Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470
Simulation Timestamp: 2023-10-16 08:40:29
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 2128.36 | 1018.20 | 1018.20 |
Net Site Energy | 2128.36 | 1018.20 | 1018.20 |
Total Source Energy | 4568.96 | 2185.77 | 2185.77 |
Net Source Energy | 4568.96 | 2185.77 | 2185.77 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 1042.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 240.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 67.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1085.85 | 1042.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 1042.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 240.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 67.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 1042.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 66.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 240.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 67.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 178.80 | 498.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 519.46 | 498.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 178.80 | 498.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 519.46 | 498.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1085.845 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1085.845 | 100.00 |
Total On-Site and Utility Electric Sources | 1085.845 | 100.00 |
Total Electricity End Uses | 1085.845 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.67 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 3252.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Latitude [deg] | 48.57 |
Longitude [deg] | -93.4 |
Elevation [m] | 359.00 |
Time Zone | -6.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUL-14:09 | 06-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 366484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 49239.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 8993.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 108969.61 | 366484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 366484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 49239.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 8993.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 1130.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 209.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 383.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 760.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 213.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3438.87 | 1130.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 540.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 100.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 363.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 102.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1645.14 | 540.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 540.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 100.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 363.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 102.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1645.14 | 540.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.06 |
SMSTORE1 DIRECT AIR | 1.08 |
SMSTORE2 DIRECT AIR | 1.09 |
SMSTORE3 DIRECT AIR | 1.08 |
SMSTORE4 DIRECT AIR | 1.08 |
LGSTORE2 DIRECT AIR | 1.96 |
SMSTORE5 DIRECT AIR | 1.01 |
SMSTORE6 DIRECT AIR | 1.01 |
SMSTORE7 DIRECT AIR | 1.01 |
SMSTORE8 DIRECT AIR | 1.24 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.06 | 2.06 | 2.06 | 2.06 | 2.06 | 2.06 | 1.00 | 1.00 | 2.06 |
PSZ-AC_2:2 | 1.08 | 1.08 | 1.08 | 1.08 | 1.10 | 1.10 | 1.00 | 0.976415 | 1.10 |
PSZ-AC_3:3 | 1.09 | 1.09 | 1.09 | 1.09 | 1.11 | 1.11 | 1.00 | 0.982301 | 1.11 |
PSZ-AC_4:4 | 1.08 | 1.08 | 1.08 | 1.08 | 1.11 | 1.11 | 1.00 | 0.973259 | 1.11 |
PSZ-AC_5:5 | 1.08 | 1.08 | 1.08 | 1.08 | 1.10 | 1.10 | 1.00 | 0.981628 | 1.10 |
PSZ-AC_6:6 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.96 | 1.00 | 1.000000 | 1.96 |
PSZ-AC_7:7 | 1.01 | 1.01 | 1.01 | 1.01 | 1.02 | 1.02 | 1.00 | 0.996585 | 1.02 |
PSZ-AC_8:8 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 0.996293 | 1.01 |
PSZ-AC_9:9 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.01 | 1.00 | 1.00 | 1.01 |
PSZ-AC_10:10 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.06 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.11 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.11 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.10 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.96 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.01 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.24 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.06 | 2199.29 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1221.80 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1223.72 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.11 | 1227.58 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.10 | 1218.51 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.96 | 2100.35 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1124.36 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1118.07 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.01 | 1122.49 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1372.63 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.06 | 2.06 | 2.06 | 2.06 | 41614.50 | 70702.30 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 22022.39 | 36443.54 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 22049.58 | 36623.13 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.11 | 1.11 | 1.11 | 1.11 | 22104.26 | 36478.63 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.10 | 1.10 | 1.10 | 1.10 | 21975.89 | 36505.59 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.96 | 1.96 | 1.96 | 1.96 | 40033.95 | 68675.84 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 20638.61 | 35009.47 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 20551.12 | 34878.92 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.01 | 1.01 | 1.01 | 1.01 | 20652.33 | 35048.53 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 24875.15 | 39999.27 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.06 | 1.03 | 2.06 | 41614.50 | 20485.97 | 41614.50 | 0.771580 | 0.771580 |
PSZ-AC_2:2 COOLING COIL | 1.10 | 0.551773 | 1.10 | 22022.39 | 10856.00 | 22022.39 | 0.776970 | 0.776970 |
PSZ-AC_3:3 COOLING COIL | 1.11 | 0.552639 | 1.11 | 22049.58 | 10869.34 | 22049.58 | 0.777070 | 0.777070 |
PSZ-AC_4:4 COOLING COIL | 1.11 | 0.554385 | 1.11 | 22104.26 | 10896.17 | 22104.26 | 0.777280 | 0.777280 |
PSZ-AC_5:5 COOLING COIL | 1.10 | 0.550286 | 1.10 | 21975.89 | 10833.20 | 21975.89 | 0.776790 | 0.776790 |
PSZ-AC_6:6 COOLING COIL | 1.96 | 0.981428 | 1.96 | 40033.95 | 19710.73 | 40033.95 | 0.768400 | 0.768400 |
PSZ-AC_7:7 COOLING COIL | 1.02 | 0.507767 | 1.02 | 20638.61 | 10177.16 | 20638.61 | 0.769460 | 0.769460 |
PSZ-AC_8:8 COOLING COIL | 1.01 | 0.504926 | 1.01 | 20551.12 | 10134.26 | 20551.12 | 0.769060 | 0.769060 |
PSZ-AC_9:9 COOLING COIL | 1.01 | 0.506924 | 1.01 | 20652.33 | 10184.34 | 20652.33 | 0.768770 | 0.768770 |
PSZ-AC_10:10 COOLING COIL | 1.24 | 0.619888 | 1.24 | 24875.15 | 12263.73 | 24875.15 | 0.775330 | 0.775330 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 70702.30 |
PSZ-AC_2:2 HEATING COIL | 36443.54 |
PSZ-AC_3:3 HEATING COIL | 36623.13 |
PSZ-AC_4:4 HEATING COIL | 36478.63 |
PSZ-AC_5:5 HEATING COIL | 36505.59 |
PSZ-AC_6:6 HEATING COIL | 68675.84 |
PSZ-AC_7:7 HEATING COIL | 35009.47 |
PSZ-AC_8:8 HEATING COIL | 34878.92 |
PSZ-AC_9:9 HEATING COIL | 35048.53 |
PSZ-AC_10:10 HEATING COIL | 39999.27 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 5.40 | -2.00 | -14.60 | -16.90 | -11.50 | -6.20 | 4.00 | 13.40 | 18.00 | 19.70 | 17.90 | 12.30 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | International Falls Intl Ap MN USA TMY3 WMO#=727470 | 48.57 | -93.40 | -6.00 | 359.00 | 97086 | 1.1539 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 3.29 | 36.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.1625 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1078 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.6115E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.1551 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 6.093 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 9.201 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 16.28 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.371 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.63083111E-06 | 0.74112372E-09 | -0.38647046E-05 | 0.15329585E-16 |
19 | 2 | 0.78415922 | 0.99752939E-03 | 1.0633801 | -0.74093433E-06 |
20 | 1 | -22.010056 | 0.66447931E-01 | -6.3131541 | 0.20386814 |
21 | 0 | 21.355302 | 0.61958938E-01 | 5.3791822 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.39532248E-08 | -0.44064807E-14 | 0.10109291E-14 | -0.41601153E-16 |
31 | 6 | 0.32173895E-05 | 0.20629171E-08 | 0.31970178E-02 | -0.26819265E-04 |
32 | 5 | -0.22044530E-03 | 0.12181552E-05 | -0.22413079 | 0.19597358E-02 |
33 | 4 | 0.49988388E-02 | 0.55368910E-04 | 4.8363104 | -0.45330008E-01 |
34 | 3 | -0.43669331E-01 | 0.43971237E-03 | -38.059625 | 0.39907609 |
35 | 2 | 0.15474085 | 0.73065327E-03 | 116.55831 | -1.4189339 |
36 | 1 | -0.22313860 | 0.22222429E-03 | -143.95108 | 2.0497593 |
37 | 0 | 0.10874004 | 0.53957455E-05 | 60.838472 | |
38 | 7 | -0.70007713E-08 | -0.80410658E-14 | -0.90308164E-15 | 0.82137675E-17 |
39 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
40 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
41 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
42 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
43 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
44 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
45 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
46 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308145E-15 | 0.82137644E-17 |
47 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
48 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
49 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
50 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
51 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
52 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
53 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
54 | 7 | -0.70007713E-08 | -0.80410658E-14 | -0.90308157E-15 | 0.82137664E-17 |
55 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
56 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
57 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
58 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
59 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
60 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
61 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
62 | 7 | -0.70007713E-08 | -0.80410657E-14 | -0.90308142E-15 | 0.82137640E-17 |
63 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
64 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
65 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
66 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
67 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
68 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
69 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
70 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308145E-15 | 0.82137644E-17 |
71 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
72 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
73 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
74 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
75 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
76 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
77 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
78 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308158E-15 | 0.82137665E-17 |
79 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
80 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
81 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
82 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
83 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
84 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
85 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
86 | 7 | -0.70007713E-08 | -0.80410658E-14 | -0.90308164E-15 | 0.82137675E-17 |
87 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
88 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
89 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
90 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
91 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
92 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
93 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
94 | 7 | -0.70007713E-08 | -0.80410659E-14 | -0.90308145E-15 | 0.82137644E-17 |
95 | 6 | 0.21712725E-05 | 0.11838265E-08 | 0.32006334E-02 | -0.26849596E-04 |
96 | 5 | -0.13301509E-03 | 0.69458749E-06 | -0.22433613 | 0.19615483E-02 |
97 | 4 | 0.29052452E-02 | 0.31467785E-04 | 4.8397276 | -0.45362860E-01 |
98 | 3 | -0.25016136E-01 | 0.24921377E-03 | -38.078914 | 0.39928933 |
99 | 2 | 0.88121217E-01 | 0.41303221E-03 | 116.59583 | -1.4194359 |
100 | 1 | -0.12672960 | 0.12519520E-03 | -143.97316 | 2.0501223 |
101 | 0 | 0.61672764E-01 | 0.30323733E-05 | 60.838472 | |
102 | 7 | -0.27342154E-08 | -0.14755226E-14 | 0.78892317E-14 | -0.11406260E-15 |
103 | 6 | 0.44275096E-05 | 0.29655051E-08 | 0.31933384E-02 | -0.26788399E-04 |
104 | 5 | -0.31313574E-03 | 0.17544743E-05 | -0.22392171 | 0.19578903E-02 |
105 | 4 | 0.71689416E-02 | 0.79816958E-04 | 4.8328290 | -0.45296542E-01 |
106 | 3 | -0.62848542E-01 | 0.63438109E-03 | -38.039963 | 0.39885876 |
107 | 2 | 0.22301735 | 0.10548637E-02 | 116.52005 | -1.4184221 |
108 | 1 | -0.32179990 | 0.32117902E-03 | -143.92856 | 2.0493892 |
109 | 0 | 0.15687064 | 0.77839935E-05 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 35 | 1 | VerySmooth | 1.657 | 1.657 | 1.000 | 0.451 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 4.25070E-002 | 0.36619 | 0.44094 | 0.44094 | 0.45000 | 0.13324 | 0.16828 | 0.00000 | 0.84000 | 0.84000 | 9.90222E-002 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 22362.18388 | 26834.62065 | 1.71276 | 2.05532 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 30.10000 | 1.27259E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 37518.61487 | 45022.33785 | 1.68750 | 2.02500 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 12051.66138 | 14461.99365 | 0.89793 | 1.07752 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 17872.06977 | 21446.48373 | 0.80385 | 0.96461 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 12138.55226 | 14566.26271 | 0.90476 | 1.08572 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 17996.29083 | 21595.54899 | 0.80943 | 0.97132 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 12066.98346 | 14480.38015 | 0.89927 | 1.07912 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 18053.55745 | 21664.26894 | 0.81201 | 0.97441 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 12080.04504 | 14496.05405 | 0.90029 | 1.08035 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.28000 | 1.27140E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 18189.54461 | 21827.45354 | 0.81813 | 0.98175 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 21356.53606 | 25627.84327 | 1.63571 | 1.96286 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 29.99667 | 1.27257E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 34475.86986 | 41371.04383 | 1.55068 | 1.86081 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11335.26695 | 13602.32034 | 0.84339 | 1.01207 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 18529.40823 | 22235.28987 | 0.83341 | 1.00010 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 11270.07869 | 13524.09442 | 0.83842 | 1.00611 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 18515.77887 | 22218.93465 | 0.83280 | 0.99936 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 11177.42773 | 13412.91328 | 0.83138 | 0.99766 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 18784.20979 | 22541.05175 | 0.84487 | 1.01385 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11857.13621 | 14228.56345 | 0.88338 | 1.06006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 25.38800 | 1.27176E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 22970.94731 | 27565.13677 | 1.03315 | 1.23978 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -32.70000 | 1.83376E-004 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 29384.61 | 2.05532 | 2.05532 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 70038.12 | 2.02500 | 2.02500 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 15667.91 | 1.10355 | 1.10355 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 33969.89 | 0.96461 | 0.96461 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 15690.18 | 1.10528 | 1.10528 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 34116.78 | 0.97132 | 0.97132 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 15735.08 | 1.10877 | 1.10877 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 34184.50 | 0.97441 | 0.97441 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 15629.69 | 1.10057 | 1.10057 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 34345.31 | 0.98175 | 0.98175 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 28194.99 | 1.96286 | 1.96286 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 66440.21 | 1.86081 | 1.86081 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 14536.22 | 1.01553 | 1.01553 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 34747.22 | 1.00010 | 1.00010 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 14456.66 | 1.00985 | 1.00985 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 34731.10 | 0.99936 | 0.99936 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 14400.95 | 1.00507 | 1.00507 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 35048.53 | 1.01385 | 1.01385 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 15178.86 | 1.07633 | 1.07633 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 39999.27 | 1.23978 | 1.23978 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.05532 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07752 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08572 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.07912 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.08035 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.96286 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01207 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00611 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01385 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.23978 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.05532 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.05532 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.05532 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.05532 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.05532 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.05532 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07752 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07752 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07752 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07752 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10355 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10355 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.97641 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08572 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08572 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08572 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08572 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10528 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10528 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.98230 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.07912 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.07912 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.07912 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.07912 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10877 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10877 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 0.97326 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.08035 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.08035 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.08035 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.08035 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.10057 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.10057 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.98163 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.96286 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.96286 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.96286 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.96286 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.96286 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.96286 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01207 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01207 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01207 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01207 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01553 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01553 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.99659 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00611 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00611 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00611 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00611 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.00985 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.00985 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.99629 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01385 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01385 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01385 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01385 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01385 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01385 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.23978 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.23978 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.23978 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.23978 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.23978 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.23978 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.05532 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.10355 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.10528 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.10877 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.10057 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.96286 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.01553 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.00985 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.01385 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.23978 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.05532 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.05532 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2199.28609 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.05532 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.05532 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.05532 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.05532 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.05532 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.02766 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.05532 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41614.50000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20485.97151 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41614.50000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77158 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77158 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41614.50000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 70702.30046 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 70702.30046 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10355 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10355 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1221.80043 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10355 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10355 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10355 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10355 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10355 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55177 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10355 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22022.39000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10856.00261 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22022.39000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77697 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77697 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22022.39000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36443.53556 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 36443.53556 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10528 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10528 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1223.71818 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10528 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10528 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10528 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10528 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10528 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55264 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10528 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22049.58000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10869.34322 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22049.58000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77707 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77707 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22049.58000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36623.13249 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 36623.13249 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10877 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10877 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1227.58472 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10877 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10877 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10877 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10877 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10877 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55439 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10877 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 22104.26000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10896.16545 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 22104.26000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77728 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77728 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 22104.26000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36478.63205 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 36478.63205 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.10057 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.10057 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1218.50727 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.10057 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.10057 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.10057 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.10057 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.10057 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.55029 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.10057 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 21975.89000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10833.19658 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 21975.89000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77679 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77679 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 21975.89000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36505.59343 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 36505.59343 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.96286 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.96286 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2100.34976 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.96286 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.96286 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.96286 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.96286 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.96286 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.98143 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.96286 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 40033.95000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 19710.73089 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 40033.95000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76840 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76840 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 40033.95000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68675.83855 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 68675.83855 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01553 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01553 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1124.35700 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01553 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01553 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01553 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01553 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01553 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50777 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01553 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20638.61000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10177.15814 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20638.61000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76946 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76946 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20638.61000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35009.47341 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 35009.47341 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.00985 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.00985 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1118.06562 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.00985 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.00985 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.00985 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.00985 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.00985 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50493 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.00985 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20551.12000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10134.25972 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20551.12000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76906 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76906 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20551.12000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 34878.92438 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 34878.92438 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01385 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01385 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1122.49176 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01385 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01385 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01385 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01385 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01385 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50692 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01385 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 20652.33000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 10184.34149 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 20652.33000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.76877 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.76877 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 20652.33000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35048.52909 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 35048.52909 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.23978 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.23978 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1372.62930 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.23978 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.23978 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.23978 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.23978 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.23978 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.61989 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.23978 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24875.15000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12263.73420 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24875.15000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.77533 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.77533 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24875.15000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 39999.27070 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 39999.27070 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 39999.0 | 10.93 | 10.93 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 21155.2 | 11.07 | 11.07 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 21181.0 | 11.07 | 11.07 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 21233.0 | 11.07 | 11.07 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 21111.0 | 11.07 | 11.07 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 38490.9 | 10.94 | 10.94 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 19840.3 | 11.10 | 11.10 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 19757.3 | 11.10 | 11.10 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 19855.3 | 11.10 | 11.10 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 23900.8 | 11.08 | 11.08 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.108 | 0.105 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 6.115E-002 | 6.026E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.2917_SHGC_0.45 | N/A | 1.657 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.155 | 0.149 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.163 | 0.158 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 0.1166530747 | 0.3565318983 | Pass | Pass | 0.2194850617 | 0.7926474066 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 7.4182445494E-002 | 0.3036711000 | Pass | Pass | 0.1328821078 | 0.7154766946 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 0.1069808862 | 0.3427316400 | Pass | Pass | 9.8224134351E-002 | 0.3793871663 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 0.1206182893 | 0.3476816544 | Pass | Pass | 0.2055986556 | 0.7845294898 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 0.1307487397 | 0.3528435304 | Pass | Pass | 0.1582415050 | 0.4442822332 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 0.1678110513 | 0.3736364951 | Pass | Pass | 0.2236776119 | 0.6486058209 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 0.1693963599 | 0.3588198576 | Pass | Pass | 0.2836817691 | 0.6516565643 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 0.1705736202 | 0.3587728240 | Pass | Pass | 0.3060056733 | 0.7424660454 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 0.1891637699 | 0.3678207810 | Pass | Pass | 0.3308752267 | 0.7383978003 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 0.4039438910 | 0.5650811236 | Pass | Pass | 0.2682597592 | 0.4473030245 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3632.26 | 348.40 | 0.00 | 855.25 | 523.36 | 5359.30 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | -32.70 | 0.00 | -32.70 | Wetbulb [C] | 2.40 | 210.00 |
INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 30.10 | 12.40 | 21.10 | Wetbulb [C] | 4.70 | 200.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 0.00 | 0 | |||
Mar | 12.00 | 13 | |||
Apr | 16.00 | 23 | |||
May | 0.00 | 0 | |||
Jun | 190.00 | 53 | |||
Jul | 136.00 | 41 | |||
Aug | 87.00 | 42 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 0.00 | 0 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.106 | 0.108 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.061 | 0.061 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.151 | 0.155 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.159 | 0.163 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.657 | 0.451 | 0.452 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.657 | 0.451 | 0.452 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 1.657 | 0.451 | 0.452 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 1.657 | 0.451 | 0.452 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.2917_SHGC_0.45 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 1.657 | 0.451 | 0.452 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 1.657 | 0.451 | 0.452 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 1.657 | 0.451 | 0.452 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.52 | 83.52 | 121.08 | |
Exterior Lighting Total | 7723.26 | 121.08 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41614.50 | 32108.92 | 9505.58 | 0.77 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22022.39 | 17110.74 | 4911.65 | 0.78 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22049.58 | 17134.07 | 4915.51 | 0.78 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 22104.26 | 17181.20 | 4923.06 | 0.78 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 21975.89 | 17070.65 | 4905.24 | 0.78 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 40033.95 | 30762.09 | 9271.86 | 0.77 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20638.61 | 15880.58 | 4758.03 | 0.77 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20551.12 | 15805.04 | 4746.08 | 0.77 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 20652.33 | 15876.89 | 4775.44 | 0.77 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24875.15 | 19286.45 | 5588.70 | 0.78 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 39999.0 | 10.93 | 10.93 | ||||
PSZ-AC_2:2 COOLING COIL | 21155.2 | 11.07 | 11.07 | ||||
PSZ-AC_3:3 COOLING COIL | 21181.0 | 11.07 | 11.07 | ||||
PSZ-AC_4:4 COOLING COIL | 21233.0 | 11.07 | 11.07 | ||||
PSZ-AC_5:5 COOLING COIL | 21111.0 | 11.07 | 11.07 | ||||
PSZ-AC_6:6 COOLING COIL | 38490.9 | 10.94 | 10.94 | ||||
PSZ-AC_7:7 COOLING COIL | 19840.3 | 11.10 | 11.10 | ||||
PSZ-AC_8:8 COOLING COIL | 19757.3 | 11.10 | 11.10 | ||||
PSZ-AC_9:9 COOLING COIL | 19855.3 | 11.10 | 11.10 | ||||
PSZ-AC_10:10 COOLING COIL | 23900.8 | 11.08 | 11.08 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 70702.30 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 36443.54 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 36623.13 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 36478.63 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 36505.59 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 68675.84 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 35009.47 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 34878.92 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 35048.53 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 39999.27 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.06 | 2199.29 | 1070.05 | 1.00 | 1.31 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1221.80 | 1107.16 | 1.00 | 1.38 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1223.72 | 1107.16 | 1.00 | 1.38 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.11 | 1227.58 | 1107.16 | 1.00 | 1.38 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.10 | 1218.51 | 1107.16 | 1.00 | 1.38 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.96 | 2100.35 | 1070.05 | 1.00 | 1.32 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1124.36 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1118.07 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.01 | 1122.49 | 1107.16 | 1.00 | 1.40 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1372.63 | 1107.16 | 1.00 | 1.35 | General | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 22362.18 | 26834.62 | 77.03 | 1.713 | 2.055 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 23.89 | 23.89 | 0.00956 | 30.10 | 0.01273 | 0.411 | 0.00 |
SMSTORE1 | 12051.66 | 14461.99 | 83.02 | 0.898 | 1.078 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00928 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE2 | 12138.55 | 14566.26 | 83.62 | 0.905 | 1.086 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00953 | 23.28 | 0.01271 | 0.206 | 0.00 |
SMSTORE3 | 12066.98 | 14480.38 | 83.13 | 0.899 | 1.079 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00952 | 23.28 | 0.01271 | 0.206 | 0.00 |
SMSTORE4 | 12080.05 | 14496.05 | 83.22 | 0.900 | 1.080 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00954 | 23.28 | 0.01271 | 0.206 | 0.00 |
LGSTORE2 | 21356.54 | 25627.84 | 73.56 | 1.636 | 1.963 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00957 | 30.00 | 0.01273 | 0.411 | 0.00 |
SMSTORE5 | 11335.27 | 13602.32 | 78.09 | 0.843 | 1.012 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00943 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE6 | 11270.08 | 13524.09 | 77.64 | 0.838 | 1.006 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00945 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE7 | 11177.43 | 13412.91 | 77.00 | 0.831 | 0.998 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.89 | 0.00948 | 25.39 | 0.01272 | 0.206 | 0.00 |
SMSTORE8 | 11857.14 | 14228.56 | 81.68 | 0.883 | 1.060 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:00:00 | 23.89 | 23.88 | 0.00947 | 25.39 | 0.01272 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 37518.61 | 45022.34 | 129.23 | 1.688 | 2.025 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00677 | -32.70 | 0.00018 | 0.411 | 0.00 |
SMSTORE1 | 17872.07 | 21446.48 | 123.12 | 0.804 | 0.965 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00665 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE2 | 17996.29 | 21595.55 | 123.97 | 0.809 | 0.971 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE3 | 18053.56 | 21664.27 | 124.37 | 0.812 | 0.974 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00666 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE4 | 18189.54 | 21827.45 | 125.31 | 0.818 | 0.982 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00667 | -32.70 | 0.00018 | 0.206 | 0.00 |
LGSTORE2 | 34475.87 | 41371.04 | 118.75 | 1.551 | 1.861 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00673 | -32.70 | 0.00018 | 0.411 | 0.00 |
SMSTORE5 | 18529.41 | 22235.29 | 127.65 | 0.833 | 1.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE6 | 18515.78 | 22218.93 | 127.55 | 0.833 | 0.999 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00669 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE7 | 18784.21 | 22541.05 | 129.40 | 0.845 | 1.014 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00670 | -32.70 | 0.00018 | 0.206 | 0.00 |
SMSTORE8 | 22970.95 | 27565.14 | 158.24 | 1.033 | 1.240 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.10 | 0.00682 | -32.70 | 0.00018 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.06 | 2.06 | 2.03 | 2.03 | 2.0553 | 2.0553 | 2.0553 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.10 | 1.10 | 0.96 | 0.96 | 1.1035 | 1.0775 | 1.1035 | 0.9764 | 1.0000 |
PSZ-AC_3:3 | 1.11 | 1.11 | 0.97 | 0.97 | 1.1053 | 1.0857 | 1.1053 | 0.9823 | 1.0000 |
PSZ-AC_4:4 | 1.11 | 1.11 | 0.97 | 0.97 | 1.1088 | 1.0791 | 1.1088 | 0.9733 | 1.0000 |
PSZ-AC_5:5 | 1.10 | 1.10 | 0.98 | 0.98 | 1.1006 | 1.0804 | 1.1006 | 0.9816 | 1.0000 |
PSZ-AC_6:6 | 1.96 | 1.96 | 1.86 | 1.86 | 1.9629 | 1.9629 | 1.9629 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.02 | 1.02 | 1.00 | 1.00 | 1.0155 | 1.0121 | 1.0155 | 0.9966 | 1.0000 |
PSZ-AC_8:8 | 1.01 | 1.01 | 1.00 | 1.00 | 1.0099 | 1.0061 | 1.0099 | 0.9963 | 1.0000 |
