Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885
Simulation Timestamp: 2023-10-16 08:40:46
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1328.93 | 635.75 | 635.75 |
Net Site Energy | 1328.93 | 635.75 | 635.75 |
Total Source Energy | 3544.13 | 1695.50 | 1695.50 |
Net Source Energy | 3544.13 | 1695.50 | 1695.50 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 319.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 12.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 220.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1009.88 | 319.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 319.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 12.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 220.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 319.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 12.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 220.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 65.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.44 | 152.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 483.12 | 152.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 142.44 | 152.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 483.12 | 152.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1009.875 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1009.875 | 100.00 |
Total On-Site and Utility Electric Sources | 1009.875 | 100.00 |
Total Electricity End Uses | 1009.875 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 0.00 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1565.33 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | William R Fairchild WA USA TMY3 WMO#=727885 |
Latitude [deg] | 48.12 |
Longitude [deg] | -123.5 |
Elevation [m] | 91.00 |
Time Zone | -8.0 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 22-JUL-14:00 | 10-JAN-09:09 | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 176597.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 28591.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5452.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 83621.50 | 176597.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 176597.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 28591.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5452.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 345.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 39.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 383.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 696.81 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 206.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 3198.27 | 345.86 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 165.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 333.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1530.04 | 165.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 165.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 18.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 183.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 333.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 98.80 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 1530.04 | 165.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 1.88 |
SMSTORE1 DIRECT AIR | 1.02 |
SMSTORE2 DIRECT AIR | 1.00 |
SMSTORE3 DIRECT AIR | 1.03 |
SMSTORE4 DIRECT AIR | 0.994838 |
LGSTORE2 DIRECT AIR | 1.77 |
SMSTORE5 DIRECT AIR | 0.955558 |
SMSTORE6 DIRECT AIR | 0.949594 |
SMSTORE7 DIRECT AIR | 0.937935 |
SMSTORE8 DIRECT AIR | 0.967314 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 1.88 | 1.88 | 1.88 | 1.88 | 1.88 | 1.88 | 1.00 | 1.00 | 1.88 |
PSZ-AC_2:2 | 1.02 | 1.02 | 1.02 | 1.02 | 1.03 | 1.03 | 1.00 | 0.989269 | 1.03 |
PSZ-AC_3:3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.02 | 1.02 | 1.00 | 0.977190 | 1.02 |
PSZ-AC_4:4 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.03 | 1.00 | 1.00 | 1.03 |
PSZ-AC_5:5 | 0.994838 | 0.994838 | 0.994838 | 0.994838 | 1.02 | 1.02 | 1.00 | 0.975884 | 1.02 |
PSZ-AC_6:6 | 1.77 | 1.77 | 1.77 | 1.77 | 1.82 | 1.82 | 1.00 | 0.973014 | 1.82 |
PSZ-AC_7:7 | 0.955558 | 0.955558 | 0.955558 | 0.955558 | 0.965322 | 0.965322 | 1.00 | 0.989885 | 0.965322 |
PSZ-AC_8:8 | 0.949594 | 0.949594 | 0.949594 | 0.949594 | 0.959717 | 0.959717 | 1.00 | 0.989452 | 0.959717 |
PSZ-AC_9:9 | 0.937935 | 0.937935 | 0.937935 | 0.937935 | 0.949648 | 0.949648 | 1.00 | 0.987666 | 0.949648 |
PSZ-AC_10:10 | 0.967314 | 0.967314 | 0.967314 | 0.967314 | 0.989185 | 0.989185 | 1.00 | 0.977890 | 0.989185 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 1.88 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.03 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.02 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 1.82 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 0.965322 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 0.959717 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 0.949648 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 0.989185 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 1.88 | 2007.50 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1140.06 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1133.94 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.03 | 1137.60 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.02 | 1128.66 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 1.82 | 1944.28 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 0.965322 | 1068.76 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 0.959717 | 1062.56 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 0.949648 | 1051.41 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 0.989185 | 1095.19 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 1.88 | 1.88 | 1.88 | 1.88 | 31055.94 | 54947.72 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17045.53 | 29297.42 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 16954.03 | 28893.94 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.03 | 1.03 | 1.03 | 1.03 | 17008.67 | 29496.98 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.02 | 1.02 | 1.02 | 1.02 | 16875.07 | 28758.41 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 1.82 | 1.82 | 1.82 | 1.82 | 30077.94 | 52502.26 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 0.965322 | 0.965322 | 0.965322 | 0.965322 | 15979.51 | 27870.00 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 0.959717 | 0.959717 | 0.959717 | 0.959717 | 15886.72 | 27735.11 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 0.949648 | 0.949648 | 0.949648 | 0.949648 | 15720.04 | 27471.42 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 0.989185 | 0.989185 | 0.989185 | 0.989185 | 16374.53 | 28136.14 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 1.88 | 0.938045 | 1.88 | 31055.94 | 15527.98 | 31055.94 | 0.800660 | 0.800660 |
PSZ-AC_2:2 COOLING COIL | 1.03 | 0.514860 | 1.03 | 17045.53 | 8522.76 | 17045.53 | 0.800660 | 0.800660 |
PSZ-AC_3:3 COOLING COIL | 1.02 | 0.512096 | 1.02 | 16954.03 | 8477.01 | 16954.03 | 0.800660 | 0.800660 |
PSZ-AC_4:4 COOLING COIL | 1.03 | 0.513747 | 1.03 | 17008.67 | 8504.33 | 17008.67 | 0.800660 | 0.800660 |
PSZ-AC_5:5 COOLING COIL | 1.02 | 0.509712 | 1.02 | 16875.07 | 8437.54 | 16875.07 | 0.800660 | 0.800660 |
PSZ-AC_6:6 COOLING COIL | 1.82 | 0.908504 | 1.82 | 30077.94 | 15038.98 | 30077.94 | 0.800660 | 0.800660 |
PSZ-AC_7:7 COOLING COIL | 0.965320 | 0.482661 | 0.965320 | 15979.51 | 7989.76 | 15979.51 | 0.800660 | 0.800660 |
PSZ-AC_8:8 COOLING COIL | 0.959720 | 0.479859 | 0.959720 | 15886.72 | 7943.39 | 15886.72 | 0.800660 | 0.800660 |
PSZ-AC_9:9 COOLING COIL | 0.949650 | 0.474824 | 0.949650 | 15720.04 | 7860.04 | 15720.04 | 0.800660 | 0.800660 |
PSZ-AC_10:10 COOLING COIL | 0.989190 | 0.494593 | 0.989190 | 16374.53 | 8187.30 | 16374.53 | 0.800660 | 0.800660 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 54947.72 |
PSZ-AC_2:2 HEATING COIL | 29297.42 |
PSZ-AC_3:3 HEATING COIL | 28893.94 |
PSZ-AC_4:4 HEATING COIL | 29496.98 |
PSZ-AC_5:5 HEATING COIL | 28758.41 |
PSZ-AC_6:6 HEATING COIL | 52502.26 |
PSZ-AC_7:7 HEATING COIL | 27870.00 |
PSZ-AC_8:8 HEATING COIL | 27735.11 |
PSZ-AC_9:9 HEATING COIL | 27471.42 |
PSZ-AC_10:10 HEATING COIL | 28136.14 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 9.30 | 6.70 | 4.10 | 4.20 | 4.20 | 5.90 | 9.00 | 10.00 | 13.30 | 15.00 | 15.70 | 13.40 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | William R Fairchild WA USA TMY3 WMO#=727885 | 48.12 | -123.50 | -8.00 | 91.00 | 100237 | 1.1914 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 9.23 | 11.60 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 2.101 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2284 | 0.900 | 0.900 | 0.770 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.6641 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1464 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.8283E-01 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2111 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.4760 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 4.319 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.272 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 6.756 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 12.00 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.659 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 2.1009573 | 2.1009573 | 2.1009573 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.62451068E-06 | 0.10350887E-08 | -0.38276125E-05 | 0.11995084E-16 |
19 | 2 | 0.77976586 | 0.13989883E-02 | 1.0579789 | -0.73382352E-06 |
20 | 1 | -21.958702 | 0.93426804E-01 | -6.3215779 | 0.20283230 |
21 | 0 | 21.361010 | 0.87247630E-01 | 5.4456762 | |
22 | 7 | -0.32972738E-12 | 0.11763143E-14 | -0.10490290E-12 | 0.10060316E-15 |
23 | 6 | 0.30001920E-07 | 0.18927851E-09 | 0.68616814E-08 | -0.14235861E-12 |
24 | 5 | -0.19683904E-03 | 0.16062604E-05 | -0.10115234E-03 | 0.67789156E-08 |
25 | 4 | 0.29998857 | 0.77587294E-03 | 0.10250533 | -0.34681058E-04 |
26 | 3 | -7.4215481 | 0.23875067E-01 | -2.3849775 | 0.29769922E-01 |
27 | 2 | 41.382972 | 0.84366340E-01 | 15.453844 | -0.33904133 |
28 | 1 | -80.937908 | 0.37867119E-01 | -29.310851 | 1.0869756 |
29 | 0 | 46.824336 | 0.75775345E-03 | 16.287225 | |
30 | 7 | -0.28997596E-08 | -0.17578320E-14 | 0.22751757E-14 | -0.53829073E-16 |
31 | 6 | 0.41991781E-05 | 0.27986603E-08 | 0.31940183E-02 | -0.26794102E-04 |
32 | 5 | -0.29588474E-03 | 0.16552611E-05 | -0.22396035 | 0.19582313E-02 |
33 | 4 | 0.67666006E-02 | 0.75295852E-04 | 4.8334724 | -0.45302727E-01 |
34 | 3 | -0.59297736E-01 | 0.59838054E-03 | -38.043598 | 0.39889893 |
35 | 2 | 0.21038411 | 0.99492606E-03 | 116.52712 | -1.4185167 |
36 | 1 | -0.30354941 | 0.30287292E-03 | -143.93272 | 2.0494576 |
37 | 0 | 0.14796861 | 0.73483799E-05 | 60.838472 | |
38 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
39 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
40 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
41 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
42 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
43 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
44 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
45 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
46 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
47 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
48 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
49 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
50 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
51 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
52 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
53 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
54 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789911E-14 | -0.32998980E-16 |
55 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
56 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
57 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
58 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
59 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
60 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
61 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
62 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
63 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
64 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
65 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
66 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
67 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
68 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
69 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
70 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
71 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
72 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
73 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
74 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
75 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
76 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
77 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
78 | 7 | -0.51571905E-08 | -0.97500957E-14 | 0.15789917E-14 | -0.32998991E-16 |
79 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
80 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
81 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
82 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
83 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
84 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
85 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
86 | 7 | -0.51571905E-08 | -0.97500959E-14 | 0.15789915E-14 | -0.32998988E-16 |
87 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
88 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
89 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
90 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
91 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
92 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
93 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
94 | 7 | -0.51571905E-08 | -0.97500958E-14 | 0.15789913E-14 | -0.32998984E-16 |
95 | 6 | 0.26247599E-05 | 0.15902949E-08 | 0.31989528E-02 | -0.26835497E-04 |
96 | 5 | -0.17282397E-03 | 0.93714128E-06 | -0.22424071 | 0.19607060E-02 |
97 | 4 | 0.38696203E-02 | 0.42548205E-04 | 4.8381400 | -0.45347597E-01 |
98 | 3 | -0.33643188E-01 | 0.33758390E-03 | -38.069955 | 0.39919029 |
99 | 2 | 0.11898200 | 0.56044665E-03 | 116.57840 | -1.4192028 |
100 | 1 | -0.17142224 | 0.17027190E-03 | -143.96290 | 2.0499538 |
101 | 0 | 0.83499932E-01 | 0.41268798E-05 | 60.838472 | |
102 | 7 | -0.19967951E-08 | -0.58252365E-15 | 0.72897552E-14 | -0.10630581E-15 |
103 | 6 | 0.59274927E-05 | 0.40433693E-08 | 0.31889525E-02 | -0.26751606E-04 |
104 | 5 | -0.42514865E-03 | 0.23948505E-05 | -0.22367243 | 0.19556901E-02 |
105 | 4 | 0.97725356E-02 | 0.10900143E-03 | 4.8286774 | -0.45256634E-01 |
106 | 3 | -0.85796444E-01 | 0.86675557E-03 | -38.016512 | 0.39859954 |
107 | 2 | 0.30461848 | 0.14417950E-02 | 116.47440 | -1.4178116 |
108 | 1 | -0.43965446 | 0.43929230E-03 | -143.90169 | 2.0489476 |
109 | 0 | 0.21434897 | 0.10616597E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 35 | 1 | VerySmooth | 2.168 | 2.168 | 1.000 | 0.401 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 3.44376E-002 | 0.31435 | 0.47922 | 0.47922 | 0.40000 | 0.13759 | 0.17962 | 0.00000 | 0.84000 | 0.84000 | 0.11914 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.157 | 4.517E-004 | 2.488E-004 | 0.314 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 3.813E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 8.993E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.241 | 6.922E-004 | 4.692E-004 | 0.481 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 4.496E-002 | 2.581E-004 | 1.749E-004 | 0.179 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 5.233E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.112 | 6.453E-004 | 2.994E-004 | 0.448 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.135 | 7.722E-004 | 3.583E-004 | 0.536 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 21079.12479 | 25294.94974 | 1.56341 | 1.87609 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 26.40000 | 8.40708E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 19486.89341 | 23384.27209 | 0.84905 | 1.01886 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 11778.99089 | 14134.78907 | 0.84889 | 1.01867 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 9179.91128 | 11015.89354 | 0.39997 | 0.47996 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 11578.26512 | 13893.91814 | 0.83403 | 1.00083 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 9293.75388 | 11152.50465 | 0.40493 | 0.48592 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 11544.66043 | 13853.59251 | 0.85624 | 1.02749 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 26.32417 | 8.40696E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 9396.37898 | 11275.65478 | 0.40940 | 0.49128 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 11510.88444 | 13813.06132 | 0.82903 | 0.99484 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 21.39500 | 8.39928E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 9576.23799 | 11491.48559 | 0.41724 | 0.50069 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 20524.49155 | 24629.38987 | 1.47331 | 1.76797 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 18603.37001 | 22324.04401 | 0.81056 | 0.97267 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 11066.50190 | 13279.80228 | 0.79630 | 0.95556 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 9897.81375 | 11877.37650 | 0.43125 | 0.51750 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 10999.41113 | 13199.29336 | 0.79133 | 0.94959 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 9895.94957 | 11875.13949 | 0.43117 | 0.51740 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 10868.30627 | 13041.96753 | 0.78161 | 0.93794 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 10178.79585 | 12214.55502 | 0.44349 | 0.53219 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 11198.69173 | 13438.43008 | 0.80610 | 0.96731 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 22.94200 | 8.40167E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 12246.71222 | 14696.05466 | 0.53358 | 0.64030 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | -4.30000 | 2.65759E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 26141.15 | 1.87609 | 1.87609 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 35559.65 | 1.01886 | 1.01886 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 14183.67 | 1.02972 | 1.02972 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 17113.42 | 0.47996 | 0.47996 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 14213.53 | 1.02419 | 1.02419 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 17248.04 | 0.48592 | 0.48592 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 14256.58 | 1.02749 | 1.02749 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 17369.40 | 0.49128 | 0.49128 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 14149.64 | 1.01942 | 1.01942 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 17582.09 | 0.50069 | 0.50069 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 25348.50 | 1.81701 | 1.81701 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 34514.93 | 0.97267 | 0.97267 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 13065.26 | 0.96532 | 0.96532 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 17962.36 | 0.51750 | 0.51750 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 12982.17 | 0.95972 | 0.95972 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 17960.16 | 0.51740 | 0.51740 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 12893.21 | 0.94965 | 0.94965 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 18294.63 | 0.53219 | 0.53219 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 13252.65 | 0.98919 | 0.98919 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 20739.92 | 0.64030 | 0.64030 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.87609 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.01867 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.00083 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.02749 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.99484 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.76797 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.95556 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.94959 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.93794 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 0.96731 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.87609 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.87609 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.87609 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.87609 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.87609 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 1.87609 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.01867 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.01867 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.01867 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.01867 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02972 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02972 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 0.98927 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.00083 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.00083 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.00083 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.00083 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02419 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02419 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 0.97719 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.02749 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.02749 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.02749 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.02749 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.02749 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.02749 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.99484 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.99484 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.99484 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.99484 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.01942 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.01942 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 0.97588 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.76797 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.76797 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.76797 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.76797 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.81701 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 1.81701 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 0.97301 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.95556 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.95556 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.95556 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.95556 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.96532 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 0.96532 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 0.98989 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.94959 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.94959 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.94959 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.94959 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.95972 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 0.95972 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 0.98945 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.93794 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.93794 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.93794 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.93794 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.94965 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 0.94965 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 0.98767 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 0.96731 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 0.96731 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 0.96731 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 0.96731 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 0.98919 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 0.98919 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 0.97789 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 1.87609 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.02972 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.02419 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.02749 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.01942 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 1.81701 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 0.96532 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 0.95972 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 0.94965 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 0.98919 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.87609 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.87609 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2007.50411 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.87609 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.87609 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.87609 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.87609 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.87609 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.93804 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.87609 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 31055.94000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15527.97550 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 31055.94000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 31055.94000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 54947.72064 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 54947.72064 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02972 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02972 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1140.06387 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02972 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02972 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02972 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02972 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02972 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51486 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02972 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17045.53000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8522.76393 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17045.53000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17045.53000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29297.41654 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 29297.41654 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02419 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02419 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1133.94392 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02419 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02419 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02419 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02419 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02419 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51210 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02419 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16954.03000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8477.01309 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16954.03000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16954.03000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28893.94227 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 28893.94227 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.02749 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.02749 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1137.59842 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.02749 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.02749 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.02749 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.02749 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.02749 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.51375 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.02749 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 17008.67000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8504.33297 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 17008.67000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 17008.67000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 29496.97845 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 29496.97845 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.01942 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.01942 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1128.66324 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.01942 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.01942 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.01942 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.01942 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.01942 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.50971 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.01942 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16875.07000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8437.53633 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16875.07000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16875.07000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28758.40856 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 28758.40856 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.81701 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.81701 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1944.28465 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.81701 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.81701 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.81701 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.81701 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.81701 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.90850 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.81701 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 30077.94000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 15038.98361 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 30077.94000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 30077.94000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 52502.26356 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 52502.26356 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.96532 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.96532 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1068.76497 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.96532 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.96532 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.96532 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.96532 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.96532 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.48266 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.96532 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15979.51000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 7989.75548 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15979.51000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15979.51000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27869.99977 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 27869.99977 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.95972 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.95972 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1062.55911 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.95972 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.95972 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.95972 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.95972 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.95972 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47986 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.95972 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15886.72000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 7943.38686 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15886.72000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15886.72000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27735.11452 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 27735.11452 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.94965 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.94965 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1051.41074 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.94965 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.94965 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.94965 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.94965 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.94965 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.47482 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.94965 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 15720.04000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 7860.03973 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 15720.04000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 15720.04000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 27471.41616 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 27471.41616 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 0.98919 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 0.98919 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1095.18536 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 0.98919 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 0.98919 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 0.98919 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 0.98919 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 0.98919 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.49459 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 0.98919 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 16374.53000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 8187.30343 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 16374.53000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.80066 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.80066 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 16374.53000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 28136.14499 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 28136.14499 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 29585.6 | 10.74 | 10.74 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 16238.5 | 11.00 | 11.00 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 16151.4 | 11.00 | 11.00 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 16203.4 | 11.00 | 11.00 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 16076.1 | 11.00 | 11.00 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 28653.9 | 10.74 | 10.74 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 15223.0 | 11.00 | 11.00 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 15134.6 | 11.00 | 11.00 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 14975.8 | 11.00 | 11.00 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 15599.3 | 11.00 | 11.00 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.146 | 0.141 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 8.283E-002 | 8.119E-002 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.3815_SHGC_0.4 | N/A | 2.168 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 2.101 | 2.101 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.664 | 0.604 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.211 | 0.201 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.228 | 0.219 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 2.4870433653E-002 | 8.6081949748E-002 | Pass | Pass | 0.2064370630 | 0.8144187527 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 4.6014965869E-002 | 8.1744888926E-002 | Pass | Pass | 0.5943250467 | 4.7565321971 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 2.6660952679E-002 | 7.7734880549E-002 | Pass | Pass | 6.9338161254E-002 | 0.2614286553 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.1634593710E-002 | 0.1125667455 | Pass | Pass | 0.1630610883 | 0.9132657834 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.6330288891E-002 | 0.1360194882 | Pass | Pass | 0.1381724453 | 0.5140906222 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 4.6155360052E-002 | 0.1652057336 | Pass | Pass | 6.6842218400E-002 | 0.2041880913 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 4.6543937298E-002 | 0.1691955740 | Pass | Pass | 7.8323761919E-002 | 0.3016414849 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 4.8198269698E-002 | 0.1825706235 | Pass | Pass | 8.4496374132E-002 | 0.3727423383 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 5.9462148852E-002 | 0.2275393774 | Pass | Pass | 9.3038788504E-002 | 0.4989403050 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 7.5686350522E-002 | 0.2996695208 | Pass | Pass | 7.3773450537E-002 | 0.2958528173 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 3516.49 | 227.88 | 0.00 | 692.53 | 124.40 | 4561.33 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | -4.30 | 0.00 | -4.30 | Wetbulb [C] | 1.20 | 110.00 |
WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 26.40 | 9.10 | 17.00 | Wetbulb [C] | 2.10 | 90.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 0.00 | 0 | |||
Feb | 42.00 | 35 | |||
Mar | 0.00 | 0 | |||
Apr | 0.00 | 0 | |||
May | 40.00 | 22 | |||
Jun | 4.00 | 8 | |||
Jul | 5.00 | 4 | |||
Aug | 7.00 | 8 | |||
Sep | 17.00 | 10 | |||
Oct | 50.00 | 49 | |||
Nov | 69.00 | 59 | |||
Dec | 95.00 | 53 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.143 | 0.146 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.082 | 0.083 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.604 | 0.664 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.204 | 0.211 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.23 | 0.221 | 0.228 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.168 | 0.401 | 0.402 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.3815_SHGC_0.4 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.168 | 0.401 | 0.402 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.168 | 0.401 | 0.402 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.168 | 0.401 | 0.402 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 1.598 | 2.101 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.54 | 83.54 | 121.11 | |
Exterior Lighting Total | 7723.26 | 121.11 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 31055.94 | 24865.25 | 6190.69 | 0.80 | 3.80 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17045.53 | 13647.67 | 3397.86 | 0.80 | 3.91 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16954.03 | 13574.41 | 3379.62 | 0.80 | 3.91 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 17008.67 | 13618.16 | 3390.51 | 0.80 | 3.91 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16875.07 | 13511.19 | 3363.88 | 0.80 | 3.91 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 30077.94 | 24082.20 | 5995.74 | 0.80 | 3.80 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15979.51 | 12794.15 | 3185.36 | 0.80 | 3.91 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15886.72 | 12719.86 | 3166.86 | 0.80 | 3.91 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 15720.04 | 12586.41 | 3133.63 | 0.80 | 3.91 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 16374.53 | 13110.43 | 3264.10 | 0.80 | 3.91 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 29585.6 | 10.74 | 10.74 | ||||
PSZ-AC_2:2 COOLING COIL | 16238.5 | 11.00 | 11.00 | ||||
PSZ-AC_3:3 COOLING COIL | 16151.4 | 11.00 | 11.00 | ||||
PSZ-AC_4:4 COOLING COIL | 16203.4 | 11.00 | 11.00 | ||||
PSZ-AC_5:5 COOLING COIL | 16076.1 | 11.00 | 11.00 | ||||
PSZ-AC_6:6 COOLING COIL | 28653.9 | 10.74 | 10.74 | ||||
PSZ-AC_7:7 COOLING COIL | 15223.0 | 11.00 | 11.00 | ||||
PSZ-AC_8:8 COOLING COIL | 15134.6 | 11.00 | 11.00 | ||||
PSZ-AC_9:9 COOLING COIL | 14975.8 | 11.00 | 11.00 | ||||
PSZ-AC_10:10 COOLING COIL | 15599.3 | 11.00 | 11.00 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 54947.72 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 29297.42 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 28893.94 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 29496.98 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 28758.41 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 52502.26 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 27870.00 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 27735.11 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 27471.42 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 28136.14 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.88 | 2007.50 | 1070.05 | 1.00 | 1.32 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1140.06 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1133.94 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.03 | 1137.60 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 1.02 | 1128.66 | 1107.16 | 1.00 | 1.40 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.82 | 1944.28 | 1070.05 | 1.00 | 1.33 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.97 | 1068.76 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.96 | 1062.56 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.95 | 1051.41 | 1107.16 | 1.00 | 1.42 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.56 | 622.50 | 0.99 | 1095.19 | 1107.16 | 1.00 | 1.41 | General | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 21079.12 | 25294.95 | 72.61 | 1.563 | 1.876 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00900 | 26.40 | 0.00841 | 0.411 | 0.00 |
SMSTORE1 | 11778.99 | 14134.79 | 81.14 | 0.849 | 1.019 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00921 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE2 | 11578.27 | 13893.92 | 79.76 | 0.834 | 1.001 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00944 | 21.39 | 0.00840 | 0.206 | 0.00 |
SMSTORE3 | 11544.66 | 13853.59 | 79.53 | 0.856 | 1.027 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00895 | 26.32 | 0.00841 | 0.206 | 0.00 |
SMSTORE4 | 11510.88 | 13813.06 | 79.30 | 0.829 | 0.995 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 09:00:00 | 23.89 | 23.89 | 0.00945 | 21.39 | 0.00840 | 0.206 | 0.00 |
LGSTORE2 | 20524.49 | 24629.39 | 70.70 | 1.473 | 1.768 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.88 | 0.00954 | 22.94 | 0.00840 | 0.411 | 0.00 |
SMSTORE5 | 11066.50 | 13279.80 | 76.24 | 0.796 | 0.956 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00941 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE6 | 10999.41 | 13199.29 | 75.77 | 0.791 | 0.950 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00942 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE7 | 10868.31 | 13041.97 | 74.87 | 0.782 | 0.938 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00944 | 22.94 | 0.00840 | 0.206 | 0.00 |
SMSTORE8 | 11198.69 | 13438.43 | 77.15 | 0.806 | 0.967 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | 23.89 | 23.89 | 0.00936 | 22.94 | 0.00840 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 19486.89 | 23384.27 | 67.12 | 0.849 | 1.019 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00685 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE1 | 9179.91 | 11015.89 | 63.24 | 0.400 | 0.480 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00672 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE2 | 9293.75 | 11152.50 | 64.02 | 0.405 | 0.486 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00673 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE3 | 9396.38 | 11275.65 | 64.73 | 0.409 | 0.491 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00674 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE4 | 9576.24 | 11491.49 | 65.97 | 0.417 | 0.501 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00675 | -4.30 | 0.00266 | 0.206 | 0.00 |
LGSTORE2 | 18603.37 | 22324.04 | 64.08 | 0.811 | 0.973 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00684 | -4.30 | 0.00266 | 0.411 | 0.00 |
SMSTORE5 | 9897.81 | 11877.38 | 68.19 | 0.431 | 0.517 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE6 | 9895.95 | 11875.14 | 68.17 | 0.431 | 0.517 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00678 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE7 | 10178.80 | 12214.56 | 70.12 | 0.443 | 0.532 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00680 | -4.30 | 0.00266 | 0.206 | 0.00 |
SMSTORE8 | 12246.71 | 14696.05 | 84.37 | 0.534 | 0.640 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00689 | -4.30 | 0.00266 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 1.88 | 1.88 | 1.02 | 1.02 | 1.8761 | 1.8761 | 1.8761 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.03 | 1.03 | 0.48 | 0.48 | 1.0297 | 1.0187 | 1.0297 | 0.9893 | 1.0000 |
PSZ-AC_3:3 | 1.02 | 1.02 | 0.49 | 0.49 | 1.0242 | 1.0008 | 1.0242 | 0.9772 | 1.0000 |
PSZ-AC_4:4 | 1.03 | 1.03 | 0.49 | 0.49 | 1.0275 | 1.0275 | 1.0275 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.02 | 1.02 | 0.50 | 0.50 | 1.0194 | 0.9948 | 1.0194 | 0.9759 | 1.0000 |
PSZ-AC_6:6 | 1.82 | 1.82 | 0.97 | 0.97 | 1.8170 | 1.7680 | 1.8170 | 0.9730 | 1.0000 |
PSZ-AC_7:7 | 0.97 | 0.97 | 0.52 | 0.52 | 0.9653 | 0.9556 | 0.9653 | 0.9899 | 1.0000 |
PSZ-AC_8:8 | 0.96 | 0.96 | 0.52 | 0.52 | 0.9597 | 0.9496 | 0.9597 | 0.9895 | 1.0000 |
PSZ-AC_9:9 | 0.95 | 0.95 | 0.53 | 0.53 | 0.9496 | 0.9379 | 0.9496 | 0.9877 | 1.0000 |
