29.03 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.67 | 33.64 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.46 | 36.62 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 137.37 | 50.21 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 155.23 | 53.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.47 | 41.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.57 | 27.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 155.23 | 53.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 144.91 | 52.89 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 107.73 | 48.33 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 85.56 | 49.63 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 75.02 | 43.24 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 42.96 | 40.10 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 37.57 | 31.42 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.53 | 27.94 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.17 | 29.03 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.67 | 33.64 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.46 | 36.62 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 137.37 | 50.21 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 155.23 | 53.72 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 93.47 | 41.36 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 37.57 | 27.94 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 155.23 | 53.72 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 173.36 | 62.59 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 129.19 | 57.11 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 102.62 | 58.60 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 89.89 | 51.16 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 51.65 | 47.37 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 45.07 | 37.20 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.66 | 33.13 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.71 | 34.39 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 115.64 | 39.86 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 147.65 | 43.38 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 164.47 | 59.42 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 185.75 | 63.62 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 111.92 | 48.94 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 45.07 | 33.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 185.75 | 63.62 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 146.09 | 49.65 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 109.28 | 44.24 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 86.78 | 45.80 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 75.68 | 40.28 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 43.77 | 37.27 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 38.12 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.60 | 26.54 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.22 | 27.53 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.99 | 31.83 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.91 | 34.76 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 138.54 | 47.10 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 156.61 | 50.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 94.25 | 38.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 38.12 | 26.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 156.61 | 50.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 96.21 | 70.58 | 25.64 | 146.09 | 49.65 | 0.00 | 0.00 | 0.00 |
February | 75.62 | 46.58 | 29.04 | 109.28 | 44.24 | 0.00 | 0.00 | 0.00 |
March | 60.28 | 29.12 | 31.16 | 86.78 | 45.80 | 0.00 | 0.00 | 0.00 |
April | 50.37 | 19.21 | 31.16 | 75.68 | 40.28 | 0.00 | 0.00 | 0.00 |
May | 35.87 | 4.41 | 31.45 | 43.77 | 37.27 | 0.00 | 0.00 | 0.00 |
June | 31.46 | 1.90 | 29.56 | 38.12 | 29.35 | 0.00 | 0.00 | 0.00 |
July | 33.33 | 3.75 | 29.58 | 46.60 | 26.54 | 0.00 | 0.00 | 0.00 |
August | 42.82 | 13.51 | 29.31 | 69.22 | 27.53 | 0.00 | 0.00 | 0.00 |
September | 59.58 | 30.19 | 29.39 | 96.99 | 31.83 | 0.00 | 0.00 | 0.00 |
October | 75.77 | 50.66 | 25.12 | 123.91 | 34.76 | 0.00 | 0.00 | 0.00 |
November | 92.10 | 65.02 | 27.08 | 138.54 | 47.10 | 0.00 | 0.00 | 0.00 |
December | 102.78 | 78.23 | 24.55 | 156.61 | 50.24 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 62.96 | 34.39 | 28.58 | 94.25 | 38.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 31.46 | 1.90 | 24.55 | 38.12 | 26.54 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 102.78 | 78.23 | 31.45 | 156.61 | 50.24 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 115.03 | 84.38 | 30.65 | 174.77 | 58.77 | 0.00 | 0.00 | 0.00 |
February | 90.41 | 55.69 | 34.72 | 131.03 | 52.31 | 0.00 | 0.00 | 0.00 |
March | 72.07 | 34.82 | 37.26 | 104.07 | 54.10 | 0.00 | 0.00 | 0.00 |
April | 60.22 | 22.96 | 37.26 | 90.68 | 47.67 | 0.00 | 0.00 | 0.00 |
May | 42.88 | 5.28 | 37.60 | 52.61 | 44.05 | 0.00 | 0.00 | 0.00 |
June | 37.62 | 2.27 | 35.35 | 45.73 | 34.75 | 0.00 | 0.00 | 0.00 |
July | 39.85 | 4.49 | 35.36 | 55.74 | 31.47 | 0.00 | 0.00 | 0.00 |
August | 51.19 | 16.15 | 35.05 | 82.77 | 32.62 | 0.00 | 0.00 | 0.00 |
September | 71.24 | 36.10 | 35.14 | 116.02 | 37.73 | 0.00 | 0.00 | 0.00 |
October | 90.59 | 60.56 | 30.03 | 148.17 | 41.20 | 0.00 | 0.00 | 0.00 |
November | 110.11 | 77.73 | 32.37 | 165.86 | 55.75 | 0.00 | 0.00 | 0.00 |
December | 122.89 | 93.53 | 29.35 | 187.39 | 59.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 75.28 | 41.11 | 34.16 | 112.85 | 45.80 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 37.62 | 2.27 | 29.35 | 45.73 | 31.47 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.89 | 93.53 | 37.60 | 187.39 | 59.52 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384429E+09 | 0.150761E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.256965E+09 | 0.126732E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.224712E+09 | 0.143697E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192220E+09 | 0.118408E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112846E+09 | 0.112423E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95753559.62 | 84479842.48 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123513E+09 | 76478260.22 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184431E+09 | 79298747.04 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249728E+09 | 89596272.20 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330263E+09 | 99654468.11 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354114E+09 | 0.135911E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412902E+09 | 0.151517E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292188E+10 | 0.136896E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95753559.62 | 76478260.22 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412902E+09 | 0.151517E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384429E+09 | 0.150761E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.256965E+09 | 0.126732E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.224712E+09 | 0.143697E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192220E+09 | 0.118408E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112846E+09 | 0.112423E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95753559.62 | 84479842.48 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123513E+09 | 76478260.22 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184431E+09 | 79298747.04 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249728E+09 | 89596272.20 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330263E+09 | 99654468.11 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354114E+09 | 0.135911E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412902E+09 | 0.151517E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292188E+10 | 0.136896E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95753559.62 | 76478260.22 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412902E+09 | 0.151517E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384429E+09 | 0.150761E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.256965E+09 | 0.126732E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.224712E+09 | 0.143697E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192220E+09 | 0.118408E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112846E+09 | 0.112423E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95753559.62 | 84479842.48 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123513E+09 | 76478260.22 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184431E+09 | 79298747.04 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249728E+09 | 89596272.20 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330263E+09 | 99654468.11 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354114E+09 | 0.135911E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412902E+09 | 0.151517E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292188E+10 | 0.136896E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95753559.62 | 76478260.22 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412902E+09 | 0.151517E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.384429E+09 | 0.150761E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.256965E+09 | 0.126732E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.224712E+09 | 0.143697E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.192220E+09 | 0.118408E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112846E+09 | 0.112423E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95753559.62 | 84479842.48 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123513E+09 | 76478260.22 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184431E+09 | 79298747.04 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249728E+09 | 89596272.20 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330263E+09 | 99654468.11 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354114E+09 | 0.135911E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.412902E+09 | 0.151517E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.292188E+10 | 0.136896E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95753559.62 | 76478260.22 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.412902E+09 | 0.151517E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309785E+09 | 0.227241E+09 | 82543450.73 | 0.462300E+09 | 0.179464E+09 |
February | 0.219912E+09 | 0.135454E+09 | 84457892.83 | 0.309735E+09 | 0.150652E+09 |
March | 0.194106E+09 | 93762249.22 | 0.100344E+09 | 0.270887E+09 | 0.170686E+09 |
April | 0.156949E+09 | 59846006.84 | 97102545.23 | 0.231474E+09 | 0.140942E+09 |
May | 0.115485E+09 | 14211981.76 | 0.101273E+09 | 0.136331E+09 | 0.133626E+09 |
June | 98042715.30 | 5919465.95 | 92123249.35 | 0.115437E+09 | 0.100639E+09 |
July | 0.107316E+09 | 12080715.02 | 95235263.81 | 0.148475E+09 | 91252638.71 |
August | 0.137869E+09 | 43488152.79 | 94380682.40 | 0.221641E+09 | 94541331.44 |
September | 0.185656E+09 | 94078320.04 | 91577646.08 | 0.300237E+09 | 0.106866E+09 |
October | 0.243981E+09 | 0.163108E+09 | 80873019.95 | 0.396977E+09 | 0.118804E+09 |
November | 0.286969E+09 | 0.202596E+09 | 84373290.15 | 0.426149E+09 | 0.161797E+09 |
December | 0.330949E+09 | 0.251896E+09 | 79053764.04 | 0.496650E+09 | 0.180479E+09 |
Annual Sum or Average | 0.238702E+10 | 0.130368E+10 | 0.108334E+10 | 0.351629E+10 | 0.162975E+10 |
Minimum of Months | 98042715.30 | 5919465.95 | 79053764.04 | 0.115437E+09 | 91252638.71 |
Maximum of Months | 0.330949E+09 | 0.251896E+09 | 0.101273E+09 | 0.496650E+09 | 0.180479E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309785E+09 | 0.227241E+09 | 82543450.73 | 0.462300E+09 | 0.179464E+09 |
February | 0.219912E+09 | 0.135454E+09 | 84457892.83 | 0.309735E+09 | 0.150652E+09 |
March | 0.194106E+09 | 93762249.22 | 0.100344E+09 | 0.270887E+09 | 0.170686E+09 |
April | 0.156949E+09 | 59846006.84 | 97102545.23 | 0.231474E+09 | 0.140942E+09 |
May | 0.115485E+09 | 14211981.76 | 0.101273E+09 | 0.136331E+09 | 0.133626E+09 |
June | 98042715.30 | 5919465.95 | 92123249.35 | 0.115437E+09 | 0.100639E+09 |
July | 0.107316E+09 | 12080715.02 | 95235263.81 | 0.148475E+09 | 91252638.71 |
August | 0.137869E+09 | 43488152.79 | 94380682.40 | 0.221641E+09 | 94541331.44 |
September | 0.185656E+09 | 94078320.04 | 91577646.08 | 0.300237E+09 | 0.106866E+09 |
October | 0.243981E+09 | 0.163108E+09 | 80873019.95 | 0.396977E+09 | 0.118804E+09 |
November | 0.286969E+09 | 0.202596E+09 | 84373290.15 | 0.426149E+09 | 0.161797E+09 |
December | 0.330949E+09 | 0.251896E+09 | 79053764.04 | 0.496650E+09 | 0.180479E+09 |
Annual Sum or Average | 0.238702E+10 | 0.130368E+10 | 0.108334E+10 | 0.351629E+10 | 0.162975E+10 |
Minimum of Months | 98042715.30 | 5919465.95 | 79053764.04 | 0.115437E+09 | 91252638.71 |
Maximum of Months | 0.330949E+09 | 0.251896E+09 | 0.101273E+09 | 0.496650E+09 | 0.180479E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.380555E+09 | 0.158099E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.253245E+09 | 0.133512E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.220414E+09 | 0.152640E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190154E+09 | 0.122252E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.110893E+09 | 0.116042E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94528887.08 | 86538130.62 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.122871E+09 | 77558754.30 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183638E+09 | 80714653.56 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248660E+09 | 91321960.24 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328817E+09 | 0.101690E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.351402E+09 | 0.140014E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.409049E+09 | 0.158087E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289423E+10 | 0.141847E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94528887.08 | 77558754.30 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.409049E+09 | 0.158099E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.380555E+09 | 0.158099E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.253245E+09 | 0.133512E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.220414E+09 | 0.152640E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190154E+09 | 0.122252E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.110893E+09 | 0.116042E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94528887.08 | 86538130.62 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.122871E+09 | 77558754.30 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183638E+09 | 80714653.56 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248660E+09 | 91321960.24 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328817E+09 | 0.101690E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.351402E+09 | 0.140014E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.409049E+09 | 0.158087E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289423E+10 | 0.141847E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94528887.08 | 77558754.30 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.409049E+09 | 0.158099E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.309785E+09 | 0.227241E+09 | 82543450.73 | 0.457780E+09 | 0.188079E+09 |
February | 0.219912E+09 | 0.135454E+09 | 84457892.83 | 0.305402E+09 | 0.158595E+09 |
March | 0.194106E+09 | 93762249.22 | 0.100344E+09 | 0.265845E+09 | 0.181153E+09 |
April | 0.156949E+09 | 59846006.84 | 97102545.23 | 0.229079E+09 | 0.145455E+09 |
May | 0.115485E+09 | 14211981.76 | 0.101273E+09 | 0.134057E+09 | 0.137850E+09 |
June | 98042715.30 | 5919465.95 | 92123249.35 | 0.114013E+09 | 0.103053E+09 |
July | 0.107316E+09 | 12080715.02 | 95235263.81 | 0.147744E+09 | 92518570.97 |
August | 0.137869E+09 | 43488152.79 | 94380682.40 | 0.220749E+09 | 96185833.89 |
September | 0.185656E+09 | 94078320.04 | 91577646.08 | 0.299041E+09 | 0.108889E+09 |
October | 0.243981E+09 | 0.163108E+09 | 80873019.95 | 0.395343E+09 | 0.121180E+09 |
November | 0.286969E+09 | 0.202596E+09 | 84373290.15 | 0.423027E+09 | 0.166605E+09 |
December | 0.330949E+09 | 0.251896E+09 | 79053764.04 | 0.492170E+09 | 0.188197E+09 |
Annual Sum or Average | 0.238702E+10 | 0.130368E+10 | 0.108334E+10 | 0.348425E+10 | 0.168776E+10 |
Minimum of Months | 98042715.30 | 5919465.95 | 79053764.04 | 0.114013E+09 | 92518570.97 |
Maximum of Months | 0.330949E+09 | 0.251896E+09 | 0.101273E+09 | 0.492170E+09 | 0.188197E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.381828E+09 | 0.155893E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.254084E+09 | 0.131673E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.221371E+09 | 0.150278E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190643E+09 | 0.122358E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111256E+09 | 0.116559E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94706466.90 | 88276716.12 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.122788E+09 | 80791053.19 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183692E+09 | 83861545.83 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248826E+09 | 93838934.79 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328785E+09 | 0.104708E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352024E+09 | 0.139885E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.409886E+09 | 0.156980E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289989E+10 | 0.142510E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94706466.90 | 80791053.19 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.409886E+09 | 0.156980E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.381828E+09 | 0.155893E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.254084E+09 | 0.131673E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.221371E+09 | 0.150278E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.190643E+09 | 0.122358E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111256E+09 | 0.116559E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94706466.90 | 88276716.12 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.122788E+09 | 80791053.19 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183692E+09 | 83861545.83 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248826E+09 | 93838934.79 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328785E+09 | 0.104708E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352024E+09 | 0.139885E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.409886E+09 | 0.156980E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.289989E+10 | 0.142510E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94706466.90 | 80791053.19 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.409886E+09 | 0.156980E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.456790E+09 | 0.184431E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.304735E+09 | 0.155551E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.265529E+09 | 0.177372E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.228408E+09 | 0.144727E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.133755E+09 | 0.137651E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.113601E+09 | 0.104474E+09 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.146836E+09 | 95743844.42 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.219600E+09 | 99294925.40 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.297601E+09 | 0.111189E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393142E+09 | 0.124006E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.421457E+09 | 0.165503E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.490477E+09 | 0.185839E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.347193E+10 | 0.168578E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.113601E+09 | 95743844.42 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.490477E+09 | 0.185839E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.382689E+09 | 0.153648E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.254724E+09 | 0.129849E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.222207E+09 | 0.147947E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191023E+09 | 0.121085E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111570E+09 | 0.115519E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94913544.76 | 87629743.64 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.122916E+09 | 80426883.87 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183797E+09 | 83510782.14 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248964E+09 | 93291019.26 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328903E+09 | 0.104275E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352415E+09 | 0.138709E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.410478E+09 | 0.155322E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.290460E+10 | 0.141121E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94913544.76 | 80426883.87 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.410478E+09 | 0.155322E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.382689E+09 | 0.153648E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.254724E+09 | 0.129849E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.222207E+09 | 0.147947E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191023E+09 | 0.121085E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.111570E+09 | 0.115519E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 94913544.76 | 87629743.64 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.122916E+09 | 80426883.87 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.183797E+09 | 83510782.14 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.248964E+09 | 93291019.26 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.328903E+09 | 0.104275E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.352415E+09 | 0.138709E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.410478E+09 | 0.155322E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.290460E+10 | 0.141121E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 94913544.76 | 80426883.87 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.410478E+09 | 0.155322E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.457821E+09 | 0.181782E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.305501E+09 | 0.153401E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.266531E+09 | 0.174627E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.228865E+09 | 0.143222E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.134133E+09 | 0.136424E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.113851E+09 | 0.103709E+09 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.146991E+09 | 95313391.17 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.219728E+09 | 98880931.57 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.297768E+09 | 0.110540E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393284E+09 | 0.123496E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.421925E+09 | 0.164113E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.491185E+09 | 0.183882E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.347758E+10 | 0.166939E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.113851E+09 | 95313391.17 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.491185E+09 | 0.183882E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.383825E+09 | 0.151197E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.255777E+09 | 0.127544E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.223590E+09 | 0.144960E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191694E+09 | 0.119434E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112187E+09 | 0.114099E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95388942.47 | 86544834.68 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123331E+09 | 79438564.64 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184173E+09 | 82509118.49 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249331E+09 | 92207039.41 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329304E+09 | 0.103189E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.353075E+09 | 0.137248E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.411449E+09 | 0.153239E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.291312E+10 | 0.139161E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95388942.47 | 79438564.64 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.411449E+09 | 0.153239E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.383825E+09 | 0.151197E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.255777E+09 | 0.127544E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.223590E+09 | 0.144960E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.191694E+09 | 0.119434E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.112187E+09 | 0.114099E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 95388942.47 | 86544834.68 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123331E+09 | 79438564.64 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184173E+09 | 82509118.49 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249331E+09 | 92207039.41 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329304E+09 | 0.103189E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.353075E+09 | 0.137248E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.411449E+09 | 0.153239E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.291312E+10 | 0.139161E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 95388942.47 | 79438564.64 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.411449E+09 | 0.153239E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.459177E+09 | 0.178894E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.306757E+09 | 0.150691E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.268183E+09 | 0.171115E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.229670E+09 | 0.141276E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.134877E+09 | 0.134756E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.114421E+09 | 0.102430E+09 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.147491E+09 | 94148989.70 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220181E+09 | 97704712.00 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.298210E+09 | 0.109263E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.393767E+09 | 0.122218E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.422714E+09 | 0.162393E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.492345E+09 | 0.181428E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.348780E+10 | 0.164632E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.114421E+09 | 94148989.70 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.492345E+09 | 0.181428E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386490E+09 | 0.145682E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258643E+09 | 0.121966E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226896E+09 | 0.138207E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193374E+09 | 0.115297E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113888E+09 | 0.110251E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96430344.98 | 83605072.07 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123846E+09 | 76655281.25 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184711E+09 | 79550475.34 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250189E+09 | 89289582.83 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330331E+09 | 0.100127E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.355018E+09 | 0.133325E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.414094E+09 | 0.148122E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293391E+10 | 0.134208E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96430344.98 | 76655281.25 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.414094E+09 | 0.148122E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386490E+09 | 0.145682E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258643E+09 | 0.121966E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226896E+09 | 0.138207E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193374E+09 | 0.115297E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113888E+09 | 0.110251E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96430344.98 | 83605072.07 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123846E+09 | 76655281.25 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184711E+09 | 79550475.34 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250189E+09 | 89289582.83 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330331E+09 | 0.100127E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.355018E+09 | 0.133325E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.414094E+09 | 0.148122E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293391E+10 | 0.134208E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96430344.98 | 76655281.25 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.414094E+09 | 0.148122E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386490E+09 | 0.145682E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258643E+09 | 0.121966E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226896E+09 | 0.138207E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193374E+09 | 0.115297E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113888E+09 | 0.110251E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96430344.98 | 83605072.07 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123846E+09 | 76655281.25 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184711E+09 | 79550475.34 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250189E+09 | 89289582.83 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330331E+09 | 0.100127E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.355018E+09 | 0.133325E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.414094E+09 | 0.148122E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293391E+10 | 0.134208E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96430344.98 | 76655281.25 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.414094E+09 | 0.148122E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386490E+09 | 0.145682E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258643E+09 | 0.121966E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226896E+09 | 0.138207E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193374E+09 | 0.115297E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113888E+09 | 0.110251E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96430344.98 | 83605072.07 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123846E+09 | 76655281.25 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184711E+09 | 79550475.34 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250189E+09 | 89289582.83 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330331E+09 | 0.100127E+09 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.355018E+09 | 0.133325E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.414094E+09 | 0.148122E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293391E+10 | 0.134208E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96430344.98 | 76655281.25 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.414094E+09 | 0.148122E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.462254E+09 | 0.172436E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.310055E+09 | 0.144174E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.272027E+09 | 0.163241E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.231615E+09 | 0.136437E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.136853E+09 | 0.130280E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115638E+09 | 98988936.05 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148099E+09 | 90884631.71 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220799E+09 | 94251269.56 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299178E+09 | 0.105840E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394920E+09 | 0.118639E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424922E+09 | 0.157809E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.495380E+09 | 0.175435E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.351174E+10 | 0.158842E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115638E+09 | 90884631.71 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.495380E+09 | 0.175435E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.462254E+09 | 0.172436E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.310055E+09 | 0.144174E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.272027E+09 | 0.163241E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.231615E+09 | 0.136437E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.136853E+09 | 0.130280E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115638E+09 | 98988936.05 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148099E+09 | 90884631.71 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220799E+09 | 94251269.56 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299178E+09 | 0.105840E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394920E+09 | 0.118639E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424922E+09 | 0.157809E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.495380E+09 | 0.175435E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.351174E+10 | 0.158842E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115638E+09 | 90884631.71 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.495380E+09 | 0.175435E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386047E+09 | 0.145528E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258174E+09 | 0.121664E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226642E+09 | 0.137816E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193067E+09 | 0.115072E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113636E+09 | 0.110154E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96390037.97 | 83270199.13 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123949E+09 | 76146590.74 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184664E+09 | 79074674.10 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249895E+09 | 88842215.01 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329911E+09 | 99750023.66 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354374E+09 | 0.133319E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413525E+09 | 0.147942E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293027E+10 | 0.133858E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96390037.97 | 76146590.74 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413525E+09 | 0.147942E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386047E+09 | 0.145528E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258174E+09 | 0.121664E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.226642E+09 | 0.137816E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193067E+09 | 0.115072E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.113636E+09 | 0.110154E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96390037.97 | 83270199.13 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.123949E+09 | 76146590.74 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184664E+09 | 79074674.10 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.249895E+09 | 88842215.01 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.329911E+09 | 99750023.66 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354374E+09 | 0.133319E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.413525E+09 | 0.147942E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293027E+10 | 0.133858E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96390037.97 | 76146590.74 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.413525E+09 | 0.147942E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.461852E+09 | 0.172196E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.309627E+09 | 0.143758E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.271843E+09 | 0.162701E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.231345E+09 | 0.136125E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.136633E+09 | 0.130106E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115647E+09 | 98562287.04 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148270E+09 | 90265359.22 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.220813E+09 | 93661785.68 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.298925E+09 | 0.105286E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394532E+09 | 0.118161E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424294E+09 | 0.157750E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.494843E+09 | 0.175170E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.350862E+10 | 0.158374E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115647E+09 | 90265359.22 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.494843E+09 | 0.175170E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386613E+09 | 0.144508E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258858E+09 | 0.120370E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227395E+09 | 0.136436E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193450E+09 | 0.114331E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114014E+09 | 0.109501E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96662104.88 | 82833953.85 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124170E+09 | 75797175.50 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184865E+09 | 78722251.78 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250096E+09 | 88425073.48 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330126E+09 | 99331911.32 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354795E+09 | 0.132557E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.414120E+09 | 0.146892E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293516E+10 | 0.132970E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96662104.88 | 75797175.50 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.414120E+09 | 0.146892E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.386613E+09 | 0.144508E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.258858E+09 | 0.120370E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.227395E+09 | 0.136436E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.193450E+09 | 0.114331E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.114014E+09 | 0.109501E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 96662104.88 | 82833953.85 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124170E+09 | 75797175.50 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.184865E+09 | 78722251.78 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250096E+09 | 88425073.48 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330126E+09 | 99331911.32 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.354795E+09 | 0.132557E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.414120E+09 | 0.146892E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.293516E+10 | 0.132970E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 96662104.88 | 75797175.50 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.414120E+09 | 0.146892E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.462526E+09 | 0.170991E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.310441E+09 | 0.142232E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.272740E+09 | 0.161076E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.231805E+09 | 0.135249E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.137087E+09 | 0.129337E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.115974E+09 | 98046870.13 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.148536E+09 | 89851661.15 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221055E+09 | 93245255.58 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299167E+09 | 0.104792E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.394790E+09 | 0.117667E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.424796E+09 | 0.156849E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.495552E+09 | 0.173931E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.351447E+10 | 0.157327E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.115974E+09 | 89851661.15 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.495552E+09 | 0.173931E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.388123E+09 | 0.141661E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.260625E+09 | 0.116921E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.229173E+09 | 0.132935E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.194454E+09 | 0.112081E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.115069E+09 | 0.107401E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 97369519.34 | 81449734.42 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124620E+09 | 74842204.67 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185271E+09 | 77745958.18 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250577E+09 | 87183787.71 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330687E+09 | 98077160.94 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.356059E+09 | 0.130148E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.415757E+09 | 0.143886E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.294778E+10 | 0.130433E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 97369519.34 | 74842204.67 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.415757E+09 | 0.143886E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.388123E+09 | 0.141661E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.260625E+09 | 0.116921E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.229173E+09 | 0.132935E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.194454E+09 | 0.112081E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.115069E+09 | 0.107401E+09 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 97369519.34 | 81449734.42 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124620E+09 | 74842204.67 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185271E+09 | 77745958.18 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.250577E+09 | 87183787.71 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.330687E+09 | 98077160.94 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.356059E+09 | 0.130148E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.415757E+09 | 0.143886E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.294778E+10 | 0.130433E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 97369519.34 | 74842204.67 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.415757E+09 | 0.143886E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.464325E+09 | 0.167640E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.312538E+09 | 0.138171E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.274857E+09 | 0.156956E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.233005E+09 | 0.132598E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.138347E+09 | 0.126866E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.116822E+09 | 96414733.39 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.149075E+09 | 88727075.15 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221541E+09 | 92097609.91 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.299745E+09 | 0.103329E+09 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.395460E+09 | 0.116190E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.426303E+09 | 0.154011E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.497500E+09 | 0.170389E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.352952E+10 | 0.154339E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.116822E+09 | 88727075.15 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.497500E+09 | 0.170389E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.391297E+09 | 0.132971E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.264367E+09 | 0.107036E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.232429E+09 | 0.122670E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.196153E+09 | 0.104414E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.117222E+09 | 99836398.91 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 98802706.94 | 76082309.86 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124821E+09 | 71088877.07 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185396E+09 | 73731814.89 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.251399E+09 | 82500809.53 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.331871E+09 | 93109235.34 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.359097E+09 | 0.122074E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.419457E+09 | 0.134575E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.297231E+10 | 0.122009E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 98802706.94 | 71088877.07 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.419457E+09 | 0.134575E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.257692E+09 | 0.189029E+09 | 68662961.73 | 0.391297E+09 | 0.132971E+09 |