PSZ-AC_9:9 | 1.01 | 1.01 | 1.01 | 1.01 | 1.0138 | 1.0138 | 1.0138 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.08 | 1.08 | 1.24 | 1.24 | 1.2398 | 1.2398 | 1.2398 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 41614.500 | 32108.916 | 2.055320 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | 41614.50 | 32486.31 | 2.055320 | 26.04 | 18.03 | 0.01019639 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 20.0202 | 23.89 | 0.00956322 | 49.5879 | 22362.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 70702.300 | 70702.300 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 70702.30 | 70702.30 | 2.055317 | 10.33 | 7.38 | 0.00544773 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.0202 | 21.10 | 0.00676549 | 41.7311 | 37518.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 22022.390 | 17110.736 | 1.103550 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22022.39 | 17373.29 | 1.103550 | 25.98 | 17.94 | 0.01010986 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 18.6434 | 23.89 | 0.00951039 | 49.3177 | 12006.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 36443.536 | 36443.536 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36443.54 | 36443.54 | 1.103546 | 11.07 | 7.72 | 0.00544414 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 18.6435 | 21.10 | 0.00664969 | 41.0248 | 17872.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 22049.580 | 17134.067 | 1.105280 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22049.58 | 17398.94 | 1.105280 | 25.98 | 17.94 | 0.01010783 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 18.6142 | 23.89 | 0.00950905 | 49.3109 | 12025.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 36623.132 | 36623.132 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36623.13 | 36623.13 | 1.105278 | 11.09 | 7.74 | 0.00545173 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 18.6143 | 21.10 | 0.00665669 | 41.0675 | 17996.29 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 22104.260 | 17181.199 | 1.108770 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 22104.26 | 17450.65 | 1.108770 | 25.98 | 17.93 | 0.01010371 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 18.5556 | 23.89 | 0.00950630 | 49.2968 | 12063.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 36478.632 | 36478.632 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36478.63 | 36478.63 | 1.108770 | 11.12 | 7.76 | 0.00545814 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 18.5556 | 21.10 | 0.00665990 | 41.0871 | 18053.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 21975.890 | 17070.652 | 1.100570 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | 21975.89 | 17329.25 | 1.100570 | 25.98 | 17.94 | 0.01011344 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 18.6939 | 23.89 | 0.00951279 | 49.3300 | 11974.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 36505.593 | 36505.593 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 36505.59 | 36505.59 | 1.100571 | 11.05 | 7.72 | 0.00545535 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 18.6939 | 21.10 | 0.00666748 | 41.1334 | 18189.54 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 40033.950 | 30762.087 | 1.962860 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 40033.95 | 31124.01 | 1.962860 | 26.09 | 18.08 | 0.01023496 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 20.9632 | 23.89 | 0.00957424 | 49.6438 | 21355.32 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 68675.839 | 68675.839 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 68675.84 | 68675.84 | 1.962857 | 9.83 | 7.03 | 0.00535798 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.9633 | 21.10 | 0.00673046 | 41.5163 | 34475.87 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 20638.610 | 15880.585 | 1.015530 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 20638.61 | 16069.77 | 1.015530 | 26.08 | 18.06 | 0.01022169 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 20.2593 | 23.89 | 0.00958545 | 49.7011 | 11049.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 35009.473 | 35009.473 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35009.47 | 35009.47 | 1.015534 | 10.20 | 7.22 | 0.00536862 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.2592 | 21.10 | 0.00668600 | 41.2464 | 18529.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 20551.120 | 15805.044 | 1.009850 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | 20551.12 | 15986.10 | 1.009850 | 26.09 | 18.07 | 0.01023013 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 20.3733 | 23.89 | 0.00959115 | 49.7301 | 10981.66 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 34878.924 | 34878.924 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 34878.92 | 34878.92 | 1.009851 | 10.14 | 7.19 | 0.00536062 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.3732 | 21.10 | 0.00668526 | 41.2419 | 18515.78 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 20652.330 | 15876.892 | 1.013850 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 20652.33 | 16053.82 | 1.013850 | 26.10 | 18.08 | 0.01023609 | 12.80 | 11.72 | 0.00850000 | 30.10 | 0.01272586 | 21.13 | 20.2929 | 23.89 | 0.00959517 | 49.7507 | 10934.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 35048.529 | 35048.529 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 35048.53 | 35048.53 | 1.013849 | 10.19 | 7.23 | 0.00537723 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 20.2929 | 21.10 | 0.00669956 | 41.3292 | 18784.21 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 24875.150 | 19286.450 | 1.239780 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 24875.15 | 19402.06 | 1.239780 | 25.94 | 17.99 | 0.01019183 | 12.80 | 11.72 | 0.00850000 | 29.69 | 0.01272514 | 21.01 | 16.5948 | 23.89 | 0.00959097 | 49.7298 | 11676.43 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 39999.271 | 39999.271 | -999.0 | -999.0 | -999.000 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 39999.27 | 39999.27 | 1.239776 | 12.18 | 8.53 | 0.00571683 | 40.00 | 20.69 | 0.00800000 | -32.70 | 0.00018338 | -32.70 | 16.5949 | 21.10 | 0.00681780 | 42.0525 | 22970.95 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41614.500 | 32108.916 | 2.055320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7946 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.055317 | 2.37168110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:40:00 | Sensible | 41614.50 | 32486.31 | 1.0000 | 2.37168484 | 2.055320 | 26.04 | 18.03 | 0.01019639 | 52155.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41614.50 | 30.10 | 0.01272586 | 21.13 | 0.41147883 | 20.0202 | 23.89 | 0.00956322 | 23.89 | 0.00956322 | 49.5879 | 22362.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 70702.300 | 70702.300 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.055317 | 2.37168110 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 70702.30 | 70702.30 | 1.0000 | 2.37168110 | 2.055317 | 10.33 | 7.38 | 0.00544773 | 24112.2 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 70702.30 | -32.70 | 0.00018338 | -32.70 | 0.41147883 | 20.0202 | 21.10 | 0.00676549 | 21.10 | 0.00676549 | 41.7311 | 37518.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22022.390 | 17110.736 | 1.103550 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6337 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.103546 | 1.27340898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 22022.39 | 17373.29 | 1.0000 | 1.27341378 | 1.103550 | 25.98 | 17.94 | 0.01010986 | 51880.0 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22022.39 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 18.6434 | 23.89 | 0.00951039 | 23.89 | 0.00951039 | 49.3177 | 12006.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36443.536 | 36443.536 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.103546 | 1.27340898 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36443.54 | 36443.54 | 1.0000 | 1.27340898 | 1.103546 | 11.07 | 7.72 | 0.00544414 | 24855.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36443.54 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 18.6435 | 21.10 | 0.00664969 | 21.10 | 0.00664969 | 41.0248 | 17872.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22049.580 | 17134.067 | 1.105280 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6300 | 1004.8586 | 1.1539 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.105278 | 1.27540774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 22049.58 | 17398.94 | 1.0000 | 1.27541007 | 1.105280 | 25.98 | 17.94 | 0.01010783 | 51872.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22049.58 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 18.6142 | 23.89 | 0.00950905 | 23.89 | 0.00950905 | 49.3109 | 12025.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36623.132 | 36623.132 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.105278 | 1.27540774 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36623.13 | 36623.13 | 1.0000 | 1.27540774 | 1.105278 | 11.09 | 7.74 | 0.00545173 | 24890.1 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36623.13 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 18.6143 | 21.10 | 0.00665669 | 21.10 | 0.00665669 | 41.0675 | 17996.29 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 22104.260 | 17181.199 | 1.108770 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6223 | 1004.8586 | 1.1539 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.108770 | 1.27943761 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 22104.26 | 17450.65 | 1.0000 | 1.27943726 | 1.108770 | 25.98 | 17.93 | 0.01010371 | 51858.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 22104.26 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 18.5556 | 23.89 | 0.00950630 | 23.89 | 0.00950630 | 49.2968 | 12063.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36478.632 | 36478.632 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.108770 | 1.27943761 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36478.63 | 36478.63 | 1.0000 | 1.27943761 | 1.108770 | 11.12 | 7.76 | 0.00545814 | 24938.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36478.63 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 18.5556 | 21.10 | 0.00665990 | 21.10 | 0.00665990 | 41.0871 | 18053.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 21975.890 | 17070.652 | 1.100570 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.6404 | 1004.8586 | 1.1539 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.100571 | 1.26997673 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | Sensible | 21975.89 | 17329.25 | 1.0000 | 1.26997508 | 1.100570 | 25.98 | 17.94 | 0.01011344 | 51892.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 21975.89 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 18.6939 | 23.89 | 0.00951279 | 23.89 | 0.00951279 | 49.3300 | 11974.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36505.593 | 36505.593 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.100571 | 1.26997673 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 36505.59 | 36505.59 | 1.0000 | 1.26997673 | 1.100571 | 11.05 | 7.72 | 0.00545535 | 24855.8 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36505.59 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 18.6939 | 21.10 | 0.00666748 | 21.10 | 0.00666748 | 41.1334 | 18189.54 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 40033.950 | 30762.087 | 1.962860 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8663 | 1004.8586 | 1.1539 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.962857 | 2.26498947 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 40033.95 | 31124.01 | 1.0000 | 2.26499294 | 1.962860 | 26.09 | 18.08 | 0.01023496 | 52314.2 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 40033.95 | 30.10 | 0.01272586 | 21.13 | 0.41147883 | 20.9632 | 23.89 | 0.00957424 | 23.89 | 0.00957424 | 49.6438 | 21355.32 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68675.839 | 68675.839 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.962857 | 2.26498947 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 68675.84 | 68675.84 | 1.0000 | 2.26498947 | 1.962857 | 9.83 | 7.03 | 0.00535798 | 23371.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68675.84 | -32.70 | 0.00018338 | -32.70 | 0.41147883 | 20.9633 | 21.11 | 0.00673046 | 21.10 | 0.00673046 | 41.5163 | 34475.87 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20638.610 | 15880.585 | 1.015530 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8416 | 1004.8586 | 1.1539 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.015534 | 1.17184957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 20638.61 | 16069.77 | 1.0000 | 1.17184531 | 1.015530 | 26.08 | 18.06 | 0.01022169 | 52267.7 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20638.61 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 20.2593 | 23.89 | 0.00958545 | 23.89 | 0.00958545 | 49.7011 | 11049.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35009.473 | 35009.473 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.015534 | 1.17184957 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35009.47 | 35009.47 | 1.0000 | 1.17184957 | 1.015534 | 10.20 | 7.22 | 0.00536862 | 23782.4 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35009.47 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.2592 | 21.11 | 0.00668600 | 21.10 | 0.00668600 | 41.2464 | 18529.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20551.120 | 15805.044 | 1.009850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8573 | 1004.8586 | 1.1539 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.009851 | 1.16529244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 10:20:00 | Sensible | 20551.12 | 15986.10 | 1.0000 | 1.16529102 | 1.009850 | 26.09 | 18.07 | 0.01023013 | 52297.1 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20551.12 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 20.3733 | 23.89 | 0.00959115 | 23.89 | 0.00959115 | 49.7301 | 10981.66 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 34878.924 | 34878.924 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.009851 | 1.16529244 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 34878.92 | 34878.92 | 1.0000 | 1.16529244 | 1.009851 | 10.14 | 7.19 | 0.00536062 | 23700.0 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 34878.92 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.3732 | 21.11 | 0.00668526 | 21.10 | 0.00668526 | 41.2419 | 18515.78 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 20652.330 | 15876.892 | 1.013850 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.8684 | 1004.8586 | 1.1539 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013849 | 1.16990554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 20652.33 | 16053.82 | 1.0000 | 1.16990672 | 1.013850 | 26.10 | 18.08 | 0.01023609 | 52317.9 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 20652.33 | 30.10 | 0.01272586 | 21.13 | 0.20573941 | 20.2929 | 23.89 | 0.00959517 | 23.89 | 0.00959517 | 49.7507 | 10934.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35048.529 | 35048.529 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.013849 | 1.16990554 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 35048.53 | 35048.53 | 1.0000 | 1.16990554 | 1.013849 | 10.19 | 7.23 | 0.00537723 | 23785.7 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35048.53 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 20.2929 | 21.11 | 0.00669956 | 21.10 | 0.00669956 | 41.3292 | 18784.21 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24875.150 | 19286.450 | 1.239780 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1023.7861 | 1004.8586 | 1.1539 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.239776 | 1.43060883 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:20:00 | INTERNATIONAL FALLS INTL AP ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 24875.15 | 19402.06 | 1.0000 | 1.43061296 | 1.239780 | 25.94 | 17.99 | 0.01019183 | 52041.3 | 12.80 | 11.72 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24875.15 | 29.69 | 0.01272514 | 21.01 | 0.20573941 | 16.5948 | 23.89 | 0.00959097 | 23.89 | 0.00959097 | 49.7298 | 11676.43 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 39999.271 | 39999.271 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1539 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.239776 | 1.43060883 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | INTERNATIONAL FALLS INTL AP ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 39999.27 | 39999.27 | 1.0000 | 1.43060883 | 1.239776 | 12.18 | 8.53 | 0.00571683 | 26661.3 | 40.00 | 20.69 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 39999.27 | -32.70 | 0.00018338 | -32.70 | 0.20573941 | 16.5949 | 21.10 | 0.00681780 | 21.10 | 0.00681780 | 42.0525 | 22970.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.06 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.10 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.11 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.10 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.96 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.01 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 3853.67 | 4151.17 | 2698.67 |
SMSTORE1 | 3227.50 | 3819.50 | 1859.17 |
SMSTORE2 | 2720.67 | 2972.33 | 1699.67 |
SMSTORE3 | 2765.17 | 2996.83 | 1755.67 |
SMSTORE4 | 2810.50 | 3053.17 | 1840.17 |
LGSTORE2 | 2681.33 | 2901.33 | 1899.17 |
SMSTORE5 | 2643.67 | 2925.17 | 1911.83 |
SMSTORE6 | 2653.00 | 2947.50 | 1941.50 |
SMSTORE7 | 2710.50 | 3015.33 | 2042.17 |
SMSTORE8 | 2857.17 | 3127.17 | 2266.17 |
Facility | 4519.17 | 4567.17 | 3252.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 12.67 | 0.17 | 0.00 | 0.17 |
SMSTORE1 | 6.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.17 | 0.00 | 0.17 |
SMSTORE3 | 0.17 | 0.17 | 0.00 | 0.17 |
SMSTORE4 | 0.00 | 0.17 | 0.00 | 0.17 |
LGSTORE2 | 1.17 | 0.50 | 0.00 | 0.50 |
SMSTORE5 | 0.67 | 0.33 | 0.00 | 0.33 |
SMSTORE6 | 0.83 | 0.33 | 0.00 | 0.33 |
SMSTORE7 | 3.00 | 0.17 | 0.00 | 0.17 |
SMSTORE8 | 130.50 | 0.00 | 0.00 | 0.00 |
Facility | 147.17 | 0.67 | 0.00 | 0.67 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 1.174 | 0.237 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 1.072 | 0.252 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 1.255 | 0.329 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 1.252 | 0.329 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 1.234 | 0.329 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 1.179 | 0.316 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 1.195 | 0.351 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 1.186 | 0.351 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 1.171 | 0.351 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 1.228 | 0.372 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.797 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 12155607.79 | 0.00 | 12155607.79 | 2824003.76 | 14979611.55 | 12976396.34 | 3177.01 | 4082.61 | 1500.38 | 0.00 |
SMSTORE1 | 5541979.94 | 0.00 | 5541979.94 | 1417423.17 | 6959403.11 | 6488198.17 | 4241.83 | 2914.73 | 1603.43 | 0.00 |
SMSTORE2 | 4889478.63 | 0.00 | 4889478.63 | 1450589.24 | 6340067.87 | 6488198.17 | 4364.67 | 3286.15 | 1109.18 | 2.50 |
SMSTORE3 | 4880154.09 | 0.00 | 4880154.09 | 1450589.24 | 6330743.32 | 6488198.17 | 4364.33 | 3308.00 | 1087.67 | 3.00 |
SMSTORE4 | 4810063.49 | 0.00 | 4810063.49 | 1450589.24 | 6260652.73 | 6488198.17 | 4364.83 | 3355.38 | 1039.79 | 1.83 |
LGSTORE2 | 8426548.56 | 0.00 | 8426548.56 | 2662612.36 | 11089160.92 | 12976396.34 | 4729.83 | 3112.17 | 917.99 | 0.83 |
SMSTORE5 | 4268309.87 | 0.00 | 4268309.87 | 1460886.51 | 5729196.38 | 6488198.17 | 4730.00 | 3115.82 | 914.18 | 0.58 |
SMSTORE6 | 4237772.91 | 0.00 | 4237772.91 | 1460886.51 | 5698659.43 | 6488198.17 | 4730.00 | 3134.82 | 895.18 | 0.33 |
SMSTORE7 | 4185259.02 | 0.00 | 4185259.02 | 1460886.51 | 5646145.53 | 6488198.17 | 4730.00 | 3180.87 | 849.13 | 0.17 |
SMSTORE8 | 4387715.66 | 0.00 | 4387715.66 | 1774399.60 | 6162115.25 | 6488198.17 | 4730.00 | 3224.32 | 805.68 | 0.17 |
Total Facility | 57782889.95 | 0.00 | 57782889.95 | 17412866.15 | 75195756.10 | 77858378.04 | 4730.00 | 4593.02 | 1813.44 | 3.83 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5782 | 0.0000 | 0.5782 | 0.1172 | 0.6954 | 0.4115 | 257.01 | 4082.61 | 1500.38 |
SMSTORE1 | 0.2636 | 0.0000 | 0.2636 | 0.0624 | 0.3260 | 0.2057 | 1321.83 | 2914.73 | 1603.43 |
SMSTORE2 | 0.3090 | 0.0000 | 0.3090 | 0.0815 | 0.3904 | 0.2057 | 0.00 | 3286.15 | 1108.85 |
SMSTORE3 | 0.3084 | 0.0000 | 0.3084 | 0.0815 | 0.3898 | 0.2057 | 0.00 | 3308.00 | 1087.00 |
SMSTORE4 | 0.3040 | 0.0000 | 0.3040 | 0.0815 | 0.3854 | 0.2057 | 0.00 | 3355.38 | 1039.62 |
LGSTORE2 | 0.5808 | 0.0000 | 0.5808 | 0.1564 | 0.7372 | 0.4115 | 0.00 | 3112.17 | 917.83 |
SMSTORE5 | 0.2942 | 0.0000 | 0.2942 | 0.0869 | 0.3811 | 0.2057 | 0.00 | 3115.82 | 914.18 |
SMSTORE6 | 0.2921 | 0.0000 | 0.2921 | 0.0869 | 0.3790 | 0.2057 | 0.00 | 3134.82 | 895.18 |
SMSTORE7 | 0.2885 | 0.0000 | 0.2885 | 0.0869 | 0.3753 | 0.2057 | 0.00 | 3180.87 | 849.13 |
SMSTORE8 | 0.3024 | 0.0000 | 0.3024 | 0.0919 | 0.3944 | 0.2057 | 0.00 | 3224.32 | 805.68 |
Total Facility | 3.5210 | 0.0000 | 3.5210 | 0.9329 | 4.4539 | 2.4689 | 1430.00 | 4593.02 | 1812.94 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 16185709.30 | 0.00 | 16185709.30 | 12976396.34 | 3174.62 | 0.17 | 5585.21 | 0.00 |
PSZ-AC_2:2 | 7379382.26 | 0.00 | 7379382.26 | 6488198.17 | 4236.50 | 1.08 | 4522.42 | 0.00 |
PSZ-AC_3:3 | 6510548.96 | 0.00 | 6510548.96 | 6488198.17 | 4364.17 | 0.17 | 4395.67 | 2.50 |
PSZ-AC_4:4 | 6498132.93 | 0.00 | 6498132.93 | 6488198.17 | 4364.00 | 0.00 | 4396.00 | 3.00 |
PSZ-AC_5:5 | 6404804.32 | 0.00 | 6404804.32 | 6488198.17 | 4364.33 | 0.00 | 4395.67 | 1.83 |
PSZ-AC_6:6 | 11220308.16 | 0.00 | 11220308.16 | 12976396.34 | 4729.83 | 0.00 | 4030.17 | 0.83 |
PSZ-AC_7:7 | 5683436.31 | 0.00 | 5683436.31 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.58 |
PSZ-AC_8:8 | 5642775.06 | 0.00 | 5642775.06 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.33 |
PSZ-AC_9:9 | 5572850.57 | 0.00 | 5572850.57 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.17 |
PSZ-AC_10:10 | 5842430.20 | 0.00 | 5842430.20 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.17 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7699 | 0.0000 | 0.7699 | 0.4115 | 254.62 | 0.17 | 5585.21 |
PSZ-AC_2:2 | 0.3510 | 0.0000 | 0.3510 | 0.2057 | 1316.50 | 1.08 | 4522.42 |
PSZ-AC_3:3 | 0.4114 | 0.0000 | 0.4114 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.4106 | 0.0000 | 0.4106 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.4047 | 0.0000 | 0.4047 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.7733 | 0.0000 | 0.7733 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3917 | 0.0000 | 0.3917 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3889 | 0.0000 | 0.3889 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3841 | 0.0000 | 0.3841 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.4027 | 0.0000 | 0.4027 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4811.82 | 783.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3903.44 | 1047.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3867.17 | 530.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3884.52 | 513.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3910.75 | 486.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3637.32 | 393.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3638.89 | 391.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3649.95 | 380.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3666.05 | 364.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3631.56 | 398.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.7565 | 1.0939 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3915 | 0.4983 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3876 | 0.5868 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3867 | 0.5931 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3808 | 0.5990 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.7335 | 1.1443 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3709 | 0.5864 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3684 | 0.5867 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3631 | 0.5972 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3730 | 0.6747 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
ElectricityPurchased:Plant | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
Cogeneration:ElectricityPurchased | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
General:Cogeneration:ElectricityPurchased | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
ElectricityNet:Plant | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
Cogeneration:ElectricityNet | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
General:Cogeneration:ElectricityNet | 1085.85 | 3178.87 | 05-FEB-07:50 | 108969.61 | 15-JUL-14:10 |
Electricity:HVAC | 306.28 | 0.00 | 03-JAN-01:40 | 67320.62 | 29-JUN-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 66.11 | 0.00 | 01-JAN-00:10 | 53391.83 | 29-JUN-16:10 |
General:Cooling:Electricity | 66.11 | 0.00 | 01-JAN-00:10 | 53391.83 | 29-JUN-16:10 |
Fans:Electricity | 240.16 | 0.00 | 03-JAN-01:40 | 13928.79 | 29-JUN-19:20 |
General:Fans:Electricity | 240.16 | 0.00 | 03-JAN-01:40 | 13928.79 | 29-JUN-19:20 |
ExteriorLights:Electricity | 121.08 | 0.00 | 01-JAN-08:20 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.08 | 0.00 | 01-JAN-08:20 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 67.46 | 1218.00 | 01-JAN-08:10 | 13837.15 | 27-JAN-12:20 |
WaterSystems:Electricity | 67.46 | 1218.00 | 01-JAN-08:10 | 13837.15 | 27-JAN-12:20 |
Water Heater:WaterSystems:Electricity | 67.46 | 1218.00 | 01-JAN-08:10 | 13837.15 | 27-JAN-12:20 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 1042.51 | 0.00 | 03-JAN-01:40 | 366484.52 | 06-JAN-09:10 |
NaturalGas:HVAC | 1042.51 | 0.00 | 03-JAN-01:40 | 366484.52 | 06-JAN-09:10 |
Heating:NaturalGas | 1042.51 | 0.00 | 03-JAN-01:40 | 366484.52 | 06-JAN-09:10 |
General:Heating:NaturalGas | 1042.51 | 0.00 | 03-JAN-01:40 | 366484.52 | 06-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1722.98 | 0.00 | 03-JAN-01:40 | 437816.31 | 06-JAN-09:10 |
EnergyTransfer:Building | 640.22 | 0.00 | 03-JAN-01:40 | 155633.87 | 09-JAN-08:10 |
EnergyTransfer:Zone:LGSTORE1 | 123.94 | 0.00 | 01-JAN-00:10 | 28077.32 | 05-JAN-09:10 |
Heating:EnergyTransfer | 345.79 | 0.00 | 03-JAN-01:40 | 155614.39 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 58.84 | 0.00 | 01-JAN-00:10 | 27797.79 | 06-JAN-09:10 |
General:Heating:EnergyTransfer | 345.79 | 0.00 | 03-JAN-01:40 | 155614.39 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 58.84 | 0.00 | 01-JAN-00:10 | 27797.79 | 06-JAN-09:10 |
Cooling:EnergyTransfer | 294.44 | 0.00 | 01-JAN-00:10 | 92381.97 | 30-JUN-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.11 | 0.00 | 01-JAN-00:10 | 20716.72 | 06-JAN-00:10 |
General:Cooling:EnergyTransfer | 294.44 | 0.00 | 01-JAN-00:10 | 92381.97 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 65.11 | 0.00 | 01-JAN-00:10 | 20716.72 | 06-JAN-00:10 |
EnergyTransfer:Zone:SMSTORE1 | 57.30 | 0.00 | 01-JAN-00:10 | 12622.27 | 24-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 19.38 | 0.00 | 01-JAN-00:10 | 12121.64 | 24-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 19.38 | 0.00 | 01-JAN-00:10 | 12121.64 | 24-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.92 | 0.00 | 01-JAN-00:10 | 12056.23 | 07-JUL-20:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.92 | 0.00 | 01-JAN-00:10 | 12056.23 | 07-JUL-20:10 |
EnergyTransfer:Zone:SMSTORE2 | 49.57 | 0.00 | 01-JAN-00:10 | 14519.57 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 22.62 | 0.00 | 01-JAN-00:10 | 14519.57 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 22.62 | 0.00 | 01-JAN-00:10 | 14519.57 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.95 | 0.00 | 01-JAN-00:10 | 8066.88 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.95 | 0.00 | 01-JAN-00:10 | 8066.88 | 30-JUN-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 50.26 | 0.00 | 01-JAN-00:10 | 14912.28 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 23.86 | 0.00 | 01-JAN-00:10 | 14892.80 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 23.86 | 0.00 | 01-JAN-00:10 | 14892.80 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 26.40 | 0.00 | 01-JAN-00:10 | 8097.28 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 26.40 | 0.00 | 01-JAN-00:10 | 8097.28 | 30-JUN-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 50.72 | 0.00 | 01-JAN-00:10 | 15271.36 | 09-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 25.93 | 0.00 | 01-JAN-00:10 | 15271.36 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 25.93 | 0.00 | 01-JAN-00:10 | 15271.36 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 24.79 | 0.00 | 01-JAN-00:10 | 7951.92 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 24.79 | 0.00 | 01-JAN-00:10 | 7951.92 | 30-JUN-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 91.22 | 0.00 | 01-JAN-00:10 | 27009.13 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 51.08 | 0.00 | 01-JAN-00:10 | 26940.65 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 51.08 | 0.00 | 01-JAN-00:10 | 26940.65 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 40.14 | 0.00 | 01-JAN-00:10 | 14534.18 | 30-JUN-14:50 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 40.14 | 0.00 | 01-JAN-00:10 | 14534.18 | 30-JUN-14:50 |
EnergyTransfer:Zone:SMSTORE5 | 48.46 | 0.00 | 01-JAN-00:10 | 14455.04 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 28.36 | 0.00 | 01-JAN-00:10 | 14455.04 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 28.36 | 0.00 | 01-JAN-00:10 | 14455.04 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.09 | 0.00 | 01-JAN-00:10 | 7564.49 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 20.09 | 0.00 | 01-JAN-00:10 | 7564.49 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 48.37 | 0.00 | 01-JAN-00:10 | 14481.52 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 28.88 | 0.00 | 01-JAN-00:10 | 14481.52 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 28.88 | 0.00 | 01-JAN-00:10 | 14481.52 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.49 | 0.00 | 01-JAN-00:10 | 7502.39 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 19.49 | 0.00 | 01-JAN-00:10 | 7502.39 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 49.76 | 0.00 | 01-JAN-00:10 | 14853.67 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 31.82 | 0.00 | 01-JAN-00:10 | 14853.67 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 31.82 | 0.00 | 01-JAN-00:10 | 14853.67 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.94 | 0.00 | 01-JAN-00:10 | 7431.68 | 30-JUN-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 17.94 | 0.00 | 01-JAN-00:10 | 7431.68 | 30-JUN-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 70.63 | 0.00 | 01-JAN-00:40 | 18950.07 | 09-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 55.02 | 0.00 | 01-JAN-00:40 | 18950.07 | 09-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 55.02 | 0.00 | 01-JAN-00:40 | 18950.07 | 09-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.61 | 0.00 | 01-JAN-00:10 | 8006.42 | 30-JUN-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 15.61 | 0.00 | 01-JAN-00:10 | 8006.42 | 30-JUN-13:00 |
EnergyTransfer:HVAC | 1082.76 | 0.00 | 03-JAN-01:40 | 293187.61 | 06-JAN-09:10 |
HeatingCoils:EnergyTransfer | 834.01 | 0.00 | 03-JAN-01:40 | 293187.61 | 06-JAN-09:10 |
CoolingCoils:EnergyTransfer | 248.75 | 0.00 | 01-JAN-00:10 | 195907.53 | 30-JUN-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 58.835 | -65.105 | 0.000 | 0.000 | 25.534 | 106.728 | 26.357 | 26.701 | 0.000 | 0.869 | 0.001 | 0.000 | -11.623 | 0.000 | -56.679 | -111.618 |
SMSTORE1 | 0.000 | 0.000 | 19.383 | -37.919 | 0.000 | 0.000 | 12.630 | 62.296 | 13.179 | 13.243 | 0.000 | 0.470 | 0.001 | 0.000 | -6.059 | 0.000 | -28.289 | -48.935 |
SMSTORE2 | 0.000 | 0.000 | 22.618 | -26.952 | 0.000 | 0.000 | 7.650 | 44.966 | 10.467 | 13.211 | 0.000 | 0.464 | 0.000 | 0.000 | -6.008 | 0.000 | -29.006 | -37.410 |
SMSTORE3 | 0.000 | 0.000 | 23.862 | -26.398 | 0.000 | 0.000 | 7.656 | 44.966 | 10.467 | 13.222 | 0.000 | 0.464 | 0.000 | 0.000 | -5.962 | 0.000 | -28.953 | -39.324 |
SMSTORE4 | 0.000 | 0.000 | 25.931 | -24.785 | 0.000 | 0.000 | 7.667 | 44.966 | 10.467 | 13.242 | 0.000 | 0.464 | 0.000 | 0.000 | -5.912 | 0.000 | -28.881 | -43.159 |
LGSTORE2 | 0.000 | 0.000 | 51.079 | -40.143 | 0.000 | 0.000 | 26.371 | 51.668 | 19.261 | 26.593 | 0.000 | 0.835 | 0.000 | 0.000 | -11.541 | 0.000 | -52.841 | -71.283 |
SMSTORE5 | 0.000 | 0.000 | 28.363 | -20.093 | 0.000 | 0.000 | 13.189 | 26.679 | 9.631 | 13.277 | 0.000 | 0.464 | 0.001 | 0.000 | -5.783 | 0.000 | -28.915 | -36.811 |
SMSTORE6 | 0.000 | 0.000 | 28.881 | -19.492 | 0.000 | 0.000 | 13.198 | 26.679 | 9.631 | 13.287 | 0.000 | 0.465 | 0.000 | 0.000 | -5.764 | 0.000 | -28.882 | -38.002 |
SMSTORE7 | 0.000 | 0.000 | 31.820 | -17.937 | 0.000 | 0.000 | 13.222 | 26.679 | 9.631 | 13.317 | 0.000 | 0.465 | 0.001 | 0.000 | -5.691 | 0.000 | -28.775 | -42.729 |
SMSTORE8 | 0.000 | 0.000 | 55.017 | -15.610 | 0.000 | 0.000 | 13.258 | 26.679 | 9.631 | 13.411 | 0.000 | 0.488 | 0.000 | 0.000 | -5.397 | 0.000 | -35.181 | -62.296 |
Total Facility | 0.000 | 0.000 | 345.791 | -294.433 | 0.000 | 0.000 | 140.376 | 462.305 | 128.721 | 159.501 | 0.000 | 5.449 | 0.005 | 0.000 | -69.742 | 0.000 | -346.400 | -531.567 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 07-JUN-08:62 | 0.00 | 0.00 | 0.00 | -43905.64 | 0.00 | 0.00 | 173.99 | 2916.31 | 749.03 | 1038.96 | 0.00 | 0.00 | 39267.04 | 0.00 | -0.00 | 0.00 | -239.69 | 0.00 |
SMSTORE1 | 21-MAY-19:12 | 0.00 | 0.00 | 0.00 | -24118.63 | 0.00 | 0.00 | 788.16 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 19501.88 | 0.00 | -66.46 | 0.00 | -13.32 | 0.00 |
SMSTORE2 | 19-MAY-07:02 | 0.00 | 0.00 | 0.00 | -24769.88 | 0.00 | 0.00 | 84.33 | 1536.36 | 374.52 | 207.67 | 0.00 | 0.00 | 22786.93 | 0.00 | -0.00 | 0.00 | -219.92 | 0.00 |
SMSTORE3 | 19-MAY-07:02 | 0.00 | 0.00 | 0.00 | -24847.52 | 0.00 | 0.00 | 84.25 | 1536.36 | 374.52 | 207.49 | 0.00 | 0.00 | 22864.98 | 0.00 | -0.00 | 0.00 | -220.08 | 0.00 |
SMSTORE4 | 19-MAY-07:02 | 0.00 | 0.00 | 0.00 | -24510.91 | 0.00 | 0.00 | 85.51 | 1536.36 | 374.52 | 209.75 | 0.00 | 0.00 | 22521.31 | 0.00 | -0.00 | 0.00 | -216.53 | 0.00 |
LGSTORE2 | 04-SEP-09:02 | 0.00 | 0.00 | 0.00 | -42952.61 | 0.00 | 0.00 | 382.49 | 1920.56 | 749.03 | 3336.93 | 0.00 | 0.00 | 37090.78 | 0.00 | -0.00 | 0.00 | -527.17 | 0.00 |
SMSTORE5 | 04-SEP-09:02 | 0.00 | 0.00 | 0.00 | -22062.39 | 0.00 | 0.00 | 192.43 | 991.67 | 374.52 | 1667.84 | 0.00 | 0.00 | 19120.35 | 0.00 | -0.00 | 0.00 | -284.42 | 0.00 |
SMSTORE6 | 04-SEP-09:02 | 0.00 | 0.00 | 0.00 | -21882.29 | 0.00 | 0.00 | 193.69 | 991.67 | 374.52 | 1669.05 | 0.00 | 0.00 | 18935.94 | 0.00 | -0.00 | 0.00 | -282.56 | 0.00 |
SMSTORE7 | 07-JUN-08:62 | 0.00 | 0.00 | 0.00 | -20569.62 | 0.00 | 0.00 | 200.14 | 991.67 | 374.52 | 522.64 | 0.00 | 0.00 | 18578.82 | 0.00 | -0.00 | 0.00 | -98.16 | 0.00 |
SMSTORE8 | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 | -23912.20 | 0.00 | 0.00 | 196.61 | 991.67 | 374.52 | 390.67 | 0.00 | 0.00 | 22190.81 | 0.00 | -0.00 | 0.00 | -232.06 | 0.00 |
Total Facility | 07-JUL-08:62 | 0.00 | 0.00 | 0.00 | -196159.88 | 0.00 | 0.00 | 1992.05 | 19263.00 | 5393.02 | 4664.87 | 0.00 | 0.00 | 167137.82 | 0.00 | 0.00 | 0.00 | -2290.88 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 24-FEB-08:61 | 0.00 | 0.00 | 70451.96 | 0.00 | 0.00 | 0.00 | 0.00 | 291.61 | 74.90 | 1191.90 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2494.51 | -69515.85 |
SMSTORE1 | 24-FEB-08:61 | 0.00 | 0.00 | 36312.14 | 0.00 | 0.00 | 0.00 | 0.00 | 170.22 | 37.45 | 564.40 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1246.91 | -35837.30 |
SMSTORE2 | 25-DEC-08:61 | 0.00 | 0.00 | 36385.90 | 0.00 | 0.00 | 0.00 | 0.00 | 153.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -657.76 | 0.00 | -1244.24 | -34674.99 |
SMSTORE3 | 25-DEC-08:61 | 0.00 | 0.00 | 36280.94 | 0.00 | 0.00 | 0.00 | 0.00 | 153.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -655.83 | 0.00 | -1252.83 | -34563.36 |
SMSTORE4 | 25-DEC-08:61 | 0.00 | 0.00 | 36319.30 | 0.00 | 0.00 | 0.00 | 0.00 | 153.64 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -654.81 | 0.00 | -1252.62 | -34602.97 |
LGSTORE2 | 24-DEC-09:01 | 0.00 | 0.00 | 68638.12 | 0.00 | 0.00 | 0.00 | 0.00 | 192.04 | 74.90 | 2794.79 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -2669.23 | -69030.62 |
SMSTORE5 | 24-DEC-09:01 | 0.00 | 0.00 | 35008.63 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 1394.11 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1459.37 | -35079.98 |
SMSTORE6 | 24-DEC-09:01 | 0.00 | 0.00 | 34883.94 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 1394.34 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1459.22 | -34955.69 |
SMSTORE7 | 13-FEB-08:61 | 0.00 | 0.00 | 35058.46 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 47.47 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1195.61 | -34046.94 |
SMSTORE8 | 24-DEC-09:01 | 0.00 | 0.00 | 39958.17 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 1410.33 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -1848.20 | -39656.91 |
Total Facility | 27-DEC-08:61 | 0.00 | 0.00 | 408397.53 | 0.00 | 0.00 | 0.00 | 814.24 | 5659.62 | 1460.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -4651.26 | 0.00 | -9501.77 | -402178.96 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0553 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0553 | 0.2002 | 1.0000 | Not calculated | 0.4115 | 0.2002 | ||
PSZ-AC_2:2 | 1.0775 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1035 | 0.1864 | 1.0000 | Not calculated | 0.2057 | 0.1864 | ||
PSZ-AC_3:3 | 1.0857 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1053 | 0.1861 | 1.0000 | Not calculated | 0.2057 | 0.1861 | ||
PSZ-AC_4:4 | 1.0791 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1088 | 0.1856 | 1.0000 | Not calculated | 0.2057 | 0.1856 | ||
PSZ-AC_5:5 | 1.0804 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.1006 | 0.1869 | 1.0000 | Not calculated | 0.2057 | 0.1869 | ||
PSZ-AC_6:6 | 1.9629 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9629 | 0.2096 | 1.0000 | Not calculated | 0.4115 | 0.2096 | ||
PSZ-AC_7:7 | 1.0121 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0155 | 0.2026 | 1.0000 | Not calculated | 0.2057 | 0.2026 | ||
PSZ-AC_8:8 | 1.0061 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0099 | 0.2037 | 1.0000 | Not calculated | 0.2057 | 0.2037 | ||
PSZ-AC_9:9 | 1.0138 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0138 | 0.2047 | 1.0000 | Not calculated | 0.2057 | 0.2029 | ||
PSZ-AC_10:10 | 1.2398 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2398 | 0.1911 | 1.0000 | Not calculated | 0.2057 | 0.1659 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.0553 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.0553 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2002 | ||
PSZ-AC_2:2 | 1.0775 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0775 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1909 | ||
PSZ-AC_3:3 | 1.0857 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0857 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1895 | ||
PSZ-AC_4:4 | 1.0791 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0791 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1907 | ||
PSZ-AC_5:5 | 1.0804 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0804 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1904 | ||
PSZ-AC_6:6 | 1.9629 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.9629 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2096 | ||
PSZ-AC_7:7 | 1.0121 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0121 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2033 | ||
PSZ-AC_8:8 | 1.0061 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0061 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2045 | ||
PSZ-AC_9:9 | 1.0138 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0138 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2029 | ||
PSZ-AC_10:10 | 1.2398 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2398 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1659 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0553 | 2.0553 | 2.0553 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0775 | 1.0775 | 1.0775 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0857 | 1.0857 | 1.0857 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0791 | 1.0791 | 1.0791 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0804 | 1.0804 | 1.0804 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9629 | 1.9629 | 1.9629 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0121 | 1.0121 | 1.0121 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0061 | 1.0061 | 1.0061 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0138 | 1.0138 | 1.0138 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2398 | 1.2398 | 1.2398 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0553 | 2.0553 | 2.0553 | 2.0553 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0775 | 1.1035 | 1.0775 | 1.0775 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0857 | 1.1053 | 1.0857 | 1.0857 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0791 | 1.1088 | 1.0791 | 1.0791 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0804 | 1.1006 | 1.0804 | 1.0804 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9629 | 1.9629 | 1.9629 | 1.9629 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0121 | 1.0155 | 1.0121 | 1.0121 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0061 | 1.0099 | 1.0061 | 1.0061 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0138 | 1.0138 | 1.0138 | 1.0138 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2398 | 1.2398 | 1.2398 | 1.2398 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.0553 | 2.0553 | 2.0553 | No | 0.4115 | 0.2032 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0775 | 1.0775 | 1.0775 | No | 0.2057 | 0.2133 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0857 | 1.0857 | 1.0857 | No | 0.2057 | 0.2118 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0791 | 1.0791 | 1.0791 | No | 0.2057 | 0.2111 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0804 | 1.0804 | 1.0804 | No | 0.2057 | 0.2096 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.9629 | 1.9629 | 1.9629 | No | 0.4115 | 0.2211 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0121 | 1.0121 | 1.0121 | No | 0.2057 | 0.2057 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0061 | 1.0061 | 1.0061 | No | 0.2057 | 0.2059 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0138 | 1.0138 | 1.0138 | No | 0.2057 | 0.2029 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2398 | 1.2398 | 1.2398 | No | 0.2057 | 0.1659 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.0553 | 2.0553 | 2.0553 | 2.0553 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0775 | 1.0775 | 1.0775 | 1.0775 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0857 | 1.0857 | 1.0857 | 1.0857 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0791 | 1.0791 | 1.0791 | 1.0791 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.0804 | 1.0804 | 1.0804 | 1.0804 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.9629 | 1.9629 | 1.9629 | 1.9629 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.0121 | 1.0121 | 1.0121 | 1.0121 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.0061 | 1.0061 | 1.0061 | 1.0061 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.0138 | 1.0138 | 1.0138 | 1.0138 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.2398 | 1.2398 | 1.2398 | 1.2398 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** International Falls Intl Ap MN USA TMY3 WMO#=727470 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.67 |
Number of hours not met | 0.67 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 1042.51 | 366484.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 66.11 | 53391.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.08 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 240.16 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 67.46 | 13837.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1085.85 |
Natural Gas | 0.00 | 1042.51 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 2128.36 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 31.63 |
Fans (All) | 114.89 |
Service Water Heating | 32.27 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 519.46 |
Subtotal | 519.46 |
Natural Gas [MJ/m2] | |
Space Heating | 498.73 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 498.73 |
Subtotal | 498.73 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 21.72 |
Space Heating | 48.98 |
Space Cooling | 3.11 |
Fans (All) | 11.28 |
Service Water Heating | 3.17 |
Receptacle Equipment | 6.05 |
Miscellaneous | 5.69 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8717.83 | 42.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8709.17 | 50.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8724.67 | 35.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8742.17 | 17.83 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8745.00 | 15.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8746.17 | 13.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8748.50 | 11.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8747.83 | 12.17 | 0.00 | 0.00 | 0.00 |
Min | 8709.17 | 0.67 | 0.00 | 0.00 | 0.00 |
Max | 8759.33 | 50.83 | 0.00 | 0.00 | 0.00 |
Average | 8740.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Sum | 87400.00 | 200.00 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25465.67 | 9.33 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25465.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25466.67 | 8.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45902.00 | 10.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45902.50 | 9.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45901.50 | 10.50 | 0.00 | 0.00 | 0.00 |
Min | 25465.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93191.00 | 20.00 | 0.00 | 0.00 | 0.00 |
Average | 48601.53 | 8.67 | 0.00 | 0.00 | 0.00 |
Sum | 486015.33 | 86.67 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8289.00 | 471.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8482.33 | 277.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8097.00 | 663.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8095.67 | 664.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8109.67 | 650.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8126.67 | 633.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8154.67 | 605.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8166.17 | 593.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8193.00 | 567.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8268.33 | 491.67 | 0.00 | 0.00 | 0.00 |
Min | 8095.67 | 277.67 | 0.00 | 0.00 | 0.00 |
Max | 8482.33 | 664.33 | 0.00 | 0.00 | 0.00 |
Average | 8198.25 | 561.75 | 0.00 | 0.00 | 0.00 |
Sum | 81982.50 | 5617.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 86484.50 | 2556.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 42972.83 | 804.17 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 24821.33 | 653.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 24815.33 | 659.67 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 24789.33 | 685.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 90221.00 | 2990.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 44438.83 | 1473.17 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 44412.50 | 1499.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 44370.50 | 1541.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 44214.17 | 1697.83 | 0.00 | 0.00 | 0.00 |
Min | 24789.33 | 653.67 | 0.00 | 0.00 | 0.00 |
Max | 90221.00 | 2990.00 | 0.00 | 0.00 | 0.00 |
Average | 47154.03 | 1456.17 | 0.00 | 0.00 | 0.00 |
Sum | 471540.33 | 14561.67 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:29
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 7
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_MN_INTERNATIONALFALLS
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | -16.89 |
February | -11.56 |
March | -6.15 |
April | 3.968 |
May | 13.433 |
June | 18.029 |
July | 19.667 |
August | 17.942 |
September | 12.293 |
October | 5.424 |
November | -2.00 |
December | -14.64 |
Annual Sum or Average | 3.363 |
Minimum of Months | -16.89 |
Maximum of Months | 19.667 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.305037E+09 | 22198.54 | 06-JAN-00:01 | -32.3 | -32.4 | 0.106186E+10 | 1275.40 | 22-JAN-18:00 | -15.6 | -16.1 |
February | 0.499398E+09 | 18300.67 | 25-FEB-00:01 | -24.1 | -24.4 | 0.958702E+09 | 1275.40 | 19-FEB-18:00 | -24.1 | -24.4 |
March | 0.981677E+09 | 15334.16 | 03-MAR-00:01 | -17.7 | -17.9 | 0.105402E+10 | 1366.67 | 26-MAR-17:30 | 9.45 | 4.66 |
April | 0.313180E+10 | 12845.64 | 05-APR-08:04 | -8.5 | -10.3 | 0.110366E+10 | 1685.89 | 23-APR-12:30 | 21.70 | 14.81 |
May | 0.806157E+10 | 39626.05 | 27-MAY-08:62 | 19.02 | 13.47 | 0.134496E+10 | 1685.90 | 28-MAY-12:00 | 21.30 | 13.54 |
June | 0.107244E+11 | 43917.28 | 07-JUN-08:62 | 20.18 | 11.27 | 0.134918E+10 | 1685.85 | 23-JUN-12:39 | 22.03 | 19.65 |
July | 0.139005E+11 | 41608.81 | 17-JUL-08:62 | 15.00 | 12.42 | 0.141291E+10 | 1685.94 | 01-JUL-12:20 | 15.00 | 12.42 |
August | 0.126927E+11 | 40832.03 | 05-AUG-08:62 | 16.88 | 12.86 | 0.139253E+10 | 1686.01 | 20-AUG-12:00 | 25.00 | 15.37 |
September | 0.861599E+10 | 41457.78 | 02-SEP-08:62 | 15.37 | 12.66 | 0.131339E+10 | 1685.99 | 02-SEP-12:50 | 19.90 | 14.39 |
October | 0.464660E+10 | 11376.45 | 30-OCT-08:04 | -6.1 | -6.7 | 0.115014E+10 | 1685.87 | 22-OCT-16:10 | -6.1 | -6.7 |
November | 0.112360E+10 | 13974.59 | 25-NOV-00:02 | -15.0 | -15.4 | 0.103422E+10 | 1335.67 | 01-NOV-17:40 | -15.0 | -15.4 |
December | 0.422244E+09 | 18031.80 | 02-DEC-00:01 | -23.5 | -23.8 | 0.106733E+10 | 1275.40 | 31-DEC-18:00 | -5.6 | -5.9 |
Annual Sum or Average | 0.651055E+11 | 0.142429E+11 | ||||||||
Minimum of Months | 0.305037E+09 | 11376.45 | -32.3 | -32.4 | 0.958702E+09 | 1275.40 | -24.1 | -24.4 | ||
Maximum of Months | 0.139005E+11 | 43917.28 | 20.18 | 13.47 | 0.141291E+10 | 1686.01 | 25.00 | 19.65 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 42984717.18 | 8494.84 | 21-JAN-09:04 | -21.0 | -21.2 | 0.533535E+09 | 688.51 | 29-JAN-18:00 | -3.3 | -4.1 |
February | 0.203924E+09 | 8981.36 | 10-FEB-09:04 | -20.3 | -20.7 | 0.485628E+09 | 739.86 | 20-FEB-18:00 | 4.40 | 1.28 |
March | 0.560566E+09 | 8352.42 | 06-MAR-09:04 | -17.5 | -18.0 | 0.541834E+09 | 837.08 | 26-MAR-17:00 | 8.90 | 4.40 |
April | 0.181598E+10 | 20368.21 | 23-APR-20:50 | 19.78 | 13.46 | 0.585611E+09 | 842.97 | 23-APR-16:10 | 19.78 | 13.46 |
May | 0.495034E+10 | 24119.30 | 21-MAY-19:12 | 17.97 | 9.63 | 0.686097E+09 | 842.93 | 28-MAY-12:00 | 21.30 | 13.54 |
June | 0.651355E+10 | 23588.45 | 07-JUN-08:62 | 20.18 | 11.27 | 0.675369E+09 | 842.90 | 25-JUN-17:40 | 25.60 | 20.85 |
July | 0.803378E+10 | 22662.48 | 17-JUL-08:62 | 15.00 | 12.42 | 0.703090E+09 | 842.95 | 04-JUL-12:09 | 15.00 | 12.42 |
August | 0.740333E+10 | 22741.65 | 02-AUG-08:62 | 13.58 | 11.91 | 0.693613E+09 | 842.99 | 20-AUG-12:39 | 24.80 | 15.76 |
September | 0.507161E+10 | 22437.30 | 02-SEP-08:62 | 15.37 | 12.66 | 0.670364E+09 | 842.97 | 02-SEP-12:30 | 19.70 | 14.40 |
October | 0.257444E+10 | 6313.84 | 23-OCT-08:63 | 5.68 | 4.09 | 0.611332E+09 | 842.92 | 22-OCT-12:00 | 5.68 | 4.09 |
November | 0.688087E+09 | 8363.13 | 25-NOV-09:04 | -17.6 | -18.0 | 0.535076E+09 | 761.25 | 19-NOV-18:00 | -17.6 | -18.0 |
December | 60272467.72 | 9272.89 | 01-DEC-09:04 | -21.5 | -21.7 | 0.536649E+09 | 681.59 | 31-DEC-18:00 | -5.6 | -5.9 |
Annual Sum or Average | 0.379189E+11 | 0.725820E+10 | ||||||||
Minimum of Months | 42984717.18 | 6313.84 | -21.5 | -21.7 | 0.485628E+09 | 681.59 | -17.6 | -18.0 | ||
Maximum of Months | 0.803378E+10 | 24119.30 | 20.18 | 13.46 | 0.703090E+09 | 842.99 | 25.60 | 20.85 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 11802195.50 | 7865.55 | 31-JAN-08:04 | -15.6 | -16.0 | 0.316913E+09 | 637.68 | 14-JAN-13:09 | -15.6 | -16.0 |
February | 82227244.52 | 7735.76 | 11-FEB-08:04 | -15.5 | -15.9 | 0.287883E+09 | 637.68 | 04-FEB-13:39 | -15.5 | -15.9 |
March | 0.322403E+09 | 8861.09 | 18-MAR-07:04 | -20.6 | -20.8 | 0.325721E+09 | 637.68 | 18-MAR-12:20 | -2.9 | -6.4 |
April | 0.136230E+10 | 5129.31 | 07-APR-07:02 | -3.4 | -5.4 | 0.338157E+09 | 842.89 | 22-APR-12:00 | 16.10 | 6.66 |
May | 0.343976E+10 | 24774.43 | 19-MAY-07:02 | 14.87 | 10.69 | 0.411745E+09 | 842.92 | 27-MAY-12:00 | 21.90 | 13.70 |
June | 0.465598E+10 | 23708.19 | 07-JUN-07:02 | 19.50 | 11.27 | 0.416506E+09 | 842.90 | 24-JUN-12:09 | 24.60 | 21.36 |
July | 0.574304E+10 | 23724.94 | 08-JUL-07:02 | 13.40 | 11.20 | 0.420308E+09 | 842.93 | 01-JUL-12:30 | 13.40 | 11.20 |
August | 0.537274E+10 | 23755.69 | 02-AUG-07:02 | 12.88 | 11.28 | 0.431193E+09 | 842.97 | 19-AUG-12:50 | 21.42 | 14.73 |
September | 0.359271E+10 | 24152.98 | 08-SEP-07:02 | 11.28 | 10.32 | 0.398251E+09 | 842.97 | 02-SEP-12:30 | 11.28 | 10.32 |
October | 0.190953E+10 | 7478.22 | 22-OCT-08:63 | 11.97 | 10.31 | 0.347118E+09 | 842.90 | 21-OCT-12:00 | 11.97 | 10.31 |
November | 0.443323E+09 | 7919.43 | 29-NOV-08:04 | -15.8 | -16.1 | 0.309230E+09 | 693.28 | 01-NOV-17:40 | -15.8 | -16.1 |
December | 16475967.90 | 9069.33 | 01-DEC-08:03 | -21.0 | -21.2 | 0.316542E+09 | 637.68 | 02-DEC-13:50 | -18.3 | -19.0 |
Annual Sum or Average | 0.269523E+11 | 0.431957E+10 | ||||||||
Minimum of Months | 11802195.50 | 5129.31 | -21.0 | -21.2 | 0.287883E+09 | 637.68 | -18.3 | -19.0 | ||
Maximum of Months | 0.574304E+10 | 24774.43 | 19.50 | 11.28 | 0.431193E+09 | 842.97 | 24.60 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8418854.36 | 7567.90 | 31-JAN-08:04 | -15.6 | -16.0 | 0.316911E+09 | 637.68 | 07-JAN-13:00 | -15.6 | -16.0 |
February | 66268541.61 | 7828.61 | 11-FEB-08:04 | -15.5 | -15.9 | 0.287874E+09 | 637.68 | 04-FEB-13:50 | -15.5 | -15.9 |
March | 0.278045E+09 | 8942.49 | 18-MAR-07:04 | -20.6 | -20.8 | 0.325632E+09 | 637.68 | 04-MAR-13:09 | -20.6 | -20.8 |
April | 0.125064E+10 | 5192.86 | 02-APR-08:04 | -5.5 | -6.6 | 0.336721E+09 | 842.89 | 22-APR-12:00 | 16.10 | 6.66 |
May | 0.335061E+10 | 24852.09 | 19-MAY-07:02 | 14.87 | 10.69 | 0.410555E+09 | 842.92 | 27-MAY-12:00 | 21.90 | 13.70 |
June | 0.461675E+10 | 23764.99 | 09-JUN-07:02 | 11.60 | 10.97 | 0.416424E+09 | 842.90 | 24-JUN-12:09 | 24.60 | 21.36 |
July | 0.576860E+10 | 23802.85 | 08-JUL-07:02 | 13.40 | 11.20 | 0.420311E+09 | 842.94 | 01-JUL-12:30 | 13.40 | 11.20 |
August | 0.537238E+10 | 23823.88 | 02-AUG-07:02 | 12.88 | 11.28 | 0.431170E+09 | 842.97 | 19-AUG-12:50 | 21.42 | 14.73 |
September | 0.352910E+10 | 24223.29 | 08-SEP-07:02 | 11.28 | 10.32 | 0.397189E+09 | 842.97 | 02-SEP-12:30 | 11.28 | 10.32 |
October | 0.176263E+10 | 6348.22 | 23-OCT-07:03 | 5.60 | 4.05 | 0.345540E+09 | 842.90 | 21-OCT-12:00 | 5.60 | 4.05 |
November | 0.381872E+09 | 7418.17 | 29-NOV-08:04 | -15.8 | -16.1 | 0.308942E+09 | 684.85 | 01-NOV-17:40 | -15.8 | -16.1 |
December | 13151421.42 | 7607.38 | 23-DEC-08:04 | -14.7 | -15.2 | 0.316536E+09 | 637.68 | 02-DEC-13:09 | -14.7 | -15.2 |
Annual Sum or Average | 0.263985E+11 | 0.431380E+10 | ||||||||
Minimum of Months | 8418854.36 | 5192.86 | -20.6 | -20.8 | 0.287874E+09 | 637.68 | -20.6 | -20.8 | ||
Maximum of Months | 0.576860E+10 | 24852.09 | 14.87 | 11.28 | 0.431170E+09 | 842.97 | 24.60 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 6700263.64 | 7195.75 | 18-JAN-08:04 | -13.8 | -14.0 | 0.316909E+09 | 637.68 | 07-JAN-13:20 | -13.8 | -14.0 |
