Program Version:EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40
Tabular Output Report in Format: HTML
Building: RetailStripmall
Environment: RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940
Simulation Timestamp: 2023-10-16 08:40:25
Report: Annual Building Utility Performance Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Values gathered over 8760.00 hoursTotal Energy [GJ] | Energy Per Total Building Area [MJ/m2] | Energy Per Conditioned Building Area [MJ/m2] | |
Total Site Energy | 1894.97 | 906.54 | 906.54 |
Net Site Energy | 1894.97 | 906.54 | 906.54 |
Total Source Energy | 6001.36 | 2871.03 | 2871.03 |
Net Source Energy | 6001.36 | 2871.03 | 2871.03 |
Site=>Source Conversion Factor | |
Electricity | 3.167 |
Natural Gas | 1.084 |
District Cooling | 1.056 |
District Heating | 3.613 |
Steam | 1.200 |
Gasoline | 1.050 |
Diesel | 1.050 |
Coal | 1.050 |
Fuel Oil No 1 | 1.050 |
Fuel Oil No 2 | 1.050 |
Propane | 1.050 |
Other Fuel 1 | 1.000 |
Other Fuel 2 | 1.000 |
Area [m2] | |
Total Building Area | 2090.32 |
Net Conditioned Building Area | 2090.32 |
Unconditioned Building Area | 0.00 |
Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 791.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 121.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 333.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 57.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 1894.97 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Subcategory | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 791.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 121.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 333.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 57.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Space Type | Electricity [GJ] | Natural Gas [GJ] | Gasoline [GJ] | Diesel [GJ] | Coal [GJ] | Fuel Oil No 1 [GJ] | Fuel Oil No 2 [GJ] | Propane [GJ] | Other Fuel 1 [GJ] | Other Fuel 2 [GJ] | District Cooling [GJ] | District Heating [GJ] | Water [m3] | |
Heating | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | Unassigned | 791.55 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | GENERAL | 462.31 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | Unassigned | 121.56 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | GENERAL | 128.72 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | Unassigned | 333.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Unassigned | 57.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 87.30 |
Refrigeration | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | Unassigned | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 565.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 906.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity Intensity [MJ/m2] | Natural Gas Intensity [MJ/m2] | Gasoline Intensity [MJ/m2] | Diesel Intensity [MJ/m2] | Coal Intensity [MJ/m2] | Fuel Oil No 1 Intensity [MJ/m2] | Fuel Oil No 2 Intensity [MJ/m2] | Propane Intensity [MJ/m2] | Other Fuel 1 Intensity [MJ/m2] | Other Fuel 2 Intensity [MJ/m2] | District Cooling Intensity [MJ/m2] | District Heating Intensity [MJ/m2] | Water Intensity [m3/m2] | |
Lighting | 279.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
HVAC | 565.65 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Other | 61.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total | 906.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.04 |
Electricity [GJ] | Percent Electricity [%] | |
Fuel-Fired Power Generation | 0.000 | 0.00 |
High Temperature Geothermal* | 0.000 | 0.00 |
Photovoltaic Power | 0.000 | 0.00 |
Wind Power | 0.000 | 0.00 |
Power Conversion | 0.000 | 0.00 |
Net Decrease in On-Site Storage | 0.000 | 0.00 |
Total On-Site Electric Sources | 0.000 | 0.00 |
Electricity Coming From Utility | 1894.967 | 100.00 |
Surplus Electricity Going To Utility | 0.000 | 0.00 |
Net Electricity From Utility | 1894.967 | 100.00 |
Total On-Site and Utility Electric Sources | 1894.967 | 100.00 |
Total Electricity End Uses | 1894.967 | 100.00 |
Heat [GJ] | Percent Heat [%] | |
Water-Side Heat Recovery | 0.00 | |
Air to Air Heat Recovery for Cooling | 0.00 | |
Air to Air Heat Recovery for Heating | 0.00 | |
High-Temperature Geothermal* | 0.00 | |
Solar Water Thermal | 0.00 | |
Solar Air Thermal | 0.00 | |
Total On-Site Thermal Sources | 0.00 |
Water [m3] | Percent Water [%] | |
Rainwater Collection | 0.00 | 0.00 |
Condensate Collection | 0.00 | 0.00 |
Groundwater Well | 0.00 | 0.00 |
Total On Site Water Sources | 0.00 | 0.00 |
- | - | - |
Initial Storage | 0.00 | 0.00 |
Final Storage | 0.00 | 0.00 |
Change in Storage | 0.00 | 0.00 |
- | - | - |
Water Supplied by Utility | 87.30 | 100.00 |
- | - | - |
Total On Site, Change in Storage, and Utility Water Sources | 87.30 | 100.00 |
Total Water End Uses | 87.30 | 100.00 |
Degrees [deltaC] | |
Tolerance for Zone Heating Setpoint Not Met Time | 0.56 |
Tolerance for Zone Cooling Setpoint Not Met Time | 0.56 |
Facility [Hours] | |
Time Setpoint Not Met During Occupied Heating | 0.00 |
Time Setpoint Not Met During Occupied Cooling | 11.17 |
Time Not Comfortable Based on Simple ASHRAE 55-2004 | 1052.17 |
Table of Contents
TopNAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
| Environment |NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
| Environment |NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
| Environment |NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
| Environment |NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
| Environment |NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
| Environment |NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
| Environment |ZoneCoolingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneHeatingSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ZoneElectricSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |PeakSpaceGainsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |SpaceGainComponentsAtCoolingPeakMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |EnergyConsumptionElectricityNaturalGasMonthly
| Meter |EndUseEnergyConsumptionElectricityMonthly
| Meter |EndUseEnergyConsumptionNaturalGasMonthly
| Meter |PeakEnergyEndUseElectricityPart1Monthly
| Meter |PeakEnergyEndUseElectricityPart2Monthly
| Meter |ElectricComponentsOfPeakDemandMonthly
| Meter |PeakEnergyEndUseNaturalGasMonthly
| Meter |SetpointsNotMetWithTemperaturesMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |ComfortReportSimple55Monthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |OccupantComfortDataSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |DXReportMonthly
| PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |WindowReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowEnergyReportMonthly
| LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR |WindowZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |WindowEnergyZoneSummaryMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AverageOutdoorConditionsMonthly
| Environment |OutdoorConditionsMaximumDryBulbMonthly
| Environment |OutdoorConditionsMinimumDryBulbMonthly
| Environment |OutdoorConditionsMaximumWetBulbMonthly
| Environment |OutdoorConditionsMaximumDewPointMonthly
| Environment |OutdoorGroundConditionsMonthly
| Environment |WaterHeaterReportMonthly
| GAS TANK1 | GAS TANK2 | GAS TANK3 | GAS TANK4 | GAS TANK5 | GAS TANK6 | GAS TANK7 |DaylightingReportMonthly
| Environment |CoilReportMonthly
| PSZ-AC_1:1 HEATING COIL | PSZ-AC_2:2 HEATING COIL | PSZ-AC_3:3 HEATING COIL | PSZ-AC_4:4 HEATING COIL | PSZ-AC_5:5 HEATING COIL | PSZ-AC_6:6 HEATING COIL | PSZ-AC_7:7 HEATING COIL | PSZ-AC_8:8 HEATING COIL | PSZ-AC_9:9 HEATING COIL | PSZ-AC_10:10 HEATING COIL | PSZ-AC_1:1 COOLING COIL | PSZ-AC_2:2 COOLING COIL | PSZ-AC_3:3 COOLING COIL | PSZ-AC_4:4 COOLING COIL | PSZ-AC_5:5 COOLING COIL | PSZ-AC_6:6 COOLING COIL | PSZ-AC_7:7 COOLING COIL | PSZ-AC_8:8 COOLING COIL | PSZ-AC_9:9 COOLING COIL | PSZ-AC_10:10 COOLING COIL |FanReportMonthly
| PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN |ZoneTemperatureOscillationReportMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |AirLoopSystemEnergyAndWaterUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentLoadsMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |AirLoopSystemComponentEnergyUseMonthly
| PSZ-AC_1:1 | PSZ-AC_2:2 | PSZ-AC_3:3 | PSZ-AC_4:4 | PSZ-AC_5:5 | PSZ-AC_6:6 | PSZ-AC_7:7 | PSZ-AC_8:8 | PSZ-AC_9:9 | PSZ-AC_10:10 |MechanicalVentilationLoadsMonthly
| LGSTORE1 | SMSTORE1 | SMSTORE2 | SMSTORE3 | SMSTORE4 | LGSTORE2 | SMSTORE5 | SMSTORE6 | SMSTORE7 | SMSTORE8 |HeatEmissionsReportMonthly
| Environment |Report: Input Verification and Results Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
GeneralValue | |
Program Version and Build | EnergyPlus, Version 22.1.0-ed759b17ee, YMD=2023.10.16 08:40 |
RunPeriod | RUNPERIOD 1 |
Weather File | Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Latitude [deg] | 25.25 |
Longitude [deg] | 55.33 |
Elevation [m] | 5.00 |
Time Zone | 4.00 |
North Axis Angle [deg] | 0.00 |
Rotation for Appendix G [deg] | 0.00 |
Hours Simulated [hrs] | 8760.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | North (315 to 45 deg) | East (45 to 135 deg) | South (135 to 225 deg) | West (225 to 315 deg) | |
Gross Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Above Ground Wall Area [m2] | 1184.15 | 473.66 | 118.41 | 473.66 | 118.41 |
Window Opening Area [m2] | 124.40 | 0.00 | 0.00 | 124.40 | 0.00 |
Gross Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Above Ground Window-Wall Ratio [%] | 10.51 | 0.00 | 0.00 | 26.26 | 0.00 |
Total | |
Gross Roof Area [m2] | 2090.32 |
Skylight Area [m2] | 0.00 |
Skylight-Roof Ratio [%] | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Volume [m3] | Multipliers | Above Ground Gross Wall Area [m2] | Underground Gross Wall Area [m2] | Window Glass Area [m2] | Opening Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
LGSTORE1 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 276.30 | 0.00 | 20.77 | 20.77 | 18.4936 | 6.19 | 4.3000 |
SMSTORE1 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.38 | 10.38 | 21.1217 | 6.19 | 4.3000 |
SMSTORE2 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE3 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
SMSTORE4 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 19.2663 | 6.19 | 4.3000 |
LGSTORE2 | 348.39 | Yes | Yes | 1805.20 | 1.00 | 157.89 | 0.00 | 20.72 | 20.72 | 12.8251 | 6.19 | 4.3000 |
SMSTORE5 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE6 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE7 | 174.19 | Yes | Yes | 902.60 | 1.00 | 78.94 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
SMSTORE8 | 174.19 | Yes | Yes | 902.60 | 1.00 | 197.36 | 0.00 | 10.36 | 10.36 | 13.0124 | 6.19 | 4.3000 |
Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Conditioned Total | 2090.32 | 10831.20 | 1184.15 | 0.00 | 124.40 | 124.40 | 16.1339 | 6.19 | 4.3000 | |||
Unconditioned Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||||||
Not Part of Total | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Area [m2] | Conditioned (Y/N) | Part of Total Floor Area (Y/N) | Multipliers | Zone Name | Space Type | Radiant/Solar Enclosure Name | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | Tags | |
LGSTORE1 | 348.39 | Yes | Yes | 1.00 | LGSTORE1 | GENERAL | LGSTORE1 | 18.4936 | 6.19 | 4.3000 | |
SMSTORE1 | 174.19 | Yes | Yes | 1.00 | SMSTORE1 | GENERAL | SMSTORE1 | 21.1217 | 6.19 | 4.3000 | |
SMSTORE2 | 174.19 | Yes | Yes | 1.00 | SMSTORE2 | GENERAL | SMSTORE2 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE3 | 174.19 | Yes | Yes | 1.00 | SMSTORE3 | GENERAL | SMSTORE3 | 19.2663 | 6.19 | 4.3000 | |
SMSTORE4 | 174.19 | Yes | Yes | 1.00 | SMSTORE4 | GENERAL | SMSTORE4 | 19.2663 | 6.19 | 4.3000 | |
LGSTORE2 | 348.39 | Yes | Yes | 1.00 | LGSTORE2 | GENERAL | LGSTORE2 | 12.8251 | 6.19 | 4.3000 | |
SMSTORE5 | 174.19 | Yes | Yes | 1.00 | SMSTORE5 | GENERAL | SMSTORE5 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE6 | 174.19 | Yes | Yes | 1.00 | SMSTORE6 | GENERAL | SMSTORE6 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE7 | 174.19 | Yes | Yes | 1.00 | SMSTORE7 | GENERAL | SMSTORE7 | 13.0124 | 6.19 | 4.3000 | |
SMSTORE8 | 174.19 | Yes | Yes | 1.00 | SMSTORE8 | GENERAL | SMSTORE8 | 13.0124 | 6.19 | 4.3000 | |
Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Conditioned Total | 2090.32 | 16.1339 | 3.10 | 4.3000 | |||||||
Unconditioned Total | 0.00 | 0.0000 | 0.00 | 0.0000 | |||||||
Not Part of Total | 0.00 | 0.0000 | 0.00 | 0.0000 |
Total Area [m2] | Conditioned Area [m2] | Unconditioned Area [m2] | Not Part of Total Area [m2] | Lighting [W/m2] | People [m2 per person] | Plug and Process [W/m2] | |
GENERAL | 2090.32 | 2090.32 | 0.00 | 0.00 | 16.1339 | 6.19 | 4.3000 |
Total | 2090.32 | 2090.32 | 0.00 | 0.00 |
Report: Demand End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
End UsesElectricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Time of Peak | 10-AUG-16:10 | - | - | - | - | - | - | - | - | - | - | - | 06-JAN-13:09 |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 115477.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 19339.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 5418.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total End Uses | 177043.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Subcategory | Electricity [W] | Natural Gas [W] | Gasoline [W] | Diesel [W] | Coal [W] | Fuel Oil No 1 [W] | Fuel Oil No 2 [W] | Propane [W] | Other Fuel 1 [W] | Other Fuel 2 [W] | District Cooling [W] | Steam [W] | Water [m3/s] | |
Heating | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | General | 115477.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | LightsWired | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | MiscPlug | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | General | 19339.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | Water Heater | 5418.77 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Source Energy End Use Components Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Values gathered over 8760.00 hoursSource Electricity [GJ] | Source Natural Gas [GJ] | Source Gasoline [GJ] | Source Diesel [GJ] | Source Coal [GJ] | Source Fuel Oil No 1 [GJ] | Source Fuel Oil No 2 [GJ] | Source Propane [GJ] | Source Other Fuel 1 [GJ] | Source Other Fuel 2 [GJ] | Source District Cooling [GJ] | Source District Heating [GJ] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 2506.84 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 1464.12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 384.99 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 407.66 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 1055.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 182.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 6001.36 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1199.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 184.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 504.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2871.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Source Electricity [MJ/m2] | Source Natural Gas [MJ/m2] | Source Gasoline [MJ/m2] | Source Diesel [MJ/m2] | Source Coal [MJ/m2] | Source Fuel Oil No 1 [MJ/m2] | Source Fuel Oil No 2 [MJ/m2] | Source Propane [MJ/m2] | Source Other Fuel 1 [MJ/m2] | Source Other Fuel 2 [MJ/m2] | Source District Cooling [MJ/m2] | Source District Heating [MJ/m2] | |
Heating | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling | 1199.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting | 700.43 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting | 184.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment | 195.02 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans | 504.79 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems | 87.35 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Total Source Energy End Use Components | 2871.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: Component Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
AirTerminal:SingleDuct:ConstantVolume:NoReheatDesign Size Maximum Air Flow Rate [m3/s] | |
LGSTORE1 DIRECT AIR | 3.06 |
SMSTORE1 DIRECT AIR | 1.54 |
SMSTORE2 DIRECT AIR | 1.54 |
SMSTORE3 DIRECT AIR | 1.54 |
SMSTORE4 DIRECT AIR | 1.54 |
LGSTORE2 DIRECT AIR | 2.77 |
SMSTORE5 DIRECT AIR | 1.46 |
SMSTORE6 DIRECT AIR | 1.46 |
SMSTORE7 DIRECT AIR | 1.46 |
SMSTORE8 DIRECT AIR | 1.71 |
Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | Sum of Air Terminal Maximum Flow Rates [m3/s] | Adjusted Heating Design Air Flow Rate [m3/s] | Adjusted Cooling Design Air Flow Rate [m3/s] | Adjusted Main Design Air Flow Rate [m3/s] | User Heating Air Flow Ratio [] | Calculated Heating Air Flow Ratio [] | Design Supply Air Flow Rate [m3/s] | |
PSZ-AC_1:1 | 3.06 | 3.06 | 3.06 | 3.06 | 3.06 | 3.06 | 1.00 | 1.00 | 3.06 |
PSZ-AC_2:2 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
PSZ-AC_3:3 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.000000 | 1.54 |
PSZ-AC_4:4 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
PSZ-AC_5:5 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.54 | 1.00 | 1.00 | 1.54 |
PSZ-AC_6:6 | 2.77 | 2.77 | 2.77 | 2.77 | 2.77 | 2.77 | 1.00 | 1.000000 | 2.77 |
PSZ-AC_7:7 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
PSZ-AC_8:8 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
PSZ-AC_9:9 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.46 | 1.00 | 1.00 | 1.46 |
PSZ-AC_10:10 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.71 | 1.00 | 1.00 | 1.71 |
Maximum Outdoor Air Flow Rate [m3/s] | Minimum Outdoor Air Flow Rate [m3/s] | |
PSZ-AC_1:1_OA_CONTROLLER | 3.06 | 0.411479 |
PSZ-AC_2:2_OA_CONTROLLER | 1.54 | 0.205739 |
PSZ-AC_3:3_OA_CONTROLLER | 1.54 | 0.205739 |
PSZ-AC_4:4_OA_CONTROLLER | 1.54 | 0.205739 |
PSZ-AC_5:5_OA_CONTROLLER | 1.54 | 0.205739 |
PSZ-AC_6:6_OA_CONTROLLER | 2.77 | 0.411479 |
PSZ-AC_7:7_OA_CONTROLLER | 1.46 | 0.205739 |
PSZ-AC_8:8_OA_CONTROLLER | 1.46 | 0.205739 |
PSZ-AC_9:9_OA_CONTROLLER | 1.46 | 0.205739 |
PSZ-AC_10:10_OA_CONTROLLER | 1.71 | 0.205739 |
Design Size Design Maximum Air Flow Rate [m3/s] | Design Electric Power Consumption [W] | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | 3.06 | 3269.64 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | 1.54 | 1650.63 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | 1.54 | 1647.34 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | 1.54 | 1650.48 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | 1.54 | 1643.77 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | 2.77 | 2960.49 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1563.90 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1558.64 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | 1.46 | 1565.04 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | 1.71 | 1829.75 |
Design Size Supply Air Flow Rate [m3/s] | Design Size Heating Supply Air Flow Rate [m3/s] | Design Size Cooling Supply Air Flow Rate [m3/s] | Design Size No Load Supply Air Flow Rate [m3/s] | User-Specified Nominal Cooling Capacity [W] | Design Size Nominal Heating Capacity [W] | Design Size Maximum Supply Air Temperature [C] | Fraction of Supply Air Flow That Goes Through the Controlling Zone | |
PSZ-AC_1:1_UNITARY_PACKAGE_DX | 3.06 | 3.06 | 3.06 | 3.06 | 75351.43 | 75266.55 | 40.00 | 1.00 |
PSZ-AC_2:2_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.54 | 38014.94 | 37333.98 | 40.00 | 1.00 |
PSZ-AC_3:3_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.54 | 37956.57 | 37263.65 | 40.00 | 1.00 |
PSZ-AC_4:4_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.54 | 38013.57 | 37330.75 | 40.00 | 1.00 |
PSZ-AC_5:5_UNITARY_PACKAGE_DX | 1.54 | 1.54 | 1.54 | 1.54 | 37892.69 | 37187.56 | 40.00 | 1.00 |
PSZ-AC_6:6_UNITARY_PACKAGE_DX | 2.77 | 2.77 | 2.77 | 2.77 | 68703.41 | 68552.12 | 40.00 | 1.00 |
PSZ-AC_7:7_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 1.46 | 36293.05 | 36013.84 | 40.00 | 1.00 |
PSZ-AC_8:8_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 1.46 | 36171.00 | 35899.99 | 40.00 | 1.00 |
PSZ-AC_9:9_UNITARY_PACKAGE_DX | 1.46 | 1.46 | 1.46 | 1.46 | 36319.61 | 36048.14 | 40.00 | 1.00 |
PSZ-AC_10:10_UNITARY_PACKAGE_DX | 1.71 | 1.71 | 1.71 | 1.71 | 41222.07 | 41721.91 | 40.00 | 1.00 |
User-Specified Speed 2 Rated Air Flow Rate [m3/s] | Design Size Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | User-Specified Speed 2 Rated Sensible Heat Ratio | User-Specified Speed 1 Rated Sensible Heat Ratio | |
PSZ-AC_1:1 COOLING COIL | 3.06 | 1.53 | 3.06 | 75351.43 | 37165.31 | 75351.43 | 0.703800 | 0.703800 |
PSZ-AC_2:2 COOLING COIL | 1.54 | 0.771289 | 1.54 | 38014.94 | 18749.72 | 38014.94 | 0.703960 | 0.703960 |
PSZ-AC_3:3 COOLING COIL | 1.54 | 0.769750 | 1.54 | 37956.57 | 18721.10 | 37956.57 | 0.703850 | 0.703850 |
PSZ-AC_4:4 COOLING COIL | 1.54 | 0.771219 | 1.54 | 38013.57 | 18749.06 | 38013.57 | 0.703950 | 0.703950 |
PSZ-AC_5:5 COOLING COIL | 1.54 | 0.768085 | 1.54 | 37892.69 | 18689.77 | 37892.69 | 0.703730 | 0.703730 |
PSZ-AC_6:6 COOLING COIL | 2.77 | 1.38 | 2.77 | 68703.41 | 34304.71 | 68703.41 | 0.701080 | 0.701080 |
PSZ-AC_7:7 COOLING COIL | 1.46 | 0.730761 | 1.46 | 36293.05 | 17982.28 | 36293.05 | 0.701080 | 0.701080 |
PSZ-AC_8:8 COOLING COIL | 1.46 | 0.728303 | 1.46 | 36171.00 | 17935.56 | 36171.00 | 0.701080 | 0.701080 |
PSZ-AC_9:9 COOLING COIL | 1.46 | 0.731295 | 1.46 | 36319.61 | 17992.77 | 36319.61 | 0.701080 | 0.701080 |
PSZ-AC_10:10 COOLING COIL | 1.71 | 0.854985 | 1.71 | 41222.07 | 20323.89 | 41222.07 | 0.710460 | 0.710460 |
Design Size Nominal Capacity [W] | |
PSZ-AC_1:1 HEATING COIL | 75266.55 |
PSZ-AC_2:2 HEATING COIL | 37333.98 |
PSZ-AC_3:3 HEATING COIL | 37263.65 |
PSZ-AC_4:4 HEATING COIL | 37330.75 |
PSZ-AC_5:5 HEATING COIL | 37187.56 |
PSZ-AC_6:6 HEATING COIL | 68552.12 |
PSZ-AC_7:7 HEATING COIL | 36013.84 |
PSZ-AC_8:8 HEATING COIL | 35899.99 |
PSZ-AC_9:9 HEATING COIL | 36048.14 |
PSZ-AC_10:10 HEATING COIL | 41721.91 |
Report: Surface Shadowing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Surfaces (Walls, Roofs, etc) that may be Shadowed by Other SurfacesNone |
Possible Shadow Receivers | |
LGSTORE1_WALL_3 | LGSTORE1_WALL_3_DOOR_1 | LGSTORE1_WALL_3_DOOR_2 | |
LGSTORE1_WALL_1 | LGSTORE1_WALL_1_WINDOW_1 | LGSTORE1_WALL_1_WINDOW_2 | LGSTORE1_WALL_1_WINDOW_3 | LGSTORE1_WALL_1_WINDOW_4 | LGSTORE1_WALL_1_DOOR_1 | LGSTORE1_WALL_1_DOOR_2 | |
SMSTORE1_WALL_1 | SMSTORE1_WALL_1_WINDOW_1 | SMSTORE1_WALL_1_WINDOW_2 | SMSTORE1_WALL_1_DOOR | |
SMSTORE1_WALL_3 | SMSTORE1_WALL_3_DOOR | |
SMSTORE2_WALL_1 | SMSTORE2_WALL_1_WINDOW_1 | SMSTORE2_WALL_1_WINDOW_2 | SMSTORE2_WALL_1_DOOR | |
SMSTORE2_WALL_3 | SMSTORE2_WALL_3_DOOR | |
SMSTORE3_WALL_1 | SMSTORE3_WALL_1_WINDOW_1 | SMSTORE3_WALL_1_WINDOW_2 | SMSTORE3_WALL_1_DOOR | |
SMSTORE3_WALL_3 | SMSTORE3_WALL_3_DOOR | |
SMSTORE4_WALL_1 | SMSTORE4_WALL_1_WINDOW_1 | SMSTORE4_WALL_1_WINDOW_2 | SMSTORE4_WALL_1_DOOR | |
SMSTORE4_WALL_3 | SMSTORE4_WALL_3_DOOR | |
LGSTORE2_WALL_3 | LGSTORE2_WALL_3_DOOR_1 | LGSTORE2_WALL_3_DOOR_2 | |
LGSTORE2_WALL_1 | LGSTORE2_WALL_1_WINDOW_1 | LGSTORE2_WALL_1_WINDOW_2 | LGSTORE2_WALL_1_WINDOW_3 | LGSTORE2_WALL_1_WINDOW_4 | LGSTORE2_WALL_1_DOOR_1 | LGSTORE2_WALL_1_DOOR_2 | |
SMSTORE5_WALL_1 | SMSTORE5_WALL_1_WINDOW_1 | SMSTORE5_WALL_1_WINDOW_2 | SMSTORE5_WALL_1_DOOR | |
SMSTORE5_WALL_3 | SMSTORE5_WALL_3_DOOR | |
SMSTORE6_WALL_1 | SMSTORE6_WALL_1_WINDOW_1 | SMSTORE6_WALL_1_WINDOW_2 | SMSTORE6_WALL_1_DOOR | |
SMSTORE6_WALL_3 | SMSTORE6_WALL_3_DOOR | |
SMSTORE7_WALL_1 | SMSTORE7_WALL_1_WINDOW_1 | SMSTORE7_WALL_1_WINDOW_2 | SMSTORE7_WALL_1_DOOR | |
SMSTORE7_WALL_3 | SMSTORE7_WALL_3_DOOR | |
SMSTORE8_WALL_1 | SMSTORE8_WALL_1_WINDOW_1 | SMSTORE8_WALL_1_WINDOW_2 | SMSTORE8_WALL_1_DOOR | |
SMSTORE8_WALL_3 | SMSTORE8_WALL_3_DOOR | |
Report: Adaptive Comfort Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Time Not Meeting the Adaptive Comfort Models during Occupied HoursASHRAE55 90% Acceptability Limits [Hours] | ASHRAE55 80% Acceptability Limits [Hours] | CEN15251 Category I Acceptability Limits [Hours] | CEN15251 Category II Acceptability Limits [Hours] | CEN15251 Category III Acceptability Limits [Hours] |
Report: Initialization Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
VersionVersion ID | |
1 | 22.1 |
#TimeSteps | Minutes per TimeStep {minutes} | |
1 | 6 | 10 |
Minimum System TimeStep {minutes} | Max HVAC Iterations | Minimum Plant Iterations | Maximum Plant Iterations | |
1 | 1 | 20 | 2 | 8 |
Do Zone Sizing | Do System Sizing | Do Plant Sizing | Do Design Days | Do Weather Simulation | Do HVAC Sizing Simulation | |
1 | Yes | Yes | Yes | No | Yes | No |
Use Coil Direct Simulation | Zone Radiant Exchange Algorithm | Override Mode | Number of Timestep In Hour | Force Euler Method | Minimum Number of Warmup Days | Force Suppress All Begin Environment Resets | Minimum System Timestep | MaxZoneTempDiff | MaxAllowedDelTemp | |
1 | No | ScriptF | Normal | 6 | No | 1 | No | 1.0 | 0.300 | 2.0000E-003 |
Tolerance for Time Heating Setpoint Not Met | Tolerance for Zone Cooling Setpoint Not Met Time | |
1 | 0.556 | 0.556 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 | 18.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 29.50 | 25.50 | 21.10 | 19.20 | 20.80 | 23.10 | 26.50 | 31.40 | 33.00 | 35.10 | 35.30 | 32.50 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 | 13.00 |
Jan{C} | Feb{C} | Mar{C} | Apr{C} | May{C} | Jun{C} | Jul{C} | Aug{C} | Sep{C} | Oct{C} | Nov{C} | Dec{C} | |
1 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 | 16.00 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Normal | Daylighting {dimensionless} | |
1 | 1.000 | 1.000 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Jan{dimensionless} | Feb{dimensionless} | Mar{dimensionless} | Apr{dimensionless} | May{dimensionless} | Jun{dimensionless} | Jul{dimensionless} | Aug{dimensionless} | Sep{dimensionless} | Oct{dimensionless} | Nov{dimensionless} | Dec{dimensionless} | |
1 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 | 0.20 |
Wind Sensor Height Above Ground {m} | Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Sensor Height Above Ground {m} | Wind Speed Modifier Coefficient-Internal | Temperature Modifier Coefficient-Internal | |
1 | 10.000 | 0.140 | 270.000 | 1.500 | 1.586 | 9.750E-003 |
Location Name | Latitude {N+/S- Deg} | Longitude {E+/W- Deg} | Time Zone Number {GMT+/-} | Elevation {m} | Standard Pressure at Elevation {Pa} | Standard RhoAir at Elevation | |
1 | Dubai Intl AP - ARE IWEC2 WMO#=411940 | 25.25 | 55.33 | 4.00 | 5.00 | 101265 | 1.2036 |
Calculation Method{} | Water Mains Temperature Schedule Name{} | Annual Average Outdoor Air Temperature{C} | Maximum Difference In Monthly Average Outdoor Air Temperatures{deltaC} | Fixed Default Water Mains Temperature{C} | |
1 | Correlation | NA | 27.75 | 16.10 | NA |
Building Name | North Axis {deg} | Terrain | Loads Convergence Tolerance Value | Temperature Convergence Tolerance Value | Solar Distribution | Maximum Number of Warmup Days | Minimum Number of Warmup Days | |
1 | RetailStripmall | 0.000 | City | 4.00000E-002 | 0.20000 | FullInteriorAndExterior | 25 | 6 |
Algorithm {Simple TARP CeilingDiffuser AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Algorithm {SimpleCombined TARP MoWitt DOE-2 AdaptiveConvectionAlgorithm} |
|
1 | TARP |
Value {Anisotropic} | |
1 | Anisotropic |
Value {ThirdOrderBackwardDifference AnalyticalSolution EulerMethod} |
|
1 | ThirdOrderBackwardDifference |
Simulation {Yes/No} | Carbon Dioxide Concentration | |
1 | No | N/A |
Simulation {Yes/No} | Generic Contaminant Concentration | |
1 | No | N/A |
Enforce Mass Balance |
Adjust Zone Mixing and Return {AdjustMixingOnly AdjustReturnOnly AdjustMixingThenReturn AdjustReturnThenMixing None} |
Adjust Zone Infiltration {AddInfiltration AdjustInfiltration None} |
Infiltration Zones {MixingSourceZonesOnly AllZones} |
|
1 | No | N/A | N/A | N/A |
Value {RegulaFalsi Bisection BisectionThenRegulaFalsi RegulaFalsiThenBisection} |
|
1 | RegulaFalsi |
Wind Speed Profile Exponent {} | Wind Speed Profile Boundary Layer Thickness {m} | Air Temperature Gradient Coefficient {K/m} | |
1 | 0.330 | 460.000 | 6.500000E-003 |
Starting Corner | Vertex Input Direction | Coordinate System | Daylight Reference Point Coordinate System | Rectangular (Simple) Surface Coordinate System | |
1 | UpperLeftCorner | Counterclockwise | RelativeCoordinateSystem | RelativeCoordinateSystem | RelativeToZoneOrigin |
Value {CTF - ConductionTransferFunction EMPD - MoisturePenetrationDepthConductionTransferFunction CondFD - ConductionFiniteDifference HAMT - CombinedHeatAndMoistureFiniteElement} - Description |
Inside Surface Max Temperature Limit{C} |
Surface Convection Coefficient Lower Limit {W/m2-K} |
Surface Convection Coefficient Upper Limit {W/m2-K} |
|
1 | CTF - ConductionTransferFunction | 200 | 0.10 | 1000.0 |
Number of Fixed Detached Shades | Number of Building Detached Shades | Number of Attached Shades | |
1 | 0 | 0 | 0 |
Number of Zones | Number of Zone Surfaces | Number of SubSurfaces | |
1 | 10 | 118 | 48 |
Zone Name | North Axis {deg} | Origin X-Coordinate {m} | Origin Y-Coordinate {m} | Origin Z-Coordinate {m} | Centroid X-Coordinate {m} | Centroid Y-Coordinate {m} | Centroid Z-Coordinate {m} | Type | Zone Multiplier | Zone List Multiplier | Minimum X {m} | Maximum X {m} | Minimum Y {m} | Maximum Y {m} | Minimum Z {m} | Maximum Z {m} | Ceiling Height {m} | Volume {m3} | Zone Inside Convection Algorithm {Simple-Detailed-CeilingDiffuser-TrombeWall} | Zone Outside Convection Algorithm {Simple-Detailed-Tarp-MoWitt-DOE-2-BLAST} | Floor Area {m2} | Exterior Gross Wall Area {m2} | Exterior Net Wall Area {m2} | Exterior Window Area {m2} | Number of Surfaces | Number of SubSurfaces | Number of Shading SubSurfaces | Part of Total Building Area | |
1 | LGSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 7.62 | 11.43 | 2.59 | 1 | 1 | 1 | 0.00 | 15.24 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 276.30 | 247.74 | 20.77 | 6 | 8 | 0 | Yes |
2 | SMSTORE1 | 0.0 | 0.00 | 0.00 | 0.00 | 19.05 | 11.43 | 2.59 | 1 | 1 | 1 | 15.24 | 22.86 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.66 | 10.38 | 6 | 4 | 0 | Yes |
3 | SMSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 26.67 | 11.43 | 2.59 | 1 | 1 | 1 | 22.86 | 30.48 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
4 | SMSTORE3 | 0.0 | 0.00 | 0.00 | 0.00 | 34.29 | 11.43 | 2.59 | 1 | 1 | 1 | 30.48 | 38.10 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
5 | SMSTORE4 | 0.0 | 0.00 | 0.00 | 0.00 | 41.91 | 11.43 | 2.59 | 1 | 1 | 1 | 38.10 | 45.72 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
6 | LGSTORE2 | 0.0 | 0.00 | 0.00 | 0.00 | 53.34 | 11.43 | 2.59 | 1 | 1 | 1 | 45.72 | 60.96 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 1805.20 | TARP | TARP | 348.39 | 157.89 | 129.41 | 20.72 | 6 | 8 | 0 | Yes |
7 | SMSTORE5 | 0.0 | 0.00 | 0.00 | 0.00 | 64.77 | 11.43 | 2.59 | 1 | 1 | 1 | 60.96 | 68.58 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
8 | SMSTORE6 | 0.0 | 0.00 | 0.00 | 0.00 | 72.39 | 11.43 | 2.59 | 1 | 1 | 1 | 68.58 | 76.20 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
9 | SMSTORE7 | 0.0 | 0.00 | 0.00 | 0.00 | 80.01 | 11.43 | 2.59 | 1 | 1 | 1 | 76.20 | 83.82 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 78.94 | 64.71 | 10.36 | 6 | 4 | 0 | Yes |
10 | SMSTORE8 | 0.0 | 0.00 | 0.00 | 0.00 | 87.63 | 11.43 | 2.59 | 1 | 1 | 1 | 83.82 | 91.44 | 0.00 | 22.86 | 0.00 | 5.18 | 5.18 | 902.60 | TARP | TARP | 174.19 | 197.36 | 183.12 | 10.36 | 6 | 4 | 0 | Yes |
Zone Name | Floor Area {m2} | # Occupants | Area per Occupant {m2/person} | Occupant per Area {person/m2} | Interior Lighting {W/m2} | Electric Load {W/m2} | Gas Load {W/m2} | Other Load {W/m2} | Hot Water Eq {W/m2} | Steam Equipment {W/m2} | Sum Loads per Area {W/m2} | Outdoor Controlled Baseboard Heat | |
1 | LGSTORE1 | 348.39 | 56.3 | 6.193 | 0.161 | 18.494 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 22.794 | No |
2 | SMSTORE1 | 174.19 | 28.1 | 6.194 | 0.161 | 21.122 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 25.422 | No |
3 | SMSTORE2 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
4 | SMSTORE3 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
5 | SMSTORE4 | 174.19 | 28.1 | 6.194 | 0.161 | 19.266 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 23.566 | No |
6 | LGSTORE2 | 348.39 | 56.3 | 6.193 | 0.161 | 12.825 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.125 | No |
7 | SMSTORE5 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
8 | SMSTORE6 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
9 | SMSTORE7 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
10 | SMSTORE8 | 174.19 | 28.1 | 6.194 | 0.161 | 13.012 | 4.300 | 0.000 | 0.000 | 0.000 | 0.000 | 17.312 | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Number of People {} | People/Floor Area {person/m2} | Floor Area per person {m2/person} | Fraction Radiant | Fraction Convected | Sensible Fraction Calculation | Activity level | ASHRAE 55 Warnings | Carbon Dioxide Generation Rate | Nominal Minimum Number of People | Nominal Maximum Number of People | MRT Calculation Type | Work Efficiency | Clothing Insulation Calculation Method | Clothing Insulation Calculation Method Schedule | Clothing | Air Velocity | Fanger Calculation | Pierce Calculation | KSU Calculation | Cooling Effect Calculation | Ankle Draft Calculation | |
1 | LGSTORE1 | TYPE1_OCC_SCH | LGSTORE1 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
2 | SMSTORE1 | TYPE1_OCC_SCH | SMSTORE1 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
3 | SMSTORE2 | TYPE2_OCC_SCH | SMSTORE2 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
4 | SMSTORE3 | TYPE2_OCC_SCH | SMSTORE3 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
5 | SMSTORE4 | TYPE2_OCC_SCH | SMSTORE4 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
6 | LGSTORE2 | TYPE3_OCC_SCH | LGSTORE2 | 348.39 | 56.3 | 56.3 | 0.161 | 6.193 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 56 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
7 | SMSTORE5 | TYPE3_OCC_SCH | SMSTORE5 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
8 | SMSTORE6 | TYPE3_OCC_SCH | SMSTORE6 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
9 | SMSTORE7 | TYPE3_OCC_SCH | SMSTORE7 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
10 | SMSTORE8 | TYPE3_OCC_SCH | SMSTORE8 | 174.19 | 28.1 | 28.1 | 0.161 | 6.194 | 0.300 | 0.700 | AutoCalculate | ACTIVITY_SCH | No | 3.8200E-008 | 0 | 28 | Zone Averaged | WORK_EFF_SCH | Clothing Insulation Schedule | N/A | CLOTHING_SCH | AIR_VELO_SCH | Yes | No | No | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Lighting Level {W} | Lights/Floor Area {W/m2} | Lights per person {W/person} | Fraction Return Air | Fraction Radiant | Fraction Short Wave | Fraction Convected | Fraction Replaceable | End-Use Category | Nominal Minimum Lighting Level {W} | Nominal Maximum Lighting Level {W} | |
1 | LGSTORE1_LIGHTS | LTG_SCH_BASE_LPD1 | LGSTORE1 | 348.39 | 56.3 | 4477.000 | 12.851 | 79.590 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4477.000 |
2 | LGSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | LGSTORE1 | 348.39 | 56.3 | 1965.923 | 5.643 | 34.949 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1965.923 |
3 | SMSTORE1_LIGHTS | LTG_SCH_BASE_SMALL_LPD1 | SMSTORE1 | 174.19 | 28.1 | 2271.127 | 13.038 | 80.753 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2271.127 |
4 | SMSTORE1_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | SMSTORE1 | 174.19 | 28.1 | 1408.135 | 8.084 | 50.068 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1408.135 |
5 | SMSTORE2_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE2 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
6 | SMSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE2 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
7 | SMSTORE3_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE3 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
8 | SMSTORE3_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE3 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
9 | SMSTORE4_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | SMSTORE4 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
10 | SMSTORE4_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | SMSTORE4 | 174.19 | 28.1 | 1089.385 | 6.254 | 38.734 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 1089.385 |
11 | LGSTORE2_LIGHTS | LTG_SCH_BASE_LPD2 | LGSTORE2 | 348.39 | 56.3 | 4468.075 | 12.825 | 79.432 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 4468.075 |
12 | LGSTORE2_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | LGSTORE2 | 348.39 | 56.3 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
13 | SMSTORE5_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE5 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
14 | SMSTORE5_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE5 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
15 | SMSTORE6_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE6 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
16 | SMSTORE6_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE6 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
17 | SMSTORE7_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE7 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
18 | SMSTORE7_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE7 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
19 | SMSTORE8_LIGHTS | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | SMSTORE8 | 174.19 | 28.1 | 2266.665 | 13.012 | 80.594 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 2266.665 |
20 | SMSTORE8_LIGHTS_ALLOWANCE | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | SMSTORE8 | 174.19 | 28.1 | 0.000 | 0.000 | 0.000 | 0.000 | 0.700 | 0.200 | 0.100 | 1.000 | LightsWired | 0.000 | 0.000 |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Equipment Level {W} | Equipment/Floor Area {W/m2} | Equipment per person {W/person} | Fraction Latent | Fraction Radiant | Fraction Lost | Fraction Convected | End-Use SubCategory | Nominal Minimum Equipment Level {W} | Nominal Maximum Equipment Level {W} | |
1 | LGSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | LGSTORE1 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
2 | SMSTORE1_MISCPLUG_EQUIP | TYPE1_EQUIP_SCH | SMSTORE1 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
3 | SMSTORE2_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE2 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
4 | SMSTORE3_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE3 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
5 | SMSTORE4_MISCPLUG_EQUIP | TYPE2_EQUIP_SCH | SMSTORE4 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
6 | LGSTORE2_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | LGSTORE2 | 348.39 | 56.3 | 1498.062 | 4.300 | 26.632 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 1498.062 |
7 | SMSTORE5_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE5 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
8 | SMSTORE6_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE6 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
9 | SMSTORE7_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE7 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
10 | SMSTORE8_MISCPLUG_EQUIP | TYPE3_EQUIP_SCH | SMSTORE8 | 174.19 | 28.1 | 749.031 | 4.300 | 26.633 | 0.000 | 0.500 | 0.000 | 0.500 | MiscPlug | 0.000 | 749.031 |
Construction Name | Index | #Layers | #CTFs | Time Step {hours} | ThermalConductance {w/m2-K} | OuterThermalAbsorptance | InnerThermalAbsorptance | OuterSolarAbsorptance | InnerSolarAbsorptance | Roughness | |
1 | SWINGING DOOR_CON | 1 | 1 | 1 | 0.167 | 3.464 | 0.900 | 0.900 | 0.700 | 0.700 | MediumRough |
2 | INTERIORFURNISHINGS | 2 | 1 | 9 | 0.167 | 0.8000 | 0.900 | 0.900 | 0.700 | 0.700 | MediumSmooth |
3 | INT_WALL | 7 | 2 | 4 | 0.167 | 6.299 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
4 | NONRES_ROOF | 17 | 3 | 3 | 0.167 | 0.2832 | 0.750 | 0.900 | 0.450 | 0.700 | Rough |
5 | NONRES_EXT_WALL_GRD | 20 | 4 | 7 | 0.167 | 0.7544 | 0.900 | 0.900 | 0.700 | 0.700 | Smooth |
6 | LGSTORE1_FLOOR_FFACTOR | 36 | 2 | 7 | 0.167 | 0.1995 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
7 | SMSTORE1_FLOOR_FFACTOR | 37 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
8 | SMSTORE2_FLOOR_FFACTOR | 38 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
9 | SMSTORE3_FLOOR_FFACTOR | 39 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
10 | SMSTORE4_FLOOR_FFACTOR | 40 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
11 | LGSTORE2_FLOOR_FFACTOR | 41 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
12 | SMSTORE5_FLOOR_FFACTOR | 42 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
13 | SMSTORE6_FLOOR_FFACTOR | 43 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
14 | SMSTORE7_FLOOR_FFACTOR | 44 | 2 | 7 | 0.167 | 0.1125 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
15 | SMSTORE8_FLOOR_FFACTOR | 45 | 2 | 7 | 0.167 | 0.2888 | 0.000 | 0.900 | 0.000 | 0.700 | MediumRough |
Material Name | Thickness {m} | Conductivity {w/m-K} | Density {kg/m3} | Specific Heat {J/kg-K} | ThermalResistance {m2-K/w} | |
1 | OPAQUE DOOR PANEL_CON | 0.0000 | 0.000 | 0.000 | 0.000 | 0.2887 |
2 | STD WOOD 6INCH | 0.1500 | 0.120 | 540.000 | 1210.000 | 1.250 |
3 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
4 | G01 13MM GYPSUM BOARD | 0.0127 | 0.160 | 800.000 | 1090.000 | 0.7937E-01 |
5 | F13 BUILT-UP ROOFING | 0.0095 | 0.160 | 1120.000 | 1460.000 | 0.5938E-01 |
6 | NONRES_ROOF_INSULATION | 0.0000 | 0.000 | 0.000 | 0.000 | 3.472 |
7 | F08 METAL SURFACE | 0.0008 | 45.280 | 7824.000 | 500.000 | 0.1767E-04 |
8 | F07 25MM STUCCO | 0.0254 | 0.720 | 1856.000 | 840.000 | 0.3528E-01 |
9 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
10 | NONRES_EXTERIOR_WALL_INSULATION_GRD | 0.0000 | 0.000 | 0.000 | 0.000 | 1.092 |
11 | G01 16MM GYPSUM BOARD | 0.0159 | 0.160 | 800.000 | 1090.000 | 0.9938E-01 |
12 | ~FC_Insulation_1 | 0.0000 | 0.000 | 0.000 | 0.000 | 4.937 |
13 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
14 | ~FC_Insulation_2 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
15 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
16 | ~FC_Insulation_3 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
17 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
18 | ~FC_Insulation_4 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
19 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
20 | ~FC_Insulation_5 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
21 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
22 | ~FC_Insulation_6 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
23 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
24 | ~FC_Insulation_7 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
25 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
26 | ~FC_Insulation_8 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
27 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
28 | ~FC_Insulation_9 | 0.0000 | 0.000 | 0.000 | 0.000 | 8.813 |
29 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
30 | ~FC_Insulation_10 | 0.0000 | 0.000 | 0.000 | 0.000 | 3.386 |
31 | ~FC_Concrete | 0.1500 | 1.950 | 2240.000 | 900.000 | 0.7692E-01 |
Time | Outside | Cross | Inside | Flux (except final one) | |
1 | 1 | 0.0000000 | 0.0000000 | -0.0000000 | -0.0000000 |
2 | 0 | 3.4637404 | 3.4637404 | 3.4637404 | |
3 | 9 | -0.27580628E-02 | 0.97439125E-12 | -0.27580628E-02 | 0.28516790E-03 |
4 | 8 | 0.73590997E-01 | 0.21837543E-08 | 0.73590997E-01 | -0.77836043E-02 |
5 | 7 | -0.82599318 | 0.23162835E-06 | -0.82599318 | 0.89703933E-01 |
6 | 6 | 5.1113916 | 0.48671053E-05 | 5.1113916 | -0.57224845 |
7 | 5 | -19.214933 | 0.30163627E-04 | -19.214933 | 2.2266322 |
8 | 4 | 45.557404 | 0.63181060E-04 | 45.557404 | -5.4853312 |
9 | 3 | -68.275533 | 0.44785456E-04 | -68.275533 | 8.5710568 |
10 | 2 | 62.555368 | 0.93952058E-05 | 62.555368 | -8.2111738 |
11 | 1 | -31.904423 | 0.39200004E-06 | -31.904423 | 4.3886678 |
12 | 0 | 6.9260389 | 0.77047546E-09 | 6.9260389 | |
13 | 4 | 0.68458728E-09 | 0.26079551E-09 | 0.68458728E-09 | -0.34507121E-18 |
14 | 3 | -0.72180374E-03 | 0.24295686E-03 | -0.72180374E-03 | 0.69691454E-09 |
15 | 2 | 0.83054762 | 0.27682775 | 0.83054762 | -0.35168967E-03 |
16 | 1 | -12.650482 | 3.3590720 | -12.650482 | 0.19281313 |
17 | 0 | 16.907513 | 1.4507143 | 16.907513 | |
18 | 3 | -0.61927053E-06 | 0.12767249E-08 | -0.37968499E-05 | 0.16832131E-17 |
19 | 2 | 0.77611055 | 0.17315568E-02 | 1.0534842 | -0.72792597E-06 |
20 | 1 | -21.915918 | 0.11588205 | -6.3286394 | 0.20197014 |
21 | 0 | 21.365777 | 0.10835518 | 5.5011278 | |
22 | 7 | -0.31526305E-12 | 0.65421067E-14 | -0.96995935E-13 | 0.16372101E-15 |
23 | 6 | 0.28934589E-07 | 0.21281465E-09 | 0.66261080E-08 | -0.13661131E-12 |
24 | 5 | -0.19144321E-03 | 0.18179002E-05 | -0.98452505E-04 | 0.65494719E-08 |
25 | 4 | 0.29370911 | 0.88327295E-03 | 0.10024532 | -0.33791493E-04 |
26 | 3 | -7.2972687 | 0.27321832E-01 | -2.3480939 | 0.29160644E-01 |
27 | 2 | 40.973187 | 0.96992104E-01 | 15.302757 | -0.33447687 |
28 | 1 | -80.623988 | 0.43709902E-01 | -29.175449 | 1.0802857 |
29 | 0 | 46.824338 | 0.87814252E-03 | 16.290426 | |
30 | 7 | -0.21163652E-08 | -0.68723841E-15 | 0.43910983E-14 | -0.57684426E-16 |
31 | 6 | 0.56109385E-05 | 0.38186281E-08 | 0.31898696E-02 | -0.26759299E-04 |
32 | 5 | -0.40164657E-03 | 0.22608617E-05 | -0.22372456 | 0.19561502E-02 |
33 | 4 | 0.92272104E-02 | 0.10289840E-03 | 4.8295456 | -0.45264980E-01 |
34 | 3 | -0.80993241E-01 | 0.81813938E-03 | -38.021416 | 0.39865375 |
35 | 2 | 0.28754352 | 0.13608947E-02 | 116.48395 | -1.4179393 |
36 | 1 | -0.41499682 | 0.41453381E-03 | -143.90731 | 2.0490399 |
37 | 0 | 0.20232414 | 0.10048102E-04 | 60.838472 | |
38 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
39 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
40 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
41 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
42 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
43 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
44 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
45 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
46 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
47 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
48 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
49 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
50 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
51 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
52 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
53 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
54 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
55 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
56 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
57 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
58 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
59 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
60 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
61 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
62 | 7 | -0.37862368E-08 | -0.38757603E-14 | 0.11479940E-14 | -0.41635801E-16 |
63 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
64 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
65 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
66 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
67 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
68 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
69 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
70 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
71 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
72 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
73 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
74 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
75 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
76 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
77 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
78 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479937E-14 | -0.41635796E-16 |
79 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
80 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
81 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
82 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
83 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
84 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
85 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
86 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479940E-14 | -0.41635801E-16 |
87 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
88 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
89 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
90 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
91 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
92 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
93 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
94 | 7 | -0.37862368E-08 | -0.38757604E-14 | 0.11479936E-14 | -0.41635794E-16 |
95 | 6 | 0.33337596E-05 | 0.21524044E-08 | 0.31966530E-02 | -0.26816204E-04 |
96 | 5 | -0.22954206E-03 | 0.12712390E-05 | -0.22411006 | 0.19595528E-02 |
97 | 4 | 0.52129973E-02 | 0.57790281E-04 | 4.8359653 | -0.45326691E-01 |
98 | 3 | -0.45565888E-01 | 0.45899116E-03 | -38.057676 | 0.39905455 |
99 | 2 | 0.16149801 | 0.76278124E-03 | 116.55452 | -1.4188832 |
100 | 1 | -0.23290653 | 0.23201668E-03 | -143.94884 | 2.0497227 |
101 | 0 | 0.11350612 | 0.56387423E-05 | 60.838472 | |
102 | 7 | -0.14484255E-08 | -0.22640907E-15 | 0.11860658E-13 | -0.17473455E-15 |
103 | 6 | 0.80640390E-05 | 0.55493782E-08 | 0.31828288E-02 | -0.26700235E-04 |
104 | 5 | -0.58275339E-03 | 0.32892043E-05 | -0.22332434 | 0.19526176E-02 |
105 | 4 | 0.13421983E-01 | 0.14977251E-03 | 4.8228790 | -0.45200897E-01 |
106 | 3 | -0.11791368 | 0.11914425E-02 | -37.983753 | 0.39823745 |
107 | 2 | 0.41875064 | 0.19825898E-02 | 116.41064 | -1.4169588 |
108 | 1 | -0.60444169 | 0.60433957E-03 | -143.86415 | 2.0483306 |
109 | 0 | 0.29470347 | 0.14596444E-04 | 60.838472 |
Construction Name | Index | #Layers | Roughness | Conductance {W/m2-K} | Conductance (Before Adjusted) {W/m2-K} | Convection Coefficient Adjustment Ratio | SHGC | Solar Transmittance at Normal Incidence | Visible Transmittance at Normal Incidence | |
1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 35 | 1 | VerySmooth | 2.861 | 2.861 | 1.000 | 0.251 |
Material Name | Optical Data Type | Spectral Data Set Name | Thickness {m} | Solar Transmittance | Front Solar Reflectance | Back Solar Reflectance | Visible Transmittance | Front Visible Reflectance | Back Visible Reflectance | Infrared Transmittance | Front Thermal Emissivity | Back Thermal Emissivity | Conductivity {W/m-K} | Dirt Factor | Solar Diffusing | |
1 | NONRES WINDOW GLAZING LAYER | SpectralAverage | 1.93170E-002 | 0.16139 | 0.61074 | 0.61074 | 0.25000 | 0.16143 | 0.23877 | 0.00000 | 0.84000 | 0.84000 | 0.10774 | 1.00000 | No |
Shading Calculation Method | Shading Calculation Update Frequency Method | Shading Calculation Update Frequency {days} | Maximum Figures in Shadow Overlap Calculations {} | Polygon Clipping Algorithm | Pixel Counting Resolution | Sky Diffuse Modeling Algorithm | Output External Shading Calculation Results | Disable Self-Shading Within Shading Zone Groups | Disable Self-Shading From Shading Zone Groups to Other Zones | |
1 | PolygonClipping | Periodic | 30 | 15000 | SutherlandHodgman | 512 | SimpleSkyDiffuseModeling | No | No | No |
Type | Name | Volume {m3} | Maximum Capacity {W} | Standard Rated Recovery Efficiency | Standard Rated Energy Factor | |
1 | WaterHeater:Mixed | GAS TANK1 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
2 | WaterHeater:Mixed | GAS TANK2 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
3 | WaterHeater:Mixed | GAS TANK3 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
4 | WaterHeater:Mixed | GAS TANK4 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
5 | WaterHeater:Mixed | GAS TANK5 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
6 | WaterHeater:Mixed | GAS TANK6 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
7 | WaterHeater:Mixed | GAS TANK7 | 0.1514 | 11722.8 | 1.020 | 0.7241 |
Surface Name | Outside Model Assignment | Outside Area [m2] | Outside Perimeter [m] | Outside Height [m] | Inside Model Assignment | Inside Height [m] | Inside Perimeter Envelope [m] | Inside Hydraulic Diameter [m] | Window Wall Ratio | Window Location | Near Radiant {Yes/No} | Has Active HVAC {Yes/No} | |
1 | LGSTORE1_WALL_2 | 0 | 118.41 | 56.08 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
2 | LGSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
3 | LGSTORE1_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
4 | LGSTORE1_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
5 | LGSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
6 | LGSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 4 | No | No |
7 | LGSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
8 | LGSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
9 | LGSTORE1_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
10 | LGSTORE1_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 2 | No | No |
11 | LGSTORE1_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
12 | LGSTORE1_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 1 | No | No |
13 | LGSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
14 | LGSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
15 | LGSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 53.34 | 18.29 | 7.52E-002 | 0 | No | No |
16 | SMSTORE1_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
17 | SMSTORE1_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
18 | SMSTORE1_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
19 | SMSTORE1_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
20 | SMSTORE1_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
21 | SMSTORE1_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
22 | SMSTORE1_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
23 | SMSTORE1_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
24 | SMSTORE1_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
25 | SMSTORE1_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
26 | SMSTORE1_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
27 | SMSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
28 | SMSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
29 | SMSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
30 | SMSTORE2_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
31 | SMSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
32 | SMSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
33 | SMSTORE2_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
34 | SMSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
35 | SMSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
36 | SMSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
37 | SMSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
38 | SMSTORE3_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
39 | SMSTORE3_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
40 | SMSTORE3_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
41 | SMSTORE3_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
42 | SMSTORE3_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
43 | SMSTORE3_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
44 | SMSTORE3_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
45 | SMSTORE3_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
46 | SMSTORE3_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
47 | SMSTORE3_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
48 | SMSTORE3_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
49 | SMSTORE4_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
50 | SMSTORE4_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
51 | SMSTORE4_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
52 | SMSTORE4_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
53 | SMSTORE4_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
54 | SMSTORE4_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
55 | SMSTORE4_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
56 | SMSTORE4_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
57 | SMSTORE4_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
58 | SMSTORE4_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
59 | SMSTORE4_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
60 | LGSTORE2_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
61 | LGSTORE2_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
62 | LGSTORE2_WALL_3_DOOR_1 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
63 | LGSTORE2_WALL_3_DOOR_2 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
64 | LGSTORE2_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
65 | LGSTORE2_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 4 | No | No |
66 | LGSTORE2_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
67 | LGSTORE2_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
68 | LGSTORE2_WALL_1_WINDOW_3 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
69 | LGSTORE2_WALL_1_WINDOW_4 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 2 | No | No |
70 | LGSTORE2_WALL_1_DOOR_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
71 | LGSTORE2_WALL_1_DOOR_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 1 | No | No |
72 | LGSTORE2_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
73 | LGSTORE2_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
74 | LGSTORE2_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 30.48 | 18.29 | 0.13 | 0 | No | No |
75 | SMSTORE5_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
76 | SMSTORE5_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
77 | SMSTORE5_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
78 | SMSTORE5_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
79 | SMSTORE5_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
80 | SMSTORE5_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
81 | SMSTORE5_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
82 | SMSTORE5_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
83 | SMSTORE5_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
84 | SMSTORE5_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
85 | SMSTORE5_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
86 | SMSTORE6_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
87 | SMSTORE6_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
88 | SMSTORE6_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
89 | SMSTORE6_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
90 | SMSTORE6_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
91 | SMSTORE6_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
92 | SMSTORE6_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
93 | SMSTORE6_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
94 | SMSTORE6_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
95 | SMSTORE6_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
96 | SMSTORE6_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
97 | SMSTORE7_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 4 | No | No |
98 | SMSTORE7_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
99 | SMSTORE7_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 2 | No | No |
100 | SMSTORE7_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 1 | No | No |
101 | SMSTORE7_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
102 | SMSTORE7_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 3 | No | No |
103 | SMSTORE7_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
104 | SMSTORE7_WALL_4 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
105 | SMSTORE7_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
106 | SMSTORE7_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
107 | SMSTORE7_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 15.24 | 11.43 | 0.13 | 0 | No | No |
108 | SMSTORE8_WALL_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 4 | No | No |
109 | SMSTORE8_WALL_1_WINDOW_1 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
110 | SMSTORE8_WALL_1_WINDOW_2 | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 2 | No | No |
111 | SMSTORE8_WALL_1_DOOR | 0 | 473.66 | 193.24 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 1 | No | No |
112 | SMSTORE8_WALL_2 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
113 | SMSTORE8_WALL_3 | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
114 | SMSTORE8_WALL_3_DOOR | 0 | 473.66 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
115 | SMSTORE8_WALL_4 | 0 | 118.41 | 198.87 | 5.18 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 3 | No | No |
116 | SMSTORE8_FLOOR | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
117 | SMSTORE8_ROOF | 0 | 2090.32 | 297.18 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
118 | SMSTORE8_INTERNALMASS_1 | 0 | 0.00 | 0.00 | 0.00 | 0 | 5.18 | 38.10 | 11.43 | 5.25E-002 | 0 | No | No |
Name | Schedule Name | Zone Name | Zone Floor Area {m2} | # Zone Occupants | Design Volume Flow Rate {m3/s} | Volume Flow Rate/Floor Area {m3/s-m2} | Volume Flow Rate/Exterior Surface Area {m3/s-m2} | ACH - Air Changes per Hour | Equation A - Constant Term Coefficient {} | Equation B - Temperature Term Coefficient {1/C} | Equation C - Velocity Term Coefficient {s/m} | Equation D - Velocity Squared Term Coefficient {s2/m2} | |
1 | LGSTORE1_INFILTRATION | TYPE1_INFIL_SCH | LGSTORE1 | 348.39 | 56.3 | 0.283 | 8.131E-004 | 4.479E-004 | 0.565 | 0.000 | 0.000 | 0.224 | 0.000 |
2 | LGSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE1 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 6.149E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
3 | SMSTORE1_INFILTRATION | TYPE1_INFIL_SCH | SMSTORE1 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
4 | SMSTORE1_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE1 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.648E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
5 | SMSTORE2_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE2 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
6 | SMSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE2 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
7 | SMSTORE3_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE3 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
8 | SMSTORE3_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE3 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
9 | SMSTORE4_INFILTRATION | TYPE2_INFIL_SCH | SMSTORE4 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
10 | SMSTORE4_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE4 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
11 | LGSTORE2_INFILTRATION | TYPE3_INFIL_SCH | LGSTORE2 | 348.39 | 56.3 | 0.162 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
12 | LGSTORE2_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | LGSTORE2 | 348.39 | 56.3 | 0.389 | 1.116E-003 | 7.565E-004 | 0.776 | 1.000 | 0.000 | 0.000 | 0.000 |
13 | SMSTORE5_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE5 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
14 | SMSTORE5_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE5 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
15 | SMSTORE6_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE6 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
16 | SMSTORE6_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE6 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
17 | SMSTORE7_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE7 | 174.19 | 28.1 | 8.093E-002 | 4.646E-004 | 3.149E-004 | 0.323 | 0.000 | 0.000 | 0.224 | 0.000 |
18 | SMSTORE7_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE7 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 8.649E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
19 | SMSTORE8_INFILTRATION | TYPE3_INFIL_SCH | SMSTORE8 | 174.19 | 28.1 | 0.202 | 1.162E-003 | 5.390E-004 | 0.807 | 0.000 | 0.000 | 0.224 | 0.000 |
20 | SMSTORE8_DOOR_INFILTRATION | INFIL_DOOR_OPENING_SCH | SMSTORE8 | 174.19 | 28.1 | 0.222 | 1.276E-003 | 5.921E-004 | 0.887 | 1.000 | 0.000 | 0.000 | 0.000 |
Simple | |
1 | Simple |
Zone Name | Mixing/Mundt/UCSDDV/UCSDCV/UCSDUFI/UCSDUFE/User Defined | |
1 | LGSTORE1 | Mixing/Well-Stirred |
2 | SMSTORE1 | Mixing/Well-Stirred |
3 | SMSTORE2 | Mixing/Well-Stirred |
4 | SMSTORE3 | Mixing/Well-Stirred |
5 | SMSTORE4 | Mixing/Well-Stirred |
6 | LGSTORE2 | Mixing/Well-Stirred |
7 | SMSTORE5 | Mixing/Well-Stirred |
8 | SMSTORE6 | Mixing/Well-Stirred |
9 | SMSTORE7 | Mixing/Well-Stirred |
10 | SMSTORE8 | Mixing/Well-Stirred |
No Multizone or Distribution/Multizone with Distribution/Multizone without Distribution/Multizone with Distribution only during Fan Operation | |
1 | NoMultizoneOrDistribution |
Sensible Heat Capacity Multiplier | Moisture Capacity Multiplier | Carbon Dioxide Capacity Multiplier | Generic Contaminant Capacity Multiplier | |
1 | 1.000 | 1.000 | 1.000 | 1.000 |
Value | |
1 | 6 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Sizing Factor ID | Value | |
1 | Global | 1.2000 |
2 | Zone LGSTORE1 | 1.2000 |
3 | Zone SMSTORE1 | 1.2000 |
4 | Zone SMSTORE2 | 1.2000 |
5 | Zone SMSTORE3 | 1.2000 |
6 | Zone SMSTORE4 | 1.2000 |
7 | Zone LGSTORE2 | 1.2000 |
8 | Zone SMSTORE5 | 1.2000 |
9 | Zone SMSTORE6 | 1.2000 |
10 | Zone SMSTORE7 | 1.2000 |
11 | Zone SMSTORE8 | 1.2000 |
Zone Name | Load Type | Calc Des Load {W} | User Des Load {W} | Calc Des Air Flow Rate {m3/s} | User Des Air Flow Rate {m3/s} | Design Day Name | Date/Time of Peak | Temperature at Peak {C} | Humidity Ratio at Peak {kgWater/kgDryAir} | Floor Area {m2} | # Occupants | Calc Outdoor Air Flow Rate {m3/s} | Calc DOAS Heat Addition Rate {W} | |
1 | LGSTORE1 | Cooling | 34579.40956 | 41495.29147 | 2.54633 | 3.05560 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 42.80000 | 1.07818E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
2 | LGSTORE1 | Heating | 9187.55828 | 11025.06993 | 0.38030 | 0.45636 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
3 | SMSTORE1 | Cooling | 17457.09951 | 20948.51942 | 1.28548 | 1.54258 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 42.80000 | 1.07818E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
4 | SMSTORE1 | Heating | 4300.75302 | 5160.90362 | 0.18551 | 0.22261 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
5 | SMSTORE2 | Cooling | 17422.27483 | 20906.72979 | 1.28292 | 1.53950 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
6 | SMSTORE2 | Heating | 4335.27506 | 5202.33008 | 0.18700 | 0.22440 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
7 | SMSTORE3 | Cooling | 17455.51620 | 20946.61944 | 1.28537 | 1.54244 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
8 | SMSTORE3 | Heating | 4378.67029 | 5254.40435 | 0.18887 | 0.22665 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
9 | SMSTORE4 | Cooling | 17384.58883 | 20861.50660 | 1.28014 | 1.53617 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
10 | SMSTORE4 | Heating | 4500.61273 | 5400.73527 | 0.19413 | 0.23296 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
11 | LGSTORE2 | Cooling | 31310.46041 | 37572.55250 | 2.30557 | 2.76669 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
12 | LGSTORE2 | Heating | 9307.38653 | 11168.86383 | 0.38460 | 0.46152 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 348.38640 | 56.25053 | 0.41148 | 0.00000 |
13 | SMSTORE5 | Cooling | 16539.80217 | 19847.76261 | 1.21793 | 1.46152 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
14 | SMSTORE5 | Heating | 4912.04907 | 5894.45888 | 0.20379 | 0.24455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
15 | SMSTORE6 | Cooling | 16484.17783 | 19781.01340 | 1.21384 | 1.45661 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 42.71917 | 1.07817E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
16 | SMSTORE6 | Heating | 4920.24407 | 5904.29288 | 0.20413 | 0.24495 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
17 | SMSTORE7 | Cooling | 16551.94919 | 19862.33903 | 1.21883 | 1.46259 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 42.63833 | 1.07815E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
18 | SMSTORE7 | Heating | 5127.05221 | 6152.46265 | 0.21278 | 0.25534 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
19 | SMSTORE8 | Cooling | 19352.25257 | 23222.70309 | 1.42497 | 1.70997 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 42.31500 | 1.07810E-002 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
20 | SMSTORE8 | Heating | 5915.25290 | 7098.30347 | 0.24680 | 0.29616 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 12.70000 | 9.15345E-003 | 174.19320 | 28.12446 | 0.20574 | 0.00000 |
System Name | Load Type | Peak Load Kind | User Design Capacity | Calc Des Air Flow Rate [m3/s] | User Des Air Flow Rate [m3/s] | Design Day Name | Date/Time of Peak | |
1 | PSZ-AC_1:1 | Cooling | Sensible | 50378.78 | 3.05560 | 3.05560 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
2 | PSZ-AC_1:1 | Heating | Sensible | 14633.00 | 0.45636 | 0.45636 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
3 | PSZ-AC_2:2 | Cooling | Sensible | 25387.68 | 1.54258 | 1.54258 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
4 | PSZ-AC_2:2 | Heating | Sensible | 7178.55 | 0.22261 | 0.22261 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
5 | PSZ-AC_3:3 | Cooling | Sensible | 25344.57 | 1.53950 | 1.53950 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
6 | PSZ-AC_3:3 | Heating | Sensible | 7219.37 | 0.22440 | 0.22440 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
7 | PSZ-AC_4:4 | Cooling | Sensible | 25383.23 | 1.54244 | 1.54244 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
8 | PSZ-AC_4:4 | Heating | Sensible | 7270.69 | 0.22665 | 0.22665 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
9 | PSZ-AC_5:5 | Cooling | Sensible | 25299.15 | 1.53617 | 1.53617 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
10 | PSZ-AC_5:5 | Heating | Sensible | 7414.89 | 0.23296 | 0.23296 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
11 | PSZ-AC_6:6 | Cooling | Sensible | 46497.55 | 2.76669 | 2.76669 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
12 | PSZ-AC_6:6 | Heating | Sensible | 14754.10 | 0.46152 | 0.46152 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
13 | PSZ-AC_7:7 | Cooling | Sensible | 24295.83 | 1.46152 | 1.46152 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
14 | PSZ-AC_7:7 | Heating | Sensible | 7696.08 | 0.24455 | 0.24455 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
15 | PSZ-AC_8:8 | Cooling | Sensible | 24229.83 | 1.45661 | 1.45661 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
16 | PSZ-AC_8:8 | Heating | Sensible | 7705.51 | 0.24495 | 0.24495 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
17 | PSZ-AC_9:9 | Cooling | Sensible | 24308.78 | 1.46259 | 1.46259 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
18 | PSZ-AC_9:9 | Heating | Sensible | 7947.57 | 0.25534 | 0.25534 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
19 | PSZ-AC_10:10 | Cooling | Sensible | 27530.40 | 1.70997 | 1.70997 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 05:00:00 |
20 | PSZ-AC_10:10 | Heating | Sensible | 8892.59 | 0.29616 | 0.29616 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
Component Type | Component Name | Input Field Description | Value | |
1 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 3.05560 |