February | 0.182932E+09 | 0.112676E+09 | 70255471.66 | 0.264367E+09 | 0.107036E+09 |
March | 0.161465E+09 | 77995209.48 | 83469784.12 | 0.232429E+09 | 0.122670E+09 |
April | 0.130556E+09 | 49782315.15 | 80773802.02 | 0.196153E+09 | 0.104414E+09 |
May | 96064863.77 | 11822097.95 | 84242765.81 | 0.117222E+09 | 99836398.91 |
June | 81555873.29 | 4924049.82 | 76631823.47 | 98802706.94 | 76082309.86 |
July | 89269746.81 | 10049224.57 | 79220522.24 | 0.124821E+09 | 71088877.07 |
August | 0.114685E+09 | 36175194.33 | 78509647.06 | 0.185396E+09 | 73731814.89 |
September | 0.154436E+09 | 78258129.89 | 76177968.73 | 0.251399E+09 | 82500809.53 |
October | 0.202954E+09 | 0.135680E+09 | 67273430.23 | 0.331871E+09 | 93109235.34 |
November | 0.238712E+09 | 0.168527E+09 | 70185095.75 | 0.359097E+09 | 0.122074E+09 |
December | 0.275297E+09 | 0.209537E+09 | 65760100.01 | 0.419457E+09 | 0.134575E+09 |
Annual Sum or Average | 0.198562E+10 | 0.108446E+10 | 0.901163E+09 | 0.297231E+10 | 0.122009E+10 |
Minimum of Months | 81555873.29 | 4924049.82 | 65760100.01 | 98802706.94 | 71088877.07 |
Maximum of Months | 0.275297E+09 | 0.209537E+09 | 84242765.81 | 0.419457E+09 | 0.134575E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.308092E+09 | 0.226000E+09 | 82092393.62 | 0.468100E+09 | 0.157408E+09 |
February | 0.218711E+09 | 0.134714E+09 | 83996374.29 | 0.316989E+09 | 0.126545E+09 |
March | 0.193045E+09 | 93249887.21 | 99795205.46 | 0.278743E+09 | 0.144889E+09 |
April | 0.156091E+09 | 59518979.48 | 96571930.22 | 0.235031E+09 | 0.123562E+09 |
May | 0.114854E+09 | 14134320.66 | 0.100719E+09 | 0.140923E+09 | 0.117976E+09 |
June | 97506962.76 | 5887119.14 | 91619843.62 | 0.118534E+09 | 90082124.25 |
July | 0.106730E+09 | 12014700.18 | 94714852.53 | 0.149306E+09 | 84295535.67 |
August | 0.137115E+09 | 43250512.61 | 93864940.96 | 0.221681E+09 | 87372008.86 |
September | 0.184641E+09 | 93564230.86 | 91077221.78 | 0.300730E+09 | 97797705.63 |
October | 0.242648E+09 | 0.162217E+09 | 80431090.87 | 0.396868E+09 | 0.110349E+09 |
November | 0.285401E+09 | 0.201489E+09 | 83912233.92 | 0.429915E+09 | 0.144507E+09 |
December | 0.329141E+09 | 0.250519E+09 | 78621776.26 | 0.501894E+09 | 0.159422E+09 |
Annual Sum or Average | 0.237398E+10 | 0.129656E+10 | 0.107742E+10 | 0.355871E+10 | 0.144421E+10 |
Minimum of Months | 97506962.76 | 5887119.14 | 78621776.26 | 0.118534E+09 | 84295535.67 |
Maximum of Months | 0.329141E+09 | 0.250519E+09 | 0.100719E+09 | 0.501894E+09 | 0.159422E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 919.32 | 359.16 | 616.16 | 451.99 | 164.18 | 0.00 | 0.00 |
February | 680.94 | 334.09 | 484.27 | 298.29 | 185.99 | 0.00 | 0.00 |
March | 537.87 | 342.05 | 386.08 | 186.49 | 199.58 | 0.00 | 0.00 |
April | 475.24 | 291.48 | 322.58 | 123.00 | 199.58 | 0.00 | 0.00 |
May | 270.33 | 267.68 | 229.70 | 28.27 | 201.43 | 0.00 | 0.00 |
June | 236.84 | 208.02 | 201.51 | 12.17 | 189.34 | 0.00 | 0.00 |
July | 295.33 | 182.35 | 213.45 | 24.03 | 189.42 | 0.00 | 0.00 |
August | 440.94 | 189.02 | 274.22 | 86.50 | 187.72 | 0.00 | 0.00 |
September | 617.05 | 220.72 | 381.58 | 193.36 | 188.22 | 0.00 | 0.00 |
October | 789.65 | 237.54 | 485.28 | 324.42 | 160.86 | 0.00 | 0.00 |
November | 875.29 | 334.58 | 589.81 | 416.40 | 173.41 | 0.00 | 0.00 |
December | 987.49 | 361.05 | 658.26 | 501.02 | 157.24 | 0.00 | 0.00 |
Annual Sum or Average | 593.61 | 276.99 | 403.24 | 220.23 | 183.01 | 0.00 | 0.00 |
Minimum of Months | 236.84 | 182.35 | 201.51 | 12.17 | 157.24 | 0.00 | 0.00 |
Maximum of Months | 987.49 | 361.05 | 658.26 | 501.02 | 201.43 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 455.08 | 188.27 | 308.08 | 225.99 | 82.09 | 0.00 | 0.00 |
February | 335.60 | 175.93 | 242.14 | 149.14 | 92.99 | 0.00 | 0.00 |
March | 263.84 | 181.61 | 193.04 | 93.25 | 99.79 | 0.00 | 0.00 |
April | 235.10 | 150.45 | 161.29 | 61.50 | 99.79 | 0.00 | 0.00 |
May | 132.86 | 138.12 | 114.85 | 14.13 | 100.72 | 0.00 | 0.00 |
June | 116.93 | 106.53 | 100.75 | 6.08 | 94.67 | 0.00 | 0.00 |
July | 146.91 | 92.46 | 106.73 | 12.01 | 94.71 | 0.00 | 0.00 |
August | 219.54 | 96.18 | 137.11 | 43.25 | 93.86 | 0.00 | 0.00 |
September | 307.24 | 112.47 | 190.79 | 96.68 | 94.11 | 0.00 | 0.00 |
October | 393.14 | 121.18 | 242.64 | 162.21 | 80.43 | 0.00 | 0.00 |
November | 434.35 | 172.31 | 294.91 | 208.20 | 86.71 | 0.00 | 0.00 |
December | 489.20 | 188.31 | 329.13 | 250.51 | 78.62 | 0.00 | 0.00 |
Annual Sum or Average | 294.04 | 143.48 | 201.62 | 110.12 | 91.50 | 0.00 | 0.00 |
Minimum of Months | 116.93 | 92.46 | 100.75 | 6.08 | 78.62 | 0.00 | 0.00 |
Maximum of Months | 489.20 | 188.31 | 329.13 | 250.51 | 100.72 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 455.66 | 185.27 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 336.02 | 173.15 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 264.44 | 178.44 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 235.22 | 150.25 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 133.01 | 138.43 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 116.90 | 108.42 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 146.51 | 96.07 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 219.15 | 99.69 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 306.81 | 115.30 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 392.29 | 124.49 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 434.22 | 171.79 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 489.19 | 186.60 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 294.00 | 143.83 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 116.90 | 96.07 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 489.19 | 186.60 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 456.69 | 182.60 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 336.87 | 170.76 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 265.44 | 175.67 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 235.69 | 148.68 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 133.39 | 137.19 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 117.16 | 107.63 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 146.66 | 95.64 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 219.28 | 99.28 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 306.98 | 114.63 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 392.43 | 123.97 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 434.70 | 170.34 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 489.90 | 184.63 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 294.48 | 142.43 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 117.16 | 95.64 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 489.90 | 184.63 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 458.04 | 179.69 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 338.26 | 167.73 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 267.09 | 172.13 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 236.52 | 146.66 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 134.13 | 135.51 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 117.75 | 106.30 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 147.16 | 94.47 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 219.73 | 98.09 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 307.43 | 113.30 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 392.91 | 122.68 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 435.52 | 168.55 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 491.06 | 182.16 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 295.35 | 140.46 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 117.75 | 94.47 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 491.06 | 182.16 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 922.37 | 346.33 | 614.90 | 451.06 | 163.84 | 0.00 | 0.00 |
February | 683.98 | 320.85 | 483.28 | 297.67 | 185.60 | 0.00 | 0.00 |
March | 541.98 | 328.30 | 385.29 | 186.11 | 199.17 | 0.00 | 0.00 |
April | 477.13 | 283.20 | 321.92 | 122.75 | 199.17 | 0.00 | 0.00 |
May | 272.27 | 261.93 | 229.23 | 28.21 | 201.02 | 0.00 | 0.00 |
June | 238.04 | 205.40 | 201.09 | 12.14 | 188.95 | 0.00 | 0.00 |
July | 295.54 | 182.34 | 213.01 | 23.98 | 189.04 | 0.00 | 0.00 |
August | 440.73 | 189.18 | 273.66 | 86.32 | 187.34 | 0.00 | 0.00 |
September | 616.94 | 219.46 | 380.80 | 192.96 | 187.83 | 0.00 | 0.00 |
October | 788.22 | 238.12 | 484.29 | 323.76 | 160.53 | 0.00 | 0.00 |
November | 875.74 | 327.51 | 588.60 | 415.54 | 173.06 | 0.00 | 0.00 |
December | 988.33 | 352.21 | 656.91 | 499.99 | 156.92 | 0.00 | 0.00 |
Annual Sum or Average | 594.85 | 270.96 | 402.41 | 219.78 | 182.63 | 0.00 | 0.00 |
Minimum of Months | 238.04 | 182.34 | 201.09 | 12.14 | 156.92 | 0.00 | 0.00 |
Maximum of Months | 988.33 | 352.21 | 656.91 | 499.99 | 201.02 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 460.70 | 172.96 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 341.42 | 160.01 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 270.73 | 163.65 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 238.22 | 141.31 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 135.87 | 130.83 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 118.99 | 102.28 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 147.91 | 90.56 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 220.33 | 94.02 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 308.15 | 109.17 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 393.65 | 118.60 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 437.13 | 163.73 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 493.54 | 175.87 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 297.09 | 135.11 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 118.99 | 90.56 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 493.54 | 175.87 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 461.38 | 171.75 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 342.33 | 158.30 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 271.63 | 162.02 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 238.70 | 140.40 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 136.32 | 130.05 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 119.33 | 101.74 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 148.18 | 90.15 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 220.57 | 93.60 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 308.39 | 108.66 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 393.91 | 118.10 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 437.65 | 162.79 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 494.25 | 174.62 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 297.59 | 134.22 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 119.33 | 90.15 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 494.25 | 174.62 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 463.18 | 168.37 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 344.65 | 153.78 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 273.75 | 157.86 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 239.94 | 137.64 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 137.58 | 127.56 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 120.20 | 100.04 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 148.71 | 89.01 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 221.06 | 92.44 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 308.99 | 107.14 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 394.58 | 116.62 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 439.21 | 159.84 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 496.20 | 171.06 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 298.87 | 131.66 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 120.20 | 89.01 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 496.20 | 171.06 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 466.96 | 158.06 | 307.45 | 225.53 | 81.92 | 0.00 | 0.00 |
February | 349.59 | 140.80 | 241.64 | 148.84 | 92.80 | 0.00 | 0.00 |
March | 277.63 | 145.69 | 192.64 | 93.06 | 99.59 | 0.00 | 0.00 |
April | 242.03 | 128.24 | 160.96 | 61.37 | 99.58 | 0.00 | 0.00 |
May | 140.15 | 118.60 | 114.61 | 14.10 | 100.51 | 0.00 | 0.00 |
June | 121.97 | 93.46 | 100.55 | 6.07 | 94.48 | 0.00 | 0.00 |
July | 148.95 | 84.56 | 106.51 | 11.99 | 94.52 | 0.00 | 0.00 |
August | 221.20 | 87.68 | 136.83 | 43.16 | 93.67 | 0.00 | 0.00 |
September | 310.00 | 101.39 | 190.40 | 96.48 | 93.92 | 0.00 | 0.00 |
October | 395.99 | 110.73 | 242.14 | 161.88 | 80.26 | 0.00 | 0.00 |
November | 442.94 | 149.94 | 294.30 | 207.77 | 86.53 | 0.00 | 0.00 |
December | 500.60 | 160.01 | 328.46 | 250.00 | 78.46 | 0.00 | 0.00 |
Annual Sum or Average | 301.35 | 123.17 | 201.21 | 109.89 | 91.32 | 0.00 | 0.00 |
Minimum of Months | 121.97 | 84.56 | 100.55 | 6.07 | 78.46 | 0.00 | 0.00 |
Maximum of Months | 500.60 | 160.01 | 328.46 | 250.00 | 100.51 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.246232E+10 | 0.961971E+09 | 0.165034E+10 | 0.121060E+10 | 0.439739E+09 | 0.00 | 0.00 |
February | 0.164733E+10 | 0.808228E+09 | 0.117155E+10 | 0.721614E+09 | 0.449938E+09 | 0.00 | 0.00 |
March | 0.144062E+10 | 0.916157E+09 | 0.103407E+10 | 0.499505E+09 | 0.534566E+09 | 0.00 | 0.00 |
April | 0.123182E+10 | 0.755513E+09 | 0.836122E+09 | 0.318821E+09 | 0.517300E+09 | 0.00 | 0.00 |
May | 0.724044E+09 | 0.716942E+09 | 0.615229E+09 | 75712355.33 | 0.539517E+09 | 0.00 | 0.00 |
June | 0.613888E+09 | 0.539197E+09 | 0.522309E+09 | 31535131.19 | 0.490774E+09 | 0.00 | 0.00 |
July | 0.791003E+09 | 0.488418E+09 | 0.571711E+09 | 64358328.32 | 0.507353E+09 | 0.00 | 0.00 |
August | 0.118100E+10 | 0.506277E+09 | 0.734477E+09 | 0.231677E+09 | 0.502800E+09 | 0.00 | 0.00 |
September | 0.159938E+10 | 0.572118E+09 | 0.989056E+09 | 0.501189E+09 | 0.487867E+09 | 0.00 | 0.00 |
October | 0.211501E+10 | 0.636225E+09 | 0.129978E+10 | 0.868937E+09 | 0.430840E+09 | 0.00 | 0.00 |
November | 0.226875E+10 | 0.867238E+09 | 0.152879E+10 | 0.107930E+10 | 0.449487E+09 | 0.00 | 0.00 |
December | 0.264491E+10 | 0.967025E+09 | 0.176309E+10 | 0.134194E+10 | 0.421148E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187201E+11 | 0.873531E+10 | 0.127165E+11 | 0.694519E+10 | 0.577133E+10 | 0.00 | 0.00 |
Minimum of Months | 0.613888E+09 | 0.488418E+09 | 0.522309E+09 | 31535131.19 | 0.421148E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264491E+10 | 0.967025E+09 | 0.176309E+10 | 0.134194E+10 | 0.539517E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.121889E+10 | 0.504275E+09 | 0.825168E+09 | 0.605299E+09 | 0.219869E+09 | 0.00 | 0.00 |
February | 0.811891E+09 | 0.425618E+09 | 0.585776E+09 | 0.360807E+09 | 0.224969E+09 | 0.00 | 0.00 |
March | 0.706671E+09 | 0.486432E+09 | 0.517036E+09 | 0.249753E+09 | 0.267283E+09 | 0.00 | 0.00 |
April | 0.609388E+09 | 0.389958E+09 | 0.418061E+09 | 0.159411E+09 | 0.258650E+09 | 0.00 | 0.00 |
May | 0.355843E+09 | 0.369932E+09 | 0.307614E+09 | 37856177.66 | 0.269758E+09 | 0.00 | 0.00 |
June | 0.303071E+09 | 0.276129E+09 | 0.261154E+09 | 15767565.59 | 0.245387E+09 | 0.00 | 0.00 |
July | 0.393486E+09 | 0.247636E+09 | 0.285855E+09 | 32179164.16 | 0.253676E+09 | 0.00 | 0.00 |
August | 0.588025E+09 | 0.257615E+09 | 0.367239E+09 | 0.115839E+09 | 0.251400E+09 | 0.00 | 0.00 |
September | 0.796361E+09 | 0.291533E+09 | 0.494528E+09 | 0.250595E+09 | 0.243934E+09 | 0.00 | 0.00 |
October | 0.105298E+10 | 0.324559E+09 | 0.649889E+09 | 0.434469E+09 | 0.215420E+09 | 0.00 | 0.00 |
November | 0.112583E+10 | 0.446632E+09 | 0.764394E+09 | 0.539650E+09 | 0.224743E+09 | 0.00 | 0.00 |
December | 0.131027E+10 | 0.504369E+09 | 0.881544E+09 | 0.670970E+09 | 0.210574E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.927270E+10 | 0.452469E+10 | 0.635826E+10 | 0.347259E+10 | 0.288566E+10 | 0.00 | 0.00 |
Minimum of Months | 0.303071E+09 | 0.247636E+09 | 0.261154E+09 | 15767565.59 | 0.210574E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131027E+10 | 0.504369E+09 | 0.881544E+09 | 0.670970E+09 | 0.269758E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122045E+10 | 0.496217E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.812901E+09 | 0.418895E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.708270E+09 | 0.477926E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.609695E+09 | 0.389443E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.356266E+09 | 0.370768E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.303013E+09 | 0.281026E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.392412E+09 | 0.257326E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.586984E+09 | 0.267018E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.795254E+09 | 0.298867E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105071E+10 | 0.333422E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112551E+10 | 0.445274E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131025E+10 | 0.499798E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.927171E+10 | 0.453598E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.303013E+09 | 0.257326E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131025E+10 | 0.499798E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122320E+10 | 0.489078E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.814948E+09 | 0.413099E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.710944E+09 | 0.470518E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.610910E+09 | 0.385391E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.357270E+09 | 0.367460E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.303677E+09 | 0.278968E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.392823E+09 | 0.256167E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.587322E+09 | 0.265902E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.795696E+09 | 0.297122E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105109E+10 | 0.332045E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112676E+10 | 0.441532E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131214E+10 | 0.494526E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.928678E+10 | 0.449181E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.303677E+09 | 0.256167E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131214E+10 | 0.494526E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.122683E+10 | 0.481288E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.818310E+09 | 0.405778E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.715362E+09 | 0.461035E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.613058E+09 | 0.380144E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.359251E+09 | 0.362953E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.305199E+09 | 0.275520E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.394152E+09 | 0.253026E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.588526E+09 | 0.262723E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.796871E+09 | 0.293677E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105238E+10 | 0.328596E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.112886E+10 | 0.436889E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.131524E+10 | 0.487904E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.931404E+10 | 0.442953E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.305199E+09 | 0.253026E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131524E+10 | 0.487904E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.247047E+10 | 0.927602E+09 | 0.164695E+10 | 0.120811E+10 | 0.438837E+09 | 0.00 | 0.00 |
