Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700
Simulation Timestamp: 2023-10-16 08:40:34
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1328.58 | 635.59 | 635.59 |
Net Site Energy | 1328.58 | 635.59 | 635.59 |
Total Source Energy | 4155.78 | 1988.11 | 1988.11 |
Net Source Energy | 4155.78 | 1988.11 | 1988.11 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 234.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 294.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 61.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1303.70 | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 234.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 294.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 61.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 24.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 234.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 294.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 61.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 282.84 | 11.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 623.68 | 11.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 282.84 | 11.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 623.68 | 11.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1303.697 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1303.697 | 100.00 |
Total On-Site and Utility Electric Sources | 1303.697 | 100.00 |
Total Electricity End Uses | 1303.697 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 701.67 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Latitude [deg] | 31.77 |
Longitude [deg] | -106.5 |
Elevation [m] | 1186.00 |
Time Zone | -7.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 15-JUN-14:00 | 27-DEC-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 117838.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 53593.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 17042.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5439.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 112883.29 | 117838.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 117838.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 53593.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 17042.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5439.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 26.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 744.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 384.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 933.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 195.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 4128.81 | 26.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 355.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 446.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1975.21 | 12.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 12.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 355.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 446.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 93.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1975.21 | 12.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 2.60 |
SMSTORE1 DIRECT AIR | 1.34 |
SMSTORE2 DIRECT AIR | 1.36 |
SMSTORE3 DIRECT AIR | 1.35 |
SMSTORE4 DIRECT AIR | 1.36 |
LGSTORE2 DIRECT AIR | 2.40 |
SMSTORE5 DIRECT AIR | 1.25 |
SMSTORE6 DIRECT AIR | 1.24 |
SMSTORE7 DIRECT AIR | 1.24 |
SMSTORE8 DIRECT AIR | 1.41 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 2.60 | 2.60 | 2.60 | 2.60 | 2.60 | 2.60 | 1.00 | 1.00 | 2.60 |
PSZ-AC_2:2 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.34 | 1.00 | 1.00 | 1.34 |
PSZ-AC_3:3 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-AC_4:4 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.35 | 1.00 | 1.00 | 1.35 |
PSZ-AC_5:5 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.36 | 1.00 | 1.00 | 1.36 |
PSZ-AC_6:6 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 2.40 | 1.00 | 1.000000 | 2.40 |
PSZ-AC_7:7 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.25 | 1.00 | 1.00 | 1.25 |
PSZ-AC_8:8 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC_9:9 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.24 | 1.00 | 1.00 | 1.24 |
PSZ-AC_10:10 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.41 | 1.00 | 1.00 | 1.41 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 2.60 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.34 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.36 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.35 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.36 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.40 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.25 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.24 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.24 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.41 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 2.60 | 2784.65 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.34 | 1487.43 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1506.62 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.35 | 1498.12 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.36 | 1501.24 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.40 | 2567.57 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.25 | 1382.45 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1376.14 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.24 | 1377.27 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.41 | 1561.25 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 2.60 | 2.60 | 2.60 | 2.60 | 48583.93 | 62954.66 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.34 | 1.34 | 1.34 | 1.34 | 24969.17 | 32315.37 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 1.36 | 25292.91 | 32659.12 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.35 | 1.35 | 1.35 | 1.35 | 25140.30 | 32506.87 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.36 | 1.36 | 1.36 | 1.36 | 25215.47 | 32562.66 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.40 | 2.40 | 2.40 | 2.40 | 45373.76 | 58931.85 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.25 | 1.25 | 1.25 | 1.25 | 23455.28 | 30435.45 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 23364.08 | 30322.50 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.24 | 1.24 | 1.24 | 1.24 | 23380.90 | 30342.80 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.41 | 1.41 | 1.41 | 1.41 | 25709.65 | 33638.10 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 2.60 | 1.30 | 2.60 | 48583.93 | 23833.13 | 48583.93 | 0.800990 | 0.800990 |
PSZ-AC_2:2 COOLING COIL | 1.34 | 0.671731 | 1.34 | 24969.17 | 12271.97 | 24969.17 | 0.800460 | 0.800460 |
PSZ-AC_3:3 COOLING COIL | 1.36 | 0.680400 | 1.36 | 25292.91 | 12431.10 | 25292.91 | 0.800440 | 0.800440 |
PSZ-AC_4:4 COOLING COIL | 1.35 | 0.676561 | 1.35 | 25140.30 | 12355.98 | 25140.30 | 0.800570 | 0.800570 |
PSZ-AC_5:5 COOLING COIL | 1.36 | 0.677968 | 1.36 | 25215.47 | 12393.19 | 25215.47 | 0.800270 | 0.800270 |
PSZ-AC_6:6 COOLING COIL | 2.40 | 1.20 | 2.40 | 45373.76 | 22265.69 | 45373.76 | 0.798850 | 0.798850 |
PSZ-AC_7:7 COOLING COIL | 1.25 | 0.624321 | 1.25 | 23455.28 | 11530.76 | 23455.28 | 0.800990 | 0.800990 |
PSZ-AC_8:8 COOLING COIL | 1.24 | 0.621473 | 1.24 | 23364.08 | 11486.10 | 23364.08 | 0.800770 | 0.800770 |
PSZ-AC_9:9 COOLING COIL | 1.24 | 0.621984 | 1.24 | 23380.90 | 11494.34 | 23380.90 | 0.800800 | 0.800800 |
PSZ-AC_10:10 COOLING COIL | 1.41 | 0.705068 | 1.41 | 25709.65 | 12631.70 | 25709.65 | 0.800810 | 0.800810 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 62954.66 |
PSZ-AC_2:2 HEATING COIL | 32315.37 |
PSZ-AC_3:3 HEATING COIL | 32659.12 |
PSZ-AC_4:4 HEATING COIL | 32506.87 |
PSZ-AC_5:5 HEATING COIL | 32562.66 |
PSZ-AC_6:6 HEATING COIL | 58931.85 |
PSZ-AC_7:7 HEATING COIL | 30435.45 |
PSZ-AC_8:8 HEATING COIL | 30322.50 |
PSZ-AC_9:9 HEATING COIL | 30342.80 |
PSZ-AC_10:10 HEATING COIL | 33638.10 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.30 | 11.20 | 6.80 | 8.10 | 10.30 | 12.50 | 19.20 | 23.80 | 27.90 | 27.50 | 26.30 | 23.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | El Paso International Ap Ut TX USA TMY3 WMO#=722700 | 31.77 | -106.50 | -7.00 | 1186.00 | 87865 | 1.0443 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 17.94 | 21.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 35 | 1 | VerySmooth | 2.632 | 2.632 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 2.49960E-002 | 0.16139 | 0.61571 | 0.61571 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.11953 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.283 | 8.131E-004 | 4.479E-004 | 0.565 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 0.162 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.202 | 1.162E-003 | 5.390E-004 | 0.807 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 25560.12465 | 30672.14958 | 2.16863 | 2.60236 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 38.10000 | 6.87148E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 19909.25372 | 23891.10447 | 0.98956 | 1.18747 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 13195.44040 | 15834.52848 | 1.11955 | 1.34346 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 37.99167 | 6.87130E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 9346.00824 | 11215.20988 | 0.46454 | 0.55744 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 13675.28828 | 16410.34593 | 1.13400 | 1.36080 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9501.73716 | 11402.08459 | 0.47228 | 0.56673 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 13599.87559 | 16319.85071 | 1.12760 | 1.35312 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9614.57115 | 11537.48538 | 0.47788 | 0.57346 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 13626.97296 | 16352.36755 | 1.12995 | 1.35594 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 30.95000 | 6.86012E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9789.49616 | 11747.39539 | 0.48658 | 0.58389 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 23567.48532 | 28280.98239 | 1.99958 | 2.39950 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 19063.22318 | 22875.86782 | 0.94753 | 1.13703 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 12264.09403 | 14716.91284 | 1.04054 | 1.24864 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 10118.51500 | 12142.21800 | 0.50293 | 0.60352 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 12208.13777 | 14649.76533 | 1.03579 | 1.24295 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 10105.93851 | 12127.12622 | 0.50231 | 0.60277 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 12218.19469 | 14661.83362 | 1.03664 | 1.24397 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 37.88333 | 6.87114E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 10310.08020 | 12372.09624 | 0.51245 | 0.61494 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 13850.15012 | 16620.18015 | 1.17511 | 1.41014 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 37.45000 | 6.87043E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12380.74515 | 14856.89418 | 0.61535 | 0.73842 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | -5.20000 | 2.80840E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 36417.44 | 2.60236 | 2.60236 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 34902.77 | 1.18747 | 1.18747 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 18699.30 | 1.34346 | 1.34346 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 16731.73 | 0.55744 | 0.55744 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 18693.10 | 1.36080 | 1.36080 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 16915.88 | 0.56673 | 0.56673 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 18736.86 | 1.35312 | 1.35312 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 17049.31 | 0.57346 | 0.57346 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 18636.22 | 1.35594 | 1.35594 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17256.16 | 0.58389 | 0.58389 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 34042.58 | 2.39950 | 2.39950 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 33902.49 | 1.13703 | 1.13703 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 17586.67 | 1.24864 | 1.24864 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17645.24 | 0.60352 | 0.60352 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 17520.22 | 1.24295 | 1.24295 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17630.37 | 0.60277 | 0.60277 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 17530.43 | 1.24397 | 1.24397 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 17871.77 | 0.61494 | 0.61494 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 19341.62 | 1.41014 | 1.41014 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 20320.23 | 0.73842 | 0.73842 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.60236 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.34346 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.36080 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35312 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.35594 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.39950 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24864 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24295 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.24397 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.41014 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.60236 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.60236 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.60236 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.60236 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.60236 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 2.60236 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.34346 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.34346 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.34346 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.34346 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.34346 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.34346 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.36080 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.36080 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.36080 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.36080 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.36080 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.36080 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35312 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35312 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35312 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35312 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35312 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35312 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.35594 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.35594 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.35594 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.35594 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.35594 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.35594 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.39950 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.39950 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.39950 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.39950 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.39950 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.39950 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24864 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24864 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24864 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24864 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24864 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24864 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24295 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24295 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24295 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24295 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24295 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24295 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.24397 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.24397 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.24397 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.24397 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.24397 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.24397 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.41014 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.41014 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.41014 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.41014 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.41014 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.41014 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 2.60236 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.34346 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.36080 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.35312 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.35594 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.39950 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.24864 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.24295 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.24397 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.41014 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.60236 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.60236 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2784.64900 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.60236 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.60236 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.60236 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.60236 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.60236 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.30118 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.60236 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 48583.93000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 23833.12791 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 48583.93000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80099 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80099 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 48583.93000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 62954.65781 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 62954.65781 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.34346 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.34346 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1487.42675 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.34346 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.34346 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.34346 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.34346 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.34346 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67173 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.34346 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 24969.17000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12271.96627 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 24969.17000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80046 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80046 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 24969.17000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32315.37376 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 32315.37376 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.36080 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.36080 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1506.62262 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.36080 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.36080 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.36080 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.36080 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.36080 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.68040 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.36080 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25292.91000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12431.09916 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25292.91000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80044 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80044 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25292.91000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32659.11554 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 32659.11554 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35312 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35312 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1498.12076 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35312 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35312 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35312 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35312 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35312 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67656 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35312 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25140.30000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12355.98014 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25140.30000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80057 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80057 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25140.30000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32506.87307 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 32506.87307 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.35594 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.35594 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1501.23616 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.35594 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.35594 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.35594 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.35594 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.35594 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.67797 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.35594 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25215.47000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12393.18563 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25215.47000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80027 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80027 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25215.47000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 32562.65819 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 32562.65819 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.39950 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.39950 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2567.57444 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.39950 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.39950 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.39950 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.39950 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.39950 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.19975 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.39950 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 45373.76000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 22265.68659 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 45373.76000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.79885 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.79885 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 45373.76000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 58931.84598 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 58931.84598 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24864 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24864 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1382.44511 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24864 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24864 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24864 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24864 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24864 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62432 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24864 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23455.28000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 11530.75871 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23455.28000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80099 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80099 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23455.28000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30435.44598 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 30435.44598 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24295 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24295 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1376.13763 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24295 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24295 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24295 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24295 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24295 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62147 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24295 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23364.08000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 11486.10093 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23364.08000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80077 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80077 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23364.08000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30322.49675 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 30322.49675 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.24397 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.24397 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1377.27111 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.24397 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.24397 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.24397 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.24397 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.24397 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.62198 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.24397 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 23380.90000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 11494.34412 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 23380.90000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80080 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80080 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 23380.90000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 30342.79555 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 30342.79555 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.41014 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.41014 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1561.24542 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.41014 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.41014 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.41014 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.41014 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.41014 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.70507 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.41014 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 25709.65000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 12631.69555 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 25709.65000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80081 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80081 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 25709.65000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 33638.10339 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 33638.10339 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 46541.0 | 10.79 | 10.79 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 23914.6 | 10.95 | 10.95 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 24224.7 | 10.95 | 10.95 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 24078.1 | 10.95 | 10.95 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 24151.1 | 10.95 | 10.95 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 43489.7 | 10.82 | 10.82 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 22475.0 | 10.97 | 10.97 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 22388.2 | 10.97 | 10.97 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 22404.2 | 10.97 | 10.97 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 24603.0 | 10.92 | 10.92 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.463_SHGC_0.25 | N/A | 2.632 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 5.5744014866E-002 | 8.4886341898E-002 | Pass | Pass | 4.5490920641E-002 | 0.1181607585 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 3.6255203826E-002 | 7.8539225991E-002 | Pass | Pass | 4.8516412570E-002 | 0.1198739828 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 5.2096965969E-002 | 8.0003449585E-002 | Pass | Pass | 4.0175921696E-002 | 0.1192224465 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 5.5207563005E-002 | 8.0541231857E-002 | Pass | Pass | 4.5197482108E-002 | 0.1441125936 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 5.9789554110E-002 | 7.9932240911E-002 | Pass | Pass | 4.0704619601E-002 | 0.1095051060 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 6.2627613401E-002 | 7.5975157102E-002 | Pass | Pass | 3.1352387630E-002 | 0.1006045909 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 6.2310598539E-002 | 7.3707699978E-002 | Pass | Pass | 4.0082090443E-002 | 0.1124268670 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 6.4073758724E-002 | 7.3423952910E-002 | Pass | Pass | 3.8071482116E-002 | 0.1095165470 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 6.1489509424E-002 | 7.0321189618E-002 | Pass | Pass | 9.3359659698E-002 | 0.5746657128 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.0969245659E-002 | 9.8545649436E-002 | Pass | Pass | 0.4797083614 | 2.7387503604 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3203.51 | 57.58 | 0.00 | 199.26 | 1043.13 | 4503.52 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | -5.20 | 0.00 | -5.20 | Wetbulb [C] | 2.20 | 20.00 |
EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 38.10 | 13.00 | 18.10 | Wetbulb [C] | 3.90 | 280.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 3.00 | 6 | |||
Feb | 3.00 | 4 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 18.00 | 7 | |||
Jul | 27.00 | 16 | |||
Aug | 41.00 | 15 | |||
Sep | 0.00 | 0 | |||
Oct | 23.00 | 18 | |||
Nov | 0.00 | 0 | |||
Dec | 7.00 | 7 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.632 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.463_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.632 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.632 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.632 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.77 | 83.77 | 121.44 | |
Exterior Lighting Total | 7723.26 | 121.44 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 48583.93 | 38915.24 | 9668.69 | 0.80 | 3.73 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 24969.17 | 19986.82 | 4982.35 | 0.80 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25292.91 | 20245.46 | 5047.45 | 0.80 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25140.30 | 20126.57 | 5013.73 | 0.80 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25215.47 | 20179.18 | 5036.29 | 0.80 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 45373.76 | 36246.83 | 9126.93 | 0.80 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23455.28 | 18787.44 | 4667.84 | 0.80 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23364.08 | 18709.25 | 4654.83 | 0.80 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 23380.90 | 18723.42 | 4657.48 | 0.80 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 25709.65 | 20588.54 | 5121.11 | 0.80 | 3.80 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 46541.0 | 10.79 | 10.79 | ||||
PSZ-AC_2:2 COOLING COIL | 23914.6 | 10.95 | 10.95 | ||||
PSZ-AC_3:3 COOLING COIL | 24224.7 | 10.95 | 10.95 | ||||
PSZ-AC_4:4 COOLING COIL | 24078.1 | 10.95 | 10.95 | ||||
PSZ-AC_5:5 COOLING COIL | 24151.1 | 10.95 | 10.95 | ||||
PSZ-AC_6:6 COOLING COIL | 43489.7 | 10.82 | 10.82 | ||||
PSZ-AC_7:7 COOLING COIL | 22475.0 | 10.97 | 10.97 | ||||
PSZ-AC_8:8 COOLING COIL | 22388.2 | 10.97 | 10.97 | ||||
PSZ-AC_9:9 COOLING COIL | 22404.2 | 10.97 | 10.97 | ||||
PSZ-AC_10:10 COOLING COIL | 24603.0 | 10.92 | 10.92 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 62954.66 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 32315.37 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 32659.12 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 32506.87 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 32562.66 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 58931.85 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 30435.45 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 30322.50 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 30342.80 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 33638.10 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.60 | 2784.65 | 1070.05 | 1.00 | 1.28 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.34 | 1487.43 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1506.62 | 1107.16 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.35 | 1498.12 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.36 | 1501.24 | 1107.16 | 1.00 | 1.34 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.40 | 2567.57 | 1070.05 | 1.00 | 1.29 | General | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.25 | 1382.45 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1376.14 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.24 | 1377.27 | 1107.16 | 1.00 | 1.35 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.41 | 1561.25 | 1107.16 | 1.00 | 1.33 | General | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 25560.12 | 30672.15 | 88.04 | 2.169 | 2.602 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 23.89 | 23.89 | 0.00741 | 38.10 | 0.00687 | 0.411 | 0.00 |
SMSTORE1 | 13195.44 | 15834.53 | 90.90 | 1.120 | 1.343 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 23.89 | 23.89 | 0.00740 | 37.99 | 0.00687 | 0.206 | 0.00 |
SMSTORE2 | 13675.29 | 16410.35 | 94.21 | 1.134 | 1.361 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00757 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE3 | 13599.88 | 16319.85 | 93.69 | 1.128 | 1.353 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00757 | 30.95 | 0.00686 | 0.206 | 0.00 |
SMSTORE4 | 13626.97 | 16352.37 | 93.87 | 1.130 | 1.356 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 23.89 | 23.89 | 0.00758 | 30.95 | 0.00686 | 0.206 | 0.00 |
LGSTORE2 | 23567.49 | 28280.98 | 81.18 | 2.000 | 2.399 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00745 | 37.88 | 0.00687 | 0.411 | 0.00 |
SMSTORE5 | 12264.09 | 14716.91 | 84.49 | 1.041 | 1.249 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00743 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE6 | 12208.14 | 14649.77 | 84.10 | 1.036 | 1.243 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00743 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE7 | 12218.19 | 14661.83 | 84.17 | 1.037 | 1.244 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23.89 | 23.89 | 0.00743 | 37.88 | 0.00687 | 0.206 | 0.00 |
SMSTORE8 | 13850.15 | 16620.18 | 95.41 | 1.175 | 1.410 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 23.89 | 23.89 | 0.00738 | 37.45 | 0.00687 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19909.25 | 23891.10 | 68.58 | 0.990 | 1.187 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00686 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE1 | 9346.01 | 11215.21 | 64.38 | 0.465 | 0.557 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00679 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE2 | 9501.74 | 11402.08 | 65.46 | 0.472 | 0.567 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE3 | 9614.57 | 11537.49 | 66.23 | 0.478 | 0.573 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00681 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE4 | 9789.50 | 11747.40 | 67.44 | 0.487 | 0.584 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00683 | -5.20 | 0.00281 | 0.206 | 0.00 |
LGSTORE2 | 19063.22 | 22875.87 | 65.66 | 0.948 | 1.137 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00690 | -5.20 | 0.00281 | 0.411 | 0.00 |
SMSTORE5 | 10118.51 | 12142.22 | 69.71 | 0.503 | 0.604 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00685 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE6 | 10105.94 | 12127.13 | 69.62 | 0.502 | 0.603 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00685 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE7 | 10310.08 | 12372.10 | 71.03 | 0.512 | 0.615 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00687 | -5.20 | 0.00281 | 0.206 | 0.00 |
SMSTORE8 | 12380.75 | 14856.89 | 85.29 | 0.615 | 0.738 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 21.11 | 21.11 | 0.00689 | -5.20 | 0.00281 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 2.60 | 2.60 | 1.19 | 1.19 | 2.6024 | 2.6024 | 2.6024 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.34 | 1.34 | 0.56 | 0.56 | 1.3435 | 1.3435 | 1.3435 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.36 | 1.36 | 0.57 | 0.57 | 1.3608 | 1.3608 | 1.3608 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.35 | 1.35 | 0.57 | 0.57 | 1.3531 | 1.3531 | 1.3531 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.36 | 1.36 | 0.58 | 0.58 | 1.3559 | 1.3559 | 1.3559 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.40 | 2.40 | 1.14 | 1.14 | 2.3995 | 2.3995 | 2.3995 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.25 | 1.25 | 0.60 | 0.60 | 1.2486 | 1.2486 | 1.2486 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.24 | 1.24 | 0.60 | 0.60 | 1.2429 | 1.2429 | 1.2429 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.24 | 1.24 | 0.61 | 0.61 | 1.2440 | 1.2440 | 1.2440 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.41 | 1.41 | 0.74 | 0.74 | 1.4101 | 1.4101 | 1.4101 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 48583.930 | 38915.242 | 2.602360 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | 48583.93 | 46706.76 | 2.602360 | 27.14 | 15.03 | 0.00732862 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 15.8118 | 23.89 | 0.00741447 | 34.9088 | 25560.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 62954.658 | 62954.658 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 62954.66 | 62954.66 | 2.602361 | 16.95 | 10.26 | 0.00622164 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.8118 | 21.11 | 0.00686270 | 38.2959 | 19909.25 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 24969.170 | 19986.822 | 1.343460 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | 24969.17 | 24021.78 | 1.343460 | 27.11 | 15.01 | 0.00732192 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 15.3141 | 23.89 | 0.00740338 | 34.8570 | 13194.18 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 32315.374 | 32315.374 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32315.37 | 32315.37 | 1.343463 | 17.08 | 10.27 | 0.00618159 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.3141 | 21.11 | 0.00679158 | 37.9030 | 9346.01 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 25292.910 | 20245.457 | 1.360800 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25292.91 | 24332.95 | 1.360800 | 27.11 | 15.01 | 0.00732203 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 15.1190 | 23.89 | 0.00740355 | 34.8578 | 13188.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 32659.116 | 32659.116 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32659.12 | 32659.12 | 1.360801 | 17.13 | 10.31 | 0.00620005 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.1190 | 21.11 | 0.00680417 | 37.9726 | 9501.74 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 25140.300 | 20126.570 | 1.353120 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25140.30 | 24187.62 | 1.353120 | 27.10 | 15.01 | 0.00732142 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 15.2048 | 23.89 | 0.00740256 | 34.8532 | 13225.88 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 32506.873 | 32506.873 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32506.87 | 32506.87 | 1.353122 | 17.11 | 10.30 | 0.00620412 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.2048 | 21.11 | 0.00681302 | 38.0214 | 9614.57 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 25215.470 | 20179.184 | 1.355940 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | 25215.47 | 24256.48 | 1.355940 | 27.11 | 15.02 | 0.00732284 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 15.1732 | 23.89 | 0.00740486 | 34.8639 | 13140.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 32562.658 | 32562.658 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 32562.66 | 32562.66 | 1.355936 | 17.12 | 10.32 | 0.00621701 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 15.1732 | 21.11 | 0.00682672 | 38.0971 | 9789.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 45373.760 | 36246.828 | 2.399500 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 45373.76 | 43513.53 | 2.399500 | 27.33 | 15.12 | 0.00735276 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 17.1485 | 23.89 | 0.00745244 | 35.0855 | 23555.47 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 58931.846 | 58931.846 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 58931.85 | 58931.85 | 2.399496 | 16.60 | 10.09 | 0.00619967 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 17.1486 | 21.11 | 0.00690159 | 38.5097 | 19063.22 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 23455.280 | 18787.445 | 1.248640 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23455.28 | 22528.73 | 1.248640 | 27.27 | 15.08 | 0.00733840 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 16.4771 | 23.89 | 0.00743059 | 34.9836 | 12254.99 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 30435.446 | 30435.446 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30435.45 | 30435.45 | 1.248642 | 16.77 | 10.15 | 0.00618525 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.4771 | 21.11 | 0.00685142 | 38.2334 | 10118.51 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 23364.080 | 18709.254 | 1.242950 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23364.08 | 22438.90 | 1.242950 | 27.28 | 15.09 | 0.00733942 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 16.5525 | 23.89 | 0.00743233 | 34.9917 | 12198.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 30322.497 | 30322.497 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30322.50 | 30322.50 | 1.242945 | 16.75 | 10.14 | 0.00618146 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.5526 | 21.11 | 0.00685053 | 38.2286 | 10105.94 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 23380.900 | 18723.425 | 1.243970 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | 23380.90 | 22455.38 | 1.243970 | 27.28 | 15.09 | 0.00733927 | 12.80 | 9.33 | 0.00700000 | 38.10 | 0.00687148 | 18.17 | 16.5389 | 23.89 | 0.00743207 | 34.9905 | 12207.53 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 30342.796 | 30342.796 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 30342.80 | 30342.80 | 1.243969 | 16.76 | 10.15 | 0.00619423 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 16.5390 | 21.11 | 0.00686518 | 38.3094 | 10310.08 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 25709.650 | 20588.545 | 1.410140 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | 25709.65 | 24783.58 | 1.410140 | 26.93 | 14.94 | 0.00730236 | 12.80 | 9.33 | 0.00700000 | 37.56 | 0.00687061 | 18.01 | 14.5900 | 23.89 | 0.00737620 | 34.7304 | 13835.07 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 33638.103 | 33638.103 | -999.0 | -999.0 | -999.000 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | 33638.10 | 33638.10 | 1.410137 | 17.27 | 10.45 | 0.00629062 | 40.00 | 19.53 | 0.00800000 | -5.20 | 0.00280840 | -5.20 | 14.5900 | 21.11 | 0.00688547 | 38.4230 | 12380.75 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 48583.930 | 38915.242 | 2.602360 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4635 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.602361 | 2.71772789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:50:00 | Sensible | 48583.93 | 46706.76 | 1.0000 | 2.71772713 | 2.602360 | 27.14 | 15.03 | 0.00732862 | 45970.8 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 48583.93 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 15.8118 | 23.89 | 0.00741447 | 23.89 | 0.00741447 | 34.9088 | 25560.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 62954.658 | 62954.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.602361 | 2.71772789 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 62954.66 | 62954.66 | 1.0000 | 2.71772789 | 2.602361 | 16.95 | 10.26 | 0.00622164 | 32785.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 62954.66 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 15.8118 | 21.11 | 0.00686270 | 21.11 | 0.00686270 | 38.2959 | 19909.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 24969.170 | 19986.822 | 1.343460 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4511 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.343463 | 1.40302100 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:50:00 | Sensible | 24969.17 | 24021.78 | 1.0000 | 1.40301791 | 1.343460 | 27.11 | 15.01 | 0.00732192 | 45917.5 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 24969.17 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 15.3141 | 23.89 | 0.00740338 | 23.89 | 0.00740338 | 34.8570 | 13194.18 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32315.374 | 32315.374 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.343463 | 1.40302100 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32315.37 | 32315.37 | 1.0000 | 1.40302100 | 1.343463 | 17.08 | 10.27 | 0.00618159 | 32817.4 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32315.37 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.3141 | 21.11 | 0.00679158 | 21.11 | 0.00679158 | 37.9030 | 9346.01 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25292.910 | 20245.457 | 1.360800 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4513 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.360801 | 1.42112757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 25292.91 | 24332.95 | 1.0000 | 1.42112662 | 1.360800 | 27.11 | 15.01 | 0.00732203 | 45918.6 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25292.91 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 15.1190 | 23.89 | 0.00740355 | 23.89 | 0.00740355 | 34.8578 | 13188.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32659.116 | 32659.116 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.360801 | 1.42112757 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32659.12 | 32659.12 | 1.0000 | 1.42112757 | 1.360801 | 17.13 | 10.31 | 0.00620005 | 32916.3 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32659.12 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.1190 | 21.11 | 0.00680417 | 21.11 | 0.00680417 | 37.9726 | 9501.74 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25140.300 | 20126.570 | 1.353120 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4501 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.353122 | 1.41310817 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 25140.30 | 24187.62 | 1.0000 | 1.41310615 | 1.353120 | 27.10 | 15.01 | 0.00732142 | 45910.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25140.30 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 15.2048 | 23.89 | 0.00740256 | 23.89 | 0.00740256 | 34.8532 | 13225.88 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32506.873 | 32506.873 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.353122 | 1.41310817 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32506.87 | 32506.87 | 1.0000 | 1.41310817 | 1.353122 | 17.11 | 10.30 | 0.00620412 | 32903.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32506.87 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.2048 | 21.11 | 0.00681302 | 21.11 | 0.00681302 | 38.0214 | 9614.57 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25215.470 | 20179.184 | 1.355940 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4528 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.355936 | 1.41604677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 09:00:00 | Sensible | 25215.47 | 24256.48 | 1.0000 | 1.41605117 | 1.355940 | 27.11 | 15.02 | 0.00732284 | 45928.8 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25215.47 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 15.1732 | 23.89 | 0.00740486 | 23.89 | 0.00740486 | 34.8639 | 13140.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 32562.658 | 32562.658 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.355936 | 1.41604677 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 32562.66 | 32562.66 | 1.0000 | 1.41604677 | 1.355936 | 17.12 | 10.32 | 0.00621701 | 32944.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 32562.66 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 15.1732 | 21.11 | 0.00682672 | 21.11 | 0.00682672 | 38.0971 | 9789.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 45373.760 | 36246.828 | 2.399500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.5084 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.399496 | 2.50587010 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 45373.76 | 43513.53 | 1.0000 | 2.50587399 | 2.399500 | 27.33 | 15.12 | 0.00735276 | 46227.1 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 45373.76 | 38.10 | 0.00687148 | 18.17 | 0.41147883 | 17.1485 | 23.89 | 0.00745244 | 23.89 | 0.00745244 | 35.0855 | 23555.47 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 58931.846 | 58931.846 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.399496 | 2.50587010 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 58931.85 | 58931.85 | 1.0000 | 2.50587010 | 2.399496 | 16.60 | 10.09 | 0.00619967 | 32372.8 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 58931.85 | -5.20 | 0.00280840 | -5.20 | 0.41147883 | 17.1486 | 21.11 | 0.00690159 | 21.11 | 0.00690159 | 38.5097 | 19063.22 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23455.280 | 18787.445 | 1.248640 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4817 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.248642 | 1.30399666 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 23455.28 | 22528.73 | 1.0000 | 1.30399437 | 1.248640 | 27.27 | 15.08 | 0.00733840 | 46129.4 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23455.28 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 16.4771 | 23.89 | 0.00743059 | 23.89 | 0.00743059 | 34.9836 | 12254.99 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30435.446 | 30435.446 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.248642 | 1.30399666 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30435.45 | 30435.45 | 1.0000 | 1.30399666 | 1.248642 | 16.77 | 10.15 | 0.00618525 | 32515.7 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30435.45 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.4771 | 21.11 | 0.00685142 | 21.11 | 0.00685142 | 38.2334 | 10118.51 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23364.080 | 18709.254 | 1.242950 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4836 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.242945 | 1.29804711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 23364.08 | 22438.90 | 1.0000 | 1.29805213 | 1.242950 | 27.28 | 15.09 | 0.00733942 | 46143.0 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23364.08 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 16.5525 | 23.89 | 0.00743233 | 23.89 | 0.00743233 | 34.9917 | 12198.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30322.497 | 30322.497 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.242945 | 1.29804711 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30322.50 | 30322.50 | 1.0000 | 1.29804711 | 1.242945 | 16.75 | 10.14 | 0.00618146 | 32485.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30322.50 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.5526 | 21.11 | 0.00685053 | 21.11 | 0.00685053 | 38.2286 | 10105.94 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 23380.900 | 18723.425 | 1.243970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4833 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.243969 | 1.29911627 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 14:00:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:40:00 | Sensible | 23380.90 | 22455.38 | 1.0000 | 1.29911734 | 1.243970 | 27.28 | 15.09 | 0.00733927 | 46140.9 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 23380.90 | 38.10 | 0.00687148 | 18.17 | 0.20573941 | 16.5389 | 23.89 | 0.00743207 | 23.89 | 0.00743207 | 34.9905 | 12207.53 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 30342.796 | 30342.796 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.243969 | 1.29911627 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 30342.80 | 30342.80 | 1.0000 | 1.29911627 | 1.243969 | 16.76 | 10.15 | 0.00619423 | 32521.9 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30342.80 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 16.5390 | 21.11 | 0.00686518 | 21.11 | 0.00686518 | 38.3094 | 10310.08 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 25709.650 | 20588.545 | 1.410140 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1018.4147 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.410137 | 1.47265074 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:10:00 | EL PASO INTERNATIONAL AP UT ANN CLG .4% CONDNS DB=>MWB | 7/21 13:00:00 | Sensible | 25709.65 | 24783.58 | 1.0000 | 1.47265395 | 1.410140 | 26.93 | 14.94 | 0.00730236 | 45684.2 | 12.80 | 9.33 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 25709.65 | 37.56 | 0.00687061 | 18.01 | 0.20573941 | 14.5900 | 23.89 | 0.00737620 | 23.89 | 0.00737620 | 34.7304 | 13835.07 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 33638.103 | 33638.103 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.0443 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.410137 | 1.47265074 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | unknown | unknown | EL PASO INTERNATIONAL AP UT ANN HTG 99.6% CONDNS DB | 12/21 13:00:00 | Sensible | 33638.10 | 33638.10 | 1.0000 | 1.47265074 | 1.410137 | 17.27 | 10.45 | 0.00629062 | 33286.5 | 40.00 | 19.53 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 33638.10 | -5.20 | 0.00280840 | -5.20 | 0.20573941 | 14.5900 | 21.11 | 0.00688547 | 21.11 | 0.00688547 | 38.4230 | 12380.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.60 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.34 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.36 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.35 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.36 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 2.40 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.25 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.24 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.41 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 2449.67 | 2687.17 | 284.33 |