2 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE1 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54258 |
3 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53950 |
4 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE3 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.54244 |
5 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE4 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.53617 |
6 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | LGSTORE2 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 2.76669 |
7 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE5 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46152 |
8 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE6 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.45661 |
9 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE7 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.46259 |
10 | AirTerminal:SingleDuct:ConstantVolume:NoReheat | SMSTORE8 DIRECT AIR | Design Size Maximum Air Flow Rate [m3/s] | 1.70997 |
11 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 3.05560 |
12 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 3.05560 |
13 | AirLoopHVAC | PSZ-AC_1:1 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 3.05560 |
14 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Heating Design Air Flow Rate [m3/s] | 3.05560 |
15 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Cooling Design Air Flow Rate [m3/s] | 3.05560 |
16 | AirLoopHVAC | PSZ-AC_1:1 | Adjusted Main Design Air Flow Rate [m3/s] | 3.05560 |
17 | AirLoopHVAC | PSZ-AC_1:1 | User Heating Air Flow Ratio [] | 1.00000 |
18 | AirLoopHVAC | PSZ-AC_1:1 | Calculated Heating Air Flow Ratio [] | 1.00000 |
19 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.54258 |
20 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54258 |
21 | AirLoopHVAC | PSZ-AC_2:2 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.54258 |
22 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54258 |
23 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.54258 |
24 | AirLoopHVAC | PSZ-AC_2:2 | Adjusted Main Design Air Flow Rate [m3/s] | 1.54258 |
25 | AirLoopHVAC | PSZ-AC_2:2 | User Heating Air Flow Ratio [] | 1.00000 |
26 | AirLoopHVAC | PSZ-AC_2:2 | Calculated Heating Air Flow Ratio [] | 1.00000 |
27 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53950 |
28 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53950 |
29 | AirLoopHVAC | PSZ-AC_3:3 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53950 |
30 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53950 |
31 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53950 |
32 | AirLoopHVAC | PSZ-AC_3:3 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53950 |
33 | AirLoopHVAC | PSZ-AC_3:3 | User Heating Air Flow Ratio [] | 1.00000 |
34 | AirLoopHVAC | PSZ-AC_3:3 | Calculated Heating Air Flow Ratio [] | 1.00000 |
35 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.54244 |
36 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.54244 |
37 | AirLoopHVAC | PSZ-AC_4:4 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.54244 |
38 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.54244 |
39 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.54244 |
40 | AirLoopHVAC | PSZ-AC_4:4 | Adjusted Main Design Air Flow Rate [m3/s] | 1.54244 |
41 | AirLoopHVAC | PSZ-AC_4:4 | User Heating Air Flow Ratio [] | 1.00000 |
42 | AirLoopHVAC | PSZ-AC_4:4 | Calculated Heating Air Flow Ratio [] | 1.00000 |
43 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.53617 |
44 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.53617 |
45 | AirLoopHVAC | PSZ-AC_5:5 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.53617 |
46 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.53617 |
47 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.53617 |
48 | AirLoopHVAC | PSZ-AC_5:5 | Adjusted Main Design Air Flow Rate [m3/s] | 1.53617 |
49 | AirLoopHVAC | PSZ-AC_5:5 | User Heating Air Flow Ratio [] | 1.00000 |
50 | AirLoopHVAC | PSZ-AC_5:5 | Calculated Heating Air Flow Ratio [] | 1.00000 |
51 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 2.76669 |
52 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 2.76669 |
53 | AirLoopHVAC | PSZ-AC_6:6 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 2.76669 |
54 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Heating Design Air Flow Rate [m3/s] | 2.76669 |
55 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Cooling Design Air Flow Rate [m3/s] | 2.76669 |
56 | AirLoopHVAC | PSZ-AC_6:6 | Adjusted Main Design Air Flow Rate [m3/s] | 2.76669 |
57 | AirLoopHVAC | PSZ-AC_6:6 | User Heating Air Flow Ratio [] | 1.00000 |
58 | AirLoopHVAC | PSZ-AC_6:6 | Calculated Heating Air Flow Ratio [] | 1.00000 |
59 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46152 |
60 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46152 |
61 | AirLoopHVAC | PSZ-AC_7:7 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46152 |
62 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46152 |
63 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46152 |
64 | AirLoopHVAC | PSZ-AC_7:7 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46152 |
65 | AirLoopHVAC | PSZ-AC_7:7 | User Heating Air Flow Ratio [] | 1.00000 |
66 | AirLoopHVAC | PSZ-AC_7:7 | Calculated Heating Air Flow Ratio [] | 1.00000 |
67 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.45661 |
68 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.45661 |
69 | AirLoopHVAC | PSZ-AC_8:8 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.45661 |
70 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.45661 |
71 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.45661 |
72 | AirLoopHVAC | PSZ-AC_8:8 | Adjusted Main Design Air Flow Rate [m3/s] | 1.45661 |
73 | AirLoopHVAC | PSZ-AC_8:8 | User Heating Air Flow Ratio [] | 1.00000 |
74 | AirLoopHVAC | PSZ-AC_8:8 | Calculated Heating Air Flow Ratio [] | 1.00000 |
75 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.46259 |
76 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.46259 |
77 | AirLoopHVAC | PSZ-AC_9:9 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.46259 |
78 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.46259 |
79 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.46259 |
80 | AirLoopHVAC | PSZ-AC_9:9 | Adjusted Main Design Air Flow Rate [m3/s] | 1.46259 |
81 | AirLoopHVAC | PSZ-AC_9:9 | User Heating Air Flow Ratio [] | 1.00000 |
82 | AirLoopHVAC | PSZ-AC_9:9 | Calculated Heating Air Flow Ratio [] | 1.00000 |
83 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Heating Flow Rates [m3/s] | 1.70997 |
84 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Minimum Heating Flow Rates [m3/s] | 1.70997 |
85 | AirLoopHVAC | PSZ-AC_10:10 | Sum of Air Terminal Maximum Flow Rates [m3/s] | 1.70997 |
86 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Heating Design Air Flow Rate [m3/s] | 1.70997 |
87 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Cooling Design Air Flow Rate [m3/s] | 1.70997 |
88 | AirLoopHVAC | PSZ-AC_10:10 | Adjusted Main Design Air Flow Rate [m3/s] | 1.70997 |
89 | AirLoopHVAC | PSZ-AC_10:10 | User Heating Air Flow Ratio [] | 1.00000 |
90 | AirLoopHVAC | PSZ-AC_10:10 | Calculated Heating Air Flow Ratio [] | 1.00000 |
91 | AirLoopHVAC | PSZ-AC_1:1 | Design Supply Air Flow Rate [m3/s] | 3.05560 |
92 | AirLoopHVAC | PSZ-AC_2:2 | Design Supply Air Flow Rate [m3/s] | 1.54258 |
93 | AirLoopHVAC | PSZ-AC_3:3 | Design Supply Air Flow Rate [m3/s] | 1.53950 |
94 | AirLoopHVAC | PSZ-AC_4:4 | Design Supply Air Flow Rate [m3/s] | 1.54244 |
95 | AirLoopHVAC | PSZ-AC_5:5 | Design Supply Air Flow Rate [m3/s] | 1.53617 |
96 | AirLoopHVAC | PSZ-AC_6:6 | Design Supply Air Flow Rate [m3/s] | 2.76669 |
97 | AirLoopHVAC | PSZ-AC_7:7 | Design Supply Air Flow Rate [m3/s] | 1.46152 |
98 | AirLoopHVAC | PSZ-AC_8:8 | Design Supply Air Flow Rate [m3/s] | 1.45661 |
99 | AirLoopHVAC | PSZ-AC_9:9 | Design Supply Air Flow Rate [m3/s] | 1.46259 |
100 | AirLoopHVAC | PSZ-AC_10:10 | Design Supply Air Flow Rate [m3/s] | 1.70997 |
101 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 3.05560 |
102 | Controller:OutdoorAir | PSZ-AC_1:1_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
103 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 3.05560 |
104 | Fan:SystemModel | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 3269.63710 |
105 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 3.05560 |
106 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 3.05560 |
107 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 3.05560 |
108 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 3.05560 |
109 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 3.05560 |
110 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.52780 |
111 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 3.05560 |
112 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 75351.43000 |
113 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 37165.31265 |
114 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 75351.43000 |
115 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70380 |
116 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70380 |
117 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 75351.43000 |
118 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 75266.54912 |
119 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
120 | AirLoopHVAC:UnitarySystem | PSZ-AC_1:1_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
121 | Coil:Heating:Fuel | PSZ-AC_1:1 HEATING COIL | Design Size Nominal Capacity [W] | 75266.54912 |
122 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.54258 |
123 | Controller:OutdoorAir | PSZ-AC_2:2_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
124 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.54258 |
125 | Fan:SystemModel | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1650.63232 |
126 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.54258 |
127 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.54258 |
128 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.54258 |
129 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.54258 |
130 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.54258 |
131 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77129 |
132 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.54258 |
133 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38014.94000 |
134 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 18749.71906 |
135 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 38014.94000 |
136 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70396 |
137 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70396 |
138 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38014.94000 |
139 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37333.98131 |
140 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
141 | AirLoopHVAC:UnitarySystem | PSZ-AC_2:2_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
142 | Coil:Heating:Fuel | PSZ-AC_2:2 HEATING COIL | Design Size Nominal Capacity [W] | 37333.98131 |
143 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53950 |
144 | Controller:OutdoorAir | PSZ-AC_3:3_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
145 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53950 |
146 | Fan:SystemModel | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1647.33857 |
147 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53950 |
148 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53950 |
149 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53950 |
150 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53950 |
151 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53950 |
152 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76975 |
153 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.53950 |
154 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37956.57000 |
155 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 18721.10351 |
156 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 37956.57000 |
157 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70385 |
158 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70385 |
159 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37956.57000 |
160 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37263.64700 |
161 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
162 | AirLoopHVAC:UnitarySystem | PSZ-AC_3:3_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
163 | Coil:Heating:Fuel | PSZ-AC_3:3 HEATING COIL | Design Size Nominal Capacity [W] | 37263.64700 |
164 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.54244 |
165 | Controller:OutdoorAir | PSZ-AC_4:4_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
166 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.54244 |
167 | Fan:SystemModel | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1650.48162 |
168 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.54244 |
169 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.54244 |
170 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.54244 |
171 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.54244 |
172 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.54244 |
173 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.77122 |
174 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.54244 |
175 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 38013.57000 |
176 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 18749.06390 |
177 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 38013.57000 |
178 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70395 |
179 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70395 |
180 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 38013.57000 |
181 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37330.75003 |
182 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
183 | AirLoopHVAC:UnitarySystem | PSZ-AC_4:4_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
184 | Coil:Heating:Fuel | PSZ-AC_4:4 HEATING COIL | Design Size Nominal Capacity [W] | 37330.75003 |
185 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.53617 |
186 | Controller:OutdoorAir | PSZ-AC_5:5_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
187 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.53617 |
188 | Fan:SystemModel | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1643.77491 |
189 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.53617 |
190 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.53617 |
191 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.53617 |
192 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.53617 |
193 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.53617 |
194 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.76809 |
195 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.53617 |
196 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 37892.69000 |
197 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 18689.76987 |
198 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 37892.69000 |
199 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70373 |
200 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70373 |
201 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 37892.69000 |
202 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 37187.56448 |
203 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
204 | AirLoopHVAC:UnitarySystem | PSZ-AC_5:5_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
205 | Coil:Heating:Fuel | PSZ-AC_5:5 HEATING COIL | Design Size Nominal Capacity [W] | 37187.56448 |
206 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 2.76669 |
207 | Controller:OutdoorAir | PSZ-AC_6:6_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.41148 |
208 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 2.76669 |
209 | Fan:SystemModel | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 2960.48514 |
210 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 2.76669 |
211 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 2.76669 |
212 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 2.76669 |
213 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 2.76669 |
214 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 2.76669 |
215 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 1.38334 |
216 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 2.76669 |
217 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 68703.41000 |
218 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 34304.71085 |
219 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 68703.41000 |
220 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
221 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
222 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 68703.41000 |
223 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 68552.11668 |
224 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
225 | AirLoopHVAC:UnitarySystem | PSZ-AC_6:6_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
226 | Coil:Heating:Fuel | PSZ-AC_6:6 HEATING COIL | Design Size Nominal Capacity [W] | 68552.11668 |
227 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46152 |
228 | Controller:OutdoorAir | PSZ-AC_7:7_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
229 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46152 |
230 | Fan:SystemModel | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1563.89689 |
231 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46152 |
232 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46152 |
233 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46152 |
234 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46152 |
235 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46152 |
236 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73076 |
237 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.46152 |
238 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36293.05000 |
239 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17982.27539 |
240 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36293.05000 |
241 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
242 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
243 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36293.05000 |
244 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36013.83705 |
245 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
246 | AirLoopHVAC:UnitarySystem | PSZ-AC_7:7_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
247 | Coil:Heating:Fuel | PSZ-AC_7:7 HEATING COIL | Design Size Nominal Capacity [W] | 36013.83705 |
248 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.45661 |
249 | Controller:OutdoorAir | PSZ-AC_8:8_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
250 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.45661 |
251 | Fan:SystemModel | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1558.63744 |
252 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.45661 |
253 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.45661 |
254 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.45661 |
255 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.45661 |
256 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.45661 |
257 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.72830 |
258 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.45661 |
259 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36171.00000 |
260 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17935.56126 |
261 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36171.00000 |
262 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
263 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
264 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36171.00000 |
265 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 35899.99028 |
266 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
267 | AirLoopHVAC:UnitarySystem | PSZ-AC_8:8_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
268 | Coil:Heating:Fuel | PSZ-AC_8:8 HEATING COIL | Design Size Nominal Capacity [W] | 35899.99028 |
269 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.46259 |
270 | Controller:OutdoorAir | PSZ-AC_9:9_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
271 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.46259 |
272 | Fan:SystemModel | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1565.04124 |
273 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.46259 |
274 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.46259 |
275 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.46259 |
276 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.46259 |
277 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.46259 |
278 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.73130 |
279 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.46259 |
280 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 36319.61000 |
281 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 17992.77175 |
282 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 36319.61000 |
283 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.70108 |
284 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.70108 |
285 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 36319.61000 |
286 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 36048.13502 |
287 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
288 | AirLoopHVAC:UnitarySystem | PSZ-AC_9:9_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
289 | Coil:Heating:Fuel | PSZ-AC_9:9 HEATING COIL | Design Size Nominal Capacity [W] | 36048.13502 |
290 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Maximum Outdoor Air Flow Rate [m3/s] | 1.70997 |
291 | Controller:OutdoorAir | PSZ-AC_10:10_OA_CONTROLLER | Minimum Outdoor Air Flow Rate [m3/s] | 0.20574 |
292 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Size Design Maximum Air Flow Rate [m3/s] | 1.70997 |
293 | Fan:SystemModel | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Design Electric Power Consumption [W] | 1829.74856 |
294 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Supply Air Flow Rate [m3/s] | 1.70997 |
295 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Heating Supply Air Flow Rate [m3/s] | 1.70997 |
296 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Cooling Supply Air Flow Rate [m3/s] | 1.70997 |
297 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size No Load Supply Air Flow Rate [m3/s] | 1.70997 |
298 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Air Flow Rate [m3/s] | 1.70997 |
299 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Rated Air Flow Rate [m3/s] | 0.85498 |
300 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Air Flow Rate [m3/s] | 1.70997 |
301 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Gross Rated Total Cooling Capacity [W] | 41222.07000 |
302 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | Design Size Speed 1 Gross Rated Total Cooling Capacity [W] | 20323.88913 |
303 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Gross Rated Total Cooling Capacity [W] | 41222.07000 |
304 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 2 Rated Sensible Heat Ratio | 0.71046 |
305 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | User-Specified Speed 1 Rated Sensible Heat Ratio | 0.71046 |
306 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | User-Specified Nominal Cooling Capacity [W] | 41222.07000 |
307 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Nominal Heating Capacity [W] | 41721.90511 |
308 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Design Size Maximum Supply Air Temperature [C] | 40.00000 |
309 | AirLoopHVAC:UnitarySystem | PSZ-AC_10:10_UNITARY_PACKAGE_DX | Fraction of Supply Air Flow That Goes Through the Controlling Zone | 1.00000 |
310 | Coil:Heating:Fuel | PSZ-AC_10:10 HEATING COIL | Design Size Nominal Capacity [W] | 41721.90511 |
Component Type | Component Name | Standard Rating (Net) Cooling Capacity {W} | Standard Rated Net COP {W/W} | EER {Btu/W-h} | SEER User {Btu/W-h} | SEER Standard {Btu/W-h} | IEER {Btu/W-h} | |
1 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_1:1 COOLING COIL | 72941.2 | 10.32 | 10.32 | |||
2 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_2:2 COOLING COIL | 36798.2 | 11.39 | 11.39 | |||
3 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_3:3 COOLING COIL | 36742.2 | 11.39 | 11.39 | |||
4 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_4:4 COOLING COIL | 36796.9 | 11.39 | 11.39 | |||
5 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_5:5 COOLING COIL | 36680.9 | 11.39 | 11.39 | |||
6 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_6:6 COOLING COIL | 66520.7 | 11.23 | 11.23 | |||
7 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_7:7 COOLING COIL | 35140.0 | 11.40 | 11.40 | |||
8 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_8:8 COOLING COIL | 35021.9 | 11.40 | 11.40 | |||
9 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_9:9 COOLING COIL | 35165.8 | 11.40 | 11.40 | |||
10 | Coil:Cooling:DX:MultiSpeed | PSZ-AC_10:10 COOLING COIL | 39873.8 | 11.19 | 11.19 |
Zone Name | # Surfaces | |
1 | LGSTORE1 | 15 |
2 | SMSTORE1 | 11 |
3 | SMSTORE2 | 11 |
4 | SMSTORE3 | 11 |
5 | SMSTORE4 | 11 |
6 | LGSTORE2 | 15 |
7 | SMSTORE5 | 11 |
8 | SMSTORE6 | 11 |
9 | SMSTORE7 | 11 |
10 | SMSTORE8 | 11 |
Surface Name | Surface Class | Base Surface | Heat Transfer Algorithm | Construction | Nominal U (w/o film coefs) {W/m2-K} | Nominal U (with film coefs) {W/m2-K} | Solar Diffusing | Area (Net) {m2} | Area (Gross) {m2} | Area (Sunlit Calc) {m2} | Azimuth {deg} | Tilt {deg} | ~Width {m} | ~Height {m} | Reveal {m} | ExtBoundCondition | ExtConvCoeffCalc | IntConvCoeffCalc | SunExposure | WindExposure | ViewFactorToGround | ViewFactorToSky | ViewFactorToGround-IR | ViewFactorToSky-IR | #Sides | |
1 | LGSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
2 | LGSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.15 | 78.94 | 71.15 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
3 | LGSTORE1_WALL_3_DOOR_1 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
4 | LGSTORE1_WALL_3_DOOR_2 | Door | LGSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
5 | LGSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
6 | LGSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.18 | 78.94 | 58.18 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
7 | LGSTORE1_WALL_1_WINDOW_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
8 | LGSTORE1_WALL_1_WINDOW_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
9 | LGSTORE1_WALL_1_WINDOW_3 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
10 | LGSTORE1_WALL_1_WINDOW_4 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
11 | LGSTORE1_WALL_1_DOOR_1 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
12 | LGSTORE1_WALL_1_DOOR_2 | Window | LGSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
13 | LGSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE1_FLOOR_FFACTOR | 0.199 | 0.190 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
14 | LGSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
15 | LGSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
16 | SMSTORE1_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.09 | 39.47 | 29.09 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
17 | SMSTORE1_WALL_1_WINDOW_1 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
18 | SMSTORE1_WALL_1_WINDOW_2 | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
19 | SMSTORE1_WALL_1_DOOR | Window | SMSTORE1_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.90 | 3.90 | 3.90 | 180.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
20 | SMSTORE1_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
21 | SMSTORE1_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.57 | 39.47 | 35.57 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
22 | SMSTORE1_WALL_3_DOOR | Door | SMSTORE1_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.90 | 3.90 | 3.90 | 0.00 | 90.00 | 1.83 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
23 | SMSTORE1_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
24 | SMSTORE1_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE1_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
25 | SMSTORE1_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
26 | SMSTORE1_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE1_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
27 | SMSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
28 | SMSTORE2_WALL_1_WINDOW_1 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
29 | SMSTORE2_WALL_1_WINDOW_2 | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
30 | SMSTORE2_WALL_1_DOOR | Window | SMSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
31 | SMSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE1_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
32 | SMSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
33 | SMSTORE2_WALL_3_DOOR | Door | SMSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
34 | SMSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
35 | SMSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
36 | SMSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
37 | SMSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
38 | SMSTORE3_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
39 | SMSTORE3_WALL_1_WINDOW_1 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
40 | SMSTORE3_WALL_1_WINDOW_2 | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
41 | SMSTORE3_WALL_1_DOOR | Window | SMSTORE3_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
42 | SMSTORE3_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
43 | SMSTORE3_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
44 | SMSTORE3_WALL_3_DOOR | Door | SMSTORE3_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
45 | SMSTORE3_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
46 | SMSTORE3_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE3_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
47 | SMSTORE3_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
48 | SMSTORE3_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE3_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
49 | SMSTORE4_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
50 | SMSTORE4_WALL_1_WINDOW_1 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
51 | SMSTORE4_WALL_1_WINDOW_2 | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
52 | SMSTORE4_WALL_1_DOOR | Window | SMSTORE4_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
53 | SMSTORE4_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE3_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
54 | SMSTORE4_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
55 | SMSTORE4_WALL_3_DOOR | Door | SMSTORE4_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
56 | SMSTORE4_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
57 | SMSTORE4_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE4_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
58 | SMSTORE4_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
59 | SMSTORE4_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE4_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
60 | LGSTORE2_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE4_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
61 | LGSTORE2_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 71.19 | 78.94 | 71.19 | 0.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
62 | LGSTORE2_WALL_3_DOOR_1 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
63 | LGSTORE2_WALL_3_DOOR_2 | Door | LGSTORE2_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
64 | LGSTORE2_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
65 | LGSTORE2_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 58.22 | 78.94 | 58.22 | 180.00 | 90.00 | 15.24 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
66 | LGSTORE2_WALL_1_WINDOW_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
67 | LGSTORE2_WALL_1_WINDOW_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
68 | LGSTORE2_WALL_1_WINDOW_3 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
69 | LGSTORE2_WALL_1_WINDOW_4 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
70 | LGSTORE2_WALL_1_DOOR_1 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
71 | LGSTORE2_WALL_1_DOOR_2 | Window | LGSTORE2_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
72 | LGSTORE2_FLOOR | Floor | CTF - ConductionTransferFunction | LGSTORE2_FLOOR_FFACTOR | 0.112 | 0.109 | 348.39 | 348.39 | 348.39 | 270.00 | 180.00 | 22.86 | 15.24 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
73 | LGSTORE2_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 348.39 | 348.39 | 348.39 | 270.00 | 0.00 | 22.86 | 15.24 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
74 | LGSTORE2_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 696.77 | 696.77 | 696.77 | 0.00 | 90.00 | 696.77 | 1.00 | 0.00 | LGSTORE2_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
75 | SMSTORE5_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
76 | SMSTORE5_WALL_1_WINDOW_1 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
77 | SMSTORE5_WALL_1_WINDOW_2 | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
78 | SMSTORE5_WALL_1_DOOR | Window | SMSTORE5_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
79 | SMSTORE5_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | LGSTORE2_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
80 | SMSTORE5_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
81 | SMSTORE5_WALL_3_DOOR | Door | SMSTORE5_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
82 | SMSTORE5_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
83 | SMSTORE5_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE5_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
84 | SMSTORE5_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
85 | SMSTORE5_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE5_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
86 | SMSTORE6_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
87 | SMSTORE6_WALL_1_WINDOW_1 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
88 | SMSTORE6_WALL_1_WINDOW_2 | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
89 | SMSTORE6_WALL_1_DOOR | Window | SMSTORE6_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
90 | SMSTORE6_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE5_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
91 | SMSTORE6_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
92 | SMSTORE6_WALL_3_DOOR | Door | SMSTORE6_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
93 | SMSTORE6_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
94 | SMSTORE6_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE6_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
95 | SMSTORE6_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
96 | SMSTORE6_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE6_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
97 | SMSTORE7_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
98 | SMSTORE7_WALL_1_WINDOW_1 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
99 | SMSTORE7_WALL_1_WINDOW_2 | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
100 | SMSTORE7_WALL_1_DOOR | Window | SMSTORE7_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
101 | SMSTORE7_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE6_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
102 | SMSTORE7_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.59 | 39.47 | 35.59 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
103 | SMSTORE7_WALL_3_DOOR | Door | SMSTORE7_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
104 | SMSTORE7_WALL_4 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE8_WALL_2 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
105 | SMSTORE7_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE7_FLOOR_FFACTOR | 0.112 | 0.109 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
106 | SMSTORE7_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
107 | SMSTORE7_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE7_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 | ||
108 | SMSTORE8_WALL_1 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 29.11 | 39.47 | 29.11 | 180.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
109 | SMSTORE8_WALL_1_WINDOW_1 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
110 | SMSTORE8_WALL_1_WINDOW_2 | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.24 | 3.24 | 3.24 | 180.00 | 90.00 | 2.13 | 1.52 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
111 | SMSTORE8_WALL_1_DOOR | Window | SMSTORE8_WALL_1 | Window5 Detailed Fenestration | NONRESWINDOW_U_0.5032_SHGC_0.25 | N/A | 2.861 | No | 3.88 | 3.88 | 3.88 | 180.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 |
112 | SMSTORE8_WALL_2 | Wall | CTF - ConductionTransferFunction | INT_WALL | 6.299 | 3.242 | 118.41 | 118.41 | 118.41 | 270.00 | 90.00 | 22.86 | 5.18 | 0.00 | SMSTORE7_WALL_4 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
113 | SMSTORE8_WALL_3 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 35.60 | 39.47 | 35.60 | 0.00 | 90.00 | 7.62 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
114 | SMSTORE8_WALL_3_DOOR | Door | SMSTORE8_WALL_3 | CTF - ConductionTransferFunction | SWINGING DOOR_CON | 3.464 | 3.464 | 3.88 | 3.88 | 3.88 | 0.00 | 90.00 | 1.82 | 2.13 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | |
115 | SMSTORE8_WALL_4 | Wall | CTF - ConductionTransferFunction | NONRES_EXT_WALL_GRD | 0.754 | 0.678 | 118.41 | 118.41 | 118.41 | 90.00 | 90.00 | 22.86 | 5.18 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.50 | 0.50 | 0.50 | 0.50 | 4 | ||
116 | SMSTORE8_FLOOR | Floor | CTF - ConductionTransferFunction | SMSTORE8_FLOOR_FFACTOR | 0.289 | 0.270 | 174.19 | 174.19 | 174.19 | 270.00 | 180.00 | 22.86 | 7.62 | 0.00 | FCGround | N/A-FCGround | ASHRAETARP | NoSun | NoWind | 1.00 | 0.00 | 1.00 | 0.00 | 4 | ||
117 | SMSTORE8_ROOF | Roof | CTF - ConductionTransferFunction | NONRES_ROOF | 0.283 | 0.269 | 174.19 | 174.19 | 174.19 | 270.00 | 0.00 | 22.86 | 7.62 | 0.00 | ExternalEnvironment | ASHRAETARP | ASHRAETARP | SunExposed | WindExposed | 0.00 | 1.00 | 0.00 | 1.00 | 4 | ||
118 | SMSTORE8_INTERNALMASS_1 | Internal Mass | CTF - ConductionTransferFunction | INTERIORFURNISHINGS | 0.800 | 0.800 | 348.39 | 348.39 | 348.39 | 0.00 | 90.00 | 348.39 | 1.00 | 0.00 | SMSTORE8_INTERNALMASS_1 | Other/Same Surface Int Conv | ASHRAETARP | NoSun | NoWind | 0.00 | 0.50 | 1.00 | 0.00 | 0 |
Environment Name | Environment Type | Start Date | End Date | Start DayOfWeek | Duration {#days} | Source:Start DayOfWeek | Use Daylight Saving | Use Holidays | Apply Weekend Holiday Rule | Use Rain Values | Use Snow Values | Sky Temperature Model | |
1 | RUNPERIOD 1 | WeatherFileRunPeriod | 01/01/2017 | 12/31/2017 | Sunday | 365 | Use RunPeriod Specified Day | No | No | No | Yes | Yes | Clark and Allen |
Special Day Name | Special Day Type | Source | Start Date | Duration {#days} | |
1 | NEW YEARS DAY | Holiday | InputFile | 01/01 | 1Environment:Special Days |
Daylight Saving Indicator | Source | Start Date | End Date | |
1 | Yes | InputFile | 03/12 | 11/05 |
Style | Unit Conversion | |
1 | Commaandhtml | commaandhtml |
Zone Name | Environment Type/Name | Average Warmup Temperature Difference {deltaC} | Std Dev Warmup Temperature Difference {deltaC} | Max Temperature Pass/Fail Convergence | Min Temperature Pass/Fail Convergence | Average Warmup Load Difference {W} | Std Dev Warmup Load Difference {W} | Heating Load Pass/Fail Convergence | Cooling Load Pass/Fail Convergence | |
1 | LGSTORE1 | RunPeriod: RUNPERIOD 1 | 1.9991101006E-002 | 3.7580491163E-002 | Pass | Pass | 4.3419037905E-002 | 0.1198329711 | Pass | Pass |
2 | SMSTORE1 | RunPeriod: RUNPERIOD 1 | 1.7963318877E-002 | 4.1036775213E-002 | Pass | Pass | 3.7251673111E-002 | 0.1138995173 | Pass | Pass |
3 | SMSTORE2 | RunPeriod: RUNPERIOD 1 | 3.5276095981E-002 | 7.5633647821E-002 | Pass | Pass | 7.0917146226E-002 | 0.4165448565 | Pass | Pass |
4 | SMSTORE3 | RunPeriod: RUNPERIOD 1 | 3.5960761864E-002 | 7.4400135141E-002 | Pass | Pass | 7.1545810657E-002 | 0.3838887551 | Pass | Pass |
5 | SMSTORE4 | RunPeriod: RUNPERIOD 1 | 3.6916199377E-002 | 7.1983453556E-002 | Pass | Pass | 7.7157355114E-002 | 0.3520768513 | Pass | Pass |
6 | LGSTORE2 | RunPeriod: RUNPERIOD 1 | 3.5080228759E-002 | 6.2897023776E-002 | Pass | Pass | 0.1056811517 | 0.4029907898 | Pass | Pass |
7 | SMSTORE5 | RunPeriod: RUNPERIOD 1 | 3.4745469262E-002 | 6.2068544179E-002 | Pass | Pass | 0.1761709266 | 0.6630211699 | Pass | Pass |
8 | SMSTORE6 | RunPeriod: RUNPERIOD 1 | 3.5087722682E-002 | 6.1525605804E-002 | Pass | Pass | 0.2022948582 | 0.8556751955 | Pass | Pass |
9 | SMSTORE7 | RunPeriod: RUNPERIOD 1 | 3.6748495694E-002 | 6.1052393253E-002 | Pass | Pass | 0.2917349322 | 1.6129678081 | Pass | Pass |
10 | SMSTORE8 | RunPeriod: RUNPERIOD 1 | 4.7850558294E-002 | 7.0306043723E-002 | Pass | Pass | 6.3051219891E-002 | 0.1851643280 | Pass | Pass |
Report: Annual Heat Emissions Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Heat Emission by ComponentsEnvelope Convection | Zone Exfiltration | Zone Exhaust Air | HVAC Relief Air | HVAC Reject Heat | Total | |
Heat Emissions [GJ] | 2272.64 | -438.1 | 0.00 | -946.2 | 3400.09 | 4288.50 |
Report: Climatic Data Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
SizingPeriod:DesignDayMaximum Dry Bulb [C] | Daily Temperature Range [deltaC] | Humidity Value | Humidity Type | Wind Speed [m/s] | Wind Direction | |
DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 12.70 | 0.00 | 12.70 | Wetbulb [C] | 2.00 | 170.00 |
DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 42.80 | 9.70 | 23.80 | Wetbulb [C] | 5.00 | 80.00 |
Monthly Total Precipitation from .epw [mm] | Monthly Total Hours of Rain from .epw | Monthly Total Precipitation in Site:Precipitation [mm] | Monthly Total Roof Irrigation Depth [mm] | Monthly Total Rain Collection Volume [m3] | |
Jan | 2.40 | 26 | |||
Feb | 9.60 | 38 | |||
Mar | 3.60 | 37 | |||
Apr | 0.00 | 0 | |||
May | 0.00 | 0 | |||
Jun | 0.00 | 0 | |||
Jul | 1.20 | 13 | |||
Aug | 0.00 | 0 | |||
Sep | 0.00 | 0 | |||
Oct | 0.00 | 0 | |||
Nov | 0.00 | 0 | |||
Dec | 18.00 | 37 |
Value | |
None |
Report: Envelope Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Opaque ExteriorConstruction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_2 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.15 | 0.00 | 90.00 | N |
LGSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.18 | 180.00 | 90.00 | S |
LGSTORE1_FLOOR | LGSTORE1_FLOOR_FFACTOR | 1.00 | 0.193 | 0.199 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE1_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.09 | 180.00 | 90.00 | S |
SMSTORE1_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.57 | 0.00 | 90.00 | N |
SMSTORE1_FLOOR | SMSTORE1_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE1_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE2_FLOOR | SMSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE3_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE3_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE3_FLOOR | SMSTORE3_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE3_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE4_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE4_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE4_FLOOR | SMSTORE4_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE4_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
LGSTORE2_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 71.19 | 0.00 | 90.00 | N |
LGSTORE2_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 78.94 | 58.22 | 180.00 | 90.00 | S |
LGSTORE2_FLOOR | LGSTORE2_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 348.39 | 348.39 | 270.00 | 180.00 | |
LGSTORE2_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 348.39 | 348.39 | 270.00 | 0.00 | |
SMSTORE5_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE5_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE5_FLOOR | SMSTORE5_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE5_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE6_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE6_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE6_FLOOR | SMSTORE6_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE6_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE7_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE7_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.59 | 0.00 | 90.00 | N |
SMSTORE7_FLOOR | SMSTORE7_FLOOR_FFACTOR | 1.00 | 0.110 | 0.112 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE7_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 | |
SMSTORE8_WALL_1 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 29.11 | 180.00 | 90.00 | S |
SMSTORE8_WALL_3 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 39.47 | 35.60 | 0.00 | 90.00 | N |
SMSTORE8_WALL_4 | NONRES_EXT_WALL_GRD | 0.30 | 0.678 | 0.754 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_FLOOR | SMSTORE8_FLOOR_FFACTOR | 1.00 | 0.276 | 0.289 | 174.19 | 174.19 | 270.00 | 180.00 | |
SMSTORE8_ROOF | NONRES_ROOF | 0.55 | 0.273 | 0.283 | 174.19 | 174.19 | 270.00 | 0.00 |
Construction | Reflectance | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Net Area [m2] | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE1_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE1_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE3_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE3_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE4_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE4_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
LGSTORE2_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE2_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE5_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE5_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE6_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE6_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE7_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
SMSTORE7_WALL_4 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 90.00 | 90.00 | E |
SMSTORE8_WALL_2 | INT_WALL | 0.30 | 2.511 | 6.299 | 118.41 | 118.41 | 270.00 | 90.00 | W |
LGSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE1_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE3_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE4_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
LGSTORE2_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 696.77 | 0.00 | 90.00 | N | ||
SMSTORE5_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE6_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE7_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N | ||
SMSTORE8_INTERNALMASS_1 | INTERIORFURNISHINGS | 0.30 | 0.800 | 348.39 | 0.00 | 90.00 | N |
Construction | Frame and Divider | Glass Area [m2] | Frame Area [m2] | Divider Area [m2] | Area of One Opening [m2] | Area of Multiplied Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | Frame Conductance [W/m2-K] | Divider Conductance [W/m2-K] | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | Shade Control | Parent Surface | Azimuth [deg] | Tilt [deg] | Cardinal Direction | |
LGSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE1_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | LGSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE1_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.90 | 0.00 | 0.00 | 3.90 | 3.90 | 2.861 | 0.251 | 0.251 | No | SMSTORE1_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE2_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE3_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE3_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE4_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE4_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_3 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_WINDOW_4 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
LGSTORE2_WALL_1_DOOR_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | LGSTORE2_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE5_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE5_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE6_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE6_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE7_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE7_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_1 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_WINDOW_2 | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.24 | 0.00 | 0.00 | 3.24 | 3.24 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
SMSTORE8_WALL_1_DOOR | NONRESWINDOW_U_0.5032_SHGC_0.25 | 3.88 | 0.00 | 0.00 | 3.88 | 3.88 | 2.861 | 0.251 | 0.251 | No | SMSTORE8_WALL_1 | 180.00 | 90.00 | S | |||||||
Total or Average | 124.40 | 2.861 | 0.251 | 0.251 | |||||||||||||||||
North Total or Average | 0.00 | - | - | - | |||||||||||||||||
Non-North Total or Average | 124.40 | 2.861 | 0.251 | 0.251 |
Frame and Divider | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | NFRC Product Type | Assembly U-Factor [W/m2-K] | Assembly SHGC | Assembly Visible Transmittance | |
None |
Construction | Area of One Opening [m2] | Area of Openings [m2] | Glass U-Factor [W/m2-K] | Glass SHGC | Glass Visible Transmittance | |
Total or Average | 0.00 | - | - | - |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
LGSTORE1_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
LGSTORE1_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | LGSTORE1_WALL_3 |
SMSTORE1_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.90 | SMSTORE1_WALL_3 |
SMSTORE2_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE2_WALL_3 |
SMSTORE3_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE3_WALL_3 |
SMSTORE4_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE4_WALL_3 |
LGSTORE2_WALL_3_DOOR_1 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
LGSTORE2_WALL_3_DOOR_2 | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | LGSTORE2_WALL_3 |
SMSTORE5_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE5_WALL_3 |
SMSTORE6_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE6_WALL_3 |
SMSTORE7_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE7_WALL_3 |
SMSTORE8_WALL_3_DOOR | SWINGING DOOR_CON | 2.281 | 3.464 | 3.88 | SMSTORE8_WALL_3 |
Construction | U-Factor with Film [W/m2-K] | U-Factor no Film [W/m2-K] | Gross Area [m2] | Parent Surface | |
None |
Report: Shading Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Sunlit FractionMarch 21 9am | March 21 noon | March 21 3pm | June 21 9am | June 21 noon | June 21 3pm | December 21 9am | December 21 noon | December 21 3pm | |
LGSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE1_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE1_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE2_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE3_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE4_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_3 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_WINDOW_4 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
LGSTORE2_WALL_1_DOOR_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE5_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE6_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE7_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_1 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_WINDOW_2 | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
SMSTORE8_WALL_1_DOOR | 1.00 | 1.00 | 1.00 | 0.00 | 1.00 | 0.00 | 1.00 | 1.00 | 1.00 |
Name | Type | Shaded Construction | Control | Glare Control | |
None |
Report: Lighting Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Interior LightingZone Name | Space Name | Space Type | Lighting Power Density [W/m2] | Space Area [m2] | Total Power [W] | End Use Subcategory | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Return Air Fraction | Conditioned (Y/N) | Consumption [GJ] | |
LGSTORE1_LIGHTS | LGSTORE1 | LGSTORE1 | GENERAL | 12.8507 | 348.39 | 4477.00 | LightsWired | LTG_SCH_BASE_LPD1 | 84.21 | 168.00 | 84.19 | 0.0000 | Y | 70.75 |
LGSTORE1_LIGHTS_ALLOWANCE | LGSTORE1 | LGSTORE1 | GENERAL | 5.6429 | 348.39 | 1965.92 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 35.97 |
SMSTORE1_LIGHTS | SMSTORE1 | SMSTORE1 | GENERAL | 13.0380 | 174.19 | 2271.13 | LightsWired | LTG_SCH_BASE_SMALL_LPD1 | 85.70 | 168.00 | 85.69 | 0.0000 | Y | 36.53 |
SMSTORE1_LIGHTS_ALLOWANCE | SMSTORE1 | SMSTORE1 | GENERAL | 8.0838 | 174.19 | 1408.14 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 97.50 | 168.00 | 97.48 | 0.0000 | Y | 25.77 |
SMSTORE2_LIGHTS | SMSTORE2 | SMSTORE2 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE2_LIGHTS_ALLOWANCE | SMSTORE2 | SMSTORE2 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE3_LIGHTS | SMSTORE3 | SMSTORE3 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE3_LIGHTS_ALLOWANCE | SMSTORE3 | SMSTORE3 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
SMSTORE4_LIGHTS | SMSTORE4 | SMSTORE4 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 68.73 | 168.00 | 68.21 | 0.0000 | Y | 29.02 |
SMSTORE4_LIGHTS_ALLOWANCE | SMSTORE4 | SMSTORE4 | GENERAL | 6.2539 | 174.19 | 1089.39 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 78.55 | 168.00 | 77.96 | 0.0000 | Y | 15.94 |
LGSTORE2_LIGHTS | LGSTORE2 | LGSTORE2 | GENERAL | 12.8251 | 348.39 | 4468.07 | LightsWired | LTG_SCH_BASE_LPD2 | 62.11 | 168.00 | 61.60 | 0.0000 | Y | 51.67 |
LGSTORE2_LIGHTS_ALLOWANCE | LGSTORE2 | LGSTORE2 | GENERAL | 0.0000 | 348.39 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE5_LIGHTS | SMSTORE5 | SMSTORE5 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE5_LIGHTS_ALLOWANCE | SMSTORE5 | SMSTORE5 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE6_LIGHTS | SMSTORE6 | SMSTORE6 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE6_LIGHTS_ALLOWANCE | SMSTORE6 | SMSTORE6 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE7_LIGHTS | SMSTORE7 | SMSTORE7 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE7_LIGHTS_ALLOWANCE | SMSTORE7 | SMSTORE7 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
SMSTORE8_LIGHTS | SMSTORE8 | SMSTORE8 | GENERAL | 13.0124 | 174.19 | 2266.66 | LightsWired | LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 63.22 | 168.00 | 62.70 | 0.0000 | Y | 26.68 |
SMSTORE8_LIGHTS_ALLOWANCE | SMSTORE8 | SMSTORE8 | GENERAL | 0.0000 | 174.19 | 0.00 | LightsWired | LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 72.25 | 0.00 | 0.0000 | Y | 0.00 | |
Interior Lighting Total | 8.0670 | 4180.64 | 33725.07 | 462.30 |
Zone | Control Name | Daylighting Method | Control Type | Fraction Controlled | Lighting Installed in Zone [W] | Lighting Controlled [W] | |
None |
Total Watts | Astronomical Clock/Schedule | Schedule Name | Scheduled Hours/Week [hr] | Hours/Week > 1% [hr] | Full Load Hours/Week [hr] | Consumption [GJ] | |
EXTERIOR_LIGHTS | 7723.26 | AstronomicalClock | - | 83.85 | 83.85 | 121.56 | |
Exterior Lighting Total | 7723.26 | 121.56 |
Report: Equipment Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Central PlantType | Reference Capacity [W] | Reference Efficiency [W/W] | Rated Capacity [W] | Rated Efficiency [W/W] | IPLV in SI Units [W/W] | IPLV in IP Units [Btu/W-h] | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Sensible Capacity [W] | Nominal Latent Capacity [W] | Nominal Sensible Heat Ratio | Nominal Efficiency [W/W] | Nominal Coil UA Value [W/C] | Nominal Coil Surface Area [m2] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 75351.43 | 53032.34 | 22319.09 | 0.70 | 3.40 | |||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38014.94 | 26761.00 | 11253.94 | 0.70 | 3.80 | |||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37956.57 | 26715.73 | 11240.84 | 0.70 | 3.80 | |||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 38013.57 | 26759.65 | 11253.92 | 0.70 | 3.80 | |||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 37892.69 | 26666.22 | 11226.47 | 0.70 | 3.80 | |||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 68703.41 | 48166.59 | 20536.82 | 0.70 | 3.73 | |||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36293.05 | 25444.33 | 10848.72 | 0.70 | 3.80 | |||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36171.00 | 25358.76 | 10812.24 | 0.70 | 3.80 | |||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 36319.61 | 25462.95 | 10856.66 | 0.70 | 3.80 | |||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | 41222.07 | 29286.63 | 11935.44 | 0.71 | 3.73 |
DX Cooling Coil Type | Standard Rated Net Cooling Capacity [W] | Standard Rated Net COP [W/W] | EER [Btu/W-h] | SEER User [Btu/W-h] | SEER Standard [Btu/W-h] | IEER [Btu/W-h] | |
PSZ-AC_1:1 COOLING COIL | 72941.2 | 10.32 | 10.32 | ||||
PSZ-AC_2:2 COOLING COIL | 36798.2 | 11.39 | 11.39 | ||||
PSZ-AC_3:3 COOLING COIL | 36742.2 | 11.39 | 11.39 | ||||
PSZ-AC_4:4 COOLING COIL | 36796.9 | 11.39 | 11.39 | ||||
PSZ-AC_5:5 COOLING COIL | 36680.9 | 11.39 | 11.39 | ||||
PSZ-AC_6:6 COOLING COIL | 66520.7 | 11.23 | 11.23 | ||||
PSZ-AC_7:7 COOLING COIL | 35140.0 | 11.40 | 11.40 | ||||
PSZ-AC_8:8 COOLING COIL | 35021.9 | 11.40 | 11.40 | ||||
PSZ-AC_9:9 COOLING COIL | 35165.8 | 11.40 | 11.40 | ||||
PSZ-AC_10:10 COOLING COIL | 39873.8 | 11.19 | 11.19 |
DX Cooling Coil Type | Rated Net Cooling Capacity Test A [W] | Rated Electric Power Test A [W] | Rated Net Cooling Capacity Test B [W] | Rated Electric Power Test B [W] | Rated Net Cooling Capacity Test C [W] | Rated Electric Power Test C [W] | Rated Net Cooling Capacity Test D [W] | Rated Electric Power Test D [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | ||||||||
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed |
DX Heating Coil Type | High Temperature Heating (net) Rating Capacity [W] | Low Temperature Heating (net) Rating Capacity [W] | HSPF [Btu/W-h] | Region Number | |
None |
Type | Design Coil Load [W] | Nominal Total Capacity [W] | Nominal Efficiency [W/W] | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | 75266.55 | 0.80 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | 37333.98 | 0.80 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | 37263.65 | 0.80 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | 37330.75 | 0.80 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | 37187.56 | 0.80 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | 68552.12 | 0.80 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | 36013.84 | 0.80 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | 35899.99 | 0.80 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | 36048.14 | 0.80 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | 41721.91 | 0.80 |
Type | Total Efficiency [W/W] | Delta Pressure [pa] | Max Air Flow Rate [m3/s] | Rated Electricity Rate [W] | Rated Power Per Max Air Flow Rate [W-s/m3] | Motor Heat In Air Fraction | Fan Energy Index | End Use Subcategory | Design Day Name for Fan Sizing Peak | Date/Time for Fan Sizing Peak | |
PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 3.06 | 3269.64 | 1070.05 | 1.00 | 1.26 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1650.63 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1647.34 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1650.48 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.54 | 1643.77 | 1070.05 | 1.00 | 1.36 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 |
PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 2.77 | 2960.49 | 1070.05 | 1.00 | 1.27 | General | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 |
PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1563.90 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1558.64 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.46 | 1565.04 | 1070.05 | 1.00 | 1.37 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 0.58 | 622.50 | 1.71 | 1829.75 | 1070.05 | 1.00 | 1.34 | General | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 |
Type | Control | Head [pa] | Water Flow [m3/s] | Electricity Rate [W] | Power Per Water Flow Rate [W-s/m3] | Motor Efficiency [W/W] | End Use Subcategory | |
None |
Type | Storage Volume [m3] | Input [W] | Thermal Efficiency [W/W] | Recovery Efficiency [W/W] | Energy Factor | |
GAS TANK1 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK2 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK3 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK4 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK5 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK6 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
GAS TANK7 | WaterHeater:Mixed | 0.15 | 11722.84 | 1.00 | 1.02 | 0.72 |
Report: HVAC Sizing Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Zone Sensible CoolingCalculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 34579.41 | 41495.29 | 119.11 | 2.546 | 3.056 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 23.89 | 23.89 | 0.00786 | 42.80 | 0.01078 | 0.411 | 0.00 |
SMSTORE1 | 17457.10 | 20948.52 | 120.26 | 1.285 | 1.543 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 23.89 | 23.89 | 0.00787 | 42.80 | 0.01078 | 0.206 | 0.00 |
SMSTORE2 | 17422.27 | 20906.73 | 120.02 | 1.283 | 1.540 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00787 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE3 | 17455.52 | 20946.62 | 120.25 | 1.285 | 1.542 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00787 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE4 | 17384.59 | 20861.51 | 119.76 | 1.280 | 1.536 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00787 | 42.72 | 0.01078 | 0.206 | 0.00 |
LGSTORE2 | 31310.46 | 37572.55 | 107.85 | 2.306 | 2.767 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00790 | 42.72 | 0.01078 | 0.411 | 0.00 |
SMSTORE5 | 16539.80 | 19847.76 | 113.94 | 1.218 | 1.462 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00791 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE6 | 16484.18 | 19781.01 | 113.56 | 1.214 | 1.457 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 23.89 | 23.89 | 0.00791 | 42.72 | 0.01078 | 0.206 | 0.00 |
SMSTORE7 | 16551.95 | 19862.34 | 114.02 | 1.219 | 1.463 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 23.89 | 23.89 | 0.00791 | 42.64 | 0.01078 | 0.206 | 0.00 |
SMSTORE8 | 19352.25 | 23222.70 | 133.32 | 1.425 | 1.710 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 23.89 | 23.88 | 0.00786 | 42.31 | 0.01078 | 0.206 | 0.00 |
Calculated Design Load [W] | User Design Load [W] | User Design Load per Area [W/m2] | Calculated Design Air Flow [m3/s] | User Design Air Flow [m3/s] | Design Day Name | Date/Time Of Peak {TIMESTAMP} | Thermostat Setpoint Temperature at Peak Load [C] | Indoor Temperature at Peak Load [C] | Indoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Outdoor Temperature at Peak Load [C] | Outdoor Humidity Ratio at Peak Load [kgWater/kgDryAir] | Minimum Outdoor Air Flow Rate [m3/s] | Heat Gain Rate from DOAS [W] | |
LGSTORE1 | 9187.56 | 11025.07 | 31.65 | 0.380 | 0.456 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00847 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE1 | 4300.75 | 5160.90 | 29.63 | 0.186 | 0.223 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00856 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE2 | 4335.28 | 5202.33 | 29.87 | 0.187 | 0.224 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00856 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE3 | 4378.67 | 5254.40 | 30.16 | 0.189 | 0.227 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00856 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE4 | 4500.61 | 5400.74 | 31.00 | 0.194 | 0.233 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 21.11 | 21.11 | 0.00855 | 12.70 | 0.00915 | 0.206 | 0.00 |
LGSTORE2 | 9307.39 | 11168.86 | 32.06 | 0.385 | 0.462 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00847 | 12.70 | 0.00915 | 0.411 | 0.00 |
SMSTORE5 | 4912.05 | 5894.46 | 33.84 | 0.204 | 0.245 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00847 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE6 | 4920.24 | 5904.29 | 33.90 | 0.204 | 0.245 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00847 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE7 | 5127.05 | 6152.46 | 35.32 | 0.213 | 0.255 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00845 | 12.70 | 0.00915 | 0.206 | 0.00 |
SMSTORE8 | 5915.25 | 7098.30 | 40.75 | 0.247 | 0.296 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 21.11 | 21.11 | 0.00852 | 12.70 | 0.00915 | 0.206 | 0.00 |
Calculated cooling [m3/s] | User cooling [m3/s] | Calculated heating [m3/s] | User heating [m3/s] | Adjusted cooling [m3/s] | Adjusted heating [m3/s] | Adjusted main [m3/s] | Calculated Heating Air Flow Ratio [] | User Heating Air Flow Ratio [] | |
PSZ-AC_1:1 | 3.06 | 3.06 | 0.46 | 0.46 | 3.0556 | 3.0556 | 3.0556 | 1.0000 | 1.0000 |
PSZ-AC_2:2 | 1.54 | 1.54 | 0.22 | 0.22 | 1.5426 | 1.5426 | 1.5426 | 1.0000 | 1.0000 |
PSZ-AC_3:3 | 1.54 | 1.54 | 0.22 | 0.22 | 1.5395 | 1.5395 | 1.5395 | 1.0000 | 1.0000 |
PSZ-AC_4:4 | 1.54 | 1.54 | 0.23 | 0.23 | 1.5424 | 1.5424 | 1.5424 | 1.0000 | 1.0000 |
PSZ-AC_5:5 | 1.54 | 1.54 | 0.23 | 0.23 | 1.5362 | 1.5362 | 1.5362 | 1.0000 | 1.0000 |
PSZ-AC_6:6 | 2.77 | 2.77 | 0.46 | 0.46 | 2.7667 | 2.7667 | 2.7667 | 1.0000 | 1.0000 |
PSZ-AC_7:7 | 1.46 | 1.46 | 0.24 | 0.24 | 1.4615 | 1.4615 | 1.4615 | 1.0000 | 1.0000 |
PSZ-AC_8:8 | 1.46 | 1.46 | 0.24 | 0.24 | 1.4566 | 1.4566 | 1.4566 | 1.0000 | 1.0000 |
PSZ-AC_9:9 | 1.46 | 1.46 | 0.26 | 0.26 | 1.4626 | 1.4626 | 1.4626 | 1.0000 | 1.0000 |
PSZ-AC_10:10 | 1.71 | 1.71 | 0.30 | 0.30 | 1.7100 | 1.7100 | 1.7100 | 1.0000 | 1.0000 |
Previous Design Volume Flow Rate [m3/s] | Algorithm Volume Flow Rate [m3/s] | Coincident Design Volume Flow Rate [m3/s] | Coincident Size Adjusted | Peak Sizing Period Name | Peak Day into Period {TIMESTAMP}[day] | Peak Hour Of Day {TIMESTAMP}[hr] | Peak Step Start Minute {TIMESTAMP}[min] | |
None |
Coil Type | HVAC Type | HVAC Name | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_1:1 | 75351.430 | 53032.336 | 3.055600 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | 75351.43 | 64438.25 | 3.055600 | 27.30 | 17.33 | 0.00825507 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 13.4664 | 23.89 | 0.00786186 | 42.6374 | 34579.41 | 0.00 | -999.00 | -999.00 |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_1:1 | 75266.549 | 75266.549 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 75266.55 | 75266.55 | 3.055601 | 19.63 | 14.85 | 0.00856532 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.4664 | 21.11 | 0.00847379 | 54.3426 | 9187.56 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_2:2 | 38014.940 | 26760.997 | 1.542580 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | 38014.94 | 32491.59 | 1.542580 | 27.28 | 17.32 | 0.00825815 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 13.3374 | 23.89 | 0.00786975 | 42.6794 | 17457.10 | 0.00 | -999.00 | -999.00 |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_2:2 | 37333.981 | 37333.981 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37333.98 | 37333.98 | 1.542579 | 19.99 | 15.05 | 0.00864292 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.3374 | 21.11 | 0.00856435 | 54.9146 | 4300.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_3:3 | 37956.570 | 26715.732 | 1.539500 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 37956.57 | 32434.73 | 1.539500 | 27.28 | 17.33 | 0.00826036 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 13.3640 | 23.89 | 0.00787137 | 42.6881 | 17420.72 | 0.00 | -999.00 | -999.00 |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_3:3 | 37263.647 | 37263.647 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37263.65 | 37263.65 | 1.539501 | 19.99 | 15.05 | 0.00864277 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.3640 | 21.11 | 0.00856400 | 54.9124 | 4335.28 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_4:4 | 38013.570 | 26759.653 | 1.542440 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 38013.57 | 32489.44 | 1.542440 | 27.28 | 17.32 | 0.00825844 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 13.3386 | 23.89 | 0.00787000 | 42.6807 | 17453.35 | 0.00 | -999.00 | -999.00 |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_4:4 | 37330.750 | 37330.750 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37330.75 | 37330.75 | 1.542438 | 19.99 | 15.05 | 0.00864033 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.3386 | 21.11 | 0.00856135 | 54.8957 | 4378.67 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_5:5 | 37892.690 | 26666.223 | 1.536170 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 37892.69 | 32373.00 | 1.536170 | 27.29 | 17.33 | 0.00826264 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 13.3930 | 23.89 | 0.00787302 | 42.6969 | 17382.37 | 0.00 | -999.00 | -999.00 |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_5:5 | 37187.564 | 37187.564 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | 37187.56 | 37187.56 | 1.536170 | 19.98 | 15.04 | 0.00863326 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 13.3930 | 21.11 | 0.00855281 | 54.8416 | 4500.61 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_6:6 | 68703.410 | 48166.587 | 2.766690 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 68703.41 | 58378.50 | 2.766690 | 27.57 | 17.48 | 0.00832923 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 14.8726 | 23.89 | 0.00790062 | 42.8444 | 31303.31 | 0.00 | -999.00 | -999.00 |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_6:6 | 68552.117 | 68552.117 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 68552.12 | 68552.12 | 2.766686 | 19.51 | 14.81 | 0.00857503 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.8726 | 21.11 | 0.00847397 | 54.3437 | 9307.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_7:7 | 36293.050 | 25444.331 | 1.461520 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 36293.05 | 30851.98 | 1.461520 | 27.42 | 17.42 | 0.00831502 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 14.0771 | 23.89 | 0.00791075 | 42.8990 | 16535.46 | 0.00 | -999.00 | -999.00 |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_7:7 | 36013.837 | 36013.837 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 36013.84 | 36013.84 | 1.461521 | 19.63 | 14.85 | 0.00856654 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.0771 | 21.11 | 0.00847039 | 54.3210 | 4912.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_8:8 | 36171.000 | 25358.765 | 1.456610 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | 36171.00 | 30737.82 | 1.456610 | 27.43 | 17.42 | 0.00831862 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 14.1245 | 23.89 | 0.00791335 | 42.9129 | 16479.75 | 0.00 | -999.00 | -999.00 |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_8:8 | 35899.990 | 35899.990 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 35899.99 | 35899.99 | 1.456606 | 19.62 | 14.84 | 0.00856668 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.1246 | 21.11 | 0.00847017 | 54.3196 | 4920.24 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_9:9 | 36319.610 | 25462.952 | 1.462590 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | 36319.61 | 30876.54 | 1.462590 | 27.42 | 17.42 | 0.00831434 | 12.80 | 10.55 | 0.00700000 | 42.80 | 0.01078182 | 23.86 | 14.0668 | 23.89 | 0.00791027 | 42.8964 | 16546.39 | 0.00 | -999.00 | -999.00 |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_9:9 | 36048.135 | 36048.135 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 36048.14 | 36048.14 | 1.462591 | 19.62 | 14.83 | 0.00855096 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 14.0668 | 21.11 | 0.00845234 | 54.2067 | 5127.05 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoopHVAC | PSZ-AC_10:10 | 41222.070 | 29286.632 | 1.709970 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | 41222.07 | 35349.75 | 1.709970 | 27.00 | 17.19 | 0.00821093 | 12.80 | 10.55 | 0.00700000 | 42.48 | 0.01078126 | 23.77 | 12.0318 | 23.88 | 0.00785901 | 42.6228 | 19314.70 | 0.00 | -999.00 | -999.00 |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoopHVAC | PSZ-AC_10:10 | 41721.905 | 41721.905 | -999.0 | -999.0 | -999.000 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | 41721.91 | 41721.91 | 1.709970 | 19.83 | 14.95 | 0.00859732 | 40.00 | 21.18 | 0.00800000 | 12.70 | 0.00915345 | 12.70 | 12.0318 | 21.11 | 0.00852126 | 54.6419 | 5915.25 | 0.00 | -999.00 | -999.00 |