PSZ-AC_10:10 | 0.99 | 0.99 | 0.64 | 0.64 | 0.9892 | 0.9673 | 0.9892 | 0.9779 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 31055.940 | 24865.249 | 1.876090 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 31055.94 | 29130.36 | 1.876090 | 25.32 | 17.05 | 0.00886755 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 21.9328 | 23.89 | 0.00899692 | 48.2017 | 21079.12 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 54947.721 | 54947.721 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 54947.72 | 54947.72 | 1.876089 | 15.54 | 10.52 | 0.00592754 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.9328 | 21.11 | 0.00684623 | 43.5830 | 19486.89 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 17045.530 | 13647.674 | 1.029720 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 17045.53 | 16046.72 | 1.029720 | 25.30 | 17.03 | 0.00884574 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 19.9801 | 23.89 | 0.00895632 | 47.9870 | 11481.73 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 29297.417 | 29297.417 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29297.42 | 29297.42 | 1.029720 | 16.03 | 10.71 | 0.00591052 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 19.9801 | 21.11 | 0.00672274 | 42.8055 | 9179.91 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 16954.030 | 13574.414 | 1.024190 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 16954.03 | 15961.72 | 1.024190 | 25.30 | 17.03 | 0.00884529 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 20.0880 | 23.89 | 0.00895546 | 47.9825 | 11507.00 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 28893.942 | 28893.942 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28893.94 | 28893.94 | 1.024193 | 16.00 | 10.70 | 0.00591318 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.0880 | 21.11 | 0.00673156 | 42.8612 | 9293.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 17008.670 | 13618.162 | 1.027490 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 17008.67 | 16014.81 | 1.027490 | 25.30 | 17.03 | 0.00884465 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 20.0235 | 23.89 | 0.00895421 | 47.9759 | 11543.44 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 29496.978 | 29496.978 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 29496.98 | 29496.98 | 1.027494 | 16.02 | 10.72 | 0.00592231 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.0234 | 21.11 | 0.00673969 | 42.9124 | 9396.38 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 16875.070 | 13511.194 | 1.019420 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 16875.07 | 15884.95 | 1.019420 | 25.31 | 17.03 | 0.00884625 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 20.1820 | 23.89 | 0.00895731 | 47.9923 | 11452.93 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 28758.409 | 28758.409 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28758.41 | 28758.41 | 1.019423 | 15.98 | 10.71 | 0.00592736 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.1819 | 21.11 | 0.00675412 | 43.0033 | 9576.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 30077.940 | 24082.203 | 1.817010 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 30077.94 | 28172.65 | 1.817010 | 25.34 | 17.06 | 0.00887653 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 22.6459 | 23.89 | 0.00901403 | 48.2921 | 20408.20 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 52502.264 | 52502.264 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 52502.26 | 52502.26 | 1.817008 | 15.35 | 10.40 | 0.00589377 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 22.6460 | 21.11 | 0.00684118 | 43.5509 | 18603.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 15979.510 | 12794.154 | 0.965320 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 15979.51 | 15001.94 | 0.965320 | 25.35 | 17.06 | 0.00886313 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 21.3131 | 23.89 | 0.00899133 | 48.1719 | 11066.50 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 27870.000 | 27870.000 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27870.00 | 27870.00 | 0.965322 | 15.69 | 10.56 | 0.00590034 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.3130 | 21.11 | 0.00677867 | 43.1580 | 9897.81 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 15886.720 | 12719.861 | 0.959720 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 15886.72 | 14911.72 | 0.959720 | 25.35 | 17.06 | 0.00886446 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 21.4374 | 23.89 | 0.00899414 | 48.1868 | 10999.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 27735.115 | 27735.115 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27735.11 | 27735.11 | 0.959717 | 15.66 | 10.54 | 0.00589514 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.4375 | 21.11 | 0.00677858 | 43.1574 | 9895.95 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 15720.040 | 12586.407 | 0.949650 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 15720.04 | 14751.97 | 0.949650 | 25.36 | 17.06 | 0.00886589 | 12.80 | 12.00 | 0.00850000 | 26.40 | 0.00840708 | 17.04 | 21.6648 | 23.89 | 0.00899719 | 48.2029 | 10868.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 27471.416 | 27471.416 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 27471.42 | 27471.42 | 0.949648 | 15.60 | 10.52 | 0.00590179 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 21.6648 | 21.11 | 0.00679902 | 43.2862 | 10178.80 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 16374.530 | 13110.431 | 0.989190 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | 16374.53 | 15383.32 | 0.989190 | 25.24 | 17.01 | 0.00885624 | 12.80 | 12.00 | 0.00850000 | 25.95 | 0.00840636 | 16.88 | 20.7988 | 23.89 | 0.00897892 | 48.1064 | 11198.69 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 28136.145 | 28136.145 | -999.0 | -999.0 | -999.000 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 28136.14 | 28136.14 | 0.989185 | 15.82 | 10.72 | 0.00600715 | 40.00 | 21.06 | 0.00800000 | -4.30 | 0.00265759 | -4.30 | 20.7989 | 21.11 | 0.00688677 | 43.8398 | 12246.71 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 31055.940 | 24865.249 | 1.876090 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3243 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.876089 | 2.23512015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 31055.94 | 29130.36 | 1.0000 | 2.23512112 | 1.876090 | 25.32 | 17.05 | 0.00886755 | 48035.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 31055.94 | 26.40 | 0.00840708 | 17.04 | 0.41147883 | 21.9328 | 23.89 | 0.00899692 | 23.89 | 0.00899692 | 48.2017 | 21079.12 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 54947.721 | 54947.721 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.876089 | 2.23512015 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 54947.72 | 54947.72 | 1.0000 | 2.23512015 | 1.876089 | 15.54 | 10.52 | 0.00592754 | 30605.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 54947.72 | -4.30 | 0.00265759 | -4.30 | 0.41147883 | 21.9328 | 21.11 | 0.00684623 | 21.11 | 0.00684623 | 43.5830 | 19486.89 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17045.530 | 13647.674 | 1.029720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2838 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.029720 | 1.22677999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 17045.53 | 16046.72 | 1.0000 | 1.22677959 | 1.029720 | 25.30 | 17.03 | 0.00884574 | 47965.1 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17045.53 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 19.9801 | 23.89 | 0.00895632 | 23.89 | 0.00895632 | 47.9870 | 11481.73 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29297.417 | 29297.417 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.029720 | 1.22677999 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29297.42 | 29297.42 | 1.0000 | 1.22677999 | 1.029720 | 16.03 | 10.71 | 0.00591052 | 31066.8 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29297.42 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 19.9801 | 21.11 | 0.00672274 | 21.11 | 0.00672274 | 42.8055 | 9179.91 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16954.030 | 13574.414 | 1.024190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2830 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.024193 | 1.22019454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 16954.03 | 15961.72 | 1.0000 | 1.22019130 | 1.024190 | 25.30 | 17.03 | 0.00884529 | 47962.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16954.03 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 20.0880 | 23.89 | 0.00895546 | 23.89 | 0.00895546 | 47.9825 | 11507.00 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28893.942 | 28893.942 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.024193 | 1.22019454 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28893.94 | 28893.94 | 1.0000 | 1.22019454 | 1.024193 | 16.00 | 10.70 | 0.00591318 | 31045.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28893.94 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.0880 | 21.11 | 0.00673156 | 21.11 | 0.00673156 | 42.8612 | 9293.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 17008.670 | 13618.162 | 1.027490 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2818 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027494 | 1.22412701 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 17008.67 | 16014.81 | 1.0000 | 1.22412283 | 1.027490 | 25.30 | 17.03 | 0.00884465 | 47959.6 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 17008.67 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 20.0235 | 23.89 | 0.00895421 | 23.89 | 0.00895421 | 47.9759 | 11543.44 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 29496.978 | 29496.978 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.027494 | 1.22412701 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 29496.98 | 29496.98 | 1.0000 | 1.22412701 | 1.027494 | 16.02 | 10.72 | 0.00592231 | 31085.4 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 29496.98 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.0234 | 21.11 | 0.00673969 | 21.11 | 0.00673969 | 42.9124 | 9396.38 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16875.070 | 13511.194 | 1.019420 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.2847 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019423 | 1.21451220 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 16875.07 | 15884.95 | 1.0000 | 1.21450846 | 1.019420 | 25.31 | 17.03 | 0.00884625 | 47967.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16875.07 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 20.1820 | 23.89 | 0.00895731 | 23.89 | 0.00895731 | 47.9923 | 11452.93 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28758.409 | 28758.409 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.019423 | 1.21451220 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28758.41 | 28758.41 | 1.0000 | 1.21451220 | 1.019423 | 15.98 | 10.71 | 0.00592736 | 31057.3 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28758.41 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.1819 | 21.11 | 0.00675412 | 21.11 | 0.00675412 | 43.0033 | 9576.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 30077.940 | 24082.203 | 1.817010 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3410 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.817008 | 2.16473270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 30077.94 | 28172.65 | 1.0000 | 2.16473486 | 1.817010 | 25.34 | 17.06 | 0.00887653 | 48077.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 30077.94 | 26.40 | 0.00840708 | 17.04 | 0.41147883 | 22.6459 | 23.89 | 0.00901403 | 23.89 | 0.00901403 | 48.2921 | 20408.20 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 52502.264 | 52502.264 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.817008 | 2.16473270 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 52502.26 | 52502.26 | 1.0000 | 2.16473270 | 1.817008 | 15.35 | 10.40 | 0.00589377 | 30336.5 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 52502.26 | -4.30 | 0.00265759 | -4.30 | 0.41147883 | 22.6460 | 21.11 | 0.00684118 | 21.11 | 0.00684118 | 43.5509 | 18603.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15979.510 | 12794.154 | 0.965320 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3161 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.965322 | 1.15005792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 15979.51 | 15001.94 | 1.0000 | 1.15005523 | 0.965320 | 25.35 | 17.06 | 0.00886313 | 48055.8 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15979.51 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 21.3131 | 23.89 | 0.00899133 | 23.89 | 0.00899133 | 48.1719 | 11066.50 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27870.000 | 27870.000 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.965322 | 1.15005792 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27870.00 | 27870.00 | 1.0000 | 1.15005792 | 0.965322 | 15.69 | 10.56 | 0.00590034 | 30697.0 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27870.00 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.3130 | 21.11 | 0.00677867 | 21.11 | 0.00677867 | 43.1580 | 9897.81 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15886.720 | 12719.861 | 0.959720 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3186 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.959717 | 1.14338002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 15886.72 | 14911.72 | 1.0000 | 1.14338355 | 0.959720 | 25.35 | 17.06 | 0.00886446 | 48063.0 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15886.72 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 21.4374 | 23.89 | 0.00899414 | 23.89 | 0.00899414 | 48.1868 | 10999.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27735.115 | 27735.115 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.959717 | 1.14338002 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27735.11 | 27735.11 | 1.0000 | 1.14338002 | 0.959717 | 15.66 | 10.54 | 0.00589514 | 30651.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27735.11 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.4375 | 21.11 | 0.00677858 | 21.11 | 0.00677858 | 43.1574 | 9895.95 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 15720.040 | 12586.407 | 0.949650 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3213 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.949648 | 1.13138368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 15720.04 | 14751.97 | 1.0000 | 1.13138643 | 0.949650 | 25.36 | 17.06 | 0.00886589 | 48070.7 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 15720.04 | 26.40 | 0.00840708 | 17.04 | 0.20573941 | 21.6648 | 23.89 | 0.00899719 | 23.89 | 0.00899719 | 48.2029 | 10868.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 27471.416 | 27471.416 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.949648 | 1.13138368 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 27471.42 | 27471.42 | 1.0000 | 1.13138368 | 0.949648 | 15.60 | 10.52 | 0.00590179 | 30609.9 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 27471.42 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 21.6648 | 21.11 | 0.00679902 | 21.11 | 0.00679902 | 43.2862 | 10178.80 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 16374.530 | 13110.431 | 0.989190 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1021.3033 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.989185 | 1.17848791 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:00:00 | WILLIAM R FAIRCHILD ANN CLG .4% CONDNS DB=>MWB | 8/21 10:20:00 | Sensible | 16374.53 | 15383.32 | 1.0000 | 1.17849328 | 0.989190 | 25.24 | 17.01 | 0.00885624 | 47925.4 | 12.80 | 12.00 | 0.00850000 | 34322.2 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 16374.53 | 25.95 | 0.00840636 | 16.88 | 0.20573941 | 20.7988 | 23.89 | 0.00897892 | 23.89 | 0.00897892 | 48.1064 | 11198.69 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 28136.145 | 28136.145 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.1914 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.989185 | 1.17848791 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | WILLIAM R FAIRCHILD ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 28136.14 | 28136.14 | 1.0000 | 1.17848791 | 0.989185 | 15.82 | 10.72 | 0.00600715 | 31099.7 | 40.00 | 21.06 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 28136.14 | -4.30 | 0.00265759 | -4.30 | 0.20573941 | 20.7989 | 21.11 | 0.00688677 | 21.11 | 0.00688677 | 43.8398 | 12246.71 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
PSZ-AC_1:1_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.88 | - | |||
PSZ-AC_2:2_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_3:3_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_4:4_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.03 | - | |||
PSZ-AC_5:5_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 1.02 | - | |||
PSZ-AC_6:6_OA_CONTROLLER | DifferentialDryBulb | 0.41 | 1.82 | - | |||
PSZ-AC_7:7_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.97 | - | |||
PSZ-AC_8:8_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.96 | - | |||
PSZ-AC_9:9_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.95 | - | |||
PSZ-AC_10:10_OA_CONTROLLER | DifferentialDryBulb | 0.21 | 0.99 | - |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 1613.00 | 4005.67 | 575.33 |
SMSTORE1 | 1331.50 | 3581.00 | 88.67 |
SMSTORE2 | 1172.00 | 2803.67 | 188.50 |
SMSTORE3 | 1196.33 | 2835.33 | 241.83 |
SMSTORE4 | 1202.83 | 2913.67 | 313.67 |
LGSTORE2 | 1184.33 | 2790.83 | 501.17 |
SMSTORE5 | 1098.50 | 2823.33 | 499.83 |
SMSTORE6 | 1114.17 | 2869.17 | 544.67 |
SMSTORE7 | 1190.83 | 2980.83 | 693.50 |
SMSTORE8 | 1665.33 | 3168.83 | 1270.00 |
Facility | 2855.67 | 4599.00 | 1565.33 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 4.17 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 0.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 0.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 0.00 | 0.00 | 0.00 | 0.00 |
Facility | 4.50 | 0.00 | 0.00 | 0.00 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 1.052 | 0.223 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 1.016 | 0.242 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 1.193 | 0.317 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 1.187 | 0.317 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 1.162 | 0.317 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 1.096 | 0.305 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 1.114 | 0.339 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 1.103 | 0.339 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 1.076 | 0.339 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 1.057 | 0.350 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.93 | 56.25 | 1805.20 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.47 | 28.12 | 902.60 | 0.000 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.08 | 28.12 | 902.60 | 0.807 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.76 | 56.25 | 1805.20 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.38 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.38 | 28.12 | 902.60 | 0.804 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.38 | 28.12 | 902.60 | 0.803 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.38 | 28.12 | 902.60 | 0.802 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.93 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.47 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.08 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.76 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.38 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 120.91 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 10919752.02 | 0.00 | 10919752.02 | 2543830.37 | 13463582.39 | 12976396.34 | 3181.28 | 4055.31 | 1523.41 | 0.00 |
SMSTORE1 | 5264314.08 | 0.00 | 5264314.08 | 1325765.83 | 6590079.90 | 6488198.17 | 4211.80 | 2641.45 | 1906.76 | 0.00 |
SMSTORE2 | 4659408.22 | 0.00 | 4659408.22 | 1348098.60 | 6007506.82 | 6488198.17 | 4365.00 | 3088.65 | 1306.35 | 0.00 |
SMSTORE3 | 4633430.07 | 0.00 | 4633430.07 | 1348098.60 | 5981528.67 | 6488198.17 | 4365.00 | 3111.85 | 1283.15 | 0.00 |
SMSTORE4 | 4539509.49 | 0.00 | 4539509.49 | 1348098.60 | 5887608.09 | 6488198.17 | 4365.00 | 3185.87 | 1209.13 | 0.00 |
LGSTORE2 | 7848478.56 | 0.00 | 7848478.56 | 2452721.70 | 10301200.26 | 12976396.34 | 4730.00 | 3013.27 | 1016.73 | 0.00 |
SMSTORE5 | 3991013.55 | 0.00 | 3991013.55 | 1353477.65 | 5344491.20 | 6488198.17 | 4730.00 | 2998.41 | 1031.59 | 0.00 |
SMSTORE6 | 3951213.47 | 0.00 | 3951213.47 | 1353477.65 | 5304691.12 | 6488198.17 | 4730.00 | 3037.17 | 992.83 | 0.00 |
SMSTORE7 | 3855735.62 | 0.00 | 3855735.62 | 1353477.65 | 5209213.27 | 6488198.17 | 4730.00 | 3127.80 | 902.20 | 0.00 |
SMSTORE8 | 3789477.79 | 0.00 | 3789477.79 | 1541577.72 | 5331055.51 | 6488198.17 | 4730.00 | 3245.65 | 784.35 | 0.00 |
Total Facility | 53452332.88 | 0.00 | 53452332.88 | 15968624.37 | 69420957.25 | 77858378.04 | 4730.00 | 4752.54 | 1986.36 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.5194 | 0.0000 | 0.5194 | 0.1105 | 0.6299 | 0.4115 | 261.28 | 4055.31 | 1523.41 |
SMSTORE1 | 0.2504 | 0.0000 | 0.2504 | 0.0599 | 0.3103 | 0.2057 | 1291.80 | 2641.45 | 1906.76 |
SMSTORE2 | 0.2945 | 0.0000 | 0.2945 | 0.0785 | 0.3730 | 0.2057 | 0.00 | 3088.65 | 1306.35 |
SMSTORE3 | 0.2928 | 0.0000 | 0.2928 | 0.0785 | 0.3713 | 0.2057 | 0.00 | 3111.85 | 1283.15 |
SMSTORE4 | 0.2869 | 0.0000 | 0.2869 | 0.0785 | 0.3654 | 0.2057 | 0.00 | 3185.87 | 1209.13 |
LGSTORE2 | 0.5410 | 0.0000 | 0.5410 | 0.1507 | 0.6916 | 0.4115 | 0.00 | 3013.27 | 1016.73 |
SMSTORE5 | 0.2751 | 0.0000 | 0.2751 | 0.0838 | 0.3589 | 0.2057 | 0.00 | 2998.41 | 1031.59 |
SMSTORE6 | 0.2723 | 0.0000 | 0.2723 | 0.0838 | 0.3562 | 0.2057 | 0.00 | 3037.17 | 992.83 |
SMSTORE7 | 0.2658 | 0.0000 | 0.2658 | 0.0838 | 0.3496 | 0.2057 | 0.00 | 3127.80 | 902.20 |
SMSTORE8 | 0.2612 | 0.0000 | 0.2612 | 0.0866 | 0.3478 | 0.2057 | 0.00 | 3245.65 | 784.35 |
Total Facility | 3.2594 | 0.0000 | 3.2594 | 0.8946 | 4.1540 | 2.4689 | 1395.55 | 4752.54 | 1986.36 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 15499138.60 | 0.00 | 15499138.60 | 12976396.34 | 3181.28 | 0.00 | 5578.72 | 0.00 |
PSZ-AC_2:2 | 7471995.12 | 0.00 | 7471995.12 | 6488198.17 | 4185.96 | 4.33 | 4569.70 | 0.00 |
PSZ-AC_3:3 | 6613411.52 | 0.00 | 6613411.52 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_4:4 | 6576538.99 | 0.00 | 6576538.99 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_5:5 | 6443231.19 | 0.00 | 6443231.19 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 0.00 |
PSZ-AC_6:6 | 11139873.58 | 0.00 | 11139873.58 | 12976396.34 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_7:7 | 5664714.00 | 0.00 | 5664714.00 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_8:8 | 5608223.07 | 0.00 | 5608223.07 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_9:9 | 5472704.94 | 0.00 | 5472704.94 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
PSZ-AC_10:10 | 5378660.74 | 0.00 | 5378660.74 | 6488198.17 | 4730.00 | 0.00 | 4030.00 | 0.00 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.7372 | 0.0000 | 0.7372 | 0.4115 | 261.28 | 0.00 | 5578.72 |
PSZ-AC_2:2 | 0.3554 | 0.0000 | 0.3554 | 0.2057 | 1265.96 | 4.33 | 4569.70 |
PSZ-AC_3:3 | 0.4180 | 0.0000 | 0.4180 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.4157 | 0.0000 | 0.4157 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.4072 | 0.0000 | 0.4072 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.7678 | 0.0000 | 0.7678 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.3905 | 0.0000 | 0.3905 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.3866 | 0.0000 | 0.3866 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.3772 | 0.0000 | 0.3772 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.3707 | 0.0000 | 0.3707 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 4445.48 | 1143.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 3155.47 | 1745.34 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 3473.52 | 921.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 3480.87 | 914.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 3534.35 | 860.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 3329.75 | 700.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 3296.51 | 733.49 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 3326.10 | 703.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 3392.54 | 637.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 3478.11 | 551.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.6988 | 1.0493 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.3899 | 0.4844 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.3725 | 0.5901 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.3703 | 0.5889 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.3631 | 0.5889 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.7003 | 1.0903 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.3524 | 0.5621 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.3495 | 0.5625 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.3429 | 0.5605 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.3382 | 0.5768 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
ElectricityPurchased:Plant | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
Cogeneration:ElectricityPurchased | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
General:Cogeneration:ElectricityPurchased | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
ElectricityNet:Plant | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
Cogeneration:ElectricityNet | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
General:Cogeneration:ElectricityNet | 1009.88 | 3178.87 | 29-JAN-08:00 | 83621.50 | 22-JUL-15:00 |
Electricity:HVAC | 232.53 | 0.00 | 01-JAN-00:10 | 41361.70 | 22-JUL-15:00 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 12.50 | 0.00 | 01-JAN-00:10 | 28591.72 | 22-JUL-15:00 |
General:Cooling:Electricity | 12.50 | 0.00 | 01-JAN-00:10 | 28591.72 | 22-JUL-15:00 |
Fans:Electricity | 220.02 | 0.00 | 01-JAN-00:10 | 12769.98 | 01-MAR-13:20 |
General:Fans:Electricity | 220.02 | 0.00 | 01-JAN-00:10 | 12769.98 | 01-MAR-13:20 |
ExteriorLights:Electricity | 121.11 | 0.00 | 01-JAN-08:20 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.11 | 0.00 | 01-JAN-08:20 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 65.21 | 1218.00 | 01-JAN-09:10 | 11862.21 | 18-JAN-14:40 |
WaterSystems:Electricity | 65.21 | 1218.00 | 01-JAN-09:10 | 11862.21 | 18-JAN-14:40 |
Water Heater:WaterSystems:Electricity | 65.21 | 1218.00 | 01-JAN-09:10 | 11862.21 | 18-JAN-14:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 319.06 | 0.00 | 01-JAN-00:10 | 176597.73 | 10-JAN-09:10 |
NaturalGas:HVAC | 319.06 | 0.00 | 01-JAN-00:10 | 176597.73 | 10-JAN-09:10 |
Heating:NaturalGas | 319.06 | 0.00 | 01-JAN-00:10 | 176597.73 | 10-JAN-09:10 |
General:Heating:NaturalGas | 319.06 | 0.00 | 01-JAN-00:10 | 176597.73 | 10-JAN-09:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 652.37 | 0.00 | 01-JAN-00:10 | 225399.86 | 10-JAN-09:10 |
EnergyTransfer:Building | 349.04 | 0.00 | 01-JAN-00:10 | 84121.68 | 10-JAN-09:10 |
EnergyTransfer:Zone:LGSTORE1 | 74.12 | 0.00 | 01-JAN-00:10 | 17086.57 | 27-DEC-09:10 |
Heating:EnergyTransfer | 76.59 | 0.00 | 01-JAN-00:10 | 81156.00 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 9.84 | 0.00 | 01-JAN-00:10 | 15828.46 | 30-DEC-09:10 |
General:Heating:EnergyTransfer | 76.59 | 0.00 | 01-JAN-00:10 | 81156.00 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 9.84 | 0.00 | 01-JAN-00:10 | 15828.46 | 30-DEC-09:10 |
Cooling:EnergyTransfer | 272.45 | 0.00 | 01-JAN-00:10 | 78942.64 | 22-JUL-15:00 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 64.28 | 0.00 | 01-JAN-00:10 | 13472.31 | 22-JUL-16:10 |
General:Cooling:EnergyTransfer | 272.45 | 0.00 | 01-JAN-00:10 | 78942.64 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 64.28 | 0.00 | 01-JAN-00:10 | 13472.31 | 22-JUL-16:10 |
EnergyTransfer:Zone:SMSTORE1 | 39.80 | 0.00 | 01-JAN-00:10 | 9617.40 | 30-APR-19:40 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 2.53 | 0.00 | 01-JAN-00:10 | 4797.60 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 2.53 | 0.00 | 01-JAN-00:10 | 4797.60 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.27 | 0.00 | 01-JAN-00:10 | 9617.40 | 30-APR-19:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 37.27 | 0.00 | 01-JAN-00:10 | 9617.40 | 30-APR-19:40 |
EnergyTransfer:Zone:SMSTORE2 | 30.29 | 0.00 | 01-JAN-00:10 | 7253.70 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 3.74 | 0.00 | 01-JAN-00:10 | 6622.98 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 3.74 | 0.00 | 01-JAN-00:10 | 6622.98 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.56 | 0.00 | 01-JAN-00:10 | 7083.94 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 26.56 | 0.00 | 01-JAN-00:10 | 7083.94 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE3 | 29.63 | 0.00 | 01-JAN-00:10 | 8146.10 | 10-JAN-08:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 4.35 | 0.00 | 01-JAN-00:10 | 7464.44 | 10-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 4.35 | 0.00 | 01-JAN-00:10 | 7464.44 | 10-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 25.28 | 0.00 | 01-JAN-00:10 | 7062.74 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 25.28 | 0.00 | 01-JAN-00:10 | 7062.74 | 22-JUL-13:00 |
EnergyTransfer:Zone:SMSTORE4 | 28.30 | 0.00 | 01-JAN-00:10 | 8972.05 | 31-DEC-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 5.31 | 0.00 | 01-JAN-00:10 | 8053.88 | 09-JAN-08:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 5.31 | 0.00 | 01-JAN-00:10 | 8053.88 | 09-JAN-08:10 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.00 | 0.00 | 01-JAN-00:10 | 6901.87 | 22-JUL-13:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 23.00 | 0.00 | 01-JAN-00:10 | 6901.87 | 22-JUL-13:00 |
EnergyTransfer:Zone:LGSTORE2 | 46.89 | 0.00 | 01-JAN-00:10 | 18042.59 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 11.23 | 0.00 | 01-JAN-00:10 | 16908.72 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 11.23 | 0.00 | 01-JAN-00:10 | 16908.72 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 35.66 | 0.00 | 01-JAN-00:10 | 12680.55 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 35.66 | 0.00 | 01-JAN-00:10 | 12680.55 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE5 | 24.05 | 0.00 | 01-JAN-00:10 | 8794.20 | 31-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 6.77 | 0.00 | 01-JAN-00:10 | 8459.12 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 6.77 | 0.00 | 01-JAN-00:10 | 8459.12 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.28 | 0.00 | 01-JAN-00:10 | 6587.50 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 17.28 | 0.00 | 01-JAN-00:10 | 6587.50 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE6 | 23.73 | 0.00 | 01-JAN-00:10 | 8936.68 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 7.14 | 0.00 | 01-JAN-00:10 | 8673.40 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 7.14 | 0.00 | 01-JAN-00:10 | 8673.40 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 16.58 | 0.00 | 01-JAN-00:10 | 6520.17 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 16.58 | 0.00 | 01-JAN-00:10 | 6520.17 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE7 | 23.52 | 0.00 | 01-JAN-00:10 | 9687.33 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 8.83 | 0.00 | 01-JAN-00:10 | 9341.79 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 8.83 | 0.00 | 01-JAN-00:10 | 9341.79 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 14.69 | 0.00 | 01-JAN-00:10 | 6396.74 | 22-JUL-15:00 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 14.69 | 0.00 | 01-JAN-00:10 | 6396.74 | 22-JUL-15:00 |
EnergyTransfer:Zone:SMSTORE8 | 28.70 | 0.00 | 01-JAN-00:10 | 12800.52 | 10-JAN-09:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 16.86 | 0.00 | 01-JAN-00:10 | 12481.78 | 10-JAN-09:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 16.86 | 0.00 | 01-JAN-00:10 | 12481.78 | 10-JAN-09:10 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.83 | 0.00 | 01-JAN-00:10 | 6573.96 | 22-JUL-14:40 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 11.83 | 0.00 | 01-JAN-00:10 | 6573.96 | 22-JUL-14:40 |
EnergyTransfer:HVAC | 303.33 | 0.00 | 01-JAN-00:10 | 141278.19 | 10-JAN-09:10 |
HeatingCoils:EnergyTransfer | 255.24 | 0.00 | 01-JAN-00:10 | 141278.19 | 10-JAN-09:10 |
CoolingCoils:EnergyTransfer | 48.09 | 0.00 | 01-JAN-00:10 | 107214.19 | 22-JUL-15:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 9.837 | -64.282 | 0.000 | 0.000 | 25.517 | 106.728 | 26.357 | 21.376 | 0.000 | 0.065 | 0.002 | 0.000 | -10.535 | 0.000 | -33.579 | -81.484 |
SMSTORE1 | 0.000 | 0.000 | 2.530 | -37.270 | 0.000 | 0.000 | 12.479 | 62.296 | 13.179 | 10.567 | 0.000 | 0.035 | 0.001 | 0.000 | -5.590 | 0.000 | -17.670 | -40.557 |
SMSTORE2 | 0.000 | 0.000 | 3.736 | -26.558 | 0.000 | 0.000 | 7.633 | 44.966 | 10.467 | 10.564 | 0.000 | 0.035 | 0.001 | 0.000 | -5.488 | 0.000 | -17.912 | -27.443 |
SMSTORE3 | 0.000 | 0.000 | 4.346 | -25.285 | 0.000 | 0.000 | 7.646 | 44.966 | 10.467 | 10.583 | 0.000 | 0.035 | 0.000 | 0.000 | -5.418 | 0.000 | -17.844 | -29.497 |
SMSTORE4 | 0.000 | 0.000 | 5.308 | -22.996 | 0.000 | 0.000 | 7.666 | 44.966 | 10.467 | 10.611 | 0.000 | 0.035 | 0.001 | 0.000 | -5.347 | 0.000 | -17.751 | -32.959 |
LGSTORE2 | 0.000 | 0.000 | 11.229 | -35.664 | 0.000 | 0.000 | 26.405 | 51.668 | 19.261 | 21.354 | 0.000 | 0.063 | 0.002 | 0.000 | -10.355 | 0.000 | -32.022 | -51.938 |
SMSTORE5 | 0.000 | 0.000 | 6.767 | -17.284 | 0.000 | 0.000 | 13.206 | 26.679 | 9.631 | 10.668 | 0.000 | 0.035 | 0.001 | 0.000 | -5.177 | 0.000 | -17.624 | -26.900 |
SMSTORE6 | 0.000 | 0.000 | 7.143 | -16.582 | 0.000 | 0.000 | 13.221 | 26.679 | 9.631 | 10.683 | 0.000 | 0.035 | 0.001 | 0.000 | -5.147 | 0.000 | -17.580 | -28.082 |
SMSTORE7 | 0.000 | 0.000 | 8.829 | -14.695 | 0.000 | 0.000 | 13.260 | 26.679 | 9.631 | 10.724 | 0.000 | 0.035 | 0.001 | 0.000 | -5.049 | 0.000 | -17.457 | -31.956 |
SMSTORE8 | 0.000 | 0.000 | 16.865 | -11.832 | 0.000 | 0.000 | 13.320 | 26.679 | 9.631 | 10.831 | 0.000 | 0.036 | 0.000 | 0.000 | -4.701 | 0.000 | -19.761 | -41.067 |
Total Facility | 0.000 | 0.000 | 76.590 | -272.449 | 0.000 | 0.000 | 140.352 | 462.305 | 128.721 | 127.960 | 0.000 | 0.408 | 0.008 | 0.000 | -62.806 | 0.000 | -209.198 | -391.883 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 | -32808.92 | 0.00 | 0.00 | 181.85 | 2916.31 | 749.03 | 424.58 | 0.00 | 0.00 | 29005.71 | 0.00 | -0.00 | 0.00 | -468.57 | 0.00 |
SMSTORE1 | 14-AUG-21:16 | 0.00 | 0.00 | 0.00 | -18937.60 | 0.00 | 0.00 | 648.60 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 14555.18 | 0.00 | -172.13 | 0.00 | -2.41 | 0.00 |
SMSTORE2 | 14-JUN-07:02 | 0.00 | 0.00 | 0.00 | -19256.48 | 0.00 | 0.00 | 88.04 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 17599.04 | 0.00 | -24.52 | 0.00 | -316.96 | 0.00 |
SMSTORE3 | 14-JUN-07:02 | 0.00 | 0.00 | 0.00 | -19284.04 | 0.00 | 0.00 | 88.25 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 17625.00 | 0.00 | -23.94 | 0.00 | -316.15 | 0.00 |
SMSTORE4 | 14-JUN-07:02 | 0.00 | 0.00 | 0.00 | -18970.63 | 0.00 | 0.00 | 89.46 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 17303.43 | 0.00 | -20.99 | 0.00 | -312.14 | 0.00 |
LGSTORE2 | 25-JUN-09:02 | 0.00 | 0.00 | 0.00 | -32986.49 | 0.00 | 0.00 | 394.65 | 1920.56 | 749.03 | 1568.76 | 0.00 | 0.00 | 28672.91 | 0.00 | -0.00 | 0.00 | -319.41 | 0.00 |
SMSTORE5 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16939.71 | 0.00 | 0.00 | 198.59 | 991.67 | 374.52 | 206.59 | 0.00 | 0.00 | 15419.68 | 0.00 | -0.00 | 0.00 | -251.34 | 0.00 |
SMSTORE6 | 25-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16780.61 | 0.00 | 0.00 | 199.68 | 991.67 | 374.52 | 207.88 | 0.00 | 0.00 | 15256.79 | 0.00 | -0.00 | 0.00 | -249.92 | 0.00 |
SMSTORE7 | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -16311.36 | 0.00 | 0.00 | 196.90 | 991.67 | 374.52 | 330.20 | 0.00 | 0.00 | 14651.71 | 0.00 | -0.00 | 0.00 | -233.63 | 0.00 |
SMSTORE8 | 23-JUL-09:01 | 0.00 | 0.00 | 0.00 | -16311.24 | 0.00 | 0.00 | 183.31 | 991.67 | 374.52 | 823.20 | 0.00 | 0.00 | 14082.68 | 0.00 | -0.00 | 0.00 | -144.13 | 0.00 |
Total Facility | 24-JUL-08:62 | 0.00 | 0.00 | 0.00 | -149783.96 | 0.00 | 0.00 | 2026.96 | 19263.00 | 5393.02 | 3977.66 | 0.00 | 0.00 | 121885.16 | 0.00 | 0.00 | 0.00 | -2761.84 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 04-DEC-09:01 | 0.00 | 0.00 | 49366.29 | 0.00 | 0.00 | 0.00 | 248.84 | 2916.31 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -331.29 | 0.00 | -592.74 | -52356.44 |
SMSTORE1 | 15-DEC-09:01 | 0.00 | 0.00 | 24915.85 | 0.00 | 0.00 | 0.00 | 120.73 | 1702.23 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -229.32 | 0.00 | -413.67 | -26470.34 |
SMSTORE2 | 25-DEC-09:01 | 0.00 | 0.00 | 24867.04 | 0.00 | 0.00 | 0.00 | 122.16 | 1536.36 | 374.52 | 292.69 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -453.95 | -26738.82 |
SMSTORE3 | 25-DEC-09:01 | 0.00 | 0.00 | 25524.89 | 0.00 | 0.00 | 0.00 | 123.99 | 1536.36 | 374.52 | 299.56 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -445.32 | -27413.99 |
SMSTORE4 | 06-MAR-08:62 | 0.00 | 0.00 | 25104.63 | 0.00 | 0.00 | 0.00 | 123.69 | 1536.36 | 374.52 | 44.93 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -367.14 | -26816.99 |
LGSTORE2 | 10-JAN-08:61 | 0.00 | 0.00 | 52621.08 | 0.00 | 0.00 | 0.00 | 0.00 | 192.04 | 74.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -164.43 | 0.00 | -1011.22 | -51712.37 |
SMSTORE5 | 09-MAR-09:01 | 0.00 | 0.00 | 25643.63 | 0.00 | 0.00 | 0.00 | 268.27 | 991.67 | 374.52 | 429.04 | 0.00 | 0.00 | 0.00 | 0.00 | -0.00 | 0.00 | -253.37 | -27453.76 |
SMSTORE6 | 10-JAN-08:61 | 0.00 | 0.00 | 27782.16 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -81.33 | 0.00 | -562.59 | -27274.86 |
SMSTORE7 | 10-JAN-08:61 | 0.00 | 0.00 | 27531.75 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -73.28 | 0.00 | -552.10 | -27042.99 |
SMSTORE8 | 10-JAN-08:61 | 0.00 | 0.00 | 28184.54 | 0.00 | 0.00 | 0.00 | 0.00 | 99.17 | 37.45 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -41.27 | 0.00 | -525.07 | -27754.82 |
Total Facility | 31-DEC-09:01 | 0.00 | 0.00 | 299240.84 | 0.00 | 0.00 | 0.00 | 758.13 | 9816.32 | 2471.80 | 4935.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -5259.17 | -311963.06 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8761 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8761 | 0.2193 | 1.0000 | Not calculated | 0.4115 | 0.2193 | ||
PSZ-AC_2:2 | 1.0187 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0297 | 0.1998 | 1.0000 | Not calculated | 0.2057 | 0.1998 | ||
PSZ-AC_3:3 | 1.0008 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0242 | 0.2009 | 1.0000 | Not calculated | 0.2057 | 0.2009 | ||
PSZ-AC_4:4 | 1.0275 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0275 | 0.2002 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_5:5 | 0.9948 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0194 | 0.2018 | 1.0000 | Not calculated | 0.2057 | 0.2018 | ||
PSZ-AC_6:6 | 1.7680 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8170 | 0.2265 | 1.0000 | Not calculated | 0.4115 | 0.2265 | ||
PSZ-AC_7:7 | 0.9556 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9653 | 0.2131 | 1.0000 | Not calculated | 0.2057 | 0.2131 | ||
PSZ-AC_8:8 | 0.9496 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9597 | 0.2144 | 1.0000 | Not calculated | 0.2057 | 0.2144 | ||
PSZ-AC_9:9 | 0.9379 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9496 | 0.2166 | 1.0000 | Not calculated | 0.2057 | 0.2166 | ||
PSZ-AC_10:10 | 0.9673 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9892 | 0.2080 | 1.0000 | Not calculated | 0.2057 | 0.2080 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 1.8761 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.8761 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2193 | ||
PSZ-AC_2:2 | 1.0187 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0187 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2020 | ||
PSZ-AC_3:3 | 1.0008 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0008 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2056 | ||
PSZ-AC_4:4 | 1.0275 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.0275 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2002 | ||
PSZ-AC_5:5 | 0.9948 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9948 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2068 | ||
PSZ-AC_6:6 | 1.7680 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 1.7680 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.2327 | ||
PSZ-AC_7:7 | 0.9556 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9556 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2153 | ||
PSZ-AC_8:8 | 0.9496 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9496 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2167 | ||
PSZ-AC_9:9 | 0.9379 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9379 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2194 | ||
PSZ-AC_10:10 | 0.9673 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 0.9673 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.2127 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8761 | 1.8761 | 1.8761 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0187 | 1.0187 | 1.0187 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0008 | 1.0008 | 1.0008 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0275 | 1.0275 | 1.0275 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9948 | 0.9948 | 0.9948 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7680 | 1.7680 | 1.7680 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9556 | 0.9556 | 0.9556 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9496 | 0.9496 | 0.9496 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9379 | 0.9379 | 0.9379 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9673 | 0.9673 | 0.9673 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8761 | 1.8761 | 1.8761 | 1.8761 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0187 | 1.0297 | 1.0187 | 1.0187 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0008 | 1.0242 | 1.0008 | 1.0008 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0275 | 1.0275 | 1.0275 | 1.0275 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9948 | 1.0194 | 0.9948 | 0.9948 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7680 | 1.8170 | 1.7680 | 1.7680 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9556 | 0.9653 | 0.9556 | 0.9556 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9496 | 0.9597 | 0.9496 | 0.9496 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9379 | 0.9496 | 0.9379 | 0.9379 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9673 | 0.9892 | 0.9673 | 0.9673 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.8761 | 1.8761 | 1.8761 | No | 0.4115 | 0.4039 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0187 | 1.0187 | 1.0187 | No | 0.2057 | 0.4287 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0008 | 1.0008 | 1.0008 | No | 0.2057 | 0.4234 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.0275 | 1.0275 | 1.0275 | No | 0.2057 | 0.4188 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9948 | 0.9948 | 0.9948 | No | 0.2057 | 0.4109 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7680 | 1.7680 | 1.7680 | No | 0.4115 | 0.4230 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9556 | 0.9556 | 0.9556 | No | 0.2057 | 0.3976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9496 | 0.9496 | 0.9496 | No | 0.2057 | 0.3976 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9379 | 0.9379 | 0.9379 | No | 0.2057 | 0.3866 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 0.9673 | 0.9673 | 0.9673 | No | 0.2057 | 0.3213 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 1.8761 | 1.8761 | 1.8761 | 1.8761 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.0187 | 1.0187 | 1.0187 | 1.0187 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.0008 | 1.0008 | 1.0008 | 1.0008 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.0275 | 1.0275 | 1.0275 | 1.0275 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 0.9948 | 0.9948 | 0.9948 | 0.9948 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 1.7680 | 1.7680 | 1.7680 | 1.7680 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 0.9556 | 0.9556 | 0.9556 | 0.9556 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 0.9496 | 0.9496 | 0.9496 | 0.9496 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 0.9379 | 0.9379 | 0.9379 | 0.9379 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 0.9673 | 0.9673 | 0.9673 | 0.9673 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** William R Fairchild WA USA TMY3 WMO#=727885 |
Total gross floor area [m2] | 2090.32 |
Principal Heating Source | Natural Gas |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 0.00 |
Number of hours not met | 0.00 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 319.06 | 176597.73 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 12.50 | 28591.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.11 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 220.02 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 65.21 | 11862.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1009.88 |
Natural Gas | 0.00 | 319.06 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1328.93 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 5.98 |
Fans (All) | 105.26 |
Service Water Heating | 31.20 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 483.12 |
Subtotal | 483.12 |
Natural Gas [MJ/m2] | |
Space Heating | 152.63 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 152.63 |
Subtotal | 152.63 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 34.79 |
Space Heating | 24.01 |
Space Cooling | 0.94 |
Fans (All) | 16.56 |
Service Water Heating | 4.91 |
Receptacle Equipment | 9.69 |
Miscellaneous | 9.11 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2477. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8758.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.33 | 0.67 | 0.00 | 0.00 | 0.00 |
Min | 8758.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 1.17 | 0.00 | 0.00 | 0.00 |
Average | 8759.32 | 0.68 | 0.00 | 0.00 | 0.00 |
Sum | 87593.17 | 6.83 | 0.00 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43777.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.50 | 0.50 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93208.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45911.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Min | 25474.50 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93208.00 | 3.00 | 0.00 | 0.00 | 0.00 |
Average | 48609.35 | 0.85 | 0.00 | 0.00 | 0.00 |
Sum | 486093.50 | 8.50 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 8760.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 8759.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 8752.00 | 8.00 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 8751.83 | 8.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 8754.00 | 6.00 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 8756.67 | 3.33 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 8757.00 | 3.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 8757.17 | 2.83 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 8757.83 | 2.17 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 8759.00 | 1.00 | 0.00 | 0.00 | 0.00 |
Min | 8751.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 8760.00 | 8.17 | 0.00 | 0.00 | 0.00 |
Average | 8756.47 | 3.53 | 0.00 | 0.00 | 0.00 |
Sum | 87564.67 | 35.33 | 0.00 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 89041.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43776.17 | 0.83 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25473.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE3 | 25473.83 | 1.17 | 0.00 | 0.00 | 0.00 |
SMSTORE4 | 25474.17 | 0.83 | 0.00 | 0.00 | 0.00 |
LGSTORE2 | 93210.00 | 1.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 45912.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Min | 25473.83 | 0.00 | 0.00 | 0.00 | 0.00 |
Max | 93210.00 | 1.17 | 0.00 | 0.00 | 0.00 |
Average | 48609.70 | 0.50 | 0.00 | 0.00 | 0.00 |
Sum | 486097.00 | 5.00 | 0.00 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:46
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 5C
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY USA_WA_PORTANGELES
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 4.180 |
February | 4.245 |
March | 5.898 |
April | 8.962 |
May | 9.987 |
June | 13.308 |
July | 15.016 |
August | 15.650 |
September | 13.434 |
October | 9.327 |
November | 6.665 |
December | 4.103 |
Annual Sum or Average | 9.257 |
Minimum of Months | 4.103 |
Maximum of Months | 15.650 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.175376E+10 | 10055.22 | 09-JAN-09:04 | -1.8 | -3.0 | 0.106409E+10 | 1275.40 | 16-JAN-18:00 | 4.00 | 3.53 |
February | 0.169306E+10 | 8624.17 | 17-FEB-09:04 | 1.33 | 0.86 | 0.960537E+09 | 1275.40 | 20-FEB-17:10 | 7.83 | 4.78 |
March | 0.233324E+10 | 7703.40 | 12-MAR-08:04 | 3.33 | 1.48 | 0.105657E+10 | 1347.98 | 19-MAR-17:00 | 11.00 | 10.48 |
April | 0.613352E+10 | 11140.02 | 30-APR-16:07 | 24.00 | 13.04 | 0.116694E+10 | 1685.86 | 29-APR-12:00 | 24.00 | 13.04 |
May | 0.668133E+10 | 10729.78 | 23-MAY-08:62 | 17.33 | 14.10 | 0.123948E+10 | 1685.86 | 21-MAY-17:00 | 17.33 | 14.10 |
June | 0.807491E+10 | 32030.66 | 26-JUN-08:62 | 18.17 | 13.96 | 0.133384E+10 | 1685.95 | 25-JUN-17:30 | 18.17 | 13.96 |
July | 0.100371E+11 | 32817.62 | 25-JUL-08:62 | 13.17 | 13.07 | 0.140768E+10 | 1685.97 | 09-JUL-17:10 | 13.17 | 13.07 |
August | 0.102473E+11 | 32219.86 | 15-AUG-08:62 | 17.67 | 13.87 | 0.139362E+10 | 1685.99 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.836465E+10 | 20479.91 | 14-SEP-08:62 | 17.00 | 12.99 | 0.135505E+10 | 1685.99 | 10-SEP-12:00 | 17.00 | 12.99 |
October | 0.520872E+10 | 6909.12 | 01-OCT-17:10 | 11.83 | 8.82 | 0.118131E+10 | 1685.81 | 07-OCT-12:00 | 17.00 | 9.21 |
November | 0.256357E+10 | 8537.32 | 29-NOV-09:04 | 1.17 | -0.2 | 0.103200E+10 | 1362.40 | 10-NOV-13:00 | 1.17 | -0.2 |
December | 0.119106E+10 | 9564.43 | 27-DEC-09:04 | -0.7 | -0.8 | 0.106910E+10 | 1275.40 | 01-DEC-13:09 | -0.7 | -0.8 |
Annual Sum or Average | 0.642823E+11 | 0.142602E+11 | ||||||||
Minimum of Months | 0.119106E+10 | 6909.12 | -1.8 | -3.0 | 0.960537E+09 | 1275.40 | -0.7 | -0.8 | ||
Maximum of Months | 0.102473E+11 | 32817.62 | 24.00 | 14.10 | 0.140768E+10 | 1685.99 | 24.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.105620E+10 | 4880.87 | 09-JAN-09:03 | -1.8 | -3.0 | 0.557021E+09 | 795.61 | 29-JAN-18:00 | 9.00 | 8.43 |
February | 0.107601E+10 | 4169.91 | 17-FEB-09:03 | 1.33 | 0.86 | 0.501986E+09 | 789.96 | 20-FEB-18:00 | 7.00 | 4.65 |
March | 0.137059E+10 | 3688.88 | 15-MAR-08:02 | 2.00 | 1.57 | 0.557894E+09 | 836.37 | 19-MAR-17:00 | 11.00 | 10.48 |
April | 0.312531E+10 | 18807.15 | 29-APR-18:35 | 18.67 | 11.76 | 0.629668E+09 | 842.91 | 29-APR-12:00 | 18.67 | 11.76 |
May | 0.350325E+10 | 17986.29 | 21-MAY-17:07 | 20.00 | 12.86 | 0.661204E+09 | 842.90 | 14-MAY-17:00 | 20.00 | 12.86 |
June | 0.485952E+10 | 17981.10 | 26-JUN-08:62 | 18.17 | 13.96 | 0.674908E+09 | 842.93 | 25-JUN-17:10 | 18.17 | 13.96 |
July | 0.598444E+10 | 18588.84 | 20-JUL-08:62 | 13.17 | 12.51 | 0.705621E+09 | 842.96 | 09-JUL-17:10 | 13.17 | 12.51 |
August | 0.623676E+10 | 18937.29 | 14-AUG-21:16 | 17.47 | 11.81 | 0.696150E+09 | 842.98 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.517548E+10 | 17769.50 | 14-SEP-08:62 | 17.00 | 12.99 | 0.681605E+09 | 842.98 | 10-SEP-12:00 | 17.00 | 12.99 |
October | 0.271253E+10 | 3873.23 | 03-OCT-17:10 | 12.50 | 8.41 | 0.638634E+09 | 842.90 | 01-OCT-17:30 | 12.50 | 8.41 |
November | 0.148635E+10 | 4141.45 | 29-NOV-09:03 | 1.17 | -0.2 | 0.549112E+09 | 836.82 | 05-NOV-17:00 | 1.17 | -0.2 |
December | 0.683696E+09 | 4610.40 | 27-DEC-09:03 | -0.7 | -0.8 | 0.555477E+09 | 747.96 | 24-DEC-18:40 | -0.7 | -0.8 |
Annual Sum or Average | 0.372701E+11 | 0.740928E+10 | ||||||||
Minimum of Months | 0.683696E+09 | 3688.88 | -1.8 | -3.0 | 0.501986E+09 | 747.96 | -0.7 | -0.8 | ||
Maximum of Months | 0.623676E+10 | 18937.29 | 20.00 | 13.96 | 0.705621E+09 | 842.98 | 21.00 | 15.44 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.659216E+09 | 5676.40 | 10-JAN-08:03 | -5.7 | -6.7 | 0.317272E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.656476E+09 | 4310.85 | 18-FEB-08:03 | 0.17 | -0.4 | 0.288130E+09 | 650.26 | 04-FEB-13:00 | 0.17 | -0.4 |
March | 0.948859E+09 | 3644.54 | 16-MAR-07:04 | 2.33 | 1.90 | 0.327109E+09 | 716.61 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.241126E+10 | 15262.62 | 30-APR-08:62 | 17.50 | 12.51 | 0.361782E+09 | 842.91 | 29-APR-12:00 | 17.50 | 12.51 |
May | 0.270750E+10 | 7844.21 | 24-MAY-07:03 | 10.33 | 9.58 | 0.384862E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.338659E+10 | 19261.47 | 14-JUN-07:02 | 12.00 | 12.00 | 0.412955E+09 | 842.89 | 17-JUN-12:20 | 14.67 | 12.94 |
July | 0.413749E+10 | 19075.97 | 13-JUL-07:02 | 13.17 | 12.51 | 0.418877E+09 | 842.94 | 22-JUL-12:09 | 27.17 | 17.06 |
August | 0.447622E+10 | 18914.19 | 15-AUG-07:02 | 17.17 | 13.06 | 0.430989E+09 | 842.98 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.361642E+10 | 17764.19 | 02-SEP-07:03 | 13.83 | 12.78 | 0.408665E+09 | 842.95 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.212171E+10 | 3586.00 | 07-OCT-15:00 | 19.00 | 10.10 | 0.361490E+09 | 842.89 | 07-OCT-12:20 | 19.00 | 10.10 |