February | 43839148.29 | 7831.93 | 11-FEB-08:04 | -15.5 | -15.9 | 0.287868E+09 | 637.68 | 04-FEB-13:09 | -15.5 | -15.9 |
March | 0.213658E+09 | 8484.98 | 18-MAR-07:04 | -20.6 | -20.8 | 0.325538E+09 | 637.68 | 11-MAR-13:00 | -20.6 | -20.8 |
April | 0.107277E+10 | 5999.15 | 05-APR-07:04 | -11.2 | -12.1 | 0.334544E+09 | 842.80 | 22-APR-12:00 | 16.10 | 6.66 |
May | 0.312488E+10 | 24515.43 | 19-MAY-07:02 | 14.87 | 10.69 | 0.407986E+09 | 842.92 | 27-MAY-12:00 | 21.90 | 13.70 |
June | 0.438656E+10 | 23407.20 | 07-JUN-07:02 | 19.50 | 11.27 | 0.416005E+09 | 842.90 | 24-JUN-12:09 | 24.60 | 21.36 |
July | 0.557407E+10 | 23283.92 | 08-JUL-07:02 | 13.40 | 11.20 | 0.420240E+09 | 842.93 | 01-JUL-12:30 | 13.40 | 11.20 |
August | 0.516579E+10 | 23525.63 | 02-AUG-07:02 | 12.88 | 11.28 | 0.430991E+09 | 842.97 | 19-AUG-12:50 | 21.42 | 14.73 |
September | 0.333905E+10 | 23822.82 | 08-SEP-07:02 | 11.28 | 10.32 | 0.394708E+09 | 842.97 | 02-SEP-12:39 | 11.28 | 10.32 |
October | 0.156429E+10 | 4316.20 | 25-OCT-07:03 | -3.2 | -3.4 | 0.343020E+09 | 842.90 | 21-OCT-12:00 | -3.2 | -3.4 |
November | 0.285029E+09 | 6654.54 | 24-NOV-08:04 | -10.0 | -10.7 | 0.308517E+09 | 670.90 | 01-NOV-17:40 | -10.0 | -10.7 |
December | 8740336.07 | 7274.60 | 15-DEC-08:04 | -13.1 | -13.6 | 0.316530E+09 | 637.68 | 02-DEC-13:39 | -13.1 | -13.6 |
Annual Sum or Average | 0.247854E+11 | 0.430286E+10 | ||||||||
Minimum of Months | 6700263.64 | 4316.20 | -20.6 | -20.8 | 0.287868E+09 | 637.68 | -20.6 | -20.8 | ||
Maximum of Months | 0.557407E+10 | 24515.43 | 19.50 | 11.28 | 0.430991E+09 | 842.97 | 24.60 | 21.36 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8602099.17 | 12786.76 | 20-JAN-09:04 | -8.3 | -8.9 | 0.108321E+10 | 1700.53 | 14-JAN-15:09 | -8.3 | -8.9 |
February | 32727402.09 | 13372.81 | 28-FEB-09:04 | -9.9 | -10.9 | 0.986222E+09 | 1700.53 | 04-FEB-15:09 | -9.9 | -10.9 |
March | 0.212315E+09 | 14073.13 | 23-MAR-08:04 | -13.2 | -13.3 | 0.111728E+10 | 1700.53 | 04-MAR-15:09 | -13.2 | -13.3 |
April | 0.155351E+10 | 12927.67 | 05-APR-08:04 | -8.5 | -10.3 | 0.113448E+10 | 2247.77 | 22-APR-14:20 | 17.97 | 7.60 |
May | 0.505197E+10 | 42090.80 | 19-MAY-08:62 | 15.27 | 11.36 | 0.137852E+10 | 2247.89 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.724533E+10 | 42223.63 | 07-JUN-08:62 | 20.18 | 11.27 | 0.142192E+10 | 2247.80 | 24-JUN-14:09 | 27.88 | 23.16 |
July | 0.937026E+10 | 40351.22 | 17-JUL-08:62 | 15.00 | 12.42 | 0.143812E+10 | 2247.80 | 01-JUL-14:09 | 15.00 | 12.42 |
August | 0.861322E+10 | 40643.63 | 02-AUG-08:62 | 13.58 | 11.91 | 0.147662E+10 | 2248.00 | 05-AUG-14:09 | 22.20 | 14.57 |
September | 0.545028E+10 | 42968.84 | 04-SEP-09:02 | 13.48 | 10.43 | 0.133618E+10 | 2247.85 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.231353E+10 | 11825.96 | 30-OCT-08:04 | -6.1 | -6.7 | 0.115686E+10 | 2247.80 | 21-OCT-14:00 | -6.1 | -6.7 |
November | 0.277004E+09 | 13644.79 | 23-NOV-10:04 | -10.0 | -10.6 | 0.104911E+10 | 1823.85 | 01-NOV-16:30 | -10.0 | -10.6 |
December | 14081042.77 | 12588.08 | 07-DEC-09:04 | -7.8 | -7.9 | 0.108504E+10 | 1700.53 | 02-DEC-15:50 | -7.8 | -7.9 |
Annual Sum or Average | 0.401428E+11 | 0.146636E+11 | ||||||||
Minimum of Months | 8602099.17 | 11825.96 | -13.2 | -13.3 | 0.986222E+09 | 1700.53 | -13.2 | -13.3 | ||
Maximum of Months | 0.937026E+10 | 42968.84 | 20.18 | 12.42 | 0.147662E+10 | 2248.00 | 27.88 | 23.16 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3582638.87 | 6307.56 | 20-JAN-09:04 | -8.3 | -8.9 | 0.541588E+09 | 850.24 | 07-JAN-15:30 | -8.3 | -8.9 |
February | 13107688.48 | 6614.79 | 28-FEB-09:04 | -9.9 | -10.9 | 0.493096E+09 | 850.24 | 18-FEB-15:20 | -9.9 | -10.9 |
March | 94940728.13 | 7256.02 | 23-MAR-08:04 | -13.2 | -13.3 | 0.558619E+09 | 850.24 | 04-MAR-15:09 | -13.2 | -13.3 |
April | 0.701236E+09 | 6388.56 | 05-APR-08:04 | -8.5 | -10.3 | 0.566389E+09 | 1123.85 | 22-APR-14:39 | 18.13 | 7.71 |
May | 0.248092E+10 | 20584.56 | 19-MAY-08:62 | 15.27 | 11.36 | 0.688074E+09 | 1123.91 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.367216E+10 | 21622.24 | 07-JUN-08:62 | 20.18 | 11.27 | 0.710535E+09 | 1123.87 | 24-JUN-14:09 | 27.88 | 23.16 |
July | 0.480645E+10 | 20705.28 | 17-JUL-08:62 | 15.00 | 12.42 | 0.718976E+09 | 1123.87 | 01-JUL-14:09 | 15.00 | 12.42 |
August | 0.439916E+10 | 20847.34 | 02-AUG-08:62 | 13.58 | 11.91 | 0.738278E+09 | 1123.96 | 05-AUG-14:09 | 22.20 | 14.57 |
September | 0.269402E+10 | 22070.92 | 04-SEP-09:02 | 13.48 | 10.43 | 0.667320E+09 | 1123.89 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.109728E+10 | 5866.78 | 30-OCT-08:04 | -6.1 | -6.7 | 0.577975E+09 | 1123.87 | 21-OCT-14:00 | -6.1 | -6.7 |
November | 0.124100E+09 | 6751.99 | 23-NOV-10:04 | -10.0 | -10.6 | 0.524394E+09 | 907.01 | 01-NOV-16:30 | -10.0 | -10.6 |
December | 6098790.66 | 6217.39 | 07-DEC-09:04 | -7.8 | -7.9 | 0.542506E+09 | 850.24 | 02-DEC-15:09 | -7.8 | -7.9 |
Annual Sum or Average | 0.200931E+11 | 0.732775E+10 | ||||||||
Minimum of Months | 3582638.87 | 5866.78 | -13.2 | -13.3 | 0.493096E+09 | 850.24 | -13.2 | -13.3 | ||
Maximum of Months | 0.480645E+10 | 22070.92 | 20.18 | 12.42 | 0.738278E+09 | 1123.96 | 27.88 | 23.16 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 3300627.60 | 6305.99 | 20-JAN-09:04 | -8.3 | -8.9 | 0.541588E+09 | 850.24 | 14-JAN-15:09 | -8.3 | -8.9 |
February | 11624901.17 | 6600.27 | 28-FEB-09:04 | -9.9 | -10.9 | 0.493095E+09 | 850.24 | 04-FEB-15:30 | -9.9 | -10.9 |
March | 83780178.41 | 6733.10 | 17-MAR-08:04 | -10.4 | -11.2 | 0.558611E+09 | 850.24 | 04-MAR-15:30 | -10.4 | -11.2 |
April | 0.645527E+09 | 6372.59 | 05-APR-08:04 | -8.5 | -10.3 | 0.564936E+09 | 1123.85 | 22-APR-14:50 | 18.22 | 7.76 |
May | 0.237897E+10 | 19783.57 | 28-MAY-09:02 | 17.98 | 13.33 | 0.685477E+09 | 1123.91 | 27-MAY-14:00 | 17.98 | 13.33 |
June | 0.356945E+10 | 21419.92 | 07-JUN-08:62 | 20.18 | 11.27 | 0.709629E+09 | 1123.87 | 24-JUN-14:09 | 27.88 | 23.16 |
July | 0.472214E+10 | 20532.39 | 17-JUL-08:62 | 15.00 | 12.42 | 0.718821E+09 | 1123.87 | 01-JUL-14:09 | 15.00 | 12.42 |
August | 0.431279E+10 | 20684.86 | 02-AUG-08:62 | 13.58 | 11.91 | 0.738063E+09 | 1123.96 | 05-AUG-14:09 | 22.20 | 14.57 |
September | 0.261392E+10 | 21890.74 | 04-SEP-09:02 | 13.48 | 10.43 | 0.664997E+09 | 1123.89 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.103378E+10 | 5934.27 | 30-OCT-08:04 | -6.1 | -6.7 | 0.576443E+09 | 1123.87 | 21-OCT-14:00 | -6.1 | -6.7 |
November | 0.111361E+09 | 6724.79 | 23-NOV-10:04 | -10.0 | -10.6 | 0.524240E+09 | 900.78 | 01-NOV-16:30 | -10.0 | -10.6 |
December | 5238833.45 | 6204.79 | 07-DEC-09:04 | -7.8 | -7.9 | 0.542506E+09 | 850.24 | 02-DEC-15:09 | -7.8 | -7.9 |
Annual Sum or Average | 0.194919E+11 | 0.731841E+10 | ||||||||
Minimum of Months | 3300627.60 | 5934.27 | -10.4 | -11.2 | 0.493095E+09 | 850.24 | -10.4 | -11.2 | ||
Maximum of Months | 0.472214E+10 | 21890.74 | 20.18 | 13.33 | 0.738063E+09 | 1123.96 | 27.88 | 23.16 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2602586.76 | 6237.62 | 20-JAN-09:04 | -8.3 | -8.9 | 0.541588E+09 | 850.24 | 07-JAN-15:09 | -8.3 | -8.9 |
February | 8958893.48 | 6206.82 | 23-FEB-09:04 | -7.7 | -8.7 | 0.493094E+09 | 850.24 | 04-FEB-15:30 | -7.7 | -8.7 |
March | 51155563.14 | 6503.25 | 11-MAR-09:04 | -9.4 | -9.9 | 0.558587E+09 | 850.24 | 04-MAR-15:50 | -9.4 | -9.9 |
April | 0.485211E+09 | 6304.80 | 05-APR-08:04 | -8.5 | -10.3 | 0.561284E+09 | 1123.86 | 22-APR-14:00 | 18.30 | 7.82 |
May | 0.210949E+10 | 19119.18 | 27-MAY-08:62 | 19.02 | 13.47 | 0.678425E+09 | 1123.91 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.331881E+10 | 20575.32 | 07-JUN-08:62 | 20.18 | 11.27 | 0.707314E+09 | 1123.87 | 24-JUN-14:09 | 27.88 | 23.16 |
July | 0.453767E+10 | 20360.13 | 17-JUL-08:62 | 15.00 | 12.42 | 0.718265E+09 | 1123.87 | 01-JUL-14:09 | 15.00 | 12.42 |
August | 0.410407E+10 | 20072.63 | 27-AUG-09:02 | 14.87 | 12.75 | 0.737263E+09 | 1123.96 | 05-AUG-14:09 | 14.87 | 12.75 |
September | 0.238850E+10 | 19902.34 | 02-SEP-08:62 | 15.37 | 12.66 | 0.659739E+09 | 1123.89 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.860042E+09 | 5853.76 | 30-OCT-08:04 | -6.1 | -6.7 | 0.572956E+09 | 1123.87 | 21-OCT-14:00 | -6.1 | -6.7 |
November | 67150447.28 | 6654.86 | 23-NOV-10:04 | -10.0 | -10.6 | 0.523742E+09 | 882.49 | 01-NOV-16:30 | -10.0 | -10.6 |
December | 3923446.46 | 6164.40 | 07-DEC-09:04 | -7.8 | -7.9 | 0.542506E+09 | 850.24 | 02-DEC-15:09 | -7.8 | -7.9 |
Annual Sum or Average | 0.179376E+11 | 0.729476E+10 | ||||||||
Minimum of Months | 2602586.76 | 5853.76 | -10.0 | -10.6 | 0.493094E+09 | 850.24 | -10.0 | -10.6 | ||
Maximum of Months | 0.453767E+10 | 20575.32 | 20.18 | 13.47 | 0.737263E+09 | 1123.96 | 27.88 | 23.16 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 2524798.81 | 5972.88 | 20-JAN-09:04 | -8.3 | -8.9 | 0.541587E+09 | 850.24 | 21-JAN-15:30 | -5.0 | -7.1 |
February | 4745222.50 | 6304.67 | 28-FEB-09:04 | -9.9 | -10.9 | 0.493094E+09 | 850.24 | 11-FEB-15:20 | -9.9 | -10.9 |
March | 9500407.72 | 6436.13 | 17-MAR-08:04 | -10.4 | -11.2 | 0.558576E+09 | 850.24 | 04-MAR-15:30 | -10.4 | -11.2 |
April | 0.166324E+09 | 6065.39 | 05-APR-08:04 | -8.5 | -10.3 | 0.556679E+09 | 1117.10 | 22-APR-14:00 | 18.30 | 7.82 |
May | 0.155430E+10 | 19281.38 | 26-MAY-08:61 | 20.60 | 16.95 | 0.667190E+09 | 1123.90 | 27-MAY-14:00 | 22.20 | 14.09 |
June | 0.305881E+10 | 23130.42 | 18-JUN-09:02 | 21.97 | 14.91 | 0.703016E+09 | 1123.87 | 24-JUN-14:09 | 27.88 | 23.16 |
July | 0.455296E+10 | 23918.69 | 07-JUL-08:62 | 17.38 | 13.04 | 0.716489E+09 | 1123.87 | 15-JUL-14:09 | 31.10 | 25.55 |
August | 0.389556E+10 | 23527.62 | 06-AUG-09:02 | 18.40 | 13.94 | 0.735013E+09 | 1123.96 | 05-AUG-14:09 | 18.40 | 13.94 |
September | 0.188636E+10 | 18381.65 | 01-SEP-08:62 | 18.17 | 16.90 | 0.652262E+09 | 1123.87 | 30-SEP-14:00 | 21.10 | 13.68 |
October | 0.458740E+09 | 5537.31 | 30-OCT-08:04 | -6.1 | -6.7 | 0.569295E+09 | 1123.84 | 21-OCT-14:09 | -6.1 | -6.7 |
November | 16677442.28 | 6385.33 | 23-NOV-10:04 | -10.0 | -10.6 | 0.523102E+09 | 860.02 | 01-NOV-16:40 | -10.0 | -10.6 |
December | 3340754.10 | 5907.30 | 07-DEC-09:04 | -7.8 | -7.9 | 0.542506E+09 | 850.24 | 02-DEC-15:09 | -7.8 | -7.9 |
Annual Sum or Average | 0.156098E+11 | 0.725881E+10 | ||||||||
Minimum of Months | 2524798.81 | 5537.31 | -10.4 | -11.2 | 0.493094E+09 | 850.24 | -10.4 | -11.2 | ||
Maximum of Months | 0.455296E+10 | 23918.69 | 21.97 | 16.95 | 0.735013E+09 | 1123.96 | 31.10 | 25.55 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169849E+11 | 70447.57 | 06-JAN-08:61 | -35.1 |
February | 0.101980E+11 | 70451.97 | 24-FEB-08:61 | -23.7 |
March | 0.752048E+10 | 70232.16 | 07-MAR-08:61 | -19.0 |
April | 0.192059E+10 | 69394.90 | 04-APR-07:01 | -8.2 |
May | 0.221388E+09 | 61624.11 | 01-MAY-08:61 | 1.73 |
June | 0.191713E+09 | 3088.61 | 25-JUN-07:05 | 22.98 |
July | 0.184624E+09 | 3037.23 | 30-JUL-07:05 | 21.65 |
August | 0.186354E+09 | 2409.83 | 27-AUG-07:07 | 12.88 |
September | 0.186682E+09 | 2198.63 | 27-SEP-07:25 | 6.70 |
October | 0.899251E+09 | 60767.04 | 06-OCT-08:61 | -0.0 |
November | 0.474960E+10 | 69872.49 | 25-NOV-08:61 | -18.2 |
December | 0.155915E+11 | 70440.72 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.588350E+11 | |||
Minimum of Months | 0.184624E+09 | 2198.63 | -35.1 | |
Maximum of Months | 0.169849E+11 | 70451.97 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.594356E+10 | 36230.47 | 06-JAN-08:61 | -35.1 |
February | 0.322077E+10 | 36312.19 | 24-FEB-08:61 | -23.7 |
March | 0.221674E+10 | 36176.87 | 15-MAR-07:01 | -23.7 |
April | 0.428857E+09 | 31221.80 | 07-APR-08:61 | -0.2 |
May | 0.112151E+09 | 1639.42 | 01-MAY-08:02 | 1.73 |
June | 0.104199E+09 | 1785.90 | 25-JUN-07:05 | 22.98 |
July | 0.103014E+09 | 1750.15 | 30-JUL-07:05 | 21.65 |
August | 0.106711E+09 | 1573.26 | 27-AUG-07:07 | 12.88 |
September | 0.102116E+09 | 1522.23 | 03-SEP-07:07 | 14.50 |
October | 0.216634E+09 | 22832.95 | 30-OCT-08:61 | -6.1 |
November | 0.137897E+10 | 30186.14 | 13-NOV-09:01 | -5.7 |
December | 0.544983E+10 | 36215.22 | 21-DEC-08:61 | -28.4 |
Annual Sum or Average | 0.193836E+11 | |||
Minimum of Months | 0.102116E+09 | 1522.23 | -35.1 | |
Maximum of Months | 0.594356E+10 | 36312.19 | 22.98 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.666751E+10 | 36369.68 | 01-JAN-08:61 | -26.7 |
February | 0.378954E+10 | 36362.01 | 19-FEB-08:61 | -23.5 |
March | 0.264753E+10 | 36311.70 | 06-MAR-07:01 | -19.3 |
April | 0.588309E+09 | 31618.32 | 10-APR-07:01 | -0.2 |
May | 0.125864E+09 | 8136.60 | 01-MAY-07:02 | -0.9 |
June | 0.134120E+09 | 2371.76 | 29-JUN-19:12 | 30.37 |
July | 0.152632E+09 | 2113.62 | 29-JUL-17:02 | 29.72 |
August | 0.125071E+09 | 1338.19 | 08-AUG-19:03 | 26.42 |
September | 0.109405E+09 | 1136.93 | 27-SEP-07:00 | 6.70 |
October | 0.314460E+09 | 29618.47 | 30-OCT-07:01 | -9.0 |
November | 0.183415E+10 | 31345.15 | 30-NOV-08:61 | -1.1 |
December | 0.612936E+10 | 36385.91 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.226180E+11 | |||
Minimum of Months | 0.109405E+09 | 1136.93 | -27.8 | |
Maximum of Months | 0.666751E+10 | 36385.91 | 30.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.696112E+10 | 36233.25 | 01-JAN-08:61 | -26.7 |
February | 0.399646E+10 | 36223.38 | 19-FEB-08:61 | -23.5 |
March | 0.282295E+10 | 36173.81 | 06-MAR-07:01 | -19.3 |
April | 0.658215E+09 | 31975.05 | 09-APR-08:61 | 1.70 |
May | 0.129361E+09 | 14686.69 | 01-MAY-07:02 | -0.9 |
June | 0.133798E+09 | 2376.21 | 29-JUN-19:12 | 30.37 |
July | 0.151583E+09 | 2115.81 | 29-JUL-17:02 | 29.72 |
August | 0.125282E+09 | 1341.62 | 08-AUG-19:03 | 26.42 |
September | 0.109662E+09 | 1138.17 | 27-SEP-07:00 | 6.70 |
October | 0.369448E+09 | 29558.44 | 30-OCT-07:01 | -9.0 |
November | 0.201164E+10 | 32430.63 | 25-NOV-07:02 | -19.2 |
December | 0.639263E+10 | 36280.94 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.238622E+11 | |||
Minimum of Months | 0.109662E+09 | 1138.17 | -27.8 | |
Maximum of Months | 0.696112E+10 | 36280.94 | 30.37 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.741000E+10 | 36294.27 | 08-JAN-08:61 | -22.9 |
February | 0.435937E+10 | 36252.25 | 19-FEB-08:61 | -23.5 |
March | 0.315869E+10 | 36203.56 | 06-MAR-07:01 | -19.3 |
April | 0.781102E+09 | 32073.97 | 09-APR-08:61 | 1.70 |
May | 0.134560E+09 | 20657.48 | 01-MAY-07:02 | -0.9 |
June | 0.135273E+09 | 2375.80 | 29-JUN-19:12 | 30.37 |
July | 0.153152E+09 | 2119.96 | 29-JUL-17:02 | 29.72 |
August | 0.125270E+09 | 1346.97 | 08-AUG-19:03 | 26.42 |
September | 0.109206E+09 | 1133.19 | 27-SEP-07:00 | 6.70 |
October | 0.459217E+09 | 29654.38 | 30-OCT-07:01 | -9.0 |
November | 0.228205E+10 | 35545.77 | 26-NOV-08:62 | -9.3 |
December | 0.682298E+10 | 36319.31 | 25-DEC-08:61 | -27.8 |
Annual Sum or Average | 0.259309E+11 | |||
Minimum of Months | 0.109206E+09 | 1133.19 | -27.8 | |
Maximum of Months | 0.741000E+10 | 36319.31 | 30.37 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.145954E+11 | 68428.86 | 13-JAN-08:61 | -31.5 |
February | 0.857860E+10 | 68572.35 | 19-FEB-09:01 | -21.4 |
March | 0.625855E+10 | 68303.82 | 06-MAR-08:61 | -18.7 |
April | 0.154339E+10 | 63737.02 | 04-APR-07:01 | -8.2 |
May | 0.230618E+09 | 59787.44 | 01-MAY-08:61 | 1.73 |
June | 0.220657E+09 | 3887.42 | 24-JUN-17:12 | 29.03 |
July | 0.253950E+09 | 4119.63 | 29-JUL-17:02 | 29.72 |
August | 0.213634E+09 | 2165.28 | 26-AUG-17:03 | 25.63 |
September | 0.198922E+09 | 2089.03 | 27-SEP-07:25 | 6.70 |
October | 0.966670E+09 | 58766.29 | 13-OCT-08:61 | 0.00 |
November | 0.456604E+10 | 68179.30 | 26-NOV-09:01 | -8.8 |
December | 0.134526E+11 | 68638.13 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.510790E+11 | |||
Minimum of Months | 0.198922E+09 | 2089.03 | -31.5 | |
Maximum of Months | 0.145954E+11 | 68638.13 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.794170E+10 | 34910.82 | 04-JAN-08:61 | -29.4 |
February | 0.476842E+10 | 34944.36 | 13-FEB-08:61 | -24.4 |
March | 0.355262E+10 | 34829.51 | 07-MAR-08:61 | -19.0 |
April | 0.925676E+09 | 31661.22 | 11-APR-08:61 | 6.33 |
May | 0.128934E+09 | 30595.26 | 01-MAY-08:61 | 1.73 |
June | 0.120912E+09 | 2014.24 | 24-JUN-17:12 | 29.03 |
July | 0.138266E+09 | 2109.85 | 29-JUL-17:02 | 29.72 |
August | 0.117087E+09 | 1132.45 | 26-AUG-17:03 | 25.63 |
September | 0.107730E+09 | 1120.66 | 27-SEP-07:25 | 6.70 |
October | 0.598768E+09 | 30459.87 | 15-OCT-09:01 | 2.38 |
November | 0.261602E+10 | 34769.27 | 26-NOV-09:01 | -8.8 |
December | 0.734687E+10 | 35008.64 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.283630E+11 | |||
Minimum of Months | 0.107730E+09 | 1120.66 | -30.9 | |
Maximum of Months | 0.794170E+10 | 35008.64 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.801421E+10 | 34784.75 | 06-JAN-08:61 | -35.1 |
February | 0.485019E+10 | 34850.94 | 19-FEB-09:01 | -21.4 |
March | 0.364905E+10 | 34710.49 | 06-MAR-08:61 | -18.7 |
April | 0.988498E+09 | 34484.12 | 02-APR-08:61 | -5.5 |
May | 0.131576E+09 | 30508.49 | 01-MAY-08:61 | 1.73 |
June | 0.120880E+09 | 2011.02 | 24-JUN-17:12 | 29.03 |
July | 0.138172E+09 | 2109.73 | 29-JUL-17:02 | 29.72 |
August | 0.116667E+09 | 1132.91 | 26-AUG-17:03 | 25.63 |
September | 0.107458E+09 | 1115.20 | 27-SEP-07:25 | 6.70 |
October | 0.637739E+09 | 30716.71 | 16-OCT-08:61 | 5.60 |
November | 0.270600E+10 | 34645.03 | 26-NOV-09:01 | -8.8 |
December | 0.742044E+10 | 34883.96 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.288809E+11 | |||
Minimum of Months | 0.107458E+09 | 1115.20 | -35.1 | |
Maximum of Months | 0.801421E+10 | 34883.96 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.856866E+10 | 34963.73 | 06-JAN-08:61 | -35.1 |
February | 0.533574E+10 | 35058.50 | 13-FEB-08:61 | -24.4 |
March | 0.415648E+10 | 34891.19 | 06-MAR-08:61 | -18.7 |
April | 0.125771E+10 | 34674.34 | 03-APR-07:01 | -3.0 |
May | 0.146972E+09 | 31872.05 | 02-MAY-08:61 | 8.18 |
June | 0.122891E+09 | 2020.87 | 24-JUN-17:12 | 29.03 |
July | 0.139849E+09 | 2117.70 | 29-JUL-17:02 | 29.72 |
August | 0.117882E+09 | 1142.35 | 26-AUG-17:03 | 25.63 |
September | 0.108770E+09 | 1120.55 | 27-SEP-07:25 | 6.70 |
October | 0.803151E+09 | 32885.37 | 30-OCT-07:01 | -9.0 |
November | 0.310950E+10 | 34839.86 | 07-NOV-08:61 | -8.0 |
December | 0.795216E+10 | 34987.61 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.318198E+11 | |||
Minimum of Months | 0.108770E+09 | 1120.55 | -35.1 | |
Maximum of Months | 0.856866E+10 | 35058.50 | 29.72 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.140577E+11 | 39880.72 | 26-JAN-08:61 | -32.1 |
February | 0.948476E+10 | 39883.26 | 17-FEB-08:61 | -28.5 |
March | 0.765916E+10 | 39729.96 | 15-MAR-07:01 | -23.7 |
April | 0.273798E+10 | 39458.16 | 09-APR-08:61 | 1.70 |
May | 0.278653E+09 | 38696.84 | 01-MAY-07:02 | -0.9 |
June | 0.147388E+09 | 2227.00 | 24-JUN-17:12 | 29.03 |
July | 0.164821E+09 | 2242.48 | 29-JUL-17:02 | 29.72 |
August | 0.141952E+09 | 1318.11 | 03-AUG-07:13 | 12.23 |
September | 0.159635E+09 | 9641.06 | 29-SEP-08:63 | 8.40 |
October | 0.167304E+10 | 39371.44 | 30-OCT-07:01 | -9.0 |
November | 0.553517E+10 | 39607.57 | 26-NOV-09:01 | -8.8 |
December | 0.129764E+11 | 39958.18 | 24-DEC-09:01 | -30.9 |
Annual Sum or Average | 0.550167E+11 | |||
Minimum of Months | 0.141952E+09 | 1318.11 | -32.1 | |
Maximum of Months | 0.140577E+11 | 39958.18 | 29.72 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107939E+11 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.790155E+10 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.687028E+10 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7125330.78 | 0.413257E+10 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.102765E+09 | 0.188338E+10 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.249716E+09 | 0.969387E+09 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354786E+09 | 0.616204E+09 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.147987E+09 | 0.958773E+09 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7119410.60 | 0.219699E+10 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.381331E+10 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.608624E+10 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104562E+11 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.869499E+09 | 0.566788E+11 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.616204E+09 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354786E+09 | 0.107939E+11 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.543933E+10 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.392120E+10 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.347348E+10 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3761138.69 | 0.204345E+10 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 55960692.12 | 0.932950E+09 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.134039E+09 | 0.460919E+09 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192397E+09 | 0.284081E+09 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 80372171.73 | 0.443437E+09 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3899907.76 | 0.109119E+10 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194331E+10 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.301314E+10 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.524220E+10 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.470429E+09 | 0.282887E+11 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284081E+09 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.192397E+09 | 0.543933E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555665E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404092E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354044E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2437179.41 | 0.208796E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55947779.35 | 0.961368E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132838E+09 | 0.483997E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188190E+09 | 0.305662E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80278402.80 | 0.469345E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899931.44 | 0.111608E+10 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197625E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.309025E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537705E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463592E+09 | 0.290060E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.305662E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188190E+09 | 0.555665E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.555174E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403589E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353663E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2461214.43 | 0.207888E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55947835.83 | 0.955855E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132809E+09 | 0.483371E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188163E+09 | 0.306035E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80278425.52 | 0.469362E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899932.85 | 0.111127E+10 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196798E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308417E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.537165E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463560E+09 | 0.289528E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306035E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188163E+09 | 0.555174E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554828E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403189E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353328E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2524092.68 | 0.206777E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55948095.78 | 0.944602E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.132882E+09 | 0.479946E+09 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188214E+09 | 0.304473E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80279039.53 | 0.467124E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899930.20 | 0.110050E+10 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.195703E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307816E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.536756E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.463747E+09 | 0.288806E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.304473E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188214E+09 | 0.554828E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.101413E+11 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.738584E+10 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.645030E+10 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4941560.75 | 0.378623E+10 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100630E+09 | 0.171885E+10 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239673E+09 | 0.883316E+09 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338759E+09 | 0.572239E+09 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144461E+09 | 0.873001E+09 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 7007465.84 | 0.200712E+10 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.355951E+10 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.564092E+10 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.982245E+10 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.835472E+09 | 0.528410E+11 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.572239E+09 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.338759E+09 | 0.101413E+11 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556849E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404329E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354207E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2775720.39 | 0.206230E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55960258.64 | 0.930911E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133136E+09 | 0.476535E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188364E+09 | 0.307853E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80308112.56 | 0.470786E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899719.21 | 0.109120E+10 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194906E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308499E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538727E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464444E+09 | 0.289148E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307853E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188364E+09 | 0.556849E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556792E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.404236E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.354093E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2841291.14 | 0.205738E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55960323.92 | 0.924046E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133169E+09 | 0.473467E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188392E+09 | 0.306800E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80308530.78 | 0.469529E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899714.43 | 0.108544E+10 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.194438E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.308298E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538656E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464571E+09 | 0.288818E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.306800E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188392E+09 | 0.556792E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.556381E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403715E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.353526E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3022401.15 | 0.204225E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 55960621.63 | 0.904439E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.133259E+09 | 0.464769E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188436E+09 | 0.303346E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 80309105.30 | 0.465348E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3899712.57 | 0.107145E+10 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.193171E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.307441E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538128E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464887E+09 | 0.287752E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.303346E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.188436E+09 | 0.556381E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.668419E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.499361E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.420273E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4033770.36 | 0.255106E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 58095729.62 | 0.113214E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.141912E+09 | 0.602923E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196565E+09 | 0.410457E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 83712673.18 | 0.628718E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 4011426.96 | 0.133983E+10 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.231116E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378529E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.653849E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.488331E+09 | 0.351806E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.410457E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.196565E+09 | 0.668419E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 18193.23 | 04-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14908.32 | 13-FEB-12:10 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 12263.51 | 15-MAR-11:10 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 843.16 | 23-APR-16:00 | 8513.93 | 04-APR-17:00 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1467.35 | 25-MAY-17:00 | 4400.29 | 01-MAY-11:10 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.95 | 29-JUN-16:00 | 3373.76 | 09-JUN-11:10 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2107.21 | 15-JUL-15:00 | 3096.49 | 08-JUL-11:10 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1965.02 | 08-AUG-16:00 | 3906.87 | 17-AUG-14:00 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 626.55 | 01-SEP-15:00 | 4425.35 | 27-SEP-11:05 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 7095.57 | 31-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 12039.97 | 25-NOV-12:10 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 17459.21 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3096.49 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3160.95 | 18193.23 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.80 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2580.69 | 08-MAY-11:05 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1913.34 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1728.62 | 08-JUL-11:10 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2166.81 | 17-AUG-14:00 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2569.02 | 27-SEP-11:05 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1728.62 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.82 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2551.43 | 08-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1917.90 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1748.31 | 08-JUL-12:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2150.42 | 17-AUG-14:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2554.10 | 27-SEP-11:05 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1748.31 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.85 | 23-APR-16:00 | 4573.76 | 04-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2529.71 | 08-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1917.96 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1748.31 | 08-JUL-12:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2146.99 | 17-AUG-14:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2536.48 | 27-SEP-11:05 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1748.31 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2490.71 | 08-MAY-11:05 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1910.01 | 09-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1741.92 | 08-JUL-12:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2127.23 | 17-AUG-14:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2493.18 | 27-SEP-11:05 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1741.92 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 17546.75 | 04-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 14741.82 | 01-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 12024.86 | 15-MAR-11:10 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 804.86 | 23-APR-16:00 | 8228.43 | 04-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1454.42 | 25-MAY-17:00 | 4348.58 | 20-MAY-11:10 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.97 | 29-JUN-16:00 | 3335.80 | 09-JUN-11:10 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2030.87 | 15-JUL-15:00 | 3095.03 | 08-JUL-11:10 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1905.87 | 08-AUG-16:00 | 3715.46 | 17-AUG-14:00 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 616.78 | 01-SEP-15:00 | 4316.53 | 27-SEP-11:05 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 6894.74 | 29-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 11862.45 | 25-NOV-17:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 16999.87 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 3095.03 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3071.97 | 17546.75 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1848.89 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1719.40 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2059.47 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2397.72 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1719.40 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1837.59 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1716.80 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2050.14 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2374.63 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1716.80 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 9736.58 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8221.95 | 01-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6688.26 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 445.95 | 23-APR-16:00 | 4573.77 | 04-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 810.18 | 25-MAY-17:00 | 2419.42 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 29-JUN-16:00 | 1801.65 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1126.80 | 15-JUL-15:00 | 1708.48 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1058.41 | 08-AUG-16:00 | 2021.52 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 343.24 | 01-SEP-15:00 | 2326.29 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3839.29 | 29-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6607.53 | 25-NOV-17:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9445.98 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1708.48 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1706.48 | 9736.58 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 10383.07 | 04-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 8455.57 | 13-FEB-12:10 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 6926.90 | 15-MAR-11:10 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 484.25 | 23-APR-16:00 | 4861.14 | 04-APR-17:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 823.11 | 25-MAY-17:00 | 2474.17 | 01-MAY-11:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.46 | 29-JUN-16:00 | 1796.04 | 09-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1203.14 | 15-JUL-15:00 | 1694.23 | 08-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1117.56 | 08-AUG-16:00 | 2104.04 | 17-AUG-14:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 353.02 | 01-SEP-15:00 | 2396.99 | 27-SEP-11:05 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 4035.44 | 31-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 6810.79 | 25-NOV-12:10 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 9905.32 | 24-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1694.23 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1795.46 | 10383.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 22198.54 | 06-JAN-00:01 | 3375.03 | 2916.13 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 337.51 |
February | 18300.67 | 25-FEB-00:01 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 410.65 |
March | 15334.16 | 03-MAR-00:01 | 2362.52 | 2041.29 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 12845.64 | 05-APR-08:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.05 |
May | 39626.05 | 27-MAY-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 244.18 |
June | 43917.28 | 07-JUN-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 239.69 |
July | 41608.81 | 17-JUL-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 459.14 |
August | 40832.03 | 05-AUG-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 357.30 |
September | 41457.78 | 02-SEP-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.30 |
October | 11376.45 | 30-OCT-08:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1427.16 |
November | 13974.59 | 25-NOV-00:02 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 712.00 |
December | 18031.80 | 02-DEC-00:01 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 479.11 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11376.45 | 1687.52 | 2041.29 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 43917.28 | 3375.03 | 23330.47 | 7490.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1533.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8494.84 | 21-JAN-09:04 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1067.47 |
February | 8981.36 | 10-FEB-09:04 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1084.80 |
March | 8352.42 | 06-MAR-09:04 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1127.10 |
April | 20368.21 | 23-APR-20:50 | 10124.81 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.88 |
May | 24119.30 | 21-MAY-19:12 | 13499.74 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 |
June | 23588.45 | 07-JUN-08:62 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 121.02 |
July | 22662.48 | 17-JUL-08:62 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.95 |
August | 22741.65 | 02-AUG-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.23 |
September | 22437.30 | 02-SEP-08:62 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.59 |
October | 6313.84 | 23-OCT-08:63 | 506.24 | 5106.68 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 430.48 |
November | 8363.13 | 25-NOV-09:04 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1078.67 |
December | 9272.89 | 01-DEC-09:04 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.01 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6313.84 | 506.24 | 5106.68 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.32 | |
Maximum of Months | 24119.30 | 13499.74 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1246.01 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7865.55 | 31-JAN-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1065.78 |
February | 7735.76 | 11-FEB-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 864.41 |
March | 8861.09 | 18-MAR-07:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1010.77 |
April | 5129.31 | 07-APR-07:02 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 617.34 |
May | 24774.43 | 19-MAY-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 219.92 |
June | 23708.19 | 07-JUN-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.47 |
July | 23724.94 | 08-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 257.98 |
August | 23755.69 | 02-AUG-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.97 |
September | 24152.98 | 08-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.28 |
October | 7478.22 | 22-OCT-08:63 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 302.62 |
November | 7919.43 | 29-NOV-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 993.17 |
December | 9069.33 | 01-DEC-08:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5129.31 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.47 | |
Maximum of Months | 24774.43 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1235.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7567.90 | 31-JAN-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.89 |
February | 7828.61 | 11-FEB-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 866.03 |
March | 8942.49 | 18-MAR-07:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1012.25 |
April | 5192.86 | 02-APR-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 756.75 |
May | 24852.09 | 19-MAY-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.08 |
June | 23764.99 | 09-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.45 |
July | 23802.85 | 08-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.23 |
August | 23823.88 | 02-AUG-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 285.00 |
September | 24223.29 | 08-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 308.34 |
October | 6348.22 | 23-OCT-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 447.89 |
November | 7418.17 | 29-NOV-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 990.41 |
December | 7607.38 | 23-DEC-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 954.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5192.86 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 220.08 | |
Maximum of Months | 24852.09 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1063.89 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 7195.75 | 18-JAN-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 914.23 |
February | 7831.93 | 11-FEB-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 862.64 |
March | 8484.98 | 18-MAR-07:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.13 |
April | 5999.15 | 05-APR-07:04 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.94 |
May | 24515.43 | 19-MAY-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 216.53 |
June | 23407.20 | 07-JUN-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.65 |
July | 23283.92 | 08-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 255.37 |
August | 23525.63 | 02-AUG-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.99 |
September | 23822.82 | 08-SEP-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 305.26 |
October | 4316.20 | 25-OCT-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 556.04 |
November | 6654.54 | 24-NOV-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 793.16 |
December | 7274.60 | 15-DEC-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 896.60 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 4316.20 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 130.65 | |
Maximum of Months | 24515.43 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1009.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 12786.76 | 20-JAN-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1527.58 |
February | 13372.81 | 28-FEB-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1473.17 |
March | 14073.13 | 23-MAR-08:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.23 |
April | 12927.67 | 05-APR-08:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1398.88 |
May | 42090.80 | 19-MAY-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 379.71 |
June | 42223.63 | 07-JUN-08:62 | 4455.04 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.91 |
July | 40351.22 | 17-JUL-08:62 | 4455.04 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 429.95 |
August | 40643.63 | 02-AUG-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.67 |
September | 42968.84 | 04-SEP-09:02 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 527.17 |
October | 11825.96 | 30-OCT-08:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1302.20 |
November | 13644.79 | 23-NOV-10:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1520.16 |
December | 12588.08 | 07-DEC-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1334.32 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 11825.96 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 203.91 | |
Maximum of Months | 42968.84 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1529.23 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6307.56 | 20-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.86 |
February | 6614.79 | 28-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 811.10 |
March | 7256.02 | 23-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847.25 |
April | 6388.56 | 05-APR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.99 |
May | 20584.56 | 19-MAY-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 206.69 |
June | 21622.24 | 07-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.78 |
July | 20705.28 | 17-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.22 |
August | 20847.34 | 02-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.55 |
September | 22070.92 | 04-SEP-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 284.42 |
October | 5866.78 | 30-OCT-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 716.22 |
November | 6751.99 | 23-NOV-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 833.22 |
December | 6217.39 | 07-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5866.78 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 106.78 | |
Maximum of Months | 22070.92 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 847.25 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6305.99 | 20-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.43 |
February | 6600.27 | 28-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 810.22 |
March | 6733.10 | 17-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 823.52 |
April | 6372.59 | 05-APR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 769.06 |
May | 19783.57 | 28-MAY-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 128.39 |
June | 21419.92 | 07-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.36 |
July | 20532.39 | 17-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 231.54 |
August | 20684.86 | 02-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.13 |
September | 21890.74 | 04-SEP-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 282.56 |
October | 5934.27 | 30-OCT-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 717.55 |
November | 6724.79 | 23-NOV-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 831.84 |
December | 6204.79 | 07-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 735.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5934.27 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.36 | |
Maximum of Months | 21890.74 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 832.43 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6237.62 | 20-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.80 |
February | 6206.82 | 23-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 760.87 |
March | 6503.25 | 11-MAR-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 806.68 |
April | 6304.80 | 05-APR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 766.60 |
May | 19119.18 | 27-MAY-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.36 |
June | 20575.32 | 07-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.16 |
July | 20360.13 | 17-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 225.39 |
August | 20072.63 | 27-AUG-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 235.17 |
September | 19902.34 | 02-SEP-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 213.26 |
October | 5853.76 | 30-OCT-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 713.97 |
November | 6654.86 | 23-NOV-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.23 |
December | 6164.40 | 07-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 733.79 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5853.76 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.16 | |
Maximum of Months | 20575.32 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 829.80 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5972.88 | 20-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.52 |
February | 6304.67 | 28-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 951.23 |
March | 6436.13 | 17-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 973.50 |
April | 6065.39 | 05-APR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 902.04 |
May | 19281.38 | 26-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.00 |
June | 23130.42 | 18-JUN-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 |
July | 23918.69 | 07-JUL-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 232.06 |
August | 23527.62 | 06-AUG-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 193.26 |
September | 18381.65 | 01-SEP-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.88 |
October | 5537.31 | 30-OCT-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 844.91 |
November | 6385.33 | 23-NOV-10:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1022.71 |
December | 5907.30 | 07-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 842.78 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 5537.31 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 74.95 | |
Maximum of Months | 23918.69 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1075.52 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.894536E+11 | 72164.21 | 27-JAN-18:30 | 0.271806E+12 | 366484.52 | 06-JAN-09:09 |
February | 0.798074E+11 | 67606.02 | 22-FEB-18:30 | 0.179694E+12 | 325941.22 | 14-FEB-09:09 |
March | 0.877937E+11 | 66051.04 | 10-MAR-19:40 | 0.146532E+12 | 290089.76 | 15-MAR-08:09 |
April | 0.827406E+11 | 74492.14 | 23-APR-14:00 | 0.469426E+11 | 199356.70 | 05-APR-08:09 |
May | 0.909014E+11 | 89209.46 | 25-MAY-14:39 | 0.187310E+10 | 108229.59 | 01-MAY-08:09 |
June | 0.971807E+11 | 108325.99 | 29-JUN-16:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.107227E+12 | 108969.61 | 15-JUL-14:09 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.102323E+12 | 101382.36 | 08-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.856471E+11 | 87918.61 | 01-SEP-15:39 | 0.503977E+09 | 17439.24 | 29-SEP-08:20 |