Report: Coil Sizing Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
CoilsCoil Type | Coil Location | HVAC Type | HVAC Name | Zone Name(s) | System Sizing Method Concurrence | System Sizing Method Capacity | System Sizing Method Air Flow | Autosized Coil Capacity? | Autosized Coil Airflow? | Autosized Coil Water Flow? | OA Pretreated prior to coil inlet? | Coil Final Gross Total Capacity [W] | Coil Final Gross Sensible Capacity [W] | Coil Final Reference Air Volume Flow Rate [m3/s] | Coil Final Reference Plant Fluid Volume Flow Rate [m3/s] | Coil U-value Times Area Value [W/K] | Terminal Unit Reheat Coil Multiplier | DX Coil Capacity Increase Ratio from Too Low Flow/Capacity Ratio | DX Coil Capacity Decrease Ratio from Too High Flow/Capacity Ratio | Moist Air Heat Capacity [J/kg-K] | Dry Air Heat Capacity [J/kg-K] | Standard Air Density Adjusted for Elevation [kg/m3] | Supply Fan Name for Coil | Supply Fan Type for Coil | Supply Fan Maximum Air Volume Flow Rate [m3/s] | Supply Fan Maximum Air Mass Flow Rate [kg/s] | Plant Name for Coil | Plant Fluid Specific Heat Capacity [J/kg-K] | Plant Fluid Density [kg/m3] | Plant Maximum Fluid Mass Flow Rate [kg/s] | Plant Design Fluid Return Temperature [C] | Plant Design Fluid Supply Temperature [C] | Plant Design Fluid Temperature Difference [deltaC] | Plant Design Capacity [W] | Coil Capacity Percentage of Plant Design Capacity [%] | Coil Fluid Flow Rate Percentage of Plant Design Flow Rate [%] | Design Day Name at Sensible Ideal Loads Peak | Date/Time at Sensible Ideal Loads Peak | Design Day Name at Total Ideal Loads Peak | Date/Time at Total Ideal Loads Peak | Design Day Name at Air Flow Ideal Loads Peak | Date/Time at Air Flow Ideal Loads Peak | Peak Load Type to Size On | Coil Total Capacity at Ideal Loads Peak [W] | Coil Sensible Capacity at Ideal Loads Peak [W] | Coil Off-Rating Capacity Modifier at Ideal Loads Peak [ ] | Coil Air Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Coil Entering Air Drybulb at Ideal Loads Peak [C] | Coil Entering Air Wetbulb at Ideal Loads Peak [C] | Coil Entering Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Leaving Air Drybulb at Ideal Loads Peak [C] | Coil Leaving Air Wetbulb at Ideal Loads Peak [C] | Coil Leaving Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Ideal Loads Peak [J/KG-K] | Coil Plant Fluid Mass Flow Rate at Ideal Loads Peak [kg/s] | Coil Entering Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Leaving Plant Fluid Temperature at Ideal Loads Peak [C] | Coil Plant Fluid Temperature Difference at Ideal Loads Peak [deltaC] | Supply Fan Air Heat Gain at Ideal Loads Peak [W] | Coil and Fan Net Total Capacity at Ideal Loads Peak [W] | Outdoor Air Drybulb at Ideal Loads Peak [C] | Outdoor Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Outdoor Air Wetbulb at Ideal Loads Peak [C] | Outdoor Air Volume Flow Rate at Ideal Loads Peak [m3/s] | Outdoor Air Flow Percentage at Ideal Loads Peak [%] | System Return Air Drybulb at Ideal Loads Peak [C] | System Return Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Drybulb at Ideal Loads Peak [C] | Zone Air Humidity Ratio at Ideal Loads Peak [kgWater/kgDryAir] | Zone Air Relative Humidity at Ideal Loads Peak [%] | Zone Sensible Heat Gain at Ideal Loads Peak [W] | Zone Latent Heat Gain at Ideal Loads Peak [W] | Coil Total Capacity at Rating Conditions [W] | Coil Sensible Capacity at Rating Conditions [W] | Coil Air Mass Flow Rate at Rating Conditions [kg/s] | Coil Entering Air Drybulb at Rating Conditions [C] | Coil Entering Air Wetbulb at Rating Conditions [C] | Coil Entering Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Entering Air Enthalpy at Rating Conditions [J/KG-K] | Coil Leaving Air Drybulb at Rating Conditions [C] | Coil Leaving Air Wetbulb at Rating Conditions [C] | Coil Leaving Air Humidity Ratio at Rating Conditions [kgWater/kgDryAir] | Coil Leaving Air Enthalpy at Rating Conditions [J/KG-K] | |
PSZ-AC_1:1 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 75351.430 | 53032.336 | 3.055600 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1858 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.055601 | 3.67770557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:40:00 | Sensible | 75351.43 | 64438.25 | 1.0000 | 3.67770483 | 3.055600 | 27.30 | 17.33 | 0.00825507 | 48500.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75351.43 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 13.4664 | 23.89 | 0.00786186 | 23.89 | 0.00786186 | 42.6374 | 34579.41 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_1:1 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_1:1 | LGSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 75266.549 | 75266.549 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 3.055601 | 3.67770557 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 75266.55 | 75266.55 | 1.0000 | 3.67770557 | 3.055601 | 19.63 | 14.85 | 0.00856532 | 41462.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 75266.55 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 13.4664 | 20.71 | 0.00847379 | 21.11 | 0.00847379 | 54.3426 | 9187.56 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38014.940 | 26760.997 | 1.542580 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1915 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.542579 | 1.85664019 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | Sensible | 38014.94 | 32491.59 | 1.0000 | 1.85664155 | 1.542580 | 27.28 | 17.32 | 0.00825815 | 48483.3 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38014.94 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 13.3374 | 23.89 | 0.00786975 | 23.89 | 0.00786975 | 42.6794 | 17457.10 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_2:2 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_2:2 | SMSTORE1 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37333.981 | 37333.981 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.542579 | 1.85664019 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 37333.98 | 37333.98 | 1.0000 | 1.85664019 | 1.542579 | 19.99 | 15.05 | 0.00864292 | 42022.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37333.98 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.3374 | 21.11 | 0.00856435 | 21.11 | 0.00856435 | 54.9146 | 4300.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37956.570 | 26715.732 | 1.539500 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1956 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.539501 | 1.85293537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 37956.57 | 32434.73 | 1.0000 | 1.85293447 | 1.539500 | 27.28 | 17.33 | 0.00826036 | 48494.3 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37956.57 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 13.3640 | 23.89 | 0.00787137 | 23.89 | 0.00787137 | 42.6881 | 17420.72 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_3:3 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_3:3 | SMSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37263.647 | 37263.647 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.539501 | 1.85293537 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 37263.65 | 37263.65 | 1.0000 | 1.85293537 | 1.539501 | 19.99 | 15.05 | 0.00864277 | 42019.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37263.65 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.3640 | 21.11 | 0.00856400 | 21.11 | 0.00856400 | 54.9124 | 4335.28 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 38013.570 | 26759.653 | 1.542440 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1920 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.542438 | 1.85647069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 38013.57 | 32489.44 | 1.0000 | 1.85647304 | 1.542440 | 27.28 | 17.32 | 0.00825844 | 48484.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 38013.57 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 13.3386 | 23.89 | 0.00787000 | 23.89 | 0.00787000 | 42.6807 | 17453.35 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_4:4 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_4:4 | SMSTORE3 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37330.750 | 37330.750 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.542438 | 1.85647069 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 37330.75 | 37330.75 | 1.0000 | 1.85647069 | 1.542438 | 19.99 | 15.05 | 0.00864033 | 42015.5 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37330.75 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.3386 | 21.11 | 0.00856135 | 21.11 | 0.00856135 | 54.8957 | 4378.67 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 37892.690 | 26666.223 | 1.536170 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1998 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.536170 | 1.84892694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 37892.69 | 32373.00 | 1.0000 | 1.84892650 | 1.536170 | 27.29 | 17.33 | 0.00826264 | 48505.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37892.69 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 13.3930 | 23.89 | 0.00787302 | 23.89 | 0.00787302 | 42.6969 | 17382.37 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_5:5 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_5:5 | SMSTORE4 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 37187.564 | 37187.564 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.536170 | 1.84892694 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 13:00:00 | Sensible | 37187.56 | 37187.56 | 1.0000 | 1.84892694 | 1.536170 | 19.98 | 15.04 | 0.00863326 | 41992.9 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 37187.56 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 13.3930 | 21.11 | 0.00855281 | 21.11 | 0.00855281 | 54.8416 | 4500.61 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 68703.410 | 48166.587 | 2.766690 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3236 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.766686 | 3.32996976 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 68703.41 | 58378.50 | 1.0000 | 3.32997420 | 2.766690 | 27.57 | 17.48 | 0.00832923 | 48961.6 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68703.41 | 42.80 | 0.01078182 | 23.86 | 0.41147883 | 14.8726 | 23.89 | 0.00790062 | 23.89 | 0.00790062 | 42.8444 | 31303.31 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_6:6 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_6:6 | LGSTORE2 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 68552.117 | 68552.117 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 2.766686 | 3.32996976 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 68552.12 | 68552.12 | 1.0000 | 3.32996976 | 2.766686 | 19.51 | 14.81 | 0.00857503 | 41364.2 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 68552.12 | 12.70 | 0.00915345 | 12.70 | 0.41147883 | 14.8726 | 20.70 | 0.00847397 | 21.11 | 0.00847397 | 54.3437 | 9307.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36293.050 | 25444.331 | 1.461520 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2972 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.461521 | 1.75907972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 36293.05 | 30851.98 | 1.0000 | 1.75907814 | 1.461520 | 27.42 | 17.42 | 0.00831502 | 48771.8 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36293.05 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 14.0771 | 23.89 | 0.00791075 | 23.89 | 0.00791075 | 42.8990 | 16535.46 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_7:7 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_7:7 | SMSTORE5 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36013.837 | 36013.837 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.461521 | 1.75907972 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 36013.84 | 36013.84 | 1.0000 | 1.75907972 | 1.461521 | 19.63 | 14.85 | 0.00856654 | 41457.8 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36013.84 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.0771 | 20.76 | 0.00847039 | 21.11 | 0.00847039 | 54.3210 | 4912.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36171.000 | 25358.765 | 1.456610 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.3039 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.456606 | 1.75316385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:50:00 | Sensible | 36171.00 | 30737.82 | 1.0000 | 1.75316849 | 1.456610 | 27.43 | 17.42 | 0.00831862 | 48790.1 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36171.00 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 14.1245 | 23.89 | 0.00791335 | 23.89 | 0.00791335 | 42.9129 | 16479.75 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_8:8 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_8:8 | SMSTORE6 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 35899.990 | 35899.990 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.456606 | 1.75316385 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 35899.99 | 35899.99 | 1.0000 | 1.75316385 | 1.456606 | 19.62 | 14.84 | 0.00856668 | 41454.0 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 35899.99 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.1246 | 20.76 | 0.00847017 | 21.11 | 0.00847017 | 54.3196 | 4920.24 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 36319.610 | 25462.952 | 1.462590 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.2959 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.462591 | 1.76036688 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 14:00:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:40:00 | Sensible | 36319.61 | 30876.54 | 1.0000 | 1.76036598 | 1.462590 | 27.42 | 17.42 | 0.00831434 | 48768.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36319.61 | 42.80 | 0.01078182 | 23.86 | 0.20573941 | 14.0668 | 23.89 | 0.00791027 | 23.89 | 0.00791027 | 42.8964 | 16546.39 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_9:9 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_9:9 | SMSTORE7 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 36048.135 | 36048.135 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.462591 | 1.76036688 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 36048.14 | 36048.14 | 1.0000 | 1.76036688 | 1.462591 | 19.62 | 14.83 | 0.00855096 | 41413.7 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 36048.14 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 14.0668 | 20.75 | 0.00845234 | 21.11 | 0.00845234 | 54.2067 | 5127.05 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 COOLING COIL | Coil:Cooling:DX:MultiSpeed | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | CoolingDesignCapacity | N/A | No | No | unknown | No | 41222.070 | 29286.632 | 1.709970 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1020.1037 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.709970 | 2.05811112 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:20:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:30:00 | DUBAI.INTL.AP_ARE ANN CLG .4% CONDNS DB=>MWB | 8/21 13:00:00 | Sensible | 41222.07 | 35349.75 | 1.0000 | 2.05811131 | 1.709970 | 27.00 | 17.19 | 0.00821093 | 48073.2 | 12.80 | 10.55 | 0.00700000 | 30535.1 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41222.07 | 42.48 | 0.01078126 | 23.77 | 0.20573941 | 12.0318 | 23.89 | 0.00785901 | 23.88 | 0.00785901 | 42.6228 | 19314.70 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | |
PSZ-AC_10:10 HEATING COIL | Coil:Heating:Fuel | AirLoop | AirLoopHVAC | PSZ-AC_10:10 | SMSTORE8 | Coincident | HeatingDesignCapacity | N/A | Yes | No | unknown | No | 41721.905 | 41721.905 | -999.0 | -999.0 | -999.000 | -999.0000 | 1.00000 | 1.00000 | 1019.7116 | 1004.8586 | 1.2036 | PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN | Fan:SystemModel | 1.709970 | 2.05811112 | -999.0000 | -999.0000 | -999.0 | -999.00 | -999.00 | -999.00 | -999.00 | -999.0000 | -999.0 | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | unknown | unknown | DUBAI.INTL.AP_ARE ANN HTG 99.6% CONDNS DB | 1/21 10:00:00 | Sensible | 41721.91 | 41721.91 | 1.0000 | 2.05811112 | 1.709970 | 19.83 | 14.95 | 0.00859732 | 41740.3 | 40.00 | 21.18 | 0.00800000 | 60796.0 | -999.0 | -999.00 | -999.00 | -999.00 | 0.000 | 41721.91 | 12.70 | 0.00915345 | 12.70 | 0.20573941 | 12.0318 | 20.80 | 0.00852126 | 21.11 | 0.00852126 | 54.6419 | 5915.25 | 0.00 | -999.00 | -999.00 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 | -999.00 | -999.00 | -999.0 | -999.0 |
Report: System Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
EconomizerHigh Limit Shutoff Control | Minimum Outdoor Air [m3/s] | Maximum Outdoor Air [m3/s] | Return Air Temp Limit | Return Air Enthalpy Limit | Outdoor Air Temperature Limit [C] | Outdoor Air Enthalpy Limit [C] | |
None |
Controller:MechanicalVentilation Name | Outdoor Air Per Person [m3/s-person] | Outdoor Air Per Area [m3/s-m2] | Outdoor Air Per Zone [m3/s] | Outdoor Air ACH [ach] | Outdoor Air Method | Outdoor Air Schedule Name | Air Distribution Effectiveness in Cooling Mode | Air Distribution Effectiveness in Heating Mode | Air Distribution Effectiveness Schedule Name | |
None |
Winter Clothes [hr] | Summer Clothes [hr] | Summer or Winter Clothes [hr] | |
LGSTORE1 | 5393.83 | 802.33 | 770.50 |
SMSTORE1 | 5247.33 | 568.83 | 553.00 |
SMSTORE2 | 4126.33 | 683.67 | 672.50 |
SMSTORE3 | 4122.00 | 674.50 | 662.33 |
SMSTORE4 | 4087.50 | 685.83 | 668.83 |
LGSTORE2 | 3671.83 | 641.17 | 626.67 |
SMSTORE5 | 3572.50 | 643.83 | 624.50 |
SMSTORE6 | 3556.00 | 649.67 | 627.83 |
SMSTORE7 | 3542.17 | 649.83 | 622.33 |
SMSTORE8 | 3613.00 | 593.50 | 551.17 |
Facility | 5540.00 | 1121.83 | 1052.17 |
During Heating [hr] | During Cooling [hr] | During Occupied Heating [hr] | During Occupied Cooling [hr] | |
LGSTORE1 | 0.00 | 3.83 | 0.00 | 3.83 |
SMSTORE1 | 0.00 | 0.83 | 0.00 | 0.83 |
SMSTORE2 | 0.00 | 3.00 | 0.00 | 3.00 |
SMSTORE3 | 0.00 | 3.00 | 0.00 | 3.00 |
SMSTORE4 | 0.00 | 3.17 | 0.00 | 3.17 |
LGSTORE2 | 0.00 | 6.33 | 0.00 | 6.33 |
SMSTORE5 | 0.00 | 4.50 | 0.00 | 4.50 |
SMSTORE6 | 0.00 | 4.50 | 0.00 | 4.50 |
SMSTORE7 | 0.00 | 4.67 | 0.00 | 4.67 |
SMSTORE8 | 0.00 | 3.67 | 0.00 | 3.33 |
Facility | 0.00 | 11.50 | 0.00 | 11.17 |
Report: Outdoor Air Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Average Outdoor Air During Occupied HoursAverage Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.848 | 0.356 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.673 | 0.387 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.848 | 0.506 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.848 | 0.506 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.848 | 0.506 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.848 | 0.475 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.848 | 0.540 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.848 | 0.540 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.848 | 0.540 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.848 | 0.574 | 0.000 | 0.000 |
Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Mechanical Ventilation [ach] | Infiltration [ach] | AFN Infiltration [ach] | Simple Ventilation [ach] | |
LGSTORE1 | 16.92 | 56.25 | 1805.20 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE1 | 8.46 | 28.12 | 902.60 | 0.033 | 0.000 | 0.000 | 0.000 |
SMSTORE2 | 7.10 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE3 | 7.10 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
SMSTORE4 | 7.10 | 28.12 | 902.60 | 0.826 | 0.000 | 0.000 | 0.000 |
LGSTORE2 | 24.82 | 56.25 | 1805.20 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE5 | 12.41 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE6 | 12.41 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE7 | 12.41 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
SMSTORE8 | 12.41 | 28.12 | 902.60 | 0.827 | 0.000 | 0.000 | 0.000 |
Report: Outdoor Air Details
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Mechanical Ventilation Parameters by ZoneAirLoop Name | Average Number of Occupants | Nominal Number of Occupants | Zone Volume [m3] | Zone Area [m2] | Design Zone Outdoor Airflow - Voz [m3/s] | Minimum Dynamic Target Ventilation - Voz-dyn-min [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 16.92 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE1 | PSZ-AC_2:2 | 8.46 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE2 | PSZ-AC_3:3 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE3 | PSZ-AC_4:4 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE4 | PSZ-AC_5:5 | 7.10 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
LGSTORE2 | PSZ-AC_6:6 | 24.82 | 56.25 | 1805.20 | 348.39 | 0.4115 | 0.411 |
SMSTORE5 | PSZ-AC_7:7 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE6 | PSZ-AC_8:8 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE7 | PSZ-AC_9:9 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
SMSTORE8 | PSZ-AC_10:10 | 12.41 | 28.12 | 902.60 | 174.19 | 0.2057 | 0.206 |
Total Facility | 121.13 | 337.50 | 10831.20 | 2090.32 | 2.4689 | 2.469 |
Mechanical Ventilation [m3] | Natural Ventilation [m3] | Total Ventilation [m3] | Infiltration [m3] | Total Ventilation and Infiltration [m3] | Dynamic Target Ventilation - Voz-dyn [m3] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
LGSTORE1 | 8803507.24 | 0.00 | 8803507.24 | 4059395.44 | 12862902.68 | 12976396.34 | 2817.00 | 5943.00 | 0.00 | 103.00 |
SMSTORE1 | 3511739.16 | 0.00 | 3511739.16 | 2102311.45 | 5614050.62 | 6488198.17 | 4303.00 | 4457.00 | 0.00 | 103.00 |
SMSTORE2 | 3525550.60 | 0.00 | 3525550.60 | 2147066.51 | 5672617.11 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE3 | 3525550.60 | 0.00 | 3525550.60 | 2147066.51 | 5672617.11 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
SMSTORE4 | 3525550.60 | 0.00 | 3525550.60 | 2147066.51 | 5672617.11 | 6488198.17 | 4000.00 | 4760.00 | 0.00 | 365.00 |
LGSTORE2 | 6510418.03 | 0.00 | 6510418.03 | 3845608.21 | 10356026.23 | 12976396.34 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE5 | 3255209.01 | 0.00 | 3255209.01 | 2158853.81 | 5414062.82 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE6 | 3255209.01 | 0.00 | 3255209.01 | 2158853.81 | 5414062.82 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE7 | 3255209.01 | 0.00 | 3255209.01 | 2158853.81 | 5414062.82 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 365.00 |
SMSTORE8 | 3255345.41 | 0.00 | 3255345.41 | 2570539.30 | 5825884.71 | 6488198.17 | 4365.00 | 4395.00 | 0.00 | 367.67 |
Total Facility | 42423288.70 | 0.00 | 42423288.70 | 25495615.36 | 67918904.05 | 77858378.04 | 4365.00 | 6246.00 | 0.00 | 732.67 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Infiltration [m3/s] | Total Ventilation and Infiltration [m3/s] | Dynamic Target Ventilation - Voz-dyn [m3/s] | Time Below Voz-dyn [hr] | Time At Voz-dyn [hr] | Time Above Voz-dyn [hr] | |
LGSTORE1 | 0.4115 | 0.0000 | 0.4115 | 0.1730 | 0.5844 | 0.4115 | 0.00 | 5840.00 | 0.00 |
SMSTORE1 | 0.1634 | 0.0000 | 0.1634 | 0.0940 | 0.2574 | 0.2057 | 1486.00 | 4354.00 | 0.00 |
SMSTORE2 | 0.2057 | 0.0000 | 0.2057 | 0.1228 | 0.3286 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE3 | 0.2057 | 0.0000 | 0.2057 | 0.1228 | 0.3286 | 0.2057 | 0.00 | 4395.00 | 0.00 |
SMSTORE4 | 0.2057 | 0.0000 | 0.2057 | 0.1228 | 0.3286 | 0.2057 | 0.00 | 4395.00 | 0.00 |
LGSTORE2 | 0.4115 | 0.0000 | 0.4115 | 0.2304 | 0.6418 | 0.4115 | 0.00 | 4030.00 | 0.00 |
SMSTORE5 | 0.2057 | 0.0000 | 0.2057 | 0.1309 | 0.3366 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE6 | 0.2057 | 0.0000 | 0.2057 | 0.1309 | 0.3366 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE7 | 0.2057 | 0.0000 | 0.2057 | 0.1309 | 0.3366 | 0.2057 | 0.00 | 4030.00 | 0.00 |
SMSTORE8 | 0.2057 | 0.0000 | 0.2057 | 0.1392 | 0.3450 | 0.2057 | 0.00 | 4030.00 | 0.00 |
Total Facility | 2.4265 | 0.0000 | 2.4265 | 1.3977 | 3.8242 | 2.4689 | 1486.00 | 5943.00 | 0.00 |
Mechanical Ventilation [m3] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | Time Above Zero When Unoccupied [hr] | |
PSZ-AC_1:1 | 12753120.48 | 0.00 | 12753120.48 | 12976396.34 | 2817.00 | 0.00 | 5943.00 | 103.00 |
PSZ-AC_2:2 | 5087248.91 | 0.00 | 5087248.91 | 6488198.17 | 4303.00 | 0.00 | 4457.00 | 103.00 |
PSZ-AC_3:3 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_4:4 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_5:5 | 5107256.73 | 0.00 | 5107256.73 | 6488198.17 | 4000.00 | 0.00 | 4760.00 | 365.00 |
PSZ-AC_6:6 | 9431257.70 | 0.00 | 9431257.70 | 12976396.34 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_7:7 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_8:8 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_9:9 | 4715628.85 | 0.00 | 4715628.85 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 365.00 |
PSZ-AC_10:10 | 4715826.44 | 0.00 | 4715826.44 | 6488198.17 | 4365.00 | 0.00 | 4395.00 | 367.50 |
Mechanical Ventilation [m3/s] | Natural Ventilation [m3/s] | Total Ventilation [m3/s] | Sum Zone Dynamic Target Ventilation - Voz-sum-dyn [m3/s] | Time Below Voz-sum-dyn [hr] | Time At Voz-sum-dyn [hr] | Time Above Voz-sum-dyn [hr] | |
PSZ-AC_1:1 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 5840.00 |
PSZ-AC_2:2 | 0.2367 | 0.0000 | 0.2367 | 0.2057 | 1486.00 | 0.00 | 4354.00 |
PSZ-AC_3:3 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_4:4 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_5:5 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4395.00 |
PSZ-AC_6:6 | 0.5961 | 0.0000 | 0.5961 | 0.4115 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_7:7 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_8:8 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_9:9 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
PSZ-AC_10:10 | 0.2980 | 0.0000 | 0.2980 | 0.2057 | 0.00 | 0.00 | 4030.00 |
No Limiting Factor [hr] | Limits and Scheduled Limits [hr] | Economizer [hr] | Exhaust Flow [hr] | Mixed Air Flow [hr] | High Humidity [hr] | Demand Controlled Ventilation [hr] | Night Ventilation [hr] | Demand Limiting [hr] | Energy Management System [hr] | |
PSZ-AC_1:1 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_2:2 | 0.00 | 5943.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_3:3 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_4:4 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_5:5 | 0.00 | 4760.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_6:6 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_7:7 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_8:8 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_9:9 | 0.00 | 4395.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
PSZ-AC_10:10 | 0.00 | 4397.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
No Limiting Factor [m3/s] | Limits and Scheduled Limits [m3/s] | Economizer [m3/s] | Exhaust Flow [m3/s] | Mixed Air Flow [m3/s] | High Humidity [m3/s] | Demand Controlled Ventilation [m3/s] | Night Ventilation [m3/s] | Demand Limiting [m3/s] | Energy Management System [m3/s] | |
PSZ-AC_1:1 | 0.0000 | 0.5961 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_2:2 | 0.0000 | 0.2367 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_3:3 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_4:4 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_5:5 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_6:6 | 0.0000 | 0.5962 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_7:7 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_8:8 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_9:9 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
PSZ-AC_10:10 | 0.0000 | 0.2981 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 |
Report: Object Count Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Surfaces by ClassTotal | Outdoors | |
Wall | 40 | 22 |
Floor | 10 | 10 |
Roof | 10 | 10 |
Internal Mass | 10 | 0 |
Building Detached Shading | 0 | 0 |
Fixed Detached Shading | 0 | 0 |
Window | 36 | 36 |
Door | 12 | 12 |
Glass Door | 12 | 12 |
Shading | 0 | 0 |
Overhang | 0 | 0 |
Fin | 0 | 0 |
Tubular Daylighting Device Dome | 0 | 0 |
Tubular Daylighting Device Diffuser | 0 | 0 |
Count | |
HVAC Air Loops | 10 |
Conditioned Zones | 10 |
Unconditioned Zones | 0 |
Supply Plenums | 0 |
Return Plenums | 0 |
Count | |
IDF Objects | 758 |
Defaulted Fields | 823 |
Fields with Defaults | 2680 |
Autosized Fields | 184 |
Autosizable Fields | 458 |
Autocalculated Fields | 128 |
Autocalculatable Fields | 256 |
Report: Energy Meters
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Annual and Peak Values - ElectricityElectricity Annual Value [GJ] | Electricity Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Electricity Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
Electricity:Facility | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
Electricity:Building | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
Electricity:Zone:LGSTORE1 | 133.09 | 366.52 | 01-JAN-00:10 | 6889.26 | 01-JAN-10:10 |
Electricity:SpaceType:GENERAL | 591.03 | 1960.87 | 01-JAN-00:10 | 36807.75 | 01-JAN-11:10 |
InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE1 | 106.73 | 291.61 | 01-JAN-00:10 | 5541.01 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:SpaceType:GENERAL | 462.31 | 1511.45 | 01-JAN-00:10 | 28718.22 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE1 | 75.47 | 207.67 | 01-JAN-00:10 | 3908.36 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE1 | 62.30 | 170.22 | 01-JAN-00:10 | 3234.23 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE2 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE2 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE3 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE3 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:SMSTORE4 | 55.43 | 191.09 | 01-JAN-00:10 | 3593.21 | 01-JAN-10:10 |
InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE4 | 44.97 | 153.64 | 01-JAN-00:10 | 2919.08 | 01-JAN-10:10 |
Electricity:Zone:LGSTORE2 | 70.93 | 266.94 | 01-JAN-00:10 | 4997.33 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:LGSTORE2 | 51.67 | 192.04 | 01-JAN-00:10 | 3649.08 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE5 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE5 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE6 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE6 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE7 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE7 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
Electricity:Zone:SMSTORE8 | 36.31 | 136.62 | 01-JAN-00:10 | 2558.29 | 01-JAN-11:10 |
InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
LightsWired:InteriorLights:Electricity:Zone:SMSTORE8 | 26.68 | 99.17 | 01-JAN-00:10 | 1884.17 | 01-JAN-11:10 |
InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE1 | 26.36 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:SpaceType:GENERAL | 128.72 | 449.42 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE1 | 13.18 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE2 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE3 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE4 | 10.47 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-10:10 |
InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:LGSTORE2 | 19.26 | 74.90 | 01-JAN-00:10 | 1348.26 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE5 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE6 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE7 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
MiscPlug:InteriorEquipment:Electricity:Zone:SMSTORE8 | 9.63 | 37.45 | 01-JAN-00:10 | 674.13 | 01-JAN-11:10 |
ElectricityPurchased:Facility | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
ElectricityPurchased:Plant | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
Cogeneration:ElectricityPurchased | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
General:Cogeneration:ElectricityPurchased | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
ElectricitySurplusSold:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricitySurplusSold:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Cogeneration:ElectricitySurplusSold | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
ElectricityNet:Facility | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
ElectricityNet:Plant | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
Cogeneration:ElectricityNet | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
General:Cogeneration:ElectricityNet | 1894.97 | 3178.87 | 01-JAN-07:10 | 177043.22 | 10-AUG-16:10 |
Electricity:HVAC | 1124.73 | 0.00 | 01-JAN-00:10 | 134816.70 | 10-AUG-16:10 |
Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:Electricity | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling:Electricity | 791.55 | 0.00 | 01-JAN-00:10 | 115477.03 | 10-AUG-16:10 |
General:Cooling:Electricity | 791.55 | 0.00 | 01-JAN-00:10 | 115477.03 | 10-AUG-16:10 |
Fans:Electricity | 333.18 | 0.00 | 01-JAN-00:10 | 19339.67 | 03-JAN-21:00 |
General:Fans:Electricity | 333.18 | 0.00 | 01-JAN-00:10 | 19339.67 | 03-JAN-21:00 |
ExteriorLights:Electricity | 121.56 | 0.00 | 01-JAN-07:10 | 7723.26 | 01-JAN-00:10 |
General:ExteriorLights:Electricity | 121.56 | 0.00 | 01-JAN-07:10 | 7723.26 | 01-JAN-00:10 |
Electricity:Plant | 57.65 | 1218.00 | 01-MAR-09:10 | 11786.01 | 11-JAN-12:40 |
WaterSystems:Electricity | 57.65 | 1218.00 | 01-MAR-09:10 | 11786.01 | 11-JAN-12:40 |
Water Heater:WaterSystems:Electricity | 57.65 | 1218.00 | 01-MAR-09:10 | 11786.01 | 11-JAN-12:40 |
Natural Gas Annual Value [GJ] | Natural Gas Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Natural Gas Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
NaturalGas:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
NaturalGas:HVAC | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
General:Heating:NaturalGas | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Cooling Annual Value [GJ] | Cooling Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Cooling Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
Water:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:Water | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Facility | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
MainsWater:Plant | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Water Heater:WaterSystems:MainsWater | 87.30 | 0.00 | 01-JAN-00:10 | 0.00 | 06-JAN-13:10 |
Annual Value [kg] | Minimum Value [kg/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [kg/s] | Timestamp of Maximum {TIMESTAMP} | |
Carbon Equivalent:Facility | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
CarbonEquivalentEmissions:Carbon Equivalent | 0.00 | 0.000 | 01-JAN-00:10 | 0.000 | 01-JAN-00:10 |
Annual Value [m3] | Minimum Value [m3/s] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [m3/s] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [L] | Minimum Value [L] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [L] | Timestamp of Maximum {TIMESTAMP} | |
None |
Annual Value [GJ] | Minimum Value [W] | Timestamp of Minimum {TIMESTAMP} | Maximum Value [W] | Timestamp of Maximum {TIMESTAMP} | |
EnergyTransfer:Facility | 3860.35 | 0.00 | 01-JAN-00:10 | 528723.89 | 10-AUG-16:10 |
EnergyTransfer:Building | 1251.81 | 0.00 | 01-JAN-00:10 | 166392.75 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE1 | 250.70 | 0.00 | 01-JAN-00:10 | 27151.60 | 16-AUG-12:10 |
Heating:EnergyTransfer | 15.85 | 0.00 | 01-JAN-00:10 | 39929.99 | 05-AUG-17:10 |
Heating:EnergyTransfer:Zone:LGSTORE1 | 0.93 | 0.00 | 01-JAN-00:10 | 4005.70 | 07-APR-08:20 |
General:Heating:EnergyTransfer | 15.85 | 0.00 | 01-JAN-00:10 | 39929.99 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE1 | 0.93 | 0.00 | 01-JAN-00:10 | 4005.70 | 07-APR-08:20 |
Cooling:EnergyTransfer | 1235.96 | 0.00 | 01-JAN-00:10 | 166392.75 | 16-AUG-12:10 |
Cooling:EnergyTransfer:Zone:LGSTORE1 | 249.77 | 0.00 | 01-JAN-00:10 | 27151.60 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer | 1235.96 | 0.00 | 01-JAN-00:10 | 166392.75 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE1 | 249.77 | 0.00 | 01-JAN-00:10 | 27151.60 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE1 | 131.12 | 0.00 | 01-JAN-00:10 | 13961.00 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE1 | 0.44 | 0.00 | 01-JAN-00:10 | 2102.09 | 29-MAY-07:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE1 | 0.44 | 0.00 | 01-JAN-00:10 | 2102.09 | 29-MAY-07:20 |
Cooling:EnergyTransfer:Zone:SMSTORE1 | 130.68 | 0.00 | 01-JAN-00:10 | 13961.00 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE1 | 130.68 | 0.00 | 01-JAN-00:10 | 13961.00 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE2 | 104.12 | 0.00 | 01-JAN-00:10 | 14058.01 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE2 | 2.49 | 0.00 | 01-JAN-00:10 | 4697.00 | 31-MAY-19:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE2 | 2.49 | 0.00 | 01-JAN-00:10 | 4697.00 | 31-MAY-19:20 |
Cooling:EnergyTransfer:Zone:SMSTORE2 | 101.63 | 0.00 | 01-JAN-00:10 | 14058.01 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE2 | 101.63 | 0.00 | 01-JAN-00:10 | 14058.01 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE3 | 104.82 | 0.00 | 01-JAN-00:10 | 14137.76 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE3 | 2.47 | 0.00 | 01-JAN-00:10 | 4696.25 | 31-MAY-19:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE3 | 2.47 | 0.00 | 01-JAN-00:10 | 4696.25 | 31-MAY-19:20 |
Cooling:EnergyTransfer:Zone:SMSTORE3 | 102.35 | 0.00 | 01-JAN-00:10 | 14137.76 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE3 | 102.35 | 0.00 | 01-JAN-00:10 | 14137.76 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE4 | 102.97 | 0.00 | 01-JAN-00:10 | 14030.43 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE4 | 2.53 | 0.00 | 01-JAN-00:10 | 4702.42 | 31-MAY-19:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE4 | 2.53 | 0.00 | 01-JAN-00:10 | 4702.42 | 31-MAY-19:20 |
Cooling:EnergyTransfer:Zone:SMSTORE4 | 100.44 | 0.00 | 01-JAN-00:10 | 14030.43 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE4 | 100.44 | 0.00 | 01-JAN-00:10 | 14030.43 | 16-AUG-12:10 |
EnergyTransfer:Zone:LGSTORE2 | 175.88 | 0.00 | 01-JAN-00:10 | 25581.00 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:LGSTORE2 | 2.19 | 0.00 | 01-JAN-00:10 | 8849.04 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:LGSTORE2 | 2.19 | 0.00 | 01-JAN-00:10 | 8849.04 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:LGSTORE2 | 173.69 | 0.00 | 01-JAN-00:10 | 25581.00 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:LGSTORE2 | 173.69 | 0.00 | 01-JAN-00:10 | 25581.00 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE5 | 92.33 | 0.00 | 01-JAN-00:10 | 13662.54 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE5 | 1.18 | 0.00 | 01-JAN-00:10 | 4470.49 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE5 | 1.18 | 0.00 | 01-JAN-00:10 | 4470.49 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE5 | 91.14 | 0.00 | 01-JAN-00:10 | 13662.54 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE5 | 91.14 | 0.00 | 01-JAN-00:10 | 13662.54 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE6 | 91.78 | 0.00 | 01-JAN-00:10 | 13628.12 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE6 | 1.19 | 0.00 | 01-JAN-00:10 | 4472.17 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE6 | 1.19 | 0.00 | 01-JAN-00:10 | 4472.17 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE6 | 90.59 | 0.00 | 01-JAN-00:10 | 13628.12 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE6 | 90.59 | 0.00 | 01-JAN-00:10 | 13628.12 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE7 | 91.89 | 0.00 | 01-JAN-00:10 | 13761.92 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE7 | 1.21 | 0.00 | 01-JAN-00:10 | 4465.61 | 05-AUG-17:10 |
General:Heating:EnergyTransfer:Zone:SMSTORE7 | 1.21 | 0.00 | 01-JAN-00:10 | 4465.61 | 05-AUG-17:10 |
Cooling:EnergyTransfer:Zone:SMSTORE7 | 90.69 | 0.00 | 01-JAN-00:10 | 13761.92 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE7 | 90.69 | 0.00 | 01-JAN-00:10 | 13761.92 | 16-AUG-12:10 |
EnergyTransfer:Zone:SMSTORE8 | 106.20 | 0.00 | 01-JAN-00:10 | 16420.37 | 16-AUG-12:10 |
Heating:EnergyTransfer:Zone:SMSTORE8 | 1.23 | 0.00 | 01-JAN-00:10 | 4411.18 | 05-AUG-17:20 |
General:Heating:EnergyTransfer:Zone:SMSTORE8 | 1.23 | 0.00 | 01-JAN-00:10 | 4411.18 | 05-AUG-17:20 |
Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.98 | 0.00 | 01-JAN-00:10 | 16420.37 | 16-AUG-12:10 |
General:Cooling:EnergyTransfer:Zone:SMSTORE8 | 104.98 | 0.00 | 01-JAN-00:10 | 16420.37 | 16-AUG-12:10 |
EnergyTransfer:HVAC | 2608.54 | 0.00 | 01-JAN-00:10 | 387619.94 | 20-JUL-13:00 |
HeatingCoils:EnergyTransfer | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
CoolingCoils:EnergyTransfer | 2608.54 | 0.00 | 01-JAN-00:10 | 387619.94 | 20-JUL-13:00 |
PlantLoopHeatingDemand:Facility | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
PlantLoopHeatingDemand:Plant | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Water Heater:WaterSystems:PlantLoopHeatingDemand | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 01-JAN-00:10 |
Report: Sensible Heat Gain Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Annual Building Sensible Heat Gain ComponentsHVAC Zone Eq & Other Sensible Air Heating [GJ] | HVAC Zone Eq & Other Sensible Air Cooling [GJ] | HVAC Terminal Unit Sensible Air Heating [GJ] | HVAC Terminal Unit Sensible Air Cooling [GJ] | HVAC Input Heated Surface Heating [GJ] | HVAC Input Cooled Surface Cooling [GJ] | People Sensible Heat Addition [GJ] | Lights Sensible Heat Addition [GJ] | Equipment Sensible Heat Addition [GJ] | Window Heat Addition [GJ] | Interzone Air Transfer Heat Addition [GJ] | Infiltration Heat Addition [GJ] | Opaque Surface Conduction and Other Heat Addition [GJ] | Equipment Sensible Heat Removal [GJ] | Window Heat Removal [GJ] | Interzone Air Transfer Heat Removal [GJ] | Infiltration Heat Removal [GJ] | Opaque Surface Conduction and Other Heat Removal [GJ] | |
LGSTORE1 | 0.000 | 0.000 | 0.931 | -249.765 | 0.000 | 0.000 | 23.194 | 106.728 | 26.357 | 20.551 | 0.000 | 34.441 | 43.311 | 0.000 | -2.698 | 0.000 | -3.051 | -0.001 |
SMSTORE1 | 0.000 | 0.000 | 0.440 | -130.680 | 0.000 | 0.000 | 11.596 | 62.296 | 13.179 | 10.335 | 0.000 | 18.581 | 16.953 | 0.000 | -1.364 | 0.000 | -1.336 | -0.001 |
SMSTORE2 | 0.000 | 0.000 | 2.494 | -101.626 | 0.000 | 0.000 | 6.959 | 44.966 | 10.467 | 10.092 | 0.000 | 18.425 | 11.178 | 0.000 | -1.484 | 0.000 | -1.471 | -0.001 |
SMSTORE3 | 0.000 | 0.000 | 2.469 | -102.346 | 0.000 | 0.000 | 6.959 | 44.966 | 10.467 | 10.069 | 0.000 | 18.408 | 11.973 | 0.000 | -1.493 | 0.000 | -1.472 | -0.000 |
SMSTORE4 | 0.000 | 0.000 | 2.527 | -100.439 | 0.000 | 0.000 | 6.960 | 44.966 | 10.467 | 10.088 | 0.000 | 18.420 | 9.934 | 0.000 | -1.468 | 0.000 | -1.455 | -0.001 |
LGSTORE2 | 0.000 | 0.000 | 2.188 | -173.690 | 0.000 | 0.000 | 23.904 | 51.668 | 19.261 | 20.221 | 0.000 | 32.528 | 29.411 | 0.000 | -2.783 | 0.000 | -2.709 | -0.001 |
SMSTORE5 | 0.000 | 0.000 | 1.182 | -91.143 | 0.000 | 0.000 | 11.952 | 26.679 | 9.631 | 10.155 | 0.000 | 18.434 | 15.943 | 0.000 | -1.369 | 0.000 | -1.462 | -0.000 |
SMSTORE6 | 0.000 | 0.000 | 1.189 | -90.588 | 0.000 | 0.000 | 11.952 | 26.679 | 9.631 | 10.162 | 0.000 | 18.436 | 15.360 | 0.000 | -1.363 | 0.000 | -1.458 | -0.001 |
SMSTORE7 | 0.000 | 0.000 | 1.207 | -90.687 | 0.000 | 0.000 | 11.952 | 26.679 | 9.631 | 10.150 | 0.000 | 18.432 | 15.437 | 0.000 | -1.356 | 0.000 | -1.445 | -0.001 |
SMSTORE8 | 0.000 | 0.000 | 1.226 | -104.973 | 0.000 | 0.000 | 11.951 | 26.679 | 9.631 | 10.006 | 0.000 | 20.127 | 28.890 | 0.000 | -1.352 | 0.000 | -2.185 | -0.000 |
Total Facility | 0.000 | 0.000 | 15.852 | -1235.937 | 0.000 | 0.000 | 127.380 | 462.305 | 128.721 | 121.829 | 0.000 | 216.233 | 198.390 | 0.000 | -16.729 | 0.000 | -18.045 | -0.005 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -65041.81 | 0.00 | 0.00 | 158.37 | 2916.31 | 749.03 | 448.55 | 0.00 | 60.97 | 60708.57 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -32878.97 | 0.00 | 0.00 | 79.12 | 1702.23 | 374.52 | 222.54 | 0.00 | 31.40 | 30469.16 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 28-MAR-07:01 | 0.00 | 0.00 | 0.00 | -33508.09 | 0.00 | 0.00 | 79.09 | 1536.36 | 374.52 | 18.53 | 0.00 | 0.00 | 31538.69 | 0.00 | -0.00 | 0.00 | -39.09 | 0.00 |
SMSTORE3 | 28-MAR-07:01 | 0.00 | 0.00 | 0.00 | -33555.89 | 0.00 | 0.00 | 79.08 | 1536.36 | 374.52 | 17.59 | 0.00 | 0.00 | 31587.43 | 0.00 | -0.00 | 0.00 | -39.09 | 0.00 |
SMSTORE4 | 28-MAR-07:01 | 0.00 | 0.00 | 0.00 | -33451.59 | 0.00 | 0.00 | 79.11 | 1536.36 | 374.52 | 19.09 | 0.00 | 0.00 | 31481.50 | 0.00 | -0.00 | 0.00 | -38.98 | 0.00 |
LGSTORE2 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -59755.41 | 0.00 | 0.00 | 348.52 | 1920.56 | 749.03 | 442.75 | 0.00 | 48.05 | 56246.49 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE5 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -31430.52 | 0.00 | 0.00 | 174.59 | 991.67 | 374.52 | 222.47 | 0.00 | 30.69 | 29636.59 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE6 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -31324.74 | 0.00 | 0.00 | 174.71 | 991.67 | 374.52 | 223.03 | 0.00 | 30.92 | 29529.91 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE7 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -31425.08 | 0.00 | 0.00 | 175.16 | 991.67 | 374.52 | 223.60 | 0.00 | 32.37 | 29627.77 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
SMSTORE8 | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -35285.75 | 0.00 | 0.00 | 174.75 | 991.67 | 374.52 | 223.72 | 0.00 | 43.96 | 33477.15 | 0.00 | -0.00 | 0.00 | 0.00 | 0.00 |
Total Facility | 28-MAR-08:61 | 0.00 | 0.00 | 0.00 | -299614.53 | 0.00 | 0.00 | 1876.26 | 19263.00 | 5393.02 | 2749.50 | 0.00 | 548.70 | 269784.06 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Time of Peak {TIMESTAMP} | HVAC Zone Eq & Other Sensible Air Heating [W] | HVAC Zone Eq & Other Sensible Air Cooling [W] | HVAC Terminal Unit Sensible Air Heating [W] | HVAC Terminal Unit Sensible Air Cooling [W] | HVAC Input Heated Surface Heating [W] | HVAC Input Cooled Surface Cooling [W] | People Sensible Heat Addition [W] | Lights Sensible Heat Addition [W] | Equipment Sensible Heat Addition [W] | Window Heat Addition [W] | Interzone Air Transfer Heat Addition [W] | Infiltration Heat Addition [W] | Opaque Surface Conduction and Other Heat Addition [W] | Equipment Sensible Heat Removal [W] | Window Heat Removal [W] | Interzone Air Transfer Heat Removal [W] | Infiltration Heat Removal [W] | Opaque Surface Conduction and Other Heat Removal [W] | |
LGSTORE1 | 10-MAY-08:04 | 0.00 | 0.00 | 11864.35 | 0.00 | 0.00 | 0.00 | 158.15 | 2916.31 | 749.03 | 1049.20 | 0.00 | 1122.16 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -17859.21 |
SMSTORE1 | 10-MAY-08:04 | 0.00 | 0.00 | 5915.71 | 0.00 | 0.00 | 0.00 | 79.07 | 1702.23 | 374.52 | 526.86 | 0.00 | 584.60 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -9182.99 |
SMSTORE2 | 31-MAY-19:11 | 0.00 | 0.00 | 5337.69 | 0.00 | 0.00 | 0.00 | 73.66 | 1536.36 | 374.52 | 312.39 | 0.00 | 87.45 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7722.06 |
SMSTORE3 | 31-MAY-19:11 | 0.00 | 0.00 | 5338.95 | 0.00 | 0.00 | 0.00 | 73.59 | 1536.36 | 374.52 | 312.05 | 0.00 | 87.42 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7722.88 |
SMSTORE4 | 31-MAY-19:11 | 0.00 | 0.00 | 5339.10 | 0.00 | 0.00 | 0.00 | 73.78 | 1536.36 | 374.52 | 312.60 | 0.00 | 87.51 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -7723.86 |
LGSTORE2 | 10-MAY-08:04 | 0.00 | 0.00 | 11667.43 | 0.00 | 0.00 | 0.00 | 347.92 | 1920.56 | 749.03 | 1044.21 | 0.00 | 1042.80 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -16771.95 |
SMSTORE5 | 10-MAY-08:04 | 0.00 | 0.00 | 5853.25 | 0.00 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 524.83 | 0.00 | 586.00 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8504.22 |
SMSTORE6 | 10-MAY-08:04 | 0.00 | 0.00 | 5849.42 | 0.00 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 525.17 | 0.00 | 586.09 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8500.82 |
SMSTORE7 | 10-MAY-08:04 | 0.00 | 0.00 | 5855.71 | 0.00 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 524.69 | 0.00 | 586.02 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8506.56 |
SMSTORE8 | 10-MAY-08:04 | 0.00 | 0.00 | 5965.14 | 0.00 | 0.00 | 0.00 | 173.96 | 991.67 | 374.52 | 519.64 | 0.00 | 663.82 | 0.00 | 0.00 | -0.00 | 0.00 | 0.00 | -8688.74 |
Total Facility | 10-MAY-08:04 | -18096.48 | 18096.48 | 52971.01 | -18096.48 | 0.00 | 0.00 | 1871.99 | 19263.00 | 5393.02 | 6390.15 | 0.00 | 6897.54 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | -74690.23 |
Report: Standard 62.1 Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
System Ventilation Requirements for CoolingSum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow - Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.0556 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 3.0556 | 0.1347 | 1.0000 | Not calculated | 0.4115 | 0.1347 | ||
PSZ-AC_2:2 | 1.5426 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5426 | 0.1334 | 1.0000 | Not calculated | 0.2057 | 0.1334 | ||
PSZ-AC_3:3 | 1.5395 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5395 | 0.1336 | 1.0000 | Not calculated | 0.2057 | 0.1336 | ||
PSZ-AC_4:4 | 1.5424 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5424 | 0.1334 | 1.0000 | Not calculated | 0.2057 | 0.1334 | ||
PSZ-AC_5:5 | 1.5362 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5362 | 0.1339 | 1.0000 | Not calculated | 0.2057 | 0.1339 | ||
PSZ-AC_6:6 | 2.7667 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.7667 | 0.1487 | 1.0000 | Not calculated | 0.4115 | 0.1487 | ||
PSZ-AC_7:7 | 1.4615 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4615 | 0.1408 | 1.0000 | Not calculated | 0.2057 | 0.1408 | ||
PSZ-AC_8:8 | 1.4566 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4566 | 0.1412 | 1.0000 | Not calculated | 0.2057 | 0.1412 | ||
PSZ-AC_9:9 | 1.4626 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4626 | 0.1407 | 1.0000 | Not calculated | 0.2057 | 0.1407 | ||
PSZ-AC_10:10 | 1.7100 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7100 | 0.1203 | 1.0000 | Not calculated | 0.2057 | 0.1203 |
Sum of Zone Primary Air Flow - Vpz-sum [m3/s] | System Population - Ps | Sum of Zone Population - Pz-sum | Occupant Diversity - D | Origin of D | Uncorrected Outdoor Air Intake Airflow - Vou [m3/s] | System Primary Airflow - Vps [m3/s] | Average Outdoor Air Fraction - Xs | System Ventilation Efficiency - Ev | Calculation Method for Ev | Outdoor Air Intake Flow Vot [m3/s] | Percent Outdoor Air - %OA | Environment Name of Peak System Population - Ps | Date and Time of Last Peak System Population - Ps | |
PSZ-AC_1:1 | 3.0556 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 3.0556 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1347 | ||
PSZ-AC_2:2 | 1.5426 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5426 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1334 | ||
PSZ-AC_3:3 | 1.5395 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5395 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1336 | ||
PSZ-AC_4:4 | 1.5424 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5424 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1334 | ||
PSZ-AC_5:5 | 1.5362 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.5362 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1339 | ||
PSZ-AC_6:6 | 2.7667 | 0.0000 | 56.2505 | 1.0000 | Calculated from schedules | 0.4115 | 2.7667 | 1.0000 | 1.0000 | Not calculated | 0.4115 | 0.1487 | ||
PSZ-AC_7:7 | 1.4615 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4615 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1408 | ||
PSZ-AC_8:8 | 1.4566 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4566 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1412 | ||
PSZ-AC_9:9 | 1.4626 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.4626 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1407 | ||
PSZ-AC_10:10 | 1.7100 | 0.0000 | 28.1245 | 1.0000 | Calculated from schedules | 0.2057 | 1.7100 | 1.0000 | 1.0000 | Not calculated | 0.2057 | 0.1203 |
AirLoop Name | People Outdoor Air Rate - Rp [m3/s-person] | Zone Population - Pz | Area Outdoor Air Rate - Ra [m3/s-m2] | Zone Floor Area - Az [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Air Distribution Effectiveness - Ez-clg | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Air Distribution Effectiveness - Ez-htg | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
LGSTORE1 | PSZ-AC_1:1 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE1 | PSZ-AC_2:2 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE2 | PSZ-AC_3:3 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE3 | PSZ-AC_4:4 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE4 | PSZ-AC_5:5 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
LGSTORE2 | PSZ-AC_6:6 | 0.000000 | 56.2505 | 0.001181 | 348.39 | 0.4115 | 1.0000 | 0.4115 | 1.000 | 0.4115 |
SMSTORE5 | PSZ-AC_7:7 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE6 | PSZ-AC_8:8 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE7 | PSZ-AC_9:9 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
SMSTORE8 | PSZ-AC_10:10 | 0.000000 | 28.1245 | 0.001181 | 174.19 | 0.2057 | 1.0000 | 0.2057 | 1.000 | 0.2057 |
People Outdoor Air Rate - Rp [m3/s-person] | Sum of Zone Population - Pz-sum | Area Outdoor Air Rate - Ra [m3/s-m2] | Sum of Zone Floor Area - Az-sum [m2] | Breathing Zone Outdoor Airflow - Vbz [m3/s] | Cooling Zone Outdoor Airflow - Voz-clg [m3/s] | Heating Zone Outdoor Airflow - Voz-htg [m3/s] | |
PSZ-AC_1:1 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_2:2 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_3:3 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_4:4 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_5:5 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_6:6 | 0.000000 | 56.25 | 0.001181 | 348.3864 | 0.4115 | 0.4115 | 0.4115 |
PSZ-AC_7:7 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_8:8 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_9:9 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
PSZ-AC_10:10 | 0.000000 | 28.12 | 0.001181 | 174.1932 | 0.2057 | 0.2057 | 0.2057 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0556 | 3.0556 | 3.0556 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5426 | 1.5426 | 1.5426 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5395 | 1.5395 | 1.5395 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5424 | 1.5424 | 1.5424 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5362 | 1.5362 | 1.5362 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7667 | 2.7667 | 2.7667 | No | 0.4115 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4615 | 1.4615 | 1.4615 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4566 | 1.4566 | 1.4566 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4626 | 1.4626 | 1.4626 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7100 | 1.7100 | 1.7100 | No | 0.2057 | 0.0000 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Cooling - Voz-clg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.0556 | 3.0556 | 3.0556 | 3.0556 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.5426 | 1.5426 | 1.5426 | 1.5426 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.5395 | 1.5395 | 1.5395 | 1.5395 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.5424 | 1.5424 | 1.5424 | 1.5424 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.5362 | 1.5362 | 1.5362 | 1.5362 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.7667 | 2.7667 | 2.7667 | 2.7667 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.4615 | 1.4615 | 1.4615 | 1.4615 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.4566 | 1.4566 | 1.4566 | 1.4566 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.4626 | 1.4626 | 1.4626 | 1.4626 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.7100 | 1.7100 | 1.7100 | 1.7100 | 0.2057 | 1.0000 |
AirLoop Name | Box Type | Zone Primary Airflow - Vpz [m3/s] | Zone Discharge Airflow - Vdz [m3/s] | Minimum Zone Primary Airflow - Vpz-min [m3/s] | Is Vpz-min calculated using the Standard 62.1 Simplified Procedure? | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Primary Outdoor Air Fraction - Zpz | Primary Air Fraction - Ep | Secondary Recirculation Fraction- Er | Supply Air Fraction- Fa | Mixed Air Fraction - Fb | Outdoor Air Fraction - Fc | Zone Ventilation Efficiency - Evz | |
LGSTORE1 | PSZ-AC_1:1 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 3.0556 | 3.0556 | 3.0556 | No | 0.4115 | 0.9017 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE1 | PSZ-AC_2:2 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5426 | 1.5426 | 1.5426 | No | 0.2057 | 0.9242 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE2 | PSZ-AC_3:3 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5395 | 1.5395 | 1.5395 | No | 0.2057 | 0.9168 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE3 | PSZ-AC_4:4 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5424 | 1.5424 | 1.5424 | No | 0.2057 | 0.9078 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE4 | PSZ-AC_5:5 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.5362 | 1.5362 | 1.5362 | No | 0.2057 | 0.8832 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
LGSTORE2 | PSZ-AC_6:6 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 2.7667 | 2.7667 | 2.7667 | No | 0.4115 | 0.8916 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE5 | PSZ-AC_7:7 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4615 | 1.4615 | 1.4615 | No | 0.2057 | 0.8413 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE6 | PSZ-AC_8:8 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4566 | 1.4566 | 1.4566 | No | 0.2057 | 0.8399 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE7 | PSZ-AC_9:9 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.4626 | 1.4626 | 1.4626 | No | 0.2057 | 0.8057 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
SMSTORE8 | PSZ-AC_10:10 | AIRTERMINAL:SINGLEDUCT:CONSTANTVOLUME:NOREHEAT | 1.7100 | 1.7100 | 1.7100 | No | 0.2057 | 0.6947 | 1.0000 | 0.0000 | 0.0000 | 0.0000 | 0.0000 | 1.0000 |
Sum of Zone Primary Airflow - Vpz-sum [m3/s] | System Primary Airflow - Vps [m3/s] | Sum of Zone Discharge Airflow - Vdz-sum [m3/s] | Sum of Min Zone Primary Airflow - Vpz-min [m3/s] | Zone Outdoor Airflow Heating - Voz-htg [m3/s] | Zone Ventilation Efficiency - Evz-min | |
PSZ-AC_1:1 | 3.0556 | 3.0556 | 3.0556 | 3.0556 | 0.4115 | 1.0000 |
PSZ-AC_2:2 | 1.5426 | 1.5426 | 1.5426 | 1.5426 | 0.2057 | 1.0000 |
PSZ-AC_3:3 | 1.5395 | 1.5395 | 1.5395 | 1.5395 | 0.2057 | 1.0000 |
PSZ-AC_4:4 | 1.5424 | 1.5424 | 1.5424 | 1.5424 | 0.2057 | 1.0000 |
PSZ-AC_5:5 | 1.5362 | 1.5362 | 1.5362 | 1.5362 | 0.2057 | 1.0000 |
PSZ-AC_6:6 | 2.7667 | 2.7667 | 2.7667 | 2.7667 | 0.4115 | 1.0000 |
PSZ-AC_7:7 | 1.4615 | 1.4615 | 1.4615 | 1.4615 | 0.2057 | 1.0000 |
PSZ-AC_8:8 | 1.4566 | 1.4566 | 1.4566 | 1.4566 | 0.2057 | 1.0000 |
PSZ-AC_9:9 | 1.4626 | 1.4626 | 1.4626 | 1.4626 | 0.2057 | 1.0000 |
PSZ-AC_10:10 | 1.7100 | 1.7100 | 1.7100 | 1.7100 | 0.2057 | 1.0000 |
Report: LEED Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Sec1.1A-General InformationData | |
Weather File | RUNPERIOD 1 ** Dubai Intl AP - ARE IWEC2 WMO#=411940 |
Total gross floor area [m2] | 2090.32 |
Space Area [m2] | Regularly Occupied Area [m2] | Unconditioned Area [m2] | Typical Hours/Week in Operation [hr/wk] | |
LGSTORE1 | 348.39 | 348.39 | 0.00 | 112.00 |
SMSTORE1 | 174.19 | 174.19 | 0.00 | 112.00 |
SMSTORE2 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE3 | 174.19 | 174.19 | 0.00 | 84.29 |
SMSTORE4 | 174.19 | 174.19 | 0.00 | 84.29 |
LGSTORE2 | 348.39 | 348.39 | 0.00 | 77.29 |
SMSTORE5 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE6 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE7 | 174.19 | 174.19 | 0.00 | 77.29 |
SMSTORE8 | 174.19 | 174.19 | 0.00 | 77.29 |
Totals | 2090.32 | 2090.32 | 0.00 |
Data | |
Number of hours heating loads not met | 0.00 |
Number of hours cooling loads not met | 11.17 |
Number of hours not met | 11.17 |
Utility Rate | Virtual Rate [$/unit energy] | Units of Energy | Units of Demand | |
None |
Electricity Energy Use [GJ] | Electricity Demand [W] | Natural Gas Energy Use [GJ] | Natural Gas Demand [W] | Gasoline Use [GJ] | Gasoline Demand [W] | Diesel Use [GJ] | Diesel Demand [W] | Coal Use [GJ] | Coal Demand [W] | Fuel Oil No 1 Use [GJ] | Fuel Oil No 1 Demand [W] | Fuel Oil No 2 Use [GJ] | Fuel Oil No 2 Demand [W] | Propane Use [GJ] | Propane Demand [W] | Other Fuel 1 Use [GJ] | Other Fuel 1 Demand [W] | Other Fuel 2 Use [GJ] | Other Fuel 2 Demand [W] | District Cooling Use [GJ] | District Cooling Demand [W] | District Heating Use [GJ] | District Heating Demand [W] | |
Heating -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Cooling -- General | 791.55 | 115477.03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Lighting -- LightsWired | 462.31 | 28718.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Lighting -- General | 121.56 | 7723.26 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Interior Equipment -- MiscPlug | 128.72 | 8089.53 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Exterior Equipment -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Fans -- General | 333.18 | 19339.67 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Pumps -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Rejection -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Humidification -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Heat Recovery -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Water Systems -- Water Heater | 57.65 | 11786.01 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Refrigeration -- Not Subdivided | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Generators -- General | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Process Subtotal [GJ] | Total Energy Use [GJ] | |
Electricity | 128.72 | 1894.97 |
Natural Gas | 0.00 | 0.00 |
Additional | 0.00 | 0.00 |
Total | 128.72 | 1894.97 |
Process Subtotal [$] | Total Energy Cost [$] | |
Electricity | 0.00 | |
Natural Gas | 0.00 | |
Additional | 0.00 | |
Total | 0.00 |
Rated Capacity [kW] | Annual Energy Generated [GJ] | |
Photovoltaic | 0.00 | 0.00 |
Wind | 0.00 | 0.00 |
Electricty [MJ/m2] | |
Interior Lighting (All) | 221.16 |
Space Heating | 0.00 |
Space Cooling | 378.68 |
Fans (All) | 159.39 |
Service Water Heating | 27.58 |
Receptacle Equipment | 61.58 |
Miscellaneous (All) | 906.54 |
Subtotal | 906.54 |
Natural Gas [MJ/m2] | |
Space Heating | 0.00 |
Service Water Heating | 0.00 |
Miscellaneous (All) | 0.00 |
Subtotal | 0.00 |
Additional [MJ/m2] | |
Subtotal | 0.00 |
Miscellaneous | 0.00 |
Percent [%] | |
Interior Lighting (All) | 24.40 |
Space Heating | 0.00 |
Space Cooling | 41.77 |
Fans (All) | 17.58 |
Service Water Heating | 3.04 |
Receptacle Equipment | 6.79 |
Miscellaneous | 6.42 |
Equivalent Full Load Hours of Operation Per Year [hr] | Hours > 1% [hr] | |
TYPE1_OCC_SCH | 1630. | 5840. |
TYPE2_OCC_SCH | 995. | 4429. |
TYPE3_OCC_SCH | 1709. | 4064. |
LTG_SCH_DISPLAY_LPD_TYPE1_SMSTORE | 3767. | 8760. |
LTG_SCH_BASE_LPD2 | 3238. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE3 | 3296. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_LGSTORE | 5084. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE3_SMSTORE | 5084. | 8760. |
LTG_SCH_BASE_SMALL_LPD1 | 4469. | 8760. |
LTG_SCH_BASE_LPD1 | 4391. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE1_LGSTORE | 3767. | 8760. |
LTG_SCH_BASE_SMALL_LPD2_TYPE2 | 3584. | 8760. |
LTG_SCH_DISPLAY_LPD_TYPE2_SMSTORE | 4096. | 8760. |
TYPE1_EQUIP_SCH | 4888. | 8760. |
TYPE2_EQUIP_SCH | 3911. | 8760. |
TYPE3_EQUIP_SCH | 3600. | 8760. |
TYPE1_INFIL_SCH | 4302. | 8760. |
TYPE2_INFIL_SCH | 5164. | 8760. |
TYPE3_INFIL_SCH | 5438. | 8760. |
INFIL_DOOR_OPENING_SCH | 2505. | 4380. |
TYPE1_MINOA_MOTORIZEDDAMPER_SCH | 5579. | 5579. |
TYPE2_MINOA_MOTORIZEDDAMPER_SCH | 4429. | 4429. |
TYPE3_MINOA_MOTORIZEDDAMPER_SCH | 4064. | 4064. |
TYPE1_SWH_SCH | 2063. | 6048. |
TYPE2_SWH_SCH | 1831. | 4429. |
TYPE3_SWH_SCH | 1733. | 4064. |
AVERAGE_SWH_SCH | 1863. | 6152. |
ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_ALWAYS_ON | 8760. | 8760. |
EXTERIOR_LGT_189_1 | 7118. | 8760. |
MINOA_SCHED | 8760. | 8760. |
WORK_EFF_SCH | 0. | 0. |
EXTERIOR_LIGHTING_SCHEDULE_A | 6570. | 6570. |
EXTERIOR_LIGHTING_SCHEDULE_B | 8103. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_A_IECC2015 | 5839. | 5839. |
EXTERIOR_LIGHTING_SCHEDULE_B_2016 | 7665. | 8760. |
EXTERIOR_LIGHTING_SCHEDULE_C_2016 | 7300. | 8760. |
SZ_SYSTEM_OA_MAX_FRAC_SCH | 6132. | 8760. |
First Object Used | Month Assumed | 11am First Wednesday [C] | Days with Same 11am Value | 11pm First Wednesday [C] | Days with Same 11pm Value | |
TYPE1_HTGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | January | 21.11 | 365 | 21.11 | 365 |
TYPE1_CLGSETP_SCH_YES_OPTIMUM | LGSTORE1 DUAL SP CONTROL | July | 23.89 | 365 | 23.89 | 365 |
TYPE2_HTGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE2_CLGSETP_SCH_YES_OPTIMUM | SMSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
TYPE3_HTGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | January | 21.11 | 365 | 15.56 | 365 |
TYPE3_CLGSETP_SCH_YES_OPTIMUM | LGSTORE2 DUAL SP CONTROL | July | 23.89 | 365 | 29.44 | 365 |
Report: Annual Thermal Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Heat Index HoursSafe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 7741.50 | 1017.33 | 1.17 | 0.00 | 0.00 |
SMSTORE1 | 7984.67 | 775.33 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 6389.17 | 2310.33 | 60.50 | 0.00 | 0.00 |
SMSTORE3 | 6333.00 | 2347.50 | 79.50 | 0.00 | 0.00 |
SMSTORE4 | 6413.50 | 2270.67 | 75.83 | 0.00 | 0.00 |
LGSTORE2 | 6802.67 | 1882.33 | 75.00 | 0.00 | 0.00 |
SMSTORE5 | 6914.50 | 1770.67 | 74.83 | 0.00 | 0.00 |
SMSTORE6 | 6934.83 | 1750.50 | 74.67 | 0.00 | 0.00 |
SMSTORE7 | 6936.83 | 1745.00 | 78.17 | 0.00 | 0.00 |
SMSTORE8 | 6619.67 | 1813.33 | 327.00 | 0.00 | 0.00 |
Min | 6333.00 | 775.33 | 0.00 | 0.00 | 0.00 |
Max | 7984.67 | 2347.50 | 327.00 | 0.00 | 0.00 |
Average | 6907.03 | 1768.30 | 84.67 | 0.00 | 0.00 |
Sum | 69070.33 | 17683.00 | 846.67 | 0.00 | 0.00 |
Safe (≤ 26.7°C) [hr] | Caution (> 26.7, ≤ 32.2°C) [hr] | Extreme Caution (> 32.2, ≤ 39.4°C) [hr] | Danger (> 39.4, ≤ 51.7°C) [hr] | Extreme Danger (> 51.7°C) [hr] | |
LGSTORE1 | 88850.33 | 190.67 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 43690.50 | 86.50 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 25295.17 | 177.17 | 2.67 | 0.00 | 0.00 |
SMSTORE3 | 25295.00 | 177.50 | 2.50 | 0.00 | 0.00 |
SMSTORE4 | 25297.67 | 175.00 | 2.33 | 0.00 | 0.00 |
LGSTORE2 | 92848.00 | 350.00 | 13.00 | 0.00 | 0.00 |
SMSTORE5 | 45729.50 | 174.50 | 8.00 | 0.00 | 0.00 |
SMSTORE6 | 45729.50 | 174.50 | 8.00 | 0.00 | 0.00 |
SMSTORE7 | 45729.50 | 174.50 | 8.00 | 0.00 | 0.00 |
SMSTORE8 | 45719.00 | 186.00 | 7.00 | 0.00 | 0.00 |
Min | 25295.00 | 86.50 | 0.00 | 0.00 | 0.00 |
Max | 92848.00 | 350.00 | 13.00 | 0.00 | 0.00 |
Average | 48418.42 | 186.63 | 5.15 | 0.00 | 0.00 |
Sum | 484184.17 | 1866.33 | 51.50 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 6313.00 | 2445.50 | 1.50 | 0.00 | 0.00 |
SMSTORE1 | 7221.33 | 1538.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 4903.83 | 3805.67 | 50.50 | 0.00 | 0.00 |
SMSTORE3 | 4894.17 | 3807.67 | 58.17 | 0.00 | 0.00 |
SMSTORE4 | 4944.17 | 3759.00 | 56.83 | 0.00 | 0.00 |
LGSTORE2 | 5096.67 | 3605.50 | 57.83 | 0.00 | 0.00 |
SMSTORE5 | 5162.33 | 3536.83 | 60.83 | 0.00 | 0.00 |
SMSTORE6 | 5168.83 | 3530.50 | 60.67 | 0.00 | 0.00 |
SMSTORE7 | 5194.83 | 3501.33 | 63.83 | 0.00 | 0.00 |
SMSTORE8 | 5104.67 | 3450.67 | 204.67 | 0.00 | 0.00 |
Min | 4894.17 | 1538.67 | 0.00 | 0.00 | 0.00 |
Max | 7221.33 | 3807.67 | 204.67 | 0.00 | 0.00 |
Average | 5400.38 | 3298.13 | 61.48 | 0.00 | 0.00 |
Sum | 54003.83 | 32981.33 | 614.83 | 0.00 | 0.00 |
Little to no Discomfort (≤ 29) [hr] | Some Discomfort (> 29, ≤ 40) [hr] | Great Discomfort; Avoid Exertion (> 40, ≤ 45) [hr] | Dangerous (> 45, ≤ 50) [hr] | Heat Stroke Quite Possible (> 50) [hr] | |
LGSTORE1 | 79613.50 | 9427.50 | 0.00 | 0.00 | 0.00 |
SMSTORE1 | 39670.33 | 4106.67 | 0.00 | 0.00 | 0.00 |
SMSTORE2 | 22369.83 | 3104.67 | 0.50 | 0.00 | 0.00 |
SMSTORE3 | 22390.50 | 3084.00 | 0.50 | 0.00 | 0.00 |
SMSTORE4 | 22358.00 | 3116.50 | 0.50 | 0.00 | 0.00 |
LGSTORE2 | 80442.50 | 12765.50 | 3.00 | 0.00 | 0.00 |
SMSTORE5 | 39555.17 | 6354.83 | 2.00 | 0.00 | 0.00 |
SMSTORE6 | 39510.83 | 6399.17 | 2.00 | 0.00 | 0.00 |
SMSTORE7 | 39570.67 | 6339.33 | 2.00 | 0.00 | 0.00 |
SMSTORE8 | 40576.17 | 5334.83 | 1.00 | 0.00 | 0.00 |
Min | 22358.00 | 3084.00 | 0.00 | 0.00 | 0.00 |
Max | 80442.50 | 12765.50 | 3.00 | 0.00 | 0.00 |
Average | 42605.75 | 6003.30 | 1.15 | 0.00 | 0.00 |
Sum | 426057.50 | 60033.00 | 11.50 | 0.00 | 0.00 |
SET ≤ 12.2°C Hours (°C) | SET ≤ 12.2°C OccupantHours (°C) | Longest SET ≤ 12.2°C Duration [hr] | Start Time of the Longest SET ≤ 12.2°C Duration | |
None |
SET > 30°C Hours (°C) | SET > 30°C OccupantHours (°C) | Longest SET > 30°C Duration [hr] | Start Time of the Longest SET > 30°C Duration | |
None |
Report: Annual CO2 Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
CO2 Level HoursSafe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Safe (<= 1000 ppm) [hr] | Caution (> 1000, <= 5000 ppm) [hr] | Hazard (> 5000 ppm) [hr] | |
None |
Report: Annual Visual Resilience Summary
For: Entire Facility
Timestamp: 2023-10-16 08:40:25
Illuminance Level HoursA Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
A Bit Dark (<= 100 lux) [hr] | Dim (> 100, <= 300 lux) [hr] | Adequate (> 300, <= 500 lux) [hr] | Bright (>500 lux) [hr] | |
None |
Report: NAMEHOLDERMONTHLYSUMMARY TASKPURPOSE PROGRESSINDICATOR
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODENAME IECC
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEYEAR 2012
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CODEAMENDMENT NONEAMEND
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY PROTOTYPENAME RETAILSTRIPMALL
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY TASKSCOPE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY STATE NATIONAL
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY CLIMATEZONE 0B
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: NAMEHOLDERMONTHLYSUMMARY REPRESENTCITY ARE_DUBAI_DUBAIINTL
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | |
January | 19.235 |
February | 20.749 |
March | 23.120 |
April | 26.486 |
May | 31.365 |
June | 32.970 |
July | 35.085 |
August | 35.314 |
September | 32.488 |
October | 29.531 |
November | 25.532 |
December | 21.128 |
Annual Sum or Average | 27.790 |
Minimum of Months | 19.235 |
Maximum of Months | 35.314 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.115520E+11 | 46848.66 | 30-JAN-09:02 | 22.15 | 19.49 | 0.140951E+10 | 1685.98 | 16-JAN-18:19 | 22.15 | 19.49 |
February | 0.117194E+11 | 46857.53 | 06-FEB-09:02 | 22.45 | 18.30 | 0.127297E+10 | 1685.85 | 18-FEB-13:00 | 22.00 | 18.65 |