November | 0.105064E+10 | 4489.41 | 29-NOV-08:03 | -0.7 | -1.6 | 0.308415E+09 | 664.44 | 25-NOV-13:50 | -0.7 | -1.6 |
December | 0.385771E+09 | 4651.98 | 27-DEC-08:03 | -1.0 | -1.4 | 0.316712E+09 | 637.68 | 02-DEC-13:20 | -1.0 | -1.4 |
Annual Sum or Average | 0.265582E+11 | 0.433726E+10 | ||||||||
Minimum of Months | 0.385771E+09 | 3586.00 | -5.7 | -6.7 | 0.288130E+09 | 637.68 | -1.0 | -1.6 | ||
Maximum of Months | 0.447622E+10 | 19261.47 | 19.00 | 13.06 | 0.430989E+09 | 842.98 | 27.17 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.541071E+09 | 5786.37 | 10-JAN-08:03 | -5.7 | -6.7 | 0.317140E+09 | 637.68 | 21-JAN-13:09 | 7.83 | 6.08 |
February | 0.555443E+09 | 4413.97 | 18-FEB-08:03 | 0.17 | -0.4 | 0.288056E+09 | 645.07 | 04-FEB-13:00 | 0.17 | -0.4 |
March | 0.819543E+09 | 3946.04 | 13-MAR-07:04 | 1.33 | 0.37 | 0.326659E+09 | 709.65 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.227644E+10 | 14380.69 | 30-APR-08:62 | 17.50 | 12.51 | 0.357841E+09 | 842.91 | 29-APR-12:00 | 17.50 | 12.51 |
May | 0.259914E+10 | 6923.42 | 24-MAY-07:03 | 10.33 | 9.58 | 0.380850E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.329433E+10 | 19289.06 | 14-JUN-07:02 | 12.00 | 12.00 | 0.412323E+09 | 842.89 | 17-JUN-12:30 | 15.00 | 12.97 |
July | 0.407311E+10 | 19101.48 | 13-JUL-07:02 | 13.17 | 12.51 | 0.418687E+09 | 842.94 | 22-JUL-12:09 | 27.17 | 17.06 |
August | 0.442225E+10 | 18958.99 | 15-AUG-07:02 | 17.17 | 13.06 | 0.430964E+09 | 842.98 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.353110E+10 | 17187.25 | 02-SEP-07:03 | 13.83 | 12.78 | 0.408468E+09 | 842.95 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.195756E+10 | 3465.01 | 07-OCT-15:00 | 19.00 | 10.10 | 0.358385E+09 | 842.89 | 07-OCT-12:20 | 19.00 | 10.10 |
November | 0.897468E+09 | 4612.41 | 29-NOV-08:03 | -0.7 | -1.6 | 0.307794E+09 | 653.68 | 25-NOV-13:50 | -0.7 | -1.6 |
December | 0.317351E+09 | 4312.08 | 31-DEC-09:04 | 0.33 | -0.2 | 0.316683E+09 | 637.68 | 02-DEC-13:39 | 0.33 | -0.2 |
Annual Sum or Average | 0.252848E+11 | 0.432385E+10 | ||||||||
Minimum of Months | 0.317351E+09 | 3465.01 | -5.7 | -6.7 | 0.288056E+09 | 637.68 | -0.7 | -1.6 | ||
Maximum of Months | 0.442225E+10 | 19289.06 | 19.00 | 13.06 | 0.430964E+09 | 842.98 | 27.17 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.393235E+09 | 5330.46 | 11-JAN-08:04 | -4.0 | -4.9 | 0.317063E+09 | 637.68 | 07-JAN-13:39 | -4.0 | -4.9 |
February | 0.407046E+09 | 4428.35 | 18-FEB-08:03 | 0.17 | -0.4 | 0.288002E+09 | 637.95 | 04-FEB-13:00 | 0.17 | -0.4 |
March | 0.631809E+09 | 4116.69 | 13-MAR-07:04 | 1.33 | 0.37 | 0.326221E+09 | 697.05 | 25-MAR-12:00 | 14.00 | 11.22 |
April | 0.207595E+10 | 11712.43 | 30-APR-08:62 | 17.50 | 12.51 | 0.352511E+09 | 842.91 | 29-APR-12:00 | 17.50 | 12.51 |
May | 0.241294E+10 | 5009.49 | 01-MAY-07:03 | 7.17 | 5.31 | 0.374974E+09 | 842.89 | 27-MAY-12:09 | 15.83 | 10.60 |
June | 0.306605E+10 | 18975.57 | 14-JUN-07:02 | 12.00 | 12.00 | 0.410452E+09 | 842.89 | 24-JUN-12:20 | 16.67 | 12.61 |
July | 0.385027E+10 | 18801.92 | 13-JUL-07:02 | 13.17 | 12.51 | 0.418103E+09 | 842.94 | 22-JUL-12:09 | 27.17 | 17.06 |
August | 0.419484E+10 | 18669.08 | 15-AUG-07:02 | 17.17 | 13.06 | 0.430850E+09 | 842.98 | 19-AUG-12:00 | 21.00 | 15.44 |
September | 0.330782E+10 | 15182.34 | 02-SEP-07:03 | 13.83 | 12.78 | 0.407873E+09 | 842.94 | 23-SEP-12:00 | 19.00 | 14.78 |
October | 0.172887E+10 | 3229.45 | 06-OCT-07:03 | 3.83 | 3.69 | 0.354198E+09 | 842.90 | 07-OCT-12:20 | 16.33 | 10.17 |
November | 0.702508E+09 | 4577.21 | 29-NOV-08:03 | -0.7 | -1.6 | 0.307205E+09 | 642.00 | 25-NOV-13:50 | -0.7 | -1.6 |
December | 0.224267E+09 | 4486.78 | 31-DEC-09:04 | 0.33 | -0.2 | 0.316656E+09 | 637.68 | 09-DEC-13:30 | 0.33 | -0.2 |
Annual Sum or Average | 0.229956E+11 | 0.430411E+10 | ||||||||
Minimum of Months | 0.224267E+09 | 3229.45 | -4.0 | -4.9 | 0.288002E+09 | 637.68 | -4.0 | -4.9 | ||
Maximum of Months | 0.419484E+10 | 18975.57 | 17.50 | 13.06 | 0.430850E+09 | 842.98 | 27.17 | 17.06 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.365521E+09 | 9071.01 | 10-JAN-09:05 | -3.8 | -5.4 | 0.108360E+10 | 1700.53 | 07-JAN-15:09 | -3.8 | -5.4 |
February | 0.369815E+09 | 8596.79 | 17-FEB-09:04 | 1.33 | 0.86 | 0.986625E+09 | 1700.53 | 04-FEB-15:09 | 1.33 | 0.86 |
March | 0.704102E+09 | 8061.70 | 15-MAR-08:04 | 2.00 | 1.57 | 0.111839E+10 | 1759.95 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.338042E+10 | 19694.28 | 30-APR-09:03 | 18.33 | 12.10 | 0.118034E+10 | 2247.80 | 29-APR-14:00 | 18.33 | 12.10 |
May | 0.397665E+10 | 7148.80 | 22-MAY-15:00 | 24.00 | 16.08 | 0.125194E+10 | 2247.80 | 27-MAY-14:00 | 14.00 | 10.25 |
June | 0.499227E+10 | 32991.18 | 25-JUN-09:02 | 16.33 | 12.18 | 0.138957E+10 | 2247.84 | 24-JUN-14:20 | 16.33 | 12.18 |
July | 0.625321E+10 | 32159.81 | 25-JUL-08:62 | 13.17 | 13.07 | 0.142826E+10 | 2247.82 | 22-JUL-14:09 | 13.17 | 13.07 |
August | 0.680030E+10 | 31822.04 | 15-AUG-08:62 | 17.67 | 13.87 | 0.147878E+10 | 2247.98 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.525786E+10 | 21647.66 | 14-SEP-08:62 | 17.00 | 12.99 | 0.139654E+10 | 2247.90 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.265277E+10 | 6159.21 | 05-OCT-20:00 | 5.00 | 4.09 | 0.118607E+10 | 2247.74 | 07-OCT-14:20 | 17.67 | 9.98 |
November | 0.782181E+09 | 8612.50 | 29-NOV-09:04 | 1.17 | -0.2 | 0.104460E+10 | 1700.53 | 25-NOV-15:09 | 1.17 | -0.2 |
December | 0.129217E+09 | 8448.90 | 08-DEC-09:04 | 1.50 | 1.37 | 0.108534E+10 | 1700.53 | 16-DEC-15:09 | 8.00 | 6.82 |
Annual Sum or Average | 0.356643E+11 | 0.146301E+11 | ||||||||
Minimum of Months | 0.129217E+09 | 6159.21 | -3.8 | -5.4 | 0.986625E+09 | 1700.53 | -3.8 | -5.4 | ||
Maximum of Months | 0.680030E+10 | 32991.18 | 24.00 | 16.08 | 0.147878E+10 | 2247.98 | 20.00 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.154306E+09 | 4262.60 | 13-JAN-09:04 | 1.17 | 0.76 | 0.541765E+09 | 850.24 | 07-JAN-15:09 | 1.17 | 0.76 |
February | 0.163983E+09 | 4288.84 | 17-FEB-09:04 | 1.33 | 0.86 | 0.493273E+09 | 850.24 | 04-FEB-15:20 | 1.33 | 0.86 |
March | 0.312249E+09 | 3903.96 | 15-MAR-08:04 | 2.00 | 1.57 | 0.559155E+09 | 878.38 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.158296E+10 | 8658.71 | 30-APR-09:03 | 18.33 | 12.10 | 0.588872E+09 | 1123.87 | 29-APR-14:00 | 18.33 | 12.10 |
May | 0.186684E+10 | 3640.84 | 22-MAY-15:00 | 24.00 | 16.08 | 0.624590E+09 | 1123.86 | 27-MAY-14:00 | 14.00 | 10.25 |
June | 0.242009E+10 | 16604.26 | 26-JUN-08:62 | 18.17 | 13.96 | 0.693901E+09 | 1123.88 | 24-JUN-14:20 | 18.17 | 13.96 |
July | 0.311669E+10 | 16944.15 | 25-JUL-08:62 | 13.17 | 13.07 | 0.713916E+09 | 1123.88 | 22-JUL-14:09 | 13.17 | 13.07 |
August | 0.342723E+10 | 16760.08 | 15-AUG-08:62 | 17.67 | 13.87 | 0.739392E+09 | 1123.96 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.260027E+10 | 9941.32 | 14-SEP-08:62 | 17.00 | 12.99 | 0.698428E+09 | 1123.92 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.122981E+10 | 3013.49 | 05-OCT-20:00 | 5.00 | 4.09 | 0.592627E+09 | 1123.84 | 07-OCT-14:20 | 17.67 | 9.98 |
November | 0.355876E+09 | 4280.53 | 29-NOV-09:04 | 1.17 | -0.2 | 0.522286E+09 | 850.24 | 25-NOV-15:09 | 1.17 | -0.2 |
December | 54012794.33 | 4095.61 | 08-DEC-09:04 | 1.50 | 1.37 | 0.542651E+09 | 850.24 | 02-DEC-15:50 | 1.50 | 1.37 |
Annual Sum or Average | 0.172843E+11 | 0.731086E+10 | ||||||||
Minimum of Months | 54012794.33 | 3013.49 | 1.17 | -0.2 | 0.493273E+09 | 850.24 | 1.17 | -0.2 | ||
Maximum of Months | 0.342723E+10 | 16944.15 | 24.00 | 16.08 | 0.739392E+09 | 1123.96 | 20.00 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.139042E+09 | 4240.53 | 13-JAN-09:04 | 1.17 | 0.76 | 0.541708E+09 | 850.24 | 14-JAN-15:30 | 7.00 | 5.36 |
February | 0.143106E+09 | 4263.35 | 17-FEB-09:04 | 1.33 | 0.86 | 0.493272E+09 | 850.24 | 04-FEB-15:39 | 1.33 | 0.86 |
March | 0.279265E+09 | 3973.98 | 15-MAR-08:04 | 2.00 | 1.57 | 0.559070E+09 | 872.77 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.151063E+10 | 7501.55 | 30-APR-09:03 | 18.33 | 12.10 | 0.585758E+09 | 1123.87 | 29-APR-14:00 | 18.33 | 12.10 |
May | 0.178280E+10 | 3518.48 | 22-MAY-15:00 | 24.00 | 16.08 | 0.621101E+09 | 1123.86 | 27-MAY-14:50 | 14.33 | 10.40 |
June | 0.233022E+10 | 16426.67 | 26-JUN-08:62 | 18.17 | 13.96 | 0.690656E+09 | 1123.88 | 24-JUN-14:20 | 18.17 | 13.96 |
July | 0.302061E+10 | 16784.99 | 25-JUL-08:62 | 13.17 | 13.07 | 0.712918E+09 | 1123.88 | 22-JUL-14:09 | 13.17 | 13.07 |
August | 0.333348E+10 | 15736.46 | 15-AUG-08:62 | 17.67 | 13.87 | 0.739316E+09 | 1123.95 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.250983E+10 | 8979.81 | 14-SEP-08:62 | 17.00 | 12.99 | 0.697300E+09 | 1123.91 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.116394E+10 | 2989.00 | 05-OCT-20:00 | 5.00 | 4.09 | 0.589640E+09 | 1123.84 | 07-OCT-14:20 | 17.67 | 9.98 |
November | 0.320753E+09 | 4256.21 | 29-NOV-09:04 | 1.17 | -0.2 | 0.522192E+09 | 850.24 | 25-NOV-15:09 | 1.17 | -0.2 |
December | 48719393.59 | 4153.85 | 08-DEC-09:04 | 1.50 | 1.37 | 0.542635E+09 | 850.24 | 02-DEC-15:39 | 1.50 | 1.37 |
Annual Sum or Average | 0.165824E+11 | 0.729557E+10 | ||||||||
Minimum of Months | 48719393.59 | 2989.00 | 1.17 | -0.2 | 0.493272E+09 | 850.24 | 1.17 | -0.2 | ||
Maximum of Months | 0.333348E+10 | 16784.99 | 24.00 | 16.08 | 0.739316E+09 | 1123.95 | 20.00 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 79680189.69 | 4053.23 | 06-JAN-09:04 | 2.17 | 1.73 | 0.541669E+09 | 850.24 | 14-JAN-15:20 | 7.00 | 5.42 |
February | 80649454.02 | 4161.12 | 18-FEB-09:04 | 1.67 | 0.83 | 0.493194E+09 | 850.24 | 11-FEB-15:09 | 1.67 | 0.83 |
March | 0.177520E+09 | 4075.64 | 15-MAR-08:04 | 2.00 | 1.57 | 0.558832E+09 | 856.01 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.132136E+10 | 4611.49 | 30-APR-15:00 | 24.00 | 13.13 | 0.579184E+09 | 1123.87 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.156116E+10 | 3258.56 | 22-MAY-15:00 | 24.00 | 16.08 | 0.613271E+09 | 1123.86 | 27-MAY-14:30 | 15.00 | 10.68 |
June | 0.212491E+10 | 15984.60 | 26-JUN-08:62 | 18.17 | 13.96 | 0.681695E+09 | 1123.87 | 24-JUN-14:20 | 18.17 | 13.96 |
July | 0.277839E+10 | 16315.74 | 24-JUL-08:62 | 14.17 | 13.49 | 0.710019E+09 | 1123.88 | 22-JUL-14:09 | 14.17 | 13.49 |
August | 0.306719E+10 | 12845.54 | 17-AUG-08:62 | 16.50 | 15.52 | 0.738972E+09 | 1123.95 | 19-AUG-14:00 | 20.00 | 15.13 |
September | 0.227862E+10 | 5591.60 | 14-SEP-08:62 | 17.00 | 12.99 | 0.693143E+09 | 1123.90 | 23-SEP-14:39 | 19.00 | 14.78 |
October | 0.989174E+09 | 2916.58 | 05-OCT-20:00 | 5.00 | 4.09 | 0.582358E+09 | 1123.85 | 07-OCT-14:20 | 17.67 | 9.98 |
November | 0.212226E+09 | 4023.37 | 28-NOV-09:04 | 2.17 | 0.49 | 0.521965E+09 | 850.24 | 04-NOV-14:09 | 2.17 | 0.49 |
December | 24043305.16 | 4217.31 | 08-DEC-09:04 | 1.50 | 1.37 | 0.542575E+09 | 850.24 | 02-DEC-15:20 | 1.50 | 1.37 |
Annual Sum or Average | 0.146949E+11 | 0.725687E+10 | ||||||||
Minimum of Months | 24043305.16 | 2916.58 | 1.50 | 0.49 | 0.493194E+09 | 850.24 | 1.50 | 0.49 | ||
Maximum of Months | 0.306719E+10 | 16315.74 | 24.00 | 16.08 | 0.738972E+09 | 1123.95 | 24.00 | 15.13 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 7417918.83 | 3098.09 | 26-JAN-09:04 | 6.00 | 5.30 | 0.541595E+09 | 850.24 | 07-JAN-15:30 | 6.00 | 5.30 |
February | 5107954.19 | 3129.29 | 10-FEB-09:04 | 6.00 | 5.05 | 0.493093E+09 | 850.24 | 04-FEB-15:09 | 6.00 | 5.05 |
March | 29087216.69 | 3105.40 | 11-MAR-09:04 | 6.00 | 4.07 | 0.558594E+09 | 850.28 | 25-MAR-14:09 | 11.83 | 9.32 |
April | 0.968043E+09 | 4347.21 | 30-APR-15:00 | 24.00 | 13.13 | 0.573273E+09 | 1123.87 | 29-APR-14:00 | 24.00 | 13.13 |
May | 0.113390E+10 | 3082.87 | 22-MAY-15:00 | 24.00 | 16.08 | 0.602988E+09 | 1102.16 | 27-MAY-14:09 | 15.67 | 10.94 |
June | 0.186608E+10 | 10648.73 | 26-JUN-08:62 | 18.17 | 13.96 | 0.664446E+09 | 1123.86 | 17-JUN-14:00 | 18.17 | 13.96 |
July | 0.247673E+10 | 16311.10 | 23-JUL-09:01 | 20.17 | 15.71 | 0.704738E+09 | 1123.88 | 22-JUL-14:09 | 20.17 | 15.71 |
August | 0.272441E+10 | 5432.83 | 20-AUG-09:02 | 16.83 | 13.42 | 0.737436E+09 | 1123.95 | 12-AUG-14:09 | 16.83 | 13.42 |
September | 0.196699E+10 | 4646.71 | 13-SEP-14:20 | 23.00 | 16.22 | 0.683678E+09 | 1123.88 | 09-SEP-14:30 | 23.00 | 16.22 |
October | 0.614632E+09 | 2884.74 | 30-OCT-08:04 | 7.17 | 6.56 | 0.572448E+09 | 1123.85 | 07-OCT-14:20 | 7.17 | 6.56 |
November | 38571791.27 | 3468.64 | 16-NOV-09:04 | 4.83 | 4.15 | 0.521733E+09 | 850.24 | 04-NOV-14:30 | 4.83 | 4.15 |
December | 864499.89 | 2554.19 | 02-DEC-09:04 | 7.00 | 6.47 | 0.542506E+09 | 850.24 | 02-DEC-15:09 | 8.83 | 7.85 |
Annual Sum or Average | 0.118318E+11 | 0.719653E+10 | ||||||||
Minimum of Months | 864499.89 | 2554.19 | 4.83 | 4.07 | 0.493093E+09 | 850.24 | 4.83 | 4.15 | ||
Maximum of Months | 0.272441E+10 | 16311.10 | 24.00 | 16.22 | 0.737436E+09 | 1123.95 | 24.00 | 16.22 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.215486E+10 | 48577.50 | 28-JAN-09:01 | 7.25 |
February | 0.136322E+10 | 48477.46 | 01-FEB-09:01 | 7.00 |
March | 0.122332E+10 | 49238.12 | 28-MAR-08:61 | 8.38 |
April | 0.252144E+09 | 47771.95 | 01-APR-08:61 | 5.50 |
May | 0.195778E+09 | 8413.40 | 05-MAY-08:62 | 8.17 |
June | 0.173709E+09 | 1987.28 | 10-JUN-07:25 | 11.00 |
July | 0.178036E+09 | 2840.45 | 22-JUL-08:05 | 24.00 |
August | 0.173479E+09 | 1936.80 | 04-AUG-07:13 | 13.33 |
September | 0.182721E+09 | 1976.95 | 21-SEP-07:25 | 10.00 |
October | 0.261038E+09 | 27180.31 | 23-OCT-08:61 | 7.33 |
November | 0.926097E+09 | 48198.11 | 21-NOV-09:01 | 6.33 |
December | 0.275250E+10 | 49367.34 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.983690E+10 | |||
Minimum of Months | 0.173479E+09 | 1936.80 | 5.50 | |
Maximum of Months | 0.275250E+10 | 49367.34 | 24.00 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.525621E+09 | 24693.26 | 13-JAN-09:01 | 1.17 |
February | 0.243511E+09 | 24710.09 | 17-FEB-09:01 | 1.33 |
March | 0.216500E+09 | 16376.60 | 16-MAR-08:61 | 4.00 |
April | 0.102457E+09 | 1115.87 | 12-APR-07:45 | 6.50 |
May | 0.107553E+09 | 1131.84 | 03-MAY-07:25 | 7.50 |
June | 93470350.19 | 1129.90 | 10-JUN-07:25 | 11.00 |
July | 92983982.30 | 1599.44 | 23-JUL-07:07 | 18.17 |
August | 96791134.35 | 1251.08 | 06-AUG-07:10 | 13.17 |
September | 94193641.84 | 1121.56 | 21-SEP-07:25 | 10.00 |
October | 0.109734E+09 | 1127.29 | 11-OCT-07:25 | 7.50 |
November | 0.192319E+09 | 22341.96 | 29-NOV-09:01 | 1.17 |
December | 0.655025E+09 | 24916.56 | 15-DEC-09:01 | 3.00 |
Annual Sum or Average | 0.253016E+10 | |||
Minimum of Months | 92983982.30 | 1115.87 | 1.17 | |
Maximum of Months | 0.655025E+09 | 24916.56 | 18.17 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.820039E+09 | 24383.77 | 08-JAN-09:01 | 2.17 |
February | 0.441217E+09 | 24631.04 | 20-FEB-09:01 | 3.33 |
March | 0.364670E+09 | 17754.94 | 05-MAR-09:02 | 5.17 |
April | 0.112724E+09 | 2372.96 | 10-APR-15:30 | 7.50 |
May | 0.102224E+09 | 1103.10 | 28-MAY-08:00 | 9.00 |
June | 0.100129E+09 | 1043.12 | 28-JUN-07:00 | 11.00 |
July | 0.108119E+09 | 2055.43 | 22-JUL-17:12 | 29.33 |
August | 0.104400E+09 | 1046.03 | 08-AUG-07:00 | 16.00 |
September | 0.101219E+09 | 1058.48 | 27-SEP-07:00 | 10.00 |
October | 0.113764E+09 | 2570.88 | 28-OCT-07:50 | 7.33 |
November | 0.336650E+09 | 18614.70 | 29-NOV-08:62 | -0.7 |
December | 0.103093E+10 | 24867.30 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.373609E+10 | |||
Minimum of Months | 0.100129E+09 | 1043.12 | -0.7 | |
Maximum of Months | 0.103093E+10 | 24867.30 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.952377E+09 | 25423.05 | 01-JAN-09:01 | 4.00 |
February | 0.557238E+09 | 25495.64 | 26-FEB-09:01 | 4.33 |
March | 0.463621E+09 | 23162.05 | 06-MAR-08:62 | 6.17 |
April | 0.122247E+09 | 3261.31 | 02-APR-08:10 | 7.33 |
May | 0.102907E+09 | 1106.03 | 28-MAY-08:00 | 9.00 |
June | 0.100416E+09 | 1044.40 | 28-JUN-07:00 | 11.00 |
July | 0.108367E+09 | 2060.10 | 22-JUL-17:12 | 29.33 |
August | 0.104662E+09 | 1047.42 | 08-AUG-07:00 | 16.00 |
September | 0.101488E+09 | 1060.14 | 27-SEP-07:00 | 10.00 |
October | 0.119197E+09 | 2292.14 | 23-OCT-07:03 | 4.50 |
November | 0.424000E+09 | 23476.82 | 20-NOV-08:62 | 1.33 |
December | 0.118985E+10 | 25525.16 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.434637E+10 | |||
Minimum of Months | 0.100416E+09 | 1044.40 | 1.33 | |
Maximum of Months | 0.118985E+10 | 25525.16 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.116378E+10 | 24813.64 | 01-JAN-09:01 | 4.00 |
February | 0.725068E+09 | 24858.35 | 26-FEB-09:01 | 4.33 |
March | 0.620242E+09 | 25104.46 | 06-MAR-08:62 | 6.17 |
April | 0.139316E+09 | 5498.16 | 01-APR-07:03 | 4.17 |
May | 0.103290E+09 | 1099.81 | 28-MAY-08:00 | 9.00 |
June | 99929713.37 | 1039.03 | 28-JUN-07:00 | 11.00 |
July | 0.107923E+09 | 2059.09 | 22-JUL-17:12 | 29.33 |
August | 0.104167E+09 | 1041.54 | 08-AUG-07:00 | 16.00 |
September | 0.101039E+09 | 1054.86 | 21-SEP-07:00 | 7.00 |
October | 0.135549E+09 | 5388.36 | 23-OCT-07:03 | 4.50 |
November | 0.550355E+09 | 24569.18 | 27-NOV-08:62 | 4.00 |
December | 0.145764E+10 | 24901.31 | 25-DEC-09:01 | 4.17 |
Annual Sum or Average | 0.530830E+10 | |||
Minimum of Months | 99929713.37 | 1039.03 | 4.00 | |
Maximum of Months | 0.145764E+10 | 25104.46 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.249134E+10 | 52621.16 | 10-JAN-08:61 | -5.7 |
February | 0.156106E+10 | 46669.83 | 22-FEB-09:01 | 8.00 |
March | 0.134647E+10 | 48079.21 | 09-MAR-09:01 | 11.00 |
April | 0.276768E+09 | 45415.16 | 01-APR-08:61 | 5.50 |
May | 0.190939E+09 | 6356.42 | 17-MAY-08:62 | 8.17 |
June | 0.182056E+09 | 1921.17 | 10-JUN-07:25 | 11.00 |
July | 0.199309E+09 | 3889.43 | 22-JUL-17:12 | 29.33 |
August | 0.187204E+09 | 1874.10 | 04-AUG-07:13 | 13.33 |
September | 0.179996E+09 | 1909.95 | 21-SEP-07:25 | 10.00 |
October | 0.318166E+09 | 46275.49 | 23-OCT-08:61 | 7.33 |
November | 0.119748E+10 | 46711.68 | 13-NOV-09:01 | 8.00 |
December | 0.309822E+10 | 49244.07 | 31-DEC-09:01 | 0.33 |
Annual Sum or Average | 0.112290E+11 | |||
Minimum of Months | 0.179996E+09 | 1874.10 | -5.7 | |
Maximum of Months | 0.309822E+10 | 52621.16 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.147558E+10 | 25601.09 | 10-JAN-08:61 | -5.7 |
February | 0.975437E+09 | 24939.28 | 22-FEB-09:01 | 8.00 |
March | 0.853199E+09 | 25643.80 | 09-MAR-09:01 | 11.00 |
April | 0.164650E+09 | 24317.80 | 01-APR-08:61 | 5.50 |
May | 0.109054E+09 | 4904.09 | 17-MAY-08:62 | 8.17 |
June | 0.101287E+09 | 1058.70 | 10-JUN-07:25 | 11.00 |
July | 0.110965E+09 | 2038.53 | 22-JUL-17:12 | 29.33 |
August | 0.104254E+09 | 1029.82 | 04-AUG-07:13 | 13.33 |
September | 0.100034E+09 | 1051.98 | 21-SEP-07:25 | 10.00 |
October | 0.198476E+09 | 24747.26 | 23-OCT-08:61 | 7.33 |
November | 0.755469E+09 | 24959.40 | 13-NOV-09:01 | 8.00 |
December | 0.181901E+10 | 25291.85 | 04-DEC-09:01 | 8.17 |
Annual Sum or Average | 0.676741E+10 | |||
Minimum of Months | 0.100034E+09 | 1029.82 | -5.7 | |
Maximum of Months | 0.181901E+10 | 25643.80 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.155677E+10 | 27782.21 | 10-JAN-08:61 | -5.7 |
February | 0.104597E+10 | 24837.11 | 22-FEB-09:01 | 8.00 |
March | 0.915674E+09 | 25537.86 | 09-MAR-09:01 | 11.00 |
April | 0.175353E+09 | 24213.04 | 01-APR-08:61 | 5.50 |
May | 0.112667E+09 | 7374.20 | 17-MAY-08:62 | 8.17 |
June | 0.100900E+09 | 1052.62 | 10-JUN-07:25 | 11.00 |
July | 0.110611E+09 | 2036.41 | 22-JUL-17:12 | 29.33 |
August | 0.103839E+09 | 1024.93 | 04-AUG-07:13 | 13.33 |
September | 99656777.10 | 1046.52 | 21-SEP-07:25 | 10.00 |
October | 0.216351E+09 | 24647.32 | 23-OCT-08:61 | 7.33 |
November | 0.806576E+09 | 24961.31 | 22-NOV-09:01 | 9.33 |
December | 0.189851E+10 | 26450.37 | 31-DEC-09:01 | 0.33 |
Annual Sum or Average | 0.714288E+10 | |||
Minimum of Months | 99656777.10 | 1024.93 | -5.7 | |
Maximum of Months | 0.189851E+10 | 27782.21 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.190337E+10 | 27531.80 | 10-JAN-08:61 | -5.7 |
February | 0.134936E+10 | 25044.49 | 13-FEB-08:61 | 1.00 |
March | 0.118829E+10 | 25380.22 | 09-MAR-09:01 | 11.00 |
April | 0.228071E+09 | 24495.49 | 03-APR-08:61 | 8.17 |
May | 0.137526E+09 | 15794.51 | 17-MAY-08:62 | 8.17 |
June | 0.100318E+09 | 1042.93 | 10-JUN-07:25 | 11.00 |
July | 0.109890E+09 | 2032.10 | 22-JUL-17:12 | 29.33 |
August | 0.103075E+09 | 1015.37 | 04-AUG-07:13 | 13.33 |
September | 99055592.91 | 1036.11 | 21-SEP-07:25 | 10.00 |
October | 0.300081E+09 | 24538.40 | 21-OCT-08:61 | 8.50 |
November | 0.103738E+10 | 25193.53 | 24-NOV-09:01 | 11.17 |
December | 0.227216E+10 | 27416.05 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.882857E+10 | |||
Minimum of Months | 99055592.91 | 1015.37 | -5.7 | |
Maximum of Months | 0.227216E+10 | 27531.80 | 29.33 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.351299E+10 | 28184.57 | 10-JAN-08:61 | -5.7 |
February | 0.276243E+10 | 28040.13 | 13-FEB-08:61 | 1.00 |
March | 0.251903E+10 | 27709.81 | 27-MAR-07:02 | 2.50 |
April | 0.461471E+09 | 25373.00 | 03-APR-08:61 | 8.17 |
May | 0.293333E+09 | 25127.04 | 17-MAY-08:62 | 8.17 |
June | 0.102231E+09 | 2512.30 | 07-JUN-08:65 | 11.67 |
July | 0.108650E+09 | 2060.67 | 22-JUL-17:12 | 29.33 |
August | 0.103515E+09 | 1056.54 | 04-AUG-07:13 | 13.33 |
September | 99944804.81 | 1074.05 | 21-SEP-07:25 | 10.00 |
October | 0.727135E+09 | 25635.29 | 17-OCT-08:62 | 10.50 |
November | 0.213135E+10 | 27732.23 | 20-NOV-08:62 | 1.33 |
December | 0.404232E+10 | 28058.51 | 18-DEC-08:61 | 1.00 |
Annual Sum or Average | 0.168644E+11 | |||
Minimum of Months | 99944804.81 | 1056.54 | -5.7 | |
Maximum of Months | 0.404232E+10 | 28184.57 | 29.33 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.378006E+10 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340602E+10 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.322802E+10 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 262349.11 | 0.243054E+10 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 18039.82 | 0.294590E+10 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10776606.80 | 0.220859E+10 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47465451.26 | 0.186045E+10 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6333297.55 | 0.148867E+10 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190320E+10 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.269339E+10 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.340246E+10 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.423152E+10 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 64855744.53 | 0.335788E+11 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.148867E+10 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 47465451.26 | 0.423152E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205025E+10 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180708E+10 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175551E+10 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 144860.97 | 0.136209E+10 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 9929.35 | 0.154036E+10 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 5881736.22 | 0.111308E+10 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25989198.85 | 0.911319E+09 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 3451349.53 | 0.729407E+09 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.960297E+09 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.146021E+10 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178758E+10 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.219271E+10 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 35477074.91 | 0.176699E+11 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.729407E+09 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 25989198.85 | 0.219271E+10 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205739E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182440E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175824E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.134921E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9931.14 | 0.155672E+10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5840221.42 | 0.115668E+10 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25488649.90 | 0.958379E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451401.37 | 0.768010E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.991731E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.145748E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.180265E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.223106E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34859308.15 | 0.179119E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.768010E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25488649.90 | 0.223106E+10 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205568E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182231E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175596E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.133415E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9931.32 | 0.153892E+10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5840483.98 | 0.115301E+10 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25484205.15 | 0.956556E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451390.56 | 0.767344E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.989982E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.144462E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179771E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222733E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34855115.33 | 0.178436E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.767344E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25484205.15 | 0.222733E+10 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205429E+10 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182056E+10 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175427E+10 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.131435E+10 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9932.19 | 0.151425E+10 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5840959.82 | 0.114394E+10 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25498129.14 | 0.952002E+09 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451601.78 | 0.765373E+09 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.986209E+09 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.142842E+10 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179357E+10 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222399E+10 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 34869727.25 | 0.177512E+11 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765373E+09 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25498129.14 | 0.222399E+10 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.369489E+10 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.328761E+10 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.315482E+10 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 123960.25 | 0.232478E+10 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 17820.48 | 0.271708E+10 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 10506097.54 | 0.206489E+10 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45871111.04 | 0.174126E+10 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 6206280.35 | 0.140700E+10 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179609E+10 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254995E+10 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325038E+10 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.403313E+10 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 62725269.66 | 0.320219E+11 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140700E+10 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 45871111.04 | 0.403313E+10 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.205051E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181809E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.175050E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.128279E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9923.87 | 0.148188E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5843721.32 | 0.112503E+10 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25548827.38 | 0.947142E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451619.15 | 0.766781E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.983321E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.140355E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179194E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222199E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34923196.04 | 0.176235E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.766781E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25548827.38 | 0.222199E+10 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204980E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181735E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174982E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.127585E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9924.62 | 0.147249E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5844024.91 | 0.111703E+10 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25554950.32 | 0.943536E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451621.91 | 0.765758E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.980091E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.139637E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.179071E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.222095E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34929626.07 | 0.175798E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.765758E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25554950.32 | 0.222095E+10 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.204749E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181396E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.174718E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69104.31 | 0.126042E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 9926.26 | 0.144976E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 5844568.32 | 0.109459E+10 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25567073.30 | 0.932799E+09 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3451717.52 | 0.761892E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.968627E+09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137791E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.178589E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221607E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 34942389.71 | 0.174566E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.761892E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 25567073.30 | 0.221607E+10 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.216289E+10 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.198658E+10 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184790E+10 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 69520.41 | 0.136166E+10 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 10131.85 | 0.173906E+10 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 6047171.93 | 0.131374E+10 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26328116.19 | 0.116778E+10 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 3579077.21 | 0.951151E+09 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.114862E+10 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.154024E+10 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201393E+10 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.252725E+10 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 36034017.59 | 0.197608E+11 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.951151E+09 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 26328116.19 | 0.252725E+10 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 8006.93 | 11-JAN-18:00 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 6020.31 | 24-FEB-18:00 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.89 | 30-APR-17:00 | 4388.34 | 10-APR-11:10 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 30.07 | 22-MAY-15:00 | 4734.10 | 01-MAY-15:00 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 905.72 | 13-JUN-17:00 | 3936.18 | 07-JUN-15:00 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.96 | 22-JUL-15:00 | 3495.44 | 04-JUL-14:00 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 903.22 | 14-AUG-17:00 | 2483.37 | 30-AUG-17:00 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3570.70 | 30-SEP-11:10 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3955.48 | 27-OCT-17:00 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6537.86 | 28-NOV-18:00 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7437.13 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2483.37 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1477.96 | 8006.93 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 30-APR-17:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 22-MAY-15:00 | 2657.25 | 01-MAY-15:00 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.38 | 13-JUN-17:00 | 2256.86 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 2010.53 | 04-JUL-14:00 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1986.52 | 30-SEP-11:10 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2220.25 | 21-OCT-17:00 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 22-MAY-15:00 | 2648.99 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.38 | 13-JUN-17:00 | 2242.03 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1986.69 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1986.52 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 22-MAY-15:00 | 2643.50 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.38 | 13-JUN-17:00 | 2221.40 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1972.26 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1986.52 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 | 22-MAY-15:00 | 2617.90 | 01-MAY-15:00 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.38 | 13-JUN-17:00 | 2172.30 | 07-JUN-11:10 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 22-JUL-15:00 | 1937.38 | 04-JUL-14:00 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1986.53 | 30-SEP-11:10 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.64 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 7953.76 | 11-JAN-18:00 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 5964.69 | 24-FEB-18:00 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 6220.37 | 15-MAR-12:00 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.63 | 30-APR-15:00 | 4338.71 | 10-APR-11:10 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 22-MAY-15:00 | 4663.04 | 01-MAY-15:00 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 893.46 | 13-JUN-17:00 | 3794.20 | 07-JUN-15:00 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.00 | 22-JUL-15:00 | 3316.36 | 04-JUL-14:00 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 892.94 | 14-AUG-17:00 | 2418.35 | 30-AUG-17:00 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 3542.59 | 30-SEP-11:10 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 3929.21 | 27-OCT-17:00 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 6449.59 | 28-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 7352.49 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2418.35 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1458.00 | 7953.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 22-MAY-15:00 | 2582.67 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.36 | 13-JUN-17:00 | 2094.56 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.63 | 22-JUL-15:00 | 1837.13 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1970.41 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.63 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 22-MAY-15:00 | 2566.05 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.36 | 13-JUN-17:00 | 2069.36 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.63 | 22-JUL-15:00 | 1814.88 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1966.35 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.63 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4431.96 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3322.40 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 30-APR-15:00 | 2416.01 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 22-MAY-15:00 | 2521.97 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.36 | 13-JUN-17:00 | 2016.83 | 07-JUN-15:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 811.63 | 22-JUL-15:00 | 1766.13 | 04-JUL-14:00 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 497.23 | 14-AUG-17:00 | 1343.79 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1952.65 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2189.42 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3590.34 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4094.19 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1343.79 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 811.63 | 4431.96 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 4485.13 | 11-JAN-18:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 3378.03 | 24-FEB-18:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 3469.29 | 15-MAR-12:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 30-APR-15:00 | 2465.64 | 10-APR-11:10 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 22-MAY-15:00 | 2542.31 | 01-MAY-15:00 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 509.59 | 13-JUN-17:00 | 2076.78 | 07-JUN-11:10 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 22-JUL-15:00 | 1741.66 | 01-JUL-11:10 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 507.51 | 14-AUG-17:00 | 1408.80 | 30-AUG-17:00 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 1952.52 | 30-SEP-11:10 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 2215.69 | 27-OCT-17:00 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 3678.60 | 28-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 4178.83 | 29-DEC-18:00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1408.80 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 831.59 | 4485.13 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 10055.22 | 09-JAN-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 964.26 |
February | 8624.17 | 17-FEB-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 815.91 |
March | 7703.40 | 12-MAR-08:04 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 870.53 |
April | 11140.02 | 30-APR-16:07 | 12150.11 | 16623.02 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 0.00 |
May | 10729.78 | 23-MAY-08:62 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 317.73 |
June | 32030.66 | 26-JUN-08:62 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 287.64 |
July | 32817.62 | 25-JUL-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.57 |
August | 32219.86 | 15-AUG-08:62 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 256.51 |
September | 20479.91 | 14-SEP-08:62 | 1350.01 | 11665.24 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 274.02 |
October | 6909.12 | 01-OCT-17:10 | 8100.08 | 11082.01 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 674.78 |
November | 8537.32 | 29-NOV-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 858.76 |
December | 9564.43 | 27-DEC-09:04 | 2700.03 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 928.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6909.12 | 1350.01 | 11082.01 | 2696.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32817.62 | 12150.11 | 23330.47 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.48 | 964.26 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4880.87 | 09-JAN-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.34 |
February | 4169.91 | 17-FEB-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.04 |
March | 3688.88 | 15-MAR-08:02 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 462.41 |
April | 18807.15 | 29-APR-18:35 | 10124.81 | 19405.40 | 4044.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.17 |
May | 17986.29 | 21-MAY-17:07 | 18224.65 | 29108.10 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 83.99 |
June | 17981.10 | 26-JUN-08:62 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 157.91 |
July | 18588.84 | 20-JUL-08:62 | 674.99 | 6808.91 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.58 |
August | 18937.29 | 14-AUG-21:16 | 7087.36 | 22639.63 | 4718.89 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 |
September | 17769.50 | 14-SEP-08:62 | 674.99 | 6808.91 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.92 |
October | 3873.23 | 03-OCT-17:10 | 1687.47 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.60 |
November | 4141.45 | 29-NOV-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.83 |
December | 4610.40 | 27-DEC-09:03 | 1349.97 | 13617.82 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.96 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3688.88 | 674.99 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 2.41 | |
Maximum of Months | 18937.29 | 18224.65 | 29108.10 | 6067.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 530.34 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5676.40 | 10-JAN-08:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 631.89 |
February | 4310.85 | 18-FEB-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 515.49 |
March | 3644.54 | 16-MAR-07:04 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 426.51 |
April | 15262.62 | 30-APR-08:62 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.39 |
May | 7844.21 | 24-MAY-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.78 |
June | 19261.47 | 14-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.96 |
July | 19075.97 | 13-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 262.64 |
August | 18914.19 | 15-AUG-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.41 |
September | 17764.19 | 02-SEP-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.08 |
October | 3586.00 | 07-OCT-15:00 | 1012.48 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.73 |
November | 4489.41 | 29-NOV-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 559.31 |
December | 4651.98 | 27-DEC-08:03 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 544.26 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3586.00 | 506.24 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.39 | |
Maximum of Months | 19261.47 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5786.37 | 10-JAN-08:03 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 632.96 |
February | 4413.97 | 18-FEB-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 517.38 |
March | 3946.04 | 13-MAR-07:04 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 448.53 |
April | 14380.69 | 30-APR-08:62 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.26 |
May | 6923.42 | 24-MAY-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 328.55 |
June | 19289.06 | 14-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 316.15 |
July | 19101.48 | 13-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 261.86 |
August | 18958.99 | 15-AUG-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 166.19 |
September | 17187.25 | 02-SEP-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 234.01 |
October | 3465.01 | 07-OCT-15:00 | 1012.48 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.73 |
November | 4612.41 | 29-NOV-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 561.66 |
December | 4312.08 | 31-DEC-09:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 502.84 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3465.01 | 506.24 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.26 | |
Maximum of Months | 19289.06 | 1518.72 | 13827.23 | 3370.64 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 799.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 5330.46 | 11-JAN-08:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.21 |
February | 4428.35 | 18-FEB-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 514.14 |
March | 4116.69 | 13-MAR-07:04 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 451.18 |
April | 11712.43 | 30-APR-08:62 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.86 |
May | 5009.49 | 01-MAY-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 450.90 |
June | 18975.57 | 14-JUN-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 312.14 |
July | 18801.92 | 13-JUL-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 258.47 |
August | 18669.08 | 15-AUG-07:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 162.90 |
September | 15182.34 | 02-SEP-07:03 | 674.99 | 6145.43 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.71 |
October | 3229.45 | 06-OCT-07:03 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 427.88 |
November | 4577.21 | 29-NOV-08:03 | 1012.48 | 9218.15 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 555.76 |
December | 4486.78 | 31-DEC-09:04 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 504.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3229.45 | 506.24 | 4609.08 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.86 | |
Maximum of Months | 18975.57 | 1349.97 | 12290.87 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 614.21 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 9071.01 | 10-JAN-09:05 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1144.05 |
February | 8596.79 | 17-FEB-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 813.57 |
March | 8061.70 | 15-MAR-08:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 841.32 |
April | 19694.28 | 30-APR-09:03 | 2227.52 | 5761.67 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 253.84 |
May | 7148.80 | 22-MAY-15:00 | 4657.54 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 0.00 |
June | 32991.18 | 25-JUN-09:02 | 2970.03 | 7682.23 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 319.41 |
July | 32159.81 | 25-JUL-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 458.03 |
August | 31822.04 | 15-AUG-08:62 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 252.71 |
September | 21647.66 | 14-SEP-08:62 | 2970.03 | 7682.23 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 270.86 |
October | 6159.21 | 05-OCT-20:00 | 742.51 | 1920.56 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 46.20 |
November | 8612.50 | 29-NOV-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 839.63 |
December | 8448.90 | 08-DEC-09:04 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 925.98 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 6159.21 | 742.51 | 1920.56 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32991.18 | 5940.06 | 15364.46 | 5992.25 | 0.00 | 0.00 | 0.00 | 0.00 | 29.70 | 1144.05 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4262.60 | 13-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 455.23 |
February | 4288.84 | 17-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 457.12 |
March | 3903.96 | 15-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 465.12 |
April | 8658.71 | 30-APR-09:03 | 1113.73 | 2975.00 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.11 |
May | 3640.84 | 22-MAY-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
June | 16604.26 | 26-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 147.97 |
July | 16944.15 | 25-JUL-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 251.34 |
August | 16760.08 | 15-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.97 |
September | 9941.32 | 14-SEP-08:62 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.77 |
October | 3013.49 | 05-OCT-20:00 | 371.24 | 991.67 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.31 |
November | 4280.53 | 29-NOV-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 470.40 |
December | 4095.61 | 08-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 508.63 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 3013.49 | 371.24 | 991.67 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16944.15 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 508.63 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4240.53 | 13-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 453.14 |
February | 4263.35 | 17-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 454.83 |
March | 3973.98 | 15-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 466.40 |
April | 7501.55 | 30-APR-09:03 | 1113.73 | 2975.00 | 1123.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 138.80 |
May | 3518.48 | 22-MAY-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
June | 16426.67 | 26-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 146.04 |
July | 16784.99 | 25-JUL-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 249.92 |
August | 15736.46 | 15-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 137.64 |
September | 8979.81 | 14-SEP-08:62 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.64 |
October | 2989.00 | 05-OCT-20:00 | 371.24 | 991.67 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.14 |
November | 4256.21 | 29-NOV-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 468.05 |
December | 4153.85 | 08-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 509.75 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2989.00 | 371.24 | 991.67 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16784.99 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 509.75 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 4053.23 | 06-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 435.41 |
February | 4161.12 | 18-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 478.55 |
March | 4075.64 | 15-MAR-08:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 464.43 |
April | 4611.49 | 30-APR-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.51 | 0.00 |
May | 3258.56 | 22-MAY-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 0.00 |
June | 15984.60 | 26-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 139.56 |
July | 16315.74 | 24-JUL-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 233.63 |