October | 0.873918E+11 | 67604.24 | 19-OCT-15:30 | 0.345547E+11 | 173368.31 | 30-OCT-08:09 |
November | 0.859017E+11 | 68157.43 | 06-NOV-18:10 | 0.109464E+12 | 268491.47 | 25-NOV-09:09 |
December | 0.894774E+11 | 66702.33 | 14-DEC-18:30 | 0.251144E+12 | 332925.75 | 20-DEC-09:09 |
Annual Sum or Average | 0.108585E+13 | 0.104251E+13 | ||||
Minimum of Months | 0.798074E+11 | 66051.04 | 0.00 | 0.00 | ||
Maximum of Months | 0.107227E+12 | 108969.61 | 0.271806E+12 | 366484.52 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.132856E+11 | 0.108804E+11 | 0.00 | 0.202747E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.591327E+10 | 0.00 |
February | 0.353889E+11 | 0.109130E+11 | 0.985143E+10 | 0.00 | 0.182726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.538160E+10 | 0.00 |
March | 0.396588E+11 | 0.106071E+11 | 0.110560E+11 | 0.00 | 0.204804E+11 | 0.00 | 0.00 | 116583.94 | 0.00 | 0.00 | 0.00 | 0.599133E+10 | 0.00 |
April | 0.379231E+11 | 0.878135E+10 | 0.105544E+11 | 0.00 | 0.195424E+11 | 0.00 | 0.00 | 0.260719E+09 | 0.00 | 0.00 | 0.00 | 0.567861E+10 | 0.00 |
May | 0.393718E+11 | 0.773871E+10 | 0.109629E+11 | 0.00 | 0.205978E+11 | 0.00 | 0.00 | 0.649014E+10 | 0.00 | 0.00 | 0.00 | 0.574005E+10 | 0.00 |
June | 0.383312E+11 | 0.676558E+10 | 0.106855E+11 | 0.00 | 0.201086E+11 | 0.00 | 0.00 | 0.158258E+11 | 0.00 | 0.00 | 0.00 | 0.546404E+10 | 0.00 |
July | 0.389786E+11 | 0.733092E+10 | 0.108424E+11 | 0.00 | 0.203563E+11 | 0.00 | 0.00 | 0.242170E+11 | 0.00 | 0.00 | 0.00 | 0.550213E+10 | 0.00 |
August | 0.396438E+11 | 0.847551E+10 | 0.110491E+11 | 0.00 | 0.207999E+11 | 0.00 | 0.00 | 0.168422E+11 | 0.00 | 0.00 | 0.00 | 0.551216E+10 | 0.00 |
September | 0.379380E+11 | 0.961546E+10 | 0.105613E+11 | 0.00 | 0.198795E+11 | 0.00 | 0.00 | 0.232208E+10 | 0.00 | 0.00 | 0.00 | 0.533072E+10 | 0.00 |
October | 0.390997E+11 | 0.114737E+11 | 0.108804E+11 | 0.00 | 0.201894E+11 | 0.00 | 0.00 | 0.154494E+09 | 0.00 | 0.00 | 0.00 | 0.559415E+10 | 0.00 |
November | 0.378782E+11 | 0.124514E+11 | 0.105443E+11 | 0.00 | 0.194976E+11 | 0.00 | 0.00 | 202048.00 | 0.00 | 0.00 | 0.00 | 0.552998E+10 | 0.00 |
December | 0.389936E+11 | 0.136424E+11 | 0.108529E+11 | 0.00 | 0.201634E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.582511E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121081E+12 | 0.128721E+12 | 0.00 | 0.240163E+12 | 0.00 | 0.00 | 0.661128E+11 | 0.00 | 0.00 | 0.00 | 0.674632E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.676558E+10 | 0.985143E+10 | 0.00 | 0.182726E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.533072E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.136424E+11 | 0.110560E+11 | 0.00 | 0.207999E+11 | 0.00 | 0.00 | 0.242170E+11 | 0.00 | 0.00 | 0.00 | 0.599133E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.271806E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.179694E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.146532E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.469426E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.187310E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.503977E+09 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.345547E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.109464E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.251144E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.104251E+13 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.271806E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 13928.79 | 03-JAN-08:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 13928.79 | 13-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 13928.79 | 07-MAR-18:10 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 13928.79 | 04-APR-08:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 13928.79 | 17-MAY-08:09 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 13928.79 | 29-JUN-19:19 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 13928.79 | 08-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 13928.79 | 02-AUG-08:09 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 13928.79 | 03-SEP-08:09 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 13928.79 | 06-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 13928.79 | 09-NOV-10:39 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 13928.79 | 24-DEC-09:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 13928.79 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 13928.79 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 13837.15 | 27-JAN-12:20 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 9773.48 | 22-FEB-13:30 | 0.00 |
March | 129.87 | 26-MAR-17:00 | 0.00 | 0.00 | 0.00 | 10937.58 | 23-MAR-11:00 | 0.00 |
April | 18726.95 | 23-APR-15:00 | 0.00 | 0.00 | 0.00 | 9767.51 | 10-APR-12:39 | 0.00 |
May | 33691.23 | 25-MAY-16:10 | 0.00 | 0.00 | 0.00 | 9757.18 | 04-MAY-12:20 | 0.00 |
June | 53391.83 | 29-JUN-16:10 | 0.00 | 0.00 | 0.00 | 9324.38 | 22-JUN-14:20 | 0.00 |
July | 49453.28 | 15-JUL-13:00 | 0.00 | 0.00 | 0.00 | 9728.39 | 29-JUL-12:20 | 0.00 |
August | 45189.61 | 08-AUG-14:00 | 0.00 | 0.00 | 0.00 | 12085.72 | 05-AUG-11:09 | 0.00 |
September | 31071.42 | 01-SEP-14:20 | 0.00 | 0.00 | 0.00 | 9791.05 | 23-SEP-15:39 | 0.00 |
October | 8357.27 | 19-OCT-14:00 | 0.00 | 0.00 | 0.00 | 9731.05 | 19-OCT-13:00 | 0.00 |
November | 277.13 | 01-NOV-20:19 | 0.00 | 0.00 | 0.00 | 9749.41 | 22-NOV-13:00 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 8242.53 | 14-DEC-18:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 8242.53 | 0.00 | ||
Maximum of Months | 53391.83 | 0.00 | 0.00 | 0.00 | 13837.15 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72164.21 | 27-JAN-18:30 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 67606.02 | 22-FEB-18:30 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66051.04 | 10-MAR-19:40 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 74492.14 | 23-APR-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 18308.59 | 0.00 |
May | 89209.46 | 25-MAY-14:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 33003.96 | 0.00 |
June | 108325.99 | 29-JUN-16:19 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 52970.28 | 0.00 |
July | 108969.61 | 15-JUL-14:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 49239.51 | 0.00 |
August | 101382.36 | 08-AUG-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 45189.61 | 0.00 |
September | 87918.61 | 01-SEP-15:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 30067.59 | 0.00 |
October | 67604.24 | 19-OCT-15:30 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 7181.39 | 0.00 |
November | 68157.43 | 06-NOV-18:10 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66702.33 | 14-DEC-18:30 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 66051.04 | 28718.22 | 8089.53 | 0.00 | 0.00 | 13928.79 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 108969.61 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 13928.79 | 0.00 | 0.00 | 52970.28 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 366484.52 | 06-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 325941.22 | 14-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 290089.76 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 199356.70 | 05-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 108229.59 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 17439.24 | 29-SEP-08:20 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 173368.31 | 30-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 268491.47 | 25-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 332925.75 | 20-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 366484.52 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 3.67 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 | 0.00 | 18.98 |
February | 2.33 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 | 0.00 | 19.10 |
March | 2.00 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 | 0.00 | 19.89 |
April | 0.83 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.50 | 0.17 | 24.50 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.33 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
November | 1.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 | 0.00 | 20.46 |
December | 2.50 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 | 0.00 | 19.80 |
Annual Sum or Average | 12.67 | 19.56 | 0.00 | 19.56 | 0.17 | 19.63 | 0.17 | 19.69 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 3.67 | 20.51 | 0.00 | 20.51 | 0.17 | 24.50 | 0.17 | 24.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 2.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 | 0.00 | 20.38 |
February | 1.33 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
March | 0.50 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
April | 0.33 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 | 0.00 | 20.49 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.33 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
December | 1.50 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 | 0.00 | 20.36 |
Annual Sum or Average | 6.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 | 0.00 | 20.42 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 2.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 | 0.00 | 20.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.17 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 | 0.00 | 14.99 |
Annual Sum or Average | 0.17 | 14.99 | 0.00 | 14.99 | 0.17 | 19.72 | 0.17 | 21.30 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.17 | 14.99 | 0.00 | 14.99 | 0.17 | 24.45 | 0.17 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.51 | 0.17 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 1.17 | 14.92 | 0.00 | 14.92 | 0.50 | 17.79 | 0.50 | 19.34 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 14.96 | 0.00 | 14.96 | 0.33 | 24.51 | 0.33 | 24.51 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.17 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 | 0.00 | 14.91 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.47 | 0.17 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 | 0.00 | 14.87 |
Annual Sum or Average | 0.67 | 14.88 | 0.00 | 14.88 | 0.33 | 18.08 | 0.33 | 19.68 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 14.91 | 0.00 | 14.91 | 0.17 | 24.49 | 0.17 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.50 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 | 0.00 | 14.86 |
Annual Sum or Average | 0.83 | 14.90 | 0.00 | 14.90 | 0.33 | 17.63 | 0.33 | 19.15 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.50 | 14.95 | 0.00 | 14.95 | 0.17 | 24.49 | 0.17 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 1.33 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 | 0.00 | 14.95 |
February | 0.33 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 | 0.00 | 14.94 |
March | 0.17 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 | 0.00 | 14.97 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 1.17 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 | 0.00 | 14.89 |
Annual Sum or Average | 3.00 | 14.93 | 0.00 | 14.93 | 0.17 | 15.43 | 0.17 | 15.88 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 14.97 | 0.00 | 14.97 | 0.17 | 24.49 | 0.17 | 24.49 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 43.17 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 | 0.00 | 14.70 |
February | 30.17 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 | 0.00 | 14.79 |
March | 14.17 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 | 0.00 | 14.84 |
April | 0.67 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 2.33 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 | 0.00 | 14.93 |
December | 40.00 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 | 0.00 | 14.74 |
Annual Sum or Average | 130.50 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 | 0.00 | 14.75 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 43.17 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 | 0.00 | 14.96 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 20.90 | 496.00 | 20.90 | 496.00 | 20.90 |
February | 448.00 | 20.91 | 422.67 | 20.90 | 422.67 | 20.90 |
March | 497.00 | 20.94 | 407.00 | 20.92 | 407.00 | 20.91 |
April | 467.83 | 21.47 | 189.33 | 21.32 | 184.67 | 21.22 |
May | 276.83 | 22.76 | 111.83 | 23.03 | 7.67 | 22.98 |
June | 162.17 | 23.73 | 306.50 | 23.86 | 98.50 | 23.88 |
July | 120.17 | 23.92 | 466.83 | 23.93 | 114.83 | 23.93 |
August | 83.83 | 23.83 | 434.17 | 23.92 | 69.33 | 23.93 |
September | 177.67 | 22.48 | 123.33 | 23.06 | 7.67 | 23.08 |
October | 445.67 | 21.42 | 64.83 | 21.37 | 59.17 | 21.31 |
November | 480.00 | 21.01 | 335.17 | 20.97 | 335.17 | 20.95 |
December | 496.00 | 20.91 | 496.00 | 20.91 | 496.00 | 20.91 |
Annual Sum or Average | 4151.17 | 21.49 | 3853.67 | 21.75 | 2698.67 | 21.62 |
Minimum of Months | 83.83 | 20.90 | 64.83 | 20.90 | 7.67 | 20.90 |
Maximum of Months | 497.00 | 23.92 | 496.00 | 23.93 | 496.00 | 23.93 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.00 | 469.00 | 20.98 | 469.00 | 20.98 |
February | 448.00 | 21.09 | 322.00 | 21.04 | 322.00 | 21.02 |
March | 497.00 | 21.26 | 253.33 | 21.16 | 253.33 | 21.11 |
April | 461.67 | 22.17 | 46.00 | 22.08 | 39.33 | 21.99 |
May | 212.83 | 23.27 | 125.33 | 23.51 | 0.33 | 23.51 |
June | 89.50 | 23.85 | 327.83 | 23.92 | 68.00 | 23.92 |
July | 59.33 | 23.86 | 471.00 | 23.91 | 58.50 | 23.90 |
August | 42.67 | 23.89 | 451.00 | 23.92 | 40.83 | 23.92 |
September | 118.50 | 23.10 | 153.17 | 23.55 | 5.33 | 23.56 |
October | 418.00 | 22.11 | 8.83 | 22.13 | 2.50 | 22.12 |
November | 480.00 | 21.42 | 140.50 | 21.31 | 140.50 | 21.24 |
December | 496.00 | 21.03 | 459.50 | 21.01 | 459.50 | 21.00 |
Annual Sum or Average | 3819.50 | 21.70 | 3227.50 | 22.01 | 1859.17 | 21.85 |
Minimum of Months | 42.67 | 21.00 | 8.83 | 20.98 | 0.33 | 20.98 |
Maximum of Months | 497.00 | 23.89 | 471.00 | 23.92 | 469.00 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 283.33 | 21.11 | 283.33 | 21.11 |
March | 379.00 | 21.11 | 244.83 | 21.11 | 244.83 | 21.11 |
April | 349.50 | 21.74 | 69.33 | 21.67 | 65.00 | 21.59 |
May | 171.67 | 22.93 | 119.00 | 23.36 | 3.50 | 23.33 |
June | 86.83 | 24.00 | 256.50 | 24.04 | 68.00 | 24.05 |
July | 63.67 | 24.19 | 360.00 | 24.08 | 63.50 | 24.09 |
August | 47.17 | 24.06 | 352.83 | 24.03 | 44.67 | 24.04 |
September | 113.50 | 22.73 | 109.50 | 23.36 | 8.00 | 23.39 |
October | 325.00 | 21.57 | 21.00 | 21.59 | 14.50 | 21.57 |
November | 360.00 | 21.17 | 166.50 | 21.15 | 166.50 | 21.14 |
December | 369.00 | 21.11 | 366.83 | 21.11 | 366.83 | 21.11 |
Annual Sum or Average | 2972.33 | 21.60 | 2720.67 | 21.99 | 1699.67 | 21.86 |
Minimum of Months | 47.17 | 21.11 | 21.00 | 21.11 | 3.50 | 21.11 |
Maximum of Months | 379.00 | 24.19 | 371.00 | 24.08 | 371.00 | 24.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 295.00 | 21.11 | 295.00 | 21.11 |
March | 379.00 | 21.11 | 253.50 | 21.11 | 253.50 | 21.11 |
April | 350.33 | 21.70 | 79.83 | 21.62 | 75.83 | 21.54 |
May | 177.67 | 22.88 | 115.50 | 23.30 | 4.33 | 23.27 |
June | 92.17 | 23.99 | 253.00 | 24.04 | 68.00 | 24.05 |
July | 63.00 | 24.20 | 361.00 | 24.08 | 62.83 | 24.09 |
August | 48.83 | 24.03 | 351.17 | 24.03 | 44.83 | 24.03 |
September | 120.33 | 22.69 | 106.50 | 23.31 | 8.00 | 23.34 |
October | 329.50 | 21.55 | 25.67 | 21.57 | 19.33 | 21.54 |
November | 360.00 | 21.17 | 184.17 | 21.15 | 184.17 | 21.14 |
December | 369.00 | 21.11 | 368.83 | 21.11 | 368.83 | 21.11 |
Annual Sum or Average | 2996.83 | 21.60 | 2765.17 | 21.97 | 1755.67 | 21.84 |
Minimum of Months | 48.83 | 21.11 | 25.67 | 21.11 | 4.33 | 21.11 |
Maximum of Months | 379.00 | 24.20 | 371.00 | 24.08 | 371.00 | 24.09 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 371.00 | 21.11 | 371.00 | 21.11 |
February | 336.00 | 21.11 | 305.33 | 21.11 | 305.33 | 21.11 |
March | 379.00 | 21.11 | 270.67 | 21.11 | 270.67 | 21.11 |
April | 352.83 | 21.65 | 95.17 | 21.56 | 91.83 | 21.48 |
May | 196.50 | 22.83 | 106.17 | 23.22 | 5.00 | 23.18 |
June | 103.83 | 23.93 | 243.17 | 24.02 | 68.50 | 24.03 |
July | 64.33 | 24.18 | 357.67 | 24.07 | 64.00 | 24.09 |
August | 55.33 | 23.98 | 347.33 | 24.02 | 49.00 | 24.02 |
September | 130.50 | 22.56 | 101.33 | 23.19 | 8.00 | 23.22 |
October | 334.83 | 21.50 | 32.67 | 21.51 | 26.83 | 21.49 |
November | 360.00 | 21.16 | 211.00 | 21.14 | 211.00 | 21.13 |
December | 369.00 | 21.11 | 369.00 | 21.11 | 369.00 | 21.11 |
Annual Sum or Average | 3053.17 | 21.61 | 2810.50 | 21.95 | 1840.17 | 21.82 |
Minimum of Months | 55.33 | 21.11 | 32.67 | 21.11 | 5.00 | 21.11 |
Maximum of Months | 379.00 | 24.18 | 371.00 | 24.07 | 371.00 | 24.09 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 301.17 | 21.11 | 301.17 | 21.11 |
March | 348.00 | 21.11 | 287.00 | 21.11 | 287.00 | 21.11 |
April | 325.33 | 21.58 | 122.83 | 21.46 | 121.83 | 21.38 |
May | 200.67 | 22.72 | 83.00 | 23.01 | 6.17 | 22.97 |
June | 116.00 | 23.75 | 199.00 | 23.87 | 69.67 | 23.88 |
July | 68.50 | 24.07 | 321.33 | 23.98 | 65.83 | 23.99 |
August | 71.33 | 23.77 | 308.83 | 23.90 | 60.17 | 23.90 |
September | 140.67 | 22.41 | 79.00 | 22.96 | 11.67 | 23.01 |
October | 314.83 | 21.44 | 58.50 | 21.42 | 55.00 | 21.38 |
November | 330.00 | 21.14 | 242.67 | 21.13 | 242.67 | 21.12 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2901.33 | 21.62 | 2681.33 | 21.87 | 1899.17 | 21.76 |
Minimum of Months | 68.50 | 21.10 | 58.50 | 21.10 | 6.17 | 21.10 |
Maximum of Months | 348.00 | 24.07 | 340.00 | 23.98 | 340.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 299.67 | 21.11 | 299.67 | 21.11 |
March | 348.00 | 21.11 | 289.17 | 21.11 | 289.17 | 21.11 |
April | 325.67 | 21.57 | 128.17 | 21.45 | 127.17 | 21.37 |
May | 206.67 | 22.74 | 72.83 | 22.98 | 6.83 | 22.93 |
June | 120.17 | 23.74 | 180.17 | 23.86 | 69.50 | 23.88 |
July | 70.00 | 24.06 | 317.00 | 23.97 | 66.67 | 23.99 |
August | 72.17 | 23.77 | 303.00 | 23.90 | 60.50 | 23.90 |
September | 149.17 | 22.48 | 71.17 | 22.95 | 11.50 | 23.00 |
October | 317.33 | 21.46 | 60.67 | 21.42 | 59.00 | 21.37 |
November | 330.00 | 21.14 | 243.83 | 21.13 | 243.83 | 21.12 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2925.17 | 21.63 | 2643.67 | 21.86 | 1911.83 | 21.75 |
Minimum of Months | 70.00 | 21.10 | 60.67 | 21.10 | 6.83 | 21.10 |
Maximum of Months | 348.00 | 24.06 | 340.00 | 23.97 | 340.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 302.00 | 21.11 | 302.00 | 21.11 |
March | 348.00 | 21.11 | 294.00 | 21.11 | 294.00 | 21.11 |
April | 326.00 | 21.55 | 136.83 | 21.43 | 135.83 | 21.35 |
May | 209.50 | 22.68 | 70.33 | 22.92 | 7.50 | 22.87 |
June | 124.83 | 23.71 | 174.33 | 23.84 | 70.00 | 23.87 |
July | 73.00 | 24.04 | 315.33 | 23.97 | 68.50 | 23.99 |
August | 74.17 | 23.76 | 300.67 | 23.90 | 61.00 | 23.90 |
September | 156.67 | 22.46 | 67.83 | 22.91 | 11.83 | 22.96 |
October | 319.33 | 21.45 | 65.67 | 21.40 | 64.83 | 21.36 |
November | 330.00 | 21.14 | 248.00 | 21.13 | 248.00 | 21.12 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 2947.50 | 21.63 | 2653.00 | 21.85 | 1941.50 | 21.74 |
Minimum of Months | 73.00 | 21.10 | 65.67 | 21.10 | 7.50 | 21.10 |
Maximum of Months | 348.00 | 24.04 | 340.00 | 23.97 | 340.00 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 340.00 | 21.10 | 340.00 | 21.10 |
February | 308.00 | 21.11 | 307.17 | 21.11 | 307.17 | 21.11 |
March | 348.00 | 21.11 | 311.50 | 21.11 | 311.50 | 21.11 |
April | 326.67 | 21.49 | 166.00 | 21.37 | 165.17 | 21.31 |
May | 222.33 | 22.57 | 70.00 | 22.79 | 10.50 | 22.73 |
June | 143.33 | 23.63 | 160.33 | 23.79 | 71.17 | 23.82 |
July | 75.83 | 24.01 | 307.67 | 23.97 | 70.00 | 23.98 |
August | 83.50 | 23.71 | 295.17 | 23.88 | 64.17 | 23.89 |
September | 173.50 | 22.42 | 63.83 | 22.82 | 13.67 | 22.88 |
October | 326.17 | 21.44 | 84.00 | 21.37 | 84.00 | 21.33 |
November | 330.00 | 21.13 | 266.83 | 21.12 | 266.83 | 21.12 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3015.33 | 21.63 | 2710.50 | 21.82 | 2042.17 | 21.72 |
Minimum of Months | 75.83 | 21.10 | 63.83 | 21.10 | 10.50 | 21.10 |
Maximum of Months | 348.00 | 24.01 | 340.00 | 23.97 | 340.00 | 23.98 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 340.00 | 21.11 | 340.00 | 21.11 |
February | 308.00 | 21.11 | 308.00 | 21.11 | 308.00 | 21.11 |
March | 348.00 | 21.11 | 346.50 | 21.11 | 346.50 | 21.11 |
April | 329.00 | 21.44 | 220.67 | 21.31 | 220.33 | 21.25 |
May | 244.17 | 22.42 | 70.50 | 22.52 | 26.67 | 22.41 |
June | 164.33 | 23.49 | 146.67 | 23.70 | 73.00 | 23.75 |
July | 88.17 | 23.88 | 295.00 | 23.94 | 71.67 | 23.96 |
August | 102.67 | 23.61 | 276.67 | 23.85 | 69.00 | 23.86 |
September | 202.67 | 22.37 | 56.17 | 22.69 | 14.00 | 22.73 |
October | 332.17 | 21.43 | 146.50 | 21.33 | 146.50 | 21.28 |
November | 330.00 | 21.13 | 312.50 | 21.12 | 312.50 | 21.11 |
December | 338.00 | 21.11 | 338.00 | 21.11 | 338.00 | 21.11 |
Annual Sum or Average | 3127.17 | 21.65 | 2857.17 | 21.78 | 2266.17 | 21.67 |
Minimum of Months | 88.17 | 21.11 | 56.17 | 21.11 | 14.00 | 21.11 |
Maximum of Months | 348.00 | 23.88 | 346.50 | 23.94 | 346.50 | 23.96 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.90331 | 8.77197 | -0.8274 | 20.07102 |
February | 448.00000 | 20.90609 | 10.73768 | -0.7597 | 17.90961 |
March | 497.00000 | 20.93605 | 14.74006 | -0.6879 | 15.68579 |
April | 479.00000 | 21.53081 | 19.60108 | -0.4182 | 10.51941 |
May | 496.00000 | 23.26567 | 32.09378 | -0.7916 | 21.05159 |
June | 481.00000 | 23.84524 | 47.57962 | -0.4391 | 9.84337 |
July | 495.00000 | 23.92365 | 54.35025 | -0.3103 | 7.25526 |
August | 497.00000 | 23.90776 | 52.81312 | -0.3451 | 7.84521 |
September | 479.00000 | 23.35807 | 40.19574 | -0.6757 | 16.85284 |
October | 496.00000 | 21.67042 | 29.37811 | -0.2782 | 8.54156 |
November | 480.00000 | 21.01250 | 18.60523 | -0.6079 | 13.52034 |
December | 496.00000 | 20.90698 | 10.09180 | -0.8093 | 19.40443 |
Annual Sum or Average | 5840.00000 | 22.18819 | 28.35501 | -0.5782 | 14.02458 |
Minimum of Months | 448.00000 | 20.90331 | 8.77197 | -0.8274 | 7.25526 |
Maximum of Months | 497.00000 | 23.92365 | 54.35025 | -0.2782 | 21.05159 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 20.99931 | 11.01605 | -0.7083 | 16.05602 |
February | 448.00000 | 21.09456 | 13.25445 | -0.6234 | 13.75111 |
March | 497.00000 | 21.26497 | 17.03831 | -0.5306 | 11.68480 |
April | 479.00000 | 22.22753 | 20.89001 | -0.2168 | 7.76966 |
May | 496.00000 | 23.61999 | 31.79030 | -0.6551 | 15.52274 |
June | 481.00000 | 23.90014 | 46.40285 | -0.4070 | 8.88833 |
July | 495.00000 | 23.89206 | 52.50890 | -0.3263 | 7.46403 |
August | 497.00000 | 23.89901 | 51.78398 | -0.3443 | 7.73942 |
September | 479.00000 | 23.69357 | 39.46589 | -0.5567 | 12.42733 |
October | 496.00000 | 22.39074 | 30.35856 | -0.0919 | 6.92314 |
November | 480.00000 | 21.42286 | 20.63764 | -0.4523 | 10.15625 |
December | 496.00000 | 21.02573 | 12.34427 | -0.6880 | 15.41026 |
Annual Sum or Average | 5840.00000 | 22.45965 | 29.05538 | -0.4661 | 11.14283 |
Minimum of Months | 448.00000 | 20.99931 | 11.01605 | -0.7083 | 6.92314 |
Maximum of Months | 497.00000 | 23.90014 | 52.50890 | -0.0919 | 16.05602 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10575 | 7.71854 | -0.7323 | 16.47560 |
February | 336.00000 | 21.10681 | 9.90644 | -0.6582 | 14.35579 |
March | 379.00000 | 21.11367 | 14.00995 | -0.5882 | 12.54660 |
April | 360.00000 | 21.80697 | 18.23608 | -0.3160 | 8.76146 |
May | 375.00000 | 23.51106 | 31.77671 | -0.6858 | 17.34916 |
June | 366.00000 | 23.99116 | 46.27942 | -0.3779 | 8.64975 |
July | 369.00000 | 24.05200 | 52.63495 | -0.2698 | 6.97188 |
August | 379.00000 | 24.00440 | 52.27187 | -0.3036 | 7.31346 |
September | 360.00000 | 23.55852 | 38.66835 | -0.5963 | 14.08046 |
October | 371.00000 | 21.85974 | 28.75985 | -0.2070 | 7.70369 |
November | 360.00000 | 21.17464 | 18.13337 | -0.5272 | 11.31991 |
December | 369.00000 | 21.10624 | 9.31168 | -0.7141 | 15.91388 |
Annual Sum or Average | 4395.00000 | 22.37704 | 27.46514 | -0.4970 | 11.77153 |
Minimum of Months | 336.00000 | 21.10575 | 7.71854 | -0.7323 | 6.97188 |
Maximum of Months | 379.00000 | 24.05200 | 52.63495 | -0.2070 | 17.34916 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10566 | 7.70790 | -0.7423 | 16.78344 |
February | 336.00000 | 21.10634 | 9.89668 | -0.6690 | 14.65316 |
March | 379.00000 | 21.11168 | 14.00169 | -0.5986 | 12.80619 |
April | 360.00000 | 21.76546 | 18.27740 | -0.3346 | 8.96861 |
May | 375.00000 | 23.47252 | 31.84199 | -0.7041 | 18.06255 |
June | 366.00000 | 23.98769 | 46.30006 | -0.3812 | 8.72658 |
July | 369.00000 | 24.05214 | 52.63000 | -0.2686 | 6.96026 |
August | 379.00000 | 24.00342 | 52.28651 | -0.3039 | 7.32065 |
September | 360.00000 | 23.52329 | 38.75723 | -0.6114 | 14.63467 |
October | 371.00000 | 21.81374 | 28.84774 | -0.2265 | 7.85762 |
November | 360.00000 | 21.16727 | 18.14253 | -0.5408 | 11.60884 |
December | 369.00000 | 21.10601 | 9.30119 | -0.7239 | 16.21077 |
Annual Sum or Average | 4395.00000 | 22.36238 | 27.48888 | -0.5077 | 12.03350 |
Minimum of Months | 336.00000 | 21.10566 | 7.70790 | -0.7423 | 6.96026 |
Maximum of Months | 379.00000 | 24.05214 | 52.63000 | -0.2265 | 18.06255 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10552 | 7.71809 | -0.7549 | 17.18608 |
February | 336.00000 | 21.10623 | 9.90656 | -0.6840 | 15.08462 |
March | 379.00000 | 21.10991 | 14.01325 | -0.6140 | 13.20625 |
April | 360.00000 | 21.70175 | 18.35725 | -0.3614 | 9.28151 |
May | 375.00000 | 23.38913 | 31.99973 | -0.7415 | 19.44875 |
June | 366.00000 | 23.97002 | 46.41305 | -0.3960 | 9.02461 |
July | 369.00000 | 24.04650 | 52.75242 | -0.2765 | 7.04453 |
August | 379.00000 | 23.99444 | 52.39907 | -0.3135 | 7.45583 |
September | 360.00000 | 23.43946 | 38.98466 | -0.6462 | 15.88864 |
October | 371.00000 | 21.74056 | 28.99905 | -0.2538 | 8.05947 |
November | 360.00000 | 21.15695 | 18.17564 | -0.5584 | 11.99086 |
December | 369.00000 | 21.10588 | 9.31133 | -0.7369 | 16.61737 |
Annual Sum or Average | 4395.00000 | 22.33326 | 27.57585 | -0.5270 | 12.50761 |
Minimum of Months | 336.00000 | 21.10552 | 7.71809 | -0.7549 | 7.04453 |
Maximum of Months | 379.00000 | 24.04650 | 52.75242 | -0.2538 | 19.44875 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10478 | 9.14597 | -0.7958 | 18.49842 |
February | 308.00000 | 21.10566 | 11.38278 | -0.7251 | 16.27928 |
March | 348.00000 | 21.10665 | 15.54624 | -0.6536 | 14.24809 |
April | 330.00000 | 21.61400 | 19.78161 | -0.4090 | 9.91111 |
May | 344.00000 | 23.21735 | 33.62201 | -0.8152 | 21.94119 |
June | 336.00000 | 23.84898 | 47.69585 | -0.4479 | 9.93500 |
July | 338.00000 | 23.94503 | 53.83152 | -0.3141 | 7.40806 |
August | 348.00000 | 23.89848 | 53.60133 | -0.3523 | 7.92676 |
September | 330.00000 | 23.25963 | 40.52075 | -0.7177 | 18.44721 |
October | 340.00000 | 21.62618 | 30.60713 | -0.3035 | 8.52618 |
November | 330.00000 | 21.14333 | 19.59739 | -0.6029 | 13.02952 |
December | 338.00000 | 21.10522 | 10.75488 | -0.7789 | 17.94172 |
Annual Sum or Average | 4030.00000 | 22.25892 | 29.00104 | -0.5752 | 13.65543 |
Minimum of Months | 308.00000 | 21.10478 | 9.14597 | -0.8152 | 7.40806 |
Maximum of Months | 348.00000 | 23.94503 | 53.83152 | -0.3035 | 21.94119 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10479 | 9.04003 | -0.7850 | 18.13773 |
February | 308.00000 | 21.10565 | 11.28005 | -0.7193 | 16.09979 |
March | 348.00000 | 21.10660 | 15.44365 | -0.6521 | 14.19447 |
April | 330.00000 | 21.60502 | 19.69556 | -0.4186 | 10.02969 |
May | 344.00000 | 23.20385 | 33.57627 | -0.8377 | 22.70186 |
June | 336.00000 | 23.84445 | 47.67171 | -0.4692 | 10.35326 |
July | 338.00000 | 23.94439 | 53.83072 | -0.3364 | 7.69655 |
August | 348.00000 | 23.89895 | 53.58065 | -0.3725 | 8.21873 |
September | 330.00000 | 23.25461 | 40.46387 | -0.7380 | 19.07170 |
October | 340.00000 | 21.62340 | 30.51587 | -0.3127 | 8.61063 |
November | 330.00000 | 21.14186 | 19.49728 | -0.6028 | 13.01082 |
December | 338.00000 | 21.10523 | 10.64800 | -0.7688 | 17.61136 |
Annual Sum or Average | 4030.00000 | 22.25588 | 28.93106 | -0.5834 | 13.79459 |
Minimum of Months | 308.00000 | 21.10479 | 9.04003 | -0.8377 | 7.69655 |
Maximum of Months | 348.00000 | 23.94439 | 53.83072 | -0.3127 | 22.70186 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10473 | 9.03969 | -0.7871 | 18.20846 |
February | 308.00000 | 21.10561 | 11.27994 | -0.7227 | 16.20341 |
March | 348.00000 | 21.10647 | 15.44342 | -0.6569 | 14.32334 |
April | 330.00000 | 21.58104 | 19.72790 | -0.4309 | 10.19889 |
May | 344.00000 | 23.15924 | 33.66944 | -0.8597 | 23.58261 |
June | 336.00000 | 23.82888 | 47.75187 | -0.4809 | 10.66593 |
July | 338.00000 | 23.94160 | 53.90238 | -0.3416 | 7.77810 |
August | 348.00000 | 23.89452 | 53.64053 | -0.3785 | 8.32928 |
September | 330.00000 | 23.21310 | 40.57992 | -0.7568 | 19.79341 |
October | 340.00000 | 21.59854 | 30.56690 | -0.3243 | 8.72933 |
November | 330.00000 | 21.13956 | 19.50286 | -0.6088 | 13.15382 |
December | 338.00000 | 21.10518 | 10.64767 | -0.7711 | 17.68716 |
Annual Sum or Average | 4030.00000 | 22.24248 | 28.97371 | -0.5923 | 14.03828 |
Minimum of Months | 308.00000 | 21.10473 | 9.03969 | -0.8597 | 7.77810 |
Maximum of Months | 348.00000 | 23.94160 | 53.90238 | -0.3243 | 23.58261 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10462 | 9.04681 | -0.7998 | 18.63474 |
February | 308.00000 | 21.10536 | 11.28684 | -0.7383 | 16.68381 |
March | 348.00000 | 21.10636 | 15.45015 | -0.6761 | 14.86232 |
April | 330.00000 | 21.52243 | 19.81146 | -0.4649 | 10.74767 |
May | 344.00000 | 23.03972 | 33.91978 | -0.9159 | 25.92804 |
June | 336.00000 | 23.78531 | 47.96324 | -0.5085 | 11.47490 |
July | 338.00000 | 23.93251 | 54.07818 | -0.3513 | 7.95381 |
August | 348.00000 | 23.87917 | 53.80756 | -0.3915 | 8.61108 |
September | 330.00000 | 23.11588 | 40.85549 | -0.8002 | 21.46731 |
October | 340.00000 | 21.54088 | 30.68961 | -0.3538 | 9.09411 |
November | 330.00000 | 21.13326 | 19.52469 | -0.6291 | 13.66914 |
December | 338.00000 | 21.10507 | 10.65485 | -0.7844 | 18.12433 |
Annual Sum or Average | 4030.00000 | 22.20837 | 29.08572 | -0.6169 | 14.75587 |
Minimum of Months | 308.00000 | 21.10462 | 9.04681 | -0.9159 | 7.95381 |
Maximum of Months | 348.00000 | 23.93251 | 54.07818 | -0.3513 | 25.92804 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10500 | 8.88976 | -0.8910 | 21.92677 |
February | 308.00000 | 21.10578 | 11.08223 | -0.8257 | 19.62287 |
March | 348.00000 | 21.10652 | 15.25585 | -0.7661 | 17.64341 |
April | 330.00000 | 21.44907 | 19.71698 | -0.5563 | 12.70472 |
May | 344.00000 | 22.85534 | 34.11457 | -1.0326 | 31.06486 |
June | 336.00000 | 23.70360 | 48.19556 | -0.5632 | 13.27286 |
July | 338.00000 | 23.90732 | 54.26544 | -0.3618 | 8.33489 |
August | 348.00000 | 23.83981 | 54.09483 | -0.4179 | 9.37791 |
September | 330.00000 | 22.96703 | 41.04648 | -0.8873 | 25.03636 |
October | 340.00000 | 21.48270 | 30.60417 | -0.4278 | 10.41554 |
November | 330.00000 | 21.12522 | 19.42034 | -0.7083 | 15.94989 |
December | 338.00000 | 21.10538 | 10.48525 | -0.8723 | 21.23690 |
Annual Sum or Average | 4030.00000 | 22.15665 | 29.09449 | -0.6914 | 17.19675 |
Minimum of Months | 308.00000 | 21.10500 | 8.88976 | -1.0326 | 8.33489 |
Maximum of Months | 348.00000 | 23.90732 | 54.26544 | -0.3618 | 31.06486 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.268461E+09 | 76056545.22 | 8.83 | 0.240707E+09 | 27754195.80 | 0.00 | 0.38 | 23-APR-16:10 | 0.00 | 01-APR-00:10 | 12897.81 | 23-APR-16:10 | 11671.45 | 23-APR-16:03 | 1303.52 | 23-APR-18:00 | 3674.76 | 23-APR-16:10 | 0.00 | 01-APR-00:10 |
May | 0.424465E+10 | 0.118612E+10 | 152.48 | 0.378760E+10 | 0.457056E+09 | 0.00 | 1.00 | 18-MAY-08:62 | 0.00 | 01-MAY-00:05 | 43019.06 | 26-MAY-08:61 | 36618.40 | 18-MAY-08:62 | 14083.64 | 26-MAY-08:03 | 9280.09 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 |
June | 0.110565E+11 | 0.299299E+10 | 276.54 | 0.826404E+10 | 0.279244E+10 | 0.00 | 1.00 | 07-JUN-08:62 | 0.00 | 01-JUN-00:10 | 46307.34 | 30-JUN-08:61 | 39575.64 | 07-JUN-08:62 | 22113.51 | 23-JUN-08:62 | 10106.02 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.176024E+11 | 0.469609E+10 | 384.91 | 0.123806E+11 | 0.522189E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 45933.24 | 23-JUL-07:02 | 31809.02 | 12-JUL-08:61 | 24514.31 | 23-JUL-07:02 | 9867.58 | 29-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.118270E+11 | 0.314901E+10 | 319.50 | 0.844699E+10 | 0.338001E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 44904.39 | 30-AUG-08:61 | 31776.14 | 05-AUG-08:62 | 21909.51 | 30-AUG-08:03 | 9538.79 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.155397E+10 | 0.422414E+09 | 88.88 | 0.128286E+10 | 0.271105E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 43476.73 | 01-SEP-08:62 | 28870.72 | 02-SEP-08:62 | 20905.85 | 19-SEP-08:62 | 9353.18 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 97468818.57 | 27535488.93 | 13.17 | 93092947.36 | 4375871.20 | 0.00 | 0.16 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 5066.22 | 19-OCT-15:00 | 4992.12 | 19-OCT-15:00 | 276.60 | 22-OCT-14:00 | 1428.59 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.466505E+11 | 0.125502E+11 | 1244.32 | 0.344958E+11 | 0.121546E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.176024E+11 | 0.469609E+10 | 384.91 | 0.123806E+11 | 0.522189E+10 | 0.00 | 1.00 | 0.00 | 46307.34 | 39575.64 | 24514.31 | 10106.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 415556.11 | 116583.94 | 0.33 | 415556.11 | -0.0 | 0.00 | 0.03 | 26-MAR-18:00 | 0.00 | 01-MAR-00:05 | 463.49 | 26-MAR-18:00 | 463.49 | 26-MAR-18:00 | 0.00 | 26-MAR-19:20 | 129.87 | 26-MAR-18:00 | 0.00 | 01-MAR-00:05 |
April | 0.184351E+09 | 49253911.27 | 16.50 | 0.167276E+09 | 17075214.88 | 0.00 | 1.00 | 23-APR-18:41 | 0.00 | 01-APR-00:10 | 21786.26 | 23-APR-18:41 | 20213.49 | 23-APR-18:47 | 2967.39 | 23-APR-20:43 | 4823.35 | 23-APR-18:41 | 0.00 | 01-APR-00:10 |
May | 0.281648E+10 | 0.748333E+09 | 159.27 | 0.253523E+10 | 0.281253E+09 | 0.00 | 1.00 | 10-MAY-20:01 | 0.00 | 01-MAY-00:05 | 22662.55 | 26-MAY-08:61 | 20901.85 | 10-MAY-20:09 | 6759.18 | 26-MAY-08:03 | 4913.15 | 25-MAY-20:31 | 0.00 | 01-MAY-00:05 |
June | 0.668770E+10 | 0.173833E+10 | 276.20 | 0.505860E+10 | 0.162910E+10 | 0.00 | 1.00 | 04-JUN-17:01 | 0.00 | 01-JUN-00:10 | 23976.25 | 27-JUN-20:02 | 21160.88 | 17-JUN-18:07 | 12758.12 | 19-JUN-20:02 | 5220.95 | 30-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.104697E+11 | 0.267370E+10 | 359.21 | 0.743774E+10 | 0.303195E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 24057.86 | 23-JUL-07:02 | 18779.42 | 02-JUL-17:07 | 12956.49 | 25-JUL-20:02 | 5123.15 | 29-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.734749E+10 | 0.186534E+10 | 309.50 | 0.524662E+10 | 0.210086E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 23959.53 | 31-AUG-20:02 | 20297.46 | 05-AUG-18:01 | 12461.31 | 28-AUG-20:02 | 5076.16 | 31-AUG-20:02 | 0.00 | 01-AUG-00:10 |
September | 0.113157E+10 | 0.294246E+09 | 104.33 | 0.937167E+09 | 0.194406E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 22998.47 | 17-SEP-17:01 | 18743.46 | 24-SEP-17:01 | 10933.40 | 19-SEP-08:62 | 4861.53 | 17-SEP-17:01 | 0.00 | 01-SEP-00:03 |
October | 0.105153E+09 | 28897721.23 | 23.81 | 0.101132E+09 | 4020664.83 | 0.00 | 0.21 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3565.50 | 19-OCT-15:00 | 3542.34 | 19-OCT-15:00 | 232.13 | 22-OCT-13:40 | 974.83 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 720794.44 | 202048.00 | 0.50 | 599020.66 | 121773.78 | 0.00 | 0.06 | 01-NOV-20:20 | 0.00 | 01-NOV-00:05 | 990.79 | 01-NOV-20:20 | 829.52 | 01-NOV-20:20 | 161.27 | 01-NOV-20:20 | 277.13 | 01-NOV-20:20 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.287436E+11 | 0.739842E+10 | 1249.64 | 0.214848E+11 | 0.725879E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.104697E+11 | 0.267370E+10 | 359.21 | 0.743774E+10 | 0.303195E+10 | 0.00 | 1.00 | 0.00 | 24057.86 | 21160.88 | 12956.49 | 5220.95 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 72068957.81 | 19990151.26 | 7.17 | 65371138.80 | 6697819.01 | 0.00 | 0.35 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 6280.50 | 23-APR-16:00 | 5814.26 | 23-APR-16:00 | 541.71 | 23-APR-14:00 | 1776.29 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.215798E+10 | 0.590852E+09 | 136.82 | 0.193743E+10 | 0.220551E+09 | 0.00 | 1.00 | 18-MAY-07:02 | 0.00 | 01-MAY-00:05 | 22601.73 | 26-MAY-07:01 | 18122.01 | 18-MAY-07:02 | 6774.92 | 26-MAY-07:03 | 4798.46 | 26-MAY-07:01 | 0.00 | 01-MAY-00:05 |
June | 0.516704E+10 | 0.137501E+10 | 236.97 | 0.398157E+10 | 0.118547E+10 | 0.00 | 1.00 | 07-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24428.48 | 30-JUN-07:01 | 20703.16 | 18-JUN-08:62 | 11519.73 | 23-JUN-07:02 | 5250.64 | 30-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.778264E+10 | 0.204191E+10 | 300.46 | 0.566409E+10 | 0.211855E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 24398.52 | 23-JUL-08:61 | 16562.39 | 30-JUL-08:61 | 12242.60 | 05-JUL-07:03 | 5150.82 | 30-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.554207E+10 | 0.144882E+10 | 269.94 | 0.402314E+10 | 0.151893E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 23430.50 | 30-AUG-07:01 | 16401.61 | 20-AUG-08:62 | 11718.37 | 30-AUG-07:03 | 4923.59 | 30-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.831857E+09 | 0.221485E+09 | 89.65 | 0.700308E+09 | 0.131549E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 22800.78 | 01-SEP-07:01 | 14858.71 | 04-SEP-08:62 | 11018.73 | 01-SEP-07:03 | 4832.04 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 68232040.50 | 18839033.70 | 16.36 | 65838151.98 | 2393888.51 | 0.00 | 0.18 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 3093.20 | 19-OCT-15:00 | 3075.29 | 19-OCT-15:00 | 167.94 | 22-OCT-13:50 | 851.71 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.216219E+11 | 0.571691E+10 | 1057.37 | 0.164377E+11 | 0.518414E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.778264E+10 | 0.204191E+10 | 300.46 | 0.566409E+10 | 0.211855E+10 | 0.00 | 1.00 | 0.00 | 24428.48 | 20703.16 | 12242.60 | 5250.64 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 67862138.11 | 18887257.79 | 6.33 | 61512622.76 | 6349515.35 | 0.00 | 0.34 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 6062.16 | 23-APR-16:00 | 5608.36 | 23-APR-16:00 | 520.45 | 23-APR-14:00 | 1720.05 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.212712E+10 | 0.582873E+09 | 136.26 | 0.190781E+10 | 0.219310E+09 | 0.00 | 1.00 | 18-MAY-07:02 | 0.00 | 01-MAY-00:05 | 22659.69 | 26-MAY-07:01 | 18167.98 | 18-MAY-07:02 | 6784.14 | 26-MAY-07:03 | 4810.69 | 26-MAY-07:01 | 0.00 | 01-MAY-00:05 |
June | 0.515142E+10 | 0.137118E+10 | 237.33 | 0.396575E+10 | 0.118567E+10 | 0.00 | 1.00 | 07-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24480.31 | 30-JUN-07:01 | 20763.76 | 18-JUN-08:62 | 11549.49 | 23-JUN-07:02 | 5263.51 | 30-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.781577E+10 | 0.205032E+10 | 301.52 | 0.568675E+10 | 0.212902E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 24465.18 | 23-JUL-08:61 | 16626.81 | 30-JUL-08:61 | 12259.20 | 05-JUL-07:03 | 5163.42 | 30-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.553833E+10 | 0.144816E+10 | 269.96 | 0.401921E+10 | 0.151912E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 23489.87 | 30-AUG-07:01 | 16436.04 | 20-AUG-08:62 | 11743.13 | 30-AUG-07:03 | 4935.96 | 30-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.812941E+09 | 0.216473E+09 | 88.10 | 0.684020E+09 | 0.128922E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 22860.07 | 01-SEP-07:01 | 14901.92 | 04-SEP-08:62 | 11040.72 | 01-SEP-07:03 | 4844.47 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 59960902.96 | 16591376.52 | 16.53 | 57916610.36 | 2044292.59 | 0.00 | 0.17 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2891.62 | 19-OCT-15:00 | 2875.62 | 19-OCT-15:00 | 150.33 | 22-OCT-13:50 | 798.70 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.215734E+11 | 0.570449E+10 | 1056.03 | 0.163830E+11 | 0.519044E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.781577E+10 | 0.205032E+10 | 301.52 | 0.568675E+10 | 0.212902E+10 | 0.00 | 1.00 | 0.00 | 24480.31 | 20763.76 | 12259.20 | 5263.51 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 62031993.77 | 17345872.27 | 4.50 | 56166903.94 | 5865089.83 | 0.00 | 0.32 | 23-APR-16:00 | 0.00 | 01-APR-00:10 | 5727.13 | 23-APR-16:00 | 5288.81 | 23-APR-16:00 | 492.55 | 23-APR-14:00 | 1631.73 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.202134E+10 | 0.555273E+09 | 129.32 | 0.181027E+10 | 0.211071E+09 | 0.00 | 1.00 | 18-MAY-07:02 | 0.00 | 01-MAY-00:05 | 22521.76 | 26-MAY-07:01 | 18004.49 | 18-MAY-07:02 | 6786.19 | 26-MAY-07:03 | 4781.65 | 26-MAY-07:01 | 0.00 | 01-MAY-00:05 |
June | 0.497687E+10 | 0.132712E+10 | 232.99 | 0.382222E+10 | 0.115465E+10 | 0.00 | 1.00 | 07-JUN-07:02 | 0.00 | 01-JUN-00:10 | 24364.35 | 30-JUN-07:01 | 20595.30 | 18-JUN-08:62 | 11525.05 | 23-JUN-07:02 | 5233.39 | 30-JUN-07:01 | 0.00 | 01-JUN-00:10 |
July | 0.760451E+10 | 0.199803E+10 | 297.78 | 0.552562E+10 | 0.207890E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 24315.06 | 23-JUL-08:61 | 16478.03 | 30-JUL-08:61 | 12221.14 | 05-JUL-07:03 | 5133.82 | 30-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.535846E+10 | 0.140323E+10 | 267.31 | 0.388600E+10 | 0.147246E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 23349.27 | 30-AUG-07:01 | 16288.36 | 20-AUG-08:62 | 11712.18 | 30-AUG-07:03 | 4906.77 | 30-AUG-07:01 | 0.00 | 01-AUG-00:10 |
September | 0.756279E+09 | 0.201599E+09 | 78.35 | 0.636265E+09 | 0.120014E+09 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 22723.15 | 01-SEP-07:01 | 14777.73 | 04-SEP-08:62 | 11016.39 | 01-SEP-07:03 | 4815.65 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 |
October | 48745806.83 | 13534161.61 | 14.22 | 47149876.28 | 1595930.55 | 0.00 | 0.16 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2587.25 | 19-OCT-15:00 | 2570.94 | 19-OCT-15:00 | 126.48 | 22-OCT-14:00 | 717.73 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.208282E+11 | 0.551614E+10 | 1024.47 | 0.157837E+11 | 0.504455E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.760451E+10 | 0.199803E+10 | 297.78 | 0.552562E+10 | 0.207890E+10 | 0.00 | 1.00 | 0.00 | 24364.35 | 20595.30 | 12221.14 | 5233.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 0.102171E+09 | 29187638.13 | 3.83 | 90232362.01 | 11939047.96 | 0.00 | 0.32 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 10333.85 | 23-APR-15:00 | 9112.69 | 23-APR-15:00 | 1221.16 | 23-APR-15:00 | 2939.31 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.350398E+10 | 0.982538E+09 | 117.92 | 0.307634E+10 | 0.427640E+09 | 0.00 | 1.00 | 18-MAY-08:62 | 0.00 | 01-MAY-00:05 | 41276.64 | 26-MAY-08:61 | 34826.09 | 18-MAY-08:62 | 13107.60 | 26-MAY-08:03 | 8909.37 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 |
June | 0.874424E+10 | 0.237255E+10 | 219.93 | 0.657599E+10 | 0.216826E+10 | 0.00 | 1.00 | 07-JUN-08:62 | 0.00 | 01-JUN-00:10 | 44230.78 | 30-JUN-08:61 | 38027.32 | 07-JUN-08:62 | 21468.10 | 23-JUN-08:62 | 9712.37 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.134298E+11 | 0.358735E+10 | 285.39 | 0.957763E+10 | 0.385216E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 44275.54 | 23-JUL-09:01 | 30612.54 | 07-JUL-08:62 | 23147.86 | 05-JUL-08:04 | 9632.99 | 30-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.954107E+10 | 0.254320E+10 | 253.06 | 0.677001E+10 | 0.277105E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 43216.35 | 30-AUG-08:61 | 31948.81 | 20-AUG-09:02 | 21492.78 | 29-AUG-08:62 | 9178.35 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.126594E+10 | 0.343582E+09 | 68.43 | 0.105151E+10 | 0.214435E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 41888.43 | 01-SEP-08:62 | 28357.97 | 04-SEP-09:02 | 20400.58 | 19-SEP-08:62 | 9007.50 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 72137281.69 | 20427763.96 | 10.25 | 69286019.91 | 2851261.78 | 0.00 | 0.15 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 4573.28 | 19-OCT-15:00 | 4459.02 | 19-OCT-15:00 | 229.77 | 22-OCT-14:10 | 1292.93 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.366593E+11 | 0.987883E+10 | 958.81 | 0.272110E+11 | 0.944834E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.134298E+11 | 0.358735E+10 | 285.39 | 0.957763E+10 | 0.385216E+10 | 0.00 | 1.00 | 0.00 | 44275.54 | 38027.32 | 23147.86 | 9712.37 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 51059839.31 | 14350004.09 | 3.83 | 45211668.89 | 5848170.42 | 0.00 | 0.31 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 5266.42 | 23-APR-15:00 | 4654.49 | 23-APR-15:00 | 611.93 | 23-APR-15:00 | 1472.99 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.179273E+10 | 0.494054E+09 | 117.40 | 0.157733E+10 | 0.215394E+09 | 0.00 | 1.00 | 18-MAY-08:62 | 0.00 | 01-MAY-00:05 | 21277.88 | 26-MAY-08:61 | 17970.08 | 18-MAY-08:62 | 6745.86 | 26-MAY-08:03 | 4512.28 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 |
June | 0.449857E+10 | 0.119930E+10 | 219.38 | 0.338865E+10 | 0.110993E+10 | 0.00 | 1.00 | 07-JUN-08:62 | 0.00 | 01-JUN-00:10 | 22808.27 | 30-JUN-08:61 | 19631.70 | 07-JUN-08:62 | 11055.41 | 23-JUN-08:62 | 4919.07 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.692597E+10 | 0.181771E+10 | 285.75 | 0.495340E+10 | 0.197258E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 22842.41 | 23-JUL-09:01 | 15796.81 | 07-JUL-08:62 | 11825.70 | 05-JUL-08:03 | 4879.62 | 30-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.491826E+10 | 0.128795E+10 | 252.32 | 0.350074E+10 | 0.141752E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22279.18 | 30-AUG-08:61 | 16486.36 | 20-AUG-09:02 | 11068.56 | 29-AUG-08:62 | 4648.75 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.647078E+09 | 0.172556E+09 | 66.84 | 0.539052E+09 | 0.108026E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 21594.68 | 01-SEP-08:62 | 14645.86 | 04-SEP-09:02 | 10115.28 | 01-SEP-08:62 | 4562.22 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 36827721.35 | 10245349.36 | 10.08 | 35448234.89 | 1379486.46 | 0.00 | 0.15 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2377.90 | 19-OCT-15:00 | 2325.14 | 19-OCT-15:00 | 114.52 | 22-OCT-14:10 | 660.27 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.188705E+11 | 0.499617E+10 | 955.60 | 0.140398E+11 | 0.483067E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.692597E+10 | 0.181771E+10 | 285.75 | 0.495340E+10 | 0.197258E+10 | 0.00 | 1.00 | 0.00 | 22842.41 | 19631.70 | 11825.70 | 4919.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 48539996.63 | 13676997.91 | 3.83 | 42936723.15 | 5603273.48 | 0.00 | 0.31 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 5079.11 | 23-APR-15:00 | 4482.68 | 23-APR-15:00 | 596.44 | 23-APR-15:00 | 1424.04 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.173944E+10 | 0.480073E+09 | 116.24 | 0.152870E+10 | 0.210742E+09 | 0.00 | 1.00 | 18-MAY-08:62 | 0.00 | 01-MAY-00:05 | 21185.11 | 26-MAY-08:61 | 17858.85 | 18-MAY-08:62 | 6636.08 | 26-MAY-08:03 | 4492.73 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 |
June | 0.441543E+10 | 0.117791E+10 | 218.38 | 0.331913E+10 | 0.109631E+10 | 0.00 | 1.00 | 07-JUN-08:62 | 0.00 | 01-JUN-00:10 | 22710.71 | 30-JUN-08:61 | 19513.64 | 07-JUN-08:62 | 11027.60 | 23-JUN-08:62 | 4898.32 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.683207E+10 | 0.179411E+10 | 285.08 | 0.488009E+10 | 0.195197E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 22753.24 | 23-JUL-09:01 | 15707.76 | 07-JUL-08:62 | 11793.77 | 05-JUL-08:03 | 4859.11 | 30-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.483707E+10 | 0.126746E+10 | 251.71 | 0.344045E+10 | 0.139662E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22183.31 | 30-AUG-08:61 | 16383.99 | 20-AUG-09:02 | 11037.81 | 29-AUG-08:62 | 4628.89 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.625140E+09 | 0.166774E+09 | 65.17 | 0.520098E+09 | 0.105042E+09 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 21501.67 | 01-SEP-08:62 | 14561.12 | 04-SEP-09:02 | 10090.46 | 01-SEP-08:62 | 4542.66 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 33041317.80 | 9205264.18 | 10.25 | 31828916.53 | 1212401.27 | 0.00 | 0.15 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 2270.21 | 19-OCT-15:00 | 2218.38 | 19-OCT-15:00 | 102.75 | 22-OCT-14:10 | 631.36 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.185307E+11 | 0.490921E+10 | 950.66 | 0.137632E+11 | 0.476750E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.683207E+10 | 0.179411E+10 | 285.08 | 0.488009E+10 | 0.195197E+10 | 0.00 | 1.00 | 0.00 | 22753.24 | 19513.64 | 11793.77 | 4898.32 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 42576772.47 | 12081741.81 | 3.83 | 37599631.14 | 4977141.33 | 0.00 | 0.28 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 4620.70 | 23-APR-15:00 | 4067.27 | 23-APR-15:00 | 553.43 | 23-APR-15:00 | 1304.78 | 23-APR-15:00 | 0.00 | 01-APR-00:10 |
May | 0.161333E+10 | 0.447449E+09 | 109.38 | 0.141552E+10 | 0.197815E+09 | 0.00 | 1.00 | 25-MAY-08:62 | 0.00 | 01-MAY-00:05 | 21281.37 | 26-MAY-08:61 | 16216.46 | 27-MAY-08:62 | 6718.58 | 26-MAY-08:61 | 4513.50 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 |
June | 0.422493E+10 | 0.113044E+10 | 212.09 | 0.316380E+10 | 0.106113E+10 | 0.00 | 1.00 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 | 22812.54 | 30-JUN-08:61 | 18854.29 | 18-JUN-09:02 | 11140.62 | 23-JUN-08:62 | 4922.41 | 30-JUN-08:13 | 0.00 | 01-JUN-00:10 |
July | 0.663437E+10 | 0.174676E+10 | 280.67 | 0.473159E+10 | 0.190277E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 22878.57 | 23-JUL-09:01 | 15736.39 | 07-JUL-08:62 | 11900.45 | 05-JUL-08:03 | 4883.17 | 23-JUL-09:13 | 0.00 | 01-JUL-00:05 |
August | 0.464628E+10 | 0.122069E+10 | 245.15 | 0.330427E+10 | 0.134201E+10 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 22288.92 | 30-AUG-08:61 | 16220.34 | 06-AUG-09:02 | 11140.39 | 29-AUG-08:62 | 4651.31 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.569613E+09 | 0.152189E+09 | 58.20 | 0.472306E+09 | 97306546.27 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 21604.31 | 01-SEP-08:62 | 13800.97 | 02-SEP-08:62 | 10189.13 | 01-SEP-08:62 | 4564.55 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 23710998.49 | 6635267.57 | 7.83 | 22895837.93 | 815160.56 | 0.00 | 0.13 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1994.59 | 19-OCT-15:00 | 1948.09 | 19-OCT-15:00 | 74.63 | 19-OCT-14:10 | 557.28 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.177548E+11 | 0.471626E+10 | 917.16 | 0.131480E+11 | 0.460683E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.663437E+10 | 0.174676E+10 | 280.67 | 0.473159E+10 | 0.190277E+10 | 0.00 | 1.00 | 0.00 | 22878.57 | 18854.29 | 11900.45 | 4922.41 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 | 0.00 | 01-JAN-00:03 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 | 0.00 | 01-FEB-00:03 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 | 0.00 | 01-MAR-00:05 |