March | 0.150315E+11 | 65041.87 | 28-MAR-08:61 | 26.03 | 13.62 | 0.139866E+10 | 1685.96 | 12-MAR-12:09 | 26.03 | 13.62 |
April | 0.180390E+11 | 63192.03 | 26-APR-08:61 | 29.33 | 14.54 | 0.136333E+10 | 1686.07 | 23-APR-16:10 | 29.33 | 14.54 |
May | 0.241897E+11 | 60101.54 | 11-MAY-08:61 | 33.67 | 17.81 | 0.140449E+10 | 1686.14 | 05-MAY-12:30 | 33.67 | 17.81 |
June | 0.255795E+11 | 56910.08 | 02-JUN-08:61 | 33.67 | 17.87 | 0.135752E+10 | 1686.16 | 03-JUN-12:50 | 39.83 | 22.91 |
July | 0.290850E+11 | 59185.19 | 04-JUL-07:01 | 31.33 | 17.56 | 0.141569E+10 | 1686.21 | 15-JUL-12:20 | 43.67 | 25.91 |
August | 0.302394E+11 | 52528.47 | 06-AUG-07:01 | 35.08 | 22.69 | 0.139747E+10 | 1686.24 | 05-AUG-12:00 | 35.08 | 22.69 |
September | 0.266766E+11 | 53127.81 | 26-SEP-08:61 | 29.83 | 18.30 | 0.136790E+10 | 1685.87 | 10-SEP-17:30 | 29.83 | 18.30 |
October | 0.245051E+11 | 62414.70 | 21-OCT-08:61 | 24.83 | 14.71 | 0.141257E+10 | 1686.09 | 09-OCT-17:10 | 24.83 | 14.71 |
November | 0.190940E+11 | 58936.44 | 18-NOV-09:02 | 23.68 | 15.96 | 0.136537E+10 | 1686.08 | 05-NOV-12:00 | 23.68 | 15.96 |
December | 0.140556E+11 | 60428.81 | 01-DEC-09:02 | 24.23 | 15.75 | 0.141752E+10 | 1686.02 | 30-DEC-13:00 | 25.00 | 14.81 |
Annual Sum or Average | 0.249767E+12 | 0.165830E+11 | ||||||||
Minimum of Months | 0.115520E+11 | 46848.66 | 22.15 | 13.62 | 0.127297E+10 | 1685.85 | 22.00 | 13.62 | ||
Maximum of Months | 0.302394E+11 | 65041.87 | 35.08 | 22.69 | 0.141752E+10 | 1686.24 | 43.67 | 25.91 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.652931E+10 | 25704.94 | 30-JAN-09:02 | 22.15 | 19.49 | 0.704957E+09 | 842.95 | 16-JAN-18:10 | 22.15 | 19.49 |
February | 0.655386E+10 | 25050.74 | 06-FEB-09:02 | 22.45 | 18.30 | 0.636625E+09 | 842.90 | 19-FEB-18:49 | 19.00 | 17.80 |
March | 0.826209E+10 | 32879.09 | 28-MAR-08:61 | 26.03 | 13.62 | 0.699456E+09 | 842.95 | 12-MAR-12:09 | 26.03 | 13.62 |
April | 0.969801E+10 | 31730.96 | 27-APR-08:61 | 29.83 | 15.29 | 0.681757E+09 | 843.01 | 23-APR-16:10 | 29.83 | 15.29 |
May | 0.125998E+11 | 31050.79 | 08-MAY-08:61 | 31.67 | 17.07 | 0.702257E+09 | 843.05 | 05-MAY-12:39 | 31.67 | 17.07 |
June | 0.131456E+11 | 30072.79 | 02-JUN-08:61 | 33.67 | 17.87 | 0.678739E+09 | 843.05 | 03-JUN-12:50 | 39.83 | 22.91 |
July | 0.147965E+11 | 30720.05 | 04-JUL-07:01 | 31.33 | 17.56 | 0.707812E+09 | 843.08 | 15-JUL-12:20 | 43.67 | 25.91 |
August | 0.152115E+11 | 28158.47 | 06-AUG-07:01 | 35.08 | 22.69 | 0.698690E+09 | 843.09 | 05-AUG-12:00 | 35.08 | 22.69 |
September | 0.135595E+11 | 28853.19 | 26-SEP-08:61 | 29.83 | 18.30 | 0.683923E+09 | 842.91 | 10-SEP-17:30 | 29.83 | 18.30 |
October | 0.126113E+11 | 32276.73 | 21-OCT-08:61 | 24.83 | 14.71 | 0.706271E+09 | 843.02 | 09-OCT-17:10 | 24.83 | 14.71 |
November | 0.100180E+11 | 30954.99 | 18-NOV-09:02 | 23.68 | 15.96 | 0.682716E+09 | 843.01 | 05-NOV-12:00 | 23.68 | 15.96 |
December | 0.769765E+10 | 31147.56 | 01-DEC-09:02 | 24.23 | 15.75 | 0.708851E+09 | 842.98 | 30-DEC-13:00 | 25.00 | 14.81 |
Annual Sum or Average | 0.130683E+12 | 0.829206E+10 | ||||||||
Minimum of Months | 0.652931E+10 | 25050.74 | 22.15 | 13.62 | 0.636625E+09 | 842.90 | 19.00 | 13.62 | ||
Maximum of Months | 0.152115E+11 | 32879.09 | 35.08 | 22.69 | 0.708851E+09 | 843.09 | 43.67 | 25.91 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.449863E+10 | 25129.74 | 29-JAN-09:02 | 23.22 | 19.02 | 0.420138E+09 | 842.92 | 21-JAN-13:00 | 23.22 | 19.02 |
February | 0.467948E+10 | 24023.91 | 06-FEB-08:62 | 21.17 | 17.80 | 0.381860E+09 | 842.90 | 18-FEB-13:50 | 21.85 | 18.69 |
March | 0.619594E+10 | 33508.71 | 28-MAR-07:01 | 24.33 | 12.69 | 0.431919E+09 | 842.90 | 18-MAR-12:00 | 24.33 | 12.69 |
April | 0.740383E+10 | 33251.01 | 26-APR-07:01 | 24.57 | 12.94 | 0.411767E+09 | 842.91 | 15-APR-12:09 | 24.57 | 12.94 |
May | 0.100323E+11 | 31317.55 | 10-MAY-07:01 | 30.52 | 16.02 | 0.427814E+09 | 842.92 | 13-MAY-12:39 | 38.33 | 19.46 |
June | 0.106110E+11 | 26670.49 | 02-JUN-07:01 | 29.67 | 18.04 | 0.418800E+09 | 843.07 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.118245E+11 | 29385.37 | 04-JUL-08:61 | 32.82 | 19.26 | 0.422253E+09 | 843.09 | 15-JUL-12:30 | 43.00 | 26.23 |
August | 0.124471E+11 | 24049.27 | 06-AUG-07:01 | 35.08 | 22.69 | 0.433878E+09 | 843.09 | 05-AUG-12:00 | 35.08 | 22.69 |
September | 0.108237E+11 | 24746.72 | 26-SEP-07:01 | 27.00 | 17.98 | 0.412725E+09 | 842.90 | 09-SEP-12:09 | 27.00 | 17.98 |
October | 0.990163E+10 | 30566.36 | 20-OCT-07:01 | 23.25 | 15.43 | 0.422104E+09 | 843.02 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.770391E+10 | 29869.24 | 19-NOV-09:01 | 25.40 | 16.09 | 0.407161E+09 | 842.90 | 25-NOV-13:30 | 26.85 | 18.98 |
December | 0.550600E+10 | 26893.44 | 27-DEC-08:62 | 21.00 | 15.40 | 0.420043E+09 | 842.99 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.101628E+12 | 0.501046E+10 | ||||||||
Minimum of Months | 0.449863E+10 | 24023.91 | 21.00 | 12.69 | 0.381860E+09 | 842.90 | 21.85 | 12.69 | ||
Maximum of Months | 0.124471E+11 | 33508.71 | 35.08 | 22.69 | 0.433878E+09 | 843.09 | 43.00 | 26.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.444587E+10 | 25152.96 | 29-JAN-09:02 | 23.22 | 19.02 | 0.420110E+09 | 842.92 | 21-JAN-13:00 | 23.22 | 19.02 |
February | 0.464967E+10 | 24094.03 | 06-FEB-08:62 | 21.17 | 17.80 | 0.381849E+09 | 842.90 | 18-FEB-13:50 | 21.85 | 18.69 |
March | 0.618673E+10 | 33556.51 | 28-MAR-07:01 | 24.33 | 12.69 | 0.431915E+09 | 842.90 | 18-MAR-12:00 | 24.33 | 12.69 |
April | 0.743585E+10 | 33353.01 | 26-APR-07:01 | 24.57 | 12.94 | 0.411773E+09 | 842.91 | 15-APR-12:09 | 24.57 | 12.94 |
May | 0.101355E+11 | 31381.51 | 10-MAY-07:01 | 30.52 | 16.02 | 0.427824E+09 | 842.92 | 13-MAY-12:39 | 38.33 | 19.46 |
June | 0.107291E+11 | 26767.43 | 02-JUN-07:01 | 29.67 | 18.04 | 0.418808E+09 | 843.07 | 03-JUN-12:00 | 39.80 | 23.10 |
July | 0.119800E+11 | 29466.79 | 04-JUL-08:61 | 32.82 | 19.26 | 0.422263E+09 | 843.09 | 15-JUL-12:30 | 43.00 | 26.23 |
August | 0.125954E+11 | 24321.66 | 06-AUG-07:01 | 35.08 | 22.69 | 0.433888E+09 | 843.08 | 05-AUG-12:00 | 35.08 | 22.69 |
September | 0.109531E+11 | 24854.44 | 26-SEP-07:01 | 27.00 | 17.98 | 0.412735E+09 | 842.90 | 09-SEP-12:09 | 27.00 | 17.98 |
October | 0.100062E+11 | 30627.17 | 20-OCT-07:01 | 23.25 | 15.43 | 0.422113E+09 | 843.02 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.774210E+10 | 29924.47 | 19-NOV-09:01 | 25.40 | 16.09 | 0.407165E+09 | 842.90 | 25-NOV-13:30 | 26.85 | 18.98 |
December | 0.548874E+10 | 26920.19 | 27-DEC-08:62 | 21.00 | 15.40 | 0.420037E+09 | 842.99 | 30-DEC-13:50 | 25.08 | 14.90 |
Annual Sum or Average | 0.102348E+12 | 0.501048E+10 | ||||||||
Minimum of Months | 0.444587E+10 | 24094.03 | 21.00 | 12.69 | 0.381849E+09 | 842.90 | 21.85 | 12.69 | ||
Maximum of Months | 0.125954E+11 | 33556.51 | 35.08 | 22.69 | 0.433888E+09 | 843.09 | 43.00 | 26.23 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.422458E+10 | 24934.74 | 29-JAN-09:02 | 23.22 | 19.02 | 0.420013E+09 | 842.92 | 21-JAN-13:00 | 23.22 | 19.02 |
February | 0.446333E+10 | 23895.93 | 06-FEB-08:62 | 21.17 | 17.80 | 0.381795E+09 | 842.90 | 18-FEB-13:00 | 22.00 | 18.65 |
March | 0.598278E+10 | 33452.21 | 28-MAR-07:01 | 24.33 | 12.69 | 0.431866E+09 | 842.90 | 18-MAR-12:00 | 24.33 | 12.69 |
April | 0.726214E+10 | 33111.08 | 26-APR-07:01 | 24.57 | 12.94 | 0.411728E+09 | 842.91 | 15-APR-12:09 | 24.57 | 12.94 |
May | 0.999208E+10 | 31302.25 | 10-MAY-07:01 | 30.52 | 16.02 | 0.427792E+09 | 842.92 | 13-MAY-12:39 | 38.33 | 19.46 |
June | 0.105901E+11 | 26619.51 | 02-JUN-07:01 | 29.67 | 18.04 | 0.418780E+09 | 843.06 | 03-JUN-12:50 | 39.83 | 22.91 |
July | 0.118673E+11 | 29354.80 | 04-JUL-08:61 | 32.82 | 19.26 | 0.422240E+09 | 843.09 | 15-JUL-12:30 | 43.00 | 26.23 |
August | 0.124778E+11 | 24143.54 | 06-AUG-07:01 | 35.08 | 22.69 | 0.433864E+09 | 843.09 | 05-AUG-12:00 | 35.08 | 22.69 |
September | 0.108281E+11 | 24707.94 | 26-SEP-07:01 | 27.00 | 17.98 | 0.412708E+09 | 842.90 | 09-SEP-12:09 | 27.00 | 17.98 |
October | 0.987285E+10 | 30501.96 | 20-OCT-07:01 | 23.25 | 15.43 | 0.422084E+09 | 843.02 | 28-OCT-12:00 | 33.40 | 20.86 |
November | 0.758787E+10 | 29803.65 | 19-NOV-09:01 | 25.40 | 16.09 | 0.407128E+09 | 842.90 | 25-NOV-13:30 | 26.85 | 18.98 |
December | 0.529232E+10 | 26696.60 | 27-DEC-08:62 | 21.00 | 15.40 | 0.419987E+09 | 842.99 | 30-DEC-13:39 | 25.17 | 14.99 |
Annual Sum or Average | 0.100441E+12 | 0.500998E+10 | ||||||||
Minimum of Months | 0.422458E+10 | 23895.93 | 21.00 | 12.69 | 0.381795E+09 | 842.90 | 22.00 | 12.69 | ||
Maximum of Months | 0.124778E+11 | 33452.21 | 35.08 | 22.69 | 0.433864E+09 | 843.09 | 43.00 | 26.23 |
Report: ZoneCoolingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.692923E+10 | 45908.58 | 29-JAN-10:02 | 24.58 | 19.01 | 0.143416E+10 | 2247.83 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.745858E+10 | 51933.12 | 05-FEB-10:01 | 27.58 | 18.59 | 0.130659E+10 | 2248.05 | 04-FEB-15:09 | 27.58 | 18.59 |
March | 0.101375E+11 | 59755.22 | 28-MAR-08:61 | 26.03 | 13.62 | 0.148042E+10 | 2247.80 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.124349E+11 | 57790.69 | 26-APR-08:61 | 29.33 | 14.54 | 0.141230E+10 | 2247.81 | 15-APR-14:00 | 29.33 | 14.54 |
May | 0.173675E+11 | 54906.10 | 11-MAY-08:61 | 33.67 | 17.81 | 0.146142E+10 | 2248.12 | 06-MAY-14:00 | 33.67 | 17.81 |
June | 0.185134E+11 | 51231.71 | 02-JUN-08:61 | 33.67 | 17.87 | 0.143331E+10 | 2247.80 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.208035E+11 | 50753.41 | 04-JUL-09:01 | 34.72 | 21.09 | 0.144280E+10 | 2247.80 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.219852E+11 | 43360.45 | 06-AUG-08:61 | 36.17 | 23.08 | 0.148384E+10 | 2247.80 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.189592E+11 | 47996.63 | 26-SEP-08:61 | 29.83 | 18.30 | 0.141409E+10 | 2247.80 | 23-SEP-14:00 | 29.83 | 18.30 |
October | 0.172325E+11 | 55661.03 | 21-OCT-08:61 | 24.83 | 14.71 | 0.143908E+10 | 2247.84 | 21-OCT-14:00 | 34.00 | 19.04 |
November | 0.130174E+11 | 55390.21 | 19-NOV-10:01 | 27.67 | 16.16 | 0.138458E+10 | 2247.80 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.885414E+10 | 53180.12 | 01-DEC-09:02 | 24.23 | 15.75 | 0.143806E+10 | 2247.98 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.173693E+12 | 0.171306E+11 | ||||||||
Minimum of Months | 0.692923E+10 | 43360.45 | 24.23 | 13.62 | 0.130659E+10 | 2247.80 | 24.58 | 13.62 | ||
Maximum of Months | 0.219852E+11 | 59755.22 | 36.17 | 23.08 | 0.148384E+10 | 2248.12 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.353232E+10 | 24064.06 | 29-JAN-10:02 | 24.58 | 19.01 | 0.717069E+09 | 1123.88 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.383723E+10 | 27233.62 | 05-FEB-10:01 | 27.58 | 18.59 | 0.653275E+09 | 1123.99 | 04-FEB-15:09 | 27.58 | 18.59 |
March | 0.526214E+10 | 31430.44 | 28-MAR-08:61 | 26.03 | 13.62 | 0.740183E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.652546E+10 | 30441.02 | 26-APR-08:61 | 29.33 | 14.54 | 0.706107E+09 | 1123.87 | 15-APR-14:00 | 29.33 | 14.54 |
May | 0.916783E+10 | 28978.01 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730660E+09 | 1124.03 | 06-MAY-14:00 | 33.67 | 17.81 |
June | 0.976898E+10 | 26970.94 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716611E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.109900E+11 | 26802.58 | 04-JUL-09:01 | 34.72 | 21.09 | 0.721361E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.115941E+11 | 22711.41 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741886E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.999300E+10 | 25280.36 | 26-SEP-08:61 | 29.83 | 18.30 | 0.706996E+09 | 1123.87 | 23-SEP-14:00 | 29.83 | 18.30 |
October | 0.907514E+10 | 29211.40 | 21-OCT-08:61 | 24.83 | 14.71 | 0.719499E+09 | 1123.89 | 21-OCT-14:00 | 34.00 | 19.04 |
November | 0.682269E+10 | 29132.98 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692264E+09 | 1123.87 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.457518E+10 | 27931.78 | 01-DEC-09:02 | 24.23 | 15.75 | 0.719010E+09 | 1123.95 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.911441E+11 | 0.856492E+10 | ||||||||
Minimum of Months | 0.353232E+10 | 22711.41 | 24.23 | 13.62 | 0.653275E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.115941E+11 | 31430.44 | 36.17 | 23.08 | 0.741886E+09 | 1124.03 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.347650E+10 | 23949.32 | 29-JAN-10:02 | 24.58 | 19.01 | 0.717031E+09 | 1123.88 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.378547E+10 | 27105.01 | 05-FEB-10:01 | 27.58 | 18.59 | 0.653255E+09 | 1123.99 | 04-FEB-15:09 | 27.58 | 18.59 |
March | 0.520493E+10 | 31324.66 | 28-MAR-08:61 | 26.03 | 13.62 | 0.740169E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.647588E+10 | 30340.20 | 26-APR-08:61 | 29.33 | 14.54 | 0.706095E+09 | 1123.87 | 15-APR-14:00 | 29.33 | 14.54 |
May | 0.912248E+10 | 28884.49 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730655E+09 | 1124.03 | 06-MAY-14:00 | 33.67 | 17.81 |
June | 0.972477E+10 | 26880.93 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716607E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.109485E+11 | 26711.01 | 04-JUL-09:01 | 34.72 | 21.09 | 0.721357E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.115533E+11 | 22635.57 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741884E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.995792E+10 | 25190.03 | 26-SEP-08:61 | 29.83 | 18.30 | 0.706994E+09 | 1123.87 | 23-SEP-14:00 | 29.83 | 18.30 |
October | 0.903593E+10 | 29096.12 | 21-OCT-08:61 | 24.83 | 14.71 | 0.719493E+09 | 1123.89 | 21-OCT-14:00 | 34.00 | 19.04 |
November | 0.677795E+10 | 29038.70 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692249E+09 | 1123.87 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.452538E+10 | 27814.10 | 01-DEC-09:02 | 24.23 | 15.75 | 0.718995E+09 | 1123.95 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.905890E+11 | 0.856478E+10 | ||||||||
Minimum of Months | 0.347650E+10 | 22635.57 | 24.23 | 13.62 | 0.653255E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.115533E+11 | 31324.66 | 36.17 | 23.08 | 0.741884E+09 | 1124.03 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.335323E+10 | 23945.76 | 29-JAN-10:02 | 24.58 | 19.01 | 0.716918E+09 | 1123.88 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.367536E+10 | 27097.72 | 05-FEB-10:01 | 27.58 | 18.59 | 0.653193E+09 | 1123.99 | 04-FEB-15:09 | 27.58 | 18.59 |
March | 0.510136E+10 | 31425.00 | 28-MAR-08:61 | 26.03 | 13.62 | 0.740132E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.642616E+10 | 30443.59 | 26-APR-08:61 | 29.33 | 14.54 | 0.706075E+09 | 1123.87 | 15-APR-14:00 | 29.33 | 14.54 |
May | 0.915865E+10 | 28995.67 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730657E+09 | 1124.03 | 06-MAY-14:00 | 33.67 | 17.81 |
June | 0.979615E+10 | 26977.35 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716612E+09 | 1123.87 | 24-JUN-14:09 | 36.00 | 27.04 |
July | 0.110711E+11 | 26831.52 | 04-JUL-09:01 | 34.72 | 21.09 | 0.721365E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.117084E+11 | 22879.87 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741890E+09 | 1123.87 | 26-AUG-14:00 | 36.00 | 27.58 |
September | 0.100632E+11 | 25292.36 | 26-SEP-08:61 | 29.83 | 18.30 | 0.707000E+09 | 1123.87 | 23-SEP-14:00 | 29.83 | 18.30 |
October | 0.910632E+10 | 29199.39 | 21-OCT-08:61 | 24.83 | 14.71 | 0.719500E+09 | 1123.89 | 21-OCT-14:00 | 34.00 | 19.04 |
November | 0.678261E+10 | 29141.98 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692244E+09 | 1123.87 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.444526E+10 | 27824.54 | 01-DEC-09:02 | 24.23 | 15.75 | 0.718960E+09 | 1123.95 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.906879E+11 | 0.856455E+10 | ||||||||
Minimum of Months | 0.335323E+10 | 22879.87 | 24.23 | 13.62 | 0.653193E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.117084E+11 | 31425.00 | 36.17 | 23.08 | 0.741890E+09 | 1124.03 | 36.00 | 27.58 |
Report: ZoneCoolingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | ZONE TOTAL INTERNAL LATENT GAIN ENERGY [J] | ZONE TOTAL INTERNAL LATENT GAIN RATE {Maximum} [W] | ZONE TOTAL INTERNAL LATENT GAIN RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 0.348114E+10 | 26780.73 | 29-JAN-10:02 | 24.58 | 19.01 | 0.716833E+09 | 1123.95 | 28-JAN-15:09 | 24.58 | 19.01 |
February | 0.384503E+10 | 30919.98 | 05-FEB-10:01 | 27.58 | 18.59 | 0.653155E+09 | 1124.00 | 04-FEB-15:30 | 27.58 | 18.59 |
March | 0.546051E+10 | 35285.69 | 28-MAR-08:61 | 26.03 | 13.62 | 0.740139E+09 | 1123.87 | 11-MAR-15:00 | 26.03 | 13.62 |
April | 0.719220E+10 | 34270.48 | 27-APR-08:61 | 29.83 | 15.29 | 0.706198E+09 | 1123.87 | 15-APR-14:00 | 29.83 | 15.29 |
May | 0.106729E+11 | 32756.03 | 11-MAY-08:61 | 33.67 | 17.81 | 0.730797E+09 | 1124.02 | 06-MAY-14:00 | 33.67 | 17.81 |
June | 0.115605E+11 | 30447.60 | 02-JUN-08:61 | 33.67 | 17.87 | 0.716732E+09 | 1123.87 | 24-JUN-14:00 | 36.00 | 27.58 |
July | 0.131955E+11 | 30854.06 | 03-JUL-08:61 | 32.33 | 19.99 | 0.721484E+09 | 1123.87 | 08-JUL-14:00 | 35.00 | 26.74 |
August | 0.141654E+11 | 27271.81 | 06-AUG-08:61 | 36.17 | 23.08 | 0.741985E+09 | 1123.87 | 05-AUG-14:09 | 36.17 | 23.08 |
September | 0.120421E+11 | 28534.85 | 26-SEP-08:61 | 29.83 | 18.30 | 0.707168E+09 | 1123.87 | 23-SEP-14:00 | 29.83 | 18.30 |
October | 0.107418E+11 | 33459.75 | 21-OCT-08:61 | 24.83 | 14.71 | 0.719685E+09 | 1123.93 | 14-OCT-14:09 | 24.83 | 14.71 |
November | 0.780856E+10 | 32361.18 | 19-NOV-10:01 | 27.67 | 16.16 | 0.692395E+09 | 1123.87 | 25-NOV-15:00 | 26.30 | 18.79 |
December | 0.480939E+10 | 28617.24 | 12-DEC-09:01 | 24.07 | 17.73 | 0.719043E+09 | 1123.95 | 30-DEC-15:09 | 24.83 | 13.98 |
Annual Sum or Average | 0.104975E+12 | 0.856561E+10 | ||||||||
Minimum of Months | 0.348114E+10 | 26780.73 | 24.07 | 13.62 | 0.653155E+09 | 1123.87 | 24.58 | 13.62 | ||
Maximum of Months | 0.141654E+11 | 35285.69 | 36.17 | 23.08 | 0.741985E+09 | 1124.02 | 36.17 | 27.58 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 16749035.98 | 4534.94 | 30-JAN-09:04 | 22.15 |
February | 58548647.83 | 4578.42 | 06-FEB-09:04 | 22.45 |
March | 0.108104E+09 | 7059.82 | 27-MAR-08:04 | 29.17 |
April | 0.199679E+09 | 8860.42 | 28-APR-08:04 | 32.67 |
May | 0.112599E+09 | 11863.54 | 10-MAY-08:04 | 38.25 |
June | 40184363.84 | 9815.45 | 01-JUN-08:04 | 33.67 |
July | 36657222.79 | 10567.72 | 21-JUL-08:04 | 36.33 |
August | 34682239.30 | 9537.77 | 06-AUG-07:05 | 35.08 |
September | 37379493.33 | 8236.07 | 04-SEP-07:05 | 31.55 |
October | 80840325.50 | 7712.87 | 04-OCT-08:04 | 29.33 |
November | 0.137374E+09 | 6932.61 | 09-NOV-09:04 | 27.48 |
December | 68504084.55 | 6163.95 | 01-DEC-09:04 | 24.23 |
Annual Sum or Average | 0.931302E+09 | |||
Minimum of Months | 16749035.98 | 4534.94 | 22.15 | |
Maximum of Months | 0.199679E+09 | 11863.54 | 38.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 8612765.96 | 2366.43 | 30-JAN-09:04 | 22.15 |
February | 27804972.88 | 2345.26 | 06-FEB-09:04 | 22.45 |
March | 50066345.38 | 3526.56 | 27-MAR-08:04 | 29.17 |
April | 89873333.32 | 4425.43 | 28-APR-08:04 | 32.67 |
May | 48767904.91 | 5915.29 | 10-MAY-08:04 | 38.25 |
June | 18731294.71 | 4935.76 | 01-JUN-08:04 | 33.67 |
July | 19201602.88 | 5425.53 | 21-JUL-08:04 | 36.33 |
August | 20100918.63 | 4579.07 | 15-AUG-08:04 | 32.67 |
September | 18670216.02 | 5319.63 | 30-SEP-08:04 | 35.47 |
October | 39747343.86 | 4055.70 | 04-OCT-08:04 | 29.33 |
November | 65570604.31 | 3491.20 | 09-NOV-09:04 | 27.48 |
December | 32928491.44 | 3084.56 | 01-DEC-09:04 | 24.23 |
Annual Sum or Average | 0.440076E+09 | |||
Minimum of Months | 8612765.96 | 2345.26 | 22.15 | |
Maximum of Months | 89873333.32 | 5915.29 | 38.25 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 29833489.03 | 2490.91 | 29-JAN-09:04 | 23.22 |
February | 55130226.47 | 2784.48 | 05-FEB-17:12 | 31.00 |
March | 0.122389E+09 | 3151.82 | 02-MAR-08:04 | 27.00 |
April | 0.222547E+09 | 3431.73 | 29-APR-17:11 | 33.33 |
May | 0.296155E+09 | 5337.75 | 31-MAY-19:11 | 41.60 |
June | 0.296849E+09 | 4523.99 | 09-JUN-19:11 | 38.00 |
July | 0.332737E+09 | 5193.28 | 21-JUL-19:11 | 41.00 |
August | 0.347796E+09 | 5166.05 | 10-AUG-19:11 | 40.73 |
September | 0.277950E+09 | 4903.54 | 04-SEP-16:01 | 40.58 |
October | 0.255277E+09 | 3944.19 | 09-OCT-16:11 | 36.53 |
November | 0.184510E+09 | 3200.30 | 20-NOV-08:04 | 26.17 |
December | 72197019.89 | 2351.44 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.249337E+10 | |||
Minimum of Months | 29833489.03 | 2351.44 | 23.17 | |
Maximum of Months | 0.347796E+09 | 5337.75 | 41.60 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 30418397.93 | 2498.61 | 29-JAN-09:04 | 23.22 |
February | 55535661.57 | 2787.73 | 05-FEB-17:12 | 31.00 |
March | 0.122216E+09 | 3154.02 | 02-MAR-08:04 | 27.00 |
April | 0.220799E+09 | 3433.85 | 29-APR-17:11 | 33.33 |
May | 0.292610E+09 | 5339.01 | 31-MAY-19:11 | 41.60 |
June | 0.294220E+09 | 4526.05 | 09-JUN-19:11 | 38.00 |
July | 0.329113E+09 | 5194.75 | 21-JUL-19:11 | 41.00 |
August | 0.343572E+09 | 5168.14 | 10-AUG-19:11 | 40.73 |
September | 0.276719E+09 | 4897.40 | 04-SEP-16:01 | 40.58 |
October | 0.249580E+09 | 3943.20 | 09-OCT-16:11 | 36.53 |
November | 0.180854E+09 | 3216.77 | 20-NOV-08:04 | 26.17 |
December | 72634842.64 | 2367.12 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.246827E+10 | |||
Minimum of Months | 30418397.93 | 2367.12 | 23.17 | |
Maximum of Months | 0.343572E+09 | 5339.01 | 41.60 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 32068865.15 | 2505.77 | 29-JAN-09:04 | 23.22 |
February | 58385698.25 | 2788.68 | 05-FEB-17:12 | 31.00 |
March | 0.126856E+09 | 3146.03 | 02-MAR-08:04 | 27.00 |
April | 0.226553E+09 | 3433.94 | 29-APR-17:11 | 33.33 |
May | 0.300433E+09 | 5339.16 | 31-MAY-19:11 | 41.60 |
June | 0.298283E+09 | 4527.08 | 09-JUN-19:11 | 38.00 |
July | 0.333453E+09 | 5195.22 | 21-JUL-19:11 | 41.00 |
August | 0.349498E+09 | 5168.50 | 10-AUG-19:11 | 40.73 |
September | 0.278923E+09 | 4897.25 | 04-SEP-16:01 | 40.58 |
October | 0.258253E+09 | 3941.52 | 09-OCT-16:11 | 36.53 |
November | 0.189520E+09 | 3203.57 | 20-NOV-08:04 | 26.17 |
December | 74702315.13 | 2275.95 | 12-DEC-08:04 | 23.17 |
Annual Sum or Average | 0.252693E+10 | |||
Minimum of Months | 32068865.15 | 2275.95 | 23.17 | |
Maximum of Months | 0.349498E+09 | 5339.16 | 41.60 |
Report: ZoneHeatingSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 53477573.29 | 4147.85 | 29-JAN-10:05 | 24.58 |
February | 0.100320E+09 | 6301.14 | 05-FEB-10:04 | 27.58 |
March | 0.158741E+09 | 6959.12 | 27-MAR-08:04 | 29.17 |
April | 0.332146E+09 | 8725.22 | 28-APR-08:04 | 32.67 |
May | 0.245399E+09 | 11666.82 | 10-MAY-08:04 | 38.25 |
June | 0.174156E+09 | 9534.00 | 02-JUN-08:04 | 33.67 |
July | 0.209067E+09 | 9682.88 | 29-JUL-17:11 | 40.00 |
August | 0.154468E+09 | 10009.34 | 05-AUG-17:01 | 40.83 |
September | 0.192933E+09 | 9774.04 | 04-SEP-16:01 | 40.58 |
October | 0.223081E+09 | 7950.92 | 15-OCT-09:04 | 31.33 |
November | 0.227600E+09 | 6710.73 | 11-NOV-10:04 | 28.25 |
December | 0.116141E+09 | 5997.91 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.218753E+10 | |||
Minimum of Months | 53477573.29 | 4147.85 | 24.58 | |
Maximum of Months | 0.332146E+09 | 11666.82 | 40.83 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31444896.69 | 2038.37 | 30-JAN-09:04 | 22.15 |
February | 55976403.22 | 3089.75 | 05-FEB-10:04 | 27.58 |
March | 88113865.24 | 3485.65 | 27-MAR-08:04 | 29.17 |
April | 0.177747E+09 | 4367.48 | 28-APR-08:04 | 32.67 |
May | 0.131885E+09 | 5852.94 | 10-MAY-08:04 | 38.25 |
June | 94129009.98 | 4792.31 | 02-JUN-08:04 | 33.67 |
July | 0.110046E+09 | 5196.78 | 21-JUL-08:04 | 36.33 |
August | 79504075.19 | 5058.13 | 05-AUG-17:11 | 40.67 |
September | 0.100122E+09 | 4885.12 | 04-SEP-16:01 | 40.58 |
October | 0.122008E+09 | 4172.96 | 15-OCT-09:04 | 31.33 |
November | 0.125189E+09 | 3522.79 | 11-NOV-10:04 | 28.25 |
December | 65708915.35 | 3159.63 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.118187E+10 | |||
Minimum of Months | 31444896.69 | 2038.37 | 22.15 | |
Maximum of Months | 0.177747E+09 | 5852.94 | 40.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 31622998.35 | 2030.15 | 30-JAN-09:04 | 22.15 |
February | 56184813.52 | 3060.26 | 05-FEB-10:04 | 27.58 |
March | 88817853.65 | 3482.77 | 27-MAR-08:04 | 29.17 |
April | 0.179473E+09 | 4364.81 | 28-APR-08:04 | 32.67 |
May | 0.134133E+09 | 5849.11 | 10-MAY-08:04 | 38.25 |
June | 94580783.14 | 4785.79 | 01-JUN-08:04 | 33.67 |
July | 0.109091E+09 | 5190.34 | 21-JUL-08:04 | 36.33 |
August | 79411649.77 | 5055.35 | 05-AUG-17:11 | 40.67 |
September | 0.102394E+09 | 4884.42 | 04-SEP-16:01 | 40.58 |
October | 0.122784E+09 | 4166.12 | 15-OCT-09:04 | 31.33 |
November | 0.124003E+09 | 3508.61 | 11-NOV-10:04 | 28.25 |
December | 66115122.57 | 3148.20 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.118861E+10 | |||
Minimum of Months | 31622998.35 | 2030.15 | 22.15 | |
Maximum of Months | 0.179473E+09 | 5849.11 | 40.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 33680027.24 | 2064.06 | 30-JAN-09:04 | 22.15 |
February | 58083246.18 | 2987.47 | 05-FEB-10:04 | 27.58 |
March | 92216663.40 | 3482.76 | 27-MAR-08:04 | 29.17 |
April | 0.184566E+09 | 4367.78 | 28-APR-08:04 | 32.67 |
May | 0.136503E+09 | 5855.41 | 10-MAY-08:04 | 38.25 |
June | 95740452.80 | 4803.28 | 02-JUN-08:04 | 33.67 |
July | 0.108865E+09 | 5179.06 | 21-JUL-08:04 | 36.33 |
August | 78890202.36 | 5058.13 | 05-AUG-17:11 | 40.67 |
September | 0.101034E+09 | 4880.77 | 04-SEP-16:01 | 40.58 |
October | 0.122821E+09 | 4152.22 | 15-OCT-09:04 | 31.33 |
November | 0.125962E+09 | 3530.87 | 11-NOV-10:04 | 28.25 |
December | 68363757.74 | 3169.84 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.120673E+10 | |||
Minimum of Months | 33680027.24 | 2064.06 | 22.15 | |
Maximum of Months | 0.184566E+09 | 5855.41 | 40.67 |
Report: ZoneHeatingSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE HEATING ENERGY [J] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE HEATING RATE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | |
January | 50065983.75 | 2450.79 | 30-JAN-09:04 | 22.15 |
February | 80475448.57 | 3091.63 | 05-FEB-10:04 | 27.58 |
March | 0.120652E+09 | 3732.72 | 23-MAR-08:03 | 25.83 |
April | 0.206563E+09 | 4473.21 | 28-APR-08:04 | 32.67 |
May | 0.123591E+09 | 5964.70 | 10-MAY-08:04 | 38.25 |
June | 80114886.12 | 5038.90 | 01-JUN-08:04 | 33.67 |
July | 89367736.24 | 5422.01 | 21-JUL-08:04 | 36.33 |
August | 63189821.28 | 5286.75 | 06-AUG-08:04 | 36.17 |
September | 83916130.59 | 4863.52 | 04-SEP-16:01 | 40.58 |
October | 0.105929E+09 | 4535.25 | 22-OCT-09:04 | 31.70 |
November | 0.132282E+09 | 3813.60 | 11-NOV-10:04 | 28.25 |
December | 89339080.13 | 3482.78 | 10-DEC-10:04 | 27.00 |
Annual Sum or Average | 0.122549E+10 | |||
Minimum of Months | 50065983.75 | 2450.79 | 22.15 | |
Maximum of Months | 0.206563E+09 | 5964.70 | 40.58 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.905830E+10 | 5541.01 | 01-JAN-10:09 | 0.223514E+10 | 1348.26 | 01-JAN-10:09 |
February | 0.818900E+10 | 5541.01 | 01-FEB-10:09 | 0.202238E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.906775E+10 | 5541.01 | 01-MAR-10:09 | 0.224215E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.877798E+10 | 5541.01 | 01-APR-09:09 | 0.216638E+10 | 1348.26 | 01-APR-09:09 |
May | 0.905830E+10 | 5541.01 | 01-MAY-09:09 | 0.223514E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.877798E+10 | 5541.01 | 01-JUN-09:09 | 0.217123E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.906775E+10 | 5541.01 | 01-JUL-09:09 | 0.223729E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.905830E+10 | 5541.01 | 01-AUG-09:09 | 0.223756E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.878743E+10 | 5541.01 | 01-SEP-09:09 | 0.217096E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.905830E+10 | 5541.01 | 01-OCT-09:09 | 0.223514E+10 | 1348.26 | 01-OCT-09:09 |
November | 0.874964E+10 | 5541.01 | 01-NOV-09:09 | 0.215964E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.907720E+10 | 5541.01 | 01-DEC-10:09 | 0.224431E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.106728E+12 | 0.263573E+11 | ||||
Minimum of Months | 0.818900E+10 | 5541.01 | 0.202238E+10 | 1348.26 | ||
Maximum of Months | 0.907720E+10 | 5541.01 | 0.224431E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.528726E+10 | 3234.23 | 01-JAN-10:09 | 0.111757E+10 | 674.13 | 01-JAN-10:09 |
February | 0.477986E+10 | 3234.23 | 01-FEB-10:09 | 0.101119E+10 | 674.13 | 01-FEB-10:09 |
March | 0.529277E+10 | 3234.23 | 01-MAR-10:09 | 0.112107E+10 | 674.13 | 01-MAR-10:09 |
April | 0.512364E+10 | 3234.23 | 01-APR-09:09 | 0.108319E+10 | 674.13 | 01-APR-09:09 |
May | 0.528726E+10 | 3234.23 | 01-MAY-09:09 | 0.111757E+10 | 674.13 | 01-MAY-09:09 |
June | 0.512364E+10 | 3234.23 | 01-JUN-09:09 | 0.108562E+10 | 674.13 | 01-JUN-09:09 |
July | 0.529277E+10 | 3234.23 | 01-JUL-09:09 | 0.111865E+10 | 674.13 | 01-JUL-09:09 |
August | 0.528726E+10 | 3234.23 | 01-AUG-09:09 | 0.111878E+10 | 674.13 | 01-AUG-09:09 |
September | 0.512915E+10 | 3234.23 | 01-SEP-09:09 | 0.108548E+10 | 674.13 | 01-SEP-09:09 |
October | 0.528726E+10 | 3234.23 | 01-OCT-09:09 | 0.111757E+10 | 674.13 | 01-OCT-09:09 |
November | 0.510709E+10 | 3234.23 | 01-NOV-09:09 | 0.107982E+10 | 674.13 | 01-NOV-09:09 |
December | 0.529829E+10 | 3234.23 | 01-DEC-10:09 | 0.112215E+10 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.622962E+11 | 0.131787E+11 | ||||
Minimum of Months | 0.477986E+10 | 3234.23 | 0.101119E+10 | 674.13 | ||
Maximum of Months | 0.529829E+10 | 3234.23 | 0.112215E+10 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.379640E+10 | 2919.08 | 01-JAN-10:09 | 0.883781E+09 | 674.13 | 01-JAN-10:09 |
February | 0.343800E+10 | 2919.08 | 01-FEB-09:09 | 0.800324E+09 | 674.13 | 01-FEB-09:09 |
March | 0.387605E+10 | 2919.08 | 01-MAR-09:09 | 0.902118E+09 | 674.13 | 01-MAR-09:09 |
April | 0.368357E+10 | 2919.08 | 01-APR-08:09 | 0.857490E+09 | 674.13 | 01-APR-08:09 |
May | 0.383623E+10 | 2919.08 | 01-MAY-08:09 | 0.892950E+09 | 674.13 | 01-MAY-08:09 |
June | 0.374331E+10 | 2919.08 | 01-JUN-08:09 | 0.871243E+09 | 674.13 | 01-JUN-08:09 |
July | 0.377649E+10 | 2919.08 | 01-JUL-08:09 | 0.879197E+09 | 674.13 | 01-JUL-08:09 |
August | 0.387605E+10 | 2919.08 | 01-AUG-08:09 | 0.902118E+09 | 674.13 | 01-AUG-08:09 |
September | 0.368357E+10 | 2919.08 | 01-SEP-08:09 | 0.857490E+09 | 674.13 | 01-SEP-08:09 |
October | 0.379640E+10 | 2919.08 | 01-OCT-09:09 | 0.883781E+09 | 674.13 | 01-OCT-09:09 |
November | 0.368357E+10 | 2919.08 | 01-NOV-08:09 | 0.857490E+09 | 674.13 | 01-NOV-08:09 |
December | 0.377649E+10 | 2919.08 | 01-DEC-09:09 | 0.879197E+09 | 674.13 | 01-DEC-09:09 |
Annual Sum or Average | 0.449661E+11 | 0.104672E+11 | ||||
Minimum of Months | 0.343800E+10 | 2919.08 | 0.800324E+09 | 674.13 | ||
Maximum of Months | 0.387605E+10 | 2919.08 | 0.902118E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.435996E+10 | 3649.08 | 01-JAN-11:09 | 0.162546E+10 | 1348.26 | 01-JAN-11:09 |
February | 0.394927E+10 | 3649.08 | 01-FEB-10:09 | 0.147229E+10 | 1348.26 | 01-FEB-10:09 |
March | 0.445953E+10 | 3649.08 | 01-MAR-10:09 | 0.166213E+10 | 1348.26 | 01-MAR-10:09 |
April | 0.423136E+10 | 3649.08 | 01-APR-09:09 | 0.157746E+10 | 1348.26 | 01-APR-09:09 |
May | 0.440975E+10 | 3649.08 | 01-MAY-09:09 | 0.164379E+10 | 1348.26 | 01-MAY-09:09 |
June | 0.430604E+10 | 3649.08 | 01-JUN-09:09 | 0.160496E+10 | 1348.26 | 01-JUN-09:09 |
July | 0.433507E+10 | 3649.08 | 01-JUL-09:09 | 0.161629E+10 | 1348.26 | 01-JUL-09:09 |
August | 0.445953E+10 | 3649.08 | 01-AUG-09:09 | 0.166213E+10 | 1348.26 | 01-AUG-09:09 |
September | 0.423136E+10 | 3649.08 | 01-SEP-09:09 | 0.157746E+10 | 1348.26 | 01-SEP-09:09 |
October | 0.435996E+10 | 3649.08 | 01-OCT-10:09 | 0.162546E+10 | 1348.26 | 01-OCT-10:09 |
November | 0.423136E+10 | 3649.08 | 01-NOV-09:09 | 0.157746E+10 | 1348.26 | 01-NOV-09:09 |
December | 0.433507E+10 | 3649.08 | 01-DEC-10:09 | 0.161629E+10 | 1348.26 | 01-DEC-10:09 |
Annual Sum or Average | 0.516683E+11 | 0.192612E+11 | ||||
Minimum of Months | 0.394927E+10 | 3649.08 | 0.147229E+10 | 1348.26 | ||
Maximum of Months | 0.445953E+10 | 3649.08 | 0.166213E+10 | 1348.26 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: ZoneElectricSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE LIGHTS ELECTRICITY ENERGY [J] | ZONE LIGHTS ELECTRICITY ENERGY {Maximum} [W] | ZONE LIGHTS ELECTRICITY ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY [J] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT ELECTRICITY ENERGY {TIMESTAMP} | |
January | 0.225124E+10 | 1884.17 | 01-JAN-11:09 | 0.812728E+09 | 674.13 | 01-JAN-11:09 |
February | 0.203918E+10 | 1884.17 | 01-FEB-10:09 | 0.736147E+09 | 674.13 | 01-FEB-10:09 |
March | 0.230265E+10 | 1884.17 | 01-MAR-10:09 | 0.831065E+09 | 674.13 | 01-MAR-10:09 |
April | 0.218484E+10 | 1884.17 | 01-APR-09:09 | 0.788729E+09 | 674.13 | 01-APR-09:09 |
May | 0.227694E+10 | 1884.17 | 01-MAY-09:09 | 0.821897E+09 | 674.13 | 01-MAY-09:09 |
June | 0.222339E+10 | 1884.17 | 01-JUN-09:09 | 0.802482E+09 | 674.13 | 01-JUN-09:09 |
July | 0.223839E+10 | 1884.17 | 01-JUL-09:09 | 0.808144E+09 | 674.13 | 01-JUL-09:09 |
August | 0.230265E+10 | 1884.17 | 01-AUG-09:09 | 0.831065E+09 | 674.13 | 01-AUG-09:09 |
September | 0.218484E+10 | 1884.17 | 01-SEP-09:09 | 0.788729E+09 | 674.13 | 01-SEP-09:09 |
October | 0.225124E+10 | 1884.17 | 01-OCT-10:09 | 0.812728E+09 | 674.13 | 01-OCT-10:09 |
November | 0.218484E+10 | 1884.17 | 01-NOV-09:09 | 0.788729E+09 | 674.13 | 01-NOV-09:09 |
December | 0.223839E+10 | 1884.17 | 01-DEC-10:09 | 0.808144E+09 | 674.13 | 01-DEC-10:09 |
Annual Sum or Average | 0.266786E+11 | 0.963059E+10 | ||||
Minimum of Months | 0.203918E+10 | 1884.17 | 0.736147E+09 | 674.13 | ||
Maximum of Months | 0.230265E+10 | 1884.17 | 0.831065E+09 | 674.13 |
Report: SpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77309877.65 | 0.100939E+10 |
February | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.414682E+09 | 0.761421E+09 |
March | 0.335708E+10 | 0.906775E+10 | 0.224215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.108684E+10 | 0.355451E+09 |
April | 0.327081E+10 | 0.877798E+10 | 0.216638E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.239700E+10 | 0.131038E+09 |
May | 0.336680E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.428222E+10 | 17724764.45 |
June | 0.325380E+10 | 0.877798E+10 | 0.217123E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.475440E+10 | 4977313.04 |
July | 0.339353E+10 | 0.906775E+10 | 0.223729E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.557184E+10 | 0.00 |
August | 0.334857E+10 | 0.905830E+10 | 0.223756E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561529E+10 | 0.00 |
September | 0.327932E+10 | 0.878743E+10 | 0.217096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.451983E+10 | 4606984.69 |
October | 0.338624E+10 | 0.905830E+10 | 0.223514E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.348419E+10 | 38824315.87 |
November | 0.327446E+10 | 0.874964E+10 | 0.215964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.183070E+10 | 0.145903E+09 |
December | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406546E+09 | 0.581681E+09 |
Annual Sum or Average | 0.397770E+11 | 0.106728E+12 | 0.263573E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.344409E+11 | 0.305102E+10 |
Minimum of Months | 0.305697E+10 | 0.818900E+10 | 0.202238E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 77309877.65 | 0.00 |
Maximum of Months | 0.340325E+10 | 0.907720E+10 | 0.224431E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.561529E+10 | 0.100939E+10 |
Report: SpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42996902.92 | 0.474391E+09 |
February | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.228907E+09 | 0.340777E+09 |
March | 0.167849E+10 | 0.529277E+10 | 0.112107E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.593842E+09 | 0.150507E+09 |
April | 0.163536E+10 | 0.512364E+10 | 0.108319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.131271E+10 | 45860326.70 |
May | 0.168335E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.232267E+10 | 6235479.28 |
June | 0.162685E+10 | 0.512364E+10 | 0.108562E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254870E+10 | 1885436.41 |
July | 0.169671E+10 | 0.529277E+10 | 0.111865E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.296696E+10 | 0.00 |
August | 0.167424E+10 | 0.528726E+10 | 0.111878E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298833E+10 | 0.00 |
September | 0.163961E+10 | 0.512915E+10 | 0.108548E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.243694E+10 | 1456878.15 |
October | 0.169307E+10 | 0.528726E+10 | 0.111757E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.190554E+10 | 13055454.74 |
November | 0.163718E+10 | 0.510709E+10 | 0.107982E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.100786E+10 | 48366561.06 |
December | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.225936E+09 | 0.253416E+09 |
Annual Sum or Average | 0.198880E+11 | 0.622962E+11 | 0.131787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.185814E+11 | 0.133595E+10 |
Minimum of Months | 0.152844E+10 | 0.477986E+10 | 0.101119E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 42996902.92 | 0.00 |
Maximum of Months | 0.170157E+10 | 0.529829E+10 | 0.112215E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298833E+10 | 0.474391E+09 |
Report: SpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42513589.08 | 0.512539E+09 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224168E+09 | 0.377698E+09 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586740E+09 | 0.170856E+09 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128852E+10 | 49201815.85 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230665E+10 | 5969226.92 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253791E+10 | 1553130.75 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295284E+10 | 0.00 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298506E+10 | 0.00 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241884E+10 | 1533653.71 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187599E+10 | 11612050.27 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984871E+09 | 54620411.25 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221286E+09 | 0.285505E+09 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184254E+11 | 0.147109E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42513589.08 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298506E+10 | 0.512539E+09 |
Report: SpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42513731.63 | 0.511588E+09 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224151E+09 | 0.377230E+09 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586656E+09 | 0.170832E+09 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128809E+10 | 49788365.56 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230475E+10 | 6392594.84 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253503E+10 | 1680329.52 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.294871E+10 | 0.00 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298150E+10 | 0.00 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241588E+10 | 1707742.30 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187437E+10 | 12434100.01 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.984575E+09 | 55468392.43 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221288E+09 | 0.285365E+09 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184075E+11 | 0.147249E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42513731.63 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298150E+10 | 0.511588E+09 |
Report: SpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42514262.48 | 0.508332E+09 |
February | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224222E+09 | 0.373988E+09 |
March | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.586959E+09 | 0.168166E+09 |
April | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128876E+10 | 47911912.55 |
May | 0.102058E+10 | 0.383623E+10 | 0.892950E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230619E+10 | 5923181.13 |
June | 0.998711E+09 | 0.374331E+10 | 0.871243E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.253722E+10 | 1513719.42 |
July | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295087E+10 | 0.00 |
August | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298362E+10 | 0.00 |
September | 0.984131E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241774E+10 | 1532725.50 |
October | 0.100722E+10 | 0.379640E+10 | 0.883781E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187571E+10 | 11635909.73 |
November | 0.973196E+09 | 0.368357E+10 | 0.857490E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985073E+09 | 53540680.13 |
December | 0.100600E+10 | 0.377649E+10 | 0.879197E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221309E+09 | 0.282561E+09 |
Annual Sum or Average | 0.119700E+11 | 0.449661E+11 | 0.104672E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184202E+11 | 0.145510E+10 |
Minimum of Months | 0.914877E+09 | 0.343800E+10 | 0.800324E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42514262.48 | 0.00 |
Maximum of Months | 0.103395E+10 | 0.387605E+10 | 0.902118E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298362E+10 | 0.508332E+09 |
Report: SpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74643646.11 | 0.922390E+09 |
February | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.394241E+09 | 0.686802E+09 |
March | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103430E+10 | 0.312463E+09 |
April | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.226891E+10 | 97726776.21 |
May | 0.349753E+10 | 0.440975E+10 | 0.164379E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.406345E+10 | 12939276.95 |
June | 0.343071E+10 | 0.430604E+10 | 0.160496E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.448807E+10 | 3978468.06 |
July | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.522793E+10 | 0.00 |
August | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528784E+10 | 0.00 |
September | 0.338259E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.426667E+10 | 3423659.04 |
October | 0.344359E+10 | 0.435996E+10 | 0.162546E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.330116E+10 | 29700158.41 |
November | 0.331698E+10 | 0.423136E+10 | 0.157746E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.173262E+10 | 0.113642E+09 |
December | 0.344942E+10 | 0.433507E+10 | 0.161629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.388607E+09 | 0.525817E+09 |
Annual Sum or Average | 0.410346E+11 | 0.516683E+11 | 0.192612E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.325284E+11 | 0.270888E+10 |
Minimum of Months | 0.313522E+10 | 0.394927E+10 | 0.147229E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 74643646.11 | 0.00 |
Maximum of Months | 0.355148E+10 | 0.445953E+10 | 0.166213E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.528784E+10 | 0.922390E+09 |
Report: SpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42495569.02 | 0.506968E+09 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224287E+09 | 0.372631E+09 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587570E+09 | 0.167030E+09 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128942E+10 | 49495124.19 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230449E+10 | 6360394.68 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254088E+10 | 1971125.02 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295554E+10 | 0.00 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298929E+10 | 0.00 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241783E+10 | 1647076.69 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187528E+10 | 14786217.34 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985292E+09 | 57369257.63 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221243E+09 | 0.284113E+09 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184336E+11 | 0.146237E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42495569.02 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298929E+10 | 0.506968E+09 |
Report: SpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42496138.43 | 0.505977E+09 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224315E+09 | 0.371650E+09 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587676E+09 | 0.166269E+09 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128964E+10 | 49018136.85 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230483E+10 | 6264912.81 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254131E+10 | 1936898.35 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295597E+10 | 0.00 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298967E+10 | 0.00 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241818E+10 | 1624084.01 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187555E+10 | 14631035.42 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985453E+09 | 56937683.40 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221250E+09 | 0.283337E+09 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184363E+11 | 0.145765E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42496138.43 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298967E+10 | 0.505977E+09 |
Report: SpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42496820.32 | 0.502900E+09 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.224357E+09 | 0.368568E+09 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.587882E+09 | 0.163972E+09 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.128988E+10 | 47761156.20 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230475E+10 | 6098126.86 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.254087E+10 | 1901075.88 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.295459E+10 | 0.00 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298819E+10 | 0.00 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.241726E+10 | 1643101.09 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.187519E+10 | 14668419.95 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.985478E+09 | 56346229.21 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.221258E+09 | 0.281286E+09 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.184322E+11 | 0.144514E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 42496820.32 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.298819E+10 | 0.502900E+09 |
Report: SpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY [J] | ZONE LIGHTS TOTAL HEATING ENERGY [J] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY [J] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY [J] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY [J] | |
January | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44260151.99 | 0.685367E+09 |
February | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.235749E+09 | 0.538661E+09 |
March | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.628671E+09 | 0.255107E+09 |
April | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.137277E+10 | 95029850.12 |
May | 0.174872E+10 | 0.227694E+10 | 0.821897E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.250086E+10 | 13720886.93 |
June | 0.171530E+10 | 0.222339E+10 | 0.802482E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.280407E+10 | 3941894.10 |
July | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.329650E+10 | 0.00 |
August | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333534E+10 | 0.00 |
September | 0.169125E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.263879E+10 | 4691212.48 |
October | 0.172174E+10 | 0.225124E+10 | 0.812728E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.200050E+10 | 35761873.61 |
November | 0.165844E+10 | 0.218484E+10 | 0.788729E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.103950E+10 | 0.124033E+09 |
December | 0.172466E+10 | 0.223839E+10 | 0.808144E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.230322E+09 | 0.428752E+09 |
Annual Sum or Average | 0.205167E+11 | 0.266786E+11 | 0.963059E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.201273E+11 | 0.218507E+10 |
Minimum of Months | 0.156756E+10 | 0.203918E+10 | 0.736147E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 44260151.99 | 0.00 |
Maximum of Months | 0.177569E+10 | 0.230265E+10 | 0.831065E+09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.333534E+10 | 0.685367E+09 |
Report: PeakSpaceGainsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 4050.04 | 01-JAN-13:09 | 5541.01 | 01-JAN-10:09 | 1348.26 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1983.75 | 23-JAN-14:00 | 2498.21 | 18-JAN-17:00 |
February | 4050.04 | 03-FEB-13:09 | 5541.01 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4165.81 | 06-FEB-15:00 | 3035.10 | 20-FEB-16:00 |
March | 4050.04 | 03-MAR-13:09 | 5541.01 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6738.47 | 27-MAR-11:10 | 2922.83 | 05-MAR-18:00 |
April | 4050.04 | 01-APR-12:09 | 5541.01 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8140.93 | 28-APR-12:00 | 607.82 | 05-APR-01:00 |
May | 4050.04 | 05-MAY-12:09 | 5541.01 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8216.37 | 21-MAY-13:00 | 362.69 | 01-MAY-07:10 |
June | 4050.04 | 02-JUN-12:09 | 5541.01 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8581.52 | 12-JUN-12:00 | 424.71 | 22-JUN-08:00 |
July | 4050.04 | 01-JUL-12:09 | 5541.01 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9784.82 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 4050.04 | 04-AUG-12:09 | 5541.01 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 10233.18 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 4050.04 | 01-SEP-12:09 | 5541.01 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7949.39 | 04-SEP-14:00 | 151.01 | 25-SEP-07:10 |
October | 4050.04 | 01-OCT-12:09 | 5541.01 | 01-OCT-09:09 | 1348.26 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6395.29 | 09-OCT-13:00 | 330.91 | 21-OCT-07:00 |
November | 4050.04 | 03-NOV-12:09 | 5541.01 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4667.77 | 05-NOV-12:00 | 546.21 | 22-NOV-07:00 |
December | 4050.04 | 01-DEC-13:09 | 5541.01 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2905.42 | 10-DEC-12:10 | 3047.80 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1983.75 | 0.00 | |||||
Maximum of Months | 4050.04 | 5541.01 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 10233.18 | 3047.80 |
Report: PeakSpaceGainsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 01-JAN-13:09 | 3234.23 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1379.63 | 18-JAN-17:00 |
February | 2024.96 | 03-FEB-13:09 | 3234.23 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.57 | 06-FEB-15:00 | 1699.76 | 20-FEB-16:00 |
March | 2024.96 | 03-MAR-13:09 | 3234.23 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1632.41 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 3234.23 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 294.71 | 01-APR-07:03 |
May | 2024.96 | 05-MAY-12:09 | 3234.23 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 199.69 | 01-MAY-07:10 |
June | 2024.96 | 02-JUN-12:09 | 3234.23 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 229.56 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 3234.23 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 04-AUG-12:09 | 3234.23 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.81 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 01-SEP-12:09 | 3234.23 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.48 | 26-SEP-13:00 | 85.13 | 25-SEP-07:10 |
October | 2024.96 | 01-OCT-12:09 | 3234.23 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.38 | 09-OCT-12:00 | 167.11 | 21-OCT-07:10 |
November | 2024.96 | 03-NOV-12:09 | 3234.23 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.09 | 05-NOV-12:00 | 295.11 | 22-NOV-08:63 |
December | 2024.96 | 01-DEC-13:09 | 3234.23 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 3234.23 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.81 | 1699.76 |
Report: PeakSpaceGainsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1431.80 | 15-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.59 | 06-FEB-15:00 | 1789.05 | 20-FEB-17:50 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1814.51 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 275.75 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 183.60 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 117.15 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.48 | 26-SEP-13:00 | 71.84 | 24-SEP-07:02 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.40 | 09-OCT-12:00 | 209.00 | 29-OCT-07:10 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.09 | 05-NOV-12:00 | 392.26 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 1814.51 |
Report: PeakSpaceGainsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1425.81 | 15-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.59 | 06-FEB-15:00 | 1783.28 | 20-FEB-17:50 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1809.39 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 280.72 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 187.57 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 117.15 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.48 | 26-SEP-13:00 | 72.21 | 24-SEP-07:02 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.40 | 09-OCT-12:00 | 211.80 | 29-OCT-07:10 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.10 | 05-NOV-12:00 | 395.36 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 1809.39 |
Report: PeakSpaceGainsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2024.96 | 07-JAN-13:09 | 2919.08 | 01-JAN-10:09 | 674.13 | 01-JAN-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1406.10 | 15-JAN-18:00 |
February | 2024.96 | 04-FEB-13:09 | 2919.08 | 01-FEB-09:09 | 674.13 | 01-FEB-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.59 | 06-FEB-15:00 | 1765.37 | 20-FEB-17:40 |
March | 2024.96 | 04-MAR-13:09 | 2919.08 | 01-MAR-09:09 | 674.13 | 01-MAR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1791.43 | 05-MAR-18:00 |
April | 2024.96 | 01-APR-12:09 | 2919.08 | 01-APR-08:09 | 674.13 | 01-APR-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 266.25 | 09-APR-17:00 |
May | 2024.96 | 06-MAY-12:09 | 2919.08 | 01-MAY-08:09 | 674.13 | 01-MAY-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 184.54 | 01-MAY-07:02 |
June | 2024.96 | 03-JUN-12:09 | 2919.08 | 01-JUN-08:09 | 674.13 | 01-JUN-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 117.15 | 22-JUN-08:00 |
July | 2024.96 | 01-JUL-12:09 | 2919.08 | 01-JUL-08:09 | 674.13 | 01-JUL-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2024.96 | 05-AUG-12:09 | 2919.08 | 01-AUG-08:09 | 674.13 | 01-AUG-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2024.96 | 02-SEP-12:09 | 2919.08 | 01-SEP-08:09 | 674.13 | 01-SEP-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.48 | 26-SEP-13:00 | 71.88 | 24-SEP-07:02 |
October | 2024.96 | 07-OCT-12:09 | 2919.08 | 01-OCT-09:09 | 674.13 | 01-OCT-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.40 | 09-OCT-12:00 | 208.03 | 29-OCT-07:10 |
November | 2024.96 | 04-NOV-12:09 | 2919.08 | 01-NOV-08:09 | 674.13 | 01-NOV-08:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.09 | 05-NOV-12:00 | 381.49 | 26-NOV-18:00 |
December | 2024.96 | 02-DEC-13:09 | 2919.08 | 01-DEC-09:09 | 674.13 | 01-DEC-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2024.96 | 2919.08 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 1791.43 |
Report: PeakSpaceGainsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 5400.05 | 07-JAN-15:09 | 3649.08 | 01-JAN-11:09 | 1348.26 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1940.29 | 23-JAN-14:00 | 2425.79 | 18-JAN-17:00 |
February | 5400.05 | 04-FEB-15:09 | 3649.08 | 01-FEB-10:09 | 1348.26 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4044.88 | 06-FEB-15:00 | 2995.04 | 20-FEB-17:40 |
March | 5400.05 | 04-MAR-15:09 | 3649.08 | 01-MAR-10:09 | 1348.26 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6501.94 | 27-MAR-11:10 | 3037.48 | 05-MAR-18:00 |
April | 5400.05 | 01-APR-14:09 | 3649.08 | 01-APR-09:09 | 1348.26 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8037.83 | 28-APR-12:00 | 496.82 | 01-APR-07:03 |
May | 5400.05 | 06-MAY-14:09 | 3649.08 | 01-MAY-09:09 | 1348.26 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7787.69 | 09-MAY-13:00 | 368.47 | 01-MAY-07:10 |
June | 5400.05 | 03-JUN-14:09 | 3649.08 | 01-JUN-09:09 | 1348.26 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 8432.72 | 12-JUN-12:00 | 403.16 | 22-JUN-08:00 |
July | 5400.05 | 01-JUL-14:09 | 3649.08 | 01-JUL-09:09 | 1348.26 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9615.16 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 5400.05 | 05-AUG-14:09 | 3649.08 | 01-AUG-09:09 | 1348.26 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 9892.17 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 5400.05 | 02-SEP-14:09 | 3649.08 | 01-SEP-09:09 | 1348.26 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 7778.69 | 26-SEP-13:00 | 150.12 | 25-SEP-07:01 |
October | 5400.05 | 07-OCT-14:09 | 3649.08 | 01-OCT-10:09 | 1348.26 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 6299.61 | 09-OCT-12:00 | 390.79 | 29-OCT-07:02 |
November | 5400.05 | 04-NOV-14:09 | 3649.08 | 01-NOV-09:09 | 1348.26 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4619.76 | 05-NOV-12:00 | 609.29 | 26-NOV-18:00 |
December | 5400.05 | 02-DEC-15:09 | 3649.08 | 01-DEC-10:09 | 1348.26 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2847.71 | 10-DEC-12:10 | 2923.87 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 1940.29 | 0.00 | |||||
Maximum of Months | 5400.05 | 3649.08 | 1348.26 | 0.00 | 0.00 | 0.00 | 0.00 | 9892.17 | 3037.48 |
Report: PeakSpaceGainsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1379.66 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.53 | 06-FEB-15:00 | 1699.97 | 20-FEB-17:30 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1718.50 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 279.70 | 01-APR-07:03 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 207.28 | 01-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 228.63 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.43 | 26-SEP-13:00 | 85.40 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.39 | 09-OCT-12:00 | 216.76 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.07 | 05-NOV-12:00 | 323.51 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 1718.50 |
Report: PeakSpaceGainsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1379.66 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.53 | 06-FEB-15:00 | 1699.76 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1712.50 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 278.24 | 01-APR-07:03 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 206.43 | 01-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 228.48 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.43 | 26-SEP-13:00 | 85.38 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.39 | 09-OCT-12:00 | 215.96 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.07 | 05-NOV-12:00 | 318.89 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 1712.50 |
Report: PeakSpaceGainsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 23-JAN-14:00 | 1379.65 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2300.53 | 06-FEB-15:00 | 1699.76 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3693.94 | 27-MAR-11:10 | 1700.30 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4584.59 | 28-APR-12:00 | 273.74 | 01-APR-07:03 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4430.97 | 09-MAY-13:00 | 204.55 | 01-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4805.95 | 12-JUN-12:00 | 228.46 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5479.85 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4431.43 | 26-SEP-13:00 | 85.47 | 25-SEP-07:01 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3596.39 | 09-OCT-12:00 | 215.65 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2636.07 | 05-NOV-12:00 | 317.76 | 26-NOV-18:00 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1622.24 | 10-DEC-12:10 | 1659.46 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1104.92 | 0.00 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5621.82 | 1700.30 |
Report: PeakSpaceGainsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE PEOPLE TOTAL HEATING ENERGY {Maximum} [W] | ZONE PEOPLE TOTAL HEATING ENERGY {TIMESTAMP} | ZONE LIGHTS TOTAL HEATING ENERGY {Maximum} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {TIMESTAMP} | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {Maximum} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {TIMESTAMP} | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {TIMESTAMP} | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {Maximum} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {TIMESTAMP} | |
January | 2699.95 | 07-JAN-15:09 | 1884.17 | 01-JAN-11:09 | 674.13 | 01-JAN-11:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.38 | 23-JAN-14:00 | 1452.12 | 18-JAN-17:00 |
February | 2699.95 | 04-FEB-15:09 | 1884.17 | 01-FEB-10:09 | 674.13 | 01-FEB-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2421.42 | 06-FEB-15:00 | 1752.39 | 20-FEB-16:00 |
March | 2699.95 | 04-MAR-15:09 | 1884.17 | 01-MAR-10:09 | 674.13 | 01-MAR-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3930.47 | 27-MAR-11:10 | 1773.86 | 05-MAR-18:00 |
April | 2699.95 | 01-APR-14:09 | 1884.17 | 01-APR-09:09 | 674.13 | 01-APR-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4687.70 | 28-APR-12:00 | 395.29 | 05-APR-01:00 |
May | 2699.95 | 06-MAY-14:09 | 1884.17 | 01-MAY-09:09 | 674.13 | 01-MAY-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4979.74 | 21-MAY-13:00 | 230.91 | 01-MAY-07:10 |
June | 2699.95 | 03-JUN-14:09 | 1884.17 | 01-JUN-09:09 | 674.13 | 01-JUN-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5007.64 | 09-JUN-15:00 | 249.35 | 22-JUN-08:00 |
July | 2699.95 | 01-JUL-14:09 | 1884.17 | 01-JUL-09:09 | 674.13 | 01-JUL-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5649.51 | 21-JUL-12:00 | 0.00 | 01-JUL-00:03 |
August | 2699.95 | 05-AUG-14:09 | 1884.17 | 01-AUG-09:09 | 674.13 | 01-AUG-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 5962.90 | 16-AUG-12:00 | 0.00 | 01-AUG-00:10 |
September | 2699.95 | 02-SEP-14:09 | 1884.17 | 01-SEP-09:09 | 674.13 | 01-SEP-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 4614.87 | 04-SEP-14:00 | 134.77 | 25-SEP-05:00 |
October | 2699.95 | 07-OCT-14:09 | 1884.17 | 01-OCT-10:09 | 674.13 | 01-OCT-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 3735.04 | 19-OCT-14:00 | 266.00 | 29-OCT-07:02 |
November | 2699.95 | 04-NOV-14:09 | 1884.17 | 01-NOV-09:09 | 674.13 | 01-NOV-09:09 | 0.00 | 0.00 | 0.00 | 0.00 | 2684.11 | 05-NOV-12:00 | 416.85 | 23-NOV-08:62 |
December | 2699.95 | 02-DEC-15:09 | 1884.17 | 01-DEC-10:09 | 674.13 | 01-DEC-10:09 | 0.00 | 0.00 | 0.00 | 0.00 | 1679.96 | 10-DEC-12:10 | 1783.39 | 15-DEC-12:10 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||||||||
Minimum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 1148.38 | 0.00 | |||||
Maximum of Months | 2699.95 | 1884.17 | 674.13 | 0.00 | 0.00 | 0.00 | 0.00 | 5962.90 | 1783.39 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 46848.66 | 30-JAN-09:02 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 173.60 |
February | 46857.53 | 06-FEB-09:02 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 188.35 |
March | 65041.87 | 28-MAR-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 60.97 | 0.00 |
April | 63192.03 | 26-APR-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 299.98 | 0.00 |
May | 60101.54 | 11-MAY-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 665.02 | 0.00 |
June | 56910.08 | 02-JUN-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 652.50 | 0.00 |
July | 59185.19 | 04-JUL-07:01 | 2700.03 | 2332.90 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 387.07 | 0.00 |
August | 52528.47 | 06-AUG-07:01 | 3375.03 | 2916.13 | 749.03 | 0.00 | 0.00 | 0.00 | 0.00 | 530.74 | 0.00 |
September | 53127.81 | 26-SEP-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 336.58 | 0.00 |
October | 62414.70 | 21-OCT-08:61 | 2362.52 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 37.16 |
November | 58936.44 | 18-NOV-09:02 | 2025.02 | 17497.85 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 100.51 |
December | 60428.81 | 01-DEC-09:02 | 1687.52 | 14581.55 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 7.89 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 46848.66 | 1687.52 | 2332.90 | 599.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 65041.87 | 3375.03 | 20414.16 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 665.02 | 188.35 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25704.94 | 30-JAN-09:02 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 91.30 |
February | 25050.74 | 06-FEB-09:02 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 96.56 |
March | 32879.09 | 28-MAR-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 31.40 | 0.00 |
April | 31730.96 | 27-APR-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 170.10 | 0.00 |
May | 31050.79 | 08-MAY-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 246.75 | 0.00 |
June | 30072.79 | 02-JUN-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 338.69 | 0.00 |
July | 30720.05 | 04-JUL-07:01 | 1349.97 | 1361.78 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 213.30 | 0.00 |
August | 28158.47 | 06-AUG-07:01 | 1687.47 | 1702.23 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 303.85 | 0.00 |
September | 28853.19 | 26-SEP-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 179.71 | 0.00 |
October | 32276.73 | 21-OCT-08:61 | 1181.23 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.41 |
November | 30954.99 | 18-NOV-09:02 | 1012.48 | 10213.37 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 53.29 |
December | 31147.56 | 01-DEC-09:02 | 843.73 | 8511.14 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.83 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 25050.74 | 843.73 | 1361.78 | 299.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 32879.09 | 1687.47 | 11915.60 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 338.69 | 96.56 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25129.74 | 29-JAN-09:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.76 |
February | 24023.91 | 06-FEB-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.48 |
March | 33508.71 | 28-MAR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
April | 33251.01 | 26-APR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 23.53 |
May | 31317.55 | 10-MAY-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 208.13 | 0.00 |
June | 26670.49 | 02-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 160.46 | 0.00 |
July | 29385.37 | 04-JUL-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 287.41 | 0.00 |
August | 24049.27 | 06-AUG-07:01 | 0.00 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 279.13 | 0.00 |
September | 24746.72 | 26-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.59 | 0.00 |
October | 30566.36 | 20-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.31 |
November | 29869.24 | 19-NOV-09:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.44 |
December | 26893.44 | 27-DEC-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.73 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24023.91 | 0.00 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33508.71 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 287.41 | 153.73 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 25152.96 | 29-JAN-09:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 73.04 |
February | 24094.03 | 06-FEB-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 149.67 |
March | 33556.51 | 28-MAR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 39.09 |
April | 33353.01 | 26-APR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 25.16 |
May | 31381.51 | 10-MAY-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 207.97 | 0.00 |
June | 26767.43 | 02-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 160.09 | 0.00 |
July | 29466.79 | 04-JUL-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 286.97 | 0.00 |
August | 24321.66 | 06-AUG-07:01 | 0.00 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 272.94 | 0.00 |
September | 24854.44 | 26-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 | 0.00 |
October | 30627.17 | 20-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.26 |
November | 29924.47 | 19-NOV-09:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.42 |
December | 26920.19 | 27-DEC-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 153.29 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 24094.03 | 0.00 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33556.51 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 286.97 | 153.29 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24934.74 | 29-JAN-09:02 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 67.40 |
February | 23895.93 | 06-FEB-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 145.52 |
March | 33452.21 | 28-MAR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.98 |
April | 33111.08 | 26-APR-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.94 |
May | 31302.25 | 10-MAY-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 206.74 | 0.00 |
June | 26619.51 | 02-JUN-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 160.27 | 0.00 |
July | 29354.80 | 04-JUL-08:61 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 286.97 | 0.00 |
August | 24143.54 | 06-AUG-07:01 | 0.00 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 275.23 | 0.00 |
September | 24707.94 | 26-SEP-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 51.47 | 0.00 |
October | 30501.96 | 20-OCT-07:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 86.33 |
November | 29803.65 | 19-NOV-09:01 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 1.30 |
December | 26696.60 | 27-DEC-08:62 | 843.73 | 7681.79 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 148.19 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 23895.93 | 0.00 | 1536.36 | 374.52 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 33452.21 | 1181.23 | 10754.51 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 286.97 | 148.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 45908.58 | 29-JAN-10:02 | 4455.04 | 11523.34 | 4494.18 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 45.96 |
February | 51933.12 | 05-FEB-10:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 189.08 | 0.00 |
March | 59755.22 | 28-MAR-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 48.05 | 0.00 |
April | 57790.69 | 26-APR-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 275.58 | 0.00 |
May | 54906.10 | 11-MAY-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 599.68 | 0.00 |
June | 51231.71 | 02-JUN-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 588.19 | 0.00 |
July | 50753.41 | 04-JUL-09:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 630.28 | 0.00 |
August | 43360.45 | 06-AUG-08:61 | 0.00 | 1344.26 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 558.55 | 0.00 |
September | 47996.63 | 26-SEP-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 303.97 | 0.00 |
October | 55661.03 | 21-OCT-08:61 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 38.29 |
November | 55390.21 | 19-NOV-10:01 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 165.55 | 0.00 |
December | 53180.12 | 01-DEC-09:02 | 3712.53 | 9602.79 | 3745.15 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 43360.45 | 0.00 | 1344.26 | 524.32 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 59755.22 | 5197.55 | 13443.90 | 5243.22 | 0.00 | 0.00 | 0.00 | 0.00 | 630.28 | 45.96 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 24064.06 | 29-JAN-10:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.19 |