February | 0.165468E+10 | 0.776211E+09 | 0.116915E+10 | 0.720134E+09 | 0.449015E+09 | 0.00 | 0.00 |
March | 0.145163E+10 | 0.879306E+09 | 0.103195E+10 | 0.498481E+09 | 0.533470E+09 | 0.00 | 0.00 |
April | 0.123673E+10 | 0.734060E+09 | 0.834406E+09 | 0.318167E+09 | 0.516239E+09 | 0.00 | 0.00 |
May | 0.729257E+09 | 0.701561E+09 | 0.613967E+09 | 75557033.12 | 0.538410E+09 | 0.00 | 0.00 |
June | 0.616997E+09 | 0.532397E+09 | 0.521237E+09 | 31470437.57 | 0.489767E+09 | 0.00 | 0.00 |
July | 0.791582E+09 | 0.488390E+09 | 0.570538E+09 | 64226298.64 | 0.506312E+09 | 0.00 | 0.00 |
August | 0.118044E+10 | 0.506704E+09 | 0.732970E+09 | 0.231202E+09 | 0.501768E+09 | 0.00 | 0.00 |
September | 0.159911E+10 | 0.568838E+09 | 0.987027E+09 | 0.500161E+09 | 0.486866E+09 | 0.00 | 0.00 |
October | 0.211116E+10 | 0.637786E+09 | 0.129711E+10 | 0.867155E+09 | 0.429956E+09 | 0.00 | 0.00 |
November | 0.226991E+10 | 0.848916E+09 | 0.152565E+10 | 0.107709E+10 | 0.448565E+09 | 0.00 | 0.00 |
December | 0.264713E+10 | 0.943358E+09 | 0.175947E+10 | 0.133919E+10 | 0.420284E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.187591E+11 | 0.854513E+10 | 0.126904E+11 | 0.693094E+10 | 0.575949E+10 | 0.00 | 0.00 |
Minimum of Months | 0.616997E+09 | 0.488390E+09 | 0.521237E+09 | 31470437.57 | 0.420284E+09 | 0.00 | 0.00 |
Maximum of Months | 0.264713E+10 | 0.943358E+09 | 0.175947E+10 | 0.133919E+10 | 0.538410E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123395E+10 | 0.463251E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.825973E+09 | 0.387085E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.725126E+09 | 0.438331E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.617479E+09 | 0.366267E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.363902E+09 | 0.350413E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.308425E+09 | 0.265101E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.396168E+09 | 0.242558E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.590141E+09 | 0.251811E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.798714E+09 | 0.282970E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105435E+10 | 0.317661E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.113304E+10 | 0.424388E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.132189E+10 | 0.471054E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.936916E+10 | 0.426089E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.308425E+09 | 0.242558E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132189E+10 | 0.471054E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.123575E+10 | 0.460006E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.828158E+09 | 0.382971E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.727528E+09 | 0.433948E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.618704E+09 | 0.363910E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.365113E+09 | 0.348339E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.309297E+09 | 0.263714E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.396875E+09 | 0.241446E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.590785E+09 | 0.250689E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.799358E+09 | 0.281642E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105504E+10 | 0.316330E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.113439E+10 | 0.421962E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.132379E+10 | 0.467715E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.938479E+10 | 0.423267E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.309297E+09 | 0.241446E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132379E+10 | 0.467715E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.124057E+10 | 0.450961E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.833787E+09 | 0.372013E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.733203E+09 | 0.422825E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.621912E+09 | 0.356759E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.368484E+09 | 0.341667E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.311560E+09 | 0.259314E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.398316E+09 | 0.238411E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.592082E+09 | 0.247589E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.800898E+09 | 0.277696E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.105683E+10 | 0.312344E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.113842E+10 | 0.414305E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.132901E+10 | 0.458160E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.942508E+10 | 0.415204E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.311560E+09 | 0.238411E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.132901E+10 | 0.458160E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.125069E+10 | 0.423350E+09 | 0.823475E+09 | 0.604057E+09 | 0.219418E+09 | 0.00 | 0.00 |
February | 0.845722E+09 | 0.340617E+09 | 0.584574E+09 | 0.360067E+09 | 0.224507E+09 | 0.00 | 0.00 |
March | 0.743599E+09 | 0.390227E+09 | 0.515975E+09 | 0.249240E+09 | 0.266735E+09 | 0.00 | 0.00 |
April | 0.627336E+09 | 0.332389E+09 | 0.417203E+09 | 0.159084E+09 | 0.258120E+09 | 0.00 | 0.00 |
May | 0.375366E+09 | 0.317648E+09 | 0.306983E+09 | 37778516.56 | 0.269205E+09 | 0.00 | 0.00 |
June | 0.316139E+09 | 0.242246E+09 | 0.260619E+09 | 15735218.78 | 0.244883E+09 | 0.00 | 0.00 |
July | 0.398946E+09 | 0.226473E+09 | 0.285269E+09 | 32113149.32 | 0.253156E+09 | 0.00 | 0.00 |
August | 0.592473E+09 | 0.234836E+09 | 0.366485E+09 | 0.115601E+09 | 0.250884E+09 | 0.00 | 0.00 |
September | 0.803527E+09 | 0.262799E+09 | 0.493514E+09 | 0.250080E+09 | 0.243433E+09 | 0.00 | 0.00 |
October | 0.106061E+10 | 0.296567E+09 | 0.648555E+09 | 0.433577E+09 | 0.214978E+09 | 0.00 | 0.00 |
November | 0.114811E+10 | 0.388655E+09 | 0.762826E+09 | 0.538543E+09 | 0.224282E+09 | 0.00 | 0.00 |
December | 0.134081E+10 | 0.428572E+09 | 0.879735E+09 | 0.669593E+09 | 0.210142E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.950333E+10 | 0.388438E+10 | 0.634521E+10 | 0.346547E+10 | 0.287974E+10 | 0.00 | 0.00 |
Minimum of Months | 0.316139E+09 | 0.226473E+09 | 0.260619E+09 | 15735218.78 | 0.210142E+09 | 0.00 | 0.00 |
Maximum of Months | 0.134081E+10 | 0.428572E+09 | 0.879735E+09 | 0.669593E+09 | 0.269205E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 13.22 | 9.61 | 5.99 | 2.23 | 0.81 | 45.19 | 208.20 | 0.00 |
February | 13.28 | 10.20 | 7.03 | 3.12 | 2.96 | 66.07 | 175.60 | 0.04 |
March | 12.64 | 10.61 | 8.97 | 2.93 | 3.55 | 84.90 | 179.28 | 0.03 |
April | 15.30 | 12.62 | 10.61 | 2.62 | 4.76 | 81.20 | 282.81 | 0.02 |
May | 15.56 | 12.65 | 10.56 | 2.92 | 6.17 | 105.80 | 234.18 | 0.01 |
June | 17.67 | 14.80 | 13.02 | 2.53 | 9.03 | 98.05 | 261.27 | 0.00 |
July | 19.43 | 16.76 | 15.28 | 2.35 | 9.62 | 86.54 | 312.15 | 0.00 |
August | 19.66 | 17.23 | 15.95 | 2.55 | 9.62 | 74.58 | 307.55 | 0.00 |
September | 18.47 | 15.50 | 13.65 | 2.19 | 8.99 | 70.75 | 240.05 | 0.00 |
October | 18.77 | 13.72 | 9.60 | 2.71 | 7.74 | 53.88 | 216.36 | 0.00 |
November | 14.32 | 10.43 | 6.22 | 2.47 | 2.41 | 50.75 | 207.87 | 0.01 |
December | 13.59 | 8.82 | 3.19 | 2.50 | 0.05 | 39.49 | 221.83 | 0.00 |
Annual Sum or Average | 16.01 | 12.76 | 10.02 | 2.59 | 5.49 | 71.44 | 237.65 | 0.01 |
Minimum of Months | 12.64 | 8.82 | 3.19 | 2.19 | 0.05 | 39.49 | 175.60 | 0.00 |
Maximum of Months | 19.66 | 17.23 | 15.95 | 3.12 | 9.62 | 105.80 | 312.15 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 26.00 | 13-JAN-13:00 | 15.46 | 8.00 | 3.10 | 11.84 | 120.00 | 725.00 |
February | 26.00 | 01-FEB-11:00 | 14.67 | 6.00 | 4.10 | 10.11 | 166.00 | 715.50 |
March | 24.00 | 11-MAR-10:00 | 13.82 | 6.00 | 2.60 | 8.15 | 120.00 | 907.00 |
April | 27.00 | 26-APR-12:00 | 17.13 | 11.00 | 4.10 | 12.22 | 159.00 | 884.00 |
May | 24.00 | 03-MAY-11:00 | 15.05 | 9.00 | 4.10 | 12.98 | 187.00 | 842.50 |
June | 25.00 | 29-JUN-10:00 | 19.59 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 28.00 | 19-JUL-10:00 | 20.49 | 17.00 | 3.60 | 14.65 | 173.00 | 813.00 |
August | 28.00 | 14-AUG-10:00 | 21.19 | 18.00 | 3.60 | 14.84 | 148.00 | 840.00 |
September | 36.00 | 29-SEP-10:00 | 17.91 | 5.00 | 3.60 | 19.35 | 159.50 | 790.00 |
October | 37.00 | 16-OCT-10:00 | 17.87 | 4.00 | 5.70 | 20.05 | 122.00 | 871.50 |
November | 27.00 | 19-NOV-12:00 | 14.96 | 6.00 | 4.10 | 11.07 | 128.50 | 796.00 |
December | 26.00 | 05-DEC-09:00 | 13.09 | 1.00 | 3.60 | 8.94 | 75.50 | 857.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 24.00 | 13.09 | 1.00 | 2.60 | 8.15 | 75.50 | 715.50 | |
Maximum of Months | 37.00 | 21.19 | 18.00 | 5.70 | 20.05 | 187.00 | 907.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.00 | 08-JAN-06:00 | -0.3 | -2.0 | 3.10 | -15.5 | 11.50 | 193.50 |
February | 5.00 | 04-FEB-05:00 | 0.22 | -8.0 | 4.10 | -10.9 | 0.00 | 0.00 |
March | 4.00 | 07-MAR-04:00 | 3.53 | 3.00 | 0.00 | -11.4 | 0.00 | 0.00 |
April | 7.00 | 01-APR-05:00 | 4.33 | 1.00 | 4.10 | -9.0 | 23.50 | 211.00 |
May | 8.00 | 14-MAY-03:00 | 7.45 | 7.00 | 1.50 | -6.6 | 0.00 | 0.00 |
June | 11.00 | 13-JUN-03:00 | 9.85 | 9.00 | 2.10 | -3.4 | 0.00 | 0.00 |
July | 13.00 | 06-JUL-00:00 | 13.00 | 13.00 | 0.00 | -0.6 | 0.00 | 0.00 |
August | 14.00 | 24-AUG-01:00 | 14.00 | 14.00 | 0.00 | 0.51 | 0.00 | 0.00 |
September | 11.00 | 20-SEP-02:00 | 9.85 | 9.00 | 1.50 | -3.4 | 0.00 | 0.00 |
October | 9.00 | 12-OCT-04:00 | 6.56 | 4.00 | 3.10 | -6.4 | 0.00 | 0.00 |
November | 7.00 | 05-NOV-01:00 | 5.54 | 4.00 | 3.10 | -8.3 | 0.00 | 0.00 |
December | 5.00 | 03-DEC-00:00 | 5.00 | 5.00 | 2.10 | -0.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.00 | -0.3 | -8.0 | 0.00 | -15.5 | 0.00 | 0.00 | |
Maximum of Months | 14.00 | 14.00 | 14.00 | 4.10 | 0.51 | 23.50 | 211.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 17.04 | 17-JAN-11:00 | 24.00 | 13.00 | 3.10 | 12.79 | 223.50 | 9.00 |
February | 16.80 | 11-FEB-13:00 | 18.00 | 16.20 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 17.41 | 22-MAR-12:00 | 22.00 | 15.00 | 3.10 | 8.35 | 145.50 | 876.00 |
April | 18.33 | 26-APR-10:00 | 26.00 | 14.00 | 4.10 | 12.03 | 141.50 | 915.50 |
May | 16.69 | 05-MAY-14:00 | 18.00 | 16.00 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 19.59 | 29-JUN-10:00 | 25.00 | 17.00 | 4.60 | 11.65 | 177.50 | 829.00 |
July | 21.19 | 19-JUL-11:00 | 28.00 | 18.00 | 4.60 | 14.84 | 182.50 | 808.00 |
August | 21.20 | 18-AUG-11:00 | 28.00 | 18.00 | 3.60 | 17.21 | 244.00 | 667.50 |
September | 21.85 | 22-SEP-11:00 | 26.00 | 20.00 | 2.60 | 20.05 | 284.00 | 21.00 |
October | 21.09 | 01-OCT-11:00 | 26.00 | 19.00 | 3.60 | 13.16 | 102.00 | 899.50 |
November | 16.52 | 10-NOV-12:00 | 21.00 | 14.00 | 5.10 | 7.15 | 131.00 | 808.50 |
December | 15.64 | 07-DEC-12:00 | 20.00 | 13.00 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 15.64 | 18.00 | 13.00 | 1.10 | 5.94 | 89.00 | 9.00 | |
Maximum of Months | 21.85 | 28.00 | 20.00 | 5.10 | 20.05 | 303.50 | 915.50 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 17-JAN-12:00 | 22.00 | 16.85 | 2.10 | 11.65 | 241.50 | 67.50 |
February | 16.20 | 11-FEB-13:00 | 18.00 | 16.80 | 1.10 | 15.02 | 241.00 | 12.50 |
March | 15.00 | 23-MAR-15:20 | 21.67 | 17.34 | 3.77 | 8.02 | 112.00 | 809.83 |
April | 15.00 | 26-APR-21:19 | 16.00 | 15.39 | 2.23 | 6.15 | 0.00 | 0.00 |
May | 16.00 | 05-MAY-14:00 | 18.00 | 16.69 | 5.10 | 8.74 | 303.50 | 269.00 |
June | 17.00 | 28-JUN-08:00 | 19.00 | 17.66 | 1.50 | 16.12 | 285.00 | 428.50 |
July | 18.00 | 18-JUL-10:00 | 26.00 | 20.47 | 4.60 | 12.79 | 169.00 | 819.00 |
August | 18.10 | 14-AUG-09:00 | 26.90 | 20.93 | 3.40 | 13.73 | 139.00 | 817.00 |
September | 20.00 | 22-SEP-09:00 | 22.00 | 20.55 | 1.50 | 16.30 | 296.00 | 18.00 |
October | 19.00 | 01-OCT-07:10 | 19.17 | 19.06 | 0.25 | 16.82 | 53.33 | 0.00 |
November | 15.00 | 10-NOV-17:19 | 16.67 | 15.62 | 2.77 | 3.34 | 0.00 | 0.00 |
December | 13.00 | 07-DEC-12:00 | 20.00 | 15.64 | 5.10 | 5.94 | 89.00 | 868.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 13.00 | 16.00 | 15.39 | 0.25 | 3.34 | 0.00 | 0.00 | |
Maximum of Months | 20.00 | 26.90 | 20.93 | 5.10 | 16.82 | 303.50 | 868.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 17.43 | 27.46 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 17.38 | 30.87 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 17.83 | 38.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 18.69 | 55.75 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 19.73 | 55.13 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 20.65 | 58.21 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 21.22 | 63.49 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 21.28 | 59.02 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 20.81 | 46.26 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 19.94 | 34.64 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 18.91 | 29.25 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 17.99 | 26.27 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 19.33 | 43.77 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 17.38 | 26.27 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 21.28 | 63.49 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.319937E+09 | -204057714.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115879294.7 | 58.99 | 0.00 | 0.00 |
February | 0.290072E+09 | -185515135.6 | 0.00 | 0.00 | 672.00 | 0.00 | -104556467.1 | 58.99 | 0.00 | 0.00 |
March | 0.323128E+09 | -206493586.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116634156.8 | 58.99 | 0.00 | 0.00 |
April | 0.303619E+09 | -193129928.4 | 0.00 | 0.00 | 720.00 | 0.00 | -110489399.5 | 58.99 | 0.00 | 0.00 |
May | 0.308726E+09 | -194777831.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113948479.1 | 58.99 | 0.00 | 0.00 |
June | 0.295437E+09 | -185930557.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109506135.2 | 58.99 | 0.00 | 0.00 |
July | 0.298076E+09 | -185411974.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112663571.8 | 58.99 | 0.00 | 0.00 |
August | 0.301768E+09 | -189052048.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112715989.1 | 58.99 | 0.00 | 0.00 |
September | 0.292388E+09 | -183130512.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109257668.9 | 58.99 | 0.00 | 0.00 |
October | 0.304871E+09 | -191740945.7 | 0.00 | 0.00 | 744.00 | 0.00 | -113129574.5 | 58.99 | 0.00 | 0.00 |
November | 0.300541E+09 | -189933667.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110607486.5 | 58.99 | 0.00 | 0.00 |
December | 0.316980E+09 | -201581786.4 | 0.00 | 0.00 | 744.00 | 0.00 | -115397841.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.365554E+10 | -0.231076E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134479E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.290072E+09 | -206493586.6 | 0.00 | 0.00 | 672.00 | 0.00 | -116634156.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.323128E+09 | -183130512.2 | 0.00 | 0.00 | 744.00 | 0.00 | -104556467.1 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.318228E+09 | -204064817.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114162881.8 | 58.99 | 0.00 | 0.00 |
February | 0.288568E+09 | -185519097.4 | 0.00 | 0.00 | 672.00 | 0.00 | -103048844.1 | 58.99 | 0.00 | 0.00 |
March | 0.321099E+09 | -206487971.4 | 0.00 | 0.00 | 744.00 | 0.00 | -114611524.8 | 58.99 | 0.00 | 0.00 |
April | 0.302846E+09 | -193128155.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109718232.5 | 58.99 | 0.00 | 0.00 |
May | 0.308002E+09 | -194773340.0 | 0.00 | 0.00 | 744.00 | 0.00 | -113229029.3 | 58.99 | 0.00 | 0.00 |
June | 0.295010E+09 | -185937723.8 | 0.00 | 0.00 | 720.00 | 0.00 | -109071913.1 | 58.99 | 0.00 | 0.00 |
July | 0.297791E+09 | -185411202.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112379606.9 | 58.99 | 0.00 | 0.00 |
August | 0.301432E+09 | -189050318.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112381687.3 | 58.99 | 0.00 | 0.00 |
September | 0.292037E+09 | -183136616.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108900773.0 | 58.99 | 0.00 | 0.00 |
October | 0.304470E+09 | -191724879.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112744906.5 | 58.99 | 0.00 | 0.00 |
November | 0.299685E+09 | -189936979.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109748349.9 | 58.99 | 0.00 | 0.00 |
December | 0.315458E+09 | -201580666.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113877713.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.364463E+10 | -0.231075E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133388E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.288568E+09 | -206487971.4 | 0.00 | 0.00 | 672.00 | 0.00 | -114611524.8 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.321099E+09 | -183136616.1 | 0.00 | 0.00 | 744.00 | 0.00 | -103048844.1 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.294316E+09 | -179442783.0 | 0.00 | 0.00 | 744.00 | 0.00 | -114873685.6 | 58.99 | 0.00 | 0.00 |
February | 0.266875E+09 | -163280349.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103595047.2 | 58.99 | 0.00 | 0.00 |
March | 0.299628E+09 | -184284191.5 | 0.00 | 0.00 | 744.00 | 0.00 | -115344177.5 | 58.99 | 0.00 | 0.00 |
April | 0.279580E+09 | -169878585.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109701198.4 | 58.98 | 0.00 | 0.00 |
May | 0.285850E+09 | -172722501.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113127459.3 | 58.99 | 0.00 | 0.00 |
June | 0.274216E+09 | -165600397.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108616093.1 | 58.99 | 0.00 | 0.00 |
July | 0.273611E+09 | -162101188.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111509545.7 | 58.99 | 0.00 | 0.00 |
August | 0.280437E+09 | -168857380.8 | 0.00 | 0.00 | 744.00 | 0.00 | -111579478.0 | 58.99 | 0.00 | 0.00 |
September | 0.269192E+09 | -160953262.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108238707.3 | 58.99 | 0.00 | 0.00 |
October | 0.280545E+09 | -168628173.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111917264.9 | 58.99 | 0.00 | 0.00 |
November | 0.277575E+09 | -167732393.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109842342.7 | 58.98 | 0.00 | 0.00 |
December | 0.290283E+09 | -175960067.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114322851.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337211E+10 | -0.203944E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133267E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.266875E+09 | -184284191.5 | 0.00 | 0.00 | 672.00 | 0.00 | -115344177.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.299628E+09 | -160953262.1 | 0.00 | 0.00 | 744.00 | 0.00 | -103595047.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.294763E+09 | -179453278.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115309689.9 | 58.99 | 0.00 | 0.00 |
February | 0.267226E+09 | -163259733.7 | 0.00 | 0.00 | 672.00 | 0.00 | -103966559.3 | 58.99 | 0.00 | 0.00 |
March | 0.300078E+09 | -184289663.7 | 0.00 | 0.00 | 744.00 | 0.00 | -115788289.4 | 58.99 | 0.00 | 0.00 |
April | 0.279806E+09 | -169848641.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109957559.2 | 58.99 | 0.00 | 0.00 |
May | 0.286025E+09 | -172730472.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113294881.8 | 58.99 | 0.00 | 0.00 |
June | 0.274337E+09 | -165607929.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108729303.0 | 58.99 | 0.00 | 0.00 |
July | 0.273667E+09 | -162102296.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111564348.0 | 58.99 | 0.00 | 0.00 |
August | 0.280500E+09 | -168861770.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111638584.1 | 58.99 | 0.00 | 0.00 |
September | 0.269292E+09 | -160951436.4 | 0.00 | 0.00 | 720.00 | 0.00 | -108340998.9 | 58.99 | 0.00 | 0.00 |
October | 0.280618E+09 | -168602743.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112015458.1 | 58.99 | 0.00 | 0.00 |
November | 0.277792E+09 | -167693644.1 | 0.00 | 0.00 | 720.00 | 0.00 | -110098069.2 | 58.99 | 0.00 | 0.00 |
December | 0.290594E+09 | -175971232.9 | 0.00 | 0.00 | 744.00 | 0.00 | -114622649.9 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.337470E+10 | -0.203937E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133533E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.267226E+09 | -184289663.7 | 0.00 | 0.00 | 672.00 | 0.00 | -115788289.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.300078E+09 | -160951436.4 | 0.00 | 0.00 | 744.00 | 0.00 | -103966559.3 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.286636E+09 | -169621767.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117014678.5 | 58.99 | 0.00 | 0.00 |
February | 0.260049E+09 | -154409546.0 | 0.00 | 0.00 | 672.00 | 0.00 | -105639203.2 | 58.99 | 0.00 | 0.00 |
March | 0.292281E+09 | -174394668.4 | 0.00 | 0.00 | 744.00 | 0.00 | -117886717.2 | 58.98 | 0.00 | 0.00 |
April | 0.271805E+09 | -160742818.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111062137.4 | 58.99 | 0.00 | 0.00 |
May | 0.277663E+09 | -163354195.1 | 0.00 | 0.00 | 744.00 | 0.00 | -114308810.4 | 58.99 | 0.00 | 0.00 |
June | 0.266218E+09 | -156698444.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109519739.4 | 58.99 | 0.00 | 0.00 |
July | 0.265613E+09 | -153305378.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112307597.6 | 58.99 | 0.00 | 0.00 |
August | 0.272163E+09 | -159767870.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112395257.1 | 58.99 | 0.00 | 0.00 |
September | 0.261412E+09 | -152318597.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109093185.8 | 58.99 | 0.00 | 0.00 |
October | 0.272163E+09 | -159362296.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112800276.8 | 58.99 | 0.00 | 0.00 |