SMSTORE1 | 2281.33 | 2464.17 | 99.33 |
SMSTORE2 | 1859.33 | 1885.33 | 165.00 |
SMSTORE3 | 1872.00 | 1915.17 | 177.50 |
SMSTORE4 | 1871.50 | 1980.50 | 201.67 |
LGSTORE2 | 1693.83 | 1914.00 | 225.00 |
SMSTORE5 | 1642.00 | 1954.17 | 238.33 |
SMSTORE6 | 1651.17 | 1976.83 | 254.83 |
SMSTORE7 | 1694.17 | 2014.17 | 309.50 |
SMSTORE8 | 1928.83 | 2047.83 | 494.00 |
Facility | 2947.50 | 3169.67 | 701.67 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 0.67 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.352 | 0.241 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 1.226 | 0.249 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.419 | 0.321 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.405 | 0.321 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.381 | 0.321 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 1.259 | 0.309 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 1.279 | 0.343 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 1.268 | 0.342 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 1.247 | 0.342 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 1.282 | 0.376 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.812 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.812 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.811 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.77 | 56.25 | 1805.20 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.39 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.39 | 28.12 | 902.60 | 0.810 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.39 | 28.12 | 902.60 | 0.809 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.39 | 28.12 | 902.60 | 0.808 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.77 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.39 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.95 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 14032626.55 | 0.00 | 14032626.55 | 3079518.32 | 17112144.88 | 12976396.34 | 3148.54 | 3851.92 | 1759.53 | 7.27 |
SMSTORE1 | 6368343.88 | 0.00 | 6368343.88 | 1457398.18 | 7825742.05 | 6488198.17 | 4174.22 | 2697.42 | 1888.35 | 10.83 |
SMSTORE2 | 5613316.98 | 0.00 | 5613316.98 | 1524342.17 | 7137659.15 | 6488198.17 | 4324.83 | 3086.16 | 1349.01 | 66.41 |
SMSTORE3 | 5565522.81 | 0.00 | 5565522.81 | 1524342.17 | 7089864.98 | 6488198.17 | 4321.64 | 3122.18 | 1316.18 | 71.95 |
SMSTORE4 | 5460450.68 | 0.00 | 5460450.68 | 1524342.17 | 6984792.85 | 6488198.17 | 4326.76 | 3187.24 | 1246.01 | 61.84 |
LGSTORE2 | 9121242.04 | 0.00 | 9121242.04 | 2833313.50 | 11954555.54 | 12976396.34 | 4702.96 | 3043.26 | 1013.78 | 37.52 |
SMSTORE5 | 4626041.09 | 0.00 | 4626041.09 | 1539227.30 | 6165268.39 | 6488198.17 | 4706.76 | 3044.37 | 1008.86 | 32.81 |
SMSTORE6 | 4584230.67 | 0.00 | 4584230.67 | 1539227.30 | 6123457.97 | 6488198.17 | 4708.23 | 3065.85 | 985.93 | 31.13 |
SMSTORE7 | 4502780.24 | 0.00 | 4502780.24 | 1539227.30 | 6042007.54 | 6488198.17 | 4711.83 | 3122.33 | 925.84 | 25.96 |
SMSTORE8 | 4652284.03 | 0.00 | 4652284.03 | 2071834.04 | 6724118.08 | 6488198.17 | 4705.29 | 3173.26 | 881.45 | 32.07 |
Total Facility | 64526838.99 | 0.00 | 64526838.99 | 18632772.44 | 83159611.43 | 77858378.04 | 4713.60 | 4426.04 | 2261.95 | 113.52 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.6663 | 0.0000 | 0.6663 | 0.1188 | 0.7850 | 0.4115 | 233.57 | 3851.75 | 1754.68 |
SMSTORE1 | 0.3021 | 0.0000 | 0.3021 | 0.0612 | 0.3633 | 0.2057 | 1261.62 | 2697.42 | 1880.96 |
SMSTORE2 | 0.3498 | 0.0000 | 0.3498 | 0.0792 | 0.4290 | 0.2057 | 0.00 | 3085.91 | 1309.09 |
SMSTORE3 | 0.3463 | 0.0000 | 0.3463 | 0.0792 | 0.4255 | 0.2057 | 0.00 | 3121.68 | 1273.32 |
SMSTORE4 | 0.3404 | 0.0000 | 0.3404 | 0.0792 | 0.4197 | 0.2057 | 0.00 | 3186.32 | 1208.68 |
LGSTORE2 | 0.6204 | 0.0000 | 0.6204 | 0.1525 | 0.7729 | 0.4115 | 0.00 | 3042.76 | 987.24 |
SMSTORE5 | 0.3152 | 0.0000 | 0.3152 | 0.0844 | 0.3996 | 0.2057 | 0.00 | 3044.21 | 985.79 |
SMSTORE6 | 0.3126 | 0.0000 | 0.3126 | 0.0844 | 0.3970 | 0.2057 | 0.00 | 3065.68 | 964.32 |
SMSTORE7 | 0.3075 | 0.0000 | 0.3075 | 0.0844 | 0.3919 | 0.2057 | 0.00 | 3122.16 | 907.84 |
SMSTORE8 | 0.3162 | 0.0000 | 0.3162 | 0.0926 | 0.4088 | 0.2057 | 0.00 | 3173.10 | 856.90 |
Total Facility | 3.8767 | 0.0000 | 3.8767 | 0.9160 | 4.7927 | 2.4689 | 1368.69 | 4423.54 | 2215.15 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15304386.18 | 0.00 | 15304386.18 | 12976396.34 | 3147.04 | 0.33 | 5612.62 | 7.27 |
PSZ-AC_2:2 | 6945498.97 | 0.00 | 6945498.97 | 6488198.17 | 4170.47 | 0.75 | 4588.78 | 10.83 |
PSZ-AC_3:3 | 6122044.97 | 0.00 | 6122044.97 | 6488198.17 | 4322.49 | 0.50 | 4437.01 | 66.41 |
PSZ-AC_4:4 | 6069919.28 | 0.00 | 6069919.28 | 6488198.17 | 4319.56 | 0.17 | 4440.27 | 71.87 |
PSZ-AC_5:5 | 5955324.59 | 0.00 | 5955324.59 | 6488198.17 | 4325.59 | 0.17 | 4434.24 | 61.67 |
PSZ-AC_6:6 | 9947888.95 | 0.00 | 9947888.95 | 12976396.34 | 4702.38 | 0.17 | 4057.45 | 37.52 |
PSZ-AC_7:7 | 5045293.49 | 0.00 | 5045293.49 | 6488198.17 | 4706.18 | 0.17 | 4053.65 | 32.81 |
PSZ-AC_8:8 | 4999693.84 | 0.00 | 4999693.84 | 6488198.17 | 4707.56 | 0.17 | 4052.27 | 31.13 |
PSZ-AC_9:9 | 4910861.66 | 0.00 | 4910861.66 | 6488198.17 | 4711.17 | 0.33 | 4048.50 | 25.80 |
PSZ-AC_10:10 | 5073914.79 | 0.00 | 5073914.79 | 6488198.17 | 4704.85 | 0.00 | 4055.15 | 32.07 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7267 | 0.0000 | 0.7267 | 0.4115 | 232.40 | 0.17 | 5607.43 |
PSZ-AC_2:2 | 0.3294 | 0.0000 | 0.3294 | 0.2057 | 1258.37 | 0.58 | 4581.05 |
PSZ-AC_3:3 | 0.3815 | 0.0000 | 0.3815 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.3777 | 0.0000 | 0.3777 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.3713 | 0.0000 | 0.3713 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.6766 | 0.0000 | 0.6766 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3438 | 0.0000 | 0.3438 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3409 | 0.0000 | 0.3409 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3353 | 0.0000 | 0.3353 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3448 | 0.0000 | 0.3448 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4610.10 | 1018.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3929.44 | 1459.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3661.87 | 799.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3693.84 | 773.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3735.50 | 721.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3507.60 | 559.92 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3504.72 | 558.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3519.94 | 541.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3557.02 | 498.78 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3578.84 | 483.23 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.7031 | 0.9922 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3341 | 0.4217 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3519 | 0.5285 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3489 | 0.5280 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3428 | 0.5311 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.6307 | 0.9814 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3196 | 0.5034 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3173 | 0.5024 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3124 | 0.5066 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3193 | 0.5437 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
ElectricityPurchased:Plant | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
Cogeneration:ElectricityPurchased | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
General:Cogeneration:ElectricityPurchased | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
ElectricityNet:Plant | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
Cogeneration:ElectricityNet | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
General:Cogeneration:ElectricityNet | 1303.70 | 3178.87 | 01-JAN-07:20 | 112883.29 | 15-JUN-15:00 |
Electricity:HVAC | 529.63 | 0.00 | 01-JAN-00:10 | 70636.19 | 15-JUN-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 234.93 | 0.00 | 01-JAN-00:10 | 53593.46 | 15-JUN-15:00 |
General:Cooling:Electricity | 234.93 | 0.00 | 01-JAN-00:10 | 53593.46 | 15-JUN-15:00 |
Fans:Electricity | 294.70 | 0.00 | 01-JAN-00:10 | 17042.73 | 02-JAN-10:00 |
General:Fans:Electricity | 294.70 | 0.00 | 01-JAN-00:10 | 17042.73 | 02-JAN-10:00 |
ExteriorLights:Electricity | 121.44 | 0.00 | 01-JAN-07:20 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.44 | 0.00 | 01-JAN-07:20 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 61.60 | 1218.00 | 07-JAN-09:10 | 11709.53 | 25-NOV-09:30 |
WaterSystems:Electricity | 61.60 | 1218.00 | 07-JAN-09:10 | 11709.53 | 25-NOV-09:30 |
Water Heater:WaterSystems:Electricity | 61.60 | 1218.00 | 07-JAN-09:10 | 11709.53 | 25-NOV-09:30 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 24.88 | 0.00 | 01-JAN-00:10 | 117838.61 | 27-DEC-09:10 |
NaturalGas:HVAC | 24.88 | 0.00 | 01-JAN-00:10 | 117838.61 | 27-DEC-09:10 |
Heating:NaturalGas | 24.88 | 0.00 | 01-JAN-00:10 | 117838.61 | 27-DEC-09:10 |
General:Heating:NaturalGas | 24.88 | 0.00 | 01-JAN-00:10 | 117838.61 | 27-DEC-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 1487.58 | 0.00 | 01-JAN-00:10 | 270691.98 | 03-JUL-13:00 |
EnergyTransfer:Building | 664.45 | 0.00 | 01-JAN-00:10 | 110005.36 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE1 | 139.00 | 0.00 | 01-JAN-00:10 | 18291.85 | 07-AUG-16:10 |
Heating:EnergyTransfer | 27.85 | 0.00 | 01-JAN-00:10 | 57202.63 | 27-DEC-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 3.13 | 0.00 | 01-JAN-00:10 | 11004.89 | 28-JAN-09:10 |
General:Heating:EnergyTransfer | 27.85 | 0.00 | 01-JAN-00:10 | 57202.63 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 3.13 | 0.00 | 01-JAN-00:10 | 11004.89 | 28-JAN-09:10 |
Cooling:EnergyTransfer | 636.60 | 0.00 | 01-JAN-00:10 | 110005.36 | 03-JUL-13:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 135.87 | 0.00 | 01-JAN-00:10 | 18291.85 | 07-AUG-16:10 |
General:Cooling:EnergyTransfer | 636.60 | 0.00 | 01-JAN-00:10 | 110005.36 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 135.87 | 0.00 | 01-JAN-00:10 | 18291.85 | 07-AUG-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 76.83 | 0.00 | 01-JAN-00:10 | 12779.94 | 24-SEP-18:50 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 1.47 | 0.00 | 01-JAN-00:10 | 1704.81 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 1.47 | 0.00 | 01-JAN-00:10 | 1704.81 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 75.35 | 0.00 | 01-JAN-00:10 | 12779.94 | 24-SEP-18:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 75.35 | 0.00 | 01-JAN-00:10 | 12779.94 | 24-SEP-18:50 |
EnergyTransfer:Zone:SMSTORE2 | 57.62 | 0.00 | 01-JAN-00:10 | 9310.48 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.58 | 0.00 | 01-JAN-00:10 | 4019.08 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.58 | 0.00 | 01-JAN-00:10 | 4019.08 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 55.04 | 0.00 | 01-JAN-00:10 | 9310.48 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 55.04 | 0.00 | 01-JAN-00:10 | 9310.48 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 57.21 | 0.00 | 01-JAN-00:10 | 9422.07 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 2.59 | 0.00 | 01-JAN-00:10 | 5281.19 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 2.59 | 0.00 | 01-JAN-00:10 | 5281.19 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 54.63 | 0.00 | 01-JAN-00:10 | 9422.07 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 54.63 | 0.00 | 01-JAN-00:10 | 9422.07 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 54.97 | 0.00 | 01-JAN-00:10 | 9345.58 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 2.75 | 0.00 | 01-JAN-00:10 | 5988.07 | 27-DEC-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 2.75 | 0.00 | 01-JAN-00:10 | 5988.07 | 27-DEC-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 52.22 | 0.00 | 01-JAN-00:10 | 9345.58 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 52.22 | 0.00 | 01-JAN-00:10 | 9345.58 | 03-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 91.51 | 0.00 | 01-JAN-00:10 | 17477.76 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 3.98 | 0.00 | 01-JAN-00:10 | 11881.66 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 3.98 | 0.00 | 01-JAN-00:10 | 11881.66 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 87.53 | 0.00 | 01-JAN-00:10 | 17477.76 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 87.53 | 0.00 | 01-JAN-00:10 | 17477.76 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE5 | 46.87 | 0.00 | 01-JAN-00:10 | 9181.81 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 2.25 | 0.00 | 01-JAN-00:10 | 6410.69 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 2.25 | 0.00 | 01-JAN-00:10 | 6410.69 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 44.61 | 0.00 | 01-JAN-00:10 | 9181.81 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 44.61 | 0.00 | 01-JAN-00:10 | 9181.81 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE6 | 46.20 | 0.00 | 01-JAN-00:10 | 9146.30 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 2.32 | 0.00 | 01-JAN-00:10 | 6780.94 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 2.32 | 0.00 | 01-JAN-00:10 | 6780.94 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 43.88 | 0.00 | 01-JAN-00:10 | 9146.30 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 43.88 | 0.00 | 01-JAN-00:10 | 9146.30 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE7 | 45.02 | 0.00 | 01-JAN-00:10 | 9210.08 | 03-JUL-13:00 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 2.61 | 0.00 | 01-JAN-00:10 | 7756.65 | 27-DEC-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 2.61 | 0.00 | 01-JAN-00:10 | 7756.65 | 27-DEC-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 42.42 | 0.00 | 01-JAN-00:10 | 9210.08 | 03-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 42.42 | 0.00 | 01-JAN-00:10 | 9210.08 | 03-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE8 | 49.22 | 0.00 | 01-JAN-00:10 | 10715.71 | 03-JUL-12:50 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 4.16 | 0.00 | 01-JAN-00:10 | 10229.35 | 02-MAR-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 4.16 | 0.00 | 01-JAN-00:10 | 10229.35 | 02-MAR-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 45.06 | 0.00 | 01-JAN-00:10 | 10715.71 | 03-JUL-12:50 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 45.06 | 0.00 | 01-JAN-00:10 | 10715.71 | 03-JUL-12:50 |
EnergyTransfer:HVAC | 823.13 | 0.00 | 01-JAN-00:10 | 165539.83 | 26-JUL-14:10 |
HeatingCoils:EnergyTransfer | 19.91 | 0.00 | 01-JAN-00:10 | 94270.89 | 27-DEC-09:10 |
CoolingCoils:EnergyTransfer | 803.22 | 0.00 | 01-JAN-00:10 | 165539.83 | 26-JUL-14:10 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 3.131 | -135.866 | 0.000 | 0.000 | 23.742 | 106.728 | 26.357 | 21.420 | 0.000 | 7.509 | 0.002 | 0.000 | -8.101 | 0.000 | -16.979 | -27.942 |
SMSTORE1 | 0.000 | 0.000 | 1.475 | -75.349 | 0.000 | 0.000 | 11.753 | 62.296 | 13.179 | 10.626 | 0.000 | 3.939 | 0.000 | 0.000 | -4.218 | 0.000 | -7.664 | -16.036 |
SMSTORE2 | 0.000 | 0.000 | 2.583 | -55.035 | 0.000 | 0.000 | 7.102 | 44.966 | 10.467 | 10.568 | 0.000 | 3.871 | 0.001 | 0.000 | -4.264 | 0.000 | -8.010 | -12.249 |
SMSTORE3 | 0.000 | 0.000 | 2.587 | -54.626 | 0.000 | 0.000 | 7.117 | 44.966 | 10.467 | 10.580 | 0.000 | 3.868 | 0.001 | 0.000 | -4.230 | 0.000 | -7.941 | -12.788 |
SMSTORE4 | 0.000 | 0.000 | 2.747 | -52.222 | 0.000 | 0.000 | 7.139 | 44.966 | 10.467 | 10.611 | 0.000 | 3.873 | 0.000 | 0.000 | -4.162 | 0.000 | -7.825 | -15.593 |
LGSTORE2 | 0.000 | 0.000 | 3.981 | -87.528 | 0.000 | 0.000 | 24.617 | 51.668 | 19.261 | 21.362 | 0.000 | 7.038 | 0.002 | 0.000 | -7.980 | 0.000 | -14.462 | -17.957 |
SMSTORE5 | 0.000 | 0.000 | 2.254 | -44.614 | 0.000 | 0.000 | 12.314 | 26.679 | 9.631 | 10.681 | 0.000 | 3.897 | 0.001 | 0.000 | -3.972 | 0.000 | -7.727 | -9.142 |
SMSTORE6 | 0.000 | 0.000 | 2.321 | -43.880 | 0.000 | 0.000 | 12.328 | 26.679 | 9.631 | 10.695 | 0.000 | 3.898 | 0.000 | 0.000 | -3.947 | 0.000 | -7.683 | -10.040 |
SMSTORE7 | 0.000 | 0.000 | 2.605 | -42.416 | 0.000 | 0.000 | 12.362 | 26.679 | 9.631 | 10.726 | 0.000 | 3.900 | 0.001 | 0.000 | -3.883 | 0.000 | -7.563 | -12.041 |
SMSTORE8 | 0.000 | 0.000 | 4.165 | -45.058 | 0.000 | 0.000 | 12.405 | 26.679 | 9.631 | 10.760 | 0.000 | 4.315 | 0.002 | 0.000 | -3.669 | 0.000 | -10.911 | -8.315 |
Total Facility | 0.000 | 0.000 | 27.848 | -636.594 | 0.000 | 0.000 | 130.879 | 462.305 | 128.721 | 128.029 | 0.000 | 46.107 | 0.011 | 0.000 | -48.426 | 0.000 | -96.766 | -142.102 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-NOV-09:02 | 0.00 | 0.00 | 0.00 | -50192.21 | 0.00 | 0.00 | 172.28 | 2916.31 | 749.03 | 3260.14 | 0.00 | 0.00 | 43552.39 | 0.00 | -0.00 | 0.00 | -457.94 | 0.00 |
SMSTORE1 | 09-NOV-09:02 | 0.00 | 0.00 | 0.00 | -27549.79 | 0.00 | 0.00 | 84.83 | 1702.23 | 374.52 | 1524.55 | 0.00 | 0.00 | 24029.79 | 0.00 | -0.00 | 0.00 | -166.13 | 0.00 |
SMSTORE2 | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | -28300.12 | 0.00 | 0.00 | 79.26 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 26484.32 | 0.00 | -24.90 | 0.00 | -149.42 | 0.00 |
SMSTORE3 | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | -28180.82 | 0.00 | 0.00 | 79.14 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 26367.41 | 0.00 | -26.56 | 0.00 | -150.05 | 0.00 |
SMSTORE4 | 11-SEP-07:01 | 0.00 | 0.00 | 0.00 | -28214.10 | 0.00 | 0.00 | 79.24 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 26398.97 | 0.00 | -25.44 | 0.00 | -149.55 | 0.00 |
LGSTORE2 | 06-OCT-08:62 | 0.00 | 0.00 | 0.00 | -48459.16 | 0.00 | 0.00 | 375.59 | 1920.56 | 749.03 | 524.05 | 0.00 | 0.00 | 45514.32 | 0.00 | -0.00 | 0.00 | -624.39 | 0.00 |
SMSTORE5 | 06-OCT-08:62 | 0.00 | 0.00 | 0.00 | -24962.61 | 0.00 | 0.00 | 189.28 | 991.67 | 374.52 | 261.90 | 0.00 | 0.00 | 23477.38 | 0.00 | -0.00 | 0.00 | -332.13 | 0.00 |
SMSTORE6 | 06-OCT-08:62 | 0.00 | 0.00 | 0.00 | -24618.51 | 0.00 | 0.00 | 189.97 | 991.67 | 374.52 | 262.84 | 0.00 | 0.00 | 23131.04 | 0.00 | -0.00 | 0.00 | -331.52 | 0.00 |
SMSTORE7 | 22-OCT-09:02 | 0.00 | 0.00 | 0.00 | -24308.70 | 0.00 | 0.00 | 189.86 | 991.67 | 374.52 | 1203.53 | 0.00 | 0.00 | 21651.29 | 0.00 | -0.00 | 0.00 | -102.16 | 0.00 |
SMSTORE8 | 22-OCT-09:02 | 0.00 | 0.00 | 0.00 | -26355.60 | 0.00 | 0.00 | 190.70 | 991.67 | 374.52 | 1204.31 | 0.00 | 0.00 | 23715.12 | 0.00 | -0.00 | 0.00 | -120.71 | 0.00 |
Total Facility | 11-SEP-08:61 | 0.00 | 0.00 | 0.00 | -231129.62 | 0.00 | 0.00 | 1886.33 | 19263.00 | 5393.02 | 4250.91 | 0.00 | 0.00 | 201426.43 | 0.00 | 0.00 | 0.00 | -1090.06 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 03-FEB-09:01 | 0.00 | 0.00 | 55106.60 | 0.00 | 0.00 | 0.00 | 248.33 | 2916.31 | 749.03 | 2052.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -681.64 | -60390.68 |
SMSTORE1 | 27-DEC-09:01 | 0.00 | 0.00 | 6808.66 | 0.00 | 0.00 | 0.00 | 117.32 | 1702.23 | 374.52 | 1048.91 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -447.37 | -9604.27 |
SMSTORE2 | 27-DEC-08:61 | 0.00 | 0.00 | 17569.70 | 0.00 | 0.00 | 0.00 | 120.10 | 1536.36 | 374.52 | 146.86 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -576.84 | -19170.69 |
SMSTORE3 | 27-DEC-08:61 | 0.00 | 0.00 | 23761.38 | 0.00 | 0.00 | 0.00 | 121.76 | 1536.36 | 374.52 | 153.54 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -576.41 | -25371.14 |
SMSTORE4 | 27-DEC-08:61 | 0.00 | 0.00 | 27341.42 | 0.00 | 0.00 | 0.00 | 123.61 | 1536.36 | 374.52 | 160.92 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -572.07 | -28964.77 |
LGSTORE2 | 03-FEB-09:01 | 0.00 | 0.00 | 51357.21 | 0.00 | 0.00 | 0.00 | 547.66 | 1920.56 | 749.03 | 2045.21 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -656.39 | -55963.27 |
SMSTORE5 | 03-FEB-09:01 | 0.00 | 0.00 | 26658.39 | 0.00 | 0.00 | 0.00 | 274.59 | 991.67 | 374.52 | 1022.88 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -363.83 | -28958.21 |
SMSTORE6 | 09-JAN-09:01 | 0.00 | 0.00 | 27010.49 | 0.00 | 0.00 | 0.00 | 270.80 | 991.67 | 374.52 | 939.19 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -421.51 | -29165.15 |
SMSTORE7 | 20-DEC-09:01 | 0.00 | 0.00 | 27188.59 | 0.00 | 0.00 | 0.00 | 272.05 | 991.67 | 374.52 | 1257.94 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -430.05 | -29654.71 |
SMSTORE8 | 02-MAR-08:61 | 0.00 | 0.00 | 32981.79 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -157.05 | 0.00 | -541.51 | -32419.86 |
Total Facility | 28-JAN-09:01 | 0.00 | 0.00 | 222557.33 | 0.00 | 0.00 | 0.00 | 2729.68 | 19263.00 | 5393.02 | 15926.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -6089.94 | -259779.24 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6024 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6024 | 0.1581 | 1.0000 | Not calculated | 0.4115 | 0.1581 | ||
PSZ-AC_2:2 | 1.3435 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3435 | 0.1531 | 1.0000 | Not calculated | 0.2057 | 0.1531 | ||
PSZ-AC_3:3 | 1.3608 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3608 | 0.1512 | 1.0000 | Not calculated | 0.2057 | 0.1512 | ||
PSZ-AC_4:4 | 1.3531 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3531 | 0.1520 | 1.0000 | Not calculated | 0.2057 | 0.1520 | ||
PSZ-AC_5:5 | 1.3559 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3559 | 0.1517 | 1.0000 | Not calculated | 0.2057 | 0.1517 | ||
PSZ-AC_6:6 | 2.3995 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3995 | 0.1715 | 1.0000 | Not calculated | 0.4115 | 0.1715 | ||
PSZ-AC_7:7 | 1.2486 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2486 | 0.1648 | 1.0000 | Not calculated | 0.2057 | 0.1648 | ||
PSZ-AC_8:8 | 1.2429 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2429 | 0.1655 | 1.0000 | Not calculated | 0.2057 | 0.1655 | ||
PSZ-AC_9:9 | 1.2440 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2440 | 0.1654 | 1.0000 | Not calculated | 0.2057 | 0.1654 | ||
PSZ-AC_10:10 | 1.4101 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4101 | 0.1459 | 1.0000 | Not calculated | 0.2057 | 0.1459 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 2.6024 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.6024 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1581 | ||
PSZ-AC_2:2 | 1.3435 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3435 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1531 | ||
PSZ-AC_3:3 | 1.3608 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3608 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1512 | ||
PSZ-AC_4:4 | 1.3531 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3531 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1520 | ||
PSZ-AC_5:5 | 1.3559 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.3559 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1517 | ||
PSZ-AC_6:6 | 2.3995 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.3995 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1715 | ||
PSZ-AC_7:7 | 1.2486 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2486 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1648 | ||
PSZ-AC_8:8 | 1.2429 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2429 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1655 | ||
PSZ-AC_9:9 | 1.2440 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.2440 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1654 | ||
PSZ-AC_10:10 | 1.4101 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4101 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1459 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6024 | 2.6024 | 2.6024 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3435 | 1.3435 | 1.3435 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3608 | 1.3608 | 1.3608 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3531 | 1.3531 | 1.3531 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3559 | 1.3559 | 1.3559 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3995 | 2.3995 | 2.3995 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2486 | 1.2486 | 1.2486 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2429 | 1.2429 | 1.2429 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2440 | 1.2440 | 1.2440 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4101 | 1.4101 | 1.4101 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6024 | 2.6024 | 2.6024 | 2.6024 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3435 | 1.3435 | 1.3435 | 1.3435 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3608 | 1.3608 | 1.3608 | 1.3608 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3531 | 1.3531 | 1.3531 | 1.3531 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3559 | 1.3559 | 1.3559 | 1.3559 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3995 | 2.3995 | 2.3995 | 2.3995 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2486 | 1.2486 | 1.2486 | 1.2486 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2429 | 1.2429 | 1.2429 | 1.2429 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2440 | 1.2440 | 1.2440 | 1.2440 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4101 | 1.4101 | 1.4101 | 1.4101 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.6024 | 2.6024 | 2.6024 | No | 0.4115 | 0.3465 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3435 | 1.3435 | 1.3435 | No | 0.2057 | 0.3691 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3608 | 1.3608 | 1.3608 | No | 0.2057 | 0.3630 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3531 | 1.3531 | 1.3531 | No | 0.2057 | 0.3588 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.3559 | 1.3559 | 1.3559 | No | 0.2057 | 0.3524 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.3995 | 2.3995 | 2.3995 | No | 0.4115 | 0.3619 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2486 | 1.2486 | 1.2486 | No | 0.2057 | 0.3409 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2429 | 1.2429 | 1.2429 | No | 0.2057 | 0.3413 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.2440 | 1.2440 | 1.2440 | No | 0.2057 | 0.3346 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4101 | 1.4101 | 1.4101 | No | 0.2057 | 0.2786 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 2.6024 | 2.6024 | 2.6024 | 2.6024 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.3435 | 1.3435 | 1.3435 | 1.3435 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.3608 | 1.3608 | 1.3608 | 1.3608 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.3531 | 1.3531 | 1.3531 | 1.3531 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.3559 | 1.3559 | 1.3559 | 1.3559 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.3995 | 2.3995 | 2.3995 | 2.3995 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.2486 | 1.2486 | 1.2486 | 1.2486 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.2429 | 1.2429 | 1.2429 | 1.2429 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.2440 | 1.2440 | 1.2440 | 1.2440 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.4101 | 1.4101 | 1.4101 | 1.4101 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** El Paso International Ap Ut TX USA TMY3 WMO#=722700 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 24.88 | 117838.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 234.93 | 53593.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.44 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 294.70 | 17042.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 61.60 | 11709.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1303.70 |
Natural Gas | 0.00 | 24.88 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1328.58 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 112.39 |
Fans (All) | 140.98 |
Service Water Heating | 29.47 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 623.68 |
Subtotal | 623.68 |
Natural Gas [MJ/m2] | |
Space Heating | 11.90 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 11.90 |
Subtotal | 11.90 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.80 |
Space Heating | 1.87 |
Space Cooling | 17.68 |
Fans (All) | 22.18 |
Service Water Heating | 4.64 |
Receptacle Equipment | 9.69 |
Miscellaneous | 9.14 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8748.83 | 11.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8747.17 | 12.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8523.33 | 236.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8479.83 | 280.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8529.83 | 230.17 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8631.50 | 128.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8648.50 | 111.50 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8652.67 | 107.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8657.33 | 102.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8606.67 | 153.33 | 0.00 | 0.00 | 0.00 |
Min | 8479.83 | 11.17 | 0.00 | 0.00 | 0.00 |
Max | 8748.83 | 280.17 | 0.00 | 0.00 | 0.00 |
Average | 8622.57 | 137.43 | 0.00 | 0.00 | 0.00 |
Sum | 86225.67 | 1374.33 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89026.67 | 14.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43768.00 | 9.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25414.00 | 61.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25413.67 | 61.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25416.33 | 58.67 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93061.00 | 150.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45841.00 | 71.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45841.50 | 70.50 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45842.00 | 70.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45833.00 | 79.00 | 0.00 | 0.00 | 0.00 |
Min | 25413.67 | 9.00 | 0.00 | 0.00 | 0.00 |
Max | 93061.00 | 150.00 | 0.00 | 0.00 | 0.00 |
Average | 48545.72 | 64.48 | 0.00 | 0.00 | 0.00 |
Sum | 485457.17 | 644.83 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8463.67 | 296.33 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8676.50 | 83.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8227.33 | 532.67 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8198.17 | 561.83 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8244.67 | 515.33 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8378.83 | 381.17 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8397.67 | 362.33 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8404.67 | 355.33 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8414.50 | 345.50 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8295.00 | 465.00 | 0.00 | 0.00 | 0.00 |
Min | 8198.17 | 83.50 | 0.00 | 0.00 | 0.00 |
Max | 8676.50 | 561.83 | 0.00 | 0.00 | 0.00 |
Average | 8370.10 | 389.90 | 0.00 | 0.00 | 0.00 |
Sum | 83701.00 | 3899.00 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 88820.33 | 220.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43718.17 | 58.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25407.50 | 67.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25407.67 | 67.33 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25405.00 | 70.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 92933.50 | 277.50 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45772.00 | 140.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45772.00 | 140.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45772.00 | 140.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45750.83 | 161.17 | 0.00 | 0.00 | 0.00 |
Min | 25405.00 | 58.83 | 0.00 | 0.00 | 0.00 |
Max | 92933.50 | 277.50 | 0.00 | 0.00 | 0.00 |
Average | 48475.90 | 134.30 | 0.00 | 0.00 | 0.00 |
Sum | 484759.00 | 1343.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:34
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 3B
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_TX_ELPASO
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 8.136 |
February | 10.272 |
March | 12.546 |
April | 19.230 |
May | 23.842 |
June | 27.856 |
July | 27.543 |
August | 26.276 |
September | 23.380 |
October | 18.301 |
November | 11.185 |
December | 6.787 |
Annual Sum or Average | 17.982 |
Minimum of Months | 6.787 |
Maximum of Months | 27.856 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.403859E+10 | 8033.00 | 27-JAN-09:03 | -1.2 | -5.7 | 0.124778E+10 | 1685.84 | 01-JAN-17:10 | -1.2 | -5.7 |
February | 0.397265E+10 | 7138.97 | 20-FEB-16:00 | 23.30 | 8.66 | 0.118110E+10 | 1685.85 | 19-FEB-17:10 | 23.30 | 8.66 |
March | 0.524666E+10 | 7553.21 | 16-MAR-16:10 | 22.02 | 8.30 | 0.135566E+10 | 1685.85 | 26-MAR-16:19 | 22.40 | 8.95 |
April | 0.995660E+10 | 45606.16 | 29-APR-08:62 | 21.28 | 13.80 | 0.135906E+10 | 1685.85 | 16-APR-17:10 | 21.28 | 13.80 |
May | 0.146062E+11 | 49012.60 | 10-MAY-08:62 | 20.78 | 10.27 | 0.140282E+10 | 1686.05 | 21-MAY-17:10 | 29.32 | 18.81 |
June | 0.182841E+11 | 44976.02 | 12-JUN-08:61 | 23.35 | 9.75 | 0.135688E+10 | 1686.03 | 03-JUN-12:00 | 23.35 | 9.75 |
July | 0.194937E+11 | 40917.73 | 03-JUL-08:61 | 29.18 | 17.25 | 0.141523E+10 | 1686.10 | 28-JUL-12:50 | 33.30 | 19.60 |
August | 0.190405E+11 | 45660.05 | 23-AUG-08:61 | 24.27 | 13.78 | 0.139665E+10 | 1686.09 | 04-AUG-12:50 | 24.27 | 13.78 |
September | 0.174139E+11 | 49259.11 | 11-SEP-08:61 | 21.57 | 11.25 | 0.136681E+10 | 1686.08 | 04-SEP-16:10 | 21.57 | 11.25 |
October | 0.129622E+11 | 47904.37 | 19-OCT-08:62 | 19.08 | 12.62 | 0.141018E+10 | 1685.96 | 28-OCT-12:50 | 21.93 | 13.70 |
November | 0.685026E+10 | 50192.51 | 10-NOV-09:02 | 18.48 | 11.84 | 0.131477E+10 | 1685.96 | 03-NOV-12:00 | 18.48 | 11.84 |
December | 0.400185E+10 | 7898.74 | 27-DEC-09:03 | -0.7 | -2.5 | 0.122798E+10 | 1685.85 | 09-DEC-13:09 | -0.7 | -2.5 |
Annual Sum or Average | 0.135867E+12 | 0.160349E+11 | ||||||||
Minimum of Months | 0.397265E+10 | 7138.97 | -1.2 | -5.7 | 0.118110E+10 | 1685.84 | -1.2 | -5.7 | ||
Maximum of Months | 0.194937E+11 | 50192.51 | 29.18 | 17.25 | 0.141523E+10 | 1686.10 | 33.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.213010E+10 | 21800.52 | 03-JAN-21:10 | 14.13 | 6.70 | 0.666759E+09 | 842.90 | 16-JAN-18:00 | 12.20 | 7.35 |
February | 0.243263E+10 | 25932.86 | 19-FEB-18:52 | 18.90 | 6.67 | 0.616614E+09 | 842.90 | 20-FEB-17:10 | 22.02 | 8.16 |
March | 0.347430E+10 | 26533.20 | 12-MAR-17:33 | 18.33 | 8.19 | 0.688394E+09 | 842.90 | 26-MAR-16:40 | 22.60 | 9.13 |
April | 0.608741E+10 | 26035.60 | 15-APR-20:52 | 18.90 | 6.31 | 0.676507E+09 | 842.92 | 09-APR-17:49 | 18.90 | 6.31 |
May | 0.822632E+10 | 26106.37 | 12-MAY-08:62 | 18.68 | 9.91 | 0.698565E+09 | 843.00 | 21-MAY-17:10 | 29.32 | 18.81 |
June | 0.980448E+10 | 23480.85 | 12-JUN-08:61 | 23.35 | 9.75 | 0.677499E+09 | 842.99 | 23-JUN-12:30 | 28.30 | 16.66 |
July | 0.102914E+11 | 21232.15 | 01-JUL-08:61 | 28.68 | 18.69 | 0.707137E+09 | 843.02 | 28-JUL-12:50 | 33.30 | 19.60 |
August | 0.100774E+11 | 23440.45 | 23-AUG-08:61 | 24.27 | 13.78 | 0.696870E+09 | 843.02 | 04-AUG-12:50 | 24.27 | 13.78 |
September | 0.936923E+10 | 27068.32 | 30-SEP-20:12 | 17.80 | 9.17 | 0.679624E+09 | 843.01 | 04-SEP-16:10 | 17.80 | 9.17 |
October | 0.742341E+10 | 26918.20 | 26-OCT-20:40 | 17.93 | 8.55 | 0.700701E+09 | 842.96 | 28-OCT-12:50 | 21.93 | 13.70 |
November | 0.404356E+10 | 27550.79 | 09-NOV-09:02 | 16.97 | 7.95 | 0.668182E+09 | 842.96 | 03-NOV-12:50 | 16.97 | 7.95 |
December | 0.199024E+10 | 3098.90 | 26-DEC-09:01 | -0.5 | -3.0 | 0.657946E+09 | 842.90 | 25-DEC-18:00 | -0.5 | -3.0 |
Annual Sum or Average | 0.753505E+11 | 0.813480E+10 | ||||||||
Minimum of Months | 0.199024E+10 | 3098.90 | -0.5 | -3.0 | 0.616614E+09 | 842.90 | -0.5 | -3.0 | ||
Maximum of Months | 0.102914E+11 | 27550.79 | 28.68 | 18.69 | 0.707137E+09 | 843.02 | 33.30 | 19.60 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155507E+10 | 3920.82 | 27-JAN-08:03 | -3.5 | -7.2 | 0.379991E+09 | 798.84 | 07-JAN-13:00 | -3.5 | -7.2 |
February | 0.164787E+10 | 3641.37 | 22-FEB-14:00 | 21.70 | 7.92 | 0.360434E+09 | 842.90 | 11-FEB-13:20 | 21.70 | 7.92 |
March | 0.232745E+10 | 4098.49 | 16-MAR-14:00 | 22.80 | 9.34 | 0.420148E+09 | 842.90 | 04-MAR-13:09 | 22.80 | 9.34 |
April | 0.413138E+10 | 25725.07 | 20-APR-07:02 | 20.60 | 8.60 | 0.410293E+09 | 842.90 | 29-APR-12:50 | 27.70 | 15.20 |
May | 0.603271E+10 | 27213.11 | 10-MAY-07:02 | 19.18 | 9.48 | 0.426957E+09 | 842.90 | 27-MAY-12:09 | 30.10 | 16.35 |
June | 0.753343E+10 | 25062.49 | 01-JUN-07:01 | 22.15 | 10.59 | 0.418363E+09 | 842.99 | 03-JUN-12:00 | 34.40 | 19.76 |
July | 0.772906E+10 | 21835.90 | 11-JUL-07:01 | 24.45 | 16.28 | 0.421476E+09 | 843.00 | 29-JUL-12:09 | 32.38 | 19.07 |
August | 0.770262E+10 | 25581.00 | 23-AUG-07:01 | 22.07 | 13.03 | 0.432896E+09 | 843.02 | 05-AUG-12:39 | 22.07 | 13.03 |
September | 0.691794E+10 | 28304.17 | 11-SEP-07:01 | 18.77 | 10.73 | 0.411721E+09 | 842.90 | 09-SEP-12:09 | 18.77 | 10.73 |
October | 0.518276E+10 | 27569.71 | 06-OCT-07:01 | 12.70 | 10.09 | 0.420496E+09 | 842.96 | 28-OCT-12:39 | 21.67 | 13.60 |
November | 0.280772E+10 | 26414.21 | 10-NOV-08:62 | 17.88 | 11.42 | 0.392849E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.146830E+10 | 4056.58 | 27-DEC-08:03 | -3.4 | -4.3 | 0.372049E+09 | 842.90 | 16-DEC-13:09 | -3.4 | -4.3 |
Annual Sum or Average | 0.550363E+11 | 0.486767E+10 | ||||||||
Minimum of Months | 0.146830E+10 | 3641.37 | -3.5 | -7.2 | 0.360434E+09 | 798.84 | -3.5 | -7.2 | ||
Maximum of Months | 0.772906E+10 | 28304.17 | 24.45 | 16.28 | 0.432896E+09 | 843.02 | 34.40 | 19.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.141039E+10 | 4087.94 | 27-JAN-08:03 | -3.5 | -7.2 | 0.374946E+09 | 788.01 | 07-JAN-13:00 | -3.5 | -7.2 |
February | 0.152582E+10 | 3652.43 | 03-FEB-08:03 | -2.0 | -5.0 | 0.357592E+09 | 842.90 | 11-FEB-13:20 | 18.50 | 6.88 |
March | 0.219547E+10 | 4014.15 | 16-MAR-14:00 | 22.80 | 9.34 | 0.419090E+09 | 842.90 | 04-MAR-13:09 | 22.80 | 9.34 |
April | 0.409349E+10 | 25583.98 | 30-APR-08:62 | 18.58 | 12.41 | 0.410238E+09 | 842.90 | 29-APR-12:50 | 18.58 | 12.41 |
May | 0.606491E+10 | 27069.55 | 10-MAY-07:02 | 19.18 | 9.48 | 0.426960E+09 | 842.90 | 27-MAY-12:09 | 30.10 | 16.35 |
June | 0.759671E+10 | 24924.90 | 01-JUN-07:01 | 22.15 | 10.59 | 0.418368E+09 | 842.99 | 03-JUN-12:00 | 34.40 | 19.76 |
July | 0.779558E+10 | 21712.15 | 11-JUL-07:01 | 24.45 | 16.28 | 0.421478E+09 | 843.00 | 29-JUL-12:09 | 32.38 | 19.07 |
August | 0.776895E+10 | 25442.31 | 23-AUG-07:01 | 22.07 | 13.03 | 0.432900E+09 | 843.02 | 05-AUG-12:39 | 22.07 | 13.03 |
September | 0.697060E+10 | 28184.71 | 11-SEP-07:01 | 18.77 | 10.73 | 0.411724E+09 | 842.90 | 09-SEP-12:09 | 18.77 | 10.73 |
October | 0.517616E+10 | 27510.57 | 06-OCT-07:01 | 12.70 | 10.09 | 0.420485E+09 | 842.96 | 28-OCT-12:39 | 21.67 | 13.60 |
November | 0.269244E+10 | 26241.89 | 10-NOV-08:62 | 17.88 | 11.42 | 0.391978E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.133619E+10 | 4266.32 | 27-DEC-08:03 | -3.4 | -4.3 | 0.367466E+09 | 842.90 | 16-DEC-13:20 | -3.4 | -4.3 |
Annual Sum or Average | 0.546267E+11 | 0.485323E+10 | ||||||||
Minimum of Months | 0.133619E+10 | 3652.43 | -3.5 | -7.2 | 0.357592E+09 | 788.01 | -3.5 | -7.2 | ||
Maximum of Months | 0.779558E+10 | 28184.71 | 24.45 | 16.28 | 0.432900E+09 | 843.02 | 34.40 | 19.76 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.120433E+10 | 4277.44 | 27-JAN-08:03 | -3.5 | -7.2 | 0.367860E+09 | 769.73 | 07-JAN-13:00 | -3.5 | -7.2 |
February | 0.131869E+10 | 3868.68 | 03-FEB-08:03 | -2.0 | -5.0 | 0.352895E+09 | 842.90 | 11-FEB-13:20 | 18.50 | 6.88 |
March | 0.193393E+10 | 3775.39 | 16-MAR-14:00 | 22.80 | 9.34 | 0.417055E+09 | 842.90 | 04-MAR-13:09 | 22.80 | 9.34 |
April | 0.385600E+10 | 25483.70 | 20-APR-07:02 | 20.60 | 8.60 | 0.410014E+09 | 842.90 | 29-APR-12:50 | 27.70 | 15.20 |
May | 0.585975E+10 | 26998.18 | 10-MAY-07:02 | 19.18 | 9.48 | 0.426903E+09 | 842.90 | 27-MAY-12:09 | 30.10 | 16.35 |
June | 0.743369E+10 | 24978.71 | 01-JUN-07:01 | 22.15 | 10.59 | 0.418333E+09 | 842.99 | 03-JUN-12:00 | 34.40 | 19.76 |
July | 0.764809E+10 | 21769.98 | 11-JUL-07:01 | 24.45 | 16.28 | 0.421447E+09 | 843.01 | 29-JUL-12:09 | 32.38 | 19.07 |
August | 0.760907E+10 | 25498.64 | 23-AUG-07:01 | 22.07 | 13.03 | 0.432865E+09 | 843.02 | 05-AUG-12:39 | 22.07 | 13.03 |
September | 0.680273E+10 | 28218.11 | 11-SEP-07:01 | 18.77 | 10.73 | 0.411684E+09 | 842.90 | 09-SEP-12:09 | 18.77 | 10.73 |
October | 0.496594E+10 | 27421.25 | 06-OCT-07:01 | 12.70 | 10.09 | 0.420394E+09 | 842.96 | 28-OCT-12:50 | 21.93 | 13.70 |
November | 0.246368E+10 | 24475.91 | 10-NOV-08:62 | 17.88 | 11.42 | 0.390647E+09 | 842.90 | 18-NOV-13:00 | 19.40 | 6.83 |
December | 0.112701E+10 | 4343.53 | 27-DEC-08:03 | -3.4 | -4.3 | 0.361172E+09 | 842.90 | 09-DEC-13:09 | -3.4 | -4.3 |
Annual Sum or Average | 0.522229E+11 | 0.483127E+10 | ||||||||
Minimum of Months | 0.112701E+10 | 3775.39 | -3.5 | -7.2 | 0.352895E+09 | 769.73 | -3.5 | -7.2 | ||
Maximum of Months | 0.764809E+10 | 28218.11 | 24.45 | 16.28 | 0.432865E+09 | 843.02 | 34.40 | 19.76 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.192282E+10 | 6722.31 | 26-JAN-09:03 | 2.30 | -3.0 | 0.121783E+10 | 2151.15 | 07-JAN-15:00 | 2.30 | -3.0 |
February | 0.205435E+10 | 7083.82 | 02-FEB-09:03 | 1.38 | -2.7 | 0.118154E+10 | 2247.79 | 04-FEB-15:09 | 18.40 | 7.56 |
March | 0.290747E+10 | 7419.77 | 02-MAR-09:03 | 0.47 | -3.7 | 0.141921E+10 | 2247.80 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.624255E+10 | 45495.22 | 30-APR-09:02 | 20.37 | 12.82 | 0.140695E+10 | 2247.80 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.984587E+10 | 45870.86 | 10-MAY-08:62 | 20.78 | 10.27 | 0.145973E+10 | 2247.80 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.127895E+11 | 43042.37 | 12-JUN-08:61 | 23.35 | 9.75 | 0.143254E+10 | 2248.13 | 03-JUN-14:50 | 23.35 | 9.75 |
July | 0.131915E+11 | 38357.78 | 03-JUL-08:61 | 29.18 | 17.25 | 0.144145E+10 | 2248.10 | 15-JUL-14:09 | 31.38 | 18.29 |
August | 0.131179E+11 | 42794.40 | 23-AUG-08:61 | 24.27 | 13.78 | 0.148298E+10 | 2248.10 | 12-AUG-14:39 | 24.27 | 13.78 |
September | 0.116701E+11 | 46770.02 | 11-SEP-08:61 | 21.57 | 11.25 | 0.141209E+10 | 2248.08 | 02-SEP-14:20 | 21.57 | 11.25 |
October | 0.823427E+10 | 48483.73 | 06-OCT-08:62 | 12.30 | 9.69 | 0.143531E+10 | 2247.86 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.379537E+10 | 46899.75 | 10-NOV-09:02 | 18.48 | 11.84 | 0.132303E+10 | 2247.80 | 18-NOV-15:30 | 19.40 | 6.83 |
December | 0.175775E+10 | 7194.17 | 30-DEC-09:03 | 1.05 | -1.3 | 0.120511E+10 | 2247.78 | 23-DEC-15:00 | 1.05 | -1.3 |
Annual Sum or Average | 0.875294E+11 | 0.164178E+11 | ||||||||
Minimum of Months | 0.175775E+10 | 6722.31 | 0.47 | -3.7 | 0.118154E+10 | 2151.15 | 1.05 | -3.0 | ||
Maximum of Months | 0.131915E+11 | 48483.73 | 29.18 | 17.25 | 0.148298E+10 | 2248.13 | 31.38 | 18.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.839765E+09 | 3314.53 | 26-JAN-09:03 | 2.30 | -3.0 | 0.606881E+09 | 1066.39 | 07-JAN-15:00 | 2.30 | -3.0 |
February | 0.926117E+09 | 3463.11 | 02-FEB-09:03 | 1.38 | -2.7 | 0.589226E+09 | 1123.86 | 04-FEB-15:30 | 18.60 | 7.64 |
March | 0.136212E+10 | 3623.87 | 02-MAR-09:03 | 0.47 | -3.7 | 0.708727E+09 | 1123.87 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.317298E+10 | 23396.64 | 30-APR-09:02 | 20.37 | 12.82 | 0.703442E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.508973E+10 | 23540.66 | 10-MAY-08:62 | 20.78 | 10.27 | 0.729810E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.665132E+10 | 22161.01 | 12-JUN-08:61 | 23.35 | 9.75 | 0.716219E+09 | 1124.03 | 03-JUN-14:50 | 23.35 | 9.75 |
July | 0.686401E+10 | 19762.33 | 03-JUL-08:61 | 29.18 | 17.25 | 0.720675E+09 | 1124.01 | 15-JUL-14:09 | 31.38 | 18.29 |
August | 0.681495E+10 | 22024.26 | 23-AUG-08:61 | 24.27 | 13.78 | 0.741438E+09 | 1124.01 | 12-AUG-14:39 | 24.27 | 13.78 |
September | 0.605030E+10 | 24077.92 | 11-SEP-08:61 | 21.57 | 11.25 | 0.706002E+09 | 1124.01 | 16-SEP-14:00 | 32.20 | 18.22 |
October | 0.422410E+10 | 24975.63 | 06-OCT-08:62 | 12.30 | 9.69 | 0.717656E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.185383E+10 | 24164.12 | 10-NOV-09:02 | 18.48 | 11.84 | 0.661521E+09 | 1123.83 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.765506E+09 | 3556.50 | 19-DEC-09:03 | 0.47 | -4.6 | 0.601028E+09 | 1123.86 | 23-DEC-15:00 | 17.20 | 6.31 |
Annual Sum or Average | 0.446147E+11 | 0.820262E+10 | ||||||||
Minimum of Months | 0.765506E+09 | 3314.53 | 0.47 | -4.6 | 0.589226E+09 | 1066.39 | 2.30 | -3.0 | ||
Maximum of Months | 0.686401E+10 | 24975.63 | 29.18 | 17.25 | 0.741438E+09 | 1124.03 | 32.20 | 18.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.780674E+09 | 3317.42 | 26-JAN-09:03 | 2.30 | -3.0 | 0.603004E+09 | 1056.49 | 07-JAN-15:00 | 2.30 | -3.0 |
February | 0.865870E+09 | 3435.17 | 02-FEB-09:03 | 1.38 | -2.7 | 0.586078E+09 | 1123.86 | 04-FEB-15:39 | 18.70 | 7.67 |
March | 0.127706E+10 | 3413.05 | 02-MAR-09:03 | 0.47 | -3.7 | 0.706642E+09 | 1123.87 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.309594E+10 | 23242.60 | 30-APR-09:02 | 20.37 | 12.82 | 0.703269E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.502477E+10 | 23411.52 | 10-MAY-08:62 | 20.78 | 10.27 | 0.729784E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.659647E+10 | 22055.48 | 12-JUN-08:61 | 23.35 | 9.75 | 0.716207E+09 | 1124.03 | 03-JUN-14:50 | 23.35 | 9.75 |
July | 0.681267E+10 | 19687.94 | 03-JUL-08:61 | 29.18 | 17.25 | 0.720660E+09 | 1124.01 | 15-JUL-14:09 | 31.38 | 18.29 |
August | 0.676450E+10 | 21931.76 | 23-AUG-08:61 | 24.27 | 13.78 | 0.741427E+09 | 1124.01 | 12-AUG-14:39 | 24.27 | 13.78 |
September | 0.599964E+10 | 23960.69 | 11-SEP-08:61 | 21.57 | 11.25 | 0.705986E+09 | 1124.01 | 16-SEP-14:00 | 32.20 | 18.22 |
October | 0.415949E+10 | 24631.23 | 06-OCT-08:62 | 12.30 | 9.69 | 0.717600E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.178619E+10 | 24005.80 | 10-NOV-09:02 | 18.48 | 11.84 | 0.660414E+09 | 1123.84 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.717434E+09 | 3648.71 | 19-DEC-09:03 | 0.47 | -4.6 | 0.597828E+09 | 1123.86 | 23-DEC-15:00 | 17.20 | 6.31 |
Annual Sum or Average | 0.438807E+11 | 0.818890E+10 | ||||||||
Minimum of Months | 0.717434E+09 | 3317.42 | 0.47 | -4.6 | 0.586078E+09 | 1056.49 | 2.30 | -3.0 | ||
Maximum of Months | 0.681267E+10 | 24631.23 | 29.18 | 17.25 | 0.741427E+09 | 1124.03 | 32.20 | 18.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.625597E+09 | 3529.71 | 27-JAN-09:04 | -1.2 | -5.7 | 0.594276E+09 | 1033.03 | 07-JAN-15:00 | -1.2 | -5.7 |
February | 0.702080E+09 | 3474.97 | 01-FEB-09:03 | 1.47 | -2.3 | 0.578207E+09 | 1123.87 | 04-FEB-15:00 | 18.90 | 7.75 |
March | 0.103757E+10 | 3167.97 | 02-MAR-09:04 | 0.47 | -3.7 | 0.700698E+09 | 1123.87 | 25-MAR-14:00 | 21.10 | 8.87 |
April | 0.289208E+10 | 22160.61 | 30-APR-09:02 | 20.37 | 12.82 | 0.702625E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.489508E+10 | 23305.99 | 10-MAY-08:62 | 20.78 | 10.27 | 0.729718E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.654981E+10 | 21958.85 | 12-JUN-08:61 | 23.35 | 9.75 | 0.716193E+09 | 1124.03 | 03-JUN-14:50 | 23.35 | 9.75 |
July | 0.679179E+10 | 19704.41 | 03-JUL-08:61 | 29.18 | 17.25 | 0.720653E+09 | 1124.01 | 15-JUL-14:09 | 31.38 | 18.29 |