February | 27233.62 | 05-FEB-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 112.26 | 0.00 |
March | 31430.44 | 28-MAR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 30.69 | 0.00 |
April | 30441.02 | 26-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 158.85 | 0.00 |
May | 28978.01 | 11-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 339.72 | 0.00 |
June | 26970.94 | 02-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 333.25 | 0.00 |
July | 26802.58 | 04-JUL-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 358.52 | 0.00 |
August | 22711.41 | 06-AUG-08:61 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 321.40 | 0.00 |
September | 25280.36 | 26-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 173.62 | 0.00 |
October | 29211.40 | 21-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 16.55 |
November | 29132.98 | 19-NOV-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 95.43 | 0.00 |
December | 27931.78 | 01-DEC-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.02 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22711.41 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31430.44 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 358.52 | 19.19 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23949.32 | 29-JAN-10:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 17.69 |
February | 27105.01 | 05-FEB-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 113.78 | 0.00 |
March | 31324.66 | 28-MAR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 30.92 | 0.00 |
April | 30340.20 | 26-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 158.83 | 0.00 |
May | 28884.49 | 11-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 339.53 | 0.00 |
June | 26880.93 | 02-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 333.05 | 0.00 |
July | 26711.01 | 04-JUL-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 358.40 | 0.00 |
August | 22635.57 | 06-AUG-08:61 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 321.24 | 0.00 |
September | 25190.03 | 26-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 173.19 | 0.00 |
October | 29096.12 | 21-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.84 |
November | 29038.70 | 19-NOV-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 95.28 | 0.00 |
December | 27814.10 | 01-DEC-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 4.86 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22635.57 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31324.66 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 358.40 | 17.69 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 23945.76 | 29-JAN-10:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 13.37 |
February | 27097.72 | 05-FEB-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 118.59 | 0.00 |
March | 31425.00 | 28-MAR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 32.37 | 0.00 |
April | 30443.59 | 26-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 159.75 | 0.00 |
May | 28995.67 | 11-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 339.83 | 0.00 |
June | 26977.35 | 02-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 333.44 | 0.00 |
July | 26831.52 | 04-JUL-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 358.42 | 0.00 |
August | 22879.87 | 06-AUG-08:61 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 317.07 | 0.00 |
September | 25292.36 | 26-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 173.84 | 0.00 |
October | 29199.39 | 21-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 15.37 |
November | 29141.98 | 19-NOV-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 95.55 | 0.00 |
December | 27824.54 | 01-DEC-09:02 | 1856.21 | 4958.33 | 1872.58 | 0.00 | 0.00 | 0.00 | 0.00 | 7.39 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 22879.87 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 31425.00 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 358.42 | 15.37 |
Report: SpaceGainComponentsAtCoolingPeakMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE AIR SYSTEM SENSIBLE COOLING RATE {Maximum} [W] | ZONE AIR SYSTEM SENSIBLE COOLING RATE {TIMESTAMP} | ZONE PEOPLE TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE LIGHTS TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE ELECTRIC EQUIPMENT TOTAL HEATING ENERGY {AT MAX/MIN} [W] | ZONE GAS EQUIPMENT TOTAL HEATING ENERGY [] | ZONE HOT WATER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE STEAM EQUIPMENT TOTAL HEATING ENERGY [] | ZONE OTHER EQUIPMENT TOTAL HEATING ENERGY [] | ZONE INFILTRATION SENSIBLE HEAT GAIN ENERGY {AT MAX/MIN} [W] | ZONE INFILTRATION SENSIBLE HEAT LOSS ENERGY {AT MAX/MIN} [W] | |
January | 26780.73 | 29-JAN-10:02 | 2227.46 | 5950.00 | 2247.09 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 19.51 |
February | 30919.98 | 05-FEB-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 166.87 | 0.00 |
March | 35285.69 | 28-MAR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 43.96 | 0.00 |
April | 34270.48 | 27-APR-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 179.66 | 0.00 |
May | 32756.03 | 11-MAY-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 404.08 | 0.00 |
June | 30447.60 | 02-JUN-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 393.84 | 0.00 |
July | 30854.06 | 03-JUL-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 311.96 | 0.00 |
August | 27271.81 | 06-AUG-08:61 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 319.30 | 0.00 |
September | 28534.85 | 26-SEP-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 202.92 | 0.00 |
October | 33459.75 | 21-OCT-08:61 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 20.53 |
November | 32361.18 | 19-NOV-10:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 120.04 | 0.00 |
December | 28617.24 | 12-DEC-09:01 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 69.69 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | |||||||
Minimum of Months | 26780.73 | 0.00 | 694.17 | 262.16 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 35285.69 | 2598.70 | 6941.66 | 2621.61 | 0.00 | 0.00 | 0.00 | 0.00 | 404.08 | 69.69 |
Report: EnergyConsumptionElectricityNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportELECTRICITY:FACILITY [J] | ELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | NATURALGAS:FACILITY [J] | NATURALGAS:FACILITY {Maximum} [W] | NATURALGAS:FACILITY {TIMESTAMP} | |
January | 0.118493E+12 | 96711.36 | 28-JAN-13:50 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 0.112415E+12 | 114890.33 | 07-FEB-13:39 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 0.132703E+12 | 123150.13 | 27-MAR-11:20 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 0.141681E+12 | 136766.51 | 28-APR-12:09 | 0.00 | 0.00 | 01-APR-00:10 |
May | 0.171312E+12 | 150772.27 | 31-MAY-12:30 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 0.182129E+12 | 161121.78 | 09-JUN-12:50 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 0.200474E+12 | 168883.20 | 20-JUL-12:50 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 0.208981E+12 | 177043.22 | 10-AUG-16:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 0.185035E+12 | 163555.80 | 07-SEP-12:00 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 0.169519E+12 | 153794.68 | 07-OCT-13:20 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 0.144406E+12 | 136847.84 | 01-NOV-14:20 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 0.127820E+12 | 107865.38 | 05-DEC-17:49 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.189497E+13 | 0.00 | ||||
Minimum of Months | 0.112415E+12 | 96711.36 | 0.00 | 0.00 | ||
Maximum of Months | 0.208981E+12 | 177043.22 | 0.00 | 0.00 |
Report: EndUseEnergyConsumptionElectricityMonthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY [J] | EXTERIORLIGHTS:ELECTRICITY [J] | INTERIOREQUIPMENT:ELECTRICITY [J] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY [J] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY [J] | COOLING:ELECTRICITY [J] | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY [J] | COGENERATION:ELECTRICITY [] | |
January | 0.390997E+11 | 0.115154E+11 | 0.108804E+11 | 0.00 | 0.280905E+11 | 0.00 | 0.00 | 0.238151E+11 | 0.00 | 0.00 | 0.00 | 0.509148E+10 | 0.00 |
February | 0.353889E+11 | 0.999081E+10 | 0.985143E+10 | 0.00 | 0.254390E+11 | 0.00 | 0.00 | 0.271643E+11 | 0.00 | 0.00 | 0.00 | 0.458096E+10 | 0.00 |
March | 0.396588E+11 | 0.104635E+11 | 0.110560E+11 | 0.00 | 0.285782E+11 | 0.00 | 0.00 | 0.379285E+11 | 0.00 | 0.00 | 0.00 | 0.501824E+10 | 0.00 |
April | 0.379231E+11 | 0.949034E+10 | 0.105544E+11 | 0.00 | 0.272836E+11 | 0.00 | 0.00 | 0.516919E+11 | 0.00 | 0.00 | 0.00 | 0.473748E+10 | 0.00 |
May | 0.393718E+11 | 0.929572E+10 | 0.109629E+11 | 0.00 | 0.283983E+11 | 0.00 | 0.00 | 0.784896E+11 | 0.00 | 0.00 | 0.00 | 0.479368E+10 | 0.00 |
June | 0.383312E+11 | 0.875818E+10 | 0.106855E+11 | 0.00 | 0.277104E+11 | 0.00 | 0.00 | 0.920670E+11 | 0.00 | 0.00 | 0.00 | 0.457697E+10 | 0.00 |
July | 0.389786E+11 | 0.913816E+10 | 0.108424E+11 | 0.00 | 0.281245E+11 | 0.00 | 0.00 | 0.108711E+12 | 0.00 | 0.00 | 0.00 | 0.467924E+10 | 0.00 |
August | 0.396438E+11 | 0.957839E+10 | 0.110491E+11 | 0.00 | 0.286944E+11 | 0.00 | 0.00 | 0.115278E+12 | 0.00 | 0.00 | 0.00 | 0.473770E+10 | 0.00 |
September | 0.379380E+11 | 0.984716E+10 | 0.105613E+11 | 0.00 | 0.273794E+11 | 0.00 | 0.00 | 0.946682E+11 | 0.00 | 0.00 | 0.00 | 0.464085E+10 | 0.00 |
October | 0.390997E+11 | 0.108064E+11 | 0.108804E+11 | 0.00 | 0.281819E+11 | 0.00 | 0.00 | 0.756558E+11 | 0.00 | 0.00 | 0.00 | 0.489459E+10 | 0.00 |
November | 0.378782E+11 | 0.110010E+11 | 0.105443E+11 | 0.00 | 0.272774E+11 | 0.00 | 0.00 | 0.528706E+11 | 0.00 | 0.00 | 0.00 | 0.483474E+10 | 0.00 |
December | 0.389936E+11 | 0.116776E+11 | 0.108529E+11 | 0.00 | 0.280190E+11 | 0.00 | 0.00 | 0.332121E+11 | 0.00 | 0.00 | 0.00 | 0.506454E+10 | 0.00 |
Annual Sum or Average | 0.462305E+12 | 0.121563E+12 | 0.128721E+12 | 0.00 | 0.333176E+12 | 0.00 | 0.00 | 0.791551E+12 | 0.00 | 0.00 | 0.00 | 0.576505E+11 | 0.00 |
Minimum of Months | 0.353889E+11 | 0.875818E+10 | 0.985143E+10 | 0.00 | 0.254390E+11 | 0.00 | 0.00 | 0.238151E+11 | 0.00 | 0.00 | 0.00 | 0.457697E+10 | 0.00 |
Maximum of Months | 0.396588E+11 | 0.116776E+11 | 0.110560E+11 | 0.00 | 0.286944E+11 | 0.00 | 0.00 | 0.115278E+12 | 0.00 | 0.00 | 0.00 | 0.509148E+10 | 0.00 |
Report: EndUseEnergyConsumptionNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS [J] | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | HUMIDIFIER:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart1Monthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportINTERIORLIGHTS:ELECTRICITY {Maximum} [W] | INTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | EXTERIORLIGHTS:ELECTRICITY {Maximum} [W] | EXTERIORLIGHTS:ELECTRICITY {TIMESTAMP} | INTERIOREQUIPMENT:ELECTRICITY {Maximum} [W] | INTERIOREQUIPMENT:ELECTRICITY {TIMESTAMP} | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {Maximum} [W] | FANS:ELECTRICITY {TIMESTAMP} | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {Maximum} [W] | HEATING:ELECTRICITY {TIMESTAMP} | |
January | 28718.22 | 01-JAN-11:09 | 7723.26 | 01-JAN-00:10 | 8089.53 | 01-JAN-11:09 | 0.00 | 19339.67 | 03-JAN-20:00 | 0.00 | 0.00 | 01-JAN-00:10 |
February | 28718.22 | 01-FEB-10:09 | 7723.26 | 01-FEB-00:10 | 8089.53 | 01-FEB-10:09 | 0.00 | 19339.67 | 04-FEB-09:09 | 0.00 | 0.00 | 01-FEB-00:10 |
March | 28718.22 | 01-MAR-10:09 | 7723.26 | 01-MAR-00:10 | 8089.53 | 01-MAR-10:09 | 0.00 | 19339.67 | 02-MAR-19:19 | 0.00 | 0.00 | 01-MAR-00:10 |
April | 28718.22 | 01-APR-09:09 | 7723.26 | 01-APR-00:10 | 8089.53 | 01-APR-09:09 | 0.00 | 19339.67 | 01-APR-10:30 | 0.00 | 0.00 | 01-APR-00:10 |
May | 28718.22 | 01-MAY-09:09 | 7723.26 | 01-MAY-00:10 | 8089.53 | 01-MAY-09:09 | 0.00 | 19339.67 | 01-MAY-09:20 | 0.00 | 0.00 | 01-MAY-00:10 |
June | 28718.22 | 01-JUN-09:09 | 7723.26 | 01-JUN-00:10 | 8089.53 | 01-JUN-09:09 | 0.00 | 19339.67 | 07-JUN-08:09 | 0.00 | 0.00 | 01-JUN-00:10 |
July | 28718.22 | 01-JUL-09:09 | 7723.26 | 01-JUL-00:10 | 8089.53 | 01-JUL-09:09 | 0.00 | 19339.67 | 03-JUL-11:30 | 0.00 | 0.00 | 01-JUL-00:10 |
August | 28718.22 | 01-AUG-09:09 | 7723.26 | 01-AUG-00:10 | 8089.53 | 01-AUG-09:09 | 0.00 | 19339.67 | 01-AUG-07:10 | 0.00 | 0.00 | 01-AUG-00:10 |
September | 28718.22 | 01-SEP-09:09 | 7723.26 | 01-SEP-00:10 | 8089.53 | 01-SEP-09:09 | 0.00 | 19339.67 | 01-SEP-19:19 | 0.00 | 0.00 | 01-SEP-00:10 |
October | 28718.22 | 01-OCT-10:09 | 7723.26 | 01-OCT-00:10 | 8089.53 | 01-OCT-10:09 | 0.00 | 19339.67 | 03-OCT-19:10 | 0.00 | 0.00 | 01-OCT-00:10 |
November | 28718.22 | 01-NOV-09:09 | 7723.26 | 01-NOV-00:10 | 8089.53 | 01-NOV-09:09 | 0.00 | 19339.67 | 06-NOV-16:19 | 0.00 | 0.00 | 01-NOV-00:10 |
December | 28718.22 | 01-DEC-10:09 | 7723.26 | 01-DEC-00:10 | 8089.53 | 01-DEC-10:09 | 0.00 | 19339.67 | 01-DEC-09:00 | 0.00 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.00 | 0.00 | ||||||||||
Minimum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 19339.67 | 0.00 | 0.00 | |||||
Maximum of Months | 28718.22 | 7723.26 | 8089.53 | 0.00 | 19339.67 | 0.00 | 0.00 |
Report: PeakEnergyEndUseElectricityPart2Monthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING:ELECTRICITY {Maximum} [W] | COOLING:ELECTRICITY {TIMESTAMP} | HEATREJECTION:ELECTRICITY [] | HUMIDIFIER:ELECTRICITY [] | HEATRECOVERY:ELECTRICITY [] | WATERSYSTEMS:ELECTRICITY {Maximum} [W] | WATERSYSTEMS:ELECTRICITY {TIMESTAMP} | COGENERATION:ELECTRICITY [] | |
January | 37424.09 | 29-JAN-15:00 | 0.00 | 0.00 | 0.00 | 11786.01 | 11-JAN-12:39 | 0.00 |
February | 51178.22 | 07-FEB-13:39 | 0.00 | 0.00 | 0.00 | 10423.88 | 02-FEB-18:30 | 0.00 |
March | 61641.21 | 27-MAR-11:09 | 0.00 | 0.00 | 0.00 | 7731.49 | 02-MAR-13:39 | 0.00 |
April | 78744.35 | 28-APR-11:00 | 0.00 | 0.00 | 0.00 | 8325.61 | 25-APR-13:50 | 0.00 |
May | 91712.94 | 31-MAY-12:09 | 0.00 | 0.00 | 0.00 | 8911.06 | 23-MAY-13:39 | 0.00 |
June | 101069.49 | 09-JUN-12:00 | 0.00 | 0.00 | 0.00 | 9617.35 | 23-JUN-15:00 | 0.00 |
July | 110535.53 | 20-JUL-12:00 | 0.00 | 0.00 | 0.00 | 7534.79 | 01-JUL-12:50 | 0.00 |
August | 115477.03 | 10-AUG-16:10 | 0.00 | 0.00 | 0.00 | 9639.64 | 17-AUG-13:09 | 0.00 |
September | 102058.29 | 07-SEP-13:30 | 0.00 | 0.00 | 0.00 | 7536.99 | 01-SEP-13:20 | 0.00 |
October | 91408.90 | 07-OCT-12:00 | 0.00 | 0.00 | 0.00 | 9651.35 | 31-OCT-11:30 | 0.00 |
November | 75188.72 | 01-NOV-13:00 | 0.00 | 0.00 | 0.00 | 9156.59 | 09-NOV-19:10 | 0.00 |
December | 46062.14 | 05-DEC-15:39 | 0.00 | 0.00 | 0.00 | 7562.80 | 06-DEC-13:30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | ||||
Minimum of Months | 37424.09 | 0.00 | 0.00 | 0.00 | 7534.79 | 0.00 | ||
Maximum of Months | 115477.03 | 0.00 | 0.00 | 0.00 | 11786.01 | 0.00 |
Report: ElectricComponentsOfPeakDemandMonthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportELECTRICITY:FACILITY {Maximum} [W] | ELECTRICITY:FACILITY {TIMESTAMP} | INTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | INTERIOREQUIPMENT:ELECTRICITY {AT MAX/MIN} [W] | EXTERIORLIGHTS:ELECTRICITY {AT MAX/MIN} [W] | EXTERIOREQUIPMENT:ELECTRICITY [] | FANS:ELECTRICITY {AT MAX/MIN} [W] | PUMPS:ELECTRICITY [] | HEATING:ELECTRICITY {AT MAX/MIN} [W] | COOLING:ELECTRICITY {AT MAX/MIN} [W] | HEATREJECTION:ELECTRICITY [] | |
January | 96711.36 | 28-JAN-13:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 32395.67 | 0.00 |
February | 114890.33 | 07-FEB-13:39 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 51178.22 | 0.00 |
March | 123150.13 | 27-MAR-11:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 61571.58 | 0.00 |
April | 136766.51 | 28-APR-12:09 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 77292.01 | 0.00 |
May | 150772.27 | 31-MAY-12:30 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 91300.46 | 0.00 |
June | 161121.78 | 09-JUN-12:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 100735.94 | 0.00 |
July | 168883.20 | 20-JUL-12:50 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 109412.84 | 0.00 |
August | 177043.22 | 10-AUG-16:10 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 115477.03 | 0.00 |
September | 163555.80 | 07-SEP-12:00 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 101975.87 | 0.00 |
October | 153794.68 | 07-OCT-13:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 90731.57 | 0.00 |
November | 136847.84 | 01-NOV-14:20 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 74273.20 | 0.00 |
December | 107865.38 | 05-DEC-17:49 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 19339.67 | 0.00 | 0.00 | 40667.42 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | ||||||||
Minimum of Months | 96711.36 | 28718.22 | 8089.53 | 0.00 | 0.00 | 19339.67 | 0.00 | 0.00 | 32395.67 | 0.00 | |
Maximum of Months | 177043.22 | 28718.22 | 8089.53 | 7723.26 | 0.00 | 19339.67 | 0.00 | 0.00 | 115477.03 | 0.00 |
Report: PeakEnergyEndUseNaturalGasMonthly
For: Meter
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportINTERIOREQUIPMENT:NATURALGAS [] | EXTERIOREQUIPMENT:NATURALGAS [] | HEATING:NATURALGAS {Maximum} [W] | HEATING:NATURALGAS {TIMESTAMP} | COOLING:NATURALGAS [] | WATERSYSTEMS:NATURALGAS [] | COGENERATION:NATURALGAS [] | |
January | 0.00 | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 01-FEB-00:10 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 01-MAR-00:10 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 01-APR-00:10 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 01-JUL-00:10 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 01-SEP-00:10 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.54 | 1.67 | 24.54 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.54 | 1.50 | 24.54 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.67 | 24.50 | 0.67 | 24.50 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.83 | 24.53 | 3.83 | 24.53 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.54 | 1.67 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.53 | 0.33 | 24.53 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.47 | 0.50 | 24.47 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.83 | 24.50 | 0.83 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.50 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 1.33 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.50 | 1.17 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 24.49 | 3.00 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.54 | 1.33 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 1.33 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.17 | 24.50 | 1.17 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.54 | 0.33 | 24.54 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.48 | 0.17 | 24.48 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.00 | 24.49 | 3.00 | 24.49 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.54 | 1.33 | 24.54 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.48 | 1.33 | 24.48 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.50 | 1.33 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.55 | 0.33 | 24.55 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.49 | 0.17 | 24.49 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.17 | 24.50 | 3.17 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.55 | 1.33 | 24.55 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.49 | 0.50 | 24.49 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.51 | 2.17 | 24.51 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.52 | 2.17 | 24.52 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 1.00 | 24.53 | 1.00 | 24.53 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.53 | 0.50 | 24.53 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 6.33 | 24.51 | 6.33 | 24.51 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 2.17 | 24.53 | 2.17 | 24.53 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.49 | 1.67 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.50 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.50 | 4.50 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.56 | 1.67 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.50 | 1.67 | 24.50 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.50 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.50 | 24.50 | 4.50 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.67 | 24.56 | 1.67 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.48 | 0.33 | 24.48 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.50 | 24.49 | 1.50 | 24.49 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.49 | 1.83 | 24.49 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.56 | 0.50 | 24.56 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.50 | 0.50 | 24.50 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 4.67 | 24.50 | 4.67 | 24.50 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.83 | 24.56 | 1.83 | 24.56 |
Report: SetpointsNotMetWithTemperaturesMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE HEATING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE HEATING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE COOLING SETPOINT NOT MET WHILE OCCUPIED TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.00 | 0.17 | 24.45 | 0.17 | 24.45 |
July | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 24.47 | 1.33 | 24.47 |
August | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.88 | 1.00 | 25.29 |
September | 0.00 | 0.00 | 0.00 | 0.00 | 0.50 | 24.51 | 0.50 | 24.51 |
October | 0.00 | 0.00 | 0.00 | 0.00 | 0.33 | 24.47 | 0.33 | 24.47 |
November | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 3.67 | 24.99 | 3.33 | 24.75 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 1.33 | 25.88 | 1.33 | 25.29 |
Report: ComfortReportSimple55Monthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.83 | 23.52 | 300.67 | 23.88 | 0.00 | 23.88 |
February | 8.33 | 24.05 | 371.00 | 23.92 | 1.67 | 23.93 |
March | 6.33 | 24.11 | 409.00 | 23.94 | 2.17 | 23.94 |
April | 9.33 | 24.82 | 459.50 | 23.97 | 9.33 | 23.99 |
May | 26.67 | 24.89 | 496.00 | 24.03 | 26.67 | 24.08 |
June | 120.00 | 24.25 | 481.00 | 24.04 | 120.00 | 24.08 |
July | 197.33 | 24.11 | 495.00 | 24.02 | 197.33 | 24.04 |
August | 197.83 | 24.17 | 497.00 | 24.05 | 197.83 | 24.08 |
September | 130.50 | 24.20 | 479.00 | 24.03 | 130.50 | 24.06 |
October | 68.50 | 24.40 | 496.00 | 24.04 | 68.50 | 24.08 |
November | 14.17 | 24.83 | 478.00 | 23.99 | 14.17 | 24.02 |
December | 4.50 | 24.15 | 431.67 | 23.92 | 2.33 | 23.92 |
Annual Sum or Average | 802.33 | 24.22 | 5393.83 | 24.00 | 770.50 | 24.03 |
Minimum of Months | 4.50 | 23.52 | 300.67 | 23.88 | 0.00 | 23.88 |
Maximum of Months | 197.83 | 24.89 | 497.00 | 24.05 | 197.83 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 23.67 | 278.33 | 23.90 | 0.00 | 23.90 |
February | 2.00 | 23.78 | 340.67 | 23.92 | 0.00 | 23.92 |
March | 0.17 | 23.72 | 383.83 | 23.95 | 0.00 | 23.95 |
April | 2.17 | 23.89 | 437.67 | 23.97 | 2.17 | 23.97 |
May | 14.17 | 24.38 | 493.50 | 24.00 | 14.17 | 24.01 |
June | 78.50 | 24.27 | 481.00 | 24.03 | 78.50 | 24.06 |
July | 148.17 | 24.17 | 495.00 | 24.03 | 148.17 | 24.05 |
August | 161.50 | 24.19 | 497.00 | 24.05 | 161.50 | 24.08 |
September | 94.50 | 24.17 | 479.00 | 24.01 | 94.50 | 24.04 |
October | 44.83 | 24.31 | 494.00 | 24.01 | 44.83 | 24.04 |
November | 6.33 | 24.18 | 464.33 | 23.98 | 6.33 | 23.98 |
December | 3.83 | 23.87 | 403.00 | 23.93 | 2.83 | 23.93 |
Annual Sum or Average | 568.83 | 24.19 | 5247.33 | 23.99 | 553.00 | 24.01 |
Minimum of Months | 0.17 | 23.67 | 278.33 | 23.90 | 0.00 | 23.90 |
Maximum of Months | 161.50 | 24.38 | 497.00 | 24.05 | 161.50 | 24.08 |
Report: ComfortReportSimple55Monthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.00 | 23.60 | 247.00 | 24.05 | 0.00 | 24.05 |
February | 1.67 | 25.08 | 292.33 | 24.05 | 0.67 | 24.06 |
March | 3.17 | 25.91 | 327.83 | 24.10 | 2.33 | 24.12 |
April | 11.17 | 26.56 | 339.67 | 24.21 | 11.17 | 24.28 |
May | 38.00 | 26.17 | 375.00 | 24.37 | 38.00 | 24.52 |
June | 95.50 | 24.99 | 366.00 | 24.37 | 95.50 | 24.48 |
July | 156.50 | 24.70 | 369.00 | 24.39 | 156.50 | 24.46 |
August | 172.50 | 24.63 | 379.00 | 24.36 | 172.50 | 24.43 |
September | 115.83 | 24.87 | 360.00 | 24.37 | 115.83 | 24.47 |
October | 57.83 | 25.29 | 371.00 | 24.33 | 57.83 | 24.44 |
November | 17.17 | 25.43 | 359.33 | 24.17 | 17.17 | 24.23 |
December | 5.33 | 24.77 | 340.17 | 24.06 | 5.00 | 24.07 |
Annual Sum or Average | 683.67 | 24.93 | 4126.33 | 24.26 | 672.50 | 24.35 |
Minimum of Months | 1.67 | 23.60 | 247.00 | 24.05 | 0.00 | 24.05 |
Maximum of Months | 172.50 | 26.56 | 379.00 | 24.39 | 172.50 | 24.52 |
Report: ComfortReportSimple55Monthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 9.67 | 23.57 | 243.17 | 24.05 | 0.00 | 24.05 |
February | 2.00 | 24.85 | 291.50 | 24.05 | 0.67 | 24.06 |
March | 3.17 | 25.91 | 326.83 | 24.10 | 2.33 | 24.12 |
April | 11.17 | 26.57 | 341.83 | 24.21 | 11.17 | 24.28 |
May | 37.83 | 26.19 | 375.00 | 24.38 | 37.83 | 24.53 |
June | 94.17 | 25.01 | 366.00 | 24.37 | 94.17 | 24.48 |
July | 154.17 | 24.72 | 369.00 | 24.39 | 154.17 | 24.46 |
August | 169.33 | 24.65 | 379.00 | 24.37 | 169.33 | 24.43 |
September | 113.33 | 24.89 | 360.00 | 24.38 | 113.33 | 24.48 |
October | 57.00 | 25.34 | 371.00 | 24.34 | 57.00 | 24.45 |
November | 17.33 | 25.50 | 359.33 | 24.17 | 17.33 | 24.23 |
December | 5.33 | 24.77 | 339.33 | 24.06 | 5.00 | 24.07 |
Annual Sum or Average | 674.50 | 24.95 | 4122.00 | 24.27 | 662.33 | 24.35 |
Minimum of Months | 2.00 | 23.57 | 243.17 | 24.05 | 0.00 | 24.05 |
Maximum of Months | 169.33 | 26.57 | 379.00 | 24.39 | 169.33 | 24.53 |
Report: ComfortReportSimple55Monthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.67 | 23.54 | 231.50 | 24.04 | 0.00 | 24.04 |
February | 2.50 | 24.25 | 285.50 | 24.05 | 0.50 | 24.05 |
March | 3.83 | 25.52 | 320.17 | 24.10 | 2.33 | 24.12 |
April | 10.67 | 26.43 | 337.17 | 24.20 | 10.67 | 24.27 |
May | 37.33 | 26.14 | 375.00 | 24.37 | 37.33 | 24.51 |
June | 96.00 | 24.97 | 366.00 | 24.37 | 96.00 | 24.47 |
July | 155.50 | 24.70 | 369.00 | 24.38 | 155.50 | 24.46 |
August | 170.83 | 24.63 | 379.00 | 24.36 | 170.83 | 24.43 |
September | 115.67 | 24.86 | 360.00 | 24.37 | 115.67 | 24.47 |
October | 58.00 | 25.28 | 371.00 | 24.33 | 58.00 | 24.44 |
November | 16.67 | 25.29 | 359.17 | 24.16 | 16.67 | 24.21 |
December | 6.17 | 24.62 | 334.00 | 24.06 | 5.33 | 24.07 |
Annual Sum or Average | 685.83 | 24.90 | 4087.50 | 24.26 | 668.83 | 24.34 |
Minimum of Months | 2.50 | 23.54 | 231.50 | 24.04 | 0.00 | 24.04 |
Maximum of Months | 170.83 | 26.43 | 379.00 | 24.38 | 170.83 | 24.51 |
Report: ComfortReportSimple55Monthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 12.83 | 23.59 | 189.33 | 23.93 | 1.17 | 23.93 |
February | 1.83 | 24.49 | 250.33 | 23.95 | 0.33 | 23.95 |
March | 2.17 | 24.93 | 269.83 | 23.96 | 1.17 | 23.96 |
April | 7.50 | 26.32 | 305.83 | 24.05 | 7.50 | 24.10 |
May | 26.83 | 25.13 | 344.00 | 24.08 | 26.83 | 24.15 |
June | 90.50 | 24.28 | 336.00 | 24.06 | 90.50 | 24.10 |
July | 150.67 | 24.23 | 338.00 | 24.10 | 150.67 | 24.13 |
August | 163.67 | 24.13 | 348.00 | 24.04 | 163.67 | 24.06 |
September | 110.00 | 24.30 | 330.00 | 24.09 | 110.00 | 24.13 |
October | 51.67 | 24.57 | 340.00 | 24.08 | 51.67 | 24.14 |
November | 12.83 | 24.41 | 329.50 | 23.99 | 12.83 | 24.00 |
December | 10.67 | 24.40 | 291.00 | 23.97 | 10.33 | 23.98 |
Annual Sum or Average | 641.17 | 24.31 | 3671.83 | 24.04 | 626.67 | 24.08 |
Minimum of Months | 1.83 | 23.59 | 189.33 | 23.93 | 0.33 | 23.93 |
Maximum of Months | 163.67 | 26.32 | 348.00 | 24.10 | 163.67 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 16.50 | 23.66 | 178.00 | 23.93 | 1.33 | 23.93 |
February | 2.17 | 24.08 | 229.00 | 23.95 | 0.17 | 23.95 |
March | 2.67 | 24.72 | 243.67 | 23.96 | 1.17 | 23.97 |
April | 7.33 | 26.23 | 293.17 | 24.05 | 7.33 | 24.10 |
May | 26.50 | 25.09 | 343.50 | 24.08 | 26.50 | 24.15 |
June | 90.83 | 24.27 | 336.00 | 24.06 | 90.83 | 24.09 |
July | 149.33 | 24.23 | 338.00 | 24.10 | 149.33 | 24.13 |
August | 164.00 | 24.12 | 348.00 | 24.04 | 164.00 | 24.06 |
September | 110.33 | 24.29 | 330.00 | 24.09 | 110.33 | 24.13 |
October | 50.17 | 24.56 | 334.17 | 24.08 | 50.17 | 24.14 |
November | 13.00 | 24.35 | 327.50 | 23.98 | 13.00 | 24.00 |
December | 11.00 | 24.38 | 271.50 | 23.97 | 10.33 | 23.99 |
Annual Sum or Average | 643.83 | 24.30 | 3572.50 | 24.04 | 624.50 | 24.07 |
Minimum of Months | 2.17 | 23.66 | 178.00 | 23.93 | 0.17 | 23.93 |
Maximum of Months | 164.00 | 26.23 | 348.00 | 24.10 | 164.00 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 18.17 | 23.66 | 176.17 | 23.93 | 1.33 | 23.93 |
February | 2.50 | 24.04 | 226.00 | 23.95 | 0.17 | 23.95 |
March | 2.83 | 24.66 | 238.83 | 23.96 | 1.17 | 23.97 |
April | 7.33 | 26.22 | 291.17 | 24.05 | 7.33 | 24.10 |
May | 26.50 | 25.09 | 343.33 | 24.08 | 26.50 | 24.15 |
June | 91.33 | 24.27 | 336.00 | 24.06 | 91.33 | 24.09 |
July | 150.17 | 24.23 | 338.00 | 24.10 | 150.17 | 24.13 |
August | 164.67 | 24.12 | 348.00 | 24.04 | 164.67 | 24.06 |
September | 111.00 | 24.29 | 330.00 | 24.09 | 111.00 | 24.13 |
October | 50.67 | 24.56 | 334.00 | 24.08 | 50.67 | 24.14 |
November | 12.83 | 24.30 | 327.00 | 23.98 | 12.83 | 23.99 |
December | 11.67 | 24.34 | 267.50 | 23.97 | 10.67 | 23.99 |
Annual Sum or Average | 649.67 | 24.29 | 3556.00 | 24.04 | 627.83 | 24.07 |
Minimum of Months | 2.50 | 23.66 | 176.17 | 23.93 | 0.17 | 23.93 |
Maximum of Months | 164.67 | 26.22 | 348.00 | 24.10 | 164.67 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 21.50 | 23.63 | 173.00 | 23.92 | 1.50 | 23.92 |
February | 3.83 | 23.88 | 221.17 | 23.95 | 0.17 | 23.95 |
March | 4.00 | 24.42 | 233.67 | 23.96 | 1.33 | 23.97 |
April | 7.33 | 26.22 | 290.83 | 24.05 | 7.33 | 24.10 |
May | 26.83 | 25.09 | 343.33 | 24.08 | 26.83 | 24.15 |
June | 90.33 | 24.28 | 336.00 | 24.06 | 90.33 | 24.10 |
July | 148.17 | 24.24 | 338.00 | 24.10 | 148.17 | 24.13 |
August | 162.50 | 24.13 | 348.00 | 24.04 | 162.50 | 24.06 |
September | 109.00 | 24.30 | 330.00 | 24.09 | 109.00 | 24.13 |
October | 50.17 | 24.56 | 334.50 | 24.08 | 50.17 | 24.14 |
November | 13.00 | 24.35 | 327.50 | 23.98 | 13.00 | 24.00 |
December | 13.17 | 24.31 | 266.17 | 23.97 | 12.00 | 23.99 |
Annual Sum or Average | 649.83 | 24.29 | 3542.17 | 24.04 | 622.33 | 24.08 |
Minimum of Months | 3.83 | 23.63 | 173.00 | 23.92 | 0.17 | 23.92 |
Maximum of Months | 162.50 | 26.22 | 348.00 | 24.10 | 162.50 | 24.15 |
Report: ComfortReportSimple55Monthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | ZONE THERMAL COMFORT ASHRAE 55 SIMPLE MODEL SUMMER OR WINTER CLOTHES NOT COMFORTABLE TIME {HOURS NON-ZERO} [HOURS] | ZONE MEAN AIR TEMPERATURE {FOR HOURS SHOWN} [C] | |
January | 25.50 | 23.59 | 177.50 | 23.92 | 1.00 | 23.92 |
February | 8.83 | 23.85 | 230.83 | 23.95 | 0.67 | 23.95 |
March | 10.67 | 24.19 | 247.33 | 23.97 | 3.17 | 23.98 |
April | 9.83 | 26.05 | 308.17 | 24.06 | 9.83 | 24.12 |
May | 24.33 | 25.37 | 344.00 | 24.10 | 24.33 | 24.18 |
June | 76.17 | 24.38 | 336.00 | 24.07 | 76.17 | 24.12 |
July | 133.67 | 24.29 | 338.00 | 24.12 | 133.67 | 24.16 |
August | 141.83 | 24.18 | 348.00 | 24.06 | 141.83 | 24.08 |
September | 91.67 | 24.41 | 330.00 | 24.11 | 91.67 | 24.17 |
October | 44.00 | 24.79 | 340.00 | 24.11 | 44.00 | 24.18 |
November | 14.00 | 24.75 | 330.00 | 24.01 | 14.00 | 24.04 |
December | 13.00 | 24.28 | 283.17 | 23.97 | 10.83 | 23.99 |
Annual Sum or Average | 593.50 | 24.38 | 3613.00 | 24.05 | 551.17 | 24.10 |
Minimum of Months | 8.83 | 23.59 | 177.50 | 23.92 | 0.67 | 23.92 |
Maximum of Months | 141.83 | 26.05 | 348.00 | 24.12 | 141.83 | 24.18 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.88711 | 44.44375 | 0.45009 | 9.36687 |
February | 448.00000 | 23.90700 | 47.48405 | 0.48942 | 10.11814 |
March | 497.00000 | 23.93274 | 45.46082 | 0.49746 | 10.30577 |
April | 479.00000 | 23.95239 | 48.86123 | 0.55692 | 11.61741 |
May | 496.00000 | 23.98839 | 50.87070 | -0.1899 | 6.04278 |
June | 481.00000 | 23.99220 | 58.15769 | -0.1069 | 5.59608 |
July | 495.00000 | 23.98558 | 60.47657 | -0.0546 | 5.47332 |
August | 497.00000 | 24.00233 | 61.88094 | -0.0219 | 5.43766 |
September | 479.00000 | 23.98172 | 60.71947 | -0.0694 | 5.41814 |
October | 496.00000 | 23.98753 | 53.96951 | 0.66579 | 14.54979 |
November | 480.00000 | 23.96953 | 50.70470 | 0.59508 | 12.58915 |
December | 496.00000 | 23.91813 | 48.80960 | 0.51465 | 10.66467 |
Annual Sum or Average | 5840.00000 | 23.95898 | 52.67351 | 0.27584 | 8.92308 |
Minimum of Months | 448.00000 | 23.88711 | 44.44375 | -0.1899 | 5.41814 |
Maximum of Months | 497.00000 | 24.00233 | 61.88094 | 0.66579 | 14.54979 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 496.00000 | 23.90239 | 42.89627 | 0.44531 | 9.24646 |
February | 448.00000 | 23.91823 | 45.38376 | 0.47784 | 9.87109 |
March | 497.00000 | 23.94186 | 43.66051 | 0.48406 | 10.01515 |
April | 479.00000 | 23.95918 | 46.30251 | 0.53131 | 11.03853 |
May | 496.00000 | 23.98996 | 48.49264 | -0.2366 | 6.45448 |
June | 481.00000 | 23.99173 | 55.00633 | -0.1679 | 5.95613 |
July | 495.00000 | 23.98452 | 57.68891 | -0.1212 | 5.70454 |
August | 497.00000 | 24.00109 | 59.19281 | -0.0948 | 5.61317 |
September | 479.00000 | 23.98099 | 57.39219 | -0.1382 | 5.73384 |
October | 496.00000 | 23.98730 | 51.12876 | 0.62022 | 13.30820 |
November | 480.00000 | 23.97218 | 48.55660 | 0.56406 | 11.83410 |
December | 496.00000 | 23.92459 | 46.58798 | 0.49688 | 10.28009 |
Annual Sum or Average | 5840.00000 | 23.96306 | 50.21189 | 0.23689 | 8.74657 |
Minimum of Months | 448.00000 | 23.90239 | 42.89627 | -0.2366 | 5.61317 |
Maximum of Months | 497.00000 | 24.00109 | 59.19281 | 0.62022 | 13.30820 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.00390 | 43.74834 | 0.46974 | 9.79758 |
February | 336.00000 | 24.02540 | 46.62915 | 0.50874 | 10.58599 |
March | 379.00000 | 24.05774 | 44.52576 | 0.51586 | 10.82855 |
April | 360.00000 | 24.11950 | 47.33334 | 0.57558 | 12.34888 |
May | 375.00000 | 24.19092 | 49.40933 | -0.1617 | 6.62948 |
June | 366.00000 | 24.20894 | 56.48512 | -0.0828 | 6.40111 |
July | 369.00000 | 24.24976 | 59.76335 | -0.0172 | 6.48098 |
August | 379.00000 | 24.23999 | 61.36103 | 0.00235 | 6.39484 |
September | 360.00000 | 24.21544 | 59.69856 | -0.0404 | 6.33154 |
October | 371.00000 | 24.18058 | 52.80854 | 0.68241 | 15.33454 |
November | 360.00000 | 24.11016 | 50.65520 | 0.61551 | 13.25420 |
December | 369.00000 | 24.03931 | 48.29381 | 0.53386 | 11.17805 |
Annual Sum or Average | 4395.00000 | 24.13761 | 51.75508 | 0.29779 | 9.61321 |
Minimum of Months | 336.00000 | 24.00390 | 43.74834 | -0.1617 | 6.33154 |
Maximum of Months | 379.00000 | 24.24976 | 61.36103 | 0.68241 | 15.33454 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 24.00129 | 43.78652 | 0.46744 | 9.75503 |
February | 336.00000 | 24.02423 | 46.65716 | 0.50744 | 10.55853 |
March | 379.00000 | 24.05733 | 44.53131 | 0.51547 | 10.82033 |
April | 360.00000 | 24.11991 | 47.31095 | 0.57666 | 12.37591 |
May | 375.00000 | 24.19199 | 49.34061 | -0.1575 | 6.61333 |
June | 366.00000 | 24.21013 | 56.37939 | -0.0785 | 6.40063 |
July | 369.00000 | 24.25095 | 59.63010 | -0.0119 | 6.49201 |
August | 379.00000 | 24.24110 | 61.23159 | 0.00712 | 6.41010 |
September | 360.00000 | 24.21667 | 59.57030 | -0.0359 | 6.33896 |
October | 371.00000 | 24.18169 | 52.70955 | 0.68503 | 15.41463 |
November | 360.00000 | 24.11049 | 50.62190 | 0.61670 | 13.28647 |
December | 369.00000 | 24.03866 | 48.30825 | 0.53317 | 11.16245 |
Annual Sum or Average | 4395.00000 | 24.13785 | 51.70170 | 0.29973 | 9.61856 |
Minimum of Months | 336.00000 | 24.00129 | 43.78652 | -0.1575 | 6.33896 |
Maximum of Months | 379.00000 | 24.25095 | 61.23159 | 0.68503 | 15.41463 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 371.00000 | 23.99232 | 43.95926 | 0.46035 | 9.62226 |
February | 336.00000 | 24.01860 | 46.84021 | 0.50183 | 10.43727 |
March | 379.00000 | 24.05298 | 44.67184 | 0.51012 | 10.70025 |
April | 360.00000 | 24.11584 | 47.44193 | 0.57225 | 12.26093 |
May | 375.00000 | 24.18870 | 49.42562 | -0.1619 | 6.61917 |
June | 366.00000 | 24.20693 | 56.49458 | -0.0822 | 6.38457 |
July | 369.00000 | 24.24858 | 59.72317 | -0.0142 | 6.46666 |
August | 379.00000 | 24.23867 | 61.33229 | 0.00482 | 6.38059 |
September | 360.00000 | 24.21363 | 59.69579 | -0.0388 | 6.31531 |
October | 371.00000 | 24.17847 | 52.82392 | 0.68264 | 15.33602 |
November | 360.00000 | 24.10678 | 50.76397 | 0.61320 | 13.18671 |
December | 369.00000 | 24.03413 | 48.49112 | 0.52824 | 11.04869 |
Annual Sum or Average | 4395.00000 | 24.13379 | 51.83339 | 0.29568 | 9.54650 |
Minimum of Months | 336.00000 | 23.99232 | 43.95926 | -0.1619 | 6.31531 |
Maximum of Months | 379.00000 | 24.24858 | 61.33229 | 0.68264 | 15.33602 |
Report: OccupantComfortDataSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91610 | 45.44843 | 0.43883 | 9.17095 |
February | 308.00000 | 23.93229 | 48.23006 | 0.48055 | 9.93083 |
March | 348.00000 | 23.93508 | 46.11251 | 0.48559 | 10.07918 |
April | 330.00000 | 23.98418 | 48.76873 | 0.54848 | 11.55278 |
May | 344.00000 | 24.00280 | 50.73892 | -0.2035 | 6.44421 |
June | 336.00000 | 23.99968 | 57.82706 | -0.1273 | 5.98219 |
July | 338.00000 | 24.04633 | 61.04228 | -0.0529 | 5.87779 |
August | 348.00000 | 24.00417 | 62.74731 | -0.0407 | 5.63097 |
September | 330.00000 | 24.02660 | 60.96248 | -0.0761 | 5.83070 |
October | 340.00000 | 24.01012 | 53.79858 | 0.65708 | 14.41494 |
November | 330.00000 | 23.96869 | 52.04614 | 0.58909 | 12.42967 |
December | 338.00000 | 23.94401 | 49.96726 | 0.50749 | 10.53360 |
Annual Sum or Average | 4030.00000 | 23.98108 | 53.16970 | 0.26467 | 8.97202 |
Minimum of Months | 308.00000 | 23.91610 | 45.44843 | -0.2035 | 5.63097 |
Maximum of Months | 348.00000 | 24.04633 | 62.74731 | 0.65708 | 14.41494 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91641 | 45.38912 | 0.42710 | 8.95556 |
February | 308.00000 | 23.93218 | 48.17909 | 0.46741 | 9.66630 |
March | 348.00000 | 23.93491 | 46.05697 | 0.47081 | 9.77631 |
April | 330.00000 | 23.98322 | 48.71066 | 0.53098 | 11.15095 |
May | 344.00000 | 24.00159 | 50.65213 | -0.2331 | 6.70679 |
June | 336.00000 | 23.99839 | 57.75733 | -0.1590 | 6.16933 |
July | 338.00000 | 24.04519 | 60.98129 | -0.0869 | 5.97967 |
August | 348.00000 | 24.00320 | 62.70629 | -0.0757 | 5.71692 |
September | 330.00000 | 24.02510 | 60.93429 | -0.1088 | 5.95151 |
October | 340.00000 | 24.00910 | 53.71388 | 0.63568 | 13.83185 |
November | 330.00000 | 23.96830 | 51.98883 | 0.57135 | 11.99309 |
December | 338.00000 | 23.94396 | 49.92641 | 0.49409 | 10.24869 |
Annual Sum or Average | 4030.00000 | 23.98036 | 53.11180 | 0.24185 | 8.82961 |
Minimum of Months | 308.00000 | 23.91641 | 45.38912 | -0.2331 | 5.71692 |
Maximum of Months | 348.00000 | 24.04519 | 62.70629 | 0.63568 | 13.83185 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.91476 | 45.44305 | 0.42466 | 8.91434 |
February | 308.00000 | 23.93139 | 48.23946 | 0.46524 | 9.62432 |
March | 348.00000 | 23.93453 | 46.10456 | 0.46875 | 9.73592 |
April | 330.00000 | 23.98278 | 48.75612 | 0.52918 | 11.11000 |
May | 344.00000 | 24.00136 | 50.68709 | -0.2352 | 6.72582 |
June | 336.00000 | 23.99822 | 57.80109 | -0.1609 | 6.18052 |
July | 338.00000 | 24.04502 | 61.02347 | -0.0886 | 5.98396 |
August | 348.00000 | 24.00310 | 62.74962 | -0.0773 | 5.72072 |
September | 330.00000 | 24.02491 | 60.97975 | -0.1105 | 5.95683 |
October | 340.00000 | 24.00887 | 53.75173 | 0.63449 | 13.79951 |
November | 330.00000 | 23.96770 | 52.03443 | 0.56986 | 11.95644 |
December | 338.00000 | 23.94350 | 49.98322 | 0.49232 | 10.21177 |
Annual Sum or Average | 4030.00000 | 23.97992 | 53.15812 | 0.24004 | 8.81094 |
Minimum of Months | 308.00000 | 23.91476 | 45.44305 | -0.2352 | 5.72072 |
Maximum of Months | 348.00000 | 24.04502 | 62.74962 | 0.63449 | 13.79951 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.90983 | 45.55195 | 0.42108 | 8.86178 |
February | 308.00000 | 23.92910 | 48.36067 | 0.46252 | 9.57574 |
March | 348.00000 | 23.93382 | 46.18480 | 0.46694 | 9.70441 |
April | 330.00000 | 23.98237 | 48.80470 | 0.52933 | 11.11484 |
May | 344.00000 | 24.00150 | 50.66343 | -0.2309 | 6.68811 |
June | 336.00000 | 23.99844 | 57.73620 | -0.1553 | 6.14719 |
July | 338.00000 | 24.04541 | 60.90920 | -0.0814 | 5.96331 |
August | 348.00000 | 24.00342 | 62.60204 | -0.0693 | 5.70088 |
September | 330.00000 | 24.02530 | 60.86622 | -0.1036 | 5.93243 |
October | 340.00000 | 24.00917 | 53.68806 | 0.63839 | 13.90647 |
November | 330.00000 | 23.96757 | 52.03083 | 0.57194 | 12.00786 |
December | 338.00000 | 23.94258 | 50.06662 | 0.49146 | 10.19633 |
Annual Sum or Average | 4030.00000 | 23.97929 | 53.14975 | 0.24251 | 8.80097 |
Minimum of Months | 308.00000 | 23.90983 | 45.55195 | -0.2309 | 5.70088 |
Maximum of Months | 348.00000 | 24.04541 | 62.60204 | 0.63839 | 13.90647 |
Report: OccupantComfortDataSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportPEOPLE OCCUPANT COUNT {HOURS NON-ZERO} [HOURS] | PEOPLE AIR TEMPERATURE {FOR HOURS SHOWN} [C] | PEOPLE AIR RELATIVE HUMIDITY {FOR HOURS SHOWN} [%] | ZONE THERMAL COMFORT FANGER MODEL PMV {FOR HOURS SHOWN} [] | ZONE THERMAL COMFORT FANGER MODEL PPD {FOR HOURS SHOWN} [%] | |
January | 340.00000 | 23.90723 | 45.49032 | 0.42535 | 8.98231 |
February | 308.00000 | 23.92919 | 48.40465 | 0.46917 | 9.73713 |
March | 348.00000 | 23.93621 | 46.23067 | 0.47846 | 9.97353 |
April | 330.00000 | 23.98985 | 48.80393 | 0.55633 | 11.76846 |
May | 344.00000 | 24.00818 | 50.43947 | -0.1666 | 6.21603 |
June | 336.00000 | 24.00419 | 57.17469 | -0.0840 | 5.84332 |
July | 338.00000 | 24.05169 | 60.07677 | -0.0002 | 5.87953 |
August | 348.00000 | 24.00800 | 61.51710 | 0.01872 | 5.65830 |
September | 330.00000 | 24.03377 | 59.93488 | -0.0240 | 5.80633 |
October | 340.00000 | 24.01810 | 53.17862 | 0.68693 | 15.29472 |
November | 330.00000 | 23.97461 | 51.69544 | 0.60657 | 12.89773 |
December | 338.00000 | 23.94772 | 49.90515 | 0.50515 | 10.50880 |
Annual Sum or Average | 4030.00000 | 23.98432 | 52.76212 | 0.28702 | 9.02977 |
Minimum of Months | 308.00000 | 23.90723 | 45.49032 | -0.1666 | 5.65830 |
Maximum of Months | 348.00000 | 24.05169 | 61.51710 | 0.68693 | 15.29472 |
Report: DXReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.183391E+11 | 0.560426E+10 | 468.29 | 0.146271E+11 | 0.371201E+10 | 0.00 | 1.00 | 30-JAN-09:02 | 0.00 | 01-JAN-00:10 | 80652.38 | 30-JAN-09:02 | 53237.36 | 30-JAN-09:02 | 27415.01 | 30-JAN-09:02 | 19073.75 | 30-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.201016E+11 | 0.622094E+10 | 428.88 | 0.156310E+11 | 0.447053E+10 | 0.00 | 1.00 | 06-FEB-09:02 | 0.00 | 01-FEB-00:05 | 81793.02 | 09-FEB-09:02 | 53276.18 | 06-FEB-09:02 | 30068.82 | 09-FEB-09:02 | 19604.95 | 07-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.265839E+11 | 0.845964E+10 | 477.44 | 0.214441E+11 | 0.513978E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 82080.51 | 29-MAR-08:62 | 73125.59 | 28-MAR-08:61 | 33992.05 | 29-MAR-08:62 | 20315.13 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.352982E+11 | 0.115822E+11 | 463.75 | 0.275031E+11 | 0.779518E+10 | 0.00 | 1.00 | 03-APR-08:61 | 0.00 | 01-APR-00:05 | 82626.05 | 30-APR-07:02 | 72878.99 | 27-APR-08:61 | 36826.52 | 30-APR-07:02 | 21020.43 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.502090E+11 | 0.172924E+11 | 496.96 | 0.386396E+11 | 0.115695E+11 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 85326.59 | 30-MAY-08:61 | 71557.66 | 11-MAY-08:61 | 42719.87 | 30-MAY-08:03 | 22780.98 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.600016E+11 | 0.202537E+11 | 488.50 | 0.409743E+11 | 0.190273E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 86897.15 | 08-JUN-08:61 | 68089.22 | 02-JUN-08:61 | 49116.57 | 08-JUN-08:03 | 22547.52 | 05-JUN-08:03 | 0.00 | 01-JUN-00:10 |
July | 0.710717E+11 | 0.240927E+11 | 503.11 | 0.467082E+11 | 0.243636E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 86153.62 | 02-JUL-07:01 | 68682.46 | 04-JUL-07:01 | 50185.60 | 18-JUL-07:01 | 22795.02 | 19-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.747730E+11 | 0.251283E+11 | 504.13 | 0.479709E+11 | 0.268021E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 86132.02 | 08-AUG-07:01 | 62108.83 | 06-AUG-07:01 | 56860.85 | 08-AUG-07:01 | 23044.62 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.643138E+11 | 0.210787E+11 | 487.56 | 0.415023E+11 | 0.228116E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 86673.51 | 23-SEP-08:61 | 61973.31 | 26-SEP-08:61 | 51105.85 | 11-SEP-08:04 | 22506.49 | 30-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.517548E+11 | 0.168817E+11 | 497.74 | 0.370077E+11 | 0.147471E+11 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 86858.03 | 07-OCT-08:61 | 69626.70 | 21-OCT-08:61 | 49879.22 | 08-OCT-07:04 | 21401.52 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.371127E+11 | 0.117426E+11 | 467.27 | 0.275923E+11 | 0.952045E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 84064.13 | 03-NOV-08:61 | 66077.06 | 18-NOV-09:02 | 37483.61 | 03-NOV-08:03 | 20269.34 | 09-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.249507E+11 | 0.764244E+10 | 476.24 | 0.187234E+11 | 0.622728E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-01:05 | 81794.17 | 06-DEC-09:02 | 69342.70 | 01-DEC-09:02 | 32364.50 | 06-DEC-09:02 | 19397.20 | 12-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.534510E+12 | 0.175980E+12 | 5759.88 | 0.378324E+12 | 0.156186E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.183391E+11 | 0.560426E+10 | 428.88 | 0.146271E+11 | 0.371201E+10 | 0.00 | 1.00 | 0.00 | 80652.38 | 53237.36 | 27415.01 | 19073.75 | 0.00 | |||||||
Maximum of Months | 0.747730E+11 | 0.251283E+11 | 504.13 | 0.479709E+11 | 0.268021E+11 | 0.00 | 1.00 | 0.00 | 86897.15 | 73125.59 | 56860.85 | 23044.62 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.976240E+10 | 0.266491E+10 | 472.68 | 0.792062E+10 | 0.184178E+10 | 0.00 | 1.00 | 30-JAN-09:02 | 0.00 | 01-JAN-00:10 | 40013.32 | 30-JAN-09:02 | 29152.17 | 30-JAN-09:02 | 10861.15 | 30-JAN-09:02 | 8531.53 | 30-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.104403E+11 | 0.288804E+10 | 429.80 | 0.828238E+10 | 0.215792E+10 | 0.00 | 1.00 | 06-FEB-09:02 | 0.00 | 01-FEB-00:05 | 40843.94 | 09-FEB-09:02 | 28426.35 | 06-FEB-09:02 | 13274.09 | 09-FEB-09:02 | 8811.56 | 07-FEB-09:02 | 0.00 | 01-FEB-00:05 |
March | 0.134346E+11 | 0.382669E+10 | 478.45 | 0.110222E+11 | 0.241238E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 40815.62 | 29-MAR-08:62 | 36967.35 | 28-MAR-08:61 | 14377.20 | 29-MAR-08:62 | 9149.09 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.171340E+11 | 0.505577E+10 | 464.64 | 0.136670E+11 | 0.346697E+10 | 0.00 | 1.00 | 03-APR-08:61 | 0.00 | 01-APR-00:05 | 41143.19 | 18-APR-08:61 | 36664.99 | 27-APR-08:61 | 14180.31 | 18-APR-08:61 | 9488.29 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.237036E+11 | 0.736961E+10 | 497.98 | 0.186654E+11 | 0.503822E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 41993.05 | 30-MAY-08:61 | 36387.36 | 08-MAY-08:61 | 17980.91 | 30-MAY-08:03 | 10281.75 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.279223E+11 | 0.853712E+10 | 488.86 | 0.196542E+11 | 0.826814E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 43024.93 | 08-JUN-08:61 | 35844.99 | 02-JUN-08:61 | 21384.24 | 08-JUN-08:03 | 10178.65 | 05-JUN-08:61 | 0.00 | 01-JUN-00:10 |
July | 0.329193E+11 | 0.101036E+11 | 502.97 | 0.221757E+11 | 0.107436E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 43273.62 | 26-JUL-08:61 | 35618.79 | 04-JUL-07:01 | 22864.06 | 26-JUL-08:04 | 10304.36 | 19-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.346657E+11 | 0.105452E+11 | 503.79 | 0.227444E+11 | 0.119212E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 43453.76 | 08-AUG-07:01 | 33195.84 | 06-AUG-07:01 | 25421.49 | 08-AUG-08:04 | 10379.30 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.297264E+11 | 0.882816E+10 | 487.49 | 0.197861E+11 | 0.994030E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 43393.41 | 11-SEP-08:61 | 33518.60 | 26-SEP-08:61 | 22891.92 | 08-SEP-08:04 | 10121.79 | 30-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.242603E+11 | 0.714769E+10 | 497.81 | 0.178244E+11 | 0.643587E+10 | 0.00 | 1.00 | 01-OCT-07:01 | 0.00 | 01-OCT-00:10 | 42850.37 | 07-OCT-08:61 | 35995.29 | 21-OCT-08:61 | 20688.06 | 07-OCT-08:03 | 9680.11 | 06-OCT-08:03 | 0.00 | 01-OCT-00:10 |
November | 0.179695E+11 | 0.510540E+10 | 467.54 | 0.135952E+11 | 0.437427E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 41636.41 | 01-NOV-08:61 | 34692.62 | 18-NOV-09:02 | 16134.16 | 01-NOV-08:03 | 9109.53 | 09-NOV-09:01 | 0.00 | 01-NOV-00:10 |
December | 0.126837E+11 | 0.347742E+10 | 477.22 | 0.973508E+10 | 0.294860E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-01:05 | 40624.72 | 06-DEC-09:02 | 35698.86 | 01-DEC-09:02 | 13452.08 | 06-DEC-09:02 | 8711.44 | 12-DEC-09:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.254622E+12 | 0.755496E+11 | 5769.23 | 0.185073E+12 | 0.695493E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.976240E+10 | 0.266491E+10 | 429.80 | 0.792062E+10 | 0.184178E+10 | 0.00 | 1.00 | 0.00 | 40013.32 | 28426.35 | 10861.15 | 8531.53 | 0.00 | |||||||
Maximum of Months | 0.346657E+11 | 0.105452E+11 | 503.79 | 0.227444E+11 | 0.119212E+11 | 0.00 | 1.00 | 0.00 | 43453.76 | 36967.35 | 25421.49 | 10379.30 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.704760E+10 | 0.192806E+10 | 330.04 | 0.568195E+10 | 0.136566E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 40217.75 | 29-JAN-09:02 | 28696.64 | 29-JAN-09:02 | 12683.59 | 30-JAN-08:62 | 8652.34 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.789557E+10 | 0.219206E+10 | 304.66 | 0.623232E+10 | 0.166325E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 41414.46 | 09-FEB-08:62 | 26946.72 | 06-FEB-08:62 | 15996.98 | 09-FEB-08:62 | 8670.72 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.106133E+11 | 0.303833E+10 | 346.77 | 0.871164E+10 | 0.190170E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:05 | 41544.24 | 29-MAR-07:02 | 37212.99 | 28-MAR-07:01 | 17843.62 | 29-MAR-07:02 | 8917.45 | 01-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.137718E+11 | 0.407508E+10 | 330.41 | 0.109997E+11 | 0.277206E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 42498.20 | 30-APR-08:61 | 37021.32 | 26-APR-07:01 | 20072.37 | 30-APR-08:03 | 8897.04 | 03-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.197941E+11 | 0.612454E+10 | 372.11 | 0.155181E+11 | 0.427599E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 43141.93 | 30-MAY-07:01 | 36416.94 | 10-MAY-07:01 | 23017.20 | 01-MAY-07:03 | 9808.46 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.236430E+11 | 0.717494E+10 | 367.47 | 0.164932E+11 | 0.714983E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 43805.60 | 08-JUN-07:01 | 31079.79 | 02-JUN-07:01 | 25401.86 | 25-JUN-08:04 | 9999.75 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.279371E+11 | 0.844525E+10 | 374.90 | 0.184024E+11 | 0.953464E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 43397.93 | 02-JUL-07:01 | 34781.84 | 04-JUL-08:61 | 28153.48 | 31-JUL-06:03 | 10151.62 | 23-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.299669E+11 | 0.897850E+10 | 383.92 | 0.192276E+11 | 0.107394E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 43397.93 | 21-AUG-06:03 | 29153.43 | 06-AUG-08:61 | 26934.41 | 21-AUG-06:03 | 10222.24 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.249626E+11 | 0.733372E+10 | 362.14 | 0.163796E+11 | 0.858294E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 43697.20 | 28-SEP-07:01 | 28275.06 | 26-SEP-07:01 | 27098.28 | 11-SEP-07:04 | 9910.99 | 04-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.201436E+11 | 0.587851E+10 | 367.83 | 0.145542E+11 | 0.558937E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 43768.10 | 07-OCT-07:01 | 33691.75 | 20-OCT-07:01 | 26222.92 | 08-OCT-08:04 | 9241.40 | 08-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.147202E+11 | 0.416619E+10 | 335.11 | 0.109380E+11 | 0.378225E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 42557.16 | 03-NOV-07:01 | 33462.52 | 19-NOV-09:01 | 19864.49 | 03-NOV-07:03 | 8958.31 | 20-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.965460E+10 | 0.265192E+10 | 334.80 | 0.732743E+10 | 0.232717E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 40755.66 | 11-DEC-08:62 | 30164.90 | 27-DEC-08:62 | 15936.62 | 05-DEC-08:62 | 8713.68 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.210150E+12 | 0.619871E+11 | 4210.15 | 0.150466E+12 | 0.596842E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.704760E+10 | 0.192806E+10 | 304.66 | 0.568195E+10 | 0.136566E+10 | 0.00 | 1.00 | 0.00 | 40217.75 | 26946.72 | 12683.59 | 8652.34 | 0.00 | |||||||
Maximum of Months | 0.299669E+11 | 0.897850E+10 | 383.92 | 0.192276E+11 | 0.107394E+11 | 0.00 | 1.00 | 0.00 | 43805.60 | 37212.99 | 28153.48 | 10222.24 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.699148E+10 | 0.191350E+10 | 329.70 | 0.563416E+10 | 0.135732E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 40275.37 | 29-JAN-09:02 | 28733.37 | 29-JAN-09:02 | 12660.04 | 30-JAN-08:62 | 8665.03 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.786392E+10 | 0.218402E+10 | 304.32 | 0.620661E+10 | 0.165731E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 41478.89 | 09-FEB-08:62 | 27025.00 | 06-FEB-08:62 | 16009.42 | 09-FEB-08:62 | 8683.91 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.106074E+11 | 0.303719E+10 | 347.11 | 0.870723E+10 | 0.190013E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:05 | 41612.30 | 29-MAR-07:02 | 37270.44 | 28-MAR-07:01 | 17835.19 | 29-MAR-07:02 | 8930.67 | 01-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.138135E+11 | 0.408703E+10 | 330.73 | 0.110370E+11 | 0.277650E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 42573.35 | 30-APR-08:61 | 37128.33 | 26-APR-07:01 | 20028.32 | 30-APR-08:03 | 8909.61 | 03-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.199224E+11 | 0.616133E+10 | 372.18 | 0.156302E+11 | 0.429222E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 43138.49 | 30-MAY-07:01 | 36481.33 | 10-MAY-07:01 | 22960.79 | 01-MAY-07:03 | 9822.89 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.237965E+11 | 0.721837E+10 | 367.87 | 0.166199E+11 | 0.717666E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 43853.91 | 08-JUN-07:01 | 31166.87 | 02-JUN-07:01 | 25230.30 | 25-JUN-08:04 | 10017.35 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.281348E+11 | 0.850089E+10 | 374.89 | 0.185666E+11 | 0.956823E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 43463.09 | 02-JUL-07:01 | 34849.87 | 04-JUL-08:61 | 27892.24 | 31-JUL-06:03 | 10167.25 | 23-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.301582E+11 | 0.903208E+10 | 384.48 | 0.193852E+11 | 0.107730E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 43463.09 | 21-AUG-06:03 | 29285.45 | 06-AUG-08:61 | 26689.63 | 21-AUG-06:03 | 10236.15 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.251299E+11 | 0.737969E+10 | 362.53 | 0.165155E+11 | 0.861439E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 43762.80 | 28-SEP-07:01 | 28384.57 | 26-SEP-07:01 | 29373.98 | 11-SEP-06:03 | 9924.56 | 04-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.202843E+11 | 0.591684E+10 | 369.17 | 0.146702E+11 | 0.561415E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 43802.31 | 07-OCT-07:01 | 33763.45 | 20-OCT-07:01 | 26071.19 | 08-OCT-08:04 | 9255.28 | 08-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.147731E+11 | 0.418075E+10 | 335.83 | 0.109837E+11 | 0.378941E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 42601.95 | 03-NOV-07:01 | 33527.81 | 19-NOV-09:01 | 19816.93 | 03-NOV-07:03 | 8970.98 | 20-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.963785E+10 | 0.264785E+10 | 334.76 | 0.731434E+10 | 0.232350E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 40822.24 | 11-DEC-08:62 | 30204.90 | 27-DEC-08:62 | 16010.02 | 05-DEC-08:62 | 8727.08 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.211113E+12 | 0.622595E+11 | 4213.58 | 0.151271E+12 | 0.598428E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.699148E+10 | 0.191350E+10 | 304.32 | 0.563416E+10 | 0.135732E+10 | 0.00 | 1.00 | 0.00 | 40275.37 | 27025.00 | 12660.04 | 8665.03 | 0.00 | |||||||
Maximum of Months | 0.301582E+11 | 0.903208E+10 | 384.48 | 0.193852E+11 | 0.107730E+11 | 0.00 | 1.00 | 0.00 | 43853.91 | 37270.44 | 29373.98 | 10236.15 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.672629E+10 | 0.184359E+10 | 327.26 | 0.540638E+10 | 0.131991E+10 | 0.00 | 1.00 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 | 40124.74 | 29-JAN-09:02 | 28505.19 | 29-JAN-09:02 | 11955.25 | 30-JAN-08:62 | 8635.03 | 29-JAN-09:02 | 0.00 | 01-JAN-00:10 |
February | 0.763275E+10 | 0.212306E+10 | 302.93 | 0.601263E+10 | 0.162013E+10 | 0.00 | 1.00 | 06-FEB-08:62 | 0.00 | 01-FEB-00:05 | 41326.92 | 09-FEB-08:62 | 26819.01 | 06-FEB-08:62 | 16083.46 | 09-FEB-08:62 | 8654.75 | 09-FEB-08:62 | 0.00 | 01-FEB-00:05 |
March | 0.103611E+11 | 0.297128E+10 | 346.34 | 0.849291E+10 | 0.186819E+10 | 0.00 | 1.00 | 01-MAR-08:61 | 0.00 | 01-MAR-00:05 | 41462.34 | 29-MAR-07:02 | 37148.24 | 28-MAR-07:01 | 17912.45 | 29-MAR-07:02 | 8900.72 | 01-MAR-08:61 | 0.00 | 01-MAR-00:05 |
April | 0.136008E+11 | 0.402864E+10 | 329.65 | 0.108523E+11 | 0.274849E+10 | 0.00 | 1.00 | 02-APR-08:62 | 0.00 | 01-APR-00:05 | 42426.82 | 30-APR-08:61 | 36880.02 | 26-APR-07:01 | 20052.52 | 30-APR-08:03 | 8882.40 | 03-APR-07:01 | 0.00 | 01-APR-00:05 |
May | 0.197415E+11 | 0.610813E+10 | 371.35 | 0.154692E+11 | 0.427232E+10 | 0.00 | 1.00 | 01-MAY-07:02 | 0.00 | 01-MAY-00:10 | 43017.77 | 30-MAY-07:01 | 36354.92 | 10-MAY-07:01 | 22965.94 | 01-MAY-07:03 | 9791.99 | 28-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.236142E+11 | 0.716497E+10 | 367.35 | 0.164666E+11 | 0.714759E+10 | 0.00 | 1.00 | 01-JUN-07:01 | 0.00 | 01-JUN-00:10 | 43731.87 | 08-JUN-07:01 | 31011.50 | 02-JUN-07:01 | 25298.54 | 25-JUN-08:04 | 9984.65 | 05-JUN-07:03 | 0.00 | 01-JUN-00:10 |
July | 0.279840E+11 | 0.845521E+10 | 374.86 | 0.184401E+11 | 0.954391E+10 | 0.00 | 1.00 | 01-JUL-07:01 | 0.00 | 01-JUL-00:03 | 43324.89 | 02-JUL-07:01 | 34721.66 | 04-JUL-08:61 | 27877.14 | 31-JUL-06:03 | 10134.80 | 23-JUL-08:03 | 0.00 | 01-JUL-00:03 |
August | 0.299978E+11 | 0.898374E+10 | 383.89 | 0.192520E+11 | 0.107458E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 43324.89 | 21-AUG-06:03 | 29165.90 | 06-AUG-08:61 | 26658.68 | 21-AUG-06:03 | 10204.02 | 06-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.249618E+11 | 0.733156E+10 | 362.12 | 0.163788E+11 | 0.858300E+10 | 0.00 | 1.00 | 01-SEP-07:01 | 0.00 | 01-SEP-00:03 | 43631.40 | 23-SEP-07:01 | 28222.62 | 26-SEP-07:01 | 29357.11 | 11-SEP-06:03 | 9893.15 | 04-SEP-08:61 | 0.00 | 01-SEP-00:03 |
October | 0.201039E+11 | 0.586642E+10 | 367.52 | 0.145182E+11 | 0.558576E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 43713.26 | 07-OCT-07:01 | 33617.40 | 20-OCT-07:01 | 26111.30 | 08-OCT-08:04 | 9225.85 | 08-OCT-08:61 | 0.00 | 01-OCT-00:10 |
November | 0.145725E+11 | 0.412719E+10 | 334.20 | 0.108146E+11 | 0.375792E+10 | 0.00 | 1.00 | 01-NOV-07:01 | 0.00 | 01-NOV-00:10 | 42505.03 | 03-NOV-07:01 | 33387.23 | 19-NOV-09:01 | 19910.92 | 03-NOV-07:03 | 8943.52 | 20-NOV-08:61 | 0.00 | 01-NOV-00:10 |
December | 0.939291E+10 | 0.258403E+10 | 334.51 | 0.711047E+10 | 0.228245E+10 | 0.00 | 1.00 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 | 40671.91 | 11-DEC-08:62 | 29968.96 | 27-DEC-08:62 | 15142.38 | 05-DEC-08:62 | 8697.37 | 10-DEC-09:02 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.208690E+12 | 0.615878E+11 | 4201.97 | 0.149214E+12 | 0.594755E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.672629E+10 | 0.184359E+10 | 302.93 | 0.540638E+10 | 0.131991E+10 | 0.00 | 1.00 | 0.00 | 40124.74 | 26819.01 | 11955.25 | 8635.03 | 0.00 | |||||||
Maximum of Months | 0.299978E+11 | 0.898374E+10 | 383.89 | 0.192520E+11 | 0.107458E+11 | 0.00 | 1.00 | 0.00 | 43731.87 | 37148.24 | 29357.11 | 10204.02 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.115744E+11 | 0.323243E+10 | 320.21 | 0.908249E+10 | 0.249186E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 74114.46 | 30-JAN-09:02 | 51660.27 | 29-JAN-10:02 | 28211.65 | 30-JAN-09:02 | 16211.51 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.133422E+11 | 0.377908E+10 | 295.84 | 0.102829E+11 | 0.305935E+10 | 0.00 | 1.00 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 | 74495.16 | 09-FEB-09:02 | 59052.93 | 05-FEB-10:01 | 28046.57 | 09-FEB-09:02 | 16606.03 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 |
March | 0.184962E+11 | 0.540006E+10 | 339.23 | 0.148644E+11 | 0.363183E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 74883.68 | 29-MAR-08:62 | 66672.43 | 28-MAR-08:61 | 31873.39 | 29-MAR-08:62 | 16858.29 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.244938E+11 | 0.737467E+10 | 323.01 | 0.192352E+11 | 0.525860E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 76854.14 | 30-APR-09:01 | 66194.66 | 26-APR-08:61 | 35451.20 | 30-APR-09:03 | 17467.45 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.361361E+11 | 0.113482E+11 | 360.93 | 0.279377E+11 | 0.819844E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 78219.43 | 01-MAY-08:62 | 65256.55 | 11-MAY-08:61 | 42579.97 | 01-MAY-08:03 | 18928.13 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.434042E+11 | 0.133427E+11 | 358.33 | 0.298638E+11 | 0.135404E+11 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 79230.46 | 08-JUN-08:61 | 61236.13 | 02-JUN-08:61 | 47198.12 | 19-JUN-07:01 | 18912.37 | 11-JUN-09:04 | 0.00 | 01-JUN-00:10 |
July | 0.512637E+11 | 0.156736E+11 | 361.63 | 0.333879E+11 | 0.178758E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 78472.25 | 18-JUL-07:01 | 61145.68 | 04-JUL-09:01 | 49937.36 | 05-JUL-07:01 | 19534.07 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.553577E+11 | 0.167694E+11 | 373.52 | 0.350606E+11 | 0.202971E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 78532.84 | 08-AUG-07:01 | 52980.51 | 06-AUG-08:61 | 48895.79 | 21-AUG-07:03 | 19145.57 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.458507E+11 | 0.136298E+11 | 350.85 | 0.296055E+11 | 0.162451E+11 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 79230.46 | 25-SEP-08:61 | 55762.59 | 26-SEP-08:61 | 53499.27 | 11-SEP-07:03 | 18848.48 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.365827E+11 | 0.108478E+11 | 355.35 | 0.261509E+11 | 0.104318E+11 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 79194.79 | 07-OCT-08:61 | 61627.43 | 21-OCT-08:61 | 48343.77 | 08-OCT-08:61 | 17775.83 | 22-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.262395E+11 | 0.755368E+10 | 328.23 | 0.191247E+11 | 0.711485E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 76866.82 | 03-NOV-08:61 | 62634.94 | 19-NOV-10:01 | 35122.00 | 03-NOV-08:03 | 16916.55 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.164711E+11 | 0.461096E+10 | 324.58 | 0.121922E+11 | 0.427897E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 75050.24 | 04-DEC-09:02 | 60463.82 | 01-DEC-09:02 | 31317.11 | 04-DEC-09:02 | 16710.16 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.379212E+12 | 0.113562E+12 | 4091.71 | 0.266788E+12 | 0.112424E+12 | 0.00 | ||||||||||||||
Minimum of Months | 0.115744E+11 | 0.323243E+10 | 295.84 | 0.908249E+10 | 0.249186E+10 | 0.00 | 1.00 | 0.00 | 74114.46 | 51660.27 | 28046.57 | 16211.51 | 0.00 | |||||||
Maximum of Months | 0.553577E+11 | 0.167694E+11 | 373.52 | 0.350606E+11 | 0.202971E+11 | 0.00 | 1.00 | 0.00 | 79230.46 | 66672.43 | 53499.27 | 19534.07 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.600155E+10 | 0.164831E+10 | 320.60 | 0.471422E+10 | 0.128733E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 39159.05 | 30-JAN-09:02 | 27229.06 | 29-JAN-10:02 | 14885.34 | 30-JAN-09:02 | 8413.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.692608E+10 | 0.192991E+10 | 295.96 | 0.534391E+10 | 0.158217E+10 | 0.00 | 1.00 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 | 39345.96 | 09-FEB-09:02 | 31090.99 | 05-FEB-10:01 | 14822.14 | 09-FEB-09:02 | 8615.28 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 |
March | 0.961031E+10 | 0.276101E+10 | 339.18 | 0.773038E+10 | 0.187993E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 39549.68 | 29-MAR-08:62 | 35216.30 | 28-MAR-08:61 | 16760.00 | 29-MAR-08:62 | 8747.86 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.127594E+11 | 0.378100E+10 | 322.67 | 0.100220E+11 | 0.273741E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 40622.38 | 30-APR-09:01 | 34961.08 | 26-APR-08:61 | 18812.86 | 30-APR-09:03 | 9065.39 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.188325E+11 | 0.582398E+10 | 360.66 | 0.145561E+11 | 0.427640E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 41346.92 | 01-MAY-08:62 | 34448.84 | 11-MAY-08:61 | 22514.19 | 01-MAY-08:03 | 9818.05 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.225969E+11 | 0.684481E+10 | 357.86 | 0.155463E+11 | 0.705061E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41854.06 | 08-JUN-08:61 | 32253.49 | 02-JUN-08:61 | 25099.70 | 19-JUN-07:01 | 9812.14 | 11-JUN-09:03 | 0.00 | 01-JUN-00:10 |
July | 0.266975E+11 | 0.804644E+10 | 360.81 | 0.173863E+11 | 0.931118E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 41453.52 | 18-JUL-07:01 | 32275.88 | 04-JUL-09:01 | 26605.75 | 05-JUL-07:01 | 10136.70 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.288089E+11 | 0.860477E+10 | 373.11 | 0.182421E+11 | 0.105668E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 41485.53 | 08-AUG-07:01 | 27781.11 | 06-AUG-08:61 | 25848.39 | 21-AUG-07:01 | 9935.40 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.238738E+11 | 0.699464E+10 | 350.95 | 0.154203E+11 | 0.845343E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 41854.06 | 25-SEP-08:61 | 29432.12 | 26-SEP-08:61 | 28483.30 | 11-SEP-07:01 | 9781.58 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.190579E+11 | 0.556584E+10 | 354.35 | 0.136348E+11 | 0.542317E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 41835.21 | 07-OCT-08:61 | 32496.52 | 21-OCT-08:61 | 23885.32 | 08-OCT-09:04 | 9225.52 | 22-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.136717E+11 | 0.387343E+10 | 327.47 | 0.997234E+10 | 0.369931E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 40599.11 | 03-NOV-08:61 | 33048.28 | 19-NOV-10:01 | 18533.11 | 03-NOV-08:03 | 8779.99 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.856574E+10 | 0.235873E+10 | 324.97 | 0.634655E+10 | 0.221919E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 39660.98 | 04-DEC-09:02 | 31929.37 | 01-DEC-09:02 | 16548.68 | 04-DEC-09:02 | 8672.85 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.197402E+12 | 0.582329E+11 | 4088.59 | 0.138915E+12 | 0.584869E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.600155E+10 | 0.164831E+10 | 295.96 | 0.471422E+10 | 0.128733E+10 | 0.00 | 1.00 | 0.00 | 39159.05 | 27229.06 | 14822.14 | 8413.00 | 0.00 | |||||||
Maximum of Months | 0.288089E+11 | 0.860477E+10 | 373.11 | 0.182421E+11 | 0.105668E+11 | 0.00 | 1.00 | 0.00 | 41854.06 | 35216.30 | 28483.30 | 10136.70 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.592725E+10 | 0.162846E+10 | 320.18 | 0.465210E+10 | 0.127515E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 39022.36 | 30-JAN-09:02 | 27100.85 | 29-JAN-10:02 | 14865.35 | 30-JAN-09:02 | 8384.12 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.685561E+10 | 0.191097E+10 | 295.29 | 0.528633E+10 | 0.156928E+10 | 0.00 | 1.00 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 | 39208.77 | 09-FEB-09:02 | 30949.83 | 05-FEB-10:01 | 14803.88 | 09-FEB-09:02 | 8585.51 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 |
March | 0.953452E+10 | 0.274011E+10 | 339.15 | 0.766604E+10 | 0.186847E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 39414.13 | 29-MAR-08:62 | 35095.05 | 28-MAR-08:61 | 16740.88 | 29-MAR-08:62 | 8718.13 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.126915E+11 | 0.376131E+10 | 322.73 | 0.996457E+10 | 0.272691E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 40490.80 | 30-APR-09:01 | 34842.95 | 26-APR-08:61 | 18770.86 | 30-APR-09:03 | 9035.25 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.187685E+11 | 0.580336E+10 | 360.66 | 0.145015E+11 | 0.426703E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 41204.74 | 01-MAY-08:62 | 34334.84 | 11-MAY-08:61 | 22459.13 | 01-MAY-08:03 | 9785.51 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.225332E+11 | 0.682370E+10 | 357.84 | 0.154947E+11 | 0.703853E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41713.27 | 08-JUN-08:61 | 32142.73 | 02-JUN-08:61 | 25023.05 | 19-JUN-07:01 | 9779.02 | 11-JUN-09:03 | 0.00 | 01-JUN-00:10 |
July | 0.266376E+11 | 0.802543E+10 | 361.02 | 0.173386E+11 | 0.929892E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 41314.09 | 18-JUL-07:01 | 32167.54 | 04-JUL-09:01 | 26524.03 | 05-JUL-07:01 | 10102.81 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.287485E+11 | 0.858319E+10 | 373.13 | 0.181942E+11 | 0.105543E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 41345.99 | 08-AUG-07:01 | 27688.47 | 06-AUG-08:61 | 25761.06 | 21-AUG-07:01 | 9902.17 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.238181E+11 | 0.697594E+10 | 350.53 | 0.153759E+11 | 0.844223E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 41713.27 | 25-SEP-08:61 | 29317.75 | 26-SEP-08:61 | 28395.74 | 11-SEP-07:01 | 9748.69 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.190013E+11 | 0.554820E+10 | 354.27 | 0.135879E+11 | 0.541338E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 41694.50 | 07-OCT-08:61 | 32365.15 | 21-OCT-08:61 | 23822.96 | 08-OCT-09:04 | 9194.63 | 22-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.136112E+11 | 0.385640E+10 | 327.66 | 0.992266E+10 | 0.368858E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 40469.51 | 03-NOV-08:61 | 32935.57 | 19-NOV-10:01 | 18499.10 | 03-NOV-08:03 | 8750.81 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.849597E+10 | 0.234006E+10 | 324.72 | 0.629012E+10 | 0.220585E+10 | 0.00 | 1.00 | 01-DEC-09:02 | 0.00 | 01-DEC-00:10 | 39523.82 | 04-DEC-09:02 | 31791.04 | 01-DEC-09:02 | 16518.60 | 04-DEC-09:02 | 8643.78 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.196623E+12 | 0.579971E+11 | 4087.19 | 0.138275E+12 | 0.583486E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.592725E+10 | 0.162846E+10 | 295.29 | 0.465210E+10 | 0.127515E+10 | 0.00 | 1.00 | 0.00 | 39022.36 | 27100.85 | 14803.88 | 8384.12 | 0.00 | |||||||
Maximum of Months | 0.287485E+11 | 0.858319E+10 | 373.13 | 0.181942E+11 | 0.105543E+11 | 0.00 | 1.00 | 0.00 | 41713.27 | 35095.05 | 28395.74 | 10102.81 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.578977E+10 | 0.159233E+10 | 318.32 | 0.453726E+10 | 0.125251E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 39168.40 | 30-JAN-09:02 | 27133.62 | 29-JAN-10:02 | 14988.66 | 30-JAN-09:02 | 8417.01 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.672910E+10 | 0.187808E+10 | 294.82 | 0.518364E+10 | 0.154546E+10 | 0.00 | 1.00 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 | 39358.53 | 09-FEB-09:02 | 30981.79 | 05-FEB-10:01 | 14927.33 | 09-FEB-09:02 | 8618.30 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 |
March | 0.942044E+10 | 0.271061E+10 | 338.65 | 0.756932E+10 | 0.185112E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 39565.00 | 29-MAR-08:62 | 35230.64 | 28-MAR-08:61 | 16865.05 | 29-MAR-08:62 | 8753.11 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.126368E+11 | 0.374825E+10 | 322.39 | 0.991898E+10 | 0.271780E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 40662.58 | 30-APR-09:01 | 34981.77 | 26-APR-08:61 | 18874.24 | 30-APR-09:03 | 9072.72 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.188173E+11 | 0.582019E+10 | 360.00 | 0.145436E+11 | 0.427362E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 41366.86 | 01-MAY-08:62 | 34474.17 | 11-MAY-08:61 | 22585.13 | 01-MAY-08:03 | 9825.25 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.226292E+11 | 0.685420E+10 | 357.69 | 0.155733E+11 | 0.705588E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 41884.68 | 08-JUN-08:61 | 32270.47 | 02-JUN-08:61 | 25117.38 | 19-JUN-07:01 | 9819.48 | 11-JUN-09:03 | 0.00 | 01-JUN-00:10 |