April | 34220059.06 | 9888912.34 | 3.17 | 30385110.34 | 3834948.72 | 0.00 | 0.21 | 23-APR-15:00 | 0.00 | 01-APR-00:10 | 4059.25 | 23-APR-15:00 | 3586.33 | 23-APR-15:00 | 472.92 | 23-APR-15:00 | 1171.43 | 23-APR-16:00 | 0.00 | 01-APR-00:10 |
May | 0.149803E+10 | 0.422569E+09 | 99.22 | 0.132347E+10 | 0.174561E+09 | 0.00 | 1.00 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 | 25638.12 | 26-MAY-08:61 | 17389.99 | 26-MAY-08:61 | 8248.13 | 26-MAY-08:61 | 5437.28 | 26-MAY-08:61 | 0.00 | 01-MAY-00:05 |
June | 0.418763E+10 | 0.114098E+10 | 198.64 | 0.315648E+10 | 0.103115E+10 | 0.00 | 1.00 | 18-JUN-09:02 | 0.00 | 01-JUN-00:10 | 27906.22 | 30-JUN-08:61 | 22943.15 | 18-JUN-09:02 | 12886.00 | 30-JUN-08:04 | 5923.07 | 30-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.676999E+10 | 0.181103E+10 | 265.18 | 0.488885E+10 | 0.188113E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 27616.54 | 23-JUL-09:01 | 18962.34 | 07-JUL-08:62 | 14482.52 | 05-JUL-08:61 | 5882.43 | 30-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.453094E+10 | 0.120831E+10 | 222.86 | 0.327315E+10 | 0.125779E+10 | 0.00 | 1.00 | 06-AUG-09:02 | 0.00 | 01-AUG-00:10 | 26837.57 | 30-AUG-08:61 | 19570.30 | 06-AUG-09:02 | 13434.70 | 29-AUG-08:62 | 5601.45 | 30-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.485774E+09 | 0.130760E+09 | 42.76 | 0.402320E+09 | 83453926.76 | 0.00 | 1.00 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 | 26011.61 | 01-SEP-08:62 | 13704.82 | 01-SEP-08:62 | 12306.79 | 01-SEP-08:62 | 5496.37 | 01-SEP-08:62 | 0.00 | 01-SEP-00:03 |
October | 9125107.52 | 2582737.57 | 2.83 | 8889397.69 | 235709.84 | 0.00 | 0.09 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 | 1570.94 | 19-OCT-15:00 | 1550.63 | 19-OCT-15:00 | 41.28 | 19-OCT-14:10 | 443.86 | 19-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 | 0.00 | 01-NOV-00:05 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 | 0.00 | 01-DEC-00:02 |
Annual Sum or Average | 0.175157E+11 | 0.472611E+10 | 834.64 | 0.130835E+11 | 0.443217E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.676999E+10 | 0.181103E+10 | 265.18 | 0.488885E+10 | 0.188113E+10 | 0.00 | 1.00 | 0.00 | 27906.22 | 22943.15 | 14482.52 | 5923.07 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.66 | 113.44 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.95 | 93.81 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.80 | 75.93 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 150.09 | 50.12 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.57 | 29.64 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.74 | 20.78 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.72 | 19.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.99 | 22.96 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.41 | 36.04 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.47 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.29 | 72.55 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 86.03 | 109.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.12 | 57.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 86.03 | 19.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.95 | 113.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.66 | 113.44 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.95 | 93.81 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.80 | 75.93 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 150.09 | 50.12 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.57 | 29.64 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.74 | 20.78 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.72 | 19.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.99 | 22.96 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.41 | 36.04 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.47 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.29 | 72.55 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 86.03 | 109.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.12 | 57.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 86.03 | 19.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.95 | 113.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.66 | 113.44 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.95 | 93.81 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.80 | 75.93 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 150.09 | 50.12 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.57 | 29.64 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.74 | 20.78 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.72 | 19.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.99 | 22.96 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.41 | 36.04 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.47 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.29 | 72.55 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 86.03 | 109.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.12 | 57.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 86.03 | 19.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.95 | 113.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.66 | 113.44 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.95 | 93.81 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.80 | 75.93 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 150.09 | 50.12 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.57 | 29.64 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.74 | 20.78 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.72 | 19.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.99 | 22.96 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.41 | 36.04 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.47 | 51.02 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.29 | 72.55 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 86.03 | 109.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.12 | 57.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 86.03 | 19.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.95 | 113.44 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.76 | 111.00 | 48.75 | 144.40 | 134.87 | 0.00 | 0.00 | 0.00 |
February | 202.56 | 136.72 | 65.84 | 203.70 | 111.59 | 0.00 | 0.00 | 0.00 |
March | 178.90 | 113.28 | 65.62 | 184.07 | 90.38 | 0.00 | 0.00 | 0.00 |
April | 162.39 | 88.35 | 74.04 | 180.70 | 59.74 | 0.00 | 0.00 | 0.00 |
May | 136.59 | 46.99 | 89.60 | 161.89 | 35.40 | 0.00 | 0.00 | 0.00 |
June | 122.57 | 32.97 | 89.60 | 152.36 | 24.86 | 0.00 | 0.00 | 0.00 |
July | 134.03 | 42.78 | 91.25 | 172.72 | 23.07 | 0.00 | 0.00 | 0.00 |
August | 143.05 | 60.08 | 82.97 | 179.16 | 27.45 | 0.00 | 0.00 | 0.00 |
September | 153.03 | 81.61 | 71.42 | 179.78 | 43.01 | 0.00 | 0.00 | 0.00 |
October | 130.44 | 76.70 | 53.73 | 139.04 | 60.85 | 0.00 | 0.00 | 0.00 |
November | 115.95 | 72.67 | 43.28 | 111.30 | 86.34 | 0.00 | 0.00 | 0.00 |
December | 123.33 | 80.74 | 42.59 | 103.91 | 129.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.52 | 78.29 | 68.23 | 159.09 | 68.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.95 | 32.97 | 42.59 | 103.91 | 23.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.56 | 136.72 | 91.25 | 203.70 | 134.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.76 | 111.00 | 48.75 | 144.40 | 134.87 | 0.00 | 0.00 | 0.00 |
February | 202.56 | 136.72 | 65.84 | 203.70 | 111.59 | 0.00 | 0.00 | 0.00 |
March | 178.90 | 113.28 | 65.62 | 184.07 | 90.38 | 0.00 | 0.00 | 0.00 |
April | 162.39 | 88.35 | 74.04 | 180.70 | 59.74 | 0.00 | 0.00 | 0.00 |
May | 136.59 | 46.99 | 89.60 | 161.89 | 35.40 | 0.00 | 0.00 | 0.00 |
June | 122.57 | 32.97 | 89.60 | 152.36 | 24.86 | 0.00 | 0.00 | 0.00 |
July | 134.03 | 42.78 | 91.25 | 172.72 | 23.07 | 0.00 | 0.00 | 0.00 |
August | 143.05 | 60.08 | 82.97 | 179.16 | 27.45 | 0.00 | 0.00 | 0.00 |
September | 153.03 | 81.61 | 71.42 | 179.78 | 43.01 | 0.00 | 0.00 | 0.00 |
October | 130.44 | 76.70 | 53.73 | 139.04 | 60.85 | 0.00 | 0.00 | 0.00 |
November | 115.95 | 72.67 | 43.28 | 111.30 | 86.34 | 0.00 | 0.00 | 0.00 |
December | 123.33 | 80.74 | 42.59 | 103.91 | 129.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.52 | 78.29 | 68.23 | 159.09 | 68.77 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.95 | 32.97 | 42.59 | 103.91 | 23.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.56 | 136.72 | 91.25 | 203.70 | 134.87 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.49 | 116.98 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.47 | 97.46 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.41 | 79.71 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 148.36 | 53.82 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.20 | 31.20 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.97 | 21.48 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.37 | 19.51 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.58 | 23.40 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.43 | 37.57 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.25 | 54.29 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.20 | 76.08 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.03 | 113.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.05 | 60.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.03 | 19.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.47 | 116.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.49 | 116.98 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.47 | 97.46 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.41 | 79.71 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 148.36 | 53.82 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.20 | 31.20 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.97 | 21.48 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.37 | 19.51 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.58 | 23.40 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.43 | 37.57 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.25 | 54.29 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.20 | 76.08 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.03 | 113.08 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.05 | 60.22 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.03 | 19.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.47 | 116.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 159.76 | 111.00 | 48.75 | 143.02 | 139.06 | 0.00 | 0.00 | 0.00 |
February | 202.56 | 136.72 | 65.84 | 201.96 | 115.92 | 0.00 | 0.00 | 0.00 |
March | 178.90 | 113.28 | 65.62 | 182.42 | 94.86 | 0.00 | 0.00 | 0.00 |
April | 162.39 | 88.35 | 74.04 | 178.64 | 64.10 | 0.00 | 0.00 | 0.00 |
May | 136.59 | 46.99 | 89.60 | 160.27 | 37.25 | 0.00 | 0.00 | 0.00 |
June | 122.57 | 32.97 | 89.60 | 151.46 | 25.70 | 0.00 | 0.00 | 0.00 |
July | 134.03 | 42.78 | 91.25 | 172.32 | 23.37 | 0.00 | 0.00 | 0.00 |
August | 143.05 | 60.08 | 82.97 | 178.68 | 27.97 | 0.00 | 0.00 | 0.00 |
September | 153.03 | 81.61 | 71.42 | 178.63 | 44.81 | 0.00 | 0.00 | 0.00 |
October | 130.44 | 76.70 | 53.73 | 137.61 | 64.70 | 0.00 | 0.00 | 0.00 |
November | 115.95 | 72.67 | 43.28 | 110.00 | 90.51 | 0.00 | 0.00 | 0.00 |
December | 123.33 | 80.74 | 42.59 | 102.72 | 134.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 146.52 | 78.29 | 68.23 | 157.82 | 71.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.95 | 32.97 | 42.59 | 102.72 | 23.37 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 202.56 | 136.72 | 91.25 | 201.96 | 139.06 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.52 | 114.97 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.50 | 95.87 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.41 | 78.45 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 148.51 | 52.85 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.16 | 31.72 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.67 | 22.59 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.83 | 21.10 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.34 | 24.86 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.42 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.47 | 53.36 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.34 | 74.62 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.04 | 111.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.00 | 59.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.04 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.50 | 114.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.52 | 114.97 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.50 | 95.87 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.41 | 78.45 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 148.51 | 52.85 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.16 | 31.72 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.67 | 22.59 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.83 | 21.10 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.34 | 24.86 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.42 | 38.29 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.47 | 53.36 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.34 | 74.62 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.04 | 111.21 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.00 | 59.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.04 | 21.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.50 | 114.97 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 142.28 | 135.93 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 200.90 | 113.42 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 181.43 | 92.86 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 177.86 | 62.63 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 159.34 | 37.65 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 150.28 | 26.85 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.73 | 25.10 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.41 | 29.53 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 177.65 | 45.41 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 137.12 | 63.25 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 109.58 | 88.29 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 102.18 | 131.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 156.91 | 70.85 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 102.18 | 25.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 200.90 | 135.93 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.63 | 114.20 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.64 | 95.14 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.54 | 77.79 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 148.73 | 52.19 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.32 | 31.43 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.71 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.80 | 21.17 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.34 | 24.88 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.52 | 38.04 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.67 | 52.69 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.48 | 73.85 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.13 | 110.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.11 | 59.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.13 | 21.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.64 | 114.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.63 | 114.20 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.64 | 95.14 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.54 | 77.79 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 148.73 | 52.19 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.32 | 31.43 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.71 | 22.52 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.80 | 21.17 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.34 | 24.88 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.52 | 38.04 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.67 | 52.69 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.48 | 73.85 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.13 | 110.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.11 | 59.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.13 | 21.17 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.64 | 114.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 142.41 | 135.02 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 201.07 | 112.55 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 181.58 | 92.08 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 178.12 | 61.84 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 159.53 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 150.33 | 26.77 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.70 | 25.18 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.41 | 29.55 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 177.77 | 45.11 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 137.35 | 62.45 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 109.75 | 87.39 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 102.29 | 130.52 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 157.04 | 70.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 102.29 | 25.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 201.07 | 135.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.76 | 113.65 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.83 | 94.52 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.72 | 77.19 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.03 | 51.54 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.65 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.91 | 22.23 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.92 | 20.95 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.45 | 24.63 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.77 | 37.57 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.93 | 52.03 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.67 | 73.19 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.25 | 109.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.31 | 58.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.25 | 20.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.83 | 113.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 118.76 | 113.65 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 167.83 | 94.52 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 151.72 | 77.19 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.03 | 51.54 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 133.65 | 30.96 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 125.91 | 22.23 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.92 | 20.95 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.45 | 24.63 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 148.77 | 37.57 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 114.93 | 52.03 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 91.67 | 73.19 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.25 | 109.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.31 | 58.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.25 | 20.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 167.83 | 113.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 142.57 | 134.36 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 201.29 | 111.82 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 181.81 | 91.36 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 178.48 | 61.07 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 159.93 | 36.75 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 150.57 | 26.43 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.85 | 24.93 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.55 | 29.26 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 178.06 | 44.57 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 137.66 | 61.68 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 109.97 | 86.60 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 102.44 | 129.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 157.28 | 69.71 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 102.44 | 24.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 201.29 | 134.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.55 | 111.63 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.82 | 92.59 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.53 | 75.41 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.79 | 50.03 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.22 | 29.86 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.20 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.94 | 20.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.52 | 23.87 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.16 | 36.51 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.50 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.34 | 71.36 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.94 | 107.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.86 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.94 | 20.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.82 | 111.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.55 | 111.63 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.82 | 92.59 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.53 | 75.41 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.79 | 50.03 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.22 | 29.86 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.20 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.94 | 20.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.52 | 23.87 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.16 | 36.51 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.50 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.34 | 71.36 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.94 | 107.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.86 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.94 | 20.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.82 | 111.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.55 | 111.63 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.82 | 92.59 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.53 | 75.41 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.79 | 50.03 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.22 | 29.86 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.20 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.94 | 20.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.52 | 23.87 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.16 | 36.51 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.50 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.34 | 71.36 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.94 | 107.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.86 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.94 | 20.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.82 | 111.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.55 | 111.63 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.82 | 92.59 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.53 | 75.41 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.79 | 50.03 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.22 | 29.86 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.20 | 21.41 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.94 | 20.26 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.52 | 23.87 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.16 | 36.51 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.50 | 50.67 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.34 | 71.36 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.94 | 107.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.86 | 57.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.94 | 20.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.82 | 111.63 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 143.50 | 132.02 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 202.44 | 109.57 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 182.74 | 89.28 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 179.36 | 59.30 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 160.59 | 35.47 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 150.91 | 25.47 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.87 | 24.11 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.63 | 28.37 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 178.51 | 43.32 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 138.33 | 60.08 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 110.76 | 84.46 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 103.24 | 127.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 157.91 | 68.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 103.24 | 24.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 202.44 | 132.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 143.50 | 132.02 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 202.44 | 109.57 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 182.74 | 89.28 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 179.36 | 59.30 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 160.59 | 35.47 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 150.91 | 25.47 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.87 | 24.11 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.63 | 28.37 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 178.51 | 43.32 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 138.33 | 60.08 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 110.76 | 84.46 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 103.24 | 127.35 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 157.91 | 68.06 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 103.24 | 24.11 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 202.44 | 132.02 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.14 | 112.30 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.36 | 93.08 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.19 | 75.72 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.58 | 50.03 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.16 | 29.71 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.20 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.94 | 20.07 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.44 | 23.70 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.03 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.33 | 50.63 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.08 | 71.66 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.60 | 108.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.65 | 57.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.60 | 20.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.36 | 112.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.14 | 112.30 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.36 | 93.08 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.19 | 75.72 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.58 | 50.03 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.16 | 29.71 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.20 | 21.24 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 142.94 | 20.07 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.44 | 23.70 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.03 | 36.37 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.33 | 50.63 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.08 | 71.66 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.60 | 108.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.65 | 57.60 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.60 | 20.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.36 | 112.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 143.03 | 132.76 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 201.94 | 110.10 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 182.38 | 89.62 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 179.15 | 59.29 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 160.55 | 35.28 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 150.92 | 25.26 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.88 | 23.88 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.55 | 28.16 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 178.38 | 43.14 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 138.15 | 60.02 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 110.48 | 84.79 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 102.86 | 128.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 157.70 | 68.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 102.86 | 23.88 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 201.94 | 132.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.16 | 112.20 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.41 | 92.93 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.25 | 75.52 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.74 | 49.72 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.38 | 29.45 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.36 | 21.07 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.03 | 19.97 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.52 | 23.58 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.18 | 36.12 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.46 | 50.34 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.15 | 71.42 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.62 | 108.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.75 | 57.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.62 | 19.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.41 | 112.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.16 | 112.20 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.41 | 92.93 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.25 | 75.52 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 149.74 | 49.72 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.38 | 29.45 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.36 | 21.07 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.03 | 19.97 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.52 | 23.58 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.18 | 36.12 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.46 | 50.34 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.15 | 71.42 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.62 | 108.34 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 131.75 | 57.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.62 | 19.97 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.41 | 112.20 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 143.06 | 132.64 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 202.00 | 109.93 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 182.45 | 89.38 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 179.34 | 58.92 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 160.81 | 34.97 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 151.12 | 25.06 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 170.99 | 23.76 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.65 | 28.02 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 178.56 | 42.85 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 138.31 | 59.67 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 110.56 | 84.50 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 102.89 | 128.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 157.82 | 67.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 102.89 | 23.76 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 202.00 | 132.64 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.30 | 111.51 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.62 | 92.10 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.51 | 74.54 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 150.20 | 48.62 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.97 | 28.70 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.77 | 20.60 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.23 | 19.71 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.71 | 23.26 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.53 | 35.47 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.80 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.41 | 70.44 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.75 | 107.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.05 | 56.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.75 | 19.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.62 | 111.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 119.30 | 111.51 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 168.62 | 92.10 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 152.51 | 74.54 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 150.20 | 48.62 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 134.97 | 28.70 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 126.77 | 20.60 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.23 | 19.71 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 148.71 | 23.26 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 149.53 | 35.47 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 115.80 | 49.43 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 92.41 | 70.44 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 85.75 | 107.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.05 | 56.68 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 85.75 | 19.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 168.62 | 111.51 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 143.23 | 131.83 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 202.25 | 108.94 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 182.77 | 88.21 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 179.89 | 57.62 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 161.52 | 34.08 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 151.61 | 24.50 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 171.23 | 23.46 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 177.88 | 27.64 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 178.98 | 42.07 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 138.73 | 58.60 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 110.87 | 83.33 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 103.04 | 127.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 158.17 | 67.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 103.04 | 23.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 202.25 | 131.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 120.21 | 107.90 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 169.67 | 88.33 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 153.60 | 70.26 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 151.54 | 44.49 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 136.46 | 26.18 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 127.74 | 18.95 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.65 | 18.69 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 149.18 | 22.02 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 150.38 | 33.32 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 116.77 | 46.32 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 93.32 | 66.50 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 86.53 | 103.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.98 | 53.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 86.53 | 18.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 169.67 | 107.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 132.89 | 92.34 | 40.56 | 120.21 | 107.90 | 0.00 | 0.00 | 0.00 |
February | 168.50 | 113.73 | 54.77 | 169.67 | 88.33 | 0.00 | 0.00 | 0.00 |
March | 148.82 | 94.23 | 54.59 | 153.60 | 70.26 | 0.00 | 0.00 | 0.00 |
April | 135.08 | 73.49 | 61.59 | 151.54 | 44.49 | 0.00 | 0.00 | 0.00 |
May | 113.62 | 39.09 | 74.53 | 136.46 | 26.18 | 0.00 | 0.00 | 0.00 |
June | 101.96 | 27.42 | 74.53 | 127.74 | 18.95 | 0.00 | 0.00 | 0.00 |
July | 111.50 | 35.59 | 75.91 | 143.65 | 18.69 | 0.00 | 0.00 | 0.00 |
August | 118.99 | 49.97 | 69.02 | 149.18 | 22.02 | 0.00 | 0.00 | 0.00 |
September | 127.30 | 67.89 | 59.41 | 150.38 | 33.32 | 0.00 | 0.00 | 0.00 |
October | 108.50 | 63.81 | 44.70 | 116.77 | 46.32 | 0.00 | 0.00 | 0.00 |
November | 96.45 | 60.45 | 36.00 | 93.32 | 66.50 | 0.00 | 0.00 | 0.00 |
December | 102.59 | 67.17 | 35.43 | 86.53 | 103.81 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 121.88 | 65.12 | 56.76 | 132.98 | 53.76 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 96.45 | 27.42 | 35.43 | 86.53 | 18.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.50 | 113.73 | 75.91 | 169.67 | 107.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 158.88 | 110.40 | 48.49 | 144.34 | 127.50 | 0.00 | 0.00 | 0.00 |
February | 201.46 | 135.97 | 65.48 | 203.52 | 104.44 | 0.00 | 0.00 | 0.00 |
March | 177.93 | 112.66 | 65.27 | 184.09 | 83.12 | 0.00 | 0.00 | 0.00 |
April | 161.50 | 87.87 | 73.64 | 181.51 | 52.73 | 0.00 | 0.00 | 0.00 |
May | 135.85 | 46.73 | 89.11 | 163.30 | 31.11 | 0.00 | 0.00 | 0.00 |
June | 121.90 | 32.79 | 89.11 | 152.76 | 22.54 | 0.00 | 0.00 | 0.00 |
July | 133.30 | 42.55 | 90.75 | 171.73 | 22.25 | 0.00 | 0.00 | 0.00 |
August | 142.27 | 59.75 | 82.52 | 178.43 | 26.18 | 0.00 | 0.00 | 0.00 |
September | 152.19 | 81.17 | 71.02 | 180.00 | 39.54 | 0.00 | 0.00 | 0.00 |
October | 129.72 | 76.28 | 53.44 | 139.90 | 54.92 | 0.00 | 0.00 | 0.00 |
November | 115.32 | 72.28 | 43.04 | 111.98 | 78.67 | 0.00 | 0.00 | 0.00 |
December | 122.66 | 80.30 | 42.36 | 104.00 | 122.60 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 145.72 | 77.86 | 67.86 | 159.30 | 63.63 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 115.32 | 32.79 | 42.36 | 104.00 | 22.25 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 201.46 | 135.97 | 90.75 | 203.52 | 127.50 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320488E+09 | 0.303842E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408720E+09 | 0.226944E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.409248E+09 | 0.203379E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.389030E+09 | 0.129920E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.360426E+09 | 79385301.49 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.328497E+09 | 53856887.01 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384933E+09 | 51580500.94 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.399063E+09 | 61490405.88 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.387264E+09 | 93404736.52 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309266E+09 | 0.136661E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239208E+09 | 0.188051E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230426E+09 | 0.292769E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.416657E+10 | 0.182128E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230426E+09 | 51580500.94 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.409248E+09 | 0.303842E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320488E+09 | 0.303842E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408720E+09 | 0.226944E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.409248E+09 | 0.203379E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.389030E+09 | 0.129920E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.360426E+09 | 79385301.49 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.328497E+09 | 53856887.01 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384933E+09 | 51580500.94 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.399063E+09 | 61490405.88 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.387264E+09 | 93404736.52 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309266E+09 | 0.136661E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239208E+09 | 0.188051E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230426E+09 | 0.292769E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.416657E+10 | 0.182128E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230426E+09 | 51580500.94 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.409248E+09 | 0.303842E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320488E+09 | 0.303842E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408720E+09 | 0.226944E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.409248E+09 | 0.203379E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.389030E+09 | 0.129920E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.360426E+09 | 79385301.49 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.328497E+09 | 53856887.01 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384933E+09 | 51580500.94 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.399063E+09 | 61490405.88 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.387264E+09 | 93404736.52 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309266E+09 | 0.136661E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239208E+09 | 0.188051E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230426E+09 | 0.292769E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.416657E+10 | 0.182128E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230426E+09 | 51580500.94 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.409248E+09 | 0.303842E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320488E+09 | 0.303842E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408720E+09 | 0.226944E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.409248E+09 | 0.203379E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.389030E+09 | 0.129920E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.360426E+09 | 79385301.49 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.328497E+09 | 53856887.01 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384933E+09 | 51580500.94 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.399063E+09 | 61490405.88 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.387264E+09 | 93404736.52 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309266E+09 | 0.136661E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239208E+09 | 0.188051E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230426E+09 | 0.292769E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.416657E+10 | 0.182128E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230426E+09 | 51580500.94 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.409248E+09 | 0.303842E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427891E+09 | 0.297308E+09 | 0.130583E+09 | 0.386773E+09 | 0.361236E+09 |
February | 0.490039E+09 | 0.330757E+09 | 0.159282E+09 | 0.492800E+09 | 0.269966E+09 |
March | 0.479176E+09 | 0.303409E+09 | 0.175766E+09 | 0.493017E+09 | 0.242070E+09 |
April | 0.420920E+09 | 0.229004E+09 | 0.191916E+09 | 0.468384E+09 | 0.154847E+09 |
May | 0.365848E+09 | 0.125862E+09 | 0.239986E+09 | 0.433593E+09 | 94828134.44 |
June | 0.317696E+09 | 85454633.93 | 0.232242E+09 | 0.394927E+09 | 64442380.79 |
July | 0.358998E+09 | 0.114595E+09 | 0.244403E+09 | 0.462601E+09 | 61779583.06 |
August | 0.383143E+09 | 0.160910E+09 | 0.222233E+09 | 0.479850E+09 | 73531294.77 |
September | 0.396653E+09 | 0.211545E+09 | 0.185108E+09 | 0.465986E+09 | 0.111475E+09 |
October | 0.349362E+09 | 0.205444E+09 | 0.143918E+09 | 0.372418E+09 | 0.162968E+09 |
November | 0.300552E+09 | 0.188372E+09 | 0.112180E+09 | 0.288485E+09 | 0.223781E+09 |
December | 0.330334E+09 | 0.216267E+09 | 0.114067E+09 | 0.278319E+09 | 0.347903E+09 |
Annual Sum or Average | 0.462061E+10 | 0.246893E+10 | 0.215168E+10 | 0.501715E+10 | 0.216883E+10 |
Minimum of Months | 0.300552E+09 | 85454633.93 | 0.112180E+09 | 0.278319E+09 | 61779583.06 |
Maximum of Months | 0.490039E+09 | 0.330757E+09 | 0.244403E+09 | 0.493017E+09 | 0.361236E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427891E+09 | 0.297308E+09 | 0.130583E+09 | 0.386773E+09 | 0.361236E+09 |
February | 0.490039E+09 | 0.330757E+09 | 0.159282E+09 | 0.492800E+09 | 0.269966E+09 |
March | 0.479176E+09 | 0.303409E+09 | 0.175766E+09 | 0.493017E+09 | 0.242070E+09 |
April | 0.420920E+09 | 0.229004E+09 | 0.191916E+09 | 0.468384E+09 | 0.154847E+09 |
May | 0.365848E+09 | 0.125862E+09 | 0.239986E+09 | 0.433593E+09 | 94828134.44 |
June | 0.317696E+09 | 85454633.93 | 0.232242E+09 | 0.394927E+09 | 64442380.79 |
July | 0.358998E+09 | 0.114595E+09 | 0.244403E+09 | 0.462601E+09 | 61779583.06 |
August | 0.383143E+09 | 0.160910E+09 | 0.222233E+09 | 0.479850E+09 | 73531294.77 |
September | 0.396653E+09 | 0.211545E+09 | 0.185108E+09 | 0.465986E+09 | 0.111475E+09 |
October | 0.349362E+09 | 0.205444E+09 | 0.143918E+09 | 0.372418E+09 | 0.162968E+09 |
November | 0.300552E+09 | 0.188372E+09 | 0.112180E+09 | 0.288485E+09 | 0.223781E+09 |
December | 0.330334E+09 | 0.216267E+09 | 0.114067E+09 | 0.278319E+09 | 0.347903E+09 |
Annual Sum or Average | 0.462061E+10 | 0.246893E+10 | 0.215168E+10 | 0.501715E+10 | 0.216883E+10 |
Minimum of Months | 0.300552E+09 | 85454633.93 | 0.112180E+09 | 0.278319E+09 | 61779583.06 |
Maximum of Months | 0.490039E+09 | 0.330757E+09 | 0.244403E+09 | 0.493017E+09 | 0.361236E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.317374E+09 | 0.313327E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.405153E+09 | 0.235786E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.405538E+09 | 0.213500E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.384540E+09 | 0.139489E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.356776E+09 | 83562586.65 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.326508E+09 | 55686399.70 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384008E+09 | 52255154.17 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397967E+09 | 62673686.39 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.384721E+09 | 97369344.40 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.306019E+09 | 0.145418E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.236383E+09 | 0.197205E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.227733E+09 | 0.302887E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.413272E+10 | 0.189916E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.227733E+09 | 52255154.17 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.405538E+09 | 0.313327E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.317374E+09 | 0.313327E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.405153E+09 | 0.235786E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.405538E+09 | 0.213500E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.384540E+09 | 0.139489E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.356776E+09 | 83562586.65 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.326508E+09 | 55686399.70 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384008E+09 | 52255154.17 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397967E+09 | 62673686.39 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.384721E+09 | 97369344.40 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.306019E+09 | 0.145418E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.236383E+09 | 0.197205E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.227733E+09 | 0.302887E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.413272E+10 | 0.189916E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.227733E+09 | 52255154.17 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.405538E+09 | 0.313327E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.427891E+09 | 0.297308E+09 | 0.130583E+09 | 0.383069E+09 | 0.372451E+09 |
February | 0.490039E+09 | 0.330757E+09 | 0.159282E+09 | 0.488579E+09 | 0.280427E+09 |
March | 0.479176E+09 | 0.303409E+09 | 0.175766E+09 | 0.488601E+09 | 0.254066E+09 |
April | 0.420920E+09 | 0.229004E+09 | 0.191916E+09 | 0.463043E+09 | 0.166156E+09 |
May | 0.365848E+09 | 0.125862E+09 | 0.239986E+09 | 0.429275E+09 | 99768199.85 |
June | 0.317696E+09 | 85454633.93 | 0.232242E+09 | 0.392578E+09 | 66620709.06 |
July | 0.358998E+09 | 0.114595E+09 | 0.244403E+09 | 0.461532E+09 | 62584246.20 |
August | 0.383143E+09 | 0.160910E+09 | 0.222233E+09 | 0.478586E+09 | 74925700.68 |
September | 0.396653E+09 | 0.211545E+09 | 0.185108E+09 | 0.463008E+09 | 0.116150E+09 |
October | 0.349362E+09 | 0.205444E+09 | 0.143918E+09 | 0.368571E+09 | 0.173301E+09 |
November | 0.300552E+09 | 0.188372E+09 | 0.112180E+09 | 0.285126E+09 | 0.234591E+09 |
December | 0.330334E+09 | 0.216267E+09 | 0.114067E+09 | 0.275117E+09 | 0.359858E+09 |
Annual Sum or Average | 0.462061E+10 | 0.246893E+10 | 0.215168E+10 | 0.497708E+10 | 0.226090E+10 |
Minimum of Months | 0.300552E+09 | 85454633.93 | 0.112180E+09 | 0.275117E+09 | 62584246.20 |