August | 0.674898E+10 | 21924.91 | 23-AUG-08:61 | 24.27 | 13.78 | 0.741417E+09 | 1124.01 | 12-AUG-14:39 | 24.27 | 13.78 |
September | 0.596684E+10 | 23919.30 | 11-SEP-08:61 | 21.57 | 11.25 | 0.705963E+09 | 1124.01 | 16-SEP-14:00 | 32.20 | 18.22 |
October | 0.401922E+10 | 24307.37 | 22-OCT-09:02 | 19.68 | 11.91 | 0.717399E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.160571E+10 | 23517.33 | 10-NOV-09:02 | 18.48 | 11.84 | 0.656931E+09 | 1123.84 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.582172E+09 | 3651.12 | 27-DEC-09:04 | -0.7 | -2.5 | 0.590602E+09 | 1123.87 | 23-DEC-15:00 | -0.7 | -2.5 |
Annual Sum or Average | 0.424169E+11 | 0.815468E+10 | ||||||||
Minimum of Months | 0.582172E+09 | 3167.97 | -1.2 | -5.7 | 0.578207E+09 | 1033.03 | -1.2 | -5.7 | ||
Maximum of Months | 0.679179E+10 | 24307.37 | 29.18 | 17.25 | 0.741417E+09 | 1124.03 | 32.20 | 18.29 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.272761E+09 | 3611.07 | 27-JAN-09:04 | -1.2 | -5.7 | 0.584605E+09 | 997.72 | 07-JAN-15:00 | -1.2 | -5.7 |
February | 0.356500E+09 | 3420.21 | 09-FEB-09:04 | 2.38 | -1.5 | 0.567338E+09 | 1123.87 | 11-FEB-15:20 | 19.60 | 6.71 |
March | 0.636841E+09 | 3242.84 | 02-MAR-09:04 | 0.47 | -3.7 | 0.691420E+09 | 1123.87 | 04-MAR-15:39 | 19.07 | 8.46 |
April | 0.284633E+10 | 23334.86 | 30-APR-09:02 | 20.37 | 12.82 | 0.701680E+09 | 1123.87 | 29-APR-14:09 | 20.37 | 12.82 |
May | 0.530443E+10 | 25017.04 | 10-MAY-08:62 | 20.78 | 10.27 | 0.729722E+09 | 1123.87 | 27-MAY-14:09 | 30.68 | 15.94 |
June | 0.742429E+10 | 23725.18 | 12-JUN-08:61 | 23.35 | 9.75 | 0.716270E+09 | 1124.04 | 03-JUN-14:00 | 23.35 | 9.75 |
July | 0.778531E+10 | 21641.20 | 03-JUL-08:61 | 29.18 | 17.25 | 0.720798E+09 | 1124.02 | 15-JUL-14:09 | 31.38 | 18.29 |
August | 0.777712E+10 | 24008.27 | 23-AUG-08:61 | 24.27 | 13.78 | 0.741546E+09 | 1124.03 | 12-AUG-14:20 | 24.27 | 13.78 |
September | 0.686910E+10 | 26249.90 | 11-SEP-08:61 | 21.57 | 11.25 | 0.706105E+09 | 1124.03 | 16-SEP-14:50 | 32.02 | 18.38 |
October | 0.417493E+10 | 26355.36 | 22-OCT-09:02 | 19.68 | 11.91 | 0.716805E+09 | 1123.89 | 28-OCT-14:09 | 22.98 | 13.61 |
November | 0.133068E+10 | 18538.92 | 10-NOV-09:02 | 18.48 | 11.84 | 0.651728E+09 | 1123.85 | 18-NOV-15:09 | 19.40 | 6.83 |
December | 0.281022E+09 | 3507.05 | 27-DEC-09:04 | -0.7 | -2.5 | 0.583695E+09 | 1123.87 | 09-DEC-15:00 | -0.7 | -2.5 |
Annual Sum or Average | 0.450593E+11 | 0.811171E+10 | ||||||||
Minimum of Months | 0.272761E+09 | 3242.84 | -1.2 | -5.7 | 0.567338E+09 | 997.72 | -1.2 | -5.7 | ||
Maximum of Months | 0.778531E+10 | 26355.36 | 29.18 | 17.25 | 0.741546E+09 | 1124.04 | 32.02 | 18.38 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.334248E+09 | 54812.22 | 28-JAN-09:01 | 2.07 |
February | 0.287095E+09 | 55106.37 | 03-FEB-09:01 | 2.95 |
March | 0.287008E+09 | 54039.75 | 02-MAR-09:01 | 0.47 |
April | 0.250376E+09 | 3245.32 | 20-APR-08:04 | 20.78 |
May | 0.258621E+09 | 5440.99 | 31-MAY-08:04 | 27.30 |
June | 0.221384E+09 | 6246.39 | 07-JUN-08:04 | 29.27 |
July | 0.162863E+09 | 6305.92 | 03-JUL-08:04 | 29.18 |
August | 0.207063E+09 | 6034.16 | 07-AUG-08:04 | 28.48 |
September | 0.234976E+09 | 4232.10 | 10-SEP-07:05 | 21.47 |
October | 0.218338E+09 | 3629.55 | 05-OCT-08:04 | 23.17 |
November | 0.257607E+09 | 28862.30 | 28-NOV-09:01 | 4.18 |
December | 0.411560E+09 | 53601.46 | 30-DEC-09:01 | 1.05 |
Annual Sum or Average | 0.313114E+10 | |||
Minimum of Months | 0.162863E+09 | 3245.32 | 0.47 | |
Maximum of Months | 0.411560E+09 | 55106.37 | 29.27 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.144514E+09 | 6553.07 | 28-JAN-09:01 | 2.07 |
February | 0.127629E+09 | 2370.50 | 03-FEB-09:01 | 2.95 |
March | 0.143312E+09 | 4410.03 | 02-MAR-09:06 | 0.47 |
April | 0.130148E+09 | 2255.21 | 14-APR-21:30 | 21.70 |
May | 0.135909E+09 | 2834.52 | 31-MAY-08:04 | 27.30 |
June | 0.101535E+09 | 3281.12 | 15-JUN-08:04 | 29.78 |
July | 74147824.32 | 3290.64 | 03-JUL-08:04 | 29.18 |
August | 0.101011E+09 | 3135.03 | 07-AUG-08:04 | 28.48 |
September | 0.122200E+09 | 2279.60 | 10-SEP-07:05 | 21.47 |
October | 0.116969E+09 | 1929.79 | 05-OCT-08:04 | 23.17 |
November | 0.128967E+09 | 1457.03 | 17-NOV-08:25 | 4.15 |
December | 0.148295E+09 | 6808.87 | 27-DEC-09:01 | -0.7 |
Annual Sum or Average | 0.147464E+10 | |||
Minimum of Months | 74147824.32 | 1457.03 | -0.7 | |
Maximum of Months | 0.148295E+09 | 6808.87 | 29.78 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.158726E+09 | 14877.96 | 28-JAN-08:61 | -0.6 |
February | 0.142025E+09 | 9428.45 | 03-FEB-08:62 | -2.0 |
March | 0.151863E+09 | 2725.40 | 02-MAR-08:61 | -0.9 |
April | 0.222037E+09 | 2416.33 | 30-APR-16:12 | 30.40 |
May | 0.304305E+09 | 2951.58 | 29-MAY-16:11 | 33.13 |
June | 0.320517E+09 | 3716.79 | 18-JUN-16:11 | 37.20 |
July | 0.271940E+09 | 3912.09 | 02-JUL-16:11 | 38.13 |
August | 0.265999E+09 | 3504.13 | 06-AUG-16:11 | 36.10 |
September | 0.237051E+09 | 2790.64 | 17-SEP-16:11 | 32.43 |
October | 0.179454E+09 | 2631.15 | 01-OCT-16:11 | 31.50 |
November | 0.138000E+09 | 1419.68 | 04-NOV-07:00 | 8.30 |
December | 0.191025E+09 | 17569.93 | 27-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.258294E+10 | |||
Minimum of Months | 0.138000E+09 | 1419.68 | -3.4 | |
Maximum of Months | 0.320517E+09 | 17569.93 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.169163E+09 | 19877.02 | 28-JAN-08:61 | -0.6 |
February | 0.146234E+09 | 14035.30 | 03-FEB-08:62 | -2.0 |
March | 0.153977E+09 | 8279.38 | 02-MAR-08:61 | -0.9 |
April | 0.221063E+09 | 2409.22 | 30-APR-16:12 | 30.40 |
May | 0.301284E+09 | 2943.30 | 29-MAY-16:11 | 33.13 |
June | 0.310980E+09 | 3708.24 | 18-JUN-16:11 | 37.20 |
July | 0.261388E+09 | 3903.75 | 02-JUL-16:11 | 38.13 |
August | 0.257291E+09 | 3495.09 | 06-AUG-16:11 | 36.10 |
September | 0.230923E+09 | 2782.39 | 17-SEP-16:11 | 32.43 |
October | 0.177618E+09 | 2624.25 | 01-OCT-16:11 | 31.50 |
November | 0.139184E+09 | 2592.73 | 28-NOV-08:62 | 2.48 |
December | 0.217496E+09 | 23761.69 | 27-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.258660E+10 | |||
Minimum of Months | 0.139184E+09 | 2409.22 | -3.4 | |
Maximum of Months | 0.310980E+09 | 23761.69 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.197185E+09 | 25906.44 | 28-JAN-08:61 | -0.6 |
February | 0.159625E+09 | 20158.18 | 03-FEB-08:62 | -2.0 |
March | 0.160574E+09 | 15804.40 | 02-MAR-08:61 | -0.9 |
April | 0.223694E+09 | 2418.10 | 30-APR-16:12 | 30.40 |
May | 0.305927E+09 | 2951.37 | 29-MAY-16:11 | 33.13 |
June | 0.326329E+09 | 3715.87 | 18-JUN-16:11 | 37.20 |
July | 0.278232E+09 | 3911.50 | 02-JUL-16:11 | 38.13 |
August | 0.270863E+09 | 3501.89 | 06-AUG-16:11 | 36.10 |
September | 0.239559E+09 | 2790.05 | 17-SEP-16:11 | 32.43 |
October | 0.180712E+09 | 2632.49 | 01-OCT-16:11 | 31.50 |
November | 0.143860E+09 | 5459.87 | 28-NOV-08:62 | 2.48 |
December | 0.259979E+09 | 27341.79 | 27-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.274654E+10 | |||
Minimum of Months | 0.143860E+09 | 2418.10 | -3.4 | |
Maximum of Months | 0.326329E+09 | 27341.79 | 38.13 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.371563E+09 | 51044.32 | 28-JAN-09:01 | 2.07 |
February | 0.281869E+09 | 51356.92 | 03-FEB-09:01 | 2.95 |
March | 0.282219E+09 | 50293.26 | 02-MAR-09:01 | 0.47 |
April | 0.338684E+09 | 4510.93 | 30-APR-16:12 | 30.40 |
May | 0.403993E+09 | 5717.00 | 21-MAY-16:02 | 33.57 |
June | 0.317775E+09 | 7197.68 | 18-JUN-16:01 | 37.20 |
July | 0.301754E+09 | 7605.06 | 02-JUL-16:01 | 38.22 |
August | 0.315271E+09 | 6734.77 | 06-AUG-16:01 | 36.10 |
September | 0.327728E+09 | 5252.19 | 17-SEP-16:02 | 32.62 |
October | 0.291199E+09 | 4935.19 | 01-OCT-16:11 | 31.50 |
November | 0.259439E+09 | 39392.05 | 28-NOV-09:01 | 4.18 |
December | 0.489507E+09 | 51233.84 | 29-DEC-09:01 | 2.85 |
Annual Sum or Average | 0.398100E+10 | |||
Minimum of Months | 0.259439E+09 | 4510.93 | 0.47 | |
Maximum of Months | 0.489507E+09 | 51356.92 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.223499E+09 | 26493.91 | 28-JAN-09:01 | 2.07 |
February | 0.164430E+09 | 26658.24 | 03-FEB-09:01 | 2.95 |
March | 0.162565E+09 | 26135.09 | 02-MAR-09:01 | 0.47 |
April | 0.185168E+09 | 2339.52 | 30-APR-16:12 | 30.40 |
May | 0.217013E+09 | 2915.59 | 21-MAY-16:02 | 33.57 |
June | 0.179369E+09 | 3653.12 | 18-JUN-16:01 | 37.20 |
July | 0.170248E+09 | 3854.65 | 02-JUL-16:01 | 38.22 |
August | 0.176173E+09 | 3421.88 | 06-AUG-16:01 | 36.10 |
September | 0.178986E+09 | 2708.90 | 17-SEP-16:11 | 32.43 |
October | 0.159833E+09 | 2552.53 | 01-OCT-16:11 | 31.50 |
November | 0.145140E+09 | 20804.85 | 28-NOV-09:01 | 4.18 |
December | 0.291595E+09 | 26588.72 | 29-DEC-09:01 | 2.85 |
Annual Sum or Average | 0.225402E+10 | |||
Minimum of Months | 0.145140E+09 | 2339.52 | 0.47 | |
Maximum of Months | 0.291595E+09 | 26658.24 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.242351E+09 | 27010.77 | 09-JAN-09:01 | 5.47 |
February | 0.174072E+09 | 26577.18 | 03-FEB-09:01 | 2.95 |
March | 0.168257E+09 | 26061.94 | 02-MAR-09:01 | 0.47 |
April | 0.184748E+09 | 2336.19 | 30-APR-16:12 | 30.40 |
May | 0.216974E+09 | 2915.26 | 21-MAY-16:02 | 33.57 |
June | 0.181649E+09 | 3652.18 | 18-JUN-16:01 | 37.20 |
July | 0.172346E+09 | 3853.99 | 02-JUL-16:01 | 38.22 |
August | 0.177970E+09 | 3420.79 | 06-AUG-16:01 | 36.10 |
September | 0.179355E+09 | 2705.10 | 17-SEP-16:11 | 32.43 |
October | 0.159471E+09 | 2548.87 | 01-OCT-16:11 | 31.50 |
November | 0.149195E+09 | 22905.00 | 28-NOV-09:01 | 4.18 |
December | 0.314140E+09 | 26502.61 | 29-DEC-09:01 | 2.85 |
Annual Sum or Average | 0.232053E+10 | |||
Minimum of Months | 0.149195E+09 | 2336.19 | 0.47 | |
Maximum of Months | 0.314140E+09 | 27010.77 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.326243E+09 | 27131.77 | 09-JAN-09:01 | 5.47 |
February | 0.225822E+09 | 26680.83 | 03-FEB-09:01 | 2.95 |
March | 0.194475E+09 | 26181.72 | 02-MAR-09:01 | 0.47 |
April | 0.186750E+09 | 2342.60 | 30-APR-16:12 | 30.40 |
May | 0.218253E+09 | 2920.05 | 21-MAY-16:02 | 33.57 |
June | 0.187560E+09 | 3653.34 | 18-JUN-16:01 | 37.20 |
July | 0.177296E+09 | 3854.46 | 02-JUL-16:01 | 38.22 |
August | 0.181126E+09 | 3419.71 | 06-AUG-16:01 | 36.10 |
September | 0.180512E+09 | 2706.96 | 17-SEP-16:11 | 32.43 |
October | 0.160375E+09 | 2552.39 | 01-OCT-16:11 | 31.50 |
November | 0.164955E+09 | 26784.02 | 28-NOV-09:01 | 4.18 |
December | 0.402090E+09 | 27188.56 | 20-DEC-09:01 | 6.20 |
Annual Sum or Average | 0.260546E+10 | |||
Minimum of Months | 0.160375E+09 | 2342.60 | 0.47 | |
Maximum of Months | 0.402090E+09 | 27188.56 | 38.22 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.784545E+09 | 32958.18 | 27-JAN-08:61 | -3.5 |
February | 0.529612E+09 | 32683.03 | 03-FEB-08:62 | -2.0 |
March | 0.416642E+09 | 32981.79 | 02-MAR-08:61 | -0.9 |
April | 0.209195E+09 | 2490.75 | 30-APR-16:12 | 30.40 |
May | 0.232629E+09 | 3019.50 | 29-MAY-16:11 | 33.13 |
June | 0.187076E+09 | 3761.19 | 18-JUN-16:11 | 37.20 |
July | 0.169831E+09 | 3947.21 | 02-JUL-16:11 | 38.13 |
August | 0.176564E+09 | 3542.14 | 06-AUG-16:11 | 36.10 |
September | 0.187763E+09 | 2833.63 | 17-SEP-16:11 | 32.43 |
October | 0.177410E+09 | 2684.13 | 01-OCT-16:11 | 31.50 |
November | 0.263300E+09 | 30059.08 | 28-NOV-09:01 | 4.18 |
December | 0.830377E+09 | 32971.62 | 27-DEC-08:61 | -3.4 |
Annual Sum or Average | 0.416494E+10 | |||
Minimum of Months | 0.169831E+09 | 2490.75 | -3.5 | |
Maximum of Months | 0.830377E+09 | 32981.79 | 38.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.327814E+10 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.248311E+10 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4719553.38 | 0.224592E+10 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.447415E+09 | 0.100407E+10 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107323E+10 | 0.419414E+09 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179998E+10 | 0.150708E+09 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.162325E+10 | 0.107695E+09 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.136690E+10 | 0.193928E+09 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.959680E+09 | 0.222341E+09 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.233776E+09 | 0.105240E+10 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 963.07 | 0.250413E+10 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.331755E+10 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750895E+10 | 0.169794E+11 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.107695E+09 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179998E+10 | 0.331755E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157220E+10 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114520E+10 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 2502993.80 | 0.988597E+09 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232994E+09 | 0.397197E+09 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.554688E+09 | 0.142984E+09 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932640E+09 | 49274208.05 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.850445E+09 | 34970639.02 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.720094E+09 | 66626467.23 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.519818E+09 | 75200618.10 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.125589E+09 | 0.431042E+09 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.114209E+10 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161908E+10 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.393877E+10 | 0.766447E+10 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34970639.02 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932640E+09 | 0.161908E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159749E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.119075E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2489693.52 | 0.105146E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224372E+09 | 0.435266E+09 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541234E+09 | 0.162960E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925626E+09 | 56747500.85 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837369E+09 | 46586660.78 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709676E+09 | 73636328.00 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509248E+09 | 91844286.98 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121196E+09 | 0.471620E+09 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.119288E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.163831E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387121E+10 | 0.800956E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46586660.78 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925626E+09 | 0.163831E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.157342E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.117674E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2489693.52 | 0.104346E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224374E+09 | 0.434231E+09 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.540861E+09 | 0.163790E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924660E+09 | 58053931.51 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.836324E+09 | 47902387.84 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.708953E+09 | 74874708.43 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509136E+09 | 92675029.94 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121121E+09 | 0.471624E+09 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.118712E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.161758E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.386792E+10 | 0.794146E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 47902387.84 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.924660E+09 | 0.161758E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154273E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.115605E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2489693.52 | 0.103084E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224633E+09 | 0.429548E+09 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.541710E+09 | 0.160213E+09 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925978E+09 | 55934960.73 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.837452E+09 | 45974147.66 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.709751E+09 | 72946614.32 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509273E+09 | 91075573.03 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121247E+09 | 0.468709E+09 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.117931E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.159132E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.387253E+10 | 0.782466E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45974147.66 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.925978E+09 | 0.159132E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.279819E+10 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.210789E+10 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 4494971.70 | 0.191318E+10 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.409003E+09 | 0.816275E+09 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989381E+09 | 0.315157E+09 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168728E+10 | 0.110517E+09 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152161E+10 | 92156553.00 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128881E+10 | 0.147729E+09 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.917884E+09 | 0.185551E+09 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219170E+09 | 0.897160E+09 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 926.48 | 0.219569E+10 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288278E+10 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.703763E+10 | 0.144623E+11 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92156553.00 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.168728E+10 | 0.288278E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.150613E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.112773E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2489693.52 | 0.101904E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226264E+09 | 0.428546E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.546982E+09 | 0.160058E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932621E+09 | 54815614.33 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842453E+09 | 45520649.71 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714016E+09 | 74762248.22 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510339E+09 | 94406810.22 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121714E+09 | 0.474928E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.118160E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155975E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389688E+10 | 0.772729E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45520649.71 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932621E+09 | 0.155975E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.149562E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.111914E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2489693.52 | 0.101231E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226397E+09 | 0.426745E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547254E+09 | 0.159021E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932954E+09 | 54286674.23 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842757E+09 | 45061664.25 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714216E+09 | 74333688.55 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510396E+09 | 93972136.04 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121752E+09 | 0.473907E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.117792E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155116E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389822E+10 | 0.768347E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45061664.25 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.932954E+09 | 0.155116E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146978E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.109577E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2489693.52 | 0.991788E+09 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226760E+09 | 0.420099E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.547854E+09 | 0.155420E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933402E+09 | 52887001.92 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.842984E+09 | 44063300.85 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.714308E+09 | 73483213.20 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510423E+09 | 93112233.78 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.121808E+09 | 0.470642E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 513.91 | 0.116566E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152988E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.390003E+10 | 0.756259E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 44063300.85 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933402E+09 | 0.152988E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198509E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154296E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 2714275.54 | 0.144955E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254216E+09 | 0.688286E+09 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.621393E+09 | 0.303095E+09 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105711E+10 | 0.112035E+09 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.933660E+09 | 96765653.12 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.783767E+09 | 0.149993E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.532641E+09 | 0.191338E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.129190E+09 | 0.754045E+09 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 550.50 | 0.163295E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200499E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.431469E+10 | 0.109111E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96765653.12 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.105711E+10 | 0.200499E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4879.74 | 26-JAN-12:10 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5270.67 | 08-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 314.35 | 22-MAR-13:00 | 4522.65 | 01-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2580.91 | 21-APR-15:00 | 3895.87 | 10-APR-24:00 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3210.62 | 19-MAY-14:00 | 1646.58 | 04-MAY-02:00 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3895.40 | 02-JUN-16:00 | 1364.49 | 28-JUN-02:00 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3860.61 | 03-JUL-17:00 | 641.49 | 08-JUL-15:00 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3545.71 | 07-AUG-16:00 | 1117.00 | 14-AUG-01:00 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2569.51 | 19-SEP-14:00 | 1710.01 | 23-SEP-17:00 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2406.64 | 01-OCT-15:00 | 2955.46 | 24-OCT-11:10 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.81 | 03-NOV-16:00 | 4541.00 | 26-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5712.07 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 641.49 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3895.40 | 5712.07 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2656.96 | 26-JAN-12:10 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2682.26 | 08-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2491.53 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1770.29 | 11-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.59 | 01-MAY-12:00 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 414.43 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.13 | 23-SEP-17:00 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1621.69 | 24-OCT-11:10 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2479.58 | 26-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2650.16 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2659.47 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2462.08 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1768.69 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.59 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 428.75 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.13 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1621.69 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2393.86 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2648.16 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2642.73 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2434.12 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1761.07 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.59 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 432.01 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.13 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1621.69 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2393.86 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2648.16 | 26-JAN-12:10 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2610.90 | 08-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2394.30 | 01-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1735.75 | 11-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.59 | 01-MAY-12:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 425.73 | 28-JUN-02:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.12 | 23-SEP-17:00 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1621.69 | 24-OCT-11:10 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2393.86 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4764.07 | 26-JAN-12:10 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 4583.29 | 08-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 296.28 | 22-MAR-13:00 | 4313.58 | 01-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2338.01 | 21-APR-15:00 | 3060.19 | 06-APR-12:00 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2986.54 | 19-MAY-14:00 | 1259.66 | 01-MAY-12:00 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3761.96 | 02-JUN-16:00 | 812.23 | 28-JUN-02:00 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3674.76 | 03-JUL-17:00 | 606.58 | 08-JUL-15:00 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3398.02 | 07-AUG-16:00 | 811.31 | 14-AUG-11:10 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2508.60 | 19-SEP-14:00 | 1644.43 | 23-SEP-17:00 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2306.40 | 01-OCT-15:00 | 2904.23 | 24-OCT-11:10 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.78 | 03-NOV-16:00 | 4322.31 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 5590.51 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 606.58 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 3761.96 | 5590.51 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2648.16 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2517.52 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2390.20 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1678.70 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.59 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 403.49 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.11 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1614.55 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2393.86 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2648.16 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2502.55 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2390.20 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1678.70 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.59 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 401.93 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.10 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1612.40 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2393.86 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2648.16 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 2465.07 | 08-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 163.85 | 22-MAR-13:00 | 2390.20 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1285.28 | 21-APR-15:00 | 1674.03 | 06-APR-12:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1648.43 | 19-MAY-14:00 | 695.56 | 01-MAY-12:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 02-JUN-16:00 | 398.35 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2035.22 | 03-JUL-17:00 | 335.62 | 08-JUL-15:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1883.81 | 07-AUG-16:00 | 451.66 | 14-AUG-11:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1394.43 | 19-SEP-14:00 | 912.10 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1278.63 | 01-OCT-15:00 | 1605.36 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.43 | 03-NOV-16:00 | 2393.86 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3108.64 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 335.62 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2087.89 | 3108.64 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 2763.83 | 26-JAN-12:10 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3420.21 | 08-FEB-21:03 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 181.92 | 22-MAR-13:00 | 2593.09 | 01-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1528.19 | 21-APR-15:00 | 2432.17 | 10-APR-24:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1872.51 | 19-MAY-14:00 | 962.72 | 28-MAY-18:51 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.60 | 05-JUN-17:00 | 909.57 | 28-JUN-02:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2221.07 | 03-JUL-17:00 | 575.13 | 18-JUL-20:55 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2031.50 | 07-AUG-16:00 | 842.15 | 14-AUG-01:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1455.34 | 19-SEP-14:00 | 977.64 | 23-SEP-17:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1378.88 | 01-OCT-15:00 | 1624.31 | 24-OCT-11:10 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.46 | 03-NOV-16:00 | 2612.45 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 3230.20 | 26-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 575.13 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 2237.60 | 3420.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 8033.00 | 27-JAN-09:03 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1238.10 |
February | 7138.97 | 20-FEB-16:00 | 2700.03 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.02 |
March | 7553.21 | 16-MAR-16:10 | 3375.03 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 542.40 |
April | 45606.16 | 29-APR-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.09 |
May | 49012.60 | 10-MAY-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.50 |
June | 44976.02 | 12-JUN-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.28 |
July | 40917.73 | 03-JUL-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 153.16 | 0.00 |
August | 45660.05 | 23-AUG-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 60.36 |
September | 49259.11 | 11-SEP-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.54 |
October | 47904.37 | 19-OCT-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.87 |
November | 50192.51 | 10-NOV-09:02 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.94 |
December | 7898.74 | 27-DEC-09:03 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 825.27 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 7138.97 | 2025.02 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 50192.51 | 3375.03 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 153.16 | 1238.10 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 21800.52 | 03-JAN-21:10 | 2024.96 | 6468.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 61.64 |
February | 25932.86 | 19-FEB-18:52 | 20249.61 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 95.00 |
March | 26533.20 | 12-MAR-17:33 | 20249.61 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.80 |
April | 26035.60 | 15-APR-20:52 | 10124.81 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 26106.37 | 12-MAY-08:62 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 118.89 |
June | 23480.85 | 12-JUN-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 |
July | 21232.15 | 01-JUL-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 0.00 |
August | 23440.45 | 23-AUG-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.56 |
September | 27068.32 | 30-SEP-20:12 | 10124.81 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 26918.20 | 26-OCT-20:40 | 10124.81 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 14.70 |
November | 27550.79 | 09-NOV-09:02 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.13 |
December | 3098.90 | 26-DEC-09:01 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 534.71 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3098.90 | 843.73 | 6468.47 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 27550.79 | 20249.61 | 32342.33 | 6741.28 | 0.00 | 0.00 | 0.00 | 0.00 | 71.50 | 534.71 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3920.82 | 27-JAN-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.18 |
February | 3641.37 | 22-FEB-14:00 | 1349.97 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 309.31 |
March | 4098.49 | 16-MAR-14:00 | 1012.48 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 |
April | 25725.07 | 20-APR-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 92.74 |
May | 27213.11 | 10-MAY-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.78 |
June | 25062.49 | 01-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.79 |
July | 21835.90 | 11-JUL-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 |
August | 25581.00 | 23-AUG-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.59 |
September | 28304.17 | 11-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.42 |
October | 27569.71 | 06-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 342.96 |
November | 26414.21 | 10-NOV-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.86 |
December | 4056.58 | 27-DEC-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 580.90 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3641.37 | 843.73 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.37 | |
Maximum of Months | 28304.17 | 1349.97 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.18 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4087.94 | 27-JAN-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.72 |
February | 3652.43 | 03-FEB-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.69 |
March | 4014.15 | 16-MAR-14:00 | 1012.48 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 |
April | 25583.98 | 30-APR-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 115.94 |
May | 27069.55 | 10-MAY-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.17 |
June | 24924.90 | 01-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.97 |
July | 21712.15 | 11-JUL-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 |
August | 25442.31 | 23-AUG-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.79 |
September | 28184.71 | 11-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.05 |
October | 27510.57 | 06-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 345.19 |
November | 26241.89 | 10-NOV-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 236.22 |
December | 4266.32 | 27-DEC-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 583.87 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3652.43 | 843.73 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.52 | |
Maximum of Months | 28184.71 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 634.72 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4277.44 | 27-JAN-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.78 |
February | 3868.68 | 03-FEB-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.35 |
March | 3775.39 | 16-MAR-14:00 | 1012.48 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 171.20 |
April | 25483.70 | 20-APR-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 88.87 |
May | 26998.18 | 10-MAY-07:02 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 135.42 |
June | 24978.71 | 01-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 62.66 |
July | 21769.98 | 11-JUL-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 |
August | 25498.64 | 23-AUG-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.60 |
September | 28218.11 | 11-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.55 |
October | 27421.25 | 06-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 341.70 |
November | 24475.91 | 10-NOV-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.59 |
December | 4343.53 | 27-DEC-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 581.49 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3775.39 | 843.73 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 26.39 | |
Maximum of Months | 28218.11 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 637.78 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 6722.31 | 26-JAN-09:03 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 929.07 |
February | 7083.82 | 02-FEB-09:03 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 860.32 |
March | 7419.77 | 02-MAR-09:03 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 789.10 |
April | 45495.22 | 30-APR-09:02 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.82 |
May | 45870.86 | 10-MAY-08:62 | 4455.04 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 204.88 |
June | 43042.37 | 12-JUN-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.18 |
July | 38357.78 | 03-JUL-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 131.99 | 0.00 |
August | 42794.40 | 23-AUG-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 55.56 |
September | 46770.02 | 11-SEP-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 185.27 |
October | 48483.73 | 06-OCT-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 624.39 |
November | 46899.75 | 10-NOV-09:02 | 4455.04 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 346.60 |
December | 7194.17 | 30-DEC-09:03 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 869.10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6722.31 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 48483.73 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 131.99 | 929.07 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3314.53 | 26-JAN-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.22 |
February | 3463.11 | 02-FEB-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.62 |
March | 3623.87 | 02-MAR-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 436.67 |
April | 23396.64 | 30-APR-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 78.94 |
May | 23540.66 | 10-MAY-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 105.78 |
June | 22161.01 | 12-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.91 |
July | 19762.33 | 03-JUL-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.80 | 0.00 |
August | 22024.26 | 23-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.32 |
September | 24077.92 | 11-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 98.17 |
October | 24975.63 | 06-OCT-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 332.13 |
November | 24164.12 | 10-NOV-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 180.89 |
December | 3556.50 | 19-DEC-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 421.59 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3314.53 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24975.63 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.80 | 504.22 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3317.42 | 26-JAN-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.20 |
February | 3435.17 | 02-FEB-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 467.35 |
March | 3413.05 | 02-MAR-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 433.46 |
April | 23242.60 | 30-APR-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 77.91 |
May | 23411.52 | 10-MAY-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 104.54 |
June | 22055.48 | 12-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 41.52 |
July | 19687.94 | 03-JUL-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.76 | 0.00 |
August | 21931.76 | 23-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 29.18 |
September | 23960.69 | 11-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 97.56 |
October | 24631.23 | 06-OCT-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 331.52 |
November | 24005.80 | 10-NOV-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 179.32 |
December | 3648.71 | 19-DEC-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 422.82 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3317.42 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24631.23 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.76 | 502.20 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3529.71 | 27-JAN-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 571.67 |
February | 3474.97 | 01-FEB-09:03 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 599.82 |
March | 3167.97 | 02-MAR-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 434.28 |
April | 22160.61 | 30-APR-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 75.81 |
May | 23305.99 | 10-MAY-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.64 |
June | 21958.85 | 12-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.35 |
July | 19704.41 | 03-JUL-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 0.00 |
August | 21924.91 | 23-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 28.73 |
September | 23919.30 | 11-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.05 |
October | 24307.37 | 22-OCT-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 102.16 |
November | 23517.33 | 10-NOV-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 174.32 |
December | 3651.12 | 27-DEC-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.92 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3167.97 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 24307.37 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 72.72 | 599.82 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3611.07 | 27-JAN-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 759.60 |
February | 3420.21 | 09-FEB-09:04 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 528.56 |
March | 3242.84 | 02-MAR-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.85 |
April | 23334.86 | 30-APR-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.68 |
May | 25017.04 | 10-MAY-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 143.54 |
June | 23725.18 | 12-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 35.30 |
July | 21641.20 | 03-JUL-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 90.90 | 0.00 |
August | 24008.27 | 23-AUG-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 34.65 |
September | 26249.90 | 11-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 134.53 |
October | 26355.36 | 22-OCT-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 120.71 |
November | 18538.92 | 10-NOV-09:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 281.28 |
December | 3507.05 | 27-DEC-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.80 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3242.84 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 26355.36 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 90.90 | 759.60 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.921219E+11 | 72401.30 | 05-JAN-19:19 | 0.692260E+10 | 110812.30 | 27-JAN-09:09 |
February | 0.836531E+11 | 71964.09 | 20-FEB-15:20 | 0.328821E+10 | 95952.97 | 03-FEB-09:09 |
March | 0.942214E+11 | 77816.45 | 22-MAR-13:09 | 0.163005E+10 | 100950.20 | 02-MAR-09:09 |
April | 0.102233E+12 | 94789.33 | 21-APR-14:30 | 10518057.02 | 2745.89 | 11-APR-08:09 |
May | 0.119506E+12 | 103476.87 | 21-MAY-14:20 | 123691.40 | 206.15 | 07-MAY-21:10 |
June | 0.130261E+12 | 112883.29 | 15-JUN-14:00 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.136132E+12 | 110867.40 | 03-JUL-13:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.132778E+12 | 110788.41 | 07-AUG-16:30 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.123062E+12 | 105379.54 | 02-SEP-13:50 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.107212E+12 | 102870.24 | 03-OCT-14:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.904902E+11 | 79145.74 | 08-NOV-15:39 | 0.179605E+10 | 71744.45 | 28-NOV-09:09 |
December | 0.920264E+11 | 70921.86 | 06-DEC-17:49 | 0.112348E+11 | 117838.61 | 27-DEC-09:09 |
Annual Sum or Average | 0.130370E+13 | 0.248824E+11 | ||||
Minimum of Months | 0.836531E+11 | 70921.86 | 0.00 | 0.00 | ||
Maximum of Months | 0.136132E+12 | 112883.29 | 0.112348E+11 | 117838.61 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.119278E+11 | 0.108804E+11 | 0.00 | 0.247556E+11 | 0.00 | 0.00 | 10450589.79 | 0.00 | 0.00 | 0.00 | 0.544797E+10 | 0.00 |
February | 0.353889E+11 | 0.102040E+11 | 0.985143E+10 | 0.00 | 0.225970E+11 | 0.00 | 0.00 | 0.692112E+09 | 0.00 | 0.00 | 0.00 | 0.491970E+10 | 0.00 |
March | 0.396588E+11 | 0.104866E+11 | 0.110560E+11 | 0.00 | 0.254830E+11 | 0.00 | 0.00 | 0.212262E+10 | 0.00 | 0.00 | 0.00 | 0.541445E+10 | 0.00 |
April | 0.379231E+11 | 0.933279E+10 | 0.105544E+11 | 0.00 | 0.241818E+11 | 0.00 | 0.00 | 0.151342E+11 | 0.00 | 0.00 | 0.00 | 0.510638E+10 | 0.00 |
May | 0.393718E+11 | 0.894354E+10 | 0.109629E+11 | 0.00 | 0.250520E+11 | 0.00 | 0.00 | 0.300044E+11 | 0.00 | 0.00 | 0.00 | 0.517089E+10 | 0.00 |
June | 0.383312E+11 | 0.830405E+10 | 0.106855E+11 | 0.00 | 0.243968E+11 | 0.00 | 0.00 | 0.436209E+11 | 0.00 | 0.00 | 0.00 | 0.492305E+10 | 0.00 |
July | 0.389786E+11 | 0.873501E+10 | 0.108424E+11 | 0.00 | 0.247559E+11 | 0.00 | 0.00 | 0.478219E+11 | 0.00 | 0.00 | 0.00 | 0.499812E+10 | 0.00 |
August | 0.396438E+11 | 0.933279E+10 | 0.110491E+11 | 0.00 | 0.252551E+11 | 0.00 | 0.00 | 0.424610E+11 | 0.00 | 0.00 | 0.00 | 0.503630E+10 | 0.00 |
September | 0.379380E+11 | 0.978692E+10 | 0.105613E+11 | 0.00 | 0.241450E+11 | 0.00 | 0.00 | 0.357217E+11 | 0.00 | 0.00 | 0.00 | 0.490906E+10 | 0.00 |
October | 0.390997E+11 | 0.109639E+11 | 0.108804E+11 | 0.00 | 0.250936E+11 | 0.00 | 0.00 | 0.160150E+11 | 0.00 | 0.00 | 0.00 | 0.515933E+10 | 0.00 |
November | 0.378782E+11 | 0.113208E+11 | 0.105443E+11 | 0.00 | 0.243078E+11 | 0.00 | 0.00 | 0.132699E+10 | 0.00 | 0.00 | 0.00 | 0.511212E+10 | 0.00 |
December | 0.389936E+11 | 0.121039E+11 | 0.108529E+11 | 0.00 | 0.246736E+11 | 0.00 | 0.00 | 3069887.13 | 0.00 | 0.00 | 0.00 | 0.539932E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121442E+12 | 0.128721E+12 | 0.00 | 0.294697E+12 | 0.00 | 0.00 | 0.234934E+12 | 0.00 | 0.00 | 0.00 | 0.615967E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.830405E+10 | 0.985143E+10 | 0.00 | 0.225970E+11 | 0.00 | 0.00 | 3069887.13 | 0.00 | 0.00 | 0.00 | 0.490906E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.121039E+11 | 0.110560E+11 | 0.00 | 0.254830E+11 | 0.00 | 0.00 | 0.478219E+11 | 0.00 | 0.00 | 0.00 | 0.544797E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.692260E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.328821E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.163005E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 10518057.02 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 123691.40 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.179605E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.112348E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.248824E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.112348E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 17042.73 | 01-JAN-09:09 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 17042.73 | 01-FEB-08:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 17042.73 | 01-MAR-08:09 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 17042.73 | 01-APR-07:10 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 17042.73 | 01-MAY-07:10 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 17042.73 | 01-JUN-07:10 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 17042.73 | 01-JUL-07:10 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 17042.73 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 17042.73 | 01-SEP-07:10 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 17042.73 | 01-OCT-08:09 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 17042.73 | 01-NOV-07:10 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 17042.73 | 01-DEC-08:09 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 17042.73 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 17042.73 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 2487.47 | 03-JAN-21:10 | 0.00 | 0.00 | 0.00 | 11055.81 | 05-JAN-12:00 | 0.00 |
February | 12701.94 | 20-FEB-15:30 | 0.00 | 0.00 | 0.00 | 9684.01 | 24-FEB-12:00 | 0.00 |
March | 17219.05 | 22-MAR-12:00 | 0.00 | 0.00 | 0.00 | 9648.10 | 05-MAR-16:10 | 0.00 |
April | 35491.00 | 21-APR-14:30 | 0.00 | 0.00 | 0.00 | 9691.48 | 29-APR-13:09 | 0.00 |
May | 42303.84 | 21-MAY-14:09 | 0.00 | 0.00 | 0.00 | 9691.15 | 04-MAY-13:39 | 0.00 |
June | 53593.46 | 15-JUN-14:00 | 0.00 | 0.00 | 0.00 | 7547.97 | 21-JUN-11:50 | 0.00 |
July | 53235.42 | 03-JUL-16:10 | 0.00 | 0.00 | 0.00 | 7560.72 | 14-JUL-12:09 | 0.00 |
August | 52064.62 | 07-AUG-16:10 | 0.00 | 0.00 | 0.00 | 9597.08 | 04-AUG-08:50 | 0.00 |
September | 44517.09 | 15-SEP-12:00 | 0.00 | 0.00 | 0.00 | 7951.68 | 02-SEP-13:50 | 0.00 |
October | 44229.78 | 03-OCT-13:00 | 0.00 | 0.00 | 0.00 | 7557.11 | 23-OCT-11:39 | 0.00 |
November | 18833.84 | 03-NOV-15:00 | 0.00 | 0.00 | 0.00 | 11709.53 | 25-NOV-09:30 | 0.00 |
December | 510.94 | 16-DEC-19:19 | 0.00 | 0.00 | 0.00 | 9713.93 | 20-DEC-13:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 510.94 | 0.00 | 0.00 | 0.00 | 7547.97 | 0.00 | ||
Maximum of Months | 53593.46 | 0.00 | 0.00 | 0.00 | 11709.53 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 72401.30 | 05-JAN-19:19 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 17042.73 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 71964.09 | 20-FEB-15:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 12681.12 | 0.00 |
March | 77816.45 | 22-MAR-13:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 16624.33 | 0.00 |
April | 94789.33 | 21-APR-14:30 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 35491.00 | 0.00 |
May | 103476.87 | 21-MAY-14:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 42098.97 | 0.00 |
June | 112883.29 | 15-JUN-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 53593.46 | 0.00 |
July | 110867.40 | 03-JUL-13:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 52691.88 | 0.00 |
August | 110788.41 | 07-AUG-16:30 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 51507.29 | 0.00 |
September | 105379.54 | 02-SEP-13:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 43577.38 | 0.00 |
October | 102870.24 | 03-OCT-14:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 43577.99 | 0.00 |
November | 79145.74 | 08-NOV-15:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 15847.00 | 0.00 |