August | 12845.54 | 17-AUG-08:62 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 170.66 |
September | 5591.60 | 14-SEP-08:62 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.19 |
October | 2916.58 | 05-OCT-20:00 | 371.24 | 991.67 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 22.67 |
November | 4023.37 | 28-NOV-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 500.13 |
December | 4217.31 | 08-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 507.08 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2916.58 | 371.24 | 991.67 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16315.74 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.54 | 507.08 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 3098.09 | 26-JAN-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 382.74 |
February | 3129.29 | 10-FEB-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 392.73 |
March | 3105.40 | 11-MAR-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 374.65 |
April | 4347.21 | 30-APR-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.71 | 0.00 |
May | 3082.87 | 22-MAY-15:00 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 0.00 |
June | 10648.73 | 26-JUN-08:62 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 151.54 |
July | 16311.10 | 23-JUL-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 144.13 |
August | 5432.83 | 20-AUG-09:02 | 1484.97 | 3966.66 | 1498.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 195.19 |
September | 4646.71 | 13-SEP-14:20 | 2328.71 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 150.49 |
October | 2884.74 | 30-OCT-08:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 327.23 |
November | 3468.64 | 16-NOV-09:04 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 373.05 |
December | 2554.19 | 02-DEC-09:04 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 324.18 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 2554.19 | 1484.97 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 16311.10 | 2969.94 | 7933.33 | 2996.12 | 0.00 | 0.00 | 0.00 | 0.00 | 16.89 | 392.73 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.872662E+11 | 69113.66 | 04-JAN-18:40 | 0.706285E+11 | 176597.73 | 10-JAN-09:09 |
February | 0.779148E+11 | 66999.38 | 21-FEB-17:49 | 0.558716E+11 | 141236.18 | 13-FEB-09:09 |
March | 0.857273E+11 | 66961.28 | 09-MAR-18:19 | 0.490895E+11 | 122407.68 | 15-MAR-08:09 |
April | 0.810996E+11 | 75306.30 | 30-APR-15:09 | 0.810200E+10 | 82938.03 | 01-APR-08:09 |
May | 0.826990E+11 | 74134.04 | 22-MAY-14:00 | 0.393722E+10 | 41316.62 | 17-MAY-08:09 |
June | 0.820297E+11 | 82404.92 | 13-JUN-16:19 | 63801331.09 | 4144.08 | 07-JUN-11:20 |
July | 0.850963E+11 | 83621.50 | 22-JUL-14:00 | 521624.63 | 588.95 | 05-JUL-08:30 |
August | 0.873716E+11 | 77255.73 | 14-AUG-14:00 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.837718E+11 | 73669.54 | 13-SEP-14:00 | 7586333.07 | 1440.20 | 08-SEP-08:00 |
October | 0.854315E+11 | 64869.67 | 30-OCT-17:00 | 0.108912E+11 | 68997.30 | 23-OCT-08:09 |
November | 0.840681E+11 | 66989.50 | 20-NOV-18:19 | 0.427062E+11 | 140026.14 | 29-NOV-09:09 |
December | 0.873992E+11 | 66139.88 | 05-DEC-18:00 | 0.777570E+11 | 162194.08 | 30-DEC-09:09 |
Annual Sum or Average | 0.100988E+13 | 0.319055E+12 | ||||
Minimum of Months | 0.779148E+11 | 64869.67 | 0.00 | 0.00 | ||
Maximum of Months | 0.873992E+11 | 83621.50 | 0.777570E+11 | 176597.73 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.132392E+11 | 0.108804E+11 | 0.00 | 0.184234E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.562345E+10 | 0.00 |
February | 0.353889E+11 | 0.108944E+11 | 0.985143E+10 | 0.00 | 0.166786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510148E+10 | 0.00 |
March | 0.396588E+11 | 0.106025E+11 | 0.110560E+11 | 0.00 | 0.187390E+11 | 0.00 | 0.00 | 103878.88 | 0.00 | 0.00 | 0.00 | 0.567091E+10 | 0.00 |
April | 0.379231E+11 | 0.878598E+10 | 0.105544E+11 | 0.00 | 0.179848E+11 | 0.00 | 0.00 | 0.452740E+09 | 0.00 | 0.00 | 0.00 | 0.539863E+10 | 0.00 |
May | 0.393718E+11 | 0.778505E+10 | 0.109629E+11 | 0.00 | 0.187433E+11 | 0.00 | 0.00 | 0.294797E+09 | 0.00 | 0.00 | 0.00 | 0.554115E+10 | 0.00 |
June | 0.383312E+11 | 0.684435E+10 | 0.106855E+11 | 0.00 | 0.184709E+11 | 0.00 | 0.00 | 0.238539E+10 | 0.00 | 0.00 | 0.00 | 0.531245E+10 | 0.00 |
July | 0.389786E+11 | 0.737726E+10 | 0.108424E+11 | 0.00 | 0.187960E+11 | 0.00 | 0.00 | 0.369422E+10 | 0.00 | 0.00 | 0.00 | 0.540778E+10 | 0.00 |
August | 0.396438E+11 | 0.850331E+10 | 0.110491E+11 | 0.00 | 0.191712E+11 | 0.00 | 0.00 | 0.356203E+10 | 0.00 | 0.00 | 0.00 | 0.544219E+10 | 0.00 |
September | 0.379380E+11 | 0.962009E+10 | 0.105613E+11 | 0.00 | 0.182890E+11 | 0.00 | 0.00 | 0.210948E+10 | 0.00 | 0.00 | 0.00 | 0.525387E+10 | 0.00 |
October | 0.390997E+11 | 0.114551E+11 | 0.108804E+11 | 0.00 | 0.185051E+11 | 0.00 | 0.00 | 3569484.23 | 0.00 | 0.00 | 0.00 | 0.548763E+10 | 0.00 |
November | 0.378782E+11 | 0.124097E+11 | 0.105443E+11 | 0.00 | 0.178609E+11 | 0.00 | 0.00 | 64335.15 | 0.00 | 0.00 | 0.00 | 0.537494E+10 | 0.00 |
December | 0.389936E+11 | 0.135960E+11 | 0.108529E+11 | 0.00 | 0.183605E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.559619E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121113E+12 | 0.128721E+12 | 0.00 | 0.220023E+12 | 0.00 | 0.00 | 0.125024E+11 | 0.00 | 0.00 | 0.00 | 0.652107E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.684435E+10 | 0.985143E+10 | 0.00 | 0.166786E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.510148E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.135960E+11 | 0.110560E+11 | 0.00 | 0.191712E+11 | 0.00 | 0.00 | 0.369422E+10 | 0.00 | 0.00 | 0.00 | 0.567091E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.706285E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.558716E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.490895E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.810200E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.393722E+10 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 63801331.09 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 521624.63 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 7586333.07 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.108912E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.427062E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.777570E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.319055E+12 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.777570E+11 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 12769.98 | 20-JAN-18:19 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 12769.98 | 01-FEB-09:00 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 12769.98 | 01-MAR-13:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 12769.98 | 04-APR-07:40 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 12769.98 | 02-MAY-08:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 12769.98 | 07-JUN-08:30 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 12769.98 | 01-JUL-13:00 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 12769.98 | 01-AUG-10:20 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 12769.98 | 23-SEP-10:39 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 12769.98 | 22-OCT-16:40 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 12769.98 | 08-NOV-16:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 12769.98 | 12-DEC-18:10 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 12769.98 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 12769.98 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 11862.21 | 18-JAN-14:39 | 0.00 |
February | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 | 10612.32 | 02-FEB-15:09 | 0.00 |
March | 84.19 | 19-MAR-19:10 | 0.00 | 0.00 | 0.00 | 10780.46 | 27-MAR-14:20 | 0.00 |
April | 19148.16 | 30-APR-14:00 | 0.00 | 0.00 | 0.00 | 9735.29 | 04-APR-12:50 | 0.00 |
May | 16974.91 | 22-MAY-14:00 | 0.00 | 0.00 | 0.00 | 9799.44 | 25-MAY-12:20 | 0.00 |
June | 25349.00 | 13-JUN-16:00 | 0.00 | 0.00 | 0.00 | 10604.23 | 03-JUN-13:30 | 0.00 |
July | 28591.72 | 22-JUL-14:00 | 0.00 | 0.00 | 0.00 | 9719.75 | 05-JUL-12:20 | 0.00 |
August | 23263.54 | 14-AUG-16:00 | 0.00 | 0.00 | 0.00 | 7717.10 | 07-AUG-13:50 | 0.00 |
September | 19043.45 | 13-SEP-14:20 | 0.00 | 0.00 | 0.00 | 9523.61 | 22-SEP-14:39 | 0.00 |
October | 615.84 | 07-OCT-19:40 | 0.00 | 0.00 | 0.00 | 9719.48 | 12-OCT-13:50 | 0.00 |
November | 59.06 | 08-NOV-21:49 | 0.00 | 0.00 | 0.00 | 9694.17 | 17-NOV-12:30 | 0.00 |
December | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 9730.37 | 22-DEC-14:50 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 7717.10 | 0.00 | ||
Maximum of Months | 28591.72 | 0.00 | 0.00 | 0.00 | 11862.21 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 69113.66 | 04-JAN-18:40 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 66999.38 | 21-FEB-17:49 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 66961.28 | 09-MAR-18:19 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 75306.30 | 30-APR-15:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 18194.15 | 0.00 |
May | 74134.04 | 22-MAY-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 16974.91 | 0.00 |
June | 82404.92 | 13-JUN-16:19 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 25259.94 | 0.00 |
July | 83621.50 | 22-JUL-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 28591.72 | 0.00 |
August | 77255.73 | 14-AUG-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 22222.60 | 0.00 |
September | 73669.54 | 13-SEP-14:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 18931.55 | 0.00 |
October | 64869.67 | 30-OCT-17:00 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 66989.50 | 20-NOV-18:19 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 66139.88 | 05-DEC-18:00 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 64869.67 | 28718.22 | 8089.53 | 0.00 | 0.00 | 12769.98 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 83621.50 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 12769.98 | 0.00 | 0.00 | 28591.72 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 176597.73 | 10-JAN-09:09 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 141236.18 | 13-FEB-09:09 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 122407.68 | 15-MAR-08:09 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 82938.03 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 41316.62 | 17-MAY-08:09 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 4144.08 | 07-JUN-11:20 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 588.95 | 05-JUL-08:30 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 1440.20 | 08-SEP-08:00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 68997.30 | 23-OCT-08:09 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 140026.14 | 29-NOV-09:09 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 162194.08 | 30-DEC-09:09 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 176597.73 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.50 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
February | 0.83 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
March | 1.33 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.67 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 | 0.00 | 20.45 |
December | 0.83 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 | 0.00 | 20.47 |
Annual Sum or Average | 4.17 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 | 0.00 | 20.48 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 1.33 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 | 0.00 | 20.52 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.33 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 | 0.00 | 20.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.01 | 155.83 | 20.95 | 155.83 | 20.92 |
February | 448.00 | 21.00 | 83.83 | 20.93 | 83.83 | 20.88 |
March | 497.00 | 21.03 | 83.50 | 20.96 | 83.50 | 20.91 |
April | 413.00 | 21.80 | 25.50 | 21.80 | 15.17 | 21.76 |
May | 395.83 | 22.04 | 42.83 | 22.20 | 2.33 | 22.19 |
June | 134.00 | 23.01 | 183.67 | 23.52 | 0.00 | 23.52 |
July | 59.67 | 23.38 | 296.17 | 23.82 | 0.00 | 23.82 |
August | 38.83 | 23.70 | 321.50 | 23.87 | 0.00 | 23.87 |
September | 102.00 | 23.23 | 185.50 | 23.65 | 0.00 | 23.65 |
October | 445.33 | 21.70 | 9.17 | 21.67 | 9.17 | 21.65 |
November | 480.00 | 21.06 | 53.67 | 21.02 | 53.67 | 20.98 |
December | 496.00 | 20.99 | 171.83 | 20.93 | 171.83 | 20.90 |
Annual Sum or Average | 4005.67 | 21.46 | 1613.00 | 21.83 | 575.33 | 21.72 |
Minimum of Months | 38.83 | 20.99 | 9.17 | 20.93 | 0.00 | 20.88 |
Maximum of Months | 497.00 | 23.70 | 321.50 | 23.87 | 171.83 | 23.87 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 496.00 | 21.52 | 30.50 | 21.48 | 30.50 | 21.44 |
February | 448.00 | 21.51 | 12.33 | 21.49 | 12.33 | 21.46 |
March | 497.00 | 21.62 | 7.83 | 21.61 | 7.83 | 21.59 |
April | 366.50 | 22.71 | 13.17 | 22.75 | 0.00 | 22.75 |
May | 318.00 | 22.86 | 48.33 | 23.00 | 0.00 | 23.00 |
June | 47.17 | 23.43 | 252.33 | 23.84 | 0.00 | 23.84 |
July | 14.50 | 23.71 | 337.33 | 23.92 | 0.00 | 23.92 |
August | 5.33 | 23.75 | 357.17 | 23.92 | 0.00 | 23.92 |
September | 39.00 | 23.65 | 231.50 | 23.86 | 0.00 | 23.86 |
October | 373.50 | 22.47 | 3.00 | 22.48 | 0.00 | 22.48 |
November | 480.00 | 21.73 | 6.17 | 21.71 | 6.17 | 21.70 |
December | 496.00 | 21.44 | 31.83 | 21.40 | 31.83 | 21.35 |
Annual Sum or Average | 3581.00 | 21.95 | 1331.50 | 22.43 | 88.67 | 22.39 |
Minimum of Months | 5.33 | 21.44 | 3.00 | 21.40 | 0.00 | 21.35 |
Maximum of Months | 497.00 | 23.75 | 357.17 | 23.92 | 31.83 | 23.92 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 59.83 | 21.11 | 59.83 | 21.11 |
February | 336.00 | 21.11 | 27.33 | 21.11 | 27.33 | 21.11 |
March | 379.00 | 21.14 | 23.67 | 21.13 | 23.67 | 21.13 |
April | 290.50 | 22.09 | 11.50 | 22.16 | 0.83 | 22.16 |
May | 273.00 | 22.34 | 46.17 | 22.57 | 0.00 | 22.57 |
June | 56.17 | 23.20 | 199.00 | 23.79 | 0.00 | 23.79 |
July | 18.17 | 23.52 | 260.50 | 23.96 | 0.33 | 23.96 |
August | 10.17 | 23.61 | 286.33 | 23.97 | 0.00 | 23.97 |
September | 41.33 | 23.29 | 181.17 | 23.83 | 0.00 | 23.83 |
October | 299.33 | 21.82 | 0.00 | 21.82 | 0.00 | 21.82 |
November | 360.00 | 21.16 | 14.17 | 21.16 | 14.17 | 21.16 |
December | 369.00 | 21.11 | 62.33 | 21.11 | 62.33 | 21.11 |
Annual Sum or Average | 2803.67 | 21.52 | 1172.00 | 22.10 | 188.50 | 22.06 |
Minimum of Months | 10.17 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.61 | 286.33 | 23.97 | 62.33 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 78.50 | 21.11 | 78.50 | 21.11 |
February | 336.00 | 21.11 | 34.33 | 21.11 | 34.33 | 21.11 |
March | 379.00 | 21.13 | 32.00 | 21.13 | 32.00 | 21.12 |
April | 295.33 | 21.98 | 11.50 | 22.05 | 1.50 | 22.04 |
May | 280.17 | 22.23 | 42.17 | 22.45 | 0.00 | 22.45 |
June | 62.50 | 23.15 | 190.00 | 23.75 | 0.00 | 23.75 |
July | 20.33 | 23.48 | 255.83 | 23.95 | 0.33 | 23.95 |
August | 10.17 | 23.60 | 284.17 | 23.97 | 0.00 | 23.97 |
September | 44.33 | 23.26 | 172.67 | 23.81 | 0.00 | 23.81 |
October | 307.50 | 21.76 | 0.00 | 21.76 | 0.00 | 21.76 |
November | 360.00 | 21.14 | 18.67 | 21.14 | 18.67 | 21.14 |
December | 369.00 | 21.11 | 76.50 | 21.11 | 76.50 | 21.11 |
Annual Sum or Average | 2835.33 | 21.49 | 1196.33 | 22.06 | 241.83 | 22.00 |
Minimum of Months | 10.17 | 21.11 | 0.00 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.60 | 284.17 | 23.97 | 78.50 | 23.97 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 371.00 | 21.11 | 97.00 | 21.11 | 97.00 | 21.11 |
February | 336.00 | 21.11 | 44.83 | 21.11 | 44.83 | 21.11 |
March | 379.00 | 21.12 | 44.50 | 21.12 | 44.50 | 21.12 |
April | 306.00 | 21.87 | 12.33 | 21.92 | 4.00 | 21.91 |
May | 295.67 | 22.10 | 37.67 | 22.30 | 0.00 | 22.30 |
June | 77.83 | 23.06 | 169.83 | 23.67 | 0.00 | 23.67 |
July | 32.00 | 23.41 | 242.67 | 23.91 | 0.33 | 23.92 |
August | 16.67 | 23.59 | 274.83 | 23.96 | 0.00 | 23.96 |
September | 52.33 | 23.20 | 156.17 | 23.75 | 0.00 | 23.75 |
October | 318.17 | 21.70 | 0.17 | 21.70 | 0.17 | 21.70 |
November | 360.00 | 21.13 | 24.83 | 21.13 | 24.83 | 21.13 |
December | 369.00 | 21.11 | 98.00 | 21.11 | 98.00 | 21.11 |
Annual Sum or Average | 2913.67 | 21.49 | 1202.83 | 21.99 | 313.67 | 21.93 |
Minimum of Months | 16.67 | 21.11 | 0.17 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 379.00 | 23.59 | 274.83 | 23.96 | 98.00 | 23.96 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 136.50 | 21.11 | 136.50 | 21.11 |
February | 308.00 | 21.11 | 66.00 | 21.11 | 66.00 | 21.11 |
March | 348.00 | 21.11 | 71.83 | 21.11 | 71.83 | 21.11 |
April | 294.17 | 21.70 | 7.83 | 21.72 | 5.33 | 21.71 |
May | 283.67 | 21.87 | 23.33 | 22.02 | 0.00 | 22.02 |
June | 110.67 | 22.91 | 109.67 | 23.40 | 0.00 | 23.40 |
July | 45.33 | 23.26 | 197.17 | 23.80 | 0.17 | 23.80 |
August | 16.83 | 23.66 | 227.50 | 23.90 | 0.00 | 23.90 |
September | 64.17 | 23.19 | 123.17 | 23.66 | 0.00 | 23.66 |
October | 312.00 | 21.64 | 0.83 | 21.64 | 0.83 | 21.63 |
November | 330.00 | 21.11 | 44.17 | 21.11 | 44.17 | 21.11 |
December | 338.00 | 21.11 | 176.33 | 21.11 | 176.33 | 21.11 |
Annual Sum or Average | 2790.83 | 21.48 | 1184.33 | 21.85 | 501.17 | 21.77 |
Minimum of Months | 16.83 | 21.11 | 0.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.66 | 227.50 | 23.90 | 176.33 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 137.50 | 21.11 | 137.50 | 21.11 |
February | 308.00 | 21.11 | 66.67 | 21.11 | 66.67 | 21.11 |
March | 348.00 | 21.11 | 74.17 | 21.11 | 74.17 | 21.11 |
April | 297.00 | 21.71 | 10.00 | 21.71 | 8.17 | 21.70 |
May | 285.83 | 21.87 | 16.50 | 21.98 | 0.00 | 21.98 |
June | 117.50 | 22.93 | 83.33 | 23.33 | 0.00 | 23.33 |
July | 50.83 | 23.29 | 179.67 | 23.79 | 0.00 | 23.79 |
August | 21.33 | 23.70 | 211.17 | 23.90 | 0.00 | 23.90 |
September | 67.50 | 23.25 | 106.17 | 23.66 | 0.00 | 23.66 |
October | 319.33 | 21.69 | 1.67 | 21.68 | 1.67 | 21.68 |
November | 330.00 | 21.11 | 45.50 | 21.11 | 45.50 | 21.11 |
December | 338.00 | 21.11 | 166.17 | 21.11 | 166.17 | 21.11 |
Annual Sum or Average | 2823.33 | 21.50 | 1098.50 | 21.82 | 499.83 | 21.74 |
Minimum of Months | 21.33 | 21.11 | 1.67 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.70 | 211.17 | 23.90 | 166.17 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 142.83 | 21.11 | 142.83 | 21.11 |
February | 308.00 | 21.11 | 75.00 | 21.11 | 75.00 | 21.11 |
March | 348.00 | 21.11 | 82.50 | 21.11 | 82.50 | 21.11 |
April | 301.67 | 21.69 | 11.67 | 21.69 | 9.83 | 21.67 |
May | 288.33 | 21.82 | 14.17 | 21.91 | 0.00 | 21.91 |
June | 131.00 | 22.87 | 74.00 | 23.25 | 0.00 | 23.25 |
July | 56.00 | 23.23 | 173.50 | 23.76 | 0.00 | 23.76 |
August | 24.00 | 23.69 | 207.00 | 23.90 | 0.00 | 23.90 |
September | 77.33 | 23.23 | 99.00 | 23.62 | 0.00 | 23.62 |
October | 326.83 | 21.69 | 2.83 | 21.68 | 2.83 | 21.68 |
November | 330.00 | 21.11 | 52.00 | 21.11 | 52.00 | 21.11 |
December | 338.00 | 21.11 | 179.67 | 21.11 | 179.67 | 21.11 |
Annual Sum or Average | 2869.17 | 21.51 | 1114.17 | 21.80 | 544.67 | 21.72 |
Minimum of Months | 24.00 | 21.11 | 2.83 | 21.11 | 0.00 | 21.11 |
Maximum of Months | 348.00 | 23.69 | 207.00 | 23.90 | 179.67 | 23.90 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.11 | 166.83 | 21.10 | 166.83 | 21.10 |
February | 308.00 | 21.11 | 101.33 | 21.11 | 101.33 | 21.11 |
March | 348.00 | 21.11 | 109.17 | 21.11 | 109.17 | 21.11 |
April | 308.00 | 21.62 | 17.67 | 21.62 | 16.00 | 21.59 |
May | 295.83 | 21.72 | 9.00 | 21.77 | 0.83 | 21.77 |
June | 162.50 | 22.74 | 56.67 | 23.05 | 0.00 | 23.05 |
July | 72.17 | 23.12 | 155.33 | 23.67 | 0.00 | 23.67 |
August | 33.50 | 23.62 | 193.67 | 23.88 | 0.00 | 23.88 |
September | 106.17 | 23.15 | 81.83 | 23.49 | 0.00 | 23.49 |
October | 338.67 | 21.64 | 8.00 | 21.63 | 8.00 | 21.62 |
November | 330.00 | 21.11 | 70.33 | 21.11 | 70.33 | 21.11 |
December | 338.00 | 21.11 | 221.00 | 21.11 | 221.00 | 21.11 |
Annual Sum or Average | 2980.83 | 21.52 | 1190.83 | 21.74 | 693.50 | 21.65 |
Minimum of Months | 33.50 | 21.11 | 8.00 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 348.00 | 23.62 | 221.00 | 23.88 | 221.00 | 23.88 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 340.00 | 21.10 | 247.00 | 21.10 | 247.00 | 21.10 |
February | 308.00 | 21.10 | 221.17 | 21.10 | 221.17 | 21.10 |
March | 348.00 | 21.11 | 244.33 | 21.10 | 244.33 | 21.10 |
April | 310.00 | 21.53 | 39.33 | 21.50 | 38.50 | 21.46 |
May | 309.33 | 21.62 | 18.17 | 21.63 | 13.33 | 21.61 |
June | 219.50 | 22.53 | 38.67 | 22.74 | 0.00 | 22.74 |
July | 106.00 | 22.97 | 129.83 | 23.50 | 0.00 | 23.50 |
August | 57.50 | 23.36 | 163.33 | 23.78 | 0.00 | 23.78 |
September | 162.50 | 22.94 | 57.83 | 23.20 | 0.00 | 23.20 |
October | 340.00 | 21.49 | 31.17 | 21.46 | 31.17 | 21.43 |
November | 330.00 | 21.11 | 156.50 | 21.11 | 156.50 | 21.10 |
December | 338.00 | 21.10 | 318.00 | 21.10 | 318.00 | 21.10 |
Annual Sum or Average | 3168.83 | 21.54 | 1665.33 | 21.62 | 1270.00 | 21.51 |
Minimum of Months | 57.50 | 21.10 | 18.17 | 21.10 | 0.00 | 21.10 |
Maximum of Months | 348.00 | 23.36 | 318.00 | 23.78 | 318.00 | 23.78 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.00726 | 32.53055 | -0.4991 | 10.60780 |
February | 448.00000 | 21.00275 | 33.52747 | -0.4811 | 10.15144 |
March | 497.00000 | 21.02633 | 33.58892 | -0.4660 | 9.82218 |
April | 479.00000 | 22.08262 | 32.80633 | -0.1288 | 7.02541 |
May | 496.00000 | 22.40577 | 38.41427 | -1.0475 | 30.62406 |
June | 481.00000 | 23.61867 | 44.35010 | -0.5665 | 12.66756 |
July | 495.00000 | 23.82769 | 45.38340 | -0.4593 | 9.86082 |
August | 497.00000 | 23.88042 | 45.64665 | -0.4410 | 9.32439 |
September | 479.00000 | 23.73037 | 43.11979 | -0.5375 | 11.73181 |
October | 496.00000 | 21.91659 | 41.72321 | -0.1366 | 6.73673 |
November | 480.00000 | 21.06416 | 37.71175 | -0.4186 | 8.91788 |
December | 496.00000 | 20.99034 | 31.65356 | -0.5327 | 11.24405 |
Annual Sum or Average | 5840.00000 | 22.21800 | 38.39920 | -0.4769 | 11.58778 |
Minimum of Months | 448.00000 | 20.99034 | 31.65356 | -1.0475 | 6.73673 |
Maximum of Months | 497.00000 | 23.88042 | 45.64665 | -0.1288 | 30.62406 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 21.52293 | 35.21154 | -0.3268 | 7.84637 |
February | 448.00000 | 21.51431 | 35.95184 | -0.3138 | 7.48280 |
March | 497.00000 | 21.62236 | 35.74112 | -0.2859 | 7.31159 |
April | 479.00000 | 22.98509 | 32.89451 | 0.08270 | 6.26979 |
May | 496.00000 | 23.22455 | 37.63715 | -0.7842 | 19.48573 |
June | 481.00000 | 23.85376 | 43.56769 | -0.4769 | 10.07895 |
July | 495.00000 | 23.90588 | 44.94866 | -0.4212 | 8.90743 |
August | 497.00000 | 23.91122 | 45.31260 | -0.4140 | 8.73337 |
September | 479.00000 | 23.87770 | 42.55858 | -0.4702 | 9.88381 |
October | 496.00000 | 22.81480 | 41.50077 | 0.07693 | 6.24785 |
November | 480.00000 | 21.72686 | 39.47651 | -0.2333 | 6.80605 |
December | 496.00000 | 21.44412 | 34.08015 | -0.3693 | 8.26795 |
Annual Sum or Average | 5840.00000 | 22.70531 | 39.09377 | -0.3287 | 8.96316 |
Minimum of Months | 448.00000 | 21.44412 | 32.89451 | -0.7842 | 6.24785 |
Maximum of Months | 497.00000 | 23.91122 | 45.31260 | 0.08270 | 19.48573 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11307 | 31.98746 | -0.4379 | 9.18907 |
February | 336.00000 | 21.11176 | 33.20033 | -0.4160 | 8.71364 |
March | 379.00000 | 21.13622 | 32.54164 | -0.4066 | 8.57279 |
April | 360.00000 | 22.44537 | 31.19484 | -0.0325 | 6.63104 |
May | 375.00000 | 22.76029 | 37.05158 | -0.9108 | 24.73669 |
June | 366.00000 | 23.80223 | 43.30764 | -0.4895 | 10.55949 |
July | 369.00000 | 23.92883 | 44.77634 | -0.4102 | 8.85772 |
August | 379.00000 | 23.95346 | 45.19804 | -0.3958 | 8.50170 |
September | 360.00000 | 23.84797 | 42.40388 | -0.4737 | 10.14448 |
October | 371.00000 | 22.21153 | 40.49889 | -0.0499 | 6.45218 |
November | 360.00000 | 21.15899 | 37.06758 | -0.3665 | 7.96651 |
December | 369.00000 | 21.10947 | 30.97440 | -0.4670 | 9.65827 |
Annual Sum or Average | 4395.00000 | 22.39014 | 37.55356 | -0.4058 | 10.03014 |
Minimum of Months | 336.00000 | 21.10947 | 30.97440 | -0.9108 | 6.45218 |
Maximum of Months | 379.00000 | 23.95346 | 45.19804 | -0.0325 | 24.73669 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.11059 | 32.01629 | -0.4515 | 9.44504 |
February | 336.00000 | 21.10971 | 33.22565 | -0.4280 | 8.92957 |
March | 379.00000 | 21.12725 | 32.58014 | -0.4196 | 8.79530 |
April | 360.00000 | 22.33357 | 31.39653 | -0.0651 | 6.73586 |
May | 375.00000 | 22.64602 | 37.29842 | -0.9549 | 26.61116 |
June | 366.00000 | 23.77936 | 43.38095 | -0.5019 | 10.88793 |
July | 369.00000 | 23.92073 | 44.81062 | -0.4162 | 8.98953 |
August | 379.00000 | 23.95129 | 45.21948 | -0.3990 | 8.55596 |
September | 360.00000 | 23.83743 | 42.44852 | -0.4817 | 10.33209 |
October | 371.00000 | 22.12432 | 40.72558 | -0.0775 | 6.54773 |
November | 360.00000 | 21.14347 | 37.12004 | -0.3818 | 8.19808 |
December | 369.00000 | 21.10920 | 30.99728 | -0.4796 | 9.91308 |
Annual Sum or Average | 4395.00000 | 22.35780 | 37.63868 | -0.4225 | 10.36286 |
Minimum of Months | 336.00000 | 21.10920 | 30.99728 | -0.9549 | 6.54773 |
Maximum of Months | 379.00000 | 23.95129 | 45.21948 | -0.0651 | 26.61116 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 21.10932 | 31.99377 | -0.4677 | 9.76703 |
February | 336.00000 | 21.10926 | 33.20405 | -0.4432 | 9.21482 |
March | 379.00000 | 21.12029 | 32.56977 | -0.4358 | 9.08797 |
April | 360.00000 | 22.17940 | 31.68100 | -0.1085 | 6.87385 |
May | 375.00000 | 22.47792 | 37.66591 | -1.0179 | 29.31529 |
June | 366.00000 | 23.71367 | 43.59333 | -0.5327 | 11.72966 |
July | 369.00000 | 23.89578 | 44.91754 | -0.4328 | 9.35253 |
August | 379.00000 | 23.94169 | 45.28701 | -0.4104 | 8.76134 |
September | 360.00000 | 23.80632 | 42.57393 | -0.5006 | 10.80567 |
October | 371.00000 | 22.00687 | 41.03015 | -0.1132 | 6.66746 |
November | 360.00000 | 21.12892 | 37.13797 | -0.3991 | 8.47437 |
December | 369.00000 | 21.10885 | 30.97435 | -0.4963 | 10.26323 |
Annual Sum or Average | 4395.00000 | 22.30801 | 37.75690 | -0.4477 | 10.89833 |
Minimum of Months | 336.00000 | 21.10885 | 30.97435 | -1.0179 | 6.66746 |
Maximum of Months | 379.00000 | 23.94169 | 45.28701 | -0.1085 | 29.31529 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10767 | 33.58183 | -0.5077 | 10.58551 |
February | 308.00000 | 21.10826 | 34.71532 | -0.4810 | 9.93668 |
March | 348.00000 | 21.11197 | 34.08578 | -0.4741 | 9.80698 |
April | 330.00000 | 21.94812 | 33.57398 | -0.1719 | 7.13594 |
May | 344.00000 | 22.21891 | 39.69269 | -1.1145 | 33.57388 |
June | 336.00000 | 23.52896 | 45.48724 | -0.6034 | 13.71277 |
July | 338.00000 | 23.81459 | 46.24541 | -0.4705 | 10.14100 |
August | 348.00000 | 23.89543 | 46.29703 | -0.4387 | 9.22258 |
September | 330.00000 | 23.74319 | 44.04766 | -0.5356 | 11.58111 |
October | 340.00000 | 21.81412 | 43.07218 | -0.1741 | 6.91538 |
November | 330.00000 | 21.11312 | 38.72280 | -0.4383 | 9.14282 |
December | 338.00000 | 21.10741 | 32.50870 | -0.5401 | 11.20642 |
Annual Sum or Average | 4030.00000 | 22.21724 | 39.37431 | -0.4971 | 11.96009 |
Minimum of Months | 308.00000 | 21.10741 | 32.50870 | -1.1145 | 6.91538 |
Maximum of Months | 348.00000 | 23.89543 | 46.29703 | -0.1719 | 33.57388 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10772 | 33.51178 | -0.5083 | 10.59589 |
February | 308.00000 | 21.10767 | 34.64646 | -0.4833 | 9.98560 |
March | 348.00000 | 21.11156 | 34.01368 | -0.4775 | 9.87639 |
April | 330.00000 | 21.93454 | 33.50201 | -0.1878 | 7.21586 |
May | 344.00000 | 22.20541 | 39.62378 | -1.1383 | 34.61220 |
June | 336.00000 | 23.52297 | 45.42043 | -0.6258 | 14.31977 |
July | 338.00000 | 23.81329 | 46.18403 | -0.4913 | 10.56086 |
August | 348.00000 | 23.89742 | 46.23500 | -0.4571 | 9.55705 |
September | 330.00000 | 23.75282 | 43.94006 | -0.5507 | 11.89845 |
October | 340.00000 | 21.81492 | 42.97166 | -0.1835 | 6.95647 |
November | 330.00000 | 21.11291 | 38.64776 | -0.4416 | 9.20207 |
December | 338.00000 | 21.10740 | 32.43853 | -0.5389 | 11.18085 |
Annual Sum or Average | 4030.00000 | 22.21530 | 39.29974 | -0.5084 | 12.21274 |
Minimum of Months | 308.00000 | 21.10740 | 32.43853 | -1.1383 | 6.95647 |
Maximum of Months | 348.00000 | 23.89742 | 46.23500 | -0.1835 | 34.61220 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10692 | 33.51279 | -0.5139 | 10.71458 |
February | 308.00000 | 21.10771 | 34.64565 | -0.4891 | 10.10726 |
March | 348.00000 | 21.11093 | 34.01426 | -0.4833 | 9.99425 |
April | 330.00000 | 21.88431 | 33.60136 | -0.2042 | 7.31849 |
May | 344.00000 | 22.14851 | 39.75820 | -1.1634 | 35.75858 |
June | 336.00000 | 23.46755 | 45.60086 | -0.6501 | 15.10833 |
July | 338.00000 | 23.79303 | 46.27106 | -0.5038 | 10.89685 |
August | 348.00000 | 23.89444 | 46.27433 | -0.4634 | 9.68566 |
September | 330.00000 | 23.72808 | 44.04093 | -0.5645 | 12.28240 |
October | 340.00000 | 21.76701 | 43.08983 | -0.1996 | 7.01112 |
November | 330.00000 | 21.11204 | 38.64907 | -0.4475 | 9.31335 |
December | 338.00000 | 21.10718 | 32.43847 | -0.5434 | 11.28466 |
Annual Sum or Average | 4030.00000 | 22.19347 | 39.36349 | -0.5203 | 12.50739 |
Minimum of Months | 308.00000 | 21.10692 | 32.43847 | -1.1634 | 7.01112 |
Maximum of Months | 348.00000 | 23.89444 | 46.27433 | -0.1996 | 35.75858 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10593 | 33.51125 | -0.5319 | 11.11820 |
February | 308.00000 | 21.10718 | 34.64373 | -0.5084 | 10.52004 |
March | 348.00000 | 21.10893 | 34.01525 | -0.5024 | 10.39517 |
April | 330.00000 | 21.78020 | 33.80819 | -0.2398 | 7.61468 |
May | 344.00000 | 22.01914 | 40.06691 | -1.2207 | 38.42820 |
June | 336.00000 | 23.31114 | 46.08510 | -0.7124 | 17.21974 |
July | 338.00000 | 23.73262 | 46.51821 | -0.5353 | 11.80714 |
August | 348.00000 | 23.88000 | 46.40155 | -0.4803 | 10.06259 |
September | 330.00000 | 23.63755 | 44.36038 | -0.6061 | 13.52741 |
October | 340.00000 | 21.65056 | 43.36209 | -0.2396 | 7.21469 |
November | 330.00000 | 21.10928 | 38.65337 | -0.4658 | 9.67086 |
December | 338.00000 | 21.10649 | 32.43724 | -0.5599 | 11.67555 |
Annual Sum or Average | 4030.00000 | 22.13673 | 39.52805 | -0.5517 | 13.32586 |
Minimum of Months | 308.00000 | 21.10593 | 32.43724 | -1.2207 | 7.21469 |
Maximum of Months | 348.00000 | 23.88000 | 46.51821 | -0.2396 | 38.42820 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 21.10494 | 33.43970 | -0.6013 | 12.82088 |
February | 308.00000 | 21.10472 | 34.50792 | -0.5799 | 12.19158 |
March | 348.00000 | 21.10531 | 33.91546 | -0.5708 | 11.97616 |
April | 330.00000 | 21.68253 | 33.86387 | -0.2993 | 8.37154 |
May | 344.00000 | 21.84730 | 40.28625 | -1.3268 | 43.57692 |
June | 336.00000 | 23.00097 | 46.77149 | -0.8389 | 22.00733 |
July | 338.00000 | 23.61175 | 46.80224 | -0.5989 | 13.81014 |
August | 348.00000 | 23.81532 | 46.56984 | -0.5264 | 11.29427 |
September | 330.00000 | 23.42347 | 44.77145 | -0.7021 | 16.80221 |
October | 340.00000 | 21.49221 | 43.51354 | -0.3238 | 8.07455 |
November | 330.00000 | 21.10656 | 38.46389 | -0.5303 | 11.05900 |
December | 338.00000 | 21.10457 | 32.23831 | -0.6282 | 13.41992 |
Annual Sum or Average | 4030.00000 | 22.04062 | 39.63612 | -0.6287 | 15.50944 |
Minimum of Months | 308.00000 | 21.10457 | 32.23831 | -1.3268 | 8.07455 |
Maximum of Months | 348.00000 | 23.81532 | 46.80224 | -0.2993 | 43.57692 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.422897E+09 | 0.112165E+09 | 21.48 | 0.421530E+09 | 1366336.63 | 0.00 | 0.51 | 30-APR-16:03 | 0.00 | 01-APR-00:05 | 13199.98 | 30-APR-16:07 | 13199.98 | 30-APR-16:07 | 230.92 | 28-APR-15:00 | 3430.45 | 30-APR-16:10 | 0.00 | 01-APR-00:05 |
May | 0.234479E+09 | 63242755.46 | 21.26 | 0.207212E+09 | 27267041.23 | 0.00 | 0.43 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 11384.04 | 22-MAY-15:00 | 10523.61 | 22-MAY-15:00 | 955.38 | 22-MAY-14:00 | 3001.84 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.175941E+10 | 0.459563E+09 | 67.92 | 0.148578E+10 | 0.273625E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 31292.50 | 13-JUN-08:62 | 26175.76 | 13-JUN-08:62 | 13854.82 | 27-JUN-08:62 | 6658.81 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.282478E+10 | 0.752827E+09 | 132.14 | 0.247270E+10 | 0.352082E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 31458.37 | 18-JUL-08:62 | 29011.18 | 22-JUL-08:62 | 12436.06 | 25-JUL-08:62 | 6944.90 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.242871E+10 | 0.645840E+09 | 166.73 | 0.206285E+10 | 0.365857E+09 | 0.00 | 1.00 | 15-AUG-08:62 | 0.00 | 01-AUG-00:10 | 31540.75 | 17-AUG-08:62 | 24671.34 | 15-AUG-08:62 | 12867.32 | 17-AUG-08:62 | 6705.85 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.147726E+10 | 0.390393E+09 | 86.17 | 0.126912E+10 | 0.208141E+09 | 0.00 | 0.59 | 13-SEP-08:62 | 0.00 | 01-SEP-00:10 | 16066.18 | 13-SEP-08:62 | 11909.78 | 14-SEP-08:62 | 5339.77 | 16-SEP-08:62 | 3887.56 | 13-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 6.46 | 1.83 | 0.17 | 6.46 | 0.00 | 0.00 | 0.00 | 07-OCT-12:10 | 0.00 | 01-OCT-00:10 | 0.01 | 07-OCT-12:10 | 0.01 | 07-OCT-12:10 | 0.00 | 01-OCT-00:10 | 0.00 | 07-OCT-12:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.914753E+10 | 0.242403E+10 | 495.87 | 0.791919E+10 | 0.122834E+10 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.282478E+10 | 0.752827E+09 | 166.73 | 0.247270E+10 | 0.365857E+09 | 0.00 | 1.00 | 0.00 | 31540.75 | 29011.18 | 13854.82 | 6944.90 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 378732.36 | 103878.88 | 0.67 | 292084.76 | 86647.60 | 0.00 | 0.02 | 19-MAR-19:10 | 0.00 | 01-MAR-00:10 | 307.64 | 19-MAR-19:10 | 227.70 | 19-MAR-19:10 | 79.94 | 19-MAR-19:10 | 84.19 | 19-MAR-19:10 | 0.00 | 01-MAR-00:10 |
April | 0.292978E+09 | 74261247.05 | 29.60 | 0.291354E+09 | 1624536.01 | 0.00 | 1.00 | 29-APR-18:01 | 0.00 | 01-APR-00:05 | 16482.99 | 30-APR-19:07 | 16482.99 | 30-APR-19:07 | 939.82 | 30-APR-19:40 | 3503.10 | 30-APR-19:07 | 0.00 | 01-APR-00:05 |
May | 0.209179E+09 | 52748962.38 | 29.33 | 0.186708E+09 | 22471502.39 | 0.00 | 1.00 | 21-MAY-17:01 | 0.00 | 01-MAY-00:10 | 16470.24 | 21-MAY-19:00 | 16271.95 | 21-MAY-17:01 | 3431.84 | 23-MAY-08:62 | 3401.69 | 21-MAY-19:00 | 0.00 | 01-MAY-00:10 |
June | 0.110677E+10 | 0.276991E+09 | 80.32 | 0.937307E+09 | 0.169460E+09 | 0.00 | 1.00 | 12-JUN-08:62 | 0.00 | 01-JUN-00:10 | 18131.02 | 25-JUN-17:57 | 14897.28 | 25-JUN-17:02 | 7496.84 | 27-JUN-08:62 | 3731.72 | 25-JUN-17:57 | 0.00 | 01-JUN-00:10 |
July | 0.176893E+10 | 0.447755E+09 | 151.58 | 0.153275E+10 | 0.236175E+09 | 0.00 | 1.00 | 09-JUL-17:02 | 0.00 | 01-JUL-00:10 | 17458.53 | 23-JUL-17:02 | 16025.69 | 22-JUL-08:62 | 6750.22 | 25-JUL-08:62 | 3704.97 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.174231E+10 | 0.439051E+09 | 198.18 | 0.146465E+10 | 0.277662E+09 | 0.00 | 1.00 | 01-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17334.83 | 17-AUG-08:62 | 16229.38 | 14-AUG-20:08 | 6953.05 | 17-AUG-08:62 | 3578.68 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.100860E+10 | 0.254998E+09 | 111.47 | 0.859565E+09 | 0.149039E+09 | 0.00 | 1.00 | 10-SEP-17:02 | 0.00 | 01-SEP-00:10 | 17344.31 | 10-SEP-17:02 | 14299.25 | 24-SEP-17:08 | 6170.07 | 16-SEP-08:62 | 3580.37 | 10-SEP-17:02 | 0.00 | 01-SEP-00:10 |
October | 11596578.06 | 3094586.38 | 5.69 | 10714322.20 | 882255.86 | 0.00 | 0.24 | 05-OCT-20:10 | 0.00 | 01-OCT-00:10 | 3110.66 | 05-OCT-20:10 | 3110.66 | 05-OCT-20:10 | 460.80 | 08-OCT-21:10 | 801.02 | 05-OCT-20:10 | 0.00 | 01-OCT-00:10 |
November | 234334.07 | 64335.15 | 0.50 | 195565.76 | 38768.31 | 0.00 | 0.02 | 08-NOV-21:50 | 0.00 | 01-NOV-00:10 | 215.23 | 08-NOV-21:50 | 169.80 | 08-NOV-21:50 | 45.43 | 08-NOV-21:50 | 59.06 | 08-NOV-21:50 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.614097E+10 | 0.154907E+10 | 607.34 | 0.528353E+10 | 0.857440E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.176893E+10 | 0.447755E+09 | 198.18 | 0.153275E+10 | 0.277662E+09 | 0.00 | 1.00 | 0.00 | 18131.02 | 16482.99 | 7496.84 | 3731.72 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.152007E+09 | 39331701.51 | 18.88 | 0.150931E+09 | 1075635.90 | 0.00 | 0.81 | 30-APR-08:62 | 0.00 | 01-APR-00:05 | 12320.27 | 30-APR-08:62 | 11178.29 | 30-APR-08:62 | 1141.98 | 30-APR-08:62 | 2702.82 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.120754E+09 | 31610582.93 | 21.78 | 0.106214E+09 | 14540252.75 | 0.00 | 0.43 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 6085.62 | 22-MAY-15:00 | 5645.10 | 22-MAY-15:00 | 508.44 | 22-MAY-14:00 | 1562.05 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.865095E+09 | 0.220164E+09 | 71.57 | 0.739146E+09 | 0.125948E+09 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17150.25 | 27-JUN-07:02 | 14359.27 | 26-JUN-07:02 | 7604.76 | 27-JUN-07:02 | 3542.89 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.130880E+10 | 0.338160E+09 | 126.98 | 0.114521E+10 | 0.163598E+09 | 0.00 | 1.00 | 07-JUL-07:03 | 0.00 | 01-JUL-00:10 | 17149.38 | 18-JUL-07:02 | 15417.12 | 22-JUL-07:02 | 6705.46 | 25-JUL-07:02 | 3641.69 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.134084E+10 | 0.345072E+09 | 177.74 | 0.113006E+10 | 0.210778E+09 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17039.89 | 17-AUG-07:02 | 14195.01 | 15-AUG-07:02 | 6997.55 | 17-AUG-07:02 | 3522.19 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.808685E+09 | 0.207428E+09 | 97.18 | 0.698044E+09 | 0.110641E+09 | 0.00 | 1.00 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 | 16827.84 | 16-SEP-07:03 | 10490.10 | 02-SEP-07:03 | 6746.05 | 16-SEP-07:03 | 3480.27 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 773199.76 | 210833.71 | 2.25 | 770786.73 | 2413.03 | 0.00 | 0.04 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 488.80 | 07-OCT-15:00 | 488.80 | 07-OCT-15:00 | 2.71 | 11-OCT-18:00 | 132.65 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.459695E+10 | 0.118198E+10 | 516.37 | 0.397037E+10 | 0.626583E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.134084E+10 | 0.345072E+09 | 177.74 | 0.114521E+10 | 0.210778E+09 | 0.00 | 1.00 | 0.00 | 17150.25 | 15417.12 | 7604.76 | 3641.69 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.145555E+09 | 37719983.91 | 16.37 | 0.144576E+09 | 979435.51 | 0.00 | 0.75 | 30-APR-08:62 | 0.00 | 01-APR-00:05 | 11320.95 | 30-APR-08:62 | 10264.36 | 30-APR-08:62 | 1056.58 | 30-APR-08:62 | 2526.38 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 0.106808E+09 | 28020855.84 | 19.32 | 94448279.20 | 12359341.86 | 0.00 | 0.41 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5853.69 | 22-MAY-15:00 | 5427.13 | 22-MAY-15:00 | 485.04 | 22-MAY-14:00 | 1509.14 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.844900E+09 | 0.215305E+09 | 66.34 | 0.722060E+09 | 0.122840E+09 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17205.13 | 27-JUN-07:02 | 14401.13 | 26-JUN-07:02 | 7634.70 | 27-JUN-07:02 | 3554.24 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.128599E+10 | 0.332496E+09 | 122.51 | 0.112617E+10 | 0.159822E+09 | 0.00 | 1.00 | 10-JUL-07:02 | 0.00 | 01-JUL-00:10 | 17203.44 | 18-JUL-07:02 | 15464.72 | 22-JUL-07:02 | 6726.73 | 25-JUL-07:02 | 3653.39 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.130596E+10 | 0.336386E+09 | 173.68 | 0.110180E+10 | 0.204159E+09 | 0.00 | 1.00 | 06-AUG-08:62 | 0.00 | 01-AUG-00:10 | 17094.15 | 17-AUG-07:02 | 14233.00 | 15-AUG-07:02 | 7023.84 | 17-AUG-07:02 | 3533.41 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.782311E+09 | 0.200946E+09 | 93.14 | 0.676024E+09 | 0.106287E+09 | 0.00 | 0.96 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 | 15931.22 | 16-SEP-07:03 | 9880.49 | 02-SEP-07:03 | 6395.01 | 16-SEP-07:03 | 3341.82 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 329593.75 | 89831.17 | 1.00 | 329593.37 | 0.38 | 0.00 | 0.03 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 357.88 | 07-OCT-15:00 | 357.88 | 07-OCT-15:00 | 0.00 | 11-OCT-10:20 | 97.39 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.447185E+10 | 0.115096E+10 | 492.36 | 0.386540E+10 | 0.606447E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.130596E+10 | 0.336386E+09 | 173.68 | 0.112617E+10 | 0.204159E+09 | 0.00 | 1.00 | 0.00 | 17205.13 | 15464.72 | 7634.70 | 3653.39 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.132413E+09 | 34418084.63 | 16.12 | 0.131627E+09 | 786191.84 | 0.00 | 0.59 | 30-APR-08:62 | 0.00 | 01-APR-00:05 | 8370.77 | 30-APR-08:62 | 7573.17 | 30-APR-08:62 | 797.59 | 30-APR-08:62 | 1961.90 | 30-APR-08:62 | 0.00 | 01-APR-00:05 |
May | 88683679.74 | 23326526.57 | 16.03 | 79080037.14 | 9603642.60 | 0.00 | 0.39 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5498.98 | 22-MAY-15:00 | 5094.51 | 22-MAY-15:00 | 449.84 | 22-MAY-14:00 | 1425.44 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.796607E+09 | 0.203528E+09 | 66.77 | 0.681106E+09 | 0.115501E+09 | 0.00 | 1.00 | 13-JUN-07:02 | 0.00 | 01-JUN-00:10 | 17065.53 | 27-JUN-07:02 | 14258.61 | 26-JUN-07:02 | 7601.79 | 27-JUN-07:02 | 3525.50 | 27-JUN-07:02 | 0.00 | 01-JUN-00:10 |
July | 0.120893E+10 | 0.313350E+09 | 117.08 | 0.106218E+10 | 0.146749E+09 | 0.00 | 1.00 | 10-JUL-07:02 | 0.00 | 01-JUL-00:10 | 17063.18 | 18-JUL-07:02 | 15311.36 | 22-JUL-07:02 | 6694.76 | 25-JUL-07:02 | 3623.86 | 22-JUL-07:02 | 0.00 | 01-JUL-00:10 |
August | 0.120520E+10 | 0.311230E+09 | 160.36 | 0.102011E+10 | 0.185084E+09 | 0.00 | 1.00 | 15-AUG-07:02 | 0.00 | 01-AUG-00:10 | 16954.76 | 17-AUG-07:02 | 14098.51 | 15-AUG-07:02 | 6995.17 | 17-AUG-07:02 | 3504.68 | 17-AUG-07:02 | 0.00 | 01-AUG-00:10 |
September | 0.722480E+09 | 0.186117E+09 | 87.74 | 0.625969E+09 | 96510293.98 | 0.00 | 0.80 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 | 12647.19 | 16-SEP-07:03 | 7900.58 | 02-SEP-07:03 | 5098.37 | 16-SEP-07:03 | 2786.04 | 16-SEP-07:03 | 0.00 | 01-SEP-00:10 |
October | 145714.38 | 39939.46 | 1.08 | 145284.79 | 429.60 | 0.00 | 0.01 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 128.39 | 07-OCT-15:00 | 128.39 | 07-OCT-15:00 | 0.68 | 01-OCT-12:50 | 35.10 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.415445E+10 | 0.107201E+10 | 465.18 | 0.360022E+10 | 0.554234E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.120893E+10 | 0.313350E+09 | 160.36 | 0.106218E+10 | 0.185084E+09 | 0.00 | 1.00 | 0.00 | 17065.53 | 15311.36 | 7601.79 | 3623.86 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.212852E+09 | 57017196.32 | 13.14 | 0.211532E+09 | 1320611.30 | 0.00 | 0.56 | 30-APR-09:03 | 0.00 | 01-APR-00:05 | 14047.38 | 30-APR-09:03 | 13552.71 | 30-APR-09:03 | 494.68 | 30-APR-09:03 | 3414.79 | 30-APR-09:03 | 0.00 | 01-APR-00:05 |
May | 0.132942E+09 | 35999666.08 | 11.26 | 0.118979E+09 | 13962930.96 | 0.00 | 0.40 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 10058.41 | 22-MAY-15:00 | 9144.29 | 22-MAY-15:00 | 914.12 | 22-MAY-15:00 | 2676.35 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.134847E+10 | 0.355197E+09 | 58.63 | 0.114428E+10 | 0.204187E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 30496.94 | 13-JUN-08:62 | 24549.16 | 13-JUN-08:62 | 13500.92 | 27-JUN-08:62 | 6485.28 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.201056E+10 | 0.536129E+09 | 105.23 | 0.176026E+10 | 0.250298E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 30484.05 | 18-JUL-08:62 | 27912.98 | 22-JUL-08:62 | 11977.15 | 25-JUL-08:62 | 6735.09 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.203560E+10 | 0.541147E+09 | 136.07 | 0.171968E+10 | 0.315916E+09 | 0.00 | 1.00 | 06-AUG-09:02 | 0.00 | 01-AUG-00:10 | 30536.24 | 17-AUG-08:62 | 24529.08 | 15-AUG-08:62 | 12374.11 | 17-AUG-08:62 | 6492.59 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.119534E+10 | 0.317323E+09 | 72.81 | 0.103373E+10 | 0.161613E+09 | 0.00 | 0.66 | 13-SEP-08:62 | 0.00 | 01-SEP-00:10 | 17735.99 | 13-SEP-08:62 | 13344.99 | 14-SEP-08:62 | 5895.37 | 13-SEP-08:62 | 4205.58 | 13-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 390455.89 | 110136.22 | 1.00 | 390455.89 | -0.0 | 0.00 | 0.01 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 295.91 | 07-OCT-15:00 | 295.91 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 83.24 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.693615E+10 | 0.184292E+10 | 398.14 | 0.598885E+10 | 0.947297E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.203560E+10 | 0.541147E+09 | 136.07 | 0.176026E+10 | 0.315916E+09 | 0.00 | 1.00 | 0.00 | 30536.24 | 27912.98 | 13500.92 | 6735.09 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.105562E+09 | 27528706.75 | 12.64 | 0.105008E+09 | 553178.59 | 0.00 | 0.46 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 6074.99 | 30-APR-15:00 | 6074.99 | 30-APR-15:00 | 197.76 | 30-APR-09:03 | 1554.46 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 63849619.33 | 16809620.53 | 9.83 | 57530449.79 | 6319169.53 | 0.00 | 0.39 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5199.96 | 22-MAY-15:00 | 4735.26 | 22-MAY-15:00 | 464.71 | 22-MAY-15:00 | 1347.33 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.683312E+09 | 0.175305E+09 | 54.07 | 0.581306E+09 | 0.102007E+09 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 16202.09 | 13-JUN-08:62 | 13037.61 | 13-JUN-08:62 | 7166.74 | 27-JUN-08:62 | 3346.13 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.100706E+10 | 0.261529E+09 | 97.86 | 0.886263E+09 | 0.120801E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16195.37 | 18-JUL-08:62 | 14828.68 | 22-JUL-08:62 | 6356.37 | 25-JUL-08:62 | 3475.06 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.100731E+10 | 0.260697E+09 | 128.04 | 0.855264E+09 | 0.152045E+09 | 0.00 | 1.00 | 15-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16223.20 | 17-AUG-08:62 | 13035.70 | 15-AUG-08:62 | 6568.59 | 17-AUG-08:62 | 3349.94 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.598261E+09 | 0.154617E+09 | 66.17 | 0.519392E+09 | 78868746.46 | 0.00 | 0.52 | 13-SEP-08:62 | 0.00 | 01-SEP-00:10 | 7143.05 | 13-SEP-08:62 | 5549.60 | 14-SEP-08:62 | 2370.13 | 13-SEP-08:62 | 1713.27 | 13-SEP-08:62 | 0.00 | 01-SEP-00:10 |
October | 51584.80 | 14151.68 | 0.50 | 51067.60 | 517.20 | 0.00 | 0.00 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 | 47.39 | 07-OCT-15:00 | 47.39 | 07-OCT-15:00 | 0.86 | 04-OCT-14:20 | 12.98 | 07-OCT-15:00 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.346541E+10 | 0.896500E+09 | 369.11 | 0.300482E+10 | 0.460594E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.100731E+10 | 0.261529E+09 | 128.04 | 0.886263E+09 | 0.152045E+09 | 0.00 | 1.00 | 0.00 | 16223.20 | 14828.68 | 7166.74 | 3475.06 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 0.100252E+09 | 26185279.70 | 12.31 | 99766852.66 | 484783.72 | 0.00 | 0.46 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5953.35 | 30-APR-15:00 | 5953.35 | 30-APR-15:00 | 160.26 | 30-APR-09:03 | 1525.87 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 59369134.02 | 15646103.77 | 9.33 | 53652190.44 | 5716943.58 | 0.00 | 0.38 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 5060.64 | 22-MAY-15:00 | 4606.75 | 22-MAY-15:00 | 453.89 | 22-MAY-15:00 | 1313.92 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.659943E+09 | 0.169553E+09 | 52.89 | 0.561571E+09 | 98372046.60 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 16104.91 | 13-JUN-08:62 | 12938.36 | 13-JUN-08:62 | 7138.92 | 27-JUN-08:62 | 3326.14 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.974491E+09 | 0.253304E+09 | 94.91 | 0.859003E+09 | 0.115489E+09 | 0.00 | 1.00 | 10-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16098.87 | 18-JUL-08:62 | 14729.28 | 22-JUL-08:62 | 6330.74 | 25-JUL-08:62 | 3454.57 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.969961E+09 | 0.251333E+09 | 123.29 | 0.824672E+09 | 0.145289E+09 | 0.00 | 1.00 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 | 16126.90 | 17-AUG-08:62 | 12024.85 | 15-AUG-08:62 | 6542.68 | 17-AUG-08:62 | 3330.12 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.572359E+09 | 0.148124E+09 | 64.90 | 0.497564E+09 | 74794432.39 | 0.00 | 0.45 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 | 6180.16 | 13-SEP-14:30 | 5296.02 | 13-SEP-14:20 | 1862.05 | 13-SEP-08:62 | 1547.73 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 6772.04 | 1859.17 | 0.33 | 6772.04 | -0.0 | 0.00 | 0.00 | 06-OCT-13:40 | 0.00 | 01-OCT-00:10 | 6.65 | 06-OCT-13:40 | 6.65 | 06-OCT-13:40 | 0.00 | 01-OCT-00:10 | 1.82 | 06-OCT-13:40 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.333638E+10 | 0.864148E+09 | 357.96 | 0.289624E+10 | 0.440146E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | -0.0 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.974491E+09 | 0.253304E+09 | 123.29 | 0.859003E+09 | 0.145289E+09 | 0.00 | 1.00 | 0.00 | 16126.90 | 14729.28 | 7138.92 | 3454.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 88872270.80 | 23290697.58 | 11.97 | 88530546.82 | 341723.98 | 0.00 | 0.44 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5689.42 | 30-APR-15:00 | 5689.42 | 30-APR-15:00 | 80.83 | 28-APR-15:00 | 1463.96 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 51521331.53 | 13616050.21 | 8.17 | 46772543.20 | 4748788.33 | 0.00 | 0.37 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4766.55 | 22-MAY-15:00 | 4335.82 | 22-MAY-15:00 | 430.73 | 22-MAY-15:00 | 1243.25 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.608162E+09 | 0.156817E+09 | 48.92 | 0.517740E+09 | 90422276.95 | 0.00 | 1.00 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 | 15927.32 | 13-JUN-08:62 | 12738.80 | 13-JUN-08:62 | 5805.89 | 27-JUN-08:62 | 3289.67 | 13-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.898239E+09 | 0.234193E+09 | 86.73 | 0.795812E+09 | 0.102427E+09 | 0.00 | 1.00 | 18-JUL-08:62 | 0.00 | 01-JUL-00:10 | 15921.67 | 18-JUL-08:62 | 14532.02 | 22-JUL-08:62 | 6038.31 | 24-JUL-08:62 | 3417.30 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.872671E+09 | 0.226900E+09 | 111.62 | 0.744996E+09 | 0.127675E+09 | 0.00 | 0.90 | 18-AUG-08:62 | 0.00 | 01-AUG-00:10 | 13700.43 | 17-AUG-08:62 | 10114.57 | 18-AUG-08:62 | 5597.50 | 17-AUG-08:62 | 2932.64 | 17-AUG-08:62 | 0.00 | 01-AUG-00:10 |
September | 0.510190E+09 | 0.132437E+09 | 60.42 | 0.444531E+09 | 65658963.86 | 0.00 | 0.45 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 | 5970.69 | 13-SEP-14:30 | 5114.55 | 13-SEP-14:30 | 1111.15 | 12-SEP-14:10 | 1499.29 | 13-SEP-14:30 | 0.00 | 01-SEP-00:10 |