July | 0.267997E+11 | 0.807492E+10 | 360.95 | 0.174702E+11 | 0.932950E+10 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 41483.86 | 18-JUL-07:01 | 32302.68 | 04-JUL-09:01 | 26571.57 | 05-JUL-07:01 | 10143.57 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.289529E+11 | 0.864401E+10 | 373.43 | 0.183586E+11 | 0.105943E+11 | 0.00 | 1.00 | 01-AUG-08:61 | 0.00 | 01-AUG-00:10 | 41515.89 | 08-AUG-07:01 | 27937.62 | 06-AUG-08:61 | 25934.54 | 21-AUG-07:03 | 9942.28 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.239613E+11 | 0.701836E+10 | 350.74 | 0.154910E+11 | 0.847038E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 41884.68 | 25-SEP-08:61 | 29456.58 | 26-SEP-08:61 | 28425.53 | 11-SEP-07:01 | 9787.98 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.190958E+11 | 0.557623E+10 | 354.43 | 0.136666E+11 | 0.542915E+10 | 0.00 | 1.00 | 01-OCT-09:01 | 0.00 | 01-OCT-00:10 | 41865.83 | 07-OCT-08:61 | 32494.64 | 21-OCT-08:61 | 23902.07 | 08-OCT-09:04 | 9232.35 | 22-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.136243E+11 | 0.386144E+10 | 327.26 | 0.993374E+10 | 0.369058E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 40632.28 | 03-NOV-08:61 | 33064.17 | 19-NOV-10:01 | 18563.09 | 03-NOV-08:03 | 8786.84 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.840583E+10 | 0.231720E+10 | 324.62 | 0.621754E+10 | 0.218829E+10 | 0.00 | 1.00 | 03-DEC-10:02 | 0.00 | 01-DEC-00:10 | 39674.46 | 04-DEC-09:02 | 31837.59 | 01-DEC-09:02 | 16637.84 | 04-DEC-09:02 | 8679.31 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.196862E+12 | 0.580958E+11 | 4083.30 | 0.138464E+12 | 0.583986E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.578977E+10 | 0.159233E+10 | 294.82 | 0.453726E+10 | 0.125251E+10 | 0.00 | 1.00 | 0.00 | 39168.40 | 27133.62 | 14927.33 | 8417.01 | 0.00 | |||||||
Maximum of Months | 0.289529E+11 | 0.864401E+10 | 373.43 | 0.183586E+11 | 0.105943E+11 | 0.00 | 1.00 | 0.00 | 41884.68 | 35230.64 | 28425.53 | 10143.57 | 0.00 |
Report: DXReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportCOOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL ELECTRICITY ENERGY [J] | COOLING COIL TOTAL COOLING ENERGY {HOURS NON-ZERO} [HOURS] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL LATENT COOLING ENERGY [J] | COOLING COIL CRANKCASE HEATER ELECTRICITY ENERGY [J] | COOLING COIL RUNTIME FRACTION {Maximum} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL RUNTIME FRACTION {MINIMUM} [] | COOLING COIL RUNTIME FRACTION {TIMESTAMP} | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {Maximum} [W] | COOLING COIL SENSIBLE COOLING RATE {TIMESTAMP} | COOLING COIL LATENT COOLING RATE {Maximum} [W] | COOLING COIL LATENT COOLING RATE {TIMESTAMP} | COOLING COIL ELECTRICITY RATE {Maximum} [W] | COOLING COIL ELECTRICITY RATE {TIMESTAMP} | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {Maximum} [W] | COOLING COIL CRANKCASE HEATER ELECTRICITY RATE {TIMESTAMP} | |
January | 0.627038E+10 | 0.175926E+10 | 317.55 | 0.498949E+10 | 0.128089E+10 | 0.00 | 1.00 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 | 43977.21 | 29-JAN-10:02 | 30832.81 | 29-JAN-10:02 | 14784.04 | 30-JAN-09:02 | 9745.79 | 29-JAN-10:02 | 0.00 | 01-JAN-00:10 |
February | 0.721855E+10 | 0.205812E+10 | 294.04 | 0.564092E+10 | 0.157763E+10 | 0.00 | 1.00 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 | 44798.57 | 07-FEB-09:02 | 35743.62 | 05-FEB-10:01 | 17053.09 | 09-FEB-09:02 | 9953.48 | 05-FEB-10:01 | 0.00 | 01-FEB-00:05 |
March | 0.101393E+11 | 0.298355E+10 | 338.34 | 0.825294E+10 | 0.188637E+10 | 0.00 | 1.00 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 | 44243.24 | 01-MAR-09:01 | 40087.37 | 28-MAR-08:61 | 19284.80 | 29-MAR-08:62 | 10125.61 | 01-MAR-09:01 | 0.00 | 01-MAR-00:05 |
April | 0.138330E+11 | 0.419794E+10 | 322.69 | 0.109953E+11 | 0.283769E+10 | 0.00 | 1.00 | 02-APR-09:01 | 0.00 | 01-APR-00:05 | 46532.03 | 30-APR-09:01 | 39900.56 | 27-APR-08:61 | 22591.21 | 30-APR-09:03 | 10487.11 | 28-APR-08:61 | 0.00 | 01-APR-00:05 |
May | 0.209690E+11 | 0.663777E+10 | 362.06 | 0.164250E+11 | 0.454406E+10 | 0.00 | 1.00 | 01-MAY-08:62 | 0.00 | 01-MAY-00:10 | 46943.49 | 01-MAY-08:62 | 39163.86 | 11-MAY-08:61 | 25053.45 | 01-MAY-08:62 | 11352.88 | 10-MAY-08:61 | 0.00 | 01-MAY-00:10 |
June | 0.252973E+11 | 0.785243E+10 | 360.01 | 0.177024E+11 | 0.759487E+10 | 0.00 | 1.00 | 01-JUN-08:61 | 0.00 | 01-JUN-00:10 | 47538.31 | 08-JUN-08:61 | 36595.58 | 02-JUN-08:61 | 28836.68 | 19-JUN-07:01 | 11346.61 | 11-JUN-09:03 | 0.00 | 01-JUN-00:10 |
July | 0.300562E+11 | 0.929253E+10 | 363.66 | 0.199689E+11 | 0.100874E+11 | 0.00 | 1.00 | 01-JUL-08:61 | 0.00 | 01-JUL-00:03 | 47119.74 | 26-JUL-07:01 | 36988.46 | 04-JUL-09:01 | 32172.94 | 05-JUL-07:03 | 11733.09 | 30-JUL-09:01 | 0.00 | 01-JUL-00:03 |
August | 0.326831E+11 | 0.100086E+11 | 376.07 | 0.211980E+11 | 0.114851E+11 | 0.00 | 1.00 | 01-AUG-07:01 | 0.00 | 01-AUG-00:10 | 47119.74 | 08-AUG-07:03 | 33087.66 | 06-AUG-08:61 | 32881.02 | 08-AUG-07:01 | 11487.49 | 05-AUG-08:61 | 0.00 | 01-AUG-00:10 |
September | 0.269758E+11 | 0.809768E+10 | 353.80 | 0.178304E+11 | 0.914538E+10 | 0.00 | 1.00 | 01-SEP-08:61 | 0.00 | 01-SEP-00:03 | 47538.31 | 25-SEP-08:61 | 33495.07 | 26-SEP-08:61 | 32805.56 | 11-SEP-07:03 | 11297.55 | 04-SEP-09:01 | 0.00 | 01-SEP-00:03 |
October | 0.215317E+11 | 0.642657E+10 | 358.10 | 0.156693E+11 | 0.586238E+10 | 0.00 | 1.00 | 01-OCT-08:61 | 0.00 | 01-OCT-00:10 | 47516.92 | 07-OCT-08:61 | 37715.12 | 21-OCT-08:61 | 31219.94 | 08-OCT-08:61 | 10669.20 | 22-OCT-09:01 | 0.00 | 01-OCT-00:10 |
November | 0.152084E+11 | 0.440351E+10 | 330.10 | 0.112863E+11 | 0.392208E+10 | 0.00 | 1.00 | 01-NOV-08:61 | 0.00 | 01-NOV-00:10 | 46480.97 | 03-NOV-08:61 | 37152.01 | 19-NOV-10:01 | 22156.06 | 03-NOV-08:03 | 10162.72 | 11-NOV-10:01 | 0.00 | 01-NOV-00:10 |
December | 0.917037E+10 | 0.258144E+10 | 325.34 | 0.689960E+10 | 0.227076E+10 | 0.00 | 1.00 | 03-DEC-10:02 | 0.00 | 01-DEC-00:10 | 44970.68 | 04-DEC-09:02 | 33362.69 | 01-DEC-09:02 | 18066.04 | 04-DEC-09:02 | 10027.61 | 10-DEC-10:01 | 0.00 | 01-DEC-00:10 |
Annual Sum or Average | 0.219353E+12 | 0.662995E+11 | 4101.75 | 0.156859E+12 | 0.624945E+11 | 0.00 | ||||||||||||||
Minimum of Months | 0.627038E+10 | 0.175926E+10 | 294.04 | 0.498949E+10 | 0.128089E+10 | 0.00 | 1.00 | 0.00 | 43977.21 | 30832.81 | 14784.04 | 9745.79 | 0.00 | |||||||
Maximum of Months | 0.326831E+11 | 0.100086E+11 | 376.07 | 0.211980E+11 | 0.114851E+11 | 0.00 | 1.00 | 0.00 | 47538.31 | 40087.37 | 32881.02 | 11733.09 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.87 | 35.78 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.18 | 30.08 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.77 | 23.04 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.01 | 13.94 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 86.89 | 3.52 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.30 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.29 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 116.94 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.69 | 1.73 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.62 | 6.28 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.97 | 16.34 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.47 | 29.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.97 | 13.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.01 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.62 | 35.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.87 | 35.78 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.18 | 30.08 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.77 | 23.04 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.01 | 13.94 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 86.89 | 3.52 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.30 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.29 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 116.94 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.69 | 1.73 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.62 | 6.28 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.97 | 16.34 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.47 | 29.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.97 | 13.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.01 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.62 | 35.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.87 | 35.78 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.18 | 30.08 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.77 | 23.04 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.01 | 13.94 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 86.89 | 3.52 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.30 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.29 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 116.94 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.69 | 1.73 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.62 | 6.28 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.97 | 16.34 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.47 | 29.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.97 | 13.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.01 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.62 | 35.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.87 | 35.78 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.18 | 30.08 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.77 | 23.04 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.01 | 13.94 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 86.89 | 3.52 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 90.30 | 0.98 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 105.29 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 116.94 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 120.69 | 1.73 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 128.62 | 6.28 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.97 | 16.34 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.47 | 29.75 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.97 | 13.38 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.01 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 128.62 | 35.78 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.47 | 35.48 | 39.99 | 114.14 | 42.68 | 0.00 | 0.00 | 0.00 |
February | 70.87 | 28.99 | 41.88 | 113.25 | 35.90 | 0.00 | 0.00 | 0.00 |
March | 58.33 | 15.84 | 42.49 | 102.95 | 27.58 | 0.00 | 0.00 | 0.00 |
April | 45.85 | 4.86 | 40.99 | 94.54 | 16.76 | 0.00 | 0.00 | 0.00 |
May | 38.84 | 0.59 | 38.24 | 103.41 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 36.58 | 0.05 | 36.53 | 107.23 | 1.23 | 0.00 | 0.00 | 0.00 |
July | 36.58 | 0.31 | 36.26 | 125.06 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 42.42 | 3.01 | 39.42 | 139.03 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.94 | 12.82 | 43.12 | 143.94 | 2.12 | 0.00 | 0.00 | 0.00 |
October | 73.23 | 29.11 | 44.12 | 153.85 | 7.61 | 0.00 | 0.00 | 0.00 |
November | 80.79 | 38.95 | 41.84 | 145.11 | 19.66 | 0.00 | 0.00 | 0.00 |
December | 75.00 | 37.05 | 37.95 | 119.55 | 35.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.41 | 17.19 | 40.22 | 121.90 | 16.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.58 | 0.05 | 36.26 | 94.54 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.79 | 38.95 | 44.12 | 153.85 | 42.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.47 | 35.48 | 39.99 | 114.14 | 42.68 | 0.00 | 0.00 | 0.00 |
February | 70.87 | 28.99 | 41.88 | 113.25 | 35.90 | 0.00 | 0.00 | 0.00 |
March | 58.33 | 15.84 | 42.49 | 102.95 | 27.58 | 0.00 | 0.00 | 0.00 |
April | 45.85 | 4.86 | 40.99 | 94.54 | 16.76 | 0.00 | 0.00 | 0.00 |
May | 38.84 | 0.59 | 38.24 | 103.41 | 4.28 | 0.00 | 0.00 | 0.00 |
June | 36.58 | 0.05 | 36.53 | 107.23 | 1.23 | 0.00 | 0.00 | 0.00 |
July | 36.58 | 0.31 | 36.26 | 125.06 | 0.04 | 0.00 | 0.00 | 0.00 |
August | 42.42 | 3.01 | 39.42 | 139.03 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.94 | 12.82 | 43.12 | 143.94 | 2.12 | 0.00 | 0.00 | 0.00 |
October | 73.23 | 29.11 | 44.12 | 153.85 | 7.61 | 0.00 | 0.00 | 0.00 |
November | 80.79 | 38.95 | 41.84 | 145.11 | 19.66 | 0.00 | 0.00 | 0.00 |
December | 75.00 | 37.05 | 37.95 | 119.55 | 35.55 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.41 | 17.19 | 40.22 | 121.90 | 16.02 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.58 | 0.05 | 36.26 | 94.54 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.79 | 38.95 | 44.12 | 153.85 | 42.68 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.41 | 36.39 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.82 | 30.66 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.63 | 23.50 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.17 | 14.23 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.73 | 3.55 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 91.58 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 106.98 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 118.91 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 122.01 | 1.61 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 129.39 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.16 | 16.23 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.22 | 30.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.56 | 13.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.17 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 129.39 | 36.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.41 | 36.39 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.82 | 30.66 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.63 | 23.50 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 79.17 | 14.23 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 87.73 | 3.55 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 91.58 | 0.93 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 106.98 | 0.02 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 118.91 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 122.01 | 1.61 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 129.39 | 6.08 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 121.16 | 16.23 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.22 | 30.05 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 102.56 | 13.52 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 79.17 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 129.39 | 36.39 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.47 | 35.48 | 39.99 | 113.64 | 43.38 | 0.00 | 0.00 | 0.00 |
February | 70.87 | 28.99 | 41.88 | 112.85 | 36.58 | 0.00 | 0.00 | 0.00 |
March | 58.33 | 15.84 | 42.49 | 102.79 | 28.12 | 0.00 | 0.00 | 0.00 |
April | 45.85 | 4.86 | 40.99 | 94.73 | 17.10 | 0.00 | 0.00 | 0.00 |
May | 38.84 | 0.59 | 38.24 | 104.39 | 4.31 | 0.00 | 0.00 | 0.00 |
June | 36.58 | 0.05 | 36.53 | 108.70 | 1.16 | 0.00 | 0.00 | 0.00 |
July | 36.58 | 0.31 | 36.26 | 127.03 | 0.03 | 0.00 | 0.00 | 0.00 |
August | 42.42 | 3.01 | 39.42 | 141.33 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.94 | 12.82 | 43.12 | 145.50 | 1.98 | 0.00 | 0.00 | 0.00 |
October | 73.23 | 29.11 | 44.12 | 154.77 | 7.38 | 0.00 | 0.00 | 0.00 |
November | 80.79 | 38.95 | 41.84 | 145.35 | 19.53 | 0.00 | 0.00 | 0.00 |
December | 75.00 | 37.05 | 37.95 | 119.29 | 35.90 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.41 | 17.19 | 40.22 | 122.60 | 16.19 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.58 | 0.05 | 36.26 | 94.73 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.79 | 38.95 | 44.12 | 154.77 | 43.38 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.44 | 37.65 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.80 | 32.13 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.44 | 25.25 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.32 | 16.32 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.38 | 4.52 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.36 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.40 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.63 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.65 | 2.18 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.99 | 7.93 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.77 | 18.73 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.22 | 31.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.33 | 14.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.32 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.99 | 37.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.44 | 37.65 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.80 | 32.13 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.44 | 25.25 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.32 | 16.32 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.38 | 4.52 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.36 | 1.38 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.40 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.63 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.65 | 2.18 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.99 | 7.93 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.77 | 18.73 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.22 | 31.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.33 | 14.75 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.32 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.99 | 37.65 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.05 | 44.60 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.21 | 38.08 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.01 | 30.00 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.24 | 19.47 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 99.94 | 5.46 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.23 | 1.72 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.85 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.42 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.66 | 2.67 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.18 | 9.55 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.12 | 22.36 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 118.64 | 37.79 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.34 | 17.55 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.24 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.18 | 44.60 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.49 | 37.49 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.83 | 32.04 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.44 | 25.26 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.28 | 16.49 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.09 | 4.75 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 86.94 | 1.54 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 100.71 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 112.95 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.22 | 2.36 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.83 | 8.28 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.72 | 18.93 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.24 | 31.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.10 | 14.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.28 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.83 | 37.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.49 | 37.49 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.83 | 32.04 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.44 | 25.26 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.28 | 16.49 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.09 | 4.75 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 86.94 | 1.54 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 100.71 | 0.10 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 112.95 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.22 | 2.36 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.83 | 8.28 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.72 | 18.93 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.24 | 31.83 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.10 | 14.84 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.28 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.83 | 37.49 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.11 | 44.41 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.25 | 37.97 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.01 | 30.01 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.19 | 19.67 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 99.61 | 5.73 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 102.73 | 1.90 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.02 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 133.62 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.15 | 2.89 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 150.99 | 9.97 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.05 | 22.58 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 118.65 | 37.76 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.08 | 17.66 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.19 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 150.99 | 44.41 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.67 | 37.03 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.98 | 31.62 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.58 | 24.85 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.41 | 16.13 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.30 | 4.58 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.21 | 1.44 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 100.99 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.25 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.43 | 2.25 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.94 | 8.04 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.84 | 18.61 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.38 | 31.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.29 | 14.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.41 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.94 | 37.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 94.67 | 37.03 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 93.98 | 31.62 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.58 | 24.85 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.41 | 16.13 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.30 | 4.58 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.21 | 1.44 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 100.99 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.25 | 0.04 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.43 | 2.25 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.94 | 8.04 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.84 | 18.61 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.38 | 31.44 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.29 | 14.59 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.41 | 0.04 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.94 | 37.03 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.33 | 43.88 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.42 | 37.49 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.18 | 29.53 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.34 | 19.25 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 99.86 | 5.53 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.05 | 1.79 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.36 | 0.12 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 133.97 | 0.05 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.40 | 2.75 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.13 | 9.68 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.19 | 22.21 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 118.82 | 37.30 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.30 | 17.37 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.34 | 0.05 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.13 | 43.88 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.18 | 35.70 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.33 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.82 | 23.55 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.43 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.53 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.53 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.20 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.60 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.63 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.94 | 7.31 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.79 | 17.50 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.64 | 30.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.51 | 13.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.43 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.94 | 35.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.18 | 35.70 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.33 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.82 | 23.55 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.43 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.53 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.53 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.20 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.60 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.63 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.94 | 7.31 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.79 | 17.50 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.64 | 30.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.51 | 13.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.43 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.94 | 35.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.18 | 35.70 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.33 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.82 | 23.55 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.43 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.53 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.53 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.20 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.60 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.63 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.94 | 7.31 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.79 | 17.50 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.64 | 30.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.51 | 13.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.43 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.94 | 35.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.18 | 35.70 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.33 | 30.34 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.82 | 23.55 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.43 | 14.97 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 84.53 | 4.09 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 87.53 | 1.17 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 101.20 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 113.60 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 117.63 | 1.95 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 126.94 | 7.31 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.79 | 17.50 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.64 | 30.22 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.51 | 13.83 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.43 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 126.94 | 35.70 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.90 | 42.32 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.83 | 35.99 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.46 | 28.00 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.38 | 17.87 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.15 | 4.93 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.47 | 1.46 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.67 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.45 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.66 | 2.38 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.12 | 8.81 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.13 | 20.90 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.12 | 35.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.58 | 16.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.38 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.12 | 42.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.90 | 42.32 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.83 | 35.99 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.46 | 28.00 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.38 | 17.87 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.15 | 4.93 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 103.47 | 1.46 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 119.67 | 0.09 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 134.45 | 0.03 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 139.66 | 2.38 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.12 | 8.81 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.13 | 20.90 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.12 | 35.88 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 119.58 | 16.46 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.38 | 0.03 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.12 | 42.32 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.03 | 35.53 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.23 | 30.12 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.84 | 23.23 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.64 | 14.61 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.25 | 3.86 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.54 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.39 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.84 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.44 | 1.78 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.31 | 6.94 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.86 | 17.10 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.56 | 29.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.96 | 13.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.64 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.31 | 35.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.03 | 35.53 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.23 | 30.12 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.84 | 23.23 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.64 | 14.61 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.25 | 3.86 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.54 | 1.03 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.39 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.84 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.44 | 1.78 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.31 | 6.94 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.86 | 17.10 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.56 | 29.96 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.96 | 13.61 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.64 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.31 | 35.53 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.77 | 42.11 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.74 | 35.72 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.50 | 27.63 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.63 | 17.45 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.97 | 4.67 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 104.61 | 1.28 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 121.02 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 135.85 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.58 | 2.18 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.56 | 8.37 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.24 | 20.43 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.06 | 35.57 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 120.10 | 16.20 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.63 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.56 | 42.11 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.10 | 35.40 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.30 | 29.99 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.90 | 23.11 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.70 | 14.51 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.33 | 3.82 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.63 | 1.01 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.48 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.93 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.51 | 1.76 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.36 | 6.89 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.92 | 17.03 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.62 | 29.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.03 | 13.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.70 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.36 | 35.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.10 | 35.40 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.30 | 29.99 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.90 | 23.11 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.70 | 14.51 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.33 | 3.82 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.63 | 1.01 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.48 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.93 | 0.01 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.51 | 1.76 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.36 | 6.89 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.92 | 17.03 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.62 | 29.86 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 101.03 | 13.54 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.70 | 0.01 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.36 | 35.40 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 113.86 | 41.96 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.82 | 35.57 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.57 | 27.49 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.70 | 17.34 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 101.07 | 4.62 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 104.72 | 1.26 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 121.13 | 0.07 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 135.96 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.67 | 2.16 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.62 | 8.31 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.30 | 20.35 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.12 | 35.45 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 120.18 | 16.12 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.70 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.62 | 41.96 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.24 | 35.10 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.42 | 29.70 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.98 | 22.87 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.72 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.19 | 3.85 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.39 | 1.05 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.04 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.42 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.18 | 1.84 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.20 | 7.02 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.88 | 17.06 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.69 | 29.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.91 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.72 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.20 | 35.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.24 | 35.10 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.42 | 29.70 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.98 | 22.87 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.72 | 14.40 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 85.19 | 3.85 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 88.39 | 1.05 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 102.04 | 0.06 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 114.42 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 118.18 | 1.84 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 127.20 | 7.02 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.88 | 17.06 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.69 | 29.70 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 100.91 | 13.48 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.72 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 127.20 | 35.10 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.03 | 41.61 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 112.97 | 35.23 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.68 | 27.21 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.73 | 17.21 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 100.90 | 4.65 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 104.43 | 1.31 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 120.61 | 0.08 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 135.35 | 0.02 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 140.28 | 2.25 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 151.43 | 8.47 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 144.26 | 20.38 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.21 | 35.25 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 120.04 | 16.05 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.73 | 0.02 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 151.43 | 41.61 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.36 | 34.14 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.49 | 28.68 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.86 | 22.10 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.19 | 14.19 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 83.51 | 4.12 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 86.05 | 1.33 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 98.58 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 110.51 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 115.51 | 2.40 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 125.64 | 8.02 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.09 | 17.63 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.57 | 29.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 99.48 | 13.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.19 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 125.64 | 34.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 62.78 | 29.51 | 33.26 | 95.36 | 34.14 | 0.00 | 0.00 | 0.00 |
February | 58.95 | 24.11 | 34.84 | 94.49 | 28.68 | 0.00 | 0.00 | 0.00 |
March | 48.52 | 13.17 | 35.35 | 85.86 | 22.10 | 0.00 | 0.00 | 0.00 |
April | 38.14 | 4.04 | 34.10 | 78.19 | 14.19 | 0.00 | 0.00 | 0.00 |
May | 32.31 | 0.49 | 31.81 | 83.51 | 4.12 | 0.00 | 0.00 | 0.00 |
June | 30.43 | 0.04 | 30.39 | 86.05 | 1.33 | 0.00 | 0.00 | 0.00 |
July | 30.42 | 0.26 | 30.17 | 98.58 | 0.13 | 0.00 | 0.00 | 0.00 |
August | 35.29 | 2.50 | 32.79 | 110.51 | 0.06 | 0.00 | 0.00 | 0.00 |
September | 46.53 | 10.66 | 35.87 | 115.51 | 2.40 | 0.00 | 0.00 | 0.00 |
October | 60.92 | 24.22 | 36.70 | 125.64 | 8.02 | 0.00 | 0.00 | 0.00 |
November | 67.21 | 32.40 | 34.81 | 120.09 | 17.63 | 0.00 | 0.00 | 0.00 |
December | 62.39 | 30.82 | 31.57 | 99.57 | 29.32 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 47.76 | 14.30 | 33.46 | 99.48 | 13.44 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 30.42 | 0.04 | 30.17 | 78.19 | 0.06 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 67.21 | 32.40 | 36.70 | 125.64 | 34.14 | 0.00 | 0.00 | 0.00 |
Report: WindowReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION RATE [W] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | SURFACE WINDOW HEAT GAIN RATE [W] | SURFACE WINDOW HEAT LOSS RATE [W] | SURFACE WINDOW INSIDE FACE GLAZING CONDENSATION STATUS {HOURS NON-ZERO} [HOURS] | SURFACE SHADING DEVICE IS ON TIME FRACTION {HOURS NON-ZERO} [HOURS] | SURFACE STORM WINDOW ON OFF STATUS {HOURS NON-ZERO} [HOURS] | |
January | 75.05 | 35.29 | 39.77 | 114.16 | 40.48 | 0.00 | 0.00 | 0.00 |
February | 70.48 | 28.83 | 41.65 | 113.05 | 34.03 | 0.00 | 0.00 | 0.00 |
March | 58.01 | 15.75 | 42.26 | 102.52 | 26.30 | 0.00 | 0.00 | 0.00 |
April | 45.60 | 4.83 | 40.76 | 93.09 | 16.97 | 0.00 | 0.00 | 0.00 |
May | 38.63 | 0.59 | 38.03 | 98.90 | 4.99 | 0.00 | 0.00 | 0.00 |
June | 36.38 | 0.05 | 36.33 | 101.65 | 1.66 | 0.00 | 0.00 | 0.00 |
July | 36.38 | 0.31 | 36.07 | 116.50 | 0.17 | 0.00 | 0.00 | 0.00 |
August | 42.19 | 2.99 | 39.20 | 130.71 | 0.08 | 0.00 | 0.00 | 0.00 |
September | 55.63 | 12.75 | 42.88 | 137.12 | 2.93 | 0.00 | 0.00 | 0.00 |
October | 72.83 | 28.96 | 43.88 | 149.57 | 9.66 | 0.00 | 0.00 | 0.00 |
November | 80.35 | 38.73 | 41.61 | 143.31 | 21.07 | 0.00 | 0.00 | 0.00 |
December | 74.59 | 36.84 | 37.74 | 119.06 | 34.82 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 57.10 | 17.10 | 40.00 | 118.34 | 16.01 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 36.38 | 0.05 | 36.07 | 93.09 | 0.08 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 80.35 | 38.73 | 43.88 | 149.57 | 40.48 | 0.00 | 0.00 | 0.00 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254089E+09 | 95841528.90 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227845E+09 | 72759341.05 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229735E+09 | 61712728.18 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204792E+09 | 36137922.44 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.232720E+09 | 9437762.65 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234067E+09 | 2550329.09 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.281999E+09 | 77521.63 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313204E+09 | 51634.22 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.312816E+09 | 4496296.68 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344507E+09 | 16809701.18 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313562E+09 | 42347020.51 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266430E+09 | 79681793.03 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.321576E+10 | 0.421904E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204792E+09 | 51634.22 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344507E+09 | 95841528.90 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254089E+09 | 95841528.90 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227845E+09 | 72759341.05 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229735E+09 | 61712728.18 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204792E+09 | 36137922.44 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.232720E+09 | 9437762.65 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234067E+09 | 2550329.09 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.281999E+09 | 77521.63 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313204E+09 | 51634.22 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.312816E+09 | 4496296.68 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344507E+09 | 16809701.18 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313562E+09 | 42347020.51 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266430E+09 | 79681793.03 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.321576E+10 | 0.421904E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204792E+09 | 51634.22 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344507E+09 | 95841528.90 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254089E+09 | 95841528.90 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227845E+09 | 72759341.05 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229735E+09 | 61712728.18 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204792E+09 | 36137922.44 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.232720E+09 | 9437762.65 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234067E+09 | 2550329.09 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.281999E+09 | 77521.63 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313204E+09 | 51634.22 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.312816E+09 | 4496296.68 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344507E+09 | 16809701.18 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313562E+09 | 42347020.51 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266430E+09 | 79681793.03 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.321576E+10 | 0.421904E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204792E+09 | 51634.22 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344507E+09 | 95841528.90 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254089E+09 | 95841528.90 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227845E+09 | 72759341.05 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229735E+09 | 61712728.18 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204792E+09 | 36137922.44 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.232720E+09 | 9437762.65 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.234067E+09 | 2550329.09 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.281999E+09 | 77521.63 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.313204E+09 | 51634.22 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.312816E+09 | 4496296.68 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.344507E+09 | 16809701.18 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313562E+09 | 42347020.51 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266430E+09 | 79681793.03 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.321576E+10 | 0.421904E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204792E+09 | 51634.22 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.344507E+09 | 95841528.90 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202130E+09 | 95030567.71 | 0.107100E+09 | 0.305723E+09 | 0.114306E+09 |
February | 0.171440E+09 | 70126581.11 | 0.101314E+09 | 0.273975E+09 | 86843174.86 |
March | 0.156221E+09 | 42413228.20 | 0.113808E+09 | 0.275733E+09 | 73874561.41 |
April | 0.118840E+09 | 12599320.14 | 0.106241E+09 | 0.245041E+09 | 43451676.35 |
May | 0.104024E+09 | 1593018.04 | 0.102431E+09 | 0.276975E+09 | 11461048.83 |
June | 94806097.65 | 117326.12 | 94688771.53 | 0.277936E+09 | 3192275.54 |
July | 97963650.72 | 832392.27 | 97131258.45 | 0.334968E+09 | 106071.63 |
August | 0.113630E+09 | 8051148.50 | 0.105579E+09 | 0.372380E+09 | 68227.87 |
September | 0.144990E+09 | 33228595.05 | 0.111761E+09 | 0.373096E+09 | 5503966.78 |
October | 0.196147E+09 | 77979510.16 | 0.118168E+09 | 0.412074E+09 | 20376088.96 |
November | 0.209410E+09 | 0.100951E+09 | 0.108459E+09 | 0.376118E+09 | 50957111.21 |
December | 0.200876E+09 | 99226436.87 | 0.101649E+09 | 0.320216E+09 | 95213720.89 |
Annual Sum or Average | 0.181048E+10 | 0.542149E+09 | 0.126833E+10 | 0.384423E+10 | 0.505354E+09 |
Minimum of Months | 94806097.65 | 117326.12 | 94688771.53 | 0.245041E+09 | 68227.87 |
Maximum of Months | 0.209410E+09 | 0.100951E+09 | 0.118168E+09 | 0.412074E+09 | 0.114306E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE1_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202130E+09 | 95030567.71 | 0.107100E+09 | 0.305723E+09 | 0.114306E+09 |
February | 0.171440E+09 | 70126581.11 | 0.101314E+09 | 0.273975E+09 | 86843174.86 |
March | 0.156221E+09 | 42413228.20 | 0.113808E+09 | 0.275733E+09 | 73874561.41 |
April | 0.118840E+09 | 12599320.14 | 0.106241E+09 | 0.245041E+09 | 43451676.35 |
May | 0.104024E+09 | 1593018.04 | 0.102431E+09 | 0.276975E+09 | 11461048.83 |
June | 94806097.65 | 117326.12 | 94688771.53 | 0.277936E+09 | 3192275.54 |
July | 97963650.72 | 832392.27 | 97131258.45 | 0.334968E+09 | 106071.63 |
August | 0.113630E+09 | 8051148.50 | 0.105579E+09 | 0.372380E+09 | 68227.87 |
September | 0.144990E+09 | 33228595.05 | 0.111761E+09 | 0.373096E+09 | 5503966.78 |
October | 0.196147E+09 | 77979510.16 | 0.118168E+09 | 0.412074E+09 | 20376088.96 |
November | 0.209410E+09 | 0.100951E+09 | 0.108459E+09 | 0.376118E+09 | 50957111.21 |
December | 0.200876E+09 | 99226436.87 | 0.101649E+09 | 0.320216E+09 | 95213720.89 |
Annual Sum or Average | 0.181048E+10 | 0.542149E+09 | 0.126833E+10 | 0.384423E+10 | 0.505354E+09 |
Minimum of Months | 94806097.65 | 117326.12 | 94688771.53 | 0.245041E+09 | 68227.87 |
Maximum of Months | 0.209410E+09 | 0.100951E+09 | 0.118168E+09 | 0.412074E+09 | 0.114306E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.252874E+09 | 97469652.46 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.226967E+09 | 74176201.21 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229347E+09 | 62938821.24 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205198E+09 | 36873767.18 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.234985E+09 | 9497031.03 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.237363E+09 | 2398201.26 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.286525E+09 | 58968.61 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.318476E+09 | 32881.54 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.316242E+09 | 4185499.96 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.346558E+09 | 16291575.42 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.314055E+09 | 42062953.74 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.265760E+09 | 80490386.76 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.323435E+10 | 0.426476E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205198E+09 | 32881.54 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.346558E+09 | 97469652.46 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.252874E+09 | 97469652.46 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.226967E+09 | 74176201.21 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229347E+09 | 62938821.24 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.205198E+09 | 36873767.18 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.234985E+09 | 9497031.03 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.237363E+09 | 2398201.26 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.286525E+09 | 58968.61 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.318476E+09 | 32881.54 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.316242E+09 | 4185499.96 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.346558E+09 | 16291575.42 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.314055E+09 | 42062953.74 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.265760E+09 | 80490386.76 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.323435E+10 | 0.426476E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.205198E+09 | 32881.54 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.346558E+09 | 97469652.46 |
Report: WindowEnergyReportMonthly
For: SMSTORE1_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.202130E+09 | 95030567.71 | 0.107100E+09 | 0.304371E+09 | 0.116200E+09 |
February | 0.171440E+09 | 70126581.11 | 0.101314E+09 | 0.273008E+09 | 88497682.70 |
March | 0.156221E+09 | 42413228.20 | 0.113808E+09 | 0.275323E+09 | 75325733.72 |
April | 0.118840E+09 | 12599320.14 | 0.106241E+09 | 0.245531E+09 | 44335356.98 |
May | 0.104024E+09 | 1593018.04 | 0.102431E+09 | 0.279598E+09 | 11545157.25 |
June | 94806097.65 | 117326.12 | 94688771.53 | 0.281740E+09 | 3015691.37 |
July | 97963650.72 | 832392.27 | 97131258.45 | 0.340235E+09 | 82198.08 |
August | 0.113630E+09 | 8051148.50 | 0.105579E+09 | 0.378547E+09 | 46257.83 |
September | 0.144990E+09 | 33228595.05 | 0.111761E+09 | 0.377136E+09 | 5135596.32 |
October | 0.196147E+09 | 77979510.16 | 0.118168E+09 | 0.414543E+09 | 19772785.07 |
November | 0.209410E+09 | 0.100951E+09 | 0.108459E+09 | 0.376760E+09 | 50609457.96 |
December | 0.200876E+09 | 99226436.87 | 0.101649E+09 | 0.319506E+09 | 96153437.86 |
Annual Sum or Average | 0.181048E+10 | 0.542149E+09 | 0.126833E+10 | 0.386630E+10 | 0.510719E+09 |
Minimum of Months | 94806097.65 | 117326.12 | 94688771.53 | 0.245531E+09 | 46257.83 |
Maximum of Months | 0.209410E+09 | 0.100951E+09 | 0.118168E+09 | 0.414543E+09 | 0.116200E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.252940E+09 | 0.100842E+09 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.226921E+09 | 77724689.07 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.228830E+09 | 67620593.87 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203007E+09 | 42303727.70 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.225996E+09 | 12119128.74 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226438E+09 | 3587250.62 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271594E+09 | 207322.88 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304344E+09 | 87733.79 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304955E+09 | 5655923.08 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340132E+09 | 21228293.81 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313039E+09 | 48560517.57 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.265762E+09 | 85323226.50 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316396E+10 | 0.465260E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203007E+09 | 87733.79 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340132E+09 | 0.100842E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.252940E+09 | 0.100842E+09 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.226921E+09 | 77724689.07 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.228830E+09 | 67620593.87 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203007E+09 | 42303727.70 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.225996E+09 | 12119128.74 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226438E+09 | 3587250.62 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271594E+09 | 207322.88 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304344E+09 | 87733.79 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304955E+09 | 5655923.08 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340132E+09 | 21228293.81 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313039E+09 | 48560517.57 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.265762E+09 | 85323226.50 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316396E+10 | 0.465260E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203007E+09 | 87733.79 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340132E+09 | 0.100842E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE2_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.302785E+09 | 0.119455E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.271461E+09 | 92121915.80 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.273216E+09 | 80351782.29 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.241675E+09 | 50460406.69 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.267682E+09 | 14623788.78 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.267561E+09 | 4460861.38 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.321003E+09 | 269751.16 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360027E+09 | 120417.32 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.362002E+09 | 6909108.81 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.404932E+09 | 25574818.37 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373549E+09 | 57945217.98 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.317752E+09 | 0.101222E+09 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.376364E+10 | 0.553515E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.241675E+09 | 120417.32 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.404932E+09 | 0.119455E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253088E+09 | 0.100406E+09 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.226991E+09 | 77506820.91 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.228842E+09 | 67645201.18 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.202891E+09 | 42754314.00 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.225237E+09 | 12722486.59 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.225350E+09 | 3981134.56 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.269729E+09 | 269681.74 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.302533E+09 | 123761.52 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.303830E+09 | 6127998.90 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.339695E+09 | 22168041.80 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.312899E+09 | 49062387.43 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.265796E+09 | 85244927.32 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.315688E+10 | 0.468013E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.202891E+09 | 123761.52 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.339695E+09 | 0.100406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253088E+09 | 0.100406E+09 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.226991E+09 | 77506820.91 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.228842E+09 | 67645201.18 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.202891E+09 | 42754314.00 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.225237E+09 | 12722486.59 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.225350E+09 | 3981134.56 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.269729E+09 | 269681.74 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.302533E+09 | 123761.52 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.303830E+09 | 6127998.90 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.339695E+09 | 22168041.80 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.312899E+09 | 49062387.43 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.265796E+09 | 85244927.32 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.315688E+10 | 0.468013E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.202891E+09 | 123761.52 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.339695E+09 | 0.100406E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE3_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.302964E+09 | 0.118942E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.271546E+09 | 91865860.03 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.273230E+09 | 80381011.99 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.241539E+09 | 50992935.80 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.266787E+09 | 15344145.34 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.266283E+09 | 4937615.45 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.318796E+09 | 346180.43 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.357887E+09 | 166525.03 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.360682E+09 | 7482703.66 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.404417E+09 | 26690562.48 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373381E+09 | 58537488.47 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.317793E+09 | 0.101129E+09 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.375530E+10 | 0.556816E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.241539E+09 | 166525.03 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.404417E+09 | 0.118942E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253568E+09 | 99192640.91 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227351E+09 | 76502272.79 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229209E+09 | 66549733.57 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203226E+09 | 41820059.23 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.225802E+09 | 12262678.80 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226045E+09 | 3724618.73 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.270481E+09 | 246008.48 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.303340E+09 | 105456.73 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304369E+09 | 5836074.86 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340005E+09 | 21526545.67 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313209E+09 | 48232293.86 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266171E+09 | 84205664.96 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316278E+10 | 0.460204E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203226E+09 | 105456.73 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340005E+09 | 99192640.91 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.253568E+09 | 99192640.91 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227351E+09 | 76502272.79 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229209E+09 | 66549733.57 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203226E+09 | 41820059.23 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.225802E+09 | 12262678.80 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226045E+09 | 3724618.73 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.270481E+09 | 246008.48 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.303340E+09 | 105456.73 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304369E+09 | 5836074.86 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340005E+09 | 21526545.67 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313209E+09 | 48232293.86 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266171E+09 | 84205664.96 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316278E+10 | 0.460204E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203226E+09 | 105456.73 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340005E+09 | 99192640.91 |
Report: WindowEnergyReportMonthly
For: SMSTORE4_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.303541E+09 | 0.117519E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.271978E+09 | 90686893.33 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.273671E+09 | 79094322.33 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.241939E+09 | 49895760.09 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.267452E+09 | 14799570.21 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.267098E+09 | 4629527.86 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.319681E+09 | 317456.81 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.358836E+09 | 144612.54 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.361314E+09 | 7133558.16 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.404782E+09 | 25933899.31 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373751E+09 | 57562869.25 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318243E+09 | 99910545.32 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.376229E+10 | 0.547628E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.241939E+09 | 144612.54 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.404782E+09 | 0.117519E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254920E+09 | 95621497.32 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228213E+09 | 73406642.76 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229861E+09 | 63066296.80 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203293E+09 | 38807245.08 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226406E+09 | 10957072.19 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226886E+09 | 3042427.11 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271058E+09 | 187145.46 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304279E+09 | 59186.50 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304904E+09 | 5060247.35 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340001E+09 | 19589422.84 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313080E+09 | 45370381.84 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266885E+09 | 80947104.95 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316979E+10 | 0.436115E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203293E+09 | 59186.50 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340001E+09 | 95621497.32 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254920E+09 | 95621497.32 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228213E+09 | 73406642.76 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229861E+09 | 63066296.80 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203293E+09 | 38807245.08 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226406E+09 | 10957072.19 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226886E+09 | 3042427.11 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271058E+09 | 187145.46 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304279E+09 | 59186.50 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304904E+09 | 5060247.35 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340001E+09 | 19589422.84 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313080E+09 | 45370381.84 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266885E+09 | 80947104.95 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316979E+10 | 0.436115E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203293E+09 | 59186.50 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340001E+09 | 95621497.32 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254920E+09 | 95621497.32 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228213E+09 | 73406642.76 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229861E+09 | 63066296.80 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203293E+09 | 38807245.08 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226406E+09 | 10957072.19 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226886E+09 | 3042427.11 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271058E+09 | 187145.46 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304279E+09 | 59186.50 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304904E+09 | 5060247.35 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340001E+09 | 19589422.84 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313080E+09 | 45370381.84 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266885E+09 | 80947104.95 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316979E+10 | 0.436115E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203293E+09 | 59186.50 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340001E+09 | 95621497.32 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_WINDOW_4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254920E+09 | 95621497.32 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228213E+09 | 73406642.76 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229861E+09 | 63066296.80 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203293E+09 | 38807245.08 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.226406E+09 | 10957072.19 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.226886E+09 | 3042427.11 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.271058E+09 | 187145.46 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.304279E+09 | 59186.50 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.304904E+09 | 5060247.35 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340001E+09 | 19589422.84 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313080E+09 | 45370381.84 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266885E+09 | 80947104.95 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.316979E+10 | 0.436115E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203293E+09 | 59186.50 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340001E+09 | 95621497.32 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305074E+09 | 0.113343E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272949E+09 | 87062844.89 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274419E+09 | 74989701.88 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242037E+09 | 46323750.83 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.268253E+09 | 13216868.44 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.268205E+09 | 3781135.07 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.320523E+09 | 241035.15 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360098E+09 | 83026.32 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.361994E+09 | 6169914.03 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.404761E+09 | 23588177.67 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373578E+09 | 54170855.61 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319043E+09 | 96087899.86 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.377093E+10 | 0.519058E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242037E+09 | 83026.32 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.404761E+09 | 0.113343E+09 |
Report: WindowEnergyReportMonthly
For: LGSTORE2_WALL_1_DOOR_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305074E+09 | 0.113343E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272949E+09 | 87062844.89 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274419E+09 | 74989701.88 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242037E+09 | 46323750.83 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.268253E+09 | 13216868.44 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.268205E+09 | 3781135.07 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.320523E+09 | 241035.15 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.360098E+09 | 83026.32 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.361994E+09 | 6169914.03 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.404761E+09 | 23588177.67 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373578E+09 | 54170855.61 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319043E+09 | 96087899.86 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.377093E+10 | 0.519058E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242037E+09 | 83026.32 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.404761E+09 | 0.113343E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254529E+09 | 95165174.64 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227962E+09 | 72862569.65 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229905E+09 | 62221627.13 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203827E+09 | 37861438.40 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228325E+09 | 10338541.82 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229500E+09 | 2659052.84 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274233E+09 | 153526.35 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.307583E+09 | 34441.05 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306985E+09 | 4622203.10 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340980E+09 | 18578299.03 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313278E+09 | 44332370.06 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266668E+09 | 80256993.77 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318378E+10 | 0.429086E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203827E+09 | 34441.05 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340980E+09 | 95165174.64 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254529E+09 | 95165174.64 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.227962E+09 | 72862569.65 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229905E+09 | 62221627.13 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203827E+09 | 37861438.40 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228325E+09 | 10338541.82 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229500E+09 | 2659052.84 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274233E+09 | 153526.35 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.307583E+09 | 34441.05 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306985E+09 | 4622203.10 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340980E+09 | 18578299.03 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313278E+09 | 44332370.06 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266668E+09 | 80256993.77 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318378E+10 | 0.429086E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203827E+09 | 34441.05 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340980E+09 | 95165174.64 |