December | 70921.86 | 06-DEC-17:49 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 17042.73 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 70921.86 | 28718.22 | 8089.53 | 0.00 | 0.00 | 17042.73 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 112883.29 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 17042.73 | 0.00 | 0.00 | 53593.46 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 110812.30 | 27-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 95952.97 | 03-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 100950.20 | 02-MAR-09:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 2745.89 | 11-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 206.15 | 07-MAY-21:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 71744.45 | 28-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 117838.61 | 27-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 117838.61 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Annual Sum or Average | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.67 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 | 0.00 | 20.50 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 482.50 | 22.27 | 38.17 | 22.17 | 38.17 | 22.08 |
February | 445.17 | 22.79 | 24.33 | 22.69 | 24.33 | 22.59 |
March | 475.83 | 23.26 | 11.83 | 23.20 | 11.83 | 23.14 |
April | 210.50 | 23.74 | 30.17 | 23.76 | 0.00 | 23.76 |
May | 52.17 | 23.91 | 212.83 | 23.95 | 0.00 | 23.95 |
June | 3.17 | 23.89 | 386.67 | 23.99 | 0.33 | 23.99 |
July | 66.83 | 24.10 | 495.00 | 23.99 | 66.83 | 24.00 |
August | 39.33 | 24.26 | 491.83 | 24.00 | 39.33 | 24.02 |
September | 42.83 | 24.00 | 422.17 | 23.96 | 40.83 | 23.96 |
October | 50.33 | 23.88 | 263.00 | 23.93 | 15.17 | 23.93 |
November | 322.50 | 23.12 | 31.00 | 23.14 | 4.83 | 23.11 |
December | 496.00 | 22.13 | 42.67 | 22.02 | 42.67 | 21.92 |
Annual Sum or Average | 2687.17 | 22.89 | 2449.67 | 23.33 | 284.33 | 23.29 |
Minimum of Months | 3.17 | 22.13 | 11.83 | 22.02 | 0.00 | 21.92 |
Maximum of Months | 496.00 | 24.26 | 495.00 | 24.00 | 66.83 | 24.02 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 467.00 | 23.09 | 3.00 | 23.07 | 3.00 | 23.06 |
February | 416.33 | 23.38 | 2.33 | 23.37 | 2.33 | 23.35 |
March | 428.50 | 23.58 | 1.83 | 23.57 | 1.83 | 23.56 |
April | 192.17 | 23.71 | 30.50 | 23.74 | 0.00 | 23.74 |
May | 51.00 | 23.53 | 207.67 | 23.90 | 0.00 | 23.90 |
June | 3.33 | 22.37 | 369.17 | 23.99 | 0.00 | 23.99 |
July | 37.33 | 24.13 | 493.33 | 23.98 | 37.17 | 23.99 |
August | 23.83 | 23.96 | 482.83 | 23.98 | 21.50 | 23.99 |
September | 27.00 | 23.48 | 402.50 | 23.91 | 18.00 | 23.91 |
October | 42.33 | 23.67 | 249.17 | 23.89 | 9.67 | 23.90 |
November | 281.17 | 23.46 | 33.50 | 23.51 | 0.33 | 23.50 |
December | 494.17 | 22.95 | 5.50 | 22.93 | 5.50 | 22.90 |
Annual Sum or Average | 2464.17 | 23.33 | 2281.33 | 23.63 | 99.33 | 23.63 |
Minimum of Months | 3.33 | 22.37 | 1.83 | 22.93 | 0.00 | 22.90 |
Maximum of Months | 494.17 | 24.13 | 493.33 | 23.99 | 37.17 | 23.99 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 355.50 | 22.56 | 11.17 | 22.52 | 11.17 | 22.48 |
February | 326.00 | 23.07 | 5.83 | 23.03 | 5.83 | 23.00 |
March | 332.67 | 23.38 | 2.83 | 23.36 | 2.83 | 23.35 |
April | 115.33 | 23.74 | 44.33 | 24.06 | 0.00 | 24.06 |
May | 24.83 | 24.29 | 173.33 | 24.35 | 2.33 | 24.40 |
June | 7.33 | 28.47 | 287.33 | 24.34 | 7.33 | 24.44 |
July | 61.00 | 25.03 | 369.00 | 24.29 | 61.00 | 24.38 |
August | 28.83 | 25.37 | 377.00 | 24.23 | 28.83 | 24.30 |
September | 24.17 | 24.70 | 333.17 | 24.17 | 22.33 | 24.20 |
October | 27.00 | 23.89 | 208.67 | 24.10 | 8.17 | 24.10 |
November | 213.67 | 23.17 | 32.33 | 23.27 | 0.83 | 23.26 |
December | 369.00 | 22.44 | 14.33 | 22.39 | 14.33 | 22.34 |
Annual Sum or Average | 1885.33 | 23.12 | 1859.33 | 23.63 | 165.00 | 23.66 |
Minimum of Months | 7.33 | 22.44 | 2.83 | 22.39 | 0.00 | 22.34 |
Maximum of Months | 369.00 | 28.47 | 377.00 | 24.35 | 61.00 | 24.44 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 361.33 | 22.44 | 14.33 | 22.39 | 14.33 | 22.35 |
February | 328.00 | 22.98 | 7.33 | 22.94 | 7.33 | 22.90 |
March | 342.50 | 23.36 | 3.50 | 23.33 | 3.50 | 23.31 |
April | 117.50 | 23.73 | 43.50 | 24.05 | 0.00 | 24.05 |
May | 24.00 | 24.30 | 174.33 | 24.35 | 2.33 | 24.40 |
June | 7.67 | 28.47 | 289.33 | 24.34 | 7.67 | 24.45 |
July | 61.33 | 25.07 | 369.00 | 24.30 | 61.33 | 24.39 |
August | 28.67 | 25.41 | 377.33 | 24.23 | 28.67 | 24.31 |
September | 23.33 | 24.73 | 333.50 | 24.17 | 21.67 | 24.20 |
October | 26.83 | 23.89 | 207.33 | 24.10 | 8.33 | 24.10 |
November | 225.00 | 23.15 | 32.00 | 23.24 | 1.83 | 23.22 |
December | 369.00 | 22.31 | 20.50 | 22.25 | 20.50 | 22.19 |
Annual Sum or Average | 1915.17 | 23.06 | 1872.00 | 23.58 | 177.50 | 23.61 |
Minimum of Months | 7.67 | 22.31 | 3.50 | 22.25 | 0.00 | 22.19 |
Maximum of Months | 369.00 | 28.47 | 377.33 | 24.35 | 61.33 | 24.45 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 367.00 | 22.28 | 22.00 | 22.21 | 22.00 | 22.15 |
February | 332.33 | 22.84 | 12.33 | 22.78 | 12.33 | 22.72 |
March | 359.33 | 23.30 | 4.83 | 23.27 | 4.83 | 23.24 |
April | 132.50 | 23.73 | 38.67 | 24.01 | 0.00 | 24.01 |
May | 27.83 | 24.24 | 169.17 | 24.34 | 2.33 | 24.39 |
June | 7.00 | 28.27 | 285.50 | 24.33 | 7.00 | 24.42 |
July | 61.50 | 24.97 | 369.00 | 24.28 | 61.50 | 24.37 |
August | 28.17 | 25.28 | 377.33 | 24.22 | 28.17 | 24.29 |
September | 24.50 | 24.68 | 331.00 | 24.16 | 22.50 | 24.20 |
October | 30.17 | 23.85 | 202.50 | 24.08 | 8.50 | 24.09 |
November | 241.17 | 23.13 | 29.67 | 23.20 | 3.00 | 23.17 |
December | 369.00 | 22.15 | 29.50 | 22.07 | 29.50 | 22.00 |
Annual Sum or Average | 1980.50 | 22.96 | 1871.50 | 23.50 | 201.67 | 23.51 |
Minimum of Months | 7.00 | 22.15 | 4.83 | 22.07 | 0.00 | 22.00 |
Maximum of Months | 369.00 | 28.27 | 377.33 | 24.34 | 61.50 | 24.42 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 22.01 | 32.67 | 21.93 | 32.67 | 21.86 |
February | 308.00 | 22.63 | 17.50 | 22.54 | 17.50 | 22.47 |
March | 345.17 | 23.26 | 8.50 | 23.21 | 8.50 | 23.16 |
April | 157.17 | 23.75 | 21.00 | 23.86 | 0.00 | 23.86 |
May | 35.17 | 24.09 | 138.33 | 24.09 | 1.83 | 24.14 |
June | 3.50 | 28.21 | 255.00 | 24.06 | 3.50 | 24.12 |
July | 60.17 | 24.40 | 338.00 | 24.07 | 60.17 | 24.11 |
August | 22.83 | 24.78 | 345.33 | 24.03 | 22.83 | 24.07 |
September | 15.83 | 24.71 | 296.17 | 24.02 | 14.00 | 24.06 |
October | 40.50 | 23.80 | 173.83 | 23.96 | 9.67 | 23.96 |
November | 247.67 | 23.11 | 18.17 | 23.11 | 5.00 | 23.07 |
December | 338.00 | 21.88 | 49.33 | 21.78 | 49.33 | 21.70 |
Annual Sum or Average | 1914.00 | 22.81 | 1693.83 | 23.29 | 225.00 | 23.26 |
Minimum of Months | 3.50 | 21.88 | 8.50 | 21.78 | 0.00 | 21.70 |
Maximum of Months | 345.17 | 28.21 | 345.33 | 24.09 | 60.17 | 24.14 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.99 | 37.67 | 21.90 | 37.67 | 21.83 |
February | 308.00 | 22.61 | 21.33 | 22.51 | 21.33 | 22.43 |
March | 346.00 | 23.25 | 10.17 | 23.19 | 10.17 | 23.13 |
April | 178.67 | 23.77 | 14.17 | 23.86 | 0.00 | 23.86 |
May | 41.83 | 24.01 | 121.00 | 24.09 | 1.33 | 24.13 |
June | 3.17 | 28.19 | 235.33 | 24.07 | 3.17 | 24.12 |
July | 59.33 | 24.40 | 337.17 | 24.07 | 59.33 | 24.11 |
August | 21.17 | 24.77 | 342.33 | 24.03 | 21.17 | 24.07 |
September | 15.67 | 24.57 | 287.83 | 24.02 | 13.33 | 24.05 |
October | 45.83 | 23.81 | 164.67 | 23.96 | 9.67 | 23.96 |
November | 256.50 | 23.15 | 14.83 | 23.13 | 5.67 | 23.09 |
December | 338.00 | 21.86 | 55.50 | 21.76 | 55.50 | 21.68 |
Annual Sum or Average | 1954.17 | 22.82 | 1642.00 | 23.26 | 238.33 | 23.23 |
Minimum of Months | 3.17 | 21.86 | 10.17 | 21.76 | 0.00 | 21.68 |
Maximum of Months | 346.00 | 28.19 | 342.33 | 24.09 | 59.33 | 24.13 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.93 | 42.33 | 21.84 | 42.33 | 21.77 |
February | 308.00 | 22.55 | 25.17 | 22.45 | 25.17 | 22.35 |
March | 347.17 | 23.22 | 12.00 | 23.15 | 12.00 | 23.08 |
April | 185.67 | 23.76 | 13.33 | 23.85 | 0.00 | 23.85 |
May | 43.83 | 24.00 | 120.00 | 24.09 | 1.33 | 24.12 |
June | 3.17 | 28.17 | 233.67 | 24.07 | 3.17 | 24.12 |
July | 59.83 | 24.38 | 337.17 | 24.06 | 59.83 | 24.11 |
August | 20.67 | 24.75 | 341.83 | 24.02 | 20.67 | 24.06 |
September | 16.00 | 24.52 | 287.00 | 24.02 | 13.33 | 24.04 |
October | 48.17 | 23.81 | 163.17 | 23.96 | 9.50 | 23.96 |
November | 266.33 | 23.15 | 14.00 | 23.12 | 6.00 | 23.08 |
December | 338.00 | 21.81 | 61.50 | 21.71 | 61.50 | 21.63 |
Annual Sum or Average | 1976.83 | 22.80 | 1651.17 | 23.23 | 254.83 | 23.19 |
Minimum of Months | 3.17 | 21.81 | 12.00 | 21.71 | 0.00 | 21.63 |
Maximum of Months | 347.17 | 28.17 | 341.83 | 24.09 | 61.50 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.80 | 55.67 | 21.71 | 55.67 | 21.63 |
February | 308.00 | 22.42 | 37.83 | 22.28 | 37.83 | 22.16 |
March | 348.00 | 23.11 | 20.33 | 23.00 | 20.33 | 22.90 |
April | 197.33 | 23.74 | 12.50 | 23.82 | 0.00 | 23.82 |
May | 50.17 | 23.97 | 117.83 | 24.08 | 1.17 | 24.10 |
June | 3.33 | 27.95 | 233.83 | 24.07 | 3.33 | 24.12 |
July | 61.00 | 24.38 | 337.00 | 24.07 | 61.00 | 24.11 |
August | 21.17 | 24.73 | 342.17 | 24.02 | 21.17 | 24.06 |
September | 16.33 | 24.51 | 286.33 | 24.02 | 13.33 | 24.04 |
October | 53.83 | 23.78 | 160.50 | 23.95 | 9.83 | 23.95 |
November | 277.00 | 23.09 | 12.17 | 23.05 | 7.83 | 22.99 |
December | 338.00 | 21.71 | 78.00 | 21.60 | 78.00 | 21.52 |
Annual Sum or Average | 2014.17 | 22.72 | 1694.17 | 23.16 | 309.50 | 23.09 |
Minimum of Months | 3.33 | 21.71 | 12.17 | 21.60 | 0.00 | 21.52 |
Maximum of Months | 348.00 | 27.95 | 342.17 | 24.08 | 78.00 | 24.12 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.66 | 104.83 | 21.53 | 104.83 | 21.45 |
February | 308.00 | 22.23 | 76.83 | 22.01 | 76.83 | 21.86 |
March | 348.00 | 22.94 | 47.83 | 22.72 | 47.83 | 22.55 |
April | 211.50 | 23.70 | 15.67 | 23.74 | 2.17 | 23.72 |
May | 49.33 | 24.02 | 126.83 | 24.09 | 1.67 | 24.13 |
June | 4.50 | 27.91 | 261.00 | 24.07 | 4.50 | 24.14 |
July | 56.67 | 24.49 | 338.00 | 24.08 | 56.67 | 24.14 |
August | 25.67 | 24.84 | 346.00 | 24.04 | 25.67 | 24.10 |
September | 18.50 | 24.87 | 298.33 | 24.04 | 16.00 | 24.09 |
October | 62.17 | 23.70 | 162.50 | 23.92 | 10.17 | 23.93 |
November | 285.50 | 22.98 | 22.50 | 22.87 | 19.17 | 22.77 |
December | 338.00 | 21.61 | 128.50 | 21.47 | 128.50 | 21.39 |
Annual Sum or Average | 2047.83 | 22.63 | 1928.83 | 23.03 | 494.00 | 22.91 |
Minimum of Months | 4.50 | 21.61 | 15.67 | 21.47 | 1.67 | 21.39 |
Maximum of Months | 348.00 | 27.91 | 346.00 | 24.09 | 128.50 | 24.14 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 22.31670 | 21.93064 | -0.1874 | 7.06178 |
February | 448.00000 | 22.79606 | 17.89527 | -0.1041 | 6.63041 |
March | 497.00000 | 23.28218 | 16.62566 | 0.01414 | 6.16158 |
April | 479.00000 | 23.82712 | 19.65717 | 0.23374 | 6.51955 |
May | 496.00000 | 23.93695 | 29.15931 | -0.4861 | 10.29830 |
June | 481.00000 | 23.97352 | 33.92569 | -0.3699 | 8.07086 |
July | 495.00000 | 23.97554 | 49.22309 | -0.2457 | 6.43900 |
August | 497.00000 | 23.98233 | 44.85494 | -0.2803 | 6.85159 |
September | 479.00000 | 23.94837 | 42.82959 | -0.3196 | 7.39508 |
October | 496.00000 | 23.91360 | 36.12723 | 0.41259 | 8.83407 |
November | 480.00000 | 23.36968 | 22.14241 | 0.11183 | 6.50539 |
December | 496.00000 | 22.12516 | 19.07513 | -0.2519 | 7.64074 |
Annual Sum or Average | 5840.00000 | 23.45568 | 29.54403 | -0.1233 | 7.37623 |
Minimum of Months | 448.00000 | 22.12516 | 16.62566 | -0.4861 | 6.16158 |
Maximum of Months | 497.00000 | 23.98233 | 49.22309 | 0.41259 | 10.29830 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.13296 | 22.25591 | 0.00830 | 5.91403 |
February | 448.00000 | 23.41506 | 17.75687 | 0.05460 | 5.75869 |
March | 497.00000 | 23.62417 | 16.47932 | 0.11504 | 5.80364 |
April | 479.00000 | 23.82457 | 20.32368 | 0.25235 | 6.56506 |
May | 496.00000 | 23.89488 | 29.95943 | -0.4920 | 10.42296 |
June | 481.00000 | 23.95875 | 34.34835 | -0.3862 | 8.36942 |
July | 495.00000 | 23.96579 | 47.98276 | -0.2780 | 6.82764 |
August | 497.00000 | 23.95015 | 44.52288 | -0.3127 | 7.32661 |
September | 479.00000 | 23.87491 | 42.02178 | -0.3662 | 8.15577 |
October | 496.00000 | 23.87287 | 36.00341 | 0.40222 | 8.62143 |
November | 480.00000 | 23.64556 | 22.13155 | 0.18375 | 6.35959 |
December | 496.00000 | 22.95298 | 19.88980 | -0.0534 | 6.09525 |
Annual Sum or Average | 5840.00000 | 23.67653 | 29.56415 | -0.0737 | 7.19478 |
Minimum of Months | 448.00000 | 22.95298 | 16.47932 | -0.4920 | 5.75869 |
Maximum of Months | 497.00000 | 23.96579 | 47.98276 | 0.40222 | 10.42296 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.61713 | 20.33738 | -0.1079 | 6.43759 |
February | 336.00000 | 23.09975 | 16.95913 | -0.0162 | 6.08197 |
March | 379.00000 | 23.47927 | 15.78798 | 0.07751 | 6.03177 |
April | 360.00000 | 23.99401 | 19.74287 | 0.27926 | 7.06279 |
May | 375.00000 | 24.11011 | 28.60981 | -0.4371 | 9.75796 |
June | 366.00000 | 24.16158 | 33.09814 | -0.3292 | 8.07130 |
July | 369.00000 | 24.16904 | 48.49308 | -0.2082 | 6.65713 |
August | 379.00000 | 24.13965 | 44.56844 | -0.2499 | 6.94181 |
September | 360.00000 | 24.10981 | 42.18756 | -0.2878 | 7.30735 |
October | 371.00000 | 24.02353 | 35.13544 | 0.43170 | 9.24375 |
November | 360.00000 | 23.48436 | 21.62377 | 0.15026 | 6.57920 |
December | 369.00000 | 22.43508 | 17.85394 | -0.1689 | 6.82230 |
Annual Sum or Average | 4395.00000 | 23.65549 | 28.79589 | -0.0735 | 7.25991 |
Minimum of Months | 336.00000 | 22.43508 | 15.78798 | -0.4371 | 6.03177 |
Maximum of Months | 379.00000 | 24.16904 | 48.49308 | 0.43170 | 9.75796 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.48048 | 20.51878 | -0.1474 | 6.66503 |
February | 336.00000 | 23.00650 | 17.08529 | -0.0448 | 6.18044 |
March | 379.00000 | 23.43564 | 15.84775 | 0.06125 | 6.05491 |
April | 360.00000 | 23.99002 | 19.74888 | 0.27682 | 7.04308 |
May | 375.00000 | 24.11016 | 28.60345 | -0.4355 | 9.72938 |
June | 366.00000 | 24.16218 | 33.09686 | -0.3258 | 8.02872 |
July | 369.00000 | 24.16970 | 48.48031 | -0.2048 | 6.63282 |
August | 379.00000 | 24.14021 | 44.55384 | -0.2467 | 6.91273 |
September | 360.00000 | 24.11014 | 42.16916 | -0.2851 | 7.27744 |
October | 371.00000 | 24.02242 | 35.13962 | 0.43122 | 9.23529 |
November | 360.00000 | 23.45100 | 21.68202 | 0.13767 | 6.58878 |
December | 369.00000 | 22.31229 | 17.98777 | -0.2053 | 7.08709 |
Annual Sum or Average | 4395.00000 | 23.61978 | 28.83836 | -0.0836 | 7.29634 |
Minimum of Months | 336.00000 | 22.31229 | 15.84775 | -0.4355 | 6.05491 |
Maximum of Months | 379.00000 | 24.16970 | 48.48031 | 0.43122 | 9.72938 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 22.29451 | 20.74580 | -0.2000 | 7.03266 |
February | 336.00000 | 22.85741 | 17.28135 | -0.0890 | 6.39689 |
March | 379.00000 | 23.35432 | 15.95941 | 0.03251 | 6.11810 |
April | 360.00000 | 23.97401 | 19.77033 | 0.26557 | 6.94126 |
May | 375.00000 | 24.10529 | 28.62632 | -0.4445 | 9.88808 |
June | 366.00000 | 24.15832 | 33.10807 | -0.3324 | 8.09813 |
July | 369.00000 | 24.16605 | 48.53699 | -0.2102 | 6.65665 |
August | 379.00000 | 24.13642 | 44.59664 | -0.2526 | 6.95588 |
September | 360.00000 | 24.10598 | 42.21728 | -0.2919 | 7.34757 |
October | 371.00000 | 24.01488 | 35.18014 | 0.42405 | 9.11034 |
November | 360.00000 | 23.39795 | 21.77814 | 0.11800 | 6.57317 |
December | 369.00000 | 22.14631 | 18.17142 | -0.2538 | 7.49184 |
Annual Sum or Average | 4395.00000 | 23.56373 | 28.92589 | -0.1039 | 7.39397 |
Minimum of Months | 336.00000 | 22.14631 | 15.95941 | -0.4445 | 6.11810 |
Maximum of Months | 379.00000 | 24.16605 | 48.53699 | 0.42405 | 9.88808 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 22.00679 | 22.39443 | -0.2855 | 7.74917 |
February | 308.00000 | 22.62540 | 18.67765 | -0.1644 | 6.81533 |
March | 348.00000 | 23.26546 | 17.06807 | -0.0120 | 6.08230 |
April | 330.00000 | 23.88684 | 21.09179 | 0.23778 | 6.57897 |
May | 344.00000 | 23.96998 | 30.16997 | -0.4864 | 10.48497 |
June | 336.00000 | 23.97961 | 34.59791 | -0.3767 | 8.36897 |
July | 338.00000 | 24.01058 | 49.79756 | -0.2492 | 6.71573 |
August | 348.00000 | 23.98053 | 45.76349 | -0.2931 | 7.15425 |
September | 330.00000 | 23.97587 | 43.02777 | -0.3286 | 7.66119 |
October | 340.00000 | 23.92983 | 36.08840 | 0.40010 | 8.64450 |
November | 330.00000 | 23.30336 | 23.10652 | 0.08067 | 6.46913 |
December | 338.00000 | 21.87536 | 19.90415 | -0.3370 | 8.29868 |
Annual Sum or Average | 4030.00000 | 23.40589 | 30.23559 | -0.1522 | 7.59480 |
Minimum of Months | 308.00000 | 21.87536 | 17.06807 | -0.4864 | 6.08230 |
Maximum of Months | 348.00000 | 24.01058 | 49.79756 | 0.40010 | 10.48497 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.98715 | 22.32032 | -0.2992 | 7.89547 |
February | 308.00000 | 22.60910 | 18.61752 | -0.1774 | 6.90953 |
March | 348.00000 | 23.25786 | 17.01249 | -0.0238 | 6.10430 |
April | 330.00000 | 23.88834 | 21.00656 | 0.22537 | 6.44834 |
May | 344.00000 | 23.96939 | 30.11562 | -0.5081 | 10.91670 |
June | 336.00000 | 23.97813 | 34.51580 | -0.4034 | 8.79379 |
July | 338.00000 | 24.00898 | 49.74825 | -0.2761 | 6.99593 |
August | 348.00000 | 23.97914 | 45.70755 | -0.3194 | 7.47271 |
September | 330.00000 | 23.97534 | 42.98750 | -0.3538 | 8.00144 |
October | 340.00000 | 23.93157 | 36.03474 | 0.38674 | 8.41229 |
November | 330.00000 | 23.31147 | 23.01504 | 0.07268 | 6.42434 |
December | 338.00000 | 21.86113 | 19.82170 | -0.3483 | 8.43632 |
Annual Sum or Average | 4030.00000 | 23.40160 | 30.17028 | -0.1697 | 7.74496 |
Minimum of Months | 308.00000 | 21.86113 | 17.01249 | -0.5081 | 6.10430 |
Maximum of Months | 348.00000 | 24.00898 | 49.74825 | 0.38674 | 10.91670 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.92957 | 22.38902 | -0.3179 | 8.09818 |
February | 308.00000 | 22.55483 | 18.69666 | -0.1950 | 7.06050 |
March | 348.00000 | 23.21856 | 17.08027 | -0.0383 | 6.16497 |
April | 330.00000 | 23.88286 | 21.02010 | 0.22016 | 6.41378 |
May | 344.00000 | 23.96873 | 30.12615 | -0.5121 | 11.00155 |
June | 336.00000 | 23.97775 | 34.51471 | -0.4065 | 8.84483 |
July | 338.00000 | 24.00839 | 49.76818 | -0.2789 | 7.02493 |
August | 348.00000 | 23.97878 | 45.71452 | -0.3221 | 7.50691 |
September | 330.00000 | 23.97481 | 43.00057 | -0.3567 | 8.04323 |
October | 340.00000 | 23.92960 | 36.05182 | 0.38369 | 8.36532 |
November | 330.00000 | 23.28780 | 23.06743 | 0.06337 | 6.42191 |
December | 338.00000 | 21.81443 | 19.87105 | -0.3637 | 8.62747 |
Annual Sum or Average | 4030.00000 | 23.38252 | 30.20311 | -0.1780 | 7.80819 |
Minimum of Months | 308.00000 | 21.81443 | 17.08027 | -0.5121 | 6.16497 |
Maximum of Months | 348.00000 | 24.00839 | 49.76818 | 0.38369 | 11.00155 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.80286 | 22.53481 | -0.3594 | 8.62062 |
February | 308.00000 | 22.41939 | 18.88571 | -0.2381 | 7.48857 |
March | 348.00000 | 23.10876 | 17.25962 | -0.0766 | 6.36803 |
April | 330.00000 | 23.86224 | 21.05593 | 0.20689 | 6.35665 |
May | 344.00000 | 23.96732 | 30.14751 | -0.5172 | 11.12448 |
June | 336.00000 | 23.97739 | 34.51504 | -0.4065 | 8.84457 |
July | 338.00000 | 24.00813 | 49.78626 | -0.2772 | 7.00586 |
August | 348.00000 | 23.97856 | 45.71895 | -0.3203 | 7.48629 |
September | 330.00000 | 23.97440 | 43.01063 | -0.3558 | 8.03668 |
October | 340.00000 | 23.92291 | 36.09078 | 0.37846 | 8.29715 |
November | 330.00000 | 23.21309 | 23.21158 | 0.03780 | 6.45365 |
December | 338.00000 | 21.71030 | 19.97836 | -0.3985 | 9.11273 |
Annual Sum or Average | 4030.00000 | 23.33467 | 30.27694 | -0.1947 | 7.94194 |
Minimum of Months | 308.00000 | 21.71030 | 17.25962 | -0.5172 | 6.35665 |
Maximum of Months | 348.00000 | 24.00813 | 49.78626 | 0.37846 | 11.12448 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.66447 | 22.43752 | -0.4320 | 9.81354 |
February | 308.00000 | 22.23488 | 19.05337 | -0.3176 | 8.54929 |
March | 348.00000 | 22.94289 | 17.33142 | -0.1500 | 6.93676 |
April | 330.00000 | 23.82494 | 20.99951 | 0.18702 | 6.35791 |
May | 344.00000 | 23.97001 | 29.86875 | -0.5033 | 10.91594 |
June | 336.00000 | 23.98149 | 34.34518 | -0.3674 | 8.24064 |
July | 338.00000 | 24.01531 | 49.42251 | -0.2318 | 6.58272 |
August | 348.00000 | 23.98453 | 45.45559 | -0.2734 | 6.98385 |
September | 330.00000 | 23.98220 | 42.73399 | -0.3098 | 7.47648 |
October | 340.00000 | 23.90635 | 36.02065 | 0.37878 | 8.40396 |
November | 330.00000 | 23.10080 | 23.22648 | -0.0086 | 6.66904 |
December | 338.00000 | 21.60907 | 19.82711 | -0.4580 | 10.19483 |
Annual Sum or Average | 4030.00000 | 23.27476 | 30.15188 | -0.2075 | 8.09737 |
Minimum of Months | 308.00000 | 21.60907 | 17.33142 | -0.5033 | 6.35791 |
Maximum of Months | 348.00000 | 24.01531 | 49.42251 | 0.37878 | 10.91594 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2817349.10 | 805077.35 | 6.01 | 2817349.10 | -0.0 | 0.00 | 0.03 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 1188.00 | 03-JAN-15:00 | 1188.00 | 03-JAN-15:00 | 0.00 | 03-JAN-11:30 | 338.41 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.511020E+09 | 0.144261E+09 | 43.25 | 0.511020E+09 | -0.0 | 0.00 | 0.24 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 | 8788.85 | 20-FEB-16:00 | 8788.85 | 20-FEB-16:00 | 0.00 | 20-FEB-16:30 | 2469.09 | 20-FEB-16:00 | 0.00 | 01-FEB-00:10 |
March | 0.141218E+10 | 0.400527E+09 | 97.43 | 0.141218E+10 | 11.47 | 0.00 | 0.29 | 14-MAR-16:20 | 0.00 | 01-MAR-00:10 | 10502.40 | 14-MAR-16:20 | 10502.40 | 14-MAR-16:20 | 0.01 | 11-MAR-15:30 | 2983.89 | 21-MAR-16:10 | 0.00 | 01-MAR-00:10 |
April | 0.107325E+11 | 0.314793E+10 | 315.09 | 0.107122E+11 | 20320450.24 | 0.00 | 1.00 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 47216.12 | 29-APR-08:62 | 43666.69 | 29-APR-08:62 | 3549.43 | 29-APR-08:62 | 10254.13 | 29-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.205702E+11 | 0.614675E+10 | 444.22 | 0.200639E+11 | 0.506347E+09 | 0.00 | 1.00 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 | 49408.54 | 25-MAY-08:62 | 46993.16 | 19-MAY-08:61 | 16036.88 | 25-MAY-08:62 | 11282.60 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.285173E+11 | 0.892570E+10 | 466.20 | 0.276173E+11 | 0.899985E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 49975.56 | 30-JUN-08:61 | 48039.70 | 09-JUN-08:61 | 18411.18 | 29-JUN-08:61 | 11697.23 | 07-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.338994E+11 | 0.997465E+10 | 485.78 | 0.285681E+11 | 0.533133E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 54010.70 | 19-JUL-08:61 | 47488.47 | 03-JUL-08:61 | 25775.06 | 17-JUL-08:03 | 11891.01 | 26-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.296562E+11 | 0.875532E+10 | 472.18 | 0.265657E+11 | 0.309052E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 52989.08 | 02-AUG-08:61 | 47670.63 | 26-AUG-08:61 | 22258.94 | 14-AUG-08:03 | 11760.97 | 03-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.248611E+11 | 0.712779E+10 | 441.94 | 0.219719E+11 | 0.288926E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 52061.67 | 22-SEP-08:61 | 46738.82 | 12-SEP-08:62 | 22044.39 | 14-SEP-08:03 | 11454.67 | 15-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.112369E+11 | 0.315384E+10 | 304.73 | 0.102093E+11 | 0.102763E+10 | 0.00 | 1.00 | 02-OCT-08:61 | 0.00 | 01-OCT-00:10 | 50928.26 | 04-OCT-08:61 | 40797.43 | 19-OCT-08:62 | 19307.10 | 04-OCT-08:03 | 11072.55 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.891627E+09 | 0.247935E+09 | 60.72 | 0.886329E+09 | 5298242.87 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 45825.06 | 10-NOV-09:02 | 42926.26 | 10-NOV-09:02 | 2898.81 | 10-NOV-09:02 | 9880.02 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 2990.76 | 859.31 | 2.50 | 2990.76 | -0.0 | 0.00 | 0.00 | 09-DEC-19:40 | 0.00 | 01-DEC-00:10 | 2.20 | 09-DEC-19:40 | 2.20 | 09-DEC-19:40 | 0.00 | 07-DEC-19:00 | 0.63 | 09-DEC-19:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.162291E+12 | 0.480255E+11 | 3140.08 | 0.148521E+12 | 0.137707E+11 | 0.00 | ||||||||||||||
Minimum of Months | 2990.76 | 859.31 | 2.50 | 2990.76 | -0.0 | 0.00 | 0.00 | 0.00 | 2.20 | 2.20 | 0.00 | 0.63 | 0.00 | |||||||
Maximum of Months | 0.338994E+11 | 0.997465E+10 | 485.78 | 0.285681E+11 | 0.533133E+10 | 0.00 | 1.00 | 0.00 | 54010.70 | 48039.70 | 25775.06 | 11891.01 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 31293170.61 | 8225291.55 | 13.28 | 31210261.92 | 82908.69 | 0.00 | 1.00 | 03-JAN-21:10 | 0.00 | 01-JAN-00:10 | 23497.57 | 03-JAN-21:10 | 23497.57 | 03-JAN-21:10 | 134.23 | 15-JAN-19:00 | 4974.84 | 03-JAN-21:10 | 0.00 | 01-JAN-00:10 |
February | 0.417298E+09 | 0.112394E+09 | 59.98 | 0.417282E+09 | 15505.02 | 0.00 | 1.00 | 12-FEB-18:01 | 0.00 | 01-FEB-00:10 | 23497.57 | 19-FEB-18:35 | 23497.57 | 12-FEB-18:01 | 25.84 | 13-FEB-24:00 | 4974.84 | 12-FEB-18:01 | 0.00 | 01-FEB-00:10 |
March | 0.104834E+10 | 0.284811E+09 | 113.84 | 0.104825E+10 | 88744.04 | 0.00 | 1.00 | 12-MAR-17:01 | 0.00 | 01-MAR-00:10 | 23497.57 | 12-MAR-17:01 | 23497.57 | 12-MAR-17:01 | 147.91 | 10-MAR-24:00 | 5070.48 | 26-MAR-17:01 | 0.00 | 01-MAR-00:10 |
April | 0.630658E+10 | 0.175920E+10 | 303.73 | 0.629095E+10 | 15636126.28 | 0.00 | 1.00 | 01-APR-21:01 | 0.00 | 01-APR-00:10 | 24384.66 | 18-APR-20:59 | 23870.91 | 29-APR-20:40 | 2428.30 | 18-APR-21:05 | 5301.38 | 29-APR-20:17 | 0.00 | 01-APR-00:10 |
May | 0.110508E+11 | 0.318836E+10 | 425.54 | 0.107447E+11 | 0.306113E+09 | 0.00 | 1.00 | 02-MAY-20:01 | 0.00 | 01-MAY-00:10 | 25450.56 | 27-MAY-21:00 | 24021.70 | 30-MAY-08:61 | 8073.57 | 25-MAY-08:62 | 5711.71 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.144043E+11 | 0.441321E+10 | 460.66 | 0.139257E+11 | 0.478612E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 25611.94 | 30-JUN-08:61 | 24698.09 | 09-JUN-08:61 | 9030.06 | 29-JUN-08:61 | 5919.63 | 07-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.168921E+11 | 0.488222E+10 | 481.61 | 0.143271E+11 | 0.256491E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 27150.19 | 19-JUL-08:61 | 24622.75 | 01-JUL-08:61 | 14815.31 | 18-JUL-22:50 | 5998.82 | 26-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.150360E+11 | 0.432933E+10 | 460.04 | 0.134262E+11 | 0.160986E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 26927.17 | 03-AUG-08:61 | 24527.13 | 26-AUG-08:61 | 11606.43 | 01-AUG-21:15 | 5937.46 | 03-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.133456E+11 | 0.367590E+10 | 406.90 | 0.117761E+11 | 0.156949E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 26646.27 | 22-SEP-08:61 | 24044.79 | 12-SEP-08:62 | 13480.14 | 23-SEP-18:01 | 5759.11 | 15-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.665529E+10 | 0.177024E+10 | 292.10 | 0.602036E+10 | 0.634927E+09 | 0.00 | 1.00 | 02-OCT-08:61 | 0.00 | 01-OCT-00:10 | 26408.87 | 03-OCT-20:01 | 23633.44 | 22-OCT-18:26 | 11624.80 | 03-OCT-21:51 | 5668.34 | 03-OCT-20:01 | 0.00 | 01-OCT-00:10 |
November | 0.623290E+09 | 0.167462E+09 | 73.88 | 0.619602E+09 | 3688139.00 | 0.00 | 1.00 | 08-NOV-21:01 | 0.00 | 01-NOV-00:10 | 23562.48 | 10-NOV-09:02 | 23497.57 | 09-NOV-21:20 | 1326.49 | 10-NOV-09:02 | 4991.60 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 11048367.58 | 3067905.98 | 10.00 | 11035340.13 | 13027.45 | 0.00 | 0.10 | 16-DEC-19:20 | 0.00 | 01-DEC-00:10 | 1857.69 | 16-DEC-19:20 | 1857.69 | 16-DEC-19:20 | 18.24 | 25-DEC-22:30 | 510.94 | 16-DEC-19:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.858219E+11 | 0.245944E+11 | 3101.57 | 0.786384E+11 | 0.718345E+10 | 0.00 | ||||||||||||||
Minimum of Months | 11048367.58 | 3067905.98 | 10.00 | 11035340.13 | 13027.45 | 0.00 | 0.10 | 0.00 | 1857.69 | 1857.69 | 18.24 | 510.94 | 0.00 | |||||||
Maximum of Months | 0.168921E+11 | 0.488222E+10 | 481.61 | 0.143271E+11 | 0.256491E+10 | 0.00 | 1.00 | 0.00 | 27150.19 | 24698.09 | 14815.31 | 5998.82 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 3183653.42 | 892302.47 | 9.92 | 3183653.42 | -0.0 | 0.00 | 0.05 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 818.54 | 03-JAN-15:00 | 818.54 | 03-JAN-15:00 | 0.00 | 03-JAN-14:50 | 228.45 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.271672E+09 | 75271614.57 | 49.00 | 0.271672E+09 | 0.00 | 0.00 | 0.24 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4471.98 | 20-FEB-15:00 | 4471.98 | 20-FEB-15:00 | 0.00 | 21-FEB-15:20 | 1236.01 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.790063E+09 | 0.219448E+09 | 91.75 | 0.790063E+09 | 2.59 | 0.00 | 0.31 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5822.24 | 22-MAR-13:00 | 5822.24 | 22-MAR-13:00 | 0.01 | 11-MAR-08:65 | 1633.96 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.438752E+10 | 0.126367E+10 | 235.04 | 0.437861E+10 | 8914745.59 | 0.00 | 1.00 | 20-APR-07:02 | 0.00 | 01-APR-00:10 | 24138.64 | 29-APR-07:02 | 23802.22 | 20-APR-07:02 | 1793.81 | 29-APR-07:02 | 5124.60 | 29-APR-07:02 | 0.00 | 01-APR-00:10 |
May | 0.837742E+10 | 0.245758E+10 | 323.90 | 0.817640E+10 | 0.201019E+09 | 0.00 | 1.00 | 09-MAY-07:01 | 0.00 | 01-MAY-00:10 | 25855.03 | 28-MAY-08:61 | 24194.96 | 31-MAY-07:01 | 8391.38 | 25-MAY-07:02 | 5591.63 | 30-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.114579E+11 | 0.352660E+10 | 336.87 | 0.110913E+11 | 0.366610E+09 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 25952.08 | 04-JUN-08:61 | 24802.83 | 05-JUN-07:01 | 9223.21 | 28-JUN-07:03 | 5838.46 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.133541E+11 | 0.385659E+10 | 345.39 | 0.112314E+11 | 0.212269E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 27605.14 | 21-JUL-07:01 | 24773.08 | 03-JUL-07:01 | 15644.64 | 19-JUL-07:03 | 6049.81 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.118476E+11 | 0.342261E+10 | 347.60 | 0.105321E+11 | 0.131555E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 27438.34 | 03-AUG-07:01 | 24371.17 | 27-AUG-08:61 | 11655.35 | 03-AUG-07:03 | 5940.49 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.103218E+11 | 0.291969E+10 | 323.18 | 0.914863E+10 | 0.117321E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 26889.20 | 23-SEP-07:01 | 23771.17 | 11-SEP-07:01 | 12068.05 | 14-SEP-07:03 | 5753.27 | 10-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.487871E+10 | 0.134337E+10 | 244.10 | 0.446020E+10 | 0.418512E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 26198.74 | 04-OCT-07:01 | 23802.22 | 01-OCT-08:62 | 10847.84 | 09-OCT-08:62 | 5549.95 | 04-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.480363E+09 | 0.131220E+09 | 59.99 | 0.477083E+09 | 3280390.14 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 23802.22 | 10-NOV-08:62 | 22388.66 | 10-NOV-08:62 | 1413.56 | 10-NOV-08:62 | 5039.34 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 620.66 | 175.21 | 3.50 | 620.66 | 0.00 | 0.00 | 0.00 | 17-DEC-16:20 | 0.00 | 01-DEC-00:10 | 0.11 | 17-DEC-16:20 | 0.11 | 17-DEC-16:20 | 0.00 | 11-DEC-12:00 | 0.03 | 17-DEC-16:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.661704E+11 | 0.192169E+11 | 2370.24 | 0.605606E+11 | 0.560979E+10 | 0.00 | ||||||||||||||
Minimum of Months | 620.66 | 175.21 | 3.50 | 620.66 | -0.0 | 0.00 | 0.00 | 0.00 | 0.11 | 0.11 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.133541E+11 | 0.385659E+10 | 347.60 | 0.112314E+11 | 0.212269E+10 | 0.00 | 1.00 | 0.00 | 27605.14 | 24802.83 | 15644.64 | 6049.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 1543410.10 | 433247.77 | 7.25 | 1543410.10 | -0.0 | 0.00 | 0.03 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 597.22 | 03-JAN-15:00 | 597.22 | 03-JAN-15:00 | 0.00 | 03-JAN-15:20 | 167.18 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.246150E+09 | 68356121.14 | 46.50 | 0.246150E+09 | 0.00 | 0.00 | 0.23 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 4224.76 | 20-FEB-15:00 | 4224.76 | 20-FEB-15:00 | 0.00 | 20-FEB-14:40 | 1171.13 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.748785E+09 | 0.208280E+09 | 89.83 | 0.748785E+09 | -0.0 | 0.00 | 0.30 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5676.75 | 22-MAR-13:00 | 5676.75 | 22-MAR-13:00 | 0.00 | 14-MAR-16:40 | 1595.46 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.435391E+10 | 0.125417E+10 | 234.70 | 0.434507E+10 | 8843352.23 | 0.00 | 1.00 | 20-APR-07:02 | 0.00 | 01-APR-00:10 | 23993.48 | 29-APR-07:02 | 23658.61 | 20-APR-07:02 | 1777.46 | 29-APR-07:02 | 5093.80 | 29-APR-07:02 | 0.00 | 01-APR-00:10 |
May | 0.840012E+10 | 0.246194E+10 | 324.16 | 0.819797E+10 | 0.202147E+09 | 0.00 | 1.00 | 09-MAY-07:01 | 0.00 | 01-MAY-00:10 | 25702.21 | 28-MAY-08:61 | 24047.55 | 31-MAY-07:01 | 8333.15 | 25-MAY-07:02 | 5555.58 | 30-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.115147E+11 | 0.353890E+10 | 337.01 | 0.111456E+11 | 0.369123E+09 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 25792.73 | 04-JUN-08:61 | 24644.96 | 05-JUN-07:01 | 9164.57 | 28-JUN-07:03 | 5803.80 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.134201E+11 | 0.387013E+10 | 345.75 | 0.112899E+11 | 0.213027E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 27435.11 | 21-JUL-07:01 | 24624.26 | 03-JUL-07:01 | 15551.16 | 19-JUL-07:03 | 6009.23 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.119129E+11 | 0.343669E+10 | 347.75 | 0.105898E+11 | 0.132312E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 27279.10 | 03-AUG-07:01 | 24220.38 | 27-AUG-08:61 | 11606.78 | 03-AUG-07:03 | 5904.78 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.103710E+11 | 0.292992E+10 | 323.79 | 0.919189E+10 | 0.117914E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 26735.01 | 23-SEP-07:01 | 23645.50 | 11-SEP-07:01 | 12005.49 | 14-SEP-07:03 | 5718.59 | 10-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.487139E+10 | 0.134079E+10 | 243.77 | 0.445378E+10 | 0.417610E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 26043.16 | 04-OCT-07:01 | 23658.61 | 01-OCT-08:62 | 10783.14 | 09-OCT-08:62 | 5516.87 | 04-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.462881E+09 | 0.126508E+09 | 59.57 | 0.459702E+09 | 3179141.48 | 0.00 | 1.00 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 23658.61 | 10-NOV-08:62 | 22250.68 | 10-NOV-08:62 | 1407.93 | 10-NOV-08:62 | 5008.94 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 524.39 | 148.03 | 3.67 | 524.39 | 0.00 | 0.00 | 0.00 | 20-DEC-15:40 | 0.00 | 01-DEC-00:10 | 0.11 | 20-DEC-15:40 | 0.11 | 20-DEC-15:40 | 0.00 | 17-DEC-16:10 | 0.03 | 20-DEC-15:40 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.663035E+11 | 0.192361E+11 | 2363.74 | 0.606701E+11 | 0.563343E+10 | 0.00 | ||||||||||||||
Minimum of Months | 524.39 | 148.03 | 3.67 | 524.39 | -0.0 | 0.00 | 0.00 | 0.00 | 0.11 | 0.11 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.134201E+11 | 0.387013E+10 | 347.75 | 0.112899E+11 | 0.213027E+10 | 0.00 | 1.00 | 0.00 | 27435.11 | 24644.96 | 15551.16 | 6009.23 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 331875.59 | 93400.95 | 4.67 | 331875.59 | -0.0 | 0.00 | 0.02 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 | 277.95 | 03-JAN-15:00 | 277.95 | 03-JAN-15:00 | 0.00 | 03-JAN-12:40 | 78.16 | 03-JAN-15:00 | 0.00 | 01-JAN-00:10 |
February | 0.208276E+09 | 58070329.90 | 42.92 | 0.208276E+09 | -0.0 | 0.00 | 0.21 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 | 3900.51 | 20-FEB-15:00 | 3900.51 | 20-FEB-15:00 | 0.00 | 21-FEB-15:10 | 1086.15 | 20-FEB-15:00 | 0.00 | 01-FEB-00:10 |
March | 0.672653E+09 | 0.187748E+09 | 87.33 | 0.672653E+09 | 0.52 | 0.00 | 0.29 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 5407.25 | 22-MAR-13:00 | 5407.25 | 22-MAR-13:00 | 0.00 | 11-MAR-16:10 | 1525.51 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.419417E+10 | 0.121223E+10 | 229.79 | 0.418580E+10 | 8367203.15 | 0.00 | 1.00 | 20-APR-07:02 | 0.00 | 01-APR-00:10 | 24056.39 | 29-APR-07:02 | 23729.33 | 20-APR-07:02 | 1824.72 | 29-APR-07:02 | 5106.85 | 29-APR-07:02 | 0.00 | 01-APR-00:10 |
May | 0.821181E+10 | 0.241326E+10 | 323.40 | 0.801369E+10 | 0.198122E+09 | 0.00 | 1.00 | 09-MAY-07:01 | 0.00 | 01-MAY-00:10 | 25773.27 | 28-MAY-08:61 | 24123.22 | 31-MAY-07:01 | 8399.44 | 25-MAY-07:02 | 5574.41 | 30-MAY-07:01 | 0.00 | 01-MAY-00:10 |
June | 0.113471E+11 | 0.349543E+10 | 336.56 | 0.109851E+11 | 0.361956E+09 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 25874.22 | 04-JUN-08:61 | 24713.70 | 05-JUN-07:01 | 9183.47 | 29-JUN-07:01 | 5820.55 | 18-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.132523E+11 | 0.382936E+10 | 345.20 | 0.111416E+11 | 0.211061E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:05 | 27535.77 | 21-JUL-07:01 | 24696.74 | 03-JUL-07:01 | 15584.12 | 19-JUL-07:03 | 6026.73 | 02-JUL-08:61 | 0.00 | 01-JUL-00:05 |
August | 0.117387E+11 | 0.339364E+10 | 346.96 | 0.104345E+11 | 0.130422E+10 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 27343.05 | 03-AUG-07:01 | 24298.40 | 27-AUG-08:61 | 11619.49 | 14-AUG-07:03 | 5922.11 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.101975E+11 | 0.288735E+10 | 323.13 | 0.903465E+10 | 0.116290E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:05 | 26796.58 | 23-SEP-07:01 | 23694.01 | 11-SEP-07:01 | 12012.77 | 14-SEP-07:03 | 5735.68 | 10-SEP-08:61 | 0.00 | 01-SEP-00:05 |
October | 0.472788E+10 | 0.130464E+10 | 239.13 | 0.432231E+10 | 0.405571E+09 | 0.00 | 1.00 | 01-OCT-08:62 | 0.00 | 01-OCT-00:10 | 26116.11 | 04-OCT-07:01 | 23729.33 | 01-OCT-08:62 | 10851.00 | 09-OCT-08:62 | 5532.57 | 04-OCT-07:01 | 0.00 | 01-OCT-00:10 |
November | 0.421431E+09 | 0.115452E+09 | 54.66 | 0.418636E+09 | 2794768.02 | 0.00 | 0.94 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 | 21809.64 | 10-NOV-08:62 | 20471.61 | 10-NOV-08:62 | 1338.03 | 10-NOV-08:62 | 4712.80 | 10-NOV-08:62 | 0.00 | 01-NOV-00:10 |
December | 1348.52 | 380.67 | 5.17 | 1348.52 | -0.0 | 0.00 | 0.00 | 15-DEC-15:20 | 0.00 | 01-DEC-00:10 | 0.15 | 15-DEC-15:20 | 0.15 | 15-DEC-15:20 | 0.00 | 15-DEC-15:20 | 0.04 | 15-DEC-15:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.649722E+11 | 0.188973E+11 | 2338.91 | 0.594176E+11 | 0.555453E+10 | 0.00 | ||||||||||||||
Minimum of Months | 1348.52 | 380.67 | 4.67 | 1348.52 | -0.0 | 0.00 | 0.00 | 0.00 | 0.15 | 0.15 | 0.00 | 0.04 | 0.00 | |||||||
Maximum of Months | 0.132523E+11 | 0.382936E+10 | 346.96 | 0.111416E+11 | 0.211061E+10 | 0.00 | 1.00 | 0.00 | 27535.77 | 24713.70 | 15584.12 | 6026.73 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 197.59 | 56.77 | 0.67 | 197.59 | 0.00 | 0.00 | 0.00 | 03-JAN-12:30 | 0.00 | 01-JAN-00:10 | 0.14 | 03-JAN-12:30 | 0.14 | 03-JAN-12:30 | 0.00 | 03-JAN-12:30 | 0.04 | 03-JAN-12:30 | 0.00 | 01-JAN-00:10 |
February | 0.310429E+09 | 88421881.93 | 32.17 | 0.310429E+09 | -0.0 | 0.00 | 0.20 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 6691.60 | 20-FEB-15:30 | 6691.60 | 20-FEB-15:30 | 0.00 | 20-FEB-15:10 | 1901.26 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.105229E+10 | 0.300178E+09 | 77.42 | 0.105229E+10 | -0.0 | 0.00 | 0.28 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 9366.73 | 22-MAR-13:00 | 9366.73 | 22-MAR-13:00 | 0.00 | 22-MAR-14:30 | 2696.97 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.732281E+10 | 0.216379E+10 | 223.51 | 0.730593E+10 | 16880598.71 | 0.00 | 1.00 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 43919.50 | 29-APR-08:62 | 42243.84 | 30-APR-09:02 | 2674.73 | 29-APR-08:62 | 9535.05 | 29-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.145520E+11 | 0.436827E+10 | 317.83 | 0.141922E+11 | 0.359818E+09 | 0.00 | 1.00 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 | 46498.80 | 28-MAY-09:01 | 43512.28 | 31-MAY-08:61 | 14431.81 | 25-MAY-08:62 | 10564.52 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.203439E+11 | 0.641003E+10 | 333.85 | 0.196831E+11 | 0.660796E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 46631.93 | 30-JUN-08:61 | 44852.92 | 21-JUN-08:61 | 16854.04 | 29-JUN-08:61 | 10965.89 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.235639E+11 | 0.694217E+10 | 338.00 | 0.197454E+11 | 0.381850E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 49434.36 | 19-JUL-08:61 | 44263.90 | 03-JUL-08:61 | 23393.54 | 17-JUL-08:03 | 11227.45 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.210064E+11 | 0.619101E+10 | 339.29 | 0.186109E+11 | 0.239555E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 48921.55 | 03-AUG-08:61 | 44397.02 | 07-AUG-08:61 | 20429.31 | 14-AUG-08:03 | 11054.62 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.181578E+11 | 0.523826E+10 | 314.19 | 0.161119E+11 | 0.204588E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 48411.29 | 22-SEP-08:61 | 43525.54 | 12-SEP-08:62 | 19806.77 | 14-SEP-08:03 | 10717.38 | 10-SEP-09:01 | 0.00 | 01-SEP-00:05 |
October | 0.829508E+10 | 0.233300E+10 | 228.94 | 0.752719E+10 | 0.767882E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 47532.59 | 04-OCT-08:61 | 43327.99 | 01-OCT-09:02 | 19682.10 | 09-OCT-09:02 | 10329.73 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.672643E+09 | 0.187750E+09 | 47.55 | 0.668089E+09 | 4554092.97 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 42760.93 | 10-NOV-09:02 | 40080.52 | 10-NOV-09:02 | 2680.42 | 10-NOV-09:02 | 9217.69 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 57.41 | 16.50 | 0.17 | 57.41 | 0.00 | 0.00 | 0.00 | 08-DEC-15:10 | 0.00 | 01-DEC-00:10 | 0.10 | 08-DEC-15:10 | 0.10 | 08-DEC-15:10 | 0.00 | 01-DEC-00:10 | 0.03 | 08-DEC-15:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.115277E+12 | 0.342229E+11 | 2253.58 | 0.105207E+12 | 0.100699E+11 | 0.00 | ||||||||||||||
Minimum of Months | 57.41 | 16.50 | 0.17 | 57.41 | -0.0 | 0.00 | 0.00 | 0.00 | 0.10 | 0.10 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.235639E+11 | 0.694217E+10 | 339.29 | 0.197454E+11 | 0.381850E+10 | 0.00 | 1.00 | 0.00 | 49434.36 | 44852.92 | 23393.54 | 11227.45 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 364.47 | 102.89 | 1.33 | 364.47 | 0.00 | 0.00 | 0.00 | 03-JAN-12:40 | 0.00 | 01-JAN-00:10 | 0.18 | 03-JAN-12:40 | 0.18 | 03-JAN-12:40 | 0.00 | 02-JAN-15:00 | 0.05 | 03-JAN-12:40 | 0.00 | 01-JAN-00:10 |
February | 0.154932E+09 | 43377895.36 | 33.92 | 0.154932E+09 | 0.00 | 0.00 | 0.20 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 3434.47 | 20-FEB-15:30 | 3434.47 | 20-FEB-15:30 | 0.00 | 21-FEB-17:00 | 959.06 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.533288E+09 | 0.149507E+09 | 75.92 | 0.533288E+09 | 0.00 | 0.00 | 0.28 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4804.25 | 22-MAR-13:00 | 4804.25 | 22-MAR-13:00 | 0.00 | 16-MAR-15:30 | 1359.78 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.379407E+10 | 0.110136E+10 | 224.41 | 0.378615E+10 | 7917982.26 | 0.00 | 1.00 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 22703.38 | 29-APR-08:62 | 21903.75 | 30-APR-09:02 | 1321.26 | 29-APR-08:62 | 4842.56 | 29-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.754910E+10 | 0.222612E+10 | 318.39 | 0.736792E+10 | 0.181184E+09 | 0.00 | 1.00 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 | 24037.26 | 28-MAY-09:01 | 22523.21 | 31-MAY-08:61 | 7422.34 | 25-MAY-08:62 | 5371.11 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.105394E+11 | 0.326178E+10 | 332.98 | 0.102082E+11 | 0.331241E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 24104.97 | 30-JUN-08:61 | 23185.81 | 21-JUN-08:61 | 8682.12 | 29-JUN-08:61 | 5570.55 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.121985E+11 | 0.353071E+10 | 336.61 | 0.102550E+11 | 0.194350E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 25544.24 | 19-JUL-08:61 | 22890.08 | 03-JUL-08:61 | 12054.56 | 17-JUL-08:03 | 5702.46 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.108832E+11 | 0.315086E+10 | 338.89 | 0.966957E+10 | 0.121359E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25277.74 | 03-AUG-08:61 | 23047.71 | 07-AUG-08:61 | 10512.69 | 14-AUG-08:03 | 5616.90 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.941458E+10 | 0.266794E+10 | 314.53 | 0.837638E+10 | 0.103820E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 25012.95 | 22-SEP-08:61 | 22504.78 | 12-SEP-08:62 | 10217.96 | 14-SEP-08:03 | 5443.95 | 10-SEP-09:01 | 0.00 | 01-SEP-00:05 |
October | 0.430665E+10 | 0.118973E+10 | 227.66 | 0.391730E+10 | 0.389340E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 24572.72 | 04-OCT-08:61 | 22404.40 | 01-OCT-09:02 | 10148.75 | 09-OCT-09:02 | 5246.22 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.348406E+09 | 95548479.97 | 47.47 | 0.346282E+09 | 2124002.88 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 22106.40 | 10-NOV-09:02 | 20782.65 | 10-NOV-09:02 | 1323.76 | 10-NOV-09:02 | 4681.88 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 37.29 | 10.53 | 0.33 | 37.29 | 0.00 | 0.00 | 0.00 | 23-DEC-14:20 | 0.00 | 01-DEC-00:10 | 0.06 | 23-DEC-14:20 | 0.06 | 23-DEC-14:20 | 0.00 | 10-DEC-14:00 | 0.02 | 23-DEC-14:20 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.597221E+11 | 0.174169E+11 | 2252.45 | 0.546150E+11 | 0.510709E+10 | 0.00 | ||||||||||||||
Minimum of Months | 37.29 | 10.53 | 0.33 | 37.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.06 | 0.06 | 0.00 | 0.02 | 0.00 | |||||||
Maximum of Months | 0.121985E+11 | 0.353071E+10 | 338.89 | 0.102550E+11 | 0.194350E+10 | 0.00 | 1.00 | 0.00 | 25544.24 | 23185.81 | 12054.56 | 5702.46 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 829.91 | 234.27 | 1.50 | 829.91 | -0.0 | 0.00 | 0.00 | 13-JAN-18:30 | 0.00 | 01-JAN-00:10 | 0.75 | 13-JAN-18:30 | 0.75 | 13-JAN-18:30 | 0.00 | 01-JAN-00:10 | 0.21 | 13-JAN-18:30 | 0.00 | 01-JAN-00:10 |
February | 0.145029E+09 | 40659320.88 | 32.92 | 0.145029E+09 | 0.00 | 0.00 | 0.19 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 3317.89 | 20-FEB-15:30 | 3317.89 | 20-FEB-15:30 | 0.00 | 19-FEB-15:20 | 927.90 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.506669E+09 | 0.142236E+09 | 75.17 | 0.506669E+09 | 0.13 | 0.00 | 0.27 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4689.62 | 22-MAR-13:00 | 4689.62 | 22-MAR-13:00 | 0.00 | 11-MAR-17:00 | 1329.17 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.373429E+10 | 0.108505E+10 | 223.60 | 0.372649E+10 | 7803735.23 | 0.00 | 1.00 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 22612.23 | 29-APR-08:62 | 21798.23 | 30-APR-09:02 | 1333.83 | 29-APR-08:62 | 4823.07 | 29-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.748002E+10 | 0.220694E+10 | 317.94 | 0.730003E+10 | 0.179993E+09 | 0.00 | 1.00 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 | 23941.46 | 28-MAY-09:01 | 22444.52 | 30-MAY-08:61 | 7411.30 | 25-MAY-08:62 | 5349.92 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.104734E+11 | 0.324237E+10 | 332.64 | 0.101447E+11 | 0.328754E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 24009.31 | 30-JUN-08:61 | 23093.50 | 21-JUN-08:61 | 8663.33 | 29-JUN-08:61 | 5548.77 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.121304E+11 | 0.351163E+10 | 336.42 | 0.101952E+11 | 0.193514E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 25441.79 | 19-JUL-08:61 | 22800.97 | 03-JUL-08:61 | 12007.90 | 17-JUL-08:03 | 5680.49 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.108197E+11 | 0.313316E+10 | 338.62 | 0.961278E+10 | 0.120692E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25173.53 | 03-AUG-08:61 | 22951.61 | 07-AUG-08:61 | 10470.38 | 14-AUG-08:03 | 5594.92 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.935403E+10 | 0.265147E+10 | 314.46 | 0.832034E+10 | 0.103370E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 24910.88 | 22-SEP-08:61 | 22414.77 | 12-SEP-08:62 | 10189.41 | 14-SEP-08:03 | 5422.94 | 10-SEP-09:01 | 0.00 | 01-SEP-00:05 |
October | 0.425836E+10 | 0.117701E+10 | 226.22 | 0.387263E+10 | 0.385733E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 24475.55 | 04-OCT-08:61 | 22313.42 | 01-OCT-09:02 | 10125.03 | 09-OCT-09:02 | 5225.64 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.335751E+09 | 92151426.97 | 46.44 | 0.333695E+09 | 2055528.76 | 0.00 | 1.00 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 22017.48 | 10-NOV-09:02 | 20681.99 | 10-NOV-09:02 | 1335.49 | 10-NOV-09:02 | 4662.91 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 118.50 | 33.45 | 0.67 | 118.50 | 0.00 | 0.00 | 0.00 | 23-DEC-14:30 | 0.00 | 01-DEC-00:10 | 0.10 | 23-DEC-14:30 | 0.10 | 23-DEC-14:30 | 0.00 | 10-DEC-13:30 | 0.03 | 23-DEC-14:30 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.592377E+11 | 0.172827E+11 | 2246.59 | 0.541576E+11 | 0.508010E+10 | 0.00 | ||||||||||||||
Minimum of Months | 118.50 | 33.45 | 0.67 | 118.50 | -0.0 | 0.00 | 0.00 | 0.00 | 0.10 | 0.10 | 0.00 | 0.03 | 0.00 | |||||||
Maximum of Months | 0.121304E+11 | 0.351163E+10 | 338.62 | 0.101952E+11 | 0.193514E+10 | 0.00 | 1.00 | 0.00 | 25441.79 | 23093.50 | 12007.90 | 5680.49 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 577.96 | 163.15 | 1.50 | 577.96 | 0.00 | 0.00 | 0.00 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 | 0.27 | 03-JAN-13:10 | 0.27 | 03-JAN-13:10 | 0.00 | 03-JAN-16:50 | 0.07 | 03-JAN-13:10 | 0.00 | 01-JAN-00:10 |
February | 0.122290E+09 | 34409884.37 | 28.58 | 0.122290E+09 | 0.00 | 0.00 | 0.18 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 | 3057.82 | 20-FEB-15:30 | 3057.82 | 20-FEB-15:30 | 0.00 | 22-FEB-14:40 | 858.45 | 20-FEB-15:30 | 0.00 | 01-FEB-00:10 |
March | 0.439201E+09 | 0.123783E+09 | 71.42 | 0.439201E+09 | 0.00 | 0.00 | 0.25 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4395.04 | 22-MAR-13:00 | 4395.04 | 22-MAR-13:00 | 0.00 | 22-MAR-13:10 | 1251.05 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.359393E+10 | 0.104752E+10 | 219.76 | 0.358659E+10 | 7340485.23 | 0.00 | 0.97 | 29-APR-08:62 | 0.00 | 01-APR-00:10 | 21797.11 | 29-APR-08:62 | 20779.10 | 30-APR-09:02 | 1320.34 | 29-APR-08:62 | 4691.68 | 29-APR-08:62 | 0.00 | 01-APR-00:10 |
May | 0.735884E+10 | 0.217501E+10 | 316.65 | 0.718175E+10 | 0.177087E+09 | 0.00 | 1.00 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 | 23952.92 | 28-MAY-09:01 | 22528.57 | 30-MAY-08:61 | 7459.05 | 25-MAY-08:62 | 5353.22 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.104198E+11 | 0.322845E+10 | 331.49 | 0.100961E+11 | 0.323721E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 24021.03 | 30-JUN-08:61 | 23094.32 | 21-JUN-08:61 | 8703.54 | 29-JUN-08:61 | 5560.74 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.121007E+11 | 0.350474E+10 | 335.64 | 0.101735E+11 | 0.192725E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 25449.72 | 19-JUL-08:61 | 22817.38 | 03-JUL-08:61 | 12012.15 | 17-JUL-08:03 | 5684.79 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.107992E+11 | 0.312837E+10 | 338.13 | 0.959999E+10 | 0.119924E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 25184.04 | 03-AUG-08:61 | 22967.10 | 07-AUG-08:61 | 10471.14 | 14-AUG-08:03 | 5598.96 | 27-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.932065E+10 | 0.264328E+10 | 314.28 | 0.829082E+10 | 0.102983E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 24922.52 | 22-SEP-08:61 | 22426.14 | 12-SEP-08:62 | 10212.90 | 14-SEP-08:03 | 5427.07 | 10-SEP-09:01 | 0.00 | 01-SEP-00:05 |
October | 0.417163E+10 | 0.115483E+10 | 225.17 | 0.379405E+10 | 0.377581E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 24489.22 | 04-OCT-08:61 | 22321.15 | 01-OCT-09:02 | 10174.05 | 09-OCT-09:02 | 5228.99 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.304833E+09 | 83853365.95 | 42.77 | 0.302980E+09 | 1853495.06 | 0.00 | 0.99 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 21674.57 | 10-NOV-09:02 | 20326.15 | 10-NOV-09:02 | 1348.42 | 10-NOV-09:02 | 4608.15 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 1213.09 | 342.44 | 1.50 | 1213.09 | -0.0 | 0.00 | 0.00 | 23-DEC-16:00 | 0.00 | 01-DEC-00:10 | 1.65 | 23-DEC-16:00 | 1.65 | 23-DEC-16:00 | 0.00 | 10-DEC-14:40 | 0.47 | 23-DEC-16:00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.586311E+11 | 0.171242E+11 | 2226.89 | 0.535872E+11 | 0.504390E+10 | 0.00 | ||||||||||||||
Minimum of Months | 577.96 | 163.15 | 1.50 | 577.96 | -0.0 | 0.00 | 0.00 | 0.00 | 0.27 | 0.27 | 0.00 | 0.07 | 0.00 | |||||||
Maximum of Months | 0.121007E+11 | 0.350474E+10 | 338.13 | 0.101735E+11 | 0.192725E+10 | 0.00 | 1.00 | 0.00 | 25449.72 | 23094.32 | 12012.15 | 5684.79 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 2524.40 | 712.61 | 3.33 | 2524.40 | 0.00 | 0.00 | 0.00 | 03-JAN-17:00 | 0.00 | 01-JAN-00:10 | 0.49 | 03-JAN-17:00 | 0.49 | 03-JAN-17:00 | 0.00 | 03-JAN-14:50 | 0.14 | 03-JAN-17:00 | 0.00 | 01-JAN-00:10 |