October | 29721.60 | 8144.61 | 0.50 | 29721.60 | 0.00 | 0.00 | 0.00 | 05-OCT-14:30 | 0.00 | 01-OCT-00:10 | 24.22 | 05-OCT-14:30 | 24.22 | 05-OCT-14:30 | 0.00 | 06-OCT-14:20 | 6.64 | 05-OCT-14:30 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.302968E+10 | 0.787262E+09 | 328.33 | 0.263841E+10 | 0.391273E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.898239E+09 | 0.234193E+09 | 111.62 | 0.795812E+09 | 0.127675E+09 | 0.00 | 1.00 | 0.00 | 15927.32 | 14532.02 | 6038.31 | 3417.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 | 0.00 | 01-FEB-00:10 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 | 0.00 | 01-MAR-00:10 |
April | 79177934.37 | 20821812.48 | 12.00 | 78990250.29 | 187684.08 | 0.00 | 0.41 | 30-APR-15:00 | 0.00 | 01-APR-00:05 | 5469.02 | 30-APR-15:00 | 5469.02 | 30-APR-15:00 | 50.02 | 28-APR-15:00 | 1419.39 | 30-APR-15:00 | 0.00 | 01-APR-00:05 |
May | 51825381.97 | 13775532.66 | 8.17 | 46867862.83 | 4957519.14 | 0.00 | 0.34 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 | 4622.02 | 22-MAY-15:00 | 4204.04 | 22-MAY-15:00 | 417.97 | 22-MAY-15:00 | 1213.20 | 22-MAY-15:00 | 0.00 | 01-MAY-00:10 |
June | 0.589939E+09 | 0.152969E+09 | 46.31 | 0.503418E+09 | 86521358.12 | 0.00 | 0.62 | 26-JUN-08:62 | 0.00 | 01-JUN-00:10 | 8881.70 | 26-JUN-08:62 | 7089.50 | 26-JUN-08:62 | 1792.21 | 26-JUN-08:62 | 2068.40 | 26-JUN-08:62 | 0.00 | 01-JUN-00:10 |
July | 0.859734E+09 | 0.224480E+09 | 73.44 | 0.770797E+09 | 88936730.93 | 0.00 | 1.00 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 | 16529.76 | 22-JUL-08:62 | 15143.23 | 22-JUL-08:62 | 3369.59 | 23-JUL-09:03 | 3554.60 | 22-JUL-08:62 | 0.00 | 01-JUL-00:10 |
August | 0.782069E+09 | 0.204377E+09 | 97.19 | 0.670321E+09 | 0.111748E+09 | 0.00 | 0.49 | 14-AUG-15:00 | 0.00 | 01-AUG-00:10 | 6944.29 | 14-AUG-13:00 | 6604.16 | 14-AUG-17:00 | 1294.70 | 17-AUG-14:10 | 1765.94 | 14-AUG-17:00 | 0.00 | 01-AUG-00:10 |
September | 0.448430E+09 | 0.117099E+09 | 55.83 | 0.390538E+09 | 57891734.78 | 0.00 | 0.42 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 | 5822.60 | 13-SEP-14:20 | 4989.72 | 13-SEP-14:20 | 1055.88 | 12-SEP-14:10 | 1472.57 | 13-SEP-14:20 | 0.00 | 01-SEP-00:10 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 | 0.00 | 01-OCT-00:10 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 | 0.00 | 01-NOV-00:10 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 | 0.00 | 01-DEC-00:03 |
Annual Sum or Average | 0.281118E+10 | 0.733522E+09 | 292.93 | 0.246093E+10 | 0.350243E+09 | 0.00 | ||||||||||||||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Maximum of Months | 0.859734E+09 | 0.224480E+09 | 97.19 | 0.770797E+09 | 0.111748E+09 | 0.00 | 1.00 | 0.00 | 16529.76 | 15143.23 | 3369.59 | 3554.60 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.58 | 69.05 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.10 | 66.49 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.13 | 55.47 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.52 | 48.69 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.24 | 42.90 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.22 | 35.11 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.63 | 32.93 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.94 | 35.92 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.36 | 45.62 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.96 | 55.00 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.78 | 63.72 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.88 | 78.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.13 | 32.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.36 | 78.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.58 | 69.05 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.10 | 66.49 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.13 | 55.47 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.52 | 48.69 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.24 | 42.90 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.22 | 35.11 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.63 | 32.93 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.94 | 35.92 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.36 | 45.62 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.96 | 55.00 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.78 | 63.72 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.88 | 78.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.13 | 32.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.36 | 78.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.58 | 69.05 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.10 | 66.49 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.13 | 55.47 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.52 | 48.69 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.24 | 42.90 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.22 | 35.11 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.63 | 32.93 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.94 | 35.92 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.36 | 45.62 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.96 | 55.00 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.78 | 63.72 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.88 | 78.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.13 | 32.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.36 | 78.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.58 | 69.05 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.10 | 66.49 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.13 | 55.47 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.52 | 48.69 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.24 | 42.90 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.22 | 35.11 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.63 | 32.93 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.94 | 35.92 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.36 | 45.62 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.96 | 55.00 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.78 | 63.72 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.88 | 78.13 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.79 | 52.35 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.13 | 32.93 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.36 | 78.13 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.95 | 60.82 | 33.13 | 97.04 | 82.25 | 0.00 | 0.00 | 0.00 |
February | 114.75 | 70.02 | 44.73 | 121.75 | 79.09 | 0.00 | 0.00 | 0.00 |
March | 70.94 | 20.66 | 50.29 | 62.90 | 66.10 | 0.00 | 0.00 | 0.00 |
April | 147.32 | 66.59 | 80.73 | 173.86 | 58.05 | 0.00 | 0.00 | 0.00 |
May | 121.85 | 39.67 | 82.18 | 133.97 | 51.02 | 0.00 | 0.00 | 0.00 |
June | 112.25 | 27.17 | 85.08 | 125.48 | 41.78 | 0.00 | 0.00 | 0.00 |
July | 121.62 | 38.09 | 83.53 | 145.12 | 39.21 | 0.00 | 0.00 | 0.00 |
August | 142.51 | 64.11 | 78.41 | 179.08 | 42.86 | 0.00 | 0.00 | 0.00 |
September | 168.41 | 98.66 | 69.75 | 209.68 | 54.39 | 0.00 | 0.00 | 0.00 |
October | 115.71 | 67.63 | 48.08 | 131.11 | 65.51 | 0.00 | 0.00 | 0.00 |
November | 82.04 | 49.90 | 32.13 | 85.25 | 75.82 | 0.00 | 0.00 | 0.00 |
December | 65.02 | 41.66 | 23.36 | 64.92 | 92.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.86 | 53.54 | 59.32 | 127.33 | 62.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.02 | 20.66 | 23.36 | 62.90 | 39.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.41 | 98.66 | 85.08 | 209.68 | 92.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.95 | 60.82 | 33.13 | 97.04 | 82.25 | 0.00 | 0.00 | 0.00 |
February | 114.75 | 70.02 | 44.73 | 121.75 | 79.09 | 0.00 | 0.00 | 0.00 |
March | 70.94 | 20.66 | 50.29 | 62.90 | 66.10 | 0.00 | 0.00 | 0.00 |
April | 147.32 | 66.59 | 80.73 | 173.86 | 58.05 | 0.00 | 0.00 | 0.00 |
May | 121.85 | 39.67 | 82.18 | 133.97 | 51.02 | 0.00 | 0.00 | 0.00 |
June | 112.25 | 27.17 | 85.08 | 125.48 | 41.78 | 0.00 | 0.00 | 0.00 |
July | 121.62 | 38.09 | 83.53 | 145.12 | 39.21 | 0.00 | 0.00 | 0.00 |
August | 142.51 | 64.11 | 78.41 | 179.08 | 42.86 | 0.00 | 0.00 | 0.00 |
September | 168.41 | 98.66 | 69.75 | 209.68 | 54.39 | 0.00 | 0.00 | 0.00 |
October | 115.71 | 67.63 | 48.08 | 131.11 | 65.51 | 0.00 | 0.00 | 0.00 |
November | 82.04 | 49.90 | 32.13 | 85.25 | 75.82 | 0.00 | 0.00 | 0.00 |
December | 65.02 | 41.66 | 23.36 | 64.92 | 92.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.86 | 53.54 | 59.32 | 127.33 | 62.33 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.02 | 20.66 | 23.36 | 62.90 | 39.21 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.41 | 98.66 | 85.08 | 209.68 | 92.83 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.57 | 73.25 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 99.91 | 70.70 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 50.87 | 59.55 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 142.41 | 52.54 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.04 | 46.38 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 102.95 | 36.65 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.82 | 33.99 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.31 | 36.90 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.44 | 47.13 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 107.52 | 59.44 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 69.87 | 68.22 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.17 | 82.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.59 | 55.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 50.87 | 33.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.44 | 82.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.57 | 73.25 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 99.91 | 70.70 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 50.87 | 59.55 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 142.41 | 52.54 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.04 | 46.38 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 102.95 | 36.65 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.82 | 33.99 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.31 | 36.90 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.44 | 47.13 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 107.52 | 59.44 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 69.87 | 68.22 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.17 | 82.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.59 | 55.56 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 50.87 | 33.99 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.44 | 82.90 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.95 | 60.82 | 33.13 | 95.84 | 87.24 | 0.00 | 0.00 | 0.00 |
February | 114.75 | 70.02 | 44.73 | 120.33 | 84.06 | 0.00 | 0.00 | 0.00 |
March | 70.94 | 20.66 | 50.29 | 61.40 | 70.94 | 0.00 | 0.00 | 0.00 |
April | 147.32 | 66.59 | 80.73 | 171.36 | 62.60 | 0.00 | 0.00 | 0.00 |
May | 121.85 | 39.67 | 82.18 | 131.37 | 55.10 | 0.00 | 0.00 | 0.00 |
June | 112.25 | 27.17 | 85.08 | 123.98 | 43.59 | 0.00 | 0.00 | 0.00 |
July | 121.62 | 38.09 | 83.53 | 144.18 | 40.46 | 0.00 | 0.00 | 0.00 |
August | 142.51 | 64.11 | 78.41 | 178.34 | 44.01 | 0.00 | 0.00 | 0.00 |
September | 168.41 | 98.66 | 69.75 | 208.61 | 56.17 | 0.00 | 0.00 | 0.00 |
October | 115.71 | 67.63 | 48.08 | 129.39 | 70.75 | 0.00 | 0.00 | 0.00 |
November | 82.04 | 49.90 | 32.13 | 84.16 | 81.14 | 0.00 | 0.00 | 0.00 |
December | 65.02 | 41.66 | 23.36 | 64.08 | 98.46 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.86 | 53.54 | 59.32 | 125.90 | 66.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 65.02 | 20.66 | 23.36 | 61.40 | 40.46 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 168.41 | 98.66 | 85.08 | 208.61 | 98.46 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.81 | 71.16 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.14 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.11 | 57.73 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 142.87 | 51.47 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.47 | 45.60 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 102.95 | 37.12 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.68 | 34.81 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.22 | 37.88 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.49 | 47.72 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 107.88 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.13 | 65.95 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.32 | 80.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.77 | 54.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.11 | 34.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.49 | 80.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.81 | 71.16 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.14 | 68.74 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.11 | 57.73 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 142.87 | 51.47 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.47 | 45.60 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 102.95 | 37.12 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.68 | 34.81 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.22 | 37.88 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.49 | 47.72 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 107.88 | 57.87 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.13 | 65.95 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.32 | 80.71 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.77 | 54.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.11 | 34.81 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.49 | 80.71 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 95.60 | 84.29 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 119.96 | 81.31 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 61.35 | 68.41 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 170.98 | 60.99 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 131.17 | 53.88 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 123.31 | 43.89 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 143.22 | 41.18 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.26 | 44.90 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 207.53 | 56.54 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 129.12 | 68.51 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.01 | 78.03 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 63.91 | 95.36 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 125.44 | 64.69 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 61.35 | 41.18 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 207.53 | 95.36 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.98 | 70.18 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.31 | 67.86 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.30 | 56.90 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.28 | 50.58 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.89 | 44.82 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.11 | 36.82 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.76 | 34.62 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.27 | 37.74 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.58 | 47.43 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.14 | 56.89 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.28 | 64.96 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.43 | 79.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.96 | 53.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.30 | 34.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.58 | 79.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 79.98 | 70.18 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.31 | 67.86 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.30 | 56.90 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.28 | 50.58 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 109.89 | 44.82 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.11 | 36.82 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.76 | 34.62 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.27 | 37.74 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.58 | 47.43 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.14 | 56.89 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.28 | 64.96 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.43 | 79.68 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 104.96 | 53.97 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.30 | 34.62 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.58 | 79.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 95.81 | 83.13 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 120.17 | 80.26 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 61.58 | 67.42 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 171.46 | 59.94 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 131.67 | 52.96 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 123.50 | 43.54 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 143.32 | 40.96 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.31 | 44.73 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 207.64 | 56.20 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 129.43 | 67.35 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.20 | 76.85 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.05 | 94.14 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 125.66 | 63.88 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 61.58 | 40.96 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 207.64 | 94.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.17 | 69.35 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.53 | 67.10 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.54 | 56.17 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.81 | 49.67 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.48 | 43.95 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.47 | 36.32 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.99 | 34.24 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.42 | 37.39 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.78 | 46.98 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.47 | 55.91 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.45 | 64.13 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.57 | 78.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.24 | 53.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.54 | 34.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.78 | 78.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.17 | 69.35 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 100.53 | 67.10 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 51.54 | 56.17 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 143.81 | 49.67 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 110.48 | 43.95 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 103.47 | 36.32 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 119.99 | 34.24 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.42 | 37.39 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 173.78 | 46.98 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 108.47 | 55.91 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.45 | 64.13 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.57 | 78.73 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.24 | 53.26 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 51.54 | 34.24 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 173.78 | 78.73 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.04 | 82.14 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 120.43 | 79.35 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 61.87 | 66.55 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 172.10 | 58.86 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 132.37 | 51.93 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 123.93 | 42.94 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 143.59 | 40.51 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.49 | 44.33 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 207.88 | 55.67 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 129.83 | 66.20 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.41 | 75.87 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.21 | 93.01 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.00 | 63.03 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 61.87 | 40.51 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 207.88 | 93.01 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.84 | 67.30 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.29 | 65.08 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.30 | 54.36 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.78 | 47.90 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.52 | 42.25 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.26 | 35.04 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.44 | 33.20 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.70 | 36.42 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.23 | 45.83 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.18 | 53.94 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.99 | 62.13 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.08 | 76.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.90 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.30 | 33.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.23 | 76.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.84 | 67.30 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.29 | 65.08 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.30 | 54.36 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.78 | 47.90 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.52 | 42.25 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.26 | 35.04 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.44 | 33.20 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.70 | 36.42 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.23 | 45.83 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.18 | 53.94 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.99 | 62.13 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.08 | 76.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.90 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.30 | 33.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.23 | 76.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.84 | 67.30 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.29 | 65.08 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.30 | 54.36 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.78 | 47.90 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.52 | 42.25 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.26 | 35.04 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.44 | 33.20 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.70 | 36.42 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.23 | 45.83 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.18 | 53.94 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.99 | 62.13 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.08 | 76.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.90 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.30 | 33.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.23 | 76.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.84 | 67.30 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.29 | 65.08 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.30 | 54.36 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.78 | 47.90 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.52 | 42.25 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.26 | 35.04 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.44 | 33.20 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.70 | 36.42 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.23 | 45.83 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.18 | 53.94 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.99 | 62.13 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.08 | 76.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.90 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.30 | 33.20 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.23 | 76.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.84 | 79.71 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.32 | 76.99 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.77 | 64.42 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.24 | 56.77 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 133.58 | 49.96 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 124.85 | 41.46 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.11 | 39.30 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.82 | 43.19 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.38 | 54.32 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.65 | 63.88 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 85.03 | 73.51 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.81 | 89.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.77 | 61.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.77 | 39.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.38 | 89.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.84 | 79.71 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.32 | 76.99 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.77 | 64.42 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.24 | 56.77 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 133.58 | 49.96 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 124.85 | 41.46 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.11 | 39.30 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.82 | 43.19 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.38 | 54.32 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.65 | 63.88 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 85.03 | 73.51 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.81 | 89.98 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.77 | 61.04 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.77 | 39.30 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.38 | 89.98 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.68 | 67.46 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.09 | 65.26 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.14 | 54.42 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.73 | 47.71 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.48 | 42.11 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.25 | 34.90 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.40 | 33.07 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.62 | 36.28 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.09 | 45.73 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.08 | 53.85 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.86 | 62.26 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.96 | 76.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.80 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.14 | 33.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.09 | 76.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.68 | 67.46 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.09 | 65.26 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.14 | 54.42 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.73 | 47.71 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.48 | 42.11 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.25 | 34.90 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.40 | 33.07 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.62 | 36.28 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.09 | 45.73 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.08 | 53.85 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.86 | 62.26 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 53.96 | 76.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.80 | 51.57 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.14 | 33.07 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.09 | 76.55 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.66 | 79.88 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.12 | 77.16 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.60 | 64.47 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.21 | 56.54 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 133.57 | 49.76 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 124.87 | 41.27 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.10 | 39.13 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.75 | 43.02 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.26 | 54.19 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.57 | 63.75 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.89 | 73.65 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.68 | 90.42 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.67 | 61.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.60 | 39.13 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.26 | 90.42 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.75 | 67.18 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.19 | 64.96 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.23 | 54.16 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.96 | 47.35 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.76 | 41.74 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.54 | 34.57 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.59 | 32.84 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.72 | 36.12 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.24 | 45.46 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.27 | 53.41 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.93 | 61.96 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.00 | 76.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.95 | 51.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.23 | 32.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.24 | 76.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 80.75 | 67.18 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.19 | 64.96 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.23 | 54.16 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 144.96 | 47.35 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 111.76 | 41.74 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 104.54 | 34.57 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 120.59 | 32.84 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 148.72 | 36.12 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.24 | 45.46 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.27 | 53.41 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 70.93 | 61.96 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.00 | 76.29 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 105.95 | 51.27 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.23 | 32.84 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.24 | 76.29 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 96.75 | 79.55 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.23 | 76.82 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 62.71 | 64.16 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 173.49 | 56.10 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 133.91 | 49.32 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 125.22 | 40.89 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.32 | 38.87 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 177.87 | 42.83 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.44 | 53.87 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 130.78 | 63.23 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 84.98 | 73.29 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.73 | 90.11 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 126.85 | 60.67 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 62.71 | 38.87 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.44 | 90.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 81.00 | 66.08 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.51 | 63.83 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.56 | 53.13 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.51 | 46.34 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.44 | 40.71 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.27 | 33.67 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.06 | 32.19 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.01 | 35.58 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.69 | 44.61 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.73 | 52.17 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.16 | 60.86 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.17 | 75.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.36 | 50.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.56 | 32.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.69 | 75.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 81.00 | 66.08 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 101.51 | 63.83 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 52.56 | 53.13 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 145.51 | 46.34 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 112.44 | 40.71 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 105.27 | 33.67 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 121.06 | 32.19 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.01 | 35.58 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 174.69 | 44.61 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 109.73 | 52.17 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.16 | 60.86 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.17 | 75.16 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 106.36 | 50.29 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 52.56 | 32.19 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 174.69 | 75.16 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 97.05 | 78.25 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 121.61 | 75.48 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 63.11 | 62.93 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 174.14 | 54.91 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 134.72 | 48.11 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 126.09 | 39.82 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 144.89 | 38.10 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 178.22 | 42.19 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 208.98 | 52.87 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 131.34 | 61.77 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 85.26 | 71.98 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 64.93 | 88.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 127.35 | 59.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 63.11 | 38.10 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 208.98 | 88.76 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 81.86 | 61.89 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 102.59 | 59.46 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 53.66 | 49.30 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 146.64 | 43.09 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 113.95 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 106.89 | 30.81 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 122.16 | 29.89 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.80 | 33.36 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 175.74 | 41.68 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 110.82 | 48.40 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.91 | 56.87 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.75 | 70.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 107.41 | 46.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 53.66 | 29.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 175.74 | 70.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 78.16 | 50.59 | 27.56 | 81.86 | 61.89 | 0.00 | 0.00 | 0.00 |
February | 95.45 | 58.25 | 37.21 | 102.59 | 59.46 | 0.00 | 0.00 | 0.00 |
March | 59.01 | 17.18 | 41.83 | 53.66 | 49.30 | 0.00 | 0.00 | 0.00 |
April | 122.55 | 55.39 | 67.16 | 146.64 | 43.09 | 0.00 | 0.00 | 0.00 |
May | 101.36 | 33.00 | 68.36 | 113.95 | 37.30 | 0.00 | 0.00 | 0.00 |
June | 93.37 | 22.60 | 70.77 | 106.89 | 30.81 | 0.00 | 0.00 | 0.00 |
July | 101.17 | 31.68 | 69.49 | 122.16 | 29.89 | 0.00 | 0.00 | 0.00 |
August | 118.55 | 53.33 | 65.22 | 149.80 | 33.36 | 0.00 | 0.00 | 0.00 |
September | 140.09 | 82.07 | 58.02 | 175.74 | 41.68 | 0.00 | 0.00 | 0.00 |
October | 96.25 | 56.25 | 40.00 | 110.82 | 48.40 | 0.00 | 0.00 | 0.00 |
November | 68.24 | 41.51 | 26.73 | 71.91 | 56.87 | 0.00 | 0.00 | 0.00 |
December | 54.09 | 34.65 | 19.43 | 54.75 | 70.56 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 93.88 | 44.54 | 49.34 | 107.41 | 46.82 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 54.09 | 17.18 | 19.43 | 53.66 | 29.89 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 140.09 | 82.07 | 70.77 | 175.74 | 70.56 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 93.44 | 60.49 | 32.95 | 98.09 | 73.26 | 0.00 | 0.00 | 0.00 |
February | 114.12 | 69.64 | 44.48 | 122.92 | 70.30 | 0.00 | 0.00 | 0.00 |
March | 70.56 | 20.54 | 50.01 | 64.45 | 58.38 | 0.00 | 0.00 | 0.00 |
April | 146.52 | 66.22 | 80.29 | 175.50 | 51.06 | 0.00 | 0.00 | 0.00 |
May | 121.18 | 39.45 | 81.73 | 136.53 | 44.11 | 0.00 | 0.00 | 0.00 |
June | 111.64 | 27.02 | 84.61 | 128.01 | 36.45 | 0.00 | 0.00 | 0.00 |
July | 120.96 | 37.88 | 83.08 | 146.20 | 35.39 | 0.00 | 0.00 | 0.00 |
August | 141.73 | 63.76 | 77.98 | 179.17 | 39.58 | 0.00 | 0.00 | 0.00 |
September | 167.49 | 98.12 | 69.37 | 210.23 | 49.41 | 0.00 | 0.00 | 0.00 |
October | 115.07 | 67.26 | 47.82 | 132.64 | 57.31 | 0.00 | 0.00 | 0.00 |
November | 81.59 | 49.63 | 31.96 | 86.17 | 67.25 | 0.00 | 0.00 | 0.00 |
December | 64.67 | 41.43 | 23.23 | 65.64 | 83.31 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 112.24 | 53.25 | 59.00 | 128.61 | 55.41 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 64.67 | 20.54 | 23.23 | 64.45 | 35.39 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 167.49 | 98.12 | 84.61 | 210.23 | 83.31 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215830E+09 | 0.184948E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244570E+09 | 0.160845E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139624E+09 | 0.148559E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.374583E+09 | 0.126216E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.297942E+09 | 0.114913E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270145E+09 | 91012755.69 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323092E+09 | 88202028.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398931E+09 | 96218837.57 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451941E+09 | 0.118249E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.291847E+09 | 0.147302E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183472E+09 | 0.165154E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144299E+09 | 0.209268E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333628E+10 | 0.165089E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139624E+09 | 88202028.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451941E+09 | 0.209268E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215830E+09 | 0.184948E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244570E+09 | 0.160845E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139624E+09 | 0.148559E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.374583E+09 | 0.126216E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.297942E+09 | 0.114913E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270145E+09 | 91012755.69 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323092E+09 | 88202028.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398931E+09 | 96218837.57 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451941E+09 | 0.118249E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.291847E+09 | 0.147302E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183472E+09 | 0.165154E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144299E+09 | 0.209268E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333628E+10 | 0.165089E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139624E+09 | 88202028.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451941E+09 | 0.209268E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215830E+09 | 0.184948E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244570E+09 | 0.160845E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139624E+09 | 0.148559E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.374583E+09 | 0.126216E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.297942E+09 | 0.114913E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270145E+09 | 91012755.69 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323092E+09 | 88202028.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398931E+09 | 96218837.57 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451941E+09 | 0.118249E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.291847E+09 | 0.147302E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183472E+09 | 0.165154E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144299E+09 | 0.209268E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333628E+10 | 0.165089E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139624E+09 | 88202028.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451941E+09 | 0.209268E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.215830E+09 | 0.184948E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244570E+09 | 0.160845E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139624E+09 | 0.148559E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.374583E+09 | 0.126216E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.297942E+09 | 0.114913E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270145E+09 | 91012755.69 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.323092E+09 | 88202028.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398931E+09 | 96218837.57 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451941E+09 | 0.118249E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.291847E+09 | 0.147302E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183472E+09 | 0.165154E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144299E+09 | 0.209268E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333628E+10 | 0.165089E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139624E+09 | 88202028.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451941E+09 | 0.209268E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.251648E+09 | 0.162902E+09 | 88745923.47 | 0.259924E+09 | 0.220299E+09 |
February | 0.277599E+09 | 0.169395E+09 | 0.108204E+09 | 0.294533E+09 | 0.191332E+09 |
March | 0.190019E+09 | 55324980.73 | 0.134694E+09 | 0.168478E+09 | 0.177029E+09 |
April | 0.381861E+09 | 0.172597E+09 | 0.209264E+09 | 0.450632E+09 | 0.150463E+09 |
May | 0.326362E+09 | 0.106253E+09 | 0.220109E+09 | 0.358832E+09 | 0.136650E+09 |
June | 0.290951E+09 | 70427123.00 | 0.220524E+09 | 0.325247E+09 | 0.108305E+09 |
July | 0.325748E+09 | 0.102012E+09 | 0.223736E+09 | 0.388681E+09 | 0.105030E+09 |
August | 0.381705E+09 | 0.171705E+09 | 0.210000E+09 | 0.479638E+09 | 0.114789E+09 |
September | 0.436525E+09 | 0.255724E+09 | 0.180801E+09 | 0.543489E+09 | 0.140981E+09 |
October | 0.309908E+09 | 0.181127E+09 | 0.128781E+09 | 0.351155E+09 | 0.175453E+09 |
November | 0.212637E+09 | 0.129352E+09 | 83284360.16 | 0.220962E+09 | 0.196529E+09 |
December | 0.174152E+09 | 0.111580E+09 | 62571945.73 | 0.173873E+09 | 0.248631E+09 |
Annual Sum or Average | 0.355912E+10 | 0.168840E+10 | 0.187072E+10 | 0.401544E+10 | 0.196549E+10 |
Minimum of Months | 0.174152E+09 | 55324980.73 | 62571945.73 | 0.168478E+09 | 0.105030E+09 |
Maximum of Months | 0.436525E+09 | 0.255724E+09 | 0.223736E+09 | 0.543489E+09 | 0.248631E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.251648E+09 | 0.162902E+09 | 88745923.47 | 0.259924E+09 | 0.220299E+09 |
February | 0.277599E+09 | 0.169395E+09 | 0.108204E+09 | 0.294533E+09 | 0.191332E+09 |
March | 0.190019E+09 | 55324980.73 | 0.134694E+09 | 0.168478E+09 | 0.177029E+09 |
April | 0.381861E+09 | 0.172597E+09 | 0.209264E+09 | 0.450632E+09 | 0.150463E+09 |
May | 0.326362E+09 | 0.106253E+09 | 0.220109E+09 | 0.358832E+09 | 0.136650E+09 |
June | 0.290951E+09 | 70427123.00 | 0.220524E+09 | 0.325247E+09 | 0.108305E+09 |
July | 0.325748E+09 | 0.102012E+09 | 0.223736E+09 | 0.388681E+09 | 0.105030E+09 |
August | 0.381705E+09 | 0.171705E+09 | 0.210000E+09 | 0.479638E+09 | 0.114789E+09 |
September | 0.436525E+09 | 0.255724E+09 | 0.180801E+09 | 0.543489E+09 | 0.140981E+09 |
October | 0.309908E+09 | 0.181127E+09 | 0.128781E+09 | 0.351155E+09 | 0.175453E+09 |
November | 0.212637E+09 | 0.129352E+09 | 83284360.16 | 0.220962E+09 | 0.196529E+09 |
December | 0.174152E+09 | 0.111580E+09 | 62571945.73 | 0.173873E+09 | 0.248631E+09 |
Annual Sum or Average | 0.355912E+10 | 0.168840E+10 | 0.187072E+10 | 0.401544E+10 | 0.196549E+10 |
Minimum of Months | 0.174152E+09 | 55324980.73 | 62571945.73 | 0.168478E+09 | 0.105030E+09 |
Maximum of Months | 0.436525E+09 | 0.255724E+09 | 0.223736E+09 | 0.543489E+09 | 0.248631E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.213121E+09 | 0.196198E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.241699E+09 | 0.171029E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136260E+09 | 0.159511E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.369116E+09 | 0.136192E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.292048E+09 | 0.124237E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.266841E+09 | 94997619.18 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.320935E+09 | 91044486.35 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397227E+09 | 98835135.81 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449568E+09 | 0.122165E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.287968E+09 | 0.159199E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181103E+09 | 0.176821E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142412E+09 | 0.222029E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.329830E+10 | 0.175226E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136260E+09 | 91044486.35 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449568E+09 | 0.222029E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.213121E+09 | 0.196198E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.241699E+09 | 0.171029E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136260E+09 | 0.159511E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.369116E+09 | 0.136192E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.292048E+09 | 0.124237E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.266841E+09 | 94997619.18 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.320935E+09 | 91044486.35 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397227E+09 | 98835135.81 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449568E+09 | 0.122165E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.287968E+09 | 0.159199E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181103E+09 | 0.176821E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142412E+09 | 0.222029E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.329830E+10 | 0.175226E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136260E+09 | 91044486.35 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449568E+09 | 0.222029E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.251648E+09 | 0.162902E+09 | 88745923.47 | 0.256691E+09 | 0.233658E+09 |
February | 0.277599E+09 | 0.169395E+09 | 0.108204E+09 | 0.291112E+09 | 0.203364E+09 |
March | 0.190019E+09 | 55324980.73 | 0.134694E+09 | 0.164445E+09 | 0.190015E+09 |
April | 0.381861E+09 | 0.172597E+09 | 0.209264E+09 | 0.444171E+09 | 0.162265E+09 |
May | 0.326362E+09 | 0.106253E+09 | 0.220109E+09 | 0.351869E+09 | 0.147591E+09 |
June | 0.290951E+09 | 70427123.00 | 0.220524E+09 | 0.321363E+09 | 0.112980E+09 |
July | 0.325748E+09 | 0.102012E+09 | 0.223736E+09 | 0.386166E+09 | 0.108356E+09 |
August | 0.381705E+09 | 0.171705E+09 | 0.210000E+09 | 0.477653E+09 | 0.117864E+09 |
September | 0.436525E+09 | 0.255724E+09 | 0.180801E+09 | 0.540724E+09 | 0.145593E+09 |
October | 0.309908E+09 | 0.181127E+09 | 0.128781E+09 | 0.346565E+09 | 0.189492E+09 |
November | 0.212637E+09 | 0.129352E+09 | 83284360.16 | 0.218151E+09 | 0.210309E+09 |
December | 0.174152E+09 | 0.111580E+09 | 62571945.73 | 0.171627E+09 | 0.263724E+09 |
Annual Sum or Average | 0.355912E+10 | 0.168840E+10 | 0.187072E+10 | 0.397054E+10 | 0.208521E+10 |
Minimum of Months | 0.174152E+09 | 55324980.73 | 62571945.73 | 0.164445E+09 | 0.108356E+09 |