November | 0.269538E+09 | -158386583.1 | 0.00 | 0.00 | 720.00 | 0.00 | -111151755.6 | 58.99 | 0.00 | 0.00 |
December | 0.282626E+09 | -166407249.6 | 0.00 | 0.00 | 744.00 | 0.00 | -116218421.1 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327817E+10 | -0.192877E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.134940E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260049E+09 | -174394668.4 | 0.00 | 0.00 | 672.00 | 0.00 | -117886717.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.292281E+09 | -152318597.7 | 0.00 | 0.00 | 744.00 | 0.00 | -105639203.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.286697E+09 | -169620198.2 | 0.00 | 0.00 | 744.00 | 0.00 | -117076690.1 | 58.99 | 0.00 | 0.00 |
February | 0.260140E+09 | -154411789.7 | 0.00 | 0.00 | 672.00 | 0.00 | -105728219.7 | 58.99 | 0.00 | 0.00 |
March | 0.292418E+09 | -174397317.9 | 0.00 | 0.00 | 744.00 | 0.00 | -118020851.2 | 58.98 | 0.00 | 0.00 |
April | 0.271857E+09 | -160747351.8 | 0.00 | 0.00 | 720.00 | 0.00 | -111109898.8 | 58.99 | 0.00 | 0.00 |
May | 0.277695E+09 | -163357223.3 | 0.00 | 0.00 | 744.00 | 0.00 | -114337735.0 | 58.99 | 0.00 | 0.00 |
June | 0.266268E+09 | -156703623.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109564561.0 | 58.99 | 0.00 | 0.00 |
July | 0.265703E+09 | -153309617.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112393415.9 | 58.99 | 0.00 | 0.00 |
August | 0.272234E+09 | -159773725.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112459782.5 | 58.99 | 0.00 | 0.00 |
September | 0.261483E+09 | -152310033.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109173010.6 | 58.99 | 0.00 | 0.00 |
October | 0.272216E+09 | -159356797.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112859277.2 | 58.99 | 0.00 | 0.00 |
November | 0.269560E+09 | -158388507.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111171306.1 | 58.99 | 0.00 | 0.00 |
December | 0.282669E+09 | -166438624.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116230415.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.327894E+10 | -0.192881E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135013E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260140E+09 | -174397317.9 | 0.00 | 0.00 | 672.00 | 0.00 | -118020851.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.292418E+09 | -152310033.2 | 0.00 | 0.00 | 744.00 | 0.00 | -105728219.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.286922E+09 | -169611355.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117310790.1 | 58.99 | 0.00 | 0.00 |
February | 0.260423E+09 | -154405043.0 | 0.00 | 0.00 | 672.00 | 0.00 | -106018347.0 | 58.99 | 0.00 | 0.00 |
March | 0.292736E+09 | -174374135.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118362274.6 | 58.99 | 0.00 | 0.00 |
April | 0.271998E+09 | -160741137.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111256601.5 | 58.99 | 0.00 | 0.00 |
May | 0.277826E+09 | -163355019.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114471196.7 | 58.99 | 0.00 | 0.00 |
June | 0.266354E+09 | -156703131.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109651128.5 | 58.99 | 0.00 | 0.00 |
July | 0.265773E+09 | -153308138.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112465293.4 | 58.99 | 0.00 | 0.00 |
August | 0.272300E+09 | -159775716.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112523974.0 | 58.99 | 0.00 | 0.00 |
September | 0.261558E+09 | -152307943.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109250305.6 | 58.99 | 0.00 | 0.00 |
October | 0.272286E+09 | -159359075.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112927291.5 | 58.99 | 0.00 | 0.00 |
November | 0.269723E+09 | -158380600.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111342451.4 | 59.00 | 0.00 | 0.00 |
December | 0.282911E+09 | -166395570.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116515629.8 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.328081E+10 | -0.192872E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135210E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.260423E+09 | -174374135.2 | 0.00 | 0.00 | 672.00 | 0.00 | -118362274.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.292736E+09 | -152307943.3 | 0.00 | 0.00 | 744.00 | 0.00 | -106018347.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 293.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 338.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 358.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 393.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 381.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 390.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 328.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 296.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 300.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 297.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4065.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 279.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7836199.57 | 3059.15 | 03-JAN-09:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 1926602.51 | 1120.48 | 28-FEB-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.118414E+09 | 32699.99 | 30-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 247254.00 | 412.09 | 13-DEC-24:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.128425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118414E+09 | 32699.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 2735899.67 | 1932.98 | 30-MAR-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 2735899.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 2735899.67 | 1932.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 7021700.08 | 2110.52 | 03-JAN-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 15891841.63 | 3657.18 | 30-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 22913541.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 15891841.63 | 3657.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 17821796.98 | 2833.68 | 03-JAN-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 24950619.42 | 2861.51 | 30-MAR-07:07 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 42772416.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24950619.42 | 2861.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 33023984.57 | 4431.32 | 03-JAN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 494841.14 | 756.39 | 27-FEB-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 44925784.46 | 5610.58 | 30-MAR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 478735.86 | 556.56 | 01-APR-07:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 78923346.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 44925784.46 | 5610.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.110346E+09 | 24919.38 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 17752642.74 | 2000.48 | 28-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.156114E+09 | 37215.48 | 30-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1093109.13 | 693.62 | 13-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.156114E+09 | 37215.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 57244990.37 | 13827.18 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 10053810.12 | 1459.17 | 28-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 80916750.62 | 20248.15 | 30-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 100550.48 | 167.58 | 13-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.148316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 80916750.62 | 20248.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 64002065.45 | 15535.49 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 15887347.19 | 1562.28 | 27-FEB-09:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 97167906.05 | 23125.64 | 30-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 251168.14 | 402.54 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 607158.02 | 380.44 | 13-DEC-21:00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 97167906.05 | 23125.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 87227159.20 | 21143.00 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 43180055.92 | 4927.10 | 28-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.148947E+09 | 25797.94 | 30-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 935773.37 | 6105.61 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 6075980.74 | 1205.71 | 13-DEC-09:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.286366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.148947E+09 | 25797.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.151608E+09 | 27790.73 | 02-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.161008E+09 | 20872.32 | 27-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.328145E+09 | 27790.73 | 29-MAR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 3268955.88 | 17877.75 | 01-APR-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 43340964.99 | 7172.00 | 13-DEC-09:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.687371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.328145E+09 | 27790.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.127206E+10 | 0.121570E+10 | 15631.61 | 24-JAN-09:02 | 15631.61 | 0.00 |
February | 0.00 | 0.00 | 0.271838E+09 | 0.268454E+09 | 14103.57 | 01-FEB-09:02 | 14103.57 | 0.00 |
March | 0.00 | 0.00 | 0.611022E+09 | 0.522450E+09 | 11311.20 | 23-MAR-14:00 | 8770.08 | 0.00 |
April | 0.00 | 0.00 | 0.214415E+10 | 0.180884E+10 | 35197.68 | 27-APR-08:62 | 22350.15 | 0.00 |
May | 0.00 | 0.00 | 0.154963E+10 | 0.130361E+10 | 35375.74 | 03-MAY-08:62 | 24350.10 | 0.00 |
June | 0.00 | 0.00 | 0.531124E+10 | 0.397599E+10 | 36248.05 | 30-JUN-08:62 | 23417.49 | 0.00 |
July | 0.00 | 0.00 | 0.121246E+11 | 0.851797E+10 | 37125.01 | 19-JUL-08:62 | 23522.24 | 0.00 |
August | 0.00 | 0.00 | 0.132703E+11 | 0.915067E+10 | 37400.90 | 14-AUG-08:62 | 23330.03 | 0.00 |
September | 0.00 | 0.00 | 0.724257E+10 | 0.552819E+10 | 37616.31 | 22-SEP-08:62 | 19124.12 | 0.00 |
October | 0.00 | 0.00 | 0.887512E+10 | 0.747404E+10 | 37163.18 | 01-OCT-07:03 | 17701.61 | 0.00 |
November | 0.00 | 0.00 | 0.116479E+10 | 0.113410E+10 | 21900.39 | 10-NOV-09:02 | 15621.50 | 0.00 |
December | 0.00 | 0.00 | 0.155004E+10 | 0.154008E+10 | 33279.73 | 05-DEC-09:02 | 33279.73 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.553874E+11 | 0.424401E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.271838E+09 | 0.268454E+09 | 11311.20 | 8770.08 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132703E+11 | 0.915067E+10 | 37616.31 | 33279.73 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.847463E+09 | 0.804398E+09 | 17724.06 | 21-JAN-09:02 | 10996.76 | 0.00 |
February | 0.00 | 0.00 | 0.242634E+09 | 0.233652E+09 | 17382.37 | 05-FEB-18:10 | 17250.70 | 0.00 |
March | 0.00 | 0.00 | 0.460417E+09 | 0.392736E+09 | 6642.65 | 23-MAR-14:00 | 5166.72 | 0.00 |
April | 0.00 | 0.00 | 0.140665E+10 | 0.118683E+10 | 18750.11 | 26-APR-08:62 | 15066.94 | 0.00 |
May | 0.00 | 0.00 | 0.107645E+10 | 0.904346E+09 | 18697.41 | 03-MAY-08:62 | 12979.32 | 0.00 |
June | 0.00 | 0.00 | 0.318088E+10 | 0.239731E+10 | 19160.37 | 30-JUN-08:62 | 12447.38 | 0.00 |
July | 0.00 | 0.00 | 0.711542E+10 | 0.500493E+10 | 19605.93 | 19-JUL-08:62 | 12561.58 | 0.00 |
August | 0.00 | 0.00 | 0.768767E+10 | 0.531199E+10 | 19755.65 | 14-AUG-08:62 | 12448.07 | 0.00 |
September | 0.00 | 0.00 | 0.431085E+10 | 0.326183E+10 | 19692.45 | 21-SEP-20:52 | 10165.50 | 0.00 |
October | 0.00 | 0.00 | 0.539621E+10 | 0.450139E+10 | 19623.90 | 01-OCT-07:03 | 9471.99 | 0.00 |
November | 0.00 | 0.00 | 0.790882E+09 | 0.761276E+09 | 18442.20 | 10-NOV-09:02 | 13251.86 | 0.00 |
December | 0.00 | 0.00 | 0.108142E+10 | 0.107136E+10 | 17617.12 | 05-DEC-09:02 | 17617.12 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.335969E+11 | 0.258320E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.242634E+09 | 0.233652E+09 | 6642.65 | 5166.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.768767E+10 | 0.531199E+10 | 19755.65 | 17617.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.736356E+09 | 0.704135E+09 | 12991.91 | 21-JAN-08:62 | 7640.52 | 0.00 |
February | 0.00 | 0.00 | 0.177844E+09 | 0.175844E+09 | 5813.01 | 01-FEB-12:10 | 5813.01 | 0.00 |
March | 0.00 | 0.00 | 0.378516E+09 | 0.325939E+09 | 6162.99 | 23-MAR-14:00 | 4797.37 | 0.00 |
April | 0.00 | 0.00 | 0.116753E+10 | 0.991052E+09 | 18471.80 | 27-APR-07:03 | 11363.23 | 0.00 |
May | 0.00 | 0.00 | 0.873828E+09 | 0.737226E+09 | 18549.75 | 03-MAY-07:03 | 12056.51 | 0.00 |
June | 0.00 | 0.00 | 0.283800E+10 | 0.214380E+10 | 19009.67 | 30-JUN-07:02 | 11304.12 | 0.00 |
July | 0.00 | 0.00 | 0.605206E+10 | 0.430434E+10 | 19581.56 | 23-JUL-08:62 | 13128.69 | 0.00 |
August | 0.00 | 0.00 | 0.677911E+10 | 0.472632E+10 | 19569.32 | 19-AUG-07:02 | 10806.40 | 0.00 |
September | 0.00 | 0.00 | 0.372250E+10 | 0.283849E+10 | 19507.35 | 22-SEP-07:02 | 10201.73 | 0.00 |
October | 0.00 | 0.00 | 0.452397E+10 | 0.383364E+10 | 19595.64 | 05-OCT-07:01 | 10602.75 | 0.00 |
November | 0.00 | 0.00 | 0.669787E+09 | 0.652072E+09 | 17789.68 | 19-NOV-09:02 | 17789.68 | 0.00 |
December | 0.00 | 0.00 | 0.942843E+09 | 0.936325E+09 | 6763.69 | 19-DEC-13:10 | 6763.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.288623E+11 | 0.223692E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.177844E+09 | 0.175844E+09 | 5813.01 | 4797.37 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.677911E+10 | 0.472632E+10 | 19595.64 | 17789.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.705061E+09 | 0.675121E+09 | 11422.89 | 21-JAN-08:62 | 6709.00 | 0.00 |
February | 0.00 | 0.00 | 0.168126E+09 | 0.166665E+09 | 5683.46 | 01-FEB-12:10 | 5683.46 | 0.00 |
March | 0.00 | 0.00 | 0.355514E+09 | 0.306336E+09 | 6051.26 | 23-MAR-14:00 | 4709.64 | 0.00 |
April | 0.00 | 0.00 | 0.111250E+10 | 0.944531E+09 | 18519.40 | 27-APR-07:03 | 11381.77 | 0.00 |
May | 0.00 | 0.00 | 0.827561E+09 | 0.698945E+09 | 18598.24 | 03-MAY-07:03 | 12077.58 | 0.00 |
June | 0.00 | 0.00 | 0.277504E+10 | 0.209562E+10 | 19060.79 | 30-JUN-07:02 | 11325.85 | 0.00 |
July | 0.00 | 0.00 | 0.598874E+10 | 0.425989E+10 | 19634.53 | 23-JUL-08:62 | 13161.42 | 0.00 |
August | 0.00 | 0.00 | 0.671829E+10 | 0.468530E+10 | 19622.39 | 19-AUG-07:02 | 10831.29 | 0.00 |
September | 0.00 | 0.00 | 0.365813E+10 | 0.279234E+10 | 19559.37 | 22-SEP-07:02 | 10223.74 | 0.00 |
October | 0.00 | 0.00 | 0.448394E+10 | 0.380049E+10 | 19649.41 | 05-OCT-07:01 | 10631.16 | 0.00 |
November | 0.00 | 0.00 | 0.642902E+09 | 0.626944E+09 | 17831.65 | 19-NOV-09:02 | 17831.65 | 0.00 |
December | 0.00 | 0.00 | 0.890728E+09 | 0.884742E+09 | 6635.34 | 19-DEC-13:10 | 6635.34 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.283265E+11 | 0.219369E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.168126E+09 | 0.166665E+09 | 5683.46 | 4709.64 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.671829E+10 | 0.468530E+10 | 19649.41 | 17831.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.645394E+09 | 0.619277E+09 | 7877.86 | 21-JAN-08:62 | 4610.75 | 0.00 |
February | 0.00 | 0.00 | 0.151064E+09 | 0.150116E+09 | 5398.15 | 01-FEB-12:10 | 5398.15 | 0.00 |
March | 0.00 | 0.00 | 0.314746E+09 | 0.271372E+09 | 5783.90 | 23-MAR-14:00 | 4497.72 | 0.00 |
April | 0.00 | 0.00 | 0.101400E+10 | 0.860929E+09 | 15381.75 | 27-APR-07:03 | 9425.17 | 0.00 |
May | 0.00 | 0.00 | 0.738715E+09 | 0.624891E+09 | 17444.23 | 03-MAY-07:03 | 11294.37 | 0.00 |
June | 0.00 | 0.00 | 0.260814E+10 | 0.196704E+10 | 18921.52 | 30-JUN-07:02 | 11204.55 | 0.00 |
July | 0.00 | 0.00 | 0.574703E+10 | 0.408207E+10 | 19491.37 | 23-JUL-08:62 | 13027.86 | 0.00 |
August | 0.00 | 0.00 | 0.646582E+10 | 0.450422E+10 | 19479.69 | 19-AUG-07:02 | 10713.63 | 0.00 |
September | 0.00 | 0.00 | 0.347151E+10 | 0.265550E+10 | 19415.14 | 22-SEP-07:02 | 10112.29 | 0.00 |
October | 0.00 | 0.00 | 0.429822E+10 | 0.364826E+10 | 19507.05 | 05-OCT-07:01 | 10515.10 | 0.00 |
November | 0.00 | 0.00 | 0.594438E+09 | 0.581119E+09 | 17236.76 | 19-NOV-09:02 | 17236.76 | 0.00 |
December | 0.00 | 0.00 | 0.802815E+09 | 0.797435E+09 | 6377.07 | 19-DEC-13:10 | 6377.07 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.268519E+11 | 0.207622E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.151064E+09 | 0.150116E+09 | 5398.15 | 4497.72 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.646582E+10 | 0.450422E+10 | 19507.05 | 17236.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.100730E+10 | 0.965867E+09 | 12630.32 | 20-JAN-09:02 | 9253.23 | 0.00 |
February | 0.00 | 0.00 | 0.233513E+09 | 0.232121E+09 | 9083.46 | 01-FEB-12:10 | 9083.46 | 0.00 |
March | 0.00 | 0.00 | 0.482966E+09 | 0.415301E+09 | 10041.14 | 23-MAR-14:10 | 7674.54 | 0.00 |
April | 0.00 | 0.00 | 0.165476E+10 | 0.139447E+10 | 33336.47 | 27-APR-08:62 | 21298.72 | 0.00 |
May | 0.00 | 0.00 | 0.117018E+10 | 0.987228E+09 | 33560.17 | 03-MAY-08:62 | 23035.02 | 0.00 |
June | 0.00 | 0.00 | 0.430292E+10 | 0.322677E+10 | 34255.65 | 30-JUN-08:62 | 22689.36 | 0.00 |
July | 0.00 | 0.00 | 0.969977E+10 | 0.682187E+10 | 35540.15 | 30-JUL-09:02 | 22030.56 | 0.00 |
August | 0.00 | 0.00 | 0.109106E+11 | 0.754317E+10 | 35477.10 | 14-AUG-08:62 | 22132.98 | 0.00 |
September | 0.00 | 0.00 | 0.587039E+10 | 0.448935E+10 | 35529.83 | 22-SEP-08:62 | 18683.18 | 0.00 |
October | 0.00 | 0.00 | 0.718503E+10 | 0.610505E+10 | 35270.80 | 01-OCT-09:02 | 20615.83 | 0.00 |
November | 0.00 | 0.00 | 0.932209E+09 | 0.912668E+09 | 32407.28 | 19-NOV-10:02 | 32407.28 | 0.00 |
December | 0.00 | 0.00 | 0.122221E+10 | 0.121384E+10 | 27177.19 | 05-DEC-09:02 | 27177.19 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.446719E+11 | 0.343077E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.233513E+09 | 0.232121E+09 | 9083.46 | 7674.54 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.109106E+11 | 0.754317E+10 | 35540.15 | 32407.28 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.513820E+09 | 0.493215E+09 | 5691.42 | 14-JAN-15:00 | 5691.42 | 0.00 |
February | 0.00 | 0.00 | 0.117354E+09 | 0.116702E+09 | 4659.06 | 01-FEB-12:10 | 4659.06 | 0.00 |
March | 0.00 | 0.00 | 0.239601E+09 | 0.206082E+09 | 5165.18 | 23-MAR-14:10 | 3952.20 | 0.00 |
April | 0.00 | 0.00 | 0.832089E+09 | 0.701699E+09 | 15003.41 | 27-APR-08:62 | 9586.34 | 0.00 |
May | 0.00 | 0.00 | 0.584834E+09 | 0.494282E+09 | 17368.70 | 03-MAY-08:62 | 11925.16 | 0.00 |
June | 0.00 | 0.00 | 0.219407E+10 | 0.164690E+10 | 17727.71 | 30-JUN-08:62 | 11745.93 | 0.00 |
July | 0.00 | 0.00 | 0.499218E+10 | 0.351671E+10 | 18394.08 | 30-JUL-09:02 | 11398.03 | 0.00 |
August | 0.00 | 0.00 | 0.562642E+10 | 0.389665E+10 | 18363.23 | 14-AUG-08:62 | 11453.72 | 0.00 |
September | 0.00 | 0.00 | 0.300810E+10 | 0.230465E+10 | 18390.71 | 22-SEP-08:62 | 9666.89 | 0.00 |
October | 0.00 | 0.00 | 0.371326E+10 | 0.315809E+10 | 18257.77 | 01-OCT-09:02 | 10660.25 | 0.00 |
November | 0.00 | 0.00 | 0.478365E+09 | 0.468630E+09 | 16758.18 | 19-NOV-10:02 | 16758.18 | 0.00 |
December | 0.00 | 0.00 | 0.620130E+09 | 0.615867E+09 | 12432.21 | 05-DEC-09:02 | 12432.21 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.229202E+11 | 0.176195E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.117354E+09 | 0.116702E+09 | 4659.06 | 3952.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.562642E+10 | 0.389665E+10 | 18394.08 | 16758.18 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.493525E+09 | 0.474103E+09 | 5571.52 | 18-JAN-13:10 | 5571.52 | 0.00 |
February | 0.00 | 0.00 | 0.111526E+09 | 0.110943E+09 | 4533.97 | 01-FEB-12:10 | 4533.97 | 0.00 |
March | 0.00 | 0.00 | 0.226478E+09 | 0.194869E+09 | 5040.78 | 23-MAR-14:10 | 3855.01 | 0.00 |
April | 0.00 | 0.00 | 0.800959E+09 | 0.675296E+09 | 13272.42 | 27-APR-08:62 | 8469.04 | 0.00 |
May | 0.00 | 0.00 | 0.559155E+09 | 0.472665E+09 | 17291.73 | 03-MAY-08:62 | 11856.93 | 0.00 |
June | 0.00 | 0.00 | 0.213882E+10 | 0.160430E+10 | 17649.87 | 30-JUN-08:62 | 11678.14 | 0.00 |
July | 0.00 | 0.00 | 0.491303E+10 | 0.345852E+10 | 18313.04 | 30-JUL-09:02 | 11333.11 | 0.00 |
August | 0.00 | 0.00 | 0.554534E+10 | 0.383825E+10 | 18282.31 | 14-AUG-08:62 | 11388.46 | 0.00 |
September | 0.00 | 0.00 | 0.294751E+10 | 0.225990E+10 | 18308.88 | 22-SEP-08:62 | 9613.15 | 0.00 |
October | 0.00 | 0.00 | 0.365148E+10 | 0.310707E+10 | 18177.40 | 01-OCT-09:02 | 10600.99 | 0.00 |
November | 0.00 | 0.00 | 0.460454E+09 | 0.451465E+09 | 16670.87 | 19-NOV-10:02 | 16670.87 | 0.00 |
December | 0.00 | 0.00 | 0.589528E+09 | 0.585469E+09 | 10745.90 | 05-DEC-09:02 | 10745.90 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.224378E+11 | 0.172329E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.111526E+09 | 0.110943E+09 | 4533.97 | 3855.01 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.554534E+10 | 0.383825E+10 | 18313.04 | 16670.87 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.445354E+09 | 0.429021E+09 | 5329.30 | 18-JAN-13:10 | 5329.30 | 0.00 |
February | 0.00 | 0.00 | 96470806.28 | 96050991.10 | 4241.50 | 01-FEB-12:10 | 4241.50 | 0.00 |
March | 0.00 | 0.00 | 0.198317E+09 | 0.171033E+09 | 4745.53 | 23-MAR-14:10 | 3628.23 | 0.00 |
April | 0.00 | 0.00 | 0.728286E+09 | 0.614475E+09 | 7393.85 | 27-APR-08:62 | 4701.30 | 0.00 |
May | 0.00 | 0.00 | 0.496388E+09 | 0.420411E+09 | 12426.84 | 03-MAY-08:62 | 8491.64 | 0.00 |
June | 0.00 | 0.00 | 0.199943E+10 | 0.149848E+10 | 17530.02 | 30-JUN-08:62 | 11558.92 | 0.00 |
July | 0.00 | 0.00 | 0.473787E+10 | 0.333356E+10 | 18188.33 | 30-JUL-09:02 | 11223.22 | 0.00 |
August | 0.00 | 0.00 | 0.536716E+10 | 0.371374E+10 | 18157.45 | 14-AUG-08:62 | 11276.57 | 0.00 |
September | 0.00 | 0.00 | 0.279430E+10 | 0.214979E+10 | 18181.58 | 22-SEP-08:62 | 9518.48 | 0.00 |