February | 94974988.40 | 26890215.68 | 27.83 | 94974988.40 | -0.0 | 0.00 | 0.16 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 | 2907.22 | 20-FEB-15:20 | 2907.22 | 20-FEB-15:20 | 0.00 | 20-FEB-15:30 | 821.14 | 20-FEB-15:20 | 0.00 | 01-FEB-00:10 |
March | 0.373882E+09 | 0.106104E+09 | 67.17 | 0.373882E+09 | 0.00 | 0.00 | 0.23 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 | 4381.80 | 22-MAR-13:00 | 4381.80 | 22-MAR-13:00 | 0.00 | 22-MAR-12:10 | 1254.74 | 22-MAR-13:00 | 0.00 | 01-MAR-00:10 |
April | 0.375701E+10 | 0.109923E+10 | 217.83 | 0.374935E+10 | 7657946.41 | 0.00 | 0.94 | 30-APR-09:02 | 0.00 | 01-APR-00:10 | 22590.17 | 30-APR-09:02 | 21750.59 | 30-APR-09:02 | 1144.72 | 29-APR-08:62 | 4894.82 | 30-APR-09:02 | 0.00 | 01-APR-00:10 |
May | 0.797209E+10 | 0.236023E+10 | 315.92 | 0.777665E+10 | 0.195444E+09 | 0.00 | 1.00 | 09-MAY-08:61 | 0.00 | 01-MAY-00:10 | 26439.50 | 28-MAY-09:01 | 24651.04 | 19-MAY-08:61 | 7135.66 | 25-MAY-08:62 | 5860.70 | 31-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.115569E+11 | 0.357847E+10 | 332.63 | 0.111947E+11 | 0.362197E+09 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 26439.72 | 30-JUN-08:61 | 25428.61 | 09-JUN-08:61 | 9973.03 | 29-JUN-08:61 | 6108.28 | 18-JUN-09:01 | 0.00 | 01-JUN-00:10 |
July | 0.135401E+11 | 0.391970E+10 | 337.56 | 0.113980E+11 | 0.214215E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:05 | 28408.15 | 20-JUL-08:61 | 25155.14 | 03-JUL-08:61 | 13786.27 | 17-JUL-08:03 | 6266.54 | 02-JUL-09:01 | 0.00 | 01-JUL-00:05 |
August | 0.121777E+11 | 0.352006E+10 | 337.70 | 0.108370E+11 | 0.134067E+10 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 27778.43 | 03-AUG-08:61 | 25132.06 | 26-AUG-08:61 | 11964.16 | 14-AUG-08:03 | 6163.53 | 06-AUG-09:01 | 0.00 | 01-AUG-00:10 |
September | 0.105368E+11 | 0.298014E+10 | 314.84 | 0.937597E+10 | 0.116078E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:05 | 27583.67 | 22-SEP-08:61 | 24670.18 | 12-SEP-08:62 | 11559.11 | 14-SEP-08:03 | 5970.32 | 03-SEP-09:01 | 0.00 | 01-SEP-00:05 |
October | 0.449922E+10 | 0.124758E+10 | 220.28 | 0.409617E+10 | 0.403048E+09 | 0.00 | 1.00 | 01-OCT-09:02 | 0.00 | 01-OCT-00:10 | 26906.53 | 04-OCT-08:61 | 24559.81 | 01-OCT-09:02 | 10094.29 | 04-OCT-08:61 | 5754.18 | 05-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.286468E+09 | 79111062.89 | 37.44 | 0.284697E+09 | 1770978.75 | 0.00 | 0.72 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 | 15940.17 | 10-NOV-09:02 | 14807.17 | 10-NOV-09:02 | 1133.01 | 10-NOV-09:02 | 3691.56 | 10-NOV-09:02 | 0.00 | 01-NOV-00:10 |
December | 53.19 | 15.01 | 0.50 | 53.19 | -0.0 | 0.00 | 0.00 | 09-DEC-13:10 | 0.00 | 01-DEC-00:10 | 0.06 | 09-DEC-13:10 | 0.06 | 09-DEC-13:10 | 0.00 | 01-DEC-00:10 | 0.02 | 09-DEC-13:10 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.647951E+11 | 0.189175E+11 | 2213.02 | 0.591814E+11 | 0.561372E+10 | 0.00 | ||||||||||||||
Minimum of Months | 53.19 | 15.01 | 0.50 | 53.19 | -0.0 | 0.00 | 0.00 | 0.00 | 0.06 | 0.06 | 0.00 | 0.02 | 0.00 | |||||||
Maximum of Months | 0.135401E+11 | 0.391970E+10 | 337.70 | 0.113980E+11 | 0.214215E+10 | 0.00 | 1.00 | 0.00 | 28408.15 | 25428.61 | 13786.27 | 6266.54 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.43 | 70.90 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.99 | 63.52 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.81 | 56.71 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.15 | 35.52 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.37 | 21.09 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.26 | 10.73 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.23 | 8.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.51 | 12.82 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.91 | 24.69 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.75 | 39.59 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.39 | 63.32 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.92 | 76.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.07 | 40.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.37 | 8.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.39 | 76.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.43 | 70.90 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.99 | 63.52 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.81 | 56.71 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.15 | 35.52 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.37 | 21.09 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.26 | 10.73 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.23 | 8.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.51 | 12.82 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.91 | 24.69 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.75 | 39.59 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.39 | 63.32 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.92 | 76.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.07 | 40.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.37 | 8.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.39 | 76.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.43 | 70.90 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.99 | 63.52 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.81 | 56.71 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.15 | 35.52 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.37 | 21.09 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.26 | 10.73 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.23 | 8.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.51 | 12.82 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.91 | 24.69 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.75 | 39.59 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.39 | 63.32 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.92 | 76.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.07 | 40.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.37 | 8.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.39 | 76.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 136.43 | 70.90 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.99 | 63.52 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.81 | 56.71 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.15 | 35.52 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.37 | 21.09 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.26 | 10.73 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.23 | 8.84 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.51 | 12.82 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.91 | 24.69 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.75 | 39.59 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.39 | 63.32 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.92 | 76.48 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.07 | 40.23 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.37 | 8.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.39 | 76.48 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 164.38 | 84.29 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 155.41 | 75.54 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 129.99 | 67.51 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 98.80 | 42.44 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.08 | 25.34 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.36 | 12.93 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 82.68 | 10.63 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 98.73 | 15.39 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.28 | 29.55 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.22 | 47.22 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 175.01 | 75.40 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 164.89 | 91.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 127.47 | 47.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.08 | 10.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 175.01 | 91.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 164.38 | 84.29 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 155.41 | 75.54 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 129.99 | 67.51 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 98.80 | 42.44 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 77.08 | 25.34 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.36 | 12.93 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 82.68 | 10.63 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 98.73 | 15.39 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.28 | 29.55 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 163.22 | 47.22 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 175.01 | 75.40 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 164.89 | 91.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 127.47 | 47.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 77.08 | 10.63 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 175.01 | 91.00 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 134.15 | 75.64 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 126.69 | 67.65 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 105.85 | 59.67 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.42 | 36.57 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.23 | 21.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.59 | 10.88 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.63 | 8.90 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.86 | 12.79 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.02 | 24.43 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.37 | 39.88 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.07 | 65.45 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 134.67 | 81.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.23 | 41.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.23 | 8.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.07 | 81.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 134.15 | 75.64 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 126.69 | 67.65 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 105.85 | 59.67 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.42 | 36.57 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.23 | 21.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 68.59 | 10.88 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 69.63 | 8.90 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 82.86 | 12.79 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 117.02 | 24.43 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.37 | 39.88 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.07 | 65.45 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 134.67 | 81.12 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.23 | 41.91 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.23 | 8.90 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.07 | 81.12 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 118.27 | 89.61 | 28.67 | 161.71 | 89.86 | 0.00 | 0.00 | 0.00 |
February | 109.71 | 77.35 | 32.37 | 152.71 | 80.40 | 0.00 | 0.00 | 0.00 |
March | 89.16 | 51.41 | 37.75 | 127.70 | 70.99 | 0.00 | 0.00 | 0.00 |
April | 60.45 | 22.56 | 37.90 | 97.94 | 43.68 | 0.00 | 0.00 | 0.00 |
May | 42.72 | 5.98 | 36.74 | 76.91 | 25.74 | 0.00 | 0.00 | 0.00 |
June | 36.86 | 2.34 | 34.52 | 81.73 | 13.12 | 0.00 | 0.00 | 0.00 |
July | 37.57 | 3.48 | 34.09 | 83.15 | 10.71 | 0.00 | 0.00 | 0.00 |
August | 47.89 | 12.68 | 35.22 | 99.16 | 15.35 | 0.00 | 0.00 | 0.00 |
September | 74.76 | 38.84 | 35.92 | 140.44 | 29.24 | 0.00 | 0.00 | 0.00 |
October | 101.57 | 68.67 | 32.90 | 162.80 | 47.56 | 0.00 | 0.00 | 0.00 |
November | 122.24 | 93.19 | 29.05 | 173.49 | 77.89 | 0.00 | 0.00 | 0.00 |
December | 121.14 | 90.93 | 30.21 | 162.25 | 96.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 80.03 | 46.24 | 33.78 | 126.49 | 49.93 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.86 | 2.34 | 28.67 | 76.91 | 10.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 122.24 | 93.19 | 37.90 | 173.49 | 96.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 134.80 | 73.40 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 127.09 | 66.29 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.09 | 59.11 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.13 | 37.88 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.49 | 23.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.83 | 12.60 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.83 | 10.71 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.54 | 14.84 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.63 | 27.16 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.10 | 41.59 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.36 | 64.97 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.30 | 78.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 104.86 | 42.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.49 | 10.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.36 | 78.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 134.80 | 73.40 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 127.09 | 66.29 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.09 | 59.11 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.13 | 37.88 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.49 | 23.43 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.83 | 12.60 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.83 | 10.71 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.54 | 14.84 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.63 | 27.16 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.10 | 41.59 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.36 | 64.97 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.30 | 78.89 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 104.86 | 42.45 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.49 | 10.71 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.36 | 78.89 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 161.60 | 86.73 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 152.35 | 78.36 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 127.29 | 69.94 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.07 | 44.97 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 75.64 | 27.95 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.27 | 15.08 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.62 | 12.79 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.09 | 17.69 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.21 | 32.26 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.59 | 49.29 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 172.88 | 76.89 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 162.11 | 93.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 125.38 | 50.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 75.64 | 12.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 172.88 | 93.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.29 | 72.00 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 127.48 | 65.23 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.36 | 58.42 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.18 | 37.75 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.45 | 23.55 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.72 | 12.83 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.71 | 10.95 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.44 | 15.09 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.58 | 27.38 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.10 | 41.58 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.57 | 64.40 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.78 | 77.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 104.98 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.45 | 10.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.57 | 77.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.29 | 72.00 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 127.48 | 65.23 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.36 | 58.42 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.18 | 37.75 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.45 | 23.55 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.72 | 12.83 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.71 | 10.95 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.44 | 15.09 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.58 | 27.38 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.10 | 41.58 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.57 | 64.40 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 135.78 | 77.58 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 104.98 | 42.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.45 | 10.95 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.57 | 77.58 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 162.19 | 85.08 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 152.83 | 77.12 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 127.61 | 69.13 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.12 | 44.81 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 75.58 | 28.10 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.13 | 15.36 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.48 | 13.07 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 96.98 | 17.98 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.15 | 32.52 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.59 | 49.27 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.13 | 76.21 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 162.68 | 91.77 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 125.52 | 49.90 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 75.58 | 13.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.13 | 91.77 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.93 | 70.53 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.08 | 63.98 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.83 | 57.53 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.39 | 37.22 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.61 | 23.19 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.89 | 12.56 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.84 | 10.69 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.56 | 14.81 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.68 | 27.05 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.24 | 41.18 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.88 | 63.73 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.41 | 76.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.29 | 41.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.61 | 10.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.88 | 76.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 135.93 | 70.53 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 128.08 | 63.98 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 106.83 | 57.53 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.39 | 37.22 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.61 | 23.19 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 66.89 | 12.56 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.84 | 10.69 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.56 | 14.81 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.68 | 27.05 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.24 | 41.18 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 144.88 | 63.73 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 136.41 | 76.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.29 | 41.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.61 | 10.69 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 144.88 | 76.22 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 162.95 | 83.35 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 153.53 | 75.64 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 128.17 | 68.08 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 97.38 | 44.19 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 75.78 | 27.67 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.33 | 15.04 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.64 | 12.77 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.12 | 17.65 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.27 | 32.14 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 161.77 | 48.80 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 173.51 | 75.43 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 163.43 | 90.15 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 125.89 | 49.11 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 75.78 | 12.77 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 173.51 | 90.15 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.53 | 67.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.63 | 61.21 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.16 | 55.34 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.02 | 35.63 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.82 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.08 | 11.69 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.87 | 9.87 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.56 | 13.77 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.66 | 25.80 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.67 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.85 | 62.02 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.00 | 73.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.00 | 39.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.82 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.85 | 73.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.53 | 67.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.63 | 61.21 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.16 | 55.34 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.02 | 35.63 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.82 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.08 | 11.69 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.87 | 9.87 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.56 | 13.77 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.66 | 25.80 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.67 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.85 | 62.02 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.00 | 73.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.00 | 39.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.82 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.85 | 73.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.53 | 67.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.63 | 61.21 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.16 | 55.34 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.02 | 35.63 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.82 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.08 | 11.69 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.87 | 9.87 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.56 | 13.77 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.66 | 25.80 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.67 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.85 | 62.02 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.00 | 73.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.00 | 39.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.82 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.85 | 73.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.53 | 67.52 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.63 | 61.21 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.16 | 55.34 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.02 | 35.63 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 63.82 | 21.92 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.08 | 11.69 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.87 | 9.87 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.56 | 13.77 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.66 | 25.80 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.67 | 39.87 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.85 | 62.02 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.00 | 73.33 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.00 | 39.72 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 63.82 | 9.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.85 | 73.33 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.79 | 79.83 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.32 | 72.40 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.70 | 65.52 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.11 | 42.31 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.03 | 26.16 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.57 | 14.00 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.68 | 11.79 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.13 | 16.42 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.24 | 30.68 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.25 | 47.26 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 174.62 | 73.42 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.28 | 86.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.70 | 47.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.03 | 11.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 174.62 | 86.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.79 | 79.83 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.32 | 72.40 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.70 | 65.52 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.11 | 42.31 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.03 | 26.16 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.57 | 14.00 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.68 | 11.79 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.13 | 16.42 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.24 | 30.68 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.25 | 47.26 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 174.62 | 73.42 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.28 | 86.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.70 | 47.09 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.03 | 11.79 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 174.62 | 86.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.29 | 67.44 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.39 | 61.16 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.91 | 55.30 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.94 | 35.44 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.00 | 21.62 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.55 | 11.38 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.24 | 9.57 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.81 | 13.44 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.69 | 25.47 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.50 | 39.68 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.57 | 62.04 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.78 | 73.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.98 | 39.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.00 | 9.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.57 | 73.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.29 | 67.44 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.39 | 61.16 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 107.91 | 55.30 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 81.94 | 35.44 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.00 | 21.62 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.55 | 11.38 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.24 | 9.57 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.81 | 13.44 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.69 | 25.47 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.50 | 39.68 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.57 | 62.04 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 137.78 | 73.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 105.98 | 39.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.00 | 9.57 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.57 | 73.30 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.57 | 79.71 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.10 | 72.31 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.46 | 65.45 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.05 | 42.09 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.24 | 25.82 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.11 | 13.64 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.11 | 11.43 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.43 | 16.03 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.30 | 30.28 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.09 | 47.04 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 174.34 | 73.42 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.07 | 86.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.72 | 46.86 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.24 | 11.43 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 174.34 | 86.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.55 | 66.90 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.65 | 60.66 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.16 | 54.87 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.06 | 35.23 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.08 | 21.51 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.63 | 11.31 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.32 | 9.49 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.87 | 13.37 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.74 | 25.38 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.58 | 39.55 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.74 | 61.76 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.01 | 72.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.13 | 39.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.08 | 9.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.74 | 72.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 137.55 | 66.90 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 129.65 | 60.66 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.16 | 54.87 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.06 | 35.23 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.08 | 21.51 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.63 | 11.31 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.32 | 9.49 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.87 | 13.37 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.74 | 25.38 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.58 | 39.55 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 145.74 | 61.76 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.01 | 72.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.13 | 39.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.08 | 9.49 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 145.74 | 72.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 164.88 | 79.07 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 155.41 | 71.72 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 129.76 | 64.95 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.19 | 41.84 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.34 | 25.68 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.20 | 13.55 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.20 | 11.35 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.50 | 15.94 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.37 | 30.17 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.18 | 46.88 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 174.54 | 73.09 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 165.34 | 86.19 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 126.89 | 46.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.34 | 11.35 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 174.54 | 86.19 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.19 | 65.48 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.33 | 59.24 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.85 | 53.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.37 | 34.56 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.23 | 21.21 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.67 | 11.21 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.30 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.85 | 13.33 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.75 | 25.30 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.72 | 39.20 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.23 | 60.86 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.58 | 71.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.43 | 38.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.23 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.23 | 71.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 138.19 | 65.48 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 130.33 | 59.24 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 108.85 | 53.57 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.37 | 34.56 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.23 | 21.21 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.67 | 11.21 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 68.30 | 9.44 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.85 | 13.33 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.75 | 25.30 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.72 | 39.20 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 146.23 | 60.86 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 138.58 | 71.67 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.43 | 38.65 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.23 | 9.44 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 146.23 | 71.67 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 165.64 | 77.40 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 156.22 | 70.06 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 130.58 | 63.42 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 98.56 | 41.05 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.51 | 25.34 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 80.25 | 13.43 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 81.19 | 11.29 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 97.47 | 15.90 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 139.38 | 30.08 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.35 | 46.47 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 175.12 | 72.03 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 166.01 | 84.78 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.25 | 45.81 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.51 | 11.29 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 175.12 | 84.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.51 | 61.13 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.82 | 54.71 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.28 | 49.12 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.86 | 31.94 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.16 | 20.02 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.05 | 10.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.45 | 9.41 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.01 | 13.38 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.12 | 25.22 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.84 | 37.89 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.27 | 57.75 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.81 | 67.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.77 | 36.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.16 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.27 | 67.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 98.39 | 74.54 | 23.85 | 139.51 | 61.13 | 0.00 | 0.00 | 0.00 |
February | 91.26 | 64.34 | 26.92 | 131.82 | 54.71 | 0.00 | 0.00 | 0.00 |
March | 74.17 | 42.77 | 31.40 | 110.28 | 49.12 | 0.00 | 0.00 | 0.00 |
April | 50.29 | 18.76 | 31.52 | 82.86 | 31.94 | 0.00 | 0.00 | 0.00 |
May | 35.54 | 4.97 | 30.56 | 64.16 | 20.02 | 0.00 | 0.00 | 0.00 |
June | 30.66 | 1.95 | 28.71 | 67.05 | 10.87 | 0.00 | 0.00 | 0.00 |
July | 31.25 | 2.90 | 28.36 | 67.45 | 9.41 | 0.00 | 0.00 | 0.00 |
August | 39.84 | 10.55 | 29.29 | 81.01 | 13.38 | 0.00 | 0.00 | 0.00 |
September | 62.19 | 32.31 | 29.88 | 116.12 | 25.22 | 0.00 | 0.00 | 0.00 |
October | 84.49 | 57.12 | 27.37 | 135.84 | 37.89 | 0.00 | 0.00 | 0.00 |
November | 101.68 | 77.52 | 24.16 | 147.27 | 57.75 | 0.00 | 0.00 | 0.00 |
December | 100.77 | 75.64 | 25.13 | 139.81 | 67.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 66.57 | 38.47 | 28.10 | 106.77 | 36.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.66 | 1.95 | 23.85 | 64.16 | 9.41 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 101.68 | 77.52 | 31.52 | 147.27 | 67.86 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 117.63 | 89.12 | 28.51 | 167.22 | 72.27 | 0.00 | 0.00 | 0.00 |
February | 109.11 | 76.92 | 32.19 | 158.00 | 64.73 | 0.00 | 0.00 | 0.00 |
March | 88.68 | 51.13 | 37.55 | 132.29 | 58.18 | 0.00 | 0.00 | 0.00 |
April | 60.12 | 22.43 | 37.69 | 99.14 | 37.98 | 0.00 | 0.00 | 0.00 |
May | 42.49 | 5.95 | 36.54 | 76.44 | 23.94 | 0.00 | 0.00 | 0.00 |
June | 36.66 | 2.33 | 34.33 | 79.51 | 13.03 | 0.00 | 0.00 | 0.00 |
July | 37.37 | 3.46 | 33.90 | 80.17 | 11.26 | 0.00 | 0.00 | 0.00 |
August | 47.63 | 12.61 | 35.02 | 96.46 | 15.97 | 0.00 | 0.00 | 0.00 |
September | 74.35 | 38.63 | 35.72 | 138.62 | 30.00 | 0.00 | 0.00 | 0.00 |
October | 101.02 | 68.30 | 32.72 | 162.48 | 44.93 | 0.00 | 0.00 | 0.00 |
November | 121.57 | 92.68 | 28.89 | 176.36 | 68.37 | 0.00 | 0.00 | 0.00 |
December | 120.48 | 90.44 | 30.04 | 167.49 | 80.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 79.59 | 45.99 | 33.60 | 127.65 | 43.30 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.66 | 2.33 | 28.51 | 76.44 | 11.26 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 121.57 | 92.68 | 37.69 | 176.36 | 80.29 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365424E+09 | 0.189897E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312058E+09 | 0.153678E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288766E+09 | 0.151883E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212937E+09 | 92076406.15 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172417E+09 | 56490584.62 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176943E+09 | 27805742.75 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185422E+09 | 23675491.21 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220983E+09 | 34349746.39 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303026E+09 | 63992960.57 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363605E+09 | 0.106029E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.376843E+09 | 0.164136E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366728E+09 | 0.204833E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334515E+10 | 0.126885E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172417E+09 | 23675491.21 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.376843E+09 | 0.204833E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365424E+09 | 0.189897E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312058E+09 | 0.153678E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288766E+09 | 0.151883E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212937E+09 | 92076406.15 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172417E+09 | 56490584.62 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176943E+09 | 27805742.75 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185422E+09 | 23675491.21 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220983E+09 | 34349746.39 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303026E+09 | 63992960.57 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363605E+09 | 0.106029E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.376843E+09 | 0.164136E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366728E+09 | 0.204833E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334515E+10 | 0.126885E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172417E+09 | 23675491.21 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.376843E+09 | 0.204833E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365424E+09 | 0.189897E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312058E+09 | 0.153678E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288766E+09 | 0.151883E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212937E+09 | 92076406.15 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172417E+09 | 56490584.62 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176943E+09 | 27805742.75 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185422E+09 | 23675491.21 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220983E+09 | 34349746.39 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303026E+09 | 63992960.57 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363605E+09 | 0.106029E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.376843E+09 | 0.164136E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366728E+09 | 0.204833E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334515E+10 | 0.126885E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172417E+09 | 23675491.21 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.376843E+09 | 0.204833E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.365424E+09 | 0.189897E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.312058E+09 | 0.153678E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.288766E+09 | 0.151883E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212937E+09 | 92076406.15 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172417E+09 | 56490584.62 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.176943E+09 | 27805742.75 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.185422E+09 | 23675491.21 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.220983E+09 | 34349746.39 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303026E+09 | 63992960.57 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363605E+09 | 0.106029E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.376843E+09 | 0.164136E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.366728E+09 | 0.204833E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334515E+10 | 0.126885E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172417E+09 | 23675491.21 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.376843E+09 | 0.204833E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.440281E+09 | 0.225754E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.375976E+09 | 0.182756E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.348165E+09 | 0.180810E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.256078E+09 | 0.110011E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.206457E+09 | 67877799.45 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.210890E+09 | 33509967.75 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.221440E+09 | 28480291.81 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.264443E+09 | 41218986.56 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.363611E+09 | 76605686.56 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.437159E+09 | 0.126478E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.453620E+09 | 0.195424E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.441630E+09 | 0.243729E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.401975E+10 | 0.151266E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.206457E+09 | 28480291.81 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.453620E+09 | 0.243729E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.440281E+09 | 0.225754E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.375976E+09 | 0.182756E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.348165E+09 | 0.180810E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.256078E+09 | 0.110011E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.206457E+09 | 67877799.45 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.210890E+09 | 33509967.75 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.221440E+09 | 28480291.81 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.264443E+09 | 41218986.56 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.363611E+09 | 76605686.56 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.437159E+09 | 0.126478E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.453620E+09 | 0.195424E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.441630E+09 | 0.243729E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.401975E+10 | 0.151266E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.206457E+09 | 28480291.81 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.453620E+09 | 0.243729E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.359300E+09 | 0.202607E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.306477E+09 | 0.163667E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.283514E+09 | 0.159813E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211031E+09 | 94800243.60 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172046E+09 | 57391192.82 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177788E+09 | 28203667.74 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186507E+09 | 23833296.06 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221929E+09 | 34266898.02 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303311E+09 | 63312729.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362567E+09 | 0.106809E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.373434E+09 | 0.169651E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.360691E+09 | 0.217274E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331859E+10 | 0.132163E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172046E+09 | 23833296.06 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.373434E+09 | 0.217274E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.359300E+09 | 0.202607E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.306477E+09 | 0.163667E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.283514E+09 | 0.159813E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.211031E+09 | 94800243.60 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172046E+09 | 57391192.82 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.177788E+09 | 28203667.74 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.186507E+09 | 23833296.06 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.221929E+09 | 34266898.02 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.303311E+09 | 63312729.93 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362567E+09 | 0.106809E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.373434E+09 | 0.169651E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.360691E+09 | 0.217274E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331859E+10 | 0.132163E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172046E+09 | 23833296.06 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.373434E+09 | 0.217274E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.316787E+09 | 0.239999E+09 | 76787787.94 | 0.433136E+09 | 0.240681E+09 |
February | 0.265418E+09 | 0.187115E+09 | 78302345.55 | 0.369441E+09 | 0.194500E+09 |
March | 0.238818E+09 | 0.137702E+09 | 0.101116E+09 | 0.342032E+09 | 0.190144E+09 |
April | 0.156695E+09 | 58466780.93 | 98228034.59 | 0.253851E+09 | 0.113229E+09 |
May | 0.114426E+09 | 16015840.86 | 98409804.77 | 0.205997E+09 | 68955099.16 |
June | 95535986.37 | 6061786.34 | 89474200.03 | 0.211838E+09 | 33995468.41 |
July | 0.100635E+09 | 9329009.15 | 91305690.16 | 0.222711E+09 | 28672335.09 |
August | 0.128281E+09 | 33956884.46 | 94324609.58 | 0.265582E+09 | 41126349.38 |
September | 0.193774E+09 | 0.100672E+09 | 93101553.68 | 0.364015E+09 | 75787553.59 |
October | 0.272058E+09 | 0.183929E+09 | 88128496.15 | 0.436037E+09 | 0.127373E+09 |
November | 0.316835E+09 | 0.241548E+09 | 75287263.97 | 0.449682E+09 | 0.201884E+09 |
December | 0.324462E+09 | 0.243556E+09 | 80906164.45 | 0.434558E+09 | 0.258354E+09 |
Annual Sum or Average | 0.252372E+10 | 0.145835E+10 | 0.106537E+10 | 0.398888E+10 | 0.157470E+10 |
Minimum of Months | 95535986.37 | 6061786.34 | 75287263.97 | 0.205997E+09 | 28672335.09 |