Maximum of Months | 0.436525E+09 | 0.255724E+09 | 0.223736E+09 | 0.540724E+09 | 0.263724E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.213757E+09 | 0.190598E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242253E+09 | 0.166307E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136905E+09 | 0.154627E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.370322E+09 | 0.133412E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.293211E+09 | 0.122133E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.266853E+09 | 96227241.53 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.320546E+09 | 93239851.28 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.396999E+09 | 0.101457E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449698E+09 | 0.123685E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.288958E+09 | 0.154995E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181768E+09 | 0.170944E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142815E+09 | 0.216177E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.330409E+10 | 0.172380E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136905E+09 | 93239851.28 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449698E+09 | 0.216177E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.213757E+09 | 0.190598E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242253E+09 | 0.166307E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.136905E+09 | 0.154627E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.370322E+09 | 0.133412E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.293211E+09 | 0.122133E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.266853E+09 | 96227241.53 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.320546E+09 | 93239851.28 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.396999E+09 | 0.101457E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449698E+09 | 0.123685E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.288958E+09 | 0.154995E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.181768E+09 | 0.170944E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.142815E+09 | 0.216177E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.330409E+10 | 0.172380E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.136905E+09 | 93239851.28 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449698E+09 | 0.216177E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.256061E+09 | 0.225770E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.290198E+09 | 0.196699E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.164331E+09 | 0.183218E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.443177E+09 | 0.158085E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.351326E+09 | 0.144308E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.319623E+09 | 0.113771E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.383598E+09 | 0.110302E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.474771E+09 | 0.120259E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.537922E+09 | 0.146545E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.345847E+09 | 0.183508E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.217759E+09 | 0.202253E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.171181E+09 | 0.255409E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.395579E+10 | 0.204013E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.164331E+09 | 0.110302E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.537922E+09 | 0.255409E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214211E+09 | 0.187979E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242677E+09 | 0.164177E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.137412E+09 | 0.152395E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.371373E+09 | 0.131116E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.294333E+09 | 0.120040E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.267258E+09 | 95441022.66 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.320767E+09 | 92731213.59 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397115E+09 | 0.101076E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449925E+09 | 0.122944E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.289647E+09 | 0.152368E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182171E+09 | 0.168371E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.143115E+09 | 0.213425E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.331001E+10 | 0.170206E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.137412E+09 | 92731213.59 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449925E+09 | 0.213425E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214211E+09 | 0.187979E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.242677E+09 | 0.164177E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.137412E+09 | 0.152395E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.371373E+09 | 0.131116E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.294333E+09 | 0.120040E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.267258E+09 | 95441022.66 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.320767E+09 | 92731213.59 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397115E+09 | 0.101076E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.449925E+09 | 0.122944E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.289647E+09 | 0.152368E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182171E+09 | 0.168371E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.143115E+09 | 0.213425E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.331001E+10 | 0.170206E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.137412E+09 | 92731213.59 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.449925E+09 | 0.213425E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.256610E+09 | 0.222654E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.290712E+09 | 0.194173E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.164946E+09 | 0.180566E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.444431E+09 | 0.155362E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.352663E+09 | 0.141840E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.320109E+09 | 0.112845E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.383864E+09 | 0.109701E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.474913E+09 | 0.119808E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.538196E+09 | 0.145670E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.346671E+09 | 0.180397E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.218244E+09 | 0.199201E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.171545E+09 | 0.252145E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.396290E+10 | 0.201436E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.164946E+09 | 0.109701E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.538196E+09 | 0.252145E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214724E+09 | 0.185745E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.243194E+09 | 0.162318E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.138047E+09 | 0.150437E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.372760E+09 | 0.128742E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.295900E+09 | 0.117705E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.268192E+09 | 94133251.37 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321374E+09 | 91704087.81 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397516E+09 | 0.100156E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.450441E+09 | 0.121784E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.290535E+09 | 0.149758E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182615E+09 | 0.166231E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.143486E+09 | 0.210877E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.331878E+10 | 0.167959E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.138047E+09 | 91704087.81 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.450441E+09 | 0.210877E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.214724E+09 | 0.185745E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.243194E+09 | 0.162318E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.138047E+09 | 0.150437E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.372760E+09 | 0.128742E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.295900E+09 | 0.117705E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.268192E+09 | 94133251.37 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.321374E+09 | 91704087.81 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.397516E+09 | 0.100156E+09 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.450441E+09 | 0.121784E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.290535E+09 | 0.149758E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.182615E+09 | 0.166231E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.143486E+09 | 0.210877E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.331878E+10 | 0.167959E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.138047E+09 | 91704087.81 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.450441E+09 | 0.210877E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.257232E+09 | 0.219997E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.291339E+09 | 0.191970E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.165714E+09 | 0.178242E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.446085E+09 | 0.152553E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.354530E+09 | 0.139091E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.321228E+09 | 0.111307E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.384593E+09 | 0.108496E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.475399E+09 | 0.118729E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.538815E+09 | 0.144303E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.347732E+09 | 0.177308E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.218780E+09 | 0.196662E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.171993E+09 | 0.249121E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.397344E+10 | 0.198778E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.165714E+09 | 0.108496E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.538815E+09 | 0.249121E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216535E+09 | 0.180246E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245042E+09 | 0.157447E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140085E+09 | 0.145607E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375281E+09 | 0.124160E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298696E+09 | 0.113170E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270246E+09 | 90831028.62 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322583E+09 | 88933107.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398278E+09 | 97544456.95 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451594E+09 | 0.118781E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292427E+09 | 0.144473E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184000E+09 | 0.161040E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144849E+09 | 0.203974E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333962E+10 | 0.162621E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140085E+09 | 88933107.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451594E+09 | 0.203974E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216535E+09 | 0.180246E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245042E+09 | 0.157447E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140085E+09 | 0.145607E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375281E+09 | 0.124160E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298696E+09 | 0.113170E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270246E+09 | 90831028.62 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322583E+09 | 88933107.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398278E+09 | 97544456.95 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451594E+09 | 0.118781E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292427E+09 | 0.144473E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184000E+09 | 0.161040E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144849E+09 | 0.203974E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333962E+10 | 0.162621E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140085E+09 | 88933107.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451594E+09 | 0.203974E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216535E+09 | 0.180246E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245042E+09 | 0.157447E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140085E+09 | 0.145607E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375281E+09 | 0.124160E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298696E+09 | 0.113170E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270246E+09 | 90831028.62 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322583E+09 | 88933107.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398278E+09 | 97544456.95 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451594E+09 | 0.118781E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292427E+09 | 0.144473E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184000E+09 | 0.161040E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144849E+09 | 0.203974E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333962E+10 | 0.162621E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140085E+09 | 88933107.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451594E+09 | 0.203974E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216535E+09 | 0.180246E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245042E+09 | 0.157447E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140085E+09 | 0.145607E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375281E+09 | 0.124160E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298696E+09 | 0.113170E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270246E+09 | 90831028.62 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322583E+09 | 88933107.18 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398278E+09 | 97544456.95 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451594E+09 | 0.118781E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292427E+09 | 0.144473E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184000E+09 | 0.161040E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144849E+09 | 0.203974E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333962E+10 | 0.162621E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140085E+09 | 88933107.18 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451594E+09 | 0.203974E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.259366E+09 | 0.213497E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293504E+09 | 0.186246E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.168131E+09 | 0.172533E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.449025E+09 | 0.147160E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.357785E+09 | 0.133803E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.323612E+09 | 0.107454E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.385982E+09 | 0.105268E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476263E+09 | 0.115678E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.540130E+09 | 0.140792E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.349945E+09 | 0.171099E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220399E+09 | 0.190543E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173589E+09 | 0.241012E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.399773E+10 | 0.192509E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.168131E+09 | 0.105268E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.540130E+09 | 0.241012E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.259366E+09 | 0.213497E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293504E+09 | 0.186246E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.168131E+09 | 0.172533E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.449025E+09 | 0.147160E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.357785E+09 | 0.133803E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.323612E+09 | 0.107454E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.385982E+09 | 0.105268E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476263E+09 | 0.115678E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.540130E+09 | 0.140792E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.349945E+09 | 0.171099E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220399E+09 | 0.190543E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173589E+09 | 0.241012E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.399773E+10 | 0.192509E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.168131E+09 | 0.105268E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.540130E+09 | 0.241012E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216095E+09 | 0.180684E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244568E+09 | 0.157865E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139645E+09 | 0.145770E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375146E+09 | 0.123674E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298588E+09 | 0.112783E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270218E+09 | 90466853.18 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322492E+09 | 88574136.39 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398059E+09 | 97181614.33 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451235E+09 | 0.118534E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292171E+09 | 0.144221E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183662E+09 | 0.161389E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144521E+09 | 0.205039E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333640E+10 | 0.162618E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139645E+09 | 88574136.39 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451235E+09 | 0.205039E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216095E+09 | 0.180684E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244568E+09 | 0.157865E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139645E+09 | 0.145770E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375146E+09 | 0.123674E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.298588E+09 | 0.112783E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270218E+09 | 90466853.18 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322492E+09 | 88574136.39 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398059E+09 | 97181614.33 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451235E+09 | 0.118534E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292171E+09 | 0.144221E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183662E+09 | 0.161389E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144521E+09 | 0.205039E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.333640E+10 | 0.162618E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139645E+09 | 88574136.39 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451235E+09 | 0.205039E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.258892E+09 | 0.213963E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293004E+09 | 0.186676E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.167657E+09 | 0.172689E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.448957E+09 | 0.146548E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.357761E+09 | 0.133289E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.323669E+09 | 0.106982E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.385964E+09 | 0.104808E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476092E+09 | 0.115223E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.539800E+09 | 0.140463E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.349708E+09 | 0.170746E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220045E+09 | 0.190895E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173236E+09 | 0.242176E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.399478E+10 | 0.192446E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.167657E+09 | 0.104808E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.539800E+09 | 0.242176E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216292E+09 | 0.179935E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244793E+09 | 0.157163E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139903E+09 | 0.145057E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375749E+09 | 0.122723E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.299336E+09 | 0.111783E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270963E+09 | 89617570.15 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322980E+09 | 87969831.07 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398331E+09 | 96744285.55 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451632E+09 | 0.117836E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292657E+09 | 0.143055E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183849E+09 | 0.160603E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144638E+09 | 0.204341E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334112E+10 | 0.161683E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139903E+09 | 87969831.07 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451632E+09 | 0.204341E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216292E+09 | 0.179935E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.244793E+09 | 0.157163E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.139903E+09 | 0.145057E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.375749E+09 | 0.122723E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.299336E+09 | 0.111783E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.270963E+09 | 89617570.15 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.322980E+09 | 87969831.07 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.398331E+09 | 96744285.55 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.451632E+09 | 0.117836E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.292657E+09 | 0.143055E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.183849E+09 | 0.160603E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.144638E+09 | 0.204341E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.334112E+10 | 0.161683E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.139903E+09 | 87969831.07 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.451632E+09 | 0.204341E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.259131E+09 | 0.213071E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.293275E+09 | 0.185842E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.167970E+09 | 0.171840E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.449677E+09 | 0.145419E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.358654E+09 | 0.132111E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.324558E+09 | 0.105981E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.386549E+09 | 0.104096E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.476419E+09 | 0.114706E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.540275E+09 | 0.139638E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.350288E+09 | 0.169364E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220270E+09 | 0.189960E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173378E+09 | 0.241347E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.400044E+10 | 0.191338E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.167970E+09 | 0.104096E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.540275E+09 | 0.241347E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216958E+09 | 0.176998E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245565E+09 | 0.154421E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140775E+09 | 0.142292E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.377157E+09 | 0.120112E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.301160E+09 | 0.109027E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272866E+09 | 87270367.07 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324256E+09 | 86227771.34 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399109E+09 | 95303231.70 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.452795E+09 | 0.115636E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293913E+09 | 0.139731E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184452E+09 | 0.157755E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.145085E+09 | 0.201301E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.335409E+10 | 0.158607E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140775E+09 | 86227771.34 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.452795E+09 | 0.201301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.216958E+09 | 0.176998E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.245565E+09 | 0.154421E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.140775E+09 | 0.142292E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.377157E+09 | 0.120112E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.301160E+09 | 0.109027E+09 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.272866E+09 | 87270367.07 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.324256E+09 | 86227771.34 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.399109E+09 | 95303231.70 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.452795E+09 | 0.115636E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.293913E+09 | 0.139731E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.184452E+09 | 0.157755E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.145085E+09 | 0.201301E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.335409E+10 | 0.158607E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.140775E+09 | 86227771.34 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.452795E+09 | 0.201301E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.259934E+09 | 0.209579E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.294208E+09 | 0.182590E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.169027E+09 | 0.168559E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.451363E+09 | 0.142328E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.360834E+09 | 0.128867E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.326822E+09 | 0.103213E+09 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.388074E+09 | 0.102047E+09 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.477353E+09 | 0.113008E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.541664E+09 | 0.137043E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.351791E+09 | 0.165434E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.220998E+09 | 0.186583E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.173917E+09 | 0.237744E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.401598E+10 | 0.187700E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.169027E+09 | 0.102047E+09 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.541664E+09 | 0.237744E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.219257E+09 | 0.165762E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.248177E+09 | 0.143856E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.143730E+09 | 0.132032E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.380081E+09 | 0.111689E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.305215E+09 | 99912616.15 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.277050E+09 | 79849360.82 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.327195E+09 | 80051668.19 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.401219E+09 | 89353848.88 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.455522E+09 | 0.108032E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.296812E+09 | 0.129632E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.186402E+09 | 0.147409E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.146650E+09 | 0.188981E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.338731E+10 | 0.147656E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.143730E+09 | 79849360.82 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.455522E+09 | 0.188981E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.209331E+09 | 0.135509E+09 | 73822427.99 | 0.219257E+09 | 0.165762E+09 |
February | 0.230918E+09 | 0.140909E+09 | 90008705.79 | 0.248177E+09 | 0.143856E+09 |
March | 0.158065E+09 | 46021543.82 | 0.112044E+09 | 0.143730E+09 | 0.132032E+09 |
April | 0.317647E+09 | 0.143573E+09 | 0.174075E+09 | 0.380081E+09 | 0.111689E+09 |
May | 0.271481E+09 | 88385508.69 | 0.183096E+09 | 0.305215E+09 | 99912616.15 |
June | 0.242025E+09 | 58584113.08 | 0.183441E+09 | 0.277050E+09 | 79849360.82 |
July | 0.270970E+09 | 84857401.35 | 0.186113E+09 | 0.327195E+09 | 80051668.19 |
August | 0.317518E+09 | 0.142831E+09 | 0.174687E+09 | 0.401219E+09 | 89353848.88 |
September | 0.363119E+09 | 0.212721E+09 | 0.150398E+09 | 0.455522E+09 | 0.108032E+09 |
October | 0.257794E+09 | 0.150669E+09 | 0.107125E+09 | 0.296812E+09 | 0.129632E+09 |
November | 0.176880E+09 | 0.107600E+09 | 69279279.99 | 0.186402E+09 | 0.147409E+09 |
December | 0.144867E+09 | 92816685.57 | 52049860.74 | 0.146650E+09 | 0.188981E+09 |
Annual Sum or Average | 0.296062E+10 | 0.140448E+10 | 0.155614E+10 | 0.338731E+10 | 0.147656E+10 |
Minimum of Months | 0.144867E+09 | 46021543.82 | 52049860.74 | 0.143730E+09 | 79849360.82 |
Maximum of Months | 0.363119E+09 | 0.212721E+09 | 0.186113E+09 | 0.455522E+09 | 0.188981E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.250273E+09 | 0.162012E+09 | 88260973.07 | 0.262730E+09 | 0.196225E+09 |
February | 0.276082E+09 | 0.168469E+09 | 0.107613E+09 | 0.297371E+09 | 0.170063E+09 |
March | 0.188981E+09 | 55022658.43 | 0.133958E+09 | 0.172610E+09 | 0.156371E+09 |
April | 0.379775E+09 | 0.171654E+09 | 0.208121E+09 | 0.454884E+09 | 0.132358E+09 |
May | 0.324579E+09 | 0.105672E+09 | 0.218907E+09 | 0.365688E+09 | 0.118142E+09 |
June | 0.289361E+09 | 70042275.33 | 0.219319E+09 | 0.331810E+09 | 94481740.41 |
July | 0.323968E+09 | 0.101454E+09 | 0.222514E+09 | 0.391584E+09 | 94785331.36 |
August | 0.379619E+09 | 0.170767E+09 | 0.208853E+09 | 0.479877E+09 | 0.106000E+09 |
September | 0.434140E+09 | 0.254326E+09 | 0.179813E+09 | 0.544916E+09 | 0.128078E+09 |
October | 0.308214E+09 | 0.180137E+09 | 0.128077E+09 | 0.355273E+09 | 0.153486E+09 |
November | 0.211475E+09 | 0.128645E+09 | 82829254.37 | 0.223354E+09 | 0.174318E+09 |
December | 0.173200E+09 | 0.110970E+09 | 62230022.53 | 0.175814E+09 | 0.223143E+09 |
Annual Sum or Average | 0.353967E+10 | 0.167917E+10 | 0.186049E+10 | 0.405591E+10 | 0.174745E+10 |
Minimum of Months | 0.173200E+09 | 55022658.43 | 62230022.53 | 0.172610E+09 | 94481740.41 |
Maximum of Months | 0.434140E+09 | 0.254326E+09 | 0.222514E+09 | 0.544916E+09 | 0.223143E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 516.42 | 440.71 | 500.53 | 324.01 | 176.52 | 0.00 | 0.00 |
February | 647.88 | 424.12 | 611.31 | 373.03 | 238.28 | 0.00 | 0.00 |
March | 334.32 | 354.05 | 377.95 | 110.04 | 267.91 | 0.00 | 0.00 |
April | 925.77 | 310.87 | 784.84 | 354.74 | 430.10 | 0.00 | 0.00 |
May | 712.90 | 273.65 | 649.14 | 211.34 | 437.80 | 0.00 | 0.00 |
June | 667.85 | 224.02 | 597.99 | 144.75 | 453.25 | 0.00 | 0.00 |
July | 772.75 | 210.15 | 647.92 | 202.90 | 445.01 | 0.00 | 0.00 |
August | 953.93 | 229.41 | 759.22 | 341.52 | 417.69 | 0.00 | 0.00 |
September | 1116.80 | 291.26 | 897.19 | 525.59 | 371.60 | 0.00 | 0.00 |
October | 698.06 | 351.00 | 616.41 | 360.26 | 256.15 | 0.00 | 0.00 |
November | 453.63 | 406.51 | 437.03 | 265.86 | 171.18 | 0.00 | 0.00 |
December | 345.33 | 498.18 | 346.39 | 221.93 | 124.46 | 0.00 | 0.00 |
Annual Sum or Average | 677.83 | 334.05 | 601.24 | 285.22 | 316.02 | 0.00 | 0.00 |
Minimum of Months | 334.32 | 210.15 | 346.39 | 110.04 | 124.46 | 0.00 | 0.00 |
Maximum of Months | 1116.80 | 498.18 | 897.19 | 525.59 | 453.25 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 254.98 | 233.74 | 250.27 | 162.01 | 88.26 | 0.00 | 0.00 |
February | 320.15 | 225.46 | 305.65 | 186.51 | 119.14 | 0.00 | 0.00 |
March | 163.14 | 190.05 | 188.97 | 55.02 | 133.95 | 0.00 | 0.00 |
April | 456.17 | 167.69 | 392.42 | 177.37 | 215.05 | 0.00 | 0.00 |
May | 349.45 | 147.87 | 324.57 | 105.67 | 218.90 | 0.00 | 0.00 |
June | 329.88 | 116.89 | 299.00 | 72.37 | 226.62 | 0.00 | 0.00 |
July | 383.82 | 108.44 | 323.96 | 101.45 | 222.51 | 0.00 | 0.00 |
August | 474.95 | 117.81 | 379.61 | 170.76 | 208.85 | 0.00 | 0.00 |
September | 555.50 | 150.43 | 448.60 | 262.80 | 185.80 | 0.00 | 0.00 |
October | 344.42 | 189.62 | 308.20 | 180.13 | 128.07 | 0.00 | 0.00 |
November | 223.90 | 217.57 | 218.52 | 132.93 | 85.59 | 0.00 | 0.00 |
December | 170.42 | 264.25 | 173.19 | 110.97 | 62.23 | 0.00 | 0.00 |
Annual Sum or Average | 335.08 | 177.25 | 300.62 | 142.61 | 158.01 | 0.00 | 0.00 |
Minimum of Months | 163.14 | 108.44 | 173.19 | 55.02 | 62.23 | 0.00 | 0.00 |
Maximum of Months | 555.50 | 264.25 | 448.60 | 262.80 | 226.62 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.22 | 226.61 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 320.23 | 218.80 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 163.58 | 183.87 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 456.72 | 163.93 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 350.11 | 145.08 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 329.22 | 118.14 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 382.58 | 110.81 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 473.70 | 120.66 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 554.52 | 151.97 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 344.89 | 184.25 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 224.26 | 209.93 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 170.55 | 256.78 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 334.98 | 174.01 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 163.58 | 110.81 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 554.52 | 256.78 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 255.76 | 223.50 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 320.79 | 215.99 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 164.19 | 181.21 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 458.02 | 161.11 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 351.45 | 142.59 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 329.72 | 117.18 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 382.84 | 110.20 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 473.84 | 120.21 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 554.80 | 151.06 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 345.72 | 181.13 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 224.76 | 206.77 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 170.91 | 253.51 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 335.58 | 171.82 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 164.19 | 110.20 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 554.80 | 253.51 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 256.38 | 220.84 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 321.48 | 213.54 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 164.95 | 178.88 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 459.72 | 158.19 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 353.32 | 139.82 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 330.87 | 115.58 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 383.57 | 108.98 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 474.32 | 119.12 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 555.44 | 149.64 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 346.78 | 178.03 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 225.31 | 204.14 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 171.36 | 250.48 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 336.47 | 169.55 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 164.95 | 108.98 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 555.44 | 250.48 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 517.05 | 428.61 | 499.50 | 323.35 | 176.15 | 0.00 | 0.00 |
February | 647.81 | 414.30 | 610.05 | 372.26 | 237.79 | 0.00 | 0.00 |
March | 334.75 | 346.29 | 377.17 | 109.82 | 267.36 | 0.00 | 0.00 |
April | 925.61 | 305.15 | 783.23 | 354.01 | 429.22 | 0.00 | 0.00 |
May | 713.24 | 268.92 | 647.81 | 210.90 | 436.90 | 0.00 | 0.00 |
June | 666.75 | 223.08 | 596.77 | 144.45 | 452.32 | 0.00 | 0.00 |
July | 769.97 | 211.42 | 646.59 | 202.49 | 444.10 | 0.00 | 0.00 |
August | 950.43 | 232.05 | 757.66 | 340.82 | 416.84 | 0.00 | 0.00 |
September | 1113.67 | 291.94 | 895.35 | 524.51 | 370.84 | 0.00 | 0.00 |
October | 698.03 | 343.52 | 615.14 | 359.52 | 255.62 | 0.00 | 0.00 |
November | 454.01 | 395.54 | 436.14 | 265.31 | 170.82 | 0.00 | 0.00 |
December | 345.94 | 484.59 | 345.68 | 221.48 | 124.20 | 0.00 | 0.00 |
Annual Sum or Average | 677.13 | 328.35 | 600.01 | 284.64 | 315.37 | 0.00 | 0.00 |
Minimum of Months | 334.75 | 211.42 | 345.68 | 109.82 | 124.20 | 0.00 | 0.00 |
Maximum of Months | 1113.67 | 484.59 | 895.35 | 524.51 | 452.32 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 258.02 | 214.80 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 323.30 | 207.67 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 166.87 | 173.32 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 462.67 | 151.97 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 356.53 | 133.98 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 333.37 | 111.08 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 384.91 | 105.27 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 474.99 | 115.59 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 556.43 | 145.65 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 348.73 | 171.44 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 226.61 | 198.18 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 172.59 | 243.52 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 338.27 | 164.16 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 166.87 | 105.27 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 556.43 | 243.52 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 258.26 | 213.91 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 323.60 | 206.75 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 167.18 | 172.47 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 463.42 | 150.80 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 357.42 | 132.79 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 334.29 | 110.04 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 385.49 | 104.55 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 475.31 | 115.07 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 556.92 | 144.80 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 349.31 | 170.05 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 226.84 | 197.21 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 172.74 | 242.69 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 338.75 | 163.21 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 167.18 | 104.55 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 556.92 | 242.69 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 259.05 | 210.41 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 324.63 | 203.14 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 168.23 | 169.18 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 465.15 | 147.59 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 359.60 | 129.52 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 336.63 | 107.16 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 387.02 | 102.49 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 476.24 | 113.36 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 558.35 | 142.10 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 350.81 | 166.10 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 227.59 | 193.71 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 173.27 | 239.08 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 340.06 | 160.11 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 168.23 | 102.49 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 558.35 | 239.08 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 261.81 | 197.04 | 249.75 | 161.67 | 88.08 | 0.00 | 0.00 |
February | 328.09 | 189.23 | 305.03 | 186.13 | 118.89 | 0.00 | 0.00 |
March | 171.77 | 156.97 | 188.59 | 54.91 | 133.68 | 0.00 | 0.00 |
April | 468.77 | 137.24 | 391.62 | 177.01 | 214.61 | 0.00 | 0.00 |
May | 364.44 | 118.72 | 323.90 | 105.45 | 218.45 | 0.00 | 0.00 |
June | 341.79 | 98.06 | 298.38 | 72.23 | 226.16 | 0.00 | 0.00 |
July | 390.52 | 95.16 | 323.29 | 101.24 | 222.05 | 0.00 | 0.00 |
August | 478.76 | 106.30 | 378.83 | 170.41 | 208.42 | 0.00 | 0.00 |
September | 561.71 | 132.77 | 447.68 | 262.26 | 185.42 | 0.00 | 0.00 |
October | 354.28 | 154.10 | 307.57 | 179.76 | 127.81 | 0.00 | 0.00 |
November | 230.00 | 180.99 | 218.07 | 132.66 | 85.41 | 0.00 | 0.00 |
December | 175.15 | 224.43 | 172.84 | 110.74 | 62.10 | 0.00 | 0.00 |
Annual Sum or Average | 343.43 | 149.05 | 300.00 | 142.32 | 157.69 | 0.00 | 0.00 |
Minimum of Months | 171.77 | 95.16 | 172.84 | 54.91 | 62.10 | 0.00 | 0.00 |
Maximum of Months | 561.71 | 224.43 | 447.68 | 262.26 | 226.16 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138317E+10 | 0.118039E+10 | 0.134062E+10 | 0.867838E+09 | 0.472782E+09 | 0.00 | 0.00 |
February | 0.156734E+10 | 0.102604E+10 | 0.147887E+10 | 0.902427E+09 | 0.576443E+09 | 0.00 | 0.00 |
March | 0.895451E+09 | 0.948295E+09 | 0.101230E+10 | 0.294736E+09 | 0.717563E+09 | 0.00 | 0.00 |
April | 0.239960E+10 | 0.805788E+09 | 0.203431E+10 | 0.919485E+09 | 0.111483E+10 | 0.00 | 0.00 |
May | 0.190943E+10 | 0.732949E+09 | 0.173865E+10 | 0.566048E+09 | 0.117260E+10 | 0.00 | 0.00 |
June | 0.173107E+10 | 0.580661E+09 | 0.155000E+10 | 0.375191E+09 | 0.117481E+10 | 0.00 | 0.00 |
July | 0.206973E+10 | 0.562868E+09 | 0.173538E+10 | 0.543453E+09 | 0.119192E+10 | 0.00 | 0.00 |
August | 0.255500E+10 | 0.614452E+09 | 0.203348E+10 | 0.914736E+09 | 0.111875E+10 | 0.00 | 0.00 |
September | 0.289474E+10 | 0.754957E+09 | 0.232553E+10 | 0.136233E+10 | 0.963194E+09 | 0.00 | 0.00 |
October | 0.186970E+10 | 0.940114E+09 | 0.165099E+10 | 0.964930E+09 | 0.686061E+09 | 0.00 | 0.00 |
November | 0.117581E+10 | 0.105367E+10 | 0.113279E+10 | 0.689106E+09 | 0.443686E+09 | 0.00 | 0.00 |
December | 0.924941E+09 | 0.133433E+10 | 0.927770E+09 | 0.594427E+09 | 0.333343E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213760E+11 | 0.105345E+11 | 0.189607E+11 | 0.899471E+10 | 0.996599E+10 | 0.00 | 0.00 |
Minimum of Months | 0.895451E+09 | 0.562868E+09 | 0.927770E+09 | 0.294736E+09 | 0.333343E+09 | 0.00 | 0.00 |
Maximum of Months | 0.289474E+10 | 0.133433E+10 | 0.232553E+10 | 0.136233E+10 | 0.119192E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.682933E+09 | 0.626054E+09 | 0.670310E+09 | 0.433919E+09 | 0.236391E+09 | 0.00 | 0.00 |
February | 0.774508E+09 | 0.545422E+09 | 0.739435E+09 | 0.451213E+09 | 0.288222E+09 | 0.00 | 0.00 |
March | 0.436964E+09 | 0.509037E+09 | 0.506150E+09 | 0.147368E+09 | 0.358782E+09 | 0.00 | 0.00 |
April | 0.118240E+10 | 0.434649E+09 | 0.101716E+10 | 0.459743E+09 | 0.557414E+09 | 0.00 | 0.00 |
May | 0.935964E+09 | 0.396065E+09 | 0.869325E+09 | 0.283024E+09 | 0.586301E+09 | 0.00 | 0.00 |
June | 0.855045E+09 | 0.302975E+09 | 0.775001E+09 | 0.187595E+09 | 0.587406E+09 | 0.00 | 0.00 |
July | 0.102804E+10 | 0.290445E+09 | 0.867689E+09 | 0.271726E+09 | 0.595962E+09 | 0.00 | 0.00 |
August | 0.127211E+10 | 0.315533E+09 | 0.101674E+10 | 0.457368E+09 | 0.559373E+09 | 0.00 | 0.00 |
September | 0.143986E+10 | 0.389924E+09 | 0.116276E+10 | 0.681166E+09 | 0.481597E+09 | 0.00 | 0.00 |
October | 0.922502E+09 | 0.507889E+09 | 0.825496E+09 | 0.482465E+09 | 0.343031E+09 | 0.00 | 0.00 |
November | 0.580356E+09 | 0.563951E+09 | 0.566396E+09 | 0.344553E+09 | 0.221843E+09 | 0.00 | 0.00 |
December | 0.456450E+09 | 0.707780E+09 | 0.463885E+09 | 0.297213E+09 | 0.166672E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105671E+11 | 0.558972E+10 | 0.948035E+10 | 0.449735E+10 | 0.498299E+10 | 0.00 | 0.00 |
Minimum of Months | 0.436964E+09 | 0.290445E+09 | 0.463885E+09 | 0.147368E+09 | 0.166672E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143986E+10 | 0.707780E+09 | 0.116276E+10 | 0.681166E+09 | 0.595962E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.683575E+09 | 0.606965E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.774703E+09 | 0.529313E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.438140E+09 | 0.492470E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.118382E+10 | 0.424907E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.937747E+09 | 0.388572E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.853328E+09 | 0.306225E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.102469E+10 | 0.296781E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.126877E+10 | 0.323173E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.143732E+10 | 0.393914E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.923763E+09 | 0.493497E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.581295E+09 | 0.544140E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.456810E+09 | 0.687761E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105640E+11 | 0.548772E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.438140E+09 | 0.296781E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143732E+10 | 0.687761E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.685032E+09 | 0.598611E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.776064E+09 | 0.522526E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.439769E+09 | 0.485354E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.118718E+10 | 0.417594E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.941328E+09 | 0.381919E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.854623E+09 | 0.303726E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.102540E+10 | 0.295163E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.126914E+10 | 0.321961E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.143805E+10 | 0.391558E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.925965E+09 | 0.485133E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.582585E+09 | 0.535943E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.457776E+09 | 0.678995E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.105829E+11 | 0.541848E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.439769E+09 | 0.295163E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143805E+10 | 0.678995E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.686681E+09 | 0.591487E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.777726E+09 | 0.516607E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.441807E+09 | 0.479115E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.119161E+10 | 0.410038E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.946328E+09 | 0.374498E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.857611E+09 | 0.299573E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.102734E+10 | 0.291903E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127043E+10 | 0.319040E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.143970E+10 | 0.387871E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.928803E+09 | 0.476823E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.584010E+09 | 0.529124E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.458964E+09 | 0.670874E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106110E+11 | 0.534695E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.441807E+09 | 0.291903E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.143970E+10 | 0.670874E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.138487E+10 | 0.114798E+10 | 0.133787E+10 | 0.866058E+09 | 0.471812E+09 | 0.00 | 0.00 |
February | 0.156718E+10 | 0.100228E+10 | 0.147584E+10 | 0.900576E+09 | 0.575261E+09 | 0.00 | 0.00 |
March | 0.896601E+09 | 0.927494E+09 | 0.101022E+10 | 0.294131E+09 | 0.716091E+09 | 0.00 | 0.00 |
April | 0.239917E+10 | 0.790958E+09 | 0.203014E+10 | 0.917599E+09 | 0.111254E+10 | 0.00 | 0.00 |
May | 0.191035E+10 | 0.720282E+09 | 0.173508E+10 | 0.564887E+09 | 0.117020E+10 | 0.00 | 0.00 |
June | 0.172821E+10 | 0.578231E+09 | 0.154682E+10 | 0.374421E+09 | 0.117240E+10 | 0.00 | 0.00 |
July | 0.206229E+10 | 0.566269E+09 | 0.173182E+10 | 0.542338E+09 | 0.118948E+10 | 0.00 | 0.00 |
August | 0.254564E+10 | 0.621533E+09 | 0.202931E+10 | 0.912859E+09 | 0.111645E+10 | 0.00 | 0.00 |
September | 0.288663E+10 | 0.756710E+09 | 0.232076E+10 | 0.135954E+10 | 0.961219E+09 | 0.00 | 0.00 |
October | 0.186960E+10 | 0.920089E+09 | 0.164760E+10 | 0.962950E+09 | 0.684654E+09 | 0.00 | 0.00 |
November | 0.117680E+10 | 0.102525E+10 | 0.113047E+10 | 0.687693E+09 | 0.442776E+09 | 0.00 | 0.00 |
December | 0.926575E+09 | 0.129792E+10 | 0.925867E+09 | 0.593207E+09 | 0.332659E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.213539E+11 | 0.103550E+11 | 0.189218E+11 | 0.897626E+10 | 0.994554E+10 | 0.00 | 0.00 |
Minimum of Months | 0.896601E+09 | 0.566269E+09 | 0.925867E+09 | 0.294131E+09 | 0.332659E+09 | 0.00 | 0.00 |