Report: WindowEnergyReportMonthly
For: SMSTORE5_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.304722E+09 | 0.112782E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272739E+09 | 86407605.29 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274534E+09 | 73998894.19 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242679E+09 | 45226862.18 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.270439E+09 | 12499188.13 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.271158E+09 | 3327921.20 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.324138E+09 | 198773.28 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.363864E+09 | 50416.53 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.364394E+09 | 5653109.31 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405936E+09 | 22417060.49 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373876E+09 | 52961204.65 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318880E+09 | 95264604.81 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.378736E+10 | 0.510788E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242679E+09 | 50416.53 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405936E+09 | 0.112782E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254719E+09 | 94828657.48 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228123E+09 | 72562617.93 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230073E+09 | 61907929.67 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203987E+09 | 37617205.78 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228539E+09 | 10233981.30 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229740E+09 | 2610717.00 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274478E+09 | 151472.53 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.307818E+09 | 32497.29 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.307175E+09 | 4574832.22 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.341117E+09 | 18451176.08 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313412E+09 | 44142103.45 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266818E+09 | 79981821.64 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318600E+10 | 0.427095E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203987E+09 | 32497.29 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.341117E+09 | 94828657.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.254719E+09 | 94828657.48 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228123E+09 | 72562617.93 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230073E+09 | 61907929.67 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.203987E+09 | 37617205.78 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228539E+09 | 10233981.30 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229740E+09 | 2610717.00 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.274478E+09 | 151472.53 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.307818E+09 | 32497.29 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.307175E+09 | 4574832.22 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.341117E+09 | 18451176.08 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313412E+09 | 44142103.45 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266818E+09 | 79981821.64 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318600E+10 | 0.427095E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.203987E+09 | 32497.29 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.341117E+09 | 94828657.48 |
Report: WindowEnergyReportMonthly
For: SMSTORE6_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.304951E+09 | 0.112386E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.272933E+09 | 86053540.23 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274735E+09 | 73628517.13 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242870E+09 | 44938070.16 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.270694E+09 | 12374840.56 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.271442E+09 | 3268967.83 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.324429E+09 | 196298.98 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.364144E+09 | 47852.73 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.364619E+09 | 5595137.02 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.406099E+09 | 22265450.77 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.374035E+09 | 52735864.19 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319060E+09 | 94939760.40 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.379001E+10 | 0.508430E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242870E+09 | 47852.73 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.406099E+09 | 0.112386E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255103E+09 | 94025025.81 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228429E+09 | 71854692.83 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230299E+09 | 61266984.17 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204053E+09 | 37322609.96 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228165E+09 | 10303833.23 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229099E+09 | 2714859.67 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.273307E+09 | 173082.76 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.306467E+09 | 45145.70 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306327E+09 | 4765593.56 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340700E+09 | 18804014.01 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313317E+09 | 44206972.86 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267013E+09 | 79535589.05 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318228E+10 | 0.425018E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204053E+09 | 45145.70 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340700E+09 | 94025025.81 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255103E+09 | 94025025.81 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228429E+09 | 71854692.83 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.230299E+09 | 61266984.17 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.204053E+09 | 37322609.96 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.228165E+09 | 10303833.23 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.229099E+09 | 2714859.67 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.273307E+09 | 173082.76 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.306467E+09 | 45145.70 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.306327E+09 | 4765593.56 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.340700E+09 | 18804014.01 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.313317E+09 | 44206972.86 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.267013E+09 | 79535589.05 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.318228E+10 | 0.425018E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.204053E+09 | 45145.70 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.340700E+09 | 94025025.81 |
Report: WindowEnergyReportMonthly
For: SMSTORE7_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305410E+09 | 0.111445E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273298E+09 | 85224836.58 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.275006E+09 | 72878791.41 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.242948E+09 | 44597541.03 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.270246E+09 | 12463096.97 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.270677E+09 | 3397942.88 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.323031E+09 | 223964.87 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.362532E+09 | 65209.81 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.363611E+09 | 5830507.30 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.405602E+09 | 22690711.44 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.373921E+09 | 52820059.01 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.319292E+09 | 94419843.25 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.378557E+10 | 0.506058E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.242948E+09 | 65209.81 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.405602E+09 | 0.111445E+09 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255402E+09 | 91452703.71 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228588E+09 | 69372066.06 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229962E+09 | 59180816.26 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.202662E+09 | 36782933.06 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.223684E+09 | 11047539.45 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.223031E+09 | 3451862.12 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.264043E+09 | 346513.40 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.295999E+09 | 168438.25 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.299407E+09 | 6220719.25 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.336513E+09 | 21481008.80 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.311266E+09 | 45705849.42 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266676E+09 | 78536758.50 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.313723E+10 | 0.423747E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.202662E+09 | 168438.25 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.336513E+09 | 91452703.71 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_WINDOW_2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.168140E+09 | 79050247.79 | 89089825.42 | 0.255402E+09 | 91452703.71 |
February | 0.142611E+09 | 58334110.25 | 84276813.20 | 0.228588E+09 | 69372066.06 |
March | 0.129951E+09 | 35281028.83 | 94670103.70 | 0.229962E+09 | 59180816.26 |
April | 98856132.43 | 10480621.16 | 88375511.27 | 0.202662E+09 | 36782933.06 |
May | 86531017.69 | 1325136.47 | 85205881.22 | 0.223684E+09 | 11047539.45 |
June | 78863524.57 | 97596.59 | 78765927.99 | 0.223031E+09 | 3451862.12 |
July | 81490104.20 | 692417.37 | 80797686.83 | 0.264043E+09 | 346513.40 |
August | 94522041.84 | 6697269.10 | 87824772.74 | 0.295999E+09 | 168438.25 |
September | 0.120608E+09 | 27640881.62 | 92967288.71 | 0.299407E+09 | 6220719.25 |
October | 0.163163E+09 | 64866492.43 | 98296522.40 | 0.336513E+09 | 21481008.80 |
November | 0.174195E+09 | 83975166.54 | 90220290.42 | 0.311266E+09 | 45705849.42 |
December | 0.167096E+09 | 82540540.50 | 84555830.53 | 0.266676E+09 | 78536758.50 |
Annual Sum or Average | 0.150603E+10 | 0.450982E+09 | 0.105505E+10 | 0.313723E+10 | 0.423747E+09 |
Minimum of Months | 78863524.57 | 97596.59 | 78765927.99 | 0.202662E+09 | 168438.25 |
Maximum of Months | 0.174195E+09 | 83975166.54 | 98296522.40 | 0.336513E+09 | 91452703.71 |
Report: WindowEnergyReportMonthly
For: SMSTORE8_WALL_1_DOOR
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSURFACE WINDOW TRANSMITTED SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | SURFACE WINDOW TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | SURFACE WINDOW HEAT GAIN ENERGY [J] | SURFACE WINDOW HEAT LOSS ENERGY [J] | |
January | 0.201026E+09 | 94511274.99 | 0.106514E+09 | 0.305757E+09 | 0.108434E+09 |
February | 0.170503E+09 | 69743375.75 | 0.100760E+09 | 0.273483E+09 | 82323930.37 |
March | 0.155368E+09 | 42181461.93 | 0.113186E+09 | 0.274597E+09 | 70433517.44 |
April | 0.118191E+09 | 12530471.39 | 0.105660E+09 | 0.241278E+09 | 43973839.63 |
May | 0.103455E+09 | 1584313.03 | 0.101871E+09 | 0.264902E+09 | 13356911.00 |
June | 94288031.54 | 116684.99 | 94171346.55 | 0.263478E+09 | 4303708.25 |
July | 97428330.23 | 827843.68 | 96600486.54 | 0.312026E+09 | 444294.79 |
August | 0.113009E+09 | 8007153.16 | 0.105002E+09 | 0.350094E+09 | 223465.78 |
September | 0.144197E+09 | 33047018.03 | 0.111150E+09 | 0.355408E+09 | 7606256.37 |
October | 0.195075E+09 | 77553392.62 | 0.117522E+09 | 0.400598E+09 | 25874996.72 |
November | 0.208265E+09 | 0.100399E+09 | 0.107866E+09 | 0.371467E+09 | 54616370.48 |
December | 0.199778E+09 | 98684215.90 | 0.101094E+09 | 0.318879E+09 | 93259273.88 |
Annual Sum or Average | 0.180058E+10 | 0.539187E+09 | 0.126140E+10 | 0.373197E+10 | 0.504851E+09 |
Minimum of Months | 94288031.54 | 116684.99 | 94171346.55 | 0.241278E+09 | 223465.78 |
Maximum of Months | 0.208265E+09 | 0.100399E+09 | 0.117522E+09 | 0.400598E+09 | 0.108434E+09 |
Report: WindowZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 607.75 | 228.49 | 402.04 | 189.02 | 213.02 | 0.00 | 0.00 |
February | 603.23 | 192.10 | 377.53 | 154.43 | 223.10 | 0.00 | 0.00 |
March | 548.99 | 147.33 | 310.73 | 84.36 | 226.37 | 0.00 | 0.00 |
April | 505.11 | 89.29 | 244.25 | 25.90 | 218.36 | 0.00 | 0.00 |
May | 554.37 | 22.65 | 206.90 | 3.17 | 203.74 | 0.00 | 0.00 |
June | 575.67 | 6.40 | 194.86 | 0.24 | 194.61 | 0.00 | 0.00 |
July | 671.27 | 0.19 | 194.85 | 1.66 | 193.19 | 0.00 | 0.00 |
August | 745.81 | 0.13 | 226.01 | 16.01 | 210.00 | 0.00 | 0.00 |
September | 770.62 | 11.18 | 298.00 | 68.30 | 229.70 | 0.00 | 0.00 |
October | 822.20 | 40.32 | 390.14 | 155.10 | 235.04 | 0.00 | 0.00 |
November | 774.10 | 104.67 | 430.40 | 207.49 | 222.92 | 0.00 | 0.00 |
December | 637.00 | 190.10 | 399.54 | 197.36 | 202.18 | 0.00 | 0.00 |
Annual Sum or Average | 651.68 | 85.56 | 305.84 | 91.58 | 214.26 | 0.00 | 0.00 |
Minimum of Months | 505.11 | 0.13 | 194.85 | 0.24 | 193.19 | 0.00 | 0.00 |
Maximum of Months | 822.20 | 228.49 | 430.40 | 207.49 | 235.04 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.46 | 116.17 | 201.02 | 94.51 | 106.51 | 0.00 | 0.00 |
February | 300.49 | 97.90 | 188.77 | 77.21 | 111.55 | 0.00 | 0.00 |
March | 274.05 | 75.12 | 155.36 | 42.18 | 113.18 | 0.00 | 0.00 |
April | 253.06 | 45.56 | 122.13 | 12.95 | 109.18 | 0.00 | 0.00 |
May | 279.86 | 11.40 | 103.45 | 1.58 | 101.87 | 0.00 | 0.00 |
June | 291.85 | 3.01 | 97.43 | 0.12 | 97.31 | 0.00 | 0.00 |
July | 340.98 | 0.07 | 97.43 | 0.83 | 96.60 | 0.00 | 0.00 |
August | 379.14 | 0.04 | 113.01 | 8.01 | 105.00 | 0.00 | 0.00 |
September | 389.51 | 5.21 | 149.00 | 34.15 | 114.85 | 0.00 | 0.00 |
October | 413.55 | 19.55 | 195.07 | 77.55 | 117.52 | 0.00 | 0.00 |
November | 387.68 | 51.98 | 215.20 | 103.74 | 111.46 | 0.00 | 0.00 |
December | 317.74 | 96.00 | 199.77 | 98.68 | 101.09 | 0.00 | 0.00 |
Annual Sum or Average | 327.72 | 43.24 | 152.92 | 45.79 | 107.13 | 0.00 | 0.00 |
Minimum of Months | 253.06 | 0.04 | 97.43 | 0.12 | 96.60 | 0.00 | 0.00 |
Maximum of Months | 413.55 | 116.17 | 215.20 | 103.74 | 117.52 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 301.92 | 119.90 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 299.81 | 102.34 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 272.88 | 80.49 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 249.88 | 52.11 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 268.69 | 14.51 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 277.95 | 4.49 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 322.65 | 0.26 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 361.68 | 0.11 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 374.97 | 7.03 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 405.16 | 25.40 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 385.66 | 59.82 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 317.08 | 101.50 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 320.00 | 47.06 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 249.88 | 0.11 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 405.16 | 119.90 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.10 | 119.38 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 299.90 | 102.05 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 272.89 | 80.52 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 249.74 | 52.66 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 267.79 | 15.23 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 276.61 | 4.98 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 320.44 | 0.33 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 359.53 | 0.15 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 373.59 | 7.61 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 404.65 | 26.52 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 385.48 | 60.44 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 317.12 | 101.41 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 319.29 | 47.34 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 249.74 | 0.15 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 404.65 | 119.38 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 302.67 | 117.95 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 300.38 | 100.73 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 273.33 | 79.22 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 250.15 | 51.52 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 268.46 | 14.68 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 277.46 | 4.66 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 321.33 | 0.30 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 360.48 | 0.13 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 374.25 | 7.25 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 405.01 | 25.76 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 385.87 | 59.42 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 317.57 | 100.18 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 319.88 | 46.55 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 250.15 | 0.13 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 405.01 | 117.95 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 608.51 | 227.44 | 401.21 | 188.63 | 212.59 | 0.00 | 0.00 |
February | 602.99 | 193.35 | 376.76 | 154.11 | 222.65 | 0.00 | 0.00 |
March | 548.19 | 150.18 | 310.09 | 84.19 | 225.90 | 0.00 | 0.00 |
April | 500.48 | 95.63 | 243.75 | 25.84 | 217.91 | 0.00 | 0.00 |
May | 538.43 | 26.23 | 206.48 | 3.16 | 203.32 | 0.00 | 0.00 |
June | 557.08 | 7.61 | 194.46 | 0.24 | 194.22 | 0.00 | 0.00 |
July | 644.14 | 0.46 | 194.45 | 1.65 | 192.80 | 0.00 | 0.00 |
August | 723.31 | 0.15 | 225.55 | 15.98 | 209.57 | 0.00 | 0.00 |
September | 749.85 | 12.57 | 297.39 | 68.15 | 229.23 | 0.00 | 0.00 |
October | 810.01 | 46.87 | 389.34 | 154.78 | 234.55 | 0.00 | 0.00 |
November | 771.40 | 111.81 | 429.52 | 207.06 | 222.46 | 0.00 | 0.00 |
December | 636.81 | 192.64 | 398.72 | 196.96 | 201.77 | 0.00 | 0.00 |
Annual Sum or Average | 641.20 | 88.23 | 305.22 | 91.40 | 213.82 | 0.00 | 0.00 |
Minimum of Months | 500.48 | 0.15 | 194.45 | 0.24 | 192.80 | 0.00 | 0.00 |
Maximum of Months | 810.01 | 227.44 | 429.52 | 207.06 | 234.55 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 303.83 | 113.17 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 301.20 | 95.95 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.17 | 74.09 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 250.90 | 46.66 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 271.46 | 12.39 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 281.70 | 3.34 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 325.79 | 0.19 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 365.53 | 0.04 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 377.45 | 5.75 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 406.17 | 22.24 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 385.97 | 54.64 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.18 | 95.50 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 322.01 | 43.41 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 250.90 | 0.04 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 406.17 | 113.17 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.06 | 112.77 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 301.41 | 95.56 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.37 | 73.72 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 251.10 | 46.36 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 271.72 | 12.26 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 281.99 | 3.27 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 326.08 | 0.19 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 365.81 | 0.04 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 377.69 | 5.69 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 406.34 | 22.09 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.13 | 54.41 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.36 | 95.17 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 322.23 | 43.21 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 251.10 | 0.04 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 406.34 | 112.77 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.52 | 111.82 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 301.82 | 94.63 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.64 | 72.96 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 251.18 | 46.00 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 271.27 | 12.35 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 281.20 | 3.40 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 324.69 | 0.21 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 364.20 | 0.06 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 376.64 | 5.93 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 405.84 | 22.51 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 386.02 | 54.49 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.59 | 94.64 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 321.86 | 43.00 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 251.18 | 0.06 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 405.84 | 111.82 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN RATE [W] | ZONE WINDOWS TOTAL HEAT LOSS RATE [W] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION RATE [W] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION RATE [W] | |
January | 304.87 | 108.77 | 200.61 | 94.31 | 106.29 | 0.00 | 0.00 |
February | 302.02 | 91.38 | 188.38 | 77.06 | 111.32 | 0.00 | 0.00 |
March | 274.24 | 70.49 | 155.04 | 42.09 | 112.95 | 0.00 | 0.00 |
April | 249.46 | 45.35 | 121.88 | 12.92 | 108.96 | 0.00 | 0.00 |
May | 265.93 | 13.24 | 103.24 | 1.58 | 101.66 | 0.00 | 0.00 |
June | 273.74 | 4.32 | 97.23 | 0.12 | 97.11 | 0.00 | 0.00 |
July | 313.66 | 0.42 | 97.23 | 0.83 | 96.40 | 0.00 | 0.00 |
August | 351.74 | 0.21 | 112.77 | 7.99 | 104.78 | 0.00 | 0.00 |
September | 368.14 | 7.73 | 148.69 | 34.08 | 114.62 | 0.00 | 0.00 |
October | 400.84 | 25.70 | 194.67 | 77.39 | 117.28 | 0.00 | 0.00 |
November | 383.49 | 56.34 | 214.76 | 103.53 | 111.23 | 0.00 | 0.00 |
December | 318.19 | 93.46 | 199.36 | 98.48 | 100.88 | 0.00 | 0.00 |
Annual Sum or Average | 317.30 | 42.88 | 152.61 | 45.70 | 106.91 | 0.00 | 0.00 |
Minimum of Months | 249.46 | 0.21 | 97.23 | 0.12 | 96.40 | 0.00 | 0.00 |
Maximum of Months | 400.84 | 108.77 | 214.76 | 103.53 | 117.28 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162780E+10 | 0.611977E+09 | 0.107682E+10 | 0.506262E+09 | 0.570559E+09 | 0.00 | 0.00 |
February | 0.145933E+10 | 0.464723E+09 | 0.913324E+09 | 0.373590E+09 | 0.539735E+09 | 0.00 | 0.00 |
March | 0.147040E+10 | 0.394599E+09 | 0.832247E+09 | 0.225951E+09 | 0.606296E+09 | 0.00 | 0.00 |
April | 0.130925E+10 | 0.231452E+09 | 0.633105E+09 | 67121124.92 | 0.565984E+09 | 0.00 | 0.00 |
May | 0.148483E+10 | 60671703.47 | 0.554171E+09 | 8486581.97 | 0.545685E+09 | 0.00 | 0.00 |
June | 0.149214E+10 | 16582873.56 | 0.505066E+09 | 625038.59 | 0.504441E+09 | 0.00 | 0.00 |
July | 0.179793E+10 | 521868.09 | 0.521888E+09 | 4434454.02 | 0.517453E+09 | 0.00 | 0.00 |
August | 0.199758E+10 | 342894.02 | 0.605348E+09 | 42891373.39 | 0.562457E+09 | 0.00 | 0.00 |
September | 0.199745E+10 | 28991070.05 | 0.772412E+09 | 0.177021E+09 | 0.595391E+09 | 0.00 | 0.00 |
October | 0.220217E+10 | 0.107986E+09 | 0.104495E+10 | 0.415425E+09 | 0.629521E+09 | 0.00 | 0.00 |
November | 0.200647E+10 | 0.271294E+09 | 0.111560E+10 | 0.537803E+09 | 0.577799E+09 | 0.00 | 0.00 |
December | 0.170615E+10 | 0.509154E+09 | 0.107014E+10 | 0.528615E+09 | 0.541522E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.205515E+11 | 0.269830E+10 | 0.964507E+10 | 0.288822E+10 | 0.675684E+10 | 0.00 | 0.00 |
Minimum of Months | 0.130925E+10 | 342894.02 | 0.505066E+09 | 625038.59 | 0.504441E+09 | 0.00 | 0.00 |
Maximum of Months | 0.220217E+10 | 0.611977E+09 | 0.111560E+10 | 0.537803E+09 | 0.629521E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.810118E+09 | 0.311138E+09 | 0.538410E+09 | 0.253131E+09 | 0.285279E+09 | 0.00 | 0.00 |
February | 0.726941E+09 | 0.236849E+09 | 0.456662E+09 | 0.186795E+09 | 0.269867E+09 | 0.00 | 0.00 |
March | 0.734017E+09 | 0.201203E+09 | 0.416124E+09 | 0.112975E+09 | 0.303148E+09 | 0.00 | 0.00 |
April | 0.655925E+09 | 0.118081E+09 | 0.316553E+09 | 33560562.46 | 0.282992E+09 | 0.00 | 0.00 |
May | 0.749566E+09 | 30537233.52 | 0.277086E+09 | 4243290.99 | 0.272842E+09 | 0.00 | 0.00 |
June | 0.756464E+09 | 7810081.17 | 0.252533E+09 | 312519.29 | 0.252221E+09 | 0.00 | 0.00 |
July | 0.913284E+09 | 199838.90 | 0.260944E+09 | 2217227.01 | 0.258727E+09 | 0.00 | 0.00 |
August | 0.101550E+10 | 112020.92 | 0.302674E+09 | 21445686.70 | 0.281228E+09 | 0.00 | 0.00 |
September | 0.100962E+10 | 13505609.36 | 0.386206E+09 | 88510358.30 | 0.297696E+09 | 0.00 | 0.00 |
October | 0.110766E+10 | 52353935.14 | 0.522473E+09 | 0.207712E+09 | 0.314761E+09 | 0.00 | 0.00 |
November | 0.100487E+10 | 0.134734E+09 | 0.557801E+09 | 0.268901E+09 | 0.288899E+09 | 0.00 | 0.00 |
December | 0.851027E+09 | 0.257134E+09 | 0.535068E+09 | 0.264308E+09 | 0.270761E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.103350E+11 | 0.136366E+10 | 0.482253E+10 | 0.144411E+10 | 0.337842E+10 | 0.00 | 0.00 |
Minimum of Months | 0.655925E+09 | 112020.92 | 0.252533E+09 | 312519.29 | 0.252221E+09 | 0.00 | 0.00 |
Maximum of Months | 0.110766E+10 | 0.311138E+09 | 0.557801E+09 | 0.268901E+09 | 0.314761E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.808665E+09 | 0.321138E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.725301E+09 | 0.247570E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.730876E+09 | 0.215593E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.647688E+09 | 0.135068E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.719672E+09 | 38860853.50 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.720434E+09 | 11633019.15 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.864192E+09 | 683748.56 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.968714E+09 | 294892.63 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.971910E+09 | 18219264.20 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108519E+10 | 68030483.79 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.999625E+09 | 0.155064E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.849277E+09 | 0.271868E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100915E+11 | 0.148402E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.647688E+09 | 294892.63 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108519E+10 | 0.321138E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.809139E+09 | 0.319753E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.725526E+09 | 0.246878E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.730913E+09 | 0.215671E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.647321E+09 | 0.136501E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.717261E+09 | 40788004.10 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.716982E+09 | 12898377.97 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.858254E+09 | 885328.68 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.962952E+09 | 413940.45 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.968340E+09 | 19737111.18 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108381E+10 | 71025853.48 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.999177E+09 | 0.156660E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.849384E+09 | 0.271619E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100691E+11 | 0.149283E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.647321E+09 | 413940.45 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108381E+10 | 0.319753E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.810677E+09 | 0.315904E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.726681E+09 | 0.243691E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.732089E+09 | 0.212194E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.648390E+09 | 0.133535E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.719055E+09 | 39323916.20 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.719186E+09 | 12076596.96 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.860643E+09 | 809330.20 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.965515E+09 | 355455.33 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.970050E+09 | 18803876.52 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108479E+10 | 68985739.56 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100017E+10 | 0.154026E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.850585E+09 | 0.268321E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100878E+11 | 0.146803E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.648390E+09 | 355455.33 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108479E+10 | 0.315904E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.162982E+10 | 0.609169E+09 | 0.107461E+10 | 0.505224E+09 | 0.569388E+09 | 0.00 | 0.00 |
February | 0.145875E+10 | 0.467750E+09 | 0.911451E+09 | 0.372823E+09 | 0.538627E+09 | 0.00 | 0.00 |
March | 0.146828E+10 | 0.402243E+09 | 0.830540E+09 | 0.225487E+09 | 0.605053E+09 | 0.00 | 0.00 |
April | 0.129724E+10 | 0.247874E+09 | 0.631806E+09 | 66983427.43 | 0.564823E+09 | 0.00 | 0.00 |
May | 0.144213E+10 | 70260663.70 | 0.553034E+09 | 8469171.94 | 0.544565E+09 | 0.00 | 0.00 |
June | 0.144395E+10 | 19729197.61 | 0.504030E+09 | 623756.33 | 0.503406E+09 | 0.00 | 0.00 |
July | 0.172528E+10 | 1230090.24 | 0.520817E+09 | 4425356.84 | 0.516392E+09 | 0.00 | 0.00 |
August | 0.193731E+10 | 401267.29 | 0.604106E+09 | 42803382.70 | 0.561303E+09 | 0.00 | 0.00 |
September | 0.194360E+10 | 32577261.18 | 0.770827E+09 | 0.176658E+09 | 0.594170E+09 | 0.00 | 0.00 |
October | 0.216952E+10 | 0.125532E+09 | 0.104280E+10 | 0.414573E+09 | 0.628230E+09 | 0.00 | 0.00 |
November | 0.199947E+10 | 0.289818E+09 | 0.111331E+10 | 0.536700E+09 | 0.576613E+09 | 0.00 | 0.00 |
December | 0.170563E+10 | 0.515964E+09 | 0.106794E+10 | 0.527531E+09 | 0.540411E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.202210E+11 | 0.278255E+10 | 0.962528E+10 | 0.288230E+10 | 0.674298E+10 | 0.00 | 0.00 |
Minimum of Months | 0.129724E+10 | 401267.29 | 0.504030E+09 | 623756.33 | 0.503406E+09 | 0.00 | 0.00 |
Maximum of Months | 0.216952E+10 | 0.609169E+09 | 0.111331E+10 | 0.536700E+09 | 0.628230E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.813778E+09 | 0.303111E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.728661E+09 | 0.232132E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.734345E+09 | 0.198442E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.650334E+09 | 0.120949E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.727088E+09 | 33175424.63 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.730156E+09 | 8644476.85 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.872604E+09 | 505732.61 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.979029E+09 | 119003.02 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.978362E+09 | 14895708.50 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108789E+10 | 59572424.95 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100043E+10 | 0.141624E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.852216E+09 | 0.255778E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101549E+11 | 0.136895E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.650334E+09 | 119003.02 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108789E+10 | 0.303111E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.814388E+09 | 0.302042E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.729179E+09 | 0.231179E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.734879E+09 | 0.197443E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.650843E+09 | 0.120172E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.727772E+09 | 32842292.10 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.730921E+09 | 8488669.00 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.873386E+09 | 499101.34 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.979779E+09 | 112628.71 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.978966E+09 | 14742459.26 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108833E+10 | 59166386.35 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100086E+10 | 0.141019E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.852695E+09 | 0.254903E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101620E+11 | 0.136261E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.650843E+09 | 112628.71 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108833E+10 | 0.302042E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.815616E+09 | 0.299495E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.730155E+09 | 0.228934E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.735603E+09 | 0.195411E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.651054E+09 | 0.119242E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.726576E+09 | 33070152.47 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.728873E+09 | 8825655.33 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.869644E+09 | 568963.48 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.975466E+09 | 155170.87 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.976263E+09 | 15360286.43 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.108700E+10 | 60297742.35 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.100055E+10 | 0.141232E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.853318E+09 | 0.253491E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.101501E+11 | 0.135608E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.651054E+09 | 155170.87 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.108700E+10 | 0.299495E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: WindowEnergyZoneSummaryMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE WINDOWS TOTAL HEAT GAIN ENERGY [J] | ZONE WINDOWS TOTAL HEAT LOSS ENERGY [J] | ZONE WINDOWS TOTAL TRANSMITTED SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | ZONE EXTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED DIFFUSE SOLAR RADIATION ENERGY [J] | ZONE INTERIOR WINDOWS TOTAL TRANSMITTED BEAM SOLAR RADIATION ENERGY [J] | |
January | 0.816561E+09 | 0.291339E+09 | 0.537306E+09 | 0.252612E+09 | 0.284694E+09 | 0.00 | 0.00 |
February | 0.730657E+09 | 0.221067E+09 | 0.455725E+09 | 0.186412E+09 | 0.269314E+09 | 0.00 | 0.00 |
March | 0.734521E+09 | 0.188795E+09 | 0.415270E+09 | 0.112744E+09 | 0.302526E+09 | 0.00 | 0.00 |
April | 0.646601E+09 | 0.117539E+09 | 0.315903E+09 | 33491713.71 | 0.282411E+09 | 0.00 | 0.00 |
May | 0.712271E+09 | 35451308.41 | 0.276517E+09 | 4234585.97 | 0.272283E+09 | 0.00 | 0.00 |
June | 0.709536E+09 | 11204036.21 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
July | 0.840112E+09 | 1137241.78 | 0.260409E+09 | 2212678.42 | 0.258196E+09 | 0.00 | 0.00 |
August | 0.942091E+09 | 560081.68 | 0.302053E+09 | 21401691.35 | 0.280652E+09 | 0.00 | 0.00 |
September | 0.954220E+09 | 20046268.85 | 0.385414E+09 | 88328781.27 | 0.297085E+09 | 0.00 | 0.00 |
October | 0.107362E+10 | 68835825.72 | 0.521401E+09 | 0.207286E+09 | 0.314115E+09 | 0.00 | 0.00 |
November | 0.993995E+09 | 0.146025E+09 | 0.556656E+09 | 0.268350E+09 | 0.288307E+09 | 0.00 | 0.00 |
December | 0.852230E+09 | 0.250332E+09 | 0.533971E+09 | 0.263765E+09 | 0.270205E+09 | 0.00 | 0.00 |
Annual Sum or Average | 0.100064E+11 | 0.135233E+10 | 0.481264E+10 | 0.144115E+10 | 0.337149E+10 | 0.00 | 0.00 |
Minimum of Months | 0.646601E+09 | 560081.68 | 0.252015E+09 | 311878.17 | 0.251703E+09 | 0.00 | 0.00 |
Maximum of Months | 0.107362E+10 | 0.291339E+09 | 0.556656E+09 | 0.268350E+09 | 0.314115E+09 | 0.00 | 0.00 |
Report: AverageOutdoorConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE [C] | SITE WIND SPEED [m/s] | SITE SKY TEMPERATURE [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA [W/m2] | SITE RAIN STATUS [] | |
January | 19.24 | 14.74 | 11.63 | 2.95 | 7.91 | 83.00 | 101.34 | 0.00 |
February | 20.75 | 16.26 | 13.46 | 3.66 | 9.80 | 96.50 | 106.33 | 0.00 |
March | 23.12 | 16.75 | 12.67 | 3.48 | 11.63 | 114.51 | 110.36 | 0.00 |
April | 26.49 | 19.17 | 14.91 | 3.36 | 14.65 | 129.52 | 127.73 | 0.00 |
May | 31.37 | 21.91 | 17.14 | 3.30 | 19.37 | 135.62 | 152.47 | 0.00 |
June | 32.97 | 24.78 | 21.39 | 3.95 | 20.59 | 135.23 | 162.31 | 0.00 |
July | 35.08 | 26.48 | 23.16 | 3.85 | 24.14 | 131.49 | 150.69 | 0.00 |
August | 35.31 | 27.02 | 24.10 | 3.89 | 24.33 | 129.32 | 147.63 | 0.00 |
September | 32.49 | 25.68 | 23.13 | 3.64 | 20.59 | 118.70 | 140.92 | 0.00 |
October | 29.53 | 22.66 | 19.34 | 3.16 | 16.84 | 101.82 | 135.23 | 0.00 |
November | 25.53 | 19.62 | 16.50 | 2.98 | 12.88 | 85.82 | 121.41 | 0.00 |
December | 21.13 | 16.84 | 14.23 | 2.84 | 10.14 | 76.46 | 98.30 | 0.00 |
Annual Sum or Average | 27.79 | 21.02 | 17.66 | 3.42 | 16.11 | 111.56 | 129.66 | 0.00 |
Minimum of Months | 19.24 | 14.74 | 11.63 | 2.84 | 7.91 | 76.46 | 98.30 | 0.00 |
Maximum of Months | 35.31 | 27.02 | 24.10 | 3.95 | 24.33 | 135.62 | 162.31 | 0.00 |
Report: OutdoorConditionsMaximumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 28.00 | 23-JAN-13:00 | 16.55 | 9.00 | 4.60 | 16.85 | 268.00 | 249.50 |
February | 32.50 | 06-FEB-14:00 | 17.28 | 6.50 | 6.20 | 21.27 | 242.00 | 327.50 |
March | 38.00 | 27-MAR-10:00 | 18.84 | 6.00 | 7.70 | 21.44 | 329.50 | 440.00 |
April | 42.00 | 28-APR-11:00 | 19.18 | 2.00 | 2.60 | 24.16 | 371.50 | 432.50 |
May | 42.10 | 31-MAY-18:00 | 20.76 | 8.00 | 5.10 | 30.18 | 0.00 | 0.00 |
June | 43.00 | 12-JUN-11:00 | 24.56 | 17.00 | 3.60 | 28.91 | 372.00 | 427.00 |
July | 46.00 | 21-JUL-11:00 | 22.01 | 9.00 | 3.60 | 32.99 | 306.00 | 562.50 |
August | 46.00 | 16-AUG-11:00 | 25.38 | 17.00 | 7.20 | 31.75 | 273.00 | 629.50 |
September | 41.20 | 26-SEP-12:00 | 22.43 | 13.00 | 4.10 | 26.15 | 325.00 | 455.00 |
October | 38.00 | 04-OCT-11:00 | 19.81 | 9.00 | 1.00 | 22.13 | 338.00 | 421.50 |
November | 34.00 | 05-NOV-11:00 | 17.15 | 5.00 | 2.10 | 17.39 | 294.00 | 427.50 |
December | 30.00 | 10-DEC-11:00 | 19.04 | 13.00 | 4.10 | 21.27 | 305.00 | 214.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 28.00 | 16.55 | 2.00 | 1.00 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 46.00 | 25.38 | 17.00 | 7.70 | 32.99 | 372.00 | 629.50 |
Report: OutdoorConditionsMinimumDryBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DRYBULB TEMPERATURE {MINIMUM} [C] | SITE OUTDOOR AIR DRYBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 12.00 | 09-JAN-07:00 | 12.00 | 12.00 | 1.00 | -1.9 | 54.50 | 10.00 |
February | 13.00 | 01-FEB-04:00 | 12.45 | 12.00 | 1.00 | -0.8 | 0.00 | 0.00 |
March | 14.00 | 07-MAR-05:00 | 11.74 | 10.00 | 0.50 | 2.64 | 0.00 | 0.00 |
April | 17.00 | 01-APR-05:00 | 15.74 | 15.00 | 0.50 | 3.69 | 0.00 | 0.00 |
May | 20.40 | 01-MAY-05:00 | 20.40 | 20.40 | 2.10 | 9.33 | 28.50 | 50.50 |
June | 21.00 | 22-JUN-07:00 | 19.59 | 19.00 | 1.50 | 8.35 | 206.50 | 266.00 |
July | 28.00 | 03-JUL-05:00 | 16.06 | 8.00 | 1.00 | 12.41 | 32.50 | 30.50 |
August | 28.80 | 31-AUG-03:00 | 25.95 | 25.00 | 1.50 | 17.03 | 0.00 | 0.00 |
September | 23.00 | 25-SEP-04:00 | 22.27 | 22.00 | 2.10 | 10.88 | 0.00 | 0.00 |
October | 20.60 | 29-OCT-06:00 | 17.24 | 15.40 | 0.50 | 7.15 | 49.50 | 123.00 |
November | 16.90 | 22-NOV-06:00 | 14.44 | 12.90 | 3.10 | 3.06 | 31.00 | 106.50 |
December | 13.00 | 18-DEC-04:00 | 10.82 | 9.00 | 1.80 | -1.4 | 0.00 | 0.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 12.00 | 10.82 | 8.00 | 0.50 | -1.9 | 0.00 | 0.00 | |
Maximum of Months | 28.80 | 25.95 | 25.00 | 3.10 | 17.03 | 206.50 | 266.00 |
Report: OutdoorConditionsMaximumWetBulbMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR WETBULB TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.89 | 30-JAN-13:00 | 23.00 | 20.00 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 23.21 | 07-FEB-15:00 | 28.00 | 21.30 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 23.05 | 28-MAR-10:00 | 28.00 | 21.00 | 7.20 | 23.82 | 374.50 | 58.00 |
April | 26.40 | 30-APR-14:00 | 31.00 | 25.00 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 29.11 | 29-MAY-12:00 | 33.40 | 27.90 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 29.09 | 04-JUN-18:00 | 33.20 | 28.00 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.86 | 18-JUL-20:00 | 34.00 | 30.00 | 3.60 | 26.32 | 0.00 | 0.00 |
August | 31.14 | 22-AUG-16:00 | 36.00 | 30.00 | 9.30 | 25.16 | 159.00 | 168.50 |
September | 30.39 | 09-SEP-13:00 | 36.00 | 29.00 | 5.70 | 28.11 | 339.50 | 377.00 |
October | 30.18 | 07-OCT-09:00 | 30.60 | 30.10 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 26.24 | 01-NOV-13:00 | 33.00 | 24.00 | 6.20 | 20.92 | 269.00 | 349.50 |
December | 23.18 | 05-DEC-14:00 | 26.00 | 22.00 | 4.60 | 16.85 | 185.00 | 295.00 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.89 | 23.00 | 20.00 | 3.60 | 16.85 | 0.00 | 0.00 | |
Maximum of Months | 31.14 | 36.00 | 30.10 | 9.30 | 28.11 | 421.00 | 377.00 |
Report: OutdoorConditionsMaximumDewPointMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE OUTDOOR AIR DEWPOINT TEMPERATURE {Maximum} [C] | SITE OUTDOOR AIR DEWPOINT TEMPERATURE {TIMESTAMP} | SITE OUTDOOR AIR DRYBULB TEMPERATURE {AT MAX/MIN} [C] | SITE OUTDOOR AIR WETBULB TEMPERATURE {AT MAX/MIN} [C] | SITE WIND SPEED {AT MAX/MIN} [m/s] | SITE SKY TEMPERATURE {AT MAX/MIN} [C] | SITE DIFFUSE SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | SITE DIRECT SOLAR RADIATION RATE PER AREA {AT MAX/MIN} [W/m2] | |
January | 20.00 | 30-JAN-13:00 | 23.00 | 20.89 | 3.60 | 18.82 | 266.50 | 27.50 |
February | 21.30 | 07-FEB-15:00 | 28.00 | 23.21 | 6.20 | 18.64 | 178.50 | 219.50 |
March | 22.00 | 31-MAR-09:00 | 23.00 | 22.27 | 0.50 | 10.88 | 323.50 | 305.50 |
April | 25.00 | 30-APR-14:00 | 31.00 | 26.40 | 8.70 | 22.98 | 350.50 | 184.00 |
May | 27.90 | 29-MAY-12:00 | 33.40 | 29.11 | 7.70 | 22.13 | 421.00 | 303.50 |
June | 28.00 | 04-JUN-18:00 | 33.20 | 29.09 | 4.10 | 21.96 | 16.50 | 15.50 |
July | 30.00 | 19-JUL-23:19 | 34.00 | 30.86 | 0.83 | 25.33 | 0.00 | 0.00 |
August | 30.00 | 07-AUG-23:19 | 33.00 | 30.56 | 3.43 | 22.30 | 0.00 | 0.00 |
September | 29.00 | 08-SEP-07:00 | 31.00 | 29.41 | 1.50 | 24.33 | 179.00 | 151.00 |
October | 30.10 | 07-OCT-09:00 | 30.60 | 30.18 | 4.60 | 19.87 | 295.50 | 353.00 |
November | 24.00 | 01-NOV-10:00 | 32.00 | 26.10 | 3.10 | 20.05 | 300.50 | 377.00 |
December | 23.00 | 25-DEC-10:00 | 23.00 | 23.00 | 0.80 | 14.10 | 245.00 | 376.50 |
Annual Sum or Average | ||||||||
Minimum of Months | 20.00 | 23.00 | 20.89 | 0.50 | 10.88 | 0.00 | 0.00 | |
Maximum of Months | 30.10 | 34.00 | 30.86 | 8.70 | 25.33 | 421.00 | 377.00 |
Report: OutdoorGroundConditionsMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE GROUND TEMPERATURE [C] | SITE SURFACE GROUND TEMPERATURE [C] | SITE DEEP GROUND TEMPERATURE [C] | SITE MAINS WATER TEMPERATURE [C] | SITE GROUND REFLECTED SOLAR RADIATION RATE PER AREA [W/m2] | SITE SNOW ON GROUND STATUS [] | |
January | 18.00 | 13.00 | 16.00 | 24.90 | 26.90 | 0.00 |
February | 18.00 | 13.00 | 16.00 | 25.87 | 32.18 | 0.00 |
March | 18.00 | 13.00 | 16.00 | 28.18 | 38.22 | 0.00 |
April | 18.00 | 13.00 | 16.00 | 31.32 | 44.91 | 0.00 |
May | 18.00 | 13.00 | 16.00 | 34.39 | 50.41 | 0.00 |
June | 18.00 | 13.00 | 16.00 | 36.58 | 52.39 | 0.00 |
July | 18.00 | 13.00 | 16.00 | 37.28 | 50.68 | 0.00 |
August | 18.00 | 13.00 | 16.00 | 36.29 | 48.56 | 0.00 |
September | 18.00 | 13.00 | 16.00 | 33.90 | 43.99 | 0.00 |
October | 18.00 | 13.00 | 16.00 | 30.75 | 37.43 | 0.00 |
November | 18.00 | 13.00 | 16.00 | 27.69 | 30.34 | 0.00 |
December | 18.00 | 13.00 | 16.00 | 25.55 | 25.09 | 0.00 |
Annual Sum or Average | 18.00 | 13.00 | 16.00 | 31.09 | 40.13 | 0.00 |
Minimum of Months | 18.00 | 13.00 | 16.00 | 24.90 | 25.09 | 0.00 |
Maximum of Months | 18.00 | 13.00 | 16.00 | 37.28 | 52.39 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.280275E+09 | -167381152.4 | 0.00 | 0.00 | 744.00 | 0.00 | -112894187.0 | 58.99 | 0.00 | 0.00 |
February | 0.249442E+09 | -147679704.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101762503.8 | 58.99 | 0.00 | 0.00 |
March | 0.266846E+09 | -154575095.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112270502.6 | 58.99 | 0.00 | 0.00 |
April | 0.240838E+09 | -132641813.1 | 0.00 | 0.00 | 720.00 | 0.00 | -108195993.3 | 58.99 | 0.00 | 0.00 |
May | 0.232865E+09 | -122088584.4 | 0.00 | 0.00 | 744.00 | 0.00 | -110776746.2 | 58.99 | 0.00 | 0.00 |
June | 0.215423E+09 | -108678946.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106744374.3 | 58.99 | 0.00 | 0.00 |
July | 0.216325E+09 | -106575340.9 | 0.00 | 0.00 | 744.00 | 0.00 | -109749889.7 | 58.99 | 0.00 | 0.00 |
August | 0.223320E+09 | -113792309.0 | 0.00 | 0.00 | 744.00 | 0.00 | -109528078.6 | 58.99 | 0.00 | 0.00 |
September | 0.226957E+09 | -120412913.6 | 0.00 | 0.00 | 720.00 | 0.00 | -106544498.8 | 58.99 | 0.00 | 0.00 |
October | 0.249307E+09 | -138703136.7 | 0.00 | 0.00 | 744.00 | 0.00 | -110603583.3 | 58.99 | 0.00 | 0.00 |
November | 0.256091E+09 | -148290845.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107800152.5 | 58.99 | 0.00 | 0.00 |
December | 0.276739E+09 | -164404283.0 | 0.00 | 0.00 | 744.00 | 0.00 | -112334369.4 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293443E+10 | -0.162522E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130920E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215423E+09 | -167381152.4 | 0.00 | 0.00 | 672.00 | 0.00 | -112894187.0 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.280275E+09 | -106575340.9 | 0.00 | 0.00 | 744.00 | 0.00 | -101762503.8 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.279920E+09 | -167381021.2 | 0.00 | 0.00 | 744.00 | 0.00 | -112538567.1 | 58.99 | 0.00 | 0.00 |
February | 0.249138E+09 | -147690789.7 | 0.00 | 0.00 | 672.00 | 0.00 | -101447246.4 | 58.99 | 0.00 | 0.00 |
March | 0.266553E+09 | -154556158.2 | 0.00 | 0.00 | 744.00 | 0.00 | -111996799.4 | 58.99 | 0.00 | 0.00 |
April | 0.240615E+09 | -132642403.3 | 0.00 | 0.00 | 720.00 | 0.00 | -107972601.2 | 58.99 | 0.00 | 0.00 |
May | 0.232812E+09 | -122086707.1 | 0.00 | 0.00 | 744.00 | 0.00 | -110725184.2 | 58.99 | 0.00 | 0.00 |
June | 0.215480E+09 | -108680249.1 | 0.00 | 0.00 | 720.00 | 0.00 | -106799474.0 | 58.99 | 0.00 | 0.00 |
July | 0.216490E+09 | -106569044.8 | 0.00 | 0.00 | 744.00 | 0.00 | -109920790.4 | 58.99 | 0.00 | 0.00 |
August | 0.223553E+09 | -113797111.1 | 0.00 | 0.00 | 744.00 | 0.00 | -109756367.3 | 58.99 | 0.00 | 0.00 |
September | 0.227081E+09 | -120425085.3 | 0.00 | 0.00 | 720.00 | 0.00 | -106655669.1 | 58.99 | 0.00 | 0.00 |
October | 0.249338E+09 | -138698801.9 | 0.00 | 0.00 | 744.00 | 0.00 | -110638783.4 | 58.99 | 0.00 | 0.00 |
November | 0.256014E+09 | -148299701.8 | 0.00 | 0.00 | 720.00 | 0.00 | -107714612.9 | 58.99 | 0.00 | 0.00 |
December | 0.276488E+09 | -164398914.9 | 0.00 | 0.00 | 744.00 | 0.00 | -112088742.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.293348E+10 | -0.162523E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.130825E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.215480E+09 | -167381021.2 | 0.00 | 0.00 | 672.00 | 0.00 | -112538567.1 | 58.99 | 0.00 | 0.00 |
Maximum of Months | 0.279920E+09 | -106569044.8 | 0.00 | 0.00 | 744.00 | 0.00 | -101447246.4 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.258809E+09 | -147182900.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111626076.0 | 58.99 | 0.00 | 0.00 |
February | 0.230454E+09 | -129975737.1 | 0.00 | 0.00 | 672.00 | 0.00 | -100477807.9 | 58.99 | 0.00 | 0.00 |
March | 0.248541E+09 | -137939769.3 | 0.00 | 0.00 | 744.00 | 0.00 | -110601353.5 | 58.99 | 0.00 | 0.00 |
April | 0.222630E+09 | -116670528.7 | 0.00 | 0.00 | 720.00 | 0.00 | -105959637.7 | 58.98 | 0.00 | 0.00 |
May | 0.216266E+09 | -108356150.7 | 0.00 | 0.00 | 744.00 | 0.00 | -107909570.5 | 58.98 | 0.00 | 0.00 |
June | 0.200768E+09 | -96800588.5 | 0.00 | 0.00 | 720.00 | 0.00 | -103967353.8 | 58.99 | 0.00 | 0.00 |
July | 0.199685E+09 | -93181329.4 | 0.00 | 0.00 | 744.00 | 0.00 | -106503569.5 | 58.99 | 0.00 | 0.00 |
August | 0.208168E+09 | -101615897.8 | 0.00 | 0.00 | 744.00 | 0.00 | -106552297.8 | 58.99 | 0.00 | 0.00 |
September | 0.209552E+09 | -105937053.3 | 0.00 | 0.00 | 720.00 | 0.00 | -103614873.8 | 58.97 | 0.00 | 0.00 |
October | 0.229862E+09 | -122004342.4 | 0.00 | 0.00 | 744.00 | 0.00 | -107857562.9 | 58.99 | 0.00 | 0.00 |
November | 0.236667E+09 | -130922849.6 | 0.00 | 0.00 | 720.00 | 0.00 | -105744357.8 | 58.99 | 0.00 | 0.00 |
December | 0.254302E+09 | -143543800.5 | 0.00 | 0.00 | 744.00 | 0.00 | -110758598.1 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.271570E+10 | -0.143413E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128157E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.199685E+09 | -147182900.4 | 0.00 | 0.00 | 672.00 | 0.00 | -111626076.0 | 58.97 | 0.00 | 0.00 |
Maximum of Months | 0.258809E+09 | -93181329.4 | 0.00 | 0.00 | 744.00 | 0.00 | -100477807.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.258881E+09 | -147181290.6 | 0.00 | 0.00 | 744.00 | 0.00 | -111699980.9 | 59.00 | 0.00 | 0.00 |
February | 0.230488E+09 | -129955786.4 | 0.00 | 0.00 | 672.00 | 0.00 | -100531798.2 | 59.00 | 0.00 | 0.00 |
March | 0.248533E+09 | -137934908.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110598587.5 | 58.99 | 0.00 | 0.00 |
April | 0.222549E+09 | -116672182.3 | 0.00 | 0.00 | 720.00 | 0.00 | -105877108.1 | 58.98 | 0.00 | 0.00 |
May | 0.216078E+09 | -108362372.3 | 0.00 | 0.00 | 744.00 | 0.00 | -107715602.7 | 58.98 | 0.00 | 0.00 |
June | 0.200563E+09 | -96779550.9 | 0.00 | 0.00 | 720.00 | 0.00 | -103783798.9 | 58.99 | 0.00 | 0.00 |
July | 0.199409E+09 | -93162112.3 | 0.00 | 0.00 | 744.00 | 0.00 | -106246696.7 | 58.99 | 0.00 | 0.00 |
August | 0.207937E+09 | -101657013.9 | 0.00 | 0.00 | 744.00 | 0.00 | -106280242.1 | 58.99 | 0.00 | 0.00 |
September | 0.209312E+09 | -105908199.7 | 0.00 | 0.00 | 720.00 | 0.00 | -103403479.8 | 58.98 | 0.00 | 0.00 |
October | 0.229674E+09 | -122004172.9 | 0.00 | 0.00 | 744.00 | 0.00 | -107669998.5 | 58.99 | 0.00 | 0.00 |
November | 0.236577E+09 | -130927225.4 | 0.00 | 0.00 | 720.00 | 0.00 | -105649533.5 | 58.99 | 0.00 | 0.00 |
December | 0.254320E+09 | -143547731.6 | 0.00 | 0.00 | 744.00 | 0.00 | -110771990.8 | 58.98 | 0.00 | 0.00 |
Annual Sum or Average | 0.271432E+10 | -0.143409E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128023E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.199409E+09 | -147181290.6 | 0.00 | 0.00 | 672.00 | 0.00 | -111699980.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.258881E+09 | -93162112.3 | 0.00 | 0.00 | 744.00 | 0.00 | -100531798.2 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.251725E+09 | -139116434.3 | 0.00 | 0.00 | 744.00 | 0.00 | -112608968.9 | 58.99 | 0.00 | 0.00 |
February | 0.224191E+09 | -122917490.9 | 0.00 | 0.00 | 672.00 | 0.00 | -101273713.9 | 58.99 | 0.00 | 0.00 |
March | 0.242011E+09 | -130501183.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111510192.3 | 58.99 | 0.00 | 0.00 |
April | 0.217084E+09 | -110369936.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106714013.0 | 58.99 | 0.00 | 0.00 |
May | 0.210978E+09 | -102446418.7 | 0.00 | 0.00 | 744.00 | 0.00 | -108531168.1 | 58.99 | 0.00 | 0.00 |
June | 0.196081E+09 | -91559727.0 | 0.00 | 0.00 | 720.00 | 0.00 | -104521712.2 | 58.99 | 0.00 | 0.00 |
July | 0.194910E+09 | -88095384.0 | 0.00 | 0.00 | 744.00 | 0.00 | -106814202.1 | 58.99 | 0.00 | 0.00 |
August | 0.203116E+09 | -96192562.9 | 0.00 | 0.00 | 744.00 | 0.00 | -106923128.2 | 58.98 | 0.00 | 0.00 |
September | 0.204244E+09 | -100200334.3 | 0.00 | 0.00 | 720.00 | 0.00 | -104043282.9 | 58.99 | 0.00 | 0.00 |
October | 0.223662E+09 | -115327669.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108334596.3 | 58.99 | 0.00 | 0.00 |
November | 0.230023E+09 | -123655705.7 | 0.00 | 0.00 | 720.00 | 0.00 | -106367377.0 | 58.99 | 0.00 | 0.00 |
December | 0.247318E+09 | -135732540.3 | 0.00 | 0.00 | 744.00 | 0.00 | -111585747.6 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264534E+10 | -0.135612E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.128923E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.194910E+09 | -139116434.3 | 0.00 | 0.00 | 672.00 | 0.00 | -112608968.9 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.251725E+09 | -88095384.0 | 0.00 | 0.00 | 744.00 | 0.00 | -101273713.9 | 58.99 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.251781E+09 | -139117108.5 | 0.00 | 0.00 | 744.00 | 0.00 | -112664263.5 | 58.99 | 0.00 | 0.00 |
February | 0.224254E+09 | -122923431.9 | 0.00 | 0.00 | 672.00 | 0.00 | -101330737.0 | 58.99 | 0.00 | 0.00 |
March | 0.242103E+09 | -130508865.5 | 0.00 | 0.00 | 744.00 | 0.00 | -111593749.1 | 58.99 | 0.00 | 0.00 |
April | 0.217204E+09 | -110376336.4 | 0.00 | 0.00 | 720.00 | 0.00 | -106827180.8 | 58.99 | 0.00 | 0.00 |
May | 0.211130E+09 | -102458414.4 | 0.00 | 0.00 | 744.00 | 0.00 | -108671753.0 | 58.98 | 0.00 | 0.00 |
June | 0.196277E+09 | -91601604.2 | 0.00 | 0.00 | 720.00 | 0.00 | -104675765.0 | 58.99 | 0.00 | 0.00 |
July | 0.195138E+09 | -88127417.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107010525.1 | 58.99 | 0.00 | 0.00 |
August | 0.203343E+09 | -96198817.5 | 0.00 | 0.00 | 744.00 | 0.00 | -107143916.4 | 58.98 | 0.00 | 0.00 |
September | 0.204433E+09 | -100191574.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104241731.6 | 58.99 | 0.00 | 0.00 |
October | 0.223822E+09 | -115323141.8 | 0.00 | 0.00 | 744.00 | 0.00 | -108498799.0 | 58.99 | 0.00 | 0.00 |
November | 0.230144E+09 | -123656085.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106488409.2 | 58.99 | 0.00 | 0.00 |
December | 0.247404E+09 | -135708005.1 | 0.00 | 0.00 | 744.00 | 0.00 | -111695746.3 | 59.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.264703E+10 | -0.135619E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129084E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195138E+09 | -139117108.5 | 0.00 | 0.00 | 672.00 | 0.00 | -112664263.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.251781E+09 | -88127417.6 | 0.00 | 0.00 | 744.00 | 0.00 | -101330737.0 | 59.00 | 0.00 | 0.00 |
Report: WaterHeaterReportMonthly
For: GAS TANK7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportWATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY [J] | WATER HEATER USE SIDE HEAT TRANSFER ENERGY [J] | WATER HEATER BURNER HEATING ENERGY [] | WATER HEATER GAS CONSUMPTION [] | WATER HEATER TOTAL DEMAND HEAT TRANSFER ENERGY {HOURS NON-ZERO} [HOURS] | WATER HEATER LOSS DEMAND ENERGY [] | WATER HEATER HEAT LOSS ENERGY [J] | WATER HEATER TANK TEMPERATURE [C] | WATER HEATER HEAT RECOVERY SUPPLY ENERGY [] | WATER HEATER SOURCE ENERGY [] | |
January | 0.251839E+09 | -139115591.8 | 0.00 | 0.00 | 744.00 | 0.00 | -112723808.5 | 58.99 | 0.00 | 0.00 |
February | 0.224305E+09 | -122926233.6 | 0.00 | 0.00 | 672.00 | 0.00 | -101378720.7 | 58.99 | 0.00 | 0.00 |
March | 0.242153E+09 | -130513729.4 | 0.00 | 0.00 | 744.00 | 0.00 | -111639421.4 | 58.99 | 0.00 | 0.00 |
April | 0.217255E+09 | -110390246.0 | 0.00 | 0.00 | 720.00 | 0.00 | -106865001.5 | 58.99 | 0.00 | 0.00 |
May | 0.211163E+09 | -102434848.2 | 0.00 | 0.00 | 744.00 | 0.00 | -108728313.7 | 58.99 | 0.00 | 0.00 |
June | 0.196296E+09 | -91578786.8 | 0.00 | 0.00 | 720.00 | 0.00 | -104717565.4 | 58.99 | 0.00 | 0.00 |
July | 0.195152E+09 | -88104850.2 | 0.00 | 0.00 | 744.00 | 0.00 | -107047093.8 | 58.99 | 0.00 | 0.00 |
August | 0.203366E+09 | -96186415.6 | 0.00 | 0.00 | 744.00 | 0.00 | -107179611.3 | 58.99 | 0.00 | 0.00 |
September | 0.204450E+09 | -100226269.7 | 0.00 | 0.00 | 720.00 | 0.00 | -104223785.7 | 58.98 | 0.00 | 0.00 |
October | 0.223854E+09 | -115329488.0 | 0.00 | 0.00 | 744.00 | 0.00 | -108524737.3 | 58.99 | 0.00 | 0.00 |
November | 0.230189E+09 | -123664069.8 | 0.00 | 0.00 | 720.00 | 0.00 | -106525316.8 | 58.99 | 0.00 | 0.00 |
December | 0.247443E+09 | -135724021.9 | 0.00 | 0.00 | 744.00 | 0.00 | -111719352.2 | 58.99 | 0.00 | 0.00 |
Annual Sum or Average | 0.264747E+10 | -0.135619E+10 | 0.00 | 0.00 | 8760.00 | 0.00 | -0.129127E+10 | 58.99 | 0.00 | 0.00 |
Minimum of Months | 0.195152E+09 | -139115591.8 | 0.00 | 0.00 | 672.00 | 0.00 | -112723808.5 | 58.98 | 0.00 | 0.00 |
Maximum of Months | 0.251839E+09 | -88104850.2 | 0.00 | 0.00 | 744.00 | 0.00 | -101378720.7 | 58.99 | 0.00 | 0.00 |
Report: DaylightingReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE EXTERIOR BEAM NORMAL ILLUMINANCE {HOURS NON-ZERO} [HOURS] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING LIGHTING POWER MULTIPLIER [] | DAYLIGHTING REFERENCE POINT 1 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 1 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 1 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 ILLUMINANCE [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX [] | DAYLIGHTING REFERENCE POINT 2 GLARE INDEX SETPOINT EXCEEDED TIME [] | DAYLIGHTING REFERENCE POINT 2 DAYLIGHT ILLUMINANCE SETPOINT EXCEEDED TIME [] | |
January | 325.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 357.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 375.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 403.50 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 405.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 395.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 358.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 351.17 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 318.83 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 319.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 4323.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 308.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 405.33 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 HEATING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [J] | HEATING COIL HEATING RATE {Maximum} [W] | HEATING COIL HEATING RATE {TIMESTAMP} | COOLING COIL TOTAL COOLING ENERGY [] | COOLING COIL SENSIBLE COOLING ENERGY [] | COOLING COIL TOTAL COOLING RATE [] | COOLING COIL SENSIBLE COOLING RATE [] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 01-JAN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 01-FEB-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 01-MAR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 01-APR-00:05 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 01-MAY-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 01-JUN-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 01-JUL-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 01-AUG-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 01-SEP-00:03 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 01-OCT-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 01-NOV-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 01-DEC-00:10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | ||
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_1:1 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.183391E+11 | 0.146271E+11 | 80652.38 | 30-JAN-09:02 | 53237.36 | 0.00 |
February | 0.00 | 0.00 | 0.201016E+11 | 0.156310E+11 | 81793.02 | 09-FEB-09:02 | 51724.20 | 0.00 |
March | 0.00 | 0.00 | 0.265839E+11 | 0.214441E+11 | 82080.51 | 29-MAR-08:62 | 48088.46 | 0.00 |
April | 0.00 | 0.00 | 0.352982E+11 | 0.275031E+11 | 82626.05 | 30-APR-07:02 | 45799.52 | 0.00 |
May | 0.00 | 0.00 | 0.502090E+11 | 0.386396E+11 | 85326.59 | 30-MAY-08:61 | 42934.61 | 0.00 |
June | 0.00 | 0.00 | 0.600016E+11 | 0.409743E+11 | 86897.15 | 08-JUN-08:61 | 38065.24 | 0.00 |
July | 0.00 | 0.00 | 0.710717E+11 | 0.467082E+11 | 86153.62 | 02-JUL-07:01 | 41831.88 | 0.00 |
August | 0.00 | 0.00 | 0.747730E+11 | 0.479709E+11 | 86132.02 | 08-AUG-07:01 | 29271.17 | 0.00 |
September | 0.00 | 0.00 | 0.643138E+11 | 0.415023E+11 | 86673.51 | 23-SEP-08:61 | 39266.06 | 0.00 |
October | 0.00 | 0.00 | 0.517548E+11 | 0.370077E+11 | 86858.03 | 07-OCT-08:61 | 38441.00 | 0.00 |
November | 0.00 | 0.00 | 0.371127E+11 | 0.275923E+11 | 84064.13 | 03-NOV-08:61 | 47141.92 | 0.00 |
December | 0.00 | 0.00 | 0.249507E+11 | 0.187234E+11 | 81794.17 | 06-DEC-09:02 | 49429.67 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.534510E+12 | 0.378324E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.183391E+11 | 0.146271E+11 | 80652.38 | 29271.17 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.747730E+11 | 0.479709E+11 | 86897.15 | 53237.36 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_2:2 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.976240E+10 | 0.792062E+10 | 40013.32 | 30-JAN-09:02 | 29152.17 | 0.00 |
February | 0.00 | 0.00 | 0.104403E+11 | 0.828238E+10 | 40843.94 | 09-FEB-09:02 | 27569.85 | 0.00 |
March | 0.00 | 0.00 | 0.134346E+11 | 0.110222E+11 | 40815.62 | 29-MAR-08:62 | 26438.42 | 0.00 |
April | 0.00 | 0.00 | 0.171340E+11 | 0.136670E+11 | 41143.19 | 18-APR-08:61 | 26962.88 | 0.00 |
May | 0.00 | 0.00 | 0.237036E+11 | 0.186654E+11 | 41993.05 | 30-MAY-08:61 | 24344.82 | 0.00 |
June | 0.00 | 0.00 | 0.279223E+11 | 0.196542E+11 | 43024.93 | 08-JUN-08:61 | 21870.99 | 0.00 |
July | 0.00 | 0.00 | 0.329193E+11 | 0.221757E+11 | 43273.62 | 26-JUL-08:61 | 20778.71 | 0.00 |
August | 0.00 | 0.00 | 0.346657E+11 | 0.227444E+11 | 43453.76 | 08-AUG-07:01 | 20304.98 | 0.00 |
September | 0.00 | 0.00 | 0.297264E+11 | 0.197861E+11 | 43393.41 | 11-SEP-08:61 | 20824.84 | 0.00 |
October | 0.00 | 0.00 | 0.242603E+11 | 0.178244E+11 | 42850.37 | 07-OCT-08:61 | 22429.94 | 0.00 |
November | 0.00 | 0.00 | 0.179695E+11 | 0.135952E+11 | 41636.41 | 01-NOV-08:61 | 25918.08 | 0.00 |
December | 0.00 | 0.00 | 0.126837E+11 | 0.973508E+10 | 40624.72 | 06-DEC-09:02 | 27172.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.254622E+12 | 0.185073E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.976240E+10 | 0.792062E+10 | 40013.32 | 20304.98 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.346657E+11 | 0.227444E+11 | 43453.76 | 29152.17 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_3:3 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.704760E+10 | 0.568195E+10 | 40217.75 | 29-JAN-09:02 | 28696.64 | 0.00 |
February | 0.00 | 0.00 | 0.789557E+10 | 0.623232E+10 | 41414.46 | 09-FEB-08:62 | 25417.48 | 0.00 |
March | 0.00 | 0.00 | 0.106133E+11 | 0.871164E+10 | 41544.24 | 29-MAR-07:02 | 23700.62 | 0.00 |
April | 0.00 | 0.00 | 0.137718E+11 | 0.109997E+11 | 42498.20 | 30-APR-08:61 | 22656.70 | 0.00 |
May | 0.00 | 0.00 | 0.197941E+11 | 0.155181E+11 | 43141.93 | 30-MAY-07:01 | 21381.34 | 0.00 |
June | 0.00 | 0.00 | 0.236430E+11 | 0.164932E+11 | 43805.60 | 08-JUN-07:01 | 19326.00 | 0.00 |
July | 0.00 | 0.00 | 0.279371E+11 | 0.184024E+11 | 43397.93 | 02-JUL-07:01 | 18682.32 | 0.00 |
August | 0.00 | 0.00 | 0.299669E+11 | 0.192276E+11 | 43397.93 | 21-AUG-06:03 | 16463.52 | 0.00 |
September | 0.00 | 0.00 | 0.249626E+11 | 0.163796E+11 | 43697.20 | 28-SEP-07:01 | 19002.11 | 0.00 |
October | 0.00 | 0.00 | 0.201436E+11 | 0.145542E+11 | 43768.10 | 07-OCT-07:01 | 19361.91 | 0.00 |
November | 0.00 | 0.00 | 0.147202E+11 | 0.109380E+11 | 42557.16 | 03-NOV-07:01 | 22943.96 | 0.00 |
December | 0.00 | 0.00 | 0.965460E+10 | 0.732743E+10 | 40755.66 | 11-DEC-08:62 | 27310.69 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.210150E+12 | 0.150466E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.704760E+10 | 0.568195E+10 | 40217.75 | 16463.52 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.299669E+11 | 0.192276E+11 | 43805.60 | 28696.64 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_4:4 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.699148E+10 | 0.563416E+10 | 40275.37 | 29-JAN-09:02 | 28733.37 | 0.00 |
February | 0.00 | 0.00 | 0.786392E+10 | 0.620661E+10 | 41478.89 | 09-FEB-08:62 | 25469.47 | 0.00 |
March | 0.00 | 0.00 | 0.106074E+11 | 0.870723E+10 | 41612.30 | 29-MAR-07:02 | 23777.10 | 0.00 |
April | 0.00 | 0.00 | 0.138135E+11 | 0.110370E+11 | 42573.35 | 30-APR-08:61 | 22783.51 | 0.00 |
May | 0.00 | 0.00 | 0.199224E+11 | 0.156302E+11 | 43138.49 | 30-MAY-07:01 | 21599.01 | 0.00 |
June | 0.00 | 0.00 | 0.237965E+11 | 0.166199E+11 | 43853.91 | 08-JUN-07:01 | 19356.43 | 0.00 |
July | 0.00 | 0.00 | 0.281348E+11 | 0.185666E+11 | 43463.09 | 02-JUL-07:01 | 18870.13 | 0.00 |
August | 0.00 | 0.00 | 0.301582E+11 | 0.193852E+11 | 43463.09 | 21-AUG-06:03 | 16773.46 | 0.00 |
September | 0.00 | 0.00 | 0.251299E+11 | 0.165155E+11 | 43762.80 | 28-SEP-07:01 | 19109.66 | 0.00 |
October | 0.00 | 0.00 | 0.202843E+11 | 0.146702E+11 | 43802.31 | 07-OCT-07:01 | 19486.83 | 0.00 |
November | 0.00 | 0.00 | 0.147731E+11 | 0.109837E+11 | 42601.95 | 03-NOV-07:01 | 23040.04 | 0.00 |
December | 0.00 | 0.00 | 0.963785E+10 | 0.731434E+10 | 40822.24 | 11-DEC-08:62 | 27379.51 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.211113E+12 | 0.151271E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.699148E+10 | 0.563416E+10 | 40275.37 | 16773.46 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.301582E+11 | 0.193852E+11 | 43853.91 | 28733.37 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_5:5 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.672629E+10 | 0.540638E+10 | 40124.74 | 29-JAN-09:02 | 28505.19 | 0.00 |
February | 0.00 | 0.00 | 0.763275E+10 | 0.601263E+10 | 41326.92 | 09-FEB-08:62 | 25243.46 | 0.00 |
March | 0.00 | 0.00 | 0.103611E+11 | 0.849291E+10 | 41462.34 | 29-MAR-07:02 | 23549.89 | 0.00 |
April | 0.00 | 0.00 | 0.136008E+11 | 0.108523E+11 | 42426.82 | 30-APR-08:61 | 22603.93 | 0.00 |
May | 0.00 | 0.00 | 0.197415E+11 | 0.154692E+11 | 43017.77 | 30-MAY-07:01 | 21481.89 | 0.00 |
June | 0.00 | 0.00 | 0.236142E+11 | 0.164666E+11 | 43731.87 | 08-JUN-07:01 | 19129.95 | 0.00 |
July | 0.00 | 0.00 | 0.279840E+11 | 0.184401E+11 | 43324.89 | 02-JUL-07:01 | 18688.39 | 0.00 |
August | 0.00 | 0.00 | 0.299978E+11 | 0.192520E+11 | 43324.89 | 21-AUG-06:03 | 16666.21 | 0.00 |
September | 0.00 | 0.00 | 0.249618E+11 | 0.163788E+11 | 43631.40 | 23-SEP-07:01 | 19667.19 | 0.00 |
October | 0.00 | 0.00 | 0.201039E+11 | 0.145182E+11 | 43713.26 | 07-OCT-07:01 | 19270.48 | 0.00 |
November | 0.00 | 0.00 | 0.145725E+11 | 0.108146E+11 | 42505.03 | 03-NOV-07:01 | 22841.85 | 0.00 |
December | 0.00 | 0.00 | 0.939291E+10 | 0.711047E+10 | 40671.91 | 11-DEC-08:62 | 27175.66 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.208690E+12 | 0.149214E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.672629E+10 | 0.540638E+10 | 40124.74 | 16666.21 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.299978E+11 | 0.192520E+11 | 43731.87 | 28505.19 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_6:6 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.115744E+11 | 0.908249E+10 | 74114.46 | 30-JAN-09:02 | 45902.81 | 0.00 |
February | 0.00 | 0.00 | 0.133422E+11 | 0.102829E+11 | 74495.16 | 09-FEB-09:02 | 46448.59 | 0.00 |
March | 0.00 | 0.00 | 0.184962E+11 | 0.148644E+11 | 74883.68 | 29-MAR-08:62 | 43010.29 | 0.00 |
April | 0.00 | 0.00 | 0.244938E+11 | 0.192352E+11 | 76854.14 | 30-APR-09:01 | 41789.18 | 0.00 |
May | 0.00 | 0.00 | 0.361361E+11 | 0.279377E+11 | 78219.43 | 01-MAY-08:62 | 35756.22 | 0.00 |
June | 0.00 | 0.00 | 0.434042E+11 | 0.298638E+11 | 79230.46 | 08-JUN-08:61 | 34853.08 | 0.00 |
July | 0.00 | 0.00 | 0.512637E+11 | 0.333879E+11 | 78472.25 | 18-JUL-07:01 | 35348.64 | 0.00 |
August | 0.00 | 0.00 | 0.553577E+11 | 0.350606E+11 | 78532.84 | 08-AUG-07:01 | 32071.56 | 0.00 |
September | 0.00 | 0.00 | 0.458507E+11 | 0.296055E+11 | 79230.46 | 25-SEP-08:61 | 33282.77 | 0.00 |
October | 0.00 | 0.00 | 0.365827E+11 | 0.261509E+11 | 79194.79 | 07-OCT-08:61 | 34942.56 | 0.00 |
November | 0.00 | 0.00 | 0.262395E+11 | 0.191247E+11 | 76866.82 | 03-NOV-08:61 | 42159.84 | 0.00 |
December | 0.00 | 0.00 | 0.164711E+11 | 0.121922E+11 | 75050.24 | 04-DEC-09:02 | 43733.13 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.379212E+12 | 0.266788E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.115744E+11 | 0.908249E+10 | 74114.46 | 32071.56 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.553577E+11 | 0.350606E+11 | 79230.46 | 46448.59 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_7:7 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.600155E+10 | 0.471422E+10 | 39159.05 | 30-JAN-09:02 | 24273.70 | 0.00 |
February | 0.00 | 0.00 | 0.692608E+10 | 0.534391E+10 | 39345.96 | 09-FEB-09:02 | 24523.82 | 0.00 |
March | 0.00 | 0.00 | 0.961031E+10 | 0.773038E+10 | 39549.68 | 29-MAR-08:62 | 22789.68 | 0.00 |
April | 0.00 | 0.00 | 0.127594E+11 | 0.100220E+11 | 40622.38 | 30-APR-09:01 | 22017.22 | 0.00 |
May | 0.00 | 0.00 | 0.188325E+11 | 0.145561E+11 | 41346.92 | 01-MAY-08:62 | 18891.61 | 0.00 |
June | 0.00 | 0.00 | 0.225969E+11 | 0.155463E+11 | 41854.06 | 08-JUN-08:61 | 18417.72 | 0.00 |
July | 0.00 | 0.00 | 0.266975E+11 | 0.173863E+11 | 41453.52 | 18-JUL-07:01 | 18630.27 | 0.00 |
August | 0.00 | 0.00 | 0.288089E+11 | 0.182421E+11 | 41485.53 | 08-AUG-07:01 | 16902.99 | 0.00 |
September | 0.00 | 0.00 | 0.238738E+11 | 0.154203E+11 | 41854.06 | 25-SEP-08:61 | 17540.64 | 0.00 |
October | 0.00 | 0.00 | 0.190579E+11 | 0.136348E+11 | 41835.21 | 07-OCT-08:61 | 18503.18 | 0.00 |
November | 0.00 | 0.00 | 0.136717E+11 | 0.997234E+10 | 40599.11 | 03-NOV-08:61 | 22297.48 | 0.00 |
December | 0.00 | 0.00 | 0.856574E+10 | 0.634655E+10 | 39660.98 | 04-DEC-09:02 | 23112.30 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.197402E+12 | 0.138915E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.600155E+10 | 0.471422E+10 | 39159.05 | 16902.99 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.288089E+11 | 0.182421E+11 | 41854.06 | 24523.82 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_8:8 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.592725E+10 | 0.465210E+10 | 39022.36 | 30-JAN-09:02 | 24157.01 | 0.00 |
February | 0.00 | 0.00 | 0.685561E+10 | 0.528633E+10 | 39208.77 | 09-FEB-09:02 | 24404.89 | 0.00 |
March | 0.00 | 0.00 | 0.953452E+10 | 0.766604E+10 | 39414.13 | 29-MAR-08:62 | 22673.25 | 0.00 |