Maximum of Months | 0.324462E+09 | 0.243556E+09 | 0.101116E+09 | 0.449682E+09 | 0.258354E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.361036E+09 | 0.196589E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.307447E+09 | 0.160372E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.284159E+09 | 0.158315E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210296E+09 | 98187506.63 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170061E+09 | 62742174.54 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173231E+09 | 32653884.34 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181678E+09 | 28687827.65 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218385E+09 | 39760414.99 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302304E+09 | 70393044.50 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361848E+09 | 0.111401E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374178E+09 | 0.168411E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.362375E+09 | 0.211309E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.330700E+10 | 0.133882E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170061E+09 | 28687827.65 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374178E+09 | 0.211309E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.361036E+09 | 0.196589E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.307447E+09 | 0.160372E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.284159E+09 | 0.158315E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210296E+09 | 98187506.63 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170061E+09 | 62742174.54 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173231E+09 | 32653884.34 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181678E+09 | 28687827.65 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218385E+09 | 39760414.99 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302304E+09 | 70393044.50 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361848E+09 | 0.111401E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374178E+09 | 0.168411E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.362375E+09 | 0.211309E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.330700E+10 | 0.133882E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170061E+09 | 28687827.65 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374178E+09 | 0.211309E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.432825E+09 | 0.232305E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.368575E+09 | 0.189571E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.340930E+09 | 0.187329E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.251614E+09 | 0.116549E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.202593E+09 | 74851841.31 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.205461E+09 | 39095716.39 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.215944E+09 | 34257726.84 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260057E+09 | 47375773.01 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360837E+09 | 83630472.59 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.432806E+09 | 0.132006E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.448110E+09 | 0.199296E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.434183E+09 | 0.249940E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.395393E+10 | 0.158621E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.202593E+09 | 34257726.84 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.448110E+09 | 0.249940E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.362370E+09 | 0.192842E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.308403E+09 | 0.157816E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.284888E+09 | 0.156470E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210407E+09 | 97849819.70 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.169936E+09 | 63081120.11 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.172927E+09 | 33253729.08 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181342E+09 | 29324923.23 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218126E+09 | 40419920.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302164E+09 | 70960336.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361849E+09 | 0.111358E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374713E+09 | 0.166922E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.363671E+09 | 0.207801E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331080E+10 | 0.132810E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.169936E+09 | 29324923.23 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374713E+09 | 0.207801E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.362370E+09 | 0.192842E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.308403E+09 | 0.157816E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.284888E+09 | 0.156470E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210407E+09 | 97849819.70 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.169936E+09 | 63081120.11 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.172927E+09 | 33253729.08 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181342E+09 | 29324923.23 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218126E+09 | 40419920.56 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302164E+09 | 70960336.62 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.361849E+09 | 0.111358E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.374713E+09 | 0.166922E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.363671E+09 | 0.207801E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.331080E+10 | 0.132810E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.169936E+09 | 29324923.23 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.374713E+09 | 0.207801E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.434411E+09 | 0.227883E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.369714E+09 | 0.186558E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.341799E+09 | 0.185154E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.251746E+09 | 0.116152E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.202445E+09 | 75252705.25 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.205103E+09 | 39808256.80 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.215546E+09 | 35013144.61 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.259751E+09 | 48157175.78 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360668E+09 | 84301071.90 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.432808E+09 | 0.131957E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.448750E+09 | 0.197537E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.435726E+09 | 0.245796E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.395847E+10 | 0.157357E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.202445E+09 | 35013144.61 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.448750E+09 | 0.245796E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.364086E+09 | 0.188907E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309840E+09 | 0.154775E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286145E+09 | 0.154084E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210964E+09 | 96480422.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170372E+09 | 62099816.13 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173372E+09 | 32549943.89 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181712E+09 | 28642805.35 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218449E+09 | 39658730.69 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302432E+09 | 70116847.99 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362235E+09 | 0.110288E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375541E+09 | 0.165200E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.365364E+09 | 0.204134E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.332051E+10 | 0.130694E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170372E+09 | 28642805.35 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375541E+09 | 0.204134E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.364086E+09 | 0.188907E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.309840E+09 | 0.154775E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.286145E+09 | 0.154084E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.210964E+09 | 96480422.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170372E+09 | 62099816.13 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173372E+09 | 32549943.89 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181712E+09 | 28642805.35 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218449E+09 | 39658730.69 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302432E+09 | 70116847.99 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362235E+09 | 0.110288E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.375541E+09 | 0.165200E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.365364E+09 | 0.204134E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.332051E+10 | 0.130694E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170372E+09 | 28642805.35 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.375541E+09 | 0.204134E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.436450E+09 | 0.223244E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.371426E+09 | 0.182978E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.343296E+09 | 0.182343E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.252414E+09 | 0.114540E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.202966E+09 | 74099840.89 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.205628E+09 | 38975925.13 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.215986E+09 | 34209481.29 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260135E+09 | 47261011.42 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360991E+09 | 83310214.79 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.433273E+09 | 0.130698E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.449740E+09 | 0.195508E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.437740E+09 | 0.241468E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.397005E+10 | 0.154864E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.202966E+09 | 34209481.29 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.449740E+09 | 0.241468E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368355E+09 | 0.180842E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313591E+09 | 0.148076E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289709E+09 | 0.148225E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212599E+09 | 92343664.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170926E+09 | 58702592.79 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173868E+09 | 30301632.19 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181785E+09 | 26432738.49 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218458E+09 | 36892263.87 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302380E+09 | 66886518.29 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363388E+09 | 0.106777E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378053E+09 | 0.160750E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369619E+09 | 0.196417E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334273E+10 | 0.125265E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170926E+09 | 26432738.49 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378053E+09 | 0.196417E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368355E+09 | 0.180842E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313591E+09 | 0.148076E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289709E+09 | 0.148225E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212599E+09 | 92343664.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170926E+09 | 58702592.79 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173868E+09 | 30301632.19 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181785E+09 | 26432738.49 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218458E+09 | 36892263.87 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302380E+09 | 66886518.29 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363388E+09 | 0.106777E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378053E+09 | 0.160750E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369619E+09 | 0.196417E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334273E+10 | 0.125265E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170926E+09 | 26432738.49 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378053E+09 | 0.196417E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368355E+09 | 0.180842E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313591E+09 | 0.148076E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289709E+09 | 0.148225E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212599E+09 | 92343664.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170926E+09 | 58702592.79 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173868E+09 | 30301632.19 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181785E+09 | 26432738.49 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218458E+09 | 36892263.87 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302380E+09 | 66886518.29 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363388E+09 | 0.106777E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378053E+09 | 0.160750E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369619E+09 | 0.196417E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334273E+10 | 0.125265E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170926E+09 | 26432738.49 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378053E+09 | 0.196417E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368355E+09 | 0.180842E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313591E+09 | 0.148076E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289709E+09 | 0.148225E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212599E+09 | 92343664.54 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.170926E+09 | 58702592.79 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173868E+09 | 30301632.19 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.181785E+09 | 26432738.49 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.218458E+09 | 36892263.87 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302380E+09 | 66886518.29 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363388E+09 | 0.106777E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.378053E+09 | 0.160750E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369619E+09 | 0.196417E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334273E+10 | 0.125265E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.170926E+09 | 26432738.49 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.378053E+09 | 0.196417E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.441380E+09 | 0.213825E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.375761E+09 | 0.175145E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.347402E+09 | 0.175490E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254312E+09 | 0.109678E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.203638E+09 | 70079031.51 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206257E+09 | 36278542.99 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216094E+09 | 31570598.97 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260145E+09 | 43976770.51 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360912E+09 | 79519548.33 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434558E+09 | 0.126595E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.452606E+09 | 0.190312E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.442675E+09 | 0.232432E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.399574E+10 | 0.148490E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.203638E+09 | 31570598.97 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.452606E+09 | 0.232432E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.441380E+09 | 0.213825E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.375761E+09 | 0.175145E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.347402E+09 | 0.175490E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254312E+09 | 0.109678E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.203638E+09 | 70079031.51 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206257E+09 | 36278542.99 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.216094E+09 | 31570598.97 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260145E+09 | 43976770.51 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.360912E+09 | 79519548.33 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434558E+09 | 0.126595E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.452606E+09 | 0.190312E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.442675E+09 | 0.232432E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.399574E+10 | 0.148490E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.203638E+09 | 31570598.97 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.452606E+09 | 0.232432E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.367705E+09 | 0.180627E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313025E+09 | 0.147951E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289023E+09 | 0.148104E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212391E+09 | 91858620.93 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171406E+09 | 57909654.42 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175080E+09 | 29504976.04 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182778E+09 | 25619379.85 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219127E+09 | 36004609.97 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302458E+09 | 66012429.04 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362933E+09 | 0.106288E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377328E+09 | 0.160806E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369029E+09 | 0.196331E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334228E+10 | 0.124702E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171406E+09 | 25619379.85 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377328E+09 | 0.196331E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.367705E+09 | 0.180627E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313025E+09 | 0.147951E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289023E+09 | 0.148104E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212391E+09 | 91858620.93 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171406E+09 | 57909654.42 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175080E+09 | 29504976.04 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182778E+09 | 25619379.85 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219127E+09 | 36004609.97 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302458E+09 | 66012429.04 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.362933E+09 | 0.106288E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377328E+09 | 0.160806E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369029E+09 | 0.196331E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334228E+10 | 0.124702E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171406E+09 | 25619379.85 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377328E+09 | 0.196331E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.440773E+09 | 0.213485E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.375226E+09 | 0.174936E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.346737E+09 | 0.175296E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254134E+09 | 0.109101E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204203E+09 | 69158501.47 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207634E+09 | 35351316.94 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217248E+09 | 30617317.45 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.260951E+09 | 42935851.86 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361076E+09 | 78485186.86 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434144E+09 | 0.125989E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.451894E+09 | 0.190316E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.442117E+09 | 0.232255E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.399614E+10 | 0.147792E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204203E+09 | 30617317.45 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.451894E+09 | 0.232255E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368415E+09 | 0.179181E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313659E+09 | 0.146748E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289709E+09 | 0.146976E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212699E+09 | 91314716.31 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171633E+09 | 57599902.18 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175294E+09 | 29307709.14 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182975E+09 | 25428184.81 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219287E+09 | 35807027.44 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302595E+09 | 65774509.10 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363127E+09 | 0.105921E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377762E+09 | 0.160071E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369637E+09 | 0.195154E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334679E+10 | 0.123928E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171633E+09 | 25428184.81 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377762E+09 | 0.195154E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.368415E+09 | 0.179181E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.313659E+09 | 0.146748E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.289709E+09 | 0.146976E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.212699E+09 | 91314716.31 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171633E+09 | 57599902.18 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175294E+09 | 29307709.14 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182975E+09 | 25428184.81 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219287E+09 | 35807027.44 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302595E+09 | 65774509.10 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363127E+09 | 0.105921E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.377762E+09 | 0.160071E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.369637E+09 | 0.195154E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.334679E+10 | 0.123928E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171633E+09 | 25428184.81 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.377762E+09 | 0.195154E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.441619E+09 | 0.211778E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.375980E+09 | 0.173515E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.347553E+09 | 0.173966E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.254503E+09 | 0.108458E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204472E+09 | 68792352.43 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.207888E+09 | 35117159.23 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217483E+09 | 30390391.25 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261143E+09 | 42701515.75 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361241E+09 | 78203875.39 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434378E+09 | 0.125555E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.452412E+09 | 0.189446E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.442841E+09 | 0.230864E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.400151E+10 | 0.146879E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204472E+09 | 30390391.25 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.452412E+09 | 0.230864E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370116E+09 | 0.175382E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315304E+09 | 0.143325E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.291549E+09 | 0.143489E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213498E+09 | 89567485.57 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172021E+09 | 56815887.40 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175396E+09 | 29052771.32 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182948E+09 | 25290377.31 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219223E+09 | 35707603.05 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302620E+09 | 65569642.40 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363517E+09 | 0.104989E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379022E+09 | 0.157747E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371159E+09 | 0.191950E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335637E+10 | 0.121888E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172021E+09 | 25290377.31 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379022E+09 | 0.191950E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.370116E+09 | 0.175382E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.315304E+09 | 0.143325E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.291549E+09 | 0.143489E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.213498E+09 | 89567485.57 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.172021E+09 | 56815887.40 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.175396E+09 | 29052771.32 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.182948E+09 | 25290377.31 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.219223E+09 | 35707603.05 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.302620E+09 | 65569642.40 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363517E+09 | 0.104989E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.379022E+09 | 0.157747E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.371159E+09 | 0.191950E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.335637E+10 | 0.121888E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.172021E+09 | 25290377.31 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.379022E+09 | 0.191950E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.443643E+09 | 0.207298E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.377937E+09 | 0.169483E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.349743E+09 | 0.169857E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.255457E+09 | 0.106402E+09 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204934E+09 | 67872065.78 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.208007E+09 | 34819928.01 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.217448E+09 | 30233699.67 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.261065E+09 | 42590273.55 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.361269E+09 | 77967998.34 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.434843E+09 | 0.124459E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.453912E+09 | 0.186706E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.444653E+09 | 0.227081E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.401291E+10 | 0.144477E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204934E+09 | 30233699.67 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.453912E+09 | 0.227081E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373655E+09 | 0.163721E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318909E+09 | 0.132364E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295387E+09 | 0.131566E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214778E+09 | 82794187.45 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171851E+09 | 53612622.14 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173797E+09 | 28165191.69 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.180668E+09 | 25209670.04 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.216974E+09 | 35850321.33 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.300982E+09 | 65379940.15 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363822E+09 | 0.101485E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.381730E+09 | 0.149691E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374467E+09 | 0.181744E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336702E+10 | 0.115158E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171851E+09 | 25209670.04 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.381730E+09 | 0.181744E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.263516E+09 | 0.199641E+09 | 63875169.97 | 0.373655E+09 | 0.163721E+09 |
February | 0.220785E+09 | 0.155650E+09 | 65135039.89 | 0.318909E+09 | 0.132364E+09 |
March | 0.198659E+09 | 0.114546E+09 | 84112693.66 | 0.295387E+09 | 0.131566E+09 |
April | 0.130345E+09 | 48635019.57 | 81710029.33 | 0.214778E+09 | 82794187.45 |
May | 95183853.57 | 13322620.49 | 81861233.08 | 0.171851E+09 | 53612622.14 |
June | 79470675.37 | 5042437.65 | 74428237.72 | 0.173797E+09 | 28165191.69 |
July | 83711989.83 | 7760244.97 | 75951744.86 | 0.180668E+09 | 25209670.04 |
August | 0.106710E+09 | 28246702.05 | 78463003.44 | 0.216974E+09 | 35850321.33 |
September | 0.161189E+09 | 83743175.85 | 77445616.35 | 0.300982E+09 | 65379940.15 |
October | 0.226308E+09 | 0.153000E+09 | 73308827.12 | 0.363822E+09 | 0.101485E+09 |
November | 0.263556E+09 | 0.200929E+09 | 62626973.79 | 0.381730E+09 | 0.149691E+09 |
December | 0.269901E+09 | 0.202600E+09 | 67301001.16 | 0.374467E+09 | 0.181744E+09 |
Annual Sum or Average | 0.209934E+10 | 0.121312E+10 | 0.886220E+09 | 0.336702E+10 | 0.115158E+10 |
Minimum of Months | 79470675.37 | 5042437.65 | 62626973.79 | 0.171851E+09 | 25209670.04 |
Maximum of Months | 0.269901E+09 | 0.202600E+09 | 84112693.66 | 0.381730E+09 | 0.181744E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.315056E+09 | 0.238688E+09 | 76368182.54 | 0.447871E+09 | 0.193556E+09 |
February | 0.263967E+09 | 0.186093E+09 | 77874463.88 | 0.382240E+09 | 0.156595E+09 |
March | 0.237513E+09 | 0.136950E+09 | 0.100564E+09 | 0.354325E+09 | 0.155838E+09 |
April | 0.155839E+09 | 58147290.33 | 97691269.37 | 0.256982E+09 | 98437876.76 |
May | 0.113800E+09 | 15928322.61 | 97872046.28 | 0.204725E+09 | 64110087.99 |
June | 95013931.80 | 6028661.83 | 88985269.98 | 0.206095E+09 | 33783506.25 |
July | 0.100085E+09 | 9278030.96 | 90806751.97 | 0.214725E+09 | 30155076.42 |
August | 0.127581E+09 | 33771327.72 | 93809174.56 | 0.258370E+09 | 42776905.72 |
September | 0.192715E+09 | 0.100122E+09 | 92592802.02 | 0.359293E+09 | 77758106.55 |
October | 0.270571E+09 | 0.182924E+09 | 87646919.67 | 0.435200E+09 | 0.120348E+09 |
November | 0.315104E+09 | 0.240228E+09 | 74875858.16 | 0.457138E+09 | 0.177224E+09 |
December | 0.322689E+09 | 0.242225E+09 | 80464054.26 | 0.448605E+09 | 0.215048E+09 |
Annual Sum or Average | 0.250993E+10 | 0.145038E+10 | 0.105955E+10 | 0.402557E+10 | 0.136563E+10 |
Minimum of Months | 95013931.80 | 6028661.83 | 74875858.16 | 0.204725E+09 | 30155076.42 |
Maximum of Months | 0.322689E+09 | 0.242225E+09 | 0.100564E+09 | 0.457138E+09 | 0.215048E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 874.50 | 452.17 | 630.09 | 477.36 | 152.73 | 0.00 | 0.00 |
February | 826.80 | 405.19 | 584.48 | 412.05 | 172.43 | 0.00 | 0.00 |
March | 691.23 | 361.84 | 475.01 | 273.89 | 201.12 | 0.00 | 0.00 |
April | 526.20 | 226.98 | 322.06 | 120.17 | 201.89 | 0.00 | 0.00 |
May | 411.65 | 135.05 | 227.59 | 31.86 | 195.74 | 0.00 | 0.00 |
June | 435.78 | 68.77 | 196.36 | 12.46 | 183.90 | 0.00 | 0.00 |
July | 442.27 | 56.62 | 200.16 | 18.56 | 181.61 | 0.00 | 0.00 |
August | 527.48 | 82.08 | 255.15 | 67.54 | 187.61 | 0.00 | 0.00 |
September | 748.20 | 157.86 | 398.26 | 206.91 | 191.35 | 0.00 | 0.00 |
October | 869.45 | 252.79 | 541.12 | 365.84 | 175.29 | 0.00 | 0.00 |
November | 931.56 | 404.09 | 651.19 | 496.46 | 154.74 | 0.00 | 0.00 |
December | 877.45 | 487.90 | 645.36 | 484.44 | 160.92 | 0.00 | 0.00 |
Annual Sum or Average | 679.23 | 256.87 | 426.33 | 246.36 | 179.97 | 0.00 | 0.00 |
Minimum of Months | 411.65 | 56.62 | 196.36 | 12.46 | 152.73 | 0.00 | 0.00 |
Maximum of Months | 931.56 | 487.90 | 651.19 | 496.46 | 201.89 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 430.01 | 241.15 | 315.05 | 238.68 | 76.37 | 0.00 | 0.00 |
February | 406.08 | 215.71 | 292.24 | 206.02 | 86.22 | 0.00 | 0.00 |
March | 339.40 | 190.33 | 237.51 | 136.95 | 100.56 | 0.00 | 0.00 |
April | 260.77 | 116.83 | 161.03 | 60.08 | 100.94 | 0.00 | 0.00 |
May | 205.38 | 68.60 | 113.80 | 15.93 | 97.87 | 0.00 | 0.00 |
June | 218.91 | 34.88 | 98.18 | 6.23 | 91.95 | 0.00 | 0.00 |
July | 222.42 | 28.50 | 100.08 | 9.28 | 90.80 | 0.00 | 0.00 |
August | 264.87 | 40.94 | 127.58 | 33.77 | 93.81 | 0.00 | 0.00 |
September | 374.47 | 78.09 | 199.13 | 103.46 | 95.68 | 0.00 | 0.00 |
October | 433.53 | 127.31 | 270.56 | 182.92 | 87.64 | 0.00 | 0.00 |
November | 461.63 | 208.79 | 325.60 | 248.23 | 77.37 | 0.00 | 0.00 |
December | 431.58 | 258.70 | 322.68 | 242.22 | 80.46 | 0.00 | 0.00 |
Annual Sum or Average | 336.95 | 133.75 | 213.17 | 123.18 | 89.99 | 0.00 | 0.00 |
Minimum of Months | 205.38 | 28.50 | 98.18 | 6.23 | 76.37 | 0.00 | 0.00 |
Maximum of Months | 461.63 | 258.70 | 325.60 | 248.23 | 100.94 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 431.19 | 233.53 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 406.53 | 210.94 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 339.47 | 188.16 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 259.34 | 120.73 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 202.63 | 74.80 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 212.93 | 40.28 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 216.29 | 34.21 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 260.16 | 47.38 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.47 | 86.58 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 431.79 | 132.47 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 461.60 | 206.84 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 432.70 | 251.10 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 335.11 | 135.21 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 202.63 | 34.21 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 461.60 | 251.10 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 432.78 | 229.08 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 407.79 | 207.58 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 340.34 | 185.97 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 259.47 | 120.31 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 202.48 | 75.20 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 212.56 | 41.02 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 215.89 | 34.97 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 259.86 | 48.16 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.30 | 87.28 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 431.79 | 132.42 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 462.26 | 205.01 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 434.24 | 246.94 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 335.49 | 134.12 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 202.48 | 34.97 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 462.26 | 246.94 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 434.82 | 224.41 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 409.68 | 203.59 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 341.84 | 183.14 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 260.16 | 118.63 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 203.00 | 74.04 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 213.11 | 40.15 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 216.33 | 34.16 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 260.24 | 47.26 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.63 | 86.24 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 432.25 | 131.15 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 463.28 | 202.90 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 436.26 | 242.58 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 336.47 | 131.99 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 203.00 | 34.16 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 463.28 | 242.58 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 879.70 | 429.74 | 628.80 | 476.38 | 152.42 | 0.00 | 0.00 |
February | 829.15 | 389.63 | 583.28 | 411.20 | 172.08 | 0.00 | 0.00 |
March | 692.07 | 352.40 | 474.04 | 273.33 | 200.71 | 0.00 | 0.00 |
April | 524.31 | 227.13 | 321.40 | 119.92 | 201.47 | 0.00 | 0.00 |
May | 407.32 | 140.00 | 227.13 | 31.79 | 195.34 | 0.00 | 0.00 |
June | 427.46 | 74.75 | 195.95 | 12.43 | 183.52 | 0.00 | 0.00 |
July | 432.84 | 63.05 | 199.75 | 18.52 | 181.24 | 0.00 | 0.00 |
August | 520.50 | 87.93 | 254.63 | 67.40 | 187.23 | 0.00 | 0.00 |
September | 745.12 | 164.58 | 397.45 | 206.49 | 190.96 | 0.00 | 0.00 |
October | 867.18 | 253.99 | 540.01 | 365.09 | 174.93 | 0.00 | 0.00 |
November | 932.65 | 394.92 | 649.86 | 495.44 | 154.42 | 0.00 | 0.00 |
December | 882.55 | 466.90 | 644.03 | 483.44 | 160.59 | 0.00 | 0.00 |
Annual Sum or Average | 677.40 | 253.06 | 425.46 | 245.85 | 179.60 | 0.00 | 0.00 |
Minimum of Months | 407.32 | 63.05 | 195.95 | 12.43 | 152.42 | 0.00 | 0.00 |
Maximum of Months | 932.65 | 466.90 | 649.86 | 495.44 | 201.47 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 439.14 | 214.58 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 413.89 | 194.63 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 345.27 | 176.04 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 261.93 | 112.97 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.23 | 69.06 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.20 | 36.40 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 217.59 | 30.56 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.05 | 42.92 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.68 | 81.21 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.10 | 126.41 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 465.49 | 197.50 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 440.63 | 233.32 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 338.68 | 125.95 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.23 | 30.56 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 465.49 | 233.32 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 439.98 | 212.87 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 414.72 | 193.04 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 346.09 | 174.70 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 262.31 | 112.30 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.50 | 68.69 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.46 | 36.16 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 217.83 | 30.33 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.24 | 42.68 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.85 | 80.92 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.33 | 125.97 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 466.02 | 196.60 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 441.35 | 231.92 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 339.14 | 125.17 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.50 | 30.33 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 466.02 | 231.92 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 442.01 | 208.36 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 416.89 | 188.55 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 348.28 | 170.56 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 263.29 | 110.16 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.96 | 67.77 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 215.59 | 35.85 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 217.80 | 30.17 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 261.17 | 42.56 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 372.88 | 80.67 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 433.80 | 124.86 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 467.57 | 193.75 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 443.16 | 228.11 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 340.11 | 123.11 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.96 | 30.17 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 467.57 | 228.11 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 446.23 | 194.52 | 314.40 | 238.19 | 76.21 | 0.00 | 0.00 |
February | 421.65 | 174.16 | 291.64 | 205.60 | 86.04 | 0.00 | 0.00 |
March | 352.86 | 156.42 | 237.02 | 136.66 | 100.35 | 0.00 | 0.00 |
April | 264.87 | 101.86 | 160.70 | 59.96 | 100.74 | 0.00 | 0.00 |
May | 204.76 | 63.97 | 113.56 | 15.90 | 97.67 | 0.00 | 0.00 |
June | 213.61 | 34.77 | 97.98 | 6.22 | 91.76 | 0.00 | 0.00 |
July | 215.08 | 30.08 | 99.88 | 9.26 | 90.62 | 0.00 | 0.00 |
August | 258.48 | 42.74 | 127.31 | 33.70 | 93.61 | 0.00 | 0.00 |
September | 370.85 | 80.45 | 198.72 | 103.24 | 95.48 | 0.00 | 0.00 |
October | 434.16 | 120.71 | 270.01 | 182.54 | 87.46 | 0.00 | 0.00 |
November | 470.91 | 183.88 | 324.93 | 247.72 | 77.21 | 0.00 | 0.00 |
December | 447.11 | 216.00 | 322.02 | 241.72 | 80.30 | 0.00 | 0.00 |
Annual Sum or Average | 341.18 | 116.34 | 212.73 | 122.93 | 89.80 | 0.00 | 0.00 |
Minimum of Months | 204.76 | 30.08 | 97.98 | 6.22 | 76.21 | 0.00 | 0.00 |
Maximum of Months | 470.91 | 216.00 | 324.93 | 247.72 | 100.74 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.234226E+10 | 0.121110E+10 | 0.168764E+10 | 0.127856E+10 | 0.409076E+09 | 0.00 | 0.00 |
February | 0.200018E+10 | 0.980224E+09 | 0.141398E+10 | 0.996831E+09 | 0.417145E+09 | 0.00 | 0.00 |
March | 0.185139E+10 | 0.969151E+09 | 0.127227E+10 | 0.733588E+09 | 0.538684E+09 | 0.00 | 0.00 |
April | 0.136390E+10 | 0.588325E+09 | 0.834770E+09 | 0.311474E+09 | 0.523296E+09 | 0.00 | 0.00 |
May | 0.110258E+10 | 0.361712E+09 | 0.609587E+09 | 85322163.70 | 0.524265E+09 | 0.00 | 0.00 |
June | 0.112955E+10 | 0.178239E+09 | 0.508955E+09 | 32293323.27 | 0.476661E+09 | 0.00 | 0.00 |
July | 0.118457E+10 | 0.151658E+09 | 0.536117E+09 | 49698998.17 | 0.486418E+09 | 0.00 | 0.00 |
August | 0.141282E+10 | 0.219835E+09 | 0.683402E+09 | 0.180901E+09 | 0.502501E+09 | 0.00 | 0.00 |
September | 0.193932E+10 | 0.409182E+09 | 0.103230E+10 | 0.536317E+09 | 0.495986E+09 | 0.00 | 0.00 |
October | 0.232874E+10 | 0.677073E+09 | 0.144935E+10 | 0.979857E+09 | 0.469492E+09 | 0.00 | 0.00 |
November | 0.241461E+10 | 0.104739E+10 | 0.168790E+10 | 0.128681E+10 | 0.401082E+09 | 0.00 | 0.00 |
December | 0.235017E+10 | 0.130679E+10 | 0.172853E+10 | 0.129751E+10 | 0.431016E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.214201E+11 | 0.810068E+10 | 0.134448E+11 | 0.776917E+10 | 0.567562E+10 | 0.00 | 0.00 |
Minimum of Months | 0.110258E+10 | 0.151658E+09 | 0.508955E+09 | 32293323.27 | 0.401082E+09 | 0.00 | 0.00 |
Maximum of Months | 0.241461E+10 | 0.130679E+10 | 0.172853E+10 | 0.129751E+10 | 0.538684E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115173E+10 | 0.645893E+09 | 0.843820E+09 | 0.639281E+09 | 0.204538E+09 | 0.00 | 0.00 |
February | 0.982394E+09 | 0.521834E+09 | 0.706988E+09 | 0.498416E+09 | 0.208572E+09 | 0.00 | 0.00 |
March | 0.909059E+09 | 0.509770E+09 | 0.636136E+09 | 0.366794E+09 | 0.269342E+09 | 0.00 | 0.00 |
April | 0.675912E+09 | 0.302829E+09 | 0.417385E+09 | 0.155737E+09 | 0.261648E+09 | 0.00 | 0.00 |
May | 0.550086E+09 | 0.183734E+09 | 0.304793E+09 | 42661081.85 | 0.262132E+09 | 0.00 | 0.00 |
June | 0.567410E+09 | 90399351.71 | 0.254477E+09 | 16146661.64 | 0.238331E+09 | 0.00 | 0.00 |
July | 0.595722E+09 | 76336948.54 | 0.268059E+09 | 24849499.09 | 0.243209E+09 | 0.00 | 0.00 |
August | 0.709437E+09 | 0.109658E+09 | 0.341701E+09 | 90450288.55 | 0.251251E+09 | 0.00 | 0.00 |
September | 0.970637E+09 | 0.202412E+09 | 0.516151E+09 | 0.268159E+09 | 0.247993E+09 | 0.00 | 0.00 |
October | 0.116117E+10 | 0.340990E+09 | 0.724674E+09 | 0.489928E+09 | 0.234746E+09 | 0.00 | 0.00 |
November | 0.119655E+10 | 0.541184E+09 | 0.843948E+09 | 0.643407E+09 | 0.200541E+09 | 0.00 | 0.00 |
December | 0.115594E+10 | 0.692902E+09 | 0.864264E+09 | 0.648756E+09 | 0.215508E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106260E+11 | 0.421794E+10 | 0.672240E+10 | 0.388458E+10 | 0.283781E+10 | 0.00 | 0.00 |
Minimum of Months | 0.550086E+09 | 76336948.54 | 0.254477E+09 | 16146661.64 | 0.200541E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119655E+10 | 0.692902E+09 | 0.864264E+09 | 0.648756E+09 | 0.269342E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115490E+10 | 0.625481E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.983468E+09 | 0.510315E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.909248E+09 | 0.503959E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.672205E+09 | 0.312923E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.542712E+09 | 0.200334E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.551921E+09 | 0.104402E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.579300E+09 | 91632699.97 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.696826E+09 | 0.126896E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965444E+09 | 0.224416E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115650E+10 | 0.354808E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.119646E+10 | 0.536117E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.115893E+10 | 0.672557E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105679E+11 | 0.426384E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.542712E+09 | 91632699.97 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119646E+10 | 0.672557E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.115915E+10 | 0.613567E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.986521E+09 | 0.502189E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.911574E+09 | 0.498094E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.672559E+09 | 0.311850E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.542316E+09 | 0.201413E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.550955E+09 | 0.106314E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.578228E+09 | 93662132.47 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.696002E+09 | 0.128996E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.964995E+09 | 0.226221E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115651E+10 | 0.354672E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.119817E+10 | 0.531380E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.116307E+10 | 0.661396E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105800E+11 | 0.422976E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.542316E+09 | 93662132.47 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.119817E+10 | 0.661396E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.116462E+10 | 0.601057E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.991104E+09 | 0.492528E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.915586E+09 | 0.490510E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.674342E+09 | 0.307500E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.543709E+09 | 0.198298E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.552370E+09 | 0.104074E+09 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.579409E+09 | 91493026.99 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.697031E+09 | 0.126578E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965855E+09 | 0.223543E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.115774E+10 | 0.351273E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120082E+10 | 0.525906E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.116847E+10 | 0.649736E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106111E+11 | 0.416250E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.543709E+09 | 91493026.99 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120082E+10 | 0.649736E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.235618E+10 | 0.115102E+10 | 0.168418E+10 | 0.127594E+10 | 0.408237E+09 | 0.00 | 0.00 |
February | 0.200589E+10 | 0.942593E+09 | 0.141108E+10 | 0.994786E+09 | 0.416289E+09 | 0.00 | 0.00 |
March | 0.185364E+10 | 0.943878E+09 | 0.126966E+10 | 0.732083E+09 | 0.537578E+09 | 0.00 | 0.00 |
April | 0.135902E+10 | 0.588729E+09 | 0.833057E+09 | 0.310835E+09 | 0.522223E+09 | 0.00 | 0.00 |
May | 0.109098E+10 | 0.374963E+09 | 0.608336E+09 | 85147127.19 | 0.523189E+09 | 0.00 | 0.00 |
June | 0.110798E+10 | 0.193761E+09 | 0.507911E+09 | 32227074.24 | 0.475683E+09 | 0.00 | 0.00 |
July | 0.115933E+10 | 0.168871E+09 | 0.535018E+09 | 49597041.79 | 0.485420E+09 | 0.00 | 0.00 |
August | 0.139412E+10 | 0.235521E+09 | 0.682000E+09 | 0.180529E+09 | 0.501470E+09 | 0.00 | 0.00 |
September | 0.193134E+10 | 0.426584E+09 | 0.103018E+10 | 0.535217E+09 | 0.494968E+09 | 0.00 | 0.00 |
October | 0.232267E+10 | 0.680298E+09 | 0.144638E+10 | 0.977846E+09 | 0.468529E+09 | 0.00 | 0.00 |
November | 0.241742E+10 | 0.102362E+10 | 0.168443E+10 | 0.128417E+10 | 0.400260E+09 | 0.00 | 0.00 |
December | 0.236383E+10 | 0.125053E+10 | 0.172498E+10 | 0.129485E+10 | 0.430132E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213624E+11 | 0.798037E+10 | 0.134172E+11 | 0.775323E+10 | 0.566398E+10 | 0.00 | 0.00 |
Minimum of Months | 0.109098E+10 | 0.168871E+09 | 0.507911E+09 | 32227074.24 | 0.400260E+09 | 0.00 | 0.00 |
Maximum of Months | 0.241742E+10 | 0.125053E+10 | 0.172498E+10 | 0.129485E+10 | 0.537578E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117618E+10 | 0.574737E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100128E+10 | 0.470838E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.924783E+09 | 0.471503E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.678915E+09 | 0.292818E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.547013E+09 | 0.184975E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.557792E+09 | 94359497.68 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.582803E+09 | 81855282.35 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.699203E+09 | 0.114944E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.965990E+09 | 0.210509E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116001E+10 | 0.338564E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120655E+10 | 0.511927E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118017E+10 | 0.624917E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106807E+11 | 0.397195E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.547013E+09 | 81855282.35 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120655E+10 | 0.624917E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.117845E+10 | 0.570139E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100330E+10 | 0.467011E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.926970E+09 | 0.467917E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.679900E+09 | 0.291087E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.547736E+09 | 0.183990E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.558475E+09 | 93730774.89 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.583432E+09 | 81245692.64 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.699716E+09 | 0.114314E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.966431E+09 | 0.209752E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116063E+10 | 0.337396E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.120794E+10 | 0.509587E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118211E+10 | 0.621172E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106951E+11 | 0.394734E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.547736E+09 | 81245692.64 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.120794E+10 | 0.621172E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.118387E+10 | 0.558060E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.100854E+10 | 0.456132E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.932840E+09 | 0.456834E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.682452E+09 | 0.285536E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.548974E+09 | 0.181502E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.558798E+09 | 92923816.52 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.583343E+09 | 80813474.68 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.699509E+09 | 0.114004E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.966507E+09 | 0.209106E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116188E+10 | 0.334436E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.121195E+10 | 0.502199E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.118697E+10 | 0.610980E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107256E+11 | 0.388253E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.548974E+09 | 80813474.68 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.121195E+10 | 0.610980E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.119518E+10 | 0.520997E+09 | 0.842088E+09 | 0.637970E+09 | 0.204119E+09 | 0.00 | 0.00 |
February | 0.102006E+10 | 0.421322E+09 | 0.705538E+09 | 0.497393E+09 | 0.208145E+09 | 0.00 | 0.00 |
March | 0.945098E+09 | 0.418968E+09 | 0.634831E+09 | 0.366042E+09 | 0.268789E+09 | 0.00 | 0.00 |
April | 0.686537E+09 | 0.264025E+09 | 0.416529E+09 | 0.155417E+09 | 0.261111E+09 | 0.00 | 0.00 |
May | 0.548424E+09 | 0.171334E+09 | 0.304168E+09 | 42573563.60 | 0.261595E+09 | 0.00 | 0.00 |
June | 0.553687E+09 | 90112630.72 | 0.253955E+09 | 16113537.12 | 0.237842E+09 | 0.00 | 0.00 |
July | 0.576060E+09 | 80573578.31 | 0.267509E+09 | 24798520.89 | 0.242710E+09 | 0.00 | 0.00 |