Maximum of Months | 0.490039E+09 | 0.330757E+09 | 0.244403E+09 | 0.488601E+09 | 0.372451E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.317449E+09 | 0.307937E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.405222E+09 | 0.231932E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.405537E+09 | 0.210134E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.384949E+09 | 0.136999E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.356654E+09 | 84948149.21 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.325735E+09 | 58544956.74 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382550E+09 | 56519371.59 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397305E+09 | 66595105.31 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.384707E+09 | 99244097.24 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.306597E+09 | 0.142911E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.236757E+09 | 0.193404E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.227780E+09 | 0.297876E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.413124E+10 | 0.188705E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.227780E+09 | 56519371.59 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.405537E+09 | 0.307937E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.317449E+09 | 0.307937E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.405222E+09 | 0.231932E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.405537E+09 | 0.210134E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.384949E+09 | 0.136999E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.356654E+09 | 84948149.21 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.325735E+09 | 58544956.74 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382550E+09 | 56519371.59 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397305E+09 | 66595105.31 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.384707E+09 | 99244097.24 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.306597E+09 | 0.142911E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.236757E+09 | 0.193404E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.227780E+09 | 0.297876E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.413124E+10 | 0.188705E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.227780E+09 | 56519371.59 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.405537E+09 | 0.307937E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.381088E+09 | 0.364083E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.486013E+09 | 0.274378E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.485946E+09 | 0.248726E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.461009E+09 | 0.162333E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.426785E+09 | 0.100834E+09 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.389524E+09 | 69597723.74 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457290E+09 | 67238130.92 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475185E+09 | 79103242.52 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.460459E+09 | 0.117705E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.367250E+09 | 0.169411E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.284028E+09 | 0.228848E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.273687E+09 | 0.352005E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.494826E+10 | 0.223426E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.273687E+09 | 67238130.92 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.486013E+09 | 0.364083E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.317729E+09 | 0.305879E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.405558E+09 | 0.230157E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.405874E+09 | 0.208362E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.385506E+09 | 0.135282E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.357078E+09 | 84172826.51 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.325845E+09 | 58366615.76 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382476E+09 | 56699756.35 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397303E+09 | 66635543.79 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.384976E+09 | 98588661.53 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.307121E+09 | 0.141112E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.237122E+09 | 0.191431E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.228014E+09 | 0.295833E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.413460E+10 | 0.187252E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.228014E+09 | 56699756.35 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.405874E+09 | 0.305879E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.317729E+09 | 0.305879E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.405558E+09 | 0.230157E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.405874E+09 | 0.208362E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.385506E+09 | 0.135282E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.357078E+09 | 84172826.51 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.325845E+09 | 58366615.76 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382476E+09 | 56699756.35 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397303E+09 | 66635543.79 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.384976E+09 | 98588661.53 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.307121E+09 | 0.141112E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.237122E+09 | 0.191431E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.228014E+09 | 0.295833E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.413460E+10 | 0.187252E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.228014E+09 | 56699756.35 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.405874E+09 | 0.305879E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.381428E+09 | 0.361636E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.486421E+09 | 0.272271E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.486355E+09 | 0.246622E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.461678E+09 | 0.160298E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.427293E+09 | 99917501.47 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.389656E+09 | 69386596.57 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457202E+09 | 67452150.06 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475182E+09 | 79151131.04 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.460782E+09 | 0.116929E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.367881E+09 | 0.167276E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.284470E+09 | 0.226506E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.273972E+09 | 0.349577E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.495232E+10 | 0.221702E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.273972E+09 | 67452150.06 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.486421E+09 | 0.361636E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.318084E+09 | 0.304399E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.406011E+09 | 0.228670E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.406363E+09 | 0.206734E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.386286E+09 | 0.133590E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.357966E+09 | 82924244.72 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.326364E+09 | 57611581.93 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382809E+09 | 56121751.33 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397606E+09 | 65973582.44 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.385604E+09 | 97393565.85 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.307818E+09 | 0.139362E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.237600E+09 | 0.189701E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.228336E+09 | 0.294253E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.414085E+10 | 0.185673E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.228336E+09 | 56121751.33 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.406363E+09 | 0.304399E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.318084E+09 | 0.304399E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.406011E+09 | 0.228670E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.406363E+09 | 0.206734E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.386286E+09 | 0.133590E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.357966E+09 | 82924244.72 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.326364E+09 | 57611581.93 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382809E+09 | 56121751.33 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397606E+09 | 65973582.44 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.385604E+09 | 97393565.85 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.307818E+09 | 0.139362E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.237600E+09 | 0.189701E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.228336E+09 | 0.294253E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.414085E+10 | 0.185673E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.228336E+09 | 56121751.33 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.406363E+09 | 0.304399E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.381861E+09 | 0.359875E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.486970E+09 | 0.270505E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.486949E+09 | 0.244686E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.462615E+09 | 0.158296E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.428355E+09 | 98443926.94 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.390278E+09 | 68495121.09 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457601E+09 | 66770302.80 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475548E+09 | 78372419.46 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.461531E+09 | 0.115518E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.368717E+09 | 0.165206E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.285050E+09 | 0.224456E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.274365E+09 | 0.347700E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.495984E+10 | 0.219832E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.274365E+09 | 66770302.80 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.486970E+09 | 0.359875E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320214E+09 | 0.298980E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408420E+09 | 0.224001E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.408525E+09 | 0.201968E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.388259E+09 | 0.129684E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359483E+09 | 79987082.33 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327122E+09 | 55507134.55 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382864E+09 | 54263322.67 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397805E+09 | 63945602.44 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386622E+09 | 94628919.01 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309357E+09 | 0.135706E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239344E+09 | 0.184956E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230186E+09 | 0.288552E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415820E+10 | 0.181218E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230186E+09 | 54263322.67 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.408525E+09 | 0.298980E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320214E+09 | 0.298980E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408420E+09 | 0.224001E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.408525E+09 | 0.201968E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.388259E+09 | 0.129684E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359483E+09 | 79987082.33 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327122E+09 | 55507134.55 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382864E+09 | 54263322.67 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397805E+09 | 63945602.44 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386622E+09 | 94628919.01 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309357E+09 | 0.135706E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239344E+09 | 0.184956E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230186E+09 | 0.288552E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415820E+10 | 0.181218E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230186E+09 | 54263322.67 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.408525E+09 | 0.298980E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320214E+09 | 0.298980E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408420E+09 | 0.224001E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.408525E+09 | 0.201968E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.388259E+09 | 0.129684E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359483E+09 | 79987082.33 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327122E+09 | 55507134.55 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382864E+09 | 54263322.67 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397805E+09 | 63945602.44 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386622E+09 | 94628919.01 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309357E+09 | 0.135706E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239344E+09 | 0.184956E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230186E+09 | 0.288552E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415820E+10 | 0.181218E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230186E+09 | 54263322.67 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.408525E+09 | 0.298980E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.320214E+09 | 0.298980E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.408420E+09 | 0.224001E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.408525E+09 | 0.201968E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.388259E+09 | 0.129684E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359483E+09 | 79987082.33 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327122E+09 | 55507134.55 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382864E+09 | 54263322.67 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397805E+09 | 63945602.44 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386622E+09 | 94628919.01 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309357E+09 | 0.135706E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239344E+09 | 0.184956E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.230186E+09 | 0.288552E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415820E+10 | 0.181218E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.230186E+09 | 54263322.67 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.408525E+09 | 0.298980E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.384338E+09 | 0.353602E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.489750E+09 | 0.265075E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.489462E+09 | 0.239117E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.464911E+09 | 0.153718E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.430120E+09 | 94991015.75 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.391158E+09 | 66008679.35 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457646E+09 | 64573696.81 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475754E+09 | 75989603.68 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.462690E+09 | 0.112274E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.370509E+09 | 0.160921E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.287084E+09 | 0.218914E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.276515E+09 | 0.341098E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.497994E+10 | 0.214628E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.276515E+09 | 64573696.81 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.489750E+09 | 0.353602E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.384338E+09 | 0.353602E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.489750E+09 | 0.265075E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.489462E+09 | 0.239117E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.464911E+09 | 0.153718E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.430120E+09 | 94991015.75 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.391158E+09 | 66008679.35 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457646E+09 | 64573696.81 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475754E+09 | 75989603.68 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.462690E+09 | 0.112274E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.370509E+09 | 0.160921E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.287084E+09 | 0.218914E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.276515E+09 | 0.341098E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.497994E+10 | 0.214628E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.276515E+09 | 64573696.81 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.489750E+09 | 0.353602E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.319103E+09 | 0.300778E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.407308E+09 | 0.225175E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.407623E+09 | 0.202812E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.387722E+09 | 0.129688E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359332E+09 | 79577494.23 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327106E+09 | 55050905.12 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382858E+09 | 53745267.62 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397585E+09 | 63471495.53 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386292E+09 | 94265682.34 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.308897E+09 | 0.135608E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.238683E+09 | 0.185748E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.229262E+09 | 0.290478E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415177E+10 | 0.181640E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.229262E+09 | 53745267.62 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.407623E+09 | 0.300778E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.319103E+09 | 0.300778E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.407308E+09 | 0.225175E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.407623E+09 | 0.202812E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.387722E+09 | 0.129688E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359332E+09 | 79577494.23 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327106E+09 | 55050905.12 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.382858E+09 | 53745267.62 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397585E+09 | 63471495.53 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386292E+09 | 94265682.34 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.308897E+09 | 0.135608E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.238683E+09 | 0.185748E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.229262E+09 | 0.290478E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415177E+10 | 0.181640E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.229262E+09 | 53745267.62 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.407623E+09 | 0.300778E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.383103E+09 | 0.355587E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.488535E+09 | 0.266363E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.488479E+09 | 0.240032E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.464355E+09 | 0.153675E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.430009E+09 | 94487882.69 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.391187E+09 | 65464814.61 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457691E+09 | 63958854.49 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475556E+09 | 75416981.19 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.462372E+09 | 0.111813E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.370029E+09 | 0.160756E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.286362E+09 | 0.219767E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.275491E+09 | 0.343228E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.497317E+10 | 0.215055E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.275491E+09 | 63958854.49 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.488535E+09 | 0.355587E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.319164E+09 | 0.300516E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.407418E+09 | 0.224813E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.407792E+09 | 0.202269E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.388127E+09 | 0.128874E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359924E+09 | 78885156.38 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327528E+09 | 54616582.89 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.383098E+09 | 53476793.02 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397800E+09 | 63153382.72 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386667E+09 | 93627643.38 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309240E+09 | 0.134820E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.238865E+09 | 0.185132E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.229324E+09 | 0.290176E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415495E+10 | 0.181036E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.229324E+09 | 53476793.02 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.407792E+09 | 0.300516E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.319164E+09 | 0.300516E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.407418E+09 | 0.224813E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.407792E+09 | 0.202269E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.388127E+09 | 0.128874E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.359924E+09 | 78885156.38 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.327528E+09 | 54616582.89 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.383098E+09 | 53476793.02 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.397800E+09 | 63153382.72 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.386667E+09 | 93627643.38 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.309240E+09 | 0.134820E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.238865E+09 | 0.185132E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.229324E+09 | 0.290176E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.415495E+10 | 0.181036E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.229324E+09 | 53476793.02 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.407792E+09 | 0.300516E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.383178E+09 | 0.355276E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.488668E+09 | 0.265933E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.488684E+09 | 0.239386E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.464842E+09 | 0.152710E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.430716E+09 | 93668772.81 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.391693E+09 | 64949464.34 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.457978E+09 | 63640215.78 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.475815E+09 | 75039791.07 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.462822E+09 | 0.111058E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.370441E+09 | 0.159821E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.286582E+09 | 0.219035E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.275567E+09 | 0.342869E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.497699E+10 | 0.214339E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.275567E+09 | 63640215.78 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.488684E+09 | 0.355276E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.319535E+09 | 0.298673E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.407918E+09 | 0.222814E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.408486E+09 | 0.199648E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.389325E+09 | 0.126032E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.361505E+09 | 76869664.16 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.328595E+09 | 53394959.20 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.383632E+09 | 52787095.34 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.398309E+09 | 62292942.10 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.387586E+09 | 91932185.06 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.310170E+09 | 0.132400E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239515E+09 | 0.182573E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.229675E+09 | 0.288135E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.416425E+10 | 0.178755E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.229675E+09 | 52787095.34 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.408486E+09 | 0.298673E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.319535E+09 | 0.298673E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.407918E+09 | 0.222814E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.408486E+09 | 0.199648E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.389325E+09 | 0.126032E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.361505E+09 | 76869664.16 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.328595E+09 | 53394959.20 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.383632E+09 | 52787095.34 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.398309E+09 | 62292942.10 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.387586E+09 | 91932185.06 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.310170E+09 | 0.132400E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.239515E+09 | 0.182573E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.229675E+09 | 0.288135E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.416425E+10 | 0.178755E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.229675E+09 | 52787095.34 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.408486E+09 | 0.298673E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.383631E+09 | 0.353081E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.489276E+09 | 0.263559E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.489524E+09 | 0.236271E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.466284E+09 | 0.149344E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.432605E+09 | 91287917.81 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.392966E+09 | 63504347.18 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.458616E+09 | 62825833.49 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.476424E+09 | 74025135.76 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.463920E+09 | 0.109055E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.371562E+09 | 0.156959E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.287370E+09 | 0.216002E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.275995E+09 | 0.340440E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.498817E+10 | 0.211635E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.275995E+09 | 62825833.49 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.489524E+09 | 0.353081E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.321968E+09 | 0.289009E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.410462E+09 | 0.213687E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.411403E+09 | 0.188180E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.392792E+09 | 0.115327E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.365502E+09 | 70121960.47 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.331104E+09 | 49111375.77 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384764E+09 | 50048491.88 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.399555E+09 | 58987998.41 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.389786E+09 | 86367455.79 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.312768E+09 | 0.124073E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.241874E+09 | 0.172364E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.231764E+09 | 0.278047E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.419374E+10 | 0.169532E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.231764E+09 | 49111375.77 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.411403E+09 | 0.289009E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.355937E+09 | 0.247313E+09 | 0.108624E+09 | 0.321968E+09 | 0.289009E+09 |
February | 0.407634E+09 | 0.275137E+09 | 0.132498E+09 | 0.410462E+09 | 0.213687E+09 |
March | 0.398597E+09 | 0.252388E+09 | 0.146210E+09 | 0.411403E+09 | 0.188180E+09 |
April | 0.350138E+09 | 0.190495E+09 | 0.159643E+09 | 0.392792E+09 | 0.115327E+09 |
May | 0.304327E+09 | 0.104697E+09 | 0.199630E+09 | 0.365502E+09 | 70121960.47 |
June | 0.264273E+09 | 71084600.99 | 0.193188E+09 | 0.331104E+09 | 49111375.77 |
July | 0.298629E+09 | 95324627.14 | 0.203304E+09 | 0.384764E+09 | 50048491.88 |
August | 0.318714E+09 | 0.133851E+09 | 0.184862E+09 | 0.399555E+09 | 58987998.41 |
September | 0.329952E+09 | 0.175972E+09 | 0.153980E+09 | 0.389786E+09 | 86367455.79 |
October | 0.290613E+09 | 0.170896E+09 | 0.119717E+09 | 0.312768E+09 | 0.124073E+09 |
November | 0.250011E+09 | 0.156696E+09 | 93315453.69 | 0.241874E+09 | 0.172364E+09 |
December | 0.274785E+09 | 0.179900E+09 | 94885566.97 | 0.231764E+09 | 0.278047E+09 |
Annual Sum or Average | 0.384361E+10 | 0.205375E+10 | 0.178986E+10 | 0.419374E+10 | 0.169532E+10 |
Minimum of Months | 0.250011E+09 | 71084600.99 | 93315453.69 | 0.231764E+09 | 49111375.77 |
Maximum of Months | 0.407634E+09 | 0.275137E+09 | 0.203304E+09 | 0.411403E+09 | 0.289009E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.425553E+09 | 0.295683E+09 | 0.129870E+09 | 0.386594E+09 | 0.341492E+09 |
February | 0.487361E+09 | 0.328949E+09 | 0.158412E+09 | 0.492366E+09 | 0.252661E+09 |
March | 0.476557E+09 | 0.301751E+09 | 0.174806E+09 | 0.493071E+09 | 0.222620E+09 |
April | 0.418619E+09 | 0.227752E+09 | 0.190867E+09 | 0.470477E+09 | 0.136682E+09 |
May | 0.363849E+09 | 0.125174E+09 | 0.238675E+09 | 0.437386E+09 | 83316084.29 |
June | 0.315960E+09 | 84987668.72 | 0.230973E+09 | 0.395961E+09 | 58435007.52 |
July | 0.357036E+09 | 0.113969E+09 | 0.243067E+09 | 0.459961E+09 | 59586167.46 |
August | 0.381049E+09 | 0.160031E+09 | 0.221018E+09 | 0.477914E+09 | 70124037.84 |
September | 0.394486E+09 | 0.210389E+09 | 0.184096E+09 | 0.466554E+09 | 0.102482E+09 |
October | 0.347452E+09 | 0.204321E+09 | 0.143131E+09 | 0.374700E+09 | 0.147105E+09 |
November | 0.298910E+09 | 0.187343E+09 | 0.111567E+09 | 0.290240E+09 | 0.203907E+09 |
December | 0.328529E+09 | 0.215085E+09 | 0.113444E+09 | 0.278546E+09 | 0.328374E+09 |
Annual Sum or Average | 0.459536E+10 | 0.245544E+10 | 0.213993E+10 | 0.502377E+10 | 0.200678E+10 |
Minimum of Months | 0.298910E+09 | 84987668.72 | 0.111567E+09 | 0.278546E+09 | 58435007.52 |
Maximum of Months | 0.487361E+09 | 0.328949E+09 | 0.243067E+09 | 0.493071E+09 | 0.341492E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 767.43 | 723.51 | 851.08 | 591.35 | 259.73 | 0.00 | 0.00 |
February | 1083.20 | 598.42 | 1079.12 | 728.36 | 350.76 | 0.00 | 0.00 |
March | 979.33 | 484.49 | 953.08 | 603.48 | 349.60 | 0.00 | 0.00 |
April | 961.76 | 319.97 | 865.12 | 470.67 | 394.45 | 0.00 | 0.00 |
May | 862.04 | 189.37 | 727.67 | 250.34 | 477.33 | 0.00 | 0.00 |
June | 811.67 | 132.84 | 652.96 | 175.64 | 477.33 | 0.00 | 0.00 |
July | 920.30 | 123.16 | 714.05 | 227.93 | 486.12 | 0.00 | 0.00 |
August | 954.28 | 146.74 | 762.07 | 320.05 | 442.02 | 0.00 | 0.00 |
September | 957.19 | 230.16 | 815.25 | 434.79 | 380.45 | 0.00 | 0.00 |
October | 739.96 | 325.78 | 694.88 | 408.63 | 286.25 | 0.00 | 0.00 |
November | 591.74 | 462.87 | 617.73 | 387.16 | 230.56 | 0.00 | 0.00 |
December | 551.95 | 697.01 | 657.04 | 430.16 | 226.88 | 0.00 | 0.00 |
Annual Sum or Average | 846.67 | 368.56 | 780.56 | 417.07 | 363.48 | 0.00 | 0.00 |
Minimum of Months | 551.95 | 123.16 | 617.73 | 175.64 | 226.88 | 0.00 | 0.00 |
Maximum of Months | 1083.20 | 723.51 | 1079.12 | 728.36 | 486.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 380.01 | 373.02 | 425.54 | 295.67 | 129.87 | 0.00 | 0.00 |
February | 536.91 | 310.85 | 539.56 | 364.18 | 175.38 | 0.00 | 0.00 |
March | 485.24 | 254.28 | 476.54 | 301.74 | 174.80 | 0.00 | 0.00 |
April | 475.36 | 171.73 | 432.56 | 235.34 | 197.22 | 0.00 | 0.00 |
May | 426.68 | 99.65 | 363.84 | 125.17 | 238.67 | 0.00 | 0.00 |
June | 403.39 | 68.67 | 326.48 | 87.82 | 238.66 | 0.00 | 0.00 |
July | 459.06 | 62.39 | 357.02 | 113.97 | 243.06 | 0.00 | 0.00 |
August | 475.85 | 74.77 | 381.04 | 160.03 | 221.01 | 0.00 | 0.00 |
September | 475.48 | 119.94 | 407.62 | 217.40 | 190.23 | 0.00 | 0.00 |
October | 366.12 | 173.29 | 347.44 | 204.31 | 143.13 | 0.00 | 0.00 |
November | 292.40 | 242.67 | 308.86 | 193.58 | 115.28 | 0.00 | 0.00 |
December | 272.77 | 360.53 | 328.52 | 215.08 | 113.44 | 0.00 | 0.00 |
Annual Sum or Average | 419.92 | 192.14 | 390.28 | 208.54 | 181.74 | 0.00 | 0.00 |
Minimum of Months | 272.77 | 62.39 | 308.86 | 87.82 | 113.44 | 0.00 | 0.00 |
Maximum of Months | 536.91 | 373.02 | 539.56 | 364.18 | 243.06 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.32 | 365.87 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 535.90 | 305.16 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 484.25 | 249.77 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 474.89 | 168.34 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 425.66 | 101.08 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 401.62 | 72.02 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 456.39 | 67.31 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 474.09 | 79.26 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 474.49 | 121.99 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 366.06 | 169.96 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 292.26 | 237.52 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 272.27 | 353.85 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 418.91 | 190.52 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 272.27 | 67.31 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 535.90 | 365.87 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 379.66 | 363.42 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 536.35 | 302.82 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 484.66 | 247.66 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 475.57 | 166.23 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 426.17 | 100.16 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 401.75 | 71.81 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 456.30 | 67.52 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 474.08 | 79.31 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 474.82 | 121.18 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 366.68 | 167.82 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 292.71 | 235.10 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 272.55 | 351.42 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 419.25 | 189.06 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 272.55 | 67.52 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 536.35 | 363.42 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 380.09 | 361.66 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 536.95 | 300.86 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 485.24 | 245.73 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 476.54 | 164.15 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 427.23 | 98.68 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 402.39 | 70.88 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 456.70 | 66.84 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 474.45 | 78.52 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 475.59 | 119.72 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 367.51 | 165.74 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 293.31 | 232.97 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 272.94 | 349.54 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 419.89 | 187.46 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 272.94 | 66.84 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 536.95 | 361.66 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 765.21 | 710.54 | 849.33 | 590.14 | 259.20 | 0.00 | 0.00 |
February | 1080.18 | 589.51 | 1076.91 | 726.87 | 350.04 | 0.00 | 0.00 |
March | 975.59 | 480.18 | 951.13 | 602.25 | 348.88 | 0.00 | 0.00 |
April | 957.89 | 318.74 | 863.35 | 469.71 | 393.64 | 0.00 | 0.00 |
May | 858.04 | 190.39 | 726.18 | 249.83 | 476.36 | 0.00 | 0.00 |
June | 806.64 | 136.59 | 651.62 | 175.28 | 476.35 | 0.00 | 0.00 |
July | 913.51 | 129.26 | 712.58 | 227.46 | 485.12 | 0.00 | 0.00 |
August | 949.35 | 152.24 | 760.51 | 319.39 | 441.12 | 0.00 | 0.00 |
September | 953.65 | 232.66 | 813.57 | 433.90 | 379.67 | 0.00 | 0.00 |
October | 738.67 | 322.83 | 693.46 | 407.79 | 285.67 | 0.00 | 0.00 |
November | 590.87 | 454.34 | 616.46 | 386.37 | 230.09 | 0.00 | 0.00 |
December | 550.24 | 685.63 | 655.69 | 429.27 | 226.41 | 0.00 | 0.00 |
Annual Sum or Average | 843.25 | 365.97 | 778.96 | 416.22 | 362.74 | 0.00 | 0.00 |
Minimum of Months | 550.24 | 129.26 | 616.46 | 175.28 | 226.41 | 0.00 | 0.00 |
Maximum of Months | 1080.18 | 710.54 | 1076.91 | 726.87 | 485.12 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 381.31 | 357.35 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 538.67 | 296.26 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 486.75 | 241.06 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 478.32 | 159.36 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 428.87 | 94.70 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 403.32 | 67.73 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 456.77 | 64.01 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 474.43 | 75.55 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 476.45 | 115.87 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 368.81 | 161.28 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 294.65 | 228.11 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 274.05 | 345.05 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 421.00 | 183.39 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 274.05 | 64.01 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 538.67 | 357.35 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 381.39 | 357.04 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 538.82 | 295.78 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 486.96 | 240.41 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 478.82 | 158.36 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 429.57 | 93.88 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 403.84 | 67.20 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 457.05 | 63.69 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 474.69 | 75.17 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 476.91 | 115.09 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 369.22 | 160.34 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 294.87 | 227.35 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 274.12 | 344.69 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 421.32 | 182.78 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 274.12 | 63.69 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 538.82 | 357.04 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 381.83 | 354.85 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 539.48 | 293.15 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 487.79 | 237.29 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 480.30 | 154.86 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 431.46 | 91.48 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 405.15 | 65.70 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 457.69 | 62.87 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 475.30 | 74.15 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 478.04 | 113.01 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 370.33 | 157.47 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 295.68 | 224.21 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 274.55 | 342.26 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 422.27 | 180.47 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 274.55 | 62.87 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 539.48 | 354.85 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 384.76 | 343.31 | 424.67 | 295.07 | 129.60 | 0.00 | 0.00 |
February | 542.86 | 281.10 | 538.45 | 363.44 | 175.02 | 0.00 | 0.00 |
March | 491.29 | 223.63 | 475.56 | 301.12 | 174.44 | 0.00 | 0.00 |
April | 484.59 | 141.72 | 431.67 | 234.85 | 196.82 | 0.00 | 0.00 |
May | 436.23 | 83.47 | 363.09 | 124.91 | 238.18 | 0.00 | 0.00 |
June | 408.24 | 60.44 | 325.81 | 87.64 | 238.17 | 0.00 | 0.00 |
July | 459.04 | 59.62 | 356.29 | 113.73 | 242.56 | 0.00 | 0.00 |
August | 476.79 | 70.23 | 380.26 | 159.70 | 220.56 | 0.00 | 0.00 |
September | 480.76 | 106.18 | 406.79 | 216.95 | 189.84 | 0.00 | 0.00 |
October | 373.45 | 147.57 | 346.73 | 203.90 | 142.83 | 0.00 | 0.00 |
November | 298.60 | 211.66 | 308.23 | 193.18 | 115.05 | 0.00 | 0.00 |
December | 277.06 | 330.22 | 327.84 | 214.64 | 113.21 | 0.00 | 0.00 |
Annual Sum or Average | 425.27 | 171.15 | 389.48 | 208.11 | 181.37 | 0.00 | 0.00 |
Minimum of Months | 277.06 | 59.62 | 308.23 | 87.64 | 113.21 | 0.00 | 0.00 |
Maximum of Months | 542.86 | 343.31 | 538.45 | 363.44 | 242.56 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.205549E+10 | 0.193784E+10 | 0.227953E+10 | 0.158387E+10 | 0.695664E+09 | 0.00 | 0.00 |
February | 0.262048E+10 | 0.144771E+10 | 0.261061E+10 | 0.176206E+10 | 0.848555E+09 | 0.00 | 0.00 |
March | 0.262303E+10 | 0.129765E+10 | 0.255274E+10 | 0.161637E+10 | 0.936371E+09 | 0.00 | 0.00 |
April | 0.249289E+10 | 0.829372E+09 | 0.224239E+10 | 0.121999E+10 | 0.102240E+10 | 0.00 | 0.00 |
May | 0.230889E+10 | 0.507197E+09 | 0.194900E+10 | 0.670510E+09 | 0.127849E+10 | 0.00 | 0.00 |
June | 0.210384E+10 | 0.344312E+09 | 0.169248E+10 | 0.455248E+09 | 0.123724E+10 | 0.00 | 0.00 |
July | 0.246493E+10 | 0.329881E+09 | 0.191251E+10 | 0.610488E+09 | 0.130202E+10 | 0.00 | 0.00 |
August | 0.255595E+10 | 0.393024E+09 | 0.204114E+10 | 0.857225E+09 | 0.118391E+10 | 0.00 | 0.00 |
September | 0.248103E+10 | 0.596569E+09 | 0.211312E+10 | 0.112698E+10 | 0.986137E+09 | 0.00 | 0.00 |
October | 0.198190E+10 | 0.872581E+09 | 0.186118E+10 | 0.109447E+10 | 0.766702E+09 | 0.00 | 0.00 |
November | 0.153380E+10 | 0.119976E+10 | 0.160115E+10 | 0.100353E+10 | 0.597621E+09 | 0.00 | 0.00 |
December | 0.147833E+10 | 0.186688E+10 | 0.175981E+10 | 0.115213E+10 | 0.607676E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.267006E+11 | 0.116228E+11 | 0.246157E+11 | 0.131529E+11 | 0.114628E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147833E+10 | 0.329881E+09 | 0.160115E+10 | 0.455248E+09 | 0.597621E+09 | 0.00 | 0.00 |
Maximum of Months | 0.262303E+10 | 0.193784E+10 | 0.261061E+10 | 0.176206E+10 | 0.130202E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101782E+10 | 0.999104E+09 | 0.113977E+10 | 0.791934E+09 | 0.347832E+09 | 0.00 | 0.00 |
February | 0.129888E+10 | 0.751998E+09 | 0.130531E+10 | 0.881030E+09 | 0.424277E+09 | 0.00 | 0.00 |
March | 0.129968E+10 | 0.681064E+09 | 0.127637E+10 | 0.808185E+09 | 0.468185E+09 | 0.00 | 0.00 |
April | 0.123212E+10 | 0.445132E+09 | 0.112120E+10 | 0.609993E+09 | 0.511202E+09 | 0.00 | 0.00 |
May | 0.114283E+10 | 0.266893E+09 | 0.974501E+09 | 0.335255E+09 | 0.639246E+09 | 0.00 | 0.00 |
June | 0.104559E+10 | 0.177993E+09 | 0.846242E+09 | 0.227624E+09 | 0.618618E+09 | 0.00 | 0.00 |
July | 0.122955E+10 | 0.167094E+09 | 0.956255E+09 | 0.305244E+09 | 0.651011E+09 | 0.00 | 0.00 |
August | 0.127452E+10 | 0.200273E+09 | 0.102057E+10 | 0.428612E+09 | 0.591957E+09 | 0.00 | 0.00 |
September | 0.123245E+10 | 0.310889E+09 | 0.105656E+10 | 0.563489E+09 | 0.493069E+09 | 0.00 | 0.00 |
October | 0.980609E+09 | 0.464135E+09 | 0.930588E+09 | 0.547236E+09 | 0.383351E+09 | 0.00 | 0.00 |
November | 0.757889E+09 | 0.628998E+09 | 0.800574E+09 | 0.501764E+09 | 0.298810E+09 | 0.00 | 0.00 |
December | 0.730582E+09 | 0.965631E+09 | 0.879904E+09 | 0.576066E+09 | 0.303838E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132425E+11 | 0.605920E+10 | 0.123078E+11 | 0.657643E+10 | 0.573140E+10 | 0.00 | 0.00 |
Minimum of Months | 0.730582E+09 | 0.167094E+09 | 0.800574E+09 | 0.227624E+09 | 0.298810E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129968E+10 | 0.999104E+09 | 0.130531E+10 | 0.881030E+09 | 0.651011E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101598E+10 | 0.979955E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.129645E+10 | 0.738241E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.129702E+10 | 0.668992E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.123091E+10 | 0.436332E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.114009E+10 | 0.270730E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.104099E+10 | 0.186687E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122239E+10 | 0.180277E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.126979E+10 | 0.212293E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.122987E+10 | 0.316193E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.980443E+09 | 0.455233E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.757539E+09 | 0.615654E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.729246E+09 | 0.947754E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132107E+11 | 0.600834E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.729246E+09 | 0.180277E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129702E+10 | 0.979955E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101688E+10 | 0.973392E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.129754E+10 | 0.732585E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.129810E+10 | 0.663345E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.123269E+10 | 0.430861E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.114145E+10 | 0.268263E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.104135E+10 | 0.186119E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122215E+10 | 0.180852E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.126979E+10 | 0.212422E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.123073E+10 | 0.314106E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.982124E+09 | 0.449499E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.758712E+09 | 0.609366E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.729997E+09 | 0.941240E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132215E+11 | 0.596205E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.729997E+09 | 0.180852E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129810E+10 | 0.973392E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.101803E+10 | 0.968671E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.129899E+10 | 0.727845E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.129967E+10 | 0.658152E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.123518E+10 | 0.425474E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.114429E+10 | 0.264292E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.104301E+10 | 0.183718E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122322E+10 | 0.179014E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.127076E+10 | 0.210319E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.123274E+10 | 0.310305E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.984352E+09 | 0.443930E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.760248E+09 | 0.603857E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.731034E+09 | 0.936202E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132415E+11 | 0.591178E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.731034E+09 | 0.179014E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.129967E+10 | 0.968671E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.204953E+10 | 0.190312E+10 | 0.227486E+10 | 0.158062E+10 | 0.694237E+09 | 0.00 | 0.00 |
February | 0.261318E+10 | 0.142615E+10 | 0.260526E+10 | 0.175844E+10 | 0.846814E+09 | 0.00 | 0.00 |
March | 0.261302E+10 | 0.128611E+10 | 0.254750E+10 | 0.161305E+10 | 0.934450E+09 | 0.00 | 0.00 |
April | 0.248286E+10 | 0.826170E+09 | 0.223779E+10 | 0.121748E+10 | 0.102031E+10 | 0.00 | 0.00 |
May | 0.229817E+10 | 0.509930E+09 | 0.194500E+10 | 0.669134E+09 | 0.127587E+10 | 0.00 | 0.00 |
June | 0.209080E+10 | 0.354045E+09 | 0.168901E+10 | 0.454314E+09 | 0.123470E+10 | 0.00 | 0.00 |
July | 0.244675E+10 | 0.346200E+09 | 0.190859E+10 | 0.609236E+09 | 0.129935E+10 | 0.00 | 0.00 |
August | 0.254273E+10 | 0.407761E+09 | 0.203695E+10 | 0.855466E+09 | 0.118149E+10 | 0.00 | 0.00 |
September | 0.247187E+10 | 0.603063E+09 | 0.210878E+10 | 0.112467E+10 | 0.984114E+09 | 0.00 | 0.00 |
October | 0.197844E+10 | 0.864662E+09 | 0.185736E+10 | 0.109223E+10 | 0.765130E+09 | 0.00 | 0.00 |
November | 0.153154E+10 | 0.117765E+10 | 0.159786E+10 | 0.100147E+10 | 0.596395E+09 | 0.00 | 0.00 |
December | 0.147377E+10 | 0.183640E+10 | 0.175620E+10 | 0.114977E+10 | 0.606430E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.265927E+11 | 0.115413E+11 | 0.245652E+11 | 0.131259E+11 | 0.114393E+11 | 0.00 | 0.00 |
Minimum of Months | 0.147377E+10 | 0.346200E+09 | 0.159786E+10 | 0.454314E+09 | 0.596395E+09 | 0.00 | 0.00 |