Maximum of Months | 0.288663E+10 | 0.129792E+10 | 0.232076E+10 | 0.135954E+10 | 0.118948E+10 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.691082E+09 | 0.575330E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.782139E+09 | 0.502405E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.446946E+09 | 0.464228E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.119925E+10 | 0.393896E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.954936E+09 | 0.358853E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.864104E+09 | 0.287915E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.103095E+10 | 0.281956E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127221E+10 | 0.309586E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144227E+10 | 0.377531E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.934049E+09 | 0.459188E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.587370E+09 | 0.513673E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.462278E+09 | 0.652254E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106676E+11 | 0.517682E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.446946E+09 | 0.281956E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144227E+10 | 0.652254E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.691716E+09 | 0.572939E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.782859E+09 | 0.500167E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.447775E+09 | 0.461952E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.120117E+10 | 0.390864E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.957324E+09 | 0.355677E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.866483E+09 | 0.285215E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.103251E+10 | 0.280035E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127308E+10 | 0.308195E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144354E+10 | 0.375310E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.935601E+09 | 0.455473E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.587969E+09 | 0.511167E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.462655E+09 | 0.650028E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.106827E+11 | 0.514702E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.447775E+09 | 0.280035E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144354E+10 | 0.650028E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.693849E+09 | 0.563574E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.785338E+09 | 0.491430E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.450576E+09 | 0.453142E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.120568E+10 | 0.382551E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.963153E+09 | 0.346919E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.872554E+09 | 0.277754E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.103659E+10 | 0.274503E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.127557E+10 | 0.303615E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.144725E+10 | 0.368315E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.939617E+09 | 0.444895E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.589902E+09 | 0.502093E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.464086E+09 | 0.640346E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.107242E+11 | 0.504913E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.450576E+09 | 0.274503E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.144725E+10 | 0.640346E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.701244E+09 | 0.527747E+09 | 0.668935E+09 | 0.433029E+09 | 0.235906E+09 | 0.00 | 0.00 |
February | 0.793725E+09 | 0.457774E+09 | 0.737918E+09 | 0.450288E+09 | 0.287630E+09 | 0.00 | 0.00 |
March | 0.460070E+09 | 0.420434E+09 | 0.505111E+09 | 0.147066E+09 | 0.358046E+09 | 0.00 | 0.00 |
April | 0.121505E+10 | 0.355736E+09 | 0.101507E+10 | 0.458800E+09 | 0.556270E+09 | 0.00 | 0.00 |
May | 0.976118E+09 | 0.317966E+09 | 0.867542E+09 | 0.282443E+09 | 0.585099E+09 | 0.00 | 0.00 |
June | 0.885910E+09 | 0.254180E+09 | 0.773411E+09 | 0.187211E+09 | 0.586201E+09 | 0.00 | 0.00 |
July | 0.104597E+10 | 0.254888E+09 | 0.865909E+09 | 0.271169E+09 | 0.594740E+09 | 0.00 | 0.00 |
August | 0.128231E+10 | 0.284707E+09 | 0.101466E+10 | 0.456430E+09 | 0.558226E+09 | 0.00 | 0.00 |
September | 0.145596E+10 | 0.344141E+09 | 0.116038E+10 | 0.679769E+09 | 0.480609E+09 | 0.00 | 0.00 |
October | 0.948898E+09 | 0.412751E+09 | 0.823802E+09 | 0.481475E+09 | 0.342327E+09 | 0.00 | 0.00 |
November | 0.596157E+09 | 0.469135E+09 | 0.565234E+09 | 0.343846E+09 | 0.221388E+09 | 0.00 | 0.00 |
December | 0.469113E+09 | 0.601104E+09 | 0.462933E+09 | 0.296604E+09 | 0.166330E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.108305E+11 | 0.470056E+10 | 0.946090E+10 | 0.448813E+10 | 0.497277E+10 | 0.00 | 0.00 |
Minimum of Months | 0.460070E+09 | 0.254180E+09 | 0.462933E+09 | 0.147066E+09 | 0.166330E+09 | 0.00 | 0.00 |
Maximum of Months | 0.145596E+10 | 0.601104E+09 | 0.116038E+10 | 0.679769E+09 | 0.594740E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 4.18 | 3.23 | 2.03 | 1.05 | -4.0 | 28.28 | 62.93 | 0.00 |
February | 4.25 | 3.55 | 2.74 | 1.60 | -5.0 | 43.80 | 86.73 | 0.02 |
March | 5.90 | 4.45 | 2.76 | 1.18 | -1.9 | 68.95 | 35.00 | 0.00 |
April | 8.96 | 6.24 | 3.38 | 1.56 | -0.7 | 96.13 | 186.12 | 0.00 |
May | 9.99 | 8.07 | 6.28 | 3.35 | -0.9 | 110.92 | 199.68 | 0.02 |
June | 13.31 | 11.27 | 9.70 | 3.33 | 3.35 | 121.69 | 199.28 | 0.00 |
July | 15.02 | 12.39 | 10.49 | 3.21 | 4.49 | 111.91 | 220.83 | 0.00 |
August | 15.65 | 12.75 | 10.65 | 2.92 | 3.95 | 91.47 | 211.91 | 0.00 |
September | 13.43 | 11.01 | 9.10 | 2.64 | 1.43 | 68.72 | 198.32 | 0.01 |
October | 9.33 | 8.03 | 6.81 | 1.97 | -1.0 | 48.92 | 91.86 | 0.04 |
November | 6.66 | 5.66 | 4.54 | 2.05 | -2.3 | 30.27 | 53.24 | 0.04 |
December | 4.10 | 3.14 | 1.95 | 2.36 | -5.1 | 20.52 | 40.74 | 0.04 |
Annual Sum or Average | 9.26 | 7.50 | 5.89 | 2.27 | -0.6 | 70.25 | 132.30 | 0.02 |
Minimum of Months | 4.10 | 3.14 | 1.95 | 1.05 | -5.1 | 20.52 | 35.00 | 0.00 |
Maximum of Months | 15.65 | 12.75 | 10.65 | 3.35 | 4.49 | 121.69 | 220.83 | 0.04 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 14.00 | 29-JAN-05:00 | 9.37 | 5.00 | 3.60 | 8.35 | 0.00 | 0.00 |
February | 11.00 | 07-FEB-14:00 | 9.86 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 14.00 | 25-MAR-12:00 | 11.22 | 9.00 | 2.60 | 7.35 | 287.00 | 93.00 |
April | 24.00 | 30-APR-14:00 | 13.13 | 4.00 | 1.50 | 7.75 | 167.50 | 716.00 |
May | 24.00 | 22-MAY-14:00 | 16.08 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 27.00 | 13-JUN-16:00 | 17.53 | 12.00 | 3.10 | 12.41 | 141.50 | 652.50 |
July | 30.00 | 22-JUL-17:00 | 16.80 | 8.00 | 0.00 | 14.28 | 122.00 | 407.00 |
August | 27.00 | 14-AUG-17:19 | 14.18 | 3.33 | 2.60 | 10.37 | 133.00 | 358.83 |
September | 23.00 | 11-SEP-16:00 | 16.22 | 12.00 | 2.60 | 8.74 | 108.00 | 325.50 |
October | 19.00 | 07-OCT-14:00 | 10.10 | 1.00 | 1.50 | 2.22 | 131.00 | 540.50 |
November | 16.00 | 24-NOV-11:00 | 12.01 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 13.00 | 23-DEC-10:00 | 7.64 | 2.00 | 7.70 | 6.75 | 70.50 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 11.00 | 7.64 | 1.00 | 0.00 | 2.22 | 0.00 | 0.00 | |
Maximum of Months | 30.00 | 17.53 | 12.00 | 7.70 | 14.28 | 287.00 | 769.00 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | -6.0 | 10-JAN-07:00 | -7.0 | -9.0 | 0.00 | -20.0 | 0.00 | 0.00 |
February | -4.0 | 17-FEB-06:00 | -4.0 | -4.0 | 0.00 | -20.5 | 0.00 | 0.00 |
March | -1.0 | 08-MAR-06:00 | -1.4 | -2.0 | 0.00 | -14.4 | 17.50 | 184.50 |
April | 0.00 | 08-APR-04:00 | -0.9 | -2.0 | 0.00 | -12.7 | 0.00 | 0.00 |
May | 2.00 | 06-MAY-04:00 | 1.57 | 1.00 | 3.60 | -13.7 | 12.50 | 117.00 |
June | 6.00 | 01-JUN-03:00 | 5.05 | 4.00 | 0.00 | -9.2 | 0.00 | 0.00 |
July | 7.00 | 05-JUL-04:00 | 6.47 | 6.00 | 3.10 | -7.8 | 28.00 | 155.00 |
August | 8.00 | 20-AUG-04:00 | 7.45 | 7.00 | 0.00 | -6.6 | 0.00 | 0.00 |
September | 5.00 | 20-SEP-03:00 | 5.00 | 5.00 | 2.60 | -10.0 | 0.00 | 0.00 |
October | 2.00 | 07-OCT-03:00 | 2.00 | 2.00 | 0.00 | -13.4 | 0.00 | 0.00 |
November | -2.0 | 29-NOV-01:00 | -2.0 | -2.0 | 3.10 | -10.7 | 0.00 | 0.00 |
December | -3.0 | 29-DEC-20:00 | -4.5 | -7.0 | 3.60 | -20.2 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | -6.0 | -7.0 | -9.0 | 0.00 | -20.5 | 0.00 | 0.00 | |
Maximum of Months | 8.00 | 7.45 | 7.00 | 3.60 | -6.6 | 28.00 | 184.50 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.44 | 29-JAN-04:00 | 13.00 | 12.00 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.86 | 07-FEB-14:00 | 11.00 | 9.00 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.39 | 28-APR-07:00 | 16.00 | 15.00 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 16.08 | 22-MAY-14:00 | 24.00 | 11.00 | 2.60 | 9.33 | 159.00 | 769.00 |
June | 19.93 | 25-JUN-17:00 | 22.00 | 19.00 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 17.31 | 22-JUL-09:00 | 26.00 | 12.00 | 4.60 | 11.46 | 224.50 | 619.50 |
August | 17.06 | 14-AUG-12:00 | 24.00 | 13.00 | 2.60 | 9.91 | 205.50 | 669.50 |
September | 16.54 | 10-SEP-15:00 | 21.00 | 14.00 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.58 | 17-OCT-14:00 | 16.00 | 12.00 | 0.00 | 12.03 | 144.00 | 44.50 |
November | 12.01 | 24-NOV-11:00 | 16.00 | 9.00 | 4.10 | 9.33 | 61.50 | 0.00 |
December | 7.93 | 02-DEC-12:00 | 9.00 | 7.00 | 0.00 | 2.01 | 135.50 | 84.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.93 | 9.00 | 7.00 | 0.00 | 2.01 | 0.00 | 0.00 | |
Maximum of Months | 19.93 | 26.00 | 19.00 | 4.60 | 15.94 | 224.50 | 769.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 29-JAN-04:00 | 13.00 | 12.44 | 0.00 | 9.13 | 0.00 | 0.00 |
February | 9.00 | 07-FEB-14:00 | 11.00 | 9.86 | 2.10 | 6.35 | 138.00 | 225.00 |
March | 12.00 | 19-MAR-11:00 | 12.00 | 12.00 | 2.60 | 8.15 | 131.00 | 0.00 |
April | 15.00 | 28-APR-07:00 | 16.00 | 15.39 | 0.00 | 5.54 | 119.50 | 626.00 |
May | 12.00 | 23-MAY-07:00 | 17.00 | 13.95 | 3.10 | 5.13 | 112.00 | 719.50 |
June | 19.00 | 25-JUN-17:00 | 22.00 | 19.93 | 0.00 | 15.94 | 136.50 | 360.50 |
July | 14.00 | 17-JUL-17:00 | 18.00 | 15.45 | 3.60 | 9.91 | 120.00 | 0.00 |
August | 16.00 | 08-AUG-12:00 | 18.00 | 16.70 | 1.50 | 11.46 | 154.00 | 0.00 |
September | 14.00 | 10-SEP-15:00 | 21.00 | 16.54 | 3.60 | 8.54 | 160.50 | 483.00 |
October | 13.00 | 17-OCT-18:00 | 13.00 | 13.00 | 2.60 | 9.33 | 0.00 | 0.00 |
November | 12.00 | 08-NOV-14:00 | 12.00 | 12.00 | 0.00 | 8.15 | 93.00 | 106.00 |
December | 7.00 | 02-DEC-11:00 | 8.00 | 7.45 | 3.10 | 1.16 | 144.50 | 146.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 7.00 | 8.00 | 7.45 | 0.00 | 1.16 | 0.00 | 0.00 | |
Maximum of Months | 19.00 | 22.00 | 19.93 | 3.60 | 15.94 | 160.50 | 719.50 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 10.33 | 8.85 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 10.00 | 14.79 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 10.33 | 17.09 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 11.26 | 40.86 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 12.54 | 47.73 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 13.82 | 50.98 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 14.77 | 51.67 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 15.12 | 44.67 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 14.78 | 34.25 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 13.84 | 17.71 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 12.55 | 9.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 11.27 | 6.14 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 12.57 | 28.73 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 10.00 | 6.14 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 15.12 | 51.67 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.363056E+09 | -238922050.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124134311.3 | 58.99 | 0.00 | 0.00 |
February | 0.330657E+09 | -218405379.9 | 0.00 | 0.00 | 672.00 | 0.00 | -112251269.0 | 58.99 | 0.00 | 0.00 |
March | 0.368020E+09 | -244121091.7 | 0.00 | 0.00 | 744.00 | 0.00 | -123899282.6 | 58.99 | 0.00 | 0.00 |
April | 0.344939E+09 | -228768079.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116170870.4 | 58.99 | 0.00 | 0.00 |
May | 0.349300E+09 | -230435655.2 | 0.00 | 0.00 | 744.00 | 0.00 | -118864101.4 | 58.99 | 0.00 | 0.00 |
June | 0.329962E+09 | -219055365.2 | 0.00 | 0.00 | 720.00 | 0.00 | -110906460.8 | 58.99 | 0.00 | 0.00 |
July | 0.330758E+09 | -217099085.6 | 0.00 | 0.00 | 744.00 | 0.00 | -113659353.7 | 58.99 | 0.00 | 0.00 |
August | 0.333354E+09 | -219920912.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113433031.8 | 58.99 | 0.00 | 0.00 |
September | 0.322586E+09 | -212072267.0 | 0.00 | 0.00 | 720.00 | 0.00 | -110513708.7 | 58.99 | 0.00 | 0.00 |
October | 0.342002E+09 | -221711630.4 | 0.00 | 0.00 | 744.00 | 0.00 | -120290512.1 | 58.99 | 0.00 | 0.00 |
November | 0.339546E+09 | -220050155.9 | 0.00 | 0.00 | 720.00 | 0.00 | -119495715.5 | 58.99 | 0.00 | 0.00 |
December | 0.359137E+09 | -234600167.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124537064.5 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.411332E+10 | -0.270516E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.140816E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.322586E+09 | -244121091.7 | 0.00 | 0.00 | 672.00 | 0.00 | -124537064.5 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.368020E+09 | -212072267.0 | 0.00 | 0.00 | 744.00 | 0.00 | -110513708.7 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.360761E+09 | -238920341.9 | 0.00 | 0.00 | 744.00 | 0.00 | -121840552.8 | 58.99 | 0.00 | 0.00 |
February | 0.328548E+09 | -218406839.4 | 0.00 | 0.00 | 672.00 | 0.00 | -110140712.5 | 58.99 | 0.00 | 0.00 |
March | 0.365495E+09 | -244117130.8 | 0.00 | 0.00 | 744.00 | 0.00 | -121377729.6 | 58.99 | 0.00 | 0.00 |
April | 0.341764E+09 | -228762840.2 | 0.00 | 0.00 | 720.00 | 0.00 | -113000888.4 | 58.99 | 0.00 | 0.00 |
May | 0.346259E+09 | -230436315.6 | 0.00 | 0.00 | 744.00 | 0.00 | -115822401.6 | 59.00 | 0.00 | 0.00 |
June | 0.328707E+09 | -219058696.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109648516.3 | 58.99 | 0.00 | 0.00 |
July | 0.329974E+09 | -217084248.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112889839.5 | 58.99 | 0.00 | 0.00 |
August | 0.332741E+09 | -219926057.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112814850.0 | 58.99 | 0.00 | 0.00 |
September | 0.321602E+09 | -212067397.4 | 0.00 | 0.00 | 720.00 | 0.00 | -109534292.6 | 58.99 | 0.00 | 0.00 |
October | 0.338802E+09 | -221712145.5 | 0.00 | 0.00 | 744.00 | 0.00 | -117089901.0 | 58.99 | 0.00 | 0.00 |
November | 0.336999E+09 | -220049249.7 | 0.00 | 0.00 | 720.00 | 0.00 | -116949882.1 | 58.99 | 0.00 | 0.00 |
December | 0.356938E+09 | -234599292.4 | 0.00 | 0.00 | 744.00 | 0.00 | -122338783.3 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.408859E+10 | -0.270514E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.138345E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.321602E+09 | -244117130.8 | 0.00 | 0.00 | 672.00 | 0.00 | -122338783.3 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.365495E+09 | -212067397.4 | 0.00 | 0.00 | 744.00 | 0.00 | -109534292.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.333747E+09 | -210106647.1 | 0.00 | 0.00 | 744.00 | 0.00 | -123640576.2 | 58.99 | 0.00 | 0.00 |
February | 0.303880E+09 | -192218486.5 | 0.00 | 0.00 | 672.00 | 0.00 | -111661668.3 | 58.99 | 0.00 | 0.00 |
March | 0.340952E+09 | -217880459.3 | 0.00 | 0.00 | 744.00 | 0.00 | -123071052.1 | 58.99 | 0.00 | 0.00 |
April | 0.315455E+09 | -201183303.6 | 0.00 | 0.00 | 720.00 | 0.00 | -114271669.6 | 59.00 | 0.00 | 0.00 |
May | 0.321210E+09 | -204356074.3 | 0.00 | 0.00 | 744.00 | 0.00 | -116853911.7 | 58.99 | 0.00 | 0.00 |
June | 0.304501E+09 | -195107460.9 | 0.00 | 0.00 | 720.00 | 0.00 | -109393673.2 | 58.99 | 0.00 | 0.00 |
July | 0.302021E+09 | -189795935.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112225343.0 | 58.99 | 0.00 | 0.00 |
August | 0.308547E+09 | -196438244.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112109161.3 | 58.99 | 0.00 | 0.00 |
September | 0.295639E+09 | -186372486.1 | 0.00 | 0.00 | 720.00 | 0.00 | -109266580.6 | 59.00 | 0.00 | 0.00 |
October | 0.313659E+09 | -194978479.3 | 0.00 | 0.00 | 744.00 | 0.00 | -118680924.2 | 58.99 | 0.00 | 0.00 |
November | 0.313094E+09 | -194326440.7 | 0.00 | 0.00 | 720.00 | 0.00 | -118767719.7 | 58.98 | 0.00 | 0.00 |
December | 0.328896E+09 | -204785750.0 | 0.00 | 0.00 | 744.00 | 0.00 | -124110034.2 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378160E+10 | -0.238755E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139405E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.295639E+09 | -217880459.3 | 0.00 | 0.00 | 672.00 | 0.00 | -124110034.2 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.340952E+09 | -186372486.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109266580.6 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.334205E+09 | -210109301.1 | 0.00 | 0.00 | 744.00 | 0.00 | -124096190.7 | 58.99 | 0.00 | 0.00 |
February | 0.304267E+09 | -192205604.4 | 0.00 | 0.00 | 672.00 | 0.00 | -112061336.8 | 59.00 | 0.00 | 0.00 |
March | 0.341376E+09 | -217882221.9 | 0.00 | 0.00 | 744.00 | 0.00 | -123493834.6 | 58.99 | 0.00 | 0.00 |
April | 0.316047E+09 | -201207366.8 | 0.00 | 0.00 | 720.00 | 0.00 | -114839337.8 | 58.99 | 0.00 | 0.00 |
May | 0.321784E+09 | -204364450.9 | 0.00 | 0.00 | 744.00 | 0.00 | -117419356.4 | 58.99 | 0.00 | 0.00 |
June | 0.304697E+09 | -195105662.7 | 0.00 | 0.00 | 720.00 | 0.00 | -109591677.5 | 58.99 | 0.00 | 0.00 |
July | 0.302140E+09 | -189799728.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112340748.6 | 58.99 | 0.00 | 0.00 |
August | 0.308623E+09 | -196439141.6 | 0.00 | 0.00 | 744.00 | 0.00 | -112183890.2 | 58.99 | 0.00 | 0.00 |
September | 0.295784E+09 | -186377164.0 | 0.00 | 0.00 | 720.00 | 0.00 | -109406535.4 | 58.99 | 0.00 | 0.00 |
October | 0.314236E+09 | -194980554.3 | 0.00 | 0.00 | 744.00 | 0.00 | -119255326.4 | 58.99 | 0.00 | 0.00 |
November | 0.313548E+09 | -194325495.7 | 0.00 | 0.00 | 720.00 | 0.00 | -119222651.7 | 58.98 | 0.00 | 0.00 |
December | 0.329343E+09 | -204769895.5 | 0.00 | 0.00 | 744.00 | 0.00 | -124573551.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.378605E+10 | -0.238757E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.139848E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.295784E+09 | -217882221.9 | 0.00 | 0.00 | 672.00 | 0.00 | -124573551.3 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.341376E+09 | -186377164.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109406535.4 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.324224E+09 | -198567937.4 | 0.00 | 0.00 | 744.00 | 0.00 | -125655859.7 | 59.00 | 0.00 | 0.00 |
February | 0.295159E+09 | -181785317.0 | 0.00 | 0.00 | 672.00 | 0.00 | -113373188.4 | 58.98 | 0.00 | 0.00 |
March | 0.331102E+09 | -206166275.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124935674.4 | 58.99 | 0.00 | 0.00 |
April | 0.307265E+09 | -190392863.4 | 0.00 | 0.00 | 720.00 | 0.00 | -116872577.6 | 58.99 | 0.00 | 0.00 |
May | 0.312740E+09 | -193260456.1 | 0.00 | 0.00 | 744.00 | 0.00 | -119479901.8 | 58.99 | 0.00 | 0.00 |
June | 0.295576E+09 | -184615737.6 | 0.00 | 0.00 | 720.00 | 0.00 | -110959939.1 | 58.99 | 0.00 | 0.00 |
July | 0.292845E+09 | -179482938.9 | 0.00 | 0.00 | 744.00 | 0.00 | -113362303.5 | 59.00 | 0.00 | 0.00 |
August | 0.298891E+09 | -185848496.1 | 0.00 | 0.00 | 744.00 | 0.00 | -113042466.4 | 59.00 | 0.00 | 0.00 |
September | 0.286784E+09 | -176371448.7 | 0.00 | 0.00 | 720.00 | 0.00 | -110412726.9 | 58.99 | 0.00 | 0.00 |
October | 0.305400E+09 | -184280112.0 | 0.00 | 0.00 | 744.00 | 0.00 | -121119680.0 | 58.99 | 0.00 | 0.00 |
November | 0.304141E+09 | -183497079.2 | 0.00 | 0.00 | 720.00 | 0.00 | -120643425.3 | 59.00 | 0.00 | 0.00 |
December | 0.319853E+09 | -193680449.6 | 0.00 | 0.00 | 744.00 | 0.00 | -126172227.8 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367398E+10 | -0.225795E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141603E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.286784E+09 | -206166275.2 | 0.00 | 0.00 | 672.00 | 0.00 | -126172227.8 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.331102E+09 | -176371448.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110412726.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.324214E+09 | -198568517.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125645104.8 | 59.00 | 0.00 | 0.00 |
February | 0.295154E+09 | -181788244.8 | 0.00 | 0.00 | 672.00 | 0.00 | -113366156.4 | 58.98 | 0.00 | 0.00 |
March | 0.331104E+09 | -206166850.2 | 0.00 | 0.00 | 744.00 | 0.00 | -124937418.1 | 58.99 | 0.00 | 0.00 |
April | 0.307400E+09 | -190394988.4 | 0.00 | 0.00 | 720.00 | 0.00 | -117004852.4 | 58.99 | 0.00 | 0.00 |
May | 0.312876E+09 | -193257144.0 | 0.00 | 0.00 | 744.00 | 0.00 | -119618882.9 | 58.99 | 0.00 | 0.00 |
June | 0.295691E+09 | -184615008.3 | 0.00 | 0.00 | 720.00 | 0.00 | -111076341.3 | 58.99 | 0.00 | 0.00 |
July | 0.292924E+09 | -179504495.2 | 0.00 | 0.00 | 744.00 | 0.00 | -113419773.2 | 58.99 | 0.00 | 0.00 |
August | 0.298947E+09 | -185921322.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113026122.6 | 58.97 | 0.00 | 0.00 |
September | 0.286828E+09 | -176370418.8 | 0.00 | 0.00 | 720.00 | 0.00 | -110457697.9 | 58.99 | 0.00 | 0.00 |
October | 0.305493E+09 | -184298577.3 | 0.00 | 0.00 | 744.00 | 0.00 | -121193954.9 | 58.99 | 0.00 | 0.00 |
November | 0.304137E+09 | -183503998.0 | 0.00 | 0.00 | 720.00 | 0.00 | -120633307.6 | 58.99 | 0.00 | 0.00 |
December | 0.319817E+09 | -193676111.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126141014.7 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.367459E+10 | -0.225807E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141652E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.286828E+09 | -206166850.2 | 0.00 | 0.00 | 672.00 | 0.00 | -126141014.7 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.331104E+09 | -176370418.8 | 0.00 | 0.00 | 744.00 | 0.00 | -110457697.9 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.324344E+09 | -198564274.6 | 0.00 | 0.00 | 744.00 | 0.00 | -125780142.6 | 59.00 | 0.00 | 0.00 |
February | 0.295282E+09 | -181761412.1 | 0.00 | 0.00 | 672.00 | 0.00 | -113520104.9 | 58.99 | 0.00 | 0.00 |
March | 0.331225E+09 | -206154806.7 | 0.00 | 0.00 | 744.00 | 0.00 | -125070262.8 | 58.99 | 0.00 | 0.00 |
April | 0.307664E+09 | -190389679.8 | 0.00 | 0.00 | 720.00 | 0.00 | -117274353.8 | 58.99 | 0.00 | 0.00 |
May | 0.313169E+09 | -193263761.9 | 0.00 | 0.00 | 744.00 | 0.00 | -119904996.2 | 58.99 | 0.00 | 0.00 |
June | 0.295961E+09 | -184617937.0 | 0.00 | 0.00 | 720.00 | 0.00 | -111342957.0 | 58.99 | 0.00 | 0.00 |
July | 0.293092E+09 | -179508327.4 | 0.00 | 0.00 | 744.00 | 0.00 | -113583745.6 | 58.99 | 0.00 | 0.00 |
August | 0.299070E+09 | -185847183.5 | 0.00 | 0.00 | 744.00 | 0.00 | -113223178.2 | 59.00 | 0.00 | 0.00 |
September | 0.287008E+09 | -176364556.5 | 0.00 | 0.00 | 720.00 | 0.00 | -110643302.0 | 58.99 | 0.00 | 0.00 |
October | 0.305758E+09 | -184273191.6 | 0.00 | 0.00 | 744.00 | 0.00 | -121484701.1 | 58.99 | 0.00 | 0.00 |
November | 0.304272E+09 | -183514287.5 | 0.00 | 0.00 | 720.00 | 0.00 | -120757983.8 | 58.99 | 0.00 | 0.00 |
December | 0.319914E+09 | -193684440.8 | 0.00 | 0.00 | 744.00 | 0.00 | -126229534.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.367676E+10 | -0.225794E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.141882E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.287008E+09 | -206154806.7 | 0.00 | 0.00 | 672.00 | 0.00 | -126229534.6 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.331225E+09 | -176364556.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110643302.0 | 59.00 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 195.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 217.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 215.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 359.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 417.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 410.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 396.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 337.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 234.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 171.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 3515.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 131.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 429.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.105578E+11 | 54947.72 | 02-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.859076E+10 | 54947.72 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.728622E+10 | 54947.72 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.104287E+10 | 54947.72 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.462778E+09 | 13221.50 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.128718E+10 | 32870.14 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.614600E+10 | 54947.72 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.118333E+11 | 54947.72 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.472070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.118333E+11 | 54947.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.282997E+10 | 29297.42 | 09-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.203429E+10 | 29297.42 | 17-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.159883E+10 | 20044.42 | 16-MAR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 87514852.60 | 3316.96 | 01-APR-08:04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 1464308.04 | 566.73 | 05-MAY-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 79888078.87 | 2554.17 | 23-OCT-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.126782E+10 | 26897.12 | 29-NOV-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.331418E+10 | 29297.42 | 27-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.112140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.331418E+10 | 29297.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.383376E+10 | 28893.94 | 08-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.292937E+10 | 28893.94 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243460E+10 | 21373.95 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.236277E+09 | 4940.19 | 08-APR-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 31418434.25 | 2895.58 | 06-MAY-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.291591E+09 | 5084.45 | 28-OCT-07:50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.205807E+10 | 23672.33 | 29-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.430140E+10 | 28893.94 | 17-DEC-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.161165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.430140E+10 | 28893.94 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.407953E+10 | 29496.98 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.314212E+10 | 29496.98 | 13-FEB-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265568E+10 | 26797.87 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.302590E+09 | 6248.63 | 01-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 53428021.01 | 2854.79 | 17-MAY-07:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.397585E+09 | 5409.54 | 23-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.229031E+10 | 28272.86 | 20-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.452451E+10 | 29496.98 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.174458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.452451E+10 | 29496.98 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.445215E+10 | 28758.41 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.347034E+10 | 28758.41 | 12-FEB-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.301161E+10 | 28758.41 | 05-MAR-09:02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.412848E+09 | 8982.80 | 01-APR-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.114112E+09 | 3476.87 | 06-MAY-07:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.560265E+09 | 8777.79 | 23-OCT-07:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.262078E+10 | 28758.41 | 20-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.489871E+10 | 28758.41 | 03-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.195408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.489871E+10 | 28758.41 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.915112E+10 | 52502.26 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.721550E+10 | 52502.26 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.647517E+10 | 52502.26 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.110675E+10 | 52502.26 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.511838E+09 | 11083.93 | 17-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.157730E+10 | 52502.26 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.577127E+10 | 52502.26 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.996158E+10 | 52502.26 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.417705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.996158E+10 | 52502.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.470548E+10 | 27870.00 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.370717E+10 | 27870.00 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.332612E+10 | 27870.00 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.564741E+09 | 27870.00 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.263957E+09 | 7250.00 | 17-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.798073E+09 | 27870.00 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.295304E+10 | 27870.00 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.513356E+10 | 27870.00 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.214521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.513356E+10 | 27870.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.480957E+10 | 27735.11 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.380577E+10 | 27735.11 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.342958E+10 | 27735.11 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.621403E+09 | 27735.11 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.314802E+09 | 9830.30 | 17-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 802474.65 | 348.50 | 08-JUN-08:40 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.863717E+09 | 27735.11 | 23-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.304696E+10 | 27735.11 | 03-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.522601E+10 | 27735.11 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.221186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.522601E+10 | 27735.11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.522905E+10 | 27471.42 | 01-JAN-10:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.418335E+10 | 27471.42 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.381801E+10 | 27471.42 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.808558E+09 | 27471.42 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.478066E+09 | 18610.81 | 17-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 7953458.63 | 1114.85 | 07-JUN-11:20 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.108412E+10 | 27471.42 | 21-OCT-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.339955E+10 | 27471.42 | 02-NOV-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.563728E+10 | 27471.42 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.563728E+10 | 27471.42 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.685436E+10 | 28136.14 | 01-JAN-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.561860E+10 | 28136.14 | 01-FEB-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.523575E+10 | 28136.14 | 01-MAR-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.129805E+10 | 28136.14 | 01-APR-08:61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.917914E+09 | 28136.14 | 05-MAY-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 42285131.59 | 4023.57 | 07-JUN-08:65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 417299.70 | 471.16 | 05-JUL-08:30 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 6069066.46 | 1174.29 | 08-SEP-08:15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.177327E+10 | 28136.14 | 14-OCT-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.461115E+10 | 28136.14 | 01-NOV-08:62 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.737502E+10 | 28136.14 | 01-DEC-09:01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.337329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.737502E+10 | 28136.14 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.422897E+09 | 0.421530E+09 | 13199.98 | 30-APR-16:07 | 13199.98 | 0.00 |
May | 0.00 | 0.00 | 0.234479E+09 | 0.207212E+09 | 11384.04 | 22-MAY-15:00 | 10523.61 | 0.00 |
June | 0.00 | 0.00 | 0.175941E+10 | 0.148578E+10 | 31292.50 | 13-JUN-08:62 | 26175.76 | 0.00 |
July | 0.00 | 0.00 | 0.282478E+10 | 0.247270E+10 | 31458.37 | 18-JUL-08:62 | 21274.33 | 0.00 |
August | 0.00 | 0.00 | 0.242871E+10 | 0.206285E+10 | 31540.75 | 17-AUG-08:62 | 18673.43 | 0.00 |
September | 0.00 | 0.00 | 0.147726E+10 | 0.126912E+10 | 16066.18 | 13-SEP-08:62 | 10822.46 | 0.00 |
October | 0.00 | 0.00 | 6.46 | 6.46 | 0.01 | 07-OCT-12:10 | 0.01 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.914753E+10 | 0.791919E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.282478E+10 | 0.247270E+10 | 31540.75 | 26175.76 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 378732.36 | 292084.76 | 307.64 | 19-MAR-19:10 | 227.70 | 0.00 |
April | 0.00 | 0.00 | 0.292978E+09 | 0.291354E+09 | 16482.99 | 30-APR-19:07 | 16482.99 | 0.00 |
May | 0.00 | 0.00 | 0.209179E+09 | 0.186708E+09 | 16470.24 | 21-MAY-19:00 | 14920.60 | 0.00 |
June | 0.00 | 0.00 | 0.110677E+10 | 0.937307E+09 | 18131.02 | 25-JUN-17:57 | 10896.40 | 0.00 |
July | 0.00 | 0.00 | 0.176893E+10 | 0.153275E+10 | 17458.53 | 23-JUL-17:02 | 12726.20 | 0.00 |
August | 0.00 | 0.00 | 0.174231E+10 | 0.146465E+10 | 17334.83 | 17-AUG-08:62 | 10381.78 | 0.00 |
September | 0.00 | 0.00 | 0.100860E+10 | 0.859565E+09 | 17344.31 | 10-SEP-17:02 | 11656.68 | 0.00 |
October | 0.00 | 0.00 | 11596578.06 | 10714322.20 | 3110.66 | 05-OCT-20:10 | 3110.66 | 0.00 |
November | 0.00 | 0.00 | 234334.07 | 195565.76 | 215.23 | 08-NOV-21:50 | 169.80 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.614097E+10 | 0.528353E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.176893E+10 | 0.153275E+10 | 18131.02 | 16482.99 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.152007E+09 | 0.150931E+09 | 12320.27 | 30-APR-08:62 | 11178.29 | 0.00 |
May | 0.00 | 0.00 | 0.120754E+09 | 0.106214E+09 | 6085.62 | 22-MAY-15:00 | 5645.10 | 0.00 |
June | 0.00 | 0.00 | 0.865095E+09 | 0.739146E+09 | 17150.25 | 27-JUN-07:02 | 9545.49 | 0.00 |
July | 0.00 | 0.00 | 0.130880E+10 | 0.114521E+10 | 17149.38 | 18-JUL-07:02 | 11217.08 | 0.00 |
August | 0.00 | 0.00 | 0.134084E+10 | 0.113006E+10 | 17039.89 | 17-AUG-07:02 | 10042.34 | 0.00 |
September | 0.00 | 0.00 | 0.808685E+09 | 0.698044E+09 | 16827.84 | 16-SEP-07:03 | 10081.79 | 0.00 |
October | 0.00 | 0.00 | 773199.76 | 770786.73 | 488.80 | 07-OCT-15:00 | 488.80 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.459695E+10 | 0.397037E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.134084E+10 | 0.114521E+10 | 17150.25 | 11217.08 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.145555E+09 | 0.144576E+09 | 11320.95 | 30-APR-08:62 | 10264.36 | 0.00 |
May | 0.00 | 0.00 | 0.106808E+09 | 94448279.20 | 5853.69 | 22-MAY-15:00 | 5427.13 | 0.00 |
June | 0.00 | 0.00 | 0.844900E+09 | 0.722060E+09 | 17205.13 | 27-JUN-07:02 | 9570.42 | 0.00 |
July | 0.00 | 0.00 | 0.128599E+10 | 0.112617E+10 | 17203.44 | 18-JUL-07:02 | 11245.36 | 0.00 |
August | 0.00 | 0.00 | 0.130596E+10 | 0.110180E+10 | 17094.15 | 17-AUG-07:02 | 10070.32 | 0.00 |
September | 0.00 | 0.00 | 0.782311E+09 | 0.676024E+09 | 15931.22 | 16-SEP-07:03 | 9536.21 | 0.00 |
October | 0.00 | 0.00 | 329593.75 | 329593.37 | 357.88 | 07-OCT-15:00 | 357.88 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.447185E+10 | 0.386540E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.130596E+10 | 0.112617E+10 | 17205.13 | 11245.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.132413E+09 | 0.131627E+09 | 8370.77 | 30-APR-08:62 | 7573.17 | 0.00 |
May | 0.00 | 0.00 | 88683679.74 | 79080037.14 | 5498.98 | 22-MAY-15:00 | 5094.51 | 0.00 |
June | 0.00 | 0.00 | 0.796607E+09 | 0.681106E+09 | 17065.53 | 27-JUN-07:02 | 9463.74 | 0.00 |
July | 0.00 | 0.00 | 0.120893E+10 | 0.106218E+10 | 17063.18 | 18-JUL-07:02 | 11125.36 | 0.00 |
August | 0.00 | 0.00 | 0.120520E+10 | 0.102011E+10 | 16954.76 | 17-AUG-07:02 | 9959.59 | 0.00 |
September | 0.00 | 0.00 | 0.722480E+09 | 0.625969E+09 | 12647.19 | 16-SEP-07:03 | 7548.82 | 0.00 |
October | 0.00 | 0.00 | 145714.38 | 145284.79 | 128.39 | 07-OCT-15:00 | 128.39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.415445E+10 | 0.360022E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.120893E+10 | 0.106218E+10 | 17065.53 | 11125.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.212852E+09 | 0.211532E+09 | 14047.38 | 30-APR-09:03 | 13552.71 | 0.00 |
May | 0.00 | 0.00 | 0.132942E+09 | 0.118979E+09 | 10058.41 | 22-MAY-15:00 | 9144.29 | 0.00 |
June | 0.00 | 0.00 | 0.134847E+10 | 0.114428E+10 | 30496.94 | 13-JUN-08:62 | 24549.16 | 0.00 |
July | 0.00 | 0.00 | 0.201056E+10 | 0.176026E+10 | 30484.05 | 18-JUL-08:62 | 20494.64 | 0.00 |
August | 0.00 | 0.00 | 0.203560E+10 | 0.171968E+10 | 30536.24 | 17-AUG-08:62 | 18162.13 | 0.00 |
September | 0.00 | 0.00 | 0.119534E+10 | 0.103373E+10 | 17735.99 | 13-SEP-08:62 | 11840.62 | 0.00 |
October | 0.00 | 0.00 | 390455.89 | 390455.89 | 295.91 | 07-OCT-15:00 | 295.91 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.693615E+10 | 0.598885E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.203560E+10 | 0.176026E+10 | 30536.24 | 24549.16 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.105562E+09 | 0.105008E+09 | 6074.99 | 30-APR-15:00 | 6074.99 | 0.00 |
May | 0.00 | 0.00 | 63849619.33 | 57530449.79 | 5199.96 | 22-MAY-15:00 | 4735.26 | 0.00 |
June | 0.00 | 0.00 | 0.683312E+09 | 0.581306E+09 | 16202.09 | 13-JUN-08:62 | 13037.61 | 0.00 |
July | 0.00 | 0.00 | 0.100706E+10 | 0.886263E+09 | 16195.37 | 18-JUL-08:62 | 10893.64 | 0.00 |
August | 0.00 | 0.00 | 0.100731E+10 | 0.855264E+09 | 16223.20 | 17-AUG-08:62 | 9654.61 | 0.00 |
September | 0.00 | 0.00 | 0.598261E+09 | 0.519392E+09 | 7143.05 | 13-SEP-08:62 | 4772.91 | 0.00 |
October | 0.00 | 0.00 | 51584.80 | 51067.60 | 47.39 | 07-OCT-15:00 | 47.39 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.346541E+10 | 0.300482E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.100731E+10 | 0.886263E+09 | 16223.20 | 13037.61 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.100252E+09 | 99766852.66 | 5953.35 | 30-APR-15:00 | 5953.35 | 0.00 |
May | 0.00 | 0.00 | 59369134.02 | 53652190.44 | 5060.64 | 22-MAY-15:00 | 4606.75 | 0.00 |
June | 0.00 | 0.00 | 0.659943E+09 | 0.561571E+09 | 16104.91 | 13-JUN-08:62 | 12938.36 | 0.00 |
July | 0.00 | 0.00 | 0.974491E+09 | 0.859003E+09 | 16098.87 | 18-JUL-08:62 | 10814.33 | 0.00 |
August | 0.00 | 0.00 | 0.969961E+09 | 0.824672E+09 | 16126.90 | 17-AUG-08:62 | 9584.22 | 0.00 |
September | 0.00 | 0.00 | 0.572359E+09 | 0.497564E+09 | 6180.16 | 13-SEP-14:30 | 5295.62 | 0.00 |
October | 0.00 | 0.00 | 6772.04 | 6772.04 | 6.65 | 06-OCT-13:40 | 6.65 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.333638E+10 | 0.289624E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.974491E+09 | 0.859003E+09 | 16126.90 | 12938.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 88872270.80 | 88530546.82 | 5689.42 | 30-APR-15:00 | 5689.42 | 0.00 |
May | 0.00 | 0.00 | 51521331.53 | 46772543.20 | 4766.55 | 22-MAY-15:00 | 4335.82 | 0.00 |
June | 0.00 | 0.00 | 0.608162E+09 | 0.517740E+09 | 15927.32 | 13-JUN-08:62 | 12738.80 | 0.00 |
July | 0.00 | 0.00 | 0.898239E+09 | 0.795812E+09 | 15921.67 | 18-JUL-08:62 | 10647.36 | 0.00 |
August | 0.00 | 0.00 | 0.872671E+09 | 0.744996E+09 | 13700.43 | 17-AUG-08:62 | 8102.94 | 0.00 |
September | 0.00 | 0.00 | 0.510190E+09 | 0.444531E+09 | 5970.69 | 13-SEP-14:30 | 5114.55 | 0.00 |
October | 0.00 | 0.00 | 29721.60 | 29721.60 | 24.22 | 05-OCT-14:30 | 24.22 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.302968E+10 | 0.263841E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.898239E+09 | 0.795812E+09 | 15927.32 | 12738.80 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 79177934.37 | 78990250.29 | 5469.02 | 30-APR-15:00 | 5469.02 | 0.00 |
May | 0.00 | 0.00 | 51825381.97 | 46867862.83 | 4622.02 | 22-MAY-15:00 | 4204.04 | 0.00 |
June | 0.00 | 0.00 | 0.589939E+09 | 0.503418E+09 | 8881.70 | 26-JUN-08:62 | 7089.50 | 0.00 |
July | 0.00 | 0.00 | 0.859734E+09 | 0.770797E+09 | 16529.76 | 22-JUL-08:62 | 15143.23 | 0.00 |
August | 0.00 | 0.00 | 0.782069E+09 | 0.670321E+09 | 6944.29 | 14-AUG-13:00 | 5841.55 | 0.00 |
September | 0.00 | 0.00 | 0.448430E+09 | 0.390538E+09 | 5822.60 | 13-SEP-14:20 | 4989.72 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 01-DEC-00:03 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.281118E+10 | 0.246093E+10 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.859734E+09 | 0.770797E+09 | 16529.76 | 15143.23 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.364479E+10 | 0.60 | 2007.50 | 12-JAN-19:20 | 0.89 |
February | 0.329706E+10 | 0.60 | 2007.50 | 05-FEB-12:00 | 0.89 |
March | 0.365814E+10 | 0.60 | 2007.50 | 01-MAR-09:55 | 0.89 |
April | 0.352678E+10 | 0.60 | 2007.50 | 11-APR-20:13 | 0.89 |
May | 0.364242E+10 | 0.60 | 2007.50 | 05-MAY-14:20 | 0.88 |
June | 0.354124E+10 | 0.60 | 2007.50 | 09-JUN-14:40 | 0.88 |
July | 0.364242E+10 | 0.60 | 2007.50 | 10-JUL-18:00 | 0.88 |
August | 0.364964E+10 | 0.60 | 2007.50 | 01-AUG-09:00 | 0.88 |
September | 0.353401E+10 | 0.60 | 2007.50 | 23-SEP-10:40 | 0.88 |
October | 0.364242E+10 | 0.60 | 2007.50 | 22-OCT-16:40 | 0.88 |
November | 0.352032E+10 | 0.60 | 2007.50 | 02-NOV-22:00 | 0.89 |
December | 0.365951E+10 | 0.61 | 2007.50 | 12-DEC-18:10 | 0.89 |
Annual Sum or Average | 0.429587E+11 | 0.60 | |||
Minimum of Months | 0.329706E+10 | 0.60 | 2007.50 | 0.88 | |
Maximum of Months | 0.365951E+10 | 0.61 | 2007.50 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.154748E+10 | 0.46 | 1140.06 | 03-JAN-19:20 | 0.92 |
February | 0.139954E+10 | 0.46 | 1140.06 | 02-FEB-16:10 | 0.92 |
March | 0.157262E+10 | 0.48 | 1140.06 | 01-MAR-13:20 | 0.92 |
April | 0.162017E+10 | 0.59 | 1140.06 | 10-APR-14:40 | 0.91 |
May | 0.173117E+10 | 0.60 | 1140.06 | 05-MAY-08:40 | 0.91 |
June | 0.188395E+10 | 0.62 | 1140.06 | 01-JUN-15:10 | 0.91 |
July | 0.199173E+10 | 0.61 | 1140.06 | 06-JUL-09:20 | 0.91 |
August | 0.201327E+10 | 0.61 | 1140.06 | 04-AUG-14:50 | 0.91 |
September | 0.191717E+10 | 0.62 | 1140.06 | 06-SEP-10:20 | 0.91 |
October | 0.163150E+10 | 0.57 | 1140.06 | 27-OCT-16:10 | 0.91 |
November | 0.150271E+10 | 0.47 | 1140.06 | 05-NOV-09:20 | 0.92 |
December | 0.153909E+10 | 0.46 | 1140.06 | 03-DEC-11:30 | 0.92 |
Annual Sum or Average | 0.203504E+11 | 0.55 | |||
Minimum of Months | 0.139954E+10 | 0.46 | 1140.06 | 0.91 | |
Maximum of Months | 0.201327E+10 | 0.62 | 1140.06 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164104E+10 | 0.50 | 1133.94 | 01-JAN-09:40 | 0.92 |
February | 0.148592E+10 | 0.50 | 1133.94 | 01-FEB-09:00 | 0.92 |
March | 0.167370E+10 | 0.50 | 1133.94 | 01-MAR-08:62 | 0.92 |
April | 0.159206E+10 | 0.50 | 1133.94 | 01-APR-07:40 | 0.92 |
May | 0.165737E+10 | 0.50 | 1133.94 | 04-MAY-15:40 | 0.91 |
June | 0.161655E+10 | 0.50 | 1133.94 | 04-JUN-08:63 | 0.91 |
July | 0.163288E+10 | 0.49 | 1133.94 | 02-JUL-09:30 | 0.91 |
August | 0.167370E+10 | 0.50 | 1133.94 | 01-AUG-07:30 | 0.91 |
September | 0.159206E+10 | 0.49 | 1133.94 | 01-SEP-08:05 | 0.91 |
October | 0.164104E+10 | 0.49 | 1133.94 | 07-OCT-14:50 | 0.92 |
November | 0.159206E+10 | 0.50 | 1133.94 | 01-NOV-08:00 | 0.92 |
December | 0.163288E+10 | 0.49 | 1133.94 | 01-DEC-08:15 | 0.92 |
Annual Sum or Average | 0.194313E+11 | 0.50 | |||
Minimum of Months | 0.148592E+10 | 0.49 | 1133.94 | 0.91 | |
Maximum of Months | 0.167370E+10 | 0.50 | 1133.94 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.164633E+10 | 0.50 | 1137.60 | 20-JAN-18:20 | 0.92 |
February | 0.149071E+10 | 0.50 | 1137.60 | 02-FEB-19:20 | 0.92 |
March | 0.167910E+10 | 0.50 | 1137.60 | 09-MAR-17:30 | 0.92 |
April | 0.159719E+10 | 0.50 | 1137.60 | 04-APR-07:40 | 0.92 |
May | 0.166271E+10 | 0.50 | 1137.60 | 04-MAY-15:00 | 0.91 |
June | 0.162176E+10 | 0.50 | 1137.60 | 09-JUN-07:05 | 0.91 |
July | 0.163814E+10 | 0.49 | 1137.60 | 02-JUL-09:40 | 0.91 |
August | 0.167910E+10 | 0.50 | 1137.60 | 02-AUG-14:00 | 0.91 |
September | 0.159719E+10 | 0.49 | 1137.60 | 01-SEP-08:05 | 0.91 |
October | 0.164633E+10 | 0.49 | 1137.60 | 22-OCT-09:07 | 0.92 |
November | 0.159719E+10 | 0.50 | 1137.60 | 01-NOV-07:05 | 0.92 |
December | 0.163814E+10 | 0.49 | 1137.60 | 01-DEC-11:50 | 0.92 |
Annual Sum or Average | 0.194939E+11 | 0.50 | |||
Minimum of Months | 0.149071E+10 | 0.49 | 1137.60 | 0.91 | |
Maximum of Months | 0.167910E+10 | 0.50 | 1137.60 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.163340E+10 | 0.50 | 1128.66 | 01-JAN-10:09 | 0.92 |
February | 0.147900E+10 | 0.50 | 1128.66 | 01-FEB-09:03 | 0.92 |
March | 0.166591E+10 | 0.50 | 1128.66 | 01-MAR-08:10 | 0.92 |
April | 0.158464E+10 | 0.50 | 1128.66 | 01-APR-07:30 | 0.92 |
May | 0.164965E+10 | 0.50 | 1128.66 | 04-MAY-11:50 | 0.91 |
June | 0.160902E+10 | 0.50 | 1128.66 | 08-JUN-15:00 | 0.91 |
July | 0.162528E+10 | 0.49 | 1128.66 | 06-JUL-09:20 | 0.91 |
August | 0.166591E+10 | 0.50 | 1128.66 | 01-AUG-09:20 | 0.91 |
September | 0.158464E+10 | 0.49 | 1128.66 | 01-SEP-08:07 | 0.91 |
October | 0.163340E+10 | 0.49 | 1128.66 | 15-OCT-10:10 | 0.91 |
November | 0.158464E+10 | 0.50 | 1128.66 | 01-NOV-08:00 | 0.92 |
December | 0.162528E+10 | 0.49 | 1128.66 | 01-DEC-08:15 | 0.92 |
Annual Sum or Average | 0.193408E+11 | 0.50 | |||
Minimum of Months | 0.147900E+10 | 0.49 | 1128.66 | 0.91 | |
Maximum of Months | 0.166591E+10 | 0.50 | 1128.66 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.259679E+10 | 0.44 | 1944.28 | 15-JAN-14:15 | 0.88 |
February | 0.235181E+10 | 0.44 | 1944.28 | 03-FEB-11:50 | 0.89 |
March | 0.265278E+10 | 0.45 | 1944.28 | 03-MAR-18:10 | 0.89 |
April | 0.251979E+10 | 0.44 | 1944.28 | 02-APR-13:30 | 0.89 |
May | 0.262478E+10 | 0.45 | 1944.28 | 04-MAY-08:40 | 0.88 |
June | 0.256179E+10 | 0.45 | 1944.28 | 02-JUN-13:50 | 0.88 |
July | 0.258279E+10 | 0.44 | 1944.28 | 17-JUL-16:10 | 0.88 |
August | 0.265278E+10 | 0.45 | 1944.28 | 01-AUG-10:00 | 0.88 |
September | 0.251979E+10 | 0.44 | 1944.28 | 11-SEP-18:10 | 0.88 |
October | 0.259679E+10 | 0.44 | 1944.28 | 16-OCT-15:40 | 0.88 |
November | 0.251979E+10 | 0.44 | 1944.28 | 02-NOV-11:00 | 0.88 |
December | 0.258279E+10 | 0.44 | 1944.28 | 06-DEC-14:50 | 0.88 |
Annual Sum or Average | 0.307625E+11 | 0.44 | |||
Minimum of Months | 0.235181E+10 | 0.44 | 1944.28 | 0.88 | |
Maximum of Months | 0.265278E+10 | 0.45 | 1944.28 | 0.89 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.142744E+10 | 0.46 | 1068.76 | 01-JAN-09:01 | 0.92 |
February | 0.129278E+10 | 0.46 | 1068.76 | 01-FEB-09:03 | 0.92 |
March | 0.145822E+10 | 0.47 | 1068.76 | 28-MAR-12:40 | 0.92 |
April | 0.138512E+10 | 0.46 | 1068.76 | 04-APR-09:50 | 0.92 |
May | 0.144283E+10 | 0.46 | 1068.76 | 18-MAY-12:10 | 0.91 |
June | 0.140820E+10 | 0.46 | 1068.76 | 02-JUN-19:00 | 0.91 |
July | 0.141975E+10 | 0.45 | 1068.76 | 01-JUL-15:20 | 0.91 |
August | 0.145822E+10 | 0.46 | 1068.76 | 01-AUG-08:30 | 0.91 |
September | 0.138512E+10 | 0.46 | 1068.76 | 01-SEP-09:40 | 0.91 |
October | 0.142744E+10 | 0.46 | 1068.76 | 20-OCT-16:20 | 0.91 |
November | 0.138512E+10 | 0.46 | 1068.76 | 14-NOV-11:40 | 0.91 |
December | 0.141975E+10 | 0.45 | 1068.76 | 01-DEC-09:05 | 0.92 |
Annual Sum or Average | 0.169100E+11 | 0.46 | |||
Minimum of Months | 0.129278E+10 | 0.45 | 1068.76 | 0.91 | |
Maximum of Months | 0.145822E+10 | 0.47 | 1068.76 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.141915E+10 | 0.46 | 1062.56 | 01-JAN-10:03 | 0.92 |
February | 0.128527E+10 | 0.46 | 1062.56 | 01-FEB-09:15 | 0.92 |
March | 0.144976E+10 | 0.47 | 1062.56 | 01-MAR-15:10 | 0.91 |
April | 0.137708E+10 | 0.46 | 1062.56 | 01-APR-08:09 | 0.92 |
May | 0.143445E+10 | 0.46 | 1062.56 | 03-MAY-08:50 | 0.91 |
June | 0.140003E+10 | 0.46 | 1062.56 | 08-JUN-08:40 | 0.92 |
July | 0.141150E+10 | 0.45 | 1062.56 | 06-JUL-14:00 | 0.91 |
August | 0.144976E+10 | 0.46 | 1062.56 | 01-AUG-10:00 | 0.91 |
September | 0.137708E+10 | 0.46 | 1062.56 | 06-SEP-13:40 | 0.91 |
October | 0.141915E+10 | 0.46 | 1062.56 | 09-OCT-16:10 | 0.91 |
November | 0.137708E+10 | 0.46 | 1062.56 | 01-NOV-17:20 | 0.91 |
December | 0.141150E+10 | 0.45 | 1062.56 | 01-DEC-10:10 | 0.92 |
Annual Sum or Average | 0.168118E+11 | 0.46 | |||
Minimum of Months | 0.128527E+10 | 0.45 | 1062.56 | 0.91 | |
Maximum of Months | 0.144976E+10 | 0.47 | 1062.56 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.140426E+10 | 0.46 | 1051.41 | 01-JAN-10:15 | 0.92 |
February | 0.127179E+10 | 0.46 | 1051.41 | 01-FEB-09:03 | 0.92 |
March | 0.143454E+10 | 0.47 | 1051.41 | 28-MAR-11:00 | 0.92 |
April | 0.136263E+10 | 0.46 | 1051.41 | 01-APR-08:05 | 0.92 |
May | 0.141940E+10 | 0.46 | 1051.41 | 30-MAY-13:50 | 0.91 |
June | 0.138534E+10 | 0.46 | 1051.41 | 07-JUN-08:30 | 0.92 |
July | 0.139669E+10 | 0.45 | 1051.41 | 01-JUL-14:00 | 0.91 |
August | 0.143454E+10 | 0.46 | 1051.41 | 12-AUG-14:50 | 0.91 |
September | 0.136263E+10 | 0.46 | 1051.41 | 01-SEP-08:62 | 0.91 |
October | 0.140426E+10 | 0.46 | 1051.41 | 17-OCT-19:20 | 0.91 |
November | 0.136263E+10 | 0.46 | 1051.41 | 10-NOV-14:50 | 0.91 |
December | 0.139669E+10 | 0.45 | 1051.41 | 10-DEC-12:50 | 0.92 |
Annual Sum or Average | 0.166354E+11 | 0.46 | |||
Minimum of Months | 0.127179E+10 | 0.45 | 1051.41 | 0.91 | |
Maximum of Months | 0.143454E+10 | 0.47 | 1051.41 | 0.92 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.146273E+10 | 0.46 | 1095.19 | 03-JAN-08:07 | 0.92 |
February | 0.132474E+10 | 0.46 | 1095.19 | 03-FEB-09:05 | 0.92 |
March | 0.149427E+10 | 0.47 | 1095.19 | 01-MAR-18:10 | 0.92 |
April | 0.141936E+10 | 0.46 | 1095.19 | 01-APR-12:10 | 0.92 |
May | 0.147850E+10 | 0.46 | 1095.19 | 01-MAY-11:40 | 0.92 |
June | 0.144302E+10 | 0.46 | 1095.19 | 05-JUN-08:50 | 0.91 |
July | 0.145484E+10 | 0.45 | 1095.19 | 06-JUL-12:50 | 0.91 |
August | 0.149427E+10 | 0.46 | 1095.19 | 05-AUG-12:10 | 0.91 |
September | 0.141936E+10 | 0.46 | 1095.19 | 08-SEP-09:20 | 0.91 |
October | 0.146273E+10 | 0.46 | 1095.19 | 04-OCT-08:15 | 0.92 |
November | 0.141936E+10 | 0.46 | 1095.19 | 01-NOV-10:40 | 0.92 |
December | 0.145484E+10 | 0.45 | 1095.19 | 01-DEC-08:40 | 0.92 |
Annual Sum or Average | 0.173280E+11 | 0.46 | |||
Minimum of Months | 0.132474E+10 | 0.45 | 1095.19 | 0.91 | |