August | 0.692316E+09 | 0.114476E+09 | 0.341000E+09 | 90264731.81 | 0.250735E+09 | 0.00 | 0.00 |
September | 0.961255E+09 | 0.208517E+09 | 0.515092E+09 | 0.267608E+09 | 0.247484E+09 | 0.00 | 0.00 |
October | 0.116284E+10 | 0.323318E+09 | 0.723188E+09 | 0.488923E+09 | 0.234265E+09 | 0.00 | 0.00 |
November | 0.122060E+10 | 0.476606E+09 | 0.842216E+09 | 0.642087E+09 | 0.200130E+09 | 0.00 | 0.00 |
December | 0.119754E+10 | 0.578536E+09 | 0.862491E+09 | 0.647425E+09 | 0.215066E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107596E+11 | 0.366879E+10 | 0.670861E+10 | 0.387662E+10 | 0.283199E+10 | 0.00 | 0.00 |
Minimum of Months | 0.548424E+09 | 80573578.31 | 0.253955E+09 | 16113537.12 | 0.200130E+09 | 0.00 | 0.00 |
Maximum of Months | 0.122060E+10 | 0.578536E+09 | 0.862491E+09 | 0.647425E+09 | 0.268789E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 8.14 | 3.28 | -3.0 | 3.49 | -5.4 | 41.12 | 223.64 | 0.00 |
February | 10.27 | 3.71 | -4.6 | 3.82 | -5.0 | 51.61 | 245.22 | 0.00 |
March | 12.55 | 4.68 | -5.5 | 4.62 | -3.1 | 72.41 | 273.25 | 0.00 |
April | 19.23 | 8.50 | -2.7 | 4.72 | 3.38 | 79.21 | 314.56 | 0.00 |
May | 23.84 | 12.23 | 2.64 | 5.25 | 8.38 | 86.83 | 326.20 | 0.00 |
June | 27.86 | 15.03 | 5.88 | 4.15 | 14.09 | 80.19 | 344.14 | 0.01 |
July | 27.54 | 18.92 | 14.64 | 3.53 | 17.44 | 86.25 | 283.04 | 0.01 |
August | 26.28 | 17.11 | 12.00 | 3.28 | 15.48 | 80.55 | 269.68 | 0.02 |
September | 23.38 | 15.82 | 11.20 | 2.23 | 11.29 | 66.71 | 294.09 | 0.00 |
October | 18.30 | 12.02 | 7.27 | 3.24 | 6.21 | 54.59 | 257.93 | 0.01 |
November | 11.18 | 5.22 | -1.5 | 3.40 | -3.3 | 40.23 | 258.80 | 0.00 |
December | 6.79 | 1.84 | -4.8 | 2.82 | -8.9 | 42.65 | 217.21 | 0.00 |
Annual Sum or Average | 17.98 | 9.90 | 2.67 | 3.71 | 4.26 | 65.29 | 275.60 | 0.00 |
Minimum of Months | 6.79 | 1.84 | -5.5 | 2.23 | -8.9 | 40.23 | 217.21 | 0.00 |
Maximum of Months | 27.86 | 18.92 | 14.64 | 5.25 | 17.44 | 86.83 | 344.14 | 0.02 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.60 | 03-JAN-14:00 | 8.39 | -5.0 | 9.80 | 2.22 | 118.50 | 530.50 |
February | 23.30 | 20-FEB-14:00 | 8.88 | -7.8 | 4.10 | 4.10 | 55.00 | 955.00 |
March | 25.00 | 21-MAR-15:00 | 9.53 | -8.3 | 6.20 | 5.54 | 50.00 | 873.00 |
April | 32.20 | 21-APR-13:00 | 15.21 | 2.80 | 13.90 | 18.28 | 265.50 | 638.50 |
May | 35.00 | 19-MAY-13:00 | 17.23 | 6.10 | 10.30 | 21.78 | 145.00 | 874.50 |
June | 38.90 | 02-JUN-15:00 | 16.22 | -1.1 | 4.60 | 20.40 | 234.50 | 284.00 |
July | 38.30 | 01-JUL-16:00 | 19.19 | 8.90 | 3.60 | 26.81 | 165.50 | 256.50 |
August | 37.20 | 07-AUG-15:00 | 17.89 | 6.70 | 5.70 | 24.66 | 143.50 | 615.00 |
September | 33.90 | 19-SEP-13:00 | 16.85 | 6.70 | 3.10 | 17.75 | 113.00 | 912.00 |
October | 32.80 | 01-OCT-14:00 | 15.90 | 4.40 | 5.70 | 16.12 | 127.50 | 736.50 |
November | 23.90 | 03-NOV-15:00 | 13.45 | 6.10 | 5.70 | 12.22 | 48.50 | 648.50 |
December | 18.30 | 10-DEC-14:00 | 7.97 | -2.8 | 7.20 | 4.10 | 123.00 | 52.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 18.30 | 7.97 | -8.3 | 3.10 | 2.22 | 48.50 | 52.50 | |
Maximum of Months | 38.90 | 19.19 | 8.90 | 13.90 | 26.81 | 265.50 | 955.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -4.4 | 27-JAN-06:00 | -7.5 | -15.0 | 3.60 | -23.6 | 0.00 | 0.00 |
February | -5.6 | 03-FEB-06:00 | -7.5 | -11.7 | 1.50 | -23.9 | 0.00 | 0.00 |
March | -3.9 | 02-MAR-04:00 | -6.5 | -12.8 | 1.50 | -21.3 | 0.00 | 0.00 |
April | 3.30 | 12-APR-05:00 | -1.8 | -9.4 | 2.10 | -14.9 | 37.00 | 217.50 |
May | 9.40 | 02-MAY-05:00 | 3.98 | -2.2 | 3.60 | -7.6 | 51.00 | 277.50 |
June | 15.00 | 13-JUN-04:00 | 4.43 | -10.6 | 2.10 | -4.3 | 0.00 | 0.00 |
July | 17.80 | 05-JUL-05:00 | 15.98 | 15.00 | 4.10 | 4.31 | 39.00 | 249.00 |
August | 16.70 | 31-AUG-05:00 | 13.89 | 12.20 | 4.10 | 2.64 | 36.00 | 126.50 |
September | 8.30 | 30-SEP-05:00 | 5.77 | 3.30 | 1.50 | -7.3 | 0.00 | 0.00 |
October | 6.70 | 11-OCT-05:00 | 5.82 | 5.00 | 1.50 | -5.5 | 0.00 | 0.00 |
November | -0.6 | 17-NOV-03:00 | -3.1 | -6.7 | 1.50 | -18.1 | 0.00 | 0.00 |
December | -4.4 | 27-DEC-06:00 | -5.1 | -6.1 | 2.10 | -18.6 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -5.6 | -7.5 | -15.0 | 1.50 | -23.9 | 0.00 | 0.00 | |
Maximum of Months | 17.80 | 15.98 | 15.00 | 4.10 | 4.31 | 51.00 | 277.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 10.18 | 12-JAN-15:00 | 18.90 | 2.80 | 3.60 | 6.15 | 70.50 | 491.50 |
February | 11.42 | 13-FEB-16:00 | 12.80 | 10.60 | 4.10 | 6.55 | 34.00 | 18.50 |
March | 10.75 | 10-MAR-18:00 | 13.30 | 8.90 | 1.50 | 8.54 | 0.00 | 0.00 |
April | 15.74 | 29-APR-13:00 | 30.00 | 6.70 | 4.10 | 18.28 | 336.50 | 432.50 |
May | 19.12 | 24-MAY-12:00 | 27.80 | 15.00 | 5.20 | 17.57 | 188.50 | 862.00 |
June | 20.21 | 03-JUN-14:00 | 33.90 | 13.90 | 8.80 | 23.66 | 264.50 | 316.00 |
July | 22.88 | 20-JUL-15:39 | 25.53 | 21.87 | 2.93 | 18.99 | 184.00 | 15.83 |
August | 21.18 | 02-AUG-11:00 | 30.60 | 17.20 | 3.60 | 20.75 | 154.50 | 850.00 |
September | 20.65 | 14-SEP-09:00 | 25.00 | 18.90 | 2.10 | 14.47 | 126.50 | 835.50 |
October | 19.64 | 03-OCT-13:00 | 32.80 | 13.30 | 2.60 | 21.44 | 224.50 | 577.50 |
November | 13.57 | 03-NOV-14:00 | 23.30 | 7.20 | 0.00 | 10.88 | 72.50 | 802.00 |
December | 8.30 | 10-DEC-12:00 | 17.20 | -0.6 | 5.70 | 1.58 | 198.50 | 507.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 8.30 | 12.80 | -0.6 | 0.00 | 1.58 | 0.00 | 0.00 | |
Maximum of Months | 22.88 | 33.90 | 21.87 | 8.80 | 23.66 | 336.50 | 862.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 9.00 | 16-JAN-01:00 | 9.00 | 9.00 | 2.10 | 4.51 | 0.00 | 0.00 |
February | 10.60 | 13-FEB-13:09 | 12.20 | 11.24 | 5.53 | 5.71 | 147.33 | 0.00 |
March | 10.00 | 11-MAR-00:00 | 10.60 | 10.24 | 2.10 | 6.15 | 0.00 | 0.00 |
April | 10.60 | 17-APR-01:00 | 17.80 | 13.38 | 7.20 | 3.48 | 0.00 | 0.00 |
May | 15.00 | 24-MAY-10:00 | 25.60 | 18.41 | 7.20 | 15.39 | 171.00 | 872.50 |
June | 17.20 | 19-JUN-17:00 | 23.90 | 19.20 | 3.60 | 15.39 | 86.00 | 324.00 |
July | 22.20 | 20-JUL-14:00 | 24.40 | 22.82 | 4.60 | 17.93 | 283.00 | 59.50 |
August | 18.90 | 01-AUG-20:00 | 22.20 | 19.91 | 4.60 | 17.75 | 0.00 | 0.00 |
September | 19.40 | 22-SEP-01:00 | 20.60 | 19.76 | 1.50 | 16.30 | 0.00 | 0.00 |
October | 17.20 | 03-OCT-19:00 | 23.30 | 19.11 | 4.60 | 18.46 | 0.00 | 0.00 |
November | 10.00 | 01-NOV-09:00 | 13.30 | 11.28 | 3.10 | 8.94 | 123.50 | 0.00 |
December | 6.10 | 13-DEC-00:00 | 8.30 | 7.10 | 7.70 | 3.06 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 6.10 | 8.30 | 7.10 | 1.50 | 3.06 | 0.00 | 0.00 | |
Maximum of Months | 22.20 | 25.60 | 22.82 | 7.70 | 18.46 | 283.00 | 872.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 15.16 | 28.38 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 15.21 | 35.58 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 16.80 | 47.71 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 19.62 | 58.45 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 22.88 | 63.58 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 25.71 | 66.73 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 27.35 | 58.19 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 27.33 | 54.44 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 25.68 | 50.89 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 22.83 | 39.37 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 19.57 | 32.11 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 16.77 | 26.90 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 21.28 | 46.90 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 15.16 | 26.90 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 27.35 | 66.73 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.335251E+09 | -215183966.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120067298.3 | 58.99 | 0.00 | 0.00 |
February | 0.302434E+09 | -195221677.8 | 0.00 | 0.00 | 672.00 | 0.00 | -107212245.5 | 58.99 | 0.00 | 0.00 |
March | 0.328594E+09 | -211649659.1 | 0.00 | 0.00 | 744.00 | 0.00 | -116944371.5 | 58.99 | 0.00 | 0.00 |
April | 0.299022E+09 | -188708080.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110314371.4 | 58.99 | 0.00 | 0.00 |
May | 0.291883E+09 | -179190940.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112692205.2 | 58.99 | 0.00 | 0.00 |
June | 0.269448E+09 | -161371480.0 | 0.00 | 0.00 | 720.00 | 0.00 | -108076594.5 | 58.99 | 0.00 | 0.00 |
July | 0.266655E+09 | -155342399.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111312133.4 | 58.99 | 0.00 | 0.00 |
August | 0.270149E+09 | -158727777.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111421182.2 | 58.99 | 0.00 | 0.00 |
September | 0.268144E+09 | -159855740.6 | 0.00 | 0.00 | 720.00 | 0.00 | -108288080.4 | 58.99 | 0.00 | 0.00 |
October | 0.290474E+09 | -177582926.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112891400.7 | 58.99 | 0.00 | 0.00 |
November | 0.299020E+09 | -186792121.3 | 0.00 | 0.00 | 720.00 | 0.00 | -112227883.5 | 58.99 | 0.00 | 0.00 |
December | 0.328286E+09 | -207562714.0 | 0.00 | 0.00 | 744.00 | 0.00 | -120722974.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.354936E+10 | -0.219719E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135217E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.266655E+09 | -215183966.0 | 0.00 | 0.00 | 672.00 | 0.00 | -120722974.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.335251E+09 | -155342399.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107212245.5 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.332171E+09 | -215182026.2 | 0.00 | 0.00 | 744.00 | 0.00 | -116988542.5 | 59.00 | 0.00 | 0.00 |
February | 0.300049E+09 | -195221684.5 | 0.00 | 0.00 | 672.00 | 0.00 | -104827213.9 | 58.99 | 0.00 | 0.00 |
March | 0.326762E+09 | -211649745.0 | 0.00 | 0.00 | 744.00 | 0.00 | -115111956.5 | 58.99 | 0.00 | 0.00 |
April | 0.298450E+09 | -188702791.2 | 0.00 | 0.00 | 720.00 | 0.00 | -109747437.8 | 58.99 | 0.00 | 0.00 |
May | 0.291614E+09 | -179184785.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112429123.0 | 58.99 | 0.00 | 0.00 |
June | 0.269284E+09 | -161383096.0 | 0.00 | 0.00 | 720.00 | 0.00 | -107900723.0 | 58.99 | 0.00 | 0.00 |
July | 0.266539E+09 | -155316387.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111222569.0 | 58.99 | 0.00 | 0.00 |
August | 0.270107E+09 | -158691903.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111415478.3 | 59.00 | 0.00 | 0.00 |
September | 0.268212E+09 | -159858765.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108353613.6 | 58.99 | 0.00 | 0.00 |
October | 0.290263E+09 | -177589102.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112673901.4 | 58.99 | 0.00 | 0.00 |
November | 0.297668E+09 | -186791073.9 | 0.00 | 0.00 | 720.00 | 0.00 | -110877240.8 | 58.99 | 0.00 | 0.00 |
December | 0.325196E+09 | -207554896.3 | 0.00 | 0.00 | 744.00 | 0.00 | -117641367.6 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.353632E+10 | -0.219713E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133919E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.266539E+09 | -215182026.2 | 0.00 | 0.00 | 672.00 | 0.00 | -117641367.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.332171E+09 | -155316387.9 | 0.00 | 0.00 | 744.00 | 0.00 | -104827213.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.307986E+09 | -189230705.7 | 0.00 | 0.00 | 744.00 | 0.00 | -118755048.8 | 58.99 | 0.00 | 0.00 |
February | 0.277630E+09 | -171812622.5 | 0.00 | 0.00 | 672.00 | 0.00 | -105816895.1 | 58.99 | 0.00 | 0.00 |
March | 0.304476E+09 | -188879892.1 | 0.00 | 0.00 | 744.00 | 0.00 | -115596035.3 | 58.99 | 0.00 | 0.00 |
April | 0.274595E+09 | -165980459.3 | 0.00 | 0.00 | 720.00 | 0.00 | -108614543.8 | 58.99 | 0.00 | 0.00 |
May | 0.269448E+09 | -158965812.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110481768.3 | 58.99 | 0.00 | 0.00 |
June | 0.249290E+09 | -143691769.5 | 0.00 | 0.00 | 720.00 | 0.00 | -105598154.9 | 59.00 | 0.00 | 0.00 |
July | 0.244473E+09 | -135787754.5 | 0.00 | 0.00 | 744.00 | 0.00 | -108685454.9 | 58.99 | 0.00 | 0.00 |
August | 0.250805E+09 | -141766168.3 | 0.00 | 0.00 | 744.00 | 0.00 | -109038874.3 | 58.99 | 0.00 | 0.00 |
September | 0.246746E+09 | -140518103.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106227859.0 | 58.99 | 0.00 | 0.00 |
October | 0.267534E+09 | -156190714.7 | 0.00 | 0.00 | 744.00 | 0.00 | -111343210.5 | 58.99 | 0.00 | 0.00 |
November | 0.276226E+09 | -164918260.4 | 0.00 | 0.00 | 720.00 | 0.00 | -111307616.8 | 58.99 | 0.00 | 0.00 |
December | 0.300593E+09 | -181170871.7 | 0.00 | 0.00 | 744.00 | 0.00 | -119422318.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.326980E+10 | -0.193891E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133089E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244473E+09 | -189230705.7 | 0.00 | 0.00 | 672.00 | 0.00 | -119422318.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.307986E+09 | -135787754.5 | 0.00 | 0.00 | 744.00 | 0.00 | -105598154.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.308742E+09 | -189229815.4 | 0.00 | 0.00 | 744.00 | 0.00 | -119512510.8 | 58.99 | 0.00 | 0.00 |
February | 0.278147E+09 | -171822535.9 | 0.00 | 0.00 | 672.00 | 0.00 | -106324538.5 | 58.99 | 0.00 | 0.00 |
March | 0.304843E+09 | -188891155.3 | 0.00 | 0.00 | 744.00 | 0.00 | -115951546.2 | 58.99 | 0.00 | 0.00 |
April | 0.274653E+09 | -165941968.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108711280.9 | 59.00 | 0.00 | 0.00 |
May | 0.269386E+09 | -158966251.2 | 0.00 | 0.00 | 744.00 | 0.00 | -110420025.1 | 58.99 | 0.00 | 0.00 |
June | 0.249157E+09 | -143717507.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105439946.5 | 58.99 | 0.00 | 0.00 |
July | 0.244336E+09 | -135786292.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108549879.3 | 58.99 | 0.00 | 0.00 |
August | 0.250676E+09 | -141761679.1 | 0.00 | 0.00 | 744.00 | 0.00 | -108914417.2 | 58.99 | 0.00 | 0.00 |
September | 0.246642E+09 | -140495130.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106147062.4 | 59.00 | 0.00 | 0.00 |
October | 0.267541E+09 | -156189470.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111351165.9 | 58.99 | 0.00 | 0.00 |
November | 0.276516E+09 | -164929514.9 | 0.00 | 0.00 | 720.00 | 0.00 | -111586132.6 | 58.99 | 0.00 | 0.00 |
December | 0.301313E+09 | -181166754.2 | 0.00 | 0.00 | 744.00 | 0.00 | -120146003.4 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.327195E+10 | -0.193890E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.133305E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.244336E+09 | -189229815.4 | 0.00 | 0.00 | 672.00 | 0.00 | -120146003.4 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.308742E+09 | -135786292.8 | 0.00 | 0.00 | 744.00 | 0.00 | -105439946.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301040E+09 | -178861575.1 | 0.00 | 0.00 | 744.00 | 0.00 | -122178431.0 | 58.99 | 0.00 | 0.00 |
February | 0.271013E+09 | -162482266.4 | 0.00 | 0.00 | 672.00 | 0.00 | -108530610.7 | 58.99 | 0.00 | 0.00 |
March | 0.296490E+09 | -178734166.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117755581.2 | 58.99 | 0.00 | 0.00 |
April | 0.266954E+09 | -157059703.6 | 0.00 | 0.00 | 720.00 | 0.00 | -109894346.6 | 58.99 | 0.00 | 0.00 |
May | 0.261795E+09 | -150349186.0 | 0.00 | 0.00 | 744.00 | 0.00 | -111445353.5 | 58.98 | 0.00 | 0.00 |
June | 0.242338E+09 | -135984842.9 | 0.00 | 0.00 | 720.00 | 0.00 | -106353240.5 | 58.99 | 0.00 | 0.00 |
July | 0.237736E+09 | -128415716.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109320059.2 | 58.99 | 0.00 | 0.00 |
August | 0.243878E+09 | -134148974.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109729213.6 | 58.99 | 0.00 | 0.00 |
September | 0.239912E+09 | -132982571.2 | 0.00 | 0.00 | 720.00 | 0.00 | -106929749.2 | 58.99 | 0.00 | 0.00 |
October | 0.259906E+09 | -147636881.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112269469.5 | 58.99 | 0.00 | 0.00 |
November | 0.268701E+09 | -155745520.3 | 0.00 | 0.00 | 720.00 | 0.00 | -112954992.6 | 59.00 | 0.00 | 0.00 |
December | 0.294063E+09 | -171337738.6 | 0.00 | 0.00 | 744.00 | 0.00 | -122725195.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.318383E+10 | -0.183374E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135009E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.237736E+09 | -178861575.1 | 0.00 | 0.00 | 672.00 | 0.00 | -122725195.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.301040E+09 | -128415716.8 | 0.00 | 0.00 | 744.00 | 0.00 | -106353240.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301156E+09 | -178858535.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122297456.3 | 58.99 | 0.00 | 0.00 |
February | 0.271085E+09 | -162478530.4 | 0.00 | 0.00 | 672.00 | 0.00 | -108606877.2 | 58.99 | 0.00 | 0.00 |
March | 0.296540E+09 | -178704409.6 | 0.00 | 0.00 | 744.00 | 0.00 | -117835825.8 | 59.00 | 0.00 | 0.00 |
April | 0.266992E+09 | -157056766.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109934797.7 | 58.99 | 0.00 | 0.00 |
May | 0.261881E+09 | -150326926.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111554198.6 | 58.99 | 0.00 | 0.00 |
June | 0.242478E+09 | -135988236.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106489814.5 | 58.99 | 0.00 | 0.00 |
July | 0.237871E+09 | -128425149.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109446228.5 | 58.99 | 0.00 | 0.00 |
August | 0.244012E+09 | -134128750.6 | 0.00 | 0.00 | 744.00 | 0.00 | -109883602.2 | 58.99 | 0.00 | 0.00 |
September | 0.240034E+09 | -132989467.7 | 0.00 | 0.00 | 720.00 | 0.00 | -107044274.8 | 58.99 | 0.00 | 0.00 |
October | 0.259976E+09 | -147643411.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112332294.2 | 58.99 | 0.00 | 0.00 |
November | 0.268707E+09 | -155759210.0 | 0.00 | 0.00 | 720.00 | 0.00 | -112947800.4 | 58.99 | 0.00 | 0.00 |
December | 0.294151E+09 | -171354939.7 | 0.00 | 0.00 | 744.00 | 0.00 | -122795616.0 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.318488E+10 | -0.183371E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135117E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.237871E+09 | -178858535.4 | 0.00 | 0.00 | 672.00 | 0.00 | -122795616.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.301156E+09 | -128425149.6 | 0.00 | 0.00 | 744.00 | 0.00 | -106489814.5 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.301466E+09 | -178845411.3 | 0.00 | 0.00 | 744.00 | 0.00 | -122621024.9 | 59.00 | 0.00 | 0.00 |
February | 0.271336E+09 | -162472948.8 | 0.00 | 0.00 | 672.00 | 0.00 | -108863206.0 | 58.99 | 0.00 | 0.00 |
March | 0.296785E+09 | -178742620.4 | 0.00 | 0.00 | 744.00 | 0.00 | -118042427.0 | 58.99 | 0.00 | 0.00 |
April | 0.267096E+09 | -157058781.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110036967.5 | 58.99 | 0.00 | 0.00 |
May | 0.261940E+09 | -150352321.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111587461.0 | 58.98 | 0.00 | 0.00 |
June | 0.242527E+09 | -135983097.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106544232.6 | 58.99 | 0.00 | 0.00 |
July | 0.237914E+09 | -128430302.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109483285.4 | 58.99 | 0.00 | 0.00 |
August | 0.244063E+09 | -134143676.5 | 0.00 | 0.00 | 744.00 | 0.00 | -109919556.6 | 58.99 | 0.00 | 0.00 |
September | 0.240071E+09 | -132991833.9 | 0.00 | 0.00 | 720.00 | 0.00 | -107079565.3 | 58.99 | 0.00 | 0.00 |
October | 0.260046E+09 | -147630972.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112415129.3 | 58.99 | 0.00 | 0.00 |
November | 0.268867E+09 | -155757170.9 | 0.00 | 0.00 | 720.00 | 0.00 | -113109888.2 | 58.99 | 0.00 | 0.00 |
December | 0.294398E+09 | -171354014.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123044434.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.318651E+10 | -0.183376E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.135275E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.237914E+09 | -178845411.3 | 0.00 | 0.00 | 672.00 | 0.00 | -123044434.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.301466E+09 | -128430302.8 | 0.00 | 0.00 | 744.00 | 0.00 | -106544232.6 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 276.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 351.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 373.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 398.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 400.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 377.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 365.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 295.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 289.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4125.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 268.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 408.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.655977E+09 | 62954.66 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.372662E+09 | 62954.66 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.179249E+09 | 62954.66 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 237621.35 | 339.20 | 11-APR-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.171352E+09 | 34889.32 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.131625E+10 | 62954.66 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.269573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.131625E+10 | 62954.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 49827522.45 | 9732.51 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 26273925.47 | 4914.51 | 03-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 12715681.99 | 7535.09 | 02-MAR-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 717534.28 | 2150.13 | 14-APR-21:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 98953.12 | 329.84 | 07-MAY-21:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 10840231.89 | 3361.56 | 28-NOV-09:06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.184410E+09 | 10395.19 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.284884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.184410E+09 | 10395.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.194402E+09 | 18840.60 | 28-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 95804655.15 | 13447.80 | 03-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 39466893.46 | 6070.35 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 46442897.81 | 3946.16 | 28-NOV-08:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.429961E+09 | 22291.58 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.806078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.429961E+09 | 22291.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.263969E+09 | 24119.55 | 28-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.119300E+09 | 18353.26 | 03-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 51769692.20 | 11937.07 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66109356.20 | 5281.05 | 28-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.523781E+09 | 28825.60 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.102493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.523781E+09 | 28825.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.376078E+09 | 30480.00 | 28-JAN-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.168106E+09 | 24863.27 | 03-FEB-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 75968691.86 | 19870.92 | 02-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 93211757.88 | 8407.66 | 28-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.668371E+09 | 32562.66 | 27-DEC-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.138174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.668371E+09 | 32562.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.953617E+09 | 58931.85 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.396098E+09 | 58931.85 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.183504E+09 | 58931.85 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.275272E+09 | 46027.45 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.158804E+10 | 58931.85 | 04-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.339653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.158804E+10 | 58931.85 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.497515E+09 | 30435.45 | 27-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.204050E+09 | 30435.45 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 96047250.24 | 30435.45 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138936E+09 | 24112.71 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.816279E+09 | 30435.45 | 04-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.175283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.816279E+09 | 30435.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.555868E+09 | 30322.50 | 09-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.234165E+09 | 30322.50 | 02-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.111644E+09 | 30322.50 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.151479E+09 | 26317.68 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.877063E+09 | 30322.50 | 04-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.877063E+09 | 30322.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.737599E+09 | 30342.80 | 07-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.340053E+09 | 30342.80 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.173618E+09 | 30342.80 | 02-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 520812.57 | 611.40 | 11-APR-08:25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.190959E+09 | 30342.80 | 28-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.106128E+10 | 30342.80 | 04-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.250403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.106128E+10 | 30342.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.125323E+10 | 33638.10 | 05-JAN-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.674059E+09 | 33638.10 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.380061E+09 | 33638.10 | 01-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 6938477.41 | 2648.85 | 11-APR-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.292233E+09 | 33638.10 | 27-NOV-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.152242E+10 | 33638.10 | 03-DEC-10:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.412894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.152242E+10 | 33638.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2817349.10 | 2817349.10 | 1188.00 | 03-JAN-15:00 | 1188.00 | 0.00 |
February | 0.00 | 0.00 | 0.511020E+09 | 0.511020E+09 | 8788.85 | 20-FEB-16:00 | 8788.85 | 0.00 |
March | 0.00 | 0.00 | 0.141218E+10 | 0.141218E+10 | 10502.40 | 14-MAR-16:20 | 10502.40 | 0.00 |
April | 0.00 | 0.00 | 0.107325E+11 | 0.107122E+11 | 47216.12 | 29-APR-08:62 | 43666.69 | 0.00 |
May | 0.00 | 0.00 | 0.205702E+11 | 0.200639E+11 | 49408.54 | 25-MAY-08:62 | 33371.66 | 0.00 |
June | 0.00 | 0.00 | 0.285173E+11 | 0.276173E+11 | 49975.56 | 30-JUN-08:61 | 36784.73 | 0.00 |
July | 0.00 | 0.00 | 0.338994E+11 | 0.285681E+11 | 54010.70 | 19-JUL-08:61 | 29009.85 | 0.00 |
August | 0.00 | 0.00 | 0.296562E+11 | 0.265657E+11 | 52989.08 | 02-AUG-08:61 | 34043.95 | 0.00 |
September | 0.00 | 0.00 | 0.248611E+11 | 0.219719E+11 | 52061.67 | 22-SEP-08:61 | 31490.91 | 0.00 |
October | 0.00 | 0.00 | 0.112369E+11 | 0.102093E+11 | 50928.26 | 04-OCT-08:61 | 31877.92 | 0.00 |
November | 0.00 | 0.00 | 0.891627E+09 | 0.886329E+09 | 45825.06 | 10-NOV-09:02 | 42926.26 | 0.00 |
December | 0.00 | 0.00 | 2990.76 | 2990.76 | 2.20 | 09-DEC-19:40 | 2.20 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.162291E+12 | 0.148521E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 2990.76 | 2990.76 | 2.20 | 2.20 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.338994E+11 | 0.285681E+11 | 54010.70 | 43666.69 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 31293170.61 | 31210261.92 | 23497.57 | 03-JAN-21:10 | 23497.57 | 0.00 |
February | 0.00 | 0.00 | 0.417298E+09 | 0.417282E+09 | 23497.57 | 19-FEB-18:35 | 23497.57 | 0.00 |
March | 0.00 | 0.00 | 0.104834E+10 | 0.104825E+10 | 23497.57 | 12-MAR-17:01 | 23497.57 | 0.00 |
April | 0.00 | 0.00 | 0.630658E+10 | 0.629095E+10 | 24384.66 | 18-APR-20:59 | 22016.65 | 0.00 |
May | 0.00 | 0.00 | 0.110508E+11 | 0.107447E+11 | 25450.56 | 27-MAY-21:00 | 19386.55 | 0.00 |
June | 0.00 | 0.00 | 0.144043E+11 | 0.139257E+11 | 25611.94 | 30-JUN-08:61 | 19293.74 | 0.00 |
July | 0.00 | 0.00 | 0.168921E+11 | 0.143271E+11 | 27150.19 | 19-JUL-08:61 | 17338.13 | 0.00 |
August | 0.00 | 0.00 | 0.150360E+11 | 0.134262E+11 | 26927.17 | 03-AUG-08:61 | 18215.08 | 0.00 |
September | 0.00 | 0.00 | 0.133456E+11 | 0.117761E+11 | 26646.27 | 22-SEP-08:61 | 16580.10 | 0.00 |
October | 0.00 | 0.00 | 0.665529E+10 | 0.602036E+10 | 26408.87 | 03-OCT-20:01 | 15996.86 | 0.00 |
November | 0.00 | 0.00 | 0.623290E+09 | 0.619602E+09 | 23562.48 | 10-NOV-09:02 | 22235.99 | 0.00 |
December | 0.00 | 0.00 | 11048367.58 | 11035340.13 | 1857.69 | 16-DEC-19:20 | 1857.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.858219E+11 | 0.786384E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 11048367.58 | 11035340.13 | 1857.69 | 1857.69 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.168921E+11 | 0.143271E+11 | 27150.19 | 23497.57 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 3183653.42 | 3183653.42 | 818.54 | 03-JAN-15:00 | 818.54 | 0.00 |
February | 0.00 | 0.00 | 0.271672E+09 | 0.271672E+09 | 4471.98 | 20-FEB-15:00 | 4471.98 | 0.00 |
March | 0.00 | 0.00 | 0.790063E+09 | 0.790063E+09 | 5822.24 | 22-MAR-13:00 | 5822.24 | 0.00 |
April | 0.00 | 0.00 | 0.438752E+10 | 0.437861E+10 | 24138.64 | 29-APR-07:02 | 22344.83 | 0.00 |
May | 0.00 | 0.00 | 0.837742E+10 | 0.817640E+10 | 25855.03 | 28-MAY-08:61 | 19842.60 | 0.00 |
June | 0.00 | 0.00 | 0.114579E+11 | 0.110913E+11 | 25952.08 | 04-JUN-08:61 | 21042.24 | 0.00 |
July | 0.00 | 0.00 | 0.133541E+11 | 0.112314E+11 | 27605.14 | 21-JUL-07:01 | 17456.89 | 0.00 |
August | 0.00 | 0.00 | 0.118476E+11 | 0.105321E+11 | 27438.34 | 03-AUG-07:01 | 15914.05 | 0.00 |
September | 0.00 | 0.00 | 0.103218E+11 | 0.914863E+10 | 26889.20 | 23-SEP-07:01 | 16118.72 | 0.00 |
October | 0.00 | 0.00 | 0.487871E+10 | 0.446020E+10 | 26198.74 | 04-OCT-07:01 | 16242.27 | 0.00 |
November | 0.00 | 0.00 | 0.480363E+09 | 0.477083E+09 | 23802.22 | 10-NOV-08:62 | 22388.66 | 0.00 |
December | 0.00 | 0.00 | 620.66 | 620.66 | 0.11 | 17-DEC-16:20 | 0.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.661704E+11 | 0.605606E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 620.66 | 620.66 | 0.11 | 0.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.133541E+11 | 0.112314E+11 | 27605.14 | 22388.66 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 1543410.10 | 1543410.10 | 597.22 | 03-JAN-15:00 | 597.22 | 0.00 |
February | 0.00 | 0.00 | 0.246150E+09 | 0.246150E+09 | 4224.76 | 20-FEB-15:00 | 4224.76 | 0.00 |
March | 0.00 | 0.00 | 0.748785E+09 | 0.748785E+09 | 5676.75 | 22-MAR-13:00 | 5676.75 | 0.00 |
April | 0.00 | 0.00 | 0.435391E+10 | 0.434507E+10 | 23993.48 | 29-APR-07:02 | 22216.01 | 0.00 |
May | 0.00 | 0.00 | 0.840012E+10 | 0.819797E+10 | 25702.21 | 28-MAY-08:61 | 19744.36 | 0.00 |
June | 0.00 | 0.00 | 0.115147E+11 | 0.111456E+11 | 25792.73 | 04-JUN-08:61 | 20927.90 | 0.00 |
July | 0.00 | 0.00 | 0.134201E+11 | 0.112899E+11 | 27435.11 | 21-JUL-07:01 | 17360.38 | 0.00 |
August | 0.00 | 0.00 | 0.119129E+11 | 0.105898E+11 | 27279.10 | 03-AUG-07:01 | 15799.86 | 0.00 |
September | 0.00 | 0.00 | 0.103710E+11 | 0.919189E+10 | 26735.01 | 23-SEP-07:01 | 15996.78 | 0.00 |
October | 0.00 | 0.00 | 0.487139E+10 | 0.445378E+10 | 26043.16 | 04-OCT-07:01 | 16162.40 | 0.00 |
November | 0.00 | 0.00 | 0.462881E+09 | 0.459702E+09 | 23658.61 | 10-NOV-08:62 | 22250.68 | 0.00 |
December | 0.00 | 0.00 | 524.39 | 524.39 | 0.11 | 20-DEC-15:40 | 0.11 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.663035E+11 | 0.606701E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 524.39 | 524.39 | 0.11 | 0.11 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134201E+11 | 0.112899E+11 | 27435.11 | 22250.68 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 331875.59 | 331875.59 | 277.95 | 03-JAN-15:00 | 277.95 | 0.00 |
February | 0.00 | 0.00 | 0.208276E+09 | 0.208276E+09 | 3900.51 | 20-FEB-15:00 | 3900.51 | 0.00 |
March | 0.00 | 0.00 | 0.672653E+09 | 0.672653E+09 | 5407.25 | 22-MAR-13:00 | 5407.25 | 0.00 |
April | 0.00 | 0.00 | 0.419417E+10 | 0.418580E+10 | 24056.39 | 29-APR-07:02 | 22231.67 | 0.00 |
May | 0.00 | 0.00 | 0.821181E+10 | 0.801369E+10 | 25773.27 | 28-MAY-08:61 | 19762.66 | 0.00 |
June | 0.00 | 0.00 | 0.113471E+11 | 0.109851E+11 | 25874.22 | 04-JUN-08:61 | 20967.65 | 0.00 |
July | 0.00 | 0.00 | 0.132523E+11 | 0.111416E+11 | 27535.77 | 21-JUL-07:01 | 17342.27 | 0.00 |
August | 0.00 | 0.00 | 0.117387E+11 | 0.104345E+11 | 27343.05 | 03-AUG-07:01 | 15898.65 | 0.00 |
September | 0.00 | 0.00 | 0.101975E+11 | 0.903465E+10 | 26796.58 | 23-SEP-07:01 | 16100.80 | 0.00 |
October | 0.00 | 0.00 | 0.472788E+10 | 0.432231E+10 | 26116.11 | 04-OCT-07:01 | 16168.65 | 0.00 |
November | 0.00 | 0.00 | 0.421431E+09 | 0.418636E+09 | 21809.64 | 10-NOV-08:62 | 20471.61 | 0.00 |
December | 0.00 | 0.00 | 1348.52 | 1348.52 | 0.15 | 15-DEC-15:20 | 0.15 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.649722E+11 | 0.594176E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 1348.52 | 1348.52 | 0.15 | 0.15 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.132523E+11 | 0.111416E+11 | 27535.77 | 22231.67 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 197.59 | 197.59 | 0.14 | 03-JAN-12:30 | 0.14 | 0.00 |
February | 0.00 | 0.00 | 0.310429E+09 | 0.310429E+09 | 6691.60 | 20-FEB-15:30 | 6691.60 | 0.00 |
March | 0.00 | 0.00 | 0.105229E+10 | 0.105229E+10 | 9366.73 | 22-MAR-13:00 | 9366.73 | 0.00 |
April | 0.00 | 0.00 | 0.732281E+10 | 0.730593E+10 | 43919.50 | 29-APR-08:62 | 41244.77 | 0.00 |
May | 0.00 | 0.00 | 0.145520E+11 | 0.141922E+11 | 46498.80 | 28-MAY-09:01 | 36875.33 | 0.00 |
June | 0.00 | 0.00 | 0.203439E+11 | 0.196831E+11 | 46631.93 | 30-JUN-08:61 | 34495.85 | 0.00 |
July | 0.00 | 0.00 | 0.235639E+11 | 0.197454E+11 | 49434.36 | 19-JUL-08:61 | 30333.38 | 0.00 |
August | 0.00 | 0.00 | 0.210064E+11 | 0.186109E+11 | 48921.55 | 03-AUG-08:61 | 33010.41 | 0.00 |
September | 0.00 | 0.00 | 0.181578E+11 | 0.161119E+11 | 48411.29 | 22-SEP-08:61 | 30044.08 | 0.00 |
October | 0.00 | 0.00 | 0.829508E+10 | 0.752719E+10 | 47532.59 | 04-OCT-08:61 | 29811.86 | 0.00 |
November | 0.00 | 0.00 | 0.672643E+09 | 0.668089E+09 | 42760.93 | 10-NOV-09:02 | 40080.52 | 0.00 |
December | 0.00 | 0.00 | 57.41 | 57.41 | 0.10 | 08-DEC-15:10 | 0.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.115277E+12 | 0.105207E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 57.41 | 57.41 | 0.10 | 0.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.235639E+11 | 0.197454E+11 | 49434.36 | 41244.77 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 364.47 | 364.47 | 0.18 | 03-JAN-12:40 | 0.18 | 0.00 |
February | 0.00 | 0.00 | 0.154932E+09 | 0.154932E+09 | 3434.47 | 20-FEB-15:30 | 3434.47 | 0.00 |
March | 0.00 | 0.00 | 0.533288E+09 | 0.533288E+09 | 4804.25 | 22-MAR-13:00 | 4804.25 | 0.00 |
April | 0.00 | 0.00 | 0.379407E+10 | 0.378615E+10 | 22703.38 | 29-APR-08:62 | 21382.13 | 0.00 |
May | 0.00 | 0.00 | 0.754910E+10 | 0.736792E+10 | 24037.26 | 28-MAY-09:01 | 19110.07 | 0.00 |
June | 0.00 | 0.00 | 0.105394E+11 | 0.102082E+11 | 24104.97 | 30-JUN-08:61 | 17873.64 | 0.00 |
July | 0.00 | 0.00 | 0.121985E+11 | 0.102550E+11 | 25544.24 | 19-JUL-08:61 | 15728.74 | 0.00 |
August | 0.00 | 0.00 | 0.108832E+11 | 0.966957E+10 | 25277.74 | 03-AUG-08:61 | 17191.05 | 0.00 |
September | 0.00 | 0.00 | 0.941458E+10 | 0.837638E+10 | 25012.95 | 22-SEP-08:61 | 15650.34 | 0.00 |
October | 0.00 | 0.00 | 0.430665E+10 | 0.391730E+10 | 24572.72 | 04-OCT-08:61 | 15446.31 | 0.00 |
November | 0.00 | 0.00 | 0.348406E+09 | 0.346282E+09 | 22106.40 | 10-NOV-09:02 | 20782.65 | 0.00 |
December | 0.00 | 0.00 | 37.29 | 37.29 | 0.06 | 23-DEC-14:20 | 0.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.597221E+11 | 0.546150E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 37.29 | 37.29 | 0.06 | 0.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121985E+11 | 0.102550E+11 | 25544.24 | 21382.13 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 829.91 | 829.91 | 0.75 | 13-JAN-18:30 | 0.75 | 0.00 |
February | 0.00 | 0.00 | 0.145029E+09 | 0.145029E+09 | 3317.89 | 20-FEB-15:30 | 3317.89 | 0.00 |
March | 0.00 | 0.00 | 0.506669E+09 | 0.506669E+09 | 4689.62 | 22-MAR-13:00 | 4689.62 | 0.00 |
April | 0.00 | 0.00 | 0.373429E+10 | 0.372649E+10 | 22612.23 | 29-APR-08:62 | 21278.40 | 0.00 |
May | 0.00 | 0.00 | 0.748002E+10 | 0.730003E+10 | 23941.46 | 28-MAY-09:01 | 19016.95 | 0.00 |
June | 0.00 | 0.00 | 0.104734E+11 | 0.101447E+11 | 24009.31 | 30-JUN-08:61 | 17784.91 | 0.00 |
July | 0.00 | 0.00 | 0.121304E+11 | 0.101952E+11 | 25441.79 | 19-JUL-08:61 | 15616.30 | 0.00 |
August | 0.00 | 0.00 | 0.108197E+11 | 0.961278E+10 | 25173.53 | 03-AUG-08:61 | 17137.04 | 0.00 |
September | 0.00 | 0.00 | 0.935403E+10 | 0.832034E+10 | 24910.88 | 22-SEP-08:61 | 15597.80 | 0.00 |
October | 0.00 | 0.00 | 0.425836E+10 | 0.387263E+10 | 24475.55 | 04-OCT-08:61 | 15371.64 | 0.00 |
November | 0.00 | 0.00 | 0.335751E+09 | 0.333695E+09 | 22017.48 | 10-NOV-09:02 | 20681.99 | 0.00 |
December | 0.00 | 0.00 | 118.50 | 118.50 | 0.10 | 23-DEC-14:30 | 0.10 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.592377E+11 | 0.541576E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 118.50 | 118.50 | 0.10 | 0.10 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121304E+11 | 0.101952E+11 | 25441.79 | 21278.40 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 577.96 | 577.96 | 0.27 | 03-JAN-13:10 | 0.27 | 0.00 |
February | 0.00 | 0.00 | 0.122290E+09 | 0.122290E+09 | 3057.82 | 20-FEB-15:30 | 3057.82 | 0.00 |
March | 0.00 | 0.00 | 0.439201E+09 | 0.439201E+09 | 4395.04 | 22-MAR-13:00 | 4395.04 | 0.00 |
April | 0.00 | 0.00 | 0.359393E+10 | 0.358659E+10 | 21797.11 | 29-APR-08:62 | 20476.78 | 0.00 |
May | 0.00 | 0.00 | 0.735884E+10 | 0.718175E+10 | 23952.92 | 28-MAY-09:01 | 18997.72 | 0.00 |
June | 0.00 | 0.00 | 0.104198E+11 | 0.100961E+11 | 24021.03 | 30-JUN-08:61 | 17758.61 | 0.00 |
July | 0.00 | 0.00 | 0.121007E+11 | 0.101735E+11 | 25449.72 | 19-JUL-08:61 | 15535.93 | 0.00 |
August | 0.00 | 0.00 | 0.107992E+11 | 0.959999E+10 | 25184.04 | 03-AUG-08:61 | 17172.80 | 0.00 |
September | 0.00 | 0.00 | 0.932065E+10 | 0.829082E+10 | 24922.52 | 22-SEP-08:61 | 15624.30 | 0.00 |
October | 0.00 | 0.00 | 0.417163E+10 | 0.379405E+10 | 24489.22 | 04-OCT-08:61 | 15354.43 | 0.00 |
November | 0.00 | 0.00 | 0.304833E+09 | 0.302980E+09 | 21674.57 | 10-NOV-09:02 | 20326.15 | 0.00 |
December | 0.00 | 0.00 | 1213.09 | 1213.09 | 1.65 | 23-DEC-16:00 | 1.65 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.586311E+11 | 0.535872E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 577.96 | 577.96 | 0.27 | 0.27 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.121007E+11 | 0.101735E+11 | 25449.72 | 20476.78 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 2524.40 | 2524.40 | 0.49 | 03-JAN-17:00 | 0.49 | 0.00 |
February | 0.00 | 0.00 | 94974988.40 | 94974988.40 | 2907.22 | 20-FEB-15:20 | 2907.22 | 0.00 |
March | 0.00 | 0.00 | 0.373882E+09 | 0.373882E+09 | 4381.80 | 22-MAR-13:00 | 4381.80 | 0.00 |
April | 0.00 | 0.00 | 0.375701E+10 | 0.374935E+10 | 22590.17 | 30-APR-09:02 | 21750.59 | 0.00 |
May | 0.00 | 0.00 | 0.797209E+10 | 0.777665E+10 | 26439.50 | 28-MAY-09:01 | 20605.78 | 0.00 |
June | 0.00 | 0.00 | 0.115569E+11 | 0.111947E+11 | 26439.72 | 30-JUN-08:61 | 19350.53 | 0.00 |
July | 0.00 | 0.00 | 0.135401E+11 | 0.113980E+11 | 28408.15 | 20-JUL-08:61 | 16664.74 | 0.00 |
August | 0.00 | 0.00 | 0.121777E+11 | 0.108370E+11 | 27778.43 | 03-AUG-08:61 | 18583.97 | 0.00 |
September | 0.00 | 0.00 | 0.105368E+11 | 0.937597E+10 | 27583.67 | 22-SEP-08:61 | 16576.39 | 0.00 |
October | 0.00 | 0.00 | 0.449922E+10 | 0.409617E+10 | 26906.53 | 04-OCT-08:61 | 16812.24 | 0.00 |
November | 0.00 | 0.00 | 0.286468E+09 | 0.284697E+09 | 15940.17 | 10-NOV-09:02 | 14807.17 | 0.00 |
December | 0.00 | 0.00 | 53.19 | 53.19 | 0.06 | 09-DEC-13:10 | 0.06 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.647951E+11 | 0.591814E+11 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 53.19 | 53.19 | 0.06 | 0.06 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.135401E+11 | 0.113980E+11 | 28408.15 | 21750.59 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.505301E+10 | 0.69 | 2784.65 | 26-JAN-18:50 | 1.02 |
February | 0.457150E+10 | 0.69 | 2784.65 | 09-FEB-12:40 | 1.02 |
March | 0.507272E+10 | 0.69 | 2784.65 | 02-MAR-10:10 | 1.02 |
April | 0.489207E+10 | 0.69 | 2784.65 | 01-APR-15:40 | 1.01 |
May | 0.505247E+10 | 0.68 | 2784.65 | 01-MAY-15:40 | 1.01 |
June | 0.491212E+10 | 0.68 | 2784.65 | 03-JUN-22:01 | 1.00 |
July | 0.505247E+10 | 0.68 | 2784.65 | 02-JUL-08:00 | 1.00 |
August | 0.506249E+10 | 0.68 | 2784.65 | 01-AUG-18:10 | 1.00 |
September | 0.490210E+10 | 0.68 | 2784.65 | 01-SEP-22:25 | 1.00 |
October | 0.505247E+10 | 0.68 | 2784.65 | 02-OCT-20:54 | 1.00 |
November | 0.488205E+10 | 0.68 | 2784.65 | 08-NOV-14:20 | 1.01 |
December | 0.507300E+10 | 0.69 | 2784.65 | 27-DEC-11:20 | 1.01 |
Annual Sum or Average | 0.595785E+11 | 0.68 | |||
Minimum of Months | 0.457150E+10 | 0.68 | 2784.65 | 1.00 | |
Maximum of Months | 0.507300E+10 | 0.69 | 2784.65 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.214325E+10 | 0.67 | 1487.43 | 28-JAN-09:09 | 1.05 |
February | 0.212396E+10 | 0.68 | 1487.43 | 22-FEB-14:00 | 1.05 |
March | 0.248309E+10 | 0.70 | 1487.43 | 07-MAR-15:10 | 1.05 |
April | 0.225233E+10 | 0.68 | 1487.43 | 02-APR-11:10 | 1.05 |
May | 0.225629E+10 | 0.70 | 1487.43 | 17-MAY-19:20 | 1.05 |
June | 0.217145E+10 | 0.73 | 1487.43 | 03-JUN-08:00 | 1.04 |
July | 0.223598E+10 | 0.73 | 1487.43 | 01-JUL-07:50 | 1.04 |
August | 0.226547E+10 | 0.72 | 1487.43 | 20-AUG-08:03 | 1.04 |
September | 0.220549E+10 | 0.68 | 1487.43 | 06-SEP-19:15 | 1.04 |
October | 0.248174E+10 | 0.68 | 1487.43 | 02-OCT-19:10 | 1.04 |
November | 0.238838E+10 | 0.70 | 1487.43 | 09-NOV-19:50 | 1.04 |
December | 0.213323E+10 | 0.65 | 1487.43 | 20-DEC-09:40 | 1.05 |
Annual Sum or Average | 0.271407E+11 | 0.69 | |||
Minimum of Months | 0.212396E+10 | 0.65 | 1487.43 | 1.04 | |
Maximum of Months | 0.248309E+10 | 0.73 | 1487.43 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.218038E+10 | 0.57 | 1506.62 | 07-JAN-09:30 | 1.05 |
February | 0.197428E+10 | 0.57 | 1506.62 | 01-FEB-09:07 | 1.05 |
March | 0.222377E+10 | 0.58 | 1506.62 | 06-MAR-11:00 | 1.05 |
April | 0.211530E+10 | 0.57 | 1506.62 | 03-APR-09:10 | 1.05 |
May | 0.220208E+10 | 0.57 | 1506.62 | 01-MAY-11:00 | 1.05 |
June | 0.214784E+10 | 0.57 | 1506.62 | 03-JUN-07:25 | 1.04 |
July | 0.216954E+10 | 0.56 | 1506.62 | 01-JUL-07:25 | 1.04 |
August | 0.222377E+10 | 0.57 | 1506.62 | 01-AUG-07:40 | 1.03 |
September | 0.211530E+10 | 0.56 | 1506.62 | 01-SEP-07:06 | 1.03 |
October | 0.218038E+10 | 0.56 | 1506.62 | 02-OCT-07:50 | 1.04 |
November | 0.211530E+10 | 0.57 | 1506.62 | 03-NOV-13:50 | 1.04 |
December | 0.216954E+10 | 0.56 | 1506.62 | 03-DEC-14:10 | 1.05 |
Annual Sum or Average | 0.258175E+11 | 0.57 | |||
Minimum of Months | 0.197428E+10 | 0.56 | 1506.62 | 1.03 | |
Maximum of Months | 0.222377E+10 | 0.58 | 1506.62 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.216808E+10 | 0.57 | 1498.12 | 02-JAN-08:50 | 1.05 |
February | 0.196314E+10 | 0.57 | 1498.12 | 03-FEB-08:30 | 1.05 |
March | 0.221123E+10 | 0.58 | 1498.12 | 02-MAR-08:20 | 1.05 |
April | 0.210336E+10 | 0.57 | 1498.12 | 01-APR-11:10 | 1.05 |
May | 0.218965E+10 | 0.57 | 1498.12 | 01-MAY-12:10 | 1.05 |
June | 0.213572E+10 | 0.57 | 1498.12 | 03-JUN-07:07 | 1.04 |
July | 0.215729E+10 | 0.56 | 1498.12 | 02-JUL-07:40 | 1.03 |
August | 0.221123E+10 | 0.57 | 1498.12 | 07-AUG-06:20 | 1.04 |
September | 0.210336E+10 | 0.56 | 1498.12 | 02-SEP-08:61 | 1.03 |
October | 0.216808E+10 | 0.56 | 1498.12 | 09-OCT-10:20 | 1.03 |
November | 0.210336E+10 | 0.57 | 1498.12 | 03-NOV-16:30 | 1.04 |
December | 0.215729E+10 | 0.56 | 1498.12 | 04-DEC-09:04 | 1.05 |
Annual Sum or Average | 0.256718E+11 | 0.57 | |||
Minimum of Months | 0.196314E+10 | 0.56 | 1498.12 | 1.03 | |
Maximum of Months | 0.221123E+10 | 0.58 | 1498.12 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.217259E+10 | 0.57 | 1501.24 | 03-JAN-08:20 | 1.05 |
February | 0.196722E+10 | 0.57 | 1501.24 | 01-FEB-08:10 | 1.05 |
March | 0.221582E+10 | 0.58 | 1501.24 | 01-MAR-09:10 | 1.05 |
April | 0.210774E+10 | 0.57 | 1501.24 | 01-APR-10:50 | 1.05 |
May | 0.219421E+10 | 0.57 | 1501.24 | 01-MAY-12:00 | 1.05 |
June | 0.214016E+10 | 0.57 | 1501.24 | 01-JUN-08:03 | 1.05 |
July | 0.216178E+10 | 0.56 | 1501.24 | 01-JUL-07:07 | 1.04 |
August | 0.221582E+10 | 0.57 | 1501.24 | 01-AUG-07:06 | 1.03 |
September | 0.210774E+10 | 0.56 | 1501.24 | 01-SEP-07:09 | 1.03 |
October | 0.217259E+10 | 0.56 | 1501.24 | 01-OCT-08:10 | 1.04 |
November | 0.210774E+10 | 0.57 | 1501.24 | 01-NOV-07:03 | 1.04 |
December | 0.216178E+10 | 0.56 | 1501.24 | 02-DEC-08:20 | 1.05 |
Annual Sum or Average | 0.257252E+11 | 0.57 | |||
Minimum of Months | 0.196722E+10 | 0.56 | 1501.24 | 1.03 | |
Maximum of Months | 0.221582E+10 | 0.58 | 1501.24 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.342925E+10 | 0.50 | 2567.57 | 26-JAN-15:00 | 1.02 |
February | 0.310574E+10 | 0.51 | 2567.57 | 01-FEB-09:15 | 1.01 |
March | 0.350320E+10 | 0.52 | 2567.57 | 01-MAR-09:03 | 1.01 |
April | 0.332758E+10 | 0.51 | 2567.57 | 01-APR-13:10 | 1.01 |
May | 0.346623E+10 | 0.51 | 2567.57 | 04-MAY-11:30 | 1.01 |
June | 0.338304E+10 | 0.51 | 2567.57 | 01-JUN-08:09 | 1.01 |
July | 0.341077E+10 | 0.50 | 2567.57 | 01-JUL-07:35 | 1.01 |
August | 0.350320E+10 | 0.51 | 2567.57 | 01-AUG-08:07 | 1.00 |
September | 0.332758E+10 | 0.50 | 2567.57 | 01-SEP-08:06 | 1.00 |
October | 0.342925E+10 | 0.50 | 2567.57 | 15-OCT-15:50 | 1.00 |
November | 0.332758E+10 | 0.51 | 2567.57 | 14-NOV-15:00 | 1.01 |
December | 0.341077E+10 | 0.50 | 2567.57 | 02-DEC-09:15 | 1.01 |
Annual Sum or Average | 0.406242E+11 | 0.51 | |||
Minimum of Months | 0.310574E+10 | 0.50 | 2567.57 | 1.00 | |
Maximum of Months | 0.350320E+10 | 0.52 | 2567.57 | 1.02 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.184639E+10 | 0.52 | 1382.45 | 02-JAN-10:00 | 1.04 |
February | 0.167221E+10 | 0.52 | 1382.45 | 01-FEB-09:10 | 1.05 |
March | 0.188621E+10 | 0.53 | 1382.45 | 01-MAR-09:07 | 1.05 |
April | 0.179165E+10 | 0.52 | 1382.45 | 02-APR-10:00 | 1.05 |
May | 0.186630E+10 | 0.53 | 1382.45 | 01-MAY-13:10 | 1.05 |
June | 0.182151E+10 | 0.53 | 1382.45 | 01-JUN-08:10 | 1.05 |
July | 0.183644E+10 | 0.51 | 1382.45 | 02-JUL-16:50 | 1.04 |
August | 0.188621E+10 | 0.53 | 1382.45 | 01-AUG-08:06 | 1.03 |
September | 0.179165E+10 | 0.52 | 1382.45 | 05-SEP-10:00 | 1.03 |
October | 0.184639E+10 | 0.52 | 1382.45 | 02-OCT-09:00 | 1.03 |
November | 0.179165E+10 | 0.52 | 1382.45 | 03-NOV-12:40 | 1.04 |
December | 0.183644E+10 | 0.52 | 1382.45 | 01-DEC-09:30 | 1.05 |
Annual Sum or Average | 0.218730E+11 | 0.52 | |||
Minimum of Months | 0.167221E+10 | 0.51 | 1382.45 | 1.03 | |
Maximum of Months | 0.188621E+10 | 0.53 | 1382.45 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183797E+10 | 0.52 | 1376.14 | 02-JAN-09:02 | 1.04 |
February | 0.166458E+10 | 0.52 | 1376.14 | 01-FEB-09:01 | 1.05 |
March | 0.187760E+10 | 0.53 | 1376.14 | 01-MAR-11:10 | 1.05 |
April | 0.178347E+10 | 0.52 | 1376.14 | 01-APR-10:20 | 1.05 |
May | 0.185779E+10 | 0.53 | 1376.14 | 01-MAY-13:40 | 1.05 |
June | 0.181320E+10 | 0.53 | 1376.14 | 01-JUN-10:00 | 1.05 |
July | 0.182806E+10 | 0.51 | 1376.14 | 01-JUL-08:07 | 1.04 |
August | 0.187760E+10 | 0.53 | 1376.14 | 01-AUG-11:10 | 1.03 |
September | 0.178347E+10 | 0.52 | 1376.14 | 01-SEP-08:06 | 1.03 |
October | 0.183797E+10 | 0.52 | 1376.14 | 01-OCT-13:30 | 1.04 |
November | 0.178347E+10 | 0.52 | 1376.14 | 07-NOV-14:00 | 1.05 |
December | 0.182806E+10 | 0.52 | 1376.14 | 02-DEC-09:05 | 1.05 |
Annual Sum or Average | 0.217732E+11 | 0.52 | |||
Minimum of Months | 0.166458E+10 | 0.51 | 1376.14 | 1.03 | |
Maximum of Months | 0.187760E+10 | 0.53 | 1376.14 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.183948E+10 | 0.52 | 1377.27 | 15-JAN-12:10 | 1.04 |
February | 0.166595E+10 | 0.52 | 1377.27 | 01-FEB-19:40 | 1.05 |
March | 0.187915E+10 | 0.53 | 1377.27 | 28-MAR-08:30 | 1.05 |
April | 0.178494E+10 | 0.52 | 1377.27 | 20-APR-19:07 | 1.05 |
May | 0.185932E+10 | 0.53 | 1377.27 | 01-MAY-08:62 | 1.05 |
June | 0.181469E+10 | 0.53 | 1377.27 | 01-JUN-08:07 | 1.05 |
July | 0.182957E+10 | 0.51 | 1377.27 | 01-JUL-08:00 | 1.04 |
August | 0.187915E+10 | 0.53 | 1377.27 | 01-AUG-08:09 | 1.03 |
September | 0.178494E+10 | 0.52 | 1377.27 | 01-SEP-08:06 | 1.03 |
October | 0.183948E+10 | 0.52 | 1377.27 | 05-OCT-19:12 | 1.04 |
November | 0.178494E+10 | 0.52 | 1377.27 | 01-NOV-08:63 | 1.04 |
December | 0.182957E+10 | 0.52 | 1377.27 | 22-DEC-09:04 | 1.05 |
Annual Sum or Average | 0.217912E+11 | 0.52 | |||
Minimum of Months | 0.166595E+10 | 0.51 | 1377.27 | 1.03 | |
Maximum of Months | 0.187915E+10 | 0.53 | 1377.27 | 1.05 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208520E+10 | 0.52 | 1561.25 | 01-JAN-10:30 | 1.05 |
February | 0.188848E+10 | 0.52 | 1561.25 | 01-FEB-09:09 | 1.05 |
March | 0.213016E+10 | 0.53 | 1561.25 | 01-MAR-09:10 | 1.05 |
April | 0.202337E+10 | 0.52 | 1561.25 | 01-APR-10:40 | 1.05 |
May | 0.210768E+10 | 0.53 | 1561.25 | 01-MAY-12:10 | 1.05 |
June | 0.205710E+10 | 0.53 | 1561.25 | 01-JUN-08:09 | 1.05 |
July | 0.207396E+10 | 0.51 | 1561.25 | 01-JUL-08:30 | 1.04 |
August | 0.213016E+10 | 0.53 | 1561.25 | 01-AUG-08:00 | 1.03 |
September | 0.202337E+10 | 0.52 | 1561.25 | 01-SEP-09:00 | 1.03 |
October | 0.208520E+10 | 0.52 | 1561.25 | 01-OCT-09:10 | 1.04 |
November | 0.202337E+10 | 0.52 | 1561.25 | 03-NOV-12:00 | 1.04 |
December | 0.207396E+10 | 0.52 | 1561.25 | 02-DEC-09:08 | 1.05 |
Annual Sum or Average | 0.247020E+11 | 0.52 | |||
Minimum of Months | 0.188848E+10 | 0.51 | 1561.25 | 1.03 | |