Maximum of Months | 0.261318E+10 | 0.190312E+10 | 0.260526E+10 | 0.175844E+10 | 0.129935E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102131E+10 | 0.957138E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.130315E+10 | 0.716712E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.130372E+10 | 0.645656E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.123980E+10 | 0.413049E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.114867E+10 | 0.253643E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.104540E+10 | 0.175566E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122341E+10 | 0.171449E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.127073E+10 | 0.202360E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.123496E+10 | 0.300344E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.987822E+09 | 0.431971E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.763725E+09 | 0.591261E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.734013E+09 | 0.924182E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132767E+11 | 0.578333E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.734013E+09 | 0.171449E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130372E+10 | 0.957138E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102150E+10 | 0.956304E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.130350E+10 | 0.715559E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.130427E+10 | 0.643922E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.124109E+10 | 0.410457E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.115056E+10 | 0.251439E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.104675E+10 | 0.174182E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122417E+10 | 0.170594E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.127141E+10 | 0.201347E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.123616E+10 | 0.298313E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.988919E+09 | 0.429460E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.764310E+09 | 0.589297E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.734214E+09 | 0.923218E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.132869E+11 | 0.576409E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.734214E+09 | 0.170594E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130427E+10 | 0.956304E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.102270E+10 | 0.950422E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.130511E+10 | 0.709184E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.130649E+10 | 0.635567E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.124493E+10 | 0.401408E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.115561E+10 | 0.245027E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.105016E+10 | 0.170294E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122588E+10 | 0.168400E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.127304E+10 | 0.198610E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.123909E+10 | 0.292919E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.991902E+09 | 0.421759E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.766398E+09 | 0.581145E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.735343E+09 | 0.916708E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.133167E+11 | 0.569144E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.735343E+09 | 0.168400E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.130649E+10 | 0.950422E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.103053E+10 | 0.919509E+09 | 0.113743E+10 | 0.790309E+09 | 0.347119E+09 | 0.00 | 0.00 |
February | 0.131329E+10 | 0.680035E+09 | 0.130263E+10 | 0.879222E+09 | 0.423407E+09 | 0.00 | 0.00 |
March | 0.131588E+10 | 0.598980E+09 | 0.127375E+10 | 0.806527E+09 | 0.467225E+09 | 0.00 | 0.00 |
April | 0.125606E+10 | 0.367335E+09 | 0.111890E+10 | 0.608742E+09 | 0.510154E+09 | 0.00 | 0.00 |
May | 0.116839E+10 | 0.223560E+09 | 0.972502E+09 | 0.334567E+09 | 0.637935E+09 | 0.00 | 0.00 |
June | 0.105817E+10 | 0.156657E+09 | 0.844506E+09 | 0.227157E+09 | 0.617349E+09 | 0.00 | 0.00 |
July | 0.122949E+10 | 0.159683E+09 | 0.954294E+09 | 0.304618E+09 | 0.649676E+09 | 0.00 | 0.00 |
August | 0.127702E+10 | 0.188100E+09 | 0.101848E+10 | 0.427733E+09 | 0.590743E+09 | 0.00 | 0.00 |
September | 0.124613E+10 | 0.275217E+09 | 0.105439E+10 | 0.562333E+09 | 0.492057E+09 | 0.00 | 0.00 |
October | 0.100024E+10 | 0.395250E+09 | 0.928678E+09 | 0.546114E+09 | 0.382565E+09 | 0.00 | 0.00 |
November | 0.773984E+09 | 0.548629E+09 | 0.798932E+09 | 0.500735E+09 | 0.298197E+09 | 0.00 | 0.00 |
December | 0.742072E+09 | 0.884464E+09 | 0.878099E+09 | 0.574884E+09 | 0.303215E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.134112E+11 | 0.539742E+10 | 0.122826E+11 | 0.656294E+10 | 0.571964E+10 | 0.00 | 0.00 |
Minimum of Months | 0.742072E+09 | 0.156657E+09 | 0.798932E+09 | 0.227157E+09 | 0.298197E+09 | 0.00 | 0.00 |
Maximum of Months | 0.131588E+10 | 0.919509E+09 | 0.130263E+10 | 0.879222E+09 | 0.649676E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | -16.9 | -17.4 | -20.0 | 3.73 | -31.9 | 33.25 | 98.18 | 0.00 |
February | -11.6 | -12.7 | -16.7 | 4.33 | -26.7 | 48.91 | 138.70 | 0.00 |
March | -6.2 | -7.6 | -10.8 | 3.55 | -19.4 | 56.69 | 163.76 | 0.01 |
April | 3.97 | 0.41 | -4.8 | 4.72 | -9.1 | 70.41 | 207.70 | 0.01 |
May | 13.43 | 8.45 | 3.53 | 3.60 | 2.20 | 102.27 | 202.62 | 0.00 |
June | 18.03 | 14.19 | 11.55 | 3.74 | 7.84 | 104.36 | 210.60 | 0.06 |
July | 19.67 | 16.51 | 14.78 | 3.14 | 8.97 | 101.67 | 223.82 | 0.04 |
August | 17.94 | 15.20 | 13.59 | 3.45 | 8.99 | 87.39 | 175.79 | 0.04 |
September | 12.29 | 9.87 | 7.80 | 3.78 | 3.34 | 70.27 | 143.96 | 0.00 |
October | 5.42 | 3.47 | 1.07 | 3.53 | -4.7 | 51.74 | 90.11 | 0.00 |
November | -2.0 | -3.6 | -6.9 | 4.42 | -13.7 | 34.68 | 65.95 | 0.00 |
December | -14.6 | -15.1 | -18.1 | 3.91 | -28.3 | 29.58 | 68.99 | 0.00 |
Annual Sum or Average | 3.36 | 1.04 | -2.0 | 3.82 | -8.4 | 66.03 | 149.18 | 0.01 |
Minimum of Months | -16.9 | -17.4 | -20.0 | 3.14 | -31.9 | 29.58 | 65.95 | 0.00 |
Maximum of Months | 19.67 | 16.51 | 14.78 | 4.72 | 8.99 | 104.36 | 223.82 | 0.06 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 1.10 | 29-JAN-14:00 | -1.0 | -4.4 | 2.60 | -11.4 | 145.00 | 110.00 |
February | 8.90 | 20-FEB-15:00 | 2.87 | -6.7 | 8.80 | -9.0 | 49.00 | 646.00 |
March | 11.10 | 26-MAR-15:00 | 5.48 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 26.70 | 23-APR-15:00 | 16.95 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 29.40 | 25-MAY-17:00 | 19.26 | 13.90 | 1.50 | 16.49 | 47.50 | 582.00 |
June | 35.00 | 29-JUN-15:00 | 24.72 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 31.10 | 15-JUL-14:20 | 25.35 | 23.33 | 8.07 | 19.93 | 299.67 | 518.33 |
August | 30.60 | 08-AUG-14:00 | 23.36 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 26.10 | 01-SEP-14:00 | 17.82 | 13.30 | 3.60 | 14.28 | 112.00 | 751.50 |
October | 22.20 | 19-OCT-14:00 | 13.62 | 7.20 | 6.70 | 8.15 | 35.50 | 701.50 |
November | 18.30 | 01-NOV-14:00 | 13.44 | 10.00 | 3.10 | 11.84 | 105.00 | 30.50 |
December | 1.10 | 28-DEC-02:00 | 0.43 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 1.10 | -1.0 | -6.7 | 1.50 | -11.4 | 0.00 | 0.00 | |
Maximum of Months | 35.00 | 25.35 | 23.33 | 11.30 | 24.66 | 299.67 | 842.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -35.6 | 06-JAN-08:00 | -35.7 | -37.8 | 0.00 | -57.8 | 27.00 | 381.00 |
February | -33.3 | 14-FEB-06:00 | -33.4 | -36.7 | 0.00 | -55.6 | 0.00 | 0.00 |
March | -28.9 | 05-MAR-06:00 | -29.1 | -32.2 | 1.50 | -50.6 | 27.00 | 41.50 |
April | -13.9 | 05-APR-05:00 | -14.4 | -16.1 | 0.00 | -32.5 | 14.50 | 199.00 |
May | -3.9 | 01-MAY-05:00 | -6.2 | -12.2 | 0.00 | -22.4 | 35.00 | 415.00 |
June | 1.10 | 04-JUN-04:00 | 0.62 | 0.00 | 0.00 | -14.9 | 37.00 | 169.50 |
July | 6.10 | 02-JUL-04:00 | 6.10 | 6.10 | 0.00 | -8.8 | 33.50 | 204.50 |
August | 4.40 | 19-AUG-03:00 | 4.40 | 4.40 | 0.00 | -10.7 | 0.00 | 0.00 |
September | 1.10 | 06-SEP-03:00 | 1.10 | 1.10 | 0.00 | -14.7 | 0.00 | 0.00 |
October | -10.0 | 30-OCT-03:00 | -10.7 | -12.8 | 1.50 | -28.2 | 0.00 | 0.00 |
November | -20.6 | 29-NOV-05:00 | -20.8 | -22.2 | 2.10 | -37.8 | 0.00 | 0.00 |
December | -31.1 | 24-DEC-06:19 | -31.3 | -35.1 | 3.33 | -53.1 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -35.6 | -35.7 | -37.8 | 0.00 | -57.8 | 0.00 | 0.00 | |
Maximum of Months | 6.10 | 6.10 | 6.10 | 3.33 | -8.8 | 37.00 | 415.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -0.5 | 16-JAN-12:00 | 0.00 | -1.1 | 5.70 | -6.6 | 172.50 | 3.00 |
February | 3.34 | 21-FEB-12:00 | 6.70 | -1.1 | 7.70 | -6.0 | 270.00 | 303.00 |
March | 5.48 | 26-MAR-15:00 | 11.10 | -1.1 | 5.20 | -5.7 | 53.00 | 842.00 |
April | 16.95 | 23-APR-15:00 | 26.70 | 11.10 | 11.30 | 12.03 | 75.50 | 811.00 |
May | 19.91 | 26-MAY-11:00 | 25.60 | 17.20 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 24.72 | 29-JUN-15:00 | 35.00 | 21.10 | 6.70 | 24.66 | 132.00 | 705.00 |
July | 25.76 | 15-JUL-13:00 | 31.10 | 23.90 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 23.36 | 08-AUG-14:00 | 30.60 | 20.60 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 18.67 | 01-SEP-00:00 | 19.00 | 17.50 | 2.80 | 16.30 | 0.00 | 0.00 |
October | 13.72 | 19-OCT-13:00 | 21.70 | 7.80 | 5.70 | 7.75 | 54.50 | 739.00 |
November | 14.29 | 21-NOV-12:00 | 15.00 | 13.90 | 5.20 | 11.46 | 134.50 | 25.50 |
December | 0.43 | 28-DEC-02:00 | 1.10 | -0.6 | 4.60 | -5.5 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -0.5 | 0.00 | -1.1 | 2.80 | -6.6 | 0.00 | 0.00 | |
Maximum of Months | 25.76 | 35.00 | 23.90 | 11.30 | 24.66 | 333.00 | 842.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -1.1 | 16-JAN-11:00 | -0.6 | -0.8 | 5.70 | -7.3 | 164.50 | 5.00 |
February | -0.6 | 21-FEB-08:00 | 4.40 | 2.25 | 8.80 | -6.6 | 123.00 | 89.50 |
March | 0.00 | 29-MAR-20:00 | 1.70 | 0.95 | 1.50 | -4.8 | 0.00 | 0.00 |
April | 11.10 | 23-APR-13:00 | 24.40 | 16.08 | 10.80 | 9.72 | 98.50 | 903.50 |
May | 17.20 | 26-MAY-11:00 | 25.60 | 19.91 | 6.20 | 22.64 | 300.50 | 6.00 |
June | 22.80 | 29-JUN-23:19 | 26.30 | 23.71 | 5.20 | 14.28 | 0.00 | 0.00 |
July | 23.90 | 15-JUL-13:00 | 31.10 | 25.76 | 7.70 | 18.99 | 333.00 | 421.00 |
August | 20.60 | 08-AUG-14:00 | 30.60 | 23.36 | 6.70 | 17.93 | 163.50 | 672.50 |
September | 17.92 | 01-SEP-00:10 | 19.75 | 18.15 | 3.22 | 13.23 | 0.00 | 0.00 |
October | 12.20 | 07-OCT-12:20 | 14.47 | 13.17 | 3.43 | 9.20 | 163.17 | 18.50 |
November | 13.90 | 21-NOV-12:00 | 15.00 | 14.29 | 5.20 | 11.46 | 134.50 | 25.50 |
December | -0.0 | 05-DEC-17:00 | 0.00 | -0.0 | 1.50 | -6.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -1.1 | -0.6 | -0.8 | 1.50 | -7.3 | 0.00 | 0.00 | |
Maximum of Months | 23.90 | 31.10 | 25.76 | 10.80 | 22.64 | 333.00 | 903.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 1.89 | 11.66 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 0.58 | 19.92 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 0.81 | 26.63 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 2.58 | 37.52 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 5.43 | 45.25 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 8.61 | 47.76 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 11.25 | 48.86 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 12.66 | 38.94 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 12.41 | 29.23 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 10.60 | 17.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 7.72 | 10.89 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 4.55 | 9.11 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 6.63 | 28.63 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 0.58 | 9.11 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 12.66 | 48.86 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.407732E+09 | -280357929.9 | 0.00 | 0.00 | 744.00 | 0.00 | -127374258.9 | 58.99 | 0.00 | 0.00 |
February | 0.375136E+09 | -260411654.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114724273.6 | 59.00 | 0.00 | 0.00 |
March | 0.417979E+09 | -291899980.7 | 0.00 | 0.00 | 744.00 | 0.00 | -126078709.9 | 58.99 | 0.00 | 0.00 |
April | 0.389344E+09 | -270392590.6 | 0.00 | 0.00 | 720.00 | 0.00 | -118951713.2 | 58.99 | 0.00 | 0.00 |
May | 0.381674E+09 | -265735853.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115938027.1 | 58.99 | 0.00 | 0.00 |
June | 0.354083E+09 | -244324252.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109759247.6 | 59.00 | 0.00 | 0.00 |
July | 0.346838E+09 | -234333654.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112504647.8 | 58.99 | 0.00 | 0.00 |
August | 0.344969E+09 | -232292255.7 | 0.00 | 0.00 | 744.00 | 0.00 | -112676701.1 | 58.99 | 0.00 | 0.00 |
September | 0.334793E+09 | -223460014.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111332873.9 | 58.99 | 0.00 | 0.00 |
October | 0.358901E+09 | -237647776.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121252877.8 | 58.99 | 0.00 | 0.00 |
November | 0.363887E+09 | -242945898.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120941601.5 | 59.00 | 0.00 | 0.00 |
December | 0.394872E+09 | -267637728.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127234574.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.447021E+10 | -0.305144E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141877E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.334793E+09 | -291899980.7 | 0.00 | 0.00 | 672.00 | 0.00 | -127374258.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.417979E+09 | -223460014.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109759247.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.406244E+09 | -280357400.9 | 0.00 | 0.00 | 744.00 | 0.00 | -125886807.1 | 59.00 | 0.00 | 0.00 |
February | 0.373430E+09 | -260404021.1 | 0.00 | 0.00 | 672.00 | 0.00 | -113026402.6 | 59.00 | 0.00 | 0.00 |
March | 0.415751E+09 | -291896895.0 | 0.00 | 0.00 | 744.00 | 0.00 | -123854040.1 | 58.99 | 0.00 | 0.00 |
April | 0.386321E+09 | -270389913.8 | 0.00 | 0.00 | 720.00 | 0.00 | -115930714.6 | 58.99 | 0.00 | 0.00 |
May | 0.379922E+09 | -265737500.5 | 0.00 | 0.00 | 744.00 | 0.00 | -114184499.0 | 58.99 | 0.00 | 0.00 |
June | 0.353359E+09 | -244327477.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109031422.9 | 58.99 | 0.00 | 0.00 |
July | 0.346549E+09 | -234335108.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112214006.3 | 58.99 | 0.00 | 0.00 |
August | 0.344565E+09 | -232299370.1 | 0.00 | 0.00 | 744.00 | 0.00 | -112265458.9 | 58.99 | 0.00 | 0.00 |
September | 0.333318E+09 | -223441874.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109876321.7 | 59.00 | 0.00 | 0.00 |
October | 0.356056E+09 | -237655185.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118400845.9 | 58.99 | 0.00 | 0.00 |
November | 0.361733E+09 | -242949380.8 | 0.00 | 0.00 | 720.00 | 0.00 | -118783247.4 | 58.99 | 0.00 | 0.00 |
December | 0.393219E+09 | -267644370.2 | 0.00 | 0.00 | 744.00 | 0.00 | -125574695.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.445047E+10 | -0.305144E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139903E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.333318E+09 | -291896895.0 | 0.00 | 0.00 | 672.00 | 0.00 | -125886807.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.415751E+09 | -223441874.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109031422.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.374501E+09 | -246546282.5 | 0.00 | 0.00 | 744.00 | 0.00 | -127955020.8 | 58.99 | 0.00 | 0.00 |
February | 0.343797E+09 | -229169753.9 | 0.00 | 0.00 | 672.00 | 0.00 | -114627055.5 | 59.00 | 0.00 | 0.00 |
March | 0.385904E+09 | -260519613.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125384607.2 | 58.99 | 0.00 | 0.00 |
April | 0.355169E+09 | -237800492.7 | 0.00 | 0.00 | 720.00 | 0.00 | -117368163.3 | 59.00 | 0.00 | 0.00 |
May | 0.349638E+09 | -235709566.8 | 0.00 | 0.00 | 744.00 | 0.00 | -113928411.1 | 58.98 | 0.00 | 0.00 |
June | 0.325551E+09 | -217616740.6 | 0.00 | 0.00 | 720.00 | 0.00 | -107934358.8 | 58.98 | 0.00 | 0.00 |
July | 0.315299E+09 | -204848283.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110450826.2 | 58.99 | 0.00 | 0.00 |
August | 0.318418E+09 | -207482057.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110935532.6 | 59.00 | 0.00 | 0.00 |
September | 0.305941E+09 | -196383884.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109557083.9 | 58.99 | 0.00 | 0.00 |
October | 0.328860E+09 | -209015736.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119844576.9 | 58.99 | 0.00 | 0.00 |
November | 0.334999E+09 | -214524221.1 | 0.00 | 0.00 | 720.00 | 0.00 | -120474786.6 | 58.99 | 0.00 | 0.00 |
December | 0.361209E+09 | -233642390.0 | 0.00 | 0.00 | 744.00 | 0.00 | -127566862.0 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.409929E+10 | -0.269326E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140603E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.305941E+09 | -260519613.4 | 0.00 | 0.00 | 672.00 | 0.00 | -127955020.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.385904E+09 | -196383884.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107934358.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.374928E+09 | -246543992.1 | 0.00 | 0.00 | 744.00 | 0.00 | -128383842.1 | 58.99 | 0.00 | 0.00 |
February | 0.344173E+09 | -229185330.7 | 0.00 | 0.00 | 672.00 | 0.00 | -114987881.5 | 58.99 | 0.00 | 0.00 |
March | 0.386300E+09 | -260514783.0 | 0.00 | 0.00 | 744.00 | 0.00 | -125785070.3 | 58.99 | 0.00 | 0.00 |
April | 0.355617E+09 | -237838770.0 | 0.00 | 0.00 | 720.00 | 0.00 | -117778474.6 | 58.98 | 0.00 | 0.00 |
May | 0.349908E+09 | -235691074.2 | 0.00 | 0.00 | 744.00 | 0.00 | -114216918.7 | 58.99 | 0.00 | 0.00 |
June | 0.325621E+09 | -217579011.8 | 0.00 | 0.00 | 720.00 | 0.00 | -108042438.8 | 59.00 | 0.00 | 0.00 |
July | 0.315254E+09 | -204834025.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110420414.6 | 59.00 | 0.00 | 0.00 |
August | 0.318391E+09 | -207492843.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110898488.8 | 58.99 | 0.00 | 0.00 |
September | 0.306148E+09 | -196394018.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109753672.3 | 58.99 | 0.00 | 0.00 |
October | 0.329336E+09 | -209000345.3 | 0.00 | 0.00 | 744.00 | 0.00 | -120335211.3 | 58.99 | 0.00 | 0.00 |
November | 0.335443E+09 | -214511533.8 | 0.00 | 0.00 | 720.00 | 0.00 | -120931072.7 | 58.99 | 0.00 | 0.00 |
December | 0.361634E+09 | -233611769.5 | 0.00 | 0.00 | 744.00 | 0.00 | -128022467.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.410275E+10 | -0.269320E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140956E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.306148E+09 | -260514783.0 | 0.00 | 0.00 | 672.00 | 0.00 | -128383842.1 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.386300E+09 | -196394018.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108042438.8 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363103E+09 | -233025344.7 | 0.00 | 0.00 | 744.00 | 0.00 | -130078069.9 | 58.99 | 0.00 | 0.00 |
February | 0.333397E+09 | -216711303.7 | 0.00 | 0.00 | 672.00 | 0.00 | -116686084.0 | 59.00 | 0.00 | 0.00 |
March | 0.374012E+09 | -246494308.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127517624.6 | 58.99 | 0.00 | 0.00 |
April | 0.344642E+09 | -225030722.6 | 0.00 | 0.00 | 720.00 | 0.00 | -119611444.3 | 59.00 | 0.00 | 0.00 |
May | 0.338739E+09 | -222893998.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115844659.1 | 58.99 | 0.00 | 0.00 |
June | 0.314989E+09 | -205885921.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109103516.0 | 58.99 | 0.00 | 0.00 |
July | 0.304973E+09 | -193712088.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111261186.3 | 59.00 | 0.00 | 0.00 |
August | 0.308083E+09 | -196336332.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111746742.3 | 58.99 | 0.00 | 0.00 |
September | 0.296949E+09 | -185844067.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111104484.9 | 58.99 | 0.00 | 0.00 |
October | 0.319517E+09 | -197527450.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121989703.2 | 59.00 | 0.00 | 0.00 |
November | 0.325180E+09 | -202572035.1 | 0.00 | 0.00 | 720.00 | 0.00 | -122607831.9 | 59.00 | 0.00 | 0.00 |
December | 0.350695E+09 | -220935597.5 | 0.00 | 0.00 | 744.00 | 0.00 | -129759713.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.397428E+10 | -0.254697E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142731E+10 | 59.00 | 0.00 | 0.00 |
Minimum of Months | 0.296949E+09 | -246494308.3 | 0.00 | 0.00 | 672.00 | 0.00 | -130078069.9 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374012E+09 | -185844067.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109103516.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.362957E+09 | -233031953.4 | 0.00 | 0.00 | 744.00 | 0.00 | -129924816.6 | 58.99 | 0.00 | 0.00 |
February | 0.333286E+09 | -216716782.1 | 0.00 | 0.00 | 672.00 | 0.00 | -116569146.4 | 59.00 | 0.00 | 0.00 |
March | 0.373939E+09 | -246497041.4 | 0.00 | 0.00 | 744.00 | 0.00 | -127441845.5 | 58.99 | 0.00 | 0.00 |
April | 0.344693E+09 | -225037323.1 | 0.00 | 0.00 | 720.00 | 0.00 | -119655875.9 | 59.00 | 0.00 | 0.00 |
May | 0.338880E+09 | -222878422.8 | 0.00 | 0.00 | 744.00 | 0.00 | -116001709.1 | 59.00 | 0.00 | 0.00 |
June | 0.315114E+09 | -205876670.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109237648.5 | 59.00 | 0.00 | 0.00 |
July | 0.305102E+09 | -193718010.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111384344.7 | 59.00 | 0.00 | 0.00 |
August | 0.308196E+09 | -196328407.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111867790.6 | 58.99 | 0.00 | 0.00 |
September | 0.297072E+09 | -185842742.2 | 0.00 | 0.00 | 720.00 | 0.00 | -111228974.5 | 58.99 | 0.00 | 0.00 |
October | 0.319579E+09 | -197560221.2 | 0.00 | 0.00 | 744.00 | 0.00 | -122019214.1 | 58.98 | 0.00 | 0.00 |
November | 0.325134E+09 | -202628652.8 | 0.00 | 0.00 | 720.00 | 0.00 | -122505150.3 | 58.98 | 0.00 | 0.00 |
December | 0.350533E+09 | -220937517.7 | 0.00 | 0.00 | 744.00 | 0.00 | -129595858.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.397449E+10 | -0.254705E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142743E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.297072E+09 | -246497041.4 | 0.00 | 0.00 | 672.00 | 0.00 | -129924816.6 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.373939E+09 | -185842742.2 | 0.00 | 0.00 | 744.00 | 0.00 | -109237648.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363005E+09 | -233029373.5 | 0.00 | 0.00 | 744.00 | 0.00 | -129976005.1 | 58.99 | 0.00 | 0.00 |
February | 0.333363E+09 | -216713177.2 | 0.00 | 0.00 | 672.00 | 0.00 | -116649794.8 | 59.00 | 0.00 | 0.00 |
March | 0.374055E+09 | -246489837.3 | 0.00 | 0.00 | 744.00 | 0.00 | -127565116.9 | 59.00 | 0.00 | 0.00 |
April | 0.344920E+09 | -225033837.7 | 0.00 | 0.00 | 720.00 | 0.00 | -119885895.1 | 59.00 | 0.00 | 0.00 |
May | 0.339131E+09 | -222909937.0 | 0.00 | 0.00 | 744.00 | 0.00 | -116221146.4 | 58.99 | 0.00 | 0.00 |
June | 0.315275E+09 | -205875947.3 | 0.00 | 0.00 | 720.00 | 0.00 | -109398731.0 | 59.00 | 0.00 | 0.00 |
July | 0.305189E+09 | -193734007.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111455186.5 | 58.99 | 0.00 | 0.00 |
August | 0.308292E+09 | -196335014.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111956837.0 | 58.99 | 0.00 | 0.00 |
September | 0.297283E+09 | -185841070.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111441923.8 | 58.99 | 0.00 | 0.00 |
October | 0.319799E+09 | -197560013.9 | 0.00 | 0.00 | 744.00 | 0.00 | -122238733.5 | 58.99 | 0.00 | 0.00 |
November | 0.325266E+09 | -202591722.6 | 0.00 | 0.00 | 720.00 | 0.00 | -122674559.2 | 58.99 | 0.00 | 0.00 |
December | 0.350604E+09 | -220932411.2 | 0.00 | 0.00 | 744.00 | 0.00 | -129671680.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.397618E+10 | -0.254705E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.142914E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.297283E+09 | -246489837.3 | 0.00 | 0.00 | 672.00 | 0.00 | -129976005.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.374055E+09 | -185841070.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109398731.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 243.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 265.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 254.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 296.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 401.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 409.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 352.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 344.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 299.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 255.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3785.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 226.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 437.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.426866E+11 | 70702.30 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.286016E+11 | 70702.30 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.231303E+11 | 70702.30 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.760644E+10 | 70702.30 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.222575E+09 | 70702.30 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 19186546.52 | 4090.58 | 29-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.519051E+10 | 70702.30 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171860E+11 | 70702.30 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.396136E+11 | 70702.30 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.164257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.426866E+11 | 70702.30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.152512E+11 | 36443.54 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.957565E+10 | 36443.54 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.745894E+10 | 36443.54 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.189193E+10 | 36443.54 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 21921642.70 | 5020.64 | 01-MAY-08:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.116702E+10 | 28969.76 | 30-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.527475E+10 | 36443.54 | 07-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.140331E+11 | 36443.54 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.546744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152512E+11 | 36443.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.167000E+11 | 36623.13 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.108743E+11 | 36623.13 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.870414E+10 | 36623.13 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.245625E+10 | 36623.13 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 57010585.89 | 12526.11 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.170022E+10 | 36623.13 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.634956E+10 | 36623.13 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153802E+11 | 36623.13 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.622217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.167000E+11 | 36623.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.169912E+11 | 36478.63 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.110931E+11 | 36478.63 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.891840E+10 | 36478.63 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.259051E+10 | 36478.63 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 67952409.78 | 19401.58 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.185297E+10 | 36478.63 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.658156E+10 | 36478.63 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.156414E+11 | 36478.63 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.637372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.169912E+11 | 36478.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.174549E+11 | 36505.59 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.114909E+11 | 36505.59 | 01-FEB-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.933177E+10 | 36505.59 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.283823E+10 | 36505.59 | 02-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 86703989.03 | 25671.37 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 1179986.87 | 592.15 | 29-SEP-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208442E+10 | 36505.59 | 30-OCT-07:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.695853E+10 | 36505.59 | 05-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.160888E+11 | 36505.59 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.663354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.174549E+11 | 36505.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.332420E+11 | 68675.84 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.218289E+11 | 68675.84 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179134E+11 | 68675.84 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.571084E+10 | 68675.84 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.206888E+09 | 68675.84 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 32175962.43 | 4384.17 | 29-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.451794E+10 | 68675.84 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136203E+11 | 68675.84 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.307015E+11 | 68675.84 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.127774E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.332420E+11 | 68675.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.171676E+11 | 35009.47 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113081E+11 | 35009.47 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.929057E+10 | 35009.47 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.298257E+10 | 35009.47 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.110043E+09 | 35009.47 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 18173208.58 | 2088.47 | 28-SEP-08:13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.234033E+10 | 35009.47 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.706126E+10 | 35009.47 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158749E+11 | 35009.47 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.661536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.171676E+11 | 35009.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.172486E+11 | 34878.92 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.113991E+11 | 34878.92 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.940626E+10 | 34878.92 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.309104E+10 | 34878.92 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.129430E+09 | 34878.92 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 28405134.68 | 2755.79 | 29-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243094E+10 | 34878.92 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.717111E+10 | 34878.92 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.159576E+11 | 34878.92 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.668625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.172486E+11 | 34878.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.177959E+11 | 35048.53 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.118810E+11 | 35048.53 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.993985E+10 | 35048.53 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.347416E+10 | 35048.53 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.195140E+09 | 35048.53 | 01-MAY-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 74093010.81 | 2608.11 | 23-SEP-08:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.272170E+10 | 35048.53 | 06-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.761024E+10 | 35048.53 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.164840E+11 | 35048.53 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.701761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.177959E+11 | 35048.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.229067E+11 | 39999.27 | 01-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.157028E+11 | 39999.27 | 01-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.131316E+11 | 39999.27 | 01-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.491213E+10 | 39999.27 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.400813E+09 | 39999.27 | 01-MAY-07:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.229968E+09 | 12322.54 | 29-SEP-08:63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.363773E+10 | 39999.27 | 04-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.975802E+10 | 39999.27 | 01-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.211398E+11 | 39999.27 | 01-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.918195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.229067E+11 | 39999.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.268461E+09 | 0.240707E+09 | 12897.81 | 23-APR-16:10 | 11671.23 | 0.00 |
May | 0.00 | 0.00 | 0.424465E+10 | 0.378760E+10 | 43019.06 | 26-MAY-08:61 | 29153.38 | 0.00 |
June | 0.00 | 0.00 | 0.110565E+11 | 0.826404E+10 | 46307.34 | 30-JUN-08:61 | 27423.43 | 0.00 |
July | 0.00 | 0.00 | 0.176024E+11 | 0.123806E+11 | 45933.24 | 23-JUL-07:02 | 21418.93 | 0.00 |
August | 0.00 | 0.00 | 0.118270E+11 | 0.844699E+10 | 44904.39 | 30-AUG-08:61 | 23153.56 | 0.00 |
September | 0.00 | 0.00 | 0.155397E+10 | 0.128286E+10 | 43476.73 | 01-SEP-08:62 | 23329.54 | 0.00 |
October | 0.00 | 0.00 | 97468818.57 | 93092947.36 | 5066.22 | 19-OCT-15:00 | 4992.12 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.466505E+11 | 0.344958E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176024E+11 | 0.123806E+11 | 46307.34 | 29153.38 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 415556.11 | 415556.11 | 463.49 | 26-MAR-18:00 | 463.49 | 0.00 |
April | 0.00 | 0.00 | 0.184351E+09 | 0.167276E+09 | 21786.26 | 23-APR-18:41 | 20192.14 | 0.00 |
May | 0.00 | 0.00 | 0.281648E+10 | 0.253523E+10 | 22662.55 | 26-MAY-08:61 | 16061.31 | 0.00 |
June | 0.00 | 0.00 | 0.668770E+10 | 0.505860E+10 | 23976.25 | 27-JUN-20:02 | 12772.83 | 0.00 |
July | 0.00 | 0.00 | 0.104697E+11 | 0.743774E+10 | 24057.86 | 23-JUL-07:02 | 12418.60 | 0.00 |
August | 0.00 | 0.00 | 0.734749E+10 | 0.524662E+10 | 23959.53 | 31-AUG-20:02 | 12786.46 | 0.00 |
September | 0.00 | 0.00 | 0.113157E+10 | 0.937167E+09 | 22998.47 | 17-SEP-17:01 | 13667.49 | 0.00 |
October | 0.00 | 0.00 | 0.105153E+09 | 0.101132E+09 | 3565.50 | 19-OCT-15:00 | 3542.34 | 0.00 |
November | 0.00 | 0.00 | 720794.44 | 599020.66 | 990.79 | 01-NOV-20:20 | 829.52 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.287436E+11 | 0.214848E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.104697E+11 | 0.743774E+10 | 24057.86 | 20192.14 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 72068957.81 | 65371138.80 | 6280.50 | 23-APR-16:00 | 5814.26 | 0.00 |
May | 0.00 | 0.00 | 0.215798E+10 | 0.193743E+10 | 22601.73 | 26-MAY-07:01 | 15965.74 | 0.00 |
June | 0.00 | 0.00 | 0.516704E+10 | 0.398157E+10 | 24428.48 | 30-JUN-07:01 | 15014.83 | 0.00 |
July | 0.00 | 0.00 | 0.778264E+10 | 0.566409E+10 | 24398.52 | 23-JUL-08:61 | 12787.96 | 0.00 |
August | 0.00 | 0.00 | 0.554207E+10 | 0.402314E+10 | 23430.50 | 30-AUG-07:01 | 11799.74 | 0.00 |
September | 0.00 | 0.00 | 0.831857E+09 | 0.700308E+09 | 22800.78 | 01-SEP-07:01 | 11848.07 | 0.00 |
October | 0.00 | 0.00 | 68232040.50 | 65838151.98 | 3093.20 | 19-OCT-15:00 | 3075.29 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.216219E+11 | 0.164377E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.778264E+10 | 0.566409E+10 | 24428.48 | 15965.74 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 67862138.11 | 61512622.76 | 6062.16 | 23-APR-16:00 | 5608.36 | 0.00 |
May | 0.00 | 0.00 | 0.212712E+10 | 0.190781E+10 | 22659.69 | 26-MAY-07:01 | 16015.65 | 0.00 |
June | 0.00 | 0.00 | 0.515142E+10 | 0.396575E+10 | 24480.31 | 30-JUN-07:01 | 15084.53 | 0.00 |
July | 0.00 | 0.00 | 0.781577E+10 | 0.568675E+10 | 24465.18 | 23-JUL-08:61 | 12801.43 | 0.00 |
August | 0.00 | 0.00 | 0.553833E+10 | 0.401921E+10 | 23489.87 | 30-AUG-07:01 | 11835.10 | 0.00 |
September | 0.00 | 0.00 | 0.812941E+09 | 0.684020E+09 | 22860.07 | 01-SEP-07:01 | 11886.12 | 0.00 |
October | 0.00 | 0.00 | 59960902.96 | 57916610.36 | 2891.62 | 19-OCT-15:00 | 2875.62 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.215734E+11 | 0.163830E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.781577E+10 | 0.568675E+10 | 24480.31 | 16015.65 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 62031993.77 | 56166903.94 | 5727.13 | 23-APR-16:00 | 5288.81 | 0.00 |
May | 0.00 | 0.00 | 0.202134E+10 | 0.181027E+10 | 22521.76 | 26-MAY-07:01 | 15871.53 | 0.00 |
June | 0.00 | 0.00 | 0.497687E+10 | 0.382222E+10 | 24364.35 | 30-JUN-07:01 | 14902.84 | 0.00 |
July | 0.00 | 0.00 | 0.760451E+10 | 0.552562E+10 | 24315.06 | 23-JUL-08:61 | 12748.16 | 0.00 |
August | 0.00 | 0.00 | 0.535846E+10 | 0.388600E+10 | 23349.27 | 30-AUG-07:01 | 11722.08 | 0.00 |
September | 0.00 | 0.00 | 0.756279E+09 | 0.636265E+09 | 22723.15 | 01-SEP-07:01 | 11770.26 | 0.00 |
October | 0.00 | 0.00 | 48745806.83 | 47149876.28 | 2587.25 | 19-OCT-15:00 | 2570.94 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208282E+11 | 0.157837E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.760451E+10 | 0.552562E+10 | 24364.35 | 15871.53 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.102171E+09 | 90232362.01 | 10333.85 | 23-APR-15:00 | 9112.69 | 0.00 |
May | 0.00 | 0.00 | 0.350398E+10 | 0.307634E+10 | 41276.64 | 26-MAY-08:61 | 28393.06 | 0.00 |
June | 0.00 | 0.00 | 0.874424E+10 | 0.657599E+10 | 44230.78 | 30-JUN-08:61 | 27269.48 | 0.00 |
July | 0.00 | 0.00 | 0.134298E+11 | 0.957763E+10 | 44275.54 | 23-JUL-09:01 | 27043.03 | 0.00 |
August | 0.00 | 0.00 | 0.954107E+10 | 0.677001E+10 | 43216.35 | 30-AUG-08:61 | 22159.95 | 0.00 |
September | 0.00 | 0.00 | 0.126594E+10 | 0.105151E+10 | 41888.43 | 01-SEP-08:62 | 22251.16 | 0.00 |
October | 0.00 | 0.00 | 72137281.69 | 69286019.91 | 4573.28 | 19-OCT-15:00 | 4459.02 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.366593E+11 | 0.272110E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134298E+11 | 0.957763E+10 | 44275.54 | 28393.06 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 51059839.31 | 45211668.89 | 5266.42 | 23-APR-15:00 | 4654.49 | 0.00 |
May | 0.00 | 0.00 | 0.179273E+10 | 0.157733E+10 | 21277.88 | 26-MAY-08:61 | 14650.12 | 0.00 |
June | 0.00 | 0.00 | 0.449857E+10 | 0.338865E+10 | 22808.27 | 30-JUN-08:61 | 14085.94 | 0.00 |
July | 0.00 | 0.00 | 0.692597E+10 | 0.495340E+10 | 22842.41 | 23-JUL-09:01 | 13953.83 | 0.00 |
August | 0.00 | 0.00 | 0.491826E+10 | 0.350074E+10 | 22279.18 | 30-AUG-08:61 | 11432.41 | 0.00 |
September | 0.00 | 0.00 | 0.647078E+09 | 0.539052E+09 | 21594.68 | 01-SEP-08:62 | 11479.41 | 0.00 |
October | 0.00 | 0.00 | 36827721.35 | 35448234.89 | 2377.90 | 19-OCT-15:00 | 2325.14 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.188705E+11 | 0.140398E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.692597E+10 | 0.495340E+10 | 22842.41 | 14650.12 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 48539996.63 | 42936723.15 | 5079.11 | 23-APR-15:00 | 4482.68 | 0.00 |
May | 0.00 | 0.00 | 0.173944E+10 | 0.152870E+10 | 21185.11 | 26-MAY-08:61 | 14559.80 | 0.00 |
June | 0.00 | 0.00 | 0.441543E+10 | 0.331913E+10 | 22710.71 | 30-JUN-08:61 | 13980.06 | 0.00 |
July | 0.00 | 0.00 | 0.683207E+10 | 0.488009E+10 | 22753.24 | 23-JUL-09:01 | 13860.79 | 0.00 |
August | 0.00 | 0.00 | 0.483707E+10 | 0.344045E+10 | 22183.31 | 30-AUG-08:61 | 11362.46 | 0.00 |
September | 0.00 | 0.00 | 0.625140E+09 | 0.520098E+09 | 21501.67 | 01-SEP-08:62 | 11411.21 | 0.00 |
October | 0.00 | 0.00 | 33041317.80 | 31828916.53 | 2270.21 | 19-OCT-15:00 | 2218.38 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.185307E+11 | 0.137632E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.683207E+10 | 0.488009E+10 | 22753.24 | 14559.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 42576772.47 | 37599631.14 | 4620.70 | 23-APR-15:00 | 4067.27 | 0.00 |
May | 0.00 | 0.00 | 0.161333E+10 | 0.141552E+10 | 21281.37 | 26-MAY-08:61 | 14562.79 | 0.00 |
June | 0.00 | 0.00 | 0.422493E+10 | 0.316380E+10 | 22812.54 | 30-JUN-08:61 | 13955.96 | 0.00 |
July | 0.00 | 0.00 | 0.663437E+10 | 0.473159E+10 | 22878.57 | 23-JUL-09:01 | 13879.97 | 0.00 |
August | 0.00 | 0.00 | 0.464628E+10 | 0.330427E+10 | 22288.92 | 30-AUG-08:61 | 11360.72 | 0.00 |
September | 0.00 | 0.00 | 0.569613E+09 | 0.472306E+09 | 21604.31 | 01-SEP-08:62 | 11415.18 | 0.00 |
October | 0.00 | 0.00 | 23710998.49 | 22895837.93 | 1994.59 | 19-OCT-15:00 | 1948.09 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.177548E+11 | 0.131480E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.663437E+10 | 0.473159E+10 | 22878.57 | 14562.79 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:03 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:03 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 34220059.06 | 30385110.34 | 4059.25 | 23-APR-15:00 | 3586.33 | 0.00 |
May | 0.00 | 0.00 | 0.149803E+10 | 0.132347E+10 | 25638.12 | 26-MAY-08:61 | 17389.99 | 0.00 |
June | 0.00 | 0.00 | 0.418763E+10 | 0.315648E+10 | 27906.22 | 30-JUN-08:61 | 15392.46 | 0.00 |
July | 0.00 | 0.00 | 0.676999E+10 | 0.488885E+10 | 27616.54 | 23-JUL-09:01 | 16730.15 | 0.00 |
August | 0.00 | 0.00 | 0.453094E+10 | 0.327315E+10 | 26837.57 | 30-AUG-08:61 | 13625.72 | 0.00 |
September | 0.00 | 0.00 | 0.485774E+09 | 0.402320E+09 | 26011.61 | 01-SEP-08:62 | 13704.82 | 0.00 |
October | 0.00 | 0.00 | 9125107.52 | 8889397.69 | 1570.94 | 19-OCT-15:00 | 1550.63 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:05 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:02 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.175157E+11 | 0.130835E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.676999E+10 | 0.488885E+10 | 27906.22 | 17389.99 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.402000E+10 | 0.67 | 2199.29 | 10-JAN-08:10 | 0.92 |
February | 0.362349E+10 | 0.65 | 2199.29 | 01-FEB-08:10 | 0.92 |
March | 0.401526E+10 | 0.64 | 2199.29 | 03-MAR-21:00 | 0.92 |
April | 0.386637E+10 | 0.63 | 2199.29 | 05-APR-17:40 | 0.92 |
May | 0.399038E+10 | 0.62 | 2199.29 | 02-MAY-08:40 | 0.92 |
June | 0.387954E+10 | 0.62 | 2199.29 | 04-JUN-14:20 | 0.91 |
July | 0.399038E+10 | 0.61 | 2199.29 | 01-JUL-11:50 | 0.91 |
August | 0.399830E+10 | 0.61 | 2199.29 | 03-AUG-09:40 | 0.91 |
September | 0.387162E+10 | 0.62 | 2199.29 | 02-SEP-09:20 | 0.91 |
October | 0.399080E+10 | 0.62 | 2199.29 | 03-OCT-13:10 | 0.92 |
November | 0.386085E+10 | 0.63 | 2199.29 | 04-NOV-18:45 | 0.92 |
December | 0.402644E+10 | 0.66 | 2199.29 | 04-DEC-09:00 | 0.92 |
Annual Sum or Average | 0.471334E+11 | 0.63 | |||
Minimum of Months | 0.362349E+10 | 0.61 | 2199.29 | 0.91 | |
Maximum of Months | 0.402644E+10 | 0.67 | 2199.29 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.167540E+10 | 0.60 | 1221.80 | 01-JAN-08:27 | 0.95 |
February | 0.150576E+10 | 0.55 | 1221.80 | 06-FEB-19:50 | 0.95 |
March | 0.168740E+10 | 0.51 | 1221.80 | 22-MAR-16:30 | 0.95 |
April | 0.165815E+10 | 0.55 | 1221.80 | 18-APR-11:10 | 0.94 |
May | 0.201248E+10 | 0.63 | 1221.80 | 28-MAY-09:06 | 0.94 |
June | 0.198778E+10 | 0.62 | 1221.80 | 01-JUN-09:10 | 0.94 |
July | 0.199790E+10 | 0.61 | 1221.80 | 07-JUL-19:10 | 0.94 |
August | 0.205537E+10 | 0.61 | 1221.80 | 01-AUG-08:03 | 0.94 |
September | 0.199354E+10 | 0.63 | 1221.80 | 30-SEP-14:00 | 0.94 |
October | 0.175491E+10 | 0.56 | 1221.80 | 02-OCT-08:65 | 0.94 |
November | 0.161161E+10 | 0.49 | 1221.80 | 05-NOV-09:03 | 0.95 |
December | 0.166321E+10 | 0.58 | 1221.80 | 01-DEC-08:61 | 0.95 |
Annual Sum or Average | 0.216035E+11 | 0.58 | |||
Minimum of Months | 0.150576E+10 | 0.49 | 1221.80 | 0.94 | |
Maximum of Months | 0.205537E+10 | 0.63 | 1221.80 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177180E+10 | 0.52 | 1223.72 | 01-JAN-08:07 | 0.95 |
February | 0.160356E+10 | 0.52 | 1223.72 | 01-FEB-17:10 | 0.95 |
March | 0.180621E+10 | 0.52 | 1223.72 | 01-MAR-13:10 | 0.95 |
April | 0.171810E+10 | 0.51 | 1223.72 | 01-APR-14:20 | 0.95 |
May | 0.178859E+10 | 0.52 | 1223.72 | 01-MAY-07:07 | 0.95 |
June | 0.174453E+10 | 0.52 | 1223.72 | 01-JUN-18:30 | 0.95 |
July | 0.176215E+10 | 0.50 | 1223.72 | 01-JUL-08:03 | 0.94 |
August | 0.180621E+10 | 0.52 | 1223.72 | 01-AUG-08:15 | 0.94 |
September | 0.171810E+10 | 0.51 | 1223.72 | 01-SEP-07:15 | 0.93 |
October | 0.177096E+10 | 0.51 | 1223.72 | 04-OCT-08:50 | 0.95 |
November | 0.171810E+10 | 0.51 | 1223.72 | 02-NOV-08:10 | 0.95 |
December | 0.176278E+10 | 0.51 | 1223.72 | 01-DEC-08:50 | 0.95 |
Annual Sum or Average | 0.209711E+11 | 0.51 | |||
Minimum of Months | 0.160356E+10 | 0.50 | 1223.72 | 0.93 | |
Maximum of Months | 0.180621E+10 | 0.52 | 1223.72 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.177840E+10 | 0.52 | 1227.58 | 02-JAN-07:40 | 0.95 |
February | 0.160863E+10 | 0.52 | 1227.58 | 03-FEB-07:25 | 0.95 |
March | 0.181192E+10 | 0.52 | 1227.58 | 03-MAR-09:30 | 0.95 |
April | 0.172353E+10 | 0.51 | 1227.58 | 01-APR-07:06 | 0.95 |
May | 0.179424E+10 | 0.52 | 1227.58 | 01-MAY-11:50 | 0.95 |
June | 0.175004E+10 | 0.52 | 1227.58 | 05-JUN-17:00 | 0.94 |
July | 0.176772E+10 | 0.50 | 1227.58 | 01-JUL-13:40 | 0.94 |
August | 0.181192E+10 | 0.52 | 1227.58 | 06-AUG-09:08 | 0.94 |
September | 0.172353E+10 | 0.51 | 1227.58 | 02-SEP-12:20 | 0.94 |
October | 0.177656E+10 | 0.51 | 1227.58 | 05-OCT-11:30 | 0.95 |
November | 0.172353E+10 | 0.51 | 1227.58 | 02-NOV-15:50 | 0.95 |
December | 0.176885E+10 | 0.52 | 1227.58 | 02-DEC-07:50 | 0.95 |
Annual Sum or Average | 0.210389E+11 | 0.52 | |||
Minimum of Months | 0.160863E+10 | 0.50 | 1227.58 | 0.94 | |
Maximum of Months | 0.181192E+10 | 0.52 | 1227.58 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.176637E+10 | 0.53 | 1218.51 | 01-JAN-08:10 | 0.95 |
February | 0.159681E+10 | 0.52 | 1218.51 | 01-FEB-07:02 | 0.95 |
March | 0.179852E+10 | 0.52 | 1218.51 | 01-MAR-08:05 | 0.95 |
April | 0.171078E+10 | 0.51 | 1218.51 | 01-APR-07:04 | 0.95 |
May | 0.178097E+10 | 0.52 | 1218.51 | 01-MAY-07:10 | 0.95 |
June | 0.173710E+10 | 0.52 | 1218.51 | 01-JUN-11:20 | 0.94 |
July | 0.175465E+10 | 0.50 | 1218.51 | 01-JUL-07:03 | 0.94 |
August | 0.179852E+10 | 0.52 | 1218.51 | 01-AUG-07:40 | 0.94 |
September | 0.171078E+10 | 0.51 | 1218.51 | 23-SEP-07:20 | 0.95 |
October | 0.176342E+10 | 0.51 | 1218.51 | 03-OCT-11:40 | 0.95 |
November | 0.171078E+10 | 0.51 | 1218.51 | 01-NOV-07:40 | 0.95 |
December | 0.175657E+10 | 0.52 | 1218.51 | 01-DEC-07:27 | 0.95 |
Annual Sum or Average | 0.208853E+11 | 0.52 | |||
Minimum of Months | 0.159681E+10 | 0.50 | 1218.51 | 0.94 | |
Maximum of Months | 0.179852E+10 | 0.53 | 1218.51 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.282184E+10 | 0.50 | 2100.35 | 20-JAN-08:40 | 0.92 |
February | 0.254319E+10 | 0.47 | 2100.35 | 01-FEB-08:02 | 0.92 |
March | 0.286658E+10 | 0.47 | 2100.35 | 26-MAR-15:50 | 0.92 |
April | 0.272205E+10 | 0.46 | 2100.35 | 24-APR-13:50 | 0.92 |
May | 0.283547E+10 | 0.46 | 2100.35 | 08-MAY-09:40 | 0.92 |
June | 0.276742E+10 | 0.46 | 2100.35 | 01-JUN-09:00 | 0.91 |
July | 0.279010E+10 | 0.45 | 2100.35 | 31-JUL-09:30 | 0.91 |
August | 0.286572E+10 | 0.46 | 2100.35 | 01-AUG-08:03 | 0.91 |
September | 0.272205E+10 | 0.46 | 2100.35 | 01-SEP-19:07 | 0.90 |
October | 0.280523E+10 | 0.46 | 2100.35 | 03-OCT-08:30 | 0.91 |
November | 0.272205E+10 | 0.46 | 2100.35 | 30-NOV-19:00 | 0.92 |
December | 0.280129E+10 | 0.48 | 2100.35 | 17-DEC-10:00 | 0.92 |
Annual Sum or Average | 0.332630E+11 | 0.47 | |||
Minimum of Months | 0.254319E+10 | 0.45 | 2100.35 | 0.90 | |
Maximum of Months | 0.286658E+10 | 0.50 | 2100.35 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150927E+10 | 0.51 | 1124.36 | 11-JAN-17:00 | 0.95 |
February | 0.136111E+10 | 0.48 | 1124.36 | 01-FEB-16:40 | 0.95 |
March | 0.153444E+10 | 0.49 | 1124.36 | 01-MAR-09:05 | 0.95 |
April | 0.145717E+10 | 0.47 | 1124.36 | 04-APR-11:30 | 0.95 |
May | 0.151788E+10 | 0.48 | 1124.36 | 08-MAY-09:10 | 0.95 |
June | 0.148145E+10 | 0.48 | 1124.36 | 01-JUN-15:00 | 0.94 |
July | 0.149360E+10 | 0.46 | 1124.36 | 01-JUL-11:20 | 0.94 |
August | 0.153407E+10 | 0.48 | 1124.36 | 01-AUG-08:50 | 0.94 |
September | 0.145717E+10 | 0.47 | 1124.36 | 01-SEP-14:40 | 0.94 |
October | 0.150169E+10 | 0.47 | 1124.36 | 03-OCT-13:30 | 0.95 |
November | 0.145717E+10 | 0.47 | 1124.36 | 05-NOV-12:30 | 0.95 |
December | 0.149876E+10 | 0.50 | 1124.36 | 04-DEC-21:00 | 0.95 |
Annual Sum or Average | 0.178038E+11 | 0.48 | |||
Minimum of Months | 0.136111E+10 | 0.46 | 1124.36 | 0.94 | |
Maximum of Months | 0.153444E+10 | 0.51 | 1124.36 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.150121E+10 | 0.51 | 1118.07 | 28-JAN-08:09 | 0.95 |
February | 0.135367E+10 | 0.48 | 1118.07 | 03-FEB-08:40 | 0.95 |
March | 0.152593E+10 | 0.49 | 1118.07 | 10-MAR-09:00 | 0.95 |
April | 0.144901E+10 | 0.47 | 1118.07 | 06-APR-10:40 | 0.95 |
May | 0.150939E+10 | 0.48 | 1118.07 | 01-MAY-09:10 | 0.95 |
June | 0.147316E+10 | 0.48 | 1118.07 | 01-JUN-10:40 | 0.94 |
July | 0.148524E+10 | 0.46 | 1118.07 | 02-JUL-10:10 | 0.94 |
August | 0.152549E+10 | 0.48 | 1118.07 | 07-AUG-09:30 | 0.94 |
September | 0.144901E+10 | 0.47 | 1118.07 | 02-SEP-15:10 | 0.94 |
October | 0.149329E+10 | 0.47 | 1118.07 | 03-OCT-13:10 | 0.95 |
November | 0.144901E+10 | 0.47 | 1118.07 | 06-NOV-09:00 | 0.95 |
December | 0.149067E+10 | 0.50 | 1118.07 | 08-DEC-08:30 | 0.95 |
Annual Sum or Average | 0.177051E+11 | 0.48 | |||
Minimum of Months | 0.135367E+10 | 0.46 | 1118.07 | 0.94 | |
Maximum of Months | 0.152593E+10 | 0.51 | 1118.07 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.151072E+10 | 0.53 | 1122.49 | 01-JAN-10:04 | 0.95 |
February | 0.136102E+10 | 0.50 | 1122.49 | 01-FEB-09:08 | 0.95 |
March | 0.153252E+10 | 0.49 | 1122.49 | 01-MAR-09:03 | 0.95 |
April | 0.145475E+10 | 0.47 | 1122.49 | 01-APR-08:09 | 0.95 |
May | 0.151536E+10 | 0.48 | 1122.49 | 01-MAY-09:10 | 0.95 |
June | 0.147900E+10 | 0.48 | 1122.49 | 01-JUN-10:10 | 0.94 |
July | 0.149112E+10 | 0.46 | 1122.49 | 04-JUL-10:50 | 0.93 |
August | 0.153153E+10 | 0.48 | 1122.49 | 01-AUG-11:50 | 0.94 |
September | 0.145475E+10 | 0.47 | 1122.49 | 01-SEP-08:15 | 0.93 |
October | 0.149920E+10 | 0.47 | 1122.49 | 02-OCT-08:50 | 0.94 |
November | 0.145475E+10 | 0.47 | 1122.49 | 01-NOV-08:40 | 0.95 |
December | 0.149907E+10 | 0.51 | 1122.49 | 01-DEC-08:02 | 0.95 |
Annual Sum or Average | 0.177838E+11 | 0.48 | |||
Minimum of Months | 0.136102E+10 | 0.46 | 1122.49 | 0.93 | |
Maximum of Months | 0.153252E+10 | 0.53 | 1122.49 | 0.95 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.191967E+10 | 0.69 | 1372.63 | 01-JAN-15:30 | 0.95 |
February | 0.171533E+10 | 0.65 | 1372.63 | 01-FEB-12:40 | 0.95 |
March | 0.190163E+10 | 0.58 | 1372.63 | 01-MAR-14:30 | 0.95 |
April | 0.178253E+10 | 0.49 | 1372.63 | 02-APR-09:20 | 0.95 |
May | 0.185305E+10 | 0.48 | 1372.63 | 01-MAY-07:15 | 0.95 |
June | 0.180858E+10 | 0.48 | 1372.63 | 01-JUN-12:00 | 0.94 |
July | 0.182340E+10 | 0.46 | 1372.63 | 02-JUL-13:30 | 0.94 |
August | 0.187282E+10 | 0.48 | 1372.63 | 02-AUG-16:00 | 0.94 |
September | 0.177893E+10 | 0.47 | 1372.63 | 01-SEP-18:20 | 0.94 |
October | 0.183335E+10 | 0.47 | 1372.63 | 03-OCT-08:17 | 0.95 |
November | 0.178978E+10 | 0.52 | 1372.63 | 02-NOV-15:40 | 0.95 |
December | 0.189579E+10 | 0.66 | 1372.63 | 01-DEC-08:07 | 0.95 |
Annual Sum or Average | 0.219749E+11 | 0.54 | |||
Minimum of Months | 0.171533E+10 | 0.46 | 1372.63 | 0.94 | |