April | 0.00 | 0.00 | 0.126915E+11 | 0.996457E+10 | 40490.80 | 30-APR-09:01 | 21925.12 | 0.00 |
May | 0.00 | 0.00 | 0.187685E+11 | 0.145015E+11 | 41204.74 | 01-MAY-08:62 | 18801.89 | 0.00 |
June | 0.00 | 0.00 | 0.225332E+11 | 0.154947E+11 | 41713.27 | 08-JUN-08:61 | 18316.26 | 0.00 |
July | 0.00 | 0.00 | 0.266376E+11 | 0.173386E+11 | 41314.09 | 18-JUL-07:01 | 18544.65 | 0.00 |
August | 0.00 | 0.00 | 0.287485E+11 | 0.181942E+11 | 41345.99 | 08-AUG-07:01 | 16829.57 | 0.00 |
September | 0.00 | 0.00 | 0.238181E+11 | 0.153759E+11 | 41713.27 | 25-SEP-08:61 | 17464.61 | 0.00 |
October | 0.00 | 0.00 | 0.190013E+11 | 0.135879E+11 | 41694.50 | 07-OCT-08:61 | 18405.57 | 0.00 |
November | 0.00 | 0.00 | 0.136112E+11 | 0.992266E+10 | 40469.51 | 03-NOV-08:61 | 22199.23 | 0.00 |
December | 0.00 | 0.00 | 0.849597E+10 | 0.629012E+10 | 39523.82 | 04-DEC-09:02 | 23005.23 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196623E+12 | 0.138275E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.592725E+10 | 0.465210E+10 | 39022.36 | 16829.57 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.287485E+11 | 0.181942E+11 | 41713.27 | 24404.89 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_9:9 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.578977E+10 | 0.453726E+10 | 39168.40 | 30-JAN-09:02 | 24179.74 | 0.00 |
February | 0.00 | 0.00 | 0.672910E+10 | 0.518364E+10 | 39358.53 | 09-FEB-09:02 | 24431.20 | 0.00 |
March | 0.00 | 0.00 | 0.942044E+10 | 0.756932E+10 | 39565.00 | 29-MAR-08:62 | 22699.95 | 0.00 |
April | 0.00 | 0.00 | 0.126368E+11 | 0.991898E+10 | 40662.58 | 30-APR-09:01 | 21994.85 | 0.00 |
May | 0.00 | 0.00 | 0.188173E+11 | 0.145436E+11 | 41366.86 | 01-MAY-08:62 | 18837.04 | 0.00 |
June | 0.00 | 0.00 | 0.226292E+11 | 0.155733E+11 | 41884.68 | 08-JUN-08:61 | 18382.65 | 0.00 |
July | 0.00 | 0.00 | 0.267997E+11 | 0.174702E+11 | 41483.86 | 18-JUL-07:01 | 18681.45 | 0.00 |
August | 0.00 | 0.00 | 0.289529E+11 | 0.183586E+11 | 41515.89 | 08-AUG-07:01 | 16978.32 | 0.00 |
September | 0.00 | 0.00 | 0.239613E+11 | 0.154910E+11 | 41884.68 | 25-SEP-08:61 | 17586.34 | 0.00 |
October | 0.00 | 0.00 | 0.190958E+11 | 0.136666E+11 | 41865.83 | 07-OCT-08:61 | 18514.65 | 0.00 |
November | 0.00 | 0.00 | 0.136243E+11 | 0.993374E+10 | 40632.28 | 03-NOV-08:61 | 22301.07 | 0.00 |
December | 0.00 | 0.00 | 0.840583E+10 | 0.621754E+10 | 39674.46 | 04-DEC-09:02 | 23036.62 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.196862E+12 | 0.138464E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.578977E+10 | 0.453726E+10 | 39168.40 | 16978.32 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.289529E+11 | 0.183586E+11 | 41884.68 | 24431.20 | 0.00 |
Report: CoilReportMonthly
For: PSZ-AC_10:10 COOLING COIL
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportHEATING COIL HEATING ENERGY [] | HEATING COIL HEATING RATE [] | COOLING COIL TOTAL COOLING ENERGY [J] | COOLING COIL SENSIBLE COOLING ENERGY [J] | COOLING COIL TOTAL COOLING RATE {Maximum} [W] | COOLING COIL TOTAL COOLING RATE {TIMESTAMP} | COOLING COIL SENSIBLE COOLING RATE {AT MAX/MIN} [W] | COOLING COIL WETTED AREA FRACTION [] | |
January | 0.00 | 0.00 | 0.627038E+10 | 0.498949E+10 | 43977.21 | 29-JAN-10:02 | 30832.81 | 0.00 |
February | 0.00 | 0.00 | 0.721855E+10 | 0.564092E+10 | 44798.57 | 07-FEB-09:02 | 27824.18 | 0.00 |
March | 0.00 | 0.00 | 0.101393E+11 | 0.825294E+10 | 44243.24 | 01-MAR-09:01 | 29955.79 | 0.00 |
April | 0.00 | 0.00 | 0.138330E+11 | 0.109953E+11 | 46532.03 | 30-APR-09:01 | 24178.29 | 0.00 |
May | 0.00 | 0.00 | 0.209690E+11 | 0.164250E+11 | 46943.49 | 01-MAY-08:62 | 21890.05 | 0.00 |
June | 0.00 | 0.00 | 0.252973E+11 | 0.177024E+11 | 47538.31 | 08-JUN-08:61 | 19375.78 | 0.00 |
July | 0.00 | 0.00 | 0.300562E+11 | 0.199689E+11 | 47119.74 | 26-JUL-07:01 | 17482.67 | 0.00 |
August | 0.00 | 0.00 | 0.326831E+11 | 0.211980E+11 | 47119.74 | 08-AUG-07:03 | 14246.48 | 0.00 |
September | 0.00 | 0.00 | 0.269758E+11 | 0.178304E+11 | 47538.31 | 25-SEP-08:61 | 20520.73 | 0.00 |
October | 0.00 | 0.00 | 0.215317E+11 | 0.156693E+11 | 47516.92 | 07-OCT-08:61 | 19931.68 | 0.00 |
November | 0.00 | 0.00 | 0.152084E+11 | 0.112863E+11 | 46480.97 | 03-NOV-08:61 | 24601.56 | 0.00 |
December | 0.00 | 0.00 | 0.917037E+10 | 0.689960E+10 | 44970.68 | 04-DEC-09:02 | 26904.64 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.219353E+12 | 0.156859E+12 | 0.00 | |||
Minimum of Months | 0.00 | 0.00 | 0.627038E+10 | 0.498949E+10 | 43977.21 | 14246.48 | 0.00 | |
Maximum of Months | 0.00 | 0.00 | 0.326831E+11 | 0.211980E+11 | 47538.31 | 30832.81 | 0.00 |
Report: FanReportMonthly
For: PSZ-AC_1:1_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.593243E+10 | 0.59 | 3269.64 | 01-JAN-17:00 | 0.87 |
February | 0.536744E+10 | 0.59 | 3269.64 | 04-FEB-09:10 | 0.87 |
March | 0.595597E+10 | 0.59 | 3269.64 | 02-MAR-23:50 | 0.87 |
April | 0.574410E+10 | 0.59 | 3269.64 | 01-APR-17:14 | 0.87 |
May | 0.593243E+10 | 0.59 | 3269.64 | 02-MAY-19:45 | 0.87 |
June | 0.576764E+10 | 0.59 | 3269.64 | 03-JUN-07:10 | 0.87 |
July | 0.593243E+10 | 0.59 | 3269.64 | 04-JUL-07:20 | 0.87 |
August | 0.594420E+10 | 0.59 | 3269.64 | 01-AUG-07:40 | 0.86 |
September | 0.575587E+10 | 0.59 | 3269.64 | 05-SEP-07:06 | 0.86 |
October | 0.593243E+10 | 0.59 | 3269.64 | 03-OCT-07:50 | 0.86 |
November | 0.573233E+10 | 0.59 | 3269.64 | 12-NOV-23:10 | 0.87 |
December | 0.595597E+10 | 0.59 | 3269.64 | 02-DEC-09:10 | 0.87 |
Annual Sum or Average | 0.699532E+11 | 0.59 | |||
Minimum of Months | 0.536744E+10 | 0.59 | 3269.64 | 0.86 | |
Maximum of Months | 0.595597E+10 | 0.59 | 3269.64 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_2:2_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.234807E+10 | 0.63 | 1650.63 | 01-JAN-10:00 | 0.87 |
February | 0.213172E+10 | 0.63 | 1650.63 | 01-FEB-12:20 | 0.87 |
March | 0.239692E+10 | 0.63 | 1650.63 | 02-MAR-16:30 | 0.87 |
April | 0.231821E+10 | 0.63 | 1650.63 | 01-APR-08:10 | 0.87 |
May | 0.244816E+10 | 0.62 | 1650.63 | 01-MAY-19:27 | 0.87 |
June | 0.241002E+10 | 0.62 | 1650.63 | 02-JUN-07:09 | 0.87 |
July | 0.248554E+10 | 0.62 | 1650.63 | 01-JUL-07:15 | 0.86 |
August | 0.252409E+10 | 0.62 | 1650.63 | 02-AUG-12:10 | 0.87 |
September | 0.240185E+10 | 0.62 | 1650.63 | 01-SEP-12:10 | 0.87 |
October | 0.243939E+10 | 0.62 | 1650.63 | 03-OCT-07:09 | 0.87 |
November | 0.232382E+10 | 0.63 | 1650.63 | 02-NOV-08:00 | 0.86 |
December | 0.235683E+10 | 0.63 | 1650.63 | 01-DEC-16:10 | 0.87 |
Annual Sum or Average | 0.285846E+11 | 0.63 | |||
Minimum of Months | 0.213172E+10 | 0.62 | 1650.63 | 0.86 | |
Maximum of Months | 0.252409E+10 | 0.63 | 1650.63 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_3:3_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238403E+10 | 0.47 | 1647.34 | 19-JAN-10:40 | 0.87 |
February | 0.215867E+10 | 0.47 | 1647.34 | 01-FEB-18:50 | 0.87 |
March | 0.243147E+10 | 0.48 | 1647.34 | 01-MAR-08:03 | 0.87 |
April | 0.231286E+10 | 0.47 | 1647.34 | 01-APR-07:30 | 0.87 |
May | 0.240775E+10 | 0.47 | 1647.34 | 04-MAY-16:40 | 0.87 |
June | 0.234845E+10 | 0.48 | 1647.34 | 28-JUN-18:10 | 0.87 |
July | 0.237217E+10 | 0.46 | 1647.34 | 01-JUL-06:30 | 0.86 |
August | 0.243147E+10 | 0.48 | 1647.34 | 01-AUG-06:50 | 0.86 |
September | 0.231286E+10 | 0.47 | 1647.34 | 01-SEP-06:20 | 0.86 |
October | 0.238403E+10 | 0.47 | 1647.34 | 03-OCT-08:15 | 0.87 |
November | 0.231286E+10 | 0.47 | 1647.34 | 14-NOV-12:10 | 0.87 |
December | 0.237217E+10 | 0.47 | 1647.34 | 01-DEC-08:50 | 0.87 |
Annual Sum or Average | 0.282288E+11 | 0.47 | |||
Minimum of Months | 0.215867E+10 | 0.46 | 1647.34 | 0.86 | |
Maximum of Months | 0.243147E+10 | 0.48 | 1647.34 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_4:4_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.238858E+10 | 0.47 | 1650.48 | 10-JAN-14:10 | 0.87 |
February | 0.216279E+10 | 0.47 | 1650.48 | 05-FEB-15:10 | 0.87 |
March | 0.243611E+10 | 0.48 | 1650.48 | 13-MAR-08:10 | 0.87 |
April | 0.231728E+10 | 0.47 | 1650.48 | 10-APR-07:07 | 0.87 |
May | 0.241234E+10 | 0.47 | 1650.48 | 04-MAY-06:40 | 0.87 |
June | 0.235293E+10 | 0.48 | 1650.48 | 25-JUN-07:06 | 0.86 |
July | 0.237669E+10 | 0.46 | 1650.48 | 04-JUL-07:09 | 0.87 |
August | 0.243611E+10 | 0.48 | 1650.48 | 06-AUG-07:20 | 0.86 |
September | 0.231728E+10 | 0.47 | 1650.48 | 14-SEP-08:06 | 0.87 |
October | 0.238858E+10 | 0.47 | 1650.48 | 06-OCT-10:10 | 0.86 |
November | 0.231728E+10 | 0.47 | 1650.48 | 11-NOV-09:30 | 0.87 |
December | 0.237669E+10 | 0.47 | 1650.48 | 14-DEC-08:20 | 0.87 |
Annual Sum or Average | 0.282827E+11 | 0.47 | |||
Minimum of Months | 0.216279E+10 | 0.46 | 1650.48 | 0.86 | |
Maximum of Months | 0.243611E+10 | 0.48 | 1650.48 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_5:5_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.237887E+10 | 0.47 | 1643.77 | 05-JAN-17:20 | 0.87 |
February | 0.215400E+10 | 0.47 | 1643.77 | 03-FEB-14:10 | 0.87 |
March | 0.242621E+10 | 0.48 | 1643.77 | 03-MAR-16:40 | 0.87 |
April | 0.230786E+10 | 0.47 | 1643.77 | 10-APR-15:00 | 0.87 |
May | 0.240254E+10 | 0.47 | 1643.77 | 02-MAY-09:20 | 0.87 |
June | 0.234337E+10 | 0.48 | 1643.77 | 02-JUN-08:40 | 0.87 |
July | 0.236704E+10 | 0.46 | 1643.77 | 01-JUL-13:20 | 0.86 |
August | 0.242621E+10 | 0.48 | 1643.77 | 01-AUG-08:40 | 0.87 |
September | 0.230786E+10 | 0.47 | 1643.77 | 02-SEP-08:09 | 0.87 |
October | 0.237887E+10 | 0.47 | 1643.77 | 04-OCT-09:10 | 0.87 |
November | 0.230786E+10 | 0.47 | 1643.77 | 01-NOV-08:15 | 0.87 |
December | 0.236704E+10 | 0.47 | 1643.77 | 04-DEC-13:50 | 0.87 |
Annual Sum or Average | 0.281677E+11 | 0.47 | |||
Minimum of Months | 0.215400E+10 | 0.46 | 1643.77 | 0.86 | |
Maximum of Months | 0.242621E+10 | 0.48 | 1643.77 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_6:6_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.395402E+10 | 0.43 | 2960.49 | 02-JAN-17:00 | 0.87 |
February | 0.358100E+10 | 0.44 | 2960.49 | 01-FEB-14:10 | 0.87 |
March | 0.403929E+10 | 0.44 | 2960.49 | 01-MAR-15:20 | 0.87 |
April | 0.383679E+10 | 0.43 | 2960.49 | 01-APR-09:20 | 0.87 |
May | 0.399665E+10 | 0.44 | 2960.49 | 01-MAY-19:14 | 0.87 |
June | 0.390074E+10 | 0.44 | 2960.49 | 01-JUN-10:00 | 0.87 |
July | 0.393271E+10 | 0.43 | 2960.49 | 02-JUL-09:50 | 0.86 |
August | 0.403929E+10 | 0.44 | 2960.49 | 01-AUG-19:08 | 0.87 |
September | 0.383679E+10 | 0.43 | 2960.49 | 01-SEP-08:07 | 0.86 |
October | 0.395402E+10 | 0.43 | 2960.49 | 02-OCT-19:40 | 0.87 |
November | 0.383679E+10 | 0.43 | 2960.49 | 01-NOV-19:00 | 0.87 |
December | 0.393271E+10 | 0.43 | 2960.49 | 01-DEC-15:30 | 0.87 |
Annual Sum or Average | 0.468408E+11 | 0.44 | |||
Minimum of Months | 0.358100E+10 | 0.43 | 2960.49 | 0.86 | |
Maximum of Months | 0.403929E+10 | 0.44 | 2960.49 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_7:7_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208874E+10 | 0.43 | 1563.90 | 01-JAN-11:30 | 0.87 |
February | 0.189169E+10 | 0.44 | 1563.90 | 01-FEB-10:50 | 0.87 |
March | 0.213378E+10 | 0.44 | 1563.90 | 01-MAR-14:20 | 0.87 |
April | 0.202681E+10 | 0.43 | 1563.90 | 01-APR-08:20 | 0.87 |
May | 0.211126E+10 | 0.44 | 1563.90 | 01-MAY-09:20 | 0.86 |
June | 0.206059E+10 | 0.44 | 1563.90 | 01-JUN-09:10 | 0.87 |
July | 0.207748E+10 | 0.43 | 1563.90 | 01-JUL-07:50 | 0.86 |
August | 0.213378E+10 | 0.44 | 1563.90 | 01-AUG-08:15 | 0.86 |
September | 0.202681E+10 | 0.43 | 1563.90 | 01-SEP-08:04 | 0.86 |
October | 0.208874E+10 | 0.43 | 1563.90 | 01-OCT-08:06 | 0.85 |
November | 0.202681E+10 | 0.43 | 1563.90 | 01-NOV-09:10 | 0.86 |
December | 0.207748E+10 | 0.43 | 1563.90 | 01-DEC-10:00 | 0.87 |
Annual Sum or Average | 0.247440E+11 | 0.44 | |||
Minimum of Months | 0.189169E+10 | 0.43 | 1563.90 | 0.85 | |
Maximum of Months | 0.213378E+10 | 0.44 | 1563.90 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_8:8_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.208172E+10 | 0.43 | 1558.64 | 03-JAN-13:10 | 0.87 |
February | 0.188533E+10 | 0.44 | 1558.64 | 01-FEB-20:25 | 0.87 |
March | 0.212660E+10 | 0.44 | 1558.64 | 01-MAR-09:30 | 0.87 |
April | 0.201999E+10 | 0.43 | 1558.64 | 01-APR-08:20 | 0.87 |
May | 0.210416E+10 | 0.44 | 1558.64 | 01-MAY-14:00 | 0.87 |
June | 0.205366E+10 | 0.44 | 1558.64 | 01-JUN-19:04 | 0.87 |
July | 0.207049E+10 | 0.43 | 1558.64 | 03-JUL-08:40 | 0.87 |
August | 0.212660E+10 | 0.44 | 1558.64 | 01-AUG-07:50 | 0.86 |
September | 0.201999E+10 | 0.43 | 1558.64 | 01-SEP-08:09 | 0.86 |
October | 0.208172E+10 | 0.43 | 1558.64 | 04-OCT-19:08 | 0.87 |
November | 0.201999E+10 | 0.43 | 1558.64 | 01-NOV-08:00 | 0.86 |
December | 0.207049E+10 | 0.43 | 1558.64 | 04-DEC-15:10 | 0.87 |
Annual Sum or Average | 0.246608E+11 | 0.44 | |||
Minimum of Months | 0.188533E+10 | 0.43 | 1558.64 | 0.86 | |
Maximum of Months | 0.212660E+10 | 0.44 | 1558.64 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_9:9_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.209027E+10 | 0.43 | 1565.04 | 03-JAN-16:40 | 0.87 |
February | 0.189307E+10 | 0.44 | 1565.04 | 04-FEB-15:30 | 0.87 |
March | 0.213534E+10 | 0.44 | 1565.04 | 06-MAR-14:30 | 0.87 |
April | 0.202829E+10 | 0.43 | 1565.04 | 03-APR-09:50 | 0.87 |
May | 0.211281E+10 | 0.44 | 1565.04 | 01-MAY-10:50 | 0.87 |
June | 0.206210E+10 | 0.44 | 1565.04 | 02-JUN-08:50 | 0.87 |
July | 0.207900E+10 | 0.43 | 1565.04 | 01-JUL-07:40 | 0.86 |
August | 0.213534E+10 | 0.44 | 1565.04 | 02-AUG-19:30 | 0.87 |
September | 0.202829E+10 | 0.43 | 1565.04 | 01-SEP-19:11 | 0.87 |
October | 0.209027E+10 | 0.43 | 1565.04 | 02-OCT-19:33 | 0.87 |
November | 0.202829E+10 | 0.43 | 1565.04 | 01-NOV-08:09 | 0.86 |
December | 0.207900E+10 | 0.43 | 1565.04 | 01-DEC-15:30 | 0.87 |
Annual Sum or Average | 0.247621E+11 | 0.44 | |||
Minimum of Months | 0.189307E+10 | 0.43 | 1565.04 | 0.86 | |
Maximum of Months | 0.213534E+10 | 0.44 | 1565.04 | 0.87 |
Report: FanReportMonthly
For: PSZ-AC_10:10_ADDAQ_UNITARY_PACKAGE_FAN
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportFAN ELECTRICITY ENERGY [J] | FAN RISE IN AIR TEMPERATURE [deltaC] | FAN ELECTRICITY RATE {Maximum} [W] | FAN ELECTRICITY RATE {TIMESTAMP} | FAN RISE IN AIR TEMPERATURE {AT MAX/MIN} [deltaC] | |
January | 0.244381E+10 | 0.43 | 1829.75 | 01-JAN-11:30 | 0.87 |
February | 0.221326E+10 | 0.44 | 1829.75 | 01-FEB-12:50 | 0.87 |
March | 0.249651E+10 | 0.44 | 1829.75 | 01-MAR-10:50 | 0.87 |
April | 0.237135E+10 | 0.43 | 1829.75 | 01-APR-11:30 | 0.87 |
May | 0.247016E+10 | 0.44 | 1829.75 | 01-MAY-09:30 | 0.87 |
June | 0.241088E+10 | 0.44 | 1829.75 | 01-JUN-07:04 | 0.87 |
July | 0.243094E+10 | 0.43 | 1829.75 | 01-JUL-08:06 | 0.86 |
August | 0.249728E+10 | 0.44 | 1829.75 | 01-AUG-07:09 | 0.86 |
September | 0.237183E+10 | 0.43 | 1829.75 | 01-SEP-08:30 | 0.86 |
October | 0.244381E+10 | 0.43 | 1829.75 | 01-OCT-08:50 | 0.86 |
November | 0.237135E+10 | 0.43 | 1829.75 | 01-NOV-08:30 | 0.86 |
December | 0.243064E+10 | 0.43 | 1829.75 | 01-DEC-11:00 | 0.87 |
Annual Sum or Average | 0.289518E+11 | 0.44 | |||
Minimum of Months | 0.221326E+10 | 0.43 | 1829.75 | 0.86 | |
Maximum of Months | 0.249728E+10 | 0.44 | 1829.75 | 0.87 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: ZoneTemperatureOscillationReportMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE OSCILLATING TEMPERATURES TIME {HOURS NON-ZERO} [HOURS] | ZONE PEOPLE OCCUPANT COUNT {FOR HOURS SHOWN} [] | |
January | 0.00 | 0.00 |
February | 0.00 | 0.00 |
March | 0.00 | 0.00 |
April | 0.00 | 0.00 |
May | 0.00 | 0.00 |
June | 0.00 | 0.00 |
July | 0.00 | 0.00 |
August | 0.00 | 0.00 |
September | 0.00 | 0.00 |
October | 0.00 | 0.00 |
November | 0.00 | 0.00 |
December | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | |
Minimum of Months | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.115367E+11 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.115884E+11 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.144156E+11 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.173263E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.232249E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.260214E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.300252E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.310725E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.268345E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.228141E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.174749E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.135984E+11 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.245933E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.115367E+11 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.310725E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.501298E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.501976E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.622361E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.737398E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.981777E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.109471E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.125891E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.130693E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.112300E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.958708E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.742922E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.583425E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.104134E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.501298E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.130693E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.431208E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.435073E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.546981E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.638794E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.853229E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.952338E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.108174E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114100E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.964658E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.826254E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.647905E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.502409E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.902159E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.431208E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114100E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.430208E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.434681E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.547330E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.640431E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.857367E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.957130E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.108776E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114682E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.969696E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.830542E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.649802E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.502455E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.905422E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.430208E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114682E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.422247E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.427706E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.539749E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.633650E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.851067E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.950834E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.108222E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.114100E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.963942E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.824529E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.643505E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.495106E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.897555E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.422247E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.114100E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.718645E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.736008E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.943935E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.112115E+11 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.153449E+11 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.172434E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.196063E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.208087E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.174666E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.148018E+11 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.113905E+11 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.854367E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.160403E+12 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.718645E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.208087E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.373705E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.382160E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.489479E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.580781E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.793525E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.890540E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.101239E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107385E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.902145E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.765458E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.590024E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.443621E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.829768E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.373705E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107385E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.371018E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.379630E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.486671E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.578130E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.790752E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.887736E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.100959E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107098E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.899593E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.762992E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.587640E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.441056E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.826579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.371018E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107098E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.368260E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.377115E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.484595E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.577655E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.793300E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.891630E+10 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.101539E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.107794E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.904665E+10 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.766650E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.588973E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.439620E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.828579E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.368260E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.107794E+11 | 0.00 | 0.00 |
Report: AirLoopSystemEnergyAndWaterUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM HOT WATER ENERGY [J] | AIR SYSTEM STEAM ENERGY [J] | AIR SYSTEM CHILLED WATER ENERGY [J] | AIR SYSTEM ELECTRICITY ENERGY [J] | AIR SYSTEM NATURAL GAS ENERGY [] | AIR SYSTEM WATER VOLUME [m3] | |
January | 0.00 | 0.00 | 0.00 | 0.420307E+10 | 0.00 | 0.00 |
February | 0.00 | 0.00 | 0.00 | 0.427138E+10 | 0.00 | 0.00 |
March | 0.00 | 0.00 | 0.00 | 0.548006E+10 | 0.00 | 0.00 |
April | 0.00 | 0.00 | 0.00 | 0.656929E+10 | 0.00 | 0.00 |
May | 0.00 | 0.00 | 0.00 | 0.910793E+10 | 0.00 | 0.00 |
June | 0.00 | 0.00 | 0.00 | 0.102633E+11 | 0.00 | 0.00 |
July | 0.00 | 0.00 | 0.00 | 0.117235E+11 | 0.00 | 0.00 |
August | 0.00 | 0.00 | 0.00 | 0.125059E+11 | 0.00 | 0.00 |
September | 0.00 | 0.00 | 0.00 | 0.104695E+11 | 0.00 | 0.00 |
October | 0.00 | 0.00 | 0.00 | 0.887039E+10 | 0.00 | 0.00 |
November | 0.00 | 0.00 | 0.00 | 0.677486E+10 | 0.00 | 0.00 |
December | 0.00 | 0.00 | 0.00 | 0.501208E+10 | 0.00 | 0.00 |
Annual Sum or Average | 0.00 | 0.00 | 0.00 | 0.952513E+11 | 0.00 | 0.00 |
Minimum of Months | 0.00 | 0.00 | 0.00 | 0.420307E+10 | 0.00 | 0.00 |
Maximum of Months | 0.00 | 0.00 | 0.00 | 0.125059E+11 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.593243E+10 | 0.183391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.536744E+10 | 0.201016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595597E+10 | 0.265839E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.574410E+10 | 0.352982E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593243E+10 | 0.502090E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576764E+10 | 0.600016E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.593243E+10 | 0.710717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.594420E+10 | 0.747730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.575587E+10 | 0.643138E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.593243E+10 | 0.517548E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.573233E+10 | 0.371127E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595597E+10 | 0.249507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699532E+11 | 0.534510E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536744E+10 | 0.183391E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.595597E+10 | 0.747730E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.234807E+10 | 0.976240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213172E+10 | 0.104403E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239692E+10 | 0.134346E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231821E+10 | 0.171340E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244816E+10 | 0.237036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241002E+10 | 0.279223E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.248554E+10 | 0.329193E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252409E+10 | 0.346657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240185E+10 | 0.297264E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243939E+10 | 0.242603E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232382E+10 | 0.179695E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235683E+10 | 0.126837E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285846E+11 | 0.254622E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.213172E+10 | 0.976240E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252409E+10 | 0.346657E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.238403E+10 | 0.704760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215867E+10 | 0.789557E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243147E+10 | 0.106133E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231286E+10 | 0.137718E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240775E+10 | 0.197941E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234845E+10 | 0.236430E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237217E+10 | 0.279371E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.243147E+10 | 0.299669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231286E+10 | 0.249626E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238403E+10 | 0.201436E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231286E+10 | 0.147202E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237217E+10 | 0.965460E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282288E+11 | 0.210150E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.215867E+10 | 0.704760E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.243147E+10 | 0.299669E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.238858E+10 | 0.699148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216279E+10 | 0.786392E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243611E+10 | 0.106074E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231728E+10 | 0.138135E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241234E+10 | 0.199224E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.235293E+10 | 0.237965E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237669E+10 | 0.281348E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.243611E+10 | 0.301582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231728E+10 | 0.251299E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238858E+10 | 0.202843E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231728E+10 | 0.147731E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237669E+10 | 0.963785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282827E+11 | 0.211113E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.216279E+10 | 0.699148E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.243611E+10 | 0.301582E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.237887E+10 | 0.672629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215400E+10 | 0.763275E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242621E+10 | 0.103611E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230786E+10 | 0.136008E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240254E+10 | 0.197415E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234337E+10 | 0.236142E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.236704E+10 | 0.279840E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.242621E+10 | 0.299978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230786E+10 | 0.249618E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237887E+10 | 0.201039E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230786E+10 | 0.145725E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236704E+10 | 0.939291E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281677E+11 | 0.208690E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.215400E+10 | 0.672629E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242621E+10 | 0.299978E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.395402E+10 | 0.115744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358100E+10 | 0.133422E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403929E+10 | 0.184962E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383679E+10 | 0.244938E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399665E+10 | 0.361361E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.390074E+10 | 0.434042E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.393271E+10 | 0.512637E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.403929E+10 | 0.553577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.383679E+10 | 0.458507E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395402E+10 | 0.365827E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383679E+10 | 0.262395E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393271E+10 | 0.164711E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468408E+11 | 0.379212E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358100E+10 | 0.115744E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.403929E+10 | 0.553577E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208874E+10 | 0.600155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189169E+10 | 0.692608E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213378E+10 | 0.961031E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202681E+10 | 0.127594E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211126E+10 | 0.188325E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206059E+10 | 0.225969E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207748E+10 | 0.266975E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213378E+10 | 0.288089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202681E+10 | 0.238738E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208874E+10 | 0.190579E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202681E+10 | 0.136717E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207748E+10 | 0.856574E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247440E+11 | 0.197402E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.189169E+10 | 0.600155E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213378E+10 | 0.288089E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.208172E+10 | 0.592725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188533E+10 | 0.685561E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212660E+10 | 0.953452E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201999E+10 | 0.126915E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210416E+10 | 0.187685E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205366E+10 | 0.225332E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207049E+10 | 0.266376E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212660E+10 | 0.287485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.201999E+10 | 0.238181E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208172E+10 | 0.190013E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201999E+10 | 0.136112E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207049E+10 | 0.849597E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246608E+11 | 0.196623E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.188533E+10 | 0.592725E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212660E+10 | 0.287485E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.209027E+10 | 0.578977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189307E+10 | 0.672910E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213534E+10 | 0.942044E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202829E+10 | 0.126368E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211281E+10 | 0.188173E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206210E+10 | 0.226292E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207900E+10 | 0.267997E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213534E+10 | 0.289529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202829E+10 | 0.239613E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209027E+10 | 0.190958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202829E+10 | 0.136243E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207900E+10 | 0.840583E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247621E+11 | 0.196862E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.189307E+10 | 0.578977E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213534E+10 | 0.289529E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentLoadsMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN AIR HEATING ENERGY [J] | AIR SYSTEM COOLING COIL TOTAL COOLING ENERGY [J] | AIR SYSTEM HEATING COIL TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL HEATING ENERGY [J] | AIR SYSTEM HEAT EXCHANGER TOTAL COOLING ENERGY [J] | AIR SYSTEM HUMIDIFIER TOTAL HEATING ENERGY [J] | AIR SYSTEM EVAPORATIVE COOLER TOTAL COOLING ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER TOTAL COOLING ENERGY [J] | |
January | 0.244381E+10 | 0.627038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221326E+10 | 0.721855E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.249651E+10 | 0.101393E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237135E+10 | 0.138330E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247016E+10 | 0.209690E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241088E+10 | 0.252973E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243094E+10 | 0.300562E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249728E+10 | 0.326831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237183E+10 | 0.269758E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244381E+10 | 0.215317E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237135E+10 | 0.152084E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243064E+10 | 0.917037E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289518E+11 | 0.219353E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.221326E+10 | 0.627038E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.249728E+10 | 0.326831E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_1:1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.593243E+10 | 0.00 | 0.00 | 0.00 | 0.560426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.536744E+10 | 0.00 | 0.00 | 0.00 | 0.622094E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.595597E+10 | 0.00 | 0.00 | 0.00 | 0.845964E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.574410E+10 | 0.00 | 0.00 | 0.00 | 0.115822E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.593243E+10 | 0.00 | 0.00 | 0.00 | 0.172924E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.576764E+10 | 0.00 | 0.00 | 0.00 | 0.202537E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.593243E+10 | 0.00 | 0.00 | 0.00 | 0.240927E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.594420E+10 | 0.00 | 0.00 | 0.00 | 0.251283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.575587E+10 | 0.00 | 0.00 | 0.00 | 0.210787E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.593243E+10 | 0.00 | 0.00 | 0.00 | 0.168817E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.573233E+10 | 0.00 | 0.00 | 0.00 | 0.117426E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.595597E+10 | 0.00 | 0.00 | 0.00 | 0.764244E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.699532E+11 | 0.00 | 0.00 | 0.00 | 0.175980E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.536744E+10 | 0.00 | 0.00 | 0.00 | 0.560426E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.595597E+10 | 0.00 | 0.00 | 0.00 | 0.251283E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_2:2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.234807E+10 | 0.00 | 0.00 | 0.00 | 0.266491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.213172E+10 | 0.00 | 0.00 | 0.00 | 0.288804E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.239692E+10 | 0.00 | 0.00 | 0.00 | 0.382669E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231821E+10 | 0.00 | 0.00 | 0.00 | 0.505577E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.244816E+10 | 0.00 | 0.00 | 0.00 | 0.736961E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241002E+10 | 0.00 | 0.00 | 0.00 | 0.853712E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.248554E+10 | 0.00 | 0.00 | 0.00 | 0.101036E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.252409E+10 | 0.00 | 0.00 | 0.00 | 0.105452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.240185E+10 | 0.00 | 0.00 | 0.00 | 0.882816E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.243939E+10 | 0.00 | 0.00 | 0.00 | 0.714769E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.232382E+10 | 0.00 | 0.00 | 0.00 | 0.510540E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.235683E+10 | 0.00 | 0.00 | 0.00 | 0.347742E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.285846E+11 | 0.00 | 0.00 | 0.00 | 0.755496E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.213172E+10 | 0.00 | 0.00 | 0.00 | 0.266491E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.252409E+10 | 0.00 | 0.00 | 0.00 | 0.105452E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_3:3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.238403E+10 | 0.00 | 0.00 | 0.00 | 0.192806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215867E+10 | 0.00 | 0.00 | 0.00 | 0.219206E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243147E+10 | 0.00 | 0.00 | 0.00 | 0.303833E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231286E+10 | 0.00 | 0.00 | 0.00 | 0.407508E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240775E+10 | 0.00 | 0.00 | 0.00 | 0.612454E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234845E+10 | 0.00 | 0.00 | 0.00 | 0.717494E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237217E+10 | 0.00 | 0.00 | 0.00 | 0.844525E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.243147E+10 | 0.00 | 0.00 | 0.00 | 0.897850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231286E+10 | 0.00 | 0.00 | 0.00 | 0.733372E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238403E+10 | 0.00 | 0.00 | 0.00 | 0.587851E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231286E+10 | 0.00 | 0.00 | 0.00 | 0.416619E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237217E+10 | 0.00 | 0.00 | 0.00 | 0.265192E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282288E+11 | 0.00 | 0.00 | 0.00 | 0.619871E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.215867E+10 | 0.00 | 0.00 | 0.00 | 0.192806E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.243147E+10 | 0.00 | 0.00 | 0.00 | 0.897850E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_4:4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.238858E+10 | 0.00 | 0.00 | 0.00 | 0.191350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.216279E+10 | 0.00 | 0.00 | 0.00 | 0.218402E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.243611E+10 | 0.00 | 0.00 | 0.00 | 0.303719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.231728E+10 | 0.00 | 0.00 | 0.00 | 0.408703E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.241234E+10 | 0.00 | 0.00 | 0.00 | 0.616133E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.235293E+10 | 0.00 | 0.00 | 0.00 | 0.721837E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.237669E+10 | 0.00 | 0.00 | 0.00 | 0.850089E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.243611E+10 | 0.00 | 0.00 | 0.00 | 0.903208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.231728E+10 | 0.00 | 0.00 | 0.00 | 0.737969E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.238858E+10 | 0.00 | 0.00 | 0.00 | 0.591684E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.231728E+10 | 0.00 | 0.00 | 0.00 | 0.418075E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.237669E+10 | 0.00 | 0.00 | 0.00 | 0.264785E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.282827E+11 | 0.00 | 0.00 | 0.00 | 0.622595E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.216279E+10 | 0.00 | 0.00 | 0.00 | 0.191350E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.243611E+10 | 0.00 | 0.00 | 0.00 | 0.903208E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_5:5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.237887E+10 | 0.00 | 0.00 | 0.00 | 0.184359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.215400E+10 | 0.00 | 0.00 | 0.00 | 0.212306E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.242621E+10 | 0.00 | 0.00 | 0.00 | 0.297128E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.230786E+10 | 0.00 | 0.00 | 0.00 | 0.402864E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.240254E+10 | 0.00 | 0.00 | 0.00 | 0.610813E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.234337E+10 | 0.00 | 0.00 | 0.00 | 0.716497E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.236704E+10 | 0.00 | 0.00 | 0.00 | 0.845521E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.242621E+10 | 0.00 | 0.00 | 0.00 | 0.898374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.230786E+10 | 0.00 | 0.00 | 0.00 | 0.733156E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.237887E+10 | 0.00 | 0.00 | 0.00 | 0.586642E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.230786E+10 | 0.00 | 0.00 | 0.00 | 0.412719E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.236704E+10 | 0.00 | 0.00 | 0.00 | 0.258403E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.281677E+11 | 0.00 | 0.00 | 0.00 | 0.615878E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.215400E+10 | 0.00 | 0.00 | 0.00 | 0.184359E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.242621E+10 | 0.00 | 0.00 | 0.00 | 0.898374E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_6:6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.395402E+10 | 0.00 | 0.00 | 0.00 | 0.323243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.358100E+10 | 0.00 | 0.00 | 0.00 | 0.377908E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.403929E+10 | 0.00 | 0.00 | 0.00 | 0.540006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.383679E+10 | 0.00 | 0.00 | 0.00 | 0.737467E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.399665E+10 | 0.00 | 0.00 | 0.00 | 0.113482E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.390074E+10 | 0.00 | 0.00 | 0.00 | 0.133427E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.393271E+10 | 0.00 | 0.00 | 0.00 | 0.156736E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.403929E+10 | 0.00 | 0.00 | 0.00 | 0.167694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.383679E+10 | 0.00 | 0.00 | 0.00 | 0.136298E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.395402E+10 | 0.00 | 0.00 | 0.00 | 0.108478E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.383679E+10 | 0.00 | 0.00 | 0.00 | 0.755368E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.393271E+10 | 0.00 | 0.00 | 0.00 | 0.461096E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.468408E+11 | 0.00 | 0.00 | 0.00 | 0.113562E+12 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.358100E+10 | 0.00 | 0.00 | 0.00 | 0.323243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.403929E+10 | 0.00 | 0.00 | 0.00 | 0.167694E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_7:7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.208874E+10 | 0.00 | 0.00 | 0.00 | 0.164831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189169E+10 | 0.00 | 0.00 | 0.00 | 0.192991E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213378E+10 | 0.00 | 0.00 | 0.00 | 0.276101E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202681E+10 | 0.00 | 0.00 | 0.00 | 0.378100E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211126E+10 | 0.00 | 0.00 | 0.00 | 0.582398E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206059E+10 | 0.00 | 0.00 | 0.00 | 0.684481E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207748E+10 | 0.00 | 0.00 | 0.00 | 0.804644E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213378E+10 | 0.00 | 0.00 | 0.00 | 0.860477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202681E+10 | 0.00 | 0.00 | 0.00 | 0.699464E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208874E+10 | 0.00 | 0.00 | 0.00 | 0.556584E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202681E+10 | 0.00 | 0.00 | 0.00 | 0.387343E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207748E+10 | 0.00 | 0.00 | 0.00 | 0.235873E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247440E+11 | 0.00 | 0.00 | 0.00 | 0.582329E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.189169E+10 | 0.00 | 0.00 | 0.00 | 0.164831E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213378E+10 | 0.00 | 0.00 | 0.00 | 0.860477E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_8:8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.208172E+10 | 0.00 | 0.00 | 0.00 | 0.162846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.188533E+10 | 0.00 | 0.00 | 0.00 | 0.191097E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.212660E+10 | 0.00 | 0.00 | 0.00 | 0.274011E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.201999E+10 | 0.00 | 0.00 | 0.00 | 0.376131E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.210416E+10 | 0.00 | 0.00 | 0.00 | 0.580336E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.205366E+10 | 0.00 | 0.00 | 0.00 | 0.682370E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207049E+10 | 0.00 | 0.00 | 0.00 | 0.802543E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.212660E+10 | 0.00 | 0.00 | 0.00 | 0.858319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.201999E+10 | 0.00 | 0.00 | 0.00 | 0.697594E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.208172E+10 | 0.00 | 0.00 | 0.00 | 0.554820E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.201999E+10 | 0.00 | 0.00 | 0.00 | 0.385640E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207049E+10 | 0.00 | 0.00 | 0.00 | 0.234006E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.246608E+11 | 0.00 | 0.00 | 0.00 | 0.579971E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.188533E+10 | 0.00 | 0.00 | 0.00 | 0.162846E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.212660E+10 | 0.00 | 0.00 | 0.00 | 0.858319E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_9:9
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.209027E+10 | 0.00 | 0.00 | 0.00 | 0.159233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.189307E+10 | 0.00 | 0.00 | 0.00 | 0.187808E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.213534E+10 | 0.00 | 0.00 | 0.00 | 0.271061E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.202829E+10 | 0.00 | 0.00 | 0.00 | 0.374825E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.211281E+10 | 0.00 | 0.00 | 0.00 | 0.582019E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.206210E+10 | 0.00 | 0.00 | 0.00 | 0.685420E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.207900E+10 | 0.00 | 0.00 | 0.00 | 0.807492E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.213534E+10 | 0.00 | 0.00 | 0.00 | 0.864401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.202829E+10 | 0.00 | 0.00 | 0.00 | 0.701836E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.209027E+10 | 0.00 | 0.00 | 0.00 | 0.557623E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.202829E+10 | 0.00 | 0.00 | 0.00 | 0.386144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.207900E+10 | 0.00 | 0.00 | 0.00 | 0.231720E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.247621E+11 | 0.00 | 0.00 | 0.00 | 0.580958E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.189307E+10 | 0.00 | 0.00 | 0.00 | 0.159233E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.213534E+10 | 0.00 | 0.00 | 0.00 | 0.864401E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: AirLoopSystemComponentEnergyUseMonthly
For: PSZ-AC_10:10
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportAIR SYSTEM FAN ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL HOT WATER ENERGY [J] | AIR SYSTEM COOLING COIL CHILLED WATER ENERGY [J] | AIR SYSTEM DX HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM DX COOLING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL ELECTRICITY ENERGY [J] | AIR SYSTEM HEATING COIL NATURAL GAS ENERGY [] | AIR SYSTEM HEATING COIL STEAM ENERGY [J] | AIR SYSTEM HUMIDIFIER ELECTRICITY ENERGY [J] | AIR SYSTEM HUMIDIFIER NATURAL GAS ENERGY [] | AIR SYSTEM EVAPORATIVE COOLER ELECTRICITY ENERGY [J] | AIR SYSTEM DESICCANT DEHUMIDIFIER ELECTRICITY ENERGY [J] | |
January | 0.244381E+10 | 0.00 | 0.00 | 0.00 | 0.175926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
February | 0.221326E+10 | 0.00 | 0.00 | 0.00 | 0.205812E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
March | 0.249651E+10 | 0.00 | 0.00 | 0.00 | 0.298355E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
April | 0.237135E+10 | 0.00 | 0.00 | 0.00 | 0.419794E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
May | 0.247016E+10 | 0.00 | 0.00 | 0.00 | 0.663777E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
June | 0.241088E+10 | 0.00 | 0.00 | 0.00 | 0.785243E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
July | 0.243094E+10 | 0.00 | 0.00 | 0.00 | 0.929253E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
August | 0.249728E+10 | 0.00 | 0.00 | 0.00 | 0.100086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
September | 0.237183E+10 | 0.00 | 0.00 | 0.00 | 0.809768E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
October | 0.244381E+10 | 0.00 | 0.00 | 0.00 | 0.642657E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
November | 0.237135E+10 | 0.00 | 0.00 | 0.00 | 0.440351E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
December | 0.243064E+10 | 0.00 | 0.00 | 0.00 | 0.258144E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Annual Sum or Average | 0.289518E+11 | 0.00 | 0.00 | 0.00 | 0.662995E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Minimum of Months | 0.221326E+10 | 0.00 | 0.00 | 0.00 | 0.175926E+10 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Maximum of Months | 0.249728E+10 | 0.00 | 0.00 | 0.00 | 0.100086E+11 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 | 0.00 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.474260E+09 | 0.803474E+09 | 0.00 | 11377172.52 | 3866325.72 | 0.00 | 0.155334E+10 | 0.00 | 0.57 |
February | 0.268297E+09 | 0.189995E+10 | 0.00 | 7008760.42 | 2238507.57 | 0.00 | 0.790240E+09 | 0.00 | 0.57 |
March | 0.238532E+09 | 0.385258E+10 | 0.00 | 4399939.24 | 15347307.75 | 0.00 | 0.365893E+09 | 0.00 | 0.57 |
April | 0.148645E+09 | 0.861217E+10 | 0.00 | 1295695.69 | 68837518.88 | 0.00 | 44704846.58 | 0.00 | 0.57 |
May | 30699393.30 | 0.156877E+11 | 0.00 | 510545.12 | 0.115189E+09 | 0.00 | 9170898.64 | 0.00 | 0.58 |
June | 7612163.31 | 0.219448E+11 | 0.00 | 252580.92 | 71756583.86 | 0.00 | 10263944.45 | 0.00 | 0.58 |
July | 744765.65 | 0.272914E+11 | 0.00 | 112089.98 | 0.101257E+09 | 0.00 | 1807022.24 | 0.00 | 0.58 |
August | 23506.72 | 0.290778E+11 | 0.00 | 21953.50 | 0.115144E+09 | 0.00 | 39688.56 | 0.00 | 0.58 |
September | 3063714.98 | 0.239794E+11 | 0.00 | 154410.76 | 0.110923E+09 | 0.00 | 5520698.94 | 0.00 | 0.58 |
October | 26824832.09 | 0.159551E+11 | 0.00 | 702377.23 | 0.198317E+09 | 0.00 | 11869944.55 | 0.00 | 0.57 |
November | 38066536.59 | 0.845270E+10 | 0.00 | 963209.31 | 0.143302E+09 | 0.00 | 6260615.29 | 0.00 | 0.57 |
December | 0.234671E+09 | 0.298018E+10 | 0.00 | 7246200.28 | 12080240.49 | 0.00 | 0.651470E+09 | 0.00 | 0.57 |
Annual Sum or Average | 0.147144E+10 | 0.160537E+12 | 0.00 | 34044934.96 | 0.958258E+09 | 0.00 | 0.345059E+10 | 0.00 | 0.58 |
Minimum of Months | 23506.72 | 0.803474E+09 | 0.00 | 21953.50 | 2238507.57 | 0.00 | 39688.56 | 0.00 | 0.57 |
Maximum of Months | 0.474260E+09 | 0.290778E+11 | 0.00 | 11377172.52 | 0.198317E+09 | 0.00 | 0.155334E+10 | 0.00 | 0.58 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE1
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.163004E+09 | 0.408638E+09 | 0.00 | 5859881.30 | 7069112.54 | 0.00 | 0.442941E+09 | 0.00 | 0.44 |
February | 75807392.93 | 0.863334E+09 | 0.00 | 3159181.46 | 8705403.39 | 0.00 | 0.183065E+09 | 0.00 | 0.44 |
March | 71478999.47 | 0.167358E+10 | 0.00 | 2101477.01 | 20265313.64 | 0.00 | 71851680.99 | 0.00 | 0.45 |
April | 30805842.34 | 0.348944E+10 | 0.00 | 346371.93 | 77778918.12 | 0.00 | 3990874.56 | 0.00 | 0.45 |
May | 1054316.31 | 0.632943E+10 | 0.00 | 1909.64 | 0.100659E+09 | 0.00 | 254670.45 | 0.00 | 0.46 |
June | 334829.28 | 0.890577E+10 | 0.00 | 4959.42 | 56348431.66 | 0.00 | 164768.71 | 0.00 | 0.48 |
July | 0.00 | 0.111869E+11 | 0.00 | 888.56 | 70797112.76 | 0.00 | 0.00 | 0.00 | 0.47 |
August | 0.00 | 0.121085E+11 | 0.00 | 0.00 | 88949910.34 | 0.00 | 0.00 | 0.00 | 0.48 |
September | 0.00 | 0.973219E+10 | 0.00 | 0.00 | 92598254.27 | 0.00 | 0.00 | 0.00 | 0.47 |
October | 5141654.92 | 0.643867E+10 | 0.00 | 160564.87 | 0.170990E+09 | 0.00 | 626636.29 | 0.00 | 0.46 |
November | 5198743.77 | 0.357365E+10 | 0.00 | 135292.03 | 0.149529E+09 | 0.00 | 101062.61 | 0.00 | 0.45 |
December | 68226569.78 | 0.133434E+10 | 0.00 | 3450996.14 | 30068620.46 | 0.00 | 0.127815E+09 | 0.00 | 0.44 |
Annual Sum or Average | 0.421053E+09 | 0.660445E+11 | 0.00 | 15221522.35 | 0.873760E+09 | 0.00 | 0.830810E+09 | 0.00 | 0.46 |
Minimum of Months | 0.00 | 0.408638E+09 | 0.00 | 0.00 | 7069112.54 | 0.00 | 0.00 | 0.00 | 0.44 |
Maximum of Months | 0.163004E+09 | 0.121085E+11 | 0.00 | 5859881.30 | 0.170990E+09 | 0.00 | 0.442941E+09 | 0.00 | 0.48 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.418025E+09 | 0.355163E+09 | 0.00 | 3656717.99 | 8186464.48 | 0.00 | 0.516221E+09 | 0.00 | 0.45 |
February | 0.257858E+09 | 0.740908E+09 | 0.00 | 2326648.15 | 35279751.39 | 0.00 | 0.263683E+09 | 0.00 | 0.46 |
March | 0.236202E+09 | 0.146473E+10 | 0.00 | 1830603.73 | 80967354.40 | 0.00 | 0.149506E+09 | 0.00 | 0.47 |
April | 0.176707E+09 | 0.295225E+10 | 0.00 | 1568438.91 | 0.217637E+09 | 0.00 | 37633496.25 | 0.00 | 0.46 |
May | 55749349.46 | 0.536477E+10 | 0.00 | 1076171.41 | 0.401240E+09 | 0.00 | 19322983.63 | 0.00 | 0.46 |
June | 5351790.00 | 0.748445E+10 | 0.00 | 239201.38 | 0.588800E+09 | 0.00 | 15575013.79 | 0.00 | 0.47 |
July | 2902639.07 | 0.950611E+10 | 0.00 | 135646.29 | 0.700064E+09 | 0.00 | 5943866.30 | 0.00 | 0.46 |
August | 1019952.92 | 0.104009E+11 | 0.00 | 37384.71 | 0.792824E+09 | 0.00 | 2151257.34 | 0.00 | 0.47 |
September | 4338796.98 | 0.802965E+10 | 0.00 | 269730.27 | 0.646460E+09 | 0.00 | 20289630.24 | 0.00 | 0.46 |
October | 32951143.27 | 0.545794E+10 | 0.00 | 792378.84 | 0.442888E+09 | 0.00 | 13341629.88 | 0.00 | 0.46 |
November | 82708002.00 | 0.317371E+10 | 0.00 | 916818.32 | 0.196418E+09 | 0.00 | 5319987.50 | 0.00 | 0.46 |
December | 0.268783E+09 | 0.110920E+10 | 0.00 | 2342506.57 | 61952501.27 | 0.00 | 0.190676E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.154260E+10 | 0.560398E+11 | 0.00 | 15192246.57 | 0.417272E+10 | 0.00 | 0.123966E+10 | 0.00 | 0.46 |
Minimum of Months | 1019952.92 | 0.355163E+09 | 0.00 | 37384.71 | 8186464.48 | 0.00 | 2151257.34 | 0.00 | 0.45 |
Maximum of Months | 0.418025E+09 | 0.104009E+11 | 0.00 | 3656717.99 | 0.792824E+09 | 0.00 | 0.516221E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE3
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.421760E+09 | 0.353104E+09 | 0.00 | 3608910.93 | 8160728.46 | 0.00 | 0.513548E+09 | 0.00 | 0.45 |
February | 0.257437E+09 | 0.739193E+09 | 0.00 | 2310466.47 | 35207216.12 | 0.00 | 0.265095E+09 | 0.00 | 0.46 |
March | 0.236291E+09 | 0.146458E+10 | 0.00 | 1835079.50 | 80922002.63 | 0.00 | 0.149845E+09 | 0.00 | 0.47 |
April | 0.177266E+09 | 0.295538E+10 | 0.00 | 1595472.03 | 0.217532E+09 | 0.00 | 37696473.74 | 0.00 | 0.46 |
May | 44222481.72 | 0.538034E+10 | 0.00 | 1089437.97 | 0.396859E+09 | 0.00 | 30745050.64 | 0.00 | 0.46 |
June | 4575361.84 | 0.750731E+10 | 0.00 | 248069.09 | 0.585258E+09 | 0.00 | 16110319.10 | 0.00 | 0.47 |
July | 3314343.32 | 0.953238E+10 | 0.00 | 148103.07 | 0.700086E+09 | 0.00 | 5426911.89 | 0.00 | 0.46 |
August | 967410.27 | 0.104295E+11 | 0.00 | 45304.59 | 0.790231E+09 | 0.00 | 2001104.68 | 0.00 | 0.47 |
September | 1069081.61 | 0.805179E+10 | 0.00 | 277439.02 | 0.647298E+09 | 0.00 | 22755336.24 | 0.00 | 0.46 |
October | 31548640.51 | 0.547971E+10 | 0.00 | 794084.34 | 0.438577E+09 | 0.00 | 14604201.29 | 0.00 | 0.46 |
November | 83295878.14 | 0.318025E+10 | 0.00 | 922573.94 | 0.194683E+09 | 0.00 | 5297311.09 | 0.00 | 0.46 |
December | 0.268746E+09 | 0.110826E+10 | 0.00 | 2340793.60 | 61870266.22 | 0.00 | 0.191372E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.153049E+10 | 0.561818E+11 | 0.00 | 15215734.55 | 0.415668E+10 | 0.00 | 0.125450E+10 | 0.00 | 0.46 |
Minimum of Months | 967410.27 | 0.353104E+09 | 0.00 | 45304.59 | 8160728.46 | 0.00 | 2001104.68 | 0.00 | 0.45 |
Maximum of Months | 0.421760E+09 | 0.104295E+11 | 0.00 | 3608910.93 | 0.790231E+09 | 0.00 | 0.513548E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE4
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.439608E+09 | 0.341847E+09 | 0.00 | 3448882.16 | 8214873.30 | 0.00 | 0.501646E+09 | 0.00 | 0.45 |
February | 0.264577E+09 | 0.725265E+09 | 0.00 | 2225794.55 | 34823582.47 | 0.00 | 0.263152E+09 | 0.00 | 0.46 |
March | 0.232236E+09 | 0.144914E+10 | 0.00 | 1762669.04 | 81116604.73 | 0.00 | 0.155308E+09 | 0.00 | 0.47 |
April | 0.175323E+09 | 0.293963E+10 | 0.00 | 1508680.59 | 0.217371E+09 | 0.00 | 38722446.88 | 0.00 | 0.46 |
May | 56656799.72 | 0.536496E+10 | 0.00 | 1083295.61 | 0.400135E+09 | 0.00 | 18480121.61 | 0.00 | 0.46 |
June | 5303420.95 | 0.748497E+10 | 0.00 | 244304.49 | 0.588605E+09 | 0.00 | 15782388.00 | 0.00 | 0.47 |
July | 3347259.08 | 0.951596E+10 | 0.00 | 140437.17 | 0.699325E+09 | 0.00 | 5503755.84 | 0.00 | 0.46 |
August | 1034764.80 | 0.104090E+11 | 0.00 | 46738.13 | 0.791869E+09 | 0.00 | 2195751.87 | 0.00 | 0.47 |
September | 4385371.86 | 0.803159E+10 | 0.00 | 280069.13 | 0.646946E+09 | 0.00 | 20107592.83 | 0.00 | 0.46 |
October | 33046520.07 | 0.544666E+10 | 0.00 | 792346.81 | 0.453617E+09 | 0.00 | 13264157.86 | 0.00 | 0.46 |
November | 81852502.67 | 0.315870E+10 | 0.00 | 891086.66 | 0.197352E+09 | 0.00 | 5587254.85 | 0.00 | 0.46 |
December | 0.267267E+09 | 0.109000E+10 | 0.00 | 2246548.75 | 61320493.31 | 0.00 | 0.196636E+09 | 0.00 | 0.45 |
Annual Sum or Average | 0.156464E+10 | 0.559577E+11 | 0.00 | 14670853.08 | 0.418070E+10 | 0.00 | 0.123639E+10 | 0.00 | 0.46 |
Minimum of Months | 1034764.80 | 0.341847E+09 | 0.00 | 46738.13 | 8214873.30 | 0.00 | 2195751.87 | 0.00 | 0.45 |
Maximum of Months | 0.439608E+09 | 0.104090E+11 | 0.00 | 3448882.16 | 0.791869E+09 | 0.00 | 0.501646E+09 | 0.00 | 0.47 |
Report: MechanicalVentilationLoadsMonthly
For: LGSTORE2
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.538806E+09 | 0.491611E+09 | 0.00 | 6653791.97 | 13256382.65 | 0.00 | 0.988680E+09 | 0.00 | 0.42 |
February | 0.345170E+09 | 0.125105E+10 | 0.00 | 4437698.24 | 27812429.91 | 0.00 | 0.470732E+09 | 0.00 | 0.42 |
March | 0.282502E+09 | 0.271222E+10 | 0.00 | 3083612.54 | 46115222.42 | 0.00 | 0.210044E+09 | 0.00 | 0.43 |
April | 0.185123E+09 | 0.570668E+10 | 0.00 | 1450549.86 | 0.202743E+09 | 0.00 | 25665493.01 | 0.00 | 0.42 |
May | 35755300.25 | 0.106451E+11 | 0.00 | 591575.67 | 0.290560E+09 | 0.00 | 32028798.03 | 0.00 | 0.43 |
June | 5632351.11 | 0.148258E+11 | 0.00 | 281547.86 | 0.342563E+09 | 0.00 | 12627130.13 | 0.00 | 0.44 |
July | 1899434.97 | 0.185428E+11 | 0.00 | 217328.07 | 0.436605E+09 | 0.00 | 1657242.26 | 0.00 | 0.43 |
August | 74256.27 | 0.205615E+11 | 0.00 | 99230.94 | 0.374997E+09 | 0.00 | 86222.51 | 0.00 | 0.44 |
September | 5429404.67 | 0.159295E+11 | 0.00 | 370629.82 | 0.417595E+09 | 0.00 | 10276609.54 | 0.00 | 0.43 |
October | 46841514.55 | 0.105294E+11 | 0.00 | 945889.32 | 0.435941E+09 | 0.00 | 19967132.84 | 0.00 | 0.42 |
November | 54474696.69 | 0.603717E+10 | 0.00 | 842132.54 | 0.214701E+09 | 0.00 | 4219497.69 | 0.00 | 0.42 |
December | 0.309072E+09 | 0.193572E+10 | 0.00 | 4498932.54 | 57618038.09 | 0.00 | 0.338883E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.181078E+10 | 0.109169E+12 | 0.00 | 23472919.36 | 0.286051E+10 | 0.00 | 0.211487E+10 | 0.00 | 0.43 |
Minimum of Months | 74256.27 | 0.491611E+09 | 0.00 | 99230.94 | 13256382.65 | 0.00 | 86222.51 | 0.00 | 0.42 |
Maximum of Months | 0.538806E+09 | 0.205615E+11 | 0.00 | 6653791.97 | 0.436605E+09 | 0.00 | 0.988680E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE5
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.269633E+09 | 0.246595E+09 | 0.00 | 3361752.23 | 6422564.99 | 0.00 | 0.485957E+09 | 0.00 | 0.42 |
February | 0.171065E+09 | 0.629349E+09 | 0.00 | 2232761.76 | 13891935.93 | 0.00 | 0.233130E+09 | 0.00 | 0.42 |
March | 0.140004E+09 | 0.136231E+10 | 0.00 | 1537948.97 | 23124075.39 | 0.00 | 0.103176E+09 | 0.00 | 0.43 |
April | 90818538.60 | 0.286163E+10 | 0.00 | 709173.96 | 0.101621E+09 | 0.00 | 12998943.87 | 0.00 | 0.42 |
May | 21124602.48 | 0.533481E+10 | 0.00 | 291042.74 | 0.146740E+09 | 0.00 | 12578728.04 | 0.00 | 0.43 |
June | 3536530.52 | 0.741194E+10 | 0.00 | 139751.27 | 0.182654E+09 | 0.00 | 5514832.51 | 0.00 | 0.44 |
July | 1076947.68 | 0.927577E+10 | 0.00 | 111670.66 | 0.223000E+09 | 0.00 | 736356.11 | 0.00 | 0.43 |
August | 22494.48 | 0.102838E+11 | 0.00 | 48863.22 | 0.191105E+09 | 0.00 | 57993.73 | 0.00 | 0.44 |
September | 2495363.97 | 0.795771E+10 | 0.00 | 174025.31 | 0.220223E+09 | 0.00 | 5501960.62 | 0.00 | 0.43 |
October | 24309106.33 | 0.526440E+10 | 0.00 | 473274.90 | 0.230558E+09 | 0.00 | 8955829.43 | 0.00 | 0.42 |
November | 27825554.87 | 0.302934E+10 | 0.00 | 408142.74 | 0.105648E+09 | 0.00 | 1044139.01 | 0.00 | 0.42 |
December | 0.152824E+09 | 0.970753E+09 | 0.00 | 2261945.88 | 28454599.75 | 0.00 | 0.166919E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.904735E+09 | 0.546284E+11 | 0.00 | 11750353.65 | 0.147344E+10 | 0.00 | 0.103657E+10 | 0.00 | 0.43 |
Minimum of Months | 22494.48 | 0.246595E+09 | 0.00 | 48863.22 | 6422564.99 | 0.00 | 57993.73 | 0.00 | 0.42 |
Maximum of Months | 0.269633E+09 | 0.102838E+11 | 0.00 | 3361752.23 | 0.230558E+09 | 0.00 | 0.485957E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE6
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.273658E+09 | 0.243421E+09 | 0.00 | 3312985.30 | 6432970.72 | 0.00 | 0.484548E+09 | 0.00 | 0.42 |
February | 0.172900E+09 | 0.624910E+09 | 0.00 | 2211156.90 | 13905597.49 | 0.00 | 0.233549E+09 | 0.00 | 0.42 |
March | 0.140827E+09 | 0.135686E+10 | 0.00 | 1523541.87 | 23112674.61 | 0.00 | 0.102965E+09 | 0.00 | 0.43 |
April | 90145779.12 | 0.285569E+10 | 0.00 | 702129.13 | 0.101754E+09 | 0.00 | 13534125.42 | 0.00 | 0.42 |
May | 21462957.80 | 0.532958E+10 | 0.00 | 292909.40 | 0.146664E+09 | 0.00 | 12305178.68 | 0.00 | 0.43 |
June | 3567414.87 | 0.740195E+10 | 0.00 | 141632.18 | 0.185710E+09 | 0.00 | 5560194.15 | 0.00 | 0.44 |
July | 1078243.13 | 0.926939E+10 | 0.00 | 111372.99 | 0.222755E+09 | 0.00 | 738924.67 | 0.00 | 0.43 |
August | 23376.17 | 0.102766E+11 | 0.00 | 48591.47 | 0.191067E+09 | 0.00 | 61615.83 | 0.00 | 0.44 |
September | 3411186.36 | 0.794651E+10 | 0.00 | 178449.54 | 0.224310E+09 | 0.00 | 4680471.90 | 0.00 | 0.43 |
October | 24303898.65 | 0.525857E+10 | 0.00 | 468260.55 | 0.230526E+09 | 0.00 | 8879556.00 | 0.00 | 0.42 |
November | 27723339.46 | 0.302247E+10 | 0.00 | 405696.05 | 0.106741E+09 | 0.00 | 1052210.20 | 0.00 | 0.42 |
December | 0.153479E+09 | 0.965227E+09 | 0.00 | 2238425.92 | 28370687.26 | 0.00 | 0.167935E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.912580E+09 | 0.545512E+11 | 0.00 | 11635151.30 | 0.148135E+10 | 0.00 | 0.103581E+10 | 0.00 | 0.43 |
Minimum of Months | 23376.17 | 0.243421E+09 | 0.00 | 48591.47 | 6432970.72 | 0.00 | 61615.83 | 0.00 | 0.42 |
Maximum of Months | 0.273658E+09 | 0.102766E+11 | 0.00 | 3312985.30 | 0.230526E+09 | 0.00 | 0.484548E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE7
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.278521E+09 | 0.237946E+09 | 0.00 | 3195265.84 | 6496549.50 | 0.00 | 0.483272E+09 | 0.00 | 0.42 |
February | 0.174120E+09 | 0.617079E+09 | 0.00 | 2136864.70 | 14013088.72 | 0.00 | 0.236120E+09 | 0.00 | 0.42 |
March | 0.138361E+09 | 0.134857E+10 | 0.00 | 1455346.42 | 23198894.18 | 0.00 | 0.105914E+09 | 0.00 | 0.43 |
April | 88768758.69 | 0.284956E+10 | 0.00 | 676690.25 | 0.102167E+09 | 0.00 | 13952035.44 | 0.00 | 0.42 |
May | 21404197.08 | 0.533242E+10 | 0.00 | 291005.60 | 0.147383E+09 | 0.00 | 12225615.15 | 0.00 | 0.43 |
June | 3385991.35 | 0.741346E+10 | 0.00 | 142393.35 | 0.183923E+09 | 0.00 | 5720384.55 | 0.00 | 0.44 |
July | 954689.62 | 0.929372E+10 | 0.00 | 113136.02 | 0.217050E+09 | 0.00 | 851339.58 | 0.00 | 0.43 |
August | 21728.81 | 0.103049E+11 | 0.00 | 52237.56 | 0.188152E+09 | 0.00 | 55007.65 | 0.00 | 0.44 |
September | 2583416.28 | 0.796995E+10 | 0.00 | 179696.76 | 0.218589E+09 | 0.00 | 5346755.36 | 0.00 | 0.43 |
October | 24333410.99 | 0.527083E+10 | 0.00 | 467283.73 | 0.227997E+09 | 0.00 | 8791128.16 | 0.00 | 0.42 |
November | 27337184.61 | 0.302274E+10 | 0.00 | 395933.70 | 0.107503E+09 | 0.00 | 1059992.17 | 0.00 | 0.42 |
December | 0.151688E+09 | 0.958158E+09 | 0.00 | 2208881.94 | 28415190.66 | 0.00 | 0.171805E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.911480E+09 | 0.546193E+11 | 0.00 | 11314735.87 | 0.146489E+10 | 0.00 | 0.104511E+10 | 0.00 | 0.43 |
Minimum of Months | 21728.81 | 0.237946E+09 | 0.00 | 52237.56 | 6496549.50 | 0.00 | 55007.65 | 0.00 | 0.42 |
Maximum of Months | 0.278521E+09 | 0.103049E+11 | 0.00 | 3195265.84 | 0.227997E+09 | 0.00 | 0.483272E+09 | 0.00 | 0.44 |
Report: MechanicalVentilationLoadsMonthly
For: SMSTORE8
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportZONE MECHANICAL VENTILATION NO LOAD HEAT REMOVAL ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD INCREASE DUE TO OVERHEATING ENERGY [J] | ZONE MECHANICAL VENTILATION COOLING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION NO LOAD HEAT ADDITION ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD INCREASE DUE TO OVERCOOLING ENERGY [J] | ZONE MECHANICAL VENTILATION HEATING LOAD DECREASE ENERGY [J] | ZONE MECHANICAL VENTILATION AIR CHANGES PER HOUR [ach] | |
January | 0.272833E+09 | 0.245970E+09 | 0.00 | 3239572.22 | 5529096.85 | 0.00 | 0.473780E+09 | 0.00 | 0.42 |
February | 0.177600E+09 | 0.616832E+09 | 0.00 | 2166176.10 | 13279374.35 | 0.00 | 0.234453E+09 | 0.00 | 0.42 |
March | 0.143893E+09 | 0.134818E+10 | 0.00 | 1374990.56 | 23244852.05 | 0.00 | 0.105310E+09 | 0.00 | 0.43 |
April | 0.100285E+09 | 0.285063E+10 | 0.00 | 708156.84 | 89517288.37 | 0.00 | 17249837.05 | 0.00 | 0.42 |
May | 23957028.66 | 0.536085E+10 | 0.00 | 464354.48 | 0.111748E+09 | 0.00 | 18391088.13 | 0.00 | 0.43 |
June | 4777819.52 | 0.746902E+10 | 0.00 | 271149.88 | 0.142698E+09 | 0.00 | 10359422.69 | 0.00 | 0.44 |
July | 1098319.99 | 0.935752E+10 | 0.00 | 337958.77 | 0.189153E+09 | 0.00 | 2005928.91 | 0.00 | 0.43 |
August | 608781.67 | 0.104219E+11 | 0.00 | 178504.76 | 0.149941E+09 | 0.00 | 1324658.16 | 0.00 | 0.44 |
September | 2018754.90 | 0.808858E+10 | 0.00 | 415052.14 | 0.165315E+09 | 0.00 | 10983206.36 | 0.00 | 0.43 |
October | 23197503.31 | 0.535399E+10 | 0.00 | 538887.16 | 0.148496E+09 | 0.00 | 16070217.41 | 0.00 | 0.42 |
November | 35512218.79 | 0.307226E+10 | 0.00 | 487035.59 | 72411339.30 | 0.00 | 4191318.61 | 0.00 | 0.42 |
December | 0.153009E+09 | 0.978911E+09 | 0.00 | 2294555.21 | 28207362.84 | 0.00 | 0.170004E+09 | 0.00 | 0.42 |
Annual Sum or Average | 0.938790E+09 | 0.551646E+11 | 0.00 | 12476393.72 | 0.113954E+10 | 0.00 | 0.106412E+10 | 0.00 | 0.43 |
Minimum of Months | 608781.67 | 0.245970E+09 | 0.00 | 178504.76 | 5529096.85 | 0.00 | 1324658.16 | 0.00 | 0.42 |
Maximum of Months | 0.272833E+09 | 0.104219E+11 | 0.00 | 3239572.22 | 0.189153E+09 | 0.00 | 0.473780E+09 | 0.00 | 0.44 |
Report: HeatEmissionsReportMonthly
For: Environment
Timestamp: 2023-10-16 08:40:25
Custom Monthly ReportSITE TOTAL SURFACE HEAT EMISSION TO AIR [J] | SITE TOTAL ZONE EXFILTRATION HEAT LOSS [J] | SITE TOTAL ZONE EXHAUST AIR HEAT LOSS [J] | AIR SYSTEM RELIEF AIR TOTAL HEAT LOSS ENERGY [J] | HVAC SYSTEM TOTAL HEAT REJECTION ENERGY [J] | |
January | 0.134525E+12 | 0.203113E+10 | 0.00 | 0.335117E+11 | 0.108245E+12 |
February | 0.156981E+12 | -0.324576E+10 | 0.00 | 0.137631E+11 | 0.122170E+12 |
March | 0.203407E+12 | -0.107998E+11 | 0.00 | -0.337187E+10 | 0.166730E+12 |
April | 0.224488E+12 | -0.254273E+11 | 0.00 | -0.403016E+11 | 0.221725E+12 |
May | 0.245754E+12 | -0.444043E+11 | 0.00 | -0.100686E+12 | 0.325384E+12 |
June | 0.239915E+12 | -0.599235E+11 | 0.00 | -0.147184E+12 | 0.387505E+12 |
July | 0.242701E+12 | -0.753864E+11 | 0.00 | -0.193237E+12 | 0.458212E+12 |
August | 0.232479E+12 | -0.807490E+11 | 0.00 | -0.207498E+12 | 0.489391E+12 |
September | 0.196629E+12 | -0.647891E+11 | 0.00 | -0.157557E+12 | 0.408242E+12 |
October | 0.159522E+12 | -0.429763E+11 | 0.00 | -0.107016E+12 | 0.327472E+12 |
November | 0.120339E+12 | -0.251844E+11 | 0.00 | -0.455409E+11 | 0.234374E+12 |
December | 0.115899E+12 | -0.722358E+10 | 0.00 | 0.891963E+10 | 0.150641E+12 |
Annual Sum or Average | 0.227264E+13 | -0.438078E+12 | 0.00 | -0.946198E+12 | 0.340009E+13 |
Minimum of Months | 0.115899E+12 | -0.807490E+11 | 0.00 | -0.207498E+12 | 0.108245E+12 |
Maximum of Months | 0.245754E+12 | 0.203113E+10 | 0.00 | 0.335117E+11 | 0.489391E+12 |