Maximum of Months | 0.213016E+10 | 0.53 | 1561.25 | 1.05 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.505381E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.471576E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.547325E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.804000E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.111992E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.138378E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.150271E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.138178E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.120299E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.820631E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.512998E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.507300E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.107604E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.471576E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.150271E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.215148E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.223636E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.276790E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.401154E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.544465E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.658466E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.711821E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.659480E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.588139E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.425199E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.255584E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.213630E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.517351E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.213630E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.711821E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.218128E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.204955E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.244322E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.337897E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.465966E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.567444E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.602613E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.564638E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.503498E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.352375E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.224652E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.216954E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.450344E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.204955E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.602613E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.216851E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.203149E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.241951E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.335753E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.465159E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.567462E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.602743E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.564791E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.503328E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.350887E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.222987E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.215729E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.449079E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.203149E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.602743E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.217268E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.202529E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.240357E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.331997E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.460746E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.563559E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.599114E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.560947E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.499508E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.347723E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.222319E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.216178E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.446225E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.202529E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.599114E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.342925E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.319416E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.380338E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.549137E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.783449E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.979307E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.103529E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.969421E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.856583E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.576225E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.351533E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.341077E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.748470E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.319416E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.103529E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.184639E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.171558E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.203571E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.289301E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.409242E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.508329E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.536715E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.503706E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.445959E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.303612E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.188720E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.183644E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.392900E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.171558E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.536715E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.183797E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.170524E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.201984E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.286853E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.406473E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.505557E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.533969E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.501076E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.443494E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.301498E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.187563E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.182806E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.390559E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170524E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.533969E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.183948E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.170036E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.200293E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.283246E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.403433E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.504314E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.533431E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.500752E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.442822E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.299431E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.186880E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.182957E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.389154E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.170036E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.533431E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.208520E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.191537E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.223627E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.312261E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.446791E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.563556E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.599365E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.565022E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.500352E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.333278E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.210249E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.207396E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.436195E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.191537E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.599365E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.505301E+10 | 2817349.10 | 0.655977E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.457150E+10 | 0.511020E+09 | 0.372662E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507272E+10 | 0.141218E+10 | 0.179249E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489207E+10 | 0.107325E+11 | 237621.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.505247E+10 | 0.205702E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.491212E+10 | 0.285173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505247E+10 | 0.338994E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.506249E+10 | 0.296562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.490210E+10 | 0.248611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.505247E+10 | 0.112369E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488205E+10 | 0.891627E+09 | 0.171352E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507300E+10 | 2990.76 | 0.131625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.595785E+11 | 0.162291E+12 | 0.269573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.457150E+10 | 2990.76 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.507300E+10 | 0.338994E+11 | 0.131625E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.214325E+10 | 31293170.61 | 49827522.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212396E+10 | 0.417298E+09 | 26273925.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248309E+10 | 0.104834E+10 | 12715681.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225233E+10 | 0.630658E+10 | 717534.28 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225629E+10 | 0.110508E+11 | 98953.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217145E+10 | 0.144043E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223598E+10 | 0.168921E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226547E+10 | 0.150360E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220549E+10 | 0.133456E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248174E+10 | 0.665529E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238838E+10 | 0.623290E+09 | 10840231.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213323E+10 | 11048367.58 | 0.184410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271407E+11 | 0.858219E+11 | 0.284884E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212396E+10 | 11048367.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.248309E+10 | 0.168921E+11 | 0.184410E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.218038E+10 | 3183653.42 | 0.194402E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197428E+10 | 0.271672E+09 | 95804655.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222377E+10 | 0.790063E+09 | 39466893.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211530E+10 | 0.438752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220208E+10 | 0.837742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214784E+10 | 0.114579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216954E+10 | 0.133541E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222377E+10 | 0.118476E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211530E+10 | 0.103218E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218038E+10 | 0.487871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211530E+10 | 0.480363E+09 | 46442897.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216954E+10 | 620.66 | 0.429961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258175E+11 | 0.661704E+11 | 0.806078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197428E+10 | 620.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.222377E+10 | 0.133541E+11 | 0.429961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.216808E+10 | 1543410.10 | 0.263969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196314E+10 | 0.246150E+09 | 0.119300E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221123E+10 | 0.748785E+09 | 51769692.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210336E+10 | 0.435391E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218965E+10 | 0.840012E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.213572E+10 | 0.115147E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.215729E+10 | 0.134201E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.221123E+10 | 0.119129E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210336E+10 | 0.103710E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216808E+10 | 0.487139E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210336E+10 | 0.462881E+09 | 66109356.20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215729E+10 | 524.39 | 0.523781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256718E+11 | 0.663035E+11 | 0.102493E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196314E+10 | 524.39 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.221123E+10 | 0.134201E+11 | 0.523781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.217259E+10 | 331875.59 | 0.376078E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196722E+10 | 0.208276E+09 | 0.168106E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221582E+10 | 0.672653E+09 | 75968691.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210774E+10 | 0.419417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219421E+10 | 0.821181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214016E+10 | 0.113471E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216178E+10 | 0.132523E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.221582E+10 | 0.117387E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210774E+10 | 0.101975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217259E+10 | 0.472788E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210774E+10 | 0.421431E+09 | 93211757.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216178E+10 | 1348.52 | 0.668371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257252E+11 | 0.649722E+11 | 0.138174E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196722E+10 | 1348.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.221582E+10 | 0.132523E+11 | 0.668371E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.342925E+10 | 197.59 | 0.953617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310574E+10 | 0.310429E+09 | 0.396098E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350320E+10 | 0.105229E+10 | 0.183504E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332758E+10 | 0.732281E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346623E+10 | 0.145520E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.338304E+10 | 0.203439E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.341077E+10 | 0.235639E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350320E+10 | 0.210064E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.332758E+10 | 0.181578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342925E+10 | 0.829508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332758E+10 | 0.672643E+09 | 0.275272E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341077E+10 | 57.41 | 0.158804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406242E+11 | 0.115277E+12 | 0.339653E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310574E+10 | 57.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350320E+10 | 0.235639E+11 | 0.158804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.184639E+10 | 364.47 | 0.497515E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167221E+10 | 0.154932E+09 | 0.204050E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188621E+10 | 0.533288E+09 | 96047250.24 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179165E+10 | 0.379407E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186630E+10 | 0.754910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182151E+10 | 0.105394E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183644E+10 | 0.121985E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188621E+10 | 0.108832E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179165E+10 | 0.941458E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184639E+10 | 0.430665E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179165E+10 | 0.348406E+09 | 0.138936E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183644E+10 | 37.29 | 0.816279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218730E+11 | 0.597221E+11 | 0.175283E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167221E+10 | 37.29 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188621E+10 | 0.121985E+11 | 0.816279E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183797E+10 | 829.91 | 0.555868E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166458E+10 | 0.145029E+09 | 0.234165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187760E+10 | 0.506669E+09 | 0.111644E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178347E+10 | 0.373429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185779E+10 | 0.748002E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181320E+10 | 0.104734E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182806E+10 | 0.121304E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187760E+10 | 0.108197E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178347E+10 | 0.935403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183797E+10 | 0.425836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178347E+10 | 0.335751E+09 | 0.151479E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182806E+10 | 118.50 | 0.877063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217732E+11 | 0.592377E+11 | 0.193022E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166458E+10 | 118.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187760E+10 | 0.121304E+11 | 0.877063E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.183948E+10 | 577.96 | 0.737599E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166595E+10 | 0.122290E+09 | 0.340053E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187915E+10 | 0.439201E+09 | 0.173618E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178494E+10 | 0.359393E+10 | 520812.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185932E+10 | 0.735884E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181469E+10 | 0.104198E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182957E+10 | 0.121007E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187915E+10 | 0.107992E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178494E+10 | 0.932065E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183948E+10 | 0.417163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178494E+10 | 0.304833E+09 | 0.190959E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182957E+10 | 1213.09 | 0.106128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217912E+11 | 0.586311E+11 | 0.250403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166595E+10 | 577.96 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187915E+10 | 0.121007E+11 | 0.106128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208520E+10 | 2524.40 | 0.125323E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188848E+10 | 94974988.40 | 0.674059E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213016E+10 | 0.373882E+09 | 0.380061E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202337E+10 | 0.375701E+10 | 6938477.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210768E+10 | 0.797209E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205710E+10 | 0.115569E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207396E+10 | 0.135401E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213016E+10 | 0.121777E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202337E+10 | 0.105368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208520E+10 | 0.449922E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202337E+10 | 0.286468E+09 | 0.292233E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207396E+10 | 53.19 | 0.152242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247020E+11 | 0.647951E+11 | 0.412894E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.188848E+10 | 53.19 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213016E+10 | 0.135401E+11 | 0.152242E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.505301E+10 | 0.00 | 0.00 | 0.00 | 805077.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.457150E+10 | 0.00 | 0.00 | 0.00 | 0.144261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.507272E+10 | 0.00 | 0.00 | 0.00 | 0.400527E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.489207E+10 | 0.00 | 0.00 | 0.00 | 0.314793E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.505247E+10 | 0.00 | 0.00 | 0.00 | 0.614675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.491212E+10 | 0.00 | 0.00 | 0.00 | 0.892570E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.505247E+10 | 0.00 | 0.00 | 0.00 | 0.997465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.506249E+10 | 0.00 | 0.00 | 0.00 | 0.875532E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.490210E+10 | 0.00 | 0.00 | 0.00 | 0.712779E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.505247E+10 | 0.00 | 0.00 | 0.00 | 0.315384E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.488205E+10 | 0.00 | 0.00 | 0.00 | 0.247935E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.507300E+10 | 0.00 | 0.00 | 0.00 | 859.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.595785E+11 | 0.00 | 0.00 | 0.00 | 0.480255E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.457150E+10 | 0.00 | 0.00 | 0.00 | 859.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.507300E+10 | 0.00 | 0.00 | 0.00 | 0.997465E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.214325E+10 | 0.00 | 0.00 | 0.00 | 8225291.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.212396E+10 | 0.00 | 0.00 | 0.00 | 0.112394E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.248309E+10 | 0.00 | 0.00 | 0.00 | 0.284811E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.225233E+10 | 0.00 | 0.00 | 0.00 | 0.175920E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.225629E+10 | 0.00 | 0.00 | 0.00 | 0.318836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.217145E+10 | 0.00 | 0.00 | 0.00 | 0.441321E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.223598E+10 | 0.00 | 0.00 | 0.00 | 0.488222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.226547E+10 | 0.00 | 0.00 | 0.00 | 0.432933E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.220549E+10 | 0.00 | 0.00 | 0.00 | 0.367590E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.248174E+10 | 0.00 | 0.00 | 0.00 | 0.177024E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.238838E+10 | 0.00 | 0.00 | 0.00 | 0.167462E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.213323E+10 | 0.00 | 0.00 | 0.00 | 3067905.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.271407E+11 | 0.00 | 0.00 | 0.00 | 0.245944E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.212396E+10 | 0.00 | 0.00 | 0.00 | 3067905.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.248309E+10 | 0.00 | 0.00 | 0.00 | 0.488222E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.218038E+10 | 0.00 | 0.00 | 0.00 | 892302.47 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.197428E+10 | 0.00 | 0.00 | 0.00 | 75271614.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.222377E+10 | 0.00 | 0.00 | 0.00 | 0.219448E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.211530E+10 | 0.00 | 0.00 | 0.00 | 0.126367E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.220208E+10 | 0.00 | 0.00 | 0.00 | 0.245758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214784E+10 | 0.00 | 0.00 | 0.00 | 0.352660E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 0.385659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.222377E+10 | 0.00 | 0.00 | 0.00 | 0.342261E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.211530E+10 | 0.00 | 0.00 | 0.00 | 0.291969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.218038E+10 | 0.00 | 0.00 | 0.00 | 0.134337E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.211530E+10 | 0.00 | 0.00 | 0.00 | 0.131220E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216954E+10 | 0.00 | 0.00 | 0.00 | 175.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.258175E+11 | 0.00 | 0.00 | 0.00 | 0.192169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.197428E+10 | 0.00 | 0.00 | 0.00 | 175.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.222377E+10 | 0.00 | 0.00 | 0.00 | 0.385659E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.216808E+10 | 0.00 | 0.00 | 0.00 | 433247.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196314E+10 | 0.00 | 0.00 | 0.00 | 68356121.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221123E+10 | 0.00 | 0.00 | 0.00 | 0.208280E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210336E+10 | 0.00 | 0.00 | 0.00 | 0.125417E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.218965E+10 | 0.00 | 0.00 | 0.00 | 0.246194E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.213572E+10 | 0.00 | 0.00 | 0.00 | 0.353890E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.215729E+10 | 0.00 | 0.00 | 0.00 | 0.387013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.221123E+10 | 0.00 | 0.00 | 0.00 | 0.343669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210336E+10 | 0.00 | 0.00 | 0.00 | 0.292992E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.216808E+10 | 0.00 | 0.00 | 0.00 | 0.134079E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210336E+10 | 0.00 | 0.00 | 0.00 | 0.126508E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.215729E+10 | 0.00 | 0.00 | 0.00 | 148.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.256718E+11 | 0.00 | 0.00 | 0.00 | 0.192361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196314E+10 | 0.00 | 0.00 | 0.00 | 148.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.221123E+10 | 0.00 | 0.00 | 0.00 | 0.387013E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.217259E+10 | 0.00 | 0.00 | 0.00 | 93400.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.196722E+10 | 0.00 | 0.00 | 0.00 | 58070329.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.221582E+10 | 0.00 | 0.00 | 0.00 | 0.187748E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.210774E+10 | 0.00 | 0.00 | 0.00 | 0.121223E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.219421E+10 | 0.00 | 0.00 | 0.00 | 0.241326E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.214016E+10 | 0.00 | 0.00 | 0.00 | 0.349543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.216178E+10 | 0.00 | 0.00 | 0.00 | 0.382936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.221582E+10 | 0.00 | 0.00 | 0.00 | 0.339364E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.210774E+10 | 0.00 | 0.00 | 0.00 | 0.288735E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.217259E+10 | 0.00 | 0.00 | 0.00 | 0.130464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.210774E+10 | 0.00 | 0.00 | 0.00 | 0.115452E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.216178E+10 | 0.00 | 0.00 | 0.00 | 380.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.257252E+11 | 0.00 | 0.00 | 0.00 | 0.188973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.196722E+10 | 0.00 | 0.00 | 0.00 | 380.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.221582E+10 | 0.00 | 0.00 | 0.00 | 0.382936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.342925E+10 | 0.00 | 0.00 | 0.00 | 56.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.310574E+10 | 0.00 | 0.00 | 0.00 | 88421881.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.350320E+10 | 0.00 | 0.00 | 0.00 | 0.300178E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.332758E+10 | 0.00 | 0.00 | 0.00 | 0.216379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.346623E+10 | 0.00 | 0.00 | 0.00 | 0.436827E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.338304E+10 | 0.00 | 0.00 | 0.00 | 0.641003E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.341077E+10 | 0.00 | 0.00 | 0.00 | 0.694217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.350320E+10 | 0.00 | 0.00 | 0.00 | 0.619101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.332758E+10 | 0.00 | 0.00 | 0.00 | 0.523826E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.342925E+10 | 0.00 | 0.00 | 0.00 | 0.233300E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.332758E+10 | 0.00 | 0.00 | 0.00 | 0.187750E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.341077E+10 | 0.00 | 0.00 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.406242E+11 | 0.00 | 0.00 | 0.00 | 0.342229E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.310574E+10 | 0.00 | 0.00 | 0.00 | 16.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.350320E+10 | 0.00 | 0.00 | 0.00 | 0.694217E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.184639E+10 | 0.00 | 0.00 | 0.00 | 102.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.167221E+10 | 0.00 | 0.00 | 0.00 | 43377895.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.188621E+10 | 0.00 | 0.00 | 0.00 | 0.149507E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.179165E+10 | 0.00 | 0.00 | 0.00 | 0.110136E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.186630E+10 | 0.00 | 0.00 | 0.00 | 0.222612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.182151E+10 | 0.00 | 0.00 | 0.00 | 0.326178E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.183644E+10 | 0.00 | 0.00 | 0.00 | 0.353071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.188621E+10 | 0.00 | 0.00 | 0.00 | 0.315086E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.179165E+10 | 0.00 | 0.00 | 0.00 | 0.266794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.184639E+10 | 0.00 | 0.00 | 0.00 | 0.118973E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.179165E+10 | 0.00 | 0.00 | 0.00 | 95548479.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.183644E+10 | 0.00 | 0.00 | 0.00 | 10.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.218730E+11 | 0.00 | 0.00 | 0.00 | 0.174169E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.167221E+10 | 0.00 | 0.00 | 0.00 | 10.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.188621E+10 | 0.00 | 0.00 | 0.00 | 0.353071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183797E+10 | 0.00 | 0.00 | 0.00 | 234.27 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166458E+10 | 0.00 | 0.00 | 0.00 | 40659320.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187760E+10 | 0.00 | 0.00 | 0.00 | 0.142236E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178347E+10 | 0.00 | 0.00 | 0.00 | 0.108505E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185779E+10 | 0.00 | 0.00 | 0.00 | 0.220694E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181320E+10 | 0.00 | 0.00 | 0.00 | 0.324237E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182806E+10 | 0.00 | 0.00 | 0.00 | 0.351163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187760E+10 | 0.00 | 0.00 | 0.00 | 0.313316E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178347E+10 | 0.00 | 0.00 | 0.00 | 0.265147E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183797E+10 | 0.00 | 0.00 | 0.00 | 0.117701E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178347E+10 | 0.00 | 0.00 | 0.00 | 92151426.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182806E+10 | 0.00 | 0.00 | 0.00 | 33.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217732E+11 | 0.00 | 0.00 | 0.00 | 0.172827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166458E+10 | 0.00 | 0.00 | 0.00 | 33.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187760E+10 | 0.00 | 0.00 | 0.00 | 0.351163E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.183948E+10 | 0.00 | 0.00 | 0.00 | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.166595E+10 | 0.00 | 0.00 | 0.00 | 34409884.37 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.187915E+10 | 0.00 | 0.00 | 0.00 | 0.123783E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.178494E+10 | 0.00 | 0.00 | 0.00 | 0.104752E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.185932E+10 | 0.00 | 0.00 | 0.00 | 0.217501E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.181469E+10 | 0.00 | 0.00 | 0.00 | 0.322845E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.182957E+10 | 0.00 | 0.00 | 0.00 | 0.350474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.187915E+10 | 0.00 | 0.00 | 0.00 | 0.312837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.178494E+10 | 0.00 | 0.00 | 0.00 | 0.264328E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.183948E+10 | 0.00 | 0.00 | 0.00 | 0.115483E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.178494E+10 | 0.00 | 0.00 | 0.00 | 83853365.95 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.182957E+10 | 0.00 | 0.00 | 0.00 | 342.44 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.217912E+11 | 0.00 | 0.00 | 0.00 | 0.171242E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.166595E+10 | 0.00 | 0.00 | 0.00 | 163.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.187915E+10 | 0.00 | 0.00 | 0.00 | 0.350474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.208520E+10 | 0.00 | 0.00 | 0.00 | 712.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188848E+10 | 0.00 | 0.00 | 0.00 | 26890215.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213016E+10 | 0.00 | 0.00 | 0.00 | 0.106104E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202337E+10 | 0.00 | 0.00 | 0.00 | 0.109923E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210768E+10 | 0.00 | 0.00 | 0.00 | 0.236023E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205710E+10 | 0.00 | 0.00 | 0.00 | 0.357847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207396E+10 | 0.00 | 0.00 | 0.00 | 0.391970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213016E+10 | 0.00 | 0.00 | 0.00 | 0.352006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202337E+10 | 0.00 | 0.00 | 0.00 | 0.298014E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208520E+10 | 0.00 | 0.00 | 0.00 | 0.124758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202337E+10 | 0.00 | 0.00 | 0.00 | 79111062.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207396E+10 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247020E+11 | 0.00 | 0.00 | 0.00 | 0.189175E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.188848E+10 | 0.00 | 0.00 | 0.00 | 15.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213016E+10 | 0.00 | 0.00 | 0.00 | 0.391970E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.814658E+10 | 0.00 | 0.00 | 1172393.62 | 0.00 | 0.294332E+09 | 0.185181E+10 | 0.00 | 0.58 |
February | 0.528709E+10 | 0.00 | 0.00 | 3516509.33 | 0.00 | 0.157552E+09 | 0.355385E+10 | 0.00 | 0.83 |
March | 0.310213E+10 | 548433.56 | 0.00 | 7569429.16 | 0.00 | 81500197.47 | 0.666522E+10 | 0.00 | 1.07 |
April | 0.486319E+09 | 0.504178E+09 | 0.00 | 17521478.35 | 814468.25 | 0.00 | 0.497844E+10 | 0.00 | 1.19 |
May | 38421216.42 | 0.207410E+10 | 0.00 | 13720262.47 | 9075614.94 | 0.00 | 0.202657E+10 | 0.00 | 0.94 |
June | 6413180.47 | 0.449133E+10 | 0.00 | 4406234.90 | 41151766.45 | 0.00 | 0.201754E+09 | 0.00 | 0.67 |
July | 2696548.01 | 0.721551E+10 | 0.00 | 1806005.95 | 74085168.20 | 0.00 | 48945949.51 | 0.00 | 0.64 |
August | 19425394.85 | 0.463024E+10 | 0.00 | 5238747.78 | 64910262.98 | 0.00 | 0.583174E+09 | 0.00 | 0.84 |
September | 18638704.74 | 0.321741E+10 | 0.00 | 18683018.34 | 22876715.33 | 0.00 | 0.195057E+10 | 0.00 | 1.03 |
October | 0.157364E+09 | 0.755244E+09 | 0.00 | 25472887.47 | 3084298.72 | 0.00 | 0.842128E+10 | 0.00 | 1.48 |
November | 0.298246E+10 | 0.00 | 0.00 | 9545100.83 | 0.00 | 63639826.85 | 0.872624E+10 | 0.00 | 1.03 |
December | 0.889402E+10 | 0.00 | 0.00 | 709684.83 | 0.00 | 0.613141E+09 | 0.134699E+10 | 0.00 | 0.55 |
Annual Sum or Average | 0.291416E+11 | 0.228886E+11 | 0.00 | 0.109362E+09 | 0.215998E+09 | 0.121017E+10 | 0.403548E+11 | 0.00 | 0.90 |
Minimum of Months | 2696548.01 | 0.00 | 0.00 | 709684.83 | 0.00 | 0.00 | 48945949.51 | 0.00 | 0.55 |
Maximum of Months | 0.889402E+10 | 0.721551E+10 | 0.00 | 25472887.47 | 74085168.20 | 0.613141E+09 | 0.872624E+10 | 0.00 | 1.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.239229E+10 | 0.00 | 0.00 | 1796115.09 | 0.00 | 29793020.04 | 0.215880E+10 | 0.00 | 0.53 |
February | 0.147658E+10 | 0.00 | 0.00 | 3085186.17 | 0.00 | 14243262.12 | 0.299418E+10 | 0.00 | 0.87 |
March | 0.897842E+09 | 291745.40 | 0.00 | 5419509.40 | 0.00 | 5154085.61 | 0.442342E+10 | 0.00 | 1.17 |
April | 0.129591E+09 | 0.239857E+09 | 0.00 | 7251400.42 | 277236.88 | 12107.08 | 0.261087E+10 | 0.00 | 1.03 |
May | 18244467.45 | 0.982666E+09 | 0.00 | 5663538.59 | 6166065.25 | 4074.75 | 0.874439E+09 | 0.00 | 0.75 |
June | 12357223.05 | 0.195976E+10 | 0.00 | 1708241.67 | 19781011.14 | 0.00 | 68033537.86 | 0.00 | 0.54 |
July | 0.00 | 0.320245E+10 | 0.00 | 0.00 | 65927671.39 | 0.00 | 0.00 | 0.00 | 0.51 |
August | 5063546.31 | 0.208316E+10 | 0.00 | 2038794.21 | 51301946.12 | 0.00 | 0.242601E+09 | 0.00 | 0.68 |
September | 5534812.77 | 0.166402E+10 | 0.00 | 4974268.88 | 24186320.29 | 0.00 | 0.689557E+09 | 0.00 | 0.77 |
October | 44409957.42 | 0.392148E+09 | 0.00 | 10566657.14 | 1199798.43 | 0.00 | 0.424321E+10 | 0.00 | 1.41 |
November | 0.811707E+09 | 0.00 | 0.00 | 6409388.19 | 0.00 | 3186314.61 | 0.539676E+10 | 0.00 | 1.10 |
December | 0.278064E+10 | 0.00 | 0.00 | 1344179.29 | 0.00 | 94882281.15 | 0.171025E+10 | 0.00 | 0.48 |
Annual Sum or Average | 0.857427E+10 | 0.105244E+11 | 0.00 | 50257279.05 | 0.168840E+09 | 0.147275E+09 | 0.254121E+11 | 0.00 | 0.82 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.48 |
Maximum of Months | 0.278064E+10 | 0.320245E+10 | 0.00 | 10566657.14 | 65927671.39 | 94882281.15 | 0.539676E+10 | 0.00 | 1.41 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295729E+10 | 0.00 | 0.00 | 647601.14 | 0.00 | 80769766.10 | 0.947523E+09 | 0.00 | 0.48 |
February | 0.195196E+10 | 0.00 | 0.00 | 1439726.42 | 0.00 | 46186577.78 | 0.154203E+10 | 0.00 | 0.71 |
March | 0.135266E+10 | 514293.63 | 0.00 | 2933991.81 | 0.00 | 17308497.83 | 0.256530E+10 | 0.00 | 0.95 |
April | 0.297467E+09 | 0.234939E+09 | 0.00 | 3508275.62 | 5685617.46 | 0.00 | 0.181501E+10 | 0.00 | 0.89 |
May | 62469844.18 | 0.911512E+09 | 0.00 | 3262537.05 | 37017475.72 | 0.00 | 0.669281E+09 | 0.00 | 0.71 |
June | 31157275.15 | 0.177947E+10 | 0.00 | 2260943.09 | 0.112392E+09 | 0.00 | 0.100334E+09 | 0.00 | 0.56 |
July | 23234732.06 | 0.274315E+10 | 0.00 | 1035114.16 | 0.205591E+09 | 0.00 | 3695167.14 | 0.00 | 0.52 |
August | 24999217.70 | 0.182043E+10 | 0.00 | 2275767.62 | 0.101315E+09 | 0.00 | 0.273802E+09 | 0.00 | 0.69 |
September | 44604061.15 | 0.137818E+10 | 0.00 | 2422122.95 | 43676328.17 | 0.00 | 0.372831E+09 | 0.00 | 0.68 |
October | 0.197874E+09 | 0.310888E+09 | 0.00 | 6701865.79 | 12309429.07 | 0.00 | 0.280614E+10 | 0.00 | 1.12 |
November | 0.124054E+10 | 0.00 | 0.00 | 3955454.26 | 0.00 | 14848229.69 | 0.334834E+10 | 0.00 | 0.92 |
December | 0.312287E+10 | 0.00 | 0.00 | 417202.79 | 0.00 | 0.273169E+09 | 0.702393E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.113071E+11 | 0.917909E+10 | 0.00 | 30860602.69 | 0.517987E+09 | 0.432282E+09 | 0.151467E+11 | 0.00 | 0.72 |
Minimum of Months | 23234732.06 | 0.00 | 0.00 | 417202.79 | 0.00 | 0.00 | 3695167.14 | 0.00 | 0.44 |
Maximum of Months | 0.312287E+10 | 0.274315E+10 | 0.00 | 6701865.79 | 0.205591E+09 | 0.273169E+09 | 0.334834E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.296773E+10 | 0.00 | 0.00 | 503612.77 | 0.00 | 0.151895E+09 | 0.765247E+09 | 0.00 | 0.47 |
February | 0.200144E+10 | 0.00 | 0.00 | 1251022.01 | 0.00 | 58998746.14 | 0.138660E+10 | 0.00 | 0.70 |
March | 0.136716E+10 | 511051.65 | 0.00 | 2725684.40 | 0.00 | 23053364.54 | 0.244832E+10 | 0.00 | 0.93 |
April | 0.299434E+09 | 0.234873E+09 | 0.00 | 3470106.24 | 5728770.79 | 0.00 | 0.179775E+10 | 0.00 | 0.88 |
May | 64173600.87 | 0.912625E+09 | 0.00 | 3312974.81 | 36936212.09 | 0.00 | 0.669331E+09 | 0.00 | 0.71 |
June | 36731010.37 | 0.178124E+10 | 0.00 | 2321348.23 | 0.110107E+09 | 0.00 | 99275221.57 | 0.00 | 0.57 |
July | 25616520.11 | 0.274785E+10 | 0.00 | 1081715.09 | 0.204622E+09 | 0.00 | 4934940.30 | 0.00 | 0.52 |
August | 26538890.94 | 0.182070E+10 | 0.00 | 2325319.76 | 0.100669E+09 | 0.00 | 0.270435E+09 | 0.00 | 0.69 |
September | 46191018.18 | 0.138123E+10 | 0.00 | 2474896.55 | 42642781.74 | 0.00 | 0.371380E+09 | 0.00 | 0.68 |
October | 0.197330E+09 | 0.310478E+09 | 0.00 | 6705039.81 | 12540182.81 | 0.00 | 0.279674E+10 | 0.00 | 1.12 |
November | 0.126029E+10 | 0.00 | 0.00 | 3762771.65 | 0.00 | 22956816.61 | 0.322693E+10 | 0.00 | 0.90 |
December | 0.312565E+10 | 0.00 | 0.00 | 309278.24 | 0.00 | 0.336979E+09 | 0.554019E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.114183E+11 | 0.918951E+10 | 0.00 | 30243769.55 | 0.513245E+09 | 0.593884E+09 | 0.143910E+11 | 0.00 | 0.72 |
Minimum of Months | 25616520.11 | 0.00 | 0.00 | 309278.24 | 0.00 | 0.00 | 4934940.30 | 0.00 | 0.44 |
Maximum of Months | 0.312565E+10 | 0.274785E+10 | 0.00 | 6705039.81 | 0.204622E+09 | 0.336979E+09 | 0.322693E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.295631E+10 | 0.00 | 0.00 | 327389.24 | 0.00 | 0.253232E+09 | 0.554100E+09 | 0.00 | 0.46 |
February | 0.206388E+10 | 0.00 | 0.00 | 988960.26 | 0.00 | 0.107064E+09 | 0.113897E+10 | 0.00 | 0.67 |
March | 0.141076E+10 | 512348.99 | 0.00 | 2332801.79 | 0.00 | 41566233.45 | 0.221632E+10 | 0.00 | 0.90 |
April | 0.318167E+09 | 0.234875E+09 | 0.00 | 3135526.57 | 5895091.64 | 0.00 | 0.170241E+10 | 0.00 | 0.87 |
May | 62899821.71 | 0.909922E+09 | 0.00 | 3075265.47 | 37434680.72 | 0.00 | 0.651043E+09 | 0.00 | 0.70 |
June | 27517891.13 | 0.177899E+10 | 0.00 | 2200410.62 | 0.112297E+09 | 0.00 | 0.100314E+09 | 0.00 | 0.56 |
July | 21663994.93 | 0.273767E+10 | 0.00 | 1014856.44 | 0.206444E+09 | 0.00 | 3668702.50 | 0.00 | 0.51 |
August | 23216780.50 | 0.181648E+10 | 0.00 | 2236920.79 | 0.102745E+09 | 0.00 | 0.274332E+09 | 0.00 | 0.69 |
September | 44081666.18 | 0.137398E+10 | 0.00 | 2343476.10 | 44341530.93 | 0.00 | 0.367996E+09 | 0.00 | 0.67 |
October | 0.211537E+09 | 0.307552E+09 | 0.00 | 6309513.38 | 12355298.49 | 0.00 | 0.271306E+10 | 0.00 | 1.10 |
November | 0.129592E+10 | 0.00 | 0.00 | 3367378.61 | 0.00 | 56142086.37 | 0.299370E+10 | 0.00 | 0.87 |
December | 0.311264E+10 | 0.00 | 0.00 | 176060.67 | 0.00 | 0.424503E+09 | 0.370039E+09 | 0.00 | 0.43 |
Annual Sum or Average | 0.115486E+11 | 0.915999E+10 | 0.00 | 27508559.93 | 0.521512E+09 | 0.882508E+09 | 0.130860E+11 | 0.00 | 0.70 |
Minimum of Months | 21663994.93 | 0.00 | 0.00 | 176060.67 | 0.00 | 0.00 | 3668702.50 | 0.00 | 0.43 |
Maximum of Months | 0.311264E+10 | 0.273767E+10 | 0.00 | 6309513.38 | 0.206444E+09 | 0.424503E+09 | 0.299370E+10 | 0.00 | 1.10 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.552504E+10 | 0.00 | 0.00 | 318003.11 | 0.00 | 0.559269E+09 | 0.598496E+09 | 0.00 | 0.40 |
February | 0.389971E+10 | 0.00 | 0.00 | 1304679.50 | 0.00 | 0.169274E+09 | 0.170679E+10 | 0.00 | 0.57 |
March | 0.244139E+10 | 0.00 | 0.00 | 3452184.44 | 0.00 | 86092047.95 | 0.375361E+10 | 0.00 | 0.75 |
April | 0.389821E+09 | 0.293628E+09 | 0.00 | 5782022.89 | 6011965.98 | 0.00 | 0.276622E+10 | 0.00 | 0.72 |
May | 34763382.48 | 0.152879E+10 | 0.00 | 4481058.12 | 55666002.55 | 0.00 | 0.866578E+09 | 0.00 | 0.56 |
June | 26369817.15 | 0.331544E+10 | 0.00 | 2539311.81 | 0.113639E+09 | 0.00 | 82315139.57 | 0.00 | 0.46 |
July | 20144171.73 | 0.501084E+10 | 0.00 | 667751.80 | 0.202573E+09 | 0.00 | 3114531.67 | 0.00 | 0.44 |
August | 11566326.92 | 0.331079E+10 | 0.00 | 2811203.68 | 0.135569E+09 | 0.00 | 0.369805E+09 | 0.00 | 0.56 |
September | 46472928.15 | 0.241441E+10 | 0.00 | 4288209.15 | 67895718.07 | 0.00 | 0.471482E+09 | 0.00 | 0.54 |
October | 0.236022E+09 | 0.565640E+09 | 0.00 | 10141176.48 | 11904693.30 | 0.00 | 0.466914E+10 | 0.00 | 0.93 |
November | 0.231058E+10 | 0.00 | 0.00 | 4942681.01 | 0.00 | 0.124267E+09 | 0.495997E+10 | 0.00 | 0.72 |
December | 0.571096E+10 | 0.00 | 0.00 | 141898.04 | 0.00 | 0.948195E+09 | 0.352892E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.206528E+11 | 0.164395E+11 | 0.00 | 40870180.04 | 0.593260E+09 | 0.188710E+10 | 0.206004E+11 | 0.00 | 0.59 |
Minimum of Months | 11566326.92 | 0.00 | 0.00 | 141898.04 | 0.00 | 0.00 | 3114531.67 | 0.00 | 0.38 |
Maximum of Months | 0.571096E+10 | 0.501084E+10 | 0.00 | 10141176.48 | 0.202573E+09 | 0.948195E+09 | 0.495997E+10 | 0.00 | 0.93 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.268446E+10 | 0.00 | 0.00 | 135078.79 | 0.00 | 0.359523E+09 | 0.274643E+09 | 0.00 | 0.40 |
February | 0.193114E+10 | 0.00 | 0.00 | 607211.23 | 0.00 | 0.113543E+09 | 0.829821E+09 | 0.00 | 0.57 |
March | 0.123005E+10 | 0.00 | 0.00 | 1651520.92 | 0.00 | 56356531.60 | 0.185879E+10 | 0.00 | 0.76 |
April | 0.189276E+09 | 0.152457E+09 | 0.00 | 2822263.89 | 3219647.10 | 0.00 | 0.141366E+10 | 0.00 | 0.74 |
May | 15937436.11 | 0.770743E+09 | 0.00 | 2185579.60 | 30367664.87 | 0.00 | 0.445601E+09 | 0.00 | 0.57 |
June | 10547653.06 | 0.167104E+10 | 0.00 | 1204501.83 | 55550906.12 | 0.00 | 43047332.01 | 0.00 | 0.46 |
July | 10735752.11 | 0.251850E+10 | 0.00 | 339968.22 | 97332361.68 | 0.00 | 505238.57 | 0.00 | 0.44 |
August | 5548385.31 | 0.166916E+10 | 0.00 | 1360520.61 | 63817357.96 | 0.00 | 0.192497E+09 | 0.00 | 0.57 |
September | 21681303.38 | 0.121459E+10 | 0.00 | 2108931.68 | 34863894.84 | 0.00 | 0.243092E+09 | 0.00 | 0.55 |
October | 0.116658E+09 | 0.284444E+09 | 0.00 | 5128744.46 | 6438213.31 | 0.00 | 0.240054E+10 | 0.00 | 0.96 |
November | 0.114441E+10 | 0.00 | 0.00 | 2461672.34 | 0.00 | 85614862.95 | 0.251459E+10 | 0.00 | 0.74 |
December | 0.276463E+10 | 0.00 | 0.00 | 51032.90 | 0.00 | 0.581398E+09 | 0.137563E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.101251E+11 | 0.828093E+10 | 0.00 | 20057026.47 | 0.291590E+09 | 0.119644E+10 | 0.103543E+11 | 0.00 | 0.60 |
Minimum of Months | 5548385.31 | 0.00 | 0.00 | 51032.90 | 0.00 | 0.00 | 505238.57 | 0.00 | 0.38 |
Maximum of Months | 0.276463E+10 | 0.251850E+10 | 0.00 | 5128744.46 | 97332361.68 | 0.581398E+09 | 0.251459E+10 | 0.00 | 0.96 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.263095E+10 | 0.00 | 0.00 | 112357.29 | 0.00 | 0.407651E+09 | 0.249344E+09 | 0.00 | 0.40 |
February | 0.191726E+10 | 0.00 | 0.00 | 553823.51 | 0.00 | 0.137473E+09 | 0.778550E+09 | 0.00 | 0.56 |
March | 0.127173E+10 | 0.00 | 0.00 | 1517752.15 | 0.00 | 71002012.20 | 0.174065E+10 | 0.00 | 0.75 |
April | 0.195308E+09 | 0.152458E+09 | 0.00 | 2713631.30 | 3274397.10 | 0.00 | 0.138182E+10 | 0.00 | 0.73 |
May | 17722477.44 | 0.769616E+09 | 0.00 | 2129834.14 | 30384352.70 | 0.00 | 0.438243E+09 | 0.00 | 0.57 |
June | 9588689.65 | 0.167031E+10 | 0.00 | 1182066.75 | 55417940.32 | 0.00 | 42951416.45 | 0.00 | 0.46 |
July | 10086960.31 | 0.251562E+10 | 0.00 | 337901.36 | 95400274.14 | 0.00 | 515232.90 | 0.00 | 0.44 |
August | 5494159.46 | 0.166829E+10 | 0.00 | 1332835.47 | 62155394.11 | 0.00 | 0.191915E+09 | 0.00 | 0.57 |
September | 21247220.01 | 0.121199E+10 | 0.00 | 2070921.33 | 35014966.48 | 0.00 | 0.241639E+09 | 0.00 | 0.55 |
October | 0.122503E+09 | 0.283292E+09 | 0.00 | 5016239.74 | 6376850.46 | 0.00 | 0.236819E+10 | 0.00 | 0.95 |
November | 0.117027E+10 | 0.00 | 0.00 | 2324972.70 | 0.00 | 99243131.40 | 0.241770E+10 | 0.00 | 0.72 |
December | 0.270190E+10 | 0.00 | 0.00 | 39794.02 | 0.00 | 0.642167E+09 | 0.119002E+09 | 0.00 | 0.38 |
Annual Sum or Average | 0.100741E+11 | 0.827158E+10 | 0.00 | 19332129.77 | 0.288024E+09 | 0.135754E+10 | 0.997052E+10 | 0.00 | 0.59 |
Minimum of Months | 5494159.46 | 0.00 | 0.00 | 39794.02 | 0.00 | 0.00 | 515232.90 | 0.00 | 0.38 |
Maximum of Months | 0.270190E+10 | 0.251562E+10 | 0.00 | 5016239.74 | 95400274.14 | 0.642167E+09 | 0.241770E+10 | 0.00 | 0.95 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.243383E+10 | 0.00 | 0.00 | 68535.59 | 0.00 | 0.602790E+09 | 0.188965E+09 | 0.00 | 0.39 |
February | 0.185545E+10 | 0.00 | 0.00 | 426854.47 | 0.00 | 0.234175E+09 | 0.648499E+09 | 0.00 | 0.54 |
March | 0.134020E+10 | 0.00 | 0.00 | 1192455.75 | 0.00 | 0.120503E+09 | 0.147460E+10 | 0.00 | 0.71 |
April | 0.230527E+09 | 0.152800E+09 | 0.00 | 2417243.92 | 3442435.11 | 0.00 | 0.127933E+10 | 0.00 | 0.71 |
May | 18935489.27 | 0.767144E+09 | 0.00 | 1990378.49 | 30796124.01 | 0.00 | 0.424506E+09 | 0.00 | 0.57 |
June | 7918352.86 | 0.166917E+10 | 0.00 | 1112575.42 | 54187036.34 | 0.00 | 43464059.52 | 0.00 | 0.46 |
July | 8893718.52 | 0.251303E+10 | 0.00 | 332016.52 | 93375181.69 | 0.00 | 366172.32 | 0.00 | 0.43 |
August | 5203277.28 | 0.166754E+10 | 0.00 | 1280272.08 | 60838603.29 | 0.00 | 0.192742E+09 | 0.00 | 0.56 |
September | 20625352.34 | 0.121018E+10 | 0.00 | 1996155.97 | 34480938.78 | 0.00 | 0.240597E+09 | 0.00 | 0.55 |
October | 0.141527E+09 | 0.281132E+09 | 0.00 | 4763419.17 | 6312977.59 | 0.00 | 0.229155E+10 | 0.00 | 0.94 |
November | 0.125804E+10 | 0.00 | 0.00 | 1987508.99 | 0.00 | 0.164857E+09 | 0.213113E+10 | 0.00 | 0.70 |
December | 0.248046E+10 | 0.00 | 0.00 | 17493.45 | 0.00 | 0.863230E+09 | 76469186.49 | 0.00 | 0.38 |
Annual Sum or Average | 0.980161E+10 | 0.826099E+10 | 0.00 | 17584909.83 | 0.283433E+09 | 0.198555E+10 | 0.899221E+10 | 0.00 | 0.58 |
Minimum of Months | 5203277.28 | 0.00 | 0.00 | 17493.45 | 0.00 | 0.00 | 366172.32 | 0.00 | 0.38 |
Maximum of Months | 0.248046E+10 | 0.251303E+10 | 0.00 | 4763419.17 | 93375181.69 | 0.863230E+09 | 0.229155E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.172676E+10 | 0.00 | 0.00 | 19985.95 | 0.00 | 0.130800E+10 | 93321709.67 | 0.00 | 0.39 |
February | 0.151028E+10 | 0.00 | 0.00 | 276096.14 | 0.00 | 0.642687E+09 | 0.488876E+09 | 0.00 | 0.54 |
March | 0.124609E+10 | 0.00 | 0.00 | 791563.97 | 0.00 | 0.394415E+09 | 0.113719E+10 | 0.00 | 0.71 |
April | 0.269951E+09 | 0.158862E+09 | 0.00 | 2147992.91 | 3290297.04 | 9374083.97 | 0.120365E+10 | 0.00 | 0.75 |
May | 20111095.09 | 0.794395E+09 | 0.00 | 1761868.74 | 30647001.19 | 0.00 | 0.435385E+09 | 0.00 | 0.60 |
June | 10844387.66 | 0.169384E+10 | 0.00 | 1118547.71 | 46558849.64 | 0.00 | 53839925.95 | 0.00 | 0.47 |
July | 13604823.66 | 0.255553E+10 | 0.00 | 878416.58 | 77720705.10 | 0.00 | 11856758.81 | 0.00 | 0.45 |
August | 15808453.92 | 0.170745E+10 | 0.00 | 1711783.29 | 48970011.63 | 0.00 | 0.227763E+09 | 0.00 | 0.60 |
September | 29965043.55 | 0.123336E+10 | 0.00 | 2374351.93 | 27097161.05 | 0.00 | 0.270491E+09 | 0.00 | 0.58 |
October | 0.192466E+09 | 0.291587E+09 | 0.00 | 4666940.90 | 5199394.81 | 0.00 | 0.230803E+10 | 0.00 | 1.01 |
November | 0.120038E+10 | 0.00 | 0.00 | 1694508.11 | 0.00 | 0.353012E+09 | 0.193391E+10 | 0.00 | 0.72 |
December | 0.186135E+10 | 0.00 | 0.00 | 4253.86 | 0.00 | 0.146150E+10 | 28678026.86 | 0.00 | 0.38 |
Annual Sum or Average | 0.809761E+10 | 0.843503E+10 | 0.00 | 17446310.10 | 0.239483E+09 | 0.416899E+10 | 0.819299E+10 | 0.00 | 0.60 |
Minimum of Months | 10844387.66 | 0.00 | 0.00 | 4253.86 | 0.00 | 0.00 | 11856758.81 | 0.00 | 0.38 |
Maximum of Months | 0.186135E+10 | 0.255553E+10 | 0.00 | 4666940.90 | 77720705.10 | 0.146150E+10 | 0.230803E+10 | 0.00 | 1.01 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:34
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.180306E+12 | 0.209017E+11 | 0.00 | 0.466586E+11 | 0.143414E+10 |
February | 0.191296E+12 | 0.156526E+11 | 0.00 | 0.409861E+11 | 0.383182E+10 |
March | 0.295350E+12 | 0.142475E+11 | 0.00 | 0.450005E+11 | 0.100260E+11 |
April | 0.321505E+12 | 0.467313E+10 | 0.00 | 0.215117E+11 | 0.673131E+11 |
May | 0.347695E+12 | -0.259845E+10 | 0.00 | -0.279122E+10 | 0.131527E+12 |
June | 0.347377E+12 | -0.913392E+10 | 0.00 | -0.215057E+11 | 0.184196E+12 |
July | 0.343310E+12 | -0.139366E+11 | 0.00 | -0.348963E+11 | 0.212173E+12 |
August | 0.313101E+12 | -0.882506E+10 | 0.00 | -0.200533E+11 | 0.188339E+12 |
September | 0.283384E+12 | -0.577764E+10 | 0.00 | -0.111732E+11 | 0.161603E+12 |
October | 0.246878E+12 | 0.499541E+10 | 0.00 | 0.328825E+11 | 0.739161E+11 |
November | 0.186129E+12 | 0.160262E+11 | 0.00 | 0.535145E+11 | 0.651389E+10 |
December | 0.147179E+12 | 0.213579E+11 | 0.00 | 0.491293E+11 | 0.226109E+10 |
Annual Sum or Average | 0.320351E+13 | 0.575826E+11 | 0.00 | 0.199263E+12 | 0.104313E+13 |
Minimum of Months | 0.147179E+12 | -0.139366E+11 | 0.00 | -0.348963E+11 | 0.143414E+10 |