October | 0.00 | 0.00 | 0.349456E+10 | 0.297950E+10 | 18054.26 | 01-OCT-09:02 | 10503.87 | 0.00 |
November | 0.00 | 0.00 | 0.414599E+09 | 0.407680E+09 | 16520.44 | 19-NOV-10:02 | 16520.44 | 0.00 |
December | 0.00 | 0.00 | 0.516847E+09 | 0.513386E+09 | 5429.80 | 05-DEC-09:02 | 5429.80 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.212896E+11 | 0.163271E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 96470806.28 | 96050991.10 | 4241.50 | 3628.23 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.536716E+10 | 0.371374E+10 | 18188.33 | 16520.44 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.419722E+09 | 0.405415E+09 | 5409.33 | 18-JAN-13:10 | 5409.33 | 0.00 |
February | 0.00 | 0.00 | 85404090.83 | 85104944.65 | 4434.31 | 01-FEB-12:10 | 4434.31 | 0.00 |
March | 0.00 | 0.00 | 0.199848E+09 | 0.172762E+09 | 4763.39 | 23-MAR-14:10 | 3640.46 | 0.00 |
April | 0.00 | 0.00 | 0.770908E+09 | 0.652873E+09 | 7526.89 | 26-APR-13:00 | 6832.14 | 0.00 |
May | 0.00 | 0.00 | 0.503897E+09 | 0.428334E+09 | 6181.87 | 04-MAY-12:10 | 5437.24 | 0.00 |
June | 0.00 | 0.00 | 0.206600E+10 | 0.155441E+10 | 18938.86 | 30-JUN-08:62 | 12395.40 | 0.00 |
July | 0.00 | 0.00 | 0.507288E+10 | 0.359238E+10 | 19641.21 | 30-JUL-09:02 | 12108.61 | 0.00 |
August | 0.00 | 0.00 | 0.573899E+10 | 0.399566E+10 | 19612.90 | 14-AUG-08:62 | 12141.70 | 0.00 |
September | 0.00 | 0.00 | 0.280425E+10 | 0.217978E+10 | 19645.23 | 22-SEP-08:62 | 10172.80 | 0.00 |
October | 0.00 | 0.00 | 0.347262E+10 | 0.300093E+10 | 19507.35 | 01-OCT-09:02 | 11225.69 | 0.00 |
November | 0.00 | 0.00 | 0.387734E+09 | 0.383473E+09 | 17369.36 | 19-NOV-10:02 | 17369.36 | 0.00 |
December | 0.00 | 0.00 | 0.465582E+09 | 0.463027E+09 | 5494.02 | 19-DEC-13:10 | 5494.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219878E+11 | 0.169141E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 85404090.83 | 85104944.65 | 4434.31 | 3640.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.573899E+10 | 0.399566E+10 | 19645.23 | 17369.36 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.386611E+10 | 0.60 | 2130.79 | 14-JAN-15:20 | 0.89 |
February | 0.349791E+10 | 0.60 | 2130.79 | 01-FEB-09:15 | 0.89 |
March | 0.388145E+10 | 0.60 | 2130.79 | 11-MAR-13:10 | 0.89 |
April | 0.374338E+10 | 0.60 | 2130.79 | 04-APR-14:20 | 0.89 |
May | 0.386611E+10 | 0.60 | 2130.79 | 01-MAY-16:10 | 0.89 |
June | 0.375872E+10 | 0.60 | 2130.79 | 02-JUN-08:30 | 0.89 |
July | 0.386611E+10 | 0.60 | 2130.79 | 01-JUL-18:03 | 0.88 |
August | 0.387378E+10 | 0.60 | 2130.79 | 10-AUG-18:20 | 0.88 |
September | 0.375105E+10 | 0.60 | 2130.79 | 01-SEP-11:40 | 0.89 |
October | 0.386611E+10 | 0.60 | 2130.79 | 01-OCT-08:30 | 0.88 |
November | 0.373571E+10 | 0.60 | 2130.79 | 06-NOV-15:00 | 0.89 |
December | 0.388145E+10 | 0.61 | 2130.79 | 05-DEC-10:00 | 0.89 |
Annual Sum or Average | 0.455879E+11 | 0.60 | |||
Minimum of Months | 0.349791E+10 | 0.60 | 2130.79 | 0.88 | |
Maximum of Months | 0.388145E+10 | 0.61 | 2130.79 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.188749E+10 | 0.62 | 1171.40 | 13-JAN-10:40 | 0.92 |
February | 0.169848E+10 | 0.62 | 1171.40 | 01-FEB-11:30 | 0.92 |
March | 0.187113E+10 | 0.62 | 1171.40 | 10-MAR-09:10 | 0.92 |
April | 0.198687E+10 | 0.62 | 1171.40 | 01-APR-16:00 | 0.93 |
May | 0.206488E+10 | 0.62 | 1171.40 | 01-MAY-08:30 | 0.92 |
June | 0.204444E+10 | 0.62 | 1171.40 | 03-JUN-11:00 | 0.92 |
July | 0.204048E+10 | 0.61 | 1171.40 | 01-JUL-14:10 | 0.91 |
August | 0.206871E+10 | 0.61 | 1171.40 | 01-AUG-08:04 | 0.91 |
September | 0.200493E+10 | 0.62 | 1171.40 | 01-SEP-12:20 | 0.92 |
October | 0.202720E+10 | 0.61 | 1171.40 | 02-OCT-08:30 | 0.91 |
November | 0.194634E+10 | 0.62 | 1171.40 | 03-NOV-09:00 | 0.92 |
December | 0.190553E+10 | 0.63 | 1171.40 | 04-DEC-10:20 | 0.92 |
Annual Sum or Average | 0.235465E+11 | 0.62 | |||
Minimum of Months | 0.169848E+10 | 0.61 | 1171.40 | 0.91 | |
Maximum of Months | 0.206871E+10 | 0.63 | 1171.40 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.169751E+10 | 0.50 | 1172.96 | 01-JAN-17:30 | 0.92 |
February | 0.153705E+10 | 0.50 | 1172.96 | 01-FEB-08:20 | 0.92 |
March | 0.173129E+10 | 0.51 | 1172.96 | 21-MAR-12:30 | 0.92 |
April | 0.164684E+10 | 0.50 | 1172.96 | 01-APR-10:00 | 0.92 |
May | 0.171440E+10 | 0.50 | 1172.96 | 01-MAY-07:30 | 0.92 |
June | 0.167218E+10 | 0.50 | 1172.96 | 01-JUN-09:30 | 0.92 |
July | 0.168907E+10 | 0.49 | 1172.96 | 01-JUL-07:30 | 0.91 |
August | 0.173129E+10 | 0.50 | 1172.96 | 01-AUG-07:15 | 0.91 |
September | 0.164684E+10 | 0.50 | 1172.96 | 01-SEP-07:30 | 0.92 |
October | 0.169751E+10 | 0.50 | 1172.96 | 01-OCT-08:09 | 0.91 |
November | 0.164684E+10 | 0.50 | 1172.96 | 06-NOV-11:00 | 0.92 |
December | 0.168907E+10 | 0.50 | 1172.96 | 01-DEC-11:20 | 0.92 |
Annual Sum or Average | 0.200999E+11 | 0.50 | |||
Minimum of Months | 0.153705E+10 | 0.49 | 1172.96 | 0.91 | |
Maximum of Months | 0.173129E+10 | 0.51 | 1172.96 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.170264E+10 | 0.50 | 1176.51 | 01-JAN-09:25 | 0.92 |
February | 0.154170E+10 | 0.50 | 1176.51 | 02-FEB-13:30 | 0.92 |
March | 0.173653E+10 | 0.51 | 1176.51 | 02-MAR-12:10 | 0.92 |
April | 0.165182E+10 | 0.50 | 1176.51 | 01-APR-15:20 | 0.93 |
May | 0.171959E+10 | 0.50 | 1176.51 | 01-MAY-13:30 | 0.92 |
June | 0.167723E+10 | 0.50 | 1176.51 | 01-JUN-11:00 | 0.92 |
July | 0.169417E+10 | 0.49 | 1176.51 | 02-JUL-08:03 | 0.91 |
August | 0.173653E+10 | 0.50 | 1176.51 | 02-AUG-08:15 | 0.91 |
September | 0.165182E+10 | 0.50 | 1176.51 | 01-SEP-16:10 | 0.92 |
October | 0.170264E+10 | 0.50 | 1176.51 | 02-OCT-08:05 | 0.91 |
November | 0.165182E+10 | 0.50 | 1176.51 | 07-NOV-11:50 | 0.92 |
December | 0.169417E+10 | 0.50 | 1176.51 | 01-DEC-11:20 | 0.92 |
Annual Sum or Average | 0.201607E+11 | 0.50 | |||
Minimum of Months | 0.154170E+10 | 0.49 | 1176.51 | 0.91 | |
Maximum of Months | 0.173653E+10 | 0.51 | 1176.51 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.168915E+10 | 0.50 | 1167.18 | 01-JAN-09:20 | 0.92 |
February | 0.152948E+10 | 0.50 | 1167.18 | 01-FEB-09:00 | 0.92 |
March | 0.172276E+10 | 0.51 | 1167.18 | 01-MAR-11:00 | 0.92 |
April | 0.163873E+10 | 0.50 | 1167.18 | 01-APR-07:15 | 0.92 |
May | 0.170596E+10 | 0.50 | 1167.18 | 01-MAY-11:40 | 0.92 |
June | 0.166394E+10 | 0.50 | 1167.18 | 01-JUN-09:30 | 0.92 |
July | 0.168075E+10 | 0.49 | 1167.18 | 08-JUL-07:30 | 0.92 |
August | 0.172276E+10 | 0.50 | 1167.18 | 01-AUG-07:30 | 0.91 |
September | 0.163873E+10 | 0.50 | 1167.18 | 15-SEP-10:10 | 0.92 |
October | 0.168915E+10 | 0.50 | 1167.18 | 01-OCT-08:40 | 0.91 |
November | 0.163873E+10 | 0.50 | 1167.18 | 06-NOV-11:20 | 0.92 |
December | 0.168075E+10 | 0.50 | 1167.18 | 25-DEC-11:30 | 0.93 |
Annual Sum or Average | 0.200009E+11 | 0.50 | |||
Minimum of Months | 0.152948E+10 | 0.49 | 1167.18 | 0.91 | |
Maximum of Months | 0.172276E+10 | 0.51 | 1167.18 | 0.93 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.268231E+10 | 0.44 | 2008.32 | 01-JAN-14:50 | 0.89 |
February | 0.242927E+10 | 0.44 | 2008.32 | 07-FEB-11:00 | 0.90 |
March | 0.274015E+10 | 0.45 | 2008.32 | 11-MAR-14:40 | 0.89 |
April | 0.260278E+10 | 0.44 | 2008.32 | 03-APR-09:40 | 0.89 |
May | 0.271123E+10 | 0.45 | 2008.32 | 01-MAY-11:00 | 0.89 |
June | 0.264616E+10 | 0.45 | 2008.32 | 03-JUN-10:00 | 0.89 |
July | 0.266785E+10 | 0.44 | 2008.32 | 06-JUL-09:50 | 0.89 |
August | 0.274015E+10 | 0.45 | 2008.32 | 02-AUG-17:40 | 0.88 |
September | 0.260278E+10 | 0.44 | 2008.32 | 06-SEP-11:10 | 0.88 |
October | 0.268231E+10 | 0.44 | 2008.32 | 03-OCT-19:15 | 0.88 |
November | 0.260278E+10 | 0.44 | 2008.32 | 10-NOV-14:00 | 0.89 |
December | 0.266785E+10 | 0.44 | 2008.32 | 07-DEC-12:50 | 0.89 |
Annual Sum or Average | 0.317757E+11 | 0.44 | |||
Minimum of Months | 0.242927E+10 | 0.44 | 2008.32 | 0.88 | |
Maximum of Months | 0.274015E+10 | 0.45 | 2008.32 | 0.90 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.144399E+10 | 0.46 | 1081.15 | 01-JAN-12:00 | 0.92 |
February | 0.130776E+10 | 0.46 | 1081.15 | 01-FEB-09:05 | 0.92 |
March | 0.147513E+10 | 0.47 | 1081.15 | 08-MAR-09:30 | 0.92 |
April | 0.140118E+10 | 0.46 | 1081.15 | 01-APR-13:20 | 0.92 |
May | 0.145956E+10 | 0.46 | 1081.15 | 01-MAY-13:30 | 0.92 |
June | 0.142453E+10 | 0.47 | 1081.15 | 01-JUN-12:00 | 0.92 |
July | 0.143621E+10 | 0.45 | 1081.15 | 01-JUL-08:10 | 0.91 |
August | 0.147513E+10 | 0.47 | 1081.15 | 02-AUG-08:15 | 0.91 |
September | 0.140118E+10 | 0.46 | 1081.15 | 01-SEP-09:40 | 0.92 |
October | 0.144399E+10 | 0.46 | 1081.15 | 02-OCT-08:08 | 0.91 |
November | 0.140118E+10 | 0.46 | 1081.15 | 07-NOV-13:20 | 0.92 |
December | 0.143621E+10 | 0.46 | 1081.15 | 04-DEC-13:00 | 0.92 |
Annual Sum or Average | 0.171060E+11 | 0.46 | |||
Minimum of Months | 0.130776E+10 | 0.45 | 1081.15 | 0.91 | |
Maximum of Months | 0.147513E+10 | 0.47 | 1081.15 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.143684E+10 | 0.46 | 1075.80 | 01-JAN-10:10 | 0.92 |
February | 0.130129E+10 | 0.46 | 1075.80 | 01-FEB-09:20 | 0.92 |
March | 0.146782E+10 | 0.47 | 1075.80 | 06-MAR-09:40 | 0.92 |
April | 0.139424E+10 | 0.46 | 1075.80 | 01-APR-08:05 | 0.92 |
May | 0.145233E+10 | 0.46 | 1075.80 | 01-MAY-11:10 | 0.92 |
June | 0.141747E+10 | 0.47 | 1075.80 | 01-JUN-11:20 | 0.92 |
July | 0.142909E+10 | 0.45 | 1075.80 | 01-JUL-13:00 | 0.91 |
August | 0.146782E+10 | 0.47 | 1075.80 | 01-AUG-09:30 | 0.91 |
September | 0.139424E+10 | 0.46 | 1075.80 | 01-SEP-08:30 | 0.92 |
October | 0.143684E+10 | 0.46 | 1075.80 | 24-OCT-14:30 | 0.92 |
November | 0.139424E+10 | 0.46 | 1075.80 | 07-NOV-14:00 | 0.92 |
December | 0.142909E+10 | 0.46 | 1075.80 | 01-DEC-14:10 | 0.92 |
Annual Sum or Average | 0.170213E+11 | 0.46 | |||
Minimum of Months | 0.130129E+10 | 0.45 | 1075.80 | 0.91 | |
Maximum of Months | 0.146782E+10 | 0.47 | 1075.80 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142910E+10 | 0.46 | 1070.01 | 01-JAN-11:20 | 0.92 |
February | 0.129428E+10 | 0.46 | 1070.01 | 27-FEB-10:30 | 0.92 |
March | 0.145992E+10 | 0.47 | 1070.01 | 07-MAR-19:00 | 0.92 |
April | 0.138673E+10 | 0.46 | 1070.01 | 20-APR-13:00 | 0.92 |
May | 0.144451E+10 | 0.46 | 1070.01 | 04-MAY-14:10 | 0.92 |
June | 0.140984E+10 | 0.47 | 1070.01 | 02-JUN-14:10 | 0.92 |
July | 0.142140E+10 | 0.45 | 1070.01 | 17-JUL-11:00 | 0.91 |
August | 0.145992E+10 | 0.47 | 1070.01 | 01-AUG-08:30 | 0.91 |
September | 0.138673E+10 | 0.46 | 1070.01 | 03-SEP-09:30 | 0.92 |
October | 0.142910E+10 | 0.46 | 1070.01 | 19-OCT-13:20 | 0.92 |
November | 0.138673E+10 | 0.46 | 1070.01 | 02-NOV-10:20 | 0.92 |
December | 0.142140E+10 | 0.46 | 1070.01 | 07-DEC-10:20 | 0.92 |
Annual Sum or Average | 0.169296E+11 | 0.46 | |||
Minimum of Months | 0.129428E+10 | 0.45 | 1070.01 | 0.91 | |
Maximum of Months | 0.145992E+10 | 0.47 | 1070.01 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.157103E+10 | 0.46 | 1176.27 | 01-JAN-16:50 | 0.92 |
February | 0.142282E+10 | 0.46 | 1176.27 | 01-FEB-13:50 | 0.92 |
March | 0.160490E+10 | 0.47 | 1176.27 | 01-MAR-20:50 | 0.92 |
April | 0.152445E+10 | 0.46 | 1176.27 | 01-APR-14:40 | 0.93 |
May | 0.158797E+10 | 0.46 | 1176.27 | 02-MAY-11:20 | 0.92 |
June | 0.154985E+10 | 0.47 | 1176.27 | 01-JUN-13:00 | 0.92 |
July | 0.156256E+10 | 0.45 | 1176.27 | 01-JUL-08:50 | 0.91 |
August | 0.160490E+10 | 0.47 | 1176.27 | 10-AUG-09:00 | 0.91 |
September | 0.152445E+10 | 0.46 | 1176.27 | 05-SEP-13:40 | 0.91 |
October | 0.157103E+10 | 0.46 | 1176.27 | 03-OCT-08:30 | 0.91 |
November | 0.152445E+10 | 0.46 | 1176.27 | 09-NOV-16:40 | 0.91 |
December | 0.156256E+10 | 0.46 | 1176.27 | 04-DEC-11:40 | 0.92 |
Annual Sum or Average | 0.186110E+11 | 0.46 | |||
Minimum of Months | 0.142282E+10 | 0.45 | 1176.27 | 0.91 | |
Maximum of Months | 0.160490E+10 | 0.47 | 1176.27 | 0.93 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.421495E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.357256E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.404760E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.432189E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.428600E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.516178E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.700369E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.728809E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.569192E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.627895E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.405365E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.430518E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.602263E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.357256E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.728809E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.211048E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.176221E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.199170E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.235175E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.234571E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.285258E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.380165E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.396529E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.310966E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.341842E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.215370E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.218948E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.320526E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.176221E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.396529E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189280E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158424E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.183071E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.195257E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.194367E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.239881E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.321012E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.342468E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.261367E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.289138E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182362E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193863E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.275049E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158424E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.342468E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.189008E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.158637E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.183008E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.194363E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.193697E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.238861E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.320077E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.341642E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.260333E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.288705E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.182186E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.193057E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.274357E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.158637E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.341642E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.186144E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.156974E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180589E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.190547E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.190049E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.233430E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.312964E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.334311E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.254461E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.282776E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.179650E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189466E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.269136E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.156974E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.334311E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.296035E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.249364E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.287183E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.305170E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.302881E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.378650E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.518352E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.555293E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.418160E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.464358E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.285851E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.300472E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.436177E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.249364E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.555293E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.158179E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133920E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153862E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.162054E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.161377E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.198953E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.269425E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.288437E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.218740E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.242852E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.152866E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.160228E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.230089E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133920E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.288437E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.156942E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.133121E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152793E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.160564E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.159988E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.196871E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.266806E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.285776E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.216547E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.240596E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.151714E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.158726E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.228044E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.133121E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.285776E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154920E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132026E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.151274E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.157952E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.157584E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.192639E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.261821E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.280758E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.212024E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.235922E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.149785E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.156068E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.224278E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132026E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.280758E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.168481E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.144597E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.165827E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172864E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.172146E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.208468E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.284450E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.304638E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.226399E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.250177E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.162899E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.168874E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.242982E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.144597E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.304638E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.386611E+10 | 0.127206E+10 | 7836199.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349791E+10 | 0.271838E+09 | 1926602.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388145E+10 | 0.611022E+09 | 0.118414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.374338E+10 | 0.214415E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386611E+10 | 0.154963E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375872E+10 | 0.531124E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386611E+10 | 0.121246E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387378E+10 | 0.132703E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375105E+10 | 0.724257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386611E+10 | 0.887512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373571E+10 | 0.116479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388145E+10 | 0.155004E+10 | 247254.