Maximum of Months | 0.191967E+10 | 0.69 | 1372.63 | 0.95 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.402000E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.362349E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.401526E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.394242E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.517651E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.687253E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.868648E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.714731E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.429404E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.401834E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.386085E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.402644E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.596837E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.362349E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.868648E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.167540E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.150576E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.168752E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.170740E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.276082E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.372611E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.467160E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.392071E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.228779E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.178381E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.161182E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.166321E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.290019E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.150576E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.467160E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177180E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160356E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.180621E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173809E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.237944E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.311954E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.380407E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.325503E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.193959E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.178980E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.171810E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176278E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.266880E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160356E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.380407E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.177840E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.160863E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.181192E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.174242E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.237711E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.312123E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.381805E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.326007E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.194000E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.179315E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.172353E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.176885E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.267433E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.160863E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.381805E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.176637E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.159681E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.179852E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.172813E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.233624E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.306423E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.375268E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.320175E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.191238E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.177696E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.171078E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.175657E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.264014E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.159681E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.375268E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.282184E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.254319E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.286658E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.275124E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.381801E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.513997E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.637745E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.540892E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.306564E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.282565E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.272205E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.280129E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.431418E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.254319E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.637745E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150927E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136111E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153444E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.147152E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.201194E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.268075E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.331130E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.282203E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.162972E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.151194E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145717E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149876E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.227999E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136111E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.331130E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.150121E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.135367E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.152593E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146269E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.198946E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.265108E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.327935E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.279295E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.161579E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150249E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.144901E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149067E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.226143E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.135367E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.327935E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.151072E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.136102E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.153252E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.146683E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.196281E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.260944E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.323788E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.275222E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.160694E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.150584E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.145475E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.149907E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.225000E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.136102E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.323788E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.191967E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171533E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.190163E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.179242E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.227562E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.294955E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.363443E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.308112E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.190969E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.183593E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.178978E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.189579E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.267010E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171533E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.363443E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.402000E+10 | 0.00 | 0.426866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362349E+10 | 0.00 | 0.286016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401526E+10 | 0.00 | 0.231303E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.386637E+10 | 0.268461E+09 | 0.760644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399038E+10 | 0.424465E+10 | 0.222575E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387954E+10 | 0.110565E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.399038E+10 | 0.176024E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399830E+10 | 0.118270E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387162E+10 | 0.155397E+10 | 19186546.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399080E+10 | 97468818.57 | 0.519051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386085E+10 | 0.00 | 0.171860E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402644E+10 | 0.00 | 0.396136E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471334E+11 | 0.466505E+11 | 0.164257E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.362349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402644E+10 | 0.176024E+11 | 0.426866E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.167540E+10 | 0.00 | 0.152512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150576E+10 | 0.00 | 0.957565E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168740E+10 | 415556.11 | 0.745894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165815E+10 | 0.184351E+09 | 0.189193E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201248E+10 | 0.281648E+10 | 21921642.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.198778E+10 | 0.668770E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199790E+10 | 0.104697E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205537E+10 | 0.734749E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199354E+10 | 0.113157E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175491E+10 | 0.105153E+09 | 0.116702E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161161E+10 | 720794.44 | 0.527475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166321E+10 | 0.00 | 0.140331E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216035E+11 | 0.287436E+11 | 0.546744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205537E+10 | 0.104697E+11 | 0.152512E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177180E+10 | 0.00 | 0.167000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160356E+10 | 0.00 | 0.108743E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180621E+10 | 0.00 | 0.870414E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171810E+10 | 72068957.81 | 0.245625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178859E+10 | 0.215798E+10 | 57010585.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174453E+10 | 0.516704E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176215E+10 | 0.778264E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180621E+10 | 0.554207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171810E+10 | 0.831857E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177096E+10 | 68232040.50 | 0.170022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171810E+10 | 0.00 | 0.634956E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176278E+10 | 0.00 | 0.153802E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209711E+11 | 0.216219E+11 | 0.622217E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180621E+10 | 0.778264E+10 | 0.167000E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.177840E+10 | 0.00 | 0.169912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160863E+10 | 0.00 | 0.110931E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181192E+10 | 0.00 | 0.891840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172353E+10 | 67862138.11 | 0.259051E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179424E+10 | 0.212712E+10 | 67952409.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175004E+10 | 0.515142E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176772E+10 | 0.781577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181192E+10 | 0.553833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172353E+10 | 0.812941E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177656E+10 | 59960902.96 | 0.185297E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172353E+10 | 0.00 | 0.658156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176885E+10 | 0.00 | 0.156414E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210389E+11 | 0.215734E+11 | 0.637372E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181192E+10 | 0.781577E+10 | 0.169912E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.176637E+10 | 0.00 | 0.174549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159681E+10 | 0.00 | 0.114909E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179852E+10 | 0.00 | 0.933177E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171078E+10 | 62031993.77 | 0.283823E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178097E+10 | 0.202134E+10 | 86703989.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173710E+10 | 0.497687E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175465E+10 | 0.760451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179852E+10 | 0.535846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171078E+10 | 0.756279E+09 | 1179986.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176342E+10 | 48745806.83 | 0.208442E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171078E+10 | 0.00 | 0.695853E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175657E+10 | 0.00 | 0.160888E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208853E+11 | 0.208282E+11 | 0.663354E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179852E+10 | 0.760451E+10 | 0.174549E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.282184E+10 | 0.00 | 0.332420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254319E+10 | 0.00 | 0.218289E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286658E+10 | 0.00 | 0.179134E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272205E+10 | 0.102171E+09 | 0.571084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283547E+10 | 0.350398E+10 | 0.206888E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276742E+10 | 0.874424E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279010E+10 | 0.134298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286572E+10 | 0.954107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272205E+10 | 0.126594E+10 | 32175962.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280523E+10 | 72137281.69 | 0.451794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272205E+10 | 0.00 | 0.136203E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280129E+10 | 0.00 | 0.307015E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332630E+11 | 0.366593E+11 | 0.127774E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.254319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.286658E+10 | 0.134298E+11 | 0.332420E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150927E+10 | 0.00 | 0.171676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136111E+10 | 0.00 | 0.113081E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153444E+10 | 0.00 | 0.929057E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145717E+10 | 51059839.31 | 0.298257E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151788E+10 | 0.179273E+10 | 0.110043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148145E+10 | 0.449857E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149360E+10 | 0.692597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153407E+10 | 0.491826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145717E+10 | 0.647078E+09 | 18173208.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150169E+10 | 36827721.35 | 0.234033E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145717E+10 | 0.00 | 0.706126E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149876E+10 | 0.00 | 0.158749E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178038E+11 | 0.188705E+11 | 0.661536E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153444E+10 | 0.692597E+10 | 0.171676E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.150121E+10 | 0.00 | 0.172486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135367E+10 | 0.00 | 0.113991E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152593E+10 | 0.00 | 0.940626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144901E+10 | 48539996.63 | 0.309104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150939E+10 | 0.173944E+10 | 0.129430E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147316E+10 | 0.441543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148524E+10 | 0.683207E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152549E+10 | 0.483707E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144901E+10 | 0.625140E+09 | 28405134.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149329E+10 | 33041317.80 | 0.243094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144901E+10 | 0.00 | 0.717111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149067E+10 | 0.00 | 0.159576E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177051E+11 | 0.185307E+11 | 0.668625E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152593E+10 | 0.683207E+10 | 0.172486E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.151072E+10 | 0.00 | 0.177959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136102E+10 | 0.00 | 0.118810E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153252E+10 | 0.00 | 0.993985E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145475E+10 | 42576772.47 | 0.347416E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151536E+10 | 0.161333E+10 | 0.195140E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147900E+10 | 0.422493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149112E+10 | 0.663437E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153153E+10 | 0.464628E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145475E+10 | 0.569613E+09 | 74093010.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149920E+10 | 23710998.49 | 0.272170E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145475E+10 | 0.00 | 0.761024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149907E+10 | 0.00 | 0.164840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177838E+11 | 0.177548E+11 | 0.701761E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153252E+10 | 0.663437E+10 | 0.177959E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.191967E+10 | 0.00 | 0.229067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171533E+10 | 0.00 | 0.157028E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190163E+10 | 0.00 | 0.131316E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178253E+10 | 34220059.06 | 0.491213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185305E+10 | 0.149803E+10 | 0.400813E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180858E+10 | 0.418763E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182340E+10 | 0.676999E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187282E+10 | 0.453094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177893E+10 | 0.485774E+09 | 0.229968E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183335E+10 | 9125107.52 | 0.363773E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178978E+10 | 0.00 | 0.975802E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189579E+10 | 0.00 | 0.211398E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219749E+11 | 0.175157E+11 | 0.918195E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191967E+10 | 0.676999E+10 | 0.229067E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.402000E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.362349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.401526E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.386637E+10 | 0.00 | 0.00 | 0.00 | 76056545.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399038E+10 | 0.00 | 0.00 | 0.00 | 0.118612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.387954E+10 | 0.00 | 0.00 | 0.00 | 0.299299E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.399038E+10 | 0.00 | 0.00 | 0.00 | 0.469609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.399830E+10 | 0.00 | 0.00 | 0.00 | 0.314901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.387162E+10 | 0.00 | 0.00 | 0.00 | 0.422414E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.399080E+10 | 0.00 | 0.00 | 0.00 | 27535488.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.386085E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.402644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.471334E+11 | 0.00 | 0.00 | 0.00 | 0.125502E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.362349E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.402644E+10 | 0.00 | 0.00 | 0.00 | 0.469609E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.167540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.150576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.168740E+10 | 0.00 | 0.00 | 0.00 | 116583.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.165815E+10 | 0.00 | 0.00 | 0.00 | 49253911.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.201248E+10 | 0.00 | 0.00 | 0.00 | 0.748333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.198778E+10 | 0.00 | 0.00 | 0.00 | 0.173833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199790E+10 | 0.00 | 0.00 | 0.00 | 0.267370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.205537E+10 | 0.00 | 0.00 | 0.00 | 0.186534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.199354E+10 | 0.00 | 0.00 | 0.00 | 0.294246E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.175491E+10 | 0.00 | 0.00 | 0.00 | 28897721.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.161161E+10 | 0.00 | 0.00 | 0.00 | 202048.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.166321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.216035E+11 | 0.00 | 0.00 | 0.00 | 0.739842E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.150576E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.205537E+10 | 0.00 | 0.00 | 0.00 | 0.267370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177180E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.180621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171810E+10 | 0.00 | 0.00 | 0.00 | 19990151.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178859E+10 | 0.00 | 0.00 | 0.00 | 0.590852E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.174453E+10 | 0.00 | 0.00 | 0.00 | 0.137501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176215E+10 | 0.00 | 0.00 | 0.00 | 0.204191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.180621E+10 | 0.00 | 0.00 | 0.00 | 0.144882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171810E+10 | 0.00 | 0.00 | 0.00 | 0.221485E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177096E+10 | 0.00 | 0.00 | 0.00 | 18839033.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171810E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.209711E+11 | 0.00 | 0.00 | 0.00 | 0.571691E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.180621E+10 | 0.00 | 0.00 | 0.00 | 0.204191E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.177840E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.160863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.181192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.172353E+10 | 0.00 | 0.00 | 0.00 | 18887257.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.179424E+10 | 0.00 | 0.00 | 0.00 | 0.582873E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.175004E+10 | 0.00 | 0.00 | 0.00 | 0.137118E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.176772E+10 | 0.00 | 0.00 | 0.00 | 0.205032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.181192E+10 | 0.00 | 0.00 | 0.00 | 0.144816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.172353E+10 | 0.00 | 0.00 | 0.00 | 0.216473E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177656E+10 | 0.00 | 0.00 | 0.00 | 16591376.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.172353E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.176885E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.210389E+11 | 0.00 | 0.00 | 0.00 | 0.570449E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.160863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.181192E+10 | 0.00 | 0.00 | 0.00 | 0.205032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.176637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.159681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179852E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.171078E+10 | 0.00 | 0.00 | 0.00 | 17345872.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.178097E+10 | 0.00 | 0.00 | 0.00 | 0.555273E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.173710E+10 | 0.00 | 0.00 | 0.00 | 0.132712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.175465E+10 | 0.00 | 0.00 | 0.00 | 0.199803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.179852E+10 | 0.00 | 0.00 | 0.00 | 0.140323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.171078E+10 | 0.00 | 0.00 | 0.00 | 0.201599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.176342E+10 | 0.00 | 0.00 | 0.00 | 13534161.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.175657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.208853E+11 | 0.00 | 0.00 | 0.00 | 0.551614E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.159681E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.179852E+10 | 0.00 | 0.00 | 0.00 | 0.199803E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.282184E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.254319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.286658E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.272205E+10 | 0.00 | 0.00 | 0.00 | 29187638.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.283547E+10 | 0.00 | 0.00 | 0.00 | 0.982538E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.276742E+10 | 0.00 | 0.00 | 0.00 | 0.237255E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.279010E+10 | 0.00 | 0.00 | 0.00 | 0.358735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.286572E+10 | 0.00 | 0.00 | 0.00 | 0.254320E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.272205E+10 | 0.00 | 0.00 | 0.00 | 0.343582E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.280523E+10 | 0.00 | 0.00 | 0.00 | 20427763.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.272205E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.280129E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.332630E+11 | 0.00 | 0.00 | 0.00 | 0.987883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.254319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.286658E+10 | 0.00 | 0.00 | 0.00 | 0.358735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150927E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153444E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145717E+10 | 0.00 | 0.00 | 0.00 | 14350004.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151788E+10 | 0.00 | 0.00 | 0.00 | 0.494054E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.148145E+10 | 0.00 | 0.00 | 0.00 | 0.119930E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149360E+10 | 0.00 | 0.00 | 0.00 | 0.181771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153407E+10 | 0.00 | 0.00 | 0.00 | 0.128795E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145717E+10 | 0.00 | 0.00 | 0.00 | 0.172556E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.150169E+10 | 0.00 | 0.00 | 0.00 | 10245349.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149876E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.178038E+11 | 0.00 | 0.00 | 0.00 | 0.499617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136111E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153444E+10 | 0.00 | 0.00 | 0.00 | 0.181771E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.150121E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.135367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.152593E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 13676997.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.150939E+10 | 0.00 | 0.00 | 0.00 | 0.480073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147316E+10 | 0.00 | 0.00 | 0.00 | 0.117791E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.148524E+10 | 0.00 | 0.00 | 0.00 | 0.179411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.152549E+10 | 0.00 | 0.00 | 0.00 | 0.126746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.166774E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149329E+10 | 0.00 | 0.00 | 0.00 | 9205264.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.144901E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149067E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177051E+11 | 0.00 | 0.00 | 0.00 | 0.490921E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.135367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.152593E+10 | 0.00 | 0.00 | 0.00 | 0.179411E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.151072E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.136102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.153252E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.145475E+10 | 0.00 | 0.00 | 0.00 | 12081741.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.151536E+10 | 0.00 | 0.00 | 0.00 | 0.447449E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.147900E+10 | 0.00 | 0.00 | 0.00 | 0.113044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.149112E+10 | 0.00 | 0.00 | 0.00 | 0.174676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.153153E+10 | 0.00 | 0.00 | 0.00 | 0.122069E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.145475E+10 | 0.00 | 0.00 | 0.00 | 0.152189E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.149920E+10 | 0.00 | 0.00 | 0.00 | 6635267.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.145475E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.149907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.177838E+11 | 0.00 | 0.00 | 0.00 | 0.471626E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.136102E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.153252E+10 | 0.00 | 0.00 | 0.00 | 0.174676E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.191967E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.171533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.190163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178253E+10 | 0.00 | 0.00 | 0.00 | 9888912.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185305E+10 | 0.00 | 0.00 | 0.00 | 0.422569E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.180858E+10 | 0.00 | 0.00 | 0.00 | 0.114098E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182340E+10 | 0.00 | 0.00 | 0.00 | 0.181103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187282E+10 | 0.00 | 0.00 | 0.00 | 0.120831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.177893E+10 | 0.00 | 0.00 | 0.00 | 0.130760E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183335E+10 | 0.00 | 0.00 | 0.00 | 2582737.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178978E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.189579E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.219749E+11 | 0.00 | 0.00 | 0.00 | 0.472611E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.171533E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.191967E+10 | 0.00 | 0.00 | 0.00 | 0.181103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.571172E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.302457E+11 | 0.00 | 0.00 | 0.52 |
February | 0.213538E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.211118E+11 | 0.00 | 0.00 | 0.52 |
March | 0.457783E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168416E+11 | 0.00 | 0.00 | 0.53 |
April | 0.765831E+10 | 14531236.83 | 0.00 | 1001526.33 | 0.00 | 0.472482E+10 | 0.855864E+09 | 0.00 | 0.56 |
May | 0.365311E+10 | 0.293266E+09 | 0.00 | 11520967.25 | 0.00 | 82285603.43 | 0.548047E+10 | 0.00 | 0.91 |
June | 0.903042E+09 | 0.205365E+10 | 0.00 | 15401901.96 | 5199240.49 | 0.00 | 0.606489E+10 | 0.00 | 1.17 |
July | 0.162505E+09 | 0.336333E+10 | 0.00 | 19308986.01 | 10288131.76 | 0.00 | 0.533586E+10 | 0.00 | 1.21 |
August | 0.341601E+09 | 0.151018E+10 | 0.00 | 22621711.31 | 604001.87 | 0.00 | 0.746958E+10 | 0.00 | 1.33 |
September | 0.345638E+10 | 58399474.62 | 0.00 | 11910428.31 | 0.00 | 1118566.98 | 0.849152E+10 | 0.00 | 0.96 |
October | 0.904788E+10 | 0.00 | 0.00 | 1776273.45 | 0.00 | 0.299428E+10 | 0.172405E+10 | 0.00 | 0.59 |
November | 0.644139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117539E+11 | 0.00 | 0.00 | 0.53 |
December | 0.798670E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.284780E+11 | 0.00 | 0.00 | 0.52 |
Annual Sum or Average | 0.397473E+11 | 0.729335E+10 | 0.00 | 83541794.63 | 16091374.12 | 0.116233E+12 | 0.354222E+11 | 0.00 | 0.78 |
Minimum of Months | 0.162505E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.904788E+10 | 0.336333E+10 | 0.00 | 22621711.31 | 10288131.76 | 0.302457E+11 | 0.849152E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.564196E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108220E+11 | 0.00 | 0.00 | 0.39 |
February | 0.141194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.696869E+10 | 0.00 | 0.00 | 0.38 |
March | 0.266923E+10 | 0.00 | 0.00 | 1264.12 | 0.00 | 0.520188E+10 | 522198.62 | 0.00 | 0.39 |
April | 0.276882E+10 | 6693783.55 | 0.00 | 1067447.85 | 0.00 | 0.139529E+10 | 0.992777E+09 | 0.00 | 0.47 |
May | 0.105713E+10 | 0.156325E+09 | 0.00 | 6442117.35 | 209569.19 | 7961691.73 | 0.375360E+10 | 0.00 | 0.94 |
June | 88827712.05 | 0.105158E+10 | 0.00 | 7765545.04 | 6425610.90 | 0.00 | 0.354192E+10 | 0.00 | 1.20 |
July | 12621530.58 | 0.181268E+10 | 0.00 | 7182829.47 | 13965754.55 | 0.00 | 0.245319E+10 | 0.00 | 1.12 |
August | 79754406.06 | 0.827762E+09 | 0.00 | 10354963.26 | 823517.44 | 0.00 | 0.369278E+10 | 0.00 | 1.33 |
September | 0.980787E+09 | 30827560.89 | 0.00 | 7853481.48 | 0.00 | 0.00 | 0.546209E+10 | 0.00 | 1.05 |
October | 0.351967E+10 | 0.00 | 0.00 | 1714579.19 | 0.00 | 0.691192E+09 | 0.143289E+10 | 0.00 | 0.52 |
November | 0.275156E+10 | 0.00 | 0.00 | 16123.55 | 0.00 | 0.377908E+10 | 23346665.89 | 0.00 | 0.39 |
December | 0.721539E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.993739E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.166261E+11 | 0.388587E+10 | 0.00 | 42398351.30 | 21424452.08 | 0.388035E+11 | 0.213531E+11 | 0.00 | 0.71 |
Minimum of Months | 12621530.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.351967E+10 | 0.181268E+10 | 0.00 | 10354963.26 | 13965754.55 | 0.108220E+11 | 0.546209E+10 | 0.00 | 1.33 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.132394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.118802E+11 | 0.00 | 0.00 | 0.41 |
February | 0.759628E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817800E+10 | 0.00 | 0.00 | 0.41 |
March | 0.178457E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.660355E+10 | 0.00 | 0.00 | 0.42 |
April | 0.282378E+10 | 4579706.69 | 0.00 | 447206.33 | 1116003.05 | 0.173998E+10 | 0.513925E+09 | 0.00 | 0.46 |
May | 0.145327E+10 | 0.149680E+09 | 0.00 | 3260013.92 | 1302563.94 | 28613434.65 | 0.195825E+10 | 0.00 | 0.74 |
June | 0.239829E+09 | 0.853530E+09 | 0.00 | 5245171.91 | 39738692.26 | 0.00 | 0.227886E+10 | 0.00 | 0.97 |
July | 91959752.61 | 0.133001E+10 | 0.00 | 5668404.88 | 80804612.95 | 0.00 | 0.165081E+10 | 0.00 | 0.91 |
August | 0.238795E+09 | 0.688988E+09 | 0.00 | 7228064.01 | 14907764.32 | 0.00 | 0.254005E+10 | 0.00 | 1.08 |
September | 0.143369E+10 | 32100189.81 | 0.00 | 4726381.72 | 0.00 | 0.00 | 0.328433E+10 | 0.00 | 0.83 |
October | 0.355306E+10 | 0.00 | 0.00 | 796805.71 | 0.00 | 0.994796E+09 | 0.693066E+09 | 0.00 | 0.49 |
November | 0.215617E+10 | 0.00 | 13435.34 | 1466.39 | 27839.88 | 0.469524E+10 | 6706614.17 | 370.23 | 0.41 |
December | 0.173236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110497E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.148404E+11 | 0.305888E+10 | 13435.34 | 27373514.86 | 0.137897E+09 | 0.451700E+11 | 0.129260E+11 | 370.23 | 0.63 |
Minimum of Months | 91959752.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.355306E+10 | 0.133001E+10 | 13435.34 | 7228064.01 | 80804612.95 | 0.118802E+11 | 0.328433E+10 | 370.23 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 86460488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119247E+11 | 0.00 | 0.00 | 0.41 |
February | 0.658375E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.827785E+10 | 0.00 | 0.00 | 0.41 |
March | 0.159575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.679018E+10 | 0.00 | 0.00 | 0.42 |
April | 0.272821E+10 | 4494813.84 | 0.00 | 380459.66 | 1126539.61 | 0.186029E+10 | 0.448544E+09 | 0.00 | 0.46 |
May | 0.148792E+10 | 0.149216E+09 | 0.00 | 3117936.60 | 1294350.45 | 40326673.43 | 0.186388E+10 | 0.00 | 0.73 |
June | 0.247314E+09 | 0.852379E+09 | 0.00 | 5159024.42 | 39925629.23 | 0.00 | 0.225447E+10 | 0.00 | 0.97 |
July | 92728072.52 | 0.133217E+10 | 0.00 | 5728208.52 | 80367994.71 | 0.00 | 0.165576E+10 | 0.00 | 0.92 |
August | 0.240606E+09 | 0.687892E+09 | 0.00 | 7248303.39 | 14802576.77 | 0.00 | 0.254691E+10 | 0.00 | 1.08 |
September | 0.146704E+10 | 32130105.48 | 0.00 | 4600506.92 | 0.00 | 0.00 | 0.320961E+10 | 0.00 | 0.82 |
October | 0.340734E+10 | 0.00 | 0.00 | 718420.57 | 0.00 | 0.115498E+10 | 0.639769E+09 | 0.00 | 0.48 |
November | 0.191831E+10 | 0.00 | 58513.82 | 0.00 | 0.00 | 0.493611E+10 | 0.00 | 1657.50 | 0.41 |
December | 0.132605E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110888E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.140627E+11 | 0.305828E+10 | 58513.82 | 26952860.08 | 0.137517E+09 | 0.460732E+11 | 0.126189E+11 | 1657.50 | 0.63 |
Minimum of Months | 86460488.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.340734E+10 | 0.133217E+10 | 58513.82 | 7248303.39 | 80367994.71 | 0.119247E+11 | 0.320961E+10 | 1657.50 | 1.08 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 59753120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119526E+11 | 0.00 | 0.00 | 0.41 |
February | 0.419046E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.851823E+10 | 0.00 | 0.00 | 0.41 |
March | 0.128689E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709955E+10 | 0.00 | 0.00 | 0.42 |
April | 0.251707E+10 | 4381143.90 | 0.00 | 278499.27 | 1155511.70 | 0.209424E+10 | 0.363962E+09 | 0.00 | 0.45 |
May | 0.158725E+10 | 0.147068E+09 | 0.00 | 2717986.20 | 1300557.40 | 51346388.10 | 0.162783E+10 | 0.00 | 0.71 |
June | 0.301723E+09 | 0.843966E+09 | 0.00 | 4695338.81 | 38525432.99 | 0.00 | 0.211387E+10 | 0.00 | 0.95 |
July | 93012259.33 | 0.131395E+10 | 0.00 | 5421399.14 | 80220526.01 | 0.00 | 0.162920E+10 | 0.00 | 0.90 |
August | 0.257276E+09 | 0.674238E+09 | 0.00 | 6816017.33 | 14789465.71 | 0.00 | 0.247087E+10 | 0.00 | 1.06 |
September | 0.153251E+10 | 31501483.15 | 0.00 | 4161847.07 | 0.00 | 0.00 | 0.299487E+10 | 0.00 | 0.80 |
October | 0.316814E+10 | 0.00 | 0.00 | 585525.03 | 0.00 | 0.142010E+10 | 0.552262E+09 | 0.00 | 0.48 |
November | 0.165622E+10 | 0.00 | 51082.89 | 0.00 | 19597.21 | 0.519550E+10 | 0.00 | 4862.31 | 0.41 |
December | 80276478.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111423E+11 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.129592E+11 | 0.301511E+10 | 51082.89 | 24676612.84 | 0.136011E+09 | 0.474739E+11 | 0.117529E+11 | 4862.31 | 0.62 |
Minimum of Months | 59753120.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.316814E+10 | 0.131395E+10 | 51082.89 | 6816017.33 | 80220526.01 | 0.119526E+11 | 0.299487E+10 | 4862.31 | 1.06 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 22309318.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221329E+11 | 0.00 | 0.00 | 0.38 |
February | 0.330148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161031E+11 | 0.00 | 0.00 | 0.38 |
March | 0.146172E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139931E+11 | 0.00 | 0.00 | 0.39 |
April | 0.429924E+10 | 5417324.58 | 0.00 | 282136.24 | 2085788.18 | 0.433740E+10 | 0.427740E+09 | 0.00 | 0.40 |
May | 0.293483E+10 | 0.240867E+09 | 0.00 | 4142528.11 | 161209.63 | 93735714.58 | 0.258868E+10 | 0.00 | 0.62 |
June | 0.647404E+09 | 0.158057E+10 | 0.00 | 7135317.42 | 25095363.90 | 0.00 | 0.351725E+10 | 0.00 | 0.81 |
July | 0.127955E+09 | 0.245969E+10 | 0.00 | 8415352.62 | 80471538.24 | 0.00 | 0.281966E+10 | 0.00 | 0.77 |
August | 0.334677E+09 | 0.122810E+10 | 0.00 | 10516402.06 | 4144187.45 | 0.00 | 0.423113E+10 | 0.00 | 0.91 |
September | 0.286966E+10 | 47621913.49 | 0.00 | 6298508.20 | 0.00 | 1014186.98 | 0.496027E+10 | 0.00 | 0.67 |
October | 0.537911E+10 | 0.00 | 0.00 | 772865.76 | 0.00 | 0.321623E+10 | 0.798640E+09 | 0.00 | 0.42 |
November | 0.198597E+10 | 0.00 | 35287.34 | 0.00 | 60229.66 | 0.107341E+11 | 0.00 | 45085.85 | 0.38 |
December | 55818751.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.206909E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.204488E+11 | 0.556227E+10 | 35287.34 | 37563110.40 | 0.112018E+09 | 0.913026E+11 | 0.193434E+11 | 45085.85 | 0.54 |
Minimum of Months | 22309318.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.537911E+10 | 0.245969E+10 | 35287.34 | 10516402.06 | 80471538.24 | 0.221329E+11 | 0.496027E+10 | 45085.85 | 0.91 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 8730972.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110563E+11 | 0.00 | 0.00 | 0.38 |
February | 0.127668E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.807793E+10 | 0.00 | 0.00 | 0.38 |
March | 0.607649E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.710724E+10 | 0.00 | 0.00 | 0.39 |
April | 0.202351E+10 | 2714812.65 | 0.00 | 116867.80 | 1105906.26 | 0.230290E+10 | 0.185531E+09 | 0.00 | 0.40 |
May | 0.148085E+10 | 0.121265E+09 | 0.00 | 1987900.51 | 109646.88 | 51876311.97 | 0.127296E+10 | 0.00 | 0.62 |
June | 0.369290E+09 | 0.794599E+09 | 0.00 | 3528574.99 | 12762765.35 | 0.00 | 0.174058E+10 | 0.00 | 0.83 |
July | 72086967.14 | 0.123532E+10 | 0.00 | 4170077.50 | 40583870.69 | 0.00 | 0.143953E+10 | 0.00 | 0.79 |
August | 0.163995E+09 | 0.619285E+09 | 0.00 | 5235989.41 | 1942270.24 | 0.00 | 0.217539E+10 | 0.00 | 0.94 |
September | 0.145696E+10 | 24266601.92 | 0.00 | 3135805.27 | 0.00 | 0.00 | 0.249264E+10 | 0.00 | 0.69 |
October | 0.254673E+10 | 0.00 | 0.00 | 377782.04 | 0.00 | 0.174833E+10 | 0.393322E+09 | 0.00 | 0.43 |
November | 0.885089E+09 | 0.00 | 18371.97 | 0.00 | 26319.74 | 0.546245E+10 | 0.00 | 23893.39 | 0.38 |
December | 13139546.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103477E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.975570E+10 | 0.279745E+10 | 18371.97 | 18552997.53 | 56530779.16 | 0.461548E+11 | 0.969995E+10 | 23893.39 | 0.55 |
Minimum of Months | 8730972.69 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.254673E+10 | 0.123532E+10 | 18371.97 | 5235989.41 | 40583870.69 | 0.110563E+11 | 0.249264E+10 | 23893.39 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 7755924.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110572E+11 | 0.00 | 0.00 | 0.38 |
February | 0.101458E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.810411E+10 | 0.00 | 0.00 | 0.38 |
March | 0.548818E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.716597E+10 | 0.00 | 0.00 | 0.39 |
April | 0.192130E+10 | 2648703.41 | 0.00 | 97747.21 | 1186182.85 | 0.240969E+10 | 0.163741E+09 | 0.00 | 0.39 |
May | 0.151314E+10 | 0.119878E+09 | 0.00 | 1843693.99 | 108507.47 | 54950083.49 | 0.119158E+10 | 0.00 | 0.61 |
June | 0.406645E+09 | 0.789335E+09 | 0.00 | 3348287.22 | 12494943.36 | 0.00 | 0.166623E+10 | 0.00 | 0.82 |
July | 78519261.23 | 0.122693E+10 | 0.00 | 4042279.68 | 39522384.87 | 0.00 | 0.142141E+10 | 0.00 | 0.78 |
August | 0.177389E+09 | 0.612747E+09 | 0.00 | 5061981.05 | 1898523.22 | 0.00 | 0.213894E+10 | 0.00 | 0.93 |
September | 0.149443E+10 | 23999508.25 | 0.00 | 2972673.06 | 0.00 | 504371.61 | 0.239497E+10 | 0.00 | 0.68 |
October | 0.250785E+10 | 0.00 | 0.00 | 349685.29 | 0.00 | 0.179808E+10 | 0.364258E+09 | 0.00 | 0.42 |
November | 0.825246E+09 | 0.00 | 16533.72 | 0.00 | 25397.64 | 0.552148E+10 | 0.00 | 26018.92 | 0.38 |
December | 12114804.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103487E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.959466E+10 | 0.277554E+10 | 16533.72 | 17716347.50 | 55235939.42 | 0.464607E+11 | 0.934113E+10 | 26018.92 | 0.55 |
Minimum of Months | 7755924.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.250785E+10 | 0.122693E+10 | 16533.72 | 5061981.05 | 39522384.87 | 0.110572E+11 | 0.239497E+10 | 26018.92 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 6750145.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110590E+11 | 0.00 | 0.00 | 0.38 |
February | 39436391.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.816677E+10 | 0.00 | 0.00 | 0.38 |
March | 0.384431E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.733105E+10 | 0.00 | 0.00 | 0.39 |
April | 0.155613E+10 | 2488913.37 | 0.00 | 53585.89 | 1487810.25 | 0.278794E+10 | 0.112692E+09 | 0.00 | 0.39 |
May | 0.155350E+10 | 0.116045E+09 | 0.00 | 1500602.51 | 79204.67 | 88952821.89 | 0.101539E+10 | 0.00 | 0.60 |
June | 0.448288E+09 | 0.776741E+09 | 0.00 | 2921385.41 | 12877545.05 | 0.00 | 0.154453E+10 | 0.00 | 0.80 |
July | 0.112630E+09 | 0.120755E+10 | 0.00 | 3718881.63 | 39567334.09 | 0.00 | 0.137520E+10 | 0.00 | 0.78 |
August | 0.228689E+09 | 0.598479E+09 | 0.00 | 4615436.90 | 1993049.31 | 0.00 | 0.205045E+10 | 0.00 | 0.92 |
September | 0.160817E+10 | 23521492.89 | 0.00 | 2556358.01 | 0.00 | 6586484.59 | 0.214666E+10 | 0.00 | 0.66 |
October | 0.216189E+10 | 0.00 | 0.00 | 289209.33 | 0.00 | 0.214380E+10 | 0.326947E+09 | 0.00 | 0.42 |
November | 0.561727E+09 | 0.00 | 15406.58 | 0.00 | 20215.63 | 0.578335E+10 | 0.00 | 34565.34 | 0.38 |
December | 8920305.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103527E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.867057E+10 | 0.272483E+10 | 15406.58 | 15655459.69 | 56025159.00 | 0.477202E+11 | 0.857187E+10 | 34565.34 | 0.54 |
Minimum of Months | 6750145.74 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.216189E+10 | 0.120755E+10 | 15406.58 | 4615436.90 | 39567334.09 | 0.110590E+11 | 0.214666E+10 | 34565.34 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 4083093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.110422E+11 | 0.00 | 0.00 | 0.38 |
February | 6735126.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.817641E+10 | 0.00 | 0.00 | 0.38 |
March | 32669823.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765771E+10 | 0.00 | 0.00 | 0.39 |
April | 0.854709E+09 | 2299660.50 | 598328.64 | 6676.80 | 1300427.39 | 0.350909E+10 | 30184100.99 | 5835.72 | 0.39 |
May | 0.129932E+10 | 0.110928E+09 | 0.00 | 1030430.19 | 7645.55 | 0.352554E+09 | 0.908226E+09 | 0.00 | 0.62 |
June | 0.520235E+09 | 0.765852E+09 | 0.00 | 2439023.40 | 13039688.92 | 0.00 | 0.151123E+10 | 0.00 | 0.87 |
July | 0.154479E+09 | 0.120353E+10 | 0.00 | 3397179.70 | 40724365.04 | 0.00 | 0.151343E+10 | 0.00 | 0.87 |
August | 0.335320E+09 | 0.591170E+09 | 0.00 | 3966499.89 | 1661740.33 | 0.00 | 0.211506E+10 | 0.00 | 1.02 |
September | 0.160955E+10 | 24893604.53 | 0.00 | 2052911.37 | 0.00 | 0.143241E+09 | 0.196414E+10 | 0.00 | 0.68 |
October | 0.124085E+10 | 0.00 | 0.00 | 226505.23 | 0.00 | 0.303497E+10 | 0.313799E+09 | 0.00 | 0.42 |
November | 97911460.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.622913E+10 | 0.00 | 17382.28 | 0.38 |
December | 6522816.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103341E+11 | 0.00 | 0.00 | 0.37 |
Annual Sum or Average | 0.616239E+10 | 0.269868E+10 | 598328.64 | 13119226.58 | 56733867.24 | 0.504794E+11 | 0.835607E+10 | 23218.00 | 0.56 |
Minimum of Months | 4083093.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.37 |
Maximum of Months | 0.160955E+10 | 0.120353E+10 | 598328.64 | 3966499.89 | 40724365.04 | 0.110422E+11 | 0.211506E+10 | 17382.28 | 1.02 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:29
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.118155E+12 | 0.682641E+11 | 0.00 | 0.146101E+12 | 0.543612E+11 |
February | 0.203506E+12 | 0.501069E+11 | 0.00 | 0.109969E+12 | 0.359389E+11 |
March | 0.309586E+12 | 0.440262E+11 | 0.00 | 0.103699E+12 | 0.293068E+11 |
April | 0.413381E+12 | 0.267541E+11 | 0.00 | 0.620219E+11 | 0.105826E+11 |
May | 0.497918E+12 | 0.118232E+11 | 0.00 | 0.390327E+11 | 0.303799E+11 |
June | 0.512336E+12 | 0.257264E+10 | 0.00 | 0.198746E+11 | 0.749361E+11 |
July | 0.524777E+12 | -0.265951E+10 | 0.00 | 0.530417E+10 | 0.116084E+12 |
August | 0.433026E+12 | 0.278909E+10 | 0.00 | 0.258093E+11 | 0.809291E+11 |
September | 0.310724E+12 | 0.144967E+11 | 0.00 | 0.552207E+11 | 0.111030E+11 |
October | 0.167278E+12 | 0.251982E+11 | 0.00 | 0.643551E+11 | 0.761984E+10 |
November | 0.698398E+11 | 0.388182E+11 | 0.00 | 0.863124E+11 | 0.218938E+11 |
December | 0.717357E+11 | 0.662148E+11 | 0.00 | 0.137554E+12 | 0.502288E+11 |
Annual Sum or Average | 0.363226E+13 | 0.348405E+12 | 0.00 | 0.855255E+12 | 0.523364E+12 |
Minimum of Months | 0.698398E+11 | -0.265951E+10 | 0.00 | 0.530417E+10 | 0.761984E+10 |