Maximum of Months | 0.149427E+10 | 0.47 | 1095.19 | 0.92 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.364479E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.329706E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.365814E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.363895E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.370566E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.400080E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.439524E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.429548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.392440E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.364242E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.352032E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.365951E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.453828E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.329706E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.439524E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.154748E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.139954E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.157273E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.169443E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.178392E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.216094E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.243949E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.245232E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.217217E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.163459E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.150277E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.153909E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.218995E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.139954E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.245232E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164104E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.148592E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167370E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163139E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.168898E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183671E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.197104E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.201877E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179949E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.164125E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159206E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163288E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206132E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.148592E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201877E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.164633E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.149071E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.167910E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.163491E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.169073E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.183707E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.197064E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.201548E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.179813E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.164642E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.159719E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.163814E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.206449E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.149071E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.201548E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.163340E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.147900E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.166591E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.161906E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.167298E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.181255E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.193863E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.197714E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.177076E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.163344E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.158464E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.162528E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.204128E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.147900E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.197714E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.259679E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.235181E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.265278E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.257681E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.266078E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.291699E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.311892E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.319393E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.283712E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.259690E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.251979E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.258279E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.326054E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.235181E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.319393E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.142744E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.129278E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.145822E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.141265E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145964E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.158351E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.168128E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.171892E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.153974E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.142746E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.138512E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141975E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.178065E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.129278E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.171892E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.141915E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.128527E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144976E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.140326E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.145010E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.156958E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.166481E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.170109E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.152520E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.141916E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.137708E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.141150E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.176760E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.128527E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.170109E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.140426E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.127179E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.143454E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.138592E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.143302E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.154216E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.163089E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.166144E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.149507E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.140427E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.136263E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.139669E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.174227E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.127179E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.166144E+10 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.146273E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.132474E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.149427E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.144018E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.149228E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.159599E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.167932E+10 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.169865E+10 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.153646E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.146273E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.141936E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.145484E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.180615E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.132474E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.169865E+10 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.364479E+10 | 0.00 | 0.105578E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329706E+10 | 0.00 | 0.859076E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365814E+10 | 0.00 | 0.728622E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352678E+10 | 0.422897E+09 | 0.104287E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364242E+10 | 0.234479E+09 | 0.462778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354124E+10 | 0.175941E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364242E+10 | 0.282478E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.364964E+10 | 0.242871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.353401E+10 | 0.147726E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364242E+10 | 6.46 | 0.128718E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352032E+10 | 0.00 | 0.614600E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365951E+10 | 0.00 | 0.118333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429587E+11 | 0.914753E+10 | 0.472070E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365951E+10 | 0.282478E+10 | 0.118333E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.154748E+10 | 0.00 | 0.282997E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139954E+10 | 0.00 | 0.203429E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157262E+10 | 378732.36 | 0.159883E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162017E+10 | 0.292978E+09 | 87514852.60 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173117E+10 | 0.209179E+09 | 1464308.04 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188395E+10 | 0.110677E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199173E+10 | 0.176893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201327E+10 | 0.174231E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191717E+10 | 0.100860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163150E+10 | 11596578.06 | 79888078.87 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150271E+10 | 234334.07 | 0.126782E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153909E+10 | 0.00 | 0.331418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203504E+11 | 0.614097E+10 | 0.112140E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201327E+10 | 0.176893E+10 | 0.331418E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164104E+10 | 0.00 | 0.383376E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148592E+10 | 0.00 | 0.292937E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167370E+10 | 0.00 | 0.243460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159206E+10 | 0.152007E+09 | 0.236277E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165737E+10 | 0.120754E+09 | 31418434.25 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161655E+10 | 0.865095E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163288E+10 | 0.130880E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167370E+10 | 0.134084E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159206E+10 | 0.808685E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164104E+10 | 773199.76 | 0.291591E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159206E+10 | 0.00 | 0.205807E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163288E+10 | 0.00 | 0.430140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194313E+11 | 0.459695E+10 | 0.161165E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167370E+10 | 0.134084E+10 | 0.430140E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.164633E+10 | 0.00 | 0.407953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149071E+10 | 0.00 | 0.314212E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167910E+10 | 0.00 | 0.265568E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159719E+10 | 0.145555E+09 | 0.302590E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166271E+10 | 0.106808E+09 | 53428021.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162176E+10 | 0.844900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163814E+10 | 0.128599E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167910E+10 | 0.130596E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159719E+10 | 0.782311E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164633E+10 | 329593.75 | 0.397585E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159719E+10 | 0.00 | 0.229031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163814E+10 | 0.00 | 0.452451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194939E+11 | 0.447185E+10 | 0.174458E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167910E+10 | 0.130596E+10 | 0.452451E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.163340E+10 | 0.00 | 0.445215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147900E+10 | 0.00 | 0.347034E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166591E+10 | 0.00 | 0.301161E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158464E+10 | 0.132413E+09 | 0.412848E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164965E+10 | 88683679.74 | 0.114112E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160902E+10 | 0.796607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162528E+10 | 0.120893E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166591E+10 | 0.120520E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158464E+10 | 0.722480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163340E+10 | 145714.38 | 0.560265E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158464E+10 | 0.00 | 0.262078E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162528E+10 | 0.00 | 0.489871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193408E+11 | 0.415445E+10 | 0.195408E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166591E+10 | 0.120893E+10 | 0.489871E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.259679E+10 | 0.00 | 0.915112E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235181E+10 | 0.00 | 0.721550E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265278E+10 | 0.00 | 0.647517E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251979E+10 | 0.212852E+09 | 0.110675E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.262478E+10 | 0.132942E+09 | 0.511838E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256179E+10 | 0.134847E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.258279E+10 | 0.201056E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.265278E+10 | 0.203560E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251979E+10 | 0.119534E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259679E+10 | 390455.89 | 0.157730E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251979E+10 | 0.00 | 0.577127E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258279E+10 | 0.00 | 0.996158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307625E+11 | 0.693615E+10 | 0.417705E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.265278E+10 | 0.203560E+10 | 0.996158E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.142744E+10 | 0.00 | 0.470548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129278E+10 | 0.00 | 0.370717E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145822E+10 | 0.00 | 0.332612E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138512E+10 | 0.105562E+09 | 0.564741E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144283E+10 | 63849619.33 | 0.263957E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140820E+10 | 0.683312E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141975E+10 | 0.100706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145822E+10 | 0.100731E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138512E+10 | 0.598261E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142744E+10 | 51584.80 | 0.798073E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138512E+10 | 0.00 | 0.295304E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141975E+10 | 0.00 | 0.513356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169100E+11 | 0.346541E+10 | 0.214521E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145822E+10 | 0.100731E+10 | 0.513356E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.141915E+10 | 0.00 | 0.480957E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128527E+10 | 0.00 | 0.380577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144976E+10 | 0.00 | 0.342958E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137708E+10 | 0.100252E+09 | 0.621403E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143445E+10 | 59369134.02 | 0.314802E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140003E+10 | 0.659943E+09 | 802474.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141150E+10 | 0.974491E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144976E+10 | 0.969961E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137708E+10 | 0.572359E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141915E+10 | 6772.04 | 0.863717E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137708E+10 | 0.00 | 0.304696E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141150E+10 | 0.00 | 0.522601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168118E+11 | 0.333638E+10 | 0.221186E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144976E+10 | 0.974491E+09 | 0.522601E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.140426E+10 | 0.00 | 0.522905E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127179E+10 | 0.00 | 0.418335E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143454E+10 | 0.00 | 0.381801E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136263E+10 | 88872270.80 | 0.808558E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141940E+10 | 51521331.53 | 0.478066E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138534E+10 | 0.608162E+09 | 7953458.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139669E+10 | 0.898239E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143454E+10 | 0.872671E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136263E+10 | 0.510190E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140426E+10 | 29721.60 | 0.108412E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136263E+10 | 0.00 | 0.339955E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139669E+10 | 0.00 | 0.563728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166354E+11 | 0.302968E+10 | 0.246459E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143454E+10 | 0.898239E+09 | 0.563728E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.146273E+10 | 0.00 | 0.685436E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132474E+10 | 0.00 | 0.561860E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149427E+10 | 0.00 | 0.523575E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141936E+10 | 79177934.37 | 0.129805E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147850E+10 | 51825381.97 | 0.917914E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144302E+10 | 0.589939E+09 | 42285131.59 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145484E+10 | 0.859734E+09 | 417299.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149427E+10 | 0.782069E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141936E+10 | 0.448430E+09 | 6069066.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146273E+10 | 0.00 | 0.177327E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141936E+10 | 0.00 | 0.461115E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145484E+10 | 0.00 | 0.737502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173280E+11 | 0.281118E+10 | 0.337329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149427E+10 | 0.859734E+09 | 0.737502E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.364479E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.329706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.365814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.352678E+10 | 0.00 | 0.00 | 0.00 | 0.112165E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.364242E+10 | 0.00 | 0.00 | 0.00 | 63242755.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.354124E+10 | 0.00 | 0.00 | 0.00 | 0.459563E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.364242E+10 | 0.00 | 0.00 | 0.00 | 0.752827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.364964E+10 | 0.00 | 0.00 | 0.00 | 0.645840E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.353401E+10 | 0.00 | 0.00 | 0.00 | 0.390393E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.364242E+10 | 0.00 | 0.00 | 0.00 | 1.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.352032E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.365951E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.429587E+11 | 0.00 | 0.00 | 0.00 | 0.242403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.329706E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.365951E+10 | 0.00 | 0.00 | 0.00 | 0.752827E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.154748E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.139954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.157262E+10 | 0.00 | 0.00 | 0.00 | 103878.88 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.162017E+10 | 0.00 | 0.00 | 0.00 | 74261247.05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.173117E+10 | 0.00 | 0.00 | 0.00 | 52748962.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.188395E+10 | 0.00 | 0.00 | 0.00 | 0.276991E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.199173E+10 | 0.00 | 0.00 | 0.00 | 0.447755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.201327E+10 | 0.00 | 0.00 | 0.00 | 0.439051E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.191717E+10 | 0.00 | 0.00 | 0.00 | 0.254998E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163150E+10 | 0.00 | 0.00 | 0.00 | 3094586.38 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.150271E+10 | 0.00 | 0.00 | 0.00 | 64335.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.153909E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.203504E+11 | 0.00 | 0.00 | 0.00 | 0.154907E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.139954E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.201327E+10 | 0.00 | 0.00 | 0.00 | 0.447755E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.148592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159206E+10 | 0.00 | 0.00 | 0.00 | 39331701.51 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.165737E+10 | 0.00 | 0.00 | 0.00 | 31610582.93 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.161655E+10 | 0.00 | 0.00 | 0.00 | 0.220164E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163288E+10 | 0.00 | 0.00 | 0.00 | 0.338160E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167370E+10 | 0.00 | 0.00 | 0.00 | 0.345072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159206E+10 | 0.00 | 0.00 | 0.00 | 0.207428E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164104E+10 | 0.00 | 0.00 | 0.00 | 210833.71 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163288E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194313E+11 | 0.00 | 0.00 | 0.00 | 0.118198E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.148592E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167370E+10 | 0.00 | 0.00 | 0.00 | 0.345072E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.164633E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.149071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.167910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.159719E+10 | 0.00 | 0.00 | 0.00 | 37719983.91 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.166271E+10 | 0.00 | 0.00 | 0.00 | 28020855.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.162176E+10 | 0.00 | 0.00 | 0.00 | 0.215305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.163814E+10 | 0.00 | 0.00 | 0.00 | 0.332496E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.167910E+10 | 0.00 | 0.00 | 0.00 | 0.336386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.159719E+10 | 0.00 | 0.00 | 0.00 | 0.200946E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.164633E+10 | 0.00 | 0.00 | 0.00 | 89831.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.159719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.163814E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.194939E+11 | 0.00 | 0.00 | 0.00 | 0.115096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.149071E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.167910E+10 | 0.00 | 0.00 | 0.00 | 0.336386E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.163340E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.147900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.166591E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.158464E+10 | 0.00 | 0.00 | 0.00 | 34418084.63 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.164965E+10 | 0.00 | 0.00 | 0.00 | 23326526.57 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.160902E+10 | 0.00 | 0.00 | 0.00 | 0.203528E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.162528E+10 | 0.00 | 0.00 | 0.00 | 0.313350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.166591E+10 | 0.00 | 0.00 | 0.00 | 0.311230E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.158464E+10 | 0.00 | 0.00 | 0.00 | 0.186117E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.163340E+10 | 0.00 | 0.00 | 0.00 | 39939.46 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.158464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.162528E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.193408E+11 | 0.00 | 0.00 | 0.00 | 0.107201E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.147900E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.166591E+10 | 0.00 | 0.00 | 0.00 | 0.313350E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.259679E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.235181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.265278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.251979E+10 | 0.00 | 0.00 | 0.00 | 57017196.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.262478E+10 | 0.00 | 0.00 | 0.00 | 35999666.08 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.256179E+10 | 0.00 | 0.00 | 0.00 | 0.355197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.258279E+10 | 0.00 | 0.00 | 0.00 | 0.536129E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.265278E+10 | 0.00 | 0.00 | 0.00 | 0.541147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.251979E+10 | 0.00 | 0.00 | 0.00 | 0.317323E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.259679E+10 | 0.00 | 0.00 | 0.00 | 110136.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.251979E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.258279E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.307625E+11 | 0.00 | 0.00 | 0.00 | 0.184292E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.235181E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.265278E+10 | 0.00 | 0.00 | 0.00 | 0.541147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.142744E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.129278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.145822E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.138512E+10 | 0.00 | 0.00 | 0.00 | 27528706.75 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.144283E+10 | 0.00 | 0.00 | 0.00 | 16809620.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140820E+10 | 0.00 | 0.00 | 0.00 | 0.175305E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141975E+10 | 0.00 | 0.00 | 0.00 | 0.261529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.145822E+10 | 0.00 | 0.00 | 0.00 | 0.260697E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.138512E+10 | 0.00 | 0.00 | 0.00 | 0.154617E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.142744E+10 | 0.00 | 0.00 | 0.00 | 14151.68 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.138512E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141975E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.169100E+11 | 0.00 | 0.00 | 0.00 | 0.896500E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.129278E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.145822E+10 | 0.00 | 0.00 | 0.00 | 0.261529E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.141915E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.128527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.144976E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.137708E+10 | 0.00 | 0.00 | 0.00 | 26185279.70 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.143445E+10 | 0.00 | 0.00 | 0.00 | 15646103.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.140003E+10 | 0.00 | 0.00 | 0.00 | 0.169553E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.141150E+10 | 0.00 | 0.00 | 0.00 | 0.253304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.144976E+10 | 0.00 | 0.00 | 0.00 | 0.251333E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.137708E+10 | 0.00 | 0.00 | 0.00 | 0.148124E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.141915E+10 | 0.00 | 0.00 | 0.00 | 1859.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.137708E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.141150E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.168118E+11 | 0.00 | 0.00 | 0.00 | 0.864148E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.128527E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.144976E+10 | 0.00 | 0.00 | 0.00 | 0.253304E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.140426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.127179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.143454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.136263E+10 | 0.00 | 0.00 | 0.00 | 23290697.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.141940E+10 | 0.00 | 0.00 | 0.00 | 13616050.21 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.138534E+10 | 0.00 | 0.00 | 0.00 | 0.156817E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.139669E+10 | 0.00 | 0.00 | 0.00 | 0.234193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.143454E+10 | 0.00 | 0.00 | 0.00 | 0.226900E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.136263E+10 | 0.00 | 0.00 | 0.00 | 0.132437E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.140426E+10 | 0.00 | 0.00 | 0.00 | 8144.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.136263E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.139669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.166354E+11 | 0.00 | 0.00 | 0.00 | 0.787262E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.127179E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.143454E+10 | 0.00 | 0.00 | 0.00 | 0.234193E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.146273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.132474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.149427E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.141936E+10 | 0.00 | 0.00 | 0.00 | 20821812.48 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.147850E+10 | 0.00 | 0.00 | 0.00 | 13775532.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.144302E+10 | 0.00 | 0.00 | 0.00 | 0.152969E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.145484E+10 | 0.00 | 0.00 | 0.00 | 0.224480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.149427E+10 | 0.00 | 0.00 | 0.00 | 0.204377E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.141936E+10 | 0.00 | 0.00 | 0.00 | 0.117099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.146273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.141936E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.145484E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.173280E+11 | 0.00 | 0.00 | 0.00 | 0.733522E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.132474E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.149427E+10 | 0.00 | 0.00 | 0.00 | 0.224480E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.838797E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.625600E+10 | 0.00 | 0.00 | 0.52 |
February | 0.801573E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.495363E+10 | 0.00 | 0.00 | 0.53 |
March | 0.849312E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441556E+10 | 0.00 | 0.00 | 0.53 |
April | 0.846296E+10 | 0.00 | 0.00 | 3032786.17 | 1343206.96 | 0.395412E+09 | 0.209068E+10 | 0.00 | 0.61 |
May | 0.820801E+10 | 98131.08 | 0.00 | 3447717.14 | 0.00 | 54753873.03 | 0.303308E+10 | 0.00 | 0.63 |
June | 0.265999E+10 | 71042322.25 | 0.00 | 10386202.58 | 838259.94 | 0.00 | 0.819181E+10 | 0.00 | 0.81 |
July | 0.944107E+09 | 92648928.25 | 0.00 | 16588737.16 | 1051663.48 | 0.00 | 0.110071E+11 | 0.00 | 1.04 |
August | 0.326778E+09 | 776510.15 | 0.00 | 18832907.84 | 0.00 | 0.00 | 0.121816E+11 | 0.00 | 1.22 |
September | 0.146178E+10 | 0.00 | 0.00 | 12618654.63 | 0.00 | 0.00 | 0.991162E+10 | 0.00 | 0.92 |
October | 0.875676E+10 | 0.00 | 0.00 | 1233063.86 | 0.00 | 0.486835E+09 | 0.155658E+10 | 0.00 | 0.54 |
November | 0.840273E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.366532E+10 | 0.00 | 0.00 | 0.52 |
December | 0.703107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.772810E+10 | 0.00 | 0.00 | 0.53 |
Annual Sum or Average | 0.711510E+11 | 0.164566E+09 | 0.00 | 66140069.37 | 3233130.38 | 0.279556E+11 | 0.479725E+11 | 0.00 | 0.70 |
Minimum of Months | 0.326778E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.52 |
Maximum of Months | 0.875676E+10 | 92648928.25 | 0.00 | 18832907.84 | 1343206.96 | 0.772810E+10 | 0.121816E+11 | 0.00 | 1.22 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.340103E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.197060E+10 | 0.00 | 0.00 | 0.38 |
February | 0.361757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.104392E+10 | 0.00 | 0.00 | 0.39 |
March | 0.398500E+10 | 0.00 | 0.00 | 9992.85 | 0.00 | 0.791960E+09 | 9454406.98 | 0.00 | 0.39 |
April | 0.276696E+10 | 183665.70 | 0.00 | 2817596.13 | 70541.41 | 6853707.42 | 0.215315E+10 | 0.00 | 0.56 |
May | 0.253256E+10 | 94074.41 | 0.00 | 3348359.11 | 0.00 | 0.00 | 0.286422E+10 | 0.00 | 0.60 |
June | 0.373329E+09 | 32891820.68 | 0.00 | 7650792.22 | 451898.85 | 0.00 | 0.576156E+10 | 0.00 | 0.92 |
July | 77839674.09 | 43015325.28 | 0.00 | 10115157.80 | 440234.35 | 0.00 | 0.669812E+10 | 0.00 | 1.17 |
August | 32863004.56 | 655892.79 | 0.00 | 11252546.20 | 0.00 | 0.00 | 0.701339E+10 | 0.00 | 1.38 |
September | 0.190151E+09 | 0.00 | 0.00 | 8812375.96 | 0.00 | 0.00 | 0.638118E+10 | 0.00 | 1.07 |
October | 0.283027E+10 | 0.00 | 0.00 | 2062831.71 | 0.00 | 5494939.29 | 0.193970E+10 | 0.00 | 0.48 |
November | 0.395396E+10 | 0.00 | 0.00 | 7091.27 | 0.00 | 0.508610E+09 | 6158566.53 | 0.00 | 0.39 |
December | 0.261865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.267133E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.263802E+11 | 76840778.86 | 0.00 | 46076743.25 | 962674.61 | 0.699878E+10 | 0.328269E+11 | 0.00 | 0.68 |
Minimum of Months | 32863004.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.398500E+10 | 43015325.28 | 0.00 | 11252546.20 | 451898.85 | 0.267133E+10 | 0.701339E+10 | 0.00 | 1.38 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.286863E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.264582E+10 | 0.00 | 0.00 | 0.41 |
February | 0.298621E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.182014E+10 | 0.00 | 0.00 | 0.41 |
March | 0.338125E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.152889E+10 | 0.00 | 0.00 | 0.42 |
April | 0.309212E+10 | 0.00 | 0.00 | 1246178.68 | 446937.38 | 90018585.70 | 0.103591E+10 | 0.00 | 0.51 |
May | 0.299944E+10 | 119561.58 | 0.00 | 1500801.76 | 0.00 | 1201118.42 | 0.141101E+10 | 0.00 | 0.53 |
June | 0.833137E+09 | 21815396.36 | 0.00 | 4665399.21 | 14217.70 | 0.00 | 0.351892E+10 | 0.00 | 0.72 |
July | 0.412989E+09 | 38252124.82 | 0.00 | 6558199.17 | 1774549.75 | 0.00 | 0.429116E+10 | 0.00 | 0.92 |
August | 0.318346E+09 | 741157.40 | 0.00 | 7683535.52 | 0.00 | 0.00 | 0.472221E+10 | 0.00 | 1.12 |
September | 0.662580E+09 | 0.00 | 0.00 | 5607248.60 | 0.00 | 0.00 | 0.393341E+10 | 0.00 | 0.85 |
October | 0.314111E+10 | 0.00 | 0.00 | 931027.69 | 0.00 | 55522571.31 | 0.980255E+09 | 0.00 | 0.45 |
November | 0.328225E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.126631E+10 | 0.00 | 0.00 | 0.41 |
December | 0.212758E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.335090E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.261056E+11 | 60928240.16 | 0.00 | 28192390.63 | 2235704.83 | 0.107588E+11 | 0.198929E+11 | 0.00 | 0.60 |
Minimum of Months | 0.318346E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.338125E+10 | 38252124.82 | 0.00 | 7683535.52 | 1774549.75 | 0.335090E+10 | 0.472221E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.259585E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.292044E+10 | 0.00 | 0.00 | 0.41 |
February | 0.267637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.213158E+10 | 0.00 | 0.00 | 0.41 |
March | 0.309760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.181178E+10 | 0.00 | 0.00 | 0.42 |
April | 0.308037E+10 | 0.00 | 0.00 | 1113166.71 | 482214.65 | 0.161970E+09 | 0.905047E+09 | 0.00 | 0.50 |
May | 0.306931E+10 | 100487.90 | 0.00 | 1351391.82 | 0.00 | 4458173.99 | 0.126547E+10 | 0.00 | 0.52 |
June | 0.904793E+09 | 21589322.19 | 0.00 | 4435386.25 | 13330.58 | 0.00 | 0.337779E+10 | 0.00 | 0.71 |
July | 0.441862E+09 | 38112769.92 | 0.00 | 6409686.23 | 1777699.21 | 0.00 | 0.422430E+10 | 0.00 | 0.91 |
August | 0.325043E+09 | 710133.28 | 0.00 | 7573889.55 | 0.00 | 0.00 | 0.470066E+10 | 0.00 | 1.12 |
September | 0.677659E+09 | 0.00 | 0.00 | 5429318.36 | 0.00 | 0.00 | 0.386246E+10 | 0.00 | 0.84 |
October | 0.308692E+10 | 0.00 | 0.00 | 831240.31 | 0.00 | 0.113354E+09 | 0.914313E+09 | 0.00 | 0.45 |
November | 0.298929E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.155544E+10 | 0.00 | 0.00 | 0.41 |
December | 0.188953E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.359151E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.248346E+11 | 60512713.29 | 0.00 | 27144079.22 | 2273244.44 | 0.122905E+11 | 0.192500E+11 | 0.00 | 0.60 |
Minimum of Months | 0.325043E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.309760E+10 | 38112769.92 | 0.00 | 7573889.55 | 1777699.21 | 0.359151E+10 | 0.470066E+10 | 0.00 | 1.12 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.213989E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.337231E+10 | 0.00 | 0.00 | 0.41 |
February | 0.222381E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.258110E+10 | 0.00 | 0.00 | 0.41 |
March | 0.262959E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.227371E+10 | 0.00 | 0.00 | 0.42 |
April | 0.305840E+10 | 0.00 | 0.00 | 914935.24 | 559339.07 | 0.230904E+09 | 0.745033E+09 | 0.00 | 0.49 |
May | 0.316237E+10 | 80803.05 | 0.00 | 1136838.16 | 0.00 | 10821520.28 | 0.103863E+10 | 0.00 | 0.51 |
June | 0.108948E+10 | 20803420.07 | 0.00 | 3836591.57 | 9941.24 | 0.00 | 0.299590E+10 | 0.00 | 0.69 |
July | 0.543145E+09 | 37756692.50 | 0.00 | 5867861.60 | 1827582.78 | 0.00 | 0.396183E+10 | 0.00 | 0.88 |
August | 0.355601E+09 | 637947.76 | 0.00 | 7094600.94 | 0.00 | 0.00 | 0.452831E+10 | 0.00 | 1.09 |
September | 0.756832E+09 | 0.00 | 0.00 | 4947885.03 | 0.00 | 0.00 | 0.360445E+10 | 0.00 | 0.81 |
October | 0.299212E+10 | 0.00 | 0.00 | 656800.65 | 0.00 | 0.252283E+09 | 0.768605E+09 | 0.00 | 0.44 |
November | 0.264206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.189495E+10 | 0.00 | 0.00 | 0.41 |
December | 0.149895E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397863E+10 | 0.00 | 0.00 | 0.41 |
Annual Sum or Average | 0.230922E+11 | 59278863.37 | 0.00 | 24455513.20 | 2396863.08 | 0.145947E+11 | 0.176428E+11 | 0.00 | 0.58 |
Minimum of Months | 0.355601E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.41 |
Maximum of Months | 0.316237E+10 | 37756692.50 | 0.00 | 7094600.94 | 1827582.78 | 0.397863E+10 | 0.452831E+10 | 0.00 | 1.09 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.282432E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.750088E+10 | 0.00 | 0.00 | 0.38 |
February | 0.320203E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.580538E+10 | 0.00 | 0.00 | 0.38 |
March | 0.425374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.497308E+10 | 0.00 | 0.00 | 0.39 |
April | 0.577332E+10 | 0.00 | 0.00 | 1205905.40 | 900123.95 | 0.491022E+09 | 0.105316E+10 | 0.00 | 0.43 |
May | 0.588498E+10 | 0.00 | 0.00 | 1629609.35 | 0.00 | 53522307.76 | 0.166610E+10 | 0.00 | 0.44 |
June | 0.249979E+10 | 24189127.29 | 0.00 | 5554562.70 | 0.00 | 0.00 | 0.454622E+10 | 0.00 | 0.57 |
July | 0.919876E+09 | 44621972.54 | 0.00 | 9371892.16 | 2378563.57 | 0.00 | 0.684758E+10 | 0.00 | 0.73 |
August | 0.262483E+09 | 23647.67 | 0.00 | 11728962.48 | 26996.72 | 0.00 | 0.816736E+10 | 0.00 | 0.90 |
September | 0.123525E+10 | 0.00 | 0.00 | 7525384.67 | 0.00 | 0.00 | 0.619873E+10 | 0.00 | 0.67 |
October | 0.563503E+10 | 0.00 | 0.00 | 611046.30 | 0.00 | 0.709559E+09 | 0.946559E+09 | 0.00 | 0.39 |
November | 0.423899E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428114E+10 | 0.00 | 0.00 | 0.38 |
December | 0.130537E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.895022E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.380352E+11 | 68834747.51 | 0.00 | 37627363.06 | 3305684.25 | 0.327648E+11 | 0.294257E+11 | 0.00 | 0.50 |
Minimum of Months | 0.262483E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.588498E+10 | 44621972.54 | 0.00 | 11728962.48 | 2378563.57 | 0.895022E+10 | 0.816736E+10 | 0.00 | 0.90 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.117882E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.397536E+10 | 0.00 | 0.00 | 0.38 |
February | 0.138881E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.310702E+10 | 0.00 | 0.00 | 0.38 |
March | 0.187232E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.273192E+10 | 0.00 | 0.00 | 0.39 |
April | 0.286019E+10 | 0.00 | 0.00 | 583384.47 | 486942.65 | 0.282531E+09 | 0.505496E+09 | 0.00 | 0.44 |
May | 0.290238E+10 | 0.00 | 0.00 | 781823.75 | 0.00 | 56953184.08 | 0.833227E+09 | 0.00 | 0.45 |
June | 0.128182E+10 | 12420145.39 | 0.00 | 2698753.45 | 0.00 | 0.00 | 0.225956E+10 | 0.00 | 0.58 |
July | 0.466494E+09 | 23108891.49 | 0.00 | 4659165.66 | 1254567.81 | 0.00 | 0.351280E+10 | 0.00 | 0.75 |
August | 0.133075E+09 | 15056.21 | 0.00 | 5906178.75 | 21480.19 | 0.00 | 0.423383E+10 | 0.00 | 0.94 |
September | 0.615334E+09 | 0.00 | 0.00 | 3764175.84 | 0.00 | 0.00 | 0.317616E+10 | 0.00 | 0.69 |
October | 0.269619E+10 | 0.00 | 0.00 | 273846.81 | 0.00 | 0.485031E+09 | 0.452262E+09 | 0.00 | 0.39 |
November | 0.183816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241300E+10 | 0.00 | 0.00 | 0.38 |
December | 0.554895E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.456446E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.177885E+11 | 35544093.09 | 0.00 | 18667328.74 | 1762990.65 | 0.176163E+11 | 0.149733E+11 | 0.00 | 0.51 |
Minimum of Months | 0.133075E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.290238E+10 | 23108891.49 | 0.00 | 5906178.75 | 1254567.81 | 0.456446E+10 | 0.423383E+10 | 0.00 | 0.94 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.108617E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406757E+10 | 0.00 | 0.00 | 0.38 |
February | 0.127637E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.321933E+10 | 0.00 | 0.00 | 0.38 |
March | 0.172463E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.287924E+10 | 0.00 | 0.00 | 0.39 |
April | 0.284662E+10 | 0.00 | 0.00 | 541129.62 | 525305.51 | 0.300798E+09 | 0.468624E+09 | 0.00 | 0.43 |
May | 0.289182E+10 | 0.00 | 0.00 | 715677.60 | 0.00 | 78136249.05 | 0.777859E+09 | 0.00 | 0.44 |
June | 0.139953E+10 | 12164285.09 | 0.00 | 2463874.23 | 0.00 | 0.00 | 0.206295E+10 | 0.00 | 0.57 |
July | 0.499640E+09 | 22940337.23 | 0.00 | 4441527.75 | 1269407.94 | 0.00 | 0.340445E+10 | 0.00 | 0.74 |
August | 0.148351E+09 | 12143.90 | 0.00 | 5708975.70 | 19820.68 | 0.00 | 0.415187E+10 | 0.00 | 0.92 |
September | 0.685558E+09 | 0.00 | 0.00 | 3531635.76 | 0.00 | 0.00 | 0.303015E+10 | 0.00 | 0.68 |
October | 0.267840E+10 | 0.00 | 0.00 | 197922.03 | 0.00 | 0.589861E+09 | 0.335860E+09 | 0.00 | 0.39 |
November | 0.174671E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250403E+10 | 0.00 | 0.00 | 0.38 |
December | 0.477036E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.464212E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.174608E+11 | 35116766.22 | 0.00 | 17600742.71 | 1814534.13 | 0.182811E+11 | 0.142318E+11 | 0.00 | 0.51 |
Minimum of Months | 0.148351E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.289182E+10 | 22940337.23 | 0.00 | 5708975.70 | 1269407.94 | 0.464212E+10 | 0.415187E+10 | 0.00 | 0.92 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.708723E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.444400E+10 | 0.00 | 0.00 | 0.38 |
February | 0.788520E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.370643E+10 | 0.00 | 0.00 | 0.38 |
March | 0.131104E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329142E+10 | 0.00 | 0.00 | 0.39 |
April | 0.270654E+10 | 0.00 | 0.00 | 461900.81 | 630641.84 | 0.427527E+09 | 0.416757E+09 | 0.00 | 0.43 |
May | 0.282096E+10 | 0.00 | 0.00 | 576832.41 | 0.00 | 0.172833E+09 | 0.653676E+09 | 0.00 | 0.43 |
June | 0.163342E+10 | 11658569.32 | 0.00 | 1925825.47 | 0.00 | 0.00 | 0.165428E+10 | 0.00 | 0.55 |
July | 0.623925E+09 | 22594271.10 | 0.00 | 3852402.70 | 1294680.41 | 0.00 | 0.308977E+10 | 0.00 | 0.71 |
August | 0.218306E+09 | 4913.90 | 0.00 | 5117278.34 | 8455.75 | 0.00 | 0.389147E+10 | 0.00 | 0.88 |
September | 0.938754E+09 | 0.00 | 0.00 | 2921028.53 | 0.00 | 0.00 | 0.258274E+10 | 0.00 | 0.64 |
October | 0.258926E+10 | 0.00 | 0.00 | 96612.14 | 0.00 | 0.796525E+09 | 0.157991E+09 | 0.00 | 0.39 |
November | 0.136048E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.288886E+10 | 0.00 | 0.00 | 0.38 |
December | 0.274099E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.484427E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.159740E+11 | 34257754.32 | 0.00 | 14951880.41 | 1933777.99 | 0.205719E+11 | 0.124467E+11 | 0.00 | 0.50 |
Minimum of Months | 0.218306E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.282096E+10 | 22594271.10 | 0.00 | 5117278.34 | 1294680.41 | 0.484427E+10 | 0.389147E+10 | 0.00 | 0.88 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 50568917.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.509210E+10 | 0.00 | 0.00 | 0.38 |
February | 60074568.13 | 0.00 | 0.00 | 0.00 | 0.00 | 0.441725E+10 | 0.00 | 0.00 | 0.38 |
March | 0.234269E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.435228E+10 | 0.00 | 0.00 | 0.39 |
April | 0.219376E+10 | 0.00 | 0.00 | 409329.70 | 858810.46 | 0.905691E+09 | 0.390139E+09 | 0.00 | 0.43 |
May | 0.238767E+10 | 0.00 | 0.00 | 400294.95 | 0.00 | 0.649807E+09 | 0.479931E+09 | 0.00 | 0.43 |
June | 0.196602E+10 | 11637353.75 | 0.00 | 1440878.46 | 38220.53 | 10542108.89 | 0.110148E+10 | 0.00 | 0.54 |
July | 0.777595E+09 | 24142451.81 | 0.00 | 3124361.24 | 1301007.97 | 0.00 | 0.268337E+10 | 0.00 | 0.68 |
August | 0.323898E+09 | 10995.54 | 0.00 | 4340883.75 | 4326.39 | 0.00 | 0.354526E+10 | 0.00 | 0.85 |
September | 0.127166E+10 | 0.00 | 0.00 | 2243291.79 | 0.00 | 0.00 | 0.199849E+10 | 0.00 | 0.62 |
October | 0.179249E+10 | 0.00 | 0.00 | 36012.60 | 0.00 | 0.158571E+10 | 69801091.25 | 0.00 | 0.38 |
November | 0.326607E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.389681E+10 | 0.00 | 0.00 | 0.38 |
December | 9638334.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.508178E+10 | 0.00 | 0.00 | 0.38 |
Annual Sum or Average | 0.113942E+11 | 35790801.10 | 0.00 | 11995052.49 | 2202365.35 | 0.259920E+11 | 0.102685E+11 | 0.00 | 0.49 |
Minimum of Months | 9638334.90 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.38 |
Maximum of Months | 0.238767E+10 | 24142451.81 | 0.00 | 4340883.75 | 1301007.97 | 0.509210E+10 | 0.354526E+10 | 0.00 | 0.85 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:46
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.748887E+11 | 0.256440E+11 | 0.00 | 0.701947E+11 | 0.141257E+11 |
February | 0.126463E+12 | 0.229452E+11 | 0.00 | 0.614947E+11 | 0.111743E+11 |
March | 0.165977E+12 | 0.222024E+11 | 0.00 | 0.623250E+11 | 0.981838E+10 |
April | 0.453844E+12 | 0.169308E+11 | 0.00 | 0.503759E+11 | 0.380570E+10 |
May | 0.549935E+12 | 0.197921E+11 | 0.00 | 0.522490E+11 | 0.220165E+10 |
June | 0.563843E+12 | 0.149842E+11 | 0.00 | 0.499291E+11 | 0.116608E+11 |
July | 0.573135E+12 | 0.123927E+11 | 0.00 | 0.551064E+11 | 0.178418E+11 |
August | 0.468218E+12 | 0.100709E+11 | 0.00 | 0.596854E+11 | 0.172526E+11 |
September | 0.340367E+12 | 0.131673E+11 | 0.00 | 0.532358E+11 | 0.102349E+11 |
October | 0.143890E+12 | 0.186658E+11 | 0.00 | 0.500839E+11 | 0.219514E+10 |
November | 0.485093E+11 | 0.229376E+11 | 0.00 | 0.578910E+11 | 0.854153E+10 |
December | 0.741680E+10 | 0.281494E+11 | 0.00 | 0.699618E+11 | 0.155514E+11 |
Annual Sum or Average | 0.351649E+13 | 0.227882E+12 | 0.00 | 0.692533E+12 | 0.124404E+12 |
Minimum of Months | 0.741680E+10 | 0.100709E+11 | 0.00 | 0.499291E+11 | 0.219514E+10 |
Maximum of Months | 0.573135E+12 | 0.281494E+11 | 0.00 | 0.701947E+11 | 0.178418E+11 |