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455879E+11 | 0.553874E+11 | 0.128425E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349791E+10 | 0.271838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.388145E+10 | 0.132703E+11 | 0.118414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.188749E+10 | 0.847463E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169848E+10 | 0.242634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187113E+10 | 0.460417E+09 | 2735899.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198687E+10 | 0.140665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206488E+10 | 0.107645E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.204444E+10 | 0.318088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.204048E+10 | 0.711542E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206871E+10 | 0.768767E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200493E+10 | 0.431085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202720E+10 | 0.539621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194634E+10 | 0.790882E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190553E+10 | 0.108142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235465E+11 | 0.335969E+11 | 2735899.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169848E+10 | 0.242634E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206871E+10 | 0.768767E+10 | 2735899.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.169751E+10 | 0.736356E+09 | 7021700.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153705E+10 | 0.177844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173129E+10 | 0.378516E+09 | 15891841.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164684E+10 | 0.116753E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171440E+10 | 0.873828E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167218E+10 | 0.283800E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168907E+10 | 0.605206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173129E+10 | 0.677911E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164684E+10 | 0.372250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169751E+10 | 0.452397E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164684E+10 | 0.669787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168907E+10 | 0.942843E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200999E+11 | 0.288623E+11 | 22913541.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153705E+10 | 0.177844E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173129E+10 | 0.677911E+10 | 15891841.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.170264E+10 | 0.705061E+09 | 17821796.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154170E+10 | 0.168126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173653E+10 | 0.355514E+09 | 24950619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165182E+10 | 0.111250E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171959E+10 | 0.827561E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167723E+10 | 0.277504E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169417E+10 | 0.598874E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173653E+10 | 0.671829E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165182E+10 | 0.365813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170264E+10 | 0.448394E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165182E+10 | 0.642902E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169417E+10 | 0.890728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201607E+11 | 0.283265E+11 | 42772416.40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154170E+10 | 0.168126E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173653E+10 | 0.671829E+10 | 24950619.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.168915E+10 | 0.645394E+09 | 33023984.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152948E+10 | 0.151064E+09 | 494841.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172276E+10 | 0.314746E+09 | 44925784.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163873E+10 | 0.101400E+10 | 478735.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170596E+10 | 0.738715E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166394E+10 | 0.260814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168075E+10 | 0.574703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172276E+10 | 0.646582E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163873E+10 | 0.347151E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168915E+10 | 0.429822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163873E+10 | 0.594438E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168075E+10 | 0.802815E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200009E+11 | 0.268519E+11 | 78923346.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152948E+10 | 0.151064E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172276E+10 | 0.646582E+10 | 44925784.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.268231E+10 | 0.100730E+10 | 0.110346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242927E+10 | 0.233513E+09 | 17752642.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274015E+10 | 0.482966E+09 | 0.156114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260278E+10 | 0.165476E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271123E+10 | 0.117018E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264616E+10 | 0.430292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.266785E+10 | 0.969977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274015E+10 | 0.109106E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260278E+10 | 0.587039E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268231E+10 | 0.718503E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260278E+10 | 0.932209E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266785E+10 | 0.122221E+10 | 1093109.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317757E+11 | 0.446719E+11 | 0.285306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.242927E+10 | 0.233513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274015E+10 | 0.109106E+11 | 0.156114E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.144399E+10 | 0.513820E+09 | 57244990.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130776E+10 | 0.117354E+09 | 10053810.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147513E+10 | 0.239601E+09 | 80916750.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140118E+10 | 0.832089E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145956E+10 | 0.584834E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142453E+10 | 0.219407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143621E+10 | 0.499218E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147513E+10 | 0.562642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140118E+10 | 0.300810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144399E+10 | 0.371326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140118E+10 | 0.478365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143621E+10 | 0.620130E+09 | 100550.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171060E+11 | 0.229202E+11 | 0.148316E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130776E+10 | 0.117354E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147513E+10 | 0.562642E+10 | 80916750.62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.143684E+10 | 0.493525E+09 | 64002065.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130129E+10 | 0.111526E+09 | 15887347.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146782E+10 | 0.226478E+09 | 97167906.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139424E+10 | 0.800959E+09 | 251168.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145233E+10 | 0.559155E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141747E+10 | 0.213882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142909E+10 | 0.491303E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146782E+10 | 0.554534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139424E+10 | 0.294751E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143684E+10 | 0.365148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139424E+10 | 0.460454E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142909E+10 | 0.589528E+09 | 607158.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170213E+11 | 0.224378E+11 | 0.177916E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130129E+10 | 0.111526E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146782E+10 | 0.554534E+10 | 97167906.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142910E+10 | 0.445354E+09 | 87227159.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129428E+10 | 96470806.28 | 43180055.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145992E+10 | 0.198317E+09 | 0.148947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138673E+10 | 0.728286E+09 | 935773.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144451E+10 | 0.496388E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140984E+10 | 0.199943E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142140E+10 | 0.473787E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145992E+10 | 0.536716E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138673E+10 | 0.279430E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142910E+10 | 0.349456E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138673E+10 | 0.414599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142140E+10 | 0.516847E+09 | 6075980.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169296E+11 | 0.212896E+11 | 0.286366E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129428E+10 | 96470806.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145992E+10 | 0.536716E+10 | 0.148947E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.157103E+10 | 0.419722E+09 | 0.151608E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142282E+10 | 85404090.83 | 0.161008E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160490E+10 | 0.199848E+09 | 0.328145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152445E+10 | 0.770908E+09 | 3268955.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158797E+10 | 0.503897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154985E+10 | 0.206600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156256E+10 | 0.507288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160490E+10 | 0.573899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152445E+10 | 0.280425E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157103E+10 | 0.347262E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152445E+10 | 0.387734E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156256E+10 | 0.465582E+09 | 43340964.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186110E+11 | 0.219878E+11 | 0.687371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142282E+10 | 85404090.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160490E+10 | 0.573899E+10 | 0.328145E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.386611E+10 | 0.00 | 0.00 | 0.00 | 0.348841E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.349791E+10 | 0.00 | 0.00 | 0.00 | 74652644.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.388145E+10 | 0.00 | 0.00 | 0.00 | 0.166147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.374338E+10 | 0.00 | 0.00 | 0.00 | 0.578514E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.386611E+10 | 0.00 | 0.00 | 0.00 | 0.419895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.375872E+10 | 0.00 | 0.00 | 0.00 | 0.140306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.386611E+10 | 0.00 | 0.00 | 0.00 | 0.313758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.387378E+10 | 0.00 | 0.00 | 0.00 | 0.341431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.375105E+10 | 0.00 | 0.00 | 0.00 | 0.194088E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.386611E+10 | 0.00 | 0.00 | 0.00 | 0.241284E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.373571E+10 | 0.00 | 0.00 | 0.00 | 0.317948E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.388145E+10 | 0.00 | 0.00 | 0.00 | 0.423728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.455879E+11 | 0.00 | 0.00 | 0.00 | 0.146384E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.349791E+10 | 0.00 | 0.00 | 0.00 | 74652644.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.388145E+10 | 0.00 | 0.00 | 0.00 | 0.341431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.188749E+10 | 0.00 | 0.00 | 0.00 | 0.222991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.169848E+10 | 0.00 | 0.00 | 0.00 | 63723013.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187113E+10 | 0.00 | 0.00 | 0.00 | 0.120564E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.198687E+10 | 0.00 | 0.00 | 0.00 | 0.364881E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206488E+10 | 0.00 | 0.00 | 0.00 | 0.280832E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.204444E+10 | 0.00 | 0.00 | 0.00 | 0.808146E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.204048E+10 | 0.00 | 0.00 | 0.00 | 0.176118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.206871E+10 | 0.00 | 0.00 | 0.00 | 0.189658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.200493E+10 | 0.00 | 0.00 | 0.00 | 0.110473E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.202720E+10 | 0.00 | 0.00 | 0.00 | 0.139123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.194634E+10 | 0.00 | 0.00 | 0.00 | 0.207355E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.190553E+10 | 0.00 | 0.00 | 0.00 | 0.283951E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.235465E+11 | 0.00 | 0.00 | 0.00 | 0.850616E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.169848E+10 | 0.00 | 0.00 | 0.00 | 63723013.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.206871E+10 | 0.00 | 0.00 | 0.00 | 0.189658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.169751E+10 | 0.00 | 0.00 | 0.00 | 0.195290E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.153705E+10 | 0.00 | 0.00 | 0.00 | 47186647.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173129E+10 | 0.00 | 0.00 | 0.00 | 99412150.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.164684E+10 | 0.00 | 0.00 | 0.00 | 0.305729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171440E+10 | 0.00 | 0.00 | 0.00 | 0.229265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167218E+10 | 0.00 | 0.00 | 0.00 | 0.726638E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168907E+10 | 0.00 | 0.00 | 0.00 | 0.152105E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173129E+10 | 0.00 | 0.00 | 0.00 | 0.169339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.164684E+10 | 0.00 | 0.00 | 0.00 | 0.966826E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.169751E+10 | 0.00 | 0.00 | 0.00 | 0.119386E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.164684E+10 | 0.00 | 0.00 | 0.00 | 0.176778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168907E+10 | 0.00 | 0.00 | 0.00 | 0.249562E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200999E+11 | 0.00 | 0.00 | 0.00 | 0.740499E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.153705E+10 | 0.00 | 0.00 | 0.00 | 47186647.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173129E+10 | 0.00 | 0.00 | 0.00 | 0.169339E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.170264E+10 | 0.00 | 0.00 | 0.00 | 0.187436E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.154170E+10 | 0.00 | 0.00 | 0.00 | 44668765.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173653E+10 | 0.00 | 0.00 | 0.00 | 93550196.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165182E+10 | 0.00 | 0.00 | 0.00 | 0.291807E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.171959E+10 | 0.00 | 0.00 | 0.00 | 0.217381E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.167723E+10 | 0.00 | 0.00 | 0.00 | 0.711384E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.169417E+10 | 0.00 | 0.00 | 0.00 | 0.150660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.173653E+10 | 0.00 | 0.00 | 0.00 | 0.167989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.165182E+10 | 0.00 | 0.00 | 0.00 | 0.951507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170264E+10 | 0.00 | 0.00 | 0.00 | 0.118440E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.165182E+10 | 0.00 | 0.00 | 0.00 | 0.170037E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.169417E+10 | 0.00 | 0.00 | 0.00 | 0.236395E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.201607E+11 | 0.00 | 0.00 | 0.00 | 0.727506E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.154170E+10 | 0.00 | 0.00 | 0.00 | 44668765.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.173653E+10 | 0.00 | 0.00 | 0.00 | 0.167989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.168915E+10 | 0.00 | 0.00 | 0.00 | 0.172291E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.152948E+10 | 0.00 | 0.00 | 0.00 | 40260327.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.172276E+10 | 0.00 | 0.00 | 0.00 | 83120914.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.163873E+10 | 0.00 | 0.00 | 0.00 | 0.266742E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.170596E+10 | 0.00 | 0.00 | 0.00 | 0.194537E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.166394E+10 | 0.00 | 0.00 | 0.00 | 0.670360E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.144889E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.172276E+10 | 0.00 | 0.00 | 0.00 | 0.162035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.163873E+10 | 0.00 | 0.00 | 0.00 | 0.905887E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.168915E+10 | 0.00 | 0.00 | 0.00 | 0.113861E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.163873E+10 | 0.00 | 0.00 | 0.00 | 0.157777E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.168075E+10 | 0.00 | 0.00 | 0.00 | 0.213914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.200009E+11 | 0.00 | 0.00 | 0.00 | 0.691274E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.152948E+10 | 0.00 | 0.00 | 0.00 | 40260327.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.172276E+10 | 0.00 | 0.00 | 0.00 | 0.162035E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.268231E+10 | 0.00 | 0.00 | 0.00 | 0.278035E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.242927E+10 | 0.00 | 0.00 | 0.00 | 64372015.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.274015E+10 | 0.00 | 0.00 | 0.00 | 0.131676E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.260278E+10 | 0.00 | 0.00 | 0.00 | 0.448919E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.271123E+10 | 0.00 | 0.00 | 0.00 | 0.317572E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.264616E+10 | 0.00 | 0.00 | 0.00 | 0.114034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.266785E+10 | 0.00 | 0.00 | 0.00 | 0.251567E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.274015E+10 | 0.00 | 0.00 | 0.00 | 0.281277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.260278E+10 | 0.00 | 0.00 | 0.00 | 0.157881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.268231E+10 | 0.00 | 0.00 | 0.00 | 0.196127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.260278E+10 | 0.00 | 0.00 | 0.00 | 0.255727E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.266785E+10 | 0.00 | 0.00 | 0.00 | 0.336861E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.317757E+11 | 0.00 | 0.00 | 0.00 | 0.118420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.242927E+10 | 0.00 | 0.00 | 0.00 | 64372015.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.274015E+10 | 0.00 | 0.00 | 0.00 | 0.281277E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.144399E+10 | 0.00 | 0.00 | 0.00 | 0.137805E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130776E+10 | 0.00 | 0.00 | 0.00 | 31435171.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.147513E+10 | 0.00 | 0.00 | 0.00 | 63490056.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.140118E+10 | 0.00 | 0.00 | 0.00 | 0.219365E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145956E+10 | 0.00 | 0.00 | 0.00 | 0.154215E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.142453E+10 | 0.00 | 0.00 | 0.00 | 0.565005E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.143621E+10 | 0.00 | 0.00 | 0.00 | 0.125804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.147513E+10 | 0.00 | 0.00 | 0.00 | 0.140924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.140118E+10 | 0.00 | 0.00 | 0.00 | 0.786221E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.144399E+10 | 0.00 | 0.00 | 0.00 | 0.984528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.140118E+10 | 0.00 | 0.00 | 0.00 | 0.127481E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.143621E+10 | 0.00 | 0.00 | 0.00 | 0.166078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.171060E+11 | 0.00 | 0.00 | 0.00 | 0.590291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130776E+10 | 0.00 | 0.00 | 0.00 | 31435171.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.147513E+10 | 0.00 | 0.00 | 0.00 | 0.140924E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.143684E+10 | 0.00 | 0.00 | 0.00 | 0.132579E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.130129E+10 | 0.00 | 0.00 | 0.00 | 29921715.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.146782E+10 | 0.00 | 0.00 | 0.00 | 60105498.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.139424E+10 | 0.00 | 0.00 | 0.00 | 0.211403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.145233E+10 | 0.00 | 0.00 | 0.00 | 0.147555E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.141747E+10 | 0.00 | 0.00 | 0.00 | 0.551234E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142909E+10 | 0.00 | 0.00 | 0.00 | 0.123897E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.146782E+10 | 0.00 | 0.00 | 0.00 | 0.138994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.139424E+10 | 0.00 | 0.00 | 0.00 | 0.771231E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.143684E+10 | 0.00 | 0.00 | 0.00 | 0.969127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.139424E+10 | 0.00 | 0.00 | 0.00 | 0.122904E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142909E+10 | 0.00 | 0.00 | 0.00 | 0.158167E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.170213E+11 | 0.00 | 0.00 | 0.00 | 0.578314E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.130129E+10 | 0.00 | 0.00 | 0.00 | 29921715.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.146782E+10 | 0.00 | 0.00 | 0.00 | 0.138994E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142910E+10 | 0.00 | 0.00 | 0.00 | 0.120103E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129428E+10 | 0.00 | 0.00 | 0.00 | 25984993.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145992E+10 | 0.00 | 0.00 | 0.00 | 52827389.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138673E+10 | 0.00 | 0.00 | 0.00 | 0.192791E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144451E+10 | 0.00 | 0.00 | 0.00 | 0.131332E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140984E+10 | 0.00 | 0.00 | 0.00 | 0.516548E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.142140E+10 | 0.00 | 0.00 | 0.00 | 0.119682E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145992E+10 | 0.00 | 0.00 | 0.00 | 0.134766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138673E+10 | 0.00 | 0.00 | 0.00 | 0.733513E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142910E+10 | 0.00 | 0.00 | 0.00 | 0.930119E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138673E+10 | 0.00 | 0.00 | 0.00 | 0.111127E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.142140E+10 | 0.00 | 0.00 | 0.00 | 0.139288E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169296E+11 | 0.00 | 0.00 | 0.00 | 0.549811E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129428E+10 | 0.00 | 0.00 | 0.00 | 25984993.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145992E+10 | 0.00 | 0.00 | 0.00 | 0.134766E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.157103E+10 | 0.00 | 0.00 | 0.00 | 0.113787E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.142282E+10 | 0.00 | 0.00 | 0.00 | 23148760.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.160490E+10 | 0.00 | 0.00 | 0.00 | 53361475.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.152445E+10 | 0.00 | 0.00 | 0.00 | 0.204189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.158797E+10 | 0.00 | 0.00 | 0.00 | 0.133496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.154985E+10 | 0.00 | 0.00 | 0.00 | 0.534829E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.156256E+10 | 0.00 | 0.00 | 0.00 | 0.128194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.160490E+10 | 0.00 | 0.00 | 0.00 | 0.144147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.152445E+10 | 0.00 | 0.00 | 0.00 | 0.739544E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157103E+10 | 0.00 | 0.00 | 0.00 | 0.930745E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.152445E+10 | 0.00 | 0.00 | 0.00 | 0.104543E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156256E+10 | 0.00 | 0.00 | 0.00 | 0.126179E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.186110E+11 | 0.00 | 0.00 | 0.00 | 0.568724E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.142282E+10 | 0.00 | 0.00 | 0.00 | 23148760.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.160490E+10 | 0.00 | 0.00 | 0.00 | 0.144147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.375210E+10 | 44761763.66 | 0.00 | 6940474.16 | 0.00 | 645421.86 | 0.637589E+10 | 0.00 | 0.79 |
February | 0.331948E+10 | 13395384.00 | 0.00 | 5630145.14 | 0.00 | 0.00 | 0.599593E+10 | 0.00 | 0.71 |
March | 0.500529E+10 | 67209.06 | 0.00 | 5072142.40 | 0.00 | 22411558.13 | 0.504823E+10 | 0.00 | 0.72 |
April | 0.857778E+09 | 53121604.71 | 0.00 | 12097573.81 | 0.00 | 0.00 | 0.957739E+10 | 0.00 | 1.08 |
May | 0.676825E+09 | 16137480.73 | 0.00 | 12992906.89 | 0.00 | 0.00 | 0.106918E+11 | 0.00 | 1.14 |
June | 0.111098E+09 | 0.185484E+09 | 0.00 | 16057110.22 | 0.00 | 0.00 | 0.934632E+10 | 0.00 | 1.40 |
July | 34145471.23 | 0.118587E+10 | 0.00 | 19130038.65 | 105854.65 | 0.00 | 0.686639E+10 | 0.00 | 1.44 |
August | 31465692.65 | 0.146423E+10 | 0.00 | 15984448.71 | 3190332.35 | 0.00 | 0.623542E+10 | 0.00 | 1.42 |
September | 66844092.98 | 0.425519E+09 | 0.00 | 18041926.76 | 580304.59 | 0.00 | 0.913606E+10 | 0.00 | 1.43 |
October | 0.170845E+09 | 0.990091E+09 | 0.00 | 18120134.53 | 3589022.72 | 0.00 | 0.842944E+10 | 0.00 | 1.32 |
November | 0.102610E+10 | 41836690.76 | 0.00 | 10356098.66 | 0.00 | 0.00 | 0.970681E+10 | 0.00 | 0.90 |
December | 0.340656E+10 | 22147233.95 | 0.00 | 7728619.14 | 0.00 | 0.00 | 0.675497E+10 | 0.00 | 0.86 |
Annual Sum or Average | 0.184585E+11 | 0.444266E+10 | 0.00 | 0.148152E+09 | 7465514.31 | 23056979.99 | 0.941646E+11 | 0.00 | 1.10 |
Minimum of Months | 31465692.65 | 67209.06 | 0.00 | 5072142.40 | 0.00 | 0.00 | 0.504823E+10 | 0.00 | 0.71 |
Maximum of Months | 0.500529E+10 | 0.146423E+10 | 0.00 | 19130038.65 | 3589022.72 | 22411558.13 | 0.106918E+11 | 0.00 | 1.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.553595E+09 | 23836252.16 | 0.00 | 5903888.17 | 0.00 | 0.00 | 0.487927E+10 | 0.00 | 0.88 |
February | 0.625979E+09 | 6819519.51 | 0.00 | 4926562.72 | 0.00 | 0.00 | 0.446158E+10 | 0.00 | 0.80 |
March | 0.101130E+10 | 285223.38 | 0.00 | 4786401.31 | 0.00 | 273773.74 | 0.424176E+10 | 0.00 | 0.77 |
April | 0.139081E+09 | 29956280.02 | 0.00 | 7665616.84 | 0.00 | 0.00 | 0.569081E+10 | 0.00 | 1.21 |
May | 72843626.30 | 8825209.06 | 0.00 | 8315363.30 | 0.00 | 0.00 | 0.628981E+10 | 0.00 | 1.28 |
June | 26936314.33 | 0.116130E+09 | 0.00 | 9234897.22 | 0.00 | 0.00 | 0.516892E+10 | 0.00 | 1.54 |
July | 12421580.81 | 0.655174E+09 | 0.00 | 9512995.94 | 94200.73 | 0.00 | 0.330040E+10 | 0.00 | 1.48 |
August | 12185308.88 | 0.833710E+09 | 0.00 | 8001356.60 | 2175091.85 | 0.00 | 0.309320E+10 | 0.00 | 1.48 |
September | 25740158.08 | 0.254697E+09 | 0.00 | 9762037.89 | 940919.32 | 0.00 | 0.485651E+10 | 0.00 | 1.52 |
October | 37533103.97 | 0.541759E+09 | 0.00 | 8716947.60 | 1700686.50 | 0.00 | 0.439545E+10 | 0.00 | 1.36 |
November | 88147625.65 | 21784648.66 | 0.00 | 7290001.58 | 0.00 | 0.00 | 0.603402E+10 | 0.00 | 1.04 |
December | 0.424473E+09 | 10907807.14 | 0.00 | 6526797.05 | 0.00 | 0.00 | 0.503183E+10 | 0.00 | 0.95 |
Annual Sum or Average | 0.303024E+10 | 0.250389E+10 | 0.00 | 90642866.22 | 4910898.40 | 273773.74 | 0.574436E+11 | 0.00 | 1.19 |
Minimum of Months | 12185308.88 | 285223.38 | 0.00 | 4786401.31 | 0.00 | 0.00 | 0.309320E+10 | 0.00 | 0.77 |
Maximum of Months | 0.101130E+10 | 0.833710E+09 | 0.00 | 9762037.89 | 2175091.85 | 273773.74 | 0.628981E+10 | 0.00 | 1.54 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.114860E+10 | 22890406.13 | 0.00 | 3350188.33 | 0.00 | 1088696.47 | 0.274187E+10 | 0.00 | 0.72 |
February | 0.108601E+10 | 7723137.09 | 0.00 | 2718517.32 | 0.00 | 0.00 | 0.262634E+10 | 0.00 | 0.65 |
March | 0.165048E+10 | 306790.03 | 0.00 | 2566760.57 | 0.00 | 2473617.44 | 0.229003E+10 | 0.00 | 0.65 |
April | 0.562982E+09 | 31899311.96 | 0.00 | 4699013.11 | 0.00 | 0.00 | 0.338035E+10 | 0.00 | 0.97 |
May | 0.450614E+09 | 9117596.42 | 0.00 | 5329128.26 | 0.00 | 0.00 | 0.392225E+10 | 0.00 | 1.04 |
June | 0.259592E+09 | 0.113113E+09 | 0.00 | 6124075.33 | 0.00 | 0.00 | 0.297076E+10 | 0.00 | 1.24 |
July | 0.177558E+09 | 0.627550E+09 | 0.00 | 5786834.87 | 1232170.11 | 0.00 | 0.147349E+10 | 0.00 | 1.14 |
August | 0.188941E+09 | 0.783208E+09 | 0.00 | 4888142.18 | 3066211.92 | 0.00 | 0.130560E+10 | 0.00 | 1.15 |
September | 0.237261E+09 | 0.227047E+09 | 0.00 | 6626985.59 | 562718.03 | 0.00 | 0.275672E+10 | 0.00 | 1.19 |
October | 0.282710E+09 | 0.525012E+09 | 0.00 | 5502492.89 | 2807770.00 | 0.00 | 0.245635E+10 | 0.00 | 1.07 |
November | 0.564979E+09 | 17938662.81 | 0.00 | 4498488.35 | 0.00 | 0.00 | 0.368653E+10 | 0.00 | 0.83 |
December | 0.102840E+10 | 12092196.86 | 0.00 | 3833728.35 | 0.00 | 0.00 | 0.279726E+10 | 0.00 | 0.79 |
Annual Sum or Average | 0.763813E+10 | 0.237790E+10 | 0.00 | 55924355.16 | 7668870.06 | 3562313.91 | 0.324076E+11 | 0.00 | 0.96 |
Minimum of Months | 0.177558E+09 | 306790.03 | 0.00 | 2566760.57 | 0.00 | 0.00 | 0.130560E+10 | 0.00 | 0.65 |
Maximum of Months | 0.165048E+10 | 0.783208E+09 | 0.00 | 6626985.59 | 3066211.92 | 2473617.44 | 0.392225E+10 | 0.00 | 1.24 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.121545E+10 | 22756772.45 | 0.00 | 3071439.61 | 0.00 | 11306231.52 | 0.254852E+10 | 0.00 | 0.70 |
February | 0.113879E+10 | 7672478.94 | 0.00 | 2478907.38 | 0.00 | 0.00 | 0.246677E+10 | 0.00 | 0.64 |
March | 0.175043E+10 | 236601.79 | 0.00 | 2284656.72 | 0.00 | 10941527.96 | 0.207954E+10 | 0.00 | 0.64 |
April | 0.588197E+09 | 31438789.96 | 0.00 | 4478201.61 | 0.00 | 0.00 | 0.328921E+10 | 0.00 | 0.96 |
May | 0.472320E+09 | 9052769.69 | 0.00 | 5117288.53 | 0.00 | 0.00 | 0.384342E+10 | 0.00 | 1.03 |
June | 0.265865E+09 | 0.110783E+09 | 0.00 | 5970230.10 | 0.00 | 0.00 | 0.294939E+10 | 0.00 | 1.23 |
July | 0.178950E+09 | 0.624803E+09 | 0.00 | 5709067.12 | 1306565.09 | 0.00 | 0.147996E+10 | 0.00 | 1.14 |
August | 0.188878E+09 | 0.778249E+09 | 0.00 | 4844667.88 | 3097863.60 | 0.00 | 0.131130E+10 | 0.00 | 1.15 |
September | 0.240867E+09 | 0.224678E+09 | 0.00 | 6506076.61 | 569503.07 | 0.00 | 0.275194E+10 | 0.00 | 1.19 |
October | 0.289366E+09 | 0.525151E+09 | 0.00 | 5424462.37 | 2801876.35 | 0.00 | 0.244399E+10 | 0.00 | 1.07 |
November | 0.589491E+09 | 17876731.60 | 0.00 | 4271486.24 | 0.00 | 0.00 | 0.357275E+10 | 0.00 | 0.82 |
December | 0.109229E+10 | 12038770.03 | 0.00 | 3568983.62 | 0.00 | 0.00 | 0.265406E+10 | 0.00 | 0.78 |
Annual Sum or Average | 0.801089E+10 | 0.236474E+10 | 0.00 | 53725467.80 | 7775808.11 | 22247759.47 | 0.313909E+11 | 0.00 | 0.95 |
Minimum of Months | 0.178950E+09 | 236601.79 | 0.00 | 2284656.72 | 0.00 | 0.00 | 0.131130E+10 | 0.00 | 0.64 |
Maximum of Months | 0.175043E+10 | 0.778249E+09 | 0.00 | 6506076.61 | 3097863.60 | 11306231.52 | 0.384342E+10 | 0.00 | 1.23 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.131738E+10 | 22323275.36 | 0.00 | 2591869.92 | 0.00 | 28084139.40 | 0.222902E+10 | 0.00 | 0.67 |
February | 0.129007E+10 | 7522208.96 | 0.00 | 2036222.36 | 0.00 | 0.00 | 0.210876E+10 | 0.00 | 0.60 |
March | 0.194987E+10 | 125623.94 | 0.00 | 1832138.76 | 0.00 | 12032648.84 | 0.168738E+10 | 0.00 | 0.61 |
April | 0.643246E+09 | 30286413.68 | 0.00 | 4016170.08 | 0.00 | 0.00 | 0.306605E+10 | 0.00 | 0.93 |
May | 0.522045E+09 | 8881193.51 | 0.00 | 4621026.03 | 0.00 | 0.00 | 0.362036E+10 | 0.00 | 0.99 |
June | 0.274734E+09 | 0.102829E+09 | 0.00 | 5546941.74 | 0.00 | 0.00 | 0.285856E+10 | 0.00 | 1.21 |
July | 0.180634E+09 | 0.600156E+09 | 0.00 | 5353281.48 | 1324525.11 | 0.00 | 0.147038E+10 | 0.00 | 1.13 |
August | 0.189575E+09 | 0.743957E+09 | 0.00 | 4565642.12 | 3009332.57 | 0.00 | 0.129992E+10 | 0.00 | 1.14 |
September | 0.246679E+09 | 0.217625E+09 | 0.00 | 6100808.41 | 567263.43 | 0.00 | 0.269341E+10 | 0.00 | 1.17 |
October | 0.301675E+09 | 0.516485E+09 | 0.00 | 5075270.98 | 2683297.78 | 0.00 | 0.237924E+10 | 0.00 | 1.06 |
November | 0.642400E+09 | 17868757.64 | 0.00 | 3805744.86 | 0.00 | 0.00 | 0.331324E+10 | 0.00 | 0.78 |
December | 0.121899E+10 | 11854842.63 | 0.00 | 3082595.78 | 0.00 | 0.00 | 0.235852E+10 | 0.00 | 0.75 |
Annual Sum or Average | 0.877730E+10 | 0.227991E+10 | 0.00 | 48627712.50 | 7584418.88 | 40116788.24 | 0.290848E+11 | 0.00 | 0.92 |
Minimum of Months | 0.180634E+09 | 125623.94 | 0.00 | 1832138.76 | 0.00 | 0.00 | 0.129992E+10 | 0.00 | 0.60 |
Maximum of Months | 0.194987E+10 | 0.743957E+09 | 0.00 | 6100808.41 | 3009332.57 | 28084139.40 | 0.362036E+10 | 0.00 | 1.21 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.280413E+10 | 22317127.22 | 0.00 | 3512760.45 | 0.00 | 57195239.11 | 0.328520E+10 | 0.00 | 0.55 |
February | 0.312094E+10 | 8018966.94 | 0.00 | 2423286.08 | 0.00 | 0.00 | 0.273900E+10 | 0.00 | 0.50 |
March | 0.419053E+10 | 792143.47 | 0.00 | 2248913.89 | 0.00 | 34716775.23 | 0.222749E+10 | 0.00 | 0.51 |
April | 0.106790E+10 | 41515361.05 | 0.00 | 6189695.97 | 0.00 | 0.00 | 0.523140E+10 | 0.00 | 0.75 |
May | 0.813506E+09 | 8837879.68 | 0.00 | 7028807.46 | 0.00 | 0.00 | 0.623647E+10 | 0.00 | 0.80 |
June | 0.214156E+09 | 0.105735E+09 | 0.00 | 9341736.69 | 0.00 | 0.00 | 0.518182E+10 | 0.00 | 0.99 |
July | 0.111096E+09 | 0.854264E+09 | 0.00 | 8909731.46 | 2214190.13 | 0.00 | 0.273037E+10 | 0.00 | 0.94 |
August | 77759342.62 | 0.104498E+10 | 0.00 | 7945821.20 | 10436211.00 | 0.00 | 0.248902E+10 | 0.00 | 0.95 |
September | 0.203398E+09 | 0.311630E+09 | 0.00 | 10062729.55 | 1523511.93 | 0.00 | 0.486707E+10 | 0.00 | 0.97 |
October | 0.204292E+09 | 0.795550E+09 | 0.00 | 8282871.32 | 6005976.98 | 0.00 | 0.442938E+10 | 0.00 | 0.88 |
November | 0.124992E+10 | 19536793.92 | 0.00 | 5508531.80 | 0.00 | 0.00 | 0.539700E+10 | 0.00 | 0.62 |
December | 0.262339E+10 | 12174760.44 | 0.00 | 4237460.64 | 0.00 | 0.00 | 0.356186E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.166810E+11 | 0.322535E+10 | 0.00 | 75692346.50 | 20179890.03 | 91912014.34 | 0.483761E+11 | 0.00 | 0.76 |
Minimum of Months | 77759342.62 | 792143.47 | 0.00 | 2248913.89 | 0.00 | 0.00 | 0.222749E+10 | 0.00 | 0.50 |
Maximum of Months | 0.419053E+10 | 0.104498E+10 | 0.00 | 10062729.55 | 10436211.00 | 57195239.11 | 0.623647E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.139922E+10 | 11390593.23 | 0.00 | 1691055.54 | 0.00 | 37760915.75 | 0.163906E+10 | 0.00 | 0.55 |
February | 0.156752E+10 | 4165302.93 | 0.00 | 1142709.07 | 0.00 | 937711.23 | 0.134905E+10 | 0.00 | 0.50 |
March | 0.212769E+10 | 403443.58 | 0.00 | 1056538.11 | 216607.15 | 31527047.69 | 0.104719E+10 | 0.00 | 0.52 |
April | 0.523717E+09 | 21087359.24 | 0.00 | 3053692.67 | 450435.83 | 0.00 | 0.266018E+10 | 0.00 | 0.77 |
May | 0.393576E+09 | 4538313.91 | 0.00 | 3481228.12 | 0.00 | 0.00 | 0.318580E+10 | 0.00 | 0.82 |
June | 0.107446E+09 | 54076366.78 | 0.00 | 4667770.19 | 0.00 | 0.00 | 0.266505E+10 | 0.00 | 1.03 |
July | 55198284.13 | 0.432624E+09 | 0.00 | 4440191.03 | 1223825.24 | 0.00 | 0.141955E+10 | 0.00 | 0.98 |
August | 39160405.72 | 0.528682E+09 | 0.00 | 3977812.69 | 5634258.66 | 0.00 | 0.129283E+10 | 0.00 | 0.99 |
September | 0.104593E+09 | 0.157591E+09 | 0.00 | 5061058.81 | 692384.85 | 0.00 | 0.251256E+10 | 0.00 | 1.01 |
October | 0.102032E+09 | 0.403736E+09 | 0.00 | 4179529.04 | 2878672.21 | 0.00 | 0.228456E+10 | 0.00 | 0.91 |
November | 0.604711E+09 | 10144971.04 | 0.00 | 2738821.60 | 0.00 | 0.00 | 0.275177E+10 | 0.00 | 0.63 |
December | 0.133291E+10 | 6236194.34 | 0.00 | 2079340.29 | 0.00 | 0.00 | 0.177778E+10 | 0.00 | 0.63 |
Annual Sum or Average | 0.835777E+10 | 0.163467E+10 | 0.00 | 37569747.17 | 11096183.95 | 70225674.66 | 0.245854E+11 | 0.00 | 0.78 |
Minimum of Months | 39160405.72 | 403443.58 | 0.00 | 1056538.11 | 0.00 | 0.00 | 0.104719E+10 | 0.00 | 0.50 |
Maximum of Months | 0.212769E+10 | 0.528682E+09 | 0.00 | 5061058.81 | 5634258.66 | 37760915.75 | 0.318580E+10 | 0.00 | 1.03 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.148185E+10 | 11152929.34 | 0.00 | 1545972.42 | 0.00 | 40566718.51 | 0.149976E+10 | 0.00 | 0.54 |
February | 0.164730E+10 | 4021067.64 | 0.00 | 1018699.78 | 0.00 | 1859375.01 | 0.120373E+10 | 0.00 | 0.49 |
March | 0.218130E+10 | 615473.24 | 0.00 | 957746.79 | 269336.62 | 33113097.55 | 0.940115E+09 | 0.00 | 0.51 |
April | 0.557466E+09 | 21235372.36 | 0.00 | 2902419.27 | 317767.36 | 999395.03 | 0.256826E+10 | 0.00 | 0.75 |
May | 0.431672E+09 | 4469945.01 | 0.00 | 3318174.46 | 0.00 | 0.00 | 0.308444E+10 | 0.00 | 0.81 |
June | 0.111446E+09 | 52205720.86 | 0.00 | 4527127.91 | 0.00 | 0.00 | 0.263034E+10 | 0.00 | 1.02 |
July | 55249744.14 | 0.425735E+09 | 0.00 | 4335681.05 | 1219189.35 | 0.00 | 0.141540E+10 | 0.00 | 0.97 |
August | 39435741.19 | 0.519265E+09 | 0.00 | 3881742.22 | 5411218.82 | 0.00 | 0.128626E+10 | 0.00 | 0.98 |
September | 0.109805E+09 | 0.156015E+09 | 0.00 | 4928040.86 | 642871.68 | 0.00 | 0.248764E+10 | 0.00 | 1.00 |
October | 0.103745E+09 | 0.401097E+09 | 0.00 | 4069827.23 | 2890184.25 | 0.00 | 0.226323E+10 | 0.00 | 0.91 |
November | 0.688735E+09 | 10099432.68 | 0.00 | 2542292.23 | 0.00 | 0.00 | 0.259915E+10 | 0.00 | 0.62 |
December | 0.138243E+10 | 6198818.38 | 0.00 | 1927026.22 | 0.00 | 0.00 | 0.167306E+10 | 0.00 | 0.62 |
Annual Sum or Average | 0.879042E+10 | 0.161211E+10 | 0.00 | 35954750.43 | 10750568.08 | 76538586.11 | 0.236514E+11 | 0.00 | 0.77 |
Minimum of Months | 39435741.19 | 615473.24 | 0.00 | 957746.79 | 0.00 | 0.00 | 0.940115E+09 | 0.00 | 0.49 |
Maximum of Months | 0.218130E+10 | 0.519265E+09 | 0.00 | 4928040.86 | 5411218.82 | 40566718.51 | 0.308444E+10 | 0.00 | 1.02 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.162504E+10 | 10450256.01 | 0.00 | 1228464.52 | 0.00 | 59592299.78 | 0.120884E+10 | 0.00 | 0.52 |
February | 0.175774E+10 | 3934125.85 | 0.00 | 747881.19 | 0.00 | 15802815.08 | 0.935111E+09 | 0.00 | 0.47 |
March | 0.222266E+10 | 1113554.16 | 0.00 | 777252.68 | 603952.38 | 69654071.36 | 0.752150E+09 | 0.00 | 0.49 |
April | 0.646422E+09 | 17836198.80 | 0.00 | 2518647.11 | 3538935.35 | 1646983.72 | 0.233858E+10 | 0.00 | 0.72 |
May | 0.541810E+09 | 4272271.19 | 0.00 | 2876803.39 | 0.00 | 0.00 | 0.280977E+10 | 0.00 | 0.77 |
June | 0.146574E+09 | 47476768.65 | 0.00 | 4105225.96 | 0.00 | 0.00 | 0.251507E+10 | 0.00 | 0.99 |
July | 56718837.56 | 0.410624E+09 | 0.00 | 4049352.63 | 1090781.51 | 0.00 | 0.141054E+10 | 0.00 | 0.96 |
August | 41702065.47 | 0.496439E+09 | 0.00 | 3634385.43 | 5657332.73 | 0.00 | 0.127254E+10 | 0.00 | 0.97 |
September | 0.134070E+09 | 0.151897E+09 | 0.00 | 4548161.40 | 628286.09 | 0.00 | 0.241821E+10 | 0.00 | 0.98 |
October | 0.125993E+09 | 0.394634E+09 | 0.00 | 3744687.70 | 2899227.18 | 0.00 | 0.219274E+10 | 0.00 | 0.89 |
November | 0.917967E+09 | 10009160.05 | 0.00 | 2034571.88 | 0.00 | 0.00 | 0.219129E+10 | 0.00 | 0.59 |
December | 0.150127E+10 | 5985384.77 | 0.00 | 1554058.59 | 0.00 | 0.00 | 0.141672E+10 | 0.00 | 0.59 |
Annual Sum or Average | 0.971796E+10 | 0.155467E+10 | 0.00 | 31819492.49 | 14418515.24 | 0.146696E+09 | 0.214616E+11 | 0.00 | 0.75 |
Minimum of Months | 41702065.47 | 1113554.16 | 0.00 | 747881.19 | 0.00 | 0.00 | 0.752150E+09 | 0.00 | 0.47 |
Maximum of Months | 0.222266E+10 | 0.496439E+09 | 0.00 | 4548161.40 | 5657332.73 | 69654071.36 | 0.280977E+10 | 0.00 | 0.99 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163395E+10 | 11079187.97 | 0.00 | 929174.57 | 879129.97 | 0.137028E+09 | 0.930319E+09 | 0.00 | 0.52 |
February | 0.174227E+10 | 3583057.70 | 0.00 | 473751.73 | 0.00 | 0.145461E+09 | 0.615165E+09 | 0.00 | 0.46 |
March | 0.204637E+10 | 1654958.69 | 0.00 | 677263.52 | 2334353.77 | 0.240982E+09 | 0.633668E+09 | 0.00 | 0.50 |
April | 0.779673E+09 | 22355777.40 | 0.00 | 2260045.20 | 1401830.77 | 1269963.82 | 0.212591E+10 | 0.00 | 0.74 |
May | 0.696784E+09 | 5023070.11 | 0.00 | 2509433.93 | 0.00 | 0.00 | 0.253121E+10 | 0.00 | 0.78 |
June | 0.221246E+09 | 55586770.55 | 0.00 | 3747726.45 | 0.00 | 0.00 | 0.238775E+10 | 0.00 | 1.03 |
July | 63354125.65 | 0.451237E+09 | 0.00 | 3863494.47 | 1503492.44 | 0.00 | 0.146133E+10 | 0.00 | 1.03 |
August | 47536570.75 | 0.551538E+09 | 0.00 | 3326491.14 | 5577845.09 | 0.00 | 0.130465E+10 | 0.00 | 1.03 |
September | 0.195147E+09 | 0.159824E+09 | 0.00 | 4124678.78 | 810399.25 | 0.00 | 0.237846E+10 | 0.00 | 1.02 |
October | 0.155839E+09 | 0.405578E+09 | 0.00 | 3232787.17 | 4048758.04 | 0.00 | 0.212993E+10 | 0.00 | 0.92 |
November | 0.121792E+10 | 13138724.57 | 0.00 | 1464234.72 | 302919.94 | 0.00 | 0.164063E+10 | 0.00 | 0.57 |
December | 0.161907E+10 | 8056348.81 | 0.00 | 1142911.15 | 10659.77 | 10182669.14 | 0.106918E+10 | 0.00 | 0.58 |
Annual Sum or Average | 0.104192E+11 | 0.168866E+10 | 0.00 | 27751992.84 | 16869389.03 | 0.534924E+09 | 0.192082E+11 | 0.00 | 0.77 |
Minimum of Months | 47536570.75 | 1654958.69 | 0.00 | 473751.73 | 0.00 | 0.00 | 0.615165E+09 | 0.00 | 0.46 |
Maximum of Months | 0.204637E+10 | 0.551538E+09 | 0.00 | 4124678.78 | 5577845.09 | 0.240982E+09 | 0.253121E+10 | 0.00 | 1.03 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:51
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.164262E+12 | 0.145994E+11 | 0.00 | 0.445291E+11 | 0.912924E+10 |
February | 0.201911E+12 | 0.154577E+11 | 0.00 | 0.419428E+11 | 0.216371E+10 |
March | 0.284920E+12 | 0.166248E+11 | 0.00 | 0.456776E+11 | 0.464623E+10 |
April | 0.382917E+12 | 0.101911E+11 | 0.00 | 0.460431E+11 | 0.147174E+11 |
May | 0.401948E+12 | 0.110165E+11 | 0.00 | 0.512652E+11 | 0.106067E+11 |
June | 0.403511E+12 | 0.588019E+10 | 0.00 | 0.395430E+11 | 0.370421E+11 |
July | 0.433743E+12 | 0.299040E+09 | 0.00 | 0.177600E+11 | 0.833103E+11 |
August | 0.397359E+12 | -226329256.8 | 0.00 | 0.140225E+11 | 0.928153E+11 |
September | 0.311787E+12 | 0.425032E+10 | 0.00 | 0.362063E+11 | 0.503093E+11 |
October | 0.211453E+12 | 0.447002E+10 | 0.00 | 0.297410E+11 | 0.621911E+11 |
November | 0.179937E+12 | 0.138057E+11 | 0.00 | 0.483475E+11 | 0.828783E+10 |
December | 0.144521E+12 | 0.146758E+11 | 0.00 | 0.446801E+11 | 0.110291E+11 |
Annual Sum or Average | 0.351827E+13 | 0.111044E+12 | 0.00 | 0.459758E+12 | 0.386248E+12 |
Minimum of Months | 0.144521E+12 | -226329256.8 | 0.00 | 0.140225E+11 | 0.216371